Loading...
SEE REV1 APPROVED BLD2022-1035-Structural PlansSHEARWALL SCHEDULE SWEXP Notes apply as called out in table below. 1 Anchor bolts embedded at least 7", or expansion anchors embedded at least 4". See detail SWR 2 *MASAP can be installed instead of sill bolts with washers. When replacing 1/2"0 sill bolts use 7-10dx1l/2" nails (minimum nailing) and when replacing 5/8"0 sill bolts use 9-10dx11/2" nails (maximum nailing). 3 See detail SWF. Connections vary depending on condition. 3a Substitute 16d toe nails @ 8"oc for #A35. 4 See detail SWR. For gable -end roof connections see detail SWF. 5 See detail SWB. 6 Abutting panel edges require a 2-2x (lamination connection same as WALL BASE PLATE), 3x, or greater stud. 7 See detail DSW. 8 The plate washer shall extend to within 1/2" of the edge of the bottom plate that receives the sheathing or rim. At double -sided shearwalls, stagger on both plate edges. SHEAR FLOW CONNECTIONS / SPACING S SILL -TO - FLOOR -TO - ROOF -TO - WALL BASE PLATE CALL FOUNDATION 1, 2 SILL &WALL WALL 4 5 OUT 5/8"0 @ 60"oc or *A35 @ #H1 @ 16d @ 10"oc A 1/2"0 @ 60"oc 48"oc 3a 24"oc 4 5/8"0 @ 60"oc or *A35 @ *LS50 @ 16d @ 6"oc 1/2"0 @ 40"oc 24"oc 36"oc 4 5/8"0 @ 40"oc or *A35 @ *LS50 @ 16d @ 4"oc 7/2"0 @ 24"oc 16"oc 24"oc 4 5/8"0 @ 24"oc or *A35 @ *LS50 @ 16d @ 2"oc D 1 /z0@16oc 8 " " 12"oc 12"oc 4 5/8"0 @ 12"oc or *A35 @ *L550 @ 2-16d @ 2"oc to 4x C G 1/2"0 @ 8"oc 8 6"oc 8"oc 4 rim/blkg 5/8"0 @ 10"oc or *HGA10KT N/A (2) 1/4" x 5" #SDS C 1/2"0 @ 6"oc 8 @ 6"oc @ 4"cc to 4x rim r HOLDOWN SCHEDULE N WALL SHEATHING CALL OUT SHEATHING THICKNESS EDGE NAILS G 7/16" 8d @ 6"oc 4 7/16" 8d @ 4"oc 3 7/16" 6 8d @ 3"oc 2 7/16" 6 8d @ 2"oc 33 7/16" both sides 6, 7 8d @ 3"oc 19 7 19/32" both sides 6, 7 10d @ 2"oc 1 Deepen the foundation as needed to provide the required holdown embedment into the foundation wall. See Detail MHE 2 Fasten to the end framing members of the shearwall, u.n.o. 3 FOUNDATION ANCHOR may be extended with threaded rod and coupler as required. 4 Provide the minimum embedment and edge distances specified by the manufacturer. 5 Attach to (2) 2x studs minimum (lamination connection same as WALL BASE PLATE; stagger nails), u.n.o. 6 See detail HDNfor installation. HOLDOWN / STRAP FASTENERS 5 FOUNDATION COMMENTS 1, 2, 4, 6 ANCHOR 1, 3, 4, 6 *STHD14/14RJ 30-16d sinker N/A #HDU11-SDS2.5 30 - #SDS1/4x2l/2 1"$T.R. 6x6 Min Post, See detail RFyA #CS16 22-10d N/A 13" Min End Length, See detail CSH (2) MST27 30-16d sinker N/A equal number of fasteners to both connected elements. 6x6 Min Post *MSTC66 68-16d sinker N/A equal number of nails to both connected elements (2) :#MST60 46-16d sinker N/A equal number of fasteners to both connected elements. 6x6 Min Post CITY OF EDMONDS BUILDING DIVISION GENERAL STRUCTURAL NOTES CODE All conditions, materials and construction shall conform to the code specified in the DESIGN CRITERIA, or other codes required by the governing jurisdiction. PROTECTION Through maintenance and current best practices, provide a building envelope that will preserve the integrity of the structure throughout it's lifetime. INSPECTIONS Notify Building Department for inspections required by local jurisdiction. SOILS Bearing capacity of soil shall be per DESIGN CRITERIA or greater. Footing shall bear on solid undisturbed level soil devoid of any organic material and below indicated frost line. COMPACTED FILL shall consist of predominately Well -Graded, granular soil, free of organic material and debris. Fill should be placed in maximum 8" loose lifts and compacted to a minimum of 95 percent of the maximum density at optimum moisture content determined by ASTM D-1557 test procedures. BACKFILL shall be free draining and without organic material and debris from one of the following soil classes SM-SC, SM, SP, SW, GC, GM, GP, and GW. FOUNDATIONS AND RETAINING WALLS Extend footings to undisturbed bearing soil. Do not backfill until all slabs and/or horizontal diaphragms are constructed, otherwise provide temporary bracing to resist movement. There shall be no machine compaction on the retaining side of the structure for a distance equivalent to 2/3rds the wall height. SILL PLATES Use pressure treated 2x plates u.n.o. Embed anchor bolts at least 7" (expansion anchors 4"). Use 3"x3"x0.229" washers. There shall be a minimum of two bolts per piece spaced not more than 6 feet apart, with one bolt located not more than 12" or less than 4" from each end of each piece. CONCRETE Fc = 3000 psi minimum for environmental exposure (2500 psi used in structural design, or unless greater psi indicated on the plans). 5 1/2 sacks of cement per cubic yard of concrete and a maximum of 6 gallons of water per 94 lb sack of cement. Maximum slump is 4". Segregation of materials shall be prevented through proper handling and placement. REINFORCING STEEL #4 bars and larger shall be Grade 60 deformed bars, and #3 bars shall be Grade 40 (u.n.o.), in accordance with ASTM A-615. Lap splices 32 bar diameters u.n.o. Welded wire fabric shall conform to ASTM A-185 and shall be 6x6 - W1.4xW1.4. Lap one full mesh at splices. See applicable detail(s): BD SH CLEAR COVER 3" clr when cast against Earth and 2" clr in all other locations, u.n.o. See applicable detail(s): RI FOOTING DRAINAGE Footing drainage per Building Code section 1805.4.2 & Residential Code section R405.1. WOOD FRAMING in contact with concrete or masonry, or exposed to weather, shall be pressure treated. Numbers in parenthesis, IE (1-1), refer to corresponding engineering calculations. CONNECTORS AND FASTENERS Fasteners, including nuts and washers, and connectors in contact with pressure treated wood shall be hot -dipped zinc -coated galvanized. EXCEPTION: Plain carbon steel fasteners, including nuts and washers, in SBX/DOT and zinc borate preservative treated wood in an interior, dry environment shall be permitted. SOLID SAWN LUMBER shall meet the following minimum grades (u.n.o.) conforming to "WWPA GRADING RULES FOR WESTERN LUMBER", latest edition: BEAMS, POSTS, RA FTERS, JOIST 6X and wider DF#1 4X DF#2 2x 10 and greater DF#2 2x 8 and smaller HF#2 IAIA, 1 1 C 'l lr%C 2x HF#2 ENGDNEERED WOOD shall meet the following minimum properties: Callout E x 106 (psi) Fb(psi) Fc par (psi) Fc perp (psi) Fv(psi) GLB 1.8E 2400 1650 650 240 All cantilevered and multi -span glue -laminated beams (GLB) shall be V8 unless noted otherwise, additionally cantilevered beams shall have zero camber. 24F-V4 shall be cambered with a 3500' radius u.n.o. LVL 2.0E 3100 3000 750 285 LSL 1.55E 1900 2050 900 310 PSL 2.2E 2900 2900 625 290 Engineered wood products shall be protected from moisture to preserve their structural integrity. Provide temporary bracing to avoid permanent deflections resulting from drying under construction dead loads. I -JOISTS Connect I -joist to plate using one 10d (0.131" x 3") nail on each side of bottom flange; drive nails at an agle at least 1 1/2" from end. Connect 1 1/4" LSL rim to I -joists with one 10d (0.131" x 3") nail into top and bottom flange. Full -depth blocking between joists over shearwalls shall be 1 1/4" min LSL. TRUSSES Manufactured trusses are a deferred submittal item designed per CODE section 2303.4 and shall be designed for all loads and load combinations per the CODE All connections per manufacturer, u.n.o. If truss layout is changed by manufacturer, please notify this office. For trusses over walls, if header is not specified over openings, design truss to span over it. See applicable detail(s): GEB WALL FRAMING & BEARING Walls shall be 2x studs at 16"oc max with double 2x top plate, and 2x base plate (exterior walls shall be 2x6 u.n.o. & interior walls shall be 2x4 u.n.o.). Block all supports solid to the foundation. See applicable detail(s): BHS TPS BEAM PENETRATIONS Allowable beam penetrations shall be made in the middle third of the span and the middle third of the depth. Contact this office for any penetration outside the allowable area. See applicable detail(s): BP POF apROVED PLAN GENERAL STRUCTURAL NOTES continued WOOD STRUCTURAL PANELS shall meet the performance standards of the "APA" DOC PS1 and PS2 for their intended application (group 5 species not allowed). SHEARWALLS are indicated on the plans with a bold dashed line and labeled SW. The following letter designation refers to the Shearwall Schedule's SHEAR FLOW CONNECTIONS / SPACING table, and the number designation refers to the WALL SHEATHING table. Multiple combinations of letter and number designations may be present. Wall Line numbers, shown inside triangles, refer to corresponding engineering calculations. Attach rated sheathing (indicated below) to 2x min STUDS spaced no more than 16"oc, u.n.o. See Shearwall Schedule for minimum thickness and fasteners (thickness at point of fastened edges governs shear values). All panel edges shall be blocked. Nail intermediate supports @ 12"oc. Do not penetrate nails past flush. Install squash blocks under the ends of all shearwalls where the framing below does not provide full bearing. Construct cripple walls same as the shearwall above, and gable -ends same as the shearwall below. Rated sheathing: 7/16" OSB rated with a 24/16 span rating. 1/2" CD with a 32/16 span rating. See applicable detail(s): SWE ROOF DIAPHRAGM Install either OSB or CD sheathing: 7/16" OSB rated sheathing with a 24/16 span rating; panel clips required when spacing is greater than 20" oc. 1/2" CD rated sheathing with a 32/16 span rating. Use 8' x 4' panels with long dimension perpendicular across supporting framing. Stagger panel rows half the long dimension. Nail all boundaries and supported edges with 8d @ 6"oc and interior supports with 8d @ 12"oc, blocking not required u.n.o. ROOF -TOP DECK DIAPHRAGM Install minimum 23/32" rated Sturd-I-Floor T&G with a 24oc span rating Use 8' x 4' panels with long dimension perpendicular across supporting framing. Stagger panel rows half the long dimension. Glue and nail all boundaries and supported edges with 10d @ 6"oc and interior supports with 10d @ 12" oc, blocking not required u.n.o. FLOOR DIAPHRAGM Install minimum 23/32" rated Sturd-I-Floor T&G with a 24oc span rating. Use 8' x 4' panels with long dimension perpendicular across supporting framing. Stagger panel rows half the long dimension. Glue and nail all boundaries and supported edges with 10d @ 6"oc and interior supports with 10d @ 12" oc, blocking not required u.n.o. GARAGE FLOOR DIAPHRAGM Install minimum 1 1/8" rated Sturd-I-Floor T&G with a 16oc panel index Use 8' x 4' panels with long dimension perpendicular across supporting framing. Stagger panel rows half the long dimension. Glue and nail all boundaries and supported edges with 10d @ 6"oc and interior Top with a min of 3" concrete reinforced with 6" x 6" 10/10 wire mesh. COLLECTORS Diaphragms shall be nailed continuously to rims, drag struts, drag trusses and other collector elements at boundary spacing, u.n.o. See applicable detail(s): DTC CS CONNECTIONS and fasteners shall be per CODE Table 2304.10.1 u.n.o. The symbol, "#", indicates a hardware connector from the most current Simpson Strong -Tie Catalog. Hardware with equivilent or greater capacities from other manufacturers may be substituted, example you can use USP's Dual Specification Chart to make an equivilent or greater capacity selection. Install per the manufacturer instructions. Fasteners and hardware in contact with pressure treated wood shall be hot -dipped zinc -coated galvanized. NAILS All nails shall be "Standard Common" size per the latest edition of the National Design Specification for Wood Construction (NDS) u.n.o. HOLDOWNS See the HOLDOWN SCHEDULE. See applicable detail(s): HDN HOC POST CAPS Provide a post cap on isolated columns that most nearly matches the actual member size(s) U.N.O. Each connection shall have a minimum of (3)10d to the post and (3)10d to the beam. HANGERS Model numbers will be specified on the plans for conditions that require more than minimum capacity, otherwise see CONNECTIONS. When a hanger is not specified on the plans, use any size specific model number that fits that member. Always use MAX NAILING. Hanger to match member size. Notching or shimming of beam not allowed unless specified. JOBSITE SAFETY Sound Structural Solutions Inc has not been retained or compensated to provide design and/or construction review services related to the contractor's safety precautions or to means, methods, techniques, sequences or procedures for the contractor to perform their work. The undertaking of periodic site visits by the ENGINEER shall not be construed as supervision of actual construction and not make him responsible for providing a safe place for the performance of work by the contractor, subcontractors, suppliers or their employees, or for access, visits, use work, travel, or occupancy by any person. OWNERSHIP OF DOCUMENTS These drawings and calculations are the intellectual property of Sound Structural Solutions Inc. These drawings may not be used in whole or in part by any person without permission of Sound Structural Solutions Inc. MISCELLANEOUS The contractor shall verify dimensions and conditions at job site. The contractor shall provide temporary bracing as required until all permanent connections and stiffenings have been installed. Do not scale drawings. Pre -fabricated items to be handled and installed per manufacturer's recommendations. PLAN INSTRUCTIONS READ THIS FIRST These plans are organized so that more detailed or specific information is found in the same way by following the direction shown below: GENERAL STRUCTURAL NOTES SCHEDULES, DETAILS and PLANS will often refer to GENERAL STRUCTURAL NOTES for more specific information. SCHEDULES DETAILS and PLANS will often refer to GENERAL STRUCTURAL NOTES and SCHEDULES for more specific information. DETAILS PLANS will often refer to GENERAL STRUCTURAL NOTES, SCHEDULES and DETAILS for more specific information. PLANS See the SYMBOL LEGEND as well as ABREV14TIONS AND ACRONYMS for other additional information used on the PLANS. The term, TYPICAL (or TYP), used with a detail callout or plan note, indicates that the information specified shall apply in all similar conditions. IF YOU HA VEANY QUESTIONS OR CONCERNS CONTA CT US IMMEDIA TEL Y! We can be reached immediately by phone: (425) 778-1023 For less pressing questions, email us: inbox@ssseng.com Please help us get to your plans by having this job number handy: s2202002 ABBREVIATIONS AND ACRONYMS ABV ABOVE E.S. EACH SIDE O.C. ON CENTER A.B. ANCHOR BOLT E.W. EACH WAY P.T. PRESSURE TREATED BLW BELOW EA EACH REINF REINFORCEMENT BLK BLOCK E.N. EDGE NAILING REQD REQUIRED BLKG BLOCKING EMBED EMBEDMENT SCHED SCHEDULE B.N. BOUNDARY NAILING EXIST EXISTING SIM SIMILAR BTM BOTTOM FDN FOUNDATION STD STANDARD BRG BEARING FLR FLOOR STRUCT STRUCTURAL BTWN BETWEEN FRMG FRAMING SW SHEARWALL CLR CLEAR FTG FOOTING THRU THROUGH CLTR COLLECTOR G.T. GIRDER TRUSS T.R. THREADED ROD CONIC CONCRETE GR GRADE TYP TYPICAL CONN CONNECTION HORIZ HORIZONTAL U.N.O. UNLESS NOTED CONT CONTINUOUS MAX MAXIMUM OTHERWISE CTR CENTER MFG MANUFACTURED VERT VERTICAL DBL DOUBLE MIN MINIMUM w/ WITH DET DETAIL o/ OVER w/o WITHOUT E. E. EACH END oc ON CENTER W.W.F. WELDED WIRE FABRIC DESIGN CRITERIA Governing Code 18 IBC Risk Category II Wind Design Data Basic Wind Speed (3 sec gust) mph 98 Surface Roughness B Wind Exposure Category C Earthquake Design Data Seismic Importance Factor, 1, 1.00 Site Classification D Short Period Acceleration, S, 1.296 1-Second Acceleration, S1 0.458 Seismic Design Category D Spectral Response Coefficient, Sps 0.864 Spectral Response Coefficient, Spi 0.562 Gravity Load Data Internal Pressure Coefficient +/- 0.18 Topographic Factor, Krt 2.23 Ground Elevation Factor, Ke 0.99 Seismic Force Resisting System ITable 12.2-1: A-15 2016 Equiv. Lateral Force Procedure Response Modification Factor, R 6.5 Transverse 6.5 Longitudinal Seismic Response Coefficient, C, 0.133 Transverse 0.133 Longitudinal Seismic Base Shear, V 29350 Ibs loads are psf Dead Live Snow Rafters' *Solar-Ready3 20 0 25 Trusses (pitched) *Pitches:5 8:12 •Solar-Ready3 Pitches < 8:12 Top Chord 15 0 25 Bottom Chord 5 0 0 Roors: loads are psf Dead Live Snow Joists 12 40 0 Joists (GARAGE)s 60 40 0 Decks: loads are psf Dead Live Snow Joists 60 60 25 Notes apply as called out in table above. 1 Rafters of sawn lumber or wood I -joists. 2 Roof has direct access and is intended to be used by occupants as living space. 3 Dead load includes 5psf for photovoltaic panels. 4 Slope top chords to drain; see architectural plans. 5 Joists of sawn lumber or wood I -joists. Soil Data Allowable Soil Bearing 12000 psf Passive Earth Pressure 1275 *pcf Active Soil Pressure 1 35 pcf Coefficient of Friction 10.40 At -Rest Soil Pressure 1 55 pcf Unit Weight of Soil 1 125 pcf Company: Cobalt Geosciences Report #: Date: 9/17/20 *Includes F.S. = 1.5 per Geotech Report RECEIVED Sep 06 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SSS Number: s2202002 Project Name: 191xx 94th Ave W Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M N (V O N O 00 i--1 J ^ O LU Ln [V J LU z E O ~ V V H ICU:: C c~ " can 07 p z w C/) LCO V p1 C N V) O -a 4r i This space reserved for governing jurisdiction stamps ORIGIN DATE; 7/25/2022 REVISED; ---silo - BOUNDARY NAILS SHEATHING PER PER NOTES NOTES BOUNDARY NAILS ROOF DIAPHRAGM 300 MIN 2x FLAT BLK w/ DBL ROW OF 20 NAILER CITY OF EDMONDS BOUNDARY NAILS —i EXPOSED 0.25d MFG TRUSS BUILDING DIVISION TRUSS RAFTER MAX NOTCH 2x4 BRACE @ 48"oc w/ #SDWS 0,152" x 6" #A35 AT BTM TO EACH RAFTER SHEARWALL GEB GABLE -END TRUSS BRACE RTW RAFTER TO BEARING WALL APPROVED PLAN BOUNDARY NAIL ALONG BOUNDARY NAIL ALONG N.T.S. GEBA N.T.S. CTPF LENGTH OF COLLECTOR LENGTH OF COLLECTOR FRMG COLLECTOR STRAP DIAPHRAGM PER STRUCT NOTES SSS Number: s2202002 INTERMEDIATE FRAMING ABUTTING PANEL EDGES EXTENT OF EXTENT OF SHEARWALL CRIPPLE STUD DOUBLE TOP PLATE SHEARWALL TPS SWF SWR Project Name: 191xx 94th Ave W FTC DIAPHRAGM TO COLLECTOR SB STRAP TO BEAM N.T.s. DTCA N.T.S. SBAB Owner: HEADER HEADER LQH, Inc PROVIDE (1) STUD PER STRAP, TYP (8)16d EVENLY SPACED, 16d @ 16" oc WINDOW OPENING Project Location: TYP U.N,O, TYP FACE NAILS BEAM % SPECIFIED NAILS PER 191XX 94th Ave W, EACH END LENGTH, TYP DISCONTINUOUS #CS16 w/, END DBL TOP PLATE (13) 8d NAILS EA END LENGTH DIAPHRAGM PER DOOR Edmonds, WA + _ _ STRUCT NOTES ENI POST END MIN 2x RIM/BLKG LENGTH DIAPHRAGM PER KING STUD Design Professional: STRUCT NOTES TRIMMER STUD LQH, Inc I I #CS16 STRAP(s) 4'-0" MIN I END SPLICE LENGTH END pq I N A TOP PLATE SPLICE DISCONTINUOUS DBL TOP PLATE LENGTH SWB SWF #CS16 STRAP(s) BEAM, 3%" 4" x 4" IS THE MAXIMUM PENETRATION CRIPPLE STUD BASE PLATE WRAP STRAP WIDE MIN. OR HOLE THAT CAN BE ADDED TO A SHEARWALL UNDER BEAM M N N TPS DOUBLE TOP PLATE SPLICE STRAP BETWEEN FLOOR STRAP TO BEAM BELOW FSWE�SHEARWALL ELEVATION o N o 00 N.T.s. TPSA CSH COILED STRAP HOLDOWN N.T.S. DRDDD N.T.S. O w N DBL 2x STUD ROOF DIAPHRAGM w J PER STRUCT NOTES EDGE NAILING SW SHEATHING #LS50 @SHEARWALLS 1 If you can't lap the sheathing then you Z O E EDGE NAILS R SCHED DIAPHRAGM PER must install the A35's as shown (Not Optional) = H U �55 STRUCT NOTES DC SOLID BLKG DIAPHRAGM PER �— HOLDOWN RIP TO FIT STRUCT NOTES PROVIDE c/� Ln EMBEDDED BOUNDARY BLKG @ 48"oc C Z cn STRAP NAILS DIAPHRAGM RAFTER #A35 PER T&G ROOF DECKING #H2.5A MIN RAFTER SW SCHED GABLE RAFTER STRAP SHOWN @ ALL ROOF w 3: MEMBERS @ INTERMEDIATE & 16" MAX AROUND CORNER MEMBERS @ ALL MIN U.N.O. @ @ALL ROOF BLKG #H2.5 @ALL EDGE NAILS END BEARING SUPPORTS, TYP p O STUDS PER � SHEARWALLS MEMBERS EDGE NAILS # A35 PER ROOF MEMBERS HOEDOWN SCHED SW SHEATHING 3y" MIN WALL SW SCHED cc SHEARWALLS p1 SHEARWALL w TRUSS BEARING SHEARWALL w/ RAFTER BEARING SHEARWALL w/ RAFTER PARALLEL 0) EDGE NAILING d / Ln x x x x x____ -- 2x STUD 0.25d SWR SHEARWALL ROOF CONNECTIONS x MAX 4Y Y16" NOTCH N.T.S. � RAFTER PER PLAN O NOTE; \_ BEAM SWRA HOEDOWN SEE DETAIL SWR FOR SHEAR CONNECTIONS 2xSTUD ANCHOR RCB SHEARWALL ROOF CONNECTIONS AT BEAM DIAPHRAGM PER NAILS PER N FL DBD DECK BOARD DIAPHRAGM STRUCT NOTES SW SCHED WALL BASE N.T.S. WALL BASE EDGE NAILS PLATE CONN N.T.S. HOC HOEDOWN AT CORNER FLRRIM/BLKG PLATE CONN (SW ABOVE) (SW ABOVE) N.T.S. HOCA (OR ROOF GABLE) SOLID BLKG OR DIAPHRAGM PER COLLECTOR STRUCT NOTES RIM/BLKG EDGE NAILS *�t BEAM & #CS16 PROVIDE #A35 PER EDGE NAIL '1 w/ (16)10d REQUIRED STUDS PROVIDE BLKG @ 48"oc SW SCHED (SW BELOW) BLKG @48" oc AS SHOWN BEAM 2x4 WALL 2x6 WALL MSTC MST w/ JOIST -WALL DOUBLE -SIDED SHEARWALLS PARALLEL w/ JOIST -WALL 4x & 2-2x (SAWN) STRAP STRAP PARALLELspace 3%x (GLB) (2) 2x4 (2) 2x6 — — INTERIOR SHEARWALLS, & governing jurisdiction stamps 3%x (MANF) I I EXTERIOR SHEARWALLS EXT SHEARWALLS @ CANTILEVERS SHEARWALL TO FLOOR TO SHEARWALL 6x&32x(SAWN) - 5%x (GLB) (3) 2x4 (3) 2x6 4x MIN SWF SHEARWALL FLOOR CONNECTIONS 5%x (MANF) STRAP MAY BE WALL N.T.S. SWFA 8x (SAWN) LOCATED 6%x (GLB) (4) 2x4 (4) 2x6 ON INSIDE REQD 7x (MANF) MSTC STRAP -(A) MST STRAP- A SHEATHING PER STUDS SCHED GIRDER TRUSS j (3) 2x4 (3) 2x6 WALL BASE WALL REQUIRED TRIMMERS PLATE CONN I WALL DIAPHRAGM PER 3 (3)2x STUDS U.N.0, (r" #HDU11 SHEATHING PER ANCH PER PER SW SCHED STRUCT NOTES KING HEADER 2x4 WALL 2x6 WALL I SCHED SW SCHED STUD HEADER 4x & 2 2x (SAWN) 21 3T2" RIM/BLKG ANCH PER 3yx (GLB) 2x4 2x6 6x6 i 2x SILL U,N.O. SW SCHED 3%x (MANF) PER SW SCHED EDGE NAILS 2x SILL U.N.O. ORIGIN DATE; 7/25/2022 U.N.O.s�� ' RFA WALL FRMG 6x & 3-2x (SAWN) STHD14 1s REQD 5%x (GLB) ---- (2) 2x6 FDN FDN PER SW SCHED TRIMMERS 5%x (MANF) REVISED; NOTE: BEAR BEAMS ON THE FULL WIDTH AND BREADTH OF THE MINIMUM STHD14- A HDU11- B PLAN VIEW SHEATHING PER RECEIVED o SUPPORTS PER TABLES ABOVE UNLESS NOTED OTHERWISE ON THE PLANS SCHED SHEARWALLS TO FOUNDATION SHEARWALLS TO FLOOR TO FOUNDATION Sep 06 2022 0 fV CITY OF EDMONDS N DEVELOPMENT SERVICES NI BHS BEAM & HEADER SUPPORTS HDN HOLDOWNS DSW DBL SIDED SW AT ADJOINING WALLS SWB SHEARWALL BASE PLATE & FOUNDATION CONNECTIONS DEPARTMENTco L—iN.T.S. N.T.S. HDNA N.T.S. DSWA N.T.S. SWBA �I 0 ('V f'V CITY OF EDMONDS BUILDING DIVISION APPROVED PLAN GARAGE FLOOR DIAPHRAGM SHEATHING CONCRETE SLAB SHEAR WALL DIAPHRAGM BOUNDARY NAILS FLOOR DIAPHRAGM FLOOR 2X4 MIN FRAMING NAILER w/ 0.148 x 3" @ 8"oc GARAGE FRAMING SHEAR TRANSFER AT GARAGE N.T.S. TSFA #LSTA24 w/ MIN (9) -10d x 1 %" FASTENERS PER MEMBER DIAPHRAGM U.N.O. COLLECTOR I COLLECTOR SPLICE OPTIONAL STRAP LOCATION CS COLLECTOR SPLICE L—i N.T.S. CSAA A-12 WALL 2x10 LEDGER w/ ' (2)#SDWS%x4%" T— SCREWS@ 16" oc, MAX (2) #A34 @ TOP, (1) E.S. w/ #SD SCREWS ROOF SHEATHING PER STRUCTURAL NOTES CONTINUOUS 2x10 @ 12" oc 2X EDGE MAX, U.N.O MEMBER t (2)16d #A34 w/ #SD SCREWS 2'-0" MAX ARCHITECTURAL FEATURE ATTACHMENT N.T.S. #LSTA24 w/ MIN (9) -10d FASTENERS PER MEMBER U.N.O. TOP PLATE COLLECTOR OR RIM COLLECTOR OR RIM TOP PLATE COLLECTOR TO TOP PLATE N.T.S. SHEARWALL BOTTOM PLATE #PSPN58 FLOOR SHEATHIN PLUMBING SHEARWALL FLOOR #PSPN516 1 Z" MIN J_ --- DBL TOP PLATE III I ELEVATION VIEW TOP PLATE NOTCH #PSPN516 w/ 8-16d NAILS II TOP PLATE, E, — PLUMBING SHEARWALL 11" z NOTCHI REQUIRE #MTS20 MIN w/ MIN (7)10d x 1%" TO EA MEMBER U.N.O. #PSPN58 w/ 1-8d NAIL INTO BASE PLATE, E,S. WALL STUD, TYP WALL STUD, TYP BOTTOM PLATE NOTCH PENETRATION OF FRAMING - SHEARWALL N.T.S. CTPF PENETRATIONS IN THIS AREA DO NOT REQUIRE APPROVAL FROM THE ENGINEER DO NOT MAKE PENETRATIONS OR NOTCHES HOLES MUST BE ROUND AND ARE LIMITED TO IN THE SHADED AREA OF THE BEAM WITHOUT MIN CLEAR SPACING ly"OOR% DEPTH OF MEMBER, UNLESS PRIOR APPROVAL OF THE ENGINEER SHALL BE 8x THE APPROVED BY THE ENGINEER DIAMETER OF THE L/8 LARGER HOLE L/8 d/4 DEPTH Td2 O O d/4 L/8 r L/2 T L/8 L GLB DO NOT MAKE PENETRATIONS OR NOTCHES IN THE SHADED AREA OF THE BEAM WITHOUT PRIOR APPROVAL OF THE ENGINEER MIN CLEAR SPACING SHALL BE 2x THE DIAMETER OF THE LARGER HOLE PENETRATIONS IN THIS AREA DO NOT REQUIRE APPROVAL FROM THE ENGINEER %DEPTH DEPTH y DEPTH O y DEPTH SPAN SAWN DO NOT MAKE PENETRATIONS OR NOTCHES IN THE SHADED AREA OF THE BEAM WITHOUT PRIOR APPROVAL OF THE ENGINEER SPAN SPAN SPAN MIN CLEAR SPACING SHALL BE 2x THE DIAMETER OF THE rPENETRATIONS IN THIS AREA DO NOT LARGER HOLE I REQUIRE APPROVAL FROM THE ENGINEER %DEPTH DEPTH % DEPTH Q O O DEPTH t PSL & LVL HOLES PERMITTED IN MIDDLE %SPAN ONLY DEPTH LSL ALLOWED HOLE ZONE DEPTH SPAN MAX HOLE DIAMETER SHALL NOT EXCEED 2" U.N.O. MAX HOLE DIAMETER FOR LSL BEAMS SHALL BE: 3" FOR 9%" DEPTH 3%" FOR 11%" DEPTH 4%" FOR 14"-16 DEPTH PSL, LVL, & LSL BEAM PENETRATIONS, TYPICAL DETAIL N.T.S. SSS Number: s2202002 Project Name: 191xx 94th Ave W Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M N (V O N O i--1 0 Q w ,n [V J w z E O ~ V V_ H Ili C � � u7 p z w C/) LCO V p1 C N u7 V) O FL i This space reserved for governing jurisdiction stamps RECEIVED Sep 06 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE; 7/25/2022 REVISED; ---S211 - CITY OF EDMONDS BUILDING DIVISION APPROVED PLAN JOIST 6-0" MAX #A34 EACH SIDE SOLID BLOCK, POST, TYP MATCH WIDTH OF A24 w/ (4)10d POST POST BELOW (2) POWDER ACTUATED FASTENERS EACH SIDE INTO CONIC (1" EMBED) FTG BRG SOIL NOTE: 9" OF CS22 COILED STRAP AND (8)10d NAILS MAY BE USED IN LIEU OF THE ST9 'BF INTERIOR POST BEAM AND FOOTING N.T.S. (2)-ROWS STAGGERED 8d MIN @ 6"oc FLR DIAPHRAGM FDN WALL MIN (3) - 8d TOENAILS JOIST TO SILL FLR DIAPHRAGM JOISTS JOIST 6-0" MAX SOLID BLOCK, MATCH WIDTH OF POST BELOW EACH SIDE #A34 EACH SIDE POST, TYP A24 w/ (4)10d POST (2) POWDER ACTUATED FASTENERS INTO CONIC (1" EMBED) FTG BRG SOIL MIN (3) - 8d TOENAILS BLK TO SILL FLR SHEATHING w/ 10d @ 4"oc TO FRMG & BLKG JOISTS 2x TIGHT -FIT BLOCKS @ 48"oc FOR (2) FULL JOIST SPACES JD JOIST DROPPED JB JOIST BEARING JP JOIST PARALLEL NOTE: METAL FASTENERS LESS THAN %" O SHALL BE HOT -DIPPED GALVANIZED WHEN IN CONTACT WITH P.T. LUMBER FTC FOUNDATION WALL TOP CONNECTIONS N.T.S. FTCA THICKNESS STEEP EXCAVATI( WILL ALLC STEPPED FOOTING N.T.S. 2", TYP I A.B. PER PLAN F- 11" MIN CLC cni TrE AC nEnn ° A d . a. Q. a a a ° a 17" CLC, TYP a a. a° ° A. C HOLDOWN POST 37 2 I " n r)ER PLAN ITEM WALL SHALL 3E 2'-0" DEEP MIN :2) #4 HORIZ CONT P TOP OF WALL "x3"x3" 436 BRG PLATE N/ DBL NUT (2)#4xll 4" REINFORCED FOUNDATION ANCHOR 3/4" = V-0" RFAA HOLDOWN HOLDOWN ANCHOR e ANCHOR e _>/g 1 EMBEDDED e I // FOUNDATION WALL EMBEDDED STRAP � � / MINIMUM STEM HEIGHT I I\ REQUIRED TO ACCOMMODATE ANCHORAGE PER HOLDOWN SCHEDULE FOOTING I DEEPEN FOUNDATION AS REQD TO ACCOMODATE FOR HOLDOWN L — — — EMBEDMENTS INTO WALL MHE� MINIMUM HOEDOWN EMBEDMENT N.T.S. MHE FTC FTC r 1 P.T. SILL PLATE #4 CONT @ 24"oc w/ r 1 #4 CONT w/inIF"'INISH & A.B. (1) #4 w/in TOP 12" OF WALL TOP 12" OF WALL CONC STEM WALL8" U.N.O. 8"MINCTRD ON FTG, U.N.O.VERT &DOWELSCTRD IN STEM GRADE 4'-0" MAX,\FINISH GRADE8'-0" MAX VERT/��'" y FOR 8" MIN16" MIN #4 @ 48"oc,#4 @ 48"oc Z-DTHICK WALL MAX CORNERS &DOWELS w/ OR - INTERSECTIONS 14" EXTENSION 18" 8'-0" 4'-0" 4'-6" MAX INTO WALL & STD MIN MAX MAX BACKFILL FOR 6" HOOK IN FTG THICK WALL i BACKFILL a #4 AT BTM 2" CLR CONIC FTG PER PLAN w/ 3" CLR BACKFILL (2) #4 CONT, i BRG SOIL I 'I I ICI I I U.N.O. �...i i r-11 i=�— NOTES: -DETAIL PER CODE FOR SW,SP,GW,GP,GM,GC,SM,SM-SC AND ML SOILS -TEMPORARILY BRACE WALL IF BACKFILLING BEFORE BRG SOIL =1I1=1 I I THE TOP CONN IS CONSTRUCTED I, �,I 11- -DEEPEN FOUNDATION AS REQD TO ACCOMODATE FOR HOLDOWN ALL OTHER INFORMATION PER STANDARD EMBEDMENTS STANDARD DEEP FLOOR LATERALLY SUPPORTS TOP OF STEM FWS FOUNDATION WALL - STEM N.T.S. SLAB 12" MIN (2)#4 CONT g . 3" CLR a BRG WIDTH SOIL TSFJ THICKENED SLAB FOOTING Li N.T.S. TSFA BEAM ST9 STRAP E.S. w/ (8)10d NAILS POST 6'-0" MAX A24 w/ (4)10d POST (2) POWDER ACTUATED FASTENERS INTO CONIC (1" EMBED) FTG BRG SOIL III-III-III-III-III-III=III-1 -III-III-11 NOTE: 9" OF CS22 COILED STRAP AND (8)10d NAILS MAY BE USED IN LIEU OF THE ST9 'BF INTERIOR POST BEAM AND FOOTING N.T.S. PBFA GR BEAM �...,�*..... REINF MATCH HORIZ I Zo STD 900 HOOK INTO REINF INTERSECTING GR BEAM 1-6 CORNER BAR @ ALL OUTER REINF • REINF • I WALLS STD 900 HOOK INT MATCH HORIZ Z.,, INTERSECTING GR BEAM REINF ALTERNATE EA BAR 1,-6" CORNER BAR @ ALL OUTER REINF REINFORCEMENT AT INTERSECTIONS N.T.S. RIAA FOOTING SCHEDULE CENTER UNDER CONCENTRATED LOAD U.N.O. ID FOOTING SIZE REINFORCEMENT WIDTH (Transverse) LENGTH (Longitude) THICKNESS LONGITUDE TRANSVERSE F2.5 2'-6" 2'-6" 10" (3) #4's (3) #4's F3 3'-0" 3'-0" 10" (4) #4's (4) #4's F4 4'-0" 4'-0" 12" (4) #5's (4) #5's FINISH LONGITUDE REINF TRANSVERSE REINF PnST Tn FT(; BRG SOI1LI =1 I I=11T- 1= — ALL OTHER INFORMATION PER STANDARD NO LATERAL TOP SUPPORT FWSA THICKNESS LENGTH WIDTH (LONGITUDE) (TRANSVERSE) PLYNTH ON FTG -TG FOOTING, TYPICAL N.T.S. FTG @ WALL FTG @ WALL CORNER FTG UNDER SLAB ON GRADE FTGC SSS Number: s2202002 Project Name: 191xx 94th Ave W Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M N N O N O 00 Q w ,n L.#n N J w z O ~ V V H ICU:: cn u7 0 z Ul) w V) O V p1 C N u7 Ln O -a 4r This space reserved for governing jurisdiction stamps RECEIVED Sep 06 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 7/25/2022 REVISED: ---2 S21 - CITY OF EDMONDS BUILDING DIVISION APPROVED PLAN (2) #4 CONT @ TOP OF WALL CONIC SLAB ON GRADE 8" U.N.O. 4'-6" MAX 24" MIN #4 @ 16"oc VERT — #4 CONT @ 10" oc HORIZ - CONIC FTG 16" x 8" w/ (3) #4 CONT, U.N.O. P.T. SILL PLATE &A.B. 2'-0" MAX CONIC STEM WALL BETWEEN GRADES CTRD ON FTG, U,N,O, FINISH GRADE \ #4 @ 16"oc DOWELS w/ 14" EXTENSION INTO WALL & STD 18" HOOK IN FTG MIN (2) #4 CONT @ BTM OF WALL 3" CLR NOTES: -CENTER VERTS AND DOWELS IN STEM WALL -DEEPEN FOUNDATION AS REQD TO ACCOMODATE FOR HOLDOWN EMBEDMENTS -DEEPEN EXCAVATION TO PROVIDE MINIMUM FOOTING DEPTH FWX I FOUNDATION WALL - STEM S N.T.S. FWX A B C HORIZ `6ACKHLL \ VERT \/ 2" COVER —d— J/\— @ VERT & DOWEL CONCRETE WALL H DOWEL w/ 900 HOOK EXTENDED TO TOE CONCRETE I FOOTING D 3" COVER / LONG III I I, I I I I I I BRG SOIL-1 1 1 I 11 1 1 I I I I DRAINAGE PER CODE SRW I SITE RETAINING WALL SCHEDULE AC[ 318-14 FWCBA (45 2000 300 0.4 8H) (BSFO SO SLO-0 AF02 DIMENSIONS H E S D E_FA B C7"( (FT-IN) (Fr -IN) (IN) (IN) (IN) (IN) (IN)) 4-0 3-6 6 12 24 1 8 12 44 REINFORCEMENT *1 H DOWEL LAP VERT LONG *Z *3 *2 (FT -IN) (IN oc) (IN) (IN cc) (IN cc) (IN oc) 4-0 #4 @ 12 20 #4 @ 12 #4 @ 12 #4 @ 8 *NOTES: 1 Clear cover requirements u.n.o. - 3" to soi, 2" to forms in all other locations 2 DOW EL and VERT may be the same piece provided the size and spacing of the DOWEL is used. d D 1800 4d or 2%" MIN. BAR D #3 1 %" #4 2" #5 1 2 %" #6 4y" #7 5%" #8 6" LEGEND d = BAR DIAMETER D = FINISHED BEND DIAMETER Note: 1, STANDARD HOOKS SHALL CONFORM TO ACI 318 SECTION 25.3 12d 2, REINFORCING SHALL BE COLD BENT, STANDARD HOOKS N.T.S. BAR DEVELOPMENT LENGTHS BAR SIZE LAP STRAIGHT HOOK #4 18" 18" 6.5" #5 24" 24" 8.25" #6 30" 24" 10.25" THIS IS A GRAPHICAL REPRESENTATION ONLY, THERE IS NO BEND IN THE VERTICAL BAR DOWEL w/ STD HOOK TOE BARS MUST HAVE FULL DEVELOPMENT LENGTH ON BOTH SIDES OF THIS LINE. AN EXTENDED DOWEL BAR MAY REPLACE A SEPARATE TOE BAR e e ° 2" COVER @ VERT & DOWEL e e SHA DOWELS MAY BE COMBINED WITH THE VERTICAL AND/OR TOE BARS PROVIDED THE DOWEL SIZE AND SPACING IS USED HEEL BARS MUST HAVE FULL e DEVELOPMENT LENGTH ON BOTH SIDES OF THIS LINE e 211 ° f CLR CLR 3" CLR TOE HEEL NOTE: THIS DETAIL IS INTENDED TO PROVIDE SUPPLEMENTAL INFORMATION TO THE FOUNDATION DETAILS PROVIDED. THE INFORMATION PROVIDED ON THOSE DETAILS WOULD SUPERCEDE THIS DETAIL. I BAR DEVELOPMENT - SUPPLIMENTAL INFO N.T.S. A B C FRMG T HORIZ �NtlALKHLL <1 \�\ �/ VERT \. 2" COVER @ VERT & DOWEL H CONCRETE WALL DOWEL w/ 900 HOOK EXTENDED TO TOE 5 CONCRETE SLAB CONCRETE FOOTING / 3" COVER , ID I= CONT I I —I BRIG SOIL III III I I —III III I I. —III- III 1 I I —III —I DRAINAGE PER CODE FWC1 FOUNDATION WALL - CANTILEVER SCHEDULE ACI 318-14 FWCB ( 45 2000 0) ( S) DIMENSIONS ID H A B C D (FT IN) (IN) (IN) (IN) (IN) 4 4-0 12 8 8 10 5 5-0 20 8 8 10 6 6-0 28 8 8 10 7 7-0 24 8 16 10 8 8-0 34 8 16 10 9 9-0 44 8 16 1 12 REINFORCEMENT *1 ID DOWEL *2 LAP (IN) VERT*2 HORIZ CONT 4 #4 @ 10 32 #4 @ 10 #4 @ 12 #4 @ 10 5 #4 @ 10 32 #4 @ 10 #4 @ 12 #4 @ 10 6 #4@6 32 #4@12 #4@12 #4@10 7 #5@8 40 #5@16 #4@12 #4@10 8 #5@6 40 #5@12 #4@12 #4@10 9 #5@5 40 #5@10 #4@12 #4@9 *NOTES: 1 Clear cover requirements (3" to soil, 2" to forms in all other locations) 2 DOWEL and VERT may be the same piece provided the size and spacing of the DOWEL is used a HORIZ VERT 2" CLR @ VERT & DOWEL DOWEL w/ STD 900 HOOK AND EXTEND TO TOE D Y (:LK K KEY w/ r,rri nn unnv '' I" "' I V"I. .y � HORIZ AT TOP FWC2 CANTILEVERED FOUNDATION WALL N.T.S. HORIZ VERT 2" CLR @ VERT & DOWEL DOWEL w/ STD 900 HOOK 2„ 211 CLR CLR HEEL 3" CLR FWC3 1 CANTILEVERED FOUNDATION WALL N.T.S. VERT 2" CLR @ VERT & DOWEL DOWEL w/ STD 900 HOOK 2„ 2" CLR HEEL CLR 3" CLR FWC41 CANTILEVERED FOUNDATION WALL SCHEDULE ACI 318-14 FWCCB ( 35 2000 275 0.4 7H) (BSFO/1 SO/50 SLO.69-0.46 DIMENSIONS H D K A B C W (FT -IN) (IN) (IN) (IN) (IN) (IN) (IN) 8-0 10 none 22 8 1 8 38 11-0 12 34 48 10 8 1 66 REINFORCEMENT *1 H DMELVER LAP HORIZ CONT KEY *2, *3 *2T (FF-IN) (IN oc) (IN) (IN oc) (IN oc) (IN oc) (IN cc) 8-0 #5 @ 6 40 #5 @ 12 #4 @ 12 #4 @ 10 none 11-0 1 #5@5 40 #5@5 1 #4@10 #4@8 1 #4@8 *NOTES: 1 Clear cover requirements u.n.o. - 3" to soil, 2" to forms in all other locations 2 DOWEL and VERT may be the same piece provided the size and spacing of the DOWEL is used. 3 Extend the DOWEL to within 2" of the TOE edge SCHEDULE ACI 318-14 FWCDB (35 2000 275 0.4 FWCB FO SO SLO.6-0.45 AFO) I DIMENSIONS H E S D A B C W (FT -IN) (FT -IN) (IN) (IN) (IN) (IN) (IN) (IN) 5-0 4-6 6 10 8 8 16 32 6-0 5-6 6 10 8 8 20 36 8-0 1 7-6 1 6 1 10 1 8 8 1 28 44 REINFORCEMENT *i H D 2WE3 LA P VERT HORIZ CONT HEEL (FT -IN) (IN oc) (IN) (IN oc) (IN oc) (IN oc) (IN oc) 5-0 #4 @ 12 22 #4 @ 12 #4 @ 12 #4 @ 8 none 6-0 #4 @ 12 22 #4 @ 12 #4 @ 12 #4 @ 8 none 8-0 #4@5 22 #4@10 #4@12 #4@8 #4@8 *NOTES: 1 Clear cover requirements u.n.o. - 3" to soil, 2" to forms in all other locations 2 DOWEL and VERT may be the same piece provided the size and spacing of the DOWEL is used. 3 Extend the DOWEL to within 2" of the TOE edge SCHEDULE ACI 318-14 NCDB l 35 2000 275 0.4 7H) IBSFO S50 SLO.6-0.45 AF01 DIMENSIONS H E S D A B C W (FT -IN) (FT -IN) (IN) (IN) (IN) (IN) (IN) (IN) 11-0 9-0 24 14 14 10 44 68 REINFORCEMENT *1 H DOWEL LAP VERT HORIZ CONT HEEL i (FT -IN) (IN oc) (IN) (IN oc) (IN oc) (IN oc) (IN oc) 11-0 #505 40 1 #5@10 #4@10 #5@8 #4@8 *NOTES: 1 Clear cover requirements u.n.o. - 3" to soil, 2" to forms in all other locations 2 DOWEL and VERT may be the same piece provided the size and spacing of the DOWEL is used. FWCD N.T.S. SRWA U N.T.S. FWCB U N.T.S. FWCD SSS Number: s2202002 Project Name: 191xx 94th Ave W Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M N (V O N O i--1 i J ^ p w Ln [V J w z E O ~ V V_ H ICU:: to � Ln u7 p z Ul) w V) O V Cal C N cc Ln u7 O FL 11 This space reserved for governing jurisdiction stamps RECEIVED Sep 06 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 7/25/2022 REVISED:S213 ---- [V O O [V O r11 r'V �I ; v'I Ln CV O Ci r11 CITY OF EDMONDS BUILDING DIVISION APPROVED PLAN Errdrru rnAME BACKFILL, TYP VE BEA rml CONSULT SECTION A -A N.T.S. EVrrrrnir rn Amr �,. �,..� .......� ,III 1.1� CONSULT SECTION B-B FC 0 Q DETERMINING THE DEPTH OF ADJACENT FOOTINGS DISTANCE "B" SHALL NOT BE GREATER THAN DISTANCE "A" - DEEPEN EXCAVATION AS REQ'D ADJACENT FOUNDATION DEPTH FOUNDATION OR FOOTING N.T.S. U N.T.S. AFDA SSS Number: s2202002 Project Name: 191xx 94th Ave W Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M c.n f V O N O H o J O w Lr) (V J w z o V H GC Ln p z Z p w O U N Ln Ln �V) X O C FL This space reserved for governing jurisdiction stamps RECEIVED Sep 06 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 7/25/2022 REVISED: ---S214 - SYMBOL LEGEND - FOUNDATION SLEXP #HOLDOWN MODEL HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE. — — — CONCRETE WALL AND CONTINUOUS FOOTING See CONCRETE and REINFORCING BAR specifications per DETAIL FWS. — — — CONCRETE WALL AND CONTINUOUS FOOTING See CONCRETE and REINFORCING BAR specifications per DETAIL FWS & FWC_. F_ -1 F2 SPREAD FOOTING See CONCRETE and REINFORCING BAR specifications per DETAIL FTG. L_� CITY OF EDMONDS BUILDING DIVISION APPROVED PLAN i L FOUNDATION PLAN - FIRST FLOOR & SITE RETAINING WALLS 1/4" = V-0" i i i i i i i i i i i i i #STHD14 J DO NOT SCALE - VERIFY ALL DIMENSIONS WITH ARCHITECTURAL SHEETS PRIOR TO CONSTRUCTION SSS Number: s2202002 Project Name: 191xx 94th Ave W Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M N (V O N O i--1 0 J ^ p w Ln [V J w z E O ~ V V_ H ICU:: u7 p z w C/) O V p1 C N u7 �V) O This space reserved for governing jurisdiction stamps RECEIVED Sep 06 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE; 7/25/2022 REVISED; ---- S3.0 CITY OF EDMONDS BUILDING DIVISION APPROVED PLAN SYMBOL LEGEND SLEXP ------------------- DIAPHRAGM BOUNDARY Represents boundaries of the FLOOR DIAPHRAGM and ROOF DIAPHRAGM. POST Indicates the location of a post within walls below framing. Sizes are indicated on the plan. Grades are indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Consult detail BHS for posts not indicated on DIAPHRAGM PROJECTION Represents elements such as roof eaves, facades, and the like. the plans. — — — — — — — — — — SHEARWALL Represents walls which are shearwalls and shows the extents of that wall. Connections k \ \ INTERIOR BEARING WALL Indicates interior walls which support repetitive members. Construct per WALL per the SHEARWALL SCHEDULE. FRAMING & BEARING in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. *HOLDOWN MODEL J I L u HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are HANGER Indicates hanger, standard or concealed flange. Provide fasteners in all holes. Reference the GENERAL wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE. STRUCTURAL NOTES for the minimum size hanger. If a different model no. is required, it will be noted on the plan. BEAM or HEADER Represents the location of a beam or header. Sizes are indicated on the plan. Grades are JOIST, TRUSS, OR RAFTER Repetitive member symbol points in the direction of the span. The type, size and max indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Headers (HDR) shall be 4x8 U.N.O. on the plan. spacing between members will be indicated in bold type with a symbol which is representative of the layout of the entire level. WALL WALL WALL LANE LIANE LIANE FIRST FLOOR SHEARWALLS & FRAMING ABOVE 1/4" = V-0" DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS SSS Number: s2202002 Project Name: 191xx 94th Ave W Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M N (V O N O i--1 o J ^ Q w Ln [V J w z E O ~ V V_ H IOC u7 p z w C/) LC O V C V) O FL This space reserved for governing jurisdiction stamps RECEIVED Sep 06 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE; 7/25/2022 REVISED; ---S410 - CITY OF EDMONDS BUILDING DIVISION APPROVED PLAN I> SYMBOL LEGEND SLEXP ------------------- DIAPHRAGM BOUNDARY Represents boundaries of the FLOOR DIAPHRAGM and ROOF DIAPHRAGM. POST Indicates the location of a post within walls below framing. Sizes are indicated on the plan. Grades are indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Consult detail BHS for posts not indicated on DIAPHRAGM PROJECTION Represents elements such as roof eaves, facades, and the like. the plans. — — — — — — — — — — SHEARWALL Represents walls which are shearwalls and shows the extents of that wall. Connections � INTERIOR BEARING WALL Indicates interior walls which support repetitive members. Construct per WALL per the SHEARWALL SCHEDULE. FRAMING & BEARING in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. *HOLDOWN MODEL J I L_ u HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are HANGER Indicates hanger, standard or concealed flange. Provide fasteners in all holes. Reference the GENERAL wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE. STRUCTURAL NOTES for the minimum size hanger. If a different model no. is required, it will be noted on the plan. BEAM or HEADER Represents the location of a beam or header. Sizes are indicated on the plan. Grades are JOIST, TRUSS, OR RAFTER Repetitive member symbol points in the direction of the span. The type, size and max indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Headers (HDR) shall be 4x8 U.N.O. on the plan. spacing between members will be indicated in bold type with a symbol which is representative of the layout of the entire level. WALL WALL WALL LINE LINE LINE n R r SECOND FLOOR SHEARWALLS & FRAMING ABOVE 1/4" = V-0" DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS SSS Number: s2202002 Project Name: 191xx 94th Ave W Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M N (V O N C:) i--1 o J ^ Q w Ln [V J w z E O ~ V V_ H IOC � Ul) u7 p z w C/) LCO V C" C N �V) O C FL i 1 Dom. This space reserved for governing jurisdiction stamps RECEIVED Sep 06 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE; 7/25/2022 REVISED; ---S411 - CITY OF EDMONDS BUILDING DIVISION APPROVED PLAN R� > RM R> I> SYMBOL LEGEND SLEXP ------------------- DIAPHRAGM BOUNDARY Represents boundaries of the FLOOR DIAPHRAGM and ROOF DIAPHRAGM. POST Indicates the location of a post within walls below framing. Sizes are indicated on the plan. Grades are indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Consult detail BHS for posts not indicated on DIAPHRAGM PROJECTION Represents elements such as roof eaves, facades, and the like. the plans. — — — — — — — — — — SHEARWALL Represents walls which are shearwalls and shows the extents of that wall. Connections k \ \ INTERIOR BEARING WALL Indicates interior walls which support repetitive members. Construct per WALL per the SHEARWALL SCHEDULE. FRAMING & BEARING in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. #HOLDOWN MODEL J I L_ u HOLDOWN Represents holdowns which are located at the bottom of the wall where it is called out. Connections are HANGER Indicates hanger, standard or concealed flange. Provide fasteners in all holes. Reference the GENERAL wall-to-wall or wall -to fdn u.n.o. Connections per the HOLDOWN SCHEDULE. STRUCTURAL NOTES for the minimum size hanger. If a different model no. is required, it will be noted on the plan. BEAM or HEADER Represents the location of a beam or header. Sizes are indicated on the plan. Grades are JOIST, TRUSS, OR RAFTER Repetitive member symbol points in the direction of the span. The type, size and max indicated in the GENERAL STRUCTURAL NOTES, U.N.O. on the plan. Headers (HDR) shall be 4x8 U.N.O. on the plan. spacing between members will be indicated in bold type with a symbol which is representative of the layout of the entire level. WALL WALL WALL LINE LINE LINE n n 6xl #EPCZ @ (2) #A35 @ #CS16 BEAT TO STUD THIRD FLOOR SHEARWALLS & FRAMING ABOVE 1/4" = V-0" rnv� L v n i DO NOT SCALE - REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONS SSS Number: s2202002 Project Name: 191xx 94th Ave W Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M N N O N O i--1 o J ^ O w Ln L04") N J w Z E O ~ V V_ H IOC u7 p Z w C/) LCO V p1 C N �V) O C FL This space reserved for governing jurisdiction stamps RECEIVED Sep 06 2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE; 7/25/2022 REVISED; ---S4,2 -