REV1 REVIEWED BLD2024-0321+Energy_Calculations+7.5.2024_10.59.24_AM+4359735REVISION
Jul 05 2024
CITY OF EDMONDS
WSU Code Compliance Calculator, WSEC 2018
BLD2024-0321
Project Information DEPARTMENT
Taylee Pardi
Garage Conversion to Livable Space
1.5 Total Credits with Option 1.3
Contact Information
Nathan Bonck
Olympic Hills Drafting & Design, LLC
307-258-1841
nbonck of m ichillsdraftin desi n.com
ANALYSIS SET UP
UA Reduction = 0.55, Proposed UA is better than baseline by 1
Whole House Mechanical Ventilation Airflow Rate: 90 CFM with Run Time Percent of 50%, Unbalanced, Not Distributed
Results assume your inputs are complete and correct. Results do not constitute an approval. Analysis should be reviewed by your AHJ.
What code compliance pathway are you using?
Prescriptive Path Compliance with Option 1 referred
Project Building Type?
Addition
Occupancy Type?
R3 Single family homes and duplexes
Code Version?
WSEC 2018
Classification:
Addition of 500 sf or less -- 420 sq. ft.
Baseline Description:
Code Baseline - Baseline and proposed window areas are equal.
About Your Selection:
Up to 15 sf exempt window and 24 sf exempt door allowable
RESULTS - Comparison of Baseline and Proposed Design
Component Performance. R occupancies
Doors U =
Overhead Glazing U =
Vertical Glazing U =
Flat/Vaulted Ceilings U =
Wall (above grade) U =
Floors over Crawlspace U =
Slab on Grade F =
Below Grade Wall U =
Below Grade Slab F =
Baseline
U Area UA
0.300
0
0.0
0.500
32
16.0
0.300
23
7.0
0.027
412
11.1
0.056
605
33.9
0.029
0
0.0
0.540
75
40.5
0.042
01
0.0
0.570
0
0.0
.................................................
REVIEWED
BY
CITY OF EDMONDS
e BUILDING DEPARTMENT
Proposed Design
U Area UA
0
0.0
0.500
32
16.0
0.300
23
7.0
0.029
412
11.8
0.054
605
32.7
0
0.0
0.540
751
40.5
01
0.0
01
0.0
Baseline UA Total 108.5 Proposed UA Total 107.9
Required Credits 1.5 Proposed Credits 2.0 from Tables 406.2 and 406.3
UA Percent Reduction 0.5%
UA Reduction 0.5
If the Proposed UA <_ the Target UA, and the Proposed Credits from Table 406 are >_ those required in Section R406, then the home meets the WSEC.
Table R406.2 Fuel Normalization Credits
Fuel Normalization
Total Credits
System No.
Full Description
Select System Type
Credits 406.2
Energy Credits 406.3
406.2 & 406.3
For heating system based on electric resistance with a ductless mini -split heat pump system in
Electric Resistance with Ductless
4
accordance with Section R403.7.1 including the exception
Heat Pump
0.5
1.5
2.0
Table R406.3 Energy Credits
Energy
Option No. Category Select Options Credits Brief Description of Selected Options*
1
Efficient Building Envelope
0.0
2
Air Leakage Control and Efficient Ventilation
0.0
3
High Efficiency HVAC
Option 3.4
1.5
Ductless Split System, Zonal Control. Min HSPF of 10.
4
High Efficiency HVAC Distribution System
NA
5.1
Efficient Water Heating
0.0
5.2-5.6
Efficient Water Heating
0.0
6
Renewable Electric Energy
kWh
0.0
7
Appliance Package
0.0
Energy Credits
1.5
*Refer to WSEC 2018 Table R406.3 for complete option descriptions and requirements
THERMAL ENVELOPE DETAILS - Proposed Design
Conditioned Floor Area of Addition, Proposed Desi n 420 sq. ft
Pardi Garage Conversion WSEC 2018 - Rafter Option.xlsm 6/3/2024 1
WSU Code Compliance Calculator, WSEC 2018
Classification Addition of 500 sf or less
Notes
Exterior Doors
Plan
Component
Door
Width
Hei
ht
ID
Description
Ref.
U
Qt.
Feet
I"`"
Feet
I"`"
Area
UA
Exempt
Insulated Steel, Wood Edge ISteelWE
10-6C
0.16
1
3
°
6
8
20
3.2
0
0.0
0
0.0
0
0.0
0
0.0
01
0.0
0
0.0
0
0.0
0
0.0
0
0.0
0
0.0
Sum of Area and UA (excluding exempt door) 0 0.0
Exterior Doors Area Weighted U
Overhead Glazing
Plan
ID
Component
Description
Ref.
Glazing
U
Qt.
Width
Height
Area
UA
Feet
I"`"
Feet
I"`"
2 I wood, a=0.05 argon Code Baseline
10-6E
0.50
2
2
°
6
°
24
12
2 l wood, a=0.05 argon Code Baseline
10-6E
0.50
2
2
°
2
°
8
4
0
0
0
Sum of Area and UAI 321 16
Overhead Glazing Area Weighted U 0.500
Vertical Glazing Schedule
Rows to Show
1
Plan
Component
Glazing
Width
Height
Feet
I '"`"
Feet
I"`"
ID
Description
Ref.
U
Qt.
Area
UA
Exempt
1
U=0.30 Code Baseline
Table 406.2
0.30
1 2
21
11
4
°
23.3
7.00
Sum of Area and UA 23.3
7.0
Vertical Glazing Area Weighted U
0.300
Vertical Glazing and Doors Area Weighted U
0.300
FlatNaulted Ceilings
Plan
ID
Component
Description
Ref.
Attic
U
Area
UA
R49 blown Attic STD baffled
10-7
0.027
80
2.2
R38 batt Vault unvented 2x12 16oc
10-7
0.029
332
9.6
Sum of Area and UAI 4121 11.8
Walls Above Grade
Plan
ID
Component
Description
Ref.
Wall
U
Net Area
UA
R21 cavil +RO foam INT 2X6W La Code Baseline
10-5
0.054
363
20
R21 cavil +RO foam INT 2X6W Lap Code Baseline
10-5
0.054
242
13
Sum of Area and UA 6051 33
Floor over crawl or exterior
Plan
ID
Component
Description
Ref.
Floor
U
Area
UA
0
Sum of Area and UA 1 01 0
Slab on Grade less than 2 feet belowgrade)
Plan I Component Slab
Pardi Garage Conversion W SEC 2018 - Rafter Option.xlsm 6/3/2024
WSU Code Compliance Calculator, WSEC 2018
ID
I Description
Ref.
I F
Slab Perim
FP
R-7.5 On to of slab(Existing slab conversion only)
Footnote, Ta
0.540
75
40
Sum of Perimeter and FP
75
40
Below Grade Walls and Slabs
Plan
ID
Component
Description
Ref.
Wall
U
Wall
Area
Wall
UA
Slab
F
Slab Perim
Slab
UA
Sum of Area, Length and UA 01 0.0 01 0
Ventilation
Number of Bedrooms
2
Run -Time Percent in Each 4-Hour Segment
50
Is the system Balanced?
Unbalanced
Is the system Distributed?
Not Distributed
Ventilation Code Section
IRC, Chapter 15
Whole House Mechanical Ventilation Airflow Rate
90 CFM
HVAC Thermal Distribution System Download RS-33 (2018) htt ://www.ener .wsu.edu/Documents/Duct%20Testin %20Standards%2
Is this a hydronic heating system?
INO
Location of Ducts
Unducted
Location of Air Handler
Unconditioned Space
Existing Construction: Are Any of These Exceptions True?
Are ducts systems documented to have been previously sealed as confirmed through
No
field verification and diagnostic testing per RS-33?
Is there less than 40 linear feet in unconditioned spaces?
No
Are existing duct systems constructed, insulated or sealed with asbestos?
No
Is the project an Addition less than 750 sf of conditioned floor area?
Is Duct Testing Required?
No
No
Compliance Certificate
Compliance Certificate Instructions
Insulation Certificate for Residential New Construction
Insulation Certificate
Duct Testing Affadavits
Existing Construction Affidavit, Existing
New Construction Affidavit, New
Prescriptive Checklist for 2018 WSEC
Prescriptive Checklist
Alterations (Remodel) Worksheet
Worksheet
Heating System Sizing - Proposed Design Try Out BetterBuiltNW's HVAC Sizing Tool: ht[ps://betterbLiiltnw.com/resources/hvac-sizing-tool
Nearest Weather Station
Indoor Design Temperature
Outdoor Design Temperature
Design Temperature Difference (AT)
Conditioned Floor Area of Addition, Proposed Design
Conditioned Volume
Leave blank to use default of 8.5 ft. ceiling height
HVAC System Type
Location of HVAC Distribution System
Sum of UA, including exempt door and window
70 F
24 F
46 F
420 ft2
3,571 0
All Other Svstems (not heat Dump)
Unducted
108
Envelope Heat Load
4,965 Btu / Hour
Sum of UA X AT
Air Leakage Heat Load
1,774 Btu / Hour
((volumeX 0.6) X AT) X.018))
Building Design Heat Load
6,739 Btu / Hour
Air Leakage + Envelope Heat Loss
Building and Duct Heat Load
6,739 Btu / Hour
For ducts located in unconditioned space: Sum of Building Heat Loss X 1.1
For ducts located in conditioned space or ductless: Sum of Building Heat Loss
X 1
Maximum Heat Equipment Output
9,434 Btu / Hour
Building and Duct Heat Loss X 1.25 for heat pumps
Pardi Garage Conversion WSEC 2018 - Rafter Option.xlsm 6/3/2024 3
WSU Code Compliance Calculator, WSEC 2018
Building and Duct Heat Loss X 1.40 for all other systems
Pardi Garage Conversion W SEC 2018 - Rafter Option.xlsm 6/3/2024