Loading...
REV1 APPROVED BLD - BLD2022-0439+Structural_Plan+10.30.2023_10.46.42_AM+3868534General Structural Notes Continued APPROVED ALL WORK SUBJECT PLANS MUST BE TO FIELD ON JOB SITE INSPECTION FOR CODE COMPLIANCE REVISED PLAN APPROVED CITY OF EDMONDS BUILDING DIVISION D BUILDING OFFICIAL Nov 16 2023 APPROVED DATE The following documentation shall be available on = site for the building inspector: ■ ❑ COE APPROVED ARCHITECTURAL PLAN SET COE APPROVED STRUCTURAL PLAN SET ; COE REVIEWED CALCULATION PACKET ' ENERGY CREDIT WORKSHEET SITE PLAN ; CIVIL PLAN ' x❑ ORIGINAL APPROVED ARCH. PLANS �F ORIGINAL APPROVED STRUCT. PLANS ; CITY OF EDMONDS BUILDING DEPARTMENT 2021 ■ THE FOLLOWING APPLY UNLESS SHOWN OTHERWISE ON THE DRAWINGS 39. FRAMING LUMBER SHALL BE S-DRY, KD, OR MC-19, AND GRADED AND MARKED IN 44. P EFABRICATED CONNECTOR PLATE WOOD ROOF TRUSSES SHALL BE DESIGNED BY THE CONFORMANCE WITH WCLIB STANDARD No. 17, GRADING RULES FOR WEST COAST LUMBER, KANUFACTURER IN ACCORDANCE WITH THE "NATIONAL DESIGN STANDARD FOR METAL 2018, OR WWPA STANDARD, WESTERN LUMBER GRADING RULES 2017. FURNISH TO THE PLATE -CONNECTED WOOD TRUSS CONSTRUCTION, ANSI/TPI 1" BY THE TRUSS PLATE FOLLOWING MINIMUM STANDARDS: INSTITUTE FOR THE SPANS AND CONDITIONS SHOWN ON THE PLANS. LOADING SHALL BE AS FOLLOWS: JOISTS (2X & 3X MEMBERS) AND BEAMS TOP CHORD LIVE LOAD 25 PSF TOP CHORD DEAD LOAD 10 PSF BOTTOM CHORD DEAD LOAD 5 PSF TOTAL LOAD 40 PSF WOOD (4X MEMBERS) BEAMS (INCL. 6X AND LARGER) POSTS (4X MEMBERS) (6X AND LARGER) STUDS, PLATES & MISC. FRAMING: HEM -FIR N0. 2 MINIMUM BASE VALUE, Fb = 850 PSI DOUGLAS FIR -LARCH NO. 1 MINIMUM BASE VALUE, Fb = 1000 PSI DOUGLAS FIR -LARCH NO. 1 MINIMUM BASE VALUE, Fb = 1350 PSI DOUGLAS FIR -LARCH NO. 2 MINIMUM BASE VALUE, Fc = 1350 PSI DOUGLAS FIR -LARCH NO. 1 MINIMUM BASE VALUE, Fc = 1000 PSI DOUGLAS FIR -LARCH NO. 2 OR HEM -FIR NO. 2 40. GLUED LAMINATED MEMBERS SHALL BE FABRICATED IN CONFORMANCE WITH ASTM AND ANSI/AITC STANDARDS. EACH MEMBER SHALL BEAR AN AITC OR APA IDENTIFICATION MARK AND SHALL BE ACCOMPANIED BY AN AITC OR APA CERTIFICATE OF CONFORMANCE. ALL SIMPLE SPAN BEAMS SHALL BE DOUGLAS FIR COMBINATION 24F-V4, Fb = 2,400 PSI, Fv =265 PSI. ALL CANTILEVERED BEAMS SHALL BE DOUGLAS FIR COMBINATION 24F-V8, Fb = 2400 PSI, Fv = 265 PSI. CAMBER ALL SIMPLE SPAN GLULAM BEAMS, WITH SPANS OVER 30', TO 3,500' RADIUS, UNLESS SHOWN OTHERWISE ON THE PLANS. 41. MANUFACTURED LUMBER, WHERE NOTED, BEAMS MAY BE PSL, LVL, AND LSL SHOWN ON PLAN ARE BASED ON PRODUCTS MANUFACTURED BY THE WEYERHAEUSER CORPORATION IN ACCORDANCE WITH ICC-ES REPORT ESR-1387. MEMBERS SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES: PSL (2.OE WS) Fb = 2900 PSI, E = 2000 KSI, Fv = 290 PSI LVL (2.OE-2600FB WS) Fb = 2600 PSI, E = 2000 KSI, Fv = 285 PSI LSL (1.55E) Fb = 2325 PSI, E = 1550 KSI, Fv = 310 PSI ALTERNATE MANUFACTURED LUMBER MANUFACTURERS MAY BE USED SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND STRUCTURAL ENGINEER. ALTERNATE MANUFACTURER'S PRODUCTS SHALL BE COMPATIBLE WITH THE JOIST HANGERS AND OTHER HARDWARE SPECIFIED ON PLANS, OR ALTERNATE HANGERS AND HARDWARE SHALL SUBMITTED FOR REVIEW AND APPROVAL. SUBSTITUTED ITEMS SHALL HAVE ICC-ES REPORT APPROVAL FOR EQUAL OR GREATER LOAD CAPACITIES. MANUFACTURED LUMBER PRODUCTS SHALL BE INSTALLED WITH A MOISTURE CONTENT OF 12% OR LESS. THE CONTRACTOR SHALL MAKE PROVISIONS DURING CONSTRUCTION TO PREVENT THE MOISTURE CONTENT OF INSTALLED BEAMS FROM EXCEEDING 12%. EXCESSIVE DEFLECTIONS MAY OCCUR IF MOISTURE CONTENT EXCEEDS THIS VALUE. 42. PREFABRICATED PLYWOOD WEB JOISTS SHALL BE DESIGNED BY THE MANUFACTURER FOR THE SPANS AND CONDITIONS SHOWN ON THE PLANS AND SHALL BE FURNISHED AND INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S PUBLISHED SPECIFICATIONS. ALL NECESSARY BRIDGING, BLOCKING, BLOCKING PANELS, STIFFENERS, ETC., SHALL BE DETAILED AND FURNISHED BY THE MANUFACTURER. SUBMIT SHOP DRAWINGS AND DESIGN CALCULATIONS TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW PRIOR TO FABRICATION. DESIGN SUBMITTALS SHALL BEAR THE STAMP AND SIGNATURE OF A REGISTERED PROFESSIONAL ENGINEER, STATE OF WASHINGTON. PERMANENT AND TEMPORARY BRIDGING SHALL BE INSTALLED IN CONFORMANCE WITH MANUFACTURER'S SPECIFICATIONS. THE DESIGN SHOWN ON THE PLANS IS BASED ON JOISTS MANUFACTURED BY THE WEYERHAEUSER CORPORATION, IN ACCORDANCE WITH ICC-ES REPORT ESR-1157. ALTERNATE PLYWOOD WEB JOIST MANUFACTURERS MAY BE USED SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND STRUCTURAL ENGINEER. ALTERNATE MANUFACTURER'S PRODUCTS SHALL BE COMPATIBLE WITH THE JOIST HANGERS AND OTHER HARDWARE SPECIFIED ON PLANS, OR ALTERNATE HANGERS AND HARDWARE SHALL SUBMITTED FOR REVIEW AND APPROVAL. SUBSTITUTED ITEMS SHALL HAVE ICC-ES REPORT APPROVAL FOR EQUAL OR GREATER LOAD CAPACITIES. 43. PLYWOOD SHEATHING SHALL BE GRADE C-D, EXTERIOR GLUE OR STRUCTURAL II, EXTERIOR GLUE IN CONFORMANCE WITH DOC PS 1 OR PS 2. ORIENTED STRAND BOARD OF EQUIVALENT THICKNESS, EXPOSURE RATING AND PANEL INDEX MAY BE USED IN LIEU OF PLYWOOD. FLOOR SHEATHING SHALL BE 3/4' (NOMINAL) WITH SPAN RATING 48/24. WALL SHEATHING SHALL BE 1/2" (NOMINAL) WITH SPAN RATING 24/0. ALL FLOOR SHEATHING EDGES SHALL HAVE APPROVED T&G JOINTS OR SHALL BE SUPPORTED WITH SOLID BLOCKING. ALLOW 1/8" SPACING AT ALL PANEL EDGES AND ENDS OF FLOOR AND ROOF SHEATHING. REFER TO WOOD FRAMING NOTES BELOW FOR TYPICAL NAILING REQUIREMENTS. WIND UPLIFT (TOP CHORD) 5 PSF BOTTOM CHORD LIVE LOAD 10 PSF (BOTTOM CHORD LIVE LOAD DOES NOT ACT CONCURRENTLY WITH THE ROOF LIVE LOAD) WOOD TRUSSES SHALL UTILIZE APPROVED CONNECTOR PLATES (GANGNAIL OR EQUAL). SUBMIT SHOP DRAWINGS AND DESIGN CALCULATIONS TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW PRIOR TO FABRICATION. SUBMITTED DOCUMENTS SHALL BE SIGNED AND STAMPED BY A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF WASHINGTON. PROVIDE FOR SHAPES, BEARING POINTS, INTERSECTIONS, HIPS, VALLEYS, ETC., SHOWN ON THE DRAWINGS. EXACT COMPOSITION OF SPECIAL HIP, VALLEY, AND INTERSECTION AREAS (USE OF GIRDER TRUSSES, JACK TRUSSES, STEP-DOWN TRUSSES, ETC.) SHALL BE DETERMINED BY THE MANUFACTURER UNLESS SPECIFICALLY INDICATED ON THE PLANS. PROVIDE ALL TRUSS TO TRUSS AND TRUSS TO GIRDER TRUSS CONNECTION DETAILS AND REQUIRED CONNECTION MATERIALS. PROVIDE FOR ALL TEMPORARY AND PERMANENT TRUSS BRACING AND BRIDGING. 45. TONGUE -AND -GROOVE STRUCTURAL FLOOR DECKING SHALL BE INSTALLED AS FOLLOWS: 2X DECKING SHALL BE TOENAILED THROUGH THE TONGUE AND FACE - NAILED WITH ONE 16d NAIL PER PIECE PER SUPPORT. DECKING SHALL BE PLACED WITH A CONTROLLED RANDOM LAYOUT UNLESS OTHERWISE NOTED AND SHALL EXTEND ACROSS A MINIMUM OF THREE SPANS. EACH PLANK SHALL BEAR ON AT LEAST ONE SUPPORT. ALL JOINTS SHALL BE END MATCHED AND ALL PLANKS NAILED TOGETHER WITHIN ONE FOOT OF EACH SIDE OF THE END JOINT. END JOINTS IN ADJACENT PLANKS SHALL BE AT LEAST TWO FEET APART AND END JOINTS IN ALTERNATE PLANKS SHALL BE MORE THAN ONE FOOT APART WHEN MEASURED ALONG THE LENGTH OF THE DECKING. END JOINTS NOT OCCURRING OVER SUPPORTS SHALL BE MATCHED TONGUED AND GROOVED OR SHALL BE CONNECTED WITH 10 GAUGE METAL SPLINES DRIVEN INTO PRE-CUT SLOTS. TONGUE AND GROOVE JOINTS SHALL BE GLUED WITH CONSTRUCTION ADHESIVE WHERE NOTED ON PLAN. 46. ALL WOOD IN DIRECT CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE -TREATED WITH AN APPROVED PRESERVATIVE OR (2) LAYERS OF ASPHALT IMPREGNATED BUILDING PAPER SHALL BE PROVIDED BETWEEN UNTREATED WOOD AND CONCRETE OR MASONRY. 47. PRESERVATIVE TREATED WOOD SHALL BE TREATED PER AWPA STANDARD U1 TO THE USE CATEGORY EQUAL TO OR HIGHER THAN THE INTENDED APPLICATION. TREATED WOOD FOR ABOVE GROUND USE SHALL BE TREATED TO AWPA UC3B. WOOD IN CONTINUOUS CONTACT WITH FRESH WATER OR SOIL SHALL BE TREATED TO AWPA UC4A. WOOD FOR USE IN PERMANENT FOUNDATIONS SHALL BE TREATED TO AWPA UC4B. 48. FASTENERS AND TIMBER CONNECTORS USED WITH TREATED WOOD SHALL HAVE CORROSION RESISTANCE AS INDICATED IN THE FOLLOWING TABLE, UNLESS OTHERWISE NOTED. WOOD TREATMENT HAS NO AMMONIA CARRIER CONTAINS AMMONIA CARRIER CONTAINS AMMONIA CARRIER CONTAINS AMMONIA CARRIER AZCA CONDITION PROTECTION INTERIOR DRY G90 GALVANIZED INTERIOR DRY G185 OR A185 HOT DIPPED OR CONTINUOUS HOT -GALVANIZED PER ASTM A653 INTERIOR WET TYPE 304 OR 316 STAINLESS EXTERIOR TYPE 304 OR 316 STAINLESS ANY TYPE 304 OR 316 STAINLESS INTERIOR DRY CONDITIONS SHALL HAVE WOOD MOISTURE CONTENT LESS THAN 19%. WOOD MOISTURE CONTENT IN OTHER CONDITIONS (INTERIOR WET, EXTERIOR WET, AND EXTERIOR DRY) IS EXPECTED TO EXCEED 19%. CONNECTORS AND THEIR FASTENERS SHALL BE THE SAME MATERIAL. COMPLY WITH THE TREATMENT MANUFACTURERS RECOMMENDATIONS FOR PROTECTION OF METAL. 49. TIMBER CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE" BY SIMPSON COMPANY, AS SPECIFIED IN THEIR CATALOG NUMBER C-C-2019. EQUIVALENT DEVICES BY OTHER MANUFACTURERS MAY BE SUBSTITUTED, PROVIDED THEY HAVE ICC-ES APPROVAL FOR EQUAL OR GREATER LOAD CAPACITIES. PROVIDE NUMBER AND SIZE OF FASTENERS AS SPECIFIED BY MANUFACTURER FOR MAXIMUM LOAD CARRYING CAPACITY. CONNECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ALL 2X JOISTS SHALL BE CONNECTED TO FLUSH BEAMS WITH "LUS" SERIES JOIST HANGERS. ALL TJI JOISTS SHALL BE CONNECTED TO FLUSH BEAMS WITH "ITS" SERIES JOIST HANGERS. ALL DOUBLE -JOIST BEAMS SHALL BE CONNECTED TO FLUSH BEAMS WITH "MIT" SERIES JOIST HANGERS. WHERE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE ONE-HALF OF THE NAILS OR BOLTS IN EACH MEMBER. ALL SHIMS SHALL BE SEASONED AND DRIED AND THE SAME GRADE (MINIMUM)AS MEMBERS CONNECTED. 50. WOOD FASTENERS A. NAIL SIZES SPECIFIED ON DRAWINGS ARE BASED ON THE FOLLOWING SPECIFICATIONS: SIZE LENGTH DIAMETER 8d 2-1/2" 0.131" 10d 3" 0.148" 16d BOX 3-1/2" 0.135" IF CONTRACTOR PROPOSES THE USE OF ALTERNATE NAILS, THEY SHALL SUBMIT NAIL SPECIFICATIONS TO THE STRUCTURAL ENGINEER (PRIOR TO CONSTRUCTION) FOR REVIEW AND APPROVAL. NAILS - PLYWOOD (APA RATED SHEATHING) FASTENERS TO FRAMING SHALL BE DRIVEN FLUSH TO FACE OF SHEATHING WITH NO COUNTERSINKING PERMITTED. TOE -NAILS SHALL BE DRIVEN AT AN ANGLE OF 30 DEGREES WITH THE MEMBER AND STARTED 1/3 THE LENGTH OF THE NAIL FROM THE MEMBER END. B. ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG BOLTS BEARING ON WOOD. INSTALLATION OF LAG BOLTS SHALL CONFORM TO THE NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION WITH A LEAD BORE HOLE OF 60 TO 70 PERCENT OF THE SHANK DIAMETER. LEAD HOLES ARE NOT REQUIRED FOR 3/8' AND SMALLER LAG SCREWS. 51. NOTCHES AND HOLES IN WOOD FRAMING: A. NOTCHES ON THE ENDS OF SOLID SAWN JOISTS AND RAFTERS SHALL NOT EXCEED ONE-FOURTH THE JOIST DEPTH. NOTCHES IN THE TOP OR BOTTOM OF SOLID SAWN JOISTS SHALL NOT EXCEED ONE -SIXTH THE DEPTH AND SHALL NOT BE LOCATED IN THE MIDDLE THIRD OF THE SPAN. HOLES BORED IN SOLID SAWN JOISTS AND RAFTERS SHALL NOT BE WITHIN 2 INCHES OF THE TOP OR BOTTOM OF THE JOIST, AND THE DIAMETER OF ANY SUCH HOLE SHALL NOT EXCEED ONE-THIRD THE DEPTH OF THE JOIST. B. IN EXTERIOR WALLS AND BEARING PARTITIONS, ANY WOOD STUD IS PERMITTED TO BE CUT OR NOTCHED TO A DEPTH NOT EXCEEDING 25 PERCENT OF ITS WIDTH. A HOLE NOT GREATER IN DIAMETER THAN 40 PERCENT OF THE STUD WIDTH IS PERMITTED TO BE BORED IN ANY WOOD STUD. IN NO CASE SHALL THE EDGE OF THE BORED HOLE BE NEARER THAN 5/8 INCH TO THE EDGE OF THE STUD. BORED HOLES SHALL NOT BE LOCATED AT THE SAME SECTION OF STUD AS A CUT OR NOTCH. C. NOTCHES AND HOLES IN MANUFACTURED LUMBER AND PREFABRICATED PLYWOOD WEB JOISTS SHALL BE PER THE MANUFACTURERS RECOMMENDATIONS UNLESS OTHERWISE NOTED. 52. WOOD FRAMING NOTES --THE FOLLOWING APPLY UNLESS OTHERWISE SHOWN ON THE PLANS: A. ALL WOOD FRAMING DETAILS NOT SHOWN OTHERWISE SHALL BE CONSTRUCTED TO THE MINIMUM STANDARDS OF THE INTERNATIONAL BUILDING CODE, THE AITC "TIMBER CONSTRUCTION MANUAL" AND THE AWC "NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION". MINIMUM NAILING, UNLESS OTHERWISE NOTED, SHALL CONFORM TO IBC TABLE 2304.10.1. COORDINATE THE SIZE AND LOCATION OF ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS. B. WALL FRAMING: REFER ARCHITECTURAL DRAWINGS FOR THE SIZE OF ALL WALLS. ALL STUDS SHALL BE SPACED AT 16" O.C. UNO. TWO STUDS MINIMUM SHALL BE PROVIDED AT THE END OF ALL WALLS AND AT EACH SIDE OF ALL OPENINGS, AND AT BEAM OR HEADER BEARING LOCATIONS. TWO 2x8 HEADERS SHALL BE PROVIDED OVER ALL OPENINGS NOT OTHERWISE NOTED. SOLID BLOCKING FOR WOOD COLUMNS SHALL BE PROVIDED THROUGH FLOORS TO SUPPORTS BELOW. PROVIDE CONTINUOUS SOLID BLOCKING AT MID -HEIGHT OF ALL STUD WALLS OVER 10'-0" IN HEIGHT. ALL WALLS SHALL HAVE A SINGLE BOTTOM PLATE AND A DOUBLE TOP PLATE. END NAIL TOP PLATE TO EACH STUD WITH TWO 16d NAILS, AND TOENAIL OR END NAIL EACH STUD TO BOTTOM PLATE WITH TWO 16d NAILS. FACE NAIL DOUBLE TOP PLATE WITH 16d @ 12" O.C.. LAP TOP PLATES AT JOINTS A MINIMUM 4'-0" AND NAIL WITH TWELVE 16d NAILS @ 4" O.C. EACH SIDE JOINT. ALL STUD WALLS SHALL HAVE THEIR LOWER WOOD PLATES ATTACHED TO WOOD FRAMING BELOW WITH TWO ROWS OF 16d NAILS @ 12" ON -CENTER, OR ATTACHED TO CONCRETE BELOW WITH 5/8" DIAMETER ANCHOR BOLTS @ 4'-0" ON -CENTER EMBEDDED 7" MINIMUM, UNLESS INDICATED OTHERWISE. INDIVIDUAL MEMBERS OF BUILT-UP POSTS SHALL BE NAILED TO EACH OTHER WITH TWO ROWS OF 16d @12" ON -CENTER. UNLESS OTHERWISE NOTED, GYPSUM WALLBOARD SHALL BE FASTENED TO THE INTERIOR SURFACE OF ALL STUDS AND PLATES WITH NO. 6 X 1-1/4" TYPE S OR W SCREWS @ 8" ON -CENTER. UNLESS INDICATED OTHERWISE, 1/2" (NOMINAL)APA RATED SHEATHING (SPAN RATING 24/0) SHALL BE NAILED TO ALL EXTERIOR SURFACES WITH 8d NAILS @ 6" ON -CENTER AT PANEL EDGES AND TOP AND BOTTOM PLATES (BLOCK UN -SUPPORTED EDGES)AND TO ALL INTERMEDIATE STUDS AND BLOCKING WITH 8d NAILS @ 12" ON -CENTER ALLOW 1/8" SPACING AT ALL PANEL EDGES AND PANEL ENDS. C. FLOOR FRAMING: PROVIDE DOUBLE JOISTS UNDER ALL PARALLEL PARTITIONS THAT EXTEND OVER MORE THAN HALF THE JOIST LENGTH AND AROUND ALL OPENINGS IN FLOORS UNLESS OTHERWISE NOTED. PROVIDE SOLID BLOCKING BETWEEN JOISTS AT ALL BEARING POINTS WITH A MINIMUM OF (3) 16d TOE NAILS EACH END. TOE -NAIL JOISTS TO SUPPORTS WITH TWO 16d NAILS. ATTACH TIMBER JOISTS TO FLUSH HEADERS OR BEAMS WITH SIMPSON METAL JOIST HANGERS IN ACCORDANCE WITH NOTES ABOVE. NAIL ALL MULTI JOIST BEAMS TOGETHER WITH TWO ROWS 16d @ 12" ON -CENTER. UNLESS OTHERWISE NOTED ON THE PLANS, PLYWOOD FLOOR SHEATHING SHALL BE LAID UP WITH GRAIN PERPENDICULAR TO SUPPORTS AND NAILED AT 6" ON -CENTER WITH 8d NAILS TO FRAMED PANEL EDGES, STRUTS AND OVER STUD WALLS AS SHOWN ON PLANS AND @ 12" ON -CENTER TO INTERMEDIATE SUPPORTS. ALL FLOOR SHEATHING EDGES SHALL HAVE APPROVED T&G JOINTS OR SHALL BE SUPPORTED WITH SOLID BLOCKING. ALLOW 1/8" SPACING AT ALL PANEL EDGES AND ENDS OF FLOOR SHEATHING. TOENAIL BLOCKING TO SUPPORTS WITH 16d @ 12" ON -CENTER, MINIMUM TWO NAILS PER BLOCK, UNLESS OTHERWISE NOTED. Sill L EN NEMN 2124 Third Avenue - Suite too - Seattle, WA 98121 p:2o6.443.6212 ssfengineers.com 934 Broadway - Tacoma, WA 98402 P:253•z84.9470 ssfengineers.com Copyright 2022 Swenson Say Faget - All Rights Reserved DRAWN: _ N: SRK DESIGN: RGC CHECKED: RGC APPROVED: RGC REVISIONS: Permit Revision Oct. 24, 2022 2 Permit Corrections, Round 2 Feb. 13, 2023 Roof Revisions Sept. 22, 2023 JURISDICTIONAL APPROVAL STAMP: 1:3111111l041Wel91661 REVISION Oct 30 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT PROJECT TITLE: ANGLE RESIDENCE 15724 72nd Avenue W. Edmonds, WA 98026 ARCHITECT: Cast Architecture 115-C North 36th Street Seattle, WA 98103 CASTa rc h i tect u re . co m ph 206.256.9886 ISSUE: Permit S' TITLE: General Structural Notes Continued SCALE: DATE: March 29, 2022 PROJECT NO: 00640-2021-01 SHEET NO: S 1.2 INTERIOR DRY CONDITIONS SHALL HAVE WOOD MOISTURE CONTENT LESS THAN 19%. WOOD MOISTURE CONTENT IN OTHER CONDITIONS (INTERIOR WET, EXTERIOR WET, AND EXTERIOR DRY) IS EXPECTED TO EXCEED 19%. CONNECTORS AND THEIR FASTENERS SHALL BE THE SAME MATERIAL. COMPLY WITH THE TREATMENT MANUFACTURERS RECOMMENDATIONS FOR PROTECTION OF METAL. 49. TIMBER CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE" BY SIMPSON COMPANY, AS SPECIFIED IN THEIR CATALOG NUMBER C-C-2019. EQUIVALENT DEVICES BY OTHER MANUFACTURERS MAY BE SUBSTITUTED, PROVIDED THEY HAVE ICC-ES APPROVAL FOR EQUAL OR GREATER LOAD CAPACITIES. PROVIDE NUMBER AND SIZE OF FASTENERS AS SPECIFIED BY MANUFACTURER FOR MAXIMUM LOAD CARRYING CAPACITY. CONNECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ALL 2X JOISTS SHALL BE CONNECTED TO FLUSH BEAMS WITH "LUS" SERIES JOIST HANGERS. ALL TJI JOISTS SHALL BE CONNECTED TO FLUSH BEAMS WITH "ITS" SERIES JOIST HANGERS. ALL DOUBLE -JOIST BEAMS SHALL BE CONNECTED TO FLUSH BEAMS WITH "MIT" SERIES JOIST HANGERS. WHERE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE ONE-HALF OF THE NAILS OR BOLTS IN EACH MEMBER. ALL SHIMS SHALL BE SEASONED AND DRIED AND THE SAME GRADE (MINIMUM)AS MEMBERS CONNECTED. 50. WOOD FASTENERS A. NAIL SIZES SPECIFIED ON DRAWINGS ARE BASED ON THE FOLLOWING SPECIFICATIONS: SIZE LENGTH DIAMETER 8d 2-1/2" 0.131" 10d 3" 0.148" 16d BOX 3-1/2" 0.135" IF CONTRACTOR PROPOSES THE USE OF ALTERNATE NAILS, THEY SHALL SUBMIT NAIL SPECIFICATIONS TO THE STRUCTURAL ENGINEER (PRIOR TO CONSTRUCTION) FOR REVIEW AND APPROVAL. NAILS - PLYWOOD (APA RATED SHEATHING) FASTENERS TO FRAMING SHALL BE DRIVEN FLUSH TO FACE OF SHEATHING WITH NO COUNTERSINKING PERMITTED. TOE -NAILS SHALL BE DRIVEN AT AN ANGLE OF 30 DEGREES WITH THE MEMBER AND STARTED 1/3 THE LENGTH OF THE NAIL FROM THE MEMBER END. B. ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG BOLTS BEARING ON WOOD. INSTALLATION OF LAG BOLTS SHALL CONFORM TO THE NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION WITH A LEAD BORE HOLE OF 60 TO 70 PERCENT OF THE SHANK DIAMETER. LEAD HOLES ARE NOT REQUIRED FOR 3/8' AND SMALLER LAG SCREWS. 51. NOTCHES AND HOLES IN WOOD FRAMING: A. NOTCHES ON THE ENDS OF SOLID SAWN JOISTS AND RAFTERS SHALL NOT EXCEED ONE-FOURTH THE JOIST DEPTH. NOTCHES IN THE TOP OR BOTTOM OF SOLID SAWN JOISTS SHALL NOT EXCEED ONE -SIXTH THE DEPTH AND SHALL NOT BE LOCATED IN THE MIDDLE THIRD OF THE SPAN. HOLES BORED IN SOLID SAWN JOISTS AND RAFTERS SHALL NOT BE WITHIN 2 INCHES OF THE TOP OR BOTTOM OF THE JOIST, AND THE DIAMETER OF ANY SUCH HOLE SHALL NOT EXCEED ONE-THIRD THE DEPTH OF THE JOIST. B. IN EXTERIOR WALLS AND BEARING PARTITIONS, ANY WOOD STUD IS PERMITTED TO BE CUT OR NOTCHED TO A DEPTH NOT EXCEEDING 25 PERCENT OF ITS WIDTH. A HOLE NOT GREATER IN DIAMETER THAN 40 PERCENT OF THE STUD WIDTH IS PERMITTED TO BE BORED IN ANY WOOD STUD. IN NO CASE SHALL THE EDGE OF THE BORED HOLE BE NEARER THAN 5/8 INCH TO THE EDGE OF THE STUD. BORED HOLES SHALL NOT BE LOCATED AT THE SAME SECTION OF STUD AS A CUT OR NOTCH. C. NOTCHES AND HOLES IN MANUFACTURED LUMBER AND PREFABRICATED PLYWOOD WEB JOISTS SHALL BE PER THE MANUFACTURERS RECOMMENDATIONS UNLESS OTHERWISE NOTED. 52. WOOD FRAMING NOTES --THE FOLLOWING APPLY UNLESS OTHERWISE SHOWN ON THE PLANS: A. ALL WOOD FRAMING DETAILS NOT SHOWN OTHERWISE SHALL BE CONSTRUCTED TO THE MINIMUM STANDARDS OF THE INTERNATIONAL BUILDING CODE, THE AITC "TIMBER CONSTRUCTION MANUAL" AND THE AWC "NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION". MINIMUM NAILING, UNLESS OTHERWISE NOTED, SHALL CONFORM TO IBC TABLE 2304.10.1. COORDINATE THE SIZE AND LOCATION OF ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS. B. WALL FRAMING: REFER ARCHITECTURAL DRAWINGS FOR THE SIZE OF ALL WALLS. ALL STUDS SHALL BE SPACED AT 16" O.C. UNO. TWO STUDS MINIMUM SHALL BE PROVIDED AT THE END OF ALL WALLS AND AT EACH SIDE OF ALL OPENINGS, AND AT BEAM OR HEADER BEARING LOCATIONS. TWO 2x8 HEADERS SHALL BE PROVIDED OVER ALL OPENINGS NOT OTHERWISE NOTED. SOLID BLOCKING FOR WOOD COLUMNS SHALL BE PROVIDED THROUGH FLOORS TO SUPPORTS BELOW. PROVIDE CONTINUOUS SOLID BLOCKING AT MID -HEIGHT OF ALL STUD WALLS OVER 10'-0" IN HEIGHT. ALL WALLS SHALL HAVE A SINGLE BOTTOM PLATE AND A DOUBLE TOP PLATE. END NAIL TOP PLATE TO EACH STUD WITH TWO 16d NAILS, AND TOENAIL OR END NAIL EACH STUD TO BOTTOM PLATE WITH TWO 16d NAILS. FACE NAIL DOUBLE TOP PLATE WITH 16d @ 12" O.C.. LAP TOP PLATES AT JOINTS A MINIMUM 4'-0" AND NAIL WITH TWELVE 16d NAILS @ 4" O.C. EACH SIDE JOINT. ALL STUD WALLS SHALL HAVE THEIR LOWER WOOD PLATES ATTACHED TO WOOD FRAMING BELOW WITH TWO ROWS OF 16d NAILS @ 12" ON -CENTER, OR ATTACHED TO CONCRETE BELOW WITH 5/8" DIAMETER ANCHOR BOLTS @ 4'-0" ON -CENTER EMBEDDED 7" MINIMUM, UNLESS INDICATED OTHERWISE. INDIVIDUAL MEMBERS OF BUILT-UP POSTS SHALL BE NAILED TO EACH OTHER WITH TWO ROWS OF 16d @12" ON -CENTER. UNLESS OTHERWISE NOTED, GYPSUM WALLBOARD SHALL BE FASTENED TO THE INTERIOR SURFACE OF ALL STUDS AND PLATES WITH NO. 6 X 1-1/4" TYPE S OR W SCREWS @ 8" ON -CENTER. UNLESS INDICATED OTHERWISE, 1/2" (NOMINAL)APA RATED SHEATHING (SPAN RATING 24/0) SHALL BE NAILED TO ALL EXTERIOR SURFACES WITH 8d NAILS @ 6" ON -CENTER AT PANEL EDGES AND TOP AND BOTTOM PLATES (BLOCK UN -SUPPORTED EDGES)AND TO ALL INTERMEDIATE STUDS AND BLOCKING WITH 8d NAILS @ 12" ON -CENTER ALLOW 1/8" SPACING AT ALL PANEL EDGES AND PANEL ENDS. C. FLOOR FRAMING: PROVIDE DOUBLE JOISTS UNDER ALL PARALLEL PARTITIONS THAT EXTEND OVER MORE THAN HALF THE JOIST LENGTH AND AROUND ALL OPENINGS IN FLOORS UNLESS OTHERWISE NOTED. PROVIDE SOLID BLOCKING BETWEEN JOISTS AT ALL BEARING POINTS WITH A MINIMUM OF (3) 16d TOE NAILS EACH END. TOE -NAIL JOISTS TO SUPPORTS WITH TWO 16d NAILS. ATTACH TIMBER JOISTS TO FLUSH HEADERS OR BEAMS WITH SIMPSON METAL JOIST HANGERS IN ACCORDANCE WITH NOTES ABOVE. NAIL ALL MULTI JOIST BEAMS TOGETHER WITH TWO ROWS 16d @ 12" ON -CENTER. UNLESS OTHERWISE NOTED ON THE PLANS, PLYWOOD FLOOR SHEATHING SHALL BE LAID UP WITH GRAIN PERPENDICULAR TO SUPPORTS AND NAILED AT 6" ON -CENTER WITH 8d NAILS TO FRAMED PANEL EDGES, STRUTS AND OVER STUD WALLS AS SHOWN ON PLANS AND @ 12" ON -CENTER TO INTERMEDIATE SUPPORTS. ALL FLOOR SHEATHING EDGES SHALL HAVE APPROVED T&G JOINTS OR SHALL BE SUPPORTED WITH SOLID BLOCKING. ALLOW 1/8" SPACING AT ALL PANEL EDGES AND ENDS OF FLOOR SHEATHING. TOENAIL BLOCKING TO SUPPORTS WITH 16d @ 12" ON -CENTER, MINIMUM TWO NAILS PER BLOCK, UNLESS OTHERWISE NOTED. Sill L EN NEMN 2124 Third Avenue - Suite too - Seattle, WA 98121 p:2o6.443.6212 ssfengineers.com 934 Broadway - Tacoma, WA 98402 P:253•z84.9470 ssfengineers.com Copyright 2022 Swenson Say Faget - All Rights Reserved DRAWN: _ N: SRK DESIGN: RGC CHECKED: RGC APPROVED: RGC REVISIONS: Permit Revision Oct. 24, 2022 2 Permit Corrections, Round 2 Feb. 13, 2023 Roof Revisions Sept. 22, 2023 JURISDICTIONAL APPROVAL STAMP: 1:3111111l041Wel91661 REVISION Oct 30 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT PROJECT TITLE: ANGLE RESIDENCE 15724 72nd Avenue W. Edmonds, WA 98026 ARCHITECT: Cast Architecture 115-C North 36th Street Seattle, WA 98103 CASTa rc h i tect u re . co m ph 206.256.9886 ISSUE: Permit S' TITLE: General Structural Notes Continued SCALE: DATE: March 29, 2022 PROJECT NO: 00640-2021-01 SHEET NO: S 1.2 A B C CS16 RAP EA. TOP ID" PLATE, @ CORNER 76x 4'-6" o� min. �v A -PROVIDE in�W6 x '-9" � min. / 01 L A 3/S5.1' > - s 6 Co I I N C'O� 6, s� G' � 5/S4.1 CD c� 1oF �s Z5 w O o .I` - 'l ' I � LLJ 1 /Sd.1 , 3/S4.1 3 PARALLEL CHORD TRUSSES @ 24"oc 2x8 OUTRIG ERS EA. TRUSS CD 12/S4.1 4/S4.1 / o 5/8" 0 HANGER ROD PER 2/S5.1 GEDAR GL 51/2x10l/2 4 - - Nv o w. U 4/S5.1 1 /S51 , 1 /S5 'I cr- o U � � ¢ < CN PSL 51/4x11 7/8 2/S4.1 , SIM. 6 /S4.1 /7o A(2x8 24"oc Plan Notes 0 N Cn cn Cow � Of rs 1 /S4.1 1. ALL NEW EXTERIOR WALLS SHALL BE W6 UNLESS NOTED OTHERWISE. 2. ALL NEW HEADERS SHALL BE (2) 2X8 UNLESS NOTED OTHERWISE. 3. PROVIDE (2) BEARING STUDS UNDER EACH END OF ALL HEADERS AND BEAMS OVER 5'-0" LONG UNLESS NOTED OTHERWISE. 4. PROVIDE FULL DEPTH VERTICAL BLOCKING AT MAIN FLOOR AND BASEMENT AT ALL COLUMN LOCATIONS. 5. TYPICAL BEAM -TO -BEAM HANGERS ARE HUC, UNLESS NOTED OTHERWISE. 6. TYPICAL FLOOR HOUSE FRAMING CONSISTS OF 23/32" T&G PLYWOOD, FACE GRAIN PERPENDICULAR TO THE SUPPORTS, OVER 9-1/2" TJI 210 @ 16" ON -CENTER. NAIL SHEATHING PER THE GENERAL NOTES. 7. TYPICAL LOFT FRAMING CONSISTS OF 1/2" PLYWOOD, NAILED AT 6" ON -CENTER AT PANEL EDGES, AND 12" ON -CENTER IN THE FIELD, OVER 2X DECKING, ON JOISTS PER PLAN. Q5 8. TYPICAL ROOF FRAMING CONSISTS OF 1/2" PLYWOOD, FACE GRAIN PERPENDICULAR TO SUPPORTS, OVER PRE -MANUFACTURED TRUSS SPACED AT 24" O.C. NAIL SHEATHING PER THE GENERAL STRUCTURAL NOTES. 9. INDICATES HOLDOWN PER HOLDOWN SCHEDULE. 10. COLUMNS INDICATED ON PLAN TERMINATE AT THE FLOOR THEY ARE CALLED OUT ON. 11. INDICATES (X) NUMBER OF BEARING STUDS IN A MULTI -STUD COLUMN. NAIL STUDS TOGETHER WITH (2) 16D @ 12" ON -CENTER. 12. DO NOT SCALE DRAWINGS. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS. 13. REFER TO THE GENERAL STRUCTURAL NOTES FOR ADDITIONAL REQUIREMENTS. 14. CEDAR GLUED LAMINATED MEMBERS SHALL BE FABRICATED IN CONFORMANCE WITH ASTM AND ANSI/AITC STANDARDS. EACH MEMBER SHALL BEAR AN AITC OR APA IDENTIFICATION MARK AND SHALL BE ACCOMPANIED BY AN AITC OR APA CERTIFICATE OF CONFORMANCE. ALL SIMPLE SPAN BEAMS SHALL BE ALASKA YELLOW CEDAR COMBINATION 20E-V12, Fb = 2,000 PSI, Fv =265 PSI. ALL CANTILEVERED BEAMS SHALL BE ALASKA YELLOW CEDAR COMBINATION 24F-V13, Fb = 2000 PSI, Fv = 265 PSI. CAMBER ALL SIMPLE SPAN GLULAM BEAMS, WITH SPANS OVER 30', TO 3,500' RADIUS, UNLESS SHOWN OTHERWISE ON THE PLANS. o J cn E4PROVI G A .5 CLIP PER TO BAY WINDOW -UW6 x 5'-5" - - min. min. A 1 CD U CAD I C m I: TV I x10 ) 2x10 2x4 BEARING WALL x W6 x 2'-0" W6 x 6'-0" min. A Legend O ® STRUCTURAL WALL OR POST BELOW �_________; STRUCTURAL WALL OR POST ABOVE NON-STRUCTURAL WALL BELOW Wx SHEARWALL PER t SPAN DIRECTION < T > EXTENT OF JOISTS HEADER/BEAM PER PLAN HANGER �X NO. OF STUDS IN MULTI -STUD COLUMN PER PLAN NOTE 11 XX HOLDOWN PER SCHEDULE 4/S4.2 �J PT PRESSURE TREATED CEDAR GL CEDAR GLULAM MEMBER PER NOTE 14 00 n Roof Framing Plan Scale: 1/4" - 1'-0" IN NZ/7 ENMNEEN 2124 Third Avenue - Suite loo - Seattle, WA 98121 p:2o6.443.6212 ssfengineers.com 934 Broadway - Tacoma, WA 98402 P:253•z84.9470 ssfengineers.com Copyright 2022 Swenson Say Faget - All Rights Reserved DRAWN: SRK DESIGN: RGC CHECKED: RGC APPROVED: RGC REVISIONS: Permit Revision Oct. 24, 2022 2 Permit Corrections, Round 2 Feb. 13, 2023 Roof Revisions Sept. 22, 2023 JURISDICTIONAL APPROVAL STAMP: BLD2022-0439 REVISION Oct 30 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT PROJECT TITLE: ANGLE RESIDENCE 15724 72nd Avenue W. Edmonds, WA 98026 ARCHITECT: Cast Architecture 115-C North 36th Street Seattle, WA 98103 CASTa rc h i tect u re . co m ph 206.256.9886 ISSUE: Permit SHEET TITLE: Roof Framing Plan SCALE: 1 /4" = P-0" U.N.O. DATE: March 29, 2022 PROJECT NO: 00640-2021-01 SHEET NO: S2,a3 A35 PER SHEARWALL (5) 8d INTO EA. A35 PER SHEARWALL SCHEUDLE OUTRIGGER SCHEUDLE 8d @ 6"oc (5) 8d INTO EA. 2x8 OUTRIGGERS @ 24"oc 8d @ Coc OUTRIGGER W/ LB28 HANGER 2x8 BLKG. BTWN. 2x8 BLKG. BTWN. 8d @ 6"oc PROVIDE 2x6 VERT. BLOCK TRUSS BLKG. PER TRUSS OUTRIGGERS W/ 16d @ 2x8 OUTRIGGERS @ 24"oc TRUSSES & OUTRIGGERS W/ 16d @ BELOW OUTRIGGER MANUFACTURER 6"oc TO TOP E W/ LB28 HANGER SHEATHING PER PLAN 6"oc TO TOP E VARIES gL 2x8 OUTRIGGER 16d @ Coc, OUTRIGGER TRUSSES & SHEATHING @ 24"oc TO TOP CHORD PER PLAN FASCIA PER VARIES ARCH. FASCIA PER FASCIA PER I --x X X \ X - NAILING PER ARCH. ARCH. _ SHEARWALL SCHEDULE 77 HEADER (where occurs) �� per arch. per arch. --- NAILING PER 2'-6" Max. SHEARWALL SCHEDULE (2'-0 max.) TRUSS BLOCKING PER 4'-0" min. ;; per arch. SHEARWALL PER PLAN TRUSS MFGR., TRUSS BLKG. � ;' \', (2'-0"max.) 8d @ 6"oc TO BE DESIGNED FOR - - 167 PLF (ASD) TRUSS & SHEATHING 2x BLKG. 2x BLKG. W/ (4) 16d NAILING PER SHEARWALL PER PLAN BEARING WALL PER PLAN (4) 1/4" 0 X 41/2" SDS EA. SCHEDULE �� A35 PER SHEARWALL BEAM @ SIM. BLOCK SCHEDULE _ H2.5 EA. TRUSS SHEARWALL PER PLAN HEADER/BEAM PER PLAN SHEARWALL PER PLAN HEADER/BEAM 2x10 BLK G. ALT. STUD BAYS � TRUSS PER PLAN, TOP /A\ 5 5 PER PLAN Q W/ (3) 16d NAILS EA. END CHORD BEARING 5 2x BLKG. W/ (4) 16d Exterior BearingWall 2 Trusses Parallel to Exterior Wall w/ Flat Outrigger U%3vj 99 �� BEAM PER PLAN 4 A C A35 PER SHEARWALL PANEL EDGE NAILING OVER SCHEDULE ALL HOLDOWN STUDS/POST VERTICAL GRAIN BLKG. HOLDOWN BELOW PER PLAN COLUMN PER PLAN HOLDOWN PER PLAN TO MATCH HOLDOWN (where occurs) REFER STUDS/POST 8d @ 3"oc PANEL EDGE TO HD STRAP SCHEDULE BEARING WALL SHEARWALL PER PLAN — 2x8 W/ (2) 1/4" 0 SDS NAILING FOR ADDL. INFO. (4)8d INTO EACH BLOCK PER PLAN @ 12"oc, STAGGER RIP TO COL. DEPTH to NAILING PER SHEARWALL JOIST DIRECTION AND JOISTS AND SCHEDULE, TYP. SHEATHING PER PLAN SHEATHING / PER PLAN PANEL EDGE NAILING 04 - SINGLE SIDED SHEARWALL 8d @ 4"oc 13/4" LSL RIM JOIST OR PER PLAN BEAM PER PLAN ' PANEL EDGE NAILING -----// DOUBLE SIDED SHEARWALL NAILING PER SHEARWALL / 0 0 COLUMN PER PLAN PER PLAN SCHEDULE / 2x STUD W/ (2) 1/4" 0 x 41/2" / — (2) 16d THRU EA. PANEL EDGE NAILING 2x6 W 2 1 4"0 SDS / () / SDS @ 10"oc STAGGER LEAVE ONE END OF / �i JOIST OR BLOCK @ 12"oc, STAGGER STRAP UNAILED JUST / — WHERE JOISTS ARE ITS SERIES HANGER SHEARWALL PER PLAN PRIOR TO COVERING / PARALLEL, PROVIDE BEAM PER PLAN TJI BLKG. @ 48"oc SHEARWALL PER PLAN o BEAM/HDR. PER PLAN (where occurs) • REFER TO SHEARWALL SCHEDULE FOR ADDITIONAL RIM & SILL 3" PLATE SIZE REQUIREMENTS Shearwall Offset 5 Shearwall Corner Grid C 6 Exterior Floor Framing7 Interior Bearing Wall O g A35 PER SHEARWALL SCHEDULE SHEARWALL PER PLAN — 8d @ 6"oc 16d @ Coc, OUTRIGGER TO TOP CHORD PANEL EDGE NAILING 2x8 OUTRIGGER OVER ALL HOLDOWN @ 24"oc TRUSS & SHEATHING STUDS/POST PER PLAN 8d @ 6"oc JOISTS ANDIf (4)8d INTO EACH BLOCK HANDRAIL PER ARCH. SHEATHING FASCIA PER X X X X � �---- <------ ------ ------ T-----� ---- HANDRAIL PER ARCH. PER PLAN ARCH. BLKG.@ / J 2x8 W / (2) / 4"� SDS NAILING PER SHEARWALL 16d6"oc per arch. XI SCHEDULE 2'-6" ma . BEAM PER PLAN 0 NAILING PER SHEARWALL 2x BLKG. W/ (4) 16d BTWN. BEAM PER PLAN SCHEDULE TRUSSES TOP & BOT. HOLDOWN STRAP (where occurs) 4'-0" min. BEAM PER PLAN t J PER PLAN. REFER TO HD STRAP BEAM PER PLAN z// SCHEDULE FOR ADDL. INFO THA HANGER EA. TRUSS PROVIDE EQUAL NUMBER OF JOISTS & SHEATHING 1/4" 0 x 6" SDS @ 16"oc JOIST PER PLAN W/ SPECIFIED NAILS INTO STUDS PER PLAN ITS SERIES HANGER 7 KERFED END ABOVE & BELOW BEAM i TJI BLKG. @ 24"oc — CJT4Z HANGER SHEARWALL PER PLAN HEADER/BEAM PER PLAN WHERE JOISTS ARE PERPENDICULAR, PROVIDE IUS HANGER @ BM. Loft Framing9 Upturned Floor Beam w/TJI's - Joist Perpendicular 10 � ) Typical Flush Beam Truss Perpendicular to Exterior Wall 12 p p Yp p RUCTLIRAL NEEMNS 2124 Third Avenue - Suite loo - Seattle, WA 98121 p:2o6.443.6212 ssfengineers.com 934 Broadway - Tacoma, WA 98402 p:253•z84.9470 ssfengineers.com Copyright 2022 Swenson Say Faget - All Rights Reserved ru DRAWN: SRK DESIGN: RGC CHECKED: RGC APPROVED: RGC REVISIONS: Permit Revision Oct. 24, 2022 Permit Corrections, 2 Round 2 Feb. 13, 2023 Roof Revisions Sept. 22, 2023 JURISDICTIONAL APPROVAL STAMP: 1 1.11111111 119LO, REVISION Oct 30 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT PROJECT TITLE: ANGLE RESIDENCE 15724 72nd Avenue W. Edmonds, WA 98026 ARCHITECT: Cast Architecture 115-C North 36th Street Seattle, WA 98103 CASTa rc h i tect u re . co m ph 206.256.9886 ISSUE: Permit S' TITLE: Typical Wood Framing Details SCALE: 3/4" = V-0" U.N.O. DATE: March 29, 2022 PROJECT NO: 00640-2021-01 SHEET NO: S4,01