APPROVED FIR2024-0010+Fire_Alarm_Plan+2.6.2024_10.44.12_AM+4042240L
S
I
L
10
I
C
0
E
F
G
GENERAL SYSTEM NOTES
PANEL:
1. THE SUPPLEMENTAL NOTIFICATION REMOTE POWER SUPPLY (RPS) IS TO
BE MOUNTED SURFACE, BESIDE THE FACP. THE TOP OF THE PANEL SHALL
NOT EXCEED 6 FEET ABOVE FINISHED FLOOR SURFACE. A MINIMUM
CLEARANCE OF 36" WORKING SPACE SHALL BE MAINTAINED.
2. THE RPS IS TO BE POWERED BY THE SAME DEDICATED 120 VAC
CIRCUIT AS THE FACP. TWO CONDUCTORS TO 120 VAC, ONE CONDUCTOR
TO ISOLATED GROUND, 20 AMP DEDICATED CIRCUIT. A HOUSE GROUND WILL
NOT BE ACCEPTABLE.
3. THE BOTTOM THE RPS SHALL BE PENETRATED.
DEVICES:
1. ALL SIGNALING DEVICES SHALL HAVE THE BOTTOM OF THE DEVICE
PLACED AT 80 INCHES ABOVE FINISHED FLOOR WITHIN THE SPACE, OR THE
TOP OF THE DEVICE 6 INCHES BELOW THE CEILING, WHICHEVER IS LOWER.
2. THE AUDIBLE DEVICES SIGNAL SHALL BE SET TO THE TEMPORAL
SETTING.
3. ALL DEVICES ARE TO BE LOCATED PER THE DRAWINGS.
4. WHEN APPLICABLE, VERIFY WITH MECHANICAL CONTRACTOR THE
EXISTENCE AND LOCATION OF ALL MOTORIZED SMOKE DAMPERS. THESE ARE
TO BE 120 VAC DEVICES ON AS FEW CIRCUITS AS POSSIBLE. THESE DEVICE
CIRCUITS ARE TO BE CONTROLLED BY THE FACP THROUGH AN INTERFACING
RELAY.
5. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR ALL LOCATIONS
OF THE SPRINKLER WATERFLOW, DRY FLOW, HI/LO AIR, TAMPER SWITCHES
AND PIV OR 0, S, & Y VALVES.
6. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THE EXISTENCE
OF SPRINKLER HEAT TAPE. THIS HEAT TAPE SHALL BE MONITORED BY THE
FACP AND SHALL REQUIRE AN APPROPRIATE RELAY THAT WILL PROVIDE
SUPERVISION FOR HEAT TAPE GROUND FAULTS AND LOSS OF PRIMARY
POWER.
7. WHEN APPLICABLE, VERIFY WITH SPRINKLER CONTRACTOR THAT ALL
APPLICABLE INTERSTITIAL CEILING, ATTIC, OR FLOOR SPACES ARE PROTECTED
WITH SPRINKLER HEADS.
WIRING:
1. TWO DEDICATED PHONE LINES TO BE INSTALLED BY OWNER TO
TRANSMITTER.
2. ALL AUDIBLE / VISUAL CIRCUITS ARE TO BE 14 AWG FPL WIRE. (RISER
OR PLENUM RATED WIRE WHERE REQUIRED PER NEC).
3. AUDIBLE / VISUAL CIRCUITS ARE TO HAVE AN END OF LINE RESISTOR
(ELR) AS APPROPRIATE WITH THE FACP / RPS.
4. ALL FIRE ALARM WIRES ARE REQUIRED TO BE IDENTIFIED AND
APPROPRIATELY MARKED.
5. PER NEC, NO AC VOLTAGE WIRING OF ANY KIND SHALL BE RUN IN THE
SAME CONDUIT OR RISER AS THE LOW VOLTAGE FIRE ALARM SYSTEM WIRING.
6. ALL JACKETED CABLE MUST INCLUDE A JACKET REMOVAL PULL STRING
AS PART OF THE CABLE.
7. SHIELDED CABLE IS NOT AN ACCEPTABLE SUBSTITUTION FOR CABLE
WITHOUT "SHIELDED" AS PART OF THE DESCRIPTION.
GENERAL:
1. ALL FIRE ALARM JUNCTION BOXES ARE TO BE PAINTED RED.
2. ALL END OF LINE DEVICES SHALL HAVE AN IDENTIFYING E.O.L. STICKER
AT THE E.O.L. LOCATION.
3. ONLY CONDUCTORS INTENDED FOR TERMINATION TO THE SPECIFIC
DEVICE ON ANY GIVEN JUNCTION BOX SHALL BE LEFT OPEN FOR
TERMINATION IN THAT JUNCTION BOX. ALL OTHER CONDUCTORS SHALL PASS
THROUGH, OR BE SPLICED THROUGH, THAT JUNCTION BOX.
ALL EQUIPMENT AND LABOR PROVIDED BY ABSCO SOLUTIONS, INC. HAS
A WARRANTY OF ONE YEAR FROM DATE OF INVOICE. THIS WARRANTY
EXCLUDES ALL COVERAGE FOR CONSEQUENTIAL DAMAGES, AND IS GIVEN IN
LIEU OF ALL OTHER EXPRESS WARRANTIES OR IMPLIED WARRANTIES OF
FITNESS, HABITABILITY, OR MERCHANTABILITY OTHERWISE PROVIDED UNDER
THE LAWS OF WASHINGTON. ANY WARRANTY WORK PERFORMED BY ABSCO
SOLUTIONS, INC. DOES NOT EXTEND THE WARRANTY OF ONE YEAR FROM
THE DATE OF THE INVOICE.
THIS WARRANTY SHALL BE VOID IF A PERSON OR FIRM OTHER THAN
ABSCO SOLUTIONS, INC. OR THE CONTRACTOR AUTHORIZED BY ABSCO
SOLUTIONS, INC. PERFORMS OR RE —PERFORMS ANY WORK IDENTIFIED WITHIN
THE ORIGINAL SCOPE OF THE WORK OF THE CONTRACT WITH ABSCO
SOLUTIONS, INC.
LEGAL NOTICE: THE INFORMATION CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS, INC. ANY REPRODUCTION IN PART
OR IN WHOLE WITHOUT THE WRITTEN PERMISSION OF ABSCO SOLUTIONS,
INC. IS PROHIBITED. PATENT RIGHTS (WHERE APPLICABLE) COPYRIGHTS AND
ALL OTHER PROPRIETARY RIGHTS ARE EXPRESSLY RESERVED BY ABSCO
SOLUTIONS, INC.
H
9fl6imD fl3 �?
VI C N ITY MAP
®south county
Fire Station 1 r:
Approved
D F M Chris Burt
South County Fire
Date: 02/14/2024
02-14-2024
PLAN REVIEW
NOTES:
APPROVED
DFM BURT
FINISHED
CEILING
FINISHED
FLOOR
TYPICAL MOUNTING HEIGHTS
WALL MOUNT
—EXT. STROBE
—EXT. HORN STROBE
—EXT. HORN STROBE WP
CEILING MOUNT
—SMOKE DETECTOR
—HEAT DETECTOR
CONTROL MANUAL FARA
PANEL PULL
STATION
r F1
80" ( 60" 48" 60"
Symbol Legend
SYMBOL
DESCRIPTION
MANUFACTURER
PART NUMBER
BACKBOX REQUIREMENTS
QUANTITY
FACP
1110-PT ADDRESSABLE FACP
SILENT KNIGHT
6820
RED ENCLOSURE, PROVIDED
1
FARA
REMOTE LCD ANNUNCIATOR, RED
SILENT KNIGHT
586OR
RED BEZEL, PROVIDED
1
FADC
DOCUMENT STORAGE BOX WITH GW-FCI LOCK
GAMEWELL-FCI
GW-FAD
RED ENCLOSURE, PROVIDED
1
0P
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
SILENT KNIGHT
SK-PHOTO-W
4SQR W / 3-0 RING
18
O
LOW -PROFILE INTELLIGENT ROR THERMAL SENSOR WHITE
SILENT KNIGHT
SK-HEAT-ROR-W
4SQR W / 3-0 RING
1
PULL STATION, DOUBLE ACTION, ADDRESSABLE
SILENT KNIGHT
SK-PULL-DA
DEEP 4-SQR
7
2 DUAL MONITOR, 2 RELAY OUTPUT
SILENT KNIGHT
SK-RELAYMON-2
DEEP 4-SQR
2
DH
WALL -MOUNT DOOR HOLDER, FLUSH
NOTIFIER
FM998
PROVIDED
2
EXISTING STROBE, WHITE, WALL
EXISTING SWL
EXISTING
EXISTING
5
EXISTING HORN STROBE, WHITE, WALL
EXISTING P2WL
EXISTING
EXISTING
23
WP
EXISTING HORN STROBE, WHITE, WALL, OUTDOOR
EXISTING P2WK
EXISTING
EXISTING
1
EOL Re
EXISTING EOL-4.7K
EXISTING EOL-4.7
EXISTING
EXISTING
3
Fire Alarm Device Numbering
Circuit
Circuit
Unique ID
Unique ID
NACl-001
SLC1•S:001
ADDRESSABLE DEVICE NUMBERING
ADDRESSABLE NAC NUMBERING
Wire Path Label Legend
Chr. Position
Character Purpose
#1
Quantity of the same circuit
#2
Circuit name
Existing 14/2-ns = 14AWG 2 CONDUCTOR - NON -SHIELDED CABLE
Existing 16/2-ns = 16AWG 2 CONDUCTOR - NON -SHIELDED CABLE
PROJECT NOTES
• ALL CIRCUITS ARE EXISTING
• REPLACE EXISTING FACP (EST-2)
• REPLACE EXISTING DETECTION DEVICES AS NEEDED ON A LIKE —FOR —LIKE BASIS
• REUSE EXISTING NOTIFICATION DEVICE AS IS, IN THEIR LOCATIONS AND CONFIGURATIONS
• TECHNICIAN TO AS —BUILD DEVICE ADDRESSES
• TECHNICIAN TO AS —BUILD NOTIFICATION CIRCUITS
• AMBIENT TEMPERATURE 70°F IN ALL SPACES
• AMBIENT SOUND LEVEL >40DB IN ALL SPACES
SEQUENCE OF OPERATIONS
Output Activated
Alarm Device
General
Notification - Alarm
Horn + Horn
Strobe + Strobe
Transmit
Alarm
Signals
Transmit
Trouble
Signals at
FACP
Transmit
Supervisory
Signals at
FACP
Keypad
Annunciator
Smoke Detector
X
X
X
Heat Detector
X
X
X
Manual Pull Station
X
X
X
FACP Alarm
X
X
X
FACP Trouble
X
X
FACP Supervisory
I
I
I X
X
RECEIVED
F I R2024-001 0 Feb 0E 20
CITY OF DMONDSDS
DEVELOPMENT SERVICES
DEPARTMENT
Firm Name and Address
oQ�Ahsm
SO&tk=
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771 .4422
www.abscosolutions.com
Project Name and Address
LEGAL NOTICE: THE INFORMATION
CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS,
INC. ANY REPRODUCTION IN PART OR IN
WHOLE WITHOUT THE WRITTEN
PERMISSION OF ABSCO SOLUTIONS, INC.
IS PROHIBITED. PATENT RIGHTS (WHERE
APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE
EXPRESSLY RESERVED BY
A B S C 0 SOLUTIONS, INC.
Designer of Record
KEN DAY
ABSCO SOLUTIONS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: KEN. DAY®ABSCOSOLUTIONS.COM
NICET: IV # 97083
1-01/25/24
Submittal Set
AP
Rev.# —Date
Revision
By
Drawn By
A.P.
Checked By
D.H.
Date
01 /23/24
Project Name
FIRE STATION #16
Project Number
26161
System Type
FIRE
ALARM
Sheet Name
LEGENDS,
DETAILS,
EI R E ALARM
PANS
1
01
L I
0
-7 1 R
A
B
D
E
F
G
H
Cable/Circuit Report
Job number: 26161 Job name: Fire Station 16 - FA
Cable Length Overage: 10.000000%
Source
Circuit
Circuit Type
Wiring Style
Manufacturer
Part No.
Type
Description
Gauge
Length
Color
FACP
NAC1
Notification
Class B
WINDY CITY
767960
Fire Alarm
14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
#14
61'-2 1/2
Existing
FACP
NAC2
Notification
Class B
WINDY CITY
767960
Fire Alarm
14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
#14
368'-6
Existing
FACP
NAC3
Notification
Class B
WINDY CITY
767960
Fire Alarm
14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
#14
391'-11 1/2
Existing
FACP
SLC1
Signaling line
Class B
WINDY CITY
761360
Fire Alarm
16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP
#16
627'-4
Existing
Appliance List by Circuit
Circuit
Device
FACP:SLC1-M:001
ADDRESSABLE PULL STATION
FACP:SLC1-M:002
ADDRESSABLE PULL STATION
FACP:SLC1-M:003,004,005,006
MULTI -INPUT MODULE
FACP:SLC1-M:007
ADDRESSABLE PULL STATION
FACP:SLC1-M:008
ADDRESSABLE PULL STATION
FACP:SLC1-M:009, 010, 011, 012
MULTI -INPUT MODULE
FACP:SLC1-M:013
ADDRESSABLE PULL STATION
FACP:SLC1-M:014
ADDRESSABLE PULL STATION
FACP:SLC1-M:015
ADDRESSABLE PULL STATION
FACP:SLC1-S:001
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:002
HEAT DETECTOR
FACP:SLC1-S:003
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:004
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:005
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:006
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:007
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:008
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:009
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:010
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:011
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:012
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:013
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:014
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:015
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:016
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:017
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:018
PHOTOELECTRIC DETECTOR
FACP:SLC1-S:019
PHOTOELECTRIC DETECTOR
Battery Calculations for Panel: FACP
Part No:6820-1110-PT ADDRESSABLE FACP
Job number: 26161 Job name: Fire Station 16 - FA
Part No.
Qty.
Description
Standby
Total Standby
Alarm
Total Alarm
Panel Equipment
6820_MB
1
MAIN BOARD, 6820
190.0000 mA
190.0000 mA
250.0000 mA
250.0000 mA
Total Panel Stby
190.0000 mA
Total Panel Alarm
250.0000 mA
Peripheral Devices
EXISTING P2WL
17
EXISTING HORN STROBE, WHITE, WALL (Notification) 15CD 88dB
0.0000 mA
0.0000 mA
53.0000 mA
901.0000 mA
EXISTING P2WK
1
EXISTING HORN STROBE, WHITE, WALL, OUTDOOR (Notification) 75CD 88dB
0.0000 mA
0.0000 mA
176.0000 mA
176.0000 mA
EXISTING P2WL
1
EXISTING HORN STROBE, WHITE, WALL (Notification) 110CD 88dB
0.0000 mA
0.0000 mA
164.0000 mA
164.0000 mA
EXISTING P2WL
2
EXISTING HORN STROBE, WHITE, WALL (Notification) 75CD 88dB
0.0000 mA
0.0000 mA
119.0000 mA
238.0000 mA
EXISTING SWL
4
EXISTING STROBE, WHITE, WALL (Notification) 15CD
0.0000 mA
0.0000 mA
43.0000 mA
172.0000 mA
EXISTING P2WL
3
EXISTING HORN STROBE, WHITE, WALL (Notification) 30CD 88dB
0.0000 mA
0.0000 mA
73.0000 mA
219.0000 mA
EXISTING SWL
1
EXISTING STROBE, WHITE, WALL (Notification) 30CD
0.0000 mA
0.0000 mA
63.0000 mA
63.0000 mA
FM998
2
WALL -MOUNT DOOR HOLDER, FLUSH (Power)
20.0000 mA
40.0000 mA
0.0000 mA
0.0000 mA
5860R
1
REMOTE LCD ANNUNCIATOR, RED (Power)
20.0000 mA
20.0000 mA
20.0000 mA
20.0000 mA
5860R
1
REMOTE LCD ANNUNCIATOR, RED (Serial)
0.0000 mA
0.0000 mA
0.0000 mA
0.0000 mA
SK-RELAYMON-2
2
2 DUAL MONITOR, 2 RELAY OUTPUT (Signaling line)
1.3500 mA
2.7000 mA
24.0000 mA
48.0000 mA
SK-PULL-DA
7
PULL STATION, DOUBLE ACTION, ADDRESSABLE (Signaling line)
0.3500 mA
2.4500 mA
0.3500 mA
2.4500 mA
SK-PHOTO-W
18
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE (Signaling line)
0.2000 mA
3.6000 mA
0.2000 mA
3.6000 mA
SK-HEAT-ROR-W
1
LOW -PROFILE INTELLIGENT ROR THERMAL SENSOR WHITE (Signaling line)
0.2000 mA
0.2000 mA
0.2000 mA
0.2000 mA
FM998
2
WALL -MOUNT DOOR HOLDER, FLUSH (Relay)
0.0000 mA
0.0000 mA
0.0000 mA
0.0000 mA
EXISTING EOL-4.7
3
EOL-4.7K (Notification)
0.0000 mA
0.0000 mA
0.0000 mA
0.0000 mA
Total Peripheral Stby
68.9500 mA
Total Periph Alarm
2007.2500 mA
Total Standby Amps
258.9500 mA
Total Alarm Amps
2257.2500 mA
Standby time: 24 Hrs 6.215 Ah
Alarm time: 5 Min 0.188 Ah
Battery requirement: 6.403 Ah
Compensation Factors - Standby: 1.2 Alarm: 1.2 Requirement with compensation: 7.683 Ah
Circuit Calculations Panel: FACP Card: FACP Circuit:SLC1
Circuit Name: SLC1
Circuit Type: Signaling line/SK - SLC Terminal Voltage: 20.4 V:DC Amperage: 1.0000 A
Cable: 16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP #16
Calculations based on Running Total Length.
Design Criteria: Ambient temperature: 167 OF Max. operating voltage drop: 18%
Device
Part No
Appliance Desc
Distance
Current
Voltage
Voltage Drop
6820
Panel
20.4 V
S:001
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
2'-11 1/2
0.2000 mA
20.3999 V
(0.0001 V)
S:002
SK-HEAT-ROR-W
LOW -PROFILE INTELLIGENT ROR THERMAL SENSOR WHITE
13'-11 1/2
0.2000 mA
20.3989 V
(0.0009 V)
S:003
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
29'-0 1/2
0.2000 mA
20.3969 V
(0.002 V)
M:001
SK-PULL-DA
PULL STATION, DOUBLE ACTION, ADDRESSABLE
55'-0
0.3500 mA
20.3931 V
(0.0038 V)
M:002
SK-PULL-DA
PULL STATION, DOUBLE ACTION, ADDRESSABLE
115'-7
0.3500 mA
20.3928 V
(0.0003 V)
S:004
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
4'-9
0.2000 mA
20.3929 V
(0.0003 V)
S:005
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
18'-10 1/2
0.2000 mA
20.3918 V
(0.0011 V)
S:006
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
25'-9 1/2
0.2000 mA
20.3903 V
(0.0015 V)
M:003,004,005,006
SK-RELAYMON-2
2 DUAL MONITOR, 2 RELAY OUTPUT
16'-8 1/2
1.3500 mA
20.3894 V
(0.0009 V)
M:007
SK-PULL-DA
PULL STATION, DOUBLE ACTION, ADDRESSABLE
17'-2 1/2
0.3500 mA
20.3886 V
(0.0008 V)
S:007
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
11'-11
0.2000 mA
20.3881 V
(0.0005 V)
S:008
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
27'-5 1/2
0.2000 mA
20.3869 V
(0.0011 V)
M:008
SK-PULL-DA
PULL STATION, DOUBLE ACTION, ADDRESSABLE
W-41/2
0.3500 mA
20.3868 V
(0.0001 V)
S:009
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
19'-8
0.2000 mA
20.3861 V
(0.0007 V)
S:010
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
13'-5
0.2000 mA
20.3856 V
(0.0005 V)
S:011
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
13'-10 1/2
0.2000 mA
20.3852 V
(0.0004 V)
S:012
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
24'-10 1/2
0.2000 mA
20.3844 V
(0.0008 V)
S:013
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
18'-6 1/2
0.2000 mA
20.3838 V
(0.0006 V)
M:009, 010, 011, 012
SK-RELAYMON-2
2 DUAL MONITOR, 2 RELAY OUTPUT
40'-7 1/2
1.3500 mA
20.3827 V
(0.0012 V)
S:014
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
X-9 1/2
0.2000 mA
20.3826 V
(0.0001 V)
S:015
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
29'-2
0.2000 mA
20.3821 V
(0.0005 V)
S:016
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
14'-2 1/2
0.2000 mA
20.3819 V
(0.0002 V)
S:017
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
16'-2
0.2000 mA
20.3817 V
(0.0002 V)
S:018
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
17'-2 1/2
0.2000 mA
20.3815 V
(0.0002 V)
S:019
SK-PHOTO-W
LOW -PROFILE PHOTOELECTRIC SENSOR WHITE
14'-5 1/2
0.2000 mA
20.3813 V
(0.0001 V)
M:013
SK-PULL-DA
PULL STATION, DOUBLE ACTION, ADDRESSABLE
12'-2 1/2
0.3500 mA
20.3812 V
(0.0001 V)
M:014
SK-PULL-DA
PULL STATION, DOUBLE ACTION, ADDRESSABLE
34'-51/2
0.3500 mA
20.381 V
(0.0002 V)
M:015
SK-PULL-DA
PULL STATION, DOUBLE ACTION, ADDRESSABLE
12'-0
0.3500 mA
20.381 V
(0 V)
627'-4
8.9500 mA
Total Current: 8.9500 mA
(Total VDrop Percent:0.09%) Total Voltage Drop : 0.019 V
Firm Name and Address
4%.hirdom
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771 .4422
www.abscosolutions.com
Project Name and Address
LEGAL NOTICE: THE INFORMATION
CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS,
INC. ANY REPRODUCTION IN PART OR IN
WHOLE WITHOUT THE WRITTEN
PERMISSION OF ABSCO SOLUTIONS, INC.
IS PROHIBITED. PATENT RIGHTS (WHERE
APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE
EXPRESSLY RESERVED BY
A B S C 0 SOLUTIONS, INC.
Designer of Record
KEN DAY
ABSCO SOLUTIONS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: KEN.DAY@ABSCOSOLUTIONS.COM
NICET: IV # 97083
05-
1-01/25/24
Submittal Set
AP
Rev.# -Date
Revision
By
Drawn By
A.P.
Checked By
D.H.
Date
01 /23/24
Project Name
FIRE STATION #16
Project Number
26161
System Type
FIRE
ALARM
1 1 ? I I /I I I i; 1 7 1 R
A
B
D
E
F
G
H
EXT.
1 NAC1
EOL 4.71K Q 15CD 15CD
EOL Re � E
FACP:NAC1 FACP:NAC1•N:002 FACP:NAC1.001
EXT.
1 NAC2
WP
EOL 4.7K S2 75CD
75CD
75CD
15CD
15CD
110CD
15CD
75CD
15CD
15CD
75CD
/ -
FACP:NAC2 FACP:NAC2.011
FACP:NAC2.010
FACP:NAC2.009
FACP:NAC2.008
FACP:NAC2.007
FACP:NAC2.006
FACP:NAC2.005
FACP:NAC2.004
FACP:NAC2.003
FACP:NAC2.002
FACP:NAC2.001
EXT.
1 NAC3
15CD
15CD
15CD
15CD
15CD
30CD
15CD
15CD
15CD
15CD
15CD
-
FACP:NAC3.011
FACP:NAC3.010
FACP:NAC3.009
FACP:NAC3.008
FACP:NAC3.007
FACP:NAC3.006
FACP:NAC3.005
FACP:NAC3.004
FACP:NAC3.003
FACP:NAC3.002
FACP:NAC3.001
15CD
15CD
30CD
30CD
30CD
EOL 4.71K 0
/
EOL Re
FACP:NAC3.012
FACP:NAC3.013
FACP:NAC3.014
FACP:NAC3.015
FACP:NAC3.016
FACP:NAC3
TO 120VAC
(BY OTHERS)
EXT.
1 SLC1
FACP
P � S P
SLC1•S:001 SLC1•S:002 SLC1•S:00
I I
FADC
EXT.
1 AUX1
IL ----
EXT.
1 SBP1
EXT.
1 SBC1
FARA
L- SBC1.001
SBP1.001
Circuit Legend
Firm Name and Address
antity
Circuit
Description
J�
4%.hKfions
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771 .4422
www.abscosolutions.com
1
AUX1
Existing 14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
1
NAC1
Existing 14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
1
NAC2
Existing 14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
1
NAC3
Existing 14/2-ns = 14 AWG 2 CONDUCTOR BARE COPPER, TWISTED NON -SHIELDED PLENUM FA FPLP
1
SLC1
Existing 16/2-ns = 16 AWG 2 CONDUCTOR BARE COPPER TWISTED NON -SHIELDED PLENUM FA FPLP
Project Name and Address
U0
N
M
- .
MEZZANINE O
0-)
z
3 O
N
W
MEZZANINE
MAIN FLOOR
EXT.
1 C1
DH
rC1•REL:001 LEGAL NOTICE: THE INFORMATION
AUXI.001 CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS,
INC. ANY REPRODUCTION IN PART OR IN
WHOLE WITHOUT THE WRITTEN
PERMISSION OF ABSCO SOLUTIONS, INC.
S S S P °M1 F SOP SP NF] S P P IS PROHIBITED. PATENT RIGHTS (WHERE
P I SLC1•S:004 SLC1•S:005 SLC1•S:006 SLC1•M:003004, SLC1•M:APPLICABLE) COPYRIGHTS AND ALL
007 SLC1•S:007 SLC1•S:008 SLC1•M:008 SLC1•S:009 OTHER PROPRIETARY RIGHTS ARE
005,,006 I EXPRESSLY RESERVED BY
A B S C 0 SOLUTIONS, INC.
I
F F I Designer of Record
KEN DAY
SLC1•M:001 SLC1•M:002 I ABSCO SOLUTIONS, INC.
19023 36TH AVE W STE E
L_-----------------.-------� ---� LYNNWOOD, WA 98036
DH PHONE: (425) 771-1166
FAX: (425) 771-4422
C1•REL:001 EMAIL: KEN. DAY®ABSCOSOLUTIONS.COM
EXT. AUX1.002 NICET: IV # 97083
1 C1
SP SP SP SP SP SP SP SP SP
SLC1•S:018 SLC1•S:017 SLC1•S:016 SLC1•S:015 SLC1•S:014 SLC1•M:009, 010, SLC1•S:013 SLC1•S:012 SLC1•S:011 SLC1•S:010
011,012
SP F F F
SLC1•S:019 SLC1•M:013 SLC1•M:014 SLC1•M:015
1-01/25/24 Submittal Set AP
Rev.# -Date Revision By
MAIN FLOOR
Drawn By
A.P.
Checked By
D.H.
Date
01 /23/24
Project Name
FIRE STATION #16
Project Number
26161
System Type
FIRE
ALARM
1 1 ? I I LL I I r� 1 -7 1 R
D
E
F
G
I I z
FACP
NACl -001
15CD
SLC1•S:002
MECH.
RM.
200 Q
-. SLC1•S.001 a
Os�
P LLLL
-IF
RADIO REPAIR
293
FACP
NAC1 •N:002
15CD
p
SLC1•S:003
EOL Re
STORAGE
FACP
291
NAC 1
4.7K !O -
-
MEZZANINE - FIRE ALARM PLAN
SCALE: 1 /8"=1 10"
�5
X5 --
4 I D
Y1� (Y21 (Y1 4 Y5
I I I I I
I
I I
I I
rl----I--------I I—
FACP
I NAC3.012
I r 15CD �P I
I SLC1•M:014 EXERCISE RM FACP ,0\ F EHSLC1•S:019
3-013
124 NAC1 CD SLC1•M:013 SLEEPING I
FACP
NAC3.014 F123
I 30CD -- — TSLEEPING 122
— — I SLC1•S:018
FACP OP 4_I _
I IVHl.3•U I I I
J SLC1•M:015 F 15CD
FACIP
I NAC3 015
30CPD FACP SLC1•S:017 FACP
I I / 30CD NAC3-016 NACCD3.010
°P
I Re FACPSLC1•S:016
----- 4NKS2 /
SLEEPING'F
v, MEN FACP 121 HALL J I
I I 126 NAC3.007 I`�-
15CD 132 SLEEPING
'-0 7 Ek V �� U10M.` 120 i J
( I� 125 SLC1• S:015
L e� I �) I `--�� ;O; FACP OO P
FACP
NAC3.009
I--'--'
KITCHEN/DIN/ HALL NAC3.008 15CD
I DAYROOM 12i SLC1•S:014 15CD I
13e C1•REL:001,
AUX1.0,02 o P FACP
DH , NAC3.004
j I;\r, SLC1•M:009, 15CD OP
FACP N \ I 010, 011, 012 M SLC1•S:010
I NAC3.006 `�
30CD LAUNDRY 0 SLEEPING'
P
i �
I f S S 128 NACFACP 3 005 SLC1•S:011 I 119 J �
OP OP
15CD SLEE�PINJ-J
SLC1•S:013 SLC1•S:012 ��_ _FACPI
I 7'_` x 15CD
— " NAC3.003
STORAGE I N
xi
129 OP I
I X` IF - SLC1•S:009 -: I
NAC3.002_
�t - F SLC1•M:007 15CD
FACP HALL SLC1•S:008
NACCD3.001 OP 131 REPORT DSK 0 O L _ — -
-I SLC1•S:007 193 F SLC1•M:008
= C1•REL:001, �; f
RESOURCE/ AUX1.001 I
PROJ. AREA
I 192, M:003�
SLC1, I
I
� TOOL RM 004,005,006, 10�
I l' LO I I FACP
— NAC2.004
I 15CD I
TOILET
SLC1•S:006 FACP
aP — _ NAC2.005 .-
15CD
OFFICE
n— FACP
NAC2.003
15CD_
�� SUPPLIES/
WATCH I STORAGE
OFFICE '
K P �jj >< -
SLC1•S:005D -OI MS—''
T es T 99 I I1
OIL
FACP
NAC2.002-I
I 15CD, )
LOBBY NAC2.001
1 SBC1.001, Q 15CD
199 SBP1.001 a _
aP L _
LSLC1•S:004 3
I APPARATUS
SLC1 •M:0010 ROOM
I I Il I
I I II I
I I II I
I I II
I I
-
I FACP O
NAC2.010 — — — — — —
75CD
I + I I I I
II I
EOL Re n0 FACP
FACP ZS NAC2.011
NAC2 wP 75CD
4.7K Q
b 1 Zi
Firm Name and Address
hs
4%.hirdom
P.O. BOX 2246
LYNNWOOD, WA 98036
PH: 425.771.1166
FAX: 425.771 .4422
— — — — — — — JxVfi www.abscosoIutions.com
Project Name and Address
MAIN FLOOR -FIRE ALARM PLAN 'A"��N
SCALE: 1 /8"=1 '0" V
1. ALL CIRCUITS ARE EXISTING.
2. REPLACE EXISTING FACP (EST-2).
3. REPLACE EXISTING DETECTION DEVICES AS NEEDED ON
A LIKE -FOR -LIKE BASIS.
4. REUSE EXISTING NOTIFICATION DEVICES AS IS, IN THEIR
CURRENT LOCATIONS AND CONFIGURATIONS.
BUNKER/
STORAGE
114
FACP
NAC2.009
75CD
DECON
113
FACP
+ NAC2.008
15CD
I SLC1 •M:002
�)3
- - OX-5
■
N
U� O
00
�O
0
� O
�
°0 0
W
LEGAL NOTICE: THE INFORMATION\
CONTAINED IN THIS DRAWING IS THE
SOLE PROPERTY OF ABSCO SOLUTIONS,
INC. ANY REPRODUCTION IN PART OR IN
WHOLE WITHOUT THE WRITTEN
PERMISSION OF ABSCO SOLUTIONS, INC.
IS PROHIBITED. PATENT RIGHTS (WHERE
APPLICABLE) COPYRIGHTS AND ALL
OTHER PROPRIETARY RIGHTS ARE
EXPRESSLY RESERVED BY
A B S C 0 SOLUTIONS, INC.
Designer of Record
KEN DAY
ABSCO SOLUTIONS, INC.
19023 36TH AVE W STE E
LYNNWOOD, WA 98036
PHONE: (425) 771-1166
FAX: (425) 771-4422
EMAIL: KEN. DAY®ABSCOSOLUTIONS.COM
NICET: IV # 97083
a-
1-01/25/24
Submittal Set
AP
Rev.# -Date
Revision
By
Drawn By
A.P.
Checked By
D.H.
Date
01 /23/24
Project Name
FIRE STATION #16
Project Number
26161
System Type
FIRE
ALARM
Sheet Name
MAIN FLOOR �C
MEZZANINE
FIRE ALARM PLAN