REVIEWED BLD BLD2021-1002+Structural_Plans+7.20.2021_12.41.14_AM+2309798STRUCTURAL NOTES (THESE NOTES ARE TYPICAL UNLESS NOTED OR DETAILED OTHERWISE ON DRAWINGS) CODE ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (IBC), 2018 EDITION. SPECIFICATIONS AND STANDARDS WHERE REFERENCED ON THE DRAWINGS ARE TO BE THE LATEST EDITION. DEAD LOADS: ROOF 12 PSF FLOOR 12 PSF LIVE LOADS: ROOF (SNOW LOAD) 25 PSF RESIDENTIAL 40 PSF (LIVE LOADS ARE REDUCED WHERE PERMISSIBLE PER IBC SECTION 1607.11). EARTHQUAKE LOADS: EQUIVALENT LATERAL FORCE PROCEDURE PER ASCE 7-16 SECTION 12.8. SITE CLASS (ASSUMED) D SHORT PERIOD SPECTRAL RESPONSE ACCEL (SS) 1.282 ONE SECOND SPECTRAL RESPONSE ACCEL (SI) 0.450 SHORT PERIOD DESIGN SPECTRAL RESPONSE ACCEL (SDS) 0.855 ONE SECOND DESIGN SPECTRAL RESPONSE ACCEL (SDI) 0.555 RISK CATEGORY II SEISMIC IMPORTANCE FACTOR (IF) 1.0 SEISMIC DESIGN CATEGORY D BASIC SEISMIC FORCE -RESISTING -SYSTEM PLYWOOD SHEARWALLS RESPONSE MODIFICATION FACTOR, (R) 6.5 REDUNDANCY FACTOR (p) 1.0 SEISMIC RESPONSE COEFFICIENT (CS) 0.131 W = TOTAL SEISMIC DEAD LOAD AS DEFINED PER ASCE 7-10 SECTION 12.7.2. BASE SHEAR (V), V = CSW = RD I W WIND LOADS: BASIC WIND SPEED (3 SECOND GUST) 97 MPH EXPOSURE B KzT 1.0 SEE PLANS FOR ADDITIONAL DESIGN LOADS. STATEMENT OF SPECIAL INSPECTIONS SPECIAL INSPECTIONS ARE REQUIRED AS INDICATED IN THE FOLLOWING TABLE. THE CONTRACTOR SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND OWNER PRIOR TO COMMENCEMENT OF WORK IN ACCORDANCE WITH CHAPTER 1704.4 OF THE IBC. SPECIAL INSPECTION FOR THE ABOVE SYSTEMS SHALL BE AS INDICATED IN THE SPECIAL INSPECTION TABLE BELOW. STRUCTURAL OBSERVATION OF THE STRUCTURAL SYSTEM BY THE ENGINEER IS NOT REQUIRED. FREQUENCY AND DISTRIBUTION OF REPORTS - INSPECTION REPORTS SHALL BE PROVIDED FOR EACH DAY ON SITE BY SPECIAL INSPECTOR. STRUCTURAL OBSERVATION REPORTS SHALL BE PROVIDED AFTER EACH OBSERVATION. REPORTS SHALL BE DISTRIBUTED TO THE CONTRACTOR, ARCHITECT, ENGINEER AND BUILDING OFFICIAL. SPECIAL INSPECTION OPERATION CONT PERIODIC REMARKS SOILS FOUNDATION BEARING CAPACITY VERIFICATION X NOTE: ALL ITEMS MARKED WITH AN "X" SHALL BE INSPECTED IN ACCORDANCE WITH IBC CHAPTER 17. SPECIAL INSPECTION SHALL BE PERFORMED BY A QUALIFIED TESTING AGENCY DESIGNATED BY THE OWNER. THE ARCHITECT, STRUCTURAL ENGINEER, AND BUILDING OFFICIAL SHALL BE FURNISHED WITH COPIES OF ALL RESULTS. ANY INSPECTION FAILING TO MEET THE PROJECT SPECIFICATIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE DESIGN TEAM. FOUNDATIONS: SPREAD FOOTINGS SOILS REPORT: REPORT NOT AVAILABLE AT TIME OF DESIGN ALLOWABLE SOIL PRESSURE: 2000 PSF (ASSUMED; TO BE FIELD VERIFIED DURING CONSTRUCTION) FOOTINGS SHALL BEAR ON FIRM UNDISTURBED EARTH OR 12" OF COMPACTED STRUCTURAL FILL AS REQUIRED AND AT LEAST 18" BELOW ADJACENT EXTERIOR GRADE. ANY FOOTING ELEVATIONS SHOWN IN THE DRAWINGS REPRESENT MINIMUM DEPTHS AND ARE FOR BIDDING ONLY. ACTUAL FOOTING ELEVATIONS ARE SUBJECT TO SITE CONDITIONS AND MUST THEREFORE BE ESTABLISHED BY THE CONTRACTOR. FOOTINGS SHALL BE CENTERED BELOW COLUMNS OR WALLS ABOVE, UNLESS NOTED OTHERWISE. IMPORTED STRUCTURAL FILL AND BACKFILL MATERIAL SHOULD CONSIST OF CLEAN, WELL GRADED GRANULAR MATERIAL FREE OF DEBRIS OR ORGANICS WITH A MAXIMUM PARTICLE DIAMETER OF THREE INCHES AND NO MORE THAN 10% FINES (PASSING THE #200 SIEVE). FILL AND BACKFILL MATERIAL SHOULD BE PLACED IN LEVEL LIFTS NOT EXCEEDING TWELVE (12") INCHES IN LOOSE THICKNESS AND COMPACTED TO A MINIMUM OF 95% OF ITS MAXIMUM DRY DENSITY AS DETERMINED BY ASTM TEST METHOD D1557. LUMBER ALL GRADES SPECIFIED ARE MINIMUM GRADES REQUIRED. ALL LUMBER SHALL BE IN ACCORDANCE WITH WWPA GRADING RULES, KILN -DRIED TO MC 19 AND OF THE FOLLOWING MINIMUM STANDARDS: SIZE CLASSIFICATION SPECIES GRADE Fb (PSI) Fc (PSI) SLEEPERS DOUG-FIR STUD 700 - LIGHT FRAMING (STUDS) HEM -FIR STUD 675 800 2x JOISTS AND PLANKS HEM -FIR #2 850 - PLATES AND BLOCKING HEM -FIR #2 850 - 6x AND LARGER BEAMS AND STRINGERS DOUG-FIR #2 875 - 4x AND SMALLER BEAMS AND STRINGERS HEM -FIR #2 850 - ALL POSTS AND TIMBERS DOUG-FIR T #1 i 1200 j 1000 REFER TO PLAN NOTES, SCHEDULES, AND DETAILS FOR MORE SPECIFIC LUMBER SIZE AND GRADE REQUIREMENTS. UNLESS NOTED OTHERWISE IN THE PLANS, ALL WOOD AND WOOD -BASED MEMBERS EXPOSED TO WEATHER OR IN CONTACT WITH CONCRETE, MASONRY, OR WITHIN 8" OF SOIL SHALL BE PRESERVATIVE -TREATED BY VACUUM -PRESSURE IMPREGNATION IN ACCORDANCE WITH AWPA STANDARD U1. TIMBERSTRAND, MICROLLAM, AND PARALLAM MEMBERS FABRICATED IN CONFORMANCE WITH THE INTERNATIONAL CODE COUNCIL EVALUATION SERVICE (ICC-ES) REPORT NO. ESR-1387 OR CCMC REPORT NO. 12627-R, 08675-R, AND 11161-R. EACH MEMBER SHALL BE IDENTIFIED BY A STAMP INDICATING THE PRODUCT TYPE AND GRADE, ICC-ES OR CCMC REPORT NUMBER, MANUFACTURER'S NAME, PLANT NUMBER AND INDEPENDENT INSPECTION AGENCY'S LOGO. FABRICATOR SHALL BE CERTIFIED. MEMBERS SHALL MEET THE FOLLOWING MINIMUM STANDARDS: SIZE CLASSIFICATION SPECIES GRADE Fb (PSI) Fv (PSI Fc (PSI) BEAMS & POSTS (d < 9 1/2") LSL 1.3E 1,700 425 1,835 RIMS & BEAMS (d >_ 9 1/2") LSL 1.55E 2,325 310 - BEAMS & POSTS LVL 2.0E 2,600 285 2,510 POSTS (d < 9 1/2") PSL 1.8E 2,400 190 2,500 BEAMS (d >_ 9 1/2") PSL 2.2E 2,900 290 - TIMBERSTRAND, MICROLLAM, AND UNTREATED PARALLAM MEMBERS ARE INTENDED FOR DRY -USE APPLICATIONS. UNLESS NOTED OTHERWISE, ENGINEERED WOOD BEAMS EXPOSED TO WEATHER SHALL BE TREATED PER MANUFACTURES RECOMMENDATIONS. NAILS, BOLTS, AND METAL CONNECTORS FOR WOOD ALL NAILS SHALL CONFORM TO THE STANDARDS SET FORTH BY THE NATIONAL DESIGN STANDARDS (NDS) FOR WOOD CONSTRUCTION, LATEST EDITION. NAILING NOT SPECIFIED SHALL BE PER IBC TABLE 2304.10.1 NAILING SCHEDULE. ALL NAILS CALLED OUT ON PLANS SHALL BE COMMON NAILS UNLESS NOTED OTHERWISE AND SHALL MEET OR EXCEED THE FOLLOWING MINIMUM GUIDELINES: NAIL SHANK 0 MIN LENGTH 8d COMMON 0.1310 2 1/2" SHANK 10d COMMON 0.1480 3" SHANK 12d COMMON 0.1480 3 1/4" SHANK 16d COMMON 0.1620 3 1/2" SHANK 10d BOX NAILS MAY BE SUBSTITUTED FOR 8d COMMON NAILS WITH NO CHANGE IN NAIL SPACING. FRAMING MEMBERS MAY BE NAILED WITH 16d SINKERS (0.148"0 x 3 1/4"), BUT ONLY 16d COMMON NAILS SHALL BE USED WHERE 16d NAILS ARE INDICATED IN THIS DRAWING SET. ENGINEER MAY APPROVE OTHER NAILS IF NAIL LABELS ARE SUBMITTED TO ENGINEER PRIOR TO START OF CONSTRUCTION. ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG SCREWS BEARING ON WOOD. LEAD HOLES FOR LAG BOLTS SHALL BE BORED FOR THE SHANK AND THREADED PORTIONS PER NDS 12.1.4.2. CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE" BY SIMPSON COMPANY, CATALOG TO BE THE LATEST EDITION, OR ENGINEER APPROVED EQUAL. CONNECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND WITH THE NUMBER AND SIZE OF FASTENERS AS SPECIFIED BY THE MANUFACTURER. WHERE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE ONE-HALF OF THE NAILS, SCREWS, OR BOLTS IN EACH MEMBER. INSTALL SOLID BLOCKING AT ALL BEARING POINTS. ALL SHIMS SHALL BE SEASONED, DRIED, AND THE SAME GRADE (MINIMUM) AS MEMBERS CONNECTED. GALVANIZATION UNLESS NOTED OTHERWISE, STEEL CONNECTORS IN CONTACT WITH TREATED WOOD SHALL BE GALVANIZED ACCORDING TO THE FOLLOWING TABLE: GALVANIZATION UNTREATED WOOD CCA-C SBX ACQ-C ACQ-D CBA-A CA-B OTHER BORATE ACZA OTHER PT WOOD G90 X X X G 185 X X X X X X HDG X X X X X X STT300 X X X X X X X X G90 = 0.90 OZ. OF ZINC PER SQUARE FOOT OF AREA G185 = 1.85 OZ. OF ZINC PER SQUARE FOOT OF AREA HDG = HOT DIP GALVANIZED SST300 = TYPE 316L STAINLESS STEEL RATED SHEATHING RATED SHEATHING SHALL BE GRADE C-D INT-APA WITH EXTERIOR GLUE OR OSB SHEATHING WITH EXTERIOR GLUE IN CONFORMANCE WITH IBC STANDARD 2303.1.5. TYPICAL FRAMING NOTES Im:j:_1ilk] 1►141TIT&IImaM-Al 11►10 2x STUDS @ 16" OC FOR ALL SHEAR AND/OR BEARING WALLS UNO. REFER TO FRAMING PLAN NOTES FOR TYPICAL DOOR & WINDOW HEADERS NOT CALLED OUT ON THE PLANS. HEADERS SHALL BE SUPPORTED BY A MINIMUM OF (1) CRIPPLE AND (1) FULL HEIGHT STUD UNO. COLUMNS BELOW FLUSH MULTIPLE JOIST BEAMS SHALL BE EQUAL IN WIDTH TO THE BEAM. ALL COLUMNS NOT CALLED OUT OTHERWISE SHALL BE TWO STUDS. 2. WALL BASE PLATE ON CONCRETE WALL PLATES BEARING ON CONCRETE SHALL BE PRESSURE -TREATED. FOR ALL EXTERIOR AND INTERIOR WALLS, BOLT PLATES OR SILLS TO CONCRETE WITH 5/8 INCH DIAMETER ANCHOR BOLTS WITH 7 INCH MINIMUM EMBEDMENT. PLACE AT 5'-0" OC MAXIMUM FOR SHEAR WALLS, AND AT 6'4" OC FOR BEARING WALLS AND OTHER PARTITIONS. USE MINIMUM OF TWO ANCHOR BOLTS PER SILL AND PLACE ONE WITHIN 12 INCHES OF EITHER END TYPICAL UNLESS NOTED OR DETAILED OTHERWISE. REFER TO SHEAR WALL SCHEDULE. AT ALL SILL PLATE ANCHOR BOLTS, CONTRACTOR SHALL INSTALL 1/4" x 3" x 3" FLAT PLATE WASHERS. 3. ROOF AND FLOOR FRAMING PROVIDE 1 1/2" FULL DEPTH BLOCKING FOR JOISTS AND RAFTERS AT ALL SUPPORTS AND AT 8'-0" OC MAXIMUM UNO. INTERMEDIATE 8'4' OC BLOCKING NOT REQ'D IF GWB CEILING IS INSTALLED DIRECTLY TO UNDERSIDE OF FRAMING. INSTALL DOUBLE JOISTS UNDER PARTITIONS EXTENDING ONE HALF OR MORE OF THE JOIST SPAN. PROVIDE TRUSS BLOCKING PANELS FOR ROOF TRUSSES AT SUPPORTS AND SHEAR WALLS, AND WHERE INDICATED ON PLANS AND DETAILS. 4. DIAPHRAGM NAILING ALL SHEAR WALLS, FLOOR AND ROOF DIAPHRAGM NAILINGS SHALL BE AS CALLED OUT ON SCHEDULES OR ON THE PLANS. EXTERIOR WALLS NOT INDICATED AS SHEAR WALLS SHALL BE SHEATHED AND NAILED TO SUPPORTING FRAMING WITH 8d NAILS AT 6" OC AT ALL PANEL EDGES AND 12" OC AT ALL INTERMEDIATE SUPPORTS. THE USE OF NAIL GUNS WILL BE APPROVED IF NAILING INTO THE DIAPHRAGMS CAN BE INSTALLED FLUSH WITH FACE OF SHEATHING. NAIL PENETRATIONS GREATER THAN 1/16" ARE NOT ACCEPTABLE. CUTTING AND/OR NOTCHING OF WOOD STUDS OR PLATES SHALL NOT EXCEED 25% OF THE STUD/PLATE WIDTH IN EXTERIOR AND BEARING WALLS AND SHALL NOT EXCEED 40% OF THE STUD/PLATE WIDTH IN ANY NON -BEARING PARTITIONS. BORED HOLE DIAMETER IS LIMITED TO 40% OF STUD/PLATE WIDTH IN ANY STUD AND MAY BE 60% IN NONBEARING PARTITIONS OR IF STUD IS DOUBLED. MAINTAIN 5/8" MINIMUM EDGE DISTANCE FROM HOLE EDGE. 6. GYPSUM WALLBOARD NAILING ALL GYPSUM WALLBOARD SHALL BE NAILED TO ALL STUDS AND TOP AND BOTTOM PLATES WITH 6d COOLER NAILS OR NO. 13 GAUGE x 1 5/8" @ 7" OC (5d COOLER NAILS FOR 1/2 INCH GYPSUM SHEATHING). TYPICAL UNLESS NOTED OTHERWISE. INSTALLATION OF GWB SHALL BE SUCH THAT JOINTS ARE STAGGERED ON EACH SIDE OF A SINGLE WALL. EXISTING BUILDING CONTRACTOR SHALL VERIFY ALL DIMENSIONS, MEMBER SIZES AND CONDITIONS OF THE EXISTING BUILDING DEPICTED IN THE DRAWINGS, AND NOTIFY THE STRUCTURAL ENGINEER OF ANY DISCREPANCIES FOR POSSIBLE REDESIGN. CONTRACTOR RESPONSIBLE FOR COMPLETELY SEALING ALL AREAS WHERE EXISTING ROOF MATERIAL IS PENETRATED OR REMOVED. PROVIDE WATER PROOFING AS REQUIRED BY THE ARCH. GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS FOR COMPATIBILITY BEFORE PROCEEDING. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING. CONTRACTOR SHALL BE RESPONSIBLE FOR ERECTION STABILITY AND TEMPORARY SHORING AS NECESSARY UNTIL PERMANENT SUPPORT AND STIFFENING ARE INSTALLED. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL NOT SATISFY THIS REQUIREMENT. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF A SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND THE STRUCTURAL ENGINEER. DEFINITION DIRECTION OF FRAMING EXTENT OF FRAMING COLUMNS COLUMN BEARING ON BEAM BEAM CONTINUOUS OVERSUPPORT CONCRETE WALL BEARING STUD WALL NON -BEARING STUD WALL BEARING STUD SHEAR WALL NON -BEARING STUD SHEAR WALL CMU WALL STRUCTURAL STEEL RATED SHEATHING SHEAR WALL (SEE SCHEDULE) SWX COLUMN MARK (SEE SCHEDULE) FOOTING MARK (SEE SCHEDULE) HOLDOWN MARK (SEE SCHEDULE) HANGER MARK (SEE SCHEDULE) FLAG NOTE (SEE PLAN NOTES) STEEL MOMENT FRAME CONN. ABBREVIATIONS (A) ABOVE AB ANCHOR BOLT ALT ALTERNATE GLB GLUE -LAMINATED BEAM HORIZ HORIZONTAL KIP KING POST KIPS PER SQUARE INCH ARCH ARCHITECT KSI (B) BELOW BAR DIAMETER BLOCKING BEAM L ANGLE MECHANICAL MOMENT FRAME METAL NEAR SIDE ON CENTER BD BLKG BM MECH MF MTL BOT BOTTOM BEARING NS BRNG OC BTWN BETWEEN COMPLETE JOINT PENETRATION OPP OPPOSITE CJP PL PLATE CLR CLEAR PLCS PLACES CMU CONCRETE MASONRY UNIT PSI POUNDS PER SQUARE INCH COL COLUMN PSF POUNDS PER SQUARE FOOT POST TENSIONED PRESSURE TREATED CONC CONCRETE P/T CONN CONNECTION PT CONT CONTINUOUS REINF REINFORCING REQ'D REQUIRED SCHED SCHEDULE SIM SIMILAR SOG SLAB ON GRADE STD STANDARD COORD COORDINATE DBL DOUBLE DIET DETAIL DIA DIAMETER DIM DIMENSION DIR DIRECTION STIFF STIFFENER EA EACH ELEVATION STL STEEL SYMM SYMMETRICAL SW SHEARWALL TOC TOP OF CONCRETE ELEV ES EACH SIDE EX EXISTING EXP EXPANSION FLOOR TOS TOP OF STEEL FLR TOW TOP OF WALL FDN FOUNDATION FTG FOOTING FS FAR SIDE GC GENERAL CONTRACTOR TYP TYPICAL UNLESS NOTED OTHERWISE LINO VERT VERTICAL WIDE FLANGE WF REVIEWED BY CITY OF EDMONDS ' .... BUILDING DEPARTMENT.....: ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 X 02121 J Q H H Z 2 O m F EL N - ~ U � U Ld w 0 a DESIGN: RMK DRAWN: JCP CHECK: XXX JOB NO: 20436.10 DATE: 04/02/21 RECEIVED Jul 27 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-1002 I..I..I 0 O W = N O =) 00 W p rn Q Z Q \W / w m O Z :2 M O L U O 0 Y � W SHEET: w MAIN FLOOR FRAMING & FOUNDATION PLAN SCALE: 1/4" = V-0" FRAMING PLAN NOTES: 2'-0" 2'-0" 4'-0" ROOF FRAMING PLAN SCALE: 1/4" = V-0" TYPICAL ROOF FRAMING PLAN NOTES: 2'-0" 0 2'-0" ENGINEERING, 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 04/02/21 J Q z O m n N r U � Cn re W w C) d DESIGN: RMK DRAWN: JCP CHECK: XXX JOB NO: 20436.10 DATE: 04/02/21 4'-0" 1. CONTRACTOR SHALL VERIFY ALL EXIST FRAMING SHOWN AND NOTIFY ALL PARTIES OF ANY DISCREPANCIES. 1. WALLS SHOWN ON ROOF FRAMING PLAN ARE WALLS BELOW ROOF FRAMING. HOLDOWNS SHALL BE RECEIVED PLACED AT THE BASE OF THE WALLS SHOWN. 2. FOOTINGS SHALL BEAR ON FIRM NATIVE SOIL OR COMPACTED STRUCTURAL FILL. Jul 27 2021 2. BEAMS SHOWN ON ROOF FRAMING PLAN SHALL BE ABOVE DOUBLE TOP PLATE UNLESS USED AS A DOOR 3. COLUMNS AND BEARING WALLS SHOWN ON PLANS SHALL BE CONTINUED DOWN TO THE FOUNDATION OR WINDOW HEADER. CITY OFEDMONDS DEVELOPMENT SERVICES UNLESS CARRIED BY A BEAM BELOW. DEPARTMENT 3. CONTRACTOR TO VERIFY ALL EXIST FRAMING SHOWN AND NOTIFY ALL PARTIES OF ANY DISCREPANCIES. 4. WALLS SHOWN ON THE FRAMING PLANS ARE WALLS BELOW THE FRAMING LEVELS INDICATED. 4. UNLESS NOTED OTHERWISE, HEADERS AT ALL EXTERIOR WALLS SHALL BE 4x8 HF#2 WHERE MAXIMUM 5. TYPICAL HEADERS AT BEARING LOCATION SHALL BE 4x6 DF#2 UNO SUPPORTED BY A MINIMUM OF (1) CRIPPLE SPAN = 5'-5". BLD2021-1002 STUD AND (1) FULL HEIGHT STUD. 5. STUD WALL FRAMING SHALL BE 2x HF STUDS @ 16" OC FOR ALL STUD WALLS SHOWN ON THE PLAN. `I 6. COLUMNS NOT OTHERWISE SHOWN OR CALLED OUT ON PLAN SHALL BE (2) 2x STUDS. J 6. REFER TO SHEET S6.1 FOR TYPICAL ROOF FRAMING DETAILS. La 7. UNLESS NOTED OTHERWISE ALL STUDS SHALL BE HF STUD GRADE AND SPACED AT 16" OC. Q Q 7. REFER TO DETAIL 2/55.1 FOR CONSTRUCTION OF MULTIPLE STUD COLUMNS. 0 W..." vr 7 W U 0 W = N � O D 00 w 0 (n Q Z La Q > Oaf �m� 0 z :2 M 0 Lo :m U 0 0 Y � W SHEET: S201 O G SHEAR WALL SCHEDULE MIN FRAMING AT SHEAR WALL RIM JOIST OR SILL PLATE SILL PLATE ANCHOR SHEAR TYPE APA-RATED ADJOINING PANEL NAILING BLOCK CONN TO NAILING TO BOLT TO SLAB OR FOUNDATION CAPACITY SHEATHING EDGES (SEE NOTE 5) AT PANEL EDGES TOP PLATE RIM/BLKG FOUNDATION SILL PLATE SIZE (PLF) BELOW SW6 15/32" 2x STUD 0.131"0 x 2 1/2" LTP4 OR A35 0.131"0 x 3" @ 5/8" 0 AB @ 5'-0" OC 2x 242 ONE SIDE AND BLKG @ 6" OC @ 24" OC 6" OC SW4 15/32" 2x STUD 0.131"0 x 2 1/2" LTP4 OR A35 0.131"�4 x 3" @ 5/8" 0 AB @ 4'-0" OC 2x 350 ONE SIDE AND BLKG @ 4" OC @ 20" OC 4" OC NOTES: 1. REFER TO THE TYPICAL SHEAR WALL DETAIL. 2. THE VALUES IN THIS TABLE ARE APPROPRIATE FOR HF GRADE STUDS AND HF GRADE PLATES & RIM/BLOCKING. 3. NAILS AT ADJOINING PANEL EDGES SHALL BE STAGGERED EACH SIDE OF THE COMMON JOINT. 4. INTERMEDIATE FRAMING TO BE WITH 2x MINIMUM MEMBERS. FIELD NAILING 12" OC MAXIMUM. 5. PROVIDE A MINIMUM OF 7" EMBEDMENT FOR AB INTO FOUNDATION OR STEM WALL. 6. 7/16" SHEATHING MAY BE USED IN PLACE OF 15/32" SHEATHING PROVIDED ALL STUDS ARE SPACED 16" OC OR PANELS ARE APPLIED WITH LONG DIMENSION ACROSS STUDS. 7. AT EXIST FOUNDATION WALLS, INSTALL TITEN HD ANCHOR TO MATCH TABLE AND NOTES ABOVE W/ 7" MIN EMBEDMENT. HOLDOWN SCHEDULE MARK TYPE MIN CHORD SIZE STUD NAILS OR BOLTS ANCHOR BOLT (SEE NOTE 4) CAPACITY (LB) 1 HDU2 (2) 2x (6) SDS 1/4" x 2 1/2" SCREWS 5/8"0 3,075 NOTES: 1. REFER TO THE LATEST SIMPSON STRONG -TIE CATALOG FOR ADDITIONAL INSTALLATION REQUIREMENTS. 2. INSTALL HD HOLDOWNS AT FOUNDATION WALLS PER DETAIL 1/S4.1. 3. AT ALL HOLDOWN CHORDS, PROVIDE PANEL EDGE NAILING PER SHEAR WALL SCHED. ENGINEERING, 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 04/02/21 J Q z O m n N r U 5 Cn rv- W w C) d DESIGN: RMK DRAWN: JCP CHECK: XXX JOB NO: 20436.10 DATE: 04/02/21 RECEIVED Jul 27 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-1002 J W 0 O w w U O W = N � O D 00 w O (n Q Z La 3: Q > �aV) m o O z :2 M O Lo :m U O 0 Y � W SHEET: V) W J D 0 w U cn S3ml z z O G NOTE: EXTEND THREADED ROD BETWEEN JOISTS INTO STEM WALL BELOW. PROVIDE ROD COUPLER IF REQ'D. THREADED ROD AS REQ'D PER PLAN AND HOLDOWN SCHEDULE. INSTALL W/ HILTI HIT-HY 200 EPDXY CONC STEM WALL TOP OF FTG SHEAR WALL PER PLAN AND SCHED HOLDOWN PER PLAN AND SCHED II I I SQUASH BLKG TO I I MATCH HOLDOWN I I CHORD ABOVE II II II J ii II II II o II _� II � II HOLDOWN DETAIL (EXIST FOOTING' SCALE: 1" = V-0" EXIST FLOOR JOISTS SIMPSON A34 EA SIDE OF COLUMN, (2) TOTAL SIMPSON AC4 SERIES POST CAP EA SIDE OF POST COL PER PLAN ALIGNED W/ COLUMN ABOVE SECTION SCALE: 1" = V-0" COL PER PLAN EXIST FLOOR SYSTEM EXIST JOIST BLKG, CUT AS REQ'D FOR FULL COLUMN BEARING ON WALL PLATE 10FbiIViT/e1Iato] »weTIIq SIMPSON A34 OR LTP4 EA SIDE OF COL EXIST SOG EXIST FTG ENGINEERING, 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 04/02/21 J Q H H Z O m n N r U 5 Cn rv- W w C) d DESIGN: RMK DRAWN: JCP CHECK: XXX JOB NO: 20436.10 DATE: 04/02/21 RECEIVED Jul 27 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-1002 J W 0 O w Lw U O W = N � O D 00 Lw0� V) Q z La Q > �m� O z :2 M O Lo :m U O 0 Y � LW SHEET: J Q Ld 0 Z O Q 0 Z ZD O L.L. S4.1 w z STAGGER NAILS ON EA SIDE OF PANEL JOINT AS REQUIRED PER SHEAR WALL SCHED -n-------r- - I.1 I•I II II II II HEADER PER PLAN II II II II I I I I I.1 I•I • I I I I I I I I I I I I I I I CRIPPLE STUDS PER I I I I I j I I I I PLAN; DO NOT CUT IIII I.1 I•I I. AWAY MATERIAL FROM I I• I I I I I I I• CRIPPLE STUDS j I I I I I I I I I II II I I I I I I •I I•I I I I I I FULL -HEIGHT III IIII I I•I II II I.1 I I I I I I I I •I I I I• II I. I HOLDOWN CHORD IIII IIII I I I I II II I •I I I I I II IIII IIII II II I.1 I I I.I I I II 1.1 IIII IIII II II II II I.I I I II II IIII IIII I I I II II 1.1 I.I I I I I I I.I I I I• II 1.1 j II II II II I I •I I.I I II AB W/ SIMPSON BP I I I I I •I II PL WASHER, TYP I I I•I I I• I 1.1 I I I II II I I I •I I•I I I I II PT SILL PL PER SHEAR I I I II WALL SCHED I•I •I I I A I.I II 1------1 I•I II II _ z II II CONCRETE FOOTING OR P/T SLAB NOTES: 1. REFER TO STRUCTURAL NOTES FOR ADDITIONAL INFORMATION. 2. FOR SHEAR WALLS WHERE NO HOLDOWNS ARE SPECIFIED THE FIRST AB SHALL BE LOCATED NOT MORE THAN V-0" AND NOT LESS THAN (7) BOLT DIAMETERS FROM END OF WALL. TYPICAL SHEAR WALL DETAIL SCALE: 3/4" = V-0" ------------------------------------- ------- - - - - - - - - - - - - - -------r-1-----T- I'I I'I I'I 1•I I I•I II II II II III II II II ;� �I• II II II II II II II III II II II II III II II II II I 1 I II II III FRAMING AT ADJOINING ;�I I I PANEL EDGES PER SHEAR I I I I'I WALL SCHED I I II jI l III II II II II 1�.1 II II II I II II II II I'I I•I I•I 1• II II II II II _J L - - - ;---i•I. -- ;-- ;--i F•---•-- I I I•I I•I II II II II II II II II II II II II I I I•I I•I II II II II II II II II II ff II II II I I I•I I•I II II II II II II II II II II II II I I I•I I•I II II II • -------LL------_L ------ II II 1 II II II 11 11 11 II II 11 AB SIZE AND SPACING 7A —III- II I I PER PLAN AND SHEAR WALL SCHEDULE, TYP (�:3 RIM BOARD (�=3 \\ OR BLOCKING l� C -III—III- -1I1—III--111-1I1- PANEL EDGE NAILING PER SHEAR WALL SCHEDULE, TYP PANEL EDGE NAILING INTO HOLDOWN CHORDS, TYP INTERMEDIATE NAILING @ 12" OC SHEATHING PER PLAN AND SHEAR WALL SCHEDULE HOLDOWN CHORD PER SCHEDULE. REFER TO TYPICAL BUILT-UP COLUMN DETAIL ADDITIONAL END STUD IF REQUIRED TO PROVIDE COUNTERSINK FOR HOLDOWN BOLTS HOLDOWN ANCHORAGE PER PLAN AND SCHEDULE SIMPSON CNW COUPLER 1/2" TO NUT W/ SIZE TO MATCH SHEATHED EDGE HOLDOWN ANCHORAGE PANELEDGE NAILING PER SHEAR WALL SCHED CONTINUE HOLDOWN CHORD TO FOUNDATION 141010[y0:11all Ix \Tit/_\I: CONCRETE FOOTING JOIST DIRECTION PER PLAN PLATE WASHER PER SHEAR WALL SCHED SECTION A -A SCALE: 1 1/2" = V-0" 1-3 ADJACENT NAILS IN A ROW ARE TO BE DRIVEN FROM OPPOSITE SIDES, TYP FOR 2x4 STUDS, PROVIDE SINGLE ROW OF NAILS STAGGERED EA SIDE WITH 1 1/2" EDGE DISTANCE. FOR 2x6 STUDS, PROVIDE (2) ROWS OF NAILS SPACED AT 2 1/2" W/ 1 1/2" EDGE DISTANCE 9" OC MAX SPACING BETWEEN ADJACENT NAILS IN A ROW 0.131"0 x 3" NAILS, TYP (5) STUDS MAX TO BE USED FOR BUILT-UP COLUMNS TYPICAL BUILT-UP STUD COLUMN DETAIL SCALE: 1" = V-0" (2) ROWS OF (8) 0.131"o x 3" 2 1/4" END NAILS @ 3" OC EA SIDE OF DISTANCE, TYP SPLICE AND (2) @ 9" OC ELSEWHERE W/ 1 1/2" EDGE DISTANCE 3" OC SPACING TOP CHORD / SPLICE J AT LOCATIONS WHERE IT IS NOT POSSIBLE BOTTOM TO INSTALL THE SPECIFIED 0.131"o CHORD SPLICE NAILS, THE CONTRACTOR SHALL SPLICE INSTALL SIMPSON CS20 STRAPS EA SIDE OF WALL AT SPLICE. INSTALL EA STRAP W/ (12) 10d AT EA END. WHERE BOTH PLATES ARE CUT, INSTALL CS20 STRAPS AT EA PLATE AND EA SIDE OF THE WALL. 6'-0" MIN BETWEEN SPLICES SPLICES TO OCCUR AT CENTER OF VERTICAL STUDS 0 TOP CHORD SPLICE BOTTOM CHORD SPLICE TYPIC���OP PLATE SPLICE DETAIL SCALE: 1" NOTE: SUPPORTS AT SOLID _ POSTS SIMLu a STUD WALL o SHEATHING & NAILING U_ STUD PER PLAN & SHEAR WALL WALL SCHEDULE OR BEAM PER SIMPSON LTP4 C A35 FRAMII` ANCHOR EACH SI[ OF BEA SOLID OR MULT STUD COLUMN PER P,_ BEAM WIDTH, MIN UNO PARALLEL TO STUD WALL TYPICAL FLUSH BEAM SUPPORT DETAILS SCALE: 1" = V-0" SOLID STUD COLU..,,. , PERPENDICULAR TO STUD WALL STRUCTURAL NOTES EXIST RIM SIMPSON A35 PER SHEAR WALL SCHEDULE (AT SHEAR WALLS) SIMPSON A35 (ONLY REQUIRED AT EXTERIOR HEADERS GREATER THAN 6' SPAN) (6) 0.131"0 x 3" NAILS - TYPICAL STUDS NAILING PER TYP BUILT-UP STUD COLUMN DETAIL AT HOLDOWNS: PROVIDE FULL HT HOLDOWN CHORDS PER HD SCHED OTHERWISE: (1) 2x FULL HT ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE TYP DOUBLE TOP PLATE BEAM OR HEADER PER PLAN AND NOTES CRIPPLE STUDS PER PLAN AND COLUMN SCHEDULE OR STRUCTURAL NOTES TYPICAL HEADER DETAIL SCALE: 1" = V-0" SILL PLATE NAILING PER PLAN & SHEAR WALL SCHEDULE 101..10y:1WeT1::11►10 SHEATHING & NAILING PER PLAN & SHEAR WALL SCHEDULE OR STRUCTURAL NOTES EXIST RIM SIMPSON A35 PER SHEAR WALL SCHEDULE (AT SHEAR WALLS) II EXIST CONC I I EXIST WOOD JOISTS WALL u TITEN HD PER PLAN & SHEAR NOTE: WALL SCHED NON -SHEAR WALL NAILING SHALL BE PER IBC TABLE 2304.9 A. JOIST PERPENDICULAR TO WALL Q TYPICAL STUD WALL FRAMING DETAIL SCALE: 1" = V-0" SILL PLATE NAILING PER PLAN & SHEAR WALL SCHEDULE WNR1961 1: FeA::11►10 B. JOIST PARALLEL TO WALL EXIST WOOD JOISTS O GI ENGINEERING, 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 04/02/21 J H H Z 2 O_ m F CL N _ F___ O 2i (n ct� W w 0 a LLI Q O E) ---- Itt Y Q DESIGN: RMK DRAWN: JCP CHECK: XXX JOB NO: 20436.10 DATE: 04/02/21 RECEIVED Jul 27 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-1002 J La 0 ( cO Ld La U W I N (7 c Z w O (n Q Q Z � 0 V) m O m o Z 0 :2 M O O 00 0 Y 'r- Ld SHEET: S501 ENGINEERING, 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 EXIST RAFTER (2) SIMPSON A34 EA 2x VERT, AT TOP EXIST ROOF & CEILING FRAMING EXIST FULL DEPTH BLI<G EXIST ROOF (VERIFY OR PROVIDE) SHEATHING 5 M. 2x4 VERT INSTALLED SIMPSON EA ROOF RAFTER wqg✓�oF A34 EA VERT BEAM PER PLAN 45901 1ti �s Lti ONAL EXIST CEILING SIMPSON LUS SERIES PROVIDE BOUNDARY"I \,- 2x4 BLKG W/ SILL PL JOIST HANGER NAILING AT TOP PLATE PER PLAN &SHEAR NAILING PER SHEAR 04/02/21 WALL SCHEDULE WALL SCHED (OR A35 PER SW SCHED) SHEATHING AND NAILING PER PLAN AND SHEAR EXIST STUD WALL SI 4PSON CS18 EA CEILING JOIST W/ WALL SCHEDULE 11" END LENGTHS & (9) 10d EA END (FLUSH CEILING BEAM TYPICAL RAFTER SUPPORT DETAIL 1 SCALE: 1" = V-0" SCALE: 1" = 1'-0" J z 2 O m CL N U (n W w 0 d r-I W Q O C:) ---- Itt Y Q DESIGN: RMK DRAWN: JCP CHECK: XXX JOB NO: 20436.10 DATE: 04/02/21 RECEIVED Jul 27 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-1002 J W 0 O Ld Q w W U O 0 W = N 000 w O Z Z La Q as � 0 V) m m o O z LL. :2 M O O c)oo O Y W SHEET: S601