From: Burt, Chris <cburt@southsnofire.org>
Sent: Thursday, October 3, 2024 7:09 AM RES U B
To: Kory Mehl Oct 03 2024
Subject: RE: Permit FIR2024-0092 Corrections
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Kory,
will not require full upgrade if the FACP is not being replaced. Please resubmit with this email chain added to the
submittal.
Thankyou
Chris Burt
Deputy Fire Marshal - FM16
12425 Meridian Ave. 5, Everett WA 98208
Fire Prevention: (425) 551-1264 1 O: (425) 327-5800
cburt(@southsnofire.ors I www.southsnofire.org
The , :, ...
ir!lti7t"<"r7;lttxJ71 1EFlI7.,' {? eil4 Tic.t?„rr71.>. Fuiil??L' C;: f}t f.') f i` 1? k;i>•<,:'x i>_ .,t,:r, ;z lrr'f,r" ii: rO r, If. L f7?,:'..C. ..i tf:l f7EGlt"t'a i:7;:7i!?7i'tliii7
c;<a�je=:tle�srFxc'Bf"i:trC?ri t ie?;)Cltr<il:frjJaYrS.ti' :'1;iiC;}!£)4017;fiC.�r7?£L' O''iiii; t"3J73(z1 } :i:brlr@. f✓C3r ori; noi, the inend'?Ci you
,,eo hei-eby notified 5-t7ajei�y,reviel;-v,'3dSS�r3"i�:'??ttii;?,Cil;iiilJLtitCJ;',L't'Cuplicado 01,ol;sCJrn?,-..J,r,, is;t!�c,lj3iG}?t)7'.,:,....?)/:.iLl:ir"v=i.,2(i!)e3
fhG b ti d by et) t� ood de troy ail cops S C? oli,";1r?
From: Kory Mehl <KMehl@callseacom.com>
Sent: Wednesday, October 2, 2024 1:32 PM
To: Burt, Chris <cburt@southsnofire.org>
Subject: Permit FIR2024-0092 Corrections
Chris,
I received your correction notice for Emerald Place permit application # FIR2024-0092. In your Fire
Comment Letter, it looks like you are requiring the building to be brought up to current code? This
location has an existing Silent Knight 5208 Fire Alarm Control panel. These panels are expandable with
Relay and Input zone expanders. We're not installing, replacing, or upgrading the panel. Our plan here is
to install the 5217 Zone Expander, an optional accessory as per the Silent Knight 5208 manual, to add the
input zones we need to be able to add the machine room heat, smoke, and multi -voltage relay for Shunt
Power fail, as well as the Pit heat to the existing system.
This is the same scenario we had approved for Avalon at Edmonds Permit # FIR2024-0073, with the
exception that the zone expander for the Silent Knight 5207 had already been installed on that system.
Below is a snap shot of the list of the Optional Accessories from the Silent Knight SK-5208 manual.
Model SK-5208 Inslaft0on Manual
1.3.1 Optional Accessories
Table 1-1: Compatible Modules Manufactured by Silent Knight
is
Modell
What It Does
$9 -_ 17 7ow Fxpawlx
AAW I �Ai mms to the SK -'52W to, !rnal e'xpani-
ton of 11w
SK-2190 Accessory Cabinet
Used far reraote mounting of the SK-5217 Expander.
Dimensjoitv I(Y:3/8"W x 10 31.16"H x 3.1) C26,35 CM W x 25.89 cm H x 7.62 cm 1
5220 Direct Connect Module
For direr[ alarming aid trouble tninsmis-151011 from the SIB-520s to a supenfi4ng
station,
SIB-5235 Remote Annunciator
For remote annunciation, operation., and on -site programming.
SK-5280
The Model SK-5280 Status Display'm(miu)e provides outputs and cantro I junctions'
remote annunciation of alarm, trouble, and Wpervisories for each zone,
5824
Provides Conflecti-vitY to a 8641 Or parallel printer. Section 41.12 for
SK-5499 Signal Power Expander
NotifiLation circuit puwer for additian4l ix)tifv"iojj appliancs. provides additions
9A. of 24 VDC, super, lscd.
SK-5495 Signal Power Expander
Notification circuit power for additional notification appliances. Provides additions
6A of' 24 VDC, supavise&
SKSS Downloading Software
For remote programming of dw Sly-52,08 using a per nal computes.
Model 56W
FLEX-2
Optional door accessory for sjITJe button operation. (See Section 43 for
programming.)
Thank you,
Kory Mehl, ET
Fire Alarm & Security Division Manager
425-317-8259 ext 310
425-317-8261 f / 425-359-0320 c
rn,
www.caLlseacornxam
n, U W a d