REVIEWED BLD2023-1212+Structural_Analysis_or_Calculations+9.28.2023_2.14.25_PM+38108421 of 32 REVIEWED BY CITY OF EDMONDS LONGITUDE ONE TWENTYO ENGINEERING & DESIGN calculation Package for Retaining Wall Stabilization STRUCTURAL ENGINEER L120 ENGINEERING & DESIGN 1315091s'PLNE KIRKLAND, WA 98034-5901 7300176th St SW Edmonds, WA 98026 Project no: S230721-1XR July 31s l 2023 .'•Ft.THU F . R ■ r •cc r�, vim• '. S�QNAL EN.' Prepared for: R&R Foundation Specialist 3409 McDougall Ave, suite 204 Everett, WA 98201 P: 425.760.5077 CONTACT: MANS THURRELL, PE EMAIL: MTHURFJELL@L120ENGINEERING.COM PHONE: (425) 636-3313 RECEIVED Oct 03 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2023-1212 (425) 636-3313 L120Engineering.com i I I I I I ` I I I I I I ffi- I i i i I I I I wIa I I I I I i I I I i I i I � 6nE RiW �R I L': _,_FBOPEmYIIMi Inns W PARCEL VIEW N.T.S. %LE 9PACINI 9 LOAD REOUMYENT9 TABLE MIN O.C.9PA" N MIN VERTICALCAPACITY M PROOF TE9TNG LOADM PLEA PILE TYPE BTWN END ALLOWABLE LOADING 200% MIN VERTK:AL CAPAC_(MIN LOCATIDN %LES OFFSET ULTIMATECAPAC 1-0 TIEBACK 6'-0' 2-0' 50 100 kP PERPLAN NOTES: a. MINIMUM AND MAXIMUM INSTALLATION TORQUE FOR HELICAL ASSEMBLIES SHALL BE SPECIFIED BY THE PILE MANUFACTURER. THE MINIMUM INSTALLATION TORQUE SHALL BE HIGH ENOUGH TO ACHIEVE THE REQUIRED BEARING CAPACITY LOADING, INCLUDING SAFETY FACTOR NO LESS THAN 2. THE MAXIMUM INSTALLATION TORQUE SHALL NOT EXCEED THE ALLOWABLETORSIONAL CAPACITY OF THE PILE SHAFTS OR ANY PART OF THE PILE ASSEMBLY. MAXIMUM INSTALLATION TORQUE RATING OF 6,980M.BS FORA 1.12INCH DIAMETER HELICAL PILE PER ESR3T50. b. HELICPL ASSEMBLIES AS MANUFACTURED BY IDEAL MANUFACTURING, INC., IN ACCORDANCE WITH ESR3T50. c PILE OR ANCHOR LOADS NOT TO EXCEED MAXIMUM CAPACITY AS DETERMINED BY THE MANUFACTURER FOR MY PART OF THEASSEMBLY. tl. MAXIMUM ONLENTER SPACING LISTED FOR TYPICAL PILE INSTALLATION UNLESS NOTED OTHERWISE ON PLAN. STAIRS 176th ST SW (E) RESIDENCE 7300176ih Sf SW Edmonds, WA 9602fi PROPERTY LINE ------------------------------ PARCEL NO. 00513600000902 LEGAL DESCRIPTION MEADOWDALE SOUND VIEW TRACTS BLK 000 D-02 - E 75 FT OF TR 9 AS MEAS ON N LN OWNER NAME & ADDRESS JOHNSTONE SEAN & SCHELL JEANNINE 7300170 S/ SW Edmonds, WA 98026 NOTE: THE PROJECT WILL NOT RESULT IN CHANGING OF SITE TOPOGRAPHY OR EXISTING DEVELOPED AREAS. NOTE: L120'S SCOPE IS LIMITED TO THE PERIMETER SUPPORT SYSTEMICONTINUOUS FOOTINGS. THE INTERIOR CRAWL SPACE SUPPORTED SYSTEM FOR THE FIRST FLOOR SHALL BE INSTALLED PER R&R. SITE PLAN NOTES 1. VERIFY EXISTING STRUCTURES AND ALL DIMENSIONS ON SITE. 2. FOUNDATION DIMENSIONS ARETO OUTSIDE FACE OF CONCRETE STEM WALL PER R&R FOUNDATION SPECIALIST (R&R) LEVEL SURVEY, 3. REFER TO STRUCTURAL CALCULATIONS PACKAGE BY L120 DATED JULY 31, 2023, FOR ADDITIONAL INFORMATION, SPECIFICATIONS, AND REQUIREMENTS. A. LEVEL SURVEY PER R&R PROPOSAL DATED JULY 5, 423. REFER TO STIR UCOU GALCULADONSPACKAGEFORMODIFICATIONSAND ADDITIONAL REQUIREMENTS FOR LEVEL SURVEY. 5. PARCEL DIMENSIONS APPROXIMATED BY SNOHOMISH COUNTY ASSESSOR GIS MAPPING TOOLS &TAXSIFTER INCLUDING THE SELECTED PARCEL. PROPERTYDIMENSIONS PRE APPROXIMATE FOR REPRESENTATIVE PURPOSES ONLY. NOT TO SCALE. NOT TO BE USED FOR LEGAL PURPOSES 6. SITE FEATURES AND SOME EXISTING STRUCTURES ON ADJACENT PARCELS NOT SHOWN FOR CLARITY. ❑ EXISTING RESIDENCE STRUCTURE EXISTING ADJACENT STRUCTURE - AREA OF PROPOSED WORK --- PROPERTY LINE • APPROXIMATE DIMENSION TIEBACK 1 C10X15.3 CHANNEL JI I It NLHIN PRO.ECT NAME 7300 176th St SW Edmonds, WA 98026 PRO.ECT NJMBER S230721-IXR Dwv„ r, Er - PAM CIECKEH BY-MRT SHEET DA-e- 07/31/2023 SCALE 3 of 32 PROJECT LONGITUDE SUBJECT ONE TWENTYO ENGINEERING & DESIGN BY PAM PROJECT NO. SHEET NO. S230721 7300 176th St SW, Edmonds, WA 98116 Retainina Wall Stabilization DATE 07/31 /23 Scope/Objective: To determine the required pile spacing and geometry to stabilize and lift (where required) the existing structural foundation. These findings have been based upon the calculated strength of the existing foundation system and the current vertical loading from the existing structure above (based on as -built assessments). The R&R Foundation Specialists' (R&R) proposed pile layout can be found in the following pages with structural recommendations based upon the findings of L120 Engineering & Design. Note that cosmetic damages to rigid wall coverings/members and siding are expected during a foundation lift. Such cosmetic damages/cracks are to be repaired by others following the completion of the foundation stabilization and lifting and are not included in the structural scope presented here. It should be further noted that L120's scope is limited to the perimeter support systems/continuous footings. The interior crawl -space support system for the first floor shall be installed per R&R. This could include the use of some or all of the following: longer support posts, adjustable post -base hardware, and/or the addition of taller wood support members. Settlement in these interior support areas shall be monitored and further adjustments shall be made if necessary. Structural Summary: - The foundation of the retaining wall consists of continuous cast -in -place concrete stem wall and concrete strip footings. At 2/3 of retained soil height, tiebacks are to be spaced at a distance no larger than 6-0" on -center with the addition of C10x15.3 channels installed horizontally, spanning tieback -to -tieback at the locations indicated on the attached level survey. Tiebacks and supplemental channel to be installed in accordance with SSK-01 & SSK-02. - End tiebacks are to be placed as close to corners as possible and shall not exceed a max corner offset distance of 2'-0". - The following load values represent the maximum expected tieback loads for the indicated spacing. R&R to provide tieback and equipment assemblies with capacities equal to or greater than the indicated load values. Allowable Load Capacity Requirement: Tieback Tension Load @ 6'-0" o.c. ............ 5 kip minimum vertical capacity (allowable load) Note: Refer to the attached General Notes for additional requirements. - As determined by R&R, the site appears to have no lateral (horizontal) displacements or concerns. As such, the analysis and recommendations presented in this report have been strictly limited to vertical stabilization/jacking. If lateral movement is observed or expected additional structural analysis will be required. - Structural recommendations contained in this package are based on site photographs dated July 5, 2023, provided by R&R. To the knowledge of L120, a geotechnical investigation was not performed on this site. Consequently, all structural recommendations assume adequate soil conditions to obtain the required pile capacities. Please inform L120 of site -specific conditions that were unconsidered by, may conflict with, or otherwise compromise the recommendations contained within this package, including, but not limited to, water drainage, slope stability, existing structural damage, or existing subsurface obstructions. In this instance, the structural assumptions, recommendations, and scope for this project will need to be revisited to consider and address the new findings Refer to the following pages for pile and connection specifications. L120 ENGINEERING & DESIGN 4 of 32 GENERAL NOTES HELICAL PILES & TIEBACKS 1. HELICAL PILES & TIEBACKS SHALL BE DESIGNED AND MANUFACTURED IN ACCORDANCE WITH THE 2018 INTERNATIONAL BUILDING CODE (IBC). 2. HELICAL PILES & TIEBACKS SHALL BE DESIGNED AND MANUFACTURED BY IDEAL MANUFACTURING, INC., AND SHALL BE IN ACCORDANCE WITH ESR-3750. 3. ALL MATERIAL PROPERTIES OF HELICAL PILE COMPONENTS SHALL BE IN ACCORDANCE WITH ESR-3750. 4. CORROSION PROTECTION OF ALL COMPONENTS SHALL COMPLY WITH THE ICC-ES ACCEPTANCE CRITERIA FOR CORROSION PROTECTION OF STEEL FOUNDATION SYSTEMS USING POLYMER (EAA) COATINGS (AC228). 5. ALL HELICAL FOUNDATION COMPONENTS SHALL BE GALVANICALLY ISOLATED FROM CONCRETE REINFORCING STEEL, BUILDING STRUCTURAL STEEL, OR ANY OTHER METAL BUILDING COMPONENTS PER AC358 SECTION 3.9. 6. THE SHAFT SHALL BE DESIGNED AND FABRICATED TO SUPPORT THE SPECIFIED DESIGN LOADS. 7. ONLY MANUFACTURER -APPROVED CONNECTORS, ADAPTORS, AND ACCESSORIES MAY BE USED. 8. HELICAL PILES SHALL BE INSTALLED VERTICALLY INTO THE GROUND WITH AN ALLOWABLE ANGLE OF INCLINATION OF +/- 1 DEGREE FROM VERTICAL PER SECTION 4.2.1 OF ESR-3750. 9. MONITOR AND RECORD DEPTH OF PENETRATION. PROVIDE TORQUE MONITORING DEVICE AS PART OF THE INSTALLING UNIT. MONITOR AND RECORD TORQUE APPLIED DURING THE INSTALLATION OF EACH PILE AT SPECIFIC DEPTHS. 10. HELICAL PILES & TIEBACKS SHALL BE INSTALLED TO THE MINIMUM TORQUE VALUE REQUIRED TO PROVIDE THE MINIMUM REQUIRED LOAD CAPACITIES INDICATED ON PLAN INCLUDING A FACTOR OF SAFETY NO LESS THAN TWO (2). THE MAXIMUM INSTALLATION TORQUE SHALL NOT EXCEED THE ALLOWABLE TORSIONAL CAPACITY OF ANY INDIVIDUAL COMPONENT OF THE PILE ASSEMBLY. 11. ALL BRACKETS AND HELICAL PILE & TIEBACK ASSEMBLY COMPONENTS SHALL HAVE ADEQUATE CAPACITY TO ACHIEVE THE MINIMUM REQUIRED BEARING CAPACITY INCLUDING A FACTOR OF SAFETY NO LESS THAN TWO (2). 12. REPAIR BRACKETS MUST BE CONCENTRICALLY LOADED AND THE BRACKET PLATE MUST BE FULLY ENGAGED WITH BOTTOM OF CONCRETE FOUNDATION. 13. ALL HELICAL PILE & TIEBACK ASSEMBLY COMPONENTS MUST HAVE ADEQUATE STRENGTH TO DEVELOP THE TORQUE REQUIRED FOR INSTALLATION AND ALL INDUCED STRESSES. 14. THE PILE & TIEBACK QUANTITY, LAYOUT, AND SPACING INDICATED ON PLAN SHALL NOT BE CHANGED WITHOUT WRITTEN APPROVAL FROM THE ENGINEER -OF -RECORD PRIOR TO INSTALLATION. 15. CONTINUOUS SPECIAL INSPECTION IN ACCORDANCE WITH 2O18 AND 2012 IBC SECTION 1705.9 MUST BE PROVIDED FOR THE INSTALLATION OF THE HELICAL PILES & TIEBACKS. ITEMS TO BE RECORDED AND CONFIRMED BY THE SPECIAL INSPECTOR MUST INCLUDE THE FOLLOWING: A. PRODUCT MANUFACTURER B. MANUFACTURER'S CERTIFICATION OF THE INSTALLERS C. PRODUCT TYPE AND CONFIGURATIONS FOR HELICAL PILE LEAD SHAFT SECTIONS, EXTENSIONS, BRACKETS, BOLTS, THREADED RODS, NUTS, WASHERS, AND TORQUES AS SPECIFIED IN THIS REPORT AND THE CONSTRUCTION DOCUMENTS D. INSTALLATION PROCEDURES FOR THE HELICAL PILE SHAFT, INSTALLATION EQUIPMENT USED, AND THE IDEAL FOUNDATION SYSTEMS INSTALLATION INSTRUCTIONS E. ANTICIPATED AND ACTUAL PILING DEPTH F. REQUIRED TARGET INSTALLATION TORQUE OF PILES AND MINIMUM DEPTH OF INSTALLATION G. INCLINATION AND POSITION OF PILES, TOP OF PILE EXTENSION IN FULL CONTACT WITH BRACKET, TIGHTNESS OF ALL BOLTS AND EVIDENCE THAT THE PILE FOUNDATION SYSTEMS ARE INSTALLED BY AN APPROVED IDEAL FOUNDATION SYSTEMS INSTALLER. 16. PILES & TIEBACKS IMPROPERLY INSTALLED BECAUSE OF MISLOCATION, MISALIGNMENT, OR FAILURE TO MEET OTHER SPECIFIED DESIGN/INSTALLATION CRITERIA ARE NOT ACCEPTABLE. ABANDON REJECTED PILES AND INSTALL ADDITIONAL PILES AS REQUIRED. HELICAL PILE & TIEBACKS PROOF TESTING THE CAPACITY OF THE INSTALLED PILES SHALL BE VERIFIED BY FIELD TESTING OF A MINIMUM THREE (3) PERCENT OF PILES UP TO FIVE (5) PILES MAXIMUM (ONE (1) MINIMUM) IN ACCORDANCE WITH THE PROCEDURE OUTLINED IN ASTM D1143 AND/OR THE 2018 INTERNATIONAL BUILDING CODE (IBC). THE MAXIMUM TEST LOAD SHALL BE TWO -HUNDRED (200) PERCENT OF THE SPECIFIED DESIGN LOAD. 5 of 32 GENERAL NOTES STRUCTURAL STEEL 1. REFERENCE STANDARDS: DESIGN, FABRICATION AND ERECTION ARE TO BE IN ACCORDANCE WITH THE LATEST EDITION OF THE AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES". 2. MATERIALS: BOLTS - ASTM A307, UNLESS OTHERWISE NOTED ALL OTHER STEEL - ASTM A36 (Fy = 36,000 PSI) 3. ALL WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS AND CONFORM TO AWS CODES D1.1 AND D1.3. WELDS NOT SPECIFIED ARE TO BE 1/4" CONTINUOUS FILLET MINIMUM. USE DRY E70 ELECTRODES. WHERE ON -SITE WELDING IS REQUIRED, SPECIAL INSPECTION IN ACCORDANCE WITH 2O18 AND 2012 IBC SECTION 1705.2 IS ALSO REQUIRED. CONCRETE 1. REFERENCE STANDARDS: ACI 301, ACI 318, IBC. 2. MINIMUM CONCRETE STRENGTH (28 DAYS): FOOTINGS AND STEM WALLS..................................................3,000 PSI - 5 SACK MIX BASEMENT FOUNDATION RETAINING WALLS .......................3,000 PSI - 5 SACK MIX SLAB-ON-GRADE........................................................................2,500 PSI - 5 SACK MIX SLAB -ON -GRADE... EXPOSED WEATHERING SURFACES ...... 3,000 PSI AIR -ENTRAINMENT 2.5% TO 5.5% FOR EXPOSED CONCRETE 3. MIXING: COMPLY WITH ACI 301. DO NOT EXCEED THE AMOUNT OF WATER SPECIFIED IN THE APPROVED MIX. PROPORTIONS OF AGGREGATE TO CEMENT SHALL BE SUCH AS TO PRODUCE A DENSE, WORKABLE MIX WHICH CAN BE PLACED WITHOUT SEGREGATION OR EXCESS FREE SURFACE WATER. 4. PLACING: COMPLY WITH ACI 301. PROVIDE A 3/4 INCH CHAMFER AT ALL EXPOSED CONCRETE EDGES, UNLESS INDICATED OTHERWISE ON ARCHITECTURAL DRAWINGS. 5. SLUMP: 4 INCHES PLUS OR MINUS 1 INCH. DO NOT ADD WATER TO MIX TO INCREASE SLUMP. GREATER SLUMP, ACCELERATED SET, OR HIGH EARLY STRENGTH MAY BE ACHIEVED BY USING APPROVED ADMIXTURES. 6. CURING: COMPLY WITH ACI 301. KEEP CONCRETE MOIST FOR SEVEN DAYS MINIMUM. 7. JOINTING: PROVIDE ADEQUATE JOINTING TO MINIMIZE EFFECTS OF VOLUME CHANGE. JOINTS SHOWN MAY BE ADJUSTED AT CONTRACTOR'S OPTION WITH PRIOR APPROVAL FROM ENGINEER. 8. WEATHER EXTREMES: COMPLY WITH ACI 305R FOR HOT WEATHER. COMPLY WITH ACI-306R FOR COLD WEATHER. 9. WATER/CEMENT RATIO SHALL NOT EXCEED 0.50 (BY WEIGHT), TYPICAL. 10. ALL SPECIFIED CONCRETE ANCHORS SHALL BE SIMPSON STRONG -TIE, HILTI, OR EQUIVALENT. SPECIAL INSPECTIONS REQUIRED. ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH MINIMUM EMBEDMENT, SPACING, EDGE DISTANCE, AND REQUIREMENTS PER MANUFACTURER. 6 of 32 LONGITUDE ONE TWENTY° ENGINEERING & DESIGN PROJECT PROJECT NO. SHEET NO. S230721 7300 176th St SW, Edmonds, WA 98116 SUBJECT Tieback Torque Chart By PAM DATE 07/31 /23 Ideal Foundation Systems 1-112" 0 Helical Tieback - Soil Tension Capacity per ESR-3750 DIGGA 6K Drive Head Pressure (psi) Torque, T (ft*Ibs) Torque Correlation Factor, Kt Tension (ft i) Ultimate Axial Tensile Capacity, Pa = Kt*T (kips) Allowable Axial Tensile Capacity, Pa = 0.5*Pa (kips) 500 1,554 8.5 13.2 6.6 600 1,865 8.5 15.9 7.9 700 2,176 8.5 18.5 9.2 800 2,486 8.5 21.1 10.6 900 2,797 8.5 23.8 11.9 1000 3,108 8.5 26.4 13.2 1100 3,419 8.5 29.1 14.5 1200 3,730 8.5 31.7 15.9 1300 4,040 8.5 34.3 17.2 1400 4,351 8.5 37.0 18.5 1500 4,662 8.5 39.6 19.8 1600 4,973 8.5 42.3 21.1 1700 5,284 8.5 44.9 22.5 1800 5,594 8.5 47.6 23.8 1900 5,905 8.5 50.2 25.1 2000 6,216 1 8.5 52.8 26.4 2100 6,527 1 9.5 62.0 31.0 i.) DIGGA 6K Drive Head differential pressure display to torque output has been pulled from the attached conversion charts provided by DIGGA. ii.) Per Table 5C of ESR-3750, the maximum installation torque rating of a 1-1/2" 0 helical pile is 6,980 ft*Ibs. This maximum installation torque limitation may differ from that listed by Ideal Manufacturing, Inc. Final installation torque shall not exceed the lesser of these limiting values. iii.) Piles shall reach a torque that correlates with an allowable capacity that meets or exceeds the maximum allowable load demand as listed in the structural package, but shall not exceed the maximum allowable capacity for any part of the pile assembly. iv.) Refer to ESR-3750 and Ideal Manufacturing, Inc. documents for additional information and requirements. v.) Definitions per ESR-3750: T = Final Installation torque in ft*Ibs; the last torque reading taken during pile installation, using, for example, the torque reading instruments connected to the installation equipment. Kt = Torque correlation factor per ESR-3750 Pa = Ultimate axial tensile capacity (in kips) of helical pile Pa = Allowable axial tensile capacity (in kips) of helical pile vi.) For torque readings between those listed, use the following equation to determine the allowable capacity:P, = (T*Kt)/2 vii.) 1 kip = 1,000 Ibs L120 ENGINEERING & DESIGN 7 of 32 PROJECT LONGITUDE SUBJECT ONE TWENTY° ENGINEERING & DESIGN BY PAM PROJECT NO. SHEET NO. S230721 7300 176th St SW, Edmonds, WA 98116 Tieback Torque Chart DATE 07/31 /23 Ideal Foundation Systems 1-112"0 Helical Tieback - Soil Tension Capacity per ESR-3750 DIGGA 10K Drive Head Pressure (psi) Torque, T (ft•lbs) Torque Correlation Factor, K, Tension (ft ' ) Ultimate Axial Tensile Capacity, P. = &-T (kips) 14.8 Allowable Axial Tensile Capacity, P. = 05•P„ (kips) 7.4 500 1,740 8.5 600 2,098 8.5 8.5 17.7 8.9 700 2,436 20.7 10.4 80C 2,784 8.5 23.7 11.8 900 3,132 8.5 26.6 13.3 1000 3,490 8.5 29.6 14.8 1100 3,828 8.5 32.5 16.3 1200 4,176 8.5 35.5 17.7 1300 4,524 8.5 38.5 19.2 1400 4,872 8.5 41.4 20.7 1500 5,220 8.5 44.4 22.2 1600 5,569 8.5 47.3 23.7 1700 5,916 8.5 50.3 25.1 1800 6,264 8.5 53.2 26.6 1900 6,612 8.5 56.2 28.1 2000 6,980 8.5 59.3 29.7 i.) DIGGA 10K Drive Head differential pressure display to torque output has been pulled from the attached conversion charts provided by DIGGA. ii.) Per Table 5C of ESR-3750, the maximum installation torque rating of a 1-1/2" 0 helical pile is 6,980 ft•lbs. This maximum installation torque limitation may differ from that listed by Ideal Manufacturing, Inc. Final installation torque shall not exceed the lesser of these limiting values. iii.) Piles shall reach a torque that correlates with an allowable capacity that meets or exceeds the maximum allowable load demand as listed in the structural package, but shall not exceed the maximum allowable capacity for any part of the pile assembly. iv.) Refer to ESR-3750 and Ideal Manufacturing, Inc. documents for additional information and requirements. v.) Definitions per ESR-3750: T = Final Installation torque in ft•lbs; the last torque reading taken during pile installation, using, for example, the torque reading instruments connected to the installation equipment. K, = Torque correlation factor per ESR-3750 P„= Ultimate axial tensile capacity (in kips) of helical pile P.=Allowable axial tensile capacity (in kips) of helical pile vi.) For torque readings between those listed, use the following equation to determine the allowable capacity. P. = (T•Kt)/2 vii.) 1 kip =1,000 Ibs L120 ENGINEERING & DESIGN 8 of 32 Wednesday, July 5, 2023 SCOPE OF WORK R&R CREW RESPONSIBILITIES & DETAILS: - Crew will install (4) Tie Backs to stabilize and straighten retaining wall. - Crew will install 10" Steel Channel on retaining wall. - Crew to core drill (4) holes. - Crew will install 6" Carbon Fiber on crack. - Crew will install 1' Carbon Fiber on crack. HOMEOWNER RESPONSIBILITIES: - Have work area excavated, backfill once project is complete. ADDITIONAL INFO: FOUNDATION - R&R will handle necessary permit and engineering coordination. - 25% deposit, 25% upon issue of permit and final 50% upon completion of project. - Permit cost is not included and will be billed on second 25% deposit payment. - Homeowner understands permit process may require the hiring of a WABO certified special inspector billed at additional fees depending on municipality. - Responsible party representative must be onsite during crew arrival and project completion. - Permitting/scheduling times may vary beyond R&R control. Material Clause: - Homeowner will be notified if any unexpected items arise and no additional work will be completed without homeowner approval. 9 of 32 Wednesday, July 5, 2023 ELEVATION MAP L120 is in concurrence with the tieback anchor layout recommended by R&R provided that the proposed layout is followed as marked and that a maximum tieback anchor spacing of W-0"o.c. is achieved. Supplemental C10x15.3 channels are to be installed horizontally spanning between each tieback anchor. Tiebacks and channel to be installed in accordance with SSK-01 and SSK-02. NOTES: 1. It is acceptable to install tieback anchors at the spacing shown with ± 0'-6" tolerance to allow for unexpected obstructions encountered during pile installation provided that no two adjacent spans exceed the spacing limitation of 6-0"o.c. 2. End tiebacks are to be placed as close to corners as possible and shall not exceed a maximum corner distance of 2'-0" as marked. 3. Supplemental steel to be anchored to concrete with 5/8" diam Simpson Titen HD screw anchors @ 24"oc with a 4" minimum embedment. Refer to attached SSK-02. ME NOON■ ■■■■■■■■■■ NOON ■■■■■■■■■■ NOON • ■■■■■■■■■■■ ■■■ r• • ,S �;�� ■■■■■■■■� ■■■ C■■■■■■■■E ■■■ ® ■■■■■■■■■ ■■■■ C■■■■■■■■■■ ■■■■ .........■■ NONE • ■■■■■■■E■ ■NMEN ■■ ■■■■■■ NONE■■■■■ ■■■■■■■■■■■■■■■■■■■■■■■■■ ■■■■■■ ■■■■■■■■■ ■■■■■■■■■■■■■■■■■■■■■■■■N ■■■■■N ■■■■■■■■■ ■■■■■■■■■■■■■■■■■■■■■■■■■ ■■■■■■ ■■■■■■■■■ ■■■■■■■■■■■■■■■■■■■■■■■■■ ■■■■■■ ■■■■■■■■■ ■■■■■■■■■■■■■■■■■■■■■■■■■ ■■■■■■ ■■■■■■■■■ iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii AA ='Crack!iiiii ■■■■■■■■■■■■■■■ ■■■■■■■■■■■■■ ■■■ ■■■■■■■■■■■■■■■ ��ii1■■■■■■■■■■■■ ■■■ ■■■■■■■■■■■■■■ ■■■■■■■■■ °=Tie Back ■N■ ■■■■■■■■■■■■■I ■■■■■■■■■ E■■ ■■■■EIMMEME ��� ■■■■E■■■■ N■ ■■■■■�■■■■■ME ■■■■■■■■■• .-. ■■ ■■■■■!!■■■ 1�1•� ■■■■■■■■■ ■■■■■■ii■■■■ I�t •■■■■■■■■■■■■■■■■■■■■■■■ ■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■ ■■■■■■■■■■■■■ ■■■■■■■■■■■■■■■■■■■■■■■ ■■■■■■■■■■■■■ ► ■ ■■■■■■■■■■ ■■■■e== i ■■■■■■■■■ ■■■■■■■■■■■■ ■■■■■■■ ■■■■■■■■■■■■ I ■■■■■■■ ■■■■N■NENE■■■■ ■■■■■■■■■■■■■■ ,I ■■■■■■■ ■■■■■■Oiii■■■ ■■■■■■■■■■■■■■ ■■■■■■■ ■■■■■■■■■■■■■� ■■■■■■■■■■■■■■ ■■■■■■■ ■■■■■■■■■■■■■■ ■■■■■■■■■■■■■■ ■■■■■■■ ■■■■E ■■■■■ I ■■■■■■■■■■■■■■ ■■■■■■■■■ ■■■■■ ■■■■■ ■E■■■■■■■■■■■■ ■■■■■■■■ ■■■■■ ■■■ ENE No ■■■■■��■N ■■■■■■■■■■■■■■■■■■■■■■■■■■� ■■■■■ ■ ■■■■■■■■■■■■■■■■■■■■■■■■■■ NOTE: 1-120's scope is limited to the perimeter support systems/continuous footings of the primary structure. All stabilization and replacement efforts of exterior decks and deck supporting elements are outside of 1-120's contract and scope and are not addressed in this package. - L120 10 of 32 Wednesday, July 5, 2023 JOB PHOTOS ;4".. Tie Backs 1-4 will be installed here on West side of Crew will install V Carbon Fiber here on crack. 6" Carbon retaining wall. Crew will core drill (4) holes. Crew will Fiber will be installed on crack. install 10" Steel Channel here on retaining wall. Photographs provided by R&R Foundation Specialists. Note that analysis assumptions such as building geometry, tributary areas, and loading were determined through examination of these photographs and industry knowledge of standard construction practices. - L120 11 of 32 PROJECT LONGITUDE SUBJECT ONE TWENTY ENGINEERING & DESIGN BY PAM 8" MIN THICKNESS, CONTRACTOR TO VERIFY C TIE-BACK- (E) CONIC SLAB PROJECT NO. NO. S230721-1 XR SSK-01 7300 176th St SW, Edmonds, WA 98116 Retaining Wall Stabilization DATE 07/31 /23 (E) RETAINING WALL TIE -BACK ANCHOR DETAIL PER SSK-02 T/STEM WALL • IIII= =III= 1= Y III=IIII=IIIIt1 =11 & T/FIN GRADE ° ' d IIII=IIII=11 =IIII. = d • .III—IIII—III —IIII—I IIII=IIII IIII=IIII' �- - I— IIII=IIII=1 _ I d IIII=IIM=IIII=IIII= III=11111111=IIII=11 —IIII—IIII- _ ' 111=1111�1111=IIII=111 LOCATE PILE TO IIII=III =IIII=IIII=i Er)o ° III_ lilt-IIII-IIII_ ENSURE BYPASS —IIII=_IIII==11L_ OF FTG _ III=IIII=11 — 111=11u=11.� c) d IIII=_IIII=_IIII= IIII=_ . N a III=IIII=IIII=IIII= =IIII=, • IIII=IIII=IIII=111t=III — r, • III=IIII=IIII=1111�1111=IIII=� d IIII=IIII=IIII=IIII=IIII=1� T/CONC FTG = d d III— IIII—IIII —IIII— Ill—IIIIFIELD VERIFY . IIII=IIII=IIII=1111�1111�1�1= IIII=Iiil=IIII=rill=IIII=IIII 1=IIII=IIII=till=IIII= -IIII=IIII=IIII=IIII=IIII= d ° d ° d IIII=IIII=IIII=IIII=III —IIII—IIII—IIII—IIII—IIII d d I—IIII—IIII—IIII—IIII— II=IIII=IIII=IIII=IIII =IIII=IIII=IIII=IIII=IIII IIII=IIII=IIII=IIII III=IIII=IIII=IIII=IIII=IIII=IIII=IIII=IIII=IIII= IIII=IIII=IIII III=IIII=IIII=IIII=IIII=IIII=IIII=IIII=IIII=IIII=11 -"I�=IIII III=IIII=IIII=IIII=IIII=IIII=IIII= III'—����=IIII-IIII (E) CONTINUOUS —Ill=IIII=IIII=IIII=IIII=IIII=iil'— CONIC FOOTING NOTES: 1. CONTRACTOR TO VERIFY NOTED MINIMUM EXISTING FOUNDATION DIMENSIONS PRIOR TO INSTALLATION. ENGINEER -OF -RECORD TO BE NOTIFIED PRIOR TO INSTALLATION IF MINIMUMS NOT MET. 2. ALL ASSEMBLY COMPONENTS SHALL BE FULLY SEALED BY A CORROSION RESISTANT SYSTEM. THIS INCLUDES ALL FINAL CUT ENDS AND DRILLED HOLES. CORROSION PREVENTION COATING SYSTEM BY OTHERS. PRIME AND PAINT PER MFR OR GALVANIZATION PER ASTM 153/A123. L120 ENGINEERING & DESIGN LONGITUDE ONE TWENTY ENGINEERING & DESIGN 12 of 32 PROJECT NO. NO. S230721-1XR SSK-02 PROJECT 7300 176th St SW, Edmonds, WA 98116 SUBJECT Retaining Wall Stabilization BY PAM (E) FOUNDATION WALL, 8" MIN THICKNESS, FIELD VERIFY PL1 /2" x 6" x [a + 1 "] BEARING PLATE, CTRD AT CUTOUT S \ G 1"0 (MIN) THRD ROD W/STD NUT PL TO CHANNEL EA END OF PL 1/4 HORIZ C10x15.3 CHANNEL, CTRD AT TIE -BACK (PLACE CHANNEL SEGMENT JOINTS 2'-0" FROM TIE -BACK WHERE NECESSARY) DATE 07/31 /23 FILL CUTOUT WITH STRUCTURAL GROUT POST -INSTALLATION TIE -BACK ANCHOR ADAPTER AND WASHERS PER R&R HELICAL TIE -BACK ANCHOR PER R&R HORIZONTAL PLANE �=IIII=IIII— III= =IIII= 11=IIII=)INCLINATION ANGLE, MIN, 30° MAX �' d IIII—_IIII= I —III —II I=,. IIII=IIII= IIII=IIII=IIII-_ • •IIII=IIII=IIII=III _ —III=1 I=IIII= IIII=IIII=IIII=IIII= IIII=IIII_ ° d •IIII=IIII=IIII=IIII=IIII=1 =lII=IIII=IIII=IIII. d —IIII—IIII—IIII—IIII—IIII_IIII_ 11= III—IIII—I • •IIII=IIII=IIII=IIII=IIII=IIII=IIII=_ IIII=IIII= . ° =IIII=IIII=IIII=IIII=IIII=IIII=IIII=1 IIII=11. ° ' d 'IIII=IIII=IIII=IIII— "" =IIII=IIII=IIII= IIII= IIII=IIII=1' IIII=IIII=IIII= 11= ' • •IIII=IIII=IIII' ''I =IIII=IIII=' • =IIII=IIII= ' d IIII=IIII=IIII d —IIII—IIII— • •IIII=IIII=IIII= . ° =IIII=IIII=III' �' d 'IIII-IIII-IIII' ' d IIII=IIII=IIII=IIII=IIII_ d —IIII—IIII—IIII—IIII—III • •IIII=IIII=IIII=IIII=IIII= • =IIII=IIII=IIII=IIII=111 ' d IIII=IIII=IIII=IIII=IIII d —IIII—IIII—IIII—IIII • •IIII=IIII=IIII=IIII= I. • =IIII=IIII=IIII= I=1. ' d IIII=IIII=IIII— I=IIII= d —IIII—IIII— I—IIII—IIII'. • •IIII=IIII= 1=IIII=IIII— I • =IIII= I1=IIII=11 _IIII- d IIII—_—_IIII=1 —_IIII d — I—IIII= —IIII—, • =III= =IIII=IIII= ° •=IIII— 11=IIII=IIII=IIII ' d III III=IIII=IIII=IIII I. _IIII=IIII=IIII=IIII= 11- •IIII=IIII=IIII=IIII=1 IIII=IIII=IIII=III =1 NOTES: 1. C-CHANNEL TO BE ANCHORED TO CONCRETE WITH 5/8" DIAM SIMPSON TITEN HD SCREW ANCHORS @ 24"OC W/ MIN 4" EMBEDMENT 2. PLACE CHANEL SEGMENT JOINTS 2'-0" FROM TIEBACK WHERE NECESSARY 3. ALL ASSEMBLY COMPONENTS SHALL BE FULLY SEALED BY A CORROSION RESISTANT SYSTEM. THIS INCLUDES ALL FINAL CUT ENDS AND DRILLED HOLES. CORROSION PREVENTION COATING SYSTEM BY OTHERS. PRIME AND PAINT PER MFR OR GALVANIZATION PER ASTM 153/A123. L120 ENGINEERING & DESIGN ADAPTER 1 1 /2" TIE -BACK ADAPTER U-SHAPED FOR 7/8" OR 1" ROD BOTTOM VIEW PRIMARY WASHER 1/2' PRIMARY WASHER TOP VIEW 15/ lb" 3' I I 11/2 0 1 1/16' L1 7/8'_� END VIEW; 1/2'-7 F END VIEW; 1/2' SIDE VIEW L_3'--� SIDE VIEW: NOTES; 1, MIN YEILD OF STEEL U-SHAPE IS 46 KSI, 2, ULTIMATE CAPACITY OF U-SHAPED UNIT IS 60 KIPS. TO OBTAIN FULL CAPACITY, BOLT MUST BE TIGHTENED UNTIL WALLS OF ADAPTER ARE TIGHT TO THE HELICAL SHAFT. THREADED ROD MAY LIMIT CAPACITY OF THE ASSEMBLY. 3, (1) 3/4'-10 X 4 1/4' ASTM A325 GALVANIZED THRU BOLT W/ NUT, 4, PRIMARY WASHER W/ 1 1/16' CENTER HOLE FOR 1' ROD, 5, A SECONDARY WASHER IS INCLUDED AND MUST BE UTILIZED FOR 7/8' ROD, 6, ALL COMPONENTS GALVANIZED PER ASTM A153/ASTM A123, 7, THREADED ROD AND NUTS ARE NOT INCLUDED, THEY MAY BE PURCHASED SEPARATELY FROM IDEAL. SiDEAL Group PROPRIETARY AND CONFIDENTIAL THE INFORMATION CONTAINED IN THIS DRAWN IS THE SOLE PROPERTY GF IDEAL MANUFACTURING, INC. ANY REPRODUCTION IN PART OR AS A VHOLE WITHOUT WRITTEN PERMISSION OF IDEAL MANUFACTURING, INC IS PROHIBITED. -ING Na c. SQ150TBAUG RAVN BY �xs DAIEi �+%'+� PROJECT LONGITUDE SUBJECT ONE TWENTYO ENGINEERING & DESIGN Assumed Soil Parameters Soil Density, p = 135 pcf Friction Angle, cp = 30 deg At Rest ko = 1 - since At Rest ko = 0.50 Active ka = (1 - sin(p)/(1 + sin(p) Active ka = 0.33 PAM Surcharge, w = 40psf 14 of 32 PROJECT NO. SHEET NO. S230721-1 XR 7300 176th St SW, Edmonds, WA 98116 5'-0" Retaininq Wall Seismic 10H Force Calculations DATE 07/31 /23 Surcharge w*ka At Rest Max Press = H*p*ko At Rest Press = 5' *135pcf *0.5=340 psf Po = 0.5*340psf 5' = 850 plf Surcharge Pressure = w*ka = 40psf*0.33=13.2psf Psur =13.2 psf * 5' = 70 plf Eq Pressure = 10H = 10 * 5' = 50 psf Peq = 50psf * 5' = 250 plf Mbase = - RU.anch*3.33' + 850*1.67' + (70+250)*2.5' = 0 RU_anch = 667 plf Horiz Tanch =667 plf / cos(300) = 770 plf Tension Anchors 6'-0"oc = 5.0 k per anchor L120 ENGINEERING & DESIGN PROJECT LONGITUDE SUBJECT ONE TWENTY ENGINEERING & DESIGN BY PAM SUPPLEMENTAL STEEL ANALYSIS 15 of 32 PROJECT NO. NO. S230721-1 XR 7300 176th St SW, Edmonds, WA 98116 Retainina Wall Stabilization Assume concrete wall as single span 7ft beam btwn tiebacks: Mu= 1/8 * w * L2 = 1/8 * 667plf * 62 Mu (demand) = 3.1 k-ft Tension Required at Bottom Face (assuming unreinforced): Tu=Mu/(d12) = 3.1 k-ft/((8" 12)112) = 9.3k Cfool ('hnnnol Yield Strength, Fy= 36ksi Tensile Strength, Fu= 58ksi C10x15.3 Ag = 4.48 in2 Ae = Ag - 1"0.24" = 4.24in2 GSYPn=Fy*Ag GSY1)=1.67 GSY Pn/Q = (36ki * 4.48)11.67 = 95.6 k <= Controls NSR Pn = Fu * Ae NSR 4 = 2.0 NSR Pn/Q = (58ki * 4.24)/2.0 = 123.0 k Pn/Q > Tu OK Anchorage Simpson Strong -Tie, 5/8"dia Titen HD w/ 4" min embed Ult Shear Cap = 4.8 k / fastener 9.3 k / 4.8 k = 2 anchors over a 6' span Therefore, provide anchors at 24" oc. DATE 07/31 /23 w O H= 7FT Lf 8" wf 12" L120 ENGINEERING & DESIGN 16 of 32 PROJECT LONGITUDE SUBJECT ONE TWENTY° ENGINEERING & DESIGN BY PAM PROJECT NO. SHEET NO. S230721 7300 176th St SW, Edmonds, WA 98116 Retaining Wall Stabilization DATE 07/31 /23 Titen HD Shear Strength Design Data' IBC I - Nominal Embedment Depth h„ o,,, in 1 % 2'6 1 2'% 1 3'/4 3'h 1 4 4 1 5'h 5'h 1 6'/, Steel Strength in Shear Shear Resistance of Steel V. lb. 2,0120 4,460 7,455 10,000 16,840 #n ORY Strength Reduction Factor Steel Failure — Concrete Breakout Strwo in Shear' Outside Diameter da in. 0.25 0.375 0.500 0.625 0.750 Load Bearing Length of Anchor in Shear BB in. 1.19 1 1 94 1.77 1 2.40 2.35 1 2.99 2.97 1 4.24 422 1 4.86 Strength Reduction Factor — Concrete Breakout Failure 0.704 Concrete Pryout Strength in Shear Coefficient for Pryout Strength kvi lb. 1.0 2.0 Strength Reduction Factor — Concrete Pryout Failure 0,P 0.70' Steel Strength in Shear for Seismic Applications Shear Resistance for Seismic Loads Vq Ib 1,695 2,865 4,790 8,000 9,350 Strength Reduction Factor — Steel Failure — ORY + 1. The information presented in this table is to be used in ooni nction with supplementary reinforcement is not provided. For installations- where complying the design criteria of ACI 318-14 Chapter 17 and ACI 318-11 Appendix D, suppbmentary reinforcement can be verified, the 0,b factors described it except as modified below. ACI 318-14 17.3.3(c) or ACI 318-11 D.4.3(c) for Condition A are allowed. If the 2. The tabulated value of S,. appies when the bad combinations of Section 1605.2.1 of the IBC, ACI 318-14 Section 5.3 or ACI 318-11 Section 9.2 load combinations of ACI 318-11 Appendix C are used, the appropriate value of ipxb must be determined in accordance with ACI 318-11 D.4.4(c). are used. If the load combinations of ACI 318-11 Appendix C are used, 4. The tabulated value of sip apple; when both the load combinations of IBC the appropriate value of q., rrxst be determined in accordance with ACI 318 D.4.4. Section 16052. ACI 318-14 5-3 or ACI 318-11 Section 9.2 are used and the requirements of ACI 318-14 17.3.3(c) or ACI 318-11 D.4.3(c) for Condition 3. The tabulated value of Sb appfiev when both the load combinations of Section 16052.1 of the IBC, ACI 318-14 Section 5.3 or ACI 318-11 Section 92 are used and the requirements of ACI 318-14 17.3.3(c) or B are met. If the bad combinations of ACI 318-11 Appendix C are used, appropriate value of a,pmust be determined in accordance with ACI 318-11 Section D.4.4(c). ACI 318-11 D.4.3(c) for Condition B are met. Condition B applies where L120 ENGINEERING & DESIGN 17of32 RS=60OUNI !F'M �STRUCTURAL+!•� REINFORCEMENT SOLUTIONS CARBON FIBER FABRIC A unidirectional, high -strength, non -corrosive carbon fiber fabric designed to be field laminated with SRS-1000 Epoxy adhesive to create a carbon fiber -reinforced polymer (CFRP) composite for structural reinforcement and strengthening of concrete and masonry structures TYPICALFIBER PROPERTIES Tensile Strength - 711 ksi 4900 Mpa Tensile Modulus - 33.4 Msi 230 Gpa Elongation - 2.10% Density - .065 Ibs/inA3 1.80 g/cm"3 APPLICATIONS -External Reinforcement of Existing Structures -Increasing Load Capacity -Confinement -Shear Strengthening -Flexural Strengthening -Construction Error Corrections -Restoring Damaged/Deteriorated Structural Components -Bowed Wall Stabilization -Seismic Retrofit ADAVANTAGES •High Strength to Weight Ratio -High Modulus of Elasticity -Conforms to Structure -Easy Installation -Ambient Cure -Arrests Structure Movement -Low Aesthetic Impact •Non -Corrosive •Compatible with Most Finish Coatings TECHNICA ATA PROPERTY AVEULTIMATE DESIGNVALUE Tensile Strength Tensile Modulus Tensil % Enlongation Nominal Ply Thickness Tensile Strength per in. Width Tensile Strength per 6" Strap 195,000 psi 1,352 MPa 12 Msi 86 GPa 2% 0.039 in 7,624 Ibs/in 1.34 kN/mm 45,744 Ibs The information provided on this product data sheet represents average values which have been obtained through certified testing performed in a third -party laboratory. As part of the quality assurance program at SRS, these values are verified regularly to ensure that the products being sold are represented accurately by the values on this sheet. There may be some variation in test results due to epoxy mixing methods, degree of saturation, sample preparation, and curing conditions Per the recommendations in ACI-440.2, the ultimate tensile strengths provided represent the average test values minus three times the standard deviation which creates a 99.87% probability that the actual ultimate tensile properties will exceed the statistical based design values. 169,000 psi 1,169 Mpa 1% 6,709 Ibs/in 1.18kN/mm 40,254 Ibs TYPICALDATA Storage Conditions - Store in Dry Area at 40 deg - 95 deg F (4-35 C) Shelf Life Carbon -10 years/Epoxy - 2 Years in Unopened Container Color Carbon - Black/Epoxy - Semi Transparent Yellowish resin Primary Fiber Direction - 0° Unidirectional Areal Weight - 19.5 oz/SY 600 gsm 1-888-292-2592 www.structurairs.com Made in USA 18 of 32 STRUCTURAL ROMFORCEMEHT SOLUTIONS CARBON FIBER ROLL DESIGN KIT SIZES All applications containing SRS products must be designed Roll Size (Width x Length) by a registered design professional. The number of layers, •SRS-6000N1 6" x 75 LF (37.5 SF) dimensions, and detailing of SRS-6000NI shall be designed in accordance with ACI 440.2R or another recognized design •SRS-6000N 16" x 150 LF (75 SF) guideline/code in order to meet the design performance •SRS-6000N1 6" x 200 LF (100 SF) specified for the application. Contact Structural Reinforcement Solutions LLC for design and technical support. SURFACE PREPERATION The substrate in which the CFRP is being applied to must be clean and free of loose material or contaminants. In order to take advantage of the full bond strength properties of the epoxy, the substrate should be prepared per the requirements of the ICRI Technical Guideline No. 310-2R - 2013. The substrate should be prepared to a minimum concrete surface profile, CSP-3, as defined by ICRI 310-21R. Any voids, cracks, on variations in the surface of the concrete must be filled with an appropriate repair mortar or epoxy in order to provide a smooth surface to bond to. ACI 440.2R-08 provides additional details on the surface preparation requirements for CFRP systems APPLICATION Structural Reinforcement Solutions, LLC Carbon Fiber Strengthening Systems should only be installed by professional contractors who have been trained in the application of externally bonded carbon fiber reinforcement. Once the surface preparation has been completed and when cartridge epoxy is being used, the mixing nozzles provided will sufficiently mix the 2:1 epoxy components. If bulk epoxy is being used, follow the epoxy mixing instructions to sufficiently mix the epoxy components prior to the application. Once the epoxy has been mixed, a thin layer should be applied to the surface in which the CFRP is to be bonded. This epoxy should be worked into the substrate to ensure penetration into the pores of the substrate. The carbon fiber should then be laid into the epoxy and worked in to ensure a full saturation of the fabric. To aid in achieving a full saturation of the carbon fiber straps, they can be pre -saturated with epoxy and laid into the same initial layer of epoxy layer as described previously. No matter which way the straps are initially installed, a final layer of epoxy should be applied to the strap and worked in to ensure full saturation. Refer to the full set of installation instructions at www.structuralrs.com to ensure that the appropriate procedures are followed. LIMITED This product is covered by the Structural Reinforcement Solutions LLC LIFETIME LIMITED LIFETIME WARRANTY, which is available at structuralrs.com or WARRANTY by calling Structural Reinforcement Solutions LLC at 888 292-2952. FIRST AID EYES: Wash fibers off skin with water and soap. If fibers are embedded in the skin, remove with tweezers. Discard clothing that may contain embedded fibers. Seek medical advice if exposure results in adverse effects.Eyes: Immediately flush with a continuous water stream for at least 20 minutes. Washing immediately after exposure is expected to be effective in preventing damage to the eyes. Seek medical advice. Inhalation: If there is inhalation exposure to the fibers of this product, remove source of exposure and move victim to fresh air. If victim is not breathing, give artificial respiration. If there is breathing difficulty, give oxygen. Seek medical advice for any respiratory problems. Ingestion: Ingestion is not a likely means of exposure for this product. If ingestion does occur, DO NOT INDUCE VOMITING. Nothing by mouth if unconscious. Seek medical advice. Spill/Release and Cleanup Procedures: In case of spill, collect (e.g., sweep up, vacuum, etc.) spilled material and either reuse or dispose of properly. Chopped or milled carbon fibers may be slippery if spilled posing an accident risk. Wear personal protective equipment as described in the MSDS during cleanup activities. CAUTION Protective Measures: The use of safety glasses and chemically resistant gloves is recommended. Use appropriate clothing to minimize skin contact. The use of NIOSH-approved respirator is required to protect respiratory tract when ventilation is not adequate to limit exposure below the PEL. Refer to Safety Data Sheets (SDS) available at structuralrs.com/sds for detailed information. 1-888-292-2592 www.structurairs.com 19of32 0 !F'M �STRUCTURAL 0 ' ' ` +!•� REINFORCEMENT SOLUTIONS CARBON FIBER FABRIC A bidirectional, high -strength, non -corrosive carbon fiber fabric designed to be field laminated with SRS-1000 Epoxy adhesive to create a carbon fiber -reinforced polymer (CFRP) composite for structural reinforcement and strengthening of concrete and masonry structures TYPICAL FIBER PROPERTIES Tensile Strength - 711 ksi 4900 Mpa Tensile Modulus - 33.4 Msi 230 Gpa Elongation - 2.10% Density - .065 Ibs/inA3 1.80 g/cm"3 APPLICATIONS -External Reinforcement of Existing Structures -Increasing Load Capacity -Confinement -Shear Strengthening -Flexural Strengthening -Construction Error Corrections -Restoring Damaged/Deteriorated Structural Components -Bowed Wall Stabilization -Seismic Retrofit ADAVANTAGES •High Strength to Weight Ratio -High Modulus of Elasticity -Conforms to Structure -Easy Installation -Ambient Cure -Arrests Structure Movement -Low Aesthetic Impact -Non-Corrosive -Compatible with Most Finish Coatings TECHNICAL uATA PROPERTY AVE ULTIMATE DESIGN VALUE Tensile Strength Tensile Modulus Tensil % Enlongation Nominal Ply Thickness Tensile Strength per in. Width Tensile Strength per 6" Strap 196,000 psi 1,352 MPa 11 Msi 77 GPa 2% 0.018 in 3,529 Ibs/in 0.62 kN/mm 45,744 Ibs The information provided on this product data sheet represents average values which have been obtained through certified testing performed in a third -party laboratory. As part of the quality assurance program at SRS, these values are verified regularly to ensure that the products being sold are represented accurately by the values on this sheet. There may be some variation in test results due to epoxy mixing methods, degree of saturation, sample preparation, and curing conditions Per the recommendations in ACI-440.2, the ultimate tensile strengths provided represent the average test values minus three times the standard deviation which creates a 99.87% probability that the actual ultimate tensile properties will exceed the statistical based design values. 164,300 psi 1,133 Mpa 1% 2,958 Ibs/in 1.18kN/mm 17,748 Ibs TYPICAL DATA Storage Conditions - Store in Dry Area at 40 deg - 95 deg F (4-35 C) Shelf Life Carbon -10 years/Epoxy - 2 Years in Unopened Container Color Carbon - Black/Epoxy - Semi Transparent Yellowish resin Primary Fiber Direction - 0°/90° Bidirectional Areal Weight - 19.5 oz/SY 660 gsm 1-888-292-2592 www.structuralrs.com Made in USA 20 of 32 STRUCTURAL REINFORCEMENT SOLUTIONS CARBON FIBER ROLL KIT SIZES Roll Size (Width x Length) •SRS-660131 12" x 75 LF (75 SF) •SRS-660131 12" x 100 LF (100 SF) •SRS-660131 24" x 100 LF (200 SF) SURFACE PREPERATION DESIGN All applications containing SRS products must be designed by a registered design professional. The number of layers, dimensions, and detailing of SRS-6000NI shall be designed in accordance with ACI 440.2R or another recognized design guideline/code in order to meet the design performance specified for the application. Contact Structural Reinforcement Solutions LLC for design and technical support. The substrate in which the CFRP is being applied to must be clean and free of loose material or contaminants. In order to take advantage of the full bond strength properties of the epoxy, the substrate should be prepared per the requirements of the ICRI Technical Guideline No. 310-2R - 2013. The substrate should be prepared to a minimum concrete surface profile, CSP-3, as defined by ICRI 310-2R. Any voids, cracks, on variations in the surface of the concrete must be filled with an appropriate repair mortar or epoxy in order to provide a smooth surface to bond to. ACI 440.2R-08 provides additional details on the surface preparation requirements for CFRP systems APPLICATION Structural Reinforcement Solutions, LLC Carbon Fiber Strengthening Systems should only be installed by professional contractors who have been trained in the application of externally bonded carbon fiber reinforcement. Once the surface preparation has been completed and when cartridge epoxy is being used, the mixing nozzles provided will sufficiently mix the 2:1 epoxy components. If bulk epoxy is being used, follow the epoxy mixing instructions to sufficiently mix the epoxy components prior to the application. Once the epoxy has been mixed, a thin layer should be applied to the surface in which the CFRP is to be bonded. This epoxy should be worked into the substrate to ensure penetration into the pores of the substrate. The carbon fiber should then be laid into the epoxy and worked in to ensure a full saturation of the fabric. To aid in achieving a full saturation of the carbon fiber straps, they can be pre -saturated with epoxy and laid into the same initial layer of epoxy layer as described previously. No matter which way the straps are initially installed, a final layer of epoxy should be applied to the strap and worked in to ensure full saturation. Refer to the full set of installation instructions at www.structuralrs.com to ensure that the appropriate procedures are followed. LIMITED This product is covered by the Structural Reinforcement Solutions LLC LIFETIME LIMITED LIFETIME WARRANTY, which is available at structuralrs.com or WARRANTY by calling Structural Reinforcement Solutions LLC at 888 292-2952. FIRST AID EYES: Wash fibers off skin with water and soap. If fibers are embedded in the skin, remove with tweezers. Discard clothing that may contain embedded fibers. Seek medical advice if exposure results in adverse effects.Eyes: Immediately flush with a continuous water stream for at least 20 minutes. Washing immediately after exposure is expected to be effective in preventing damage to the eyes. Seek medical advice. Inhalation: If there is inhalation exposure to the fibers of this product, remove source of exposure and move victim to fresh air. If victim is not breathing, give artificial respiration. If there is breathing difficulty, give oxygen. Seek medical advice for any respiratory problems. Ingestion: Ingestion is not a likely means of exposure for this product. If ingestion does occur, DO NOT INDUCE VOMITING. Nothing by mouth if unconscious. Seek medical advice. Spill/Release and Cleanup Procedures: In case of spill, collect (e.g., sweep up, vacuum, etc.) spilled material and either reuse or dispose of properly. Chopped or milled carbon fibers may be slippery if spilled posing an accident risk. Wear personal protective equipment as described in the MSDS during cleanup activities. CAUTION Protective Measures: The use of safety glasses and chemically resistant gloves is recommended. Use appropriate clothing to minimize skin contact. The use of NIOSH-approved respirator is required to protect respiratory tract when ventilation is not adequate to limit exposure below the PEL. Refer to Safety Data Sheets (SDS) available at structuralrs.com/sds for detailed information. ++ ++ + + + + 1-888-292-2592 www.structurairs.com 21 of 32 STRUCTURAL EPDXY ADHESIVE A two -component, high modulus structural epoxy formula designed to provide maximum adhesion of SRS carbon fiber fabric to concrete substrates. SRS 1000 is specially formulated for long pot life, providing extended workability during CFRP application. The ultra -low viscosity formula is also ideal for gravity fed repair of fine to medium cracks in concrete. APPLICATIONS STRUCTURAL REINFORC SOLUTIONS FEATURES & ADVANTAGES -Ultra low viscosity formula optimized for carbon fiber saturation and bond strength to concrete substrates. -Long pot life for extended workability and design strengths in CFRP applications. -Pressure injection of fine to medium size cracks of approximately 1 /8 in. to 1 /4 in. (3.2 mm to 6.4 mm) width. -Self-leveling, low viscosity and surface tension allows product to deeply penetrate into cracks. -Saturation and adhesion of carbon fiber fabric to concrete substrates -Repair of spalling concrete -Bonding fresh concrete to hardened concrete or a bonding agent for repairing concrete spalls -Gravity feed crack repair for horizontal applications -Low pressure crack injection for vertical, horizontal and overhead structural repair CURE SCHEDULE Working Time: 50OF(10°C)-45min; 75OF(24°C)-30min; 100 OF (38 °C) - 22 min. NOTE: Working and full cure times are approximate LIMITATIONS APPROVALS AND CERTIFICATIONS ASTM C881 / AASHTO M235 Type I, II*, IV & V* Grade 1 Class C. * With exceptions. APPLICATION TEMPERATURE 50 OF and 100 OF (4 °C and 38 °C) STORAGE AND SHELF LIFE 24 months when stored in unopened containers in dry conditions. Store between 55 OF (13 °C) and 80 OF (27 °C). COLOR AND RATIO Part A (Resin) Clear: Part B (Hardener) Amber, Mix Ratio - 2:1 by volume, Mixed Color i — Amber. Do not thin with solvents, as this may prevent cure. Not intended to repair cracks subject to movement. Product not designed to stop seeping or flowing water. New concrete should be a minimum of 28 days old prior to application 1-888-292-2592 www.structurairs.com Made in 22 of 32 STRUCTURAL REINFORC SOLUTIONS STRUCTURAL EPDXY ADHESIVE TABLE 1: SRS-1000 Structural Eaoxv Adhesive performance to ASTM C881-151.2.3 SAMPLE CONDITIONING TEMPERATURE PROPERTY CURE TIME ASTM STANDARD UNITS CLASS C 60 °F (16 °C) Gel Time - 60 Gram Massa ---- C881 min 55 Viscosity ---- cP 200 Pot Lifer,, ---- min 45 1. Results based on testing conducted on a representative lot(s) of product. Average results will vary according to the tolerances of the given property. 2. Full cure time is listed above to obtain the given properties for each product characteristic. 3. Results may vary due to environmental factors such as temperature, moisture and type of substrate. 4. Gel time may be lower than the minimum required for ASTM C881. 5. Property not referenced in ASTM C881. 6. Pot life is measured as the workable and applicable time of 1.0 gallon (3.8 L) when mixed. 1-888-292-2592 www.structuralrs.com R05M--.0 Made in USA 23 of 32 STRUCTURAL REINFORC SOLUTIONS STRUCTURAL EPf'%ff%ff ADHESIVE TABLE 1: SRS-1000 Structural Eooxv Adhesive performance to ASTM C881-151,2,3 SAMPLE CONDITIONING TEMPERATURE PROPERTY CURE TIME ASTM STANDARD UNITS CLASS C 60 °F (16 °C) psi 10,800 Compressive Yield Strength D695 (MPa) -74.5 psi Compressive Modulus ----- 7 day (MPa) psi 8,000 Tensile Strength D638 (MPa) -55.2 Tensile Elongation % 2.7 psi 1,800 2 day Bond Strength Hardened to (MPa) -12.4 psi 3,300 Hardened Concrete 14 day C882 (MPa) -22.8 Bond Strength Fresh to Hardened psi Concrete 14 day (MPa) Heat Deflection °F 121 7 day D648 Temperature Water Absorption 14 day D570 % 0.49 Linear Coefficient of 48 hr D2566 % 0.003 Shrinkage 1. Results based on testing conducted on a representative lot(s) of product. Average results will vary according to the tolerances of the given property. 2. Full cure time is listed above to obtain the given properties for each product characteristic. 3. Results may vary due to environmental factors such as temperature, moisture and type of substrate. 4. Gel time may be lower than the minimum required for ASTM C881. 5. Property not referenced in ASTM C881. 6. Pot life is measured as the workable and applicable time of 1.0 gallon (3.8 L) when mixed. 1-888-292-2592 www.structuralrs.com Made in USA 24 of 32 Etc; STRUCTURAL SOLUTIONS STRUCTURAL ADHESIVE SURFACE PREPERATION Surface preparation will be dependent upon the application of the product. Old concrete must be clean and profiled or textured. New concrete should be a minimum of 28 days old. All dirt, oil, debris, wax, grease or dust must be removed. Prepare the surface mechanically using a scarifier, sandblast, shotblast or other equipment that will give the surface profile needed for the application. A roughened surface is imperative for good adhesion. Always be sure the bonding surfaces are prepared in advance before starting a new cartridge or mixing product. If possible, schedule dispensing to consume an entire cartridge at one time with no interruption of epoxy flow. CARTRIDGE PREPARATION 1. Shake the cartridge vigorously for 60 seconds, then stand cartridge upright for at least 1 minute allowing any bubbles to rise to the top. 2. Insert cartridge into the dispenser. Make sure it is properly positioned with the shoulder of the cartridge flush with the front/top bracket of the dispenser. Point upward at about a 450 angle. Remove the plastic cap and plug from the top of the cartridge. 3. Continue to point the upward away from yourself and others while slowly applying pressure to dispenser moving any bubbles and product up through the nozzle until it reaches the tip. Dispense this first full stroke of material into disposable container. The cartridge is now purged and ready for flow control installation. 4. Find the flow control inside the threaded end of the mixing nozzle attached to a tape strip. Insert flow control into the two holes at the top of the cartridge where the product comes out. Make sure it is securely seated in place. Install mixing nozzle onto cartridge. Holding the dispenser straight up, slowly apply pressure to the dispenser moving any bubbles and product up through the nozzle until it reaches the tip. Tilting only slightly, dispense this first full stroke of material into a disposable container. 5. NOTE: Schedule dispensing to consume an entire cartridge at one time with no interruption of flow to prevent material from hardening in mixing nozzle. If problems arise during dispensing product, replace the nozzle; the product may have begun to cure in the nozzle which will affect the mix ratio. Never transfer a used nozzle to a new cartridge. Repeat the cartridge balancing steps listed above after replacing the nozzle. W'0�-.00 1-888-292-2592 www.structurairs.com Made in USA 25 of 32 F'M:)STRUCTURAL `REINFORC_ SOLUTIONS STRUCTURAL EPDXY ADHESIVE MIX INSTRUCTIONS FOR BULK PACKAGING Thoroughly stir each component separately before mixing them together. Mix only the amount of material that can be used before the working time expires. Proportion parts by volume into a clean pail at the exact and proper mix ratio. Use 2 parts by volume of component A and 1 part by volume of component B. Mix thoroughly with a low speed drill (400 - 600 rpm) with a mix paddle attachment (i.e. Jiffy Mixer). Carefully scrape the sides and the bottom of the container while mixing. Keep the paddle below the surface of the material to avoid entrapping air. Proper mixing will take at least 3 minutes. For bulk, mix only enough product that can be used within the pot life. BONDING AGENT Bonding fresh concrete to hardened concrete or when used as a bonding agent for repairing concrete spalls: Using a brush, roller or airless sprayer, apply an even coat of the bulk mixed CEP61 to the clean and prepared concrete surface. While the epoxy is still tacky, place fresh concrete over the top of the mixed epoxy. SPALL REPAIR To avoid a feathered edge, cut around the spall into sound concrete with a grinder or circular saw using a diamond or concrete abrasive blade. The edge cut should be equal to the maximum depth of the spall or to at least, a minimum depth of 3/4 in. (19 mm). Chip out all loose concrete within the entire spall to a minimum depth of 3/4 in. (19 mm). Follow surface preparation instructions above to clean the spall. Estimate the amount of bulk product needed and mix Part A and Part B: 2 to 1 by volume. Mix part A and B thoroughly. Slowly add 3-4 parts by volume of kiln -dried sand or aggregate of choice and mix well, pour and trowel until smooth/level. Note: The low viscosity of CEP61 and CEP62 will aid in wetting out aggregate to create a repair mortar. Maximum mortar thickness is 1.5 in. (38 mm per lift 1-888-292-2592 www.structurairs.com Made in USA 26 of 32 pm:)STRUCTURAL `REINFORC_ SOLUTIONS STRUCTURAL EPDXY ADHESIVE GRAVITY FEED CRACK REPAIR FOR HORIZONTAL APPLICATIONS SRS-1000 is formulated for fine to medium cracks - 0.0025 in. to 0.125 in. (0.06 mm to 3.2 mm). For best results, cut a groove to open up the crack using an abrasive or diamond blade to a width of 1 /8 in. (3.2 mm) and minimum depth of 3/8 in. (9.5 mm). Use wire brush to abrade and then blow out the crack to remove all dust, dirt, grease, wax, oil or any other contaminants. Pour or inject into the crack and its self -leveling ability will fill the entire area. Repeat application if necessary to completely fill crack. Follow the cartridge preparation set-up. LOW PRESSURE CRACK INJECTION FOR VERTICAL, HORIZONTAL AND OVERHEAD STRUTURAL REPAIR Before repairs are attempted, examine the crack to determine the type of repair that is required. Cracks in concrete and wood members are classified as either dynamic (moving) or static (dormant). Static cracks may occur from a one-time overload event such as an earthquake or flood. For static cracks in a structure that is to be rehabilitated, structural crack injection is recommended. By contrast, dynamic cracks are those which are caused by inadequate design, seasonal heaving, temperature swings or repeated over -loading. Dynamic cracks CANNOT effectively be repaired using crack injection. Dynamic cracks can be sealed using a flexible repair material. CRACK INJECTION PREPERATION Clean the surface surrounding the crack with a wire brush to achieve proper bond. Remove all dust, debris, oil and any other contaminants from the crack by blowing out with clean, oil -free compressed air. For best results crack must be dry at the time of injection. If water is seeping from crack, steps must be taken to stop the flow of water in order to achieve desired repair. 1-888-292-2592 www.structurairs.com Made in USA 27 of 32 Appendix Parcel Details & Photographs 28 of 32 7/31 /23. 8:32 AM SnohomishOnlino Government Information & Services County 4* Washington Property Account Summary 7/31/2023 Parcel Number 00513600000902 (Property Address 7300 176TH ST SW, EDMONDS, WA 98026-5527 General Information Property Description MEADOWDALE SOUND VIEW TRACTS BLK 000 D-02 - E 75 FT OF TR 9 AS MEAS ON N LN Property Category Land and Improvements Status Tax Code Area Property Characteristics Active, Locally Assessed 100217 Use Code Unit of Measure Size (gross) Parties 111 Single Family Residence - Detached Acre(s) 0.26 Role Taxpayer Owner Percent Name Address 100 JOHNSTONE SEAN/SCHELL JEANNINE 7300 176TH ST SW, EDMONDS, WA 98026 100 JOHNSTONE SEAN & SCHELL JEANNINE 7300 176TH ST SW, EDMONDS, WA 98026-5527 United States Related Properties No Related Properties Found Property Values Value Type Tax Year 2023 Tax Year 2022 Tax Year 2021 Tax Year 2020 Tax Year 2019 Taxable Value Regular $1,217,800 $689,800 $676,700 $529,100 $679,600 Exemption Amount Regular Market Total $1,217,800 $689,800 $676,700 $529,100 $679,600 Assessed Value $1,217,800 $689,800 $676,700 $529,100 $679,600 Market Land $706,800 $407,200 $413,900 $423,600 $498,400 Market Improvement $511,000 $282,600 $262,800 $105,500 $181,200 Personal Property Active Exemptions No Exemptions Found Events Effective Date- Type (Remarks Date Time 1/3 29 of 32 7131 /23, 8:32 AM 12/30/2021 12/30/2021 16:21:44 Excise Processed Temporary Excise: T157607 Finalized to: E179359 12/27/2021 01/14/2022 Recording No. Property Transfer Filing No.: E179359, Statutory Warranty Deed, new 12:19:00 Changed Recording No.: 202112307146 12/27/2021 by sasaml 12/27/2021 01/14/2022 Owner Property Transfer Filing No.: E 1793 59 12/27/2021 by sasaml 12:19:00 Terminated 12/27/2021 01/14/2022 12:19:00 Owner Added Property Transfer Filing No.: E179359 12/27/2021 by sasaml 12/27/2021 12/30/2021 Excise Processed Property Transfer Filing No.: T157607, submitted by eREET 12/27/2021 16:21:00 by ASCEREET 04/17/2019 04/17/2019 Excise Processed Temporary Excise: T093292 Finalized to: E118850 09:37:40 04/12/2019 04/18/2019 09:17:00 Owner Terminated Property Transfer Filing No.: E118850 04/12/2019 by sasset 04/12/2019 04/18/2019 Owner Added Property Transfer Filing No.: E118850 04/12/2019 by sasset 09:17:00 04/12/2019 04/17/2019 Excise Processed Property Transfer Filing No.: T093292, submitted by eREET 04/12/2019 09:37:00 by ASCEREET 11/05/2018 01/10/2019 Owner Property Transfer Filing No.: 1181586 11/05/2018 by sascaf 09:10:00 Terminated 11/05/2018 01/10/2019 Owner Added Property Transfer Filing No.: 1181586 11/05/2018 by sascaf 09:10:00 11/05/2018 11/07/2018 Taxpayer Property Transfer Filing No.: 1181586 11/05/2018 by strtpw 09:35:00 Changed 11/05/2018 11/07/2018 Excise Processed Property Transfer Filing No.: 1181586, Special Warranty Deed 09:35:00 11/05/2018 by strtpw Tax Balance Installments Pa able Tax Year linstallment IDue Date I Principall Interest, Penalties and Costsl Total Duel Cumulative Due 2023 12 10/31 /2023 1 $4,145.271 $0.001 $4,145.271 $4,145.27 Distribution of Current Taxes District Rate Amount Voted Amount Non -Voted Amount CENTRAL PUGET SOUND REGIONAL TRANSIT AUT 0.16 $189.68 $0.00 $189.68 CITY OF EDMONDS 0.96 $1,170.78 $335.18 $835.60 EDMONDS SCHOOL DISTRICT NO 15 2.62 $3,188.67 $3,188.67 $0.00 PUB HOSP #2 0.05 $56.38 $0.00 $56.38 SNO-ISLE INTERCOUNTY RURAL LIBRARY 0.31 $378.57 $0.00 $378.57 SNOHOMISH COUNTY-CNT 0.48 $581.44 $0.00 $581.44 STATE 2.23 $2,714.98 $0.001 $2,714.98 SNOHOMISH CONSERVATION DISTRICT 6.80 $10.03 $8,290.53 $0.001 $3,523.851 $10.03 $4,766.68 TOTAL Pending Property Values Pendingl Market Land Market Market Total Current Use Current Use Current Use Tax Year Value Improvement Value Land Value Improvement Total Value Value 2024 $819,000.00 $507,800.00 $1,326,800.001 $0.00 $0.00 $0.00 Levy Rate History Tax Year Total Levy Rate 2022 8.270203 2021 8.207334 2/3 30 of 32 7131 /23, 8:32 AM 20201 9.276512 Real Property Structures Description iType IYear Built Imore Information 1 Story w/Basement IDwelling 11954 IView Detailed Structure Information Feceipts Date Receipt No. Amount Applied Amount Due 04/18/2023 00:00:00 12752694 $4,145.26 $8,290.53 10/21/2022 00:00:00 12471672 $2,856.40 $2,856.40 04/21/2022 00:00:00 12199048 $2,856.40 $5,712.80 05/26/2021 00:00:00 11724288 $2,780.97 $2,780.97 03/10/2021 00:00:00 11437939 $2,780.96 $5,561.93 11/25/2020 00:00:00 11417062 $2,482.69 $2,482.69 04/29/2020 00:00:00 11086042 $2,458.11 $4,916.22 10/17/2019 00:00:00 10642745 $3,131.19 $3,131.19 04/23/2019 10:32:00 10499246 $3,131.19 $6,262.38 11/06/2018 00:00:00 10281400 $3,314.34 $3,314.34 05/04/2018 00:00:00 10011536 $3,314.33 $6,628.67 Sales History Sale Date Entry Recording Sale Excise Deed Transfer Grantor(Seller) Grantee(Buyer) Other Date Number Amount Number Type Type Parcels 08/03/1999 01/01/1900 $0.00 479357 QC S LOUISE RUTH WATHNE No WATHNE CARTER CARTER CARTER 11/05/2018 11/07/2018 $0.00 1181586 WP S RUTHANNE K No ESTATE DANIEL PHILIP _ CARTER NGUYEN 04/12/2019 04/17/2019 $500,000.00 El18850 W S DANIEL No PHILIP NANG DINH JOHNSTONE 12/27/2021 12/30/2021202112307146 $1,200,000.00 E179359 W S NGUYEN SEAN & No NANG DINH SCHELL JEANNINE Property Maps Neighborhood Code ITownship lRange Isection lQuarter 1parcel Map 1504000 127 104 108 ISW jYiew parcel maps for this Township/Range/Section 3/3 31 of 32 12• wa ok 270 s.f 10' 3i' r Cnpy r r r Conc 230sf Isfr 1449sf 10• 26' 10' 36' 40 r 6-wohn 1387 s f h r 25' >~ 1. Existing building plan provided by Snohomish County records for Parcel #:00513600000902 for address- 7300 176th St SW, Edmonds, WA 98026 Note that analysis assumptions such as building geometry, tributary areas, and loading were determined through examination of these photographs and industry knowledge of standard construction practices. -L 120 1 y 'yam-•., i.. _ - - r �.r!� s ,, ,,`'���??C��; , .`ter _^y�yt... `� II �,• w • � �\ +R`.. Jf