APPROVED FIR2023-0003+Fire_Sprinkler_Plan+1.13.2023_1.10.00_PM+3314150(l� Q Q 4 4
I I I I I I
-10.17
W .. I I I.
SECTION- LOOKING EAST@ LIVING
SCALE:NTS
MASTER BATHROOM
NTRY
L I
Approved
D F M CMrLfs i�,u.rt
South County Fire
Date: 01/25/2023
10'-7" 01-25-2023
------�2NDFLOOR PLAN REVIEW
NOTES: APPROVED WITH CONDITIONS:
1. Approved set of plans must be on site at the time of
inspection. Failure to provide the approved plan may reSL
in a re -inspection fee. System drain(s) required at riser ar
must drain to the exterior. If riser is above lowest grade,
- - �2'-101/2"(237.88'1 2nd drain required and signage at riser indicating Iocatior
AVG.GRADE is required. Systems required signage IAW NFPA 13D.
2 N RrGRADE 2. Coverage required to the following areas: Clothes
closets, linen closets and pantries exceeding 24 square
-2 feet in area, with the smallest dimension greater than 3'
, .�
FOUN[TATI(5N and having wall and ceiling surfaces of gypsum board.
Bathrooms more than 55 square feet in area. When fuel
fired equipment is present on covered decks or porches,
if living space above, at least one quick -response
intermediate temperature sprinkler shall be installed abov
equipment or area under living space. All fuel fired
appliances except attics if above all living areas.
DFM Burt
10.17
06.34 1
I I
V 9'-7"
------ ROOF
I I
MASTER BED DOM
I I 1 I
a
2NDFLOOR
I I I
;I
LIVING RID M
;i 2'-10 1/2" (237.88')
-- - ;i --------�AVG.GRADE
l
1ST FLOOR, I
- T, cnlwnannn
SECTION- LOOKING EAST@ LIVING
SCALE: NTS
I I -
I I
I I LOFT 1
I I I
I II
I I I
I I
I � I
06.34 I 2
I I II
I I F5 I
I I
I I I
I I KITCHEN DINING I
I I I
I I I
I I 4.1 Ll
I � I
I I I I
I I I I
16 I I I
I q I C CE I
M.
I I I I
I
SECTION- LOOKING EAST@ LIVING
SCALE: NTS
10'mWl1'k_
19' 7"
ROOF
16'-9 1 2"
12 T.O.P. @ KITCHEN N. WALL
01.5
14'-2 1r2"
-�---
T.O.P. @KITCH-
EN S. WALL
Jo,-7,.
2NDFLOOR
LOFT FLOOR
I
__2'-10112"(237.88')
AVG-GRADE
( Q Q
I I I I I
SECTION- LOOKING EAST@ LIVING
SCALE: NTS
NORTH DRAWING ABBREVIATION
SPR - SPRIG
RN - RISER NIPPLE
DP - DROP
FF - FINISH FLOOR
TS - TOP OF STEEL
OTS - OPEN TO STRUCTURE
COJ - CUT ON JOB
DRAWING SYMBOLS
J
EQ BRACING
f
-HANGER
- BRANCH LINE RESTRAINT
- CENTER LINE
❑
- HYDRAULIC CAL NODE
L_J
LEVEL1 - FIRE PROTECTION
SCALE: 1/4" = l'-O"
REMOTE AREA NUMBER 1
ANGLE RESIDENCE HYDRAULICALLY CALCULATED TO DELIVER
A 13D SYSTEM.
7PS1 @ 13 GPM (2 TOTAL HEADS) . 4.91K
HEADS: 16' X 16' S1.FT. SPACING (TYP. U.N.O.)
Hydraulic Information
OCCUPANCY CLASSIFICATION
Residential
TOTAL HEADS FLOWING
2
K-FACTOR
4.9
TOTAL WATER REQUIRED
26.69
TOTAL PRESSURE REQUIR
SAFETY MARGIN (psi)
+82.83
(57.1.2%)
Total gpm from
heads at node 119
and 121.
19'-7"
0
------ ROOF
J0'7"
2ND FLOOR
LOFT FLOOR
1" WATER
METER
BY OTHERS
CONDITION:
REQUIRED TO
DRAIN TO
EXTERIOR.
CITY CONNECTION FROM
15724 72ND AVE W,
EDMONDS, WA
CONNECTION PER CITY
OF EDMONDS REQUIREMENTS
STATIC PRESSURE: 145.18 PSI
RESIDUAL PRESSURE: 88.82
FLOW PRESSURE: 1000 GPM
SCOPE OF WORK:
1.COLUMBIA FIRE INC. SCOPE OF WORK IS TO INSTALL A WET, FLOW
THROUGH SPRINKLER SYSTEM FOR THE NEW SINGLE FAMILY
BUILDING TO COMPLY WITH NFPA #13D-2016.
2.SPRINKLER PLAN SUBMIT TO THE CITY OF EDMONDS FOR
APPROVAL.
3.MATERIALS PER NFPA #13D-2016 EDITION STANDARDS.
43ESTING PER NFPA #13D-2016 EDITION AND THE CITY OF EDMONDS.
GENERAL NOTES:
1.ALL MATERIAL AND EQUIPMENT TO BE NEW AND UL LISTED OR FM
APPROVED.
2.PIPE LENGTH ARE SHOWN AS CUT LENGTH.
3.PIPE HANGERS AND METHOD OF HANGING TO BE IN ACCORDANCE
WITH NFPA #13D-2016 EDITION.
4.PIPING SHALL BE IN ACCORDANCE WITH NFPA #13D-2016 EDITION.
5.JOINING OF PIPE/FITTINGS (THREADED AND WELDED) SHALL BE IN
ACCORDANCE WITH NFPA #13D-2016 EDITION.
6.OWNER TO PROVIDE ADEQUATE HEAT TO PREVENT WATER IN
PIPES FROM FREEZING IN AREAS PROTECTED BY A WET PIPE
SPRINKLER SYSTEM.
TSTRUCTURAL ADEQUACY OF THE BUILDING TO SUPPORT THE
SPRINKLER PIPING IS THE RESPONSIBILITY OF THE OWNER AND/OR
HIS STRUCTURAL.
8.ALL FIRE ALARMS, WIRING, MONITORING ARE TO BE INSTALLED BY
OTHERS. RESPONSIBILITY OF THE OWNER AND/OR HIS
SUBCONTRACTOR.
DESIGN CRITERIA:
1. RESIDENTIAL, 256 SQ.FT PER SPRINKLER.
2. SPRINKLER NOT REQUIRED IN BATHROOMS OF 55 SQ. FT OR LESS.
3. SPRINKLER NOT REQUIRED IN CLOSETS LESS THAN 24 SQ. FT.
1" OUT TO FIRE
SPRINKLER SYSTEM
PRESSURE 6SPARE
GAUGE ❑ FHEAD BOX
SHUT OFF VALVE�r `BOUT TO
(By
OTHERSI DOMESTIC
Z_
FROM CITY
0
1" PEX CONNECTION
UFLUSHED GM (BY OTHERS)
BEFORE V.
CONNECTING 1" WATER METER COPPER
TO SPRINKLER RISER (BY OTHERS)
(BY OTHERS)
RISER DETAILS
SCALE: NTS
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER AND IS THE
MINIMUM FASTENER SIZE ACCEPTABLE
O
I
CPVC DOUBLE FASTENER STRAP TYPE HANGER
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER AND IS THE
MINIMUM FASTENER SIZE ACCEPTABLE
®I I®
CPVC DOUBLE FASTENER STRAP TYPE HANGER
TOLCO FIG. 923 TOLCO RG #24
HANGER TYPE CP HANGER TYPE CP
NTS NTS
ATTIC INSULATION (BY OTHERS).
USE BATT TYPE INSULATION
FOR TENTING.
CPVC FIRE SPRINKLER PIPE
iBOTTOM CHORD
OF TRUSS
7 � 7
� TENT FIRE SPRINIERPIPE
GWBCEILING
BEFORE INSULATING ATTIC
(BY OTHERS). USE GATT TYPE
INSULATION FOR TENTING.
WET PIPE FREEZE
PROTECTION DETAIL
NTS
QTiffany Hansen Sales
3
a
L
n
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER AND IS THE
MINIMUM FASTENER SIZE ACCEPTABLE
I
"STAND-OFF" HANGER & RESTRAINER
TOLCO R G. #28
HANGER TYPE CP
1561h St SW
a.
_Q
N
15724 72nd Ave W.
Edmonds, WA 98026
NTS
0
n
`m
157th St SW
5'-611 SILL HEIG T: SILL HEIGHT:
36" (36" MA PER 36" (36"MAX PER �, 36" (36" MAX PER / 158th St SW
WAC 296-1 OM-0550 X WAC 29-150M-0550 WAC 296-15OM-0550
- - - - s -10 AVG1 GRADE
n
3(d)) 3(d)) 3(dll
FABRICATION SYMBOLS
CM1.A SPRINKLER MAIN FAB NUMBER
B 1 SPRINKLER LINE FAB NUMBER
L
Sc
Sprinkler Legend
S mbol
Manufacturer
SIN
Model
Quantity
K-Factor
Type
Size
Response
Finish
Temperature
Note
Viking
VK494
Freedom
18
4.9
Pendent
%
Fast
Brass
155OF
WH - CON.
Viking
VK494
Freedom
5
4.9
Pendent
%
Fast
Brass
200OF
WH - CON.
Total = 23
MK
DATE
WAf NI6TON STATE
� CERTIFICATEE OF lOM PETENlY
FIRE PROTECTION SPRINKLER SYSTEMS
Steve Adamson
4265-0691-C Level 3
Columbia Fire, LLC.
COLUMFL795NJ
/� � Expires
Signaturemmmmmmmmm
3 �
a a
N M�ooy n
3 dd/PR �
a- a
4,
FIR2023-0003 VICINITY MAP
SCALE: NTS
NORTH
n
RECEIVED
Jan 19 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
REVISIONS
Columbia Fire
ANGLE RESIDENCE
15724 72ND AVE W
EDMONDS, WA, 98026
JOB NO.
2210082
AHJ: CITY OF EDMONDS
SHEET DESCRIPTION
DATE
12.19.22
CAST ARCHITECTURE
115-C NORTH 36TH STREET
SEATTLE WA 98103
> >
GC: FORREST (206) 256-9886
FP
SPRINKLER SYSTEM SERVICE & REPAIR
WA CL# COLUMFL795NJ
111 South Findlay Street
Seattle, WA 98108
(206) 232-8569
DESIGNER
NAJEEB HABIB
PM
MERCEDES LAWRENCE
SCALE
1/4"=1'-0"