Loading...
APPROVED FIR2024-0055+Fire_Sprinkler_Plan+7.3.2024_8.50.19_AM+4356974TOP RIDGE +/-25.fi' TOP SE_'OND FLOOR + - 1 SECTION VIEW FP-01 1/8" =1'-011 125' r0" (gg � RISER RISER RISER I RISER � I I 1" M UNIT 4 1 UNIT 3 1 UNIT 2 1 UNIT 1 COMMENT- DRAINING THROUGH EXTERIOR WATER SPIGOT IS ACCEPTABLE. IF PLUMBED TO DRAIN THROUGH SITE PLAN THE EXTERIOR SPIGOT AND IN N ADDITION TO THE "DRAIN NITS VALVE" PLACARD, ATTACH A PLACARD AT THE INTERIOR DRAIN VALVE STATING - "SPRINKLER DRAINS THROUGH EXTERIOR SPIGOT" CASCADIA FIRE PROTECTION TO DESIGN AND INSTALL A COMPLETE "FLOW THROUGH" FIRE PROTECTION SYSTEM BASED ON NFPA#13D - 2019 AND CITY OF EDMONDS REQUIREMENTS FOR EACH UNIT. CASCADIA FIRE PROTECTION TO STARTATTHE UNDERGROUND OUTLET PROVIDED BY OTHERS. DESIGN CRITERIA: DWELLING UNITS: NFPA#13D DESIGN DENSITY:.05 GPM / 2 RESIDENTIAL SPRINKLERS HOSE ALLOWANCE: 0 GPM MAXIMUM SPACING: 256 SQ. FT. WATER SUPPLY: PRIMARY: CITY WATER SUPPLY STATIC PSI: 55 PSI RESIDUAL: 500 GPM AT 20 PSI DESIGN NOTES: 1. BUILDING IS CONSTRUCTED WITH WOOD FLOORING ON WOOD BEAMS AND TJI STRUCTURE. 2. SPRINKLER DEFLECTOR AND LOCATIONS SHALL BE DESIGNED IN ACCORDANCE WITH NFPA#13D - 2019. 3. ALL SEISMIC BRACING AND HANGER ASSEMBLIES TO BE INSTALLED IN ACCORDANCE TO NFPA#13D - 2019. 4. CPVC PIPE AND FITTINGS TO BE LISTED FOR FIRE PROTECTION. GENERAL NOTES: 1. ALL PAINTING OR LABELING OF FIRE SPRINKLER PIPING, IF REQUIRED, TO BE DONE BY OTHERS. 2. ALL MATERIALS TO BE INSTALLED SHALL BE UL LISTED. 3. IT IS THE OWNER'S RESPONSIBILITY TO ENSURE THATTHE STRUCTURE SHOWN ON THE CONTRACT DRAWINGS CAN ADEQUATELY SUPPORTALL FIRE SPRINKLER PIPE AND SEISMIC LOADS. 4. OWNER IS REPSPONSIBLE FOR MAINTAINING TEMPERATURES ABOVE 40 DEGREES TO PROTECTTHE WET FIRE SPRINKLER SYSTEM FROM FREEZING. 5. ALL WIRING OF FIRE PROTECTION SYSTEM COMPONENTS TO BE DONE BY OTHERS. 6. ALL PIPE AND COMPONENTS TO BE TESTEDAND INSPECTED IN ACCORDANCE WITH NFPA#13D - 2019. Hanger No. 17W Pipe Strap Pipe Strap Wood Screw#12 x 1Y.' Pipe Wood Joist or Beam Wood Screw #18 x 1'/x" Hanger No. 19W Offset Pipe Hanger - Pipe ffset Pipe Hanger tll Wool Joist, Beam or Deck �n 9:? ON t; 24'-0" 11' D- _ _{dAIN FLOOR t QLO. ELE 434' Approved DFM ak s Burt _ South County Fire Date. 07/08/2024 1 07-08-20' PLAN REVIEW NOTES: APPRO�ED WITH CONDITIONS 1. READ PROVI ED INFORMATION GUIDE. - 2.THE APPROVED SET OF PLANS MUST BE ON SITE AT THE TIME OF THE INSPECTION. 3. SYSTEMS BELOW GRADE REQUIRE A 2ND DRAIN. 4. SEE SIGNAGE REQUIREMENTS IN BASEMENT PLAN INFORMATION GUIDE. N 5. COVERAGE REQUIRED IN THE 1/8" =1'-018 FOLLOWING AREAS: CLOTHES, LINEN CLOSETS AND PANTRIES EXCEEDING 24 SQUARE FEET IN AREA, WITH THE SMALLEST DIMENSION GREATER THAN 3— I - FEET HAVING WALL AND CEILING DINING III, DINING DINING li li _J DINING � w SURFACES OF GYPSUM BOARD. 1 1 KITCHEN KITCHEN 1 1 1 1 KITCHEN KITCHEN 1 1 �'-s BATHROOMS MORE THAN 55 SQUARE 3'-0 Ir-s 1'-6 Ir-6 T-0 3'-o s'-s s'-s 3'-0 z FEET IN AREA. WHEN FUEL FIRE - QEQUIPMENT IS PRESENT ON COVERED o o o 0 0 0 0 0 DECKS OR PORCHES, OR IF A LIVING SPACE ABOVE, AT LEAST ONE QUICK RESPONSE INTERMEDIATE TEMPERATURE 1 1 •1 1 1 1 1 1 SPRINKLER SHALL BE INSTALLED ABOVE 3'-0 1'- 1'-s 3'-0 3'-0 3'-0 EQUIPEMENT OR AREA UNDER LIVING 0 0 �° "'�.'�� 0 0 0 C? ►N 0 EXCEPT ATTICS IF ABOVE ALL LIVING r , �► - - �� Edmonds Townhomes Remote Area: Unit 4 - Master Bedroom CALCULATION DESIGN CRITERIA: STANDARD NFPA#13D-2019 OCCUPANCYCLASS Residential MAX. COVERAGE per HEAD 2556 FF DENSITY .05 GPM / Ft- for-2 Sprinklers FF SPRINKLER Victaulic Model V4906 ORIFICE 1/2" K= 4.9 WATER FLOW INFORMATION': STATIC 55 PSI RESIDUAL 20 PSI FLOW 500 GPM AT BASE OF RISER, SYSTEM REQUIRES: 26.38 GPM @ 41.67 PSI *At time of Design a (-2RISER DETAIL �-o NTS DOMESTIC O1 11/" COMBO SUPPLY BY OTHERS 0 1'/ x 1 REDUCER O O 1" CONTROL VALVE gg ❑4 1" RESIDENTIAL RISER WITHOUT FLOW SWITCH OO O SPARE HEAD BOX 1 E3 LND 1 ❑ NDY 1 1 � r T-o 6'-9 `4 PDR PDR ssSQFr 36SQFr 1 1 1 0 1 1 1 V-9 O T-3 T-6 T-6 T-3 6'-9 LIVING fl / \ H LIVING GUEST RM INI GUEST RM 1ST FLOOR PLAN N 1/8" =1'-018 GUEST RM (NI GUEST RM GUEST RM GUEST RM GUEST RM 1 1 1 1 '-9 6'-9 1'-6 8'-9 0 0 0 b b � O Qy Q gUV%irllpx��! �� � . ' �iMASTER BEDROOM i i' ii i INSPECTOR NOTE: BUCKET TEST HEADS. Ow 10111 w N/11 2ND FLOOR PLAN N 1/8" =1'-018 F I R2024-0055 Casicadia FIRE PROTECTION PO BOX 206 PUYALLUP, WA98371 PHONE: (253) 202-3909 WA LICENSE NUMBER #CASCAFP833L2 www.cascadiafirepro.com � o 00 (r- Ix W LL.I J J a Q W W U U z O U O wCo U U U- O W J Q� (n J W_ LJL Of W co H O W U = Ui_ co � z = _ LL o100) z toLO M co j a W N Y � � wco - - ^J (V (V J O Co APPROVALS CITY OF EDMONDS: OWNER: ARCHITECT: GENERAL CONTRACTOR: OTHER: OWNER' REVISIONS RECEIVED Jul 03 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT NORTH SCALE: 1/8" = V-0" N 0 2 4 8 16 NICETSEAL r............................7 Ex Ires WASHINGTON STATE DEC P1. 24 CERTIFICATE OF COMPETENCY FIRE SPRINKLER SYSTEMS It Michael Paul Agner II ; 4344-0218-C Level Cascadia Fire Protection, LLC i CASCAFP8331-2 i 6-27-2024 jSignature Date j ------------=---------------+ PROJECT EDMONDS TOWNHOMES 8029 238TH STR E ET SW EDMONDS, WA 98026 PLAN FIRE PROTECTION PLAN DRAWN BY DATE'. MA 6-27-24 JOB NO. SHEET 1 OF 1 CASCA24-1192 F P-01