FIR2024-0054+Fire_Sprinkler_Equipment_Specification_Sheets+7.3.2024_8.54.01_AM+4356992F I R2024-0054 RECEIVED Jul 03 2024 MATERIAL SUBMITTAL AND HYDRAULIC CALCULATIONS FOR EDMONDS TOWNHOMES 8029 238T" STREET SW EDMONDS, WA 98026 Cascadia FIRE PROTECTION PO BOX 206 PUYALLUP, WA 98371 CASCAFP833L2 EDMONDS TOWNHOMES TABLE OF CONTENTS FIRE SPRINKLERS VICTAULIC FIRELOCK SERIES FL-RES/C RESIDENTIAL CONCEALED PENDENT SPRINKLER TYCO SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER PIPE AND FITTINGS TYCO CPVC PIPE AND FITTINGS HANGERS ANVIL FIGURE 184 DOUBLE OFFSET HANGER AND RESTRAINER ANVIL FIGURE 187 TWO HOLE SIDE MOUNT STRAP ANVIL FIGURE 188R TWO HOLE STANDOFF AND RESTRAINER HYDRAULIC CALCULATIONS UNIT 4 - MASTER BEDROOM (NFPA 13D) FIRE SPRINKLERS Victaulic° FireLock'" Series FL-RES/C Residential, Quick Response ✓ctaulic Concealed Pendent Sprinklers, K4.9 (7.0) K5.6 (8.0) 43.03 1.0 PRODUCT DESCRIPTION RESIDENTIAL CONCEALED PENDENT SIN V4906 V3806 ORIENTATION PENDENT PENDENT K-FACTORI 4.9Im ./7.1 S.I. 5.6Im ./8.1 S.I. CONNECTION 1/2" NPT/15 mm 1/2" NPT/15 mm MAX. WORKING PRESSURE 175 psi (1200 kPa) 175 psi (1200 kPa) GLOBE RE -DESIGNATION GL4906 — r AVAILABLE WRENCHES SPRINKLER V49 Concealed V38 Concealed PENDENT IN IN Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar Min. Operating Pressure: UL: 7 psi/48 kPa/.5 bar Temperature Rating: See tables in section 2.0 1 For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. victaulic.com 43.03 16384 Rev B Updated 07/2021 © 2021 Victaulic Company. All rights reserved. 1 �ctauIi c 1144211lir rnm 2.0 CERTIFICATION/LISTINGS D @DS LISTED Listing Agency/ Approved Temperature Max. Coverage Area Minimum Nominal K Factor Ratings Width x Length Flow Pressure Adjustment Spacing Sprinkler 155°F/68°C Deflector to Ceiling/ Cover Ft. x Ft. GPM PSI in Mounting Surface Ft. SIN Imperial S.I? 135°F/57°C m x m L/min kPa mm Distance m 12 x 12 13 7.0 3.7 x 3.7 49.2 1 48 14x14 13 7.0 4.3 x 4.3 49.2 48 7/8 Smooth Ceilings 9 16 x 16 13 7.0 V4906 4.9 7.1 cULus 4.9 x 4.9 49.2 48 22 (See appropriate 2.7 installation detail 18 x 18 17 12.0 5.5 x 5.5 64.3 83 below) OR 20 x 20 20 16.7 6.1 x 6.1 75.7 115 Beamed Ceilings: Installed within the Beam In accordance 12 x 12 16 8.2 3.7 x 3.7 60.6 57 with NFPA 13, 13D, 14x14 - 16 8.2 or13R 4.3 x 4.3 60.6 57 (Max Beam Depth 16 x 16 16 8.2 V3806 5.6 8.1 cULus 1/4 Depends on Edition 8 4.9 x 4.9 60.6 57 6 of Standard) 2.4 18x18 21 14.1 5.5 x 5.5 79.5 97 20 x 20 25 20.0 6.1 x6.1 94.6 138 Z For K-Factor when pressure is measured in bar, multiply S.I. units by 10.0. NOTE • Listings and approval as of printing. 3.0 SPECIFICATIONS - MATERIAL Deflector: Bronze Bulb Nominal Diameter: 3.0 mm Load Screw: Brass Pip Cap: Brass Spring Seal: PTFE coated Beryllium nickel alloy Frame: Brass Lodgement Spring: Stainless Steel Pin: Stainless Steel Concealed Cup: Steel Cover Plate: Steel Installation Wrench: Ductile Iron Cover Plate Finishes: • Chrome plated • White painted • Flat black painted • Custom painted NOTES • For cabinets and other accessories refer to separate sheet. 43.03 16384 Rev B Updated 07/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 2 ✓ctaulic virtaidir rnm 4.0 DIMENSIONS 2'M6"/68 mm 23/6"/60 mm — Hole in ceiling Cup Frame j Pip cap and spring seal Bulb Load screw — Pin^ Deflector Cover plate 3'/4"/ 82 mm V3806 V3806 2"/51 mm 13/4"/44 mm Typical ceiling Finished surface m Max. 43.03 16384 Rev B Updated 07/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com 3 ✓ctaulic victaulic.com 4.0 DIMENSIONS (CONTINUED) Pip ca sprin Lodgement sl I Loac DE Finished ceil Cover ply« V4906 V4906 mm mm %a"/ 4mm 43.03 16384 Rev B Updated 07/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com M ✓ctauliic victaulic.com 5.0 PERFORMANCE Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards. 6.0 NOTIFICATIONS _ Read and understand all instructions before attempting to install any Victaulic products. • Always verify that the piping system has been completely depressurized and drained immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended service. Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system failure, resulting in death or serious personal injury and property damage. 7.0 REFERENCE MATERIALS Ratings: All glass bulbs are rated for temperatures from-67°F/-55°C. 1-40: Victaulic FireLockT°^ Automatic Sprinklers Installation and Maintenance Instructions User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications. All products Victaulic products for a particular end -use application, in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications, and the applicable building codes and related Victaulic reserves the right to change product specifications, designs and standard regulations as well as Victaulic performance, maintenance, safety, and warning equipment without notice and without incurring obligations. instructions. Nothing in this or any other document, nor any verbal recommendation, Installation advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, Reference should always be made to the Victaulic installation handbook or installation or waive any provision of Victaulic Company's standard conditions of sale, installation instructions of the product you are installing. Handbooks are included with each shipment guide, or this disclaimer. of Victaulic products, providing complete installation and assembly data, and are available Intellectual Property Rights in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product, service, or design is intended, or should be constructed, to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such Trademarks material, product, service, or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right. The terms "Patented" or "Patent Pending" refer to design or utility patents Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. 43.03 16384 Rev B Updated 07/2021 © 2021 Victaulic Company. All rights reserved. victaulic.com ✓ctaull 5 tqcao Worldwide I Contacts I www tyco-fire.com RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description The TYCO RAPID RESPONSE Series LFII Residential 4.9K Concealed Pendent Sprinklers (TY3596) are dec- orative, fusible solder sprinklers, avail- able in both ordinary 160°F (71°C) and intermediate 212°F (100°C) tempera- ture rated configurations. They are designed for use in residential occu- pancies such as homes, apartments, dormitories, and hotels. The cover plate assembly conceals the sprinkler operating components above the ceiling. The flat profile of the cover plate provides the optimum aes- thetically appealing sprinkler design. In addition, the concealed design of the Series LFII Residential Con- cealed Pendent Sprinklers provides 1/2 in. (12,7 mm) vertical adjustment. This adjustment provides a measure of flexibility when cutting fixed sprin- kler drops. The Series LFII Residential Concealed Pendent Sprinklers are intended for use in the following scenarios: • Wet and dry pipe residential sprin- kler systems for one and two fam- ily dwellings and mobile homes per NFPA 13D • Wet and dry pipe residential sprin- kler systems for residential occupan- cies up to and including four stories in height per NFPA 13R IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. • Wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13 The Series LFII Residential Concealed Pendent Sprinklers have been designed with heat sensitivity and water distri- bution characteristics proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. The Series LFII Residential Con- cealed Pendent Sprinklers (TY3596) are shipped with a Disposable Protec- tive Cap. The Protective Cap is tem- porarily removed for installation, and then it can be replaced to help protect the sprinkler while the ceiling is being installed or finished. The tip of the Pro- tective Cap can also be used to mark the center of the ceiling hole into the plaster board, ceiling tiles, and so on, by gently pushing the ceiling product against the Protective Cap. When the ceiling installation is complete the Pro- tective Cap is removed and the Cover Plate Assembly is installed. Dry Pipe System Application The 160°F (71°C) temperature rated Series LFII Residential Concealed Pendent Sprinklers offer a laboratory approved option for designing dry pipe residential sprinkler systems, whereas, most residential sprinklers are labora- tory approved for wet systems only. Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Concealed Pendent Sprinklers need not be increased over the number of design sprinklers (hydraulic design area) as specified for wet pipe sprinkler systems, as is accustomed for density/ area sprinkler systems designed per NFPA 13. Consequently, the Series LFII Residen- tial Concealed Pendent Sprinklers offer the features of non -water filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA 13, 13D, or 13R. NOTICE The Series LFII Residential Concealed Pendent Sprinklers (TY3596) described herein must be installed and main- tained in compliance with this docu- ment and with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Sprinkler Identification Number (SIN) TY3596 Page 1 of 6 SEPTEMBER 2019 TFP442 TFP442 Page 2of6 Technical Data Approvals UL and C-UL Listed NYC Approved under MEA 44-03-E-2NSF Certified to all requirements of NSF/ANSI 61 Australian WaterMark Certified The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers are Listed only when installed with LFII Con- cealed Cover Plates having factory -applied finishes. Sprinklers and Cover Plates are separately ordered. See the Ordering Procedure section for more information. Maximum Working Pressure 175 psi (12,1 bar) Discharge Coefficient K=4.9 GPM/psi'' (70,6 LPM/bar'') Temperature Rating Ordinary 160OF (71°C) Sprinkler/ 139°F (59°C) Cover Plate NOTE: Maximum Ambient Ceiling Temperature for the ordinary temperature configuration is 100°F (38°C) Intermediate' 212°F (100°C) Sprinkler/ 165°F (74°C) Cover Plate "For wet pipe systems only NOTE: Maximum Ambient Ceiling Temperature for the intermediate temperature configuration is 150°F (65°C) Vertical Adjustment 1/2 in. (12,7 mm) Finishes See the Ordering Procedure section Physical Characteristics Body..............................Brass Cap..............................Bronze Saddle.............................Brass Sealing Assembly. Beryllium Nickel w/TEFLON Soldered Link Halves ................ Nickel Lever.............................Bronze Compression Screw .................. Brass Deflector .................. Copper or Brass Guide Pin Housing ..................Bronze Guide Pins ......... Stainless Steel or Bronze Support Cup ....................... Steel Cover Plate .................Copper/Brass" Retainer ......................... Copper Cover Plate Ejection Spring .... Stainless Steel " Brass Cover Plate is offered for Intermediate Tem- perature 1650F (74°C) only. Operation When exposed to heat from a fire, the Cover Plate, which is normally soldered to the Retainer at three points, falls away to expose the sprinkler assembly. At this point the Deflector supported by the Arms drops down to its operated position. The fusible link of the sprin- kler assembly is comprised of two link halves that are soldered together with a thin layer of solder. When the rated temperature is reached, the solder melts and the two link -halves separate BODY SEALING (1/2" NPT) ASSEMBLY CAP j SPRINKLER WRENCHING AREA SADDLE �( SUPPORT COMPRESSION CUP WITH I yI }� SCREW ROLL FORMED (� THREADS II LEVER GUIDE I PIN ', SOLDER LINK ELEMENT GUIDE PIN HOUSING I --- DEFLECTOR c (OPERATED DEFLECTOR - - --- - POSITION) SPRINKLER ASSEMBLY THREAD INTO RETAINER SUPPORT WITH THREAD CUP UNTIL DIMPLES MOUNTING SURFACE IS o 0 FLUSH WITH CEILING EJECTION SPRING SOLDER COVER PLATE COVER TAB ASSEMBLY PLATE FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER (TY3596) allowing the sprinkler to activate and flow water. Design Criteria The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers (TY3596) are UL and C-UL Listed for installation in accordance with this section. Note: When conditions exist that are outside the scope of the provided cri- teria, refer to the Residential Sprinkler Design Guide TFP490 for the manu- facturer's recommendations that may be acceptable to the authority having jurisdiction. System Types Per the UL and C-UL Listing, the 160°F (71°C) and 212°F (100°C) LFII Residential Concealed Pendent Sprin- klers may be utilized in wet pipe systems. Only the 160°F (71 °C) LFI I Res- idential Concealed Pendent Sprinklers may be utilized in dry pipe systems, per the UL and C-UL Listing. Refer to Technical Data Sheet TFP485 about the use of residential sprinklers in residential dry pipe systems. Ceiling Types Smooth flat horizontal, beamed, or sloped in accordance with NFPA 13D, 13R, or 13 as applicable. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the minimum required sprin- kler flow rates are given in Tables A and B as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of "design sprinklers" as specified in NFPA 13D or NFPA 13R. TFP442 Page 3 of 6 WET PIPE SYSTEM Minimum Flow and Residual Pressure2,3 Maximum Coverage Maximum Temp. Rating Area' Spacing ft 160°F (71°C), 212°F (100°C) Minimum ft x ft (m) Deflector to Installation Spacing (m x m) Flow Pressure Ceiling Type ft GPM psi (m) (LPM) (bar) 12 x 12 12 13 7.0 (3,7 x 3,7) (3,7) (49,2) (0,48) Smooth Ceilings 14 x 14 14 13 7.0 7/8 to 1-1/8 in. (4,3 x 4,3) (4,3) (49,2) (0,48) Beamed Ceilings per NFPA 13D or Concealed 8 16 x 16 16 13 7.0 (4,9 x 4,9) (4,9) (49,2) (0,48) 13R,or13. Installed in (2,4) 18 x 18 18 17 12.0 beam (5,5 x 5,5) (5,5) (64,3) (0,83) 7/8 to 1-1/8 in. below bottom 20 x 20 20 20 16.7 of beam (6,1 x 6,1) (6,1) (75,7) (1,15) Notes: 1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. 2. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. See Hydraulic Design under the Design Criteria section. 3. For NFPA 13 residential applications, the greater of 0.1 GPM/ft2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT PLATE CONCEALED PENDENT SPRINKLER (TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Minimum Flowand Residual Pressure 2,3 Maximum Coverage Maximum Ordinary Temp. Rating Area' Spacing 160°F (71°C) Minimum ft x ft ft (m) Deflector to Installation Spacing (m x m) Flow Pressure Ceiling Type ft GPM psi (m) (LPM) (bar) 12 x 12 12 13 7.0 (3,7 x 3,7) (3,7) (49,2) (0,48) Smooth Ceilings 14 x 14 14 14 8.2 7/8 to 1-1/8 in. (4,3 x 4,3) (4,3) (53,0) (0,57) Beamed Ceilings per NFPA 13D or Concealed 8 16 x 16 16 15 9.4 (4,9 x 4,9) (4,9) (56,8) (0,65) 13R,or13. Installed in (2,4) 18 x 18 18 18 13.5 beam (5,5 x 5,5) (5,5) (68,1) (0,93) 7/8 to 1-1/8 in. below bottom 20 x 20 20 21 18.4 of beam (6,1 x 6,1) (6,1) (79,5) (1,27) Notes: 1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. 2. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated us- ing the nominal K-factor. See Hydraulic Design under the Design Criteria section. 3. For NFPA 13 residential applications, the greater of 0.1 GPM/ft2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM RAPID RESPONSE SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT PLATE CONCEALED PENDENT (TY3596) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA TFP442 Page 4 of 6 1/2" NPT 2-1/2" DIA. (63,5 mm) 1/2" (12,7 mm) THREADED ADJUSTMENT TEMPERATURE RATING PROFILE DEPTH AIR GAP ORDINARY 3/16" (4,8 mm) 1/8" (3,2 mm) INTERMEDIATE 5/32" (4,0 mm) 3/32" (2,4 mm) FACE OF SPRINKLER SPRINKLER _ 1-7/8"±1/4" FITTING SUPPORT CI (47,6 mm MOUNTING ASSEMBLY ±6,41mm) SU1RFACE J 1 1 f f 5/8" (15,9 mn COVER- SPRINKLER- RETAINER SUPPORT CUP PROFILE AIR 1-1/8" (28,6 m ASSEMBLY ASSEMBLY DEPTH GAP (SEE (SEE \ 3 3/16" DIA. TABLE) TABLE) DISPOSABLE (81,0 mm) TIP PROTECTIVE CAP COVER PLATE OPERATED RETAINER SPRINKLER DEFLECTOR IN OPERATED POSITION FIGURE 2 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER (TY3596) INSTALLATION DIMENSIONS, PROTECTIVE CAP, AND ACTIVATED DEFLECTOR The number of "design sprinklers" specified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems. Hydraulic Design (NFPA 13) For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis- charge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Tables A and B as a function of temperature rating and the maximum allowable cover- age area • A minimum discharge of 0.1 GPM/ftz over the design area comprised of the four most hydrauli- cally demanding sprinklers for actual coverage areas protected by the four sprinklers The number of design sprinklers speci- fied in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems. Dry Pipe System Water Delivery When using the Series LFII Residen- tial Concealed Pendent Sprinklers in dry pipe sprinkler systems, the time for water delivery must not exceed 15 seconds for the most remote operat- ing sprinkler. Obstruction to Water Distribution Sprinklers are to be located in accor- dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational Sensitivity The sprinklers are to be installed rela- tive to the ceiling mounting surface as shown in Figure 2. Sprinkler Spacing The minimum spacing between sprin- klers is 8 ft (2,4 m). The maximum spacing between sprinklers cannot exceed the length of the coverage area (see Table A or B) being hydraulically calculated, for example, maximum 12 ft for a 12 ft x 12 ft coverage area, or 20 ft for a 20 ft x 20 ft coverage area. The Series LFII must not be used in applications where the air pres- sure above the ceiling is greater than that below. Down drafts through the Support Cup could delay sprinkler operation in a fire situation. Installation The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers (TY3596) must be installed in accordance with this section. General Instructions Damage to the fusible Link Assembly during installation can be avoided by handling the sprinkler by the support cup only. Therefore, do not apply pres- sure to the fusible Link Assembly. A 1/2 in. NPT sprinkler joint should be obtained with a minimum to maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N•m). Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Cover Plate Assembly by under -or over - tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. WRENCH RECESS 0 t PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 3 W-TYPE 18 SPRINKLER WRENCH Step 1. The sprinkler must only be installed in the pendent position and with the centerline of the sprinkler per- pendicular to the mounting surface. Step 2. Remove the Protective Cap. Step 3. With pipe thread sealant applied to the pipe threads, and using the W-Type 18 Wrench shown in Figure 3, install and tighten the Sprinkler/ Support Cup Assembly into the fitting. The W-Type 18 Wrench will accept a 1/2 in. ratchet drive. Step 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. The Protec- tive Cap helps prevent damage to the Deflector and Guide Pins during ceiling installation and/or during application of the finish coating of the ceiling. It may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Cap. TFP442 Page 5 of 6 Note: As long as the protective Cap remains in place, the system is consid- ered to be "Out Of Service." Step 5. After the ceiling has been com- pleted with the 2-1/2 in. (63 mm) diam- eter clearance hole and in preparation for installing the Cover Plate Assembly, remove and discard the Protective Cap, and verify that the Deflector moves up and down freely. If the sprinkler has been damaged and the Deflector does not move up and down freely, replace the entire sprinkler assembly. Do not attempt to modify or repair a damaged sprinkler. Step 6. Push on the Cover Plate Assembly until its flange comes in contact with the ceiling. Do not continue to push on the Cover Plate Assembly such that it lifts a ceiling panel out of its normal position. If the Cover Plate Assembly cannot be engaged with the Mounting Cup or the Cover Plate Assembly cannot be engaged sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. Care and Maintenance The TYCO RAPID RESPONSE Series LFII Residential Concealed Pendent Sprinklers (TY3596) must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system which it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Absence of a Cover Plate may delay the sprinkler operation in a fire situation. When properly installed, there is an air gap between the lip of the Cover Plate and the ceiling. The Ordinary Tem- perature Cover Plate assembly has a nominal 1/8 in. (3,2 mm) air gap. The Intermediate Temperature Cover Plate has a nominal 3/32 (2,4 mm) air gap, as shown in Figure 2. This air gap is necessary for proper operation of the sprinkler by allowing heat flow from a fire to pass below and above the Cover Plate to help assure appropriate release of the Cover Plate in a fire situation. If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does not seal off any of the air gap. Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted units. Non -factory applied paint may adversely delay or prevent sprinkler operation in the event of a fire. Do not pull the Cover Plate relative to the Enclosure. Separation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi- fied or over heated sprinklers must be replaced. Care must be exercised to avoid damage before, during, and after instal- lation. Sprinklers damaged by drop- ping, striking, wrench twist/slippage, or the like, must be replaced. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION, for example, NFPA 25, in addition to the standards of any other authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions. The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non - operation in the event of a fire or inad- vertent operation may result. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor- dance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product name and part number (P/N). Sprinkler Assemblies Specify: Series LFII (TY3596) 4.91K Res- idential Concealed Pendent Sprinkler, P/N (specify): 160°F(71°C) ...................51-112-1-160 212°F(100°C)..................51-112-1-212 Note: Sprinkler and Cover Plates are separately sold. See below for Cover Plate ordering information. Cover Plate Assemblies Specify: LFII Concealed Sprinkler Cover Plate Assembly, temperature rating (specify), (specify) finish, P/N (specify): 139°F(59°C) Ivory (RAL1015) ...............56-204-0-135 Bright Chrome ................ 56-204-1-135 Beige (RAL1001) ..............56-204-2-135 Pure White (RAL9010)* .........56-204-3-135 Signal White (RAL9003)** .......56-204-4-135 Grey White (RAL9002).......... 56-204-5-135 Brown(RAL8028)..............56-204-6-135 Black (RAL9005) .............. 56-204-7-135 Brushed Brass ................56-204-8-135 Brushed Chrome ..............56-204-9-135 Custom Paint .................56-204-X-135 165°F(74°C) Ivory (RAL1015) ...............56-204-0-165 Bright Chrome ................ 56-204-1 165 Beige (RAL1001) ..............56-204-2-165 Pure White (RAL9010)* .........56-204-3-165 Signal White (RAL9003)** .......56-204-4-165 Grey White (RAL9002).......... 56-204-5-165 Brown(RAL8028)..............56-204-6-165 Black (RAL9005) .............. 56-204-7-165 Brushed Brass ................56-204-8-165 Brushed Chrome ..............56-204-9-165 Custom Paint .................56-204-X-165 *Eastern Hemisphere sales only **Previously known as Bright White Note: All Custom Cover Plates are painted using SHER WIN- WILLIAMS Interior Latex Paint. Contact Johnson Controls Customer Service with any questions related to custom orders. Sprinkler Wrench Specify: W-Type 18 Sprinkler Wrench, P/N 56-000-1-265 TFP442 Page 6of6 1400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 Otto 6 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection traAssociation; Controls TEFLON is a registered demark of DuPont; SHERWIN-WILLIAMS Is a regist_d trademark of SWIMC LLC PIPE AND FITTINGS Tyco Fire Protection Products BLAZEMASTER CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Description TYCO CPVC Pipe and Fittings pro- duced by Tyco Fire Protection Prod- ucts (TFPP) are designed exclusively for use in wet pipe automatic fire sprinkler systems. The TYCO CPVC Pipe and Fittings are produced from BLAZEMASTER CPVC compound that is a specially developed thermo- plastic compound composed of post chlorinated polyvinyl chloride (CPVC) resin and state of the art additives. TYCO CPVC Pipe and Fittings are easier to install than traditional steel pipe systems, and at the same time, provide superior heat resistance and strength as compared to traditional CPVC and PVC piping materials used in the plumbing trade. Various adapt- ers are available to connect CPVC pipe to metallic piping. All female pipe thread adapters have brass inserts for durability. Grooved adapters connect directly to grooved end valves and metallic pipe, with flexible grooved end couplings. NOTICE The CPVC Pipe and Fittings produced with BLAZEMASTER CPVC compound described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protec- tion Association (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Technical Data Sizes 3/4 Inch thru 3 Inch Maximum Working Pressure 175 psi Approvals UL and C-UL Listed FM Approved LPCB Approved NSF Certified MEA Approved City of Los Angeles (Refer to Installation Handbook IH-1900 dated June 2008 for exact listing/approval information.) Manufacture Source U.S.A. Material Pipe: ASTM F442, SDR 13.5 Fittings: ASTM F438 (Sch. 40) ASTM F439 (Sch. 80) ASTM F1970 Color Orange Worldwide www.tyco-fire.com Contacts Installation TYCO CPVC Pipe and Fittings are to be to be installed in accordance with Installation Handbook IH-1900 dated April 2016. Page 1 of 2 APRIL 2016 TFP1915 TFP1915 Page 2of2 Care and Maintenance TYCO CPVC Pipe and Fittings are to be maintained and serviced in accordance with this section. Before closing a fire protection system control valve for inspection or main- tenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must first be obtained from the proper authorities and all person- nel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities and advise those responsible for moni- toring proprietary and/or central station alarms. The owner is responsible for the inspec- tion, testing, and maintenance of their fire protection system and de -vices in compliance with this document, as well as with the applicable standards of the National Fire Protection Associa- tion (e.g., NFPA 25), in addition to the standards of any authority having juris- diction. Contact the installing contrac- tor or product manufacturer with any questions. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor- dance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com GLOBAL HEADQUARTERS 11400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 Copyright © 2016 Tyco Fire Products, LP. All rights reserved. �ii�CO BLAZEMASTER is a trademark of The Lubrizol Corporation. Fire Protection Products Tyco Fire Protection Products Worldwide www.tyco-fire.com Contacts Rapid Seal Adapter (RSA) Fittings Sprinkler Installation and Gasket Replacement General Description Rapid Seal Adapter (RSA) Fittings are intended for use in fire protection sprinkler systems comprised of CPVC pipe and fittings. A gasket housed within the fitting eliminates the need to apply sealant to sprinkler threads and reduces the effort necessary to com- plete a leak -free installation. These installation instructions do not take the place of nor do they eliminate the need for the installer to fully read and understand the complete CPVC Fire Sprinkler Products Installation Instructions and Technical Handbook IH-1900 and individual product tech- nical data sheets. Current documen- tation can be obtained by contacting Tyco Fire Protection Products or visit- ing www.tyco-fire.com. Technical Data Approvals UL and C-UL Listed FM Approved LPCB Certified Certified to all requirements of NSF/ANSI 61, Annex G Maximum Working Pressure 175 psi (12,1 bar) Pipe Thread Connection 1/2 inch NPS Physical Characteristics Housing.... BLAZEMASTER CPVC Compound Cap ....... BLAZEMASTER CPVC Compound Gasket ....................... Polyurethane IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Sprinkler Installation in Rapid Seal Adapter (RSA) Fittings Install sprinklers in RSA Fittings in accordance with the following procedure. Refer to individual sprinkler data sheets for additional information including required sprinkler wrenches. PTIM00 M. Do not apply thread sealant or TEFLON thread tape on sprinklers intended to be installed in RSA Fittings. Thread Sealant or TEFLON tape may not allow the sprinkler to seat properly and cause leakage and/or equipment failure. Step 1. Ensure the sprinkler threads are clean and do not have thread sealant such as tape or paste applied. Avoid- ing cross -threading, gently thread the sprinkler into the fitting and hand - tighten until firmly seated. Vy-Wro M. Do not over -torque sprinklers when wrench -tightening with the manu- facturer required sprinkler wrench. Over -torquing may result in equipment damage. For recessed applications do not attempt to compensate for insufficient sprinkler depth within the Escutcheon Plate by under- or over -tightening the sprinkler. Re -adjust the sprinkler fitting position to suit. Step 2. Orient the sprinkler as needed by applying the manufacturer speci- fied sprinkler wrench to the sprinkler wrench flats and tighten up to an addi- tional full turn, or by applying up to a maximum torque of 7 ft.-Ibs. (9,5 Nm). STEP 1 FIGURE 1 RAPID SEAL ADAPTER FITTINGS SPRINKLER INSTALLATION Page 1 of 2 DECEMBER 2017 TFP1925 TFP1925 Page 2of2 Nola I I FIGURE 2 RAPID SEAL GASKET REMOVAL PICK GASKET RSA FITTING LOAD RECESS SURFACE BASE GASKET BOSS 0 GASKET HANDLE INSERTION SHAFT (RETRACTED) SHAFT -END ACCOMMODATES O 3/4" SOCKET OR LENGTH OF ROD FIGURE 3 RAPID SEAL GASKET REPLACEMENT TOOL Gasket Replacement in Rapid Seal Adapter (RSA) Fittings NOTICE Gasket Replacement and its associated tools were not evaluated as part of the UL Listing program. In the event that a sprinkler, installed in an RSA fitting longer than six months, is removed due to damage or activa- tion, the RSA fitting or the RSA fitting gasket must be replaced. Step 1. Remove the sprinkler from the RSA fitting. Use caution when removing the gasket to avoid damaging the adapter threads. Failure to do so may result in equip- ment damage or failure. Step 2. Using the Rapid Seal Gasket Removal Pick, (Ref. Figure 2) carefully remove the gasket from the RSA fitting. Discard the old gasket. Step 3. Verify that the RSA fitting port is clean - free of all debris, chips, or burrs. Failure to do so may result in equipment damage or failure. Step 4. Rotate the Rapid Seal Gasket Replacement Tool insertion shaft (Ref. Figure 3) counter -clockwise until fully retracted. Place the Rapid Seal Replacement Gasket (Ref. Figure 4) onto the shaft end boss and rotate the shaft clockwise until the gasket is flush with the surface of the base recess. Step 5. Holding the Rapid Seal Gasket Replacement Tool (Ref. Figure 3) base recess firmly against the face of the RSA fitting, rotate the insertion shaft until fully engaged. Remove the Rapid Seal Gasket Replacement Tool from the RSA and verify that the gasket is evenly seated and fully installed in the RSA fitting port. Step 6. Install the replacement sprin- kler in accordance with the Sprinkler Installation section in this data sheet. 1C) FIGURE 4 RAPID SEAL REPLACEMENT GASKET Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product name and Part Number (P/N). Rapid Seal Adapter Specify: Rapid Seal CPVC Sprinkler Adapter, (specify type), (specify size, Inch Slip x NIPS), P/N (specify): Female 3/4 x1/2.........................80175RS 1 x1/2...........................80176RS Spigot 1 x1/2...........................80178RS 90° Elbow 1 x 1/2...........................80198RS 3/4 x1/2........................ 80199RS Replacement Tools and Gasket Rapid Seal Gasket Replacement Tool ..... 3060 Rapid Seal Gasket Removal Pick ........ 3061 Rapid Seal Replacement Gasket (Qty 10)..3062 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 Copyright © 2018 Tyco Fire Products, LP. All rights reserved. �[�CO TEFLON is a registered trademark of DuPont Fire Protection Products BLAZEMASTER is a trademark of The Lubrizol Corporation HANGERS AND SEISMIC BRACING CPVC Z ANVIL Fig. 184 (Formerly Afton Fig. 515) Size Range: 3/4" through 1" Material: Carbon Steel Finish: Pre -Galvanized per ASTM A653 Service: Double Offset Hanger and Restrainer • Hanger and surge restraint for horizontal CPVC piping when installed on the side of the supporting structure. • Listed with hardware provided on structural wood beams and composite wood beams (1" minimum). For wood structures with less than 1" thickness, wood blocks may be placed on the backside of the wood structure. #14xl" fastener pro- vided must be fully engaged in the wood block. • May be installed with concrete, steel, and other structural members with fasteners which comply with the requirements of NFPA 13. Approvals: cULus Listed Installation: • Slide CPVC pipe through the double offset hanger and restrainer. • Secure the hanger to the supporting structure with the screws provided or with listed fasteners. Features: • Beveled edge design helps protect the CPVC pipe from any rough surface and eliminates pipe abrasion. • Easily attaches to wood structure with #14 x 1" hex washer head self -threading screw supplied with product. No pre -drilling required. • Bottom of pipe is offset 11/2" from the structure. Eliminates wooden spacer blocks Ordering: Specify CPVC pipe size, figure number and description. 0Cx2 +p + B L CPVC Pipe Structure Fasteners x2 >— Fig. 184 FIG.184: DIMENSIONS (IN) • WEIGHT (LBS) CPVC Pipe Size A B 0C H L Max. Hanger Spacing (FT.) Approx. Weight/100 'A 11/2 11/2 1/4 3% 5% 51/2 17 1 1112 11/2 '/a 3% 5% 6 17 PROJECTi• rAPPROVAL Project: []Approved Address: ❑ Approved as noted Contractor: ❑ Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: PH-1.18 CPVC Z ANVIL Fig. 187 (Formerly Afton Fig. 511) TWo Hole 900 Side Mount Strap Size Range: 3/4" through 2" Finish: Zinc Plated Steel (Hot -Dip Galvanized optional) Service: Hanger for CPVC pipe in the horizontal position on the bottom of structural wood beams and Steel 20 Ga. (min.) (Fig. A). Can be used as a restrainer, only in Stee120 Ga. (min) (Fig. 8). During installation, adjust hanger mounting flanges such that pipe contacts both mounting surface and hanger, minimizing vertical pipe movement. Approvals: UL and ULC Listed. Installation: • Snap hanger over pipe. • Secure hanger to mounting surface with screws provided. • Do not anchor tightly to mounting surface. Pipe must be allowed to move freely through hanger. • Steel applications require two (2) #14 x 1" hex washer head self -drilling TEK screws. Not Supplied. Part Number STD-0090. Features: c8us LISTED • Beveled edge design helps protect the CPVC pipe from any rough surface. • Easily attaches to wood structure with #10 x 1" hex washer head self threading screw supplied with product. No pre -drilling required. Ordering: Specify CPVC pipe size, figure number and description. Fig. A Fig. B FIG.187: DIMENSIONS (IN) • WEIGHT (LBS) CPVC Pipe Size A B ttC E F Max. Hanger Spacing (FT.) Approx. Weight/100 (Ibs) 3/4 1 11/z 1/4 11/8 23/a 51/z 5 1 11/8 11/z 1/4 11/8 213/ 6 6 6 11/4 1'/16 13/4 11/4 111/8 131/4 1 61/z 7 11/z 11/z 1'/s 1 1/4 1 11/8 1 31/z 1 7 8 2 13/a 2 1 1/4 1 11/s 1 3'/s 1 8 9 PROJECTi• rAPPROVAL Project: []Approved Address: ❑ Approved as noted Contractor: ❑ Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: PH-1.18 CPVC Fig* 188R (Formerly Afton Fig. 514) Size Range: 3/4" through 2" Material: Carbon Steel Finish: Pre -Galvanized per ASTM A653 Service: TWo Hole Standoff and Restrainer • Hanger and surge restraint for horizontal CPVC piping when installed on the top, bot- tom, and side of the supporting structure. • Guide for vertical CPVC piping when installed on the side of the supporting structure. • Horizontal and vertical seismic restraint per NFPA 13-2016 requirements. • Listed with hardware provided on structural wood beams and composite wood beams (1" minimum). Listed with steel (18ga minimum) with two (2) #141" or Ya"xl" hex washer head self -drilling TEK screws. For wood structures with less than 1" thickness, wood blocks may be placed on the backside of the wood structure. #10xl" fastener provided must be fully engaged in the wood block. • May be installed with concrete, steel structural members, and other structural members with fasteners which comply with the requirements of NFPA 13. Approvals: cULus Listed Patents: No. 6,648,278 Installation: • Snap hanger over pipe. If needed, squeeze strap back around pipe. • CPVC pipe must be allowed to slide freely through the Fig.188R. • Secure hanger to mounting surface with screws provided or with listed fasteners. Features: • Beveled edge design helps protect the CPVC pipe from any rough surface and eliminates pipe abrasion. • Easily attaches to wood structure with #10 x 1" hex washer head self -threading screw supplied with product. No pre -drilling required. • Bottom of pipe is offset 1%" from the structure. Eliminates wooden spacer blocks. Ordering: Specify CPVC pipe size, figure number and description. Hanger & Restrainer Hange Restra D& 'ainer c &us LISTED Installation - Backing Nut Hanger =1 - at top fastener Restraint = 2 - on each fastener Per NFPA-13D and NFPA-13R PROJECT Project: []Approved Address: ❑ Approved as noted Contractor: ❑ Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: PH-1.18