REVIEWED BLD RESUB1 BLD2024-0733+STRUCTURAL_Plan+7.16.2024_8.55.29_AM+43798301. ALL MATERIALS WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE 2021 INTERNATIONAL BUILDING CODE (IBC) INCLUDING WASHINGTON STATE MODIFICATIONS. 2. DESIGN LOADING CRITERIA SNOW LOAD FLOOR LIVE LOAD (RESIDENTIAL) WIND (MAIN WIND FORCE RESISTING SYSTEM) EARTHQUAKE (EQUIVALENT LATERAL FORCE PROCEDURE) ADDITION ONLY RAIN INTENSITY GROUND SNOW LOAD, Pg = 25 PSF ROOF SNOW LOAD, Pt = 25 PSF IMPORTANCE FACTOR, 15= 1.0 EXPOSURE FACTOR, Ce= 0.9 THERMAL FACTOR, Ct= 1.1 SLOPED ROOF FACTOR, Cs = 1.0 40 PSF BASIC WIND SPEED = 97MPH ALLOWABLE STRESS DESIGN WIND SPEED = 75 MPS IMPORTANCE FACTOR, IW= 1.0 RISK CATEGORY = II TOPOGRAPHIC FACTOR, KZc = 1.0 EXPOSURE CATEGORY = C INTERNAL PRESSURE COEFFICIENT, (GCp;)= 0.18/-0.18 SS= 1.29 Sds = 1.03 S,= 0.45 IMPORTANCE FACTOR, le= 1.0 SITE CLASS D -DEFAULT SEISMIC DESIGN CATEGORY= D RISK CATEGORY = II R = 6.5 FOR LIGHT FRAMED STRUCTURAL PANEL SHEAR WALLS OVER STRENGTH FACTOR, S�° = 2.5 (FLEXIBLE DIAPHRAGMS) DEFLECTION AMPLIFICATION FACTOR, Cd = 4.0 REDUNDANCY FACTOR = 1.0 SEISMIC RESPONSE COEFFICIENT, CS = 0.16 SEISMIC BASE SHEAR = 0.75 KIPS (ASD) 1.0 INCHES/HOUR 3. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS AND CONDITIONS FOR COMPATIBILITY AND SHALL NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO CONSTRUCTION. ALL DIMENSIONS SHOWN ON THE STRUCTURAL DRAWINGS ARE INTENDED FOR REFERENCE ONLY. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS. 4. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER SIZES, AND CONDITIONS PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THE STRUCTURAL DRAWINGS ARE INTENDED AS GUIDELINES ONLY AND MUST BE VERIFIED. 5. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR THE STRUCTURE AND STRUCTURAL COMPONENTS UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH THE PLANS. 6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AND THE METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM THE WORK. THE STRUCTURAL ENGINEER HAS NO OVERALL SUPERVISORY AUTHORITY OR ACTUAL AND/OR DIRECT RESPONSIBILITY FOR THE SPECIFIC WORKING CONDITIONS AT THE SITE AND/OR FOR ANY HAZARDS RESULTING FROM THE ACTIONS OF ANY TRADE CONTRACTOR. THE STRUCTURAL ENGINEER HAS NO DUTY TO INSPECT, SUPERVISE, NOTE, CORRECT, OR REPORT ANY HEALTH OR SAFETY DEFICIENCIES OF THE OWNER, CONTRACTORS, OR OTHER ENTITIES OR PERSONS AT THE PROJECT SITE. 7. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL NOT SATISFY THIS REQUIREMENT. 8. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED, BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND THE STRUCTURAL ENGINEER. 9. ALL STRUCTURAL SYSTEMS WHICH ARE TO BE COMPOSED OF COMPONENTS TO BE FIELD ERECTED SHALL BE SUPERVISED BY THE SUPPLIER DURING MANUFACTURING, DELIVERY, HANDLING, STORAGE, AND ERECTION IN ACCORDANCE WITH INSTRUCTIONS PREPARED BY THE SUPPLIER. 10. MECHANICAL /ELECTRICAL /PLUMBING: CONTRACTOR SHALL SUBMIT DRAWINGS SHOWING THE LOCATION, LOADS, AND ANCHORAGE OF ALL MECHANICAL, ELECTRICAL, PLUMBING, AND SPRINKLER ATTACHMENTS IN EXCESS OF 50 POUNDS TO STRUCTURAL ENGINEER FOR REVIEW PRIOR TO INSTALLATION. ALL DETAILS NECESSARY FOR ATTACHING THESE SYSTEMS TO THE BASE BUILDING STRUCTURE, INCLUDING THE DESIGN AND DETAILING OF THE DESIGNATED SEISMIC LOAD RESISTING SYSTEM AS REQUIRED BY SECTION 1705.14.3 OF THE INTERNATIONAL BUILDING CODE, ARE THE RESPONSIBILITY OF THE SUPPLIER OF THAT EQUIPMENT AND MUST BE STAMPED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF WASHINGTON. 11. STATEMENT SPECIAL INSPECTIONS: THE FOLLOWING CONSTRUCTION TYPES ARE TO BE REVIEWED BY A SPECIAL INSPECTOR DESIGNATED BY THE OWNER OR ARCHITECT. THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE COMPETENCE TO THE SATISFACTION OF THE BUILDING OFFICIAL, FOR INSPECTION OF THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION. SPECIAL INSPECTION SHALL CONFORM TO SECTION 1704 OF THE 2021 INTERNATIONAL BUILDING CODE. THE SPECIAL INSPECTION AGENCY SHALL BE RESPONSIBLE FOR KEEPING RECORDS OF SPECIAL INSPECTIONS AND TESTS. THE ARCHITECT, STRUCTURAL ENGINEER, AND BUILDING DEPARTMENT SHALL BE FURNISHED WITH COPIES OF ALL INSPECTION REPORTS AND TEST RESULTS. POST INSTALLED ANCHORS: PERIODIC SPECIAL INSPECTION IN ACCORDANCE WITH THE PRODUCTS APPROVED ICC-ES REPORT. GEOTECHNICAL 12. FOUNDATION NOTES: ALLOWABLE SOIL PRESSURE AND LATERAL EARTH PRESSURE ARE ASSUMED AND, THEREFORE, MUST BE VERIFIED BY A QUALIFIED SOILS ENGINEER. IF SOILS ARE FOUND TO BE OTHER THAN ASSUMED, NOTIFY THE STRUCTURAL ENGINEER FOR POSSIBLE FOUNDATION REDESIGN. FOOTINGS SHALL BEAR ON FIRM, UNDISTURBED EARTH AT LEAST 18" BELOW ADJACENT FINISHED GRADE, UNLESS OTHERWISE NOTED, FOOTINGS SHALL BE CENTERED BELOW COLUMNS OR WALLS ABOVE. BACKFILL BEHIND ALL RETAINING WALLS WITH FREE DRAINING, GRANULAR FILL AND PROVIDE FOR SUBSURFACE DRAINAGE. \ ALLOWABLE SOIL PRESSURE 2,000 PSF LATERAL EARTH PRESSURE (RESTRAINED/UNRESTRAINED) 60 PCF/35 PCF LATERAL EARTH PRESSURE (SEISMIC) 8H (ULTIMATE LOAD) PASSIVE EARTH PRESSURE (INCLUDES FACTOR OF SAFETY = 1.5) 150 PCF COEFFICIENT OF FRICTION (INCLUDES FACTOR OF SAFETY = 1.5) 0.25 CONCRETE 13. CONCRETE SHALL BE MIXED, PROPORTIONED, CONVEYED, AND PLACED IN ACCORDANCE WITH ACI 318-19 AND ACI 301-20. CONCRETE SHALL ATTAIN A 28-DAY STRENGTH (f'c) OF 3500 PSI BASED ON EXPOSURE CLASS F1, S0, W1, C1 AND SHALL CONTAIN NO LESS THAN 5-1/2 SACKS OF CEMENT, HAVE A MAXIMUM WATER/CEMENT RATIO OF 0.55, MAXIMUM AGGREGATE OF 3/4-INCH, AND A SLUMP OF 5 INCHES OR LESS. CONCRETE HAS BEEN DESIGNED BASED ON A CONCRETE STRENGTH (f'c) OF 2500 PSI PER INTERNATIONAL BUILDING CODE SECTION 1705.3 EXCEPTION 2.3 TO AVOID SPECIAL INSPECTIONS AND MATERIAL TESTING. ALL CONCRETE WITH SURFACES EXPOSED TO STANDING WATER SHALL BE AIR -ENTRAINED WITH AN AIR -ENTRAINING AGENT CONFORMING TO ASTM C260, C494M, AND C618. UNLESS OTHERWISE NOTED THE TOTAL AIR CONTENT SHALL BE 5%. AIR CONTENT SHALL BE SAMPLED IN ACCORDANCE WITH ASTM C172 AND AIR CONTENT MEASURED IN ACCORDANCE WITH ASTM C231 OR C173. 14. REINFORCING STEEL SHALL CONFORM TO ASTM A615 (INCLUDING SUPPLEMENTS S1), GRADE 60, Fy = 60,000 PSI. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185 15. DETAILING OF REINFORCING STEEL (INCLUDING HOOKS AND BENDS) SHALL BE IN ACCORDANCE WITH ACI SP-66-04 AND ACI 318-19 CHAPTER 25. LAP ALL REINFORCEMENTS AS FOLLOWS: BAR SIZE MINIMUM LAP LENGTH MINIMUM HOOK EMBEDMENT #3 24-INCHES 6-INCHES GENERAL RESIDENTIAL STRUCTURAL NOTES (The following apply unless shown otherwise on the plans) #4 32-INCHES 8-INCHES #5 40-INCHES 11-INCHES PROVIDE CORNER BARS AT ALL WALL AND FOOTING INTERSECTIONS. LAP ADJACENT MATS OF WELDED WIRE FABRIC A MINIMUM OF 8" AT SIDES AND ENDS. NO BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL BE FIELD BENT UNLESS SPECIFICALLY SO DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER. FIELD BENDING OF GRADE 60 REINFORCEMENT SHALL NOT BE ALLOWED. 16. CONCRETE PROTECTION (COVER) FOR REINFORCING STEEL SHALL BE AS FOLLOWS: FOOTINGS AND OTHER UNFORMED SURFACES CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3" ALL OTHER CASES 1-1/2" 17. CAST -IN -PLACE CONCRETE: SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND DIMENSIONS OF DOOR AND WINDOW OPENINGS IN ALL CONCRETE WALLS. SEE MECHANICAL DRAWINGS FOR SIZE AND LOCATION OF MISCELLANEOUS MECHANICAL OPENINGS THROUGH CONCRETE WALLS. SEE ARCHITECTURAL DRAWINGS FOR ALL GROOVES, NOTCHES, CHAMFERS, FEATURE STRIPS, COLOR, TEXTURE, AND OTHER FINISH DETAILS AT ALL EXPOSED CONCRETE SURFACES. TOLERANCES FOR ALL STRUCTURAL CONCRETE AND REINFORCEMENT SHALL BE IN ACCORDANCE WITH ACI 117-10 AND ACI 117.1R-14. RENOVATION 18. DEMOLITION: THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS BEFORE COMMENCING ANY DEMOLITION. SHORING SHALL BE INSTALLED TO SUPPORT EXISTING CONSTRUCTION AS REQUIRED, AND IN A MANNER SUITABLE TO THE WORK SEQUENCES. EXISTING REINFORCING SHALL BE SAVED WHERE AND AS NOTED ON THE PLANS. SAW CUTTING, IF AND WHERE USED, SHALL NOT CUT EXISTING REINFORCING THAT IS TO BE SAVED. DEMOLITION DEBRIS SHALL NOT BE ALLOWED TO DAMAGE OR OVERLOAD THE EXISTING STRUCTURE. LIMIT CONSTRUCTION LOADING (INCLUDING DEMOLITION DEBRIS) ON EXISTING FLOOR SYSTEMS TO 40 PSF. a. ALL NEW OPENINGS THROUGH EXISTING WALLS, SLABS AND BEAMS SHALL BE ACCOMPLISHED BY SAW CUTTING WHEREVER POSSIBLE. OVERCUTTING AT CORNERS SHALL NOT BE PERMITTED. b. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND LOCATION OF MEMBERS PRIOR TO CUTTING ANY OPENINGS. c. SMALL ROUND OPENINGS SHALL BE ACCOMPLISHED BY CORE DRILLING, IF POSSIBLE. d. WHERE NEW REINFORCING TERMINATES AT EXISTING CONCRETE, THREADED BARS INTO THREADED EXPANSION INSERTS IN EXISTING CONCRETE SHALL BE PROVIDED TO MATCH HORIZONTAL REINFORCING, UNLESS OTHERWISE NOTED ON PLANS. 19. CONTRACTOR SHALL CHECK FOR DRY ROT AT ALL EXTERIOR WALLS, EXISTING TOILET ROOM FLOORS AND WALLS, AREAS SHOWING WATER STAINS, AND ALL WOOD MEMBERS IN BASEMENT AND CRAWL SPACES. ALL ROT SHALL BE REMOVED AND DAMAGED MEMBERS SHALL BE REPLACED OR REPAIRED AS DIRECTED BY THE STRUCTURAL ENGINEER. 20. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER SIZES, AND CONDITIONS PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS ARE INTENDED AS GUIDELINES ONLY AND MUST BE VERIFIED. THE CONTRACTOR SHALL BRING ALL CONFLICTS AND DISCREPANCIES TO THE ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER. POST INSTALLED ANCHORS 21. POST -INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONSTRUCTION DOCUMENTS. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE ENGINEER -OF -RECORD PRIOR TO INSTALLING POST -INSTALLED ANCHORS IN PLACE OF MISSING OR MISPLACED CAST -IN -PLACE ANCHORS. CARE SHALL BE TAKEN IN PLACING POST - INSTALLED ANCHORS TO AVOID CONFLICTS WITH EXISTING REINFORCEMENT. HOLES SHALL BE DRILLED AND CLEANED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS AND THE ANCHOR'S ICC-ES REPORT. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE SPECIFIED BELOW SHALL BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER -OF -RECORD ALONG WITH CALCULATIONS THAT ARE PREPARED &SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF WASHINGTON. THE CALCULATIONS SHALL DEMONSTRATE THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING EQUIVALENT PERFORMANCE VALUES (MINIMUM) OF THE SPECIFIED PRODUCT USING THE APPROPRIATE DESIGN PROCEDURE AND/OR STANDARDS) AS REQUIRED BY THE INTERNATIONAL BUILDING CODE. SUBSTITUTIONS SHALL HAVE CURRENT ICC-ES APPROVAL. A. CONCRETE ANCHORS 1. MECHANICAL ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193. PRE -APPROVED MECHANICAL ANCHORS INCLUDE: a. SIMPSON STRONG -TIE "STRONG -BOLT 2" (ICC-ES ESR-3037) b. SIMPSON STRONG -TIE "TITEN-HD" (ICC-ES ESR-2713) 2. ADHESIVE ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC308. PRE -APPROVED ADHESIVE ANCHORS INCLUDE: a. SIMPSON STRONG -TIE "ET-3G" (ICC-ES ESR-5334) b. SIMPSON STRONG -TIE "SET-3G" (ICC-ES ESR-4057) c. SIMPSON STRONG -TIE "AT-3G" (ICC-ES ESR-4057) 1�••� 22. FRAMING LUMBER SHALL BE KILN DRIED OR MC-19, AND GRADED AND MARKED IN CONFORMANCE WITH WCLIB STANDARD GRADING RULES FOR WEST COAST LUMBER NO. 17, LATEST EDITION. FURNISH TO THE FOLLOWING MINIMUM STANDARDS. JOISTS: HEM -FIR NO. 2 (2X, 3X, AND 4X MEMBERS) MINIMUM BASE VALUE, Fb = 850 PSI STUDS PLATES &MISCELLANEOUS LIGHT FRAMING DOUGLAS FIR LARCH OR HEM -FIR NO. 2, MINIMUM BASIC DESIGN STRESS Fb = 850 PSI, Fc = 1,300 PSI 23. PREFABRICATED CONNECTOR PLATE WOOD ROOF TRUSSES SHALL BE DESIGNED BY THE MANUFACTURER IN ACCORDANCE WITH THE "NATIONAL DESIGN STANDARD FOR METAL PLATE CONNECTED WOOD TRUSS CONSTRUCTION", ANSI / TP 1-2014 FOR THE SPANS AND CONDITIONS SHOWN ON THE PLANS. LOADING SHALL BE AS FOLLOWS UNLESS NOTED OTHERWISE: TOP CHORD LIVE LOAD REFER TO DESIGN LOADING CRITERIA MINIMUM TOP CHORD DEAD LOAD 10 PSF MINIMUM BOTTOM CHORD DEAD LOAD 5 PSF MINIMUM WIND UPLIFT (TOP CHORD) 10 PSF WOOD TRUSSES SHALL UTILIZE APPROVED CONNECTOR PLATES (GANG -NAIL OR EQUAL) AND SHALL BE CONFIGURED SUCH THAT THE MAXIMUM OPENING BETWEEN MEMBERS DOES NOT EXCEED 42"X24". SUBMIT SHOP DRAWINGS AND DESIGN CALCULATIONS MEETING THE REQUIREMENTS OF INTERNATIONAL BUILDING CODE SECTION 2303.4 TO THE ARCHITECT, STRUCTURAL ENGINEER, AND BUILDING OFFICIAL FOR REVIEW PRIOR TO FABRICATION. SUBMITTED DOCUMENTS SHALL BEAR THE STAMP AND SIGNATURE OF A REGISTERED PROFESSIONAL ENGINEER, STATE OF WASHINGTON. PROVIDE FOR SHAPES, BEARING POINTS, INTERSECTIONS, HIPS, VALLEYS, ETC. SHOWN ON THE DRAWINGS. EXACT COMPOSITION OF SPECIAL HIP, VALLEY, AND INTERSECTION AREAS (USE OF GIRDER TRUSSES, JACK TRUSSES, STEP-DOWN TRUSSES, ETC.) SHALL BE DETERMINED BY THE MANUFACTURER UNLESS SPECIFICALLY INDICATED ON THE PLANS. PROVIDE ALL TRUSS -TO - TRUSS AND TRUSS -TO -GIRDER TRUSS CONNECTION DETAILS AND REQUIRED CONNECTION MATERIALS. PROVIDE FOR ALL TEMPORARY AND PERMANENT TRUSS BRACING AND BRIDGING. THE TRUSS MANUFACTURER SHALL COORDINATE LOCATIONS AND SUPPORT CONFIGURATIONS OF PLUMBING, MECHANICAL UNITS, DUCT WORK, AND OTHER MISCELLANEOUS ITEMS WITH THE CONTRACTOR PRIOR TO FABRICATION. TRUSSES SHALL BE DESIGNED TO SUPPORT ALL LOADS ASSOCIATED WITH SUCH ITEMS. THE TRUSS SHOP DRAWINGS SHALL INCLUDE ALL DESIGN LOADS AND APPROVED HANGER CONNECTION DETAILS TO TRUSS CHORDS FOR SUPPORT OF HUNG MECHANICAL SYSTEM COMPONENTS. ANY VARIATION FROM THE BEARING POINTS INDICATED ON THE STRUCTURAL DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR APPROVAL. 24. PLYWOOD SHEATHING SHALL BE GRADE C-D, EXTERIOR GLUE OR STRUCTURAL II, EXTERIOR GLUE IN CONFORMANCE WITH DOC PS 1-19 OR PS 2-18 AND AMERICAN PLYWOOD ASSOCIATION PERFORMANCE STANDARD PRP-108. ORIENTED STRAND BOARD OF EQUIVALENT THICKNESS, EXPOSURE RATING AND PANEL INDEX MAY BE USED IN LIEU OF PLYWOOD. SEE PLANS FOR THICKNESS, PANEL IDENTIFICATION INDEX AND NAILING REQUIREMENTS. EACH PANEL SHALL BE IDENTIFIED FOR GRADE AND GLUE TYPE BY THE TRADEMARKS OF AN APPROVED TESTING AND GRADING AGENCY. 25. ALL WOOD PLATES IN DIRECT CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE -TREATED WITH AN APPROVED PRESERVATIVE, PROVIDE 2 LAYERS OF ASPHALT IMPREGNATED BUILDING PAPER BETWEEN UNTREATED LEDGERS, BLOCKING, ETC. AND CONCRETE OR MASONRY. PRESSURE TREATED LUMBER SHALL COMPLY WITH THE AMERICAN WOOD PROTECTION ASSOCIATION (AWPA) STANDARD U1, COMMODITY SPECIFICATION A AS INDICATED BELOW OR HAVE EQUIVALENT ICC-ES APPROVAL. PROPOSED USE AWPA USE CATEGORY RESIDENTIAL DECKS DECKING 3B JOISTS ABOVE GROUND 3B JOISTS IN CONTACT WITH GROUND 4A POSTS RAILING 4A 3B LEDGERS 3B SAWN LUMBER ABOVE GROUND 3B GROUND CONTACT 4A 26 PLYWOOD DAMP ABOVE GROUND 2 EXTERIOR ABOVE GROUND 3B GROUND CONTACT 4A POLES ROUND 46 SAWN 3B FENCING PICKETS, SLATS, AND TRIM 3B SAWN POSTS 4A ROUND POSTS 4A RAILS 3B SILL PLATES INTERIOR LEDGERS IN CONTACT WITH CONCRETE OR MASONRY IN CONTACT WITH CONCRETE OR MASONRY 2 _ 2 ALL TREATED LUMBER SHALL BEAR THE QUALITY MARK OF AN ACCREDITED INSPECTION AGENCY. THE QUALITY MARK SHALL INCLUDE: A. IDENTIFICATION OF TREATING MANUFACTURER B. TYPE OF PRESERVATIVE USED C. MINIMUM PRESERVATIVE RETENTION (PCF) D. END USE FOR WHICH THE PRODUCT IS TREATED E. IDENTITY OF THE ACCREDITED INSPECTION AGENCY F. STANDARD TO WHICH THE PRODUCT IS TREATED TIMBER CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE" BY SIMPSON COMPANY, AS SPECIFIED IN THEIR CATALOG NUMBER C-C-2024. EQUIVALENT DEVICES BY OTHER MANUFACTURERS MAY BE SUBSTITUTED, PROVIDED THEY HAVE ICC-ES APPROVAL FOR EQUAL OR GREATER LOAD CAPACITIES. PROVIDE NUMBER AND SIZE OF FASTENERS AS SPECIFIED BY MANUFACTURER TO ACHIEVE THE MAXIMUM PUBLISHED ALLOWABLE LOAD. ALL CONNECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. WHERE THE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE ONE-HALF OF THE NAILS OR BOLTS IN EACH MEMBER. SHIMS, WHERE REQUIRED, SHALL BE SEASONED AND DRIED AND THE SAME GRADE (MINIMUM) AS MEMBERS CONNECTED. ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG SCREWS BEARING ON WOOD. ALL LAG SCREWS SHALL BE INSTALLED IN PRE -DRILLED HOLES. UNLESS NOTED OTHERWISE ALL SAWN LUMBER JOISTS SHALL BE CONNECTED TO FLUSH BEAMS WITH "LUS" SERIES JOIST HANGERS AND ALL PREFABRICATED PLYWOOD WEB JOISTS SHALL BE CONNECTED TO FLUSH BEAMS WITH "IUS" SERIES JOIST HANGERS. ALL CONNECTIONS/FASTENERS IN CONTACT WITH PRESERVATIVE -TREATED OR FIRE -RETARDANT -TREATED WOOD, SHALL BE OF HOT DIPPED ZINC -COATED GALVANIZED STEEL OR STAINLESS STEEL. HOT DIPPED GALVANIZED FASTENERS SHOULD CONFORM TO ASTM STANDARD 153, AND HOT DIPPED GALVANIZED CONNECTORS SHOULD CONFORM TO ASTM STANDARD A653 (CLASS G-185). STAINLESS STEEL FASTENERS AND CONNECTORS SHOULD BE TYPE 304 OR 316. NOTE: ELECTROPLATED GALVANIZED FASTENERS AND CONNECTORS ARE NOT TO BE USED WITH PRESSURE TREATED WOOD. SIMPSON PRODUCT FINISHES CORRESPONDING TO THE ABOVE REQUIREMENTS ARE ZMAX (HOT DIPPED GALVANIZED) AND SST300 (STAINLESS STEEL). STAINLESS STEEL HARDWARE AND FASTENERS SHALL NOT BE COMBINED WITH UNTREATED OR GALVANIZED MATERIAL. 27. WOOD FASTENERS A. NAIL SIZES SPECIFIED ON DRAWINGS ARE BASED ON THE FOLLOWING SPECIFICATIONS: SIZE LENGTH DIAMETER 6d 2" 0.113" 8d 2-1 /2" 0.131 " 10d 3" 0.148" 12d 3-1 /4" 0.148" 16d 3-1 /2" 0.162" DESIGN IS BASED ON COMMON STEEL WIRE NAILS MEETING THE REQUIREMENTS OF ASTM F1667. USE OF ALTERNATE FASTENERS MUST BE SUBMITTED FOR REVIEW AND APPROVAL BY THE STRUCTURAL ENGINEER PRIOR TO THE START OF CONSTRUCTION. B. NAILS -PLYWOOD (APA RATED SHEATHING) FASTENERS TO FRAMING SHALL BE DRIVEN FLUSH TO FACE OF SHEATHING WITH NO COUNTERSINKING PERMITTED. 28. WOOD FRAMING NOTES -THE FOLLOWING APPLY UNLESS OTHERWISE SHOWN ON THE PLANS: A. ALL WOOD FRAMING DETAILS NOT SHOWN OTHERWISE SHALL BE CONSTRUCTED TO THE MINIMUM STANDARDS OF THE INTERNATIONAL BUILDING CODE. MINIMUM NAILING, UNLESS OTHERWISE NOTED, SHALL CONFORM TO TABLE 2304.10.2 OF THE INTERNATIONAL BUILDING CODE. UNLESS NOTED OTHERWISE, ALL NAILS SHALL BE AS SPECIFIED ABOVE. COORDINATE THE SIZE AND LOCATION OF ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG SCREWS BEARING ON WOOD. INSTALLATION OF BOLTS AND LAG SCREWS SHALL CONFORM TO SECTIONS 12.1.3 AND 12.1.4 OF THE 2018 NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION. NATURALLY DURABLE OR PRESSURE TREATED WOOD SHALL BE PROVIDED WHERE REQUIRED BY SECTION 2304.12 OF THE INTERNATIONAL BUILDING CODE. B. WALL FRAMING: ALL STUD WALLS SHOWN AND NOT OTHERWISE NOTED SHALL BE 2X6 AT 16" O.C. TWO STUDS MINIMUM SHALL BE PROVIDED AT THE END OF ALL WALLS AND AT EACH SIDE OF ALL OPENINGS. TWO 2 x 8 HEADERS SHALL BE PROVIDED OVER ALL OPENINGS NOT OTHERWISE NOTED AND SHALL BEAR FULLY ON A MINIMUM OF TWO STUDS. SOLID BLOCKING FOR WOOD COLUMNS SHALL BE PROVIDED THROUGH FLOORS TO SUPPORTS BELOW. PROVIDE SOLID BLOCKING BETWEEN STUDS AT MID -HEIGHT OF ALL STUD WALLS OVER 10' IN HEIGHT. STUDS MAY BE NOTCHED, CUT, OR PENETRATED WITH ROUND BORED HOLES AS FOLLOWS: STUD SIZE MAXIMUM NOTCH /CUT MAXIMUM BORED HOLE 2X4 7/8" 1-3/8" 2X6 1-3/8" 2-1 /8" BORED HOLES SHALL NOT BE LOCATED WITH 5/8" FROM THE EDGE OF THE STUD OR AT THE SAME LOCATION AS A NOTCH OR CUT. WALLS SHALL HAVE A SINGLE BOTTOM PLATE AND A DOUBLE TOP PLATE. END NAIL TOP PLATE TO EACH STUD WITH TWO 16d NAILS, AND TOENAIL OR END NAIL EACH STUD TO BOTTOM PLATE WITH TWO 16d NAILS. FACE NAIL DOUBLE TOP PLATE WITH 16d AT 12" O.C. AND LAP MINIMUM 4'-0" AT JOINTS AND PROVIDE EIGHT 16d NAILS AT 4" O.C. EACH SIDE OF THE SPLICE. ALL STUD WALLS SHALL HAVE THEIR LOWER WOOD PLATES ATTACHED TO WOOD FRAMING BELOW WITH 16d NAILS AT 12" O.C. STAGGERED OR BOLTED TO CONCRETE WITH 5/8" DIAMETER ANCHOR BOLTS (WITH 7" MINIMUM EMBEDMENT) @ 4'-0" O.C. UNLESS INDICATED OTHERWISE. PROVIDE 3"x3" x1/4" HOT -DIPPED GALVANIZED PLATE WASHERS AT ALL ANCHOR BOLTS. INDIVIDUAL MEMBERS OF BUILT-UP POSTS SHALL BE NAILED TO EACH OTHER WITH 16d NAILS @ 12" O.C. STAGGERED. REFER TO THE PLANS AND SHEAR WALL SCHEDULE FOR REQUIRED SHEATHING AND NAILING. WHEN NOT OTHERWISE NOTED, PROVIDE GYPSUM WALLBOARD ON INTERIOR SURFACES NAILED TO ALL STUDS, TOP AND BOTTOM PLATES AND BLOCKING WITH NAILS AT 7" O.C. USE 5d COOLER NAILS FOR 1/2" GWB AND 6d COOLER NAILS FOR 5/8" GWB. PROVIDE 15/32" APA RATED SHEATHING (SPAN RATING 24/0) ON EXTERIOR SURFACES NAILED AT ALL PANEL EDGES (BLOCK UNSUPPORTED EDGES), TOP AND BOTTOM PLATES WITH 8d NAILS @ 6" O.C. AND TO ALL INTERMEDIATE STUDS AND BLOCKING WITH NAILS @ 12" O.C. ALLOW 1/8" SPACING AT ALL PANEL EDGES AND ENDS. C. FLOOR AND ROOF FRAMING: PROVIDE DOUBLE JOISTS UNDER ALL PARALLEL PARTITIONS THAT EXTEND OVER MORE THAN HALF THE JOIST LENGTH AND AROUND ALL OPENINGS IN FLOORS OR ROOFS UNLESS OTHERWISE NOTED. PROVIDE SOLID BLOCKING AT ALL BEARING POINTS. NOTCHES AT THE END OF JOISTS AND RAFTERS SHALL NOT EXCEED 1/4 THE DEPTH OF THE MEMBER. NOTCHES IN THE TOP OR BOTTOM SHALL NOT EXCEED 1/6 THE DEPTH OF THE MEMBER AND SHALL NOT BE LOCATED WITHIN THE MIDDLE 1/3 OF THE SPAN. THE DIAMETER OF ROUND HOLES BORED IN JOISTS AND RAFTERS SHALL NOT EXCEED 1/3 OF THE DEPTH OF THE MEMBER AND SHALL NOT BE LOCATED WITHIN 2" FROM THE TOP OR BOTTOM EDGE. TOENAIL JOISTS TO SUPPORTS WITH TWO 16d NAILS. ATTACH TIMBER JOISTS TO FLUSH HEADERS OR BEAMS WITH SIMPSON METAL JOIST HANGERS IN ACCORDANCE WITH THE NOTES ABOVE. NAIL ALL MULTI -JOIST BEAMS TOGETHER WITH TWO ROWS OF 16d @ 12" O.C. ATTACH RAFTERS AND ROOF TRUSSES AT BEARING LINES WITH H2.5A @ 24" O.C. UNLESS OTHER METAL CONNECTIONS ARE INDICATED. UNLESS OTHERWISE NOTED ON THE PLANS, APA RATED ROOF AND FLOOR SHEATHING SHALL BE LAID UP WITH STRENGTH AXIS PERPENDICULAR TO SUPPORTS AND ATTACHED WITH 10d NAILS @ 6" O.C. TO FRAMED PANEL EDGES AND OVER STUD WALLS AS SHOWN ON PLANS AND @ 12" O.C. TO INTERMEDIATE SUPPORTS. PROVIDE APPROVED PLYWOOD EDGE CLIPS CENTERED BETWEEN JOISTS/TRUSSES AT UNBLOCKED ROOF SHEATHING EDGES. ALL FLOOR SHEATHING EDGES SHALL HAVE APPROVED TONGUE -AND -GROOVE JOINTS OR SHALL BE SUPPORTED WITH SOLID BLOCKING. ALLOW 1/8" SPACING AT ALL PANEL EDGES AND ENDS OF ALL ROOF AND FLOOR SHEATHING. TOENAIL BLOCKING TO SUPPORTS WITH 16d NAILS @ 12" O.C. UNLESS OTHERWISE NOTED. AT BLOCKED FLOOR AND ROOF DIAPHRAGMS PROVIDE FLAT 2X BLOCKING AT ALL UNFRAMED PANEL EDGES AND FASTEN SHEATHING TO FRAMING/BLOCKING AS SPECIFIED. Lathrop Douglass Architects Established in 1993 3051 Paradise Bay Road Port Ludlow, WA 98365 Tel: 206.283.9730 C �� CRRTER QUINN NURLIN STRUCTURAL ENGINEERING 2033 Sixth Ave #995 Seattle, WA 98121 ► 206-264-7784 www.CON-SE.com REVIEWED BY CITY OF EDMONDS BUILDING DEPARTMENT BLD2024-0733 DAY -CROSS RESIDENCE NUMBER BY DATE REVISION RESUB J u 116 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SHEET TITLE GENERAL STRUCTURAL NOTES DATE 5.30.2024 DRAWN R.H. scA�E AS NOTED S1.0 LEGEND X INDICATES DETAIL X ON SHEET SX.X SX. .� INDICATES SIMPSON HOEDOWN. REFER TO .��J HOEDOWN SCHEDULE (81S3.0) FOR THREADED ROD CALLOUT &EMBEDMENT INTO CONCRETE FOUNDATION PLAN NOTES 1. SLABS -ON -GRADE SHALL BE 4-INCHES THICK AND REINFORCED WITH 6X6 W1.4xW1.4 WWM CENTERED, UNLESS NOTED OTHERWISE. PREPARE SOILS AND PROVIDE MINIMUM 10-MIL VISQUEEN VAPOR BARRIER UNDER ALL SLABS. 2. REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS AND ADDITIONAL TOP OF SLABICURB ELEVATIONS. Lathrop Douglass Architects Established in 1993 3051 Paradise Bay Road Port Ludlow, WA 98365 Tel: 206.283.9730 C �� CARTER QUINN NORLIN STRUCTURAL ENGINEERING 2033 Sixth Ave #995 Seattle, WA 98121 ► 206-264-7784 www.CON-SE.com A B C D E F I G �� H I I I I I I I ' I I I '�, '�, I I I I III I 1r=--i � i i I II � - - - - - - - - - - - - - - - � r � - - � - - - i - � - , I �� - - -- -- -- -- -- =---------------J �--------�--�------------ -- 11== J- - �--- 2----------- --- '-0" TO MATCH IZONTAL REINF. XY EMBED MIN. 4"INTO ONC. r�` � I I i J J �� � �i J i i __ ,a., � � 3 �J i i i �� _� DAY -CROSS RESIDENCE NUMBER BY DATE REVISION RESUB Jul 16 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT I I I I A E F G H SHEET TITLE FOUNDATION PLAN DATE 5.30.2024 FOUNDATION PLAN DRAWN R.H. SCALE AS NOTED S2.0 ��� A B C D E F I I I I I I � - - �� II I I - - - - - - ��_ �E)- I I--- �� �� � G ��� H I I I I I I I I I A E F G H --� --� TYP. ND OPENI - 3 --� C OVERFRAMIP C (E)RO TYP. C C LEGEND I� � � HANGER FB INDICATES FLUSH BEAM �� ❑ WALLI COLUMN BELOW UNO UNLESS NOTED OTHERWISE WALLI COLUMN ABOVE SWx INDICATES SHEAR WALL PER SCHEDULE 121S6.0 /, ABRUPT CHANGE IN SLABI FRAMING ELEVATION SX INDICATES DETAIL X ON SHEET SX.X SPAN AND EXTENTS �v� INDICATES SIMPSON STRAP �`G' HOEDOWN TYPICAL WOOD FRAMING PLAN NOTES 1. FLOOR SHEATHING SHALL BE 23132" APA RATED T&G STRUCTURAL SHEATHING WITH PANEL INDEX 48124. ATTACH TO FRAMING WITH 10d NAILS AT 6" oc AT FRAMED PANEL EDGES AND WALLS AND 12" oc AT INTERMEDIATE FRAMING. 2. ROOF SHEATHING SHALL BE 19132"APA RATED STRUCTURAL SHEATHING WITH PANEL INDEX 40120. ATTACH TO FRAMING WITH 8d NAILS AT 6" oc AT FRAMED PANEL EDGES AND WALLS AND 12" oc AT INTERMEDIATE FRAMING. 3. SWx INDICATES SHEAR WALL PER 121S6.0. 4. ALL HEADERS SHALL BE (2) 2x8 UNO. REFER TO NOTE 5 FOR TYPICAL SUPPORT REQUIREMENTS. 5. COLUMNS SHALL BE DOUBLE STUDS MINIMUM, U.N.O., WITH BEAM OR HEADER BEARING FULLY ON COLUMN Lathrop Douglass Architects Established in 1993 3051 Paradise Bay Road Port Ludlow, WA 98365 Tel: 206.283.9730 C �� CARTER QUINN NORLIN STRUCTURAL ENGINEERING 2033 Sixth Ave #995 Seattle, WA 98121 ► 206-264-7784 www.CQN-SE.com A B C D E F � G � H I I I I I I � 24"oc. - 2 �� JUFACTURED � @ 24"oc. --� --� DAY -CROSS RESIDENCE NUMBER BY DATE REVISION RESUB Jul 16 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT I I I I A E F G H SHEET TITLE ROO F FRAMING/SECOND FLOOR FRAMING PLAN DATE 5.30.2024 �COND FLOOR FRAMING PLAN ROOF FRAMING PLAN DRAWN R.H. S 2 SCALE AS NOTED SHEAR WALL PER PLAN CORNER BARS TO MATCH EXTERIOR HORIZ. REINF. MATCH CROSS WALL HORIZ. REINF. ADDITIONAL VERT. BARS CROSS ----- WALL TYP. C( BAR: DOUBLE CURTAIN PER ARCH 6 ANCHOR BOLTS PER � SHEAR WALL SCHED. - (E)SLAB ON GRADE PER PLAN - - - Q -, � oo�� o°Ooo -a �: a o a- ° eQ°� - (E)CONC. WALL & FTG. - - dP. � ,- - .d � � - Q , - o-. � % - I, I I I I I, I, I I II II I, I I II I, I I I I I I I, I I I I I I I, I I 6" I #4@10"oc EW BOT. CORNER BARS TO CORNER BARS TO /MATCH EXTERIOR �„ MATCH EXTERIOR HORIZ. REINF. � a PIPE SLEEVES HORIZ. REINF. (ALT. HOOKS) � ¢ AS REQUIRED z a � � � � � z� I U � _ I ►RNER ADDITIONAL o � 24 VERT. BARS `"' � �� CROSSI WALL -- - ----� I 2'-0" MIN. SINGLE CURTAIN LIFT &ATTACHMENT TO SLAB BY OTHERS SLAB ON GRADE PER PLAN SHEAR WALL n�o nl nnl (E)SLAB ON GRADE PER PLAN SW PER P c� z w J W 00 W Typical Corner Bars at Concrete Walls s3.o 2 314" HDU2 DETAIL ALLOWED BELOW THIS LINE Lathrop Douglass Architects Established in 1993 3051 Paradise Bay Road Port Ludlow, WA 98365 Tel: 206.283.9730 C �� CARTER QUINN NORLIN STRUCTURAL ENGINEERING 2033 Sixth Ave #995 Seattle, WA 98121 ► 206-264-7784 www.CON-SE.com Pipe and Trench Location Conditions Ss.o .�ur5iuu5 t SCHEDULE HOEDOWN SCHEDULE _DOWN PLAN ANCHOR EPDXY CAST- 2 MIN. N0.OF � t PLAN MARK BOLT EMBED IN -PLACE END STUDS HDU2 5/8'ID 10" 7" 2 i 1; MINIMUM N0.OF STUDS AT END OF WALL UNLESS OTHERWISE :M WALL & NOTED ON FRAMING PLANS. NFORCMENT t PLAN � 2 CAST IN PLACE ALL THREAD wl NUTIWASHERINUT EMBEDDED IN CONCRETE FOOTING & REINFORCEMENT PER PLAN S PER CHED. SLAB ON GRADE PER PLAN TG. I .V. 1L/IL VVAV U I 11.1. ANCHOR BOLTS PI SHEAR WALL SCHI (2)#4 CONT. TOP 8 S3.0 DAY -CROSS RESUB RESIDENCE Ju1162024 CITY OF EDMONDS DEVELOPMENT SERVICES 7 IORIZ. DEPARTMENT NUMBER BY DATE REVISION SLAB ON GRADE 'ER PLAN 1 RH 7.15.24 Building Dept. Comments VSULATION PER ARCH 'oc VERT. OK DIRECTION �► :�� SHEET TITLE CONCRETE DETAILS DATE 5.30.2024 DRAWN R.H. S3.0 10 S3.0 11 S3.0 0 12 S3.0 SCALE AS NOTED PRnvinF pn�iFi Fnr,F Nl PLYWOOD PANEL (MAYBE EITHER VERT. OR HORIZ. NAILING TO INTERMEDIATE FRAMING MEMBEf TOP OF FOUNDATION END OF SHEARWALL i ivLuvvviv i Liv I L/lIY BLOCKING AT ALL PANEL EDGES - REFER NOT�2� BLOCKING OR RIM JOIST DOUBLE TOPIC PANEL EDGE NAILING AT ALL JAMB, CORNER, &WALL END MEMBERS INTERMEDIATE FRAMING MEMBERS BOTTOM � ANCHOR BOLT PER SHEARWALL SCHEDULE Typical Shearwall Panel Elevation (2)10d TOENAILS EA. SIDE OF STUD (tYp�) FLOOR JOISTS PER PLAN (2)16d EA END OR (2)10d TOENAILS BLOCKING SEE NOTE 4 (4)16d MIN (typ.) (2) 8d TOENAILS(typ.) (1) 2x CRIPPLE TYP UNO-SEE NOTE 2 KING STUD WIDTH 1. PI�/���RS PER PLAN 2. PROVIDE (2) 2x CRIPPLE STUDS MINIMUM TYPICAL, U.O.N. 3. SEE ARCHITECTURAL DRAWINGS FOR OPENING SIZES AND LOCATIONS 4. 2x SOLID BLOCKING REQUIRED AT CEILING LINE, ALL PANEL EDGES, AND @ 8'-0" oc MAX. SHEARWALL SCHEDULE BOTTOM PLATE ATTACHMENT CAPACITY SW# SHEATHING PANEL EDGE BLOCKING � NAILING'�� ATTACHMENT -2) TO TOP PLATE � RIM BOARD FACENAILING TO ANCHOR BOLTING (plf) 15132" APA RATED SHEATHING YES 8d @ 6"oc CLIP @ 24"oc REQ'D WOOD BELOW C3 TO CONC. BELOW <� 2x NAILS @ 6"oc 5/8'� @ 48"oc SEISMIC 261 PLF SW1 0 NAILS SHALL BE 8d COMMON. NAILING APPLIES TO ALL PANEL EDGES (BLOCK ALL UNSUPPORTED PANEL EDGES), TOP &BOTTOM PLATES AND BLOCKING. NAIL TO INTERMEDIATE FRAMING MEMBERS wl8d @ 12"oc. 02 CLIP SHALL BE EITHER A35 OR LTP4 NAILS SHALL BE 12d COMMON (0.148� x 3.25") C' SCREWS SHALL BE SIMPSON SDS25300 ('/4"Q� x 5" MIN.) �'4 PROVIDE 3"x3"x0.229" PLATE WASHER AT ALL ANCHOR BOLTS. ANCHOR BOLTS SHALL BE POSITIONED SUCH THAT PLATE EDGE OF PALTE WASHER ISWITHIN'/2' OF THE EDGE OF THE BOTTOM PLATE (PLATE WASHERS MAYBE DIAGONALLY SLOTTED WITH A WIDTH OF UP T013116" AND A LENGTH NOT TO EXCEED 13/4") 0 .� Lathrop Douglass Architects Established in 1993 3051 Paradise Bay Road Port Ludlow, WA 98365 Tel: 206.283.9730 C �� CARTER QUINN NORLIN STRUCTURAL ENGINEERING 2033 Sixth Ave #995 Seattle, WA 98121 ► 206-264-7784 www.CON-SE.com DAY -CROSS RESUB RESIDENCE Ju1162024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT NUMBER BY DATE REVISION WOOD DETAILS DATE 5.30.2024 DRAWN R.H. SCALE 12 AS NOTED S6.0 S6.0 FULL DEPTH BLK'G @32 wl(2)A34 wIPH6121 SCRE (E)FRAMING PER PLAN CLIP PER SW SCHEDULE PER PLAN DEPTH BLK'G @32"oc. Od NAILS FRAMING PER PLAN =DGER wl �WS'/2'�x5" LAGS@32"oc. (E)FRAMING PER PLAN CLIP SCHEDULE PE FRAMING PER PLAN P. R wl z"�x5" LAGS@16"oc. SHEARWALL PER PLAN FRAMING PER PLAN K'G SCHEDULE PER PLAN INVERTED HU28 HANGER SHEARWALL PER PLAN BLK'G EPTH CONT. 2x8 RIM PER ARCH SHEARWALL CLIP PER SW PER PLAN SCHEDULE PER PLAN FRAMING PER PLAN 5 6 7 8 S6.1 S6.1 S6.1 S6.1 GABLE END TRUSS SHEA1 SHEAF OVERFRAM PER PLAN (E)ROOi FRAMIN PRE -MANUFACTURED TRUSS PER PLAN BOTTOM CHORD TRUSS BRACING @24"oc. ATTACH TO EA. TRUSS wl(2)16d NAILS SCHED. 10 S6.1 PRE -MANUFACTURED TRUSS PER PLAN HANGER PER TRUSS MANUFACTURER SHEARWALL PLAN ir�rULL DEPTH BLOCKING, ADD'L BLK'G AS :DED FOR 1SS HANGER E)PRE-MANUFACTURED �RUSS CLIP PER SHEARWALL SCHED. FULL DEPTH (MAY BE DRI NOTCHED F( 2xE 2x4@24"oc., TOENAIL TO FASCIA 2x LEDG (2)16d@ 'RE -MANUFACTURED �RUSS PER PLAN CLIP PER SHEARWALL SCHED. Lathrop Douglass Architects Established in 1993 3051 Paradise Bay Road Port Ludlow, WA 98365 Tel: 206.283.9730 C �� CARTER QUINN NORLIN STRUCTURAL ENGINEERING 2033 Sixth Ave #995 Seattle, WA 98121 ► 206-264-7784 www.CON-SE.com DAY -CROSS RESUB RESIDENCE Ju1162024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT NUMBER BY DATE REVISION WOOD DETAILS DATE 5.30.2024 DRAWN R.H. SCALE 12 AS NOTED S6.1 S6.1