Simple heating System Size: wasnington State
This heating system sizing calculator is based on the Prescriptive Requirements of the 2018 Washington State Energy Code (WSEC) and
ACCA Manuals J and S. This tool will calculate heating loads only. ACCA procedures for sizing cooling systems should be used to determine
cooling loads.
Please complete the green drop -downs and boxes that are applicable to your project. As you make selections in the drop -downs for each
section, some values will be calculated for you. If you do not see the selection you need in the drop -down options, please contact the WSU
Energy Program at energycode@energy.wsu.edu or (360) 956-2042 for assistance.
Prnipct
Kean Addition WalIsand Weeds, Inc.
10533 243rd PI SW 10016 Edmonds Way#C229
Edmonds WA98020 Edmonds WA98020
Heating System Type: O All other systems `Heat Pump
To see detailed instructions for each section, place your cursor on the word "Instructions"
Design Temperature
Instructions Design Temperature Difference (AT)
Ed m o n d s Ell OT = Indoor (70 degrees) - Outdoor Design Temp
Area of Building
Conditioned Floor Area
Instructions Conditioned Floor Area (sq ft)
695
Average Ceiling Height
Conditioned Volume
Instructions Average Ceiling Height (ft)
8.0
5,560
Glazing and Doors
U-Factor
X Area =
UA
Instructions
U-0.30
- J
0.300
216
64.80
Skylights
U-Factor
X Area =
UA
Instructions
0.50
12
6.00
Insulation
Attic
U-Factor
X Area =
UA
Instructions R-49
Ell
0.026
636
16.54
Single Rafter or Joist Vaulted Ceilings
U-Factor
X Area
UA
Instructions OR-49 Advanced
0.020
59
1.18
Above Grade Walls (see Figure1)
U-Factor
X Area
UA
Instructions `
a R-21 Intermediate
- J
0.056
1,048
58.69
Floors
U-Factor
X Area
UA
Instructions R-30
F1
0.029
695
20.16
Below Grade Walls (see Figurel)
U-Factor
X Area
UA
Instructioi No Below Grade Walls in t - j
0.028
0
Slab Below Grade (see Figure 1)
F-Factor
X Length
UA
Instructions
Select conditioning
�
No selection
---
Slab on Grade (see Figure1)
F-Factor
X Length
UA
Instructions R-10 Fully Insulated
0.360
F 44
15.84
Location of Ducts
Instructions
Duct
Leakage Coefficient
Conditioned S ace
R
1.00
Sum of UA
183.20
Figure 1.
Above Grade
46
Envelope Heat Load 8,427 Btu / Hour
Sum ofUAxAT
Air Leakage Heat Load 2,762 Btu / Hour
Volume x 0.6 x AT x 0.018
Building Design Heat Load 11,189 Btu / Hour
Air leakage + envelope heat loss
Building and Duct Heat Load 11,189 Btu/Hour
Ducts in unconditioned space: sum of building heat loss x 1.10
Ducts in conditioned space: sum of buildinq heat loss x 1
Maximum Heat Equipment Output 13,987 Btu / Hour
Buildina and duct heat loss x 1.40 for forced air furnace
Buildina and duct heat loss x 1.25 for heat oumo