SEE REV1 APPROVED BLD2023-1397+STRUCTURAL PLANS+11.2.2023_1.27.15_PM+3877721STRUCTURAL NOTES (THESE NOTES ARE TYPICAL UNLESS NOTED OR DETAILED OTHERWISE ON DRAWINGS) CODE MINIMUM LAPS AND EMBEDMENT TYPICAL FRAMING NOTES ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (IBC), 2018 EDITION. SPECIFICATIONS AND STANDARDS WHERE REFERENCED ON THE DRAWINGS ARE TO BE THE LATEST EDITION. DESIGN LOADS DEAD LOADS: ROOF 15 PSF FLOOR 15 PSF LIVE LOADS: ROOF (SNOW LOAD) 25 PSF RESIDENTIAL 40 PSF UNINHABITABLE ATTIC WITHOUT STORAGE 10 PSF (LIVE LOADS ARE REDUCED WHERE PERMISSIBLE PER IBC SECTION 1607.11). EARTHQUAKE LOADS: EQUIVALENT LATERAL FORCE PROCEDURE PER ASCE 7-16 SECTION 12.8. SITE CLASS D (DEFAULT) SHORT PERIOD SPECTRAL RESPONSE ACCEL (SS) 1.286 ONE SECOND SPECTRAL RESPONSE ACCEL (SI) 0.453 SHORT PERIOD DESIGN SPECTRAL RESPONSE ACCEL (SDS) 1.029 ONE SECOND DESIGN SPECTRAL RESPONSE ACCEL (SDI) 0.558 RISK CATEGORY II SEISMIC IMPORTANCE FACTOR (IF) 1.0 SEISMIC DESIGN CATEGORY D BASIC SEISMIC FORCE -RESISTING -SYSTEM WOOD SHEAR WALLS RESPONSE MODIFICATION FACTOR, (R) 6.5 REDUNDANCY FACTOR (p) 1.0 SEISMIC RESPONSE COEFFICIENT (CS) 0.158 W = TOTAL SEISMIC DEAD LOAD AS DEFINED PER ASCE 7-16 SECTION 12.7.2. BASE SHEAR (V), V = CSW = RIDI W WIND LOADS: BASIC WIND SPEED (3 SECOND GUST) 97 MPH EXPOSURE B KZT 1.0 STATEMENT OF SPECIAL INSPECTIONS STRUCTURAL OBSERVATION OF THE STRUCTURAL SYSTEM BY THE ENGINEER IS NOT REQUIRED. FOUNDATIONS: SPREAD FOOTINGS SOILS REPORT: ALLOWABLE SOIL PRESSURE LATERAL EARTH PRESSURE: UNRESTRAINED: RESTRAINED: PASSIVE: COEFFICIENT OF FRICTION NOT AVAILABLE AT TIME OF DESIGN 1500 PSF (ASSUMED) 35 PCF + ANY APPLICABLE SURCHARGE 50 PCF + ANY APPLICABLE SURCHARGE 300 PCF 0.35 FOOTINGS SHALL BEAR ON FIRM UNDISTURBED EARTH OR 12" OF COMPACTED STRUCTURAL FILL AS REQUIRED AND AT LEAST 18" BELOW ADJACENT EXTERIOR GRADE. ANY FOOTING ELEVATIONS SHOWN IN THE DRAWINGS REPRESENT MINIMUM DEPTHS AND ARE FOR BIDDING ONLY. ACTUAL FOOTING ELEVATIONS ARE SUBJECT TO SITE CONDITIONS AND MUST THEREFORE BE ESTABLISHED BY THE CONTRACTOR. FOOTINGS SHALL BE CENTERED BELOW COLUMNS OR WALLS ABOVE, UNLESS NOTED OTHERWISE. IMPORTED STRUCTURAL FILL AND BACKFILL MATERIAL SHOULD CONSIST OF CLEAN, WELL GRADED GRANULAR MATERIAL FREE OF DEBRIS OR ORGANICS WITH A MAXIMUM PARTICLE DIAMETER OF THREE INCHES AND NO MORE THAN 10% FINES (PASSING THE #200 SIEVE). FILL AND BACKFILL MATERIAL SHOULD BE PLACED IN LEVEL LIFTS NOT EXCEEDING TWELVE (12") INCHES IN LOOSE THICKNESS AND COMPACTED TO A MINIMUM OF 95% OF ITS MAXIMUM DRY DENSITY AS DETERMINED BY ASTM TEST METHOD D1557. ,■I■1011410:111: ALL CONCRETE SHALL BE MIXED, PROPORTIONED, CONVEYED, AND PLACED IN ACCORDANCE WITH CHAPTER 26 OF ACI 318 AND THE AMERICAN CONCRETE INSTITUTE'S SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301). ALL CONCRETE SHALL BE STONE -AGGREGATE CONCRETE HAVING A UNIT WEIGHT OF APPROXIMATELY 150 POUNDS PER CUBIC FOOT. CONCRETE STRENGTHS AT 28 DAYS (fc) AND MIX CRITERIA SHALL BE AS FOLLOWS: MAXIMUM MIN CEMENT TYPE OF CONSTRUCTION f'c* WATER/CEMENT CONTENT PER CUBIC MAXIMUM SHRINKAGE STRAIN RATIO YARD FOOTINGS 4000 PSI 0.50 5 1/2 SACK N/A THE MINIMUM AMOUNT OF CEMENT LISTED ABOVE MAY BE CHANGED IF A CONCRETE PERFORMANCE MIX IS SUBMITTED TO THE ENGINEER AND THE BUILDING DEPARTMENT FOR APPROVAL TWO WEEKS PRIOR TO PLACING ANY CONCRETE. THE PERFORMANCE MIX SHALL INCLUDE THE AMOUNTS OF CEMENT, FINE AND COARSE AGGREGATE, WATER, AND ADMIXTURES AS WELL AS THE WATER -CEMENT RATIO, SLUMP, CONCRETE YIELD, AND SUBSTANTIATING STRENGTH DATA IN ACCORDANCE WITH CHAPTER 26 OF ACI 318. ALL CONCRETE EXPOSED TO WEATHER OR TO FREEZING TEMPERATURES SHALL BE AIR -ENTRAINED IN ACCORDANCE WITH ACI 318 TABLE 19.3.3.1 FOR MODERATE EXPOSURE CLASS F1. *PROVIDE fc SPECIFIED IN TABLE FOR DURABILITY REQUIREMENTS. 2500 PSI CONCRETE MEETS STRENGTH REQUIREMENTS, THEREFORE SPECIAL INSPECTION IS NOT REQUIRED. REINFORCING STEEL REINFORCING STEEL SHALL BE DEFORMED BILLET STEEL CONFORMING TO ASTM A615, AND SHALL BE GRADE 60 (Fy = 60,000 PSI), UNLESS NOTED OTHERWISE. GRADE 60 REINFORCING BARS INDICATED ON DRAWINGS TO BE WELDED SHALL CONFORM TO ASTM A706. REINFORCING COMPLYING WITH ASTM A615 MAY BE WELDED IF MATERIAL PROPERTY REPORTS INDICATING CONFORMANCE WITH WELDING PROCEDURES SPECIFIED IN AWS D1.4 ARE SUBMITTED. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. PROVIDE WELDED WIRE FABRIC IN SHEETS NOT ROLLS. LAP WELDED WIRE FABRIC 12" AT SIDES AND ENDS. REINFORCING STEEL SHALL BE DETAILED INCLUDING HOOKS AND BENDS IN ACCORDANCE WITH ACI SP-66 AND ACI 318, LATEST EDITIONS. UNLESS OTHERWISE NOTED, REINFORCING SPLICE LENGTHS AND DEVELOPMENT LENGTHS SHALL BE PER SCHEDULE. MECHANICAL SPLICING OF REINFORCING BARS, WHERE INDICATED ON THE DRAWINGS, SHALL BE BY AN ICBO APPROVED SYSTEM, SHALL DEVELOP 125% OF THE SPECIFIED YIELD STRENGTH OF THE BAR, AND SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. REINFORCING SHALL BE PLACED AND ADEQUATELY SUPPORTED PRIOR TO PLACING CONCRETE. WET -SETTING EMBEDDED ITEMS IS NOT ALLOWED WITHOUT PRIOR ENGINEER APPROVAL. BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL NOT BE FIELD BENT UNLESS SO DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER. REFER TO CHAPTER 25 OF ACI 318 FOR OTHER REINFORCING STEEL REQUIREMENTS. UNLESS OTHERWISE NOTED, REINFORCING SPLICE LENGTHS AND DEVELOPMENT LENGTHS SHALL BE AS TABULATED BELOW: f'c = 2500 PSI DEVELOPMENT LENGTH LAP SPLICE BAR TENSION COMPRESSION TENSION COMPRESSION SIZE TOP BARS OTHER BARS ALL BARS TOP BARS OTHER BARS ALL BARS #3 24 18 9 30 23 12 #4 31 24 12 41 31 15 #5 39 30 15 51 39 19 #6 47 36 18 61 47 23 #7 68 53 21 89 68 27 #8 78 60 24 102 1 78 30 NOTE: 1. ALL LENGTHS ARE IN INCHES. 2. ALL LAP SPLICES ARE CLASS B. 3. "TOP BARS" ARE HORIZONTAL REINFORCEMENT PLACED SUCH THAT MORE THAN 12 INCHES OF CONCRETE IS CAST IN THE MEMBER BELOW THE BAR. CONCRETE COVER ON REINFORCING CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3" CONCRETE EXPOSED TO EARTH AND WEATHER: #6 BARS AND LARGER 2" #5 BARS AND SMALLER 1 1/2" CONCRETE NOT EXPOSED TO EARTH OR WEATHER: SLABS, WALLS AND JOISTS 3/4" COLUMN TIES OR SPIRALS AND BEAM STIRRUPS 1 1/2" LUMBER ALL GRADES SPECIFIED ARE MINIMUM GRADES REQUIRED. ALL LUMBER SHALL BE IN ACCORDANCE WITH WWPA GRADING RULES, KILN -DRIED TO MC 19 AND OF THE FOLLOWING MINIMUM STANDARDS: SIZE CLASSIFICATION SPECIES GRADE Fb (PSI) Fc (PSI) LIGHT FRAMING (STUDS) HEM -FIR STUD 675 800 2x JOISTS AND PLANKS HEM -FIR #2 850 - PLATES AND BLOCKING HEM -FIR #2 850 - 6x AND LARGER BEAMS AND STRINGERS DOUG-FIR #2 875 - 4x AND SMALLER BEAMS AND STRINGERS HEM -FIR #2 850 - ALL POSTS AND TIMBERS DOUG-FIR #1 1200 1000 REFER TO PLAN NOTES, SCHEDULES, AND DETAILS FOR MORE SPECIFIC LUMBER SIZE AND GRADE REQUIREMENTS. UNLESS NOTED OTHERWISE IN THE PLANS, ALL WOOD AND WOOD -BASED MEMBERS EXPOSED TO WEATHER OR IN CONTACT WITH CONCRETE, MASONRY, OR WITHIN 8" OF SOIL SHALL BE PRESERVATIVE -TREATED BY VACUUM -PRESSURE IMPREGNATION IN ACCORDANCE WITH AWPA STANDARD U1. NAILS, BOLTS, AND METAL CONNECTORS FOR WOOD ALL NAILS SHALL CONFORM TO THE STANDARDS SET FORTH BY THE NATIONAL DESIGN STANDARDS (NDS) FOR WOOD CONSTRUCTION, LATEST EDITION. NAILING NOT SPECIFIED SHALL BE PER IBC TABLE 2304.10.1 NAILING SCHEDULE. ALL NAILS CALLED OUT ON PLANS SHALL BE COMMON NAILS UNLESS NOTED OTHERWISE AND SHALL MEET OR EXCEED THE FOLLOWING MINIMUM GUIDELINES: NAIL SHANK 0 MIN LENGTH 8d COMMON 0.1310 2 1/2" SHANK 10d COMMON 0.1480 3" SHANK 12d COMMON 0.1480 3 1/4" SHANK 16d COMMON 0.1620 3 1/2" SHANK 10d BOX NAILS MAY BE SUBSTITUTED FOR 8d COMMON NAILS WITH NO CHANGE IN NAIL SPACING. FRAMING MEMBERS MAY BE NAILED WITH 16d SINKERS (0.148" 0 x 3 1/4"), BUT ONLY 16d COMMON NAILS SHALL BE USED WHERE 16d NAILS ARE INDICATED IN THIS DRAWING SET. ENGINEER MAY APPROVE OTHER NAILS IF NAIL LABELS ARE SUBMITTED TO ENGINEER PRIOR TO START OF CONSTRUCTION. ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG SCREWS BEARING ON WOOD. LEAD HOLES FOR LAG BOLTS SHALL BE BORED FOR THE SHANK AND THREADED PORTIONS PER NDS 12.1.4.2. CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE" BY SIMPSON COMPANY, CATALOG TO BE THE LATEST EDITION, OR ENGINEER APPROVED EQUAL. CONNECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND WITH THE NUMBER AND SIZE OF FASTENERS AS SPECIFIED BY THE MANUFACTURER. WHERE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE ONE-HALF OF THE NAILS, SCREWS, OR BOLTS IN EACH MEMBER. INSTALL SOLID BLOCKING AT ALL BEARING POINTS. ALL SHIMS SHALL BE SEASONED, DRIED, AND THE SAME GRADE (MINIMUM) AS MEMBERS CONNECTED. GALVANIZATION UNLESS NOTED OTHERWISE, STEEL CONNECTORS IN CONTACT WITH TREATED WOOD SHALL BE GALVANIZED ACCORDING TO THE FOLLOWING TABLE: GALVANIZATION UNTREATED WOOD CCA-C SBX ACQ-C ACQ-D CBA-A CA-B OTHER BORATE ACZA OTHER PT WOOD G90 X X X G 185 X X X X X X HDG X X X X X X STT300 X X X X X X X X G90 = 0.90 OZ. OF ZINC PER SQUARE FOOT OF AREA G185 = 1.85 OZ. OF ZINC PER SQUARE FOOT OF AREA HDG = HOT DIP GALVANIZED SST300 = TYPE 316L STAINLESS STEEL 1. BEARING WALL FRAMING 2x STUDS @ 16" OC FOR ALL SHEAR AND/OR BEARING WALLS UNO. REFER TO FRAMING PLAN NOTES FOR TYPICAL DOOR & WINDOW HEADERS NOT CALLED OUT ON THE PLANS. HEADERS SHALL BE SUPPORTED BY A MINIMUM OF (1) CRIPPLE AND (1) FULL HEIGHT STUD UNO. COLUMNS BELOW FLUSH MULTIPLE JOIST BEAMS SHALL BE EQUAL IN WIDTH TO THE BEAM. ALL COLUMNS NOT CALLED OUT OTHERWISE SHALL BE TWO STUDS. 2. WALL BASE PLATE ON CONCRETE WALL PLATES BEARING ON CONCRETE SHALL BE PRESSURE -TREATED. FOR ALL EXTERIOR AND INTERIOR WALLS, BOLT PLATES OR SILLS TO CONCRETE STEM WALLS OR THICKENED SLAB FOOTINGS WITH 5/8 INCH DIAMETER ANCHOR BOLTS WITH 7 INCH MINIMUM EMBEDMENT. PLACE AT 5-0" OC MAXIMUM FOR SHEAR WALLS, AND AT 6'-0" OC FOR BEARING WALLS AND OTHER PARTITIONS. USE MINIMUM OF TWO ANCHOR BOLTS PER SILL AND PLACE ONE WITHIN 12 INCHES OF END OF PLATES, TYPICAL UNLESS NOTED OR DETAILED OTHERWISE. REFER TO SHEAR WALL SCHEDULE. AT ALL SILL PLATE ANCHOR BOLTS, CONTRACTOR SHALL INSTALL 1/4" x 3" x 3" FLAT PLATE WASHERS. INTERIOR NON-STRUCTURAL WALLS MAY BE ANCHORED TO CONCRETE SLAB -ON -GRADE WITH 1/4" x 3" POWDER ACTUATED FASTENERS WITH 3/4" WASHERS AT 16" OC AND WITHIN 6" OF END OF PLATES. 3. ROOF AND FLOOR FRAMING PROVIDE 1 1/2" FULL DEPTH BLOCKING FOR JOISTS AND RAFTERS AT ALL SUPPORTS AND AT 8'-0" OC MAXIMUM UNO. INTERMEDIATE 8'-0" OC BLOCKING NOT REQ'D IF GWB CEILING IS INSTALLED DIRECTLY TO UNDERSIDE OF FRAMING. INSTALL DOUBLE JOISTS UNDER PARTITIONS EXTENDING ONE HALF OR MORE OF THE JOIST SPAN. PROVIDE TRUSS BLOCKING PANELS FOR ROOF TRUSSES AT SUPPORTS AND SHEAR WALLS, AND WHERE INDICATED ON PLANS AND DETAILS. 4. DIAPHRAGM NAILING ALL SHEAR WALLS, FLOOR AND ROOF DIAPHRAGM NAILINGS SHALL BE AS CALLED OUT ON SCHEDULES OR ON THE PLANS. EXTERIOR WALLS NOT INDICATED AS SHEAR WALLS SHALL BE SHEATHED AND NAILED TO SUPPORTING FRAMING WITH 8d NAILS AT 6" OC AT ALL PANEL EDGES AND 12" OC AT ALL INTERMEDIATE SUPPORTS. THE USE OF NAIL GUNS WILL BE APPROVED IF NAILING INTO THE DIAPHRAGMS CAN BE INSTALLED FLUSH WITH FACE OF SHEATHING. NAIL PENETRATIONS GREATER THAN 1/16" ARE NOT ACCEPTABLE. l.�e\��il►tit/e\ l���r�1�7e1►1�1»e���»►1��:7e��[�7►(.y CUTTING AND/OR NOTCHING OF WOOD STUDS OR PLATES SHALL NOT EXCEED 25% OF THE STUD/PLATE WIDTH IN EXTERIOR AND BEARING WALLS AND SHALL NOT EXCEED 40% OF THE STUD/PLATE WIDTH IN ANY NON -BEARING PARTITIONS. BORED HOLE DIAMETER IS LIMITED TO 40% OF STUD/PLATE WIDTH IN ANY STUD AND MAY BE 60% IN NONBEARING PARTITIONS OR IF STUD IS DOUBLED. MAINTAIN 5/8" MINIMUM EDGE DISTANCE FROM HOLE EDGE. 6. GYPSUM WALLBOARD NAILING ALL GYPSUM WALLBOARD SHALL BE NAILED TO ALL STUDS AND TOP AND BOTTOM PLATES WITH 6d COOLER NAILS OR NO. 13 GAUGE x 1 5/8" @ 7" OC (5d COOLER NAILS FOR 1/2 INCH GYPSUM SHEATHING). TYPICAL UNLESS NOTED OTHERWISE. INSTALLATION OF GWB SHALL BE SUCH THAT JOINTS ARE STAGGERED ON EACH SIDE OF A SINGLE WALL. EXISTING BUILDING CONTRACTOR SHALL VERIFY ALL DIMENSIONS, MEMBER SIZES AND CONDITIONS OF THE EXISTING BUILDING DEPICTED IN THE DRAWINGS, AND NOTIFY THE STRUCTURAL ENGINEER OF ANY DISCREPANCIES FOR POSSIBLE REDESIGN. CONTRACTOR RESPONSIBLE FOR COMPLETELY SEALING ALL AREAS WHERE EXISTING ROOF MATERIAL IS PENETRATED OR REMOVED. PROVIDE WATER PROOFING AS REQUIRED. GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS BEFORE PROCEEDING. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER BEFORE PROCEEDING. CONTRACTOR SHALL BE RESPONSIBLE FOR ERECTION STABILITY AND TEMPORARY SHORING AS NECESSARY UNTIL PERMANENT SUPPORT AND STIFFENING ARE INSTALLED. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL NOT SATISFY THIS REQUIREMENT. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF A SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE STRUCTURAL ENGINEER. APPROVED PLANS MUST BE ON JOB SITE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE LEGEND DEFINITION SYMBOL DEFINITION SYMBOL �1=1��=���=��� DIRECTION OF FRAMING NATIVE SOIL - - - - - EXTENT OF FRAMING 0.1 GRANULAR FILL STRUCTURAL STEEL COLUMNS P COLUMN BEARING RATED SHEATHING ON BEAM BEAM CONTINUOUS SHEAR WALL OVER SUPPORT (SEE SCHEDULE) SWX COLUMN MARK G� CONCRETE WALL (SEE SCHEDULE) / BEARING STUD FOOTING MARK O WALL (SEE SCHEDULE) NON -BEARING t HOLDOWN MARK STUD WALL (SEE SCHEDULE) BEARING STUD HANGER MARK O SHEAR WALL (SEE SCHEDULE) NON -BEARING FLAG NOTE STUD SHEAR WALL (SEE PLAN NOTES) CMU WALL STEEL MOMENT �V FRAME CONN. ABBREVIATIONS (A) ABOVE ANCHOR BOLT ALTERNATE ARCHITECT BELOW BLOCKING HORIZ HORIZONTAL KING POST KIPS PER SQUARE INCH AB ALT KIP KSI ARCH (B) BLKG MECH MECHANICAL MOMENT FRAME NEAR SIDE MF NS BM BOT BEAM BOTTOM OC ON CENTER OPPOSITE PLATE PLACES POUNDS PER SQUARE INCH POUNDS PER SQUARE FOOT OPP BTWN BETWEEN COMPLETE JOINT PENETRATION PL CJP PLCS CLR CLEAR CONCRETE MASONRY UNIT PSI CMU PSF COL COLUMN P/T POSTTENSIONED CONC CONCRETE PT PRESSURE TREATED CONN CONNECTION REINF REINFORCING CONT CONTINUOUS REQ'D REQUIRED DBL DET DOUBLE DETAIL SCHED SIM SCHEDULE SIMILAR SLAB ON GRADE STANDARD SHEAR WALL TOP OF CONCRETE TOP OF STEEL TOP OF WALL TYPICAL UNLESS NOTED OTHERWISE DIM DIMENSION SOG EA EACH STD ELEV ELEVATION SW EXIST EXISTING TOC EXP FLR EXPANSION TOS FLOOR TOW FDN FTG FOUNDATION FOOTING FAR SIDE FULL HEIGHT GLUE -LAMINATED BEAM TYP LINO FS VFY VERIFY VERIFY IN FIELD VERTICAL FH VIF GLB VERT C G ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 (38/ 28/ 23 m W F- 00 Q N 0 00 O DESIGN: LMS DRAWN: JCP CHECK: JGG JOB NO: 23164.10 DATE: 08/28/23 RECEIVED Nov 09 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2023-1397 La The following documentation shall be available on ! Z ■ site for the building inspector: o Lj Lj ■ U; N 0 0 x❑ COE APPROVED ARCHITECTURAL PLAN SET ! c 0)0 Z W X❑ COE APPROVED STRUCTURAL PLAN SET ; Z w ❑ COE REVIEWED CALCULATION PACKET ! Imo- Q Q ' ENERGY CREDIT WORKSHEET ' D ■ ' Z V) ❑ SITE PLAN 0 LaQ U ❑ CIVIL PLAN ! Q :2 ZO D .❑ ■ ! Q N in■ ❑ W cn !tl CITY OF EDMONDS BUILDING DEPARTMENT 2021 ■ SHEET: S1.1 EXIST 46 HDR (VFY) ----------------------- ------------ ---- -- ----- -- - - - - �� I N l I I F-- 0 0 I I I O I I oxo u O I I NO U I V)LL N I I Lu @J w I 2 I S3.1 _ II EXIT F -1 Q EXIST 46 F -1 EXIST 46 r INE4I L ■ i �I.�STCOC �/�� �}\�� V-6" x V-6" x 0'-10" LLJ Lu 00 Ln --A- DEEP FOOTING W/ (2) O > > /y/� SISTER JOISTS W/ (2) #4 REINF EA WAY BOT = O = O I 00 � 00 CC ROWS 16d NAILS @ O O 1 cv E" - 16" OC STAGGERED u` 00 I I N N WHERE EXIST JOIST N O N I I OCCURS, SISTER (1) N �q x j I 2x8 TO EXIST JOIST w @j I I I I EXIST 46 r EXIS 4x 0, EXIST 4x6 ■ L_J L_ L_J I I N I I N I I 0 I I 00 u I I cx 0 I I I__ N EXIST 14" x 14" x 10" I I Ix @) DEEP FOOTING, TYP I I I I I I I I I I I I IL------- ----- ------ I I L- - - - - - - - - - - - - - - - - - - - - - - - - - PARTIAL FOUNDATION AND MAIN FLOOR FRAMING PLAN SCALE: 1/4" = V-0" FOUNDATION PLAN NOTES: 2'-0" 0 1. FOOTINGS AND SLAB ON GRADE SHALL BEAR ON FIRM NATIVE SOIL OR COMPACTED STRUCTURAL FILL. 2. REFER TO SHEET S3.1 FOR FOUNDATION DETAILS. 3. PLACE ALL REINFORCEMENT PER THE STRUCTURAL NOTES AND FOUNDATION DETAILS. 4. FOUNDATION LEVEL HOLDOWNS ARE SHOWN ON SECOND FLOOR FRAMING PLAN. REFER TO HOLDOWN SCHEDULE FOR HOLDOWN TYPES AND SECOND FLOOR FRAMING PLAN FOR HOLDOWN ANCHOR BOLT LOCATIONS. MAIN FLOOR FRAMING PLAN NOTES: REFER TO TYPICAL FLOOR FRAMING PLAN NOTES. T-0" 4'-0" EXIST 4x8 HDR i 2 2 00 00 x x N N N N /y\C INFILL EXIST OPENING (NON-STRUCTURAL) POCKET BEAM PER 5/S3.1 EXIST BEAM O O O LL N x Lu CONNECT HOLDOWN TO FOUNDATION PER DET 1/S3.1 V) N O O 0 LL H x w 4x10 n62 HDR 5'-3 1/2" EXIST 4x6 HDR (VFY/PROVIDE) EXIST FLOOR JOISTS EXIST BEAM PARTIAL SECOND FLOOR FRAMING PLAN SCALE: 1/4" = V-0" TYPICAL FLOOR FRAMING PLAN NOTES: I 2' 4' 1. COLUMNS AND BEARING WALLS SHOWN ON PLANS SHALL BE CONTINUED DOWN TO THE FOUNDATION UNLESS CARRIED BY A BEAM BELOW. 2. REFER TO SHEET S3.1 FOR TYPICAL FLOOR FRAMING DETAILS. 3. WALLS SHOWN ON THE FRAMING PLANS ARE WALLS BELOW THE FRAMING LEVELS INDICATED. HOLDOWNS SHALL BE PLACED AT THE BASE OF THE WALLS SHOWN. 4. TYPICAL HEADERS AT BEARING LOCATION SHALL BE SUPPORTED BY A MINIMUM OF (1) CRIPPLE STUD AND (1) FULL HEIGHT STUD. 5. COLUMNS NOT OTHERWISE SHOWN OR CALLED OUT ON PLAN SHALL BE (2) 2x STUDS. 6. UNLESS NOTED OTHERWISE ALL STUDS SHALL BE HF STUD GRADE AND SPACED AT 16" OC. V-9" T-0" H EXIST WALLS TO BE REMOVED 8'-0" CONNECT HOLDOWN TO BEAM BELOW PER DETAIL 7/S3.1 NOTE: PRIOR TO DEMO OR REMOVAL OF ANY EXISTING STUD WALL, THE CONTRACTOR SHALL EVALUATE AND VERIFY THAT THE STUD WALL DOES NOT SUPPORT EXISTING FRAMING. IF IN QUESTION, CALL THE ENGINEER. ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 I V I I I (DuII I I wlI G (Du Lu J 01 1 1 1 6 1 z z 0 INFILL OPENING PER w 11 11 <I IJW z Lu TYPICAL FRAMING Q rl I I I 00 I� w u x I I I I xl I �, N @J NOTES ON S1.1 00 u N cn L__J L___�I N 1O N rA N N --- N N 11 N N r c~n = NN w OII wll� ,� Ix0 i z w p I1 S2 EXIST BEAM EXIST HDR 1 1 8 a 1 1 i 53.1 4)x6 H F # 2 IST HDR 1L rl Q 4x6 HF#2 LALALA A. I v, EXIST 2x8 RIDGE --- ■ HDR G� W L HDR g -10 2'-6" 2'-4" EXIST 2x4 RAFTERS �� of WAS S 00 2'-6" EXIST 2x8 RAFTERS W/ COLLAR TIES @ 24" OC + F (� o L.Li @ 24" 0000 x v, N x0 zu + + �d "' N_ N _EXIST EXIST w O + + + + + + 0� 39553 �o EXIST OVERFRAMING x VALLEY X @� + + + + �sIONAL��~ Lu @) y RAFTERS RAFTER EXIST N *�� wo + ++++++++ ++ 08128125 EXIST BEAM Q � N + + + + + + + L z u + + + + + + + + N J O Lu Z N LJJ z J O u rl LL Lu a O N N rNl O N N N N N LU O x XLu Lu _1 /I EF==l la T-0" 4'-0" EXIST RAFTERS PARTIAL ROOF FRAMING PLAN SCALE: 1/4" = V-0" TYPICAL ROOF FRAMING PLAN NOTES: 1. WALLS SHOWN ON ROOF FRAMING PLAN ARE WALLS BELOW ROOF FRAMING. 2. BEAMS SHOWN ON ROOF FRAMING PLAN SHALL BE ABOVE DOUBLE TOP PLATE UNLESS USED AS A DOOR OR WINDOW HEADER. 3. STUD WALL FRAMING SHALL BE 2x HF STUDS @ 16" OC FOR ALL STUD WALLS SHOWN ON THE PLAN. 4. REFER TO SHEET S3.1 FOR TYPICAL ROOF FRAMING DETAILS. 5. REFER TO DETAIL 4/S3.1 FOR CONSTRUCTION OF MULTIPLE STUD COLUMNS. 6. REFER TO THE STRUCTURAL NOTES SHEET FOR COLUMNS SUPPORTING TYPICAL BEARING WALL HEADER BEAMS. 7. COLUMNS AND BEARING WALLS SHOWN ON PLAN SHALL BE CONTINUED DOWN TO THE FOUNDATION UNLESS CARRIED BY ABEAM BELOW. 8. HOLDOWNS SHOWN ON ROOF FRAMING PLAN SHALL BE PLACED ON SECOND FLOOR LEVEL. HOLDOWN SCHEDULE MARK TYPE MIN CHORD SIZE STUD NAILS OR BOLTS ANCHOR BOLT (SEE NOTE 4) CAPACITY (LB) 1 HDU2 (2) 2x (6) SDS 1/4" x 2 1/2" SCREWS 5/8"0 2,215 NOTES: 1. REFER TO THE LATEST SIMPSON STRONG -TIE CATALOG FOR ADDITIONAL INSTALLATION REQUIREMENTS. 2. REFER TO DETAIL 6/S3.1 FOR INSTALLATION OF ROD FLOOR TO FLOOR HOLDOWNS. REFER TO DETAIL 7/S3.1 FOR CONNECTION OF ROD HOLDOWN TO BEAM BELOW. 3. INSTALL HD HOLDOWNS AT FOUNDATION WALLS OR THICKENED SLAB FOOTINGS PER DETAIL 1/S3.1. 4. AT ALL HOLDOWN CHORDS, PROVIDE PANEL EDGE NAILING PER SHEAR WALL SCHED. SHEAR WALL SCHEDULE APA-RATED MIN FRAMING AT SHEAR WALL RIM JOIST OR SILL PLATE NAILING TO SILL PLATE ANCHOR FOUNDATION SHEAR TYPE SHEATHING ADJOINING PANEL NAILING BLOCK CONN TO RIM/BLKG BOLT TO SLAB OR SILL PLATE SIZE CAPACITY EDGES (SEE NOTE 5) AT PANEL EDGES TOP PLATE FOUNDATION (PLF) BELOW 15/32" 2x STUD 0.131"0 x 2 1/2" LTP4 OR A35 0.131"0 x 3" @ 5/8" 0 AB SW6 ONE SIDE AND BLKG @ 6" OC @ 24" OC 6" OC @ 5'-0" OC 2x 242 15/32" 2x STUD 0.131"0 x 2 1/2" LTP4 OR A35 0.131"0 x 3" @ 5/8" 0 AB SW4 ONE SIDE AND BLKG @ 4" OC @ 20" OC 4" OC @ 4'-0" OC 2x 350 15/32" (2) 2x STUD AND 0.131"0 x 2 1/2" LTP4 OR A35 0.131"0 x 3" @ 5/8" 0 AB SW3 ONE SIDE 2x FLAT BLKG @ 3" OC @ 15" OC 3" OC @ T-0" OC 2x 455 15/32" 3x STUD AND 0.131"0 x 2 1/2" LTP4 OR A35 0.131"0 x 3" @ 5/8" 0 AB SW2 ONE SIDE 2x FLAT BLKG @ 2" OC @ 12" OC 2.5" OC @ 2'-6" OC 2x 595 15/32" (2) 2x STUD 0.131"0 x 2 1/2" LTP4 OR A35 0.131"0 x 3" @ 5/8" 0 AB 2SW4 BOTH SIDES AND BLKG @ 4" OC @ 10" OC 2" OC @ 2'-0" OC 2x 706 15/32" (2) 2x STUD 0.131"0 x 2 1/2" LTP4 OR A35 0.131 x 3" 5/8" 0 AB 2SW3 BOTH SIDES AND BLKG @ 3" OC @ 7.5" OC @ 1.5" OC @ V-6" OC 2x 910 15/32" 3x STUD 0.131"0 x 2 1/2" LTP4 OR A35 0.131 x 3" 5/8" 0 AB 2SW2 BOTH SIDES AND BLKG @ 2" OC @ 6" OC @ 1.5" OC @ 1'-0" OC 2x 1190 NOTES: 1. REFER TO THE TYPICAL SHEAR WALL DETAIL. 2. THE VALUES IN THIS TABLE ARE APPROPRIATE FOR HF GRADE STUDS AND HF GRADE PLATES & RIM/BLOCKING. 3. NAILS AT ADJOINING PANEL EDGES SHALL BE STAGGERED EACH SIDE OF THE COMMON JOINT. 4. WHERE PANELS ARE APPLIED ON BOTH FACES OF A WALL, PANEL JOINTS SHALL BE OFFSET TO FALL ON DIFFERENT FRAMING MEMBERS, OR FRAMING SHALL BE 3x AT ADJOINING PANEL EDGES AND NAILS SHALL BE STAGGERED. 5. WHERE TABLE SPECIFIES (2) 2x FRAMING, CONNECT (2) 2x STUDS AND BLOCKING AS FOLLOWS: SW3 = (2) 0.131"0 @ 3.5" OC, 2SW4 = 0.131" 0 @ 2.5" OC, 2SW3 = (2) 0.131" 0 @ 1.5" OC. 6. NOTE THAT 3x FRAMING MAY BE USED IN LIEU OF (2) 2x FRAMING SPECIFIED IN TABLE. 7. INTERMEDIATE FRAMING TO BE WITH 2x MINIMUM MEMBERS. FIELD NAILING 12" OC MAXIMUM. 8. AT ALL 5/8"0 SILL PLATE ANCHOR BOLTS, INSTALL 1/4" x 3" x 3" PLATE WASHERS. EDGE OF PLATE WASHER SHALL BE WITHIN 1/2" OF SHEATHED EDGE. FOR DOUBLE SIDED SHEAR WALLS, USE WIDER PLATE WASHERS AS REQUIRED TO MEET THIS REQUIREMENT. 9. PROVIDE A MINIMUM OF 7" EMBEDMENT FOR AB INTO FOUNDATION OR STEM WALL. 10. 7/16" SHEATHING MAY BE USED IN PLACE OF 15/32" SHEATHING PROVIDED ALL STUDS ARE SPACED 16" OC OR PANELS ARE APPLIED WITH LONG DIMENSION ACROSS STUDS. J Z O m U U � W 0 Lu d Ld m N F- Q 00 � 0 00 O Y Q DESIGN: LMS DRAWN: JCP CHECK: JGG JOB NO: 23164.10 DATE: 08/28/23 RECEIVED Nov 09 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Z BLD2023-1397< 0 Z Q Z 0 => w v Z Q W 0 V) N Z W 0 _,_,.,°' �- I- a 0 LL. V) O D azVj o � Ld a 7 w z Z0 0�0 W w SHEET: S2ml C GI HOLDOWN CHORD PER PLAN & HOLDOWN SCHEDULE CRIPPLE STUD AT OPENING AS REQ'D PER PLAN & DETAILS NOTE: EXTEND THREADED ROD BETWEEN JOISTS INTO STEM WALL BELOW. PROVIDE ROD COUPLER IF REQ'D. THREADED ROD AS REQ'D PER PLAN AND HOLDOWN SCHEDULE. INSTALL W/ HILTI HIT-HY 200 EPDXY EXISTING CONCRETE STEM WALL TOP OF EXISTING FOOTING SHEAR WALL PER PLAN AND SCHED HOLDOWN PER PLAN AND SCHED ii II II I I SQUASH BLKG TO MATCH HOLDOWN ///I I CHORD ABOVE II � II II II HOLDOWN DETAIL (EXIST FOOTING SCALE: 1" = V-0" NOTE: SUPPORTS AT SOLID POSTS SIM BEAM PER F SIMPSON LTPi A35 FRAN ANCHOR EACH. OF BI SOLID OR MULT STUD COLUMN PER F,_ WHIM VIVI/ PARALLEL TO STUD WALL POST PER PLAN ATTACH TO SILL W/ (4) 16d TOE -NAILS POST TO MATCH POST ABOVE EXIST SILL PLATE EXIST FLOOR SYSTEM SIMPSON A34 CLIP EA SIDE SIMPSON ABU POST BASE W/ 5/8" 0 TITEN HD SCREW ANCHOR m II z �Ilil IIII as u LU CC II e e 0 w a SIZE & REINF m PER PLAN C RAW LS PACE DETAIL SCALE: 1" = V-0" JOIST DIRECTION PER PLAN STUD WALL TYPICAL FLUSH BEAM SUPPORT DETAILS SCALE: 1" = V-0" SOLID STUD COLU,.,,. PERPENDICULAR TO STUD WALL SIMPSON A35 (ONLY REQUIRED AT EXTERIOR HEADERS GREATER THAN U SPAN) (6) 0.131"0 x 3" NAILS TYPICAL STUDS NAILING PER TYP BUILT-UP STUD COLUMN DETAIL AT HOLDOWNS: PROVIDE FULL HT HOLDOWN CHORDS PER HD SCHED OTHERWISE: (1) 2x FULL HT TYPICAL HEADER DETAIL SCALE: 1" = V-0" STUD WALL TYP DOUBLE TOP PLATE BEAM OR HEADER PER PLAN AND NOTES CRIPPLE STUDS PER PLAN AND STRUCTURAL NOTES ADJACENT NAILS IN A ROW ARE TO BE DRIVEN FROM OPPOSITE SIDES, TYP FOR 2x4 STUDS, PROVIDE SINGLE ROW OF NAILS STAGGERED EA SIDE WITH 1 1/2" EDGE DISTANCE. FOR 2x6 STUDS, PROVIDE (2) ROWS OF NAILS SPACED AT 2 1/2" W/ 1 1/2" EDGE DISTANCE 9" OC MAX SPACING BETWEEN ADJACENT NAILS IN A ROW 0.131"0 x 3" NAILS, TYP (5) STUDS MAX TO BE USED FOR BUILT-UP COLUMNS TYPICAL BUILT-UP STUD COLUMN DETAIL SCALE: 1" = V-0" CHORD SIZE PER HOLDOWN SCHEDULE SIMPSON HOLDOWN PER PLAN AND SCHEDULE JOIST DIRECTION PER PLAN FILL JOIST SPACE WITH BLOCKING TO MATCH DIMENSIONS OF STUD COLUMN ABOVE COUNTER SINK ADDITIONAL END STUD FOR BOLTS TYPICAL ROD HOLDOWN DETAIL SCALE: 1" = V-0" SHEATHING AND NAILING PER PLAN AND SHEAR WALL SCHEDULE BEARING PLATE 3/8 x 3 1/2 x 0'-3 1/2" HOLDOWN PER PLAN SILL PLATE NAILING PER PLAN AND SHEAR WALL SCHEDULE EXIST SHEATHING EXIST FLOOR JOISTS PER PLAN WOOD BEAM PER PLAN ROD HOLDOWN TO WOOD BEAM SCALE: 1" = V-0" PANEL EDGE NAILING PER EXIST RAFTER SHEAR WALL SCHEDULE PER PLAN EXIST SHEATHING Nl- rx I _N EXIST RAFTER PER PLAN 2x4 BLKG AT ALL VFY/PROVIDE CEILING I PANEL EDGES JOIST PER PLAN 11 2x4 BLOCKING 2x4 W/ (2) 10d NAILS W/ SILL PLATE @ 24" AS REQ'D FOR NAILING PER SHEAR CEILING ATTACHMENT WALL SCHEDULE SILL PLATE NAILING PER SHEAR WALL SCHEDULE EXIST CEILING JOIST PER PLAN PANEL EDGE NAILING PER SHEAR WALL SCHEDULE 2x4 BLKG @ 16" STUD WALL W/ SHEATHING OC AS REQ'D & NAILING PER PLAN AND FOR CEILING SHEAR WALL SCHEDULE ATTACHMENT A. RAFTER ALIGNED WITH SHEAR WALL INTERIOR SHEAR WALL SECTION SCALE: 1" = V-0" EXIST CEILING JOIST PER PLAN 2x CONTINUOUS FULL LENGTH TO OVERLAP SHEAR WALL NOTE: FOR NOTES AND DETAILS NOT SPECIFICALLY CALLED OUT REFER TO CASE A VFY/PROVIDE CEILING JOIST PER PLAN SILL PLATE NAILING PER SHEAR WALL SCHEDULE 2x4 BLKG @ 16" OC AS REQ'D FOR CEILING ATTACHMENT B. RAFTER ADJACENT TO SHEAR WALL ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 08/ 28/ 23 m rlj 00 Q 00 O Y Q DESIGN: LMS DRAWN: JCP CHECK: JGG JOB NO: 23164.10 DATE: 08/28/23 RECEIVED Nov 09 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT wt BLD202AL57V) z � Q ~ �Q Lf Ld La U 0 IV w OZ o O 0 () W N �:: Q cy- 0 z W Oi ' L.L "�- a 0� D V) � 0 Q z QO W Q 0 m LL m Z � 0 Ix0) < :20 0 z z �j SHEET: S3ml