APPROVED FIR2024-0010+Fire_Alarm_Plan+2.6.2024_10.44.12_AM+4042240L S I L 10 I C 0 E F G GENERAL SYSTEM NOTES PANEL: 1. THE SUPPLEMENTAL NOTIFICATION REMOTE POWER SUPPLY (RPS) IS TO BE MOUNTED SURFACE, BESIDE THE FACP. THE TOP OF THE PANEL SHALL NOT EXCEED 6 FEET ABOVE FINISHED FLOOR SURFACE. A MINIMUM CLEARANCE OF 36" WORKING SPACE SHALL BE MAINTAINED. 2. THE RPS IS TO BE POWERED BY THE SAME DEDICATED 120 VAC CIRCUIT AS THE FACP. TWO CONDUCTORS TO 120 VAC, ONE CONDUCTOR TO ISOLATED GROUND, 20 AMP DEDICATED CIRCUIT. A HOUSE GROUND WILL NOT BE ACCEPTABLE. 3. THE BOTTOM THE RPS SHALL BE PENETRATED. DEVICES: 1. ALL SIGNALING DEVICES SHALL HAVE THE BOTTOM OF THE DEVICE PLACED AT 80 INCHES ABOVE FINISHED FLOOR WITHIN THE SPACE, OR THE TOP OF THE DEVICE 6 INCHES BELOW THE CEILING, WHICHEVER IS LOWER. 2. THE AUDIBLE DEVICES SIGNAL SHALL BE SET TO THE TEMPORAL SETTING. 3. ALL DEVICES ARE TO BE LOCATED PER THE DRAWINGS. 4. WHEN APPLICABLE, VERIFY WITH MECHANICAL CONTRACTOR THE EXISTENCE AND LOCATION OF ALL MOTORIZED SMOKE DAMPERS. THESE ARE TO BE 120 VAC DEVICES ON AS FEW CIRCUITS AS POSSIBLE. THESE DEVICE CIRCUITS ARE TO BE CONTROLLED BY THE FACP THROUGH AN INTERFACING RELAY. 5. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR ALL LOCATIONS OF THE SPRINKLER WATERFLOW, DRY FLOW, HI/LO AIR, TAMPER SWITCHES AND PIV OR 0, S, & Y VALVES. 6. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THE EXISTENCE OF SPRINKLER HEAT TAPE. THIS HEAT TAPE SHALL BE MONITORED BY THE FACP AND SHALL REQUIRE AN APPROPRIATE RELAY THAT WILL PROVIDE SUPERVISION FOR HEAT TAPE GROUND FAULTS AND LOSS OF PRIMARY POWER. 7. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THAT ALL APPLICABLE INTERSTITIAL CEILING, ATTIC, OR FLOOR SPACES ARE PROTECTED WITH SPRINKLER HEADS. WIRING: 1. TWO DEDICATED PHONE LINES TO BE INSTALLED BY OWNER TO TRANSMITTER. 2. ALL AUDIBLE / VISUAL CIRCUITS ARE TO BE 14 AWG FPL WIRE. (RISER OR PLENUM RATED WIRE WHERE REQUIRED PER NEC). 3. AUDIBLE / VISUAL CIRCUITS ARE TO HAVE AN END OF LINE RESISTOR (ELR) AS APPROPRIATE WITH THE FACP / RPS. 4. ALL FIRE ALARM WIRES ARE REQUIRED TO BE IDENTIFIED AND APPROPRIATELY MARKED. 5. PER NEC, NO AC VOLTAGE WIRING OF ANY KIND SHALL BE RUN IN THE SAME CONDUIT OR RISER AS THE LOW VOLTAGE FIRE ALARM SYSTEM WIRING. 6. ALL JACKETED CABLE MUST INCLUDE A JACKET REMOVAL PULL STRING AS PART OF THE CABLE. 7. SHIELDED CABLE IS NOT AN ACCEPTABLE SUBSTITUTION FOR CABLE WITHOUT "SHIELDED" AS PART OF THE DESCRIPTION. GENERAL: 1. ALL FIRE ALARM JUNCTION BOXES ARE TO BE PAINTED RED. 2. ALL END OF LINE DEVICES SHALL HAVE AN IDENTIFYING E.O.L. STICKER AT THE E.O.L. LOCATION. 3. ONLY CONDUCTORS INTENDED FOR TERMINATION TO THE SPECIFIC DEVICE ON ANY GIVEN JUNCTION BOX SHALL BE LEFT OPEN FOR TERMINATION IN THAT JUNCTION BOX. ALL OTHER CONDUCTORS SHALL PASS THROUGH, OR BE SPLICED THROUGH, THAT JUNCTION BOX. ALL EQUIPMENT AND LABOR PROVIDED BY ABSCO SOLUTIONS, INC. HAS A WARRANTY OF ONE YEAR FROM DATE OF INVOICE. THIS WARRANTY EXCLUDES ALL COVERAGE FOR CONSEQUENTIAL DAMAGES, AND IS GIVEN IN LIEU OF ALL OTHER EXPRESS WARRANTIES OR IMPLIED WARRANTIES OF FITNESS, HABITABILITY, OR MERCHANTABILITY OTHERWISE PROVIDED UNDER THE LAWS OF WASHINGTON. ANY WARRANTY WORK PERFORMED BY ABSCO SOLUTIONS, INC. DOES NOT EXTEND THE WARRANTY OF ONE YEAR FROM THE DATE OF THE INVOICE. THIS WARRANTY SHALL BE VOID IF A PERSON OR FIRM OTHER THAN ABSCO SOLUTIONS, INC. OR THE CONTRACTOR AUTHORIZED BY ABSCO SOLUTIONS, INC. PERFORMS OR RE —PERFORMS ANY WORK IDENTIFIED WITHIN THE ORIGINAL SCOPE OF THE WORK OF THE CONTRACT WITH ABSCO SOLUTIONS, INC. LEGAL NOTICE: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ABSCO SOLUTIONS, INC. ANY REPRODUCTION IN PART OR IN WHOLE WITHOUT THE WRITTEN PERMISSION OF ABSCO SOLUTIONS, INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND ALL OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY ABSCO SOLUTIONS, INC. H 9fl6imD fl3 �? VI C N ITY MAP ®south county Fire Station 1 r: Approved D F M Chris Burt South County Fire Date: 02/14/2024 02-14-2024 PLAN REVIEW NOTES: APPROVED DFM BURT FINISHED CEILING FINISHED FLOOR TYPICAL MOUNTING HEIGHTS WALL MOUNT —EXT. STROBE —EXT. HORN STROBE —EXT. HORN STROBE WP CEILING MOUNT —SMOKE DETECTOR —HEAT DETECTOR CONTROL MANUAL FARA PANEL PULL STATION r F1 80" ( 60" 48" 60" Symbol Legend SYMBOL DESCRIPTION MANUFACTURER PART NUMBER BACKBOX REQUIREMENTS QUANTITY FACP 1110-PT ADDRESSABLE FACP SILENT KNIGHT 6820 RED ENCLOSURE, PROVIDED 1 FARA REMOTE LCD ANNUNCIATOR, RED SILENT KNIGHT 586OR RED BEZEL, PROVIDED 1 FADC DOCUMENT STORAGE BOX WITH GW-FCI LOCK GAMEWELL-FCI GW-FAD RED ENCLOSURE, PROVIDED 1 0P LOW -PROFILE PHOTOELECTRIC SENSOR WHITE SILENT KNIGHT SK-PHOTO-W 4SQR W / 3-0 RING 18 O LOW -PROFILE INTELLIGENT ROR THERMAL SENSOR WHITE SILENT KNIGHT SK-HEAT-ROR-W 4SQR W / 3-0 RING 1 PULL STATION, DOUBLE ACTION, ADDRESSABLE SILENT KNIGHT SK-PULL-DA DEEP 4-SQR 7 2 DUAL MONITOR, 2 RELAY OUTPUT SILENT KNIGHT SK-RELAYMON-2 DEEP 4-SQR 2 DH WALL -MOUNT DOOR HOLDER, FLUSH NOTIFIER FM998 PROVIDED 2 EXISTING STROBE, WHITE, WALL EXISTING SWL EXISTING EXISTING 5 EXISTING HORN STROBE, WHITE, WALL EXISTING P2WL EXISTING EXISTING 23 WP EXISTING HORN STROBE, WHITE, WALL, OUTDOOR EXISTING P2WK EXISTING EXISTING 1 EOL Re EXISTING EOL-4.7K EXISTING EOL-4.7 EXISTING EXISTING 3 Fire Alarm Device Numbering Circuit Circuit Unique ID Unique ID NACl-001 SLC1•S:001 ADDRESSABLE DEVICE NUMBERING ADDRESSABLE NAC NUMBERING Wire Path Label Legend Chr. Position Character Purpose #1 Quantity of the same circuit #2 Circuit name Existing 14/2-ns = 14AWG 2 CONDUCTOR - NON -SHIELDED CABLE Existing 16/2-ns = 16AWG 2 CONDUCTOR - NON -SHIELDED CABLE PROJECT NOTES • ALL CIRCUITS ARE EXISTING • REPLACE EXISTING FACP (EST-2) • REPLACE EXISTING DETECTION DEVICES AS NEEDED ON A LIKE —FOR —LIKE BASIS • REUSE EXISTING NOTIFICATION DEVICE AS IS, IN THEIR LOCATIONS AND CONFIGURATIONS • TECHNICIAN TO AS —BUILD DEVICE ADDRESSES • TECHNICIAN TO AS —BUILD NOTIFICATION CIRCUITS • AMBIENT TEMPERATURE 70°F IN ALL SPACES • AMBIENT SOUND LEVEL >40DB IN ALL SPACES SEQUENCE OF OPERATIONS Output Activated Alarm Device General Notification - Alarm Horn + Horn Strobe + Strobe Transmit Alarm Signals Transmit Trouble Signals at FACP Transmit Supervisory Signals at FACP Keypad Annunciator Smoke Detector X X X Heat Detector X X X Manual Pull Station X X X FACP Alarm X X X FACP Trouble X X FACP Supervisory I I I X X RECEIVED F I R2024-001 0 Feb 0E 20 CITY OF DMONDSDS DEVELOPMENT SERVICES DEPARTMENT Firm Name and Address oQ�Ahsm SO&tk= P.O. BOX 2246 LYNNWOOD, WA 98036 PH: 425.771.1166 FAX: 425.771 .4422 www.abscosolutions.com Project Name and Address LEGAL NOTICE: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ABSCO SOLUTIONS, INC. ANY REPRODUCTION IN PART OR IN WHOLE WITHOUT THE WRITTEN PERMISSION OF ABSCO SOLUTIONS, INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND ALL OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY A B S C 0 SOLUTIONS, INC. Designer of Record KEN DAY ABSCO SOLUTIONS, INC. 19023 36TH AVE W STE E LYNNWOOD, WA 98036 PHONE: (425) 771-1166 FAX: (425) 771-4422 EMAIL: KEN. DAY®ABSCOSOLUTIONS.COM NICET: IV # 97083 1-01/25/24 Submittal Set AP Rev.# —Date Revision By Drawn By A.P. Checked By D.H. Date 01 /23/24 Project Name FIRE STATION #16 Project Number 26161 System Type FIRE ALARM Sheet Name LEGENDS, DETAILS, EI R E ALARM PANS 1 01 L I 0 -7 1 R A B D E F G H Cable/Circuit Report Job number: 26161 Job name: Fire Station 16 - FA Cable Length Overage: 10.000000% Source Circuit Circuit Type Wiring Style Manufacturer Part No. Type Description Gauge Length Color FACP NAC1 Notification Class B WINDY CITY 767960 Fire Alarm 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP #14 61'-2 1/2 Existing FACP NAC2 Notification Class B WINDY CITY 767960 Fire Alarm 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP #14 368'-6 Existing FACP NAC3 Notification Class B WINDY CITY 767960 Fire Alarm 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP #14 391'-11 1/2 Existing FACP SLC1 Signaling line Class B WINDY CITY 761360 Fire Alarm 16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP #16 627'-4 Existing Appliance List by Circuit Circuit Device FACP:SLC1-M:001 ADDRESSABLE PULL STATION FACP:SLC1-M:002 ADDRESSABLE PULL STATION FACP:SLC1-M:003,004,005,006 MULTI -INPUT MODULE FACP:SLC1-M:007 ADDRESSABLE PULL STATION FACP:SLC1-M:008 ADDRESSABLE PULL STATION FACP:SLC1-M:009, 010, 011, 012 MULTI -INPUT MODULE FACP:SLC1-M:013 ADDRESSABLE PULL STATION FACP:SLC1-M:014 ADDRESSABLE PULL STATION FACP:SLC1-M:015 ADDRESSABLE PULL STATION FACP:SLC1-S:001 PHOTOELECTRIC DETECTOR FACP:SLC1-S:002 HEAT DETECTOR FACP:SLC1-S:003 PHOTOELECTRIC DETECTOR FACP:SLC1-S:004 PHOTOELECTRIC DETECTOR FACP:SLC1-S:005 PHOTOELECTRIC DETECTOR FACP:SLC1-S:006 PHOTOELECTRIC DETECTOR FACP:SLC1-S:007 PHOTOELECTRIC DETECTOR FACP:SLC1-S:008 PHOTOELECTRIC DETECTOR FACP:SLC1-S:009 PHOTOELECTRIC DETECTOR FACP:SLC1-S:010 PHOTOELECTRIC DETECTOR FACP:SLC1-S:011 PHOTOELECTRIC DETECTOR FACP:SLC1-S:012 PHOTOELECTRIC DETECTOR FACP:SLC1-S:013 PHOTOELECTRIC DETECTOR FACP:SLC1-S:014 PHOTOELECTRIC DETECTOR FACP:SLC1-S:015 PHOTOELECTRIC DETECTOR FACP:SLC1-S:016 PHOTOELECTRIC DETECTOR FACP:SLC1-S:017 PHOTOELECTRIC DETECTOR FACP:SLC1-S:018 PHOTOELECTRIC DETECTOR FACP:SLC1-S:019 PHOTOELECTRIC DETECTOR Battery Calculations for Panel: FACP Part No:6820-1110-PT ADDRESSABLE FACP Job number: 26161 Job name: Fire Station 16 - FA Part No. Qty. Description Standby Total Standby Alarm Total Alarm Panel Equipment 6820_MB 1 MAIN BOARD, 6820 190.0000 mA 190.0000 mA 250.0000 mA 250.0000 mA Total Panel Stby 190.0000 mA Total Panel Alarm 250.0000 mA Peripheral Devices EXISTING P2WL 17 EXISTING HORN STROBE, WHITE, WALL (Notification) 15CD 88dB 0.0000 mA 0.0000 mA 53.0000 mA 901.0000 mA EXISTING P2WK 1 EXISTING HORN STROBE, WHITE, WALL, OUTDOOR (Notification) 75CD 88dB 0.0000 mA 0.0000 mA 176.0000 mA 176.0000 mA EXISTING P2WL 1 EXISTING HORN STROBE, WHITE, WALL (Notification) 110CD 88dB 0.0000 mA 0.0000 mA 164.0000 mA 164.0000 mA EXISTING P2WL 2 EXISTING HORN STROBE, WHITE, WALL (Notification) 75CD 88dB 0.0000 mA 0.0000 mA 119.0000 mA 238.0000 mA EXISTING SWL 4 EXISTING STROBE, WHITE, WALL (Notification) 15CD 0.0000 mA 0.0000 mA 43.0000 mA 172.0000 mA EXISTING P2WL 3 EXISTING HORN STROBE, WHITE, WALL (Notification) 30CD 88dB 0.0000 mA 0.0000 mA 73.0000 mA 219.0000 mA EXISTING SWL 1 EXISTING STROBE, WHITE, WALL (Notification) 30CD 0.0000 mA 0.0000 mA 63.0000 mA 63.0000 mA FM998 2 WALL -MOUNT DOOR HOLDER, FLUSH (Power) 20.0000 mA 40.0000 mA 0.0000 mA 0.0000 mA 5860R 1 REMOTE LCD ANNUNCIATOR, RED (Power) 20.0000 mA 20.0000 mA 20.0000 mA 20.0000 mA 5860R 1 REMOTE LCD ANNUNCIATOR, RED (Serial) 0.0000 mA 0.0000 mA 0.0000 mA 0.0000 mA SK-RELAYMON-2 2 2 DUAL MONITOR, 2 RELAY OUTPUT (Signaling line) 1.3500 mA 2.7000 mA 24.0000 mA 48.0000 mA SK-PULL-DA 7 PULL STATION, DOUBLE ACTION, ADDRESSABLE (Signaling line) 0.3500 mA 2.4500 mA 0.3500 mA 2.4500 mA SK-PHOTO-W 18 LOW -PROFILE PHOTOELECTRIC SENSOR WHITE (Signaling line) 0.2000 mA 3.6000 mA 0.2000 mA 3.6000 mA SK-HEAT-ROR-W 1 LOW -PROFILE INTELLIGENT ROR THERMAL SENSOR WHITE (Signaling line) 0.2000 mA 0.2000 mA 0.2000 mA 0.2000 mA FM998 2 WALL -MOUNT DOOR HOLDER, FLUSH (Relay) 0.0000 mA 0.0000 mA 0.0000 mA 0.0000 mA EXISTING EOL-4.7 3 EOL-4.7K (Notification) 0.0000 mA 0.0000 mA 0.0000 mA 0.0000 mA Total Peripheral Stby 68.9500 mA Total Periph Alarm 2007.2500 mA Total Standby Amps 258.9500 mA Total Alarm Amps 2257.2500 mA Standby time: 24 Hrs 6.215 Ah Alarm time: 5 Min 0.188 Ah Battery requirement: 6.403 Ah Compensation Factors - Standby: 1.2 Alarm: 1.2 Requirement with compensation: 7.683 Ah Circuit Calculations Panel: FACP Card: FACP Circuit:SLC1 Circuit Name: SLC1 Circuit Type: Signaling line/SK - SLC Terminal Voltage: 20.4 V:DC Amperage: 1.0000 A Cable: 16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP #16 Calculations based on Running Total Length. Design Criteria: Ambient temperature: 167 OF Max. operating voltage drop: 18% Device Part No Appliance Desc Distance Current Voltage Voltage Drop 6820 Panel 20.4 V S:001 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 2'-11 1/2 0.2000 mA 20.3999 V (0.0001 V) S:002 SK-HEAT-ROR-W LOW -PROFILE INTELLIGENT ROR THERMAL SENSOR WHITE 13'-11 1/2 0.2000 mA 20.3989 V (0.0009 V) S:003 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 29'-0 1/2 0.2000 mA 20.3969 V (0.002 V) M:001 SK-PULL-DA PULL STATION, DOUBLE ACTION, ADDRESSABLE 55'-0 0.3500 mA 20.3931 V (0.0038 V) M:002 SK-PULL-DA PULL STATION, DOUBLE ACTION, ADDRESSABLE 115'-7 0.3500 mA 20.3928 V (0.0003 V) S:004 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 4'-9 0.2000 mA 20.3929 V (0.0003 V) S:005 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 18'-10 1/2 0.2000 mA 20.3918 V (0.0011 V) S:006 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 25'-9 1/2 0.2000 mA 20.3903 V (0.0015 V) M:003,004,005,006 SK-RELAYMON-2 2 DUAL MONITOR, 2 RELAY OUTPUT 16'-8 1/2 1.3500 mA 20.3894 V (0.0009 V) M:007 SK-PULL-DA PULL STATION, DOUBLE ACTION, ADDRESSABLE 17'-2 1/2 0.3500 mA 20.3886 V (0.0008 V) S:007 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 11'-11 0.2000 mA 20.3881 V (0.0005 V) S:008 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 27'-5 1/2 0.2000 mA 20.3869 V (0.0011 V) M:008 SK-PULL-DA PULL STATION, DOUBLE ACTION, ADDRESSABLE W-41/2 0.3500 mA 20.3868 V (0.0001 V) S:009 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 19'-8 0.2000 mA 20.3861 V (0.0007 V) S:010 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 13'-5 0.2000 mA 20.3856 V (0.0005 V) S:011 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 13'-10 1/2 0.2000 mA 20.3852 V (0.0004 V) S:012 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 24'-10 1/2 0.2000 mA 20.3844 V (0.0008 V) S:013 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 18'-6 1/2 0.2000 mA 20.3838 V (0.0006 V) M:009, 010, 011, 012 SK-RELAYMON-2 2 DUAL MONITOR, 2 RELAY OUTPUT 40'-7 1/2 1.3500 mA 20.3827 V (0.0012 V) S:014 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE X-9 1/2 0.2000 mA 20.3826 V (0.0001 V) S:015 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 29'-2 0.2000 mA 20.3821 V (0.0005 V) S:016 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 14'-2 1/2 0.2000 mA 20.3819 V (0.0002 V) S:017 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 16'-2 0.2000 mA 20.3817 V (0.0002 V) S:018 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 17'-2 1/2 0.2000 mA 20.3815 V (0.0002 V) S:019 SK-PHOTO-W LOW -PROFILE PHOTOELECTRIC SENSOR WHITE 14'-5 1/2 0.2000 mA 20.3813 V (0.0001 V) M:013 SK-PULL-DA PULL STATION, DOUBLE ACTION, ADDRESSABLE 12'-2 1/2 0.3500 mA 20.3812 V (0.0001 V) M:014 SK-PULL-DA PULL STATION, DOUBLE ACTION, ADDRESSABLE 34'-51/2 0.3500 mA 20.381 V (0.0002 V) M:015 SK-PULL-DA PULL STATION, DOUBLE ACTION, ADDRESSABLE 12'-0 0.3500 mA 20.381 V (0 V) 627'-4 8.9500 mA Total Current: 8.9500 mA (Total VDrop Percent:0.09%) Total Voltage Drop : 0.019 V Firm Name and Address 4%.hirdom P.O. BOX 2246 LYNNWOOD, WA 98036 PH: 425.771.1166 FAX: 425.771 .4422 www.abscosolutions.com Project Name and Address LEGAL NOTICE: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ABSCO SOLUTIONS, INC. ANY REPRODUCTION IN PART OR IN WHOLE WITHOUT THE WRITTEN PERMISSION OF ABSCO SOLUTIONS, INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND ALL OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY A B S C 0 SOLUTIONS, INC. Designer of Record KEN DAY ABSCO SOLUTIONS, INC. 19023 36TH AVE W STE E LYNNWOOD, WA 98036 PHONE: (425) 771-1166 FAX: (425) 771-4422 EMAIL: KEN.DAY@ABSCOSOLUTIONS.COM NICET: IV # 97083 05- 1-01/25/24 Submittal Set AP Rev.# -Date Revision By Drawn By A.P. Checked By D.H. Date 01 /23/24 Project Name FIRE STATION #16 Project Number 26161 System Type FIRE ALARM 1 1 ? I I /I I I i; 1 7 1 R A B D E F G H EXT. 1 NAC1 EOL 4.71K Q 15CD 15CD EOL Re � E FACP:NAC1 FACP:NAC1•N:002 FACP:NAC1.001 EXT. 1 NAC2 WP EOL 4.7K S2 75CD 75CD 75CD 15CD 15CD 110CD 15CD 75CD 15CD 15CD 75CD / - FACP:NAC2 FACP:NAC2.011 FACP:NAC2.010 FACP:NAC2.009 FACP:NAC2.008 FACP:NAC2.007 FACP:NAC2.006 FACP:NAC2.005 FACP:NAC2.004 FACP:NAC2.003 FACP:NAC2.002 FACP:NAC2.001 EXT. 1 NAC3 15CD 15CD 15CD 15CD 15CD 30CD 15CD 15CD 15CD 15CD 15CD - FACP:NAC3.011 FACP:NAC3.010 FACP:NAC3.009 FACP:NAC3.008 FACP:NAC3.007 FACP:NAC3.006 FACP:NAC3.005 FACP:NAC3.004 FACP:NAC3.003 FACP:NAC3.002 FACP:NAC3.001 15CD 15CD 30CD 30CD 30CD EOL 4.71K 0 / EOL Re FACP:NAC3.012 FACP:NAC3.013 FACP:NAC3.014 FACP:NAC3.015 FACP:NAC3.016 FACP:NAC3 TO 120VAC (BY OTHERS) EXT. 1 SLC1 FACP P � S P SLC1•S:001 SLC1•S:002 SLC1•S:00 I I FADC EXT. 1 AUX1 IL ---- EXT. 1 SBP1 EXT. 1 SBC1 FARA L- SBC1.001 SBP1.001 Circuit Legend Firm Name and Address antity Circuit Description J� 4%.hKfions P.O. BOX 2246 LYNNWOOD, WA 98036 PH: 425.771.1166 FAX: 425.771 .4422 www.abscosolutions.com 1 AUX1 Existing 14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP 1 NAC1 Existing 14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP 1 NAC2 Existing 14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP 1 NAC3 Existing 14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP 1 SLC1 Existing 16/2-ns = 16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP Project Name and Address U0 N M - . MEZZANINE O 0-) z 3 O N W MEZZANINE MAIN FLOOR EXT. 1 C1 DH rC1•REL:001 LEGAL NOTICE: THE INFORMATION AUXI.001 CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ABSCO SOLUTIONS, INC. ANY REPRODUCTION IN PART OR IN WHOLE WITHOUT THE WRITTEN PERMISSION OF ABSCO SOLUTIONS, INC. S S S P °M1 F SOP SP NF] S P P IS PROHIBITED. PATENT RIGHTS (WHERE P I SLC1•S:004 SLC1•S:005 SLC1•S:006 SLC1•M:003004, SLC1•M:APPLICABLE) COPYRIGHTS AND ALL 007 SLC1•S:007 SLC1•S:008 SLC1•M:008 SLC1•S:009 OTHER PROPRIETARY RIGHTS ARE 005,,006 I EXPRESSLY RESERVED BY A B S C 0 SOLUTIONS, INC. I F F I Designer of Record KEN DAY SLC1•M:001 SLC1•M:002 I ABSCO SOLUTIONS, INC. 19023 36TH AVE W STE E L_-----------------.-------� ---� LYNNWOOD, WA 98036 DH PHONE: (425) 771-1166 FAX: (425) 771-4422 C1•REL:001 EMAIL: KEN. DAY®ABSCOSOLUTIONS.COM EXT. AUX1.002 NICET: IV # 97083 1 C1 SP SP SP SP SP SP SP SP SP SLC1•S:018 SLC1•S:017 SLC1•S:016 SLC1•S:015 SLC1•S:014 SLC1•M:009, 010, SLC1•S:013 SLC1•S:012 SLC1•S:011 SLC1•S:010 011,012 SP F F F SLC1•S:019 SLC1•M:013 SLC1•M:014 SLC1•M:015 1-01/25/24 Submittal Set AP Rev.# -Date Revision By MAIN FLOOR Drawn By A.P. Checked By D.H. Date 01 /23/24 Project Name FIRE STATION #16 Project Number 26161 System Type FIRE ALARM 1 1 ? I I LL I I r� 1 -7 1 R D E F G I I z FACP NACl -001 15CD SLC1•S:002 MECH. RM. 200 Q -. SLC1•S.001 a Os� P LLLL -IF RADIO REPAIR 293 FACP NAC1 •N:002 15CD p SLC1•S:003 EOL Re STORAGE FACP 291 NAC 1 4.7K !O - - MEZZANINE - FIRE ALARM PLAN SCALE: 1 /8"=1 10" �5 X5 -- 4 I D Y1� (Y21 (Y1 4 Y5 I I I I I I I I I I rl----I--------I I— FACP I NAC3.012 I r 15CD �P I I SLC1•M:014 EXERCISE RM FACP ,0\ F EHSLC1•S:019 3-013 124 NAC1 CD SLC1•M:013 SLEEPING I FACP NAC3.014 F123 I 30CD -- — TSLEEPING 122 — — I SLC1•S:018 FACP OP 4_I _ I IVHl.3•U I I I J SLC1•M:015 F 15CD FACIP I NAC3 015 30CPD FACP SLC1•S:017 FACP I I / 30CD NAC3-016 NACCD3.010 °P I Re FACPSLC1•S:016 ----- 4NKS2 / SLEEPING'F v, MEN FACP 121 HALL J I I I 126 NAC3.007 I`�- 15CD 132 SLEEPING '-0 7 Ek V �� U10M.` 120 i J ( I� 125 SLC1• S:015 L e� I �) I `--�� ;O; FACP OO P FACP NAC3.009 I--'--' KITCHEN/DIN/ HALL NAC3.008 15CD I DAYROOM 12i SLC1•S:014 15CD I 13e C1•REL:001, AUX1.0,02 o P FACP DH , NAC3.004 j I;\r, SLC1•M:009, 15CD OP FACP N \ I 010, 011, 012 M SLC1•S:010 I NAC3.006 `� 30CD LAUNDRY 0 SLEEPING' P i � I f S S 128 NACFACP 3 005 SLC1•S:011 I 119 J � OP OP 15CD SLEE�PINJ-J SLC1•S:013 SLC1•S:012 ��_ _FACPI I 7'_` x 15CD — " NAC3.003 STORAGE I N xi 129 OP I I X` IF - SLC1•S:009 -: I NAC3.002_ �t - F SLC1•M:007 15CD FACP HALL SLC1•S:008 NACCD3.001 OP 131 REPORT DSK 0 O L _ — - -I SLC1•S:007 193 F SLC1•M:008 = C1•REL:001, �; f RESOURCE/ AUX1.001 I PROJ. AREA I 192, M:003� SLC1, I I � TOOL RM 004,005,006, 10� I l' LO I I FACP — NAC2.004 I 15CD I TOILET SLC1•S:006 FACP aP — _ NAC2.005 .- 15CD OFFICE n— FACP NAC2.003 15CD_ �� SUPPLIES/ WATCH I STORAGE OFFICE ' K P �jj >< - SLC1•S:005D -OI MS—'' T es T 99 I I1 OIL FACP NAC2.002-I I 15CD, ) LOBBY NAC2.001 1 SBC1.001, Q 15CD 199 SBP1.001 a _ aP L _ LSLC1•S:004 3 I APPARATUS SLC1 •M:0010 ROOM I I Il I I I II I I I II I I I II I I - I FACP O NAC2.010 — — — — — — 75CD I + I I I I II I EOL Re n0 FACP FACP ZS NAC2.011 NAC2 wP 75CD 4.7K Q b 1 Zi Firm Name and Address hs 4%.hirdom P.O. BOX 2246 LYNNWOOD, WA 98036 PH: 425.771.1166 FAX: 425.771 .4422 — — — — — — — JxVfi www.abscosoIutions.com Project Name and Address MAIN FLOOR -FIRE ALARM PLAN 'A"��N SCALE: 1 /8"=1 '0" V 1. ALL CIRCUITS ARE EXISTING. 2. REPLACE EXISTING FACP (EST-2). 3. REPLACE EXISTING DETECTION DEVICES AS NEEDED ON A LIKE -FOR -LIKE BASIS. 4. REUSE EXISTING NOTIFICATION DEVICES AS IS, IN THEIR CURRENT LOCATIONS AND CONFIGURATIONS. BUNKER/ STORAGE 114 FACP NAC2.009 75CD DECON 113 FACP + NAC2.008 15CD I SLC1 •M:002 �)3 - - OX-5 ■ N U� O 00 �O 0 � O � °0 0 W LEGAL NOTICE: THE INFORMATION\ CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ABSCO SOLUTIONS, INC. ANY REPRODUCTION IN PART OR IN WHOLE WITHOUT THE WRITTEN PERMISSION OF ABSCO SOLUTIONS, INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND ALL OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY A B S C 0 SOLUTIONS, INC. Designer of Record KEN DAY ABSCO SOLUTIONS, INC. 19023 36TH AVE W STE E LYNNWOOD, WA 98036 PHONE: (425) 771-1166 FAX: (425) 771-4422 EMAIL: KEN. DAY®ABSCOSOLUTIONS.COM NICET: IV # 97083 a- 1-01/25/24 Submittal Set AP Rev.# -Date Revision By Drawn By A.P. Checked By D.H. Date 01 /23/24 Project Name FIRE STATION #16 Project Number 26161 System Type FIRE ALARM Sheet Name MAIN FLOOR �C MEZZANINE FIRE ALARM PLAN