APPROVED RESUB 1-BLD2024-0072+Structural_Plans+3.21.2024_4.13.44_PM+4150078STRUCTURAL NOTES C GI (THESE NOTES ARE TYPICAL UNLESS NOTED OR DETAILED OTHERWISE ON DRAWINGS) CODE ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (IBC), 2018 EDITION. SPECIFICATIONS AND STANDARDS WHERE REFERENCED ON THE DRAWINGS ARE TO BE THE LATEST EDITION. DESIGN LOADS DEAD LOADS: ROOF 15 PSF FLOOR 15 PSF DECK 60 PSF LIVE LOADS: ROOF (SNOW LOAD) 25 PSF FLOOR 40 PSF (LIVE LOADS ARE REDUCED WHERE PERMISSIBLE PER IBC SECTION 1607.11). EARTHQUAKE LOADS: EQUIVALENT LATERAL FORCE PROCEDURE PER ASCE 7-16 SECTION 12.8. SITE CLASS D (DEFAULT) SHORT PERIOD SPECTRAL RESPONSE ACCEL (SS) 1.288 ONE SECOND SPECTRAL RESPONSE ACCEL (Si) 0.454 SHORT PERIOD DESIGN SPECTRAL RESPONSE ACCEL (SDS) 1.030 ONE SECOND DESIGN SPECTRAL RESPONSE ACCEL (SDI) 0.559 RISK CATEGORY II SEISMIC IMPORTANCE FACTOR (IF) 1.0 SEISMIC DESIGN CATEGORY D BASIC SEISMIC FORCE -RESISTING -SYSTEM PLYWOOD SHEAR WALLS RESPONSE MODIFICATION FACTOR, (R) 6.5 REDUNDANCY FACTOR (p) 1.3 SEISMIC RESPONSE COEFFICIENT (CS) 0.159 W = TOTAL SEISMIC DEAD LOAD AS DEFINED PER ASCE 7-16 SECTION 12.7.2. BASE SHEAR (V), V = CSW = RD I W WIND LOADS: BASIC WIND SPEED (3 SECOND GUST) 97 MPH EXPOSURE B KzT 1.03 STATEMENT OF SPECIAL INSPECTIONS SPECIAL INSPECTIONS ARE REQUIRED AS INDICATED IN THE FOLLOWING TABLE. THE CONTRACTOR SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND OWNER PRIOR TO COMMENCEMENT OF WORK IN ACCORDANCE WITH SECTION 1704.4 OF THE IBC. CONCRETE CONSTRUCTION - SPECIAL INSPECTION IS REQUIRED IN CONFORMANCE WITH IBC SECTION 1705.3 AND TABLE 1705.3. STRUCTURAL OBSERVATION OF THE STRUCTURAL SYSTEM BY THE ENGINEER IS NOT REQUIRED. FREQUENCY AND DISTRIBUTION OF REPORTS - INSPECTION REPORTS SHALL BE PROVIDED FOR EACH DAY ON SITE BY SPECIAL INSPECTOR. STRUCTURAL OBSERVATION REPORTS SHALL BE PROVIDED AFTER EACH OBSERVATION. REPORTS SHALL BE DISTRIBUTED TO THE CONTRACTOR, ARCHITECT, ENGINEER AND BUILDING OFFICIAL. SPECIAL INSPECTION OPERATION CONT PERIODIC REMARKS CONCRETE ADHESIVE ANCHORS X IF USED EXPANSION ANCHORS X IF USED NOTE: ALL ITEMS MARKED WITH AN "X" SHALL BE INSPECTED IN ACCORDANCE WITH IBC CHAPTER 17. SPECIAL INSPECTION SHALL BE PERFORMED BY A QUALIFIED TESTING AGENCY DESIGNATED BY THE OWNER. THE ARCHITECT, STRUCTURAL ENGINEER, AND BUILDING OFFICIAL SHALL BE FURNISHED WITH COPIES OF ALL RESULTS. ANY INSPECTION FAILING TO MEET THE PROJECT SPECIFICATIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE DESIGN TEAM. FOUNDATIONS: SPREAD FOOTINGS SOILS REPORT: REPORT NOT AVAILABLE AT TIME OF DESIGN ALLOWABLE SOIL PRESSURE: 2000 PSF (ASSUMED; TO BE FIELD VERIFIED DURING CONSTRUCTION) LATERAL EARTH PRESSURE: UNRESTRAINED: 35 PCF + ANY APPLICABLE SURCHARGE PASSIVE: 300 PCF COEFFICIENT OF FRICTION: 0.35 FOOTINGS SHALL BEAR ON FIRM UNDISTURBED EARTH OR 12" OF COMPACTED STRUCTURAL FILL AS REQUIRED AND AT LEAST 18" BELOW ADJACENT EXTERIOR GRADE. ANY FOOTING ELEVATIONS SHOWN IN THE DRAWINGS REPRESENT MINIMUM DEPTHS AND ARE FOR BIDDING ONLY. ACTUAL FOOTING ELEVATIONS ARE SUBJECT TO SITE CONDITIONS AND MUST THEREFORE BE ESTABLISHED BY THE CONTRACTOR. FOOTINGS SHALL BE CENTERED BELOW COLUMNS OR WALLS ABOVE, UNLESS NOTED OTHERWISE. IMPORTED STRUCTURAL FILL AND BACKFILL MATERIAL SHOULD CONSIST OF CLEAN, WELL GRADED GRANULAR MATERIAL FREE OF DEBRIS OR ORGANICS WITH A MAXIMUM PARTICLE DIAMETER OF THREE INCHES AND NO MORE THAN 10% FINES (PASSING THE #200 SIEVE). EXCAVATIONS AND DRAINAGE INSTALLATION SHALL BE OBSERVED BY A SOILS ENGINEER RETAINED BY THE OWNER. IF EXCAVATION SHOWS SOIL CONDITIONS TO BE OTHER THAN THOSE ASSUMED ABOVE NOTIFY THE STRUCTURAL ENGINEER FOR POSSIBLE FOUNDATION REDESIGN. ,K�7►141:0\l: ALL CONCRETE SHALL BE MIXED, PROPORTIONED, CONVEYED, AND PLACED IN ACCORDANCE WITH CHAPTER 26 OF ACI 318 AND THE AMERICAN CONCRETE INSTITUTE'S SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301). ALL CONCRETE SHALL BE STONE -AGGREGATE CONCRETE HAVING A UNIT WEIGHT OF APPROXIMATELY 150 POUNDS PER CUBIC FOOT. CONCRETE STRENGTHS AT 28 DAYS (fc) AND MIX CRITERIA SHALL BE AS FOLLOWS: MAXIMUM MIN CEMENT TYPE OF CONSTRUCTION PC* WATER/CEMENT CONTENT PER CUBIC MAXIMUM SHRINKAGE STRAIN RATIO YARD SLABS ON GRADE 3000 PSI 0.55 5 1/2 SACK N/A FOOTINGS 3000 PSI 0.55 5 1/2 SACK N/A WALLS 4000 PSI 0.45 5 1/2 SACK N/A THE MINIMUM AMOUNT OF CEMENT LISTED ABOVE MAY BE CHANGED IF A CONCRETE PERFORMANCE MIX IS SUBMITTED TO THE ENGINEER AND THE BUILDING DEPARTMENT FOR APPROVAL TWO WEEKS PRIOR TO PLACING ANY CONCRETE. THE PERFORMANCE MIX SHALL INCLUDE THE AMOUNTS OF CEMENT, FINE AND COARSE AGGREGATE, WATER, AND ADMIXTURES AS WELL AS THE WATER -CEMENT RATIO, SLUMP, CONCRETE YIELD, AND SUBSTANTIATING STRENGTH DATA IN ACCORDANCE WITH CHAPTER 26 OF ACI 318. ALL CONCRETE EXPOSED TO WEATHER OR TO FREEZING TEMPERATURES SHALL BE AIR -ENTRAINED IN ACCORDANCE WITH ACI 318 TABLE 19.3.3.1 FOR MODERATE EXPOSURE CLASS F1. *PROVIDE fc SPECIFIED IN TABLE FOR DURABILITY REQUIREMENTS. 2500 PSI CONCRETE MEETS STRENGTH REQUIREMENTS, THEREFORE SPECIAL INSPECTION IS NOT REQUIRED. REINFORCING STEEL REINFORCING STEEL SHALL BE DEFORMED BILLET STEEL CONFORMING TO ASTM A615, AND SHALL BE GRADE 60 (Fy = 60,000 PSI), UNLESS NOTED OTHERWISE. GRADE 60 REINFORCING BARS INDICATED ON DRAWINGS TO BE WELDED SHALL CONFORM TO ASTM A706. REINFORCING COMPLYING WITH ASTM A615 MAY BE WELDED IF MATERIAL PROPERTY REPORTS INDICATING CONFORMANCE WITH WELDING PROCEDURES SPECIFIED IN AWS D1.4 ARE SUBMITTED. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. PROVIDE WELDED WIRE FABRIC IN SHEETS NOT ROLLS. LAP WELDED WIRE FABRIC 12" AT SIDES AND ENDS. REINFORCING STEEL SHALL BE DETAILED INCLUDING HOOKS AND BENDS IN ACCORDANCE WITH ACI SP-66 AND ACI 318, LATEST EDITIONS. UNLESS OTHERWISE NOTED, REINFORCING SPLICE LENGTHS AND DEVELOPMENT LENGTHS SHALL BE PER SCHEDULE. MECHANICAL SPLICING OF REINFORCING BARS, WHERE INDICATED ON THE DRAWINGS, SHALL BE BY AN ICBO APPROVED SYSTEM, SHALL DEVELOP 125% OF THE SPECIFIED YIELD STRENGTH OF THE BAR, AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. REINFORCING SHALL BE PLACED AND ADEQUATELY SUPPORTED PRIOR TO PLACING CONCRETE. WET -SETTING EMBEDDED ITEMS IS NOT ALLOWED WITHOUT PRIOR ENGINEER APPROVAL. BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL NOT BE FIELD BENT UNLESS SO DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER. REFER TO CHAPTER 25 OF ACI 318 FOR OTHER REINFORCING STEEL REQUIREMENTS. MINIMUM LAPS AND EMBEDMENT UNLESS OTHERWISE NOTED, REINFORCING SPLICE LENGTHS AND DEVELOPMENT LENGTHS SHALL BE AS TABULATED BELOW: fc = 3000 PSI DEVELOPMENT LENGTH LAP SPLICE BAR TENSION COMPRESSION TENSION COMPRESSION SIZE TOP BARS OTHER BARS ALL BARS TOP BARS OTHER BARS ALL BARS #3 22 17 9 28 22 12 #4 29 22 11 37 29 15 #5 36 28 14 47 36 19 #6 43 33 17 56 43 23 #7 63 48 20 81 63 27 #8 j 72 j 55 j 22 j 93 72 j 30 fc = 4000 PSI DEVELOPMENT LENGTH LAP SPLICE BAR TENSION COMPRESSION TENSION COMPRESSION SIZE TOP BARS OTHER BARS ALL BARS TOP BARS OTHER BARS ALL BARS #3 19 15 8 24 19 12 #4 25 19 10 33 25 15 #5 31 24 12 41 31 19 #6 1 37 29 15 49 37 23 #7 54 42 17 71 54 27 #8 62 1 48 19 1 81 1 62 1 30 NOTE: 1. ALL LENGTHS ARE IN INCHES. 2. ALL LAP SPLICES ARE CLASS B. 3. "TOP BARS" ARE HORIZONTAL REINFORCEMENT PLACED SUCH THAT MORE THAN 12 INCHES OF CONCRETE IS CAST IN THE MEMBER BELOW THE BAR. CONCRETE COVER ON REINFORCING CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3" CONCRETE EXPOSED TO EARTH AND WEATHER: #6 BARS AND LARGER 2" #5 BARS AND SMALLER 1 1/2" CONCRETE NOT EXPOSED TO EARTH OR WEATHER: SLABS, WALLS AND JOISTS 3/4" COLUMN TIES OR SPIRALS AND BEAM STIRRUPS 1 1/2" NON -SHRINK GROUT NON -SHRINK GROUT SHALL BE CEMENT -BASED WITH A MINIMUM COMPRESSIVE STRENGTH OF 5000 PSI WHEN TESTED IN ACCORDANCE WITH ASTM C-109. GROUT SHALL BE MIXED AND PLACED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. STRUCTURAL STEEL STRUCTURAL STEEL DESIGN, FABRICATION AND ERECTION SHALL BE IN ACCORDANCE WITH THE AISC "SPECIFICATION FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS", LATEST EDITION. WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992, Fy = 50 KSI. PLATES, ANGLES, CHANNELS, AND RODS SHALL CONFORM TO ASTM A36, Fy = 36 KSI. STRUCTURAL TUBING SHALL CONFORM TO ASTM A500 GRADE C, RECTANGULAR/SQUARE Fy = 50 KSI, ROUND Fy = 46 KSI. STEEL PIPE SHALL CONFORM TO ASTM A53 GRADE B, Fy = 35 KSI. BOLTS CONNECTING STEEL MEMBERS SHALL CONFORM TO ASTM A325-N. BOLTS SHALL BE 3/4"0 MINIMUM, UNO ANCHOR BOLTS SHALL CONFORM TO ASTM A307. CONTRACTOR SHALL PROVIDE CONNECTION ADJUSTMENT TOLERANCES TO SATISFY THE REQUIREMENTS OF AISC MANUAL OF STEEL CONSTRUCTION. UNLESS SPECIFIED AS STAINLESS STEEL, ALL STEEL MEMBERS, SHAPES, BOLTS, AND ACCESSORIES EXPOSED TO WEATHER SHALL BE HOT DIP GALVANIZED. WELDING WELDING SHALL CONFORM TO AWS "STRUCTURAL WELDING CODE", LATEST EDITION. ALL WELDING SHALL BE DONE WITH 70 KSI LOW HYDROGEN ELECTRODES. WHERE NOT CALLED OUT, MINIMUM FILLET WELD SIZE SHALL BE PER TABLE 5.8 IN AWS D1.1, LATEST EDITION. WELDING OF REINFORCING BARS SHALL NOT BE PERMITTED UNLESS SPECIFICALLY CALLED OUT ON DRAWINGS OR APPROVED BY STRUCTURAL ENGINEER. WELDING OF GRADE 60 REINFORCING BARS SHALL BE PERFORMED USING LOW HYDROGEN ELECTRODES. WELDING OF GRADE 40 REINFORCING BARS SHALL BE PERFORMED USING E70XX ELECTRODES. SEE REINFORCING NOTES FOR MATERIAL REQUIREMENTS OF WELDED BARS. WELDING WITHIN 4" OF COLD BENDS IN REINFORCING BARS IS NOT PERMITTED. ALL WELDING SHALL BE DONE BY WASHINGTON ASSOCIATION OF BUILDING OFFICIALS (WABO) CERTIFIED WELDERS LUMBER ALL GRADES SPECIFIED ARE MINIMUM GRADES REQUIRED. ALL LUMBER SHALL BE IN ACCORDANCE WITH WWPA GRADING RULES, KILN -DRIED TO MC 19 AND OF THE FOLLOWING MINIMUM STANDARDS: SIZE CLASSIFICATION SPECIES GRADE Fb (PSI) Fc (PSI) SLEEPERS DOUG-FIR STUD 700 - LIGHT FRAMING (STUDS) HEM -FIR STUD 675 800 2x JOISTS AND PLANKS HEM -FIR #2 850 - PLATES AND BLOCKING HEM -FIR #2 850 - 6x AND LARGER BEAMS AND STRINGERS DOUG-FIR #2 875 - 4x AND SMALLER BEAMS AND STRINGERS HEM -FIR #2 850 - ALL POSTS AND TIMBERS DOUG-FIR #1 1200 1000 REFER TO PLAN NOTES, SCHEDULES, AND DETAILS FOR MORE SPECIFIC LUMBER SIZE AND GRADE REQUIREMENTS. UNLESS NOTED OTHERWISE IN THE PLANS, ALL WOOD AND WOOD -BASED MEMBERS EXPOSED TO WEATHER OR IN CONTACT WITH CONCRETE, MASONRY, OR WITHIN 8" OF SOIL SHALL BE PRESERVATIVE -TREATED BY VACUUM -PRESSURE IMPREGNATION IN ACCORDANCE WITH AWPA STANDARD U1. NAILS, BOLTS, AND METAL CONNECTORS FOR WOOD ALL NAILS SHALL CONFORM TO THE STANDARDS SET FORTH BY THE NATIONAL DESIGN STANDARDS (NDS) FOR WOOD CONSTRUCTION, LATEST EDITION. NAILING NOT SPECIFIED SHALL BE PER IBC TABLE 2304.10.1 NAILING SCHEDULE. ALL NAILS CALLED OUT ON PLANS SHALL BE COMMON NAILS UNLESS NOTED OTHERWISE AND SHALL MEET OR EXCEED THE FOLLOWING MINIMUM GUIDELINES: NAIL SHANK 0 MIN LENGTH 8d COMMON 0.1310 2 1/2" SHANK 10d COMMON 0.1480 3" SHANK 12d COMMON 0.1480 3 1/4" SHANK 16d COMMON 0.1620 3 1/2" SHANK 10d BOX NAILS MAY BE SUBSTITUTED FOR 8d COMMON NAILS WITH NO CHANGE IN NAIL SPACING. FRAMING MEMBERS MAY BE NAILED WITH 16d SINKERS (0.148" 0 x 3 1/4"), BUT ONLY 16d COMMON NAILS SHALL BE USED WHERE 16d NAILS ARE INDICATED IN THIS DRAWING SET. ENGINEER MAY APPROVE OTHER NAILS IF NAIL LABELS ARE SUBMITTED TO ENGINEER PRIOR TO START OF CONSTRUCTION. ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG SCREWS BEARING ON WOOD. LEAD HOLES FOR LAG BOLTS SHALL BE BORED FOR THE SHANK AND THREADED PORTIONS PER NDS 12.1.4.2. CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE" BY SIMPSON COMPANY, CATALOG TO BE THE LATEST EDITION, OR ENGINEER APPROVED EQUAL. CONNECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND WITH THE NUMBER AND SIZE OF FASTENERS AS SPECIFIED BY THE MANUFACTURER. WHERE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE ONE-HALF OF THE NAILS, SCREWS, OR BOLTS IN EACH MEMBER. INSTALL SOLID BLOCKING AT ALL BEARING POINTS. ALL SHIMS SHALL BE SEASONED, DRIED, AND THE SAME GRADE (MINIMUM) AS MEMBERS CONNECTED. GALVANIZATION UNLESS NOTED OTHERWISE, STEEL CONNECTORS IN CONTACT WITH TREATED WOOD SHALL BE GALVANIZED ACCORDING TO THE FOLLOWING TABLE: GALVANIZATION UNTREATED WOOD CCA-C SBX ACQ-C ACQ-D CBA-A CA-B OTHER BORATE ACZA OTHER PT WOOD G90 X X X G 185 X X X X X X HDG X X X X X X STT300 X X X X X X X X G90 = 0.90 OZ. OF ZINC PER SQUARE FOOT OF AREA G185 = 1.85 OZ. OF ZINC PER SQUARE FOOT OF AREA HDG = HOT DIP GALVANIZED SST300 = TYPE 316L STAINLESS STEEL RATED SHEATHING RATED SHEATHING SHALL BE GRADE C-D INT-APA WITH EXTERIOR GLUE OR OSB SHEATHING WITH EXTERIOR GLUE IN CONFORMANCE WITH IBC STANDARD 2303.1.5. TIMBERSTRAND, MICROLLAM, AND PARALLAM MEMBERS FABRICATED IN CONFORMANCE WITH THE INTERNATIONAL CODE COUNCIL EVALUATION SERVICE (ICC-ES) REPORT NO. ESR-1387 OR CCMC REPORT NO. 12627-R, 08675-R, AND 11161-R. EACH MEMBER SHALL BE IDENTIFIED BY A STAMP INDICATING THE PRODUCT TYPE AND GRADE, ICC-ES OR CCMC REPORT NUMBER, MANUFACTURER'S NAME, PLANT NUMBER AND INDEPENDENT INSPECTION AGENCY'S LOGO. FABRICATOR SHALL BE CERTIFIED. MEMBERS SHALL MEET THE FOLLOWING MINIMUM STANDARDS: SIZE CLASSIFICATION SPECIES GRADE Fb (PSI) Fv (PSI Fc (PSI) BEAMS & POSTS (d < 9 1/2") LSL 1.3E 1,700 425 1,835 RIMS & BEAMS (d >_ 9 1/2") LSL 1.55E 2,325 310 - BEAMS & POSTS LVL 2.0E 2,600 285 2,510 POSTS (d < 9 1/2") PSL 1.8E 2,400 190 2,500 BEAMS (d >_ 9 1/2") PSL 2.0E 2,900 290 - TIMBERSTRAND, MICROLLAM, AND UNTREATED PARALLAM MEMBERS ARE INTENDED FOR DRY -USE APPLICATIONS. UNLESS NOTED OTHERWISE, ENGINEERED WOOD BEAMS EXPOSED TO WEATHER SHALL BE TREATED PER MANUFACTURES RECOMMENDATIONS. GLUE -LAMINATED TIMBER GLUE -LAMINATED TIMBER SHALL BE DOUGLAS FIR, FABRICATED IN CONFORMANCE WITH ANSI/AITC STANDARD A190.1, LATEST EDITION. EACH MEMBER SHALL BEAR AN AITC IDENTIFICATION MARK AND SHALL BE ACCOMPANIED BY AN AITC CERTIFICATE OF CONFORMANCE. FABRICATOR SHALL BE CERTIFIED. MEMBERS SHALL BE OF THE FOLLOWING MINIMUM STANDARDS: SPAN COMBINATION Fb SIMPLE SPAN BEAMS 24F-V4 2400 PSI CANTILEVER OR MULTI -SPAN BEAMS 24F-V8 2400 PSI Epoxy anchors shall be inspected by a certified third party inspection service. Provide all reports to city inspector TYPICAL FRAMING NOTES 1. BEARING WALL FRAMING 2x STUDS @ 16" OC FOR ALL SHEAR AND/OR BEARING WALLS UNO. REFER TO FRAMING PLAN NOTES FOR TYPICAL DOOR & WINDOW HEADERS NOT CALLED OUT ON THE PLANS. HEADERS SHALL BE SUPPORTED BY A MINIMUM OF (1) CRIPPLE AND (1) FULL HEIGHT STUD UNO. COLUMNS BELOW FLUSH MULTIPLE JOIST BEAMS SHALL BE EQUAL IN WIDTH TO THE BEAM. ALL COLUMNS NOT CALLED OUT OTHERWISE SHALL BE TWO STUDS. 2. WALL BASE PLATE ON CONCRETE WALL PLATES BEARING ON CONCRETE SHALL BE PRESSURE -TREATED. FOR ALL EXTERIOR AND INTERIOR WALLS, BOLT PLATES OR SILLS TO CONCRETE STEM WALLS OR THICKENED SLAB FOOTINGS WITH 5/8 INCH DIAMETER ANCHOR BOLTS WITH 7 INCH MINIMUM EMBEDMENT. PLACE AT 5'-0" OC MAXIMUM FOR SHEAR WALLS, AND AT U-0" OC FOR BEARING WALLS AND OTHER PARTITIONS. USE MINIMUM OF TWO ANCHOR BOLTS PER SILL AND PLACE ONE WITHIN 12 INCHES OF END OF PLATES, TYPICAL UNLESS NOTED OR DETAILED OTHERWISE. REFER TO SHEAR WALL SCHEDULE. AT ALL SILL PLATE ANCHOR BOLTS, CONTRACTOR SHALL INSTALL 1/4" x 3" x 3" FLAT PLATE WASHERS. INTERIOR NON-STRUCTURAL WALLS MAY BE ANCHORED TO CONCRETE SLAB -ON -GRADE WITH 1/4" x 3" POWDER ACTUATED FASTENERS WITH 3/4" WASHERS AT 16" OC AND WITHIN 6" OF END OF PLATES. 3. ROOF AND FLOOR FRAMING PROVIDE 1 1/2" FULL DEPTH BLOCKING FOR JOISTS AND RAFTERS AT ALL SUPPORTS AND AT 8'-0" OC MAXIMUM UNO. INTERMEDIATE 8'-0" OC BLOCKING NOT REQ'D IF GWB CEILING IS INSTALLED DIRECTLY TO UNDERSIDE OF FRAMING. INSTALL DOUBLE JOISTS UNDER PARTITIONS EXTENDING ONE HALF OR MORE OF THE JOIST SPAN. PROVIDE TRUSS BLOCKING PANELS FOR ROOF TRUSSES AT SUPPORTS AND SHEAR WALLS, AND WHERE INDICATED ON PLANS AND DETAILS. 4. DIAPHRAGM NAILING ALL SHEAR WALLS, FLOOR AND ROOF DIAPHRAGM NAILINGS SHALL BE AS CALLED OUT ON SCHEDULES OR ON THE PLANS. EXTERIOR WALLS NOT INDICATED AS SHEAR WALLS SHALL BE SHEATHED AND NAILED TO SUPPORTING FRAMING WITH 8d NAILS AT 6" OC AT ALL PANEL EDGES AND 12" OC AT ALL INTERMEDIATE SUPPORTS. THE USE OF NAIL GUNS WILL BE APPROVED IF NAILING INTO THE DIAPHRAGMS CAN BE INSTALLED FLUSH WITH FACE OF SHEATHING. NAIL PENETRATIONS GREATER THAN 1/16" ARE NOT ACCEPTABLE. 5. ALLOWABLE STUD AND PLATE PENETRATIONS CUTTING AND/OR NOTCHING OF WOOD STUDS OR PLATES SHALL NOT EXCEED 25% OF THE STUD/PLATE WIDTH IN EXTERIOR AND BEARING WALLS AND SHALL NOT EXCEED 40% OF THE STUD/PLATE WIDTH IN ANY NON -BEARING PARTITIONS. BORED HOLE DIAMETER IS LIMITED TO 40% OF STUD/PLATE WIDTH IN ANY STUD AND MAY BE 60% IN NONBEARING PARTITIONS OR IF STUD IS DOUBLED. MAINTAIN 5/8" MINIMUM EDGE DISTANCE FROM HOLE EDGE. AeY/�Y�11/\�i1/e1��Yi7e\:��71Ie11�11[e ALL GYPSUM WALLBOARD SHALL BE NAILED TO ALL STUDS AND TOP AND BOTTOM PLATES WITH 6d COOLER NAILS OR NO. 13 GAUGE x 1 5/8" @ 7" OC (5d COOLER NAILS FOR 1/2 INCH GYPSUM SHEATHING). TYPICAL UNLESS NOTED OTHERWISE. INSTALLATION OF GWB SHALL BE SUCH THAT JOINTS ARE STAGGERED ON EACH SIDE OF A SINGLE WALL. EXISTING BUILDING CONTRACTOR SHALL VERIFY ALL DIMENSIONS, MEMBER SIZES AND CONDITIONS OF THE EXISTING BUILDING DEPICTED IN THE DRAWINGS, AND NOTIFY THE STRUCTURAL ENGINEER OF ANY DISCREPANCIES FOR POSSIBLE REDESIGN. CONTRACTOR RESPONSIBLE FOR COMPLETELY SEALING ALL AREAS WHERE EXISTING ROOF MATERIAL IS PENETRATED OR REMOVED. PROVIDE WATER PROOFING AS REQUIRED BY THE ARCH. GENERAL STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL, CIVIL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS FOR COMPATIBILITY BEFORE PROCEEDING. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT BEFORE PROCEEDING. CONTRACTOR TO SEE ARCHITECTURAL, CIVIL, ELECTRICAL AND MECHANICAL DRAWINGS FOR SIZE AND LOCATION OF PIPE, VENT, DUCT AND OTHER OPENINGS AND DETAILS NOT SHOWN ON THESE DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR ERECTION STABILITY AND TEMPORARY SHORING AS NECESSARY UNTIL PERMANENT SUPPORT AND STIFFENING ARE INSTALLED. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL NOT SATISFY THIS REQUIREMENT. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF A SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND THE STRUCTURAL ENGINEER. The following documentation shall be available on site for the building inspector: ■ 'E] COE APPROVED ARCHITECTURAL PLAN SET [:] COE APPROVED STRUCTURAL PLAN SET [:]COE REVIEWED CALCULATION PACKET ■ ENERGY CREDIT WORKSHEET ■ SITE PLAN ■ CIVIL PLAN ■ ■ ■ CITY OF EDMONDS BUILDING DEPARTMENT 2021 BLD2024-0072 ENGINEERING 250 4TH AVE. S., SUITE 200 EDM0 DS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 �AwT7iy wOF WAS$ iJ415t�, �IONAL W 20124 w N z Q O H � H N Z w O m NH z H LU W w O 0 a U m � W O O Q � N m PO Y Q DESIGN: MTM DRAWN: LVW CHECK: MTM JOB NO: 23295.10 DATE: 1 2/20/23 RESUB Mar 22 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT N w W U F_ Z O O W N o Z 0 Z 00 0) W J ��a Q LLJ Q �:: Of ZD 0 _ ~ F_ � N 0 U � Z � m M La �W �� Z M ,~^ V J SHEET: Simi STRUCTURAL NOTES (THESE NOTES ARE TYPICAL UNLESS NOTED OR DETAILED OTHERWISE ON DRAWINGS) LEGEND DEFINITION SYMBOL DEFINITION SYMBOL DIRECTION OF FRAMING NATIVE SOIL==�=�=� — — — — — EXTENT OF FRAMING el GRANULAR FILL STRUCTURAL STEEL COLUMNS COLUMN BEARING ON BEAM RATED SHEATHING P BEAM CONTINUOUS OVER SUPPORT SHEAR WALL SWX (SEE SCHEDULE) � CONCRETE WALL COLUMN MARK G� (SEE SCHEDULE) BEARING STUD FOOTING MARK O WALL (SEE SCHEDULE) NON -BEARING HOLDOWN MARK STUD WALL (SEE SCHEDULE) BEARING STUD HANGER MARK SHEAR WALL (SEE SCHEDULE) O NON -BEARING FLAG NOTE STUD SHEAR WALL (SEE PLAN NOTES) CMU WALL XXXXM STEEL MOMENT FRAME CONN. �V ABBREVIATIONS (A) ABOVE HORIZ HORIZONTAL AB ANCHOR BOLT KIP KING POST KIPS PER SQUARE INCH ALT ALTERNATE KSI ARCH (B) ARCHITECT MECH MECHANICAL MOMENT FRAME NEAR SIDE BELOW MF BLKG BLOCKING NS BM BEAM OC ON CENTER OPPOSITE BOT BOTTOM OPP BTWN BETWEEN PL PLATE PLACES POUNDS PER SQUARE INCH POUNDS PER SQUARE FOOT CJP COMPLETE JOINT PENETRATION PLCS CLR CLEAR PSI CIVIL) CONCRETE MASONRY UNIT PSF COL COLUMN P/T POSTTENSIONED CONC CONCRETE PT PRESSURE TREATED REINFORCING CONN CONNECTION REINF CONT CONTINUOUS REQ'D REQUIRED DBL DET DOUBLE SCHED SIM SCHEDULE SIMILAR DETAIL DIM DIMENSION SOG SLAB ON GRADE STANDARD EA EACH STD ELEV ELEVATION SW SHEAR WALL TOP OF CONCRETE EXIST EXISTING TOC EXP EXPANSION TOS TOP OF STEEL TOP OF WALL TYPICAL FLR FLOOR TOW FDN FOUNDATION FOOTING FAR SIDE FULL HEIGHT GLUE -LAMINATED BEAM TYP FTG LINO UNLESS NOTED OTHERWISE FS VFY VERIFY VERIFY IN FIELD FH VIF GLB VERT VERTICAL C G ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 w N oll ►' AwTxt; wO� WA iJ 465 t � �IONAL W 20124 DESIGN: MTM DRAWN: LVW CHECK: MTM JOB NO: 23295.10 DATE: 1 2/20/23 RESUB Mar 22 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT N w W U F_ z O O Ld N O z cl 0 z 00 LLI ��a Q w Q �:: 10:� 0 _ ) F_ � N U z D � m � 10:� qqt 0W ~ Z M z SHEET: S102 r- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1 PROM V-6" x 5'-0" x V-0" THIC4 BARS @ 12" OC EA WE PROM 2'-0" x 2'-0" x V-0 PROM V-6" x 5'-0" x V-0" THICK BARS @ 12"OC EA W/ FOUNDATION PLAN SCALE: 1/4" = V-0" FOUNDATION PLAN NOTES: 1. EXTERIOR FOOTINGS SHALL BEAR A MIN OF V-6" BELOW ADJACENT GRADE. 2. FOOTINGS AND SLAB ON GRADE SHALL BEAR ON FIRM NATIVE SOIL OR COMPACTED STRUCTURAL FILL. 3. WHERE SLAB ON GRADE IS INDICATED, SLAB SHALL BE 4" THICK. SLAB SHALL BE POURED OVER A 10 MIL VAPOR BARRIER OVER 4" OF 5/8" CRUSHED ROCK. 4. REFER TO SHEET S4.1 FOR FOUNDATION DETAILS. 5. PLACE ALL REINFORCEMENT PER THE STRUCTURAL NOTES AND FOUNDATION DETAILS. REFER TO SHEET S1.1 FOR ADDITIONAL CONCRETE DETAILING REQUIREMENTS. 6. FOUNDATION LEVEL HOLDOWNS ARE SHOWN ON FRAMING PLANS. REFER TO HOLDOWN SCHEDULE ON SHEET S3.1 FOR HOLDOWN TYPES AND MAIN FLOOR FRAMING PLAN FOR HOLDOWN ANCHOR BOLT LOCATIONS. 7. REFER TO FRAMING PLANS AND SHEAR WALL SCHEDULE ON SHEET S3.1 FOR LOCATION OF SHEAR WALL ANCHOR BOLTS. ANCHORAGE AT NON -SHEAR WALLS SHALL BE PER STRUCTURAL NOTES. 8. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, WALL LOCATIONS, AND CONCRETE ROUGH OPENINGS WITH ARCHITECTURAL DRAWINGS AND NOTIFY ALL PARTIES OF ANY DISCREPANCIES. 2'-0" 0 2'-0" 7116 4'-0" ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 w N oll �AwT7iy wOF WAS,0 ` �ASL t S �IONAL W 20124 DESIGN: MTM DRAWN: LVW CHECK: MTM JOB NO: 23295.10 DATE: 1 2/20/23 RESUB Mar 22 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT LLl Z C) Q Z p N J W 0 O V) Z 00 W Z � < O LLJ Q V; a W 0 0 D N Z Z ZD m O Z to L� uz SHEET: S2ml C GI 4 r- 75 m 3 LINE OF FLOOR ABOVE EXISTING 5 1/8" x 9" RIM (INFILL) �(' - - - - - -,% GLB HDR I Ni (INFILL) 00 X O I N F- in _N rl X @j w EXISTING SUNKEN LIVING ROOM AREA j FJ1 (INFILL) TO BE INFILLED TO MAKE FLOOR FLUSH I EXISTING 44 POST TO BE REMOVED 3 IS Q =XIST 3 1/8" x 14" GLB (VIF) DEMOLISH EXIST CMU/BRICK CHIMNEY I & INFILL W/ WOOD STUDS TO MATCH I ADJACENT WALLS PER TYPICAL BEARING I -- WALL NOTES ON S1.1 I 00 0 X N I N � 1 X Lu M_ I I INVERTED SIMPSON MST48 STRAP HOLDOWN @ EA END HDR. INSTALL PER 1/S5.2 PT BM6 MAIN FLOOR FRAMING PLAN SCALE: 1/4" = V-0" TYPICAL FLOOR FRAMING PLAN NOTES: EXIST 3 1/8" x 14" GLB (VIF) II DJ1 II u II cv 0 I I N � II II - - - - - - w @ I I \� O �o 00 X N N w = 00 m PROVIDE (2) DT22Z DECK TIES @ (4) LOCATIONS SHOWN, EQUALLY SPACED, FOR EXTENT OF DECK. SEE DET 4/S5.2 1. FLOOR SHEATHING SHALL BE 3/4" PI 48/24 WITH 10d COMMON NAILS SPACED AT 6" OC AT ALL DIAPHRAGM BOUNDARIES, PANEL EDGES AND SHEAR WALLS AND 12" OC AT INTERMEDIATE FRAMING. FOR SHEATHING LAYOUT AND NAILING REFER TO DETAIL 2/S5.1. 2. COLUMNS AND BEARING WALLS SHOWN ON PLANS SHALL BE CONTINUED DOWN TO THE FOUNDATION UNLESS CARRIED BY A BEAM BELOW. 3. TYPICAL HEADERS AT BEARING LOCATION SHALL BE 46 HF#2 UNO SUPPORTED BY A MINIMUM OF (1) CRIPPLE STUD AND (1) FULL HEIGHT STUD. 4. CONTRACTOR SHALL HAVE THE OPTION TO DRILL A 1 1/2"0 HOLE CENTERED IN THE DEPTH AND AT THE THIRD POINT OF THE SPAN FOR ALL WOOD FLUSH BEAMS SHOWN ON THE PLAN. 5. COLUMNS NOT OTHERWISE SHOWN OR CALLED OUT ON PLAN SHALL BE (2) 2x STUDS. REFER TO DETAIL 3/S5.1 FOR CONSTRUCTION OF MULTIPLE STUDS. 6. UNLESS NOTED OTHERWISE ALL STUDS SHALL BE HF STUD GRADE AND SPACED AT 161, OC. 7. UNLESS NOTED OTHERWISE, ALL BEAM -TO -BEAM CONNECTIONS SHALL BE SIMPSON HU SERIES FACE MOUNT HANGERS W/ MAX NAILING. 8. O INDICATES HOLDOWN. REFER TO THE HOLDOWN SCHEDULE ON SHEET S3.1. L I I I I DEMOLISH EXISTING BRICK CHIMNEY PER ARCH DWG5 00 U X 0 Ln X @1 Lu --- 00 U X 0 N N X @ Lu i SIMPSON LSTA31 STRAP EA SIDE 0 BEAM EXISTING WALL TO BE REIVIC PER ARCH DWGS, USE SIMPSON STRONG -WALL WSWH24x9 PER DETAIL 7/S4.1 .1A J 1 JIIV IF JI IV UV u I IMIVVLI%J Z� Epoxy anchors shall be inspected by a certified third party inspection service. Provide all reports to city inspector 2x8 @ 16" OC EXIST POST TO REMAIN w C m LL o a -I a x C � a N G X w u3 p co w a C:)a X. 0 0= X w VERIFY/PROVIDE SIMPSON IU410 HANGER W/ (14) 1/4" 0 I I x 1 3/4" LONG TITEN TURBO I I CONCRETE ANCHOR INTO I I EXIST CONC STEM WALL I I II II I ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 ►' AwTxt; wOF 1PAS,0 65 L"��_S� �ti �IONAL W 20/ 24 Lu N EXIST 2x8 @ 16" OC Q F- Z O a — cn 0Lu m N z F- L 0 w a O U - - i LLI Q m fV fV N .� � fV fV m O L\ Q DESIGN: MTM DRAWN: LVW CHECK: MTM JOB NO: 23295.10 DATE: 1 2/20/23 RESUB Mar 22 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Z Q J CL V Z LLB C) Q Z 0 N Lil 0 0 L.L. Z 00 0) W w � � a 0 wQ 0 � � W N p D Z cy- 0 Z :m Q w W �LLI Z tM SHEET: S2m2 C GI rA USE SIMPSON STRONG -WALL WSWH24x10 RIPPED TO WALL HEIGHT PER DETAIL 7/S4.1 ATTACH FULL -HT POST TO TOP & CQ I + + + BOT WALL PLATES W/ (2) SIMPSON + + + A35, TYP @ LOCATIONS WHERE + + + + + PLATE HEIGHT EXCEEDS 9'-0" + + + + + +RJ1 ATTACH LOW HEADER TO FULL -HT + + + + 7T__j POSTS W/ SIMPSON A35 TOP & BOT cQ + + + + + + + o EA END, TYP AT LOCATIONS WHERE BM5 + + + + + + + x PLATE HEIGHT EXCEEDS 9 -0 DROPPED + + + + + + + SIMPSON CJT4Z + + + + + m CONCEALED BEAM + + + + + + HANGER BOTH ENDS OF + + + + BEAM, TYP (6) LOCATIONS + + + - BM1 HDR, HIGH & LOW +III + + cQ N BM5 TI- DROPPED 6 I 55.2 I R.11 51 6 \N Epoxy anchors shall be inspected by a certified third party inspection service. Provide all reports to city inspector 5 5 55.2 I + ii+ + + + + + + + + + + + + + + + + +II + + + + + + + + + + + + + + + + + + 2 SW3 2 BM1 HDR 2 SW3 Ill + + + + + + + +5 + + + + + + + + -. BM6 HIGH & LOW i I . + + + + + OPPE DR + + + + + + + + + + + + + + + + + + + + + + 10 + + + + + + + + + + + — + —� + SIMPSON CMSTC16 x 4'-0" LONG 5.2 PROVIDE 6x12 CONT BLKG �'� + + + + + + + + + + +___ + + +� + STRAP ACROSS TOP SHEATHING BTWN WALL STUDS & ATTACH + + + + + + + + + + + + + + + W/ (34) 0.162"0 x 2 1/2" NAILS BEAM TO BLKG W/ (2) 5/8" 0 x + + + + + + + + + + + _ _+ + + ++ PER DETAIL 2/S5.3 8" LAG SCREWS @ 16" OC + + + + + + + + + +--+-- + + 1 + + + + + + + + + + L_��_� + S5.3+ + + + + + + + + + + + + + + + + M5 + + + -PROPtPED + + + + + + + + + + .i + + + + + + + + + + + + � + + + + + + + + + + RJ3 + + + + + + + + + + + + SIMPSON CS14 x 4'-0" LONG + + + + + + + + + + + + CC O STRAP W/ (3) 0.148"0 x 2 + + + + + + + + + Cz 1/2" LONG NAILS INSTALLED + + + + + + + + + + + coPER DET 8/S5.1 + + + + + + + + + + _ + + + + + + + + + + BM5 + + + + + + + + + + DROPPED + + + + + + + + + + + + + + + + + + + 12 + + + + + + + S5.2 c� + + + + + + Lf j- + + + + +� ro + + + + + m V I BMSDKILIPPIED + + + + + + + + + + + + + c-I 5 + Op 55.2 i ------ ---- BM6 + SW6 ----- — SW6 SW6 I SW6 SW6 BM1 HDR 7 I L — j - — 7 S5.2 DEMOLISH EXISTING BRICK S5.2 CONNECT BEAM TO MST48 CHIMNEY PER ARCH DWGS DE 4x4 BLKG BTWN WALL STUDS FOR STRAP NAILING ROOF FRAMING PLAN SCALE: 1/4" = V-0" TYPICAL ROOF FRAMING PLAN NOTES: 1. REFER TO SHEET S5.2 FOR TYPICAL ROOF FRAMING DETAILS. 2. ROOF SHEATHING SHALL BE 1/2" PI 40/20 WITH 8d COMMON NAILS SPACED AT 6" OC AT ALL DIAPHRAGM BOUNDARIES, PANEL EDGES, SHEAR WALLS, COLLECTOR BEAMS OR JOISTS, AND BLOCKING INDICATED ON PLANS. NAILING AT INTERMEDIATE FRAMING SHALL BE 8d COMMON NAILS @ 12" OC. REFER TO DETAIL 2/S5.1 FOR SHEATHING LAYOUT AND NAILING. 3. TYPICAL HEADERS AT BEARING LOCATION SHALL BE 4x8 HF#2 LINO SUPPORTED BY A MINIMUM OF (1) CRIPPLE STUD AND (1) FULL HEIGHT STUD. 4. STUD WALL FRAMING SHALL BE 2x HF STUDS @ 16" OC FOR ALL STUD WALLS SHOWN ON THE PLAN. 5. REFER TO DETAIL 3/S5.1 FOR CONSTRUCTION OF MULTIPLE STUD COLUMNS. 6. COLUMNS AND BEARING WALLS SHOWN ON PLAN SHALL BE CONTINUED DOWN TO THE FOUNDATION UNLESS CARRIED BY A BEAM BELOW. 7. HOLDOWNS SHOWN ON ROOF FRAMING PLAN SHALL BE PLACED AT BASE OF WALLS SHOWN. 8. ATTACH ALL ROOF JOISTS TO WALLS BELOW WITH SIMPSON H2.5 HURRICANE TIES. 9. + + + + INDICATES OVER -FRAMING PER DETAIL 8/S5.2. HIGH & Low SW6 I I J 7 2'-0" 0 2'-0" 4'4" ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 �AwT7iy wOF 1PAS,0 ` �ASL t S �IONAL w N W 20124 m � L O O Q C) N m rl O Q DESIGN: MTM DRAWN: LVW CHECK: MTM JOB NO: 23295.10 DATE: 1 2/20/23 RESUB Mar 22 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Z Q La U O W N 0 !^ 0 W Z 0) 00 Z ��a Q LLJ V) LL. Lv N 0 D V_ Z LL. cy-m 0 w �W 0 w Z M SHEET: S203 SHEAR WALL SCHEDULE MIN FRAMING AT SHEAR WALL RIM JOIST OR SILL PLATE SILL PLATE ANCHOR SHEAR TYPE APA-RATED ADJOINING PANEL NAILING BLOCK CONN TO NAILING TO BOLT TO SLAB OR FOUNDATION CAPACITY SHEATHING EDGES (SEE NOTE 5) AT PANEL EDGES TOP PLATE RIM/BLKG FOUNDATION SILL PLATE SIZE (pLF) BELOW 15/32" 2x STUD 0.131"� x 2 1/2" LTP4 OR A35 0.131"� x 3" @ 3/4"� AB SW6 ONE SIDE AND BLKG @ 6" OC @ 24" OC 6" OC @ 5'-0" OC 2x 242 15/32" 2x STUD 0.131"0 x 2 1/2" LTP4 OR A35 0.131"0 x 3" @ 3/4"0 AB SW4 ONE SIDE AND BLKG @ 4" OC @ 20" OC 4" OC @ 5'-0" OC 2x 350 15/32" (2) 2x STUD AND 0.131"0 x 2 1/2" LTP4 OR A35 0.131"0 x 3" @ 3/4"0 AB SW3 ONE SIDE 2x FLAT BLKG @ 3" OC @ 15" OC 3" OC @ 4'-0" OC 2x 455 15/32" 3x STUD AND 0.131"0 x 2 1/2" LTP4 OR A35 0.131"0 x 3" @ 3/4"0 AB SW2 ONE SIDE 2x FLAT BLKG @ 2" OC @ 12" OC 2.5" OC @ 3'-0" OC 2x 595 15/32" (2) 2x STUD 0.131"0 x 2 1/2" LTP4 OR A35 0.131"0 x 3" @ 3/4"0 AB 2SW4 BOTH SIDES AND BLKG @ 4" OC @ 10" OC 2" OC @ 2'-6" OC 2x 706 15/32" (2) 2x STUD 0.131"0 x 2 1/2" LTP4 OR A35 0.131 x 3" 3/4"0 AB 2SW3 BOTH SIDES AND BLKG @ 3" OC @ 7.5" OC @ 1.5" OC @ 2'-0" OC 2x 910 15/32" 3x STUD 0.131"0 x 2 1/2" LTP4 OR A35 0.131 x 3" 3/4"O AB 2SW2 JOIST SCHEDULE MARK JOIST SPACING REMARKS FJ1 1 3/4" x 9 1/4" LVL 12" OC SEE NOTES 2 & 3 RJ1 14" TJI 560 24" OC SEE NOTE 3 RJ2 14" TJI 360 24" OC SEE NOTE 3 RJ3 14" TJI 110 24" OC SEE NOTE 3 DJ1 PT 2x12 DF#2 12" OC SEE NOTES 2 & 4 NOTES: 1. FOR JOIST HANGERS REFER TO THE LATEST SIMPSON STRONG -TIE CATALOG FOR ALL INSTALLATION REQUIREMENTS. 2. TIMBER JOISTS FRAMING INTO WOOD BEAMS SHALL USE LU-SERIES FACE MOUNT HANGERS. 3. PLYWOOD WEB JOISTS FRAMING INTO WOOD BEAMS SHALL USE ITS -SERIES TOP FLANGE HANGERS. 4. SOLID SAWN DECK JOISTS SHALL HANGER OFF THE WALL RIM USING LU SERIES FACE MOUNT HANGERS. 4= - ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 of ti O� 46548 �Z � sSIONAL 0�/ 20/ 24 W Q z O H a cn Z w oo NH z H W w O 0 a U M � Wrlj I­_ O O N m .� O Y Q DESIGN: MTM DRAWN: LVW CHECK: MTM JOB NO: 23295.10 DATE: 1 2/20/23 RESUB Mar 22 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT w U O W N 0 Z �wQ w Q w J w Q 0 D N Z w m _ Z rr� �w U � SHEET: S3ml WA Lu 00 La 0 COLUMN SCHEDULE COLUMN SIZE COLUMN SIZE MARK 2x4 WALL 2x6 WALL REMARKS Cl (2) 2x4 (2) 2x6 SEE NOTE 2 C2 (3) 2x4 (3) 2x6 SEE NOTE 2 C3 4x6 HF#1 4x6 HF#1 - C4 4x8 HF#1 6x6 DF#1 - NOTES: 1. REFER TO THE LATEST SIMPSON STRONG -TIE CATALOG FOR PRE -FABRICATED CONNECTION INSTALLATION REQUIREMENTS. 2. MULTIPLE STUD COLUMNS SHALL USE GRADE OF STUD INDICATED ON WALL FRAMING SCHEDULE. REFER TO DETAIL 3/55.1 FOR FABRICATION OF MULTIPLE STUD COLUMNS. 3. CONTRACTOR TO PROVIDE BLOCKING EQUAL TO COLUMN DIMENSIONS AT JOIST SPACE FOR COLUMNS CONTINUING TO FOUNDATION. HOEDOWN SCHEDULE MARK TYPE MIN CHORD STUD NAILS OR BOLTS ANCHOR BOLT CAPACITY (LB) SIZE (SEE NOTE 4) MST48 (2) 2x (17) 16d EA END - 3,640 2 HDU4 (2) 2x (10) SIDS 1/4" x 2 1/2" SCREWS 5/8"� 3,285 NOTES: 1. REFER TO THE LATEST SIMPSON STRONG -TIE CATALOG FOR ADDITIONAL INSTALLATION REQUIREMENTS. 2. REFER TO DETAIL 2/55.2 FOR INSTALLATION OF MST FLOOR TO FLOOR STRAPS. REFER TO DETAILS 1/55.2 FOR CONNECTION OF STRAP TO BEAM BELOW. 3. INSTALL HD HOEDOWNS AT FOUNDATION WALLS OR THICKENED SLAB FOOTINGS PER DETAIL 2/54.1. 4. AT ALL HOEDOWN CHORDS, PROVIDE PANEL EDGE NAILING PER SHEAR WALL SCHED. BEAM SCHEDULE MARK BEAM REMARKS HANGER AS REQ'D (UNO) BM1 4x10 HF#2 - HU48TF BM2 (3) 1 3/4" x 7 1/4" LVL SEE NOTE 7 HU68TF BM3 3 1/2" x 9 1/4" 2.0E PARALLAM PSL SEE NOTE 6 HWU3.56/9.25 BM4 5 1/4" x 11 1/4" 2.0E PARALLAM PSL SEE NOTE 6 GLTV5.50/11.25 BM5 5 1/2" x 12" 24F-V4 GLB SEE NOTE 6 GLTV5.50/11.25 BM6 3 1/2" x 13 1/2" 24F-V4 GLB - GLTV5.514 BM7 PT 6 3/4" x 13 1/2" 24F-V4 GLB SEE NOTE 3 - BM8 3 1/2" x 14" PSL SEE NOTE 6 - NOTES: 1. REFER TO THE LATEST SIMPSON STRONG -TIE CATALOG FOR HANGER INSTALLATION INFORMATION. 2. REFER TO FRAMING PLANS AND NOTES FOR SUPPORTS AT BEAM ENDS. HANGERS CALLED OUT IN PLAN NOTES SUPERCEDE THOSE LISTED IN THIS TABLE. 3. ALL BEAMS EXPOSED TO WEATHER OR IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE TREATED. 4. REFER TO PLAN NOTES FOR BEAMS &HEADERS AT BEARING LOCATIONS THAT ARE NOT CALLED OUT. 5. USE SIMPSON HUCTF SERIES CONCEALED FLANGE TOP FLANGE HANGER AT LOCATIONS WHERE OFFSET HANGERS WOULD OTHERWISE BE REQUIRED. 6. IF PSL SUPPLIER DOES NOT STOCK EXACT DEPTH OF BEAMS LISTED, CONTRACTOR SHALL COORDINATE WITH SUPPLIER TO RIP BEAMS TO EXACT DIMENSIONS LISTED IN TABLE. 7. SISTERED BEAM SHALL BE CONNECTED USING (2) ROWS OF 16d @ 12" OC STAGGERED. C GI 4"0 PERFORATED PVC PIPE PER LOCAL CODES WITH 6" OF 3/4"-1" WASHED ROCK ALL AROUND, WRAPPED IN NON -WOVEN GEOTEXTILE FABRIC. SLOPE TO DRAIN 1/8" PER V-0" MIN. TURN DOWN PERFORATIONS AS SHOWN O\0)"°jo 0000°000O O OO°°000d LINE OF MAX EXCAVATION. /A1 IF SOIL IS OVER EXCAVATED, 1 REPLACE WITH LEAN MIX CONCRETE. FIRM BEARING SOIL OR COMPACTED STRUCTURAL FILL TYPICAL FOOTING DRAIN SCALE: 1" = V-0" NOTE: WHERE CONCRETE WALL WITH HT > T-0" EXISTS, ROD MAY EXTEND 24" MIN INTO WALL W/ NUT & WASHER AS SHOWN COUNTERSINK ADDITIONAL END STUD AS REQ'D THREADED ROD AS REQ'D FOR HOLDOWN W/ NUT AND WASHER AT BASE. EXTEND ROD INTO FTG, TYP UNO TOP OF FTG HOLDOWN DETAIL SCALE: 1" = V-0" HOLDOWN CHORD PER PLAN & HOLDOWN SCHEDULE CRIPPLE STUD AT OPENING AS REQ'D PER PLAN &DETAILS NOTE: SHEAR WALL PER EXTEND THREADED ROD BETWEEN PLAN AND SCHED JOISTS INTO STEM WALL BELOW. PROVIDE ROD COUPLER IF REQ'D. THREADED ROD AS HOLDOWN PER PLAN AND SCHED REQ'D PER PLAN AND HOLDOWN SCHEDULE. INSTALL W/ HILTI HIT-HY 200 EPDXY EXISTING CONCRETE STEM WALL TOP OF EXISTING FOOTING SHEAR WALL PER PLAN AND SCHED HOLDOWN PER PLAN AND SCHED SQUASH BLKG TO MATCH HOLDOWN CHORD ABOVE u HOLDOWN DETAIL (EXIST FOOTING SCALE: 1" = V-0" Epoxy anchors shall be inspected by a certified third party inspection service. Provide all reports to city inspector NOTE: RAISE STEM WALL AS REQ'D AT PERIMETER AREAS WHERE NEEDED DUE TO CIVIL GRADES. STUD WALL PER SILL PL AND AB DIA FRAMING PLAN NOTES AND SPACING PER SHEAR WALL SCHED SHEATHING AND NAILING PER PLAN AND SHEAR (2) #4 CONT TOP WALL SCHEDULE X #4 @ 15" OC EA WAY CENTERED IN WALL N SLAB ON GRADE AND FINISHED GRADE 0 0 SUBGRADE PER FOUNDATION PLAN (�p000° —X X X— ]o00 oo z OO ° o °� ° 00 0 00 0 0o c 0 o� 0 00 0 vo DpoO °�0 O°0 Do0 0�00°O OOO O 0 w _ U V) w a FOOTING DRAIN / PER DETAIL 1 / 8 m u / ALT HOOK ol SIZE & REINF ol AS SHOWN PER PLAN = a w 0 ®— - -0 TYPICAL STEM WALL DETAIL SCALE: 1" = V-0" NOTE: AT LOCATIONS WHERE POST IS LOCATED WITHIN STUD WALL, POST BASE NOT REQ'D. BEAR POST ON SILL PLATE & FASTEN W/ (4) 10d TOE NAILS SIMPSON ABW POST BASE W/ 1/2"0 x 6" SIMPSON TITEN HD SCREW ANCHOR POST PER PLAN #3 x V-6" @ 12" OC DOWELS EA SIDE, DRILL & EPDXY W/ SIMPSON SET-XP EXIST SLAB ON GRADE 4 d II Q u a 0 0 • wU o Cr J � M U SIZE & REINF PER PLAN SECTION 6 SCALE: 1" = V-0" HSS COL PER PLAN OF STUD WALL D I I o I I m (D I ICI FINISHED GRADE _1 al lyyTI I l �O 0 0.0 00 O ° O Oo° °?o °0 0o0- O 0°000°00 O0 °0°° OO ° ° O O O oQ0 0O o PL 1/2" x 4 1/2" x '0-9" W/ (2) 5/8"0 x 6" AB'S SLAB ON GRADE AND SUBGRADE PER FOUNDATION PLAN X X- o`O °°0 °0000 — — — — — ®— NOTE: FOR NOTES & INFO NOT SPECIFICALLY CALLED OUT REFER TO DETAIL 4. FOUNDATION DETAIL SCALE: 1" = V-0" ATTACH TO TOP PLATE PER MFR STANDARD STRONG -WALL HIGH STRENGTH WOOD SHEARWALL AT 2ND FLOOR SIMPSON A34 EA SIDE WSWH SHEAR TRANSFER PLATE WSWH MULTI -STORY KIT HOLDOWN (INCLUDED W/ WSWH-TSS_KT) STANDARD STRONG -WALL HIGH STRENGTH WOOD SHEARWALL AT 1ST FLOOR PROVIDE SIMPSON SSWABI ANCHOR BOLTS PER MFR. INSTALL INTO EXISTING FOUNDATION PER DETAIL 3 FAI ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 �Ann; OF WAS$ � � �IOIVAL W 20/ 24 w z Q o z — cn Lu 0 m N z F- Lu W w O _ 0 a U oQ o � M � LJ O O Q N m r­1 O Y Q DESIGN: MTM DRAWN: LVW CHECK: MTM JOB NO: 23295.10 DATE: 1 2/20/23 orm OVA OWM orm—OrM gw1A_ gw1A_ gw1A_ gw1A_ gw1A_ Own Own Own Own Own —WA i Wm_ OVA- RESUB Mar 22 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT W Q C) F_ Z O N W w 0 O 0 W Z � 0) W Z � O Lu Q< V; a W 0 0 D N Z Z D m Z M La LL_ ! SHEET: S mi STAGGER NAILS ON EA SIDE OF PANEL JOINT AS REQUIRED PER SHEAR WALL SCHED -n-------�- - I.1 I•I II II II II HEADER PER PLAN II II II II I I I I I.1 I•I •11 II II I I I I I I I II II 1 I 1 CRIPPLE STUDS PER .11 I I I I I j I I I I I PLAN; DO NOT CUT IIII I.1 I•I 1. AWAY MATERIAL FROM I I• I I I I I I I• CRIPPLE STUDS j I I I I I I II II 1 1.1 1 I I I I 1 •I I 1�1 I I I I FULL -HEIGHT III II II I I•I I I•j 1.1 I •1 II 011.1 HOLDOWN CHORD 1 1 1 1 1 1 I I 1111 II II 11.11 11 I I I •1 11 ICI II 1 1 11 1111 II II 1 1 1 1 1.1 I.I 11.11 II II I.I II 1 1 I.I I'I II 1111 11 I I 1111 II II 11.11 11 I I 1 .1 11 ICI II 1 1 11 1111 II II 1 1 1 1 1.1 I.I 11.11 II II I.I II 1 1 I.I I•I 11 II II II Ij 1 •I II I.I AB W/ SIMPSON BP 1 1 I I 11 1 1 1 •1 PL WASHER, TYP I I I•I I I.1 I. 1 1 I I II II I 1 1 11 I •1 1I I�1 PT SILL PL PER SHEAR I I I I1 WALL SCHED I•I •1 1 1 1 A I.I II 1-------L I'1 1I - J1 II �� II _ -J 1 1-1 1 L CONCRETE FOOTING OR P/T SLAB NOTES: 1. REFER TO STRUCTURAL NOTES FOR ADDITIONAL INFORMATION. 2. FOR SHEAR WALLS WHERE NO HOLDOWNS ARE SPECIFIED THE FIRST AB SHALL BE LOCATED NOT MORE THAN V-0" AND NOT LESS THAN (7) BOLT DIAMETERS FROM END OF WALL. TYPICAL SHEAR WALL DETAIL SCALE: 3/4" = V-0" — — — — — — — — — — — — — — — — — — — — -------r-l-----T- I'I I'I I'I 1•I I I•I II II II II III II II II �1 11• II II II II II II II III II II II II III I'I I'I I'I 1•I I I. II II II II I 1 I II II �1 III FRAMING AT ADJOINING I I 11'I I I PANEL EDGES PER SHEAR I I I I'I WALL SCHED I I II iI I III II II II II 1�.1 II II II I II II II II 1'1 1.1 1.1 1• II II II II II ,J L ;-- ;--j•I.- ;-- ;-i F•-- - I I I•I I•I II II II II II II II II II II II II I I I•I I•I II II II II II II II II II ff ft II II II I I I•I I•I II II II II II II II II II II II II I I I•I I•I - I'I II II II II II • _1L------LL------_L II II I II II II II II II II II II 1L__4_ _ 1L- __1 � II —AIL II II AB SIZE AND SPACING l� PER PLAN AND SHEARQL3 WALL SCHEDULE, TYP RIM BOARD OR BLOCKING 11 -J 1 1-1 1 L -J 1 1-1 1 L -J 1 1-1 1 C EDGE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES, TYP 0.131"0 x 3" NAILS @ 9" OC (2) ROWS OF 0.131" 0 x 3" NAILS @ 9" OC STUD WALL PER FRAMING PLAN NOTES, TYP EDGE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES, TYP SHEATHING (OR GWB) AND NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES, TYP A. CORNER INTERSECTION B. 'T' INTERSECTION TYPICAL WALL INTERSECTION DETAIL SCALE: 1" = V-0" 2x6 STUD @ 2x4 CROSS WALL 2x8 STUD @ 2x6 CROSS WALL EDGE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES, TYP 0.131"0 x 3" NAILS @ 9" OC STUD WALL PER FRAMING PLAN NOTES, TYP SHEATHING (OR GWB) AND NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES, TYP PANEL EDGE NAILING PER SHEAR WALL SCHEDULE, TYP PANEL EDGE NAILING INTO HOLDOWN CHORDS, TYP INTERMEDIATE NAILING @ 12" OC SHEATHING PER PLAN AND SHEAR WALL SCHEDULE HOLDOWN CHORD PER SCHEDULE. REFER TO TYPICAL BUILT-UP COLUMN DETAIL ADDITIONAL END STUD IF REQUIRED TO PROVIDE COUNTERSINK FOR HOLDOWN BOLTS HOLDOWN ANCHORAGE PER PLAN AND SCHEDULE SIMPSON CNW COUPLER 1/2" TO NUT W/ SIZE TO MATCH SHEATHED EDGE HOLDOWN ANCHORAGE PANELEDGE NAILING PER SHEAR WALL SCHED CONTINUE HOLDOWN CHORD TO FOUNDATION NOTE: SUPPORTS AT SOLID POSTS SIM BEAM PER AND SCHE SIMPSON LTP4 C A35 FRAMIP ANCHOR EACH SI[ OF BEA SOLID OR MULT STUD COLUMN PER P,_ CONCRETE STEM WALL CONCRETE FOOTING PARALLEL TO STUD WALL PLATE WASHER PER SHEAR WALL SCHED SECTION A -A SCALE: 1 1/2" = V-0" JOIST DIRECTION PER PLAN STUD WALL TYPICAL FLUSH BEAM SUPPORT DETAILS SCALE: 1" = V-0" NOTE: STAGGER SHEATHING AS SHOWN. INTERMEDIATE FRAMING MEMBERS SHEATHING PANEL, TYP II II I I CONTINUOUS PANEL EDGES II II I I II I I 2x OR 3x BLOCKING ONLY IF BLOCKED DIAPHRAGM IS SPECIFIED FRAMING MEMBERS W/ SPACING PER PLAN SUPPORTED PANEL EDGES II II I II II II II JL_J� DIAPHRAGM BOUNDARY (SHEAR WALL, BEAM, OR DRAG STRUT) TYPICAL FLOOR/ ROOF SHEATHING DETAIL SCALE: NTS (2) ROWS OF (8) 0.131"o x 3" 2 1/4" END NAILS @ 3" OC EA SIDE OF DISTANCE, TYP SPLICE AND (2) @ 9" OC ELSEWHERE W/ 1 1/2" EDGE DISTANCE 3" OC SPACING TOP CHORD SPLICE J AT LOCATIONS WHERE IT IS NOT POSSIBLE BOTTOM TO INSTALL THE SPECIFIED 0.131" 0 CHORD SPLICE NAILS, THE CONTRACTOR SHALL SPLICE INSTALL SIMPSON CS20 STRAPS EA SIDE OF WALL AT SPLICE. INSTALL EA STRAP W/ (12) 10d AT EA END. WHERE BOTH PLATES ARE CUT, INSTALL CS20 STRAPS AT EA PLATE AND EA SIDE OF THE WALL. 6'-0" MIN BETWEEN SPLICES SPLICES TO OCCUR AT CENTER OF VERTICAL STUDS 0 TOP CHORD SPLICE BOTTOM CHORD SPLICE ��I����OP PLATE SPLICE DETAIL SOLID STUD COLU- BEAM PER PLAN AND SCHEDULE SIMPSON A35 EACH SIDE OF BEAM i cn = O �w J U- � a PERPENDICULAR TO STUD WALL STU D WALL ADJACENT NAILS IN A ROW ARE TO BE DRIVEN FROM OPPOSITE SIDES, TYP FOR 2x4 STUDS, PROVIDE SINGLE ROW OF NAILS STAGGERED EA SIDE WITH 1 1/2" EDGE DISTANCE. FOR 2x6 STUDS, PROVIDE (2) ROWS OF NAILS SPACED AT 2 1/2" W/ 1 1/2" EDGE DISTANCE 9" OC MAX SPACING BETWEEN ADJACENT NAILS IN A ROW 0.131"0 x 3" NAILS, TYP (5) STUDS MAX TO BE USED FOR BUILT-UP COLUMNS TYPICAL BUILT-UP STUD COLUMN DETAIL SCALE: 1" = V-0" SIMPSON A35 (ONLY REQUIRED AT EXTERIOR HEADERS GREATER THAN 6' SPAN) (6) 0.131"0 x 3" NAILS TYPICAL STUDS NAILING PER TYP BUILT-UP STUD COLUMN DETAIL SHEATHING W/ BOUNDARY NAILING PER FRAMING PLAN NOTES SIMPSON LTP4 PER PLAN STUD WALL SHEATHING PER PLAN & SHEAR WALL SCHEDULE AT HOLDOWNS: PROVIDE FULL HT HOLDOWN CHORDS PER HD SCHED. OTHERWISE: (1) 2x FULL HT TYPICAL HEADER DETAIL SCALE: 1" = V-0" TYPICAL DRAG STRUT DETAIL SCALE: 1" = V-0" TYP DOUBLE TOP PLATE BEAM OR HEADER PER PLAN AND NOTES CRIPPLE STUDS PER PLAN AND COLUMN SCHEDULE OR STRUCTURAL NOTES wILAN & )ULE ENGIN6E RING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 pF WASs 46548 \L � �10NAL W 2012� w Q z O H a Z w cc� cm � vim, F- z w LiJ w O d U m 1:* W � � O O Q C) N M r-I O Y Q DESIGN: MTM DRAWN: LVW CHECK: MTM JOB NO: 23295.10 DATE: 1 2/20/23 RESUB Mar 22 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT w U O W N 0 0 V Z 0) ww Q cy- , w Q 0 w N p D Z 0 m Lw Z M y:iixims, S501 SHEAR WALL PER PLAN HOLDOWN STRAP PER PLAN, FIELD BEND AROUND BEAM BEAM PER PLAN (DIRECTION VARIES) Ia1011001 1WTI LTA JOIST P (DIRECTION SHEAR WALL PER PLAN HOLDOWN STRAP PER PLAN, FIELD BEND AROUND BEAM CONTINUOUS RIM HEADER BEAM PER PLAN HEADER TYPICAL STRAP HOLDOWN TO WOOD BEAM SCALE: 1" = V-0" DIAPHRAGM BOUNDARY NAILING PER ROOF FRAMING PLAN NOTES WEB BLKG PER JOIST MFR SIMPSON A35 CLIPS @24"OCR PANEL EDGE NAILING PER PLAN AND SHEAR WALL SCHEDULE J SHEATHING PER PLAN AND SHEAR WALL SCHEDULE OVERHANG PER ARCH J � OZ. mc� J � Q U F zoc 0 z c z 2 c 0 c 0 0 = a - FULL DEPTH BLKG RIPPED TO MATCH SLOPE OF ROOF ROOF SHEATHING AND NAILING PER ROOF FRAMING PLAN NOTES CHORD SIZE PER HOLDOWN SCHEDULE SIMPSON STRAP WITH FASTENERS PER HOLDOWN SCHEDULE INSTALL MAX NAILING INTO RIM OR BLOCKING WHERE POSSIBLE JOIST DIRECTION PER PLAN FILL JOIST SPACE WITH FULL DEPTH BLOCKING TO MATCH DIMENSIONS OF STUD COLUMN ABOVE TYPICAL STRAP HOLDOWN DETAIL SCALE: 1" = V-0" BEVELED BLOCK BELOW EA ROOF JOIST (FULL BEARING) W/ (2) 10d INTO TOP PLATE ROOF JOIST PER PLAN SIMPSON H8 TIE AT EACH JOIST STUD WALL PER PLAN & NOTES ROOF RAFTER CONNECTION (BEARING SCALE: 1" = V-0" STUD WALL PER PLAN AND NOTES BLOCKING (MATCH WALL THICKNESS) W/ A34 CLIP EA END, TOP & BOT SIMPSON A35 DIAPHRAGM BOUNDARY CLIPS @ 24" OC ROOF SHEATHING & NAILING PER NAILING PER ROOF FRAMING ROOF FRAMING PLAN NOTES PLAN NOTES ROOF SHEATHING AND NAILING PER ROOF FULL DEPTH BLKG RIPPED TO FRAMING PLAN NOTES MATCH SLOPE OF ROOF I — WEB BLKG PER JOIST MFR EA SIDE OF WEB (2'-0" LENGTH) - BEAM PER PLAN - OVERHANG PER PLAN WOOD STUD WALL AND/OR POST (BEYOND) - ROOF JOISTS PER PLAN ROOF JOIST PER PLAN SLOPED HU OR LRUZ HANGERS SIMPSON H2.5A 2x LEDGER W/ (2) ROWS TIE AT EACH JOIST OF 1/4"0 x 5" SIDS BEVELED BLOCK BELOW EA SCREWS @ 12" OC ROOF JOIST (FULL BEARING) SECTION AT LOW ROOF SCALE: 1" = V-0" DIAPHRAGM BOUNDARY NAILING PER ROOF FRAMING PLAN NOTES WEB BLKG PER JOIST MFR SIMPSON A35 CLIPS @24"OC� PANEL EDGE NAILING PER PLAN AND SHEAR / WALL SCHEDULE J SHEATHING PER PLAN AND SHEAR WALL SCHEDULE OVERHANG PER ARCH STUD WALL PER PLAN AND NOTES SILL PLATE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES SHEATHING AND 2x WOOD BLOCKING NAILING PER PLAN SILL PLATE NAILING PER SHEAR 1 1/2" LSL RIM Af WALL SCHED WOOD JOISTS PER PLAN -/ PROVIDE PANEL EDGE NAILING PER SHEAR WALL SCHEDULE AT TOP PLATE 11 2x4 BLOCKING OR A35 (PER SW SCHED) BETWEEN BLOCKING AND \ TOP PLATE AT SHEAR WALLS ONLY I.1 EXIST STUD WALL CANTILEVERED JOIST FRAMING DETAIL SCALE: 1" = V-0" FULL DEPTH BLKG RIPPED TO MATCH SLOPE OF ROOF ROOF SHEATHING AND NAILING PER ROOF FRAMING PLAN NOTES BEVELED BLOCK BELOW EA ROOF JOIST (FULL BEARING) W/ (2) 10d INTO TOP PLATE ROOF JOIST PER PLAN SIMPSON H8 TIE AT EACH JOIST STUD WALL PER PLAN & NOTES ROOF RAFTER CONNECTION (BEARING SCALE: 1" = V-0" CROSS BEAM PER PLAN AND SCHED BEAM PER PLAN 1 1/2" AND SCHED TYP A SIMPSON WPU TOP FLANGE HANGER 3/4"0 A307 BOLT, TYP 14 1/4" SHIP" Ir DEn'n SIMPSON FLANG BEAM TYP 1 4 A HSS COL PER PLAN SIDE PL 1/4 x 8 x V-0" BEARING PL 3/4 x 8 x 1'-C CANOPY COLUMN CONNECTION V / SCALE: 1" = V-0" DIAPHRAGM BOUNDARY NAILING PER ROOF FRAMING PLAN NOTES 2x FLAT OUTLOOKER @ 24" OC, 24" MAX OVERHANG FULL DEPTH LSL RIM. NOTCH AT OUTLOOKERS 1 1/2" LSL BLKG @ 4'-0" OC SECTION A -A SHEATHING PER PLAN AND SHEAR WALL SCHEDULE BEAM PER PLAN AND SCHED NOTE: FOR NOTES AND DETAILS NOT CALLED OUT REFER TO TYPICAL STUD WALL FRAMING DETAILS. DECK SECTION SCALE: 1" = V-0" (4) 10d NAILS @ BLKG ROOF SHEATHING AND NAILING PER ROOF FRAMING PLAN NOTES SIMPSON A35 CLIPS @ 24" OC SIMPSON A35 CLIPS EA BLOCK FULL -HEIGHT STUD WALL PER PLAN & NOTES (3) 10d NAILS EA END ROOF JOIST PER PLAN ROOF RAFTER CONNECTION (NON -BEARING SCALE: 1" = V-0" EAM PER PLAN kND SCHED IDE PLATES EARING PLATE PANEL EDGE NAILING PER SW SCHED DIMENSION PER ARCH DRAWINGS 2x CONT LEDGER W/ (2) 1/4"o x 3" SDS SCREWS @ 16" OC - PRE-ENGINEERED RAILING SYSTEM & ATTACHMENTS TO STRUCTURE BY OTHERS DECK JOIST PER PLAN NOTE: PROVIDE HANDRAIL PER ARCH AT SIM SECTION NO WALL AT SIM SECTION SILL PL NAILING PER SW SCHED JOIST PER PLAN SOFFIT AND DRAINAGE HSS COLUMN SYSTEM BY OTHERS 2x4 BLKG OR A35 BETWEEN WALL TOP PLATE AND RIM STUD WALL PER PLAN DECK WALL SECTION SCALE: 1" = V-0" SOFFIT AND DRAINAGE SYSTEM BY OTHERS 2x6 CONTINUOUS RIDGE BOARD, TYP 2x NAILER W/ (2 NAILS @ EACH RA NEW 2x6 STUD WALL PER PLAN EXIST OR PROPOSED PLYWOOD FLOOR SHEATHING PER PLAN NOTES EXIST 2x10 FLOOR JOISTS (FIELD VERIFY) 2x WOOD BLKG @ 4'-0" OC MAX (2) SIMPSON DTT2Z DECK TIES PER PLAN W/ 1/2"0 A36 THREADED ROD EXIST 2x FULL DEPTH LEDGER (FIELD VERIFY) EXIST 2x4 STUD WALL 2x6 RAFTERS @ 24" OC STICK FRAMED OVERFRAMING DETAIL SCALE: NTS OVERFRAMING SHEATHING & NAILING PER SW SCHED WEB FILLER PER / JOIST MFR J SLOPED HU OR LRUZ HANGERS 2x4 STUD WALL BEYOND. POCKET BEAM IN WALL SECTION / SCALE: 1" = V-0" SHEATHING AND NAILING PER PLAN NOTES 1 1/2" CONT LSL RIM 2x4 PONY WALL SILL PL NAILING PER SW SCHED BEAM PER PLAN I -JOISTS PER PLAN AND SCHEDULE NOTE: FOR NOTES & INFO NOT SPECIFICALLY CALLED OUT REFER TO DETAIL 7 & 8. 4= I ENGINES RING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 asL�� ti ONAL W 20124 w J N Z Q O I_ a Z N w O m CL V) H Z _ F___ w U 2 W w O 0 a U m rlj 00 Q N m .� O Y DESIGN: MTM DRAWN: LVW CHECK: MTM JOB NO: 23295.10 DATE: 1 2/20/23 RESUB Mar 22 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT W U 0 W N ID 0 � z � La w>a W LL1 Q 0 W N 0 D z p m OW z tM SHEET: S5m2 ROOF SHEATHING AND NAILING PER ROOF FRAMING PLAN NOTES SW6 SHEATHING AND NAILING PER SW TABLE 2x4 STUD WALL SECTION SCALE: 1" = V-0" PANEL EDGE NAILING PER ROOF FRAMING PLAN NOTES 2x4 BLI<G @ PONY WALL I -JOIST PER PLAN 2x4 PONY WALL W/ SLOPED DOUBLE TOP PLATE TO MATCH ROOF SLOPE SILL PL NAILING PER SW TABLE NOTE: • FOR NOTES & INFO NOT SPECIFICALLY CALLED OUT REFER TO TYPICAL ROOF • FRAMING DETAILS. SECTION SCALE: 1" = V-0" =-4m ENCINEE RING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 �1w 6y WAS 46548 ' v ONAL w N W 2012� DESIGN: MTM DRAWN: LVW CHECK: MTM JOB NO: 23295.10 DATE: 1 2/20/23 RESUB Mar 22 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT V I J W W 0 U Z O w N (� clZ00 Z w w � Q w Q �:: cr) = cri �` LLI N Z 0 D m o O � O W � Z to W SHEET: S503