APPROVED FIR2024-0049+Fire_Sprinkler_Plan+6.27.2024_10.52.15_PM+4348577TOP RIDGE +/-25.fi'
TOP
SE_'OND FLOOR + -
1 SECTION VIEW
FP-01 1/8" =1'-011
1 1/211
125'-0"
99 � RISER RISER RISER I RISER � I I 1" M
UNIT 4 1 UNIT 3 1 UNIT 2 1 UNIT 1
COMMENT: DRAINING
THROUGH EXTERIOR WATER
SPIGOT IS ACCEPTABLE. IF
PLUMBED TO DRAIN THROUGH
SITE PLAN THE EXTERIOR SPIGOT AND IN
ADDITION TO THE "DRAIN
N NITS VALVE" PLACARD, ATTACH A
PLACARD AT THE INTERIOR
DRAIN VALVE STATING:
"SPRINKLER DRAINS THROUGH
EXTERIOR SPIGOT"
�11016]»elATi1Le]N:14
CASCADIA FIRE PROTECTION TO DESIGN AND INSTALL A COMPLETE "FLOW THROUGH" FIRE PROTECTION
SYSTEM BASED ON NFPA#13D - 2019AND CITY OF EDMONDS REQUIREMENTS FOR EACH UNIT.
CASCADIA FIRE PROTECTION TO STARTATTHE UNDERGROUND OUTLET PROVIDED BY OTHERS.
DESIGN CRITERIA:
DWELLING UNITS: NFPA#13D
DESIGN DENSITY:.05 GPM / 2 RESIDENTIAL SPRINKLERS
HOSE ALLOWANCE: 0 GPM
MAXIMUM SPACING: 256 SQ. FT.
WATER SUPPLY:
PRIMARY: CITY WATER SUPPLY
STATIC PSI: 55 PSI
RESIDUAL: 500 GPM AT 20 PSI
DESIGN NOTES:
1. BUILDING IS CONSTRUCTED WITH WOOD FLOORING ON WOOD BEAMS AND TJI STRUCTURE.
2. SPRINKLER DEFLECTOR AND LOCATIONS SHALL BE DESIGNED IN ACCORDANCE WITH NFPA#13D - 2019.
3. ALL SEISMIC BRACING AND HANGER ASSEMBLIES TO BE INSTALLED IN ACCORDANCE TO NFPA#13D - 2019.
4. CPVC PIPE AND FITTINGS TO BE LISTED FOR FIRE PROTECTION.
GENERAL NOTES:
1. ALL PAINTING OR LABELING OF FIRE SPRINKLER PIPING, IF REQUIRED, TO BE DONE BY OTHERS.
2. ALL MATERIALS TO BE INSTALLED SHALL BE UL LISTED.
3. IT IS THE OWNER'S RESPONSIBILITY TO ENSURE THATTHE STRUCTURE SHOWN ON THE CONTRACT
DRAWINGS CAN ADEQUATELY SUPPORTALL FIRE SPRINKLER PIPE AND SEISMIC LOADS.
4. OWNER IS REPSPONSIBLE FOR MAINTAINING TEMPERATURES ABOVE 40 DEGREES TO PROTECTTHE WET
FIRE SPRINKLER SYSTEM FROM FREEZING.
5. ALL WIRING OF FIRE PROTECTION SYSTEM COMPONENTS TO BE DONE BY OTHERS.
6. ALL PIPE AND COMPONENTS TO BE TESTEDAND INSPECTED IN ACCORDANCE WITH NFPA#13D - 2019.
Hanger No. 17W
Pipe Strap
Pipe Strap
Wootl Screw#12 x l%' Pipe
I
Wood Joist or Beam
Wood Screw #18 x 1'h"
Hanger No. 19W
Offset Pipe Hanger
- Pipe
ffset Pipe Hanger
t(o
Wool Joist, Beam or Deck
ca
LU
z
W
a
I—
Nr
a
DOMESTIC
24'-0"
11' D'
Approved
D F M GMrts gust
South County Fire
Date: 07/08/2024
07-08-2024
PLAN REVIEW
NOTES: APPROVED WITH CONDITIONS
1. READ PROVIDED INFORMATION GUIDE.
2.THE APPROVED SET OF PLANS MUST BE
ON SITE AT THE TIME OF THE INSPECTION.
3. SYSTEMS BELOW GRADE REQUIRE A
2ND DRAIN.
4. SEE SIGNAGE REQUIREMENTS IN
INFORMATION GUIDE.
5. COVERAGE REQUIRED IN THE
FOLLOWING AREAS: CLOTHES, LINEN
CLOSETS AND PANTRIES EXCEEDING 24
SQUARE FEET IN AREA, WITH THE
SMALLEST DIMENSION GREATER THAN 3
FEET HAVING WALL AND CEILING
SURFACES OF GYPSUM BOARD.
BATHROOMS MORE THAN 55 SQUARE
FEET IN AREA. WHEN FUEL FIRE
EQUIPMENT IS PRESENT ON COVERED
DECKS OR PORCHES, OR IF A LIVING
SPACE ABOVE, AT LEAST ONE QUICK
RESPONSE INTERMEDIATE TEMPERATURE
SPRINKLER SHALL BE INSTALLED ABOVE
EQUIPEMENT OR AREA UNDER LIVING
SPACE. ALL FUEL FIRED APPLIANCES
EXCEPT ATTICS IF ABOVE ALL LIVING
AREAS.
DFM BURT
Edmonds Townhomes
Remote Area: Unit 4 - Master Bedroom
CALCULATION DESIGN CRITERIA:
STANDARD NFPA#13D-2019
OCCUPANCYCLASS Residential
MAX. COVERAGE per HEAD 2556 Ft'
DENSITY .05 GPM / Ft' for 2 Sprinklers FF
SPRINKLER Victaulic Model V4906
ORIFICE 1/2" K= 4.9
WATER FLOW INFORMATION':
STATIC 55 PSI
RESIDUAL 20 PSI
FLOW 500 GPM
AT BASE OF RISER, SYSTEM REQUIRES:
26.38 GPM @ 41.67 PSI
*At time of Design
RISER DETAIL
F\ P-01 / NTS
O1 11/" COMBO SUPPLY BY OTHERS
0 1'/ x 1 REDUCER
O 1" CONTROL VALVE
❑4 1" RESIDENTIAL RISER
WITHOUT FLOW SWITCH
O SPARE HEAD BOX
DINING
KITCHEN
1 • 1 1•
T-0 8'-6 '-6
0 0
1 � 1
F I R2024-0049
I I
I I
I I
I I
PASEMENTPLAN
N
1/8" =1'-018
it 11 jI J INNING DINING I L�'� Ir 11 11_J•i 1 DINING
KITCHEN KITCHEN KITCHEN
1 1 1 1 1 1• •1 1 • 1
8'-6 T-0 T-0 8'36 6 1'-6 8'-6 3'-0
0
•1 � 1 1• 1 1 • 1
T-0 1'-1 '-6 T-0 T-0 1'-6 1'-B T-0
o p o o p o
Tisi
Ar
1 PTY PTY
CD
1 -0 2'-0 "' 1
--0 L FLI— I
E3 LND NOY
1 1 ❑ 1 1
`
V-9 �'-0 6'-9 4
r PDR PDR
SQ FT 36SQFir
F F o
1 1 1 1 1 1
j-
V-9 p 3'-3 3'-6 T-6 T-3 6'-9
N ��• Div
LIVING fl / \ H LIVING
1ST FLOOR PLAN
N
1/8" =1'-018
GUEST RM INI GUEST RM
GUEST RM M GUEST RM
GUEST RM
GUEST RM GUEST RM
GUEST RM
1
1
1 1
1
1
81-9
14
1'-6
81-9
8'-9
1'4
8'-9
0
CD
0
0
0
0 0
0
�
b
b
b
��
0
1
,os
1
BATH
BATH
1 1
1
BATH
BATH
1
1
47 SQ Fr
47 SQ Fr
'-
47 SQ Fr
47 84 Fr
i
.0
br
-0
-0
-
TL
T
,o
TL
0 T
,o
1oz
1
1
WIC
t2--0-o
WIC
WIC
r-o
'-o
WIC
101
io
tlo
b
1'-6
1'-6
1'-6
1'-6
4
103
1
104
M BATH) ,:I
MM B��
6'-9 1'-3 1' 6-9
0'-g --
M BATH
M BATH
6'-9 -3
105
+yap
+��A
M T B R
MASTER BEDROOM MASTER BEDROOM
MASTER BEDROOM
INSPECTOR NOTE:
BUCKET TEST
HEADS.
2NC FLOOR PLAN
N
1/8" =1'-018
Casicadia
FIRE PROTECTION
PO BOX 206
PUYALLUP, WA98371
PHONE: (253) 202-3909
WA LICENSE NUMBER #CASCAFP833L2
www.cascadiafirepro.com
�
o
00
(r-
Ix
W
LL.I
J
J
a
Q
W
W
U
U
Z
O
U
O
wCo
U
U
U-
O
W
J
Q�
(n
J
W_
LJL
Of
W
H
O
W
U
=
co
H
Z
=
_
LL
O
Z
L()
M
j
W
U-1
L
N
Y
C
Wco
-
-
^J
(V
(V
J
O
�
•
1
r�
APPROVALS
CITY OF EDMONDS:
OWNER:
ARCHITECT:
GENERAL CONTRACTOR:
OTHER:
REVISIONS
RECEIVED
Jul 03 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
NORTH
SCALE: 1/8" = V-0"
N
0 2 4 8 16
NICETSEAL r . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Ex Ires WASHINGTON STATE
DEC P,. 24 CERTIFICATE OF COMPETENCY
FIRE SPRINKLER SYSTEMS
i
Michael Paul Agner II
;
4344-0218-C Level
Cascadia Fire Protection, LLC
i
CASCAFP8331-2
i
6-27-2024
jSignature
Date
j
mmmmmma- - - - - - - - - - - - - - -
PROJECT
EDMONDS TOWNHOMES
8029 238TH STR E ET SW
EDMONDS, WA 98026
PLAN
FIRE PROTECTION PLAN
DRAWN BY DATE'.
MA 6-27-24
JOB NO. SHEET 1 OF 1
CASCA24-1192 F P-01