REV1 APPROVED BLD BLD2023-0343+PLANS+5.17.2023_3.27.59_PM+3552161INTERNATIONAL BUILDING CODE (IBC) 2018
LOADINGS
ROOF SNOW LOAD ..................................................... 25 PSF
RESIDENTIAL LIVE LOAD ...................................... 40 PSF
DECK, BALCONY, PLATFORM LIVE LOAD ....................... 60 PSF
RETAIL, CORRIDOR, LOBBY, WALKWAY LIVE LOAD ............. 100 PSF
OFFICE LIVE LOAD......................................................................... 50 PSF
PARKING LIVE LOAD .................................. 40 PSF & 3000# WHEEL LOAD
WIND CRITERIA
BUILDING CLASSIFICATION ............................... II
ULTIMATE WIND SPEED (3 SEC GUST) MPH...... 98 MPH
WIND EXPOSURE ........................................... B
TOPOGRAPHIC FACTOR, Kzt................. 1.0
SEISMIC CRITERIA
SEISMIC RISK CATEGORY ...............................
SPECTRAL RESPONSE COEFFICIENT, Ss .... 0.8
SPECTRAL RESPONSE COEFFICIENT, S1 .... 0.4
SEISMIC SITE CLASS ................................. D
SEISMIC DESIGN CATEGORY ............................... D
DUCTILITY (R) ............................... 6.5
METHOD AND BASE SHEAR ............................... ELF
FOUNDATION DESIGN INFORMATION
1. STRUCTURAL DESIGN COMPLIES WITH SOILS REPORT PRODUCED BY:
XX
DEEP FOUNDATION SYSTEM: XX
FOOTING BEARING PRESSURE: 2000 PSF
ACTIVE/PASSIVE EARTH PRESSURE: 35 PCF
2. SUBGRADE PREPARATION, DRAINAGE PROVISIONS, AND OTHER RELEVANT SOIL
CONSIDERATIONS ARE TO BE IN ACCORDANCE WITH SAID SOILS REPORT.
GENERAL CONDITIONS
1. THE CONTRACTOR SHALL EXAMINE THE STRUCTURAL DRAWINGS AND SHALL NOTIFY THE
STRUCTURAL ENGINEER IN WRITING OF ANY DISCREPANCIES HE MAY FIND BEFORE PROCEEDING
WITH THE WORK. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS AND SITE
CONDITIONS BEFORE STARTING WORK.
2. ALL OMISSIONS OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE WORKING
DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND THE STRUCTURAL
ENGINEER BEFORE PROCEEDING WITH ANY WORK SO INVOLVED.
3. SPECIFIC NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND
TYPICAL DETAILS. WHERE THE NOTES, DRAWINGS, AND/OR SPECIFICATIONS DIFFER, THE MORE
STRINGENT REQUIREMENT SHALL APPLY.
4. IF A SPECIFIC DETAIL IS NOT SHOWN FOR ANY PART OF THE WORK, THE CONSTRUCTION
SHALL BE THE SAME AS FOR SIMILAR WORK.
5. WORKING DIMENSIONS SHALL NOT BE SCALED FROM PLANS, SECTIONS, OR DETAILS ON
THESE DRAWINGS.
6. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECT AND THE STRUCTURAL
ENGINEER OF ANY CONDITION THAT, IN HIS OPINION, MIGHT ENDANGER THE STABILITY OF THE
STRUCTURE OR CAUSE DISTRESS TO THE STRUCTURE.
7. THE CONTRACTOR SHALL SUPERVISE AND DIRECT HIS WORK AND HE SHALL BE SOLELY
RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND
PROCEDURES. PROVIDE ADEQUATE SHORING AND BRACING OF ALL STRUCTURAL MEMBERS
DURING CONSTRUCTION. NOTIFY ENGINEER OF ALL FIELD CHANGES PRIOR TO INSTALLATION.
8. REFER TO THE ARCHITECTURAL DRAWINGS FOR INFORMATION NOT COVERED BY THESE
GENERAL NOTES OR THE STRUCTURAL DRAWINGS.
9. ALL CONSTRUCTION SHALL BE DONE WITH MATERIALS, METHODS, AND WORKMANSHIP
ACCEPTED AS GOOD PRACTICE BY THE CONSTRUCTION INDUSTRY AND IN CONFORMANCE WITH
THE PROVISIONS OF PREVAILING CODE EDITION OF THE "INTERNATIONAL BUILDING CODE" (IBC)
AND STANDARDS REFERENCED THEREIN.
10. PIPES, DUCTS, SLEEVES, OPENINGS, POCKETS, CHASES, BLOCK -OUTS, ETC., SHALL NOT
BE PLACED IN SLABS, FOUNDATIONS, ETC., NOR SHALL ANY STRUCTURAL MEMBER BE CUT FOR
SUCH ITEMS, UNLESS SPECIFICALLY DETAILED ON THESE STRUCTURAL DRAWINGS.
11. STRUCTURAL ENGINEER WILL PERFORM PERIODIC STRUCTURAL OBSERVATION DURING
CONSTRUCTION OF STRUCTURAL MEMBERS AND REVIEW OF REQUESTED SUBSTITUTIONS
SHOP DRAWINGS AND SUBMITTALS:
THE FOLLOWING ITEMS SHALL BE SUBMITTED FOR REVIEW PRIOR TO FABRICATION OR INSTALL.
CONTRACTOR SHALL ALLOW SUFFICIENT TIME FOR STRUCTURAL ENGINEER'S REVIEW:
1. SLAB CONDUIT LAYOUT
2. CONCRETE OR MASONRY MIX DESIGN
3. CONCRETE OR MASONRY REINFORCING
4. CONCRETE POST TENSIONING SYSTEM
4. FORMWORK
5. CONCRETE CURING PROCEDURE
6. STRUCTURALSTEEL
7. STUD RAILS AND HEADED ANCHOR EMBED PLATES
8. WOOD FRAMING/ LUMBER PACKAGE
9. SEISMIC HOLDOWN SYSTEM SUCH AS SIMPSON PRODUCTS
DEFERRED SUBMITTALS:
THE FOLLOWING ITEMS SHALL BE SUBMITTED FOR REVIEW PRIOR TO FABRICATION OR INSTALL
1. ANCHORAGE OF NONSTRUCTURAL COMPONENTS
2. CANOPIES AND BALCONIES
3. CURTAIN WALLS
4. EXTERIOR CLADDING
5. HANDRAIL AND GUARDRAIL ASSEMBLIES
6. HEAVY HUNG FIXTURES
7. MECHANICAL EQUIPMENT SUPPORT, SEISMIC ANCHORAGE OR RESTRAINING SYSTEM
8. STEEL STAIRS
9. WINDOW WASHING AND FALL PROTECTION SYSTEMS
LUMBER. ANCHOR BOLTING AND NAILING SPECIFICATIONS
1. MEET REQUIREMENTS OF PS 20-70 AND NATIONAL GRADING RULES FOR SOFTWOOD
DIMENSIONAL LUMBER, BEARING STAMP OF WWPA. ALL EXPOSED LUMBER SHALL BE
PRESSURE TREATED OR EXTERIOR GRADE
2. LUMBER GRADES TO BE (UNLESS
NOTED OTHERWISE ON PLAN):
WALL STUDS, 2X, 3 X........
HF STUD GRADE
WALL PLATES, 2X, 3X........
HF STANDARD GRADE U.N.O
JOISTS, 2 X 6: .............
HF #2
JOISTS, 2 X 8 AND UP.......
DF #2
BEAMS, HEADERS, 6X ........
DF #2
BEAMS, HEADERS, 4X.........
DF #2, WWPA GRADING
POSTS, 4X, 6X..............
DF #2 U.N.O
LUMBER NOT NOTED HERE...
DF #2 U.N.O
GLULAM BEAMS
WESTERN SPECIES 24F-V4
PSL/LVL BEAMS
2.0E OR HIGHER
3. ALL SILLS OR PLATES RESTING ON CONCRETE OR MASONRY THAT IS IN CONTACT WITH OR
RESTING ON FOUNDATIONS SHALL BE PRESSURE -TREATED DOUGLAS FIR/ HEMFIR IN
ACCORDANCE TO WITH AWPA U1 (PLANT/SHOP TREATMENT) AND M4 (FIELD TREATMENT)
STANDARDS. ALL BEARING WALL PLATES SHALL HAVE 5/8" O x10" J-BOLTS PLACED AT MAXIMUM
OF 9" FROM THE END OF A PLATE AND SPACED AT INTERVALS SHOWN ON THE SHEARWALL
SCHEDULE (MAXIMUM 48" OC SPACING). PROVIDE BP/BPS PLATE WASHER AT ALL FOUNDATION
SILL PLATE ANCHOR BOLTS. PROVIDE TWO ANCHOR BOLTS MINIMUM PER SECTION OF SILL.
FOR NON-SHEARWALL, PLACE ANCHORS AT 48". BOLTS IN WOOD SHALL NOT BE LESS THAN 7
DIAMETERS FROM THE END AND 4 DIAMETERS FROM THE EDGE OF THE MEMBER.
4. NAILS: COMMON WIRE NAILS. NAILING IN ACCORDANCE WITH IBC TABLE 2304.9.1
5. PRESSURE TREATED WOOD: ALL NAILS INTO PT WOOD SHALL BE HOT DIPPED GALVANIZED
PER ASTM A153 OR STAINLESS STEEL. ALL METAL CONNECTORS IN CONTACT WITH PT WOOD
SHALL BE HOT DIPPED GALVANIZED AND MEET ASTM A653 CLASS G185 (1.85 OZ OF ZINC PER SQ
FT MINIMUM) OR TYPE 304 / 316 STAINLESS STEEL SIMPSON Z-MAX CONNECTORS MEET THIS
REQUIREMENT. FASTENERS AND CONNECTORS USED TOGETHER SHALL BE OF THE SAME TYPE
(E.G. HOT DIPPED NAILS WITH HOT DIPPED HANGERS)
6. ALL LUMBER WITH A LEAST DIMENSION OF 2" (NOMINAL) SHALL BE STAMPED "SURFACE -DRY"
AND SHALL HAVE A MOISTURE CONTENT WHEN SURFACED AND WHEN INSTALLED OF NO MORE
THAN 19 PERCENT. LUMBER WITH A LEAST DIMENSION OF 4" (NOMINAL) OR GREATER SHALL BE
STAMPED "SURFACE -GREEN" AND AIR-DRIED TO A MOISTURE CONTENT OF NOT MORE THAN 19
PERCENT PRIOR TO ITS USE IN FRAMING THE STRUCTURE.
7. NOTCHING AND BORING OF BEAMS AND JOISTS IS NOT ALLOWED WITHOUT PRIOR APPROVAL
OF THE STRUCTURAL ENGINEER OF RECORD.
CONCRETE AND REINFORCING SPECIFICATIONS
1. CONCRETE SHALL CONFORM TO THE INDICATED REFERENCE CODES AND STANDARDS
EXCEPT AS MODIFIED BELOW:
ACI-301 - "STANDARD SPECIFICATIONS FOR STRUCTURAL CONCRETE"
ACI-318 - "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE"
ACI-305R - "HOT WEATHER CONCRETING"
ACI-306R - "COLD WEATHER CONCRETING"
ACI-304 - "GUIDE FOR MEASURING, MIXING, TRANSPORTING AND PLACING CONCRETE"
2. CONCRETE COMPRESSIVE STRENGTH REQUIREMENTS (PSI)
LOCATION f'c AT 28 DAYS W/C RATIO AIR CONTENT ADMIXTURES REQUIREMENTS
FOOTING 2500 PSI (MIN. OF 5 SACKS OF CEMENT PER CUBIC YARD OF CONCRETE)
SLAB ON GRADE 2500 PSI (MIN. OF 5 SACKS OF CEMENT PER CUBIC YARD OF CONCRETE)
FOUNDATION WALL 2500 PSI (MIN. OF 5 SACKS OF CEMENT PER CUBIC YARD OF CONCRETE)
COLUMN NA
POST TENSIONED BLDG SLAB NA
POST TENSIONED PARKING SLAB NA
TOPPING NA
SHOTCRETE NA
3. PROVIDE GRADE 60 KSI (A615) FOR CONCRETE REINFORCING
4. TOTAL AIR CONTENT IS SPECIFIED IN THE TABLE ABOVE. AIR CONTENT TOLERANCE SHALL BE ± 1 % AND SHALL BE MEASURED
AT THE POINT OF PLACEMENT. ALL CONCRETE EXPOSED TO THE WEATHER SHALL HAVE 5% TOTAL AIR REQUIRED.
REVISION
May 17 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
REVISED PLAN APPROVED
CITY OF EDMONDS BUILDING DIVISION
7)owlW. W cl�I`
BUILDING OFFICIAL
May 25 2023
APPROVED DATE
ALL WORK SUBJECT APPROVED
TO FIELD PLANS MUST BE
INSPECTION FOR ON JOB SITE
CODE COMPLIANCE
■
I ■
■Special Inspection required for this project.
Please provide the special inspection report to ■
the City Building Inspector at time of request. ■
■ I
■
STRUCTURAL STEEL, BOLTING AND WELDING SPECIFICATIONS
1. ALL EXPOSED STEEL MEMBERS, HARDWARE, FASTENERS SHALL BE HOT DIPPED GALVANIZED OR EPDXY PAINTED PER
ARCHITECT REQUIREMENTS. ALL CUT, REPAIRED AND EXPOSED SURFACE SHALL BE PAINTED WITH (2) COAT OF 95%
ZINC RICH PAINT PER ASTM A780. COLOR TO MATCH EXISTING.
2. STEEL SHALL CONFORM TO THE FOLLOWING STANDARDS:
TUBE COLUMNS: ASTM A500, GRADE B (Fy = 46 KSI)
WIDE FLANGE COLUMNS OR BEAMS: ASTM 572 GR50
STEEL PIPES: ASTM A53, TYPE E OR S, GRADE B (Fy = 35 KSI.)
STEEL PLATES, ANGLES AND MISC: ASTM A36 (Fy = 36 KSI) OR ASTM A992
BEARING BOLTS: ASTM A325
SLIP CRITICAL BOLTS: ASTM A325 WITH LOCK WASHERS
ANCHOR BOLTS: ASTM A307 (WOOD FRAMING)
ANCHOR BOLTS: ASTM A325 (STEEL FRAMING)
3. ALL SLIP CRITICAL CONNECTIONS SHALL BE ASTM A325 BOLTS AND SHALL BE ENGINEER -APPROVED, SELF -LOAD
INDICATING TYPES, AND SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
4. STRUCTURAL STEEL WELDING SHALL CONFORM TO THE AWS CODES D1.1 AND D1.3.
ALL WELDING SHALL CONFORM TO THE AWS CODES AND STRUCTURAL DRAWINGS, AND SHALL BE PERFORMED BY
CERTIFIED WELDERS USING DRY E70XX ELECTRODES
WELDS NOT SPECIFIED SHALL BE 1/4" CONTINUOUS FILLET MINIMUM. INCREASE WELD SIZE TO AWS MINIMUM SIZES,
BASED ON PLATE THICKNESS.
DRAWING LIST
SHEET NUMBER
SHEET NAME
ISSUE DATE
S-0
GENERAL NOTES AND
SPECIFICATIONS
05-15-23
S-1
BASEMENT PLAN & DETAILS
05-15-23
Grand total: 2
info@b2engineers.com
425-318-7047 (0)
425-318-0031 (C)
REQUIRED? SPECIAL INSPECTIONS (PART 1) TYPE OF INSPECTION REQUIRED? SPECIAL INSPECTIONS (PART 2) TYPE OF INSPECTION
At
NO 1704.2.5 INSPECTION OF FABRICATORS PERIODIC NO 1705.4 MASONRY CONSTRUCTION C
Verify fabrication/quality control procedures (A) Level A, B and C Quality Assurance: P �oF wASh,�S.A
1. Verify compliance with approved submittals P4 o�.
N� 1705.1.1 SPECIAL CASES CONTINUOUS (B) Level B Quality Assurance: ' i
(work unusual in nature, including but not limited to alternative materials and systems, unusual 1. Verification of f'm and f'AAC prior to construction PERIODIC .,
design applications, materials and systems with special manufacturer's requirements) (C) Level C Quality Assurance:
1. Verification of f'm and f'AAC prior to construction and for every 5,000 SF during construction PERIODIC
2. Verification of proportions of materials in premixed or preblended mortar, prestressing grout, and CONTINUOUS ?&c 43789
ON grout other than sel
NO 17Fabric for and erector doculments (Verify reports and certificates as listed in AISC 360, chapter EACH SUBMITTAL 33. Verify placeme tfof masonry ugnitgsout, as delivered to the project site PERIODIC ♦���SS1ONAL 10-4
N,paragraph 3.2 for compliance with construction documents D Levels B and C Quality Assurance: W
p ) O Y in r- s
2. Material verification of structural steel PERIODIC 1. Verification of Slump Flow and Visual Stability Index (VSI) of self -consolidating grout as delivered CONTINUOUS
3. Embedments (Verify diameter, grade, type, length, embedment. See 1705.3 for anchors) CONTINUOUS to the project
4. Verify member locations, braces, stiffeners, and application of joint details at each connection PERIODIC 2. Verify compliance with approved submittals PERIODIC
comply with construction documents 3. Verify proportions of site -mixed mortar, grout and prestressing grout for bonded tendons P4
5. Structural steel welding: 4. Verify grade, type, and size of reinforcement and anchor bolts, and prestressing tendons and P4
a. Inspection tasks Prior to Welding (Observe, or perform for each welded joint or member, the QA OBSERVE OR PERFORM AS NOTED (4) anchorages
tasks listed in AISC 360, Table N5.4-1) 5. Verify construction of mortar joints P4
b. Inspection tasks During Welding (Observe, or perform for each welded joint or member, the QA OBSERVE (4) 6. Verify placement of reinforcement, connectors, and prestressing tendons and anchorages LEVEL B - P4
tasks listed in AISC 360, Table N5.4-1) LEVEL C - CONTINUOUS
c. Inspection tasks After Welding (Observe, or perform for each welded joint or member, the QA OBSERVE OR PERFORM AS NOTED (4) 7. Verify grout space prior to grouting LEVEL B - P4
tasks listed in AISC 360, Table N5.4-3) LEVEL C - CONTINUOUS
d. Nondestructive testing (NDT) of welded joints: see Commentary 8. Verify placement of grout and prestressing grout for bonded tendons CONTINUOUS
1) Complete penetration groove welds 5/16" or greater in risk category III or IV PERIODIC 9. Verify size and location of structural masonry elements P4 BAU D E R
2) Complete penetration groove welds 5/16" or greater in risk category II PERIODIC 10. Verify type, size, and location of anchors, including details of anchorage of masonry to structural LEVEL B - PERIODIC
3) Thermally cut surfaces of access holes when material t > 2" PERIODIC members, frames, or other construction. LEVEL C - CONTINUOUS REMODEL
4) Welded joints subject to fatigue when required by AISC 360, Appendix 3, Table A-3.1 PERIODIC 11. Verify welding of reinforcement (see 1705.2.2) CONTINUOUS
5) Fabricator's NDT reports when fabricator performs NDT EACH SUBMITTAL (5) 12. Verify preparation, construction, and protestion of masonry during cold weather (temperature P4
6. Structural steel bolting: below 40 F) or hot weather (temperature above 90 F)
a. Inspection tasks Prior to Bolting (Observe, or perform tasks for each bolted connection, in OBSERVE OR PERFORM AS NOTED (4) 13. Verify application and measurement of prestressing force CONTINUOUS
accordance with QA tasks listed in AISC 360, Table N5.6-1) 14. Verify placement of AAC masonry units and construction of thin -bed mortar joints (first 5000 SF CONTINUOUS
b.lnspection tasks During Bolting (Observe the QA tasks listed in AISC 360, Table N5.6-2) OBSERVE (4) of AAC masonry)
1) Pre -tensioned and slip -critical joints 15. Verify placement of AAC masonry units and construction of thin -bed mortar joints (after the first LEVEL B - PERIODIC
a) Turn -of -nut with matching markings PERIODIC 5000 SF of AAC masonry) LEVEL C - CONTINUOUS
b) Direct tension indicator PERIODIC 16. Verify properties of thin -bed mortar for AAC masonry (first 5000 SF of AAC masonry) CONTINUOUS
c) Twist -off type tension control bolt PERIODIC 17. Verify properties of thin -bed mortar forAAC masonry (after the first 5000 SF of AAC masonry) LEVEL B - PERIODIC
d) Turn -of -nut without matching markings CONTINUOUS LEVEL C - CONTINUOUS
e) Calibrated wrench CONTINUOUS 18. Prepare grout and mortar specimens LEVEL B - P4 1031 CAVE S
2) Snug -tight joints PERIODIC LEVEL C - CONTINUOUS ,
c. Inspection tasks After Bolting (Perform tasks for each bolted connection in accordance with QA PERFORM (4) 19. Observe preparation of prisms LEVEL B - P4
tasks listed in AISC 360, Table N5.6-3) LEVEL C- CONTINUOUS EDMONDS, WA 98020
7. Inspection of steel elements of composite construction prior to concrete placement in accordance OBSERVE OR PERFORM AS NOTED (4) NQ 1705.5 WOOD CONSTRUCTION
with QA tasks listed in AISC 360, Table N6.1 1. Inspection of the fabrication process of wood structural elements and assemblies in accordance PERIODIC
with Section 1704.2.5
NQ 1705.2.2 STEEL CONSTRUCTION OTHER THAN STRUCTURAL STEEL 2. For high -load diaphragms, verify grade and thickness of structural panel sheathing agree with P5
1. Material verification of cold -formed steel deck: approved building plans
a. Identification markings PERIODIC 3. For high -load diaphragms, verify nominal size of framing members at adjoining panel edges, nail P5
b. Manufacturer's certified test reports EACH SUBMITTAL or staple diameter and length, number of fastener lines, and that spacing between fasteners in each
2. Connection of cold -formed steel deck to supporting structure: line and at edge margins agree with approved building plans
a. Welding PERIODIC 4. Metal -plate -connected wood trusses spanning 60 feet or greater: verify temporary and permanent PERIODIC
b. Other fasteners (in accordance with AISC 360,Section N6) restraint/bracing are installed in accordance with the approved truss submittal package
1) Verify fasteners are in conformance with approved submittal PERIODIC
2) Verify fastener installation is in conformance with approved submittal and manufacturer's PERIODIC ND 1705.6 SOILS
recommendations 1. Verify materials below shallow foundations are adequate to achieve the design bearing capacity. PERIODIC
3. Reinforcing steel 2. Verify excavations are extended to proper depth and have reached proper material. PERIODIC
a. Verification of weldability of steel other than ASTM A706 PERIODIC 3. Perform classification and testing of controlled fill materials. PERIODIC
b. Reinforcing steel resisting flexural and axial forces in intermediate and special moment frames, CONTINUOUS 4. Verify use of proper materials, densities, and lift thicknesses during placement and compaction of CONTINUOUS
boundary elements of special concrete structural walls and shear reinforcement controlled fill
c. Shear reinforcement CONTINUOUS 5. Prior to placement of controlled fill, observe subgrade and verify that site has been prepared PERIODIC
d. Other reinforcing steel PERIODIC properly
4. Cold -formed steel trusses spanning 60 feet or greater
a. Verify temporary and permanent restraint/bracing are installed in accordance with the approved PERIODIC NO 1705.7 DRIVEN PILE FOUNDATIONS
truss submittal package 1. Verify element materials, sizes and lengths comply with requirements CONTINUOUS
2. Determine capacities of test elements and conduct additional load tests, as required CONTINUOUS
N� 1705.3 CONCRETE CONSTRUCTION 3. Observe driving operations and maintain complete and accurate records for each element CONTINUOUS
1. Inspection of reinforcing steel installation (see 1705.2.2 for welding) P1 4. Verify placement locations and plumbness, confirm type and size of hammer, record number of CONTINUOUS DRAWING INFO
2. Inspection of prestressing steel installation PERIODIC blows per foot of penetration, determine required penetrations to achieve design capacity, record tip
3. Inspection of anchors cast in concrete where allowable loads have been increased per section CONTINUOUS and butt elevations and document any damage to foundation element
1908.5 or where strength design is used 5. For steel elements, perform additional inspections per Section 1705.2 SEE SECTION 1705.2
4. Verify use of approved design mix P1 6. For concrete elements and concrete -filled elements, perform additional inspections per Section SEE SECTION 1705.3 ISSUE DATE 05-1 5-23
5. Fresh concrete sampling, perform slump and air content tests and determine temperature of CONTINUOUS 1705.3
concrete 7. For specialty elements, perform additional inspections as determined by the registered design SEE CONST. DOCUMENTS
6. Inspection of concrete and shotcrete placement for proper application techniques CONTINUOUS professional in responsible charge ISSUED FOR PERMIT
7. Inspection for maintenance of specified curing temperature and techniques P4 8. Perform additional inspections and tests in accordance with the construction documents SEE CONST. DOCUMENTS
8. Inspection of prestressed concrete:
a. Application of prestressing force CONTINUOUS NO 1705.8 CAST IN PLACE FOUNDATIONS PROJECT NO. 22273
b. Grouting of bonded prestressing tendons in the seismic -force -resisting system CONTINUOUS 1.Observe drilling operations and maintain complete and accurate records for each element CONTINUOUS
9. Erection of precast concrete members P4 2. Verify placement locations and plumbness, confirm element diameters, bell diameters (if CONTINUOUS
a. Inspect in accordance with construction documents SEE CONST. DOCUMENTS applicable), lengths, embedment into bedrock (if applicable) and adequate end -bearing strata ENGINEER BB
b. Perform inspections of welding and bolting in accordance with Section 1705.2 ACCORDING TO SECTION 1705.2 capacity. Record concrete or grout volumes
10. Verification of in -situ concrete strength, prior to stressing of tendons in post tensioned concrete P4 3. For concrete elements, perform additional inspections in accordance with Section 1705.3 SEE SECTION 1705.3
and prior to removal of shores and forms from beams and structural slabs 4. Perform additional inspections and tests in accordance with the construction documents SEE CONST. DOCUMENTS REVISION SCHEDULE
11. Inspection of formwork for shape, lines, location and dimensions P1
12. Concrete stren th testing and verification of compliance with construction documents P4 NO 1705.9 HELICAL PILE FOUNDATIONS NO. DATE DESCRIPTION
1. Verify installation equipment, pile dimensions, tip elevations, final depth, final installation torque CONTINUOUS
YES POST INSTALLED ANCHORS IN HARDENED CONCRETE and other data as required.
Per research reports including verification of anchor type, anchor dimensions, hole dimensions, hole P2 OR AS REQUIRED 2. Perform additional inspections and tests in accordance with the construction documents SEE CONST. DOCUMENTS
cleaning procedures, anchor spacing, edge distances, concrete minimum thickness, anchor BY THE APPROVED REPORT
embedment and tightening torque NQ 1705.10.1 STRUCTURAL WOOD SPECIAL INSPECTIONS FOR WIND RESISTANCE CONTINUOUS
1. Inspection of field gluing operations of elements of the main windforce-resisting system P5
2. Inspection of nailing, bolting, anchoring and other fastening of components within the main
INSPECTION NOTES: windforce-resisting system
(1). The inspection and testing agent(s) shall be engaged by the Owner or the Owner's Agent, and
not by the Contractor or Subcontractor whose work is to be inspected or tested. Any conflict of NO 1705.10.2 COLD FORMED STEEL INSPECTIONS FOR WIND RESISTANCE
interest must be disclosed to the BuildingOfficial prior to commencing work. The qualifications of ❑ 1.Ins ection during welding operations of elements of the main windforce-resisting system PERIODIC
9 p g g p g Y
the Special Inspector(s) and/or testing agencies may be subject to the approval of the Building 2.Inspections for screw attachment, bolting, anchoring and other fastening of components within the PERIODIC
Official and/or the Design Professional. main windforce-resisting system
(2). The list of Special Inspectors may be submitted as a separate document, if noted so above.
(3). Special Inspections as required by Section 1704.2.5 are not required where the fabricator is NO 1705.10.3 WIND RESISTANCE INSPECTIONS
approved in accordance with IBC Section 1704.2.5.2 1. Roof cladding PERIODIC
(4). Observe on a random basis, operations need not be delayed pending these inspections. 2. Wall cladding PERIODIC
Perform these tasks for each welded joint, bolted connection, or steel element.
(5). NDT of welds completed in an approved fabricator's shop may be performed by that fabricator 1705.11.1 STRUCTURAL STEEL SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE SEE AISC 341 GENERAL NOTE S
when approved by the AHJ. Refer to AISC 360, N7. INSPECTION OF STRUCTURAL STEEL IN ACCORDANCE WITH AISC 341
LEGEND: NQ 1705.11.2 STRUCTURAL WOOD SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE AND
C CONTINUOUS INSPECTION 1. Inspection of field gluing operations of elements of the seismic -force resisting system CONTINUOUS
P1 PERIODIC INSPECTION PRIOR TO CONCRETE PLACEMENT 2. Inspection of nailing, bolting, anchoring and other fastening of components within the seismic- P5
P2 PERIODIC INSPECTION PRIOR TO INSTALLATION OF ELEMENT force -resisting system SPECIFICATIONS
P3 PERIODIC INSPECTION PRIOR TO USE ON PROJECT (ONCE ONLY)
P4 PERIODIC INSPECTION AT LEAST ONCE ADAY N� 1705.11.3 COLD -FORMED STEEL LIGHT -FRAME CONSTRUCTION SPECIAL INSPECTIONS
P5 PERIODIC INSPECTION AFTER ELEMENT IS IN PLACE FOR SEISMIC RESISTANCE
S VERIFY WITH SOILS ENGINEER 1. Inspection during welding operations of elements of the seismic -force -resisting system PERIODIC S-0
T MATERIAL TEST REQUIRED 2. Inspections for screw attachment, bolting, anchoring and other fastening of components within the PERIODIC
seismic -force -resisting system
Copyright b2 Structural Engineers 2008
gsyartT �.vOaa6,VdTerO
Co* G ZA ✓tr I 'f
-A&ZIC ALA6i//i'/6
x
dM 64 a
G.CA.:�E
BEA l7 /N G FAQ ji j/C7/V
/ A ,$ vA. S, /JB I't
II
//Z " 0 P/" I I
8
vaZLAUE �-
con�c.
apE'A.ti1
EXISTING JOIST AND
SHEATHING TO REMAIN
EXISTING BLOCKING
TO REMAIN
PROVIDE NEW 2X12 JOIST I
/ BLOCKING (NAILED TO EXISTING)
STEEL CHANNEL
EXISTING 6X10 SHOULD BE TIGHT
BEAM TO REMAIN AGAINST THE JOIST
4 8., 4• I 4" i 6" 14" 6` W. 4" � 6" 4r -1 '¢" 6 i-¢-k- AND BLOCKING
ITHR EEXI TIN
Di'AI L i-1 )ETA/L. 2- 2 Dc j ,4/L 3-3 DE7A/L 4-4 DEj,4/L 5-5 DETAIL (o- 6 WBEAM
WITH C8X11.5 NEW STEEL
D Y � � •4 [ L CHANNEL; PROVIDE 5/8" THRU
-- -_ -- - -- ----- - --- - .. _...- - --__ - -- ----.. _._� --- ..-- -
--__--- __--- _-- -..-.-----------_.--___-_-_ _.. BOLT AT 12" WITH WASHER
g , _ STAGGERED 16 MAX. HOLE)
/®' 4.
-- - - -- - --- -- -- -- -- -- - - - --- - - -- . -_-__ _ - -_ -_-_ - - - -�„.s EXISTING POST TO BE
- -' /- ' _ _. _.—.� _ __ - K - -- REMOVED PROVIDE NOTES:
-- .• 5 4 5 4 .� 4 2- /D �1 2 5,g 5- 4 5' 4 5- G' Z .6-..
TEMP. SHORING AND
5/8"X4" LAG BOLTS CAN BE USED IN LIEU
Z o - - -- j'- - -E 2'8�- - ;
JACKING AS REQUIRED) OF THRU BOLTS, WHERE THE EXISTING
BEAM IS NOT ACCESIBLE
I
f
SECTION 1
B c� I
I — — - - -� I I --- -- _ _--
i a:/NE OF P.¢O E' `J:�%,/ AJ'SQVE ' � - � _-_ � A e i
y---�-------- i I t• l�Uf{� pAVJN I I
(o /25/N p0AZCED CCwC. WAL[- I 1
5/M7L4jZ M
- - -- - - - - - - - - __ - -- - .� - I }
W-*+ - - - I- L ¢'x /O" GEA•+1 ?yE/z L J " EXISTING JOIST AND
'K sMse,ru.Na' 1 I _ -- --- .. - - - - -- -- - -.-- -- --- { c,h ! SHEATHING TO REMAIN Y
Al
tiI �' z 2_1_ 2 I
N i
I
I
x L
I O -
I I C
REC,2FA
86D 2bOn�r ' ED Rog Old _i' .o !►) b _!':0Al—J200M_' /Q¢_ , .l
I / a 2 �) I+� - , 2yy' ! -• �I 1/
! I h I I 1 ..\ .6E•:,lti.vB .mod tV ; Gn' ai�1 r1 .• ,r ---- -- c
/ PROVIDE NEW 2X12 JOIST
14 BLOCKING (NAILED TO EXIS
TING)
2 EXISTING BLOCKING
/ \
TO REMAIN
5 E 0 P 107
I I N
_ NEW FOOTING �� i .' I STEEL CHANNEL SHOULD BE
f sr vs s�n¢.n+G /%�7�T� „ -- �<.. - - S C S OU
f I 1 I-.s- 3 2.5'X2.5'X10" WITH 4 #5 I �, (- _ __----__-� -.-- - _ __ -- _----__-- - TIGHT AGAINST THE JOIST
I, � ' E.W.
T � • .: a d -•a.� - - _ ..� -- --, _ -- � AND BLOCKING
a o
EXISTING 6X10
BEAM TO REMAIN REINFORCE EXISTING BEAM
4oJ s,.E-v v 1� 20!/: I /N ?C!/,4tB/A/G j t
�''F` r ,-)Q READING .�A=�[r/GN! WITH C8X11.5 NEW STEEL
- CHANNEL; PROVIDE 5/8" THRU
BOLT AT 12" WITH WASHER
�h- -oF -- --- ; 1 - r-rJ: T. �?.. -_ :. --- --- STAGGERED (9/16" MAX. HOLE)
_ I
�. }- a Ti
!_J EXISTING POST AND
I o II f3A r u „ 105 T -- PROVIDE C8X11.5 -� I I CONNECTION TO NOTES:
-- I '' I
_.._----a // , . REINFORCING � REMAIN 5/8 X4' LAG BOLTS CAN BE USED IN LIEU
CHANNEL TO --_ 1 °� I i OF THRU BOLTS, WHERE THE EXISTING
� I�
'- , ' S-1 - - - t - 2 EXISTING BEAM 6X10 ��. �i, ! I NON -SHRINK GROUT PACKED BEAM IS NOT ACCESIBLE
/ S-1 BOVE (B-1) i'- �; - s I �f I i UNDER THE EXISTING BASE
__- -� _ _ ! �; I PLATE (8"X8"X1"THICK)
17FlurfNeffi,
! GNcY,YCA V Q CUT EXISTING SLAB ON GRADE TO
BEARJti •s pae �,1 ' I 8 I i� I --- - �, I�' #4X12" REBAR (TOTAL OF 8) POUR NEW FOOTING 2500 PSI .
ppvlL /'--24'x Lo- ( )
6 TP, RA 6 E I 4 " aN e. 6 L A 43 O �F- AND NEW CONCRETE EXISTING FOOTING SHALL BE
r- I I 61 G a2 ,4 Y E L < L ENCASEMENT FOR COLUMN REMOVED. PROVIDE VAPOR BARRIER
5_9 _G'o" 1'-4-
I_.--�.------ ENCASEMENT
�0'I 1,4Z 7. M- AND SEALANT AS REQUIRED
.g\ (� I -� 2�7 /i- s.d. I; -a p
a•
c _
J', 1 .. - A . i s •! q t , .Q . y, I I i • d ° C.0
BED J20oM 03
,-- ' I I , ^ I a^ d •, a° d e•� .• ,Q' ,°_ ;a• ° 'ad°,, tl °a °`°- .ad ,°. a d'a a -O
% I �'4PLv �N I Ij t--t (All
.lklA +4s F[R`------------i a� �- I --� , ' l T"-i — - - -- ..; .;•.,., �.. s °— —O. a d .
r T 6� L� 1 j 1 1. _
SIL. a.� • tz,'.,.a� .. �'_."�.'.'.•.:'�el f�: �.— LJ - L ,—I lip.' L,].1 1 -- _ ,_ -- — —®' a•._ .'�, a, °;,° e,°'; a
.-ice I r0or.,vvs q I u - �9
¢ ° ; �o r,/vti L'Jo.4N / - i - 2 /2" Imo_` P �2 j 4 "
a d a
M ALL FOOTINGS SHALL BEAR ON SUITABLE SOIL SUCH
IN. OF MEDIUM DENSE NATIVE SOIL OR
m D 2' 5" SQUARE I OMPACTED STRUCTURAL FILL (NO SOFT OR ORGAN
Z I j 11 3 -I#5 E.W. MATERIALS). GEOTECHNICAL ENGINEER MAY B
I i I _ REQUIRED TO ASSESS EXISTING SOIL CONDITIONS.
! tJ
��° , " �= 2 o = 6, SECTION 2
" /5 =/a Ig" 5'-/%Z" �c'4" ,g',¢" 5 /� 5-0/2 5 ¢ 4 -_ "lO ��
9 o/
,�E/ /Y F o,e c INC, n/o ; 6 -
/, r)p'P/C 4 _ L/55 3/�' ; &'ir3'QC. I102/Zcl"7A LY
�jNO {/E2 T/�A1GLrGaN ,4LL CONC. WALL$
j- Ae. NCrFP. A 2,C 55I D i IVCE r OQ
L AP Ho2i Z, ,8�0p5 1'6"
T l"6r s ,Ae e poueEe RX/04 `✓1 Q C M 2 S A
�xl
jO+C• aPU/Y'' yp DAN F.IL1....E1 \, A! ��1 �,.j �:iIrCoPrv�5s, i�i
420 BALL ST. E;✓v;0 N!ntF_
r ,2/CNA Z O .sTE /Z /V /19E
9/ TL.a" 4 ./,4ME5 N 2EiG
F Of waste`'"
s/ERED pRG�� 3,4 S E Mg N i (L able- ANC
BASEMENT PLAN
N.T.S.
info@b2engineers.com
425-318-7047 (0)
425-318-0031 (C)
�P5 of Msy/ S'.A
�+fj PG 43789
RA L le
/ONAL EN�
BAUDER
REMODEL
1031 C AVE S,
EDMONDS, WA 98020
DRAWING INFO
ISSUE DATE 05-15-23
ISSUED FOR PERMIT
PROJECT N0. 22273
ENGINEER BB
REVISION SCHEDULE
NO. DATE DESCRIPTION
REVISION
May 17 2023
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BASEMENT PLAN
&DETAILS
S-1
Copyright b2 Structural Engineers 2008