APPROVED BLD BLD2023-0648+STRUCTURAL PLANS+5.26.2023_8.17.05_AM+3571007GENERAL STRUCTURAL NOTES: FOUNDATIONS: SUBGRADE: ALLOWABLE SOIL PRESSURE 1500 PSF ALLOWABLE SOIL PRESSURE ARE ASSUMED AND THEREFOR MUST BE VERIFIED BY A QUALIFIED SOILS ENGINEER OR APPROVED BY THE BUILDING OFFICIAL. IF SOILS ARE FOUND TO BE OTHER THAN ASSUMED, NOTIFY THE STRUCTURAL ENGINEER FOR POSSIBLE FOUNDATION REDESIGN. STRUCTURAL FILL: BE FREE DRAINING, GRANULAR MATERIAL CONTAINING NO MORE THAN FIVE (5) PERCENT FINES (SILT AND CLAY —SIZE PARTICLES PASSING THE NO. 200 MESH SIEVE); BE FREE OF ORGANIC MATERIAL AND OTHER DELETERIOUS SUBSTANCES, SUCH AS CONSTRUCTION DEBRIS AND GARBAGE; HAVE A MAXIMUM SIZE OF THREE (3) INCHES IN DIAMETER. ALL FILL MATERIAL SHOULD BE PLACES AT OR NEAR OPTIMUM MOISTURE CONTENT. THE OPTIMUM MOISTURE CONTENT IS THE WATER CONTENT IN SOIL THAT ENABLES THE SOIL TO BE CONPACTED TO THE HIGHEST DRY DENSITY FOR A GIVEN COMPACTION EFFORT. STRUCTURAL FILL SHOULD BE PLACED IN THIN HORIZONTAL LIFTS NOT EXCEEDING TEN INCHES IN LOOSE THICKNESS. STRUCTURAL FILL PLACED UNDER BUILDING AREA WHICH IS INTENTED TO PROVIDE STRUCTURAL SUPPORT SUCH AS AT FOOTING AND SLAB —ON —GRADE AREAS, SHOULD BE COMPACTED TO AT LEAST 92 PERCENT OF THE MAXIMUM DRY DENSITY, AS DETERMINED BY ASTM TEST DESIGNATION D-1557-91 (MODIFIED PROCTOR). CONCRETE: CONCRETE f'c = 2,500 PSI AT 28 DAYS WITH 5 1/2 SACKS CEMENT PER CUBIC YARD CONCRETE. CONCRETE PROTECTION FOR REINFORCING SHALL BE AS FOLLOWS: BOTTOM OF FOOTINGS 3" CONCRETE EXPOSED TO EARTH & WEATHER (#5 & SMALLER) 1 1/2" REINFORCING STEEL: DEFORMED BILLET STEEL CONFORMING TO ASTM A615 (STANDARD 04, 2013 CURRENT), GRADE 60. (ALL WELDED BARS NOTED BY DIA. ARE A36 STEEL.) UNLESS NOTED OTHERWISE, PROVIDE LAP SPLICE LENGTH OF 48 BAR DIAMETERS IN 2,500 PSI CONCRETE FOR #6 AND LESS GENERAL WOOD FRAMING NOTES: 1. MINIMUM NAILING SHALL BE IN ACCORDANCE WITH FASTENING SCHEDULE TABLES 11-13 IN ICC—ES EVALUATION REPORT ESR-1539. 2. PROVIDE CONTINUOUS 2x SOLID BLOCKING OR ENGINEERED LUMBER BLOCKING OR A RIM JOIST FOR FRAMING MEMBERS AT ALL SUPPORTS. 3. FLUSH BEAMS (FB) NOT CALLED OUT ON THE PLANS SHALL BE DOUBLE JOISTS. 4. PROVIDE DOUBLE JOISTS UNDER PARTITIONS EXTENDING 1/2 OR MORE OF THE JOIST SPAN. 5. PROVIDE CUT WASHERS FOR ALL BOLT HEADS AND NUTS BEARING ON WOOD. 6. PROVIDE SILL SEAL/GASKET BETWEEN LUMBER AND CONCRETE OR MASONRY. SEALER/GASKET SHALL PROVIDE A CAPILLARY BREAK. 7. PROVIDE ONE LAYER OF 40# ASPHALT IMPREGNATED BUILDING PAPER AT CONTACT SURFACES BETWEEN UNTREATED WOOD AND CONCRETE OR MASONRY. 8. CURRENT IBC BUILDING CODES ARE AVAILABLE ONLINE FOR FREE PUBLIC ACCESS AT CODES. ICCSAFE.ORG. WOOD: STRUCTURAL LUMBER GRADES AND SHEATHING RATINGS: ALL LUMBER SHALL BE GRADED IN ACCORDANCE WITH CURRENT WWPA STANDARD GRADING RULES FOR WESTERN LUMBER. USE THE FOLLOWING SPECIES AND MINIMUM GRADE: JOIST 2x4 HF#2 Fb=975psi, Fv=150psi, Fc=1300PSI, E=1,300,000psi 2x6 OR LARGER HF#2 Fb=975psi, Fv=150psi, Fc=1300PSI, E=1,300,000psi STUDS 2x4 HF#2 Fb=975psi, Fv=150psi, Fc=1300PSI, E=1,300,000psi 2x6 OR LARGER HF#2 Fb=975psi, Fv=150psi, Fc=1300PSI, E=1,300,000psi POSTS 4x4 HF#2 Fb=975psi, Fv=150psi, Fc=1300PS1, E=1,300,000psi 4x6 HF#2 Fb=975psi, Fv=150psi, Fc=1300PSI, E=1,300,000psi 6x6 DF#2 Fb=750psi, Fv=170psi, Fc=700PSI, E=1,300,000psi WOOD PROTECTION / TREATMENT: ALL LUMBER IN CONTACT WITH GROUND OR CONCRETE OR EXPOSED TO THE ELEMENTS SHALL BE PRESSURE —TREATED (NOTED P.T.) IN ACCORDANCE WITH AWPA STANDARD U1. USE THE FOLLOWING MINIMUM AWPA USE CATEGORIES: INTERIOR/DAMP (WOOD SILL PLATES): UC2 PAINT ALL SCARS, CUTS AND DRILL HOLES WITH A WOOD PRESERVATIVE THAT IS COMPATIBLE WITH THE CHEMICALS USED FOR THE PRESSURE TREATMENT OF THE WOOD. PRESERVATIVES FOR FIELD TREATMENT SHALL MEET THE REQUIREMENTS OF AWPA STANDARD M4. GLUED LAMINATED LUMBER: DOUGLAS FIR —LARCH GRADE 24F—V4 (Fb=2400 PSI) FOR SINGLE SPAN BEAMS. ALL GLULAM MATERIALS SHALL CONFORM TO THE REQUIREMENTS OF ANSI/AITC A190.1 AND BE STAMPED WITH AN AITC QUALITY MARK OR AN APA—EWS TRADEMARK. ADHESIVES USED IN THE GLULAM MANUFACTURING PROCESS SHALL CONFORM TO AITC 405 FOR WET USE ADHESIVES. GLULAM MEMBERS SHALL BE MANUFACTURED FROM DOUGLAS FIR LAMINATING LUMBER. ALL BEAMS SHALL HAVE ZERO CAMBER UNLESS NOTED OTHERWISE. MEMBERS NOT EXPOSED TO VIEW IN THE COMPLETED WORK SHALL BE INDUSTRIAL APPEARANCE GRADE. MEMBERS EXPOSED TO VIEW IN THE COMPLETED WORK SHALL BE ARCHITECTURAL APPEARANCE GRADE. STEEL: STRUCTURAL & MISCELLANEOUS STEEL: CHANNELS SHALL BE ASTM A36 Fy = 36,000 PSI. ALL FABRICATION & ERECTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF AISC "STEEL CONSTRUCTION MANUAL." FASTENERS: STEEL BOLTS: ALL BOLTS AND THREADED RODS SHALL BE ASTM A307 HOT —DIPPED GALVANIZED IN ACCORDANCE WITH ASTM A153—CLASS C UNLESS NOTED OTHERWISE. NAILS: NAIL SIZES SPECIFIED ON DRAWINGS ARE BASED ON THE FOLLOWING SPECIFICATIONS: SIZE TYPE LENGTH DIAMETER 8d COMMON 2-1/2" 0.131" 10d GUN 3" 0.131" 12d GUN 3-1/4" 0.131" 16d GUN 3-1/2" 0.131' IF CONTRACTOR PROPOSES THE USE OF ALTERNATE NAILS, THEY SHALL SUBMIT NAIL SPECIFICATIONS TO THE STRUCTURAL ENGINEER (PRIOR TO CONSTRUCTION) FOR REVIEW AND APPROVAL. NAILS —PLYWOOD (APA RATED SHEATHING) FASTENERS TO FRAMING SHALL BE DRIVEN FLUSH TO FACE OF SHEATHING WITH NO COUNTERSINKING PERMITTED. ALL NAILS EXPOSED TO WEATHER OR IN CONTACT WITH PRESSURE TREATED WOOD SHALL BE HOT —DIPPED GALVANIZED PER ASTM A153—CLASS D. LIGHT GAUGE FRAMING CONNECTORS: NOTATIONS ON DRAWINGS RELATING TO FRAMING CLIPS, JOIST HANGERS AND OTHER CONNECTING DEVICES REFER TO CATALOG NUMBERS OF CONNECTORS MANUFACTURED BY THE SIMPSON STRONG —TIE COMPANY, DUBLIN, CALIFORNIA. EQUIVALENT DEVICES BY OTHER MANUFACTURERS MAY BE SUBSTITUTED PROVIDED THEY HAVE ICC—ES APPROVAL FOR EQUAL LOAD CAPACITIES. CONNECTORS SHALL BE FASTENED TO THE FRAMING MEMBERS USING THE NUMBER AND TYPE OF FASTENERS CALLED FOR BY MANUFACTURER. HANGERS AND CLIPS IN CONTACT WITH PRESSURE TREATED LUMBER SHALL BE ZMAX/HDG GALVANIZED CONNECTORS. ALL HANGER FASTENERS USED WITH ZMAX/HDG GALVANIZED CONNECTORS SHALL BE HOT —DIPPED GALVANIZED PER ASTM A153—CLASS D OR SDS SCREWS WITH PROPRIETARY COATING. APPROVED PLANS MUST BE ON JOB SITE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE ................................................ The following documentation shall be available on ■ site for the building inspector: ■ ! ❑X COE APPROVED ARCHITECTURAL PLAN SET FRI COE APPROVED STRUCTURAL PLAN SET ; ❑ COE REVIEWED CALCULATION PACKET ❑ ENERGY CREDIT WORKSHEET ❑ SITE PLAN ; • ❑ CIVIL PLAN ■ ■ ■ :❑ CITY OF EDMONDS BUILDING DEPARTMENT 2021 ■ REMAIN EXISTING CEILING FINISHES EXISTING TENSION RING TO REMAIN EXISTING COLUMN BELOW BEING REMOVED SLOPED END CUT FOR pnn� DRA RECEIVED May 30 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT EXISTING TRUSS BOTTOM CHORD BEING MODIFIED EXISTING CONDITION EXISTING RAFTERS TO REMAIN EXISTING TENSION RING TO REMAIN EXISTING WALL BEING REMOVED CONNECT EXIST BEAM TO NEW BEAM WITH SDWS2280ODB AT 24"oc TOP OF TOP PLATE AT LIVING ROOM EXISTING BEAM TO BEAR ON 2x6 LEDGER, CONNECT LEDGER TO NEW BEAM WITH 10d NAILS AT 6"oc, STAGGER NAILS SECTION ❑� SCALE: 3/4" = 1'-0" STING HIP BEAM TO 1AIN STING TENSION RING TO 1AIN RACKET WITH BOLTS TO REMAIN EXISTING CONDITION SECTION SCALE: 3/4" = 1'-0" BLD2023-0648 REMOVE EXISTING TRUSS BOTTOM CHORD AND INSTALL VERTICAL 2x4 AT 24"oc, SO EXISTING TRUSS TOP CHOIR BEARS DIRECTLY ON NEW BEAM PROPOSED RETROFITS h O NEW 5.5x12 GLB PER PLAN i CONNECT EXIST TENSION RING TO NEW BEAM WITH SDWS221000DB AT 24"0 SCOPE OF WORK SUMMARY TYPE: ALTERATION — STRUCTURAL DRAWINGS THE PURPOSE OF THESE DRAWINGS IS TO SHOW THE STRUCTURAL DETAILS NECESSARY FOR THE PROPOSED REMODEL AT THE SUBJECT ADDRESS. THE PROPOSED ALTERATION AFFECTS THE GRAVITY SYSTEM ONLY. THERE ARE NO ALTERATIONS TO THE EXISTING LATERAL SYSTEM. THESE STRUCTURAL DRAWINGS SUPPLEMENT THE ARCHITECTURAL DRAWINGS PROVIDED BY THE CLIENT THE ENGINEERING SEAL ON THESE DRAWINGS IS FOR THE STRUCTURAL SYSTEM ONLY. DESIGNING CIVIL ENGINEERING FOR UTILITIES (STORM DRAINAGE, WATER SUPPLY, SEWER, ETC.), PREPARING SURVEYS (TOPOGRAPHICAL AND LOT LINES, ETC.), DESIGNING LANDSCAPING, DESIGNING EXTERIOR BUILDING ENVELOPE AND WEATHERPROOFING, DESIGNING MECHANICAL, ELECTRICAL, AND PLUMBING SYSTEMS, GEOTECHNICAL ENGINEERING SERVICES, PERFORMING SPECIAL INSPECTIONS, DESIGNING INTERIOR FINISHES, FIRE PROTECTION AND LIFE SAFETY SYSTEM SHALL BE BY OTHERS AS NEEDED. NOTIFY ENGINEER IF CONDITIONS DIFFER FROM WHAT IS SHOWN OF THESE DRAWINGS. SHEET INDEX SHEET S1.0 SCOPE OF WORK SUMMARY, SHEET INDEX, GENERAL STRUCTURAL NOTES, AND SECTIONS SHEET S2.0 LOW ROOF / 2ND FLOOR FRAMING, HIGH ROOF FRAMING SHEET S2.1 BASEMENT WALL FRAMING ■ CONNECT EXIST TENSION i I RING TO NEW BEAM WITH (Please indicate to Building Inspector where ■ SDWS221000DB AT 24"oc ■section three detail will be conducted (on sheet I2.0). ■ ■ I NEW 5.5x12 GLB J I \—NEW 5.5x12 GLB PER PLAN PER PLAN U 5/8"0 x 14" MACHINE BOLT WITH 3" x 3" x 0.229" PLATE WASHERS, SEE SECTION 3 HUCQ612—SDS EXIST HIP BEAM TO BEAR ON MC6x7 CHANNEL BELOW, AS SHOWN IN SECTION 3, MIN 5.5" HIP BEAM BEARING ON CHANNEL PROPOSED RETROFITS (PLAN VIEW) SECTION ❑2 SCALE: 3/4" = 1'-0" TOP OF TOP PLATE AT LIVING ROOM .5x12 GLB BEAM PER 4 POST CAP, (1) EA _.. _x6 DF#2 COLUMN PER PLAN EXISTING 2ND FLOOR WALL EXISTING FLOOR JOISTS T( REMAIf NEW 5.5x9.5 GLB DROP BEAK, PER PLAN SECTION ❑5 SCALE: 3/4" = 1'-0" "0 REMAIN SECTION 0 SCALE: 3/4" = 1'-0" 6x6 DF#2 COLUMN SIMPSON ABA66Z POST BASE WITH 5/8"0 THREADED ROD SET IN PREDRILLED HOLE FILLED WITH ADHESIVE, EMBED 5" MIN. EXISTING CONCRETE SLAB ON GRADE, SAW CUT AS NEEDED TO INSTALL NEW FOOTING NEW CONC. TO EXTEND UNDER EXIST. SLAB ON GRADE 3'-0"x3'-0"x12"MIN, CONCRETE FOOTING, WITH (3)#4 BARS EACH WAY, PLACE FOOTING ON FIRM UNDISTURBED SOIL, INCREASE FOOTING DEPTH AS NEEDED 5/8"0 x 14" MACHINE BOLT WITH 3" x 3" x 0.229" PLATE WASHERS MC6x7 CHANNEL BELOW, SEE SECTION 2 FOR ADDITIONAL INFORMATION HUCQ612—SDS NOTE: SCHEMATIC DIAGRAM .. + •�. . CV 4" 114, SECTION SCALE: 3/4" = V-0" U ZL VJL t W� f ( U) L U) e U� F F c U C J :ti J Q t 3: ui G H �a J W J fALON� N 00 M W M Iq Q 00 M f� �xooCID o `i:wwQ CID LL W Li (n Q Q U (=O (n � J W Q W W Q Z Z 00 v> IJJ f (n Lj O Lv z CU0O O Z Z 0 N ., 0 Z ao LI J Q Q� w = z � � o N 0 o Z 0 0 w w wN D �w w= O W �� z O in wQ �o O w 7 M cn z O cn > w n I w O N 0 = o U Q o cl o o lic— < Lai o ' ^ 0 w o z w z z � 0 m w Z O Q _ W _D 0 (n b 0 Z it ZW W Z ti U)ZW�� C a u.i WF- F- J W 0 Z N Lo M Z �/1 a W4M00 > ao 00 ao 2 � o � U�a)0CC M J J X N ccoHLU ULL U U (E)TENSION RING as Jyio ��P I �Q` o� �sA �!• c y N y E�J U (E)RIDGE/BEAM �� �� p �' ° 1 B � y 0 i z U) 0 z Vn LL- Ld z Ld .� w 00 m � Z HIGH ROOF FRAMING � SCALE: 1 /4" = 1'-0" ®® Z m (N) 6x6 DF#2 N COLUMN LL- (E) COLUMN TO 4 � O REMAIN 0 O (N) 6x6 DF#2 COLUMN c� o OZ BLD2023-0648 IV NRECE �i Q / O May 30 20f (F)TENSION RING Z coO D DEVELOPMENT MET SETS ER I � DEVELOPMENT DEPARTMENT w / rm■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■� Uj m /� ■ w W LLI Please indicate to Building Inspector where _ o (N) 6x6 DF#2 ■section three detail (found on sheet 1.0) will be �- (E) COLUMN COLUMN (conducted. N 0 o (E)BEAM L BEING REMOVED Ld w O o w cn w m D Li w w= W LLJ (E)FLR JOISTS E TRUSSES (N) 5.5"xl2" (E)FLR J TS > w / GLULAM BEAM Lu o Q w w J � LEGEND w w Q w ® EXIST COLUMN / 0m m w (E)BEAM (E)BEAM COL BBAM COLUMN FROM ABOVE D Ln Ln 0 / z / (N)COL (N)COL BEAM AND COLUMN LINE - SIZES PER PLANS, COLUMNS LOADS TO BE > .� CONTINUOUSLY SUPPORTED DOWN TO FOUNDATIONS, PROVIDE SOLID LLJ (N)BEAM VERTICAL GRAIN BLOCKING THRU FLOOR TO MATCHING COLUMN SIZE I I z 0 (N) 6x6 DF#2 JOIST, RAFTER, TRUSS, REPETITIVE MEMBER SYMBOL POINTS IN THE w o COLUMN DIRECTION OF THE SPAN m z EXIST WALLS (N) 6x6 DF#2 Lj v� COLUMN EXIST WALLS BEING REMOVED Lv TEMPORARY SHORING WALL BY OTHERS, INSTALL ALL TEMPORARY SHORING PRIOR TO ANY RETROFIT WORK Of J w O N O = O U N LOW ROOF Z 2N D FLOOR FRAMING � NOTE: o N SCALE: 1 /4" = V-0' ®® VAORIES FROM WHAT ITIFY ENGINEER IF S SHOWN AMING L 0 w o z Ld z z w w 0 m w z p Q = w � o cn X b 0 Z R ZW W Z U)Z� W� C a u.i WF- F- J W 0 Z N L00 o M Z �/1■ Q co ce) uJ�M00 w M J J X LLH r.WWQ N coHULL U Jaa ./aAG4/ G "uy i d-by C-3 El C� z J H W SOLID BLOCKING TO z W ALIGN WITH NEW (n COLUMNS ABOVE z Q p m u BLD2023-0648 ORECEIV O May 30 20 3 Z /Y► CITY OF EDMOND o DEVELOPMENT SERCES n r11 DEPARTMENT %w VJ LLI 2 Z w O N C Z p 0 w w w 0 zw w= AT 6 0 :::J FOOTING L_ J m w p z p 3'-0"x3'-0"x12"MIN, Cn w CONCRETE FOOTING, > El El El El WITH (3)#4 BARS ui o EACH WAY NEW 6x6 DF#2 COLUMN TO ALIGN WITH NEW COLUMNS ABOVE, PROVIDE SOLID VERTICAL GRAIN BLOCKING czn THRU FLOOR TO z MATCHING COLUMN p SIZE cn LLJ NEW 6x6 DF#2 COLUMN TO ALIGN WITH NEW COLUMNS ABOVE, COLUMN TO BEAR ON EXISTING PERIMETER z FOUNDATION WALL, CONTRACTOR TO U cn VERIFY, PROVIDE SOLID VERTICAL > GRAIN BLOCKING THRU FLOOR TO ct- mz z MATCHING COLUMN SIZE Lei vi w w O N = O � U Q o 0) IN � BASEMENT WALL FRAMING NOTE: o SCALE: 1/4" = 1'-0" ®® NO CHANGES TO THE 2ND FLOOR < < /1 FRAMING PLAN. THEREFORE, NO (/ FLOOR FRAMING SHOWN w o z LLJz z z w w 0 m w z p Q = w o I cn f