REV1 REVIEWED BLD BLD2024-0321+Structural_Calculations+7.5.2024_10.54.42_AM+43597161J
D
LD)
BALANCED STRUCTURAL ENGINEERING, LLB:
P.O. Box 3806
Lacey, WA 98509
info@BalancedSE.com
(253) 341-7139
Pardi Garage Conversion
8918 218TH ST SW
EDMONDS, WA 98026
STRUCTURAL CALCULATIONS
PREPARED FOR:
Taylee & James Pardi
Prepared By: Joshua T Mergens, PE,SE
Balanced Structural Engineering, LLC
Project No: 24012
Date: July 04, 2024 REVISED 7/03/2024
Joshua T Mergens sw 1r ne_ ,L202321131o1<,
Version: 3.3.11
Project Name
Project #
BS
O-E_
Pardi Garage Conversion
24012
Subject
Version:
SALA'- =TURALEFG_V�l
Design Criteria
3.3.11
Project Scope:
Lateral and Vertical Design of Existing Residence
GOVERNING DESIGN CODE: INTERNATIONAL BUILDING CODE 2018 EDITION
GRAVITY LOADS:
Roof Dead Load:
15 PSF Floor Live Load: 40 PSF
Ground Snow:
15 PSF Exterior Wall Dead Load: 10 PSF
Unheated Roof Snow:
25 PSF Interior Wall Dead Load: 8 PSF
Vented Roof (Heated) Snow Load:
25 PSF Deck Dead Load: 10 PSF
Floor Dead Load:
15 PSF Deck Live Load: 60 PSF
LATERAL LOADS:
WIND:
Basic Wind Speed (Ultimate):
100 mph Exposure: B
Basic Wind Speed (Service):
77 mph Kzt: 1.00
SEISMIC:
Site Class: D
Seismic Design Category: D
Ss: 1.280
S1: 0.450
Fa: 1.200
Fv: 1.850
SDS: 1.024
SD1: 0.555
R:
Cs = SDS/(R/I) =
V = CsW = 0.158 W
Cs = 0.7 SDS/(R/I) =
V = 0.7 CsW = 0.113 W
le = 1.00
Level p (Plan N/S) p (Plan E/W)
1 1.00 1.00
2 1.30 1.30
ALLOWABLE SOIL VALUES:
Geo-Technical Engineer:
N/A
Report No. & Date:
N/A
Allowable Soil Bearing Pressure: (Assumed)
Project Name Project #
TDPardi Garage Conversion 24012
DSubject Version:
SE
- ` ���• LLC Gravity Design 3.3.11
GRAVITY DESIGN
I.LEE
Project Name Project #
Pardi Garage Conversion 24012
Subject Version:
BALANCED STRUC7URAL ENGMEERIING,LLC Gravity Legend 3.3.11
ATE PER
RH 1
RH 1
I I FRH4
I II 7j"ll
II II IL------
I I
II
I I
I SISTER 2x RAFTER (E) 2x4 I I
TOP CHORD TRU5 24"O.C.
PER STRUCTURAL
a3:12
I II I
�'J I
I I
II I
I�--J
I
I
730x22C ACCESS, 5EE 5 UCTHEADER OVER NG7
I I
I I
1
RH4
3:12D
SISTER 2x RAFTER ( 2x4
TOP CHORD TRUS 2x
CEILING JOISTS@ 2 "O.C.
PER STRUCTURAL
CEILING TO HAVE
5/8" PE-X GW5
I
II IJ
- JJ
II I
I �
I r-�
II I
II I
FIRE -TAPED MIN I I L -
I I �
I I II
-RH5 -1/2" IL 5H BEAM I
rER 5TR CTURAL I
I I II II
- - - _ - - _ - - J
(E) GAbQE EAVE YFAT5. VERI
OR PROVI DITIONAL
VENTING AS REQUIRED
Project Name Project #
33-E Pardi Garage Conversion 24012
Subject Version:
BALANCED STRUCTURAL ENGINEERING, LLC Roof Snow Load and Drift 3.3.11
Pg =
Risk Category =
Is =
Surface Roughness Category
Exposure of Roof
Ce =
Thermal Condition
Ct =
Pf = 0.7*Ce*Ct*Is*Pg =
Roof Pitch =
Roof Surface Type
Cs =
Ps = CsPf =
15 PSF
11
1.0
B
Sheltered
Cold Roofs &
Structures Kept Just
Above Freezing
1.10
11.6 PSF
3:12
All Other Surfaces
1.0
11.6 PSF
Minimum Uniform Snow Load for Low Slope Roofs**:
Ground Snow Load
7.3.3
7.3.1
7.3.2
Flat Roof Snow, 7.3-1
Sloped Roof Snow, 7.4-1
Pm = IsPg1 15 PSF Minimum Roof Snow Load, 7.3.4
Source: Building Department
Vented Roof (Heated) Snow Load = I 15 PSF
For Unheated and Open Air
15 PSF (Use at roofs such as porch covers and garages)
Structures =
For Roofs of Buildings Kept
Intentionally Below Freezing Roof 15 PSF
Snow Load =
For Decks and Balconies, Snow Load
15 PSF 7.2
= IsPg =
Minimum Roof Snow Load = 25 PSF WA State Minimum Per SEAW White Paper #8
For Roofs less than 1:50 slope, add 5 PSF Rain on Snow Surcharge per 7.10
*Unobstructed slippery surfaces designation shall only apply for roofs with R>= 30 for unventalated
roofs and R>=20 for ventalated roofs where Ct = 1.0
P
Project Name: Project #:
SEPardi Garage Conversion 24012
Subject: Version:
Continuous Foundation Design 3.3.11
Uniform Loads
Roof
Floor
Wall
DL = 15 PSF
DL = 15 PSF
DL = 10 PSF
SL = 25 PSF
ILL = 40 PSF
Allowable Bearing Pressure = 1 1500 PSF
Applied Bearing Pressure = P/(Ftg Width)
Abrg = 2*D*Ftg Width
Pallow = Abrg*Allow Brg Press.-2*D*W
@ Openings:
Pallow = Abrg*Allow Brg Press.-D*W
(Allowable incresed at openings because w is only on one side)
Continuous Foundation Design
Tag Description
D
J D
2*D
(E)Perimeter Existing Typical perimeter foundation with a stemwall and footing
(E)Gable Existing Typical perimeter foundation with a stemwall and footing Maximum uniform loads are shown below
(E)Interior
Existing Typical perimeter foundation with a stemwall and footing
New Strip Footing in Garage Slab
Isolated footings, see end of the gravity design for calcs
Footings with multiple loads or special conditions, see end of gravity design for calcs
(N) Strip
Isolated
Other
Tag
Roof Trib
Floor Trib
Wall Trib
DL
SL
ILL
Factored W
Load Case
Ftg
Width
Brg
Pressure
(E)Perimeter
28.5/2+1.5
= 15.75 ft
0
= 0.00 ft
8
= 8.u0 ft
316 pif
394 plf
0 pif
711,
S
12 in
710 PSF
OK
(E)Gable
3
= 3.00 ft
0
= 0.00 ft
8
= 8.00 ft
125 plf
75 plf
0 plf
2001—
+S
12 in
200 PSF
OK
(E)Interior
14.08/2+13.83/2+1.33
=15.29 ft
0
= 0.00 ft
8
= 8.00 ft
309 pif
382 plf
0 plf
691 pif
D+S
12 in
691 PSF
OK
(N) Strip
1 14.08/2+13.83/2
= 13.96 ft
0
= 0.00 ft
8
= 8.00 ft
1 289 plf
1 349 plf
1 0 plf
1 638 plf
D+S
I 12 in
638 PSF
OK
Isolated
I See Isolated Footing Design
OK
Allowable Point Loads on Continuous Foundations
Tag
Fdn Height
Brg Length
Brg Area
P Allow
P Allow W/
Uniform Load
@ One Side
(E)Perimeter
18 in
3.00 ft
3.00 sgft
2370 #
3435 #
(E)Gable
18 in
3.00 ft
3.00 sgft
3900 #
4200 #
(E)Interior
12 in
2.00 ft
2.00 sgft
1617 #
2309 #
(N) Strip
10 in
1.67 ft
1 1.67 sgft
1436 #
1968 #
Isolated
See Isolated
Footing Design
7
Project Name Project #
Pardi Garage Conversion 24012
BS
Subject Version:
gAu��E®v Components and Cladding Wind Pressure 3.3.11
30.4 Components and Cladding Wind Pressure
Code: ASCE 7-16
Wind Speed = 100 mph Exposure Cat. = M.R.H. 12.75 ft
Least Horiz. Dim. = 59.50 ft Elev. = 428 ft
ASCE Reference
qh = 0.00256KZKZtKdKeV2 =
12.51
Table 26.10.1
Kz =
0.57
26.10.1
Kzt =
1.00
26.8
Kd =
0.85
26.6-1
Ke =
Table 26.9.1
Exposure
Wall
B
PRESSURE COEFFICIENTS
ASD Pressures
area ft2
GCpi (+)
GCpi (-)
zone
GCp (+)
GCp (-)
(+)
(-)
0
0.18
-0.1z
8.8::
-9.60
10
0.18
-0.1E
4
1.0
-1.1
8.85
-9.60
20
0.18
-0.1E
4
0.94
-1.04
8.40
-9.15
50
0.18
-0.1E
4
0.88
-0.98
7.95
-8.70
100
0.18
-0.1E
4
0.82
-0.92
7.50
-8.25
200
0.18
-0.18
4
0.76
-0.86
7.05
-7.80
500
0.18
-0.18
4
0.70
-0.80
6.60
-7.35
0
0.18
-0.1E
8.85
-11.86
10
0.18
-0.1P
5
1.00
-1.40
8.85
-11.86
20
0.18
-0.1E
5
0.94
-1.28
8.40
-10.96
50
0.18
-0.1k
5
0.88
-1.16
7.95
-10.05
100
0.18
5
0.82
-1.04
7.50
-9.15
200
0.18
-0.1P
5
0.76
-0.92
7.05
-8.25
500
0.18
-0.1E
5
0.70
-0.80
6.60
-7.35
Zone 4 = Middle Zone
Zone 5 - Corner Zone
Corner Zone Dimension:
a = 5.10 ft
ELEVATION
ProName:
Pardi Garage Conversion
Garage
Project
24012
012
111�11.111)</1)
Subject:
Horizontal Member Summary
Version:
3.3.11
Horizontal Member Summary
All
Passing?
Label
Span
Size
Species
Bending
Check
Total
Deflection
I.I. Deflection
Shear Check
Left
Trimmer
Right
Trimmer
Number
Kings
Check
Left Footing Sqr
Dim
Check
Right Footing Sqr
Dim
Check
OK
RHl
4.08 ft
4x6
DF p2
OK
OK
OK
OK
(1)
(1)
(1)
OK
Oin
OK
Oin
OK
OK
RH2
3.00 ft
4x6
DF p2
OK
OK
OK
OK
(1)
(1)
NO Kings
OK
Oin
OK
Oin
OK
OK
RH3
10.38k
4x8
DF p2
OK
OK
OK
OK
(1)
(1)
(2)
OK
Oin
OK
Oin
OK
OK
RB3
S.00ft
4x8
DF p2
OK
OK
OK
OK
(1)
(1)
NO Kings
OK
Oin
OK
Oin
OK
OK
RH4
3.25 ft
4x6
DF p2
OK
OK
OK
OK
(1)
(1)
(1)
OK
Oin
OK
Oin
OK
OK
RHS
6.00 ft
4x8
DF M2
OK
OR
OK
OK
(1)
(1)
(1)
OK
n
OK
Oin
OK
OK
RRl
13.83 k
2x10
DF M2
OK
OK
OK
OK
(1)
(1)
No Kings
OK
ated Ftg
tD.Os"
inOK
Oin
OK
RR2
14.08 ft
2x10
DF tt2
OK
OK
OK
OK
(1)(1)
No Kings
OK
n
OK
See Isolated Ftg
Design
r BPardi
��
�-
Project Name
Garage Conversion
Project #
24012
Subject
Headers, Beams, and Joists
Version:
3.3.11
Assume trimmer studs resist 100% of header reaction and king studs resist 100% of wind and load from above. Trimmer studs are braced in x-
x direction. With an applied accidental eccentricty of 1.2", 2x6 studs are controled by compression perpendicular to grain for heights up to
10' for DF#2.
Beam (B)/Header (H)/Joist (J):
RH1
Clear Span =
Trib:
PLF Load:
4.08 ft Design Span =
4.12 ft
Roof
Floor
Wall
Comment
DL =
SL =
15 PSF
DL = 15 PSF
LL = 40 PSF
0 = 0.00 ft
LL = 0 plf
DL = 10 PSF
0 = 0.00 ft
SL = 209 plf
25 PSF
14.08/2+1.33 = 8.37 ft
DL = 126 plf
Factored Load =
335 plf
LC:
D+S
Size:
4x6
Moment of Inertia =
49 in^4
Sx =
18 in^3
Area =
19 in^2
Cd =
1.:
Cm =
No
Cr =
No
Incising?
No
Species:
DF #2
CL =
1.00
Cf/Cv =
1.30
Braced?
No
Moment =
7091
fb =
482 psi
F'b =
1340 psi
Ratio:
Ratio:
0.360
OK
Shear =
6894,
fv =
F'v =
0.259
OK
Transient Deflection =
0.017 in
L/d =
?83'
L/d Limit =
360
OK
Total Load Deflection =
0.'
L/d =
L/d Limit =
240
OK
Reactions and Support Member
Reations
D
L
S
Factored
Support Type
# of
Trimmers
allowable
Ratio
Left
258 #
0 #
431 #
689
Trimmer
(1)
2395 #
Right
258 #
0 #
431 #
689 #
Trimmer
2395 #
King Studs
Stud Ht =
8.00 ft
Stud O.C. =
1.33 ft
Wall Loc.:
End Zone
Plys:
1
OK
L/d Allow. =
180
Vert Trib =
2.00 ft
Trib Width =
4.12
Trib Area =
Load from Above
Source
C&C Uniform Pressure:
Total Axial Loads
C&C UDL:
DL=
251#
LL=
0#
SL=
419#
w=
-25
Stud Size:
#2 D.F. King Studs
F'b/Cd =
F'c*/Cd =
2x4 Area = 5.25 in^2 I =
Fb Cf Cr
(900 psi) =
Fc r'
(1350 psi)
5.36 in^4
S = 3.06 in^3
E' =
E'Min =
2025 psi
1600000 psi
1553 ps
580000 psi
Cd
Moment*
Axial
fb
fc
F'b
FbE
Fc*
DL+LL
1.0
2025 psi
466
DL+SL
1.15
2329 psi
4661 p_
DL+3/4(LL+SL)
1.15
2329 psi
4661 p,
DL+3/4(LL+SL+W)
1.6
3240 psi
466
DL+W
1.6
ilb4.y .
LSl #
lUii ,
46 psi
3240 psi
4661 ps-
*Use accidental eccentrictiy of 1.2" in strong axis
Cp
F'c
FcE
Interaction
Deflection Check:
DL+LL
568 p!
63-
3.15
Deflection =
u.3L
DL+SL
578 p�
634 r�
3.19
I/d =
99
OK
DL+3/4(LL+SL)
n '
17Q r
',IA^<`
1 15
Compression Perpendicular to Grain
DL+3/4(LL+SL+W)
F'c-perp =
405 psi
Capacity =
DL+W
V.L4
S7b psi
bi4 p51
j.45
Stress Ratio =
r
OK
Interaction Less Than 1.0 Therefore OK
Spot Footing Check
UDL only on
one side?
Foundation
Area
Required
Ftg Square Dim
(in)
Area
Provided
Left Reaction:
Yes
(E)Perimeter
1.17 sgft
0 in
3.00 sgft
OK
Right Reaction:
689 #
Yes
(E)Perimeter
1.17 sgft
0 in
3.00 sgft
OK
D7,E
"LANCED STRUCTUR
Project Name
Pardi Garage Conversion
Project #
24012
Subject
Headers, Beams, and Joists
Version:
3.3.11
Beam (B)/Header (H)/Joist (J):
i
Assume trimmer studs resist 100% of header reaction and king studs resist 100% of wind and load from above. Trimmer studs are braced in x-
x direction. With an applied accidental eccentricty of 1.2", 2x6 studs are controled by compression perpendicular to grain for heights up to 10'
for DF#2.
H2
Clear Span =
Trib:
PLF Load:
3.00 ft Design Span = �.uj rr
Roof
Floor
Wall
Comment
DL =
SL =
15 PSF
DL =
ILL=
15 PSF
DL = 10 PSF
25 PSF
40 PSF
19.5/2+2/2 = 10.75 ft
0 = 0.00 ft
0 = 0.00 ft
DL = 161 plf
LL = 0 plf
SL = 269 plf
Factored Load =
430 plf
LC:
D+S
Size:
4x6
Moment of Inertia =
49 in^4
Sx =
18 in^3
Area =
19 in^2
Cd =
1.15
Cm =
No
Cr =
No
Incising?
No
Species:
DF #2
CL =
1.00
Cf/Cv =
1.30
Braced?
No
Moment =
495 fi
fb =
336 psi
F'b =
1341 psi
Ratio:
Ratio:
,,.4
^w
Shear =
652
fv =
51 psi
F'v =
207 psi
0.24
Transient Deflection =
L/d =
5519
L/d Limit =
360
OK
Total Load Deflection =
L/d =
3449
L/d Limit =
240
Reactions and Support Member
Reations
D
L
5
Factored
Support Type
# of
Trimmers
Allowable
Ratio
Left
Trimmer
2395 #
27%
Right
Trimmer
27%
Spot Footing Check
UDL only on
one side?
Foundation
Area
Required
Ftg Square Dim
(in)
Area
Provided
Left Reaction:
.,d ,
Yes
(E)Interior
., .M.,
0 in
OK
Right Reaction:
652 #
Yes
(E)Interior
0.90 sgft
0 in
OK
r BPardi
��
�-
Project Name
Garage Conversion
Project #
24012
Subject
Headers, Beams, and Joists
Version:
3.3.11
Assume trimmer studs resist 100% of header reaction and king studs resist 100% of wind and load from above. Trimmer studs are braced in x-
x direction. With an applied accidental eccentricty of 1.2", 2x6 studs are controled by compression perpendicular to grain for heights up to
10' for DF#2.
Beam (B)/Header (H)/Joist (J):
RH3
Clear Span = 10.38 ft Design Span = 10.41 ft
Roof Floor Wall Comment
DL = 15 PSF DL = 15 PSF DL = 10 PSF
SL = 25 PSF LL = 40 PSF
Trib: 3 = 3.00 ft 0 = 0.00 ft 0 = 0.00 ft
PLF Load: DL = 45 plf LL = 0 plf SL = 75 plf
Factored Load =
120 plf
LC:
D+S
Size:
4x8
Moment of Inertia =
111 in^4
Sx =
31 in^3
Area =
25 in^2
Cd =
1.:
Cm =
No
Cr =
No
Incising?
No
Species:
DF #2
CL =
0.99
Cf/Cv =
1.30
Braced?
No
Moment =
16251
fb =
636 psi
F'b =
1326 psi
Ratio:
Ratio:
0.480
OK
Shear =
624 a,
fv =
F'v =
0.178
OK
Transient Deflection =
0.111 in
L/d =
L/d Limit =
360
OK
Total Load Deflection =
0."
L/d =
L/d Limit =
240
OK
Reactions and Support Member
Reations
D
L
S
Factored
Support Type
# of
Trimmers
allowable
Ratio
Left
234 #
0 #
. #
624
Trimmer
(1)
2395 #
Right
234 #
0 #
J #
624 #
Trimmer
2395 #
King Studs
Stud Ht =
8.00 ft
Stud O.C. =
1.33 ft
Wall Loc.:
End Zone
Plys:
2
OK
L/d Allow. =
180
Vert Trib =
2.00 ft
Trib Width =
1(
Trib Area =
Load from Above
Source
C&C Uniform Pressure:
Total Axial Loads
C&C UDL:
DL=
90#
LL=
0#
SL=
1!
w=
Stud Size:
#2 D.F. King Studs
F'b/Cd =
F'c*/Cd =
2x4 Area = 10.50 in^2 I =
Fb Cf Cr
(900 psi) =
Fc r'
(1350 psi)
10.72 ��� 4 S = 6.13 in^3
2025 psi E' =
1553 ps E'Min =
1600000 psi
580000 psi
Cd
Moment*
Axial
fb
fc
F'b
FbE
Fc*
DL+LL
1.0
2025 psi
18643 psi
DL+SL
1.15
2329 psi
18643 psi
1-N�.
DL+3/4(LL+SL)
1.15
2329 psi
18643 psi
1�Qr ^<'
DL+3/4(LL+SL+W)
1.6
3240 psi
18643 psi
DL+W
1.6
bL25U.1 .
yu ftwLs
psi
y psi
3240 psi
18643 psi
24254 psi
*Use accidental eccentrictiy of 1.2" in strong axis
Cp
F'c
FcE
Interaction
Deflection Check:
DL+LL
568 p!
63-
3.02
Deflection =
1/1
1
DL+SL
578 p�
634 r�
3.02
I/d =
36
OK
DL+3/4(LL+SL)
n '
17Q r
',IA^<`
1 02
Compression Perpendicular to Grain
DL+3/4(LL+SL+W)
F'c-perp =
405 psi
Capacity = 85
DL+W
V.L4
S7b psi
bi4 p51
j.42
Stress Ratio =
r
OK
Interaction Less Than 1.0 Therefore OK
Spot Footing Check
UDL only on
one side?
Foundation
Area
Required
Ftg Square Dim
(in)
Area
Provided
Left Reaction:
Yes
(E)Gable
0.62 sgft
0 in
3.00 sgft
OK
Right Reaction:
624 #
Yes
(E)Gable
0.62 sgft
0 in
3.00 sgft
OK
D7,E
"LANCED STRUCTUR
Project Name
Pardi Garage Conversion
Project #
24012
Subject
Headers, Beams, and Joists
Version:
3.3.11
Assume trimmer studs resist 100% of header reaction and king studs resist 100% of wind and load from above. Trimmer studs are braced in x-
x direction. With an applied accidental eccentricty of 1.2", 2x6 studs are controled by compression perpendicular to grain for heights up to 10'
for DF#2.
Beam (B)/Header (H)/Joist (J):
�z61
Clear Span =
Trib:
PLF Load:
5.00 ft Design Span = �.uy rr
Roof
Floor
Wall
Comment
DL =
SL =
15 PSF
DL =
ILL=
15 PSF
DL = 10 PSF
25 PSF
40 PSF
28/2+1.5 = 15.50 ft
0 = 0.00 ft
8 = 8.00 ft
DL = 313 plf
LL = 0 plf
SL = 388 plf
Factored Load =
700 plf
LC:
D+S
Size:
4x8
Moment of Inertia =
111 in^4
Sx =
31 in^3
Area =
25 in^2
Cd =
1.15
Cm =
No
Cr =
No
Incising?
No
Species:
DF #2
CL =
1.00
Cf/Cv =
1.30
Braced?
Yes
Moment =
2268 f
fb =
888 psi
F'b =
1346 psi
Ratio:
Ratio:
.a
^w
Shear =
1782
fv =
105 psi
F'v =
207 psi
0.56
Transient Deflection =
L/d =
1855
L/d Limit =
360
OK
Total Load Deflection =
L/d =
1027
L/d Limit =
240
Reactions and Support Member
Reations
D
L
5
Factored
Support Type
# of
Trimmers
Allowable
Ratio
Left
796 #
Trimmer
2395 #
74%
Right
Trimmer
74%
Spot Footing Check
UDL only on
one side?
Foundation
Area
Required
Ftg Square Dim
(in)
Area
Provided
Left Reaction:
1782 #
Yes
(E)Perimeter
0 in
OK
Right Reaction:
1782 #
Yes
(E)Perimeter
0 in
OK
r
D
Project Name
Pardi Garage Conversion
Project #
24012
Subject
Headers, Beams, and Joists
Version:
3.3.11
Beam (B)/Header (H)/101St (1)
Assume trimmer studs resist 100% of header reaction and king studs resist 100% of wind and load from above. Trimmer studs are braced in x-x
direction. With an applied accidental eccentricty of 1.2", 2x6 studs are controled by compression perpendicular to grain for heights up to 10' for
DF#2.
:
RH4
Clear Span = 3.25 ft Design Span = 3.30 ft
Trib:
PLF Load:
Roof
Floor
Wall
Comment
DL =
SL =
15 PSF
DL =
ILL=
15 PSF
DL = 10 PSF
Max Span
25 PSF
40 PSF
13.42/2+14.08/2 = 13.75 ft
0 = 0.00 ft
0 = 0.00 ft
DL = 206 plf
LL = 0 plf
SL = 344 plf
Factored Load =
550 plf
LC:
D+S
Size:
4x6
Moment of Inertia =
49 in^4
Sx =
18 in^3
Area =
19 in^2
Cd =
1.:
Cm =
No
Cr =
No
Incising?
No
Species:
DF #2
CL =
1.00
Cf/Cv =
1.30
Braced?
No
Moment =
747 ft-#
fb =
508 psi
F'b =
1342 psi
Ratio:
Ratio:
0.379
OK
Shear =
907 #
fv =
71 psi
F'v =
207 psi
0.341
OI
Transient Deflection =
0.012 in
L/d =
3362
L/d Limit =
360
OK
Total Load Deflection =
0.019 in
L/d =
2101
L/d Limit =
240
OK
Reactions and Support Member
Reations
D
L
S
Factored
Support Type
#of
Trimmers
Allowable
Ratio
Left
340 #
0 #
567 #
907 #
Trimmer
(1)
2395 #
Right
340 #
0 #
567 #
907 #
Trimmer
(1)
2395 #
King Studs
Stud Ht =
11.00 ft
Stud O.C. =
1.33 ft
Wall Loc.:
End Zone
Plys:
1
OK
L/d Allow. =
180
Vert Trib =
2.00 ft
Trib Width =
3.30/2+1.33/2
= 2.31 ft
Trib Area =
25.45
Load from Above
Source
C&C Uniform Pressure:
Total Axial Loads
C&C UDL:
DL=
+13#
LL=
0#
SL=
688#
w=
-25..
Stud Size:
#2 D.F. King Studs
F'b/Cd =
F'c*/Cd =
2x6 Area = I =
Fb Cf Cr
(900 psi) (1.30) =
Fc Cf
(1350 psi) (1.15) =
20.80 in^4
S = 7.56 in^3
E' =
E'Min =
58f
1600000 psi
580000 psi
Cd
Moment*
Axial
fb
fc
F'b
FbE
Fc*
DL+LL
1.0
1320.0 k-ft
z157 psi
1553
DL+SL
1.16
1320.0 k-ft
ice.
L157 psi
1785 psi
DL+3/4(LL+SL)
1.16
1113.8 k-ft
Q"
L157 psi
1785 psi
DL+3/4(LL+SL+W)
1.6
4563.5 k-ft
?157 psi
DL+W
1.6
5094.7 k-ft
4�_
su psi
tsu psi
'157 psi
2484
*Use accidental eccentrictiy of 1.2" in strong axis
Cp
F'c
FcE
Interaction
Deflection Check:
DL+LL
0.4
701
�18
Deflection =
0.25 in
DL+SL
0.4
728 r=
128 p��
I/d =
526
OK
DL+3/4(LL+SL)
n
»u ^<
'Q ^<�
Compression Perpendicular to Grain
DL+3/4(LL+SL+W)
F'c-perp =
405 psi
Capacity =
DL+W
U.si
iui psi
,tu psi
�y
Stress Ratio =
0
OK
Interaction Less Than 1.0 Therefore OK
Spot Footing Check
UDL only on
one side?
Foundation
Area
Required
Ftg Square Dim
(in)
Area
Provided
Left Reaction:
Yes
(N) Strip
0.96 sgft
0 in
1.67 sgft
OK
Right Reaction:
907 #
Yes
(N) Strip
0.96 sgft
0 in
1.67 sgft
OK
7ff,S,E
B
Project Name TProject
Pardi Garage Conversion
#
24012
Subject
Headers, Beams, and Joists
Version:
3.3.11
Assume trimmer studs resist 100% of header reaction and king studs resist 100% of wind and load from above. Trimmer studs are braced in x-x
direction. With an applied accidental eccentricty of 1.2", 2x6 studs are controled by compression perpendicular to grain for heights up to 10' for
DF#2.
Beam (B)/Header (H)/Joist (J):
RHs
Clear Span = 6.00 ft Design Span = 6.09 ft
Trib:
PLF Load:
Roof
Floor
Wall
Comment
DL =
SL =
15 PSF
DL =
LL =
15 PSF
DL = 10 PSF
25 PSF
40 PSF
13.83/2+14.08/2 =13.96 ft
0 = 0.00 ft
0 = 0.00 ft
DL = 209 plf
LL = 0 plf
SL = 349 plf
Factored Load =
558 plf
LC:
D+S
Size:
4x8
Moment of Inertia =
111 in^4
Sx =
31 in^3
Area =
25 in^2
Cd =
1.15
Cm =
No
Cr =
No
Incising?
No
Species:
DF #2
CL =
0.99
Cf/CV =
1.30
Braced?
No
Moment =
2586 ft-#
fb =
1012 psi
F'b =
1335 psi
Ratio:
Ratio:
0.758
OK
Shear =
1699 #
fv =
100 psi
F'v =
207 psi
0.485
OK
Transient Deflection =
0.061 in
L/d =
1205
L/d Limit =
360
OK
Total Load Deflection =
0.097 in
L/d =
753
L/d Limit =
240
OK
Reactions and Support Member
Reations
D
L
S
Factored
Support Type
# of
Trimmers
Allowable
Ratio
Left
637 #
0 #
1062 #
1699 #
Trimmer
(
2395 #
71%
Right
637 #
0 #
1062 #
1699 #
Trimmer
(
2395 #
71%
King Studs
Stud Ht =
8.00 ft
Stud O.C. =
1.33 ft
Wall Loc.:
End Zone
Plys:
1
OK
L/d Allow. =
180
Vert Trib =
2.00 ft
Trib Width =
6.09/2+1.33/2
= 3.71 ft
Trib Area =
29.67 sgft
Load from Above
Source
C&C Uniform Pressure:
Pp= 0# P,= 0# Ps= 0#
w=
-11.0PSF
Total Axial Loads
C&C UDL:
DL=
LL=
0#
SL=
698#
w=
-40.6p1f
Stud Size:
#2 D.F. King Studs
F'b/Cd =
F'c*/Cd =
2x4 Area = 5.25 in^2 I =
Fb Cf Cr
(900 psi) (1.5 (1.50) =
Fc Cf
(1360 psi) (1.15)
5.36 in^4
S = 3.06 in^3
E' =
E'Min =
2025 psi
1600000 psi
680000 psi
Cd
Moment*
Axial
fb
fc
F'b
FbE
Fc*
DL+LL
1.0
]
:025 psi
4661 psi
1553 psi
DL+SL
1.16
13��., -
:329 psi
4661 psi
1785 psi
DL+3/4(LL+SL)
1.16
11z^ ^ 6-
:329 psi
4661 psi
1785 psi
DL+3/4(LL+SL+W)
1.6
4
1240 psi
4661 psi
2484 psi
DL+W
1.6
440L.ts K-1
�4itS p;
2SU f
1240 psi
4661 psi
2484 psi
*Use accidental eccentrictiy of 1.2" in strong axis
Cp
F'c
FcE
Interaction
Deflection Check:
DL+LL
0.37
568
0.27
Deflection =
0.4ti
DL+SL
0.3?
578 p��
0.42
I/d =
220 1OK
DL+3/4(LL+SL)
n '
"79 ^<�
0.32
Compression Perpendicular to Grain
DL+3/4(LL+SL+W)
0.66
F'c-perp =
406 psi
Capacity = 2126 #
DL+W
Cf.L4
syu psi
53
Stress Ratio =
0.53
OK
Interaction Less Than 1.0 Therefore OK
Spot Footing Check
UDL only on
one side?
Foundation
Area
Required
Ftg Square Dim
(in)
Area
Provided
Left Reaction:
1.
Yes
(E)Perimeter
1.84 sgft
0 in
.00 sgft
OK
Right Reaction:
1699 #
Yes
(N) Strip
1.49 sgft
0 in
�.67 sgft
OK
D7,E
"LANCED STRUCTUR
Project Name
Pardi Garage Conversion
Project #
24012
Subject
Headers, Beams, and Joists
Version:
3.3.11
Assume trimmer studs resist 100% of header reaction and king studs resist 100% of wind and load from above. Trimmer studs are braced in x-
x direction. With an applied accidental eccentricty of 1.2", 2x6 studs are controled by compression perpendicular to grain for heights up to 10'
for DF#2.
Beam (B)/Header (H)/Joist (J):
�zR1
Clear Span =
Trib:
PLF Load:
13.83 ft Design Span = _.,.yu rr
Roof
Floor
Wall
Comment
DL =
SL =
15 PSF
DL =
ILL=
15 PSF
DL = 10 PSF
Max Span
25 PSF
40 PSF
2/2+2/2 = 2.00 ft
0 = 0.00 ft
0 = 0.00 ft
DL = 30 plf
LL = 0 plf
SL = 50 plf
Factored Load =
D plf
LC:
D+S
Size:
2x10
Moment of Inertia =
99 in^4
Sx =
21 in^3
Area =
14 in^2
Cd =
1.15
Cm =
No
Cr =
Yes
Incising?
No
Species:
DF #2
CL =
1.00
Cf/Cv =
1.10
Braced?
Yes
Moment =
1931 f
fb =
1083 psi
F'b =
1309 psi
Ratio:
Ratio:
^w
Shear =
556
fv =
60 psi
F'v =
207 psi
0.25
Transient Deflection =
L/d =
L/d Limit =
360
OK
Total Load Deflection =
L/d =
L/d Limit =
240
Reactions and Support Member
Reations
D
L
5
Factored
Support Type
# of
Trimmers
Allowable
Ratio
Left
208 #
Trimmer
1027 #
54%
Right
Trimmer
1027 #
54%
Spot Footing Check
UDL only on
one side?
Foundation
Area
Required
Ftg Square Dim
(in)
Area
Provided
Left Reaction:
Yes
Isolated
0 in
See Isolated Ftg Design
Right Reaction:
556 #
Yes
(E)Perimeter
0 in
OK
D7,E
"LANCED STRUCTUR
Project Name
Pardi Garage Conversion
Project #
24012
Subject
Headers, Beams, and Joists
Version:
3.3.11
Assume trimmer studs resist 100% of header reaction and king studs resist 100% of wind and load from above. Trimmer studs are braced in x-
x direction. With an applied accidental eccentricty of 1.2", 2x6 studs are controled by compression perpendicular to grain for heights up to 10'
for DF#2.
Beam (B)/Header (H)/Joist (J):
�zR2
Clear Span =
Trib:
PLF Load:
14.08 ft Design Span = _Y.15 rr
Roof
Floor
Wall
Comment
DL =
SL =
15 PSF
DL =
ILL=
15 PSF
DL = 10 PSF
25 PSF
40 PSF
2/2+2/2 = 2.00 ft
0 = 0.00 ft
0 = 0.00 ft
DL = 30 plf
LL = 0 plf
SL = 50 plf
Factored Load =
D plf
LC:
D+S
Size:
2x10
Moment of Inertia =
99 in^4
Sx =
21 in^3
Area =
14 in^2
Cd =
1.15
Cm =
No
Cr =
Yes
Incising?
No
Species:
DF #2
CL =
1.00
Cf/Cv =
1.10
Braced?
Yes
Moment =
2002 f
fb =
1123 psi
F'b =
1309 psi
Ratio:
Ratio:
^w
Shear =
566
fv =
61 psi
F'v =
207 psi
0.25
Transient Deflection =
L/d =
L/d Limit =
360
OK
Total Load Deflection =
L/d =
L/d Limit =
240
Reactions and Support Member
Reations
D
L
5
Factored
Support Type
# of
Trimmers
Allowable
Ratio
Left
354 #
Trimmer
1027 #
55%
Right
3
Trimmer
1027 #
55%
Spot Footing Check
UDL only on
one side?
Foundation
Area
Required
Ftg Square Dim
(in)
Area
Provided
Left Reaction:
oG,
Yes
(E)Perimeter
0 in
OK
Right Reaction:
566 #
Yes
Isolated
0 in
See Isolated Ftg Design
�-( ��1�
F-' / LJ1
Project Name:
Pardi Garage Conversion
Project
24012
Subject:
Vertical Member Summary
Version:
3.3.11
Vertical Member Summary
Columns and Studs
Columns Only
Studs Only
All
Passing?
Label
Size
Species
Combined
Stress
Ratio
Perp. To
Grain
Footing
Footing
Check
Delfection
Plys
OK
SDI
2x6
DF it2
0.16
0.03
OK
1
Project Name: Project #:
93 SE Pardi Garage Conversion 24012
Subject: Version:
MWCEUG UC UMLENG[NEERNG,LLC Stud Check 3.3.11
SD1
Ht =
1 11.00 ft
K =
1.0
x-x Braced
Wall Location:
End Zone
Stud Size:
2x6
Plys:O Area
Fb
Cf
Cr
F'b/Cd =
(900 psi)
(1.30)
Fc
Cf
F'c*/Cd =
(1350 psi)
_ E' _
Axial Loads:
Loads based on:
DL =
Trib =
DL =
RF2
LL = 0 plf SL = 50 plf
LL = SL = 100 #
30 plf
2.00 ft
Load from Above:
Pp
PL
PS
I = 20.80 in^4
1600000 psi
S=J 7.56 in-3
E'Min = I 580000 psi (DF #2)
Lateral Loads
Trib Width = 1.33
Trib Area =
w =
w =
= 1.33 ft
14.63 sqi_
-11.9 PSF
-15.8 pif
Cd
Moment*
Axial
fb
fc
F'b
FbE
Fc*
Cp
F'c
FcE
Interaction
DL+LL
1.0
79 in-#
60 #
10 psi
7 psi
1580 psi
2157 psi
155s psi
0.46
709 ps'
828 psi
0.01
DL+SL
1.15
211 in-#
160 #
28 psi
.9 psi
1816 psi
2157 psi
1785 psi
0.41
728 psi
828 psi
0.02
DL+3/4(LL+SL)
1.15
178 in-#
135 #
24 psi
5 psi
1816 psi
2157 psi
1785 P�'
0.41
728 psi
828 psi
0.01
DL+3/4(LL+SL+W)
1.6
2325 in-#
:i
2527 psi
2157 psi
248 .
0.31
761 psi
828 psi
0.12
DL+W
1.6
2941 in-#
6,
389 psi
1 7 psi
1 2527 psi
1 -157 psi
2484 psi
- "
761 psi
828 psi
0.16
*Use accidental eccentrictiy of 1% Ht in strong axis
Deflection = 0.16 in
Compression perpendicular to grain:
I/d =
Fc-perp =
846
F625 psi
Capacity =
Interaction Less Than 1.0 Therefore OK
Allowable L/d = 180
5156 # Stress Ratio = 0.03
OK
OK
Max Interaction:
0.16
n�I TM SE
Project Name:
Pardi Garage Conversion
Project #:
24012
\'I v�
Subject:
Version:
-�- �-----
Isolated and Other Foundation
Design
3.3.11
Other Footings
Source
DL
ILL
SL
0.6W or
.07E
Load
UDL Only One
Side?
Foundation
Area Required
(sgft)
Ftg Square Dim (in)
Area Provided
RH3 (Left)+RHS (Left)
871 #
0 #
1452 #
0 #
Yes
(E)Perimeter
2.26 sgft
0 in
3.00 sgft
Design of Isolated Footing
Req'd Bearing
Square Dimensions
Circular Ftg
0.6W or
Area
(in)
Diameter (in)
Source
DL
ILL
SL
.07E
Load
3E Project Name Project #
D Pardi Garage Conversion 24012
Subject: Version:
srrtucruRAL E"C : Floor Joist Tables 3.3.11
DL = IS PSF Cr = 1.15 Floor Chace Rating = 39 Min.
LL 1.0
Fully Braced
L/d Total Limit = 360
40 PSF Cd = =
L/d Transient Limt = 360
=
LL=40PSF
Fully Braced
L/d Total Limit = 240
L/d Transient Limit = 360
Floor Choice Rating = 30 Min.
Solid Sawn floor Joist Span Table
Max Allowable Span
bust
8'-"
9
bah D_f. >s2 � 16' O.C_
11'-6'
2x8 D.F. >s2 � 16" O.C_
14'-6'
17'-3'
2x10 D.F. it2 @ 16" O.C.
� 2x12 D.F. it2 @ 16" O.C.
TJI Floor Joist Span Table
Max Allowable Span
Till Joist
14'-0'
9-1/2' TA 110's � 16" O_C
17'-0'
11-7 8" Tll 110's � 16' O.C.
18'-0'
11-7/8" Tll 110's @ 16" O.C. W/
GYP- CEILING BELOW
TJI Floor Joist Span Table
Max Allowable Span
Till Joist
14'-3
9-1/2' TA110's @ 19.2" O_C_
16'-9'
11-7/8" TJI 110's @ 19.2' O.C.
- �
— — T SE Project Name Project #
r Pardi Garage Conversion 24012
\� D Subject Version:
"TURAL Eh- Lateral Design 3.3.11
LATERAL DESIGN
� S_g Project Name Project #
rj� Pardi Garage Conversion 24012
DSubject Version:
ATC Hazards Information 3.3.11
ASCE
Address:
8918 218th St SW
Edmonds, Washington
98026
i�
Seismic
Site Soil Class:
Results:
ASCE Hazards Report
Standard: ASCE?SE17-16 Latitude: 47.801171
Risk Category: 11 Longitude: -122-353584
Soil Class: D - Default (see Elevation: 427.7591892263514 ft
Section 11.4.3) i.NAVD 88)
D - Default (see Section 11.4.3)
S.-
1.28
S,,,
N: A
S,
0.45
TL :
6
F 1,
1.2
PGA :
0.544
F,
N,,A
PGA
0.653
Sres
1.536
F PrA
1.2
SW
N,,A
I..
1
Sr;s
1.024
C,,
1.356
Ground motion hazard analysis may be required. See ASCE,'SEI 7-16 Section 11.4.8.
Data Accessed:
Wed Feb 28 2024
Date Source:
USGS Seismic Design
Maps
Project Name: Project #:
Pardi Garage Conversion 24012
133ESubject: Version:
anuXCED SPAURURAL EXGINEERING. LLC Seismic Analysis 3.3.11
Seismic Analysis: IBC 2018 / ASCE 7-16
Site Class: D (Default) (IBC 1613.3.2, ASCE Table 20.3-1)
Site Coefficients: (From https:Hhazards.atcouncil.org/)
Ss= 1.280 Fa= 1.zUU
SI = 0.450 Fv = 1.850
SMs= Fa * SS = 1.536 (IBC Eq.16-37)
SMI= Fv * SI = 0.833 (IBC Eq.16-38)
Spectral Response Parameters:
SDs= 2/3 * SMs = 1.024 (IBC Eq.16-39)
SDI= 2/3 * SMI = 10.555 (IBC Eq.16-40)
Structure Period:
Ta= Ct * (hn)x=
0.1349
(ASCE Eq. 12.8-7)
hn =
12.75 ft
Structural Height
Ct =
0.02
(ASCE Table 12.8-2)
x =
0.75
(ASCE Table 12.8-2)
Cu =
(ASCE Table 12.8-1)
T(MAX) = Cu * Ta =
(ASCE 12.8.2)
Risk Category: i or i1 w
I or 11, III, IV (ASCE Table 1.5-1) IE = (ASCE Table 1.5-2)
Seismic Design Category:
(IBC 1613.3.5, ASCE 11.6)
Seismic Design Category(SDs):
IBC Table 1613.3.5(1), ASCE Table 11.6-1 Short Period (SDs)
Seismic Design Category(SD1):
IBC Table 1613.3.5(2), ASCE Table 11.6-2 1 Second Period (SDI)
Seismic Response Coefficients:
Cs =SDs/(R/IE) = 0.1575 (ASCE Eq 12.8 2)
R =
Oo =
Cd =
IE =
CS(Max) =
SDI / ((R / IE) * Ta) =
SD1*TL / ((R / IE) * TaA2)=
CS(Min) =
0.044 SDs 1 >=.01 =
Not Required S1<=0.6g
6.50
(ASCE 7 Table 12.2-1)
(ASCE Table 1.5-2)
(ASCE Eq 12.8-3)
(ASCE Eq 12.8-4)
(ASCE Eq 12.8-5)
(ASCE Eq 12.8-6)
3.00
4.00
1.00
0.63
0.63
75.02
0.05
1 0.05
V = Cs * W =
Va = 0.7*Cs * W =
W (Ultimate, LRFD)
W (Service, ASD)
(Wood Sheathed Shearwalls)
for T <= TL OK TL= 16
for T <= TL OK ASCE Section 12.8 & 11.4.5
(ASCE fig. 22-12 thru 22-16)
Project Name: Project #:
OB SE
Pardi Garage Conversion 24012
Subject: Version:
s MCED9MUCMU LENGINEENING,LLC Seismic Forces 3.3.11
Building Weight:
Weight Tributary to Level 1:
Floor Area = ±
Roof Area = ±
(0)(15)+(3148)(15+0) _
Linear ft of Ext Walls Below = ±
Ht of Walls Below =
Wall Weight = (919)(10)(8/2) _
Linear ft of Int Wall Below = ±
(208)(8)(8/2) =
Pf =
25 PSF
0 sgft
Wt Floor =
15 PSF
3148 sqft
Wt Roof =
15 PSF
17220 #
Pf<30, No SL
0 PSF
919.00 ft
Wt Wall =
10 PSF
8.00 ft
208.00 ft Wt Wall = 8 PSF
6656 #
Total Weight Tributary to Level 1 = 90636 #
Project Name: Project #:
SE Pardi Garage Conversion 24012
11-B Subject: Version:
uuNCED srNUcruanL ENGINEENINGLLL Seismic Forces 3.3.11
Total Building Weight I Wbib ;;
Base Shears:
V=
V=
(0.158 )(90636 #) = 14279 # (Ultimate, LRFD)
(0.113 )(90636 #) = 10199 # I (Service, ASD)
Project Name: Project #:
OB SE
Pardi Garage Conversion 24012
Subject: Version:
9ALANCED STNUCTUMLENGINEENINGLLL Seismic Forces 3.3.11
Vertical Distribution of Seismic Forces Per ASCE 12.8.3:
Total Seismic Load = 10199 # (Service) k =
Diaphragm Weight Height Weight*Ht^k Cvx (%) Fx
Level 1 8.00 ft
F 90636 #
Level 1
F
Numbered Shear Lines
Lettered Shear Lines
p
pQE
Cumulative
p
pQE
Cumulative
1
10199 #
1
10199 #
Project Name:
Project #:
O
9LSERoof
Pardi Garage Conversion
24012
Subject:
Version:
BALANCED STRUCTURAL EXGINEERING.LL�
Wind Pressures
3.3.11
Type Pitched
Exp =
V=
Kzt =
Enclosure: Enclosed
z = 10.00 ft (Highest Z)
h = 12.75 ft
Pitch 5:12
Kd = 0.85
Ke =
qz= 0.00256KzKztKdKeVA2
Kz =
qz =
qh = 0.00256KhKztKdVA2
Kh = 0._
qh = 12.51 PSF
P = gGCp-gi(GCpi)
G = 0.85
Gcpi =
L = 57.75 ft (Note a smaller L/B is conservative, use smaller L/B
B = 59.50 ft from each orthoganal direction to be conservative )
Roof Area = 0 sqft (Per Side of Ridge for pitched, 0 is conservative)
Walls
Location
Cp
P @Wall
P Net
P Wall (+Gcpi)
P Wall (- Gcpi)
Windward Wall
10.76 PSF
13.82 PSF
Leeward Wall
-3.06 PSF
Side Wall
-7.44 PSF
9.00 PSF
Normal to Ridge
Windward P @Roof
Leeward P @Roof
P-Net Lateral
Cp A
CP B
P-Up
P-Down
P-Up
Normal to Ridge
Theta<10 and Parallel to Ridge
Horz. Distance From End
LC A
LC B
P-UP
P-Down
P-Net Lat
0 to h/2
-1
-,5F
h/2 to h
-0.
27 PSF
h to 2h
-0.18
-6.47 PSF
0.00 PSF
>2h
-0,"
' 56 PSF
0.00 P'
Parpets, Pp = gp(GCpn)
GCpn
Pp
z @Top of Parapet =
0.00 ft
Windard
1.5
qp = qz @Top of Parapet =
Leeward
1.0
-aTQ-)Pardi
IDSubject:
Project Name:
Garage Conversion
Project #:
24012
Wind Loading
Version:
3.3.11
Wind From 1-3
Diaphragm
Total
Horz. Dist.
Z **
Location
Area
Pressure ***
Load
Min
Pressure
Min Load
Story Shear
(Ultimate)
Story Shear
(Service)
W
(Service)
Base
Shear
(Service)
Level 1
38.00 ft
10.00 ft
Roof Normal to Ridge =
120 sgft
3.36
8 PSF
960 #
6272 #
3763 #
99 PLF
3763 #
Roof Paralell to Ridge =
0 sgft
5.79 PSF*
0 k
8 PSF
0 #
Windward Parapets =
0 sgft
18.76 PSF
^ '
3 PSF
0 #
Leeward Parpets =
0 sgft
12.51 PSF
B PSF
0 #
Walls Trib. to Diaphragm =
332 sgft
13.82 PSF
4588
6 PSF
5312 #
Wind From 3-4
Diaphragm
Total
Horz. Dist.
Z**
Location
Area
Pressure***
Load
Min
Pressure
Min Load
Story Shear
(Ultimate)
Story Shear
(Service)
W
(Service)
Base
Shear
(Service)
Level 1
20.00 ft
10.00 ft
Roof Normal to Ridge =
127 sgft
3.38 PSF
430 #
8 PSF
1016 #
2296 #
1378 #
69 PLF
1378 #
Roof Paralell to Ridge =
0 sgft
5.29 PSF*
0 #
8 PSF
0 #
Windward Parapets =
0 sgft
18.76 PSF
0 #
8 PSF
0 #
Leeward Parpets =
0 sgft
12.51 PSF
0 #
8 PSF
0 #
Walls Trib. to Diaphragm =
80 sgft
13.82 PSF
1106 #
16 PSF
1280 #
-aTQ-)Pardi
IDSubject:
Project Name:
Garage Conversion
Project #:
24012
Wind Loading
Version:
3.3.11
Wind from A-B
Diaphragm
Total
Horz. Dist.
Z **
Location
Area
Pressure ***
Load
Min
Pressure
Min Load
Story Shear
(Ultimate)
Story Shear
(Service)
W
(Service)
Base
Shear
(Service)
Level 1
10.00 ft
10.00 ft
Roof Normal to Ridge =
0 sgft
3.3F,
8 PSF
0 #
804 #
482 #
48 PLF
482 #
Roof Paralell to Ridge =
0 sgft
5.29 PSP
8 PSF
0 #
Windward Parapets =
0 sgft
18.76 PSF
8 PSF
0 #
Leeward Parpets =
0 sgft
12.51 PSF
8 PSF
0 #
Walls Trib. to Diaphragm =
50 sgft
13.82 PSF
694,
16 PSF
804 #:]
Wind from B-C
Diaphragm
Total
Horz. Dist.
Z**
Location
Area
Pressure***
Load
Min
pressure
Min Load
Story Shear
(Ultimate)
Story Shear
(Service)
W
(Service)
Base
Shear
(Service)
Level 1
23.50 ft
10.00 ft
Roof Normal to Ridge =
28 sgft
3.38 PSF
F
224 #
3296 #
1978 #
84 PLF
1978 #
Roof Paralell to Ridge =
0 sgft
5.29 PSF*
J A
8 PSF
0 #
Windward Parapets =
0 sgft
is "
8 PSF
0 #
Leeward Parpets =
0 sgft
8 PSF
0 #
Walls Trib. to Diaphragm =
192 sgft
1;.�
16 PSF
3072 #
-aTQ-)Pardi
IDSubject:
Project Name:
Garage Conversion
Project #:
24012
Wind Loading
Version:
3.3.11
Wind from C-D
Diaphragm
Total
Horz. Dist.
Z **
Location
Area
Pressure ***
Load
Min
Pressure
Min Load
Story Shear
(Ultimate)
Story Shear
(Service)
W
(Service)
Base
Shear
(Service)
Level 1
26.00 ft
10.00 ft
Roof Normal to Ridge =
105 sgft
3.38 PSF
8 PSF
840 #
2568 #
1541 #
59 PLF
1541 #
Roof Paralell to Ridge =
0 sgft
6.91 PSF*
0 k
8 PSF
0 #
Windward Parapets =
0 sgft
18.76 PSF
8 PSF
0 #
Leeward Parpets =
0 sgft
12.51 PSF
8 PSF
0 #
Walls Trib. to Diaphragm =
108 sgft
13.82 PSF
1492
16 PSF
1728 #
Wind from E-F
Diaphragm
Total
Horz. Dist.
Z**
Location
Area
Pressure***
Load
Min
pressure
Min Load
Story Shear
(Ultimate)
Story Shear
(Service)
W
(Service)
Base
Shear
(Service)
Level 1
46.00 ft
10.00 ft
Roof Normal to Ridge =
37 sgft
3.38 PSF
F
296 #
6008 #
3605 #
78 PLF
3605 #
Roof Paralell to Ridge =
0 sgft
5.38 PSF*
J A
8 PSF
0 #
Windward Parapets =
0 sgft
is "
8 PSF
0 #
Leeward Parpets =
0 sgft
8 PSF
0 #
Walls Trib. to Diaphragm =
357 sgft
1;.�
16 PSF
5712 #
Project Name: Project #:
-aTQ-)Pardi Garage Conversion 24012
IDSubject: Version:
Wind Loading 3.3.11
*Avg Pressure Based on Horiz Distance
**Z @ Top of Tributary Height of Walls at Each Diaphragm
***Wall Pressures are Adjusted Based on Z
-gTQ-)Pardi
IDSubject:
Project Name:
Garage Conversion
Project #:
24012
Wind Loading
Version:
3.3.11
DIAPHRAGM
Level 1
TOTAL WIND NUMBERED LINES WIND NUMBERED CUM.
6766 # 6766 #
TOTAL WIND LETTERED LINES
7606 #
WIND LETTERED CUM.
7606 #
.91
IS.L
E�IANCEDa UC UR
Project Name:
Pardi Garage Conversion
Project #:
24012
Subject:
Diaphgram Distribution
Version:
3.3.11
Diaphragms
Level 1
Wind:
86.58 ft
Diaphram
W
L
B
Aspect
Ratio
Open
Front?
V
v
Diaphragm Type
Floor or
Roof?
Capacity
D/C Ratio
M
T=C
1 to 3
99 PLF
38.00 ft
23.50 ft
No
iooc #
80 PLF
Unblocked Case 3
Roof
17875 ft-#
761 #
3 to 4
20.00 ft
45.75 ft
No
689 #
15 PLF
Unblocked Case 3
Roof
170 PLF
1 3
3444 ft-#
75 #
3 to 5
57 PLF
28.58 ft
26.00 ft
No
813 #
31 PLF
Unblocked Case 3
Roof
170 PLF
0.18
5807 ft-#
223 #
Diaphram
W
L
B
Aspect
Ratio
Open
Front?
V
v
Diaphragm Type
Floor or
Roof?
Capacity
D/C Ratio
M
T=C
A to B
10.00 ft
29.75 ft
Yes
482 #
16 PLF
Unblocked Case 3
Roof
.j
B to C
23.50 ft
38.50 ft
No
989 #
26 PL.
Unblocked Case 3
Roof
3.1:
5809 ft-
C to D
59 PLC
26.00 ft
28.58 ft
No
770 #
27 PLF
Unblocked Case 3
Roof
L70 PLF
3.11
5008 ft-#
175 #
E to F
78 PLI
45.75 ft
19.58 ft
No
1793 #
92 PLF
Unblocked Case 3
Roof
L70 PLF
J.S�
20503 ft-#
1047 #
.91
SETO)
Project Name:
Pardi Garage Conversion
Project #:
24012
Subject:
Version:
awxcEDS UL UEAL ENG]NEEREUG LLC
Diaphgram Distribution
3.3.11
Level 1
Seismic:
Total Seismic Force =
10199 #
(From previous
sheet)
F 86.58 ft
F 2801 sgft
100.0
10199 #
Total Seismic Force =
10199 #
(From previous
sheet)
105.25 ft
2798 sgft
100.0
10199 #
See following sheets for seismic diaphragm design
Diaphram
L
B
Diaphrgm
Area
Aspect
Ratio
Open
Front?
%
Force
W
V
1 to 3
38.00 ft
23.50 ft
1205 sgft
No
43.0
4388 #
115 PLF
2194 #
3 to 4
20.00 ft
45.75 ft
853 sgft
No
30.5
3106 #
155 PLF
1553 #
3 to 5
28.58 ft
26.00 f`
No
26.5
2706 #
95 PLF
1353 #
Diaphram
L
B
Diaphrgm
Area
Aspect
Ratio
Open
Front?
%
Force
W
V
A to B
10.00 ft
29.75 ft
298 sgft
Yes
10.6
1084 #
108 PLF
1084 #
B to C
23.50 ft
38.50 ft
9p5 cnft
No
32.3
3298 #
140 PLF
1649 #
C to D
26.00 ft
28.58 ft
No
26.6
2708 #
104 PLF
1354 #
•-- F
45.75 ft
19.58 ft
853 sgft
No
30.5
3109 #
68 PLF
1554 #
j LJ1 � f
Project Name:
Pardi Garage Conversion
Project #:
24012
l�/J]
Subject:
Version:
�o���..m■�-u=
Seismic Diaphragm Forces
3.3.11
Diaphragm Forces, ASCE 7-16, 12.10
n
"
Design
Level
Fx
Fi
Wx
I Wi
Fpx
Fmin
Finax
Base
Project Name:
Pardi Garage Conversion
1
Project #:
24012
l/J]
Subject:
Seismic Diaphragm Forces
Version:
3.3.11
Level 1
Seismic:
Total Seismic Force =
13259 #
(From previous sheet)
Diaphrgm
Aspect
86.58 ft
Total Seismic Force =
13259 #
2801 sgft
(From previous sheet)
100.0
13259 #
Diaphragm
L
B
Area
Ratio
Open
Front?
%
Force
W
V
v
Diaphragm Type
Floor or
Roof?
Capacity
D/C
Ratio
M
T=C
38.00 ft
23.50 ft
1205 sgft
1.62
N
)4 #
150 PLF
2852 #
121 PLF
Unblocked Case 3
Roof
70 PLF
0.71
27093 ft-#
1153 #
20.00 ft
45.75 ft
853 sgft
0.44
No
,j38 #
202 PLF
2019 #
44 PLF
Unblocked Case 3
Roof
70 PLF
0.26
30094 ft-#
221 #
28.58 ft
26.00 ft
743 sgft
1.10
No
26.5283
3517 #
123 PLF
1759 #
68 PLF
Unblocked Case 3
Roof
70 PLF
0.40
12566 ft-#
483 #
Diaphragm
L
B
Diaphrgm
Area
Aspect
Ratio
Open
Front?
%
Force
W
V
v
Diaphragm Type
Floor or
Roof?
Capacity
D/C
Ratio
M
T=C
A to B
10.00 ft
29.75 ft
298 sgft
0.34
Yes
11
1410 #
141 PLF
1410 #
47 PLF
Unblocked Case 3
Roof
170 PLF
0.28
7048 ft-#
237 #
B to C
23.50 ft
38.50 ft
905 sgft
0.61
No
32
4287 #
182 PLF
2143 #
56 PLF
Unblocked Case 3
Roof
170 PLF
0.33
12592 ft-#
327 #
C to D
26.00 ft
28.58 ft
743 sgft
0.91
No
27
3521 #
135 PLF
1760 #
62 PLF
Unblocked Case 3
Roof
170 PLF
0.36
11443 ft-#
400 #
E to F
45.75 ft
19.58 ft
853 sgft
2.34
No
30
4042 #
88 PLF
2021 #
103 PLF
Unblocked Case 3
Roof
170 PLF
0.61
23113 ft-#
1180 #
Project Name: Project #:
In3 S-Z Pardi Garage Conversion 24012
Subject: Version:
Too Plate (Chord) 3.3.11
Top Plate (Chord) Check:
Tension cap of single #2 DF 2x6:
Pt = (575)
(1.3) (1.6) = 1196 PSI
Ft
Cf Cd
Area
Tension Cap =
9867 #
Max Chord Force =
1180 # OK
Capacity of 10d Nail =
(118) (1.6) = 189 #
Splice Length =
4.00 ft
# of Rows =
0
Row Spacing
Splice Capacity =
OK
^�
IL u`(\(.\111v
Project Name:
Pardi Garage Conversion
Project #:
24012
Subject:
Loads to Lines
Version:
3.3.11
WIND LOADS FROM LEVEL 1
Line
Drag Load
Load Transfer
Dia. 1
V
Dia. 2
V
Dia. 3
V
Dia. 4
V
Sum
Total
1
0 #
0 #
1 to 3
1882 #
Not Used
0 #
Not Used
0 #
Not Used
0 #
1882 #
3
0 #
0 #
1 to 3
1882 #
3 to 4
689 #
3 to 5
813 #
Not Used
0 #
3383 #
6766 #
4
0 #
0 #
3 to 4
689 #
Not Used
0 #
Not Used
0 #
Not Used
0 #
689 #
5
0 #
0 #
3 to 5
813 #
Not Used
0 #
Not Used
0 #
Not Used
0 #
813 #
Line
Drag Load
Load Transfer
Dia. 1
V
Dia. 2
V
Dia. 3
V
Dia. 4
V
Sum
Total
B
u
0 #
A to B
482 #
B to C
989 #
Not Used
0 #
Not Used
0 #
1471 #
C
0 #
0 #
B to C
989 #
C to D
770 #
Not Used
0 #
Not Used
0 #
1759 #
D
0 #
0 #
C to D
770 #
Not Used
0 #
Not Used
0 #
Not Used
0 #
770 #
7586 #
E
0 #
0 #
E to F
1793 #
Not Used
0 #
Not Used
0 #
Not Used
0 #
1793 #
F
0 #
0 #
E to F
1793 #
Not Used
0 #
Not Used
0 #
Not Used
0 #
1793 #
SEISMIC LOADS FROM LEVEL 1
Line
Drag Load
Load Transfer
Dia. 1
V
Dia. 2
V
Dia. 3
V
Dia. 4
V
Sum
Total
0 #
0 #
1 to 3
2194 #
Not Used
0 #
Not Used
0 #
Not Used
2194 #
s
0#
0#
1to3
2194#
3to4
1553#
3to5
1353#
Not Used
5100#
10199#
4
0 #
0 #
3 to 4
1553 #
Not Used
0 #
Not Used
0 #
Not Used
1553 #
S
0 #
0 #
3 to 5
1353 #
Not Used
0 #
Not Used
0 #
Not Used
1353 #
Line
Drag Load
Load Transfer
Dia. 1
V
Dia. 2
V
Dia. 3
V
Dia. 4
V
Sum
Total
0 #
A to B
1084 #
I B to C
1649 #
Not Used
0 #
I Not Used
2733 #
0 #
B to C
1649 #
C to D
1354 #
Not Used
0 #
Not Used
3003 #
0 #
C to D
1354 #
Not Used
0 #
Not Used
0 #
Not Used
1354 #
10199 #
0 #
E to F
1554 #
Not Used
0 #
Not Used
0 #
Not Used
1554 #
0 #
E to F
1554 #
Not Used
0 #
Not Used
0 #
Not Used
1554 #
Project Name: Project #:
aL Pardi Garage Conversion 24012
I&ESubject: Version:
BALANCED SMMML ENGINEERM,LLC Shear Wall Desien 3.3.11
Wood Shearwalls
Line
Level
V
Wall Available
Total Wall
v
A.B.
Spacing
Min H/B
v ad'
1
Wall T
Type
Wall Ht
Uplift/
Comp.
Trib. For
Wt. Down
Weight
Down
Wall (ft)
Net Uplift
Holdown/S
trap
5
1
1353 #
9.92
9.92 ft
136 P
AZ
0.81
N/
Wl
8.00 ft
0 #
15.75
190 PLF
9.92
941 #
vone
C
1
1 3003 #
11+13.42
24.42 ft
123 PLi
Al
0.82
N/F
Wl
9.00 ft
1107 #
20/2+2/2
153 PLF
11
265 #
Ignore
1
1 1354 #
11
11.00 ft
123 PLF
Al
0.82
N/z
Wl
9.00 ft
1108 #
3
81 PLF
11
662 #
LTTP
* Designed per FTAO, v shown is for holdown sizing only, see FTAO calculations for nailing
Where h/bs >2.0, V adj = v/(1.25-.125*h/bs) for wall segments
approximately the same length and v adj = v/(2bs/h) elsehwere.