2024-09-10-Kleven Residence-TOR3630125OTTO ROSENAU & ASSOCIATES, INC.
Geotechnical Engineering, Construction Inspection & Materials Testing
CONSTRUCTION INSPECTION REPORT
Report Number: TOR3630125
Project Name: Kleven Residence Job Number: 24-0590
Project Address: 734 Fir Street, Edmonds Permit: BLD2023-0098
Client Name: Wall Tek
Steel Decking
❑
Structural Steel Fabrication
❑
Structural Steel Erection
❑
Inspections Performed
Other (specify): Torque Verification
Inspector: Joshua Gray (WABO#: SI 02288) Inspection Date: September 10, 2024
Remarks
ORA representative on site to verify the torque of the (8) hold downs at the following locations:
1) 5/8" (Quantity 6)
• (1) Main level, South side of the house underneath Kitchen entry
• (4) Basement level, along West wall
• (1) Garage, NW corner
2) 7/8" (Quantity 2)
• Level 2, bedroom# 1
• Main level, SE corner (exterior)
Torqued with ORA Torque Wrench #6066, 5/8" to 60 ft-Ibs. Max and 7/8" to 125 ft-Ibs. Max.
This report follows ORA PAA report# 446027 dated 9/9/2024. All work inspected was completed per the approved
construction documents and ESR# 4057.
Conforms
Copies e A,
0 Client ❑Engineer ❑Others Technical Responsibility: � ►M.f
❑ Owner ❑ Contractor
❑ Architect ❑.I Building Dept Jeff Rabe, Project Manager