REVIEWED ENG RESUB4 BLD2022-0439+SEWAGE PUMP INFO+6.5.2023_11.21.31_AM+3587492RESUB Jun 05 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT May 31, 2023 City of Edmonds, Development Review — Public Works ATTN: Public Works Director 7110 210th St SW Edmonds, WA, 98026 Re: MEADOWVIEW LOT 4 — ANGLE RESIDENCE E/ONE GRINDER PUMP CALCUATIONS LDC# 21-164 EXECUTIVE SUMMARY Surveying LDC1 Engineering Planning BLD2022-0439 REVIEWED BY SENIOR UTILITIES ENGINEER MIKE DELILLA The following summary and design calculations are in accordance with the City of Edmonds design standards for a residential sewage pump for the Meadowview Estates, Lot 4 project. The project proposes to build a single-family home and will necessitate the installation of a residential sewage pump and associated force main to sewer out the residence. The pump unit will be an E/One DH151 simplex grinder pump which has been designed in accordance with the City of Edmonds standards. Please see Appendix A for all calculations for head pressure and buoyancy. EXISTING CONDITIONS Lot 4 of Meadowview Estates is approximately 24.36 vertical feet below the connection point to the gravity system installed near the driveway along 72nd Ave W. The site contains moderate slopes with steep slopes located along the westerly property line. A. PUMP SELECTION A E/One DH151 grinder pump has been specified for the proposed residence. Per the manufacturer, this pump is rated for flows up to 1,500 gallons per day (GPD) with a discharge capacity of 15 gallons per minute at 0 pgis. For a single-family residence, E/One assumes a daily flow of 200-300 GPD for a single-family home and for these calculations, a value of 300 GPD was used for sizing. B. HEAD PRESSURE CALCULATIONS Total Dynamic Head (TDH) has been calculated based upon actual site conditions and takes into account the construction of 1.5" force main pipe on the lot. Minor loss calculations are summarized in Appendix A. A summary of the TDH calculation is below: Service ABOVE t it e Standard ph: 425.806.1869 • fx: 425.482.2893 • www.LDCcorp.com Meadowview Lot 4- Angle Residence May 31, 2023 Page 2 of 10 Total Dvnamic Head Calculations: Elevation head = 24.36 ft Force main pipe losses = 2.77 ft (LF 1.5" PVC, C = 150) Force main minor losses = 0.21 ft* TDH: = 27.34 ft *A summary of pipe bend and valve counts can be in Appendix A (Page A-4) C. BOUYANCY CALCULATIONS Station Weight has been calculated from standard specifications given by E/One for the DH151 unit and associated rails, fixtures, piping and pump. Full calculations for the following can be found in Appendix A. A summary of these calculations can be found below: Basin Dimensions/Data Allowable Bearing Pressure (Soil) = 2500 lb/ft3* Basin/Unit Volume = 52.84 ft3 Displaced Weight of Water = 3956.5 lbs Safety Factor = 20%** Assumed Station Weight = 900 lbs *As given by Geotechnical Report associated with Meadowview Estates Plat **As Required by the City of Edmonds Ballast Reauired Assumed Unit Weight of Concrete = 145 lb/ft3 Required Concrete/Ballast Weight = 3956.5 lbs Required Concrete Volume = 21.08 ft3 Provided Concrete Volume = 21.68 ft3 Concrete Ring Width = 1.00 ft Concrete Ring Height = 2.30 ft n- LU w Service ABOVE the Standard Meadowview Lot 4- Angle Residence May 31, 2023 Page 3 of 10 Please see the calculations and materials/equipment speciation's and designs included in Appendix A and within the plans comprise the details and requirements from City of Edmonds. Should you require additional information, please contact us. Sincerely, LDC, Inc. 1. Sang Park, PE Project Manager v v W J V V Q v Service \LOVE the Standard Meadowview Lot 4- Angle Residence May 31, 2023 Page 4 of 10 Appendix A Calculations CL LU w Service ABOVE the Standard Meadowview Lot 4- Angle Residence May 31, 2023 Page 5 of 10 Total Dynamic Head Calculations Total Dynamic Head Calculations: Discharge Pipe: 5 Linear Feet roughness, c = 150 Material: PVC diameter, d = 4 inches flow, q (gpm) = 15 (pumping capacity) f= 0.2083 X (100/c)^1.85 X q ^1.85 f= 0.017 feet/100 ft of pipe Velocity, v = 0.4 fps Velocity out of range! Total Friction Loss = 0.00 feet (3 to 6 fps is an acceptable range) Minor Losses in Discharge Pipe: HL= KxV^2 2g Number of 90 deg. bends = 0 Number of 45 deg. bends = 0 Number of 22.5 deg. bends = 0 Number of Swing CVs = 0 Number of Gate Valves = 0 where ; K= 0.9 for 90 deg. bends K= 0.5 for 45 deg. bends K= 0.3 for 22.5 deg. bends K= 2.5 for Swing Check Valve, open full K= 0.2 for Gate Valve, open full Total Minor Losses = 0.0 feet Force Main: 135 Linear Feet roughness, c = 150 Material: PVC diameter, d = 1.5 inches flow, q (gpm) = 15 (pumping capacity) f= 0.2083 X (100/c)^1.85 X q ^1.85 dA4.8655 f= 2.05 feet/100 ft of pipe Velocity, v = 2.7 fps Okay. Total Friction Loss = 2.8 feet (3.0 to 6 fps is an acceptable range) Minor Losses in Force Main: HL = K x V^2 where ; K= 0.9 for 90 deg. bends 2g K= 0.5 for 45 deg. bends K= 0.3 for 22.5 deg. bends Number of 90 deg. bends = 0 K= 2.5 for Swing Check Valve, open full Number of 45 deg. bends = 0 K= 0.2 for Gate Valve, open full Number of 22.5 deg. bends = 6 Number of Swing CVs = 0 See Minor Losses Tab for Data Entry Number of Gate Valves = 0 Total Minor Losses = 0.2 feet a Service ABOVE the Standard Meadowview Lot 4- Angle Residence May 31, 2023 Page 6 of 10 SUMMARY OF HEAD LOSSES: Force Main Friction Loss = 2.77 Force Main Minor Losses = 0.21 Discharge Pipe Friction Loss = 0.00 Discharge Pipe Minor Losses = 0.00 Elevation Head = 24.36 feet Total Dynamic Head, TDH 1 27.34 Ifeet Service ABOVE the Standard Meadowview Lot 4- Angle Residence May 31, 2023 Page 7 of 10 Buoyancy Calculations Hydrostatic Uplift - Ballast Estimate There is no evidence from geotechnical investigation, of any possibility that ground water could interact with any portion of the proposed residential lift stations specified for this project. Min Soil Allowable Soil Bearing Pressure /Design Soil Bearing Pressure = Min Req. Soil Bearing = 687.05 Ib/ft2 Volume of proposed lift Reservoir= Vol = Unit Diam= Unit Circumferance = Unit Cross Sectional Area= Area = Unit Depth = 20% FOS Displaced Water Mass = Weight of Proposed Reservoir and system = 145 Unit Mass Deficit = 52.84 ft3 3 ft 9.42 ft 7.07 ft2 7.475 ft 2500 I b/ft2 Soil Bearing is Sufficient 686.7129 lb 9576.826 lb 3956.5 Lb& (with factor of safety) 900.0 Ibs 3056.5 Ibs o b/ft3 Req. Concrete Volume = 21.08 tt Proposed Concrete Base Ring Width = 1.00 ft (Min) Concrete Ring around Proposed Concrete Base Ring Height = 2.30 ft Base of Reservoir OR Balast Slab to which Reservoir is bolted = 3.00 ft Conc. Slab Under Unit Proposed Concrete Volume = 21.68 ft3 RING OR Proposed Concrete Volume = 21.21 ft3 BASE Proposed Unit Installation Must provide total Installed Mass of: 1 3956.48 Ilbs at minimum or resistance for same force by other method. a Service ABOVE the Standard Meadowview Lot 4- Angle Residence May 31, 2023 Page 8 of 10 Performance Curve PRESSURE SYSTEM DESIGN PRE_SSLRE 611k 01 , ESD 08-0022 REV. Z 6/08 LU w Service ABOVE the Standard Meadowview Lot 4- Angle Residence May 31, 2023 Page 9 of 10 Appendix 6 Details CL LU w Service ABOVE the Standard Meadowview Lot 4- Angle Residence May 31, 2023 Page 10 of 10 E/One DH151 Detail w/ Elevations OPTIONS :Ox DH 151 LEVEL CONT OLS) FIELD JOINT REQUIRED DR 1 S 1 LE,`�NT aLs, FOR MOOELS OH151-129 / DRI5I-129 t OHISI-I60 / DRISI-160 GASKETED LID. HOPE STRAIN RELIEF CORD CONNECTOR POWR/ALARM CABLE 6 CONDUCTOR W/GND` E/CIPE EQUALIZER FINISHED GROUND + - 232.23 DUAL WALL. CORRVOATED HOPE ACCESSWAY OUICK pI$CONNECT ASSY. INTERNAL WELL VENT 2.0' DIAMETER (30, S.S.) S.S. CAST BALL VALVE DISCHARGE INLET GROMMET EL= 227 00 1 1/4' FPT TO ACCEPT 4.50' 0. . PVC PPE [STANDARB . T DUST COVER SUPPL D FOR SHPMENT (NOT SUTABLE FOR BURIAL EL- 226.54 1 1/4' DISCHARGE LINE (304 SS.) 43.9 In 1115 mm ALARM EL= 225.76 CK VALVE NORYL) 38.4 in 975 mm 975 VALVE I ON EL= 225.09 737� 6NNORYL I mm OFF EL= 224.76 116 gal 439 L 21 In 17 In 534 mm 432 mm 84 gal 318 L .,\ 50 od l E L = 223.34 POLYETHYLENE TANK 1/2' NOMINAL WALL THICKNESS 0 38.8 in 150 GALLON CAPACITY 984 m— SEU•Po51TIVE CISPI-ACEMENT TYPE PUMP fMRFCTI Y r"VFN BY A 1 HP MOTOR CIR CONCRETE BALLAST MAY BE REQUIRED SEE INSTALLATION INSTRUCTIONS FOR DETAILS NOTE: DIMENSIONS ARE FOR REFERENCE ONL a Service ABOVE the Standard