APPROVED FIR2024-0055+Fire_Sprinkler_Plan+7.3.2024_8.50.19_AM+4356974TOP RIDGE +/-25.fi'
TOP
SE_'OND FLOOR + -
1 SECTION VIEW
FP-01 1/8" =1'-011
125' r0"
(gg � RISER RISER RISER I RISER � I I 1" M
UNIT 4 1 UNIT 3 1 UNIT 2 1 UNIT 1
COMMENT- DRAINING
THROUGH EXTERIOR WATER
SPIGOT IS ACCEPTABLE. IF
PLUMBED TO DRAIN THROUGH
SITE PLAN THE EXTERIOR SPIGOT AND IN
N ADDITION TO THE "DRAIN
NITS VALVE" PLACARD, ATTACH A
PLACARD AT THE INTERIOR
DRAIN VALVE STATING -
"SPRINKLER DRAINS THROUGH
EXTERIOR SPIGOT"
CASCADIA FIRE PROTECTION TO DESIGN AND INSTALL A COMPLETE "FLOW THROUGH" FIRE PROTECTION
SYSTEM BASED ON NFPA#13D - 2019 AND CITY OF EDMONDS REQUIREMENTS FOR EACH UNIT.
CASCADIA FIRE PROTECTION TO STARTATTHE UNDERGROUND OUTLET PROVIDED BY OTHERS.
DESIGN CRITERIA:
DWELLING UNITS: NFPA#13D
DESIGN DENSITY:.05 GPM / 2 RESIDENTIAL SPRINKLERS
HOSE ALLOWANCE: 0 GPM
MAXIMUM SPACING: 256 SQ. FT.
WATER SUPPLY:
PRIMARY: CITY WATER SUPPLY
STATIC PSI: 55 PSI
RESIDUAL: 500 GPM AT 20 PSI
DESIGN NOTES:
1. BUILDING IS CONSTRUCTED WITH WOOD FLOORING ON WOOD BEAMS AND TJI STRUCTURE.
2. SPRINKLER DEFLECTOR AND LOCATIONS SHALL BE DESIGNED IN ACCORDANCE WITH NFPA#13D - 2019.
3. ALL SEISMIC BRACING AND HANGER ASSEMBLIES TO BE INSTALLED IN ACCORDANCE TO NFPA#13D - 2019.
4. CPVC PIPE AND FITTINGS TO BE LISTED FOR FIRE PROTECTION.
GENERAL NOTES:
1. ALL PAINTING OR LABELING OF FIRE SPRINKLER PIPING, IF REQUIRED, TO BE DONE BY OTHERS.
2. ALL MATERIALS TO BE INSTALLED SHALL BE UL LISTED.
3. IT IS THE OWNER'S RESPONSIBILITY TO ENSURE THATTHE STRUCTURE SHOWN ON THE CONTRACT
DRAWINGS CAN ADEQUATELY SUPPORTALL FIRE SPRINKLER PIPE AND SEISMIC LOADS.
4. OWNER IS REPSPONSIBLE FOR MAINTAINING TEMPERATURES ABOVE 40 DEGREES TO PROTECTTHE WET
FIRE SPRINKLER SYSTEM FROM FREEZING.
5. ALL WIRING OF FIRE PROTECTION SYSTEM COMPONENTS TO BE DONE BY OTHERS.
6. ALL PIPE AND COMPONENTS TO BE TESTEDAND INSPECTED IN ACCORDANCE WITH NFPA#13D - 2019.
Hanger No. 17W
Pipe Strap
Pipe Strap
Wood Screw#12 x 1Y.' Pipe
Wood Joist or Beam
Wood Screw #18 x 1'/x"
Hanger No. 19W
Offset Pipe Hanger
- Pipe
ffset Pipe Hanger
tll
Wool Joist, Beam or Deck
�n
9:? ON
t;
24'-0"
11' D-
_
_{dAIN FLOOR t QLO.
ELE 434'
Approved
DFM ak s Burt
_ South County Fire
Date. 07/08/2024
1
07-08-20'
PLAN REVIEW
NOTES: APPRO�ED WITH CONDITIONS
1. READ PROVI ED INFORMATION GUIDE.
-
2.THE APPROVED SET OF PLANS MUST BE
ON SITE AT THE TIME OF THE INSPECTION.
3. SYSTEMS BELOW GRADE REQUIRE A
2ND DRAIN.
4. SEE SIGNAGE REQUIREMENTS IN
BASEMENT PLAN
INFORMATION GUIDE.
N
5. COVERAGE REQUIRED IN THE
1/8" =1'-018
FOLLOWING AREAS: CLOTHES, LINEN
CLOSETS AND PANTRIES EXCEEDING 24
SQUARE FEET IN AREA, WITH THE
SMALLEST DIMENSION GREATER THAN 3—
I
-
FEET HAVING WALL AND CEILING
DINING III,
DINING DINING
li
li _J DINING
�
w
SURFACES OF GYPSUM BOARD.
1 1 KITCHEN
KITCHEN 1
1 1 1
KITCHEN
KITCHEN 1 1
�'-s
BATHROOMS MORE THAN 55 SQUARE
3'-0 Ir-s
1'-6 Ir-6
T-0 3'-o s'-s
s'-s 3'-0
z
FEET IN AREA. WHEN FUEL FIRE
-
QEQUIPMENT
IS PRESENT ON COVERED
o o
o
0 0
0
0 0
DECKS OR PORCHES, OR IF A LIVING
SPACE ABOVE, AT LEAST ONE QUICK
RESPONSE INTERMEDIATE TEMPERATURE
1 1
•1
1 1
1
1 1
SPRINKLER SHALL BE INSTALLED ABOVE
3'-0 1'-
1'-s
3'-0 3'-0
3'-0
EQUIPEMENT OR AREA UNDER LIVING
0 0
�° "'�.'��
0 0 0
C? ►N 0
EXCEPT ATTICS IF ABOVE ALL LIVING
r ,
�► - - ��
Edmonds Townhomes
Remote Area: Unit 4 - Master Bedroom
CALCULATION DESIGN CRITERIA:
STANDARD NFPA#13D-2019
OCCUPANCYCLASS Residential
MAX. COVERAGE per HEAD 2556 FF
DENSITY .05 GPM / Ft- for-2 Sprinklers FF
SPRINKLER Victaulic Model V4906
ORIFICE 1/2" K= 4.9
WATER FLOW INFORMATION':
STATIC 55 PSI
RESIDUAL 20 PSI
FLOW 500 GPM
AT BASE OF RISER, SYSTEM REQUIRES:
26.38 GPM @ 41.67 PSI
*At time of Design
a
(-2RISER DETAIL
�-o
NTS
DOMESTIC
O1 11/" COMBO SUPPLY BY OTHERS
0 1'/ x 1 REDUCER
O O 1" CONTROL VALVE
gg ❑4 1" RESIDENTIAL RISER
WITHOUT FLOW SWITCH
OO O SPARE HEAD BOX
1
E3 LND
1 ❑
NDY
1
1
�
r
T-o
6'-9 `4
PDR
PDR
ssSQFr
36SQFr
1
1 1 0
1 1
1
V-9 O
T-3 T-6
T-6 T-3
6'-9
LIVING
fl /
\ H
LIVING
GUEST RM INI GUEST RM
1ST FLOOR PLAN
N 1/8" =1'-018
GUEST RM (NI GUEST RM
GUEST RM GUEST RM GUEST RM
1 1 1 1
'-9 6'-9 1'-6 8'-9
0 0 0
b b �
O Qy Q
gUV%irllpx��! �� � . ' �iMASTER BEDROOM
i
i'
ii
i
INSPECTOR NOTE:
BUCKET TEST
HEADS.
Ow
10111
w
N/11
2ND FLOOR PLAN
N 1/8" =1'-018
F I R2024-0055
Casicadia
FIRE PROTECTION
PO BOX 206
PUYALLUP, WA98371
PHONE: (253) 202-3909
WA LICENSE NUMBER #CASCAFP833L2
www.cascadiafirepro.com
�
o
00
(r-
Ix
W
LL.I
J
J
a
Q
W
W
U
U
z
O
U
O
wCo
U
U
U-
O
W
J
Q�
(n
J
W_
LJL
Of
W
co
H
O
W
U
=
Ui_
co
�
z
=
_
LL
o100)
z
toLO
M
co
j
a
W
N
Y
�
�
wco
-
-
^J
(V
(V
J
O
Co
APPROVALS
CITY OF EDMONDS:
OWNER:
ARCHITECT:
GENERAL CONTRACTOR:
OTHER:
OWNER'
REVISIONS
RECEIVED
Jul 03 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
NORTH
SCALE: 1/8" = V-0"
N
0 2 4 8 16
NICETSEAL r............................7
Ex Ires WASHINGTON STATE
DEC P1. 24 CERTIFICATE OF COMPETENCY
FIRE SPRINKLER SYSTEMS
It
Michael Paul Agner II
;
4344-0218-C Level
Cascadia Fire Protection, LLC
i
CASCAFP8331-2
i
6-27-2024
jSignature
Date
j
------------=---------------+
PROJECT
EDMONDS TOWNHOMES
8029 238TH STR E ET SW
EDMONDS, WA 98026
PLAN
FIRE PROTECTION PLAN
DRAWN BY DATE'.
MA 6-27-24
JOB NO. SHEET 1 OF 1
CASCA24-1192 F P-01