APPROVED RESUB1 FIR2023-0030+PLANS+5.23.2023_8.24.52_AM+3562506APPROVED PLANS MUST BE ON JOB SITE ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE Approved D F M CM its gust South County Fire Date: 06/09/2023 06-09-2023 RESUB 1 PLAN REVIEW NOTES: APPROVED DFM BURT PROJECT DESCRIPTION ANTHOLOGY NEW 164,000 SF SENIOR INDEPENDENT LIVING BUILDING IN EDMONDS, WASHINGTON. THE BUILDING WILL HAVE 127 INDEPENDENT LIVING UNITS. THIS COMMUNITY WILL BE SPECIALLY DESIGNED FOR SENIOR RESIDENTS WHO ARE STILL ACTIVE BUT WILL BENEFIT FROM SERVICES PROVIDED BY THE OPERATOR. SERVICES INCLUDE COMMERCIAL KITCHEN AND DINING ROOM, FITNESS CENTER, SALON, LAUNDRY, SOCIAL ACTIVITIES, AND HOUSEKEEPING. PLANNING INFORMATION ZONE: CG (GENERAL COMMERCIAL) TAX LOT ID: I N 131 C B-01100 I N 131 C B-01000 PERMIT NUMBERS AUGMENTED DESIGN REVIEW: PLN2021-0004 CIVIL PERMIT: BLD2021-0116 BUILDING PERMIT: BLD2021-0088 ARCHITECT TEAM 21200 72nd AVE W DEFERRED SUBMITTALS EDMONDS, WA 98026 • SHOP FABRICATED WOOD TRUSS • FIRE STOPPING • WOOD I -JOIST • GLUED -LAMINATED CONSTRUCTION • ACOUSTICAL CEILINGS: CEILING SUPPENSION SYSTEM • ALUMINUM STOREFRONT • EXTERIOR COLD FORM FRAMING ALL DEFERRED SUBMITTALS SHALL FIRST BE SUBMITTED TO THE PROJECT ARCHITECT AND/OR ENGINEER FOR REVIEW AND COORDINATION. FOLLOWING THE COMPLETION OF PROJECT ARCHITECT'S AND/OR ENGINEER'S REVIEW AND COORDINATION, A SUBMITTAL SHALL BE MADE (FOR CITY REVIEW AND APPROVAL) BY THE CONTRACTOR, WHICH SHALL INCLUDE A LETTER (OR SHOP DRAWING APPROVAL STAMP) STATING THIS REVIEW AND COORDINATION HAS BEEN PERFORMED AND COMPLETED AND PLANS AND CALCULATIONS FOR THE DEFERRED ITEMS ARE FOUND TO BE ACCEPTABLE (E.G., WITH REGARD TO GEOMETRY, LOAD CONDITIONS, ETC.) SEPARATE PERMIT • MECHANICAL (2015 WASHINGTON STATE BUILDING CODE BASED ON 2015 IMC) • PLUMBING (2015 WASHINGTON STATE BUILDING CODE BASED ON 2015 UPC) • ELECTRICAL (2020 NEC) • FIRE ALARM (2015 WASHINGTON STATE BUILDING CODE BASED ON 2015 IFC, NFPA 13 - 2013, NFPA 99 AND 101 - 2015) • FIRE SUPPRESSION SPRINKLER SYSTEM (2075 WASHINGTON STATE BUILDING CODE BASED ON 2015 IFC, NFPA 13 - 2013, NFPA 99 AND 101 - 2015) • FIRE SPRINKLER (2015 WASHINGTON STATE BUILDING CODE BASED ON 2015 IFC,NFPA 13 - 2013, NFPA 99 AND 101 - 2015) • FIRE CONNECTION (2015 WASHINGTON STATE BUILDING CODE BASED ON 2015 IFC, NFPA 13 - 2013, NFPA 99 AND 101 - 2015) • SIGNS • CIVIL CONSTRUCTION PLAN SET - under separate Fill/Grade Permit • DEMO PERMIT - NOTE AS PART OF CIVIL • DISTRIBUTIVE ANTENNA SYSTEM (DAS) OWNER TEAM VICINITY MAP 210th SI SW a D Eleven City Of Edmonds Building Department Work SMOKE --------------G-ONT-R©L .---------------------- Address 21200 72ND AVE W -------------------------- -------------------------- Owner ANTHOLOGY Approved Date 06/06/2023 Building Official Erg Permit Number FIR2023-0030 Special Inspections and reports required for this project. Submit reports to City Inspector. = The following documentation shall be available on ' site for the building inspector: COE APPROVED ARCHITECTURAL PLAN SET '. COE APPROVED STRUCTURAL PLAN SET [:]COE REVIEWED CALCULATION PACKET ■ ENERGY CREDIT WORKSHEET ' SITE PLAN • ■ CIVIL PLAN ■ SI Report ElSmoke Control report • ■ CITY OF EDMONDS BUILDING DEPARTMENT 2021 ? i01h St SW 210th St SW p Porbug Repair Q Whole Pup a TIC Span America Q 19 a D ::E Kafe Neo Edmonds Q Edmonds 4onkey Family Medicine Banner BankeD © Q 0 < D eD 212th St SW D 21?th St St;' 212th St SW SITE LOCATION - W rptS Q Magic Toyota Q tit Park 212 Q Allied Building Products, O A Beacon Roofing... 21 sth PI SW Edmonds Park & Ride O SEAWEED Cannabis O Ell Edmonds - Dispensary... 273th PI SW O CONTRACTOR TEAM ARCHITECT STRUCTURAL OWNER GEOTECH & ENVELOPE GENERAL CONTRACTOR FIRE SUPPRESSION ANKROM MOISAN KPFF ANTHOLOGY SENIOR LIVING TERRACON CONSULTANTS CATALYST CONSTRUCTION GROUP TBD 38 NORTHWEST DAVIS 503.245.7100 111 SW FIFTH AVE 503.227.3251 2401 EAST 2ND AVE 312.994.1880 21905 64TH AVE. W 425.771.3304 130 E RANDOLPH STREET TBD SUITE 300 www.ankromoisan.com SUITE 2600 www.kpff.com SUITE 500 anthologyseniorliving.com SUITE 100 www.terracon.com SUITE 2100 TBD PORTLAND, OR 97209 PORTLAND, OR 97204 DENVER, CO 80206 MOUNTLAKE TERRACE, WA 98043 CHICAGO, IL 60601 MARK MILLER 503.952.1397 JIM VODDEN - PE, SE 503.764.0529 MICHAEL DUGGAN 720.805.0497 ZACHARY L. KOEHN - P.E. HARDIK PATEL 312.800.5376 PRINCIPAL markcm@ankrommoisan.com jim.vodden@kpff.com SVP, DEV & CON mduggan@ca-anthology.com VP, PRE -CONSTRUCTION HPatel@catalystconstructiongrp.com RICHARD GRIMES 503.952.1563 ANDI CAMP - PE, SE 503.764.0514 BEN TROUTMAN 312.994.1875 DAVID A. BASKA - P.E. OWEN SMITH 312.446.4016 PROJECT ARCHITECT richardg@ankrommoisan.com andi.camp@kpff.com SM, PRE -CONSTRUCTION btroutman@ca-anthology.com PRE -CONSTRUCTION MGR osmith@catalystconstructiongrp.com ALICIA DUNSTAN alicia.dunstan@terracon.com INTERIORS FOOD SERVICE CIVIL ADA CONSULTANT ANKROM MOISAN CLEVENGER ASSOCIATES NAVIX ENGINEERING SCULLY ADA CONSULTING 38 NORTHWEST DAVIS 503.245.7100 11803 101 ST AVENUE COURT EAST 253.841.7811 11235 SE 6th STREET 425.453.9501 HOMEWOOD, IL 708.280.6435 SUITE 300 www.ankromoisan.com SUITE 103 www.clevengerassoc.com SUITE 150 www.navixeng.com PORTLAND, OR 97209 PUYALLUP, WASHINGTON 98373 BELLEVUE, WA 98004 DARLA ESNARD 503.977.5243 TAD DOMEK 708.548.2503 JENELLE TAFLIN - P.E. 425.458.7896 CHRISTINE SCULLY 708.280.6435 PRINCIPAL darlae@ankrommoisan.com tad@clevengerassoc.com jtaflin@navixeng.com cscully@scullyada.com LINDSEY NEAL 503.952.1370 JASON GREEN 425.458.7934 INTERIOR DESIGNER lindseyn@ankrommoisan.com jgreen@navixeng.com PLUMBING MECHANICAL LANDSCAPE TRAFFIC DC ENGINEERING DC ENGINEERING THOMAS RENGSTORF & ASSOCIATES TRANSPORTATION ENGINEERING NW 440 EAST CORPORATE DRIVE 208.288.2181 440 EAST CORPORATE DRIVE 208.288.2181 811 FIRST AVE 206.682.7562 11400 SE 8th STREET 425.250.5001 SUITE 103 www.dcengineering.net SUITE 103 www.dcengineering.net SUITE 615 www.thomasrengstorfassociates.com SUITE 200 www.tenw.com MERIDIAN, ID 83642 MERIDIAN, ID 83642 SEATTLE, WA 98104 BELLEVUE, WA 98004 AARON PROUGH 2O8.493.0027 AARON PROUGH 2O8.493.0027 SCOTT EVANS sevans@trengstorf.com MICHAEL J. READ, PE 206.361.7333 ext. 101 aprough@dcengineering.net aprough@dcengineering.net PRINCIPAL mikeread@tenw.com ELECTRICAL LOW VOLTAGE DC ENGINEERING M&R DESIGN SERVICES GROUP 440 EAST CORPORATE DRIVE 208.288.2181 515 BOND STREET 847.634.1200 SUITE 103 www.dcengineering.net LINCOLNSHIRE, IL 60069 www.mandr-dsg.com MERIDIAN, ID 83642 GINA SPIRNOCK - LC 208.493.0011 BRYAN BOONE bboone@mandr-dsg.com Plan set for Smoke Control gspirnock@dcengineering.net SCOTT SUPERFINE ssuperfine@mandrelectronics.com only. Q0 1714 CD 00 Cn cn 0 Z z O 0 V W 0 z L.L 0 z OJ 0 LU C� 0 V' z > n J r O_ C: 0 J O 2 o Z1714 z Q (V Q REVISION DATE REASON FOR ISSUE A 08.20.21 City Comments #01 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT FIR2023-0030 COVER SHEET CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 1 U-0" STORM EASEMENT ZIA (E) CMU WALL i I _ I (E) CONC. WALL r i O 1O2 03 4 5O 6 8O I I I I I I I I I I I I I o SIGN y FIRE HYDRANT LANDSCAPE )PERTY LINE� 00 --- - - --- - -- -------------------------------------- FlIZ11-4 -- - - - -- - - -- - - - - - - - - -- - - - O 0 0 SEE CIVIL DRAWINGS UNDER PERMIT 10'-0" STORM ACCESSIBLE ROUTE OF CONCRETE SIDEWALK TYP. 10'-0" STREET #BLD2021-0116 FOR FIRE LANE STRIPING UP TO ^ EASEMENT TRAVEL TO PUBLIC WAY BUILDING MOUNTED FLAG POLE SETBACK BUILDING EDGE. � i F----------- i F� PLANTER, TYP. ------- - � I - - - -- -- - - --- - - - - -- 1----- - - - - - - PAINT, TYP PAINT, TYP i RISER ROOM O 1034 i 0 24 -11 DRIVE AISLE o jCONCRETE SIDEWALK TYP.I BIKE PARKING O I I CONCRETE I I I I I 0 0 PASSENGER LOADING ZONE, VERTICAL MIN Li CLR 114" � BIKE // PARKING 5' OTI 9 10 12 13 I I I N N 0 PROPERTY LINE 00, IU-0" UTILITY EASEMENT __7 I I I I I I I o 1NEW INDEPENDENT LIVING NOTE: SEE SHEETA2.01 FOR I o EHICULAR AND PEDESTRIAN BUILDING I SLOPES THROUGHOUT i m PARKING GARAGE AREA 1 j 1 163,986 SQUARE FEET I CCESSIBLE ROUTE OF TRAVEL_j TYP ------------ Li I I I I A1.2o I I I o I I I I I 0® 0 O O 0 Ll - STAIR - 1 - - - - - - I I I I I I I I I I I I CONCRETE I I I I I I Li MECHANICAL 1032 I I I I I I I I 10' SANITARY � 0'0" NWERLNE//�// // / SEWER S/ �EASEMENT��� �1 PROPERTY LINE C .. SITE PLAN I 1/8" = 1'-0" FA IF7 F u lu owo z O 0 LOADING Of I I I I I I I I I I I ADJACENT PROPERTY j 10'-0" UTILITY /,EASEMENTi 3'-0" ELECTRICAL EASEMENT 10'-0" UTILITY - EASEMENT 1 U-0" STREET SETBACK ---TRASH ROOM CANOPY ABOVE STAIR - 2 GENERAL NOTES - SITE PLAN 1. REFER TO SHEET A0.01 FOR'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK. 2. GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO CONSTRUCTION, CONFLICTS ARE TO BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO THE START OF CONSTRUCTION RELATED TO SUCH. 3. REFER TO CIVIL DRAWINGS FOR GRADING AND UTILITY INFORMATION. 4. CONTRACTORS SHALL VERIFY ALL LOCATIONS OF EXISTING UTILITIES, CARE SHOULD BE TAKE TO AVOID DAMAGE TO OR DISTURBANCE OF EXISTING UTILITIES. 5. REFER TO CIVIL AND LANDSCAPE DRAWINGS FOR ALL PUBLIC RIGHT-OF-WAY IMPROVEMENTS. 6. THE CONSTRUCTION SHALL NOT RESTRICT A FIVE-FOOT CLEAR UNOBSTRUCTED ACCESS TO ANY WATER OR POWER DISTRIBUTION FACILITIES (POWER POLES, PULL BOXES, TRANSFORMERS, VAULTS, PUMPS, VALVES, METERS, APPURTENANCES, ETC.) OR THE LOCATION OF THE HOOK-UP. 7. THE CONSTRUCTION SHALL NOT BE WITHIN 10' OF ANY POWER LINES - WHETHER OR NOT THE POWER LINES ARE LOCATED ON THE PROPERTY. FAILURE TO COMPLY MAY CAUSE CONSTRUCTION DELAYS OR ADDITIONAL EXPENSES. 8. SEE SHEET A1.01 - SITE DATA FOR FURTHER INFORMATION REGARDING NUMBER AND TYPE OF VEHICULAR AND BICYCLE PARKING SPACES PROVIDED. 9. FIRE LANE LOCATION IS DIAGRAMATIC, SEE CIVIL FOR EXACT LOCATIONS AND FOR STRIPING ❑ REQUIREMENTS. 10'-0" X 10'-0" PED & SITE DATA k7 UTILITY EASEMENT TOTAL PARKING COUNT: 83 LEVEL 1: 29 - - -- --� LEVEL P1: -')4i BICYCLE PARKINING : 10 ACCESSIBLE PARKING 5 REGULAR STALL PROVIDED (4 ON L1; 1 ON LEVEL P1) 1 VAN STALL PROVIDED (1 ON L1) A REQUIRED ACCESSIBLE PARKING *PER TABLE 1106.1 A MINIMUM OF 4 PARKING SPACES ARE REQUIRED TO 00 z00 BE ACCESSIBLE FOR A PARKING COUNT OF 83. PER 1106.5 1 SPACE IS 00 REQUIRED TO BE VAN -ACCESSIBLE. a B Note: A total of 127 R-2 units are provided, and 83 parking stalls are provided, reducing the overall parking ratio to units to less than 1 stall per unit. IBC 2015 1106.2.3 "Where at least one parking space is provided for each dwelling unit or sleeping unit, at least one accessible parking space shall be provided for each Accessible and Type A unit." 1106.2.3 does not :ONCRETE SIDEWALK TYP. apply to scope of project as the parking spaces are not meeting the r minimum provision of 1 parking space per sleeping or dwelling unit. SITE: 33,926 SF I SITE LEGEND LANDSCAPE i — C 40 1 5/8" CONCRETE SIDEWALK E CONCRETE PT DECK L J I w PEDESTRIAN ONLY WALKING AREA z�F• OF LOCATED WITHIN PARKING GARAGE LU I I lam I z o I � 'o N I I I I GENERATOR 1031 I I I tAS H -AGING 2EA� ;w Iz , J ,w to la H J K L I& only. NOTE: SEE CIVIL CONSTRUCTION PLANS, REVIEWED UNDER FILL/GRADE PERMIT #BLD2021- 0116, FOR ALL REQUIRED CIVIL SITE IMPROVEMENTS. e Control 9281 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. O 00 C, () O 0 z z O� � >a 0 � w 0 z z LL O OJ o O z O;LU J CD o O� O CD J o O ~ = Z c)N z N Q D_ Q w REVISION DATE REASON FOR ISSUE 1 06.18.21 Addendum #01 A 08.20.21 City Comments #01 B 12.18.21 City Comments #02 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SITE PLAN CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 SHEET NUMBER Al 901 KEY NOTES - PARKING LEVEL FLOOR PLANS GENERAL NOTES OSTRUCTURAL COLUMN TO RECEIVE CHAMPFER EDGE PARKING LEVEL FLOOR PLANS TREATMENT, SEE DETAIL 12 / A0.41 2O ELECTRIC VEHICLE CHARGING STATIONS 1. REFER TO SHEET A0.01 FOR'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK. 2L 2. OMITTED O3 ELECTRIC VEHICLE CHARGING STATIONS - FUTURE 3. PROVIDE GUARDS AT EXPOSED PIPING AND CONDUITS IN ACCORDANCE WITH DETAIL 20/A1.20 4. PROVIDE BOLLARDS TO PROTECT DUCTS, EQUIPMENT AND OTHER CONSTRUCTION FROM IMPACT BY O4 BICYCLE RACK; 10 STALLS TOTAL, 5%TO BE VEHICLES, IN ACCORDANCE WITH DETAILA1.20. ACCESSIBLE 5. SEE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS 6. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES. O5 COLUMN TO BE FINISHED WITH WALL ASSEMBLY 7. SEE SHEETS A0.21, A0.31 FOR WALL ASSEMBLIES. 9M•2 8. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON SHEET G2.01 FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. 9. SEE ENLARGED PLANS FOR DETAILED DIMENSIONS, WALLTAGS AND DOOR TAGS 10. MAINTAIN MINIMUM CLEAR HEIGHT OF 98 INCHES, MEASURED VERTICALLY FROM FLOOR LEVEL TO LOWEST OVERHEAD OBSTRUCTION, COMMENCING AT POINT OF ENTRY OF PARKING GARAGE TO LOCATION OF ALL ACCESSIBLE PARKING STALLS REGARDLESS OF WHERE SUCH STALLS ARE LOCATED IN THE GARAGE. 11. HM DOOR OPENINGS IN CONCRETE CURBS AND WALLS INCLUDE 1" CONSTRUCTION TOLERANCE. MASONRY OPENINGS DO NOT INCLUDE ANY TOLERANCE. 1 2 3 4 5 6 8 9 10 12 13 12. DIMENSIONS ARE TO GRIDLINE, FACE OF (FO) CONCRETE, FO MASONRY, FO FRAMING AT EXTERIOR 7 WALLS, FO STUD @ PARTITIONS, CENTER LINE OF DEMISING WALLS, DOORS AND WINDOW OPENINGS, UNO. TYPICAL ............... ............... ............... ............... ............... ............... ............... ............... ............ ............ Denotes Stair Pressurization Denotes Elevator Pressurization J J J J J F1 J J J 01 Plan set for Smoke Control only. 9281 dVd J 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 C ANKROM MOISAN ARCHITECTS, INC. Q0 (V 00 M Z V� 0 Z Z O 0 V w o Z LL O Z OJ o O 0 z O ; J �00 C) o O� O N O 0 co 1 Z ON = 4t Z � QN aws REVISION DATE REASON FOR ISSUE 1 06.18.21 Addendum #01 A 08.20.21 City Comments #01 4 01.03.22 Addendum #03 RFI - 001 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT PARKING LEVEL 1 FLOOR PLAN CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 3 0 I FO CONC 14 3 �.51 1 2 3 4 O 6 7 O8 9 10 12 I I I I I I I I I I I 18'-6" 12'-55/8" ' 14'-41/2" 1 6'-2" ' 13'-0" 23' - 31 /2" 28' - 6" 27' - 31 /2" 1 •.01 13'-83/4" 9'-53/4" 1 � �T-7 I _j \ A311 1 1 - o----------L---------------------------- --------- --------- ---- ------------------------------------------------ ------ A4.52 ---------------------------�------------------------------------ ---- ---- - ----- -- 3 ' 30' - 0" A4.52 4 1 J 6 2 15 0" 2' 7' 1 ' 31 /4" 24' - 6" 1 ' 6 A4.51 17' 0" 5' - 6" ---------- --------- ---- 5-� ----- ----- --- 1 6 1 PAINT z PAINT PLANTER, TYP 4 1007 O COLUMN, TYP _ I I o (SEE STRUCTURAL) iO - t = - 4- N - - - BOLLARD, TYP - I - - - - I - - - - - � I�co 24'-11" TYP I I DINING01 L1 6 .....- - 5.2 22'-0" MIN ACCESS AISLE 12 1007 5 --- - A1.20 Fl. PASSENGER - BISTRO I j LOADING ZONE, GREAT ROOM 1002 "RAG ' 5 VERTICAL MIN I RAG J CLR114" S10 6 S10 1001 i 1007A 1007B F 1�; 1 y �I I o o VgST• o 60"CLR 'A!. 11 j o 1 00 ` ii FRAMING OMEN'S m m - -Lj WALL BELOW- 6" o RR i o - 009A d 2 0 0 ; g'_p" 4 iP - +�� 1006 BEVERAGE KITCHEN I -J A4.52 N j - I - - I -- -- 13 e �� - -I �4 o O ' i -- -- A1.20 R 1010 I 1005 -- FAMILY ROOM I =--T 1PAINT, TYP L - - - - -- - - - - M MIN C R 60" CLR O I I MEN S I •a ' I � C� P-T-�O I I v 11 Co I 1020A - MAIL PAINT, TYP _ 1 _ A1.20 _---- 1 1 2A / 1 1003 0 I 1�� 0 DISCOVERY/ l M ELEV. 0 41TING '- ' I I `" L -IZC)NF. 6' 9" 4 o I 1 6` 8 � A6.21 W Z I oo I I - - - - - - -- 1012 l7 o USINESS OF�FIC 1 I •••••••�K-TYPE FIRE O '''''''''''' EXTINGUISHER M10 N n 25' 91/2" ® CD o- - - - -� 1� I 1027 02i1 % 102 ELFV 'I::::: 'k6 ::E::_.::: 22'-0" MIN ACCESS AISLE I I a, 1027 TYP �DNI SALES MGR __= M _ W - o - - - A1120 o ' R 10 102 1023 1019B 1019A -1 20------------- ' �- I STAIR - 3 N � I i I �1026 - RR � J 1017B - I 101 -- ACCESSIBLE ROUTE OF TRAVEL i I 0 1023 1019A J I -'--- 6 5.2 _ _ 1 6 1 ----- - 10 9B 175 A6.03 * 0 1 1 I =I 1018 RECEIVING 2/o MAX CROSS SLOPE @ ,,, 102E O ACCESSIBLE STALLS AND , EMPLOYEE 1017 CORRIDOR I TRASH 7 2K6. ROUTE OF TRAVEL I I 10.0 a 024 OF 1 1016 1015 A6.22 1 /� I ' LOUNGE 1018 1017C ' ' 0 101E o - - - - Vim\ I 10- _ 1019 - °° TRASH EXEC DIR. SALES MGR i 102E 1024 . _ I MOP SINK COLLECTION z l O o I I / LOAD I N 6 it I � � � 95'-1 5/8" 0 o- - - - - - J [No Slope] , oN I AREA TO K5.2 18 0 , 14'- 6 1/44 3 5 IQ�I PUS RECEIVE 2 6 1 L a I VAN ACCESSIBLE PAINT TYP ,i D , - A4.51 TRAFFIC 2 �. o - --------- - QB °� 4' 6" 4'-21/4" COATING D 3Bg. 1 8' 6 8 6 �0 8 6" Q x z o TY 21 00 4 = 0 4 1 22' 13/4" o 4 i::::.:.::.::.:.:.::::.::.:.:.:.:>::.:.:.:.: A6.03 "' z N o A6.03 .....:.:.:.:.:. A6.02J N , .................................. X. 0 0 ------------ ---- --- NO SLOPE 1 6 i o THIS AREA _ , N 1040 Z ::::::::: L3'� .1 1 1 O I :::::::I.:::::::::::::::::::.:: a :.:.:.:.:.:.:................. ............... 2 1 1 1J............ ....................... . GUARD RAIL @ 19'-2" SLAB EDGE / - - - - - - - - - � BOLLARD j 55 7 M K3.1 T- - - - 18'-0" I 2 IA4.01 °O DN 5.2 6 B4.2 5.2 3 8 3G 1 131121 O i N 3.5 MECHANICAL I 1032 --- Co I 1 1 CD 1`11 3.5 8'-6" 8'-6' 8'-6" 8'-6" " " 8'-68'-6 FO C NC, j z 3B 8.1 OII O I ILLI i ----- ----- --- _------_ ---I ---- _------- _-------_-------_--------_-------_---- _ - ------ _ = 23' - 7" 13 I LEVEL 1 1 /8" = 1'-0" 131121 � z I I I I I N 1 1 I 9'-0" 9'-0" 9'-0" 9'-0" 25'-6" 0 0 O O 0 O 0 I I - G 1 A3.12 2 A4.51 64.1 3 8 25- 41 /4" 1 m CLR O Of v GENERATOR o _ 1031 � DOWNSPOUT --------------- I I I FO SHTG irr N r, o io TRASH TAGING 17 1n 3 A6.01 TRANSFORMER- - - ---------- -- zl 0 O GENERAL NOTES - FLOOR PLANS 1. REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK. 2. PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS BASIS OF DESIGN. 3. REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. 4. SEE SHEETS A0.1 1 & A0.21 FOR WALL ASSEMBLIES. 5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS. 6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.20 FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. ❑ 7. REFER TO ENLARGED UNIT PLANS (A5.21-A5.25 SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT 8. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES. 9. NOTES TO ALIGN ARE TO FACE OF FINISH, UNO. 10. DIMENSIONS ARE TO GRIDLINE, FACE OF (FO) CONCRETE, FO MASONRY, FO FRAMING AT EXTERIOR WALLS, FO STUD @ PARTITIONS, CENTER LINE OF DEMISING WALLS, DOORS AND WINDOW OPENINGS, UNO. 11. CLOSET DOORS AND OPENINGS ARE CENTERED ON THE CLOSEST WALL, UNO. DEPTH MAXIMUM INSIDE OF CLOSET IS 24", UNO. 12. CORRIDORS TO BE 6'-0" MINIMUM CLEAR, TYP. 13. CORRIDOR HANDRAILS SEE SHEET Al1.02 FOR DETAILS 9/10 14. SEE EXTERIOR ELEVATION SHEETS A3.11-A3.12 FOR EXTERIOR WINDOW TAGS KEY NOTES - PARKING LEVEL FLOOR PLANS OSTRUCTURAL COLUMN TO RECEIVE CHAMPFER EDGE TREATMENT, SEE DETAIL 12 / A0.41 2O ELECTRIC VEHICLE CHARGING STATIONS 0 ELECTRIC VEHICLE CHARGING STATIONS - FUTURE 4O BICYCLE RACK; 10 STALLS TOTAL, 5% TO BE ACCESSIBLE 5O COLUMN TO BE FINISHED WITH WALL ASSEMBLY 9M.2 Ln O r, 00 CD N 4 0 �12 �I N o PROJECT I F N 0 G Plan set for Smoke Control only. 9281 OOF 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. O O 00 z v) 0 Z z O� G� Q z L.L O z OJ Lu Lu lc:� p z O V 1 CD � o O� N O N CD 1 o O O Z = � N N z w Q o_ REVISION DATE REASON FOR ISSUE 1 06.18.21 Addendum #01 2 07.6.21 Addendum #02 A 08.20.21 City Comments #01 B 12.18.21 City Comments #02 4 01.03.22 Addendum #03 RE S U B May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT LEVEL 1 FLOOR PLAN CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 D 2 3 4 5 6 7 8 T c0 12 CD 12'-5 5/8" 14'-4 1/2" 6-2" 13'-0" 18'-6" 23'-3 1/2" 28'-6" 27'-3 1/2" 13'-8 3/4" 9'-5 3/4" 23'-7" A.02 I SEE FOR CANOPY PLAN 3 1 1 1 1 = 1 A4.52 1 A4.52 A4.01 A4.51 A4. 2 Ln 5,41 - - - - ---�-----------------0 ------------ ------ ------ -----------------------------I --------------A3.11 ---------------------- - -------t`.5-tt2"- ------------------------------- ---- -- 13'-6" 4'-6" 8'-11" j 7' 11/2" 2 1' 7" 6' 1 5' 7" T _ 9" 1 T _ 0„ C ' 1 8" 3' -11 3/4" I 1 101 /2" 1 ' - 0 1 /2" i I I 21 /2" 3 6" 3 2 I I FO SHTG _ L 5G ❑ 2 1.51 IL-C3 IL-Cl (TYPE A) z IL-B5 IL-B1 z IL-B6 IL-B1 J o ❑ 218 216 Q 214 212 J O 210 208 FF'Q� I I I J I �I I ❑ 1 L L j ❑ - El C�0 Q, CEO o � I I °° ° ° sIM 6B 1 CORRIDOR -- ---------- 2100 A5.12 - - 005 ' �� I - ' ILL 1:1 I STO R. °7 � I I '40 ❑ Zoos - STOR.Ll--07 - - - - o� ❑� _ ' I L- B 1 2004 00 3 m - 1�- - i ❑111:1 Lj A4.51 ELEV. WAITING 01 �I I I- ❑ ' 2000 5 003 i I I A6.21 ELEC/IDF IANo3 71�I 00 I I L-C4 121B6 o 2002 66.1 i IDF/ELEC 213 0 I --------- 2006 I 0 __-- 2 6 6B.1 1 6 ` -- - ---------- ::::::::: 3 ' A4.02 I = a I I 1 L- ❑ L-A2 222 0 I ¢o ::;:;:;G ' 002 � II NI I 01 LL ------------------------ - 5- 11 1 /16" Fa FO SHTG JLn I L-C3 206 GENERAL NOTES - FLOOR PLANS 1. REFER TO SHEETA0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK. 2. PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS BASIS OF DESIGN. 3. REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. 4. SEE SHEETS A0.11 & A0.21 FOR WALL ASSEMBLIES. 5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS. 6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.20 FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. 7. REFER TO ENLARGED UNIT PLANS (A5.21-A5.25 SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT 8. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES. 9. NOTES TO ALIGN ARE TO FACE OF FINISH, UNO. 10. DIMENSIONS ARE TO GRIDLINE, FACE OF (FO) CONCRETE, FO MASONRY, FO FRAMING AT EXTERIOR WALLS, FO STUD @ PARTITIONS, CENTER LINE OF DEMISING WALLS, DOORS AND WINDOW OPENINGS, UNO. 11. CLOSET DOORS AND OPENINGS ARE CENTERED ON THE CLOSEST WALL, UNO. DEPTH MAXIMUM INSIDE OF CLOSET IS 24", UNO. 12. CORRIDORS TO BE 6'-0" MINIMUM CLEAR, TYP. 13. CORRIDOR HANDRAILS SEE SHEET A11.02 FOR DETAILS 9/10 14. SEE EXTERIOR ELEVATION SHEETS A3.11-A3.12 FOR EXTERIOR WINDOW TAGS 15. ALL CORRIDOR AND UNIT DEMINSING WALLS TO BE 2X6 INTERIOR WALL ASSEMBLY '6B.1I U.N.O. KEY NOTES - FLOOR PLANS ❑ STRUCTURAL COLUMN TO RECEIVE CHAMPFER EDGE TREATMENT, SEE DETAIL 12 / A0.41 O2 STRUCTURAL COLUMN TO RECEIVE 1/2" FURRING AND (1) LAYER OF 5/8" TYPE X GYPSUM ON TAGGED SIDES 2A STRUCTURAL COLUMN TO RECEIVE 1/2" FURRING AND (1) LAYER OF 5/8" TYPE X GYPSUM ON ALL SIDES O3 STORAGE LEVER TO BE BETWEEN 15"- 48" A.F.F., TYP. ��o B ! L, ! �c: ----2----- fV A4.52 �o p ' N 25'-8 3/8" v N - - E o IL-05 (TYPE A) � 204 I o ! I --- ------ 6DI - ° IL-B2+DEN 11' 8" -' [o]- 1 6. TRASH M 2 101/2" 5'-7" 5'-11" - j A3.12 I 3 9" 9' 11 " L 8 2001 0 - Q A6.03 I � C 2 1.5 0 3 18'-6" IL-A1 (TYPE A) , L9 m I o _ 203 5G i 2 1.5 N � � ❑ ❑ � I N � Q 1 COURTYARD A3 13 0 I � A3.13 ❑ I - IL-131 5G ® IL-B5 O N 224 -.0 2 .5 201 IL-63 (TYPE A) I PLEASE SEE PLAN FOR q A3 12 o ° 4 i CANOPY N TYP - - - - °O - A3.13 - - - - DETAILS ................. o 3 _ u, IL-B2 71 .......... I A5.41 A6.02 F N i i m V. 0 Lfl SEE FOR C 6'�'�.�'.'.:'.:�'.:'.:'�::�:�:�:�: : ' ' : ' .............. ... 7' 7" 5' - 4" 91 /2" T -10" 9' 5" 5' - 11 " T - 8" ;.;.......................... ...........:: . DETAILS AID N••••••;; 01 ❑ lei..... PLANS A5.41 , ......:::C:::::::• :; :;;.• •. .......... T.t- J ....... ----- -- 1 Q _ A6.01 � 13K 21 i o j160 N - � K I I ° 2 ❑ ° ° ° ° - ° A4.01 o ' QO ° QO � Op Op 0� Op Op 0� I ❑ , ' ❑ ❑ ❑ ❑ ❑ ❑ o rq Q 6B.1 I I N IL-C2 IL-135 11 6 IL-132 IL-136 IL-136 IL-136 IL-136 226 228 230 232 I L B6 6113.1 236 238 240 34 1 6 0 ! o FO SHTG 1FO SHTG ' -- � I I I I I I -- 110 73� 8'- 61 /2" 6'- 0" 5' - 01 /2" 1 7 3/4" 4„ 3/16" T - 01 /4" 1' - 0" 5' - 61 /2" 9,-0" 6' 0" L �n 4 5 0 _ 1 �_ 6 �� �_ " 5'-0" 6' -0" 5'-11" I ' 01 11' - 5" 4" 1111 1/2" 2'- 5 1 /2" 11' - 01 /2" 10' - 7 3/4" - - J - - - - - - - - 2 - GUTTER - - -1 I - -----------�-- =-------------�--------------------------------------------------------------------------------------------------------------------------------- A4.51--+----------------------------------+--------------------------------------------------------- {----------------� M °i 1 A3.12 LEVEL 2 1/8" = 1'-0" L F7 71 Plan set for Smoke Control only. PROJECT 9281 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 C ANKROM MOISAN ARCHITECTS, INC. (V O z 0 Z z O v, 0 V W 0 z z � o � OJ o 0 z O ; �00 J00 o O� N N o 0 J o 0 J m O 2 Z ON ~ Q � z o_ N aw REVISION DATE REASON FOR ISSUE 1 06.18.21 Addendum #01 3 08.10.21 Acc Review #01 A 08.20.21 City Comments #01 4 01.03.22 Addendum #03 C 02.08.22 City Comments #03 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT LEVEL 2 FLOOR PLAN CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 1 2 3 4 T 6 7 8 9 10 12 13 I I I I I I I 12'-5 5/8" 14'-4 1/2" 6-2" 13-0" 18'-6" 23-3 1/2" 28'-6" 27'-3 1/2" 13'-8 3/4" 9'-5 3/4" 23-7" CLR 3 1 1 1 1 A4.52 A3.11 A4.52 A4.01 A4.51 <( <( ❑---------------------------------------------------- ------------------------------------------ -------------------------- -- -------------------------------------------------------------------------------------------------------------------------- - T-93/4" ❑ 10'-6" 13'-6" 4'-6" 5'-10" l7 I T-11/2" 7'-9" 3-0" 5'-11" 2' 0 3/8" 1 ' 7" 6' 1 " 6' - 0" 6' - 51 /2" 5' - 7" C T - 7" O 1 ' - 01 /2" 3' - 21 /8", � I LL ❑ 21 /2" 10 1 /2" 3' 6" -11 3/4" I FO SHTC FO SHTG I I Co 1 6.3 ❑ M IL-C3 O IL-Cl IL-B5 IL-B1 IL-B6 2 5G IL-B1 1 5.5 _ 318 316 314 312 310 308 ❑ - ❑ - ❑ - - - ❑ 266 z �o z z 66.1 - I LL ❑ J J o 1 6 1 L-C3 ' Q ¢ Q LL 306 I � I I I L ❑ j El - cm I , a❑I I I ❑� 1 �,� -- I I I ° o o ALIGNIC) - ❑ o ° - - 11: 1 r--ij SIM 6B.1 - F -1 1 1 1 CORRIDOR 6 1 2 - A5.12 3100 �, A4.' r - ---E ---------- _ k 3005 - - i J 6B1 - - 1 6.❑ 3004 _ co II I STOR. ❑ � I I 6B.10, F I L 3005 1 6 STO R. -❑ o � LEV. WAITING I � I T-1 ❑❑ ❑ I A4.51 IL-B1 ❑ 6 LkN 03 o I j 320 I A6.21 0 03 O I L-Al j 3 06 OF F I I L-C4 I L- B7 I I 304 3006 313 311 --- -- I I � I I FB A IL-A2 - - --LV - 1 ELEV - ELEC/IDF IL-B2 + DEN I I 1 5.5 322 Q I -------------- G 3002 d;6'1 7/8' 323 - N A3.12 j ALIGN 1 5.5 SIM 16D.1 3 01 CD 9'-11" 101/2" 11'-8" 5' 11" 6.4 _ j 2 5G 2 8 2 LZ 11\/ Q F1 CD 9 A5.12 Q 3 C o A3.13 o j in - - - ° N I L-Al Le 303 I 00 5G - - - - - - - - _ - - - - ° t 2 1.5 _ ° o2 0 I, I _ IL-B1 5G - 1 2 ❑ 324 ❑ 2 .5 _115.5 A3.13 A3.13 INV IL-B2 1 ❑ IL-B3 1 I 301 302 GENERAL NOTES - FLOOR PLANS 1. REFER TO SHEETA0.01 FOR'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK. 2. PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS BASIS OF DESIGN. 3. REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. 4. SEE SHEETS A0.11 & A0.21 FOR WALL ASSEMBLIES. 5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS. 6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.20 FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. 7. REFER TO ENLARGED UNIT PLANS (A5.21-A5.25 SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT 8. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES. 9. NOTES TO ALIGN ARE TO FACE OF FINISH, UNO. 10. DIMENSIONS ARE TO GRIDLINE, FACE OF (FO) CONCRETE, FO MASONRY, FO FRAMING AT EXTERIOR WALLS, FO STUD @ PARTITIONS, CENTER LINE OF DEMISING WALLS, DOORS AND WINDOW OPENINGS, UNO. 11. CLOSET DOORS AND OPENINGS ARE CENTERED ON THE CLOSEST WALL, UNO. DEPTH MAXIMUM INSIDE OF CLOSET IS 24", UNO. 12. CORRIDORS TO BE 6'-0" MINIMUM CLEAR, TYP. 13. CORRIDOR HANDRAILS SEE SHEET Al1.02 FOR DETAILS 9/10 14. SEE EXTERIOR ELEVATION SHEETS A3.11-A3.12 FOR EXTERIOR WINDOW TAGS 15. ALL CORRIDOR AND UNIT DEMINSING WALLS TO BE 2X6 INTERIOR WALL ASSEMBLY'6B.1' U.N.O. 0 0 m Ln a N v -- --@ N � �0 U N 7� � o N m I L-C2 I I L-B5 I ��� I I L-B2 I I L-B6 I - 6 1 IL-B6 IL-B6 IL-B6 j 326 328 330 332 334 336 338 340 I I I I I o I I IF MF FO SHTG -1 MF FO SHTG ❑ - 1 5'- 01 /2" 7 3/4" 4" V 11 �� 1 _ 1, _ �� N 31 /2 3 9 0 6 0 8' - 61 /2" 6' - 0" �I 1 r 6' 71 /4" 5'- 61 /2" 11' 01 /2" 10' - 7 3/4" 4" 11' -11 1/2" 4'- 6" 5'- 0" 5' -11 " I 2 1 ----------------------- ------------------------------L------------------------------------------------------------------------------------ A4.51---------------- ----------------� + - - -------------------------------------------------------------- 1 A3.12 LEVEL 3 1 /8" = 1'-0" 0 N 0 G 0 --0 0 0 0 KEY NOTES - FLOOR PLANS. ❑ STRUCTURAL COLUMN TO RECEIVE CHAMPFER EDGE TREATMENT, SEE DETAIL 12 / A0.41 ❑ STRUCTURAL COLUMN TO RECEIVE 1/2" FURRING AND (1) LAYER OF 5/8" TYPE X GYPSUM ON TAGGED SIDES 2A STRUCTURAL COLUMN TO RECEIVE 1/2" FURRING AND (1) LAYER OF 5/8" TYPE X GYPSUM ON ALL SIDES ❑ STORAGE LEVER TO BE BETWEEN 15"- 48" A.F.F., TYP. '^"A Plan set for Smoke Control TRUE only. 9Q81 r •p 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 C ANKROM MOISAN ARCHITECTS, INC. N z 0 L7 Z z OL,n 0 l/1 W z L.L O z OLU O z O LU > J00 (/) 00 8 O� O N O 0 O 1 O N = ItZ z � QN aws REVISION DATE REASON FOR ISSUE 1 06.18.21 Addendum #01 A 08.20.21 City Comments #01 C 02.08.22 City Comments #03 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT LEVEL 3 FLOOR PLAN CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 11 190' - 4 5/8" 12'- 5 5/8" 14' - 41 /2" 6' - 2" 13' 0" 18' - 6" 23' - 31 /2" 28' - 6" 27' - 31 /2" 13' - 8 3/4" 9' - 5 3/4" 12 13 23' - 7" GENERAL NOTES - FLOOR PLANS 1. REFER TO SHEET A0.01 FOR 'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK. 2. PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS BASIS OF DESIGN. 3. REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. 4. SEE SHEETS A0.11 & A0.21 FOR WALL ASSEMBLIES. 5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS. 6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.20 FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. 7. REFER TO ENLARGED UNIT PLANS (A5.21-A5.25 SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT 8. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES. 9. NOTES TO ALIGN ARE TO FACE OF FINISH, UNO. 10. DIMENSIONS ARE TO GRIDLINE, FACE OF (FO) CONCRETE, FO MASONRY, FO FRAMING AT EXTERIOR WALLS, FO STUD @ PARTITIONS, CENTER LINE OF DEMISING WALLS, DOORS AND WINDOW OPENINGS, UNO. 11. CLOSET DOORS AND OPENINGS ARE CENTERED ON THE CLOSEST WALL, UNO. DEPTH MAXIMUM INSIDE OF CLOSET IS 24", UNO. 12. CORRIDORS TO BE 6-0" MINIMUM CLEAR, TYP. 13. CORRIDOR HANDRAILS SEE SHEET A11.02 FOR DETAILS 9/10 14. SEE EXTERIOR ELEVATION SHEETS A3.11-A3.12 FOR EXTERIOR WINDOW TAGS 15. ALL CORRIDOR AND UNIT DEMINSING WALLS TO BE 2X6 INTERIOR WALL ASSEMBLY'6B.1' U.N.O. LEVEL 4 1/8" = 1'-0" PROJECT KEY NOTES -FLOOR PLANS lO STRUCTURAL COLUMN TO RECEIVE CHAMPFER EDGE TREATMENT, SEE DETAIL 12 / A0.41 2O STRUCTURAL COLUMN TO RECEIVE 1/2" FURRING AND (1) LAYER OF 5/8" TYPE X GYPSUM ON TAGGED SIDES 2A STRUCTURAL COLUMN TO RECEIVE 1/2" FURRING AND (1) LAYER OF 5/8" TYPE X GYPSUM ON ALL SIDES OSTORAGE LEVER TO BE BETWEEN 15"- 48" A.F.F., TYP. 11 J Plan set for Smoke Control only. 9281 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 C ANKROM MOISAN ARCHITECTS, INC. Q0 (V O 00 M z LAI 0 Z z O 0 V w o z LL O z OJ o O 0 z O ; J00 �00 o O� O N O 1 0 co = Z ON 4t z � QN aws REVISION DATE REASON FOR ISSUE 1 06.18.21 Addendum #01 A 08.20.21 City Comments #01 C 02.08.22 City Comments #03 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT LEVEL 4 FLOOR PLAN CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 h A2*04 C ' 1 /8" = V-0" 1 2 3 4 5 6 7 8 9 10 12 13 01 12'- 5 5/8" le 14' - 41 /2" 6'- 2" 13'- 0" 18' - 6" 23' - 31 /2" 28' - 6" le 27- 31 /2" 13'- 8 3/4" Of 9' - 5 3/4" 01 23' - 7" A I GENERAL NOTES - FLOOR PLANS 1. REFER TO SHEET A0.01 FOR'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK. 2. PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS BASIS OF DESIGN. 3. REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. 4. SEE SHEETS A0.11 & A0.21 FOR WALL ASSEMBLIES. 5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS. 6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.20 FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. 7. REFER TO ENLARGED UNIT PLANS (A5.21-A5.25 SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT 8. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES. 9. NOTES TO ALIGN ARE TO FACE OF FINISH, UNO. 10. DIMENSIONS ARE TO GRIDLINE, FACE OF (FO) CONCRETE, FO MASONRY, FO FRAMING AT EXTERIOR WALLS, FO STUD @ PARTITIONS, CENTER LINE OF DEMISING WALLS, DOORS AND WINDOW OPENINGS, UNO. 11. CLOSET DOORS AND OPENINGS ARE CENTERED ON THE CLOSEST WALL, UNO. DEPTH MAXIMUM INSIDE OF CLOSET IS 24", UNO. 12. CORRIDORS TO BE 6-0" MINIMUM CLEAR, TYP. 13. CORRIDOR HANDRAILS SEE SHEET A11.02 FOR DETAILS 9/10 14. SEE EXTERIOR ELEVATION SHEETS A3.11-A3.12 FOR EXTERIOR WINDOW TAGS 15. ALL CORRIDOR AND UNIT DEMINSING WALLS TO BE 2X6 INTERIOR WALL ASSEMBLY'6B.1' U.N.O. 2 A3.11 KEY NOTES - FLOOR PLANS OSTRUCTURAL COLUMN TO RECEIVE CHAMPFER EDGE TREATMENT, SEE DETAIL 12 / A0.41 2O STRUCTURAL COLUMN TO RECEIVE 1/2" FURRING AND (1) LAYER OF 5/8" TYPE X GYPSUM ON TAGGED SIDES 2A STRUCTURAL COLUMN TO RECEIVE 1/2" FURRING AND (1) LAYER OF 5/8" TYPE X GYPSUM ON ALL SIDES OSTORAGE LEVER TO BE BETWEEN 15"- 48" A.F.F., TYP. Plan set for Smoke Control PROJECT Only. 9281 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 C ANKROM MOISAN ARCHITECTS, INC. O (V O 00 M z LAI 0 Z z O 0 V w o z z LL O OJ o O 0 z O ; �00 J00 o O� O N J o Oco Z N z Of � QN aws REVISION DATE REASON FOR ISSUE 1 06.18.21 Addendum #01 A 08.20.21 City Comments #01 C 02.08.22 City Comments #03 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT LEVEL 5 FLOOR PLAN CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 1 2 5 6 7 8 9 10 12 13 3 4 12'-5 5/8" 14'-4 1 /2" 6'-2" 13-0" 18'-6" 23-3 1 /2" 28'-6" 27'-3 1 /2" 13'-8 3/4" 9'-5 3/4" 23-7" GENERAL NOTES - FLOOR PLANS 1. REFER TO SHEET A0.01 FOR'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK. 2. PRIOR TO FRAMING VERIFY THAT FINAL APPLIANCE AND PLUMBING FIXTURE SIZES/CLEARANCES MATCH THOSE USED AS BASIS OF DESIGN. 3. REFERENCE SLAB PLANS FOR CONCRETE WALL LOCATIONS, UNO. COORDINATE WITH STRUCTURAL DRAWINGS. 4. SEE SHEETS A0.11 &A0.21 FOR WALL ASSEMBLIES. 5. SEE SHEET A0.41 FOR TYPICAL FRAMING AND ACOUSTICAL DETAILS. 6. SEE FIRE/LIFE SAFETY SHEETS BEGINNING ON G2.20 FOR LOCATIONS OF FIRE EXTINGUISHER CABINETS. 7. REFER TO ENLARGED UNIT PLANS (A5.21-A5.25 SERIES) FOR DETAILED INFORMATION WITHIN EACH RESIDENTIAL UNIT 8. REFER TO STRUCTURAL DRAWINGS FOR COLUMNS, SHEAR WALL AND BEAM SIZES. 9. NOTES TO ALIGN ARE TO FACE OF FINISH, UNO. 10. DIMENSIONS ARE TO GRIDLINE, FACE OF (FO) CONCRETE, FO MASONRY, FO FRAMING AT EXTERIOR WALLS, FO STUD @ PARTITIONS, CENTER LINE OF DEMISING WALLS, DOORS AND WINDOW OPENINGS, UNO. 11. CLOSET DOORS AND OPENINGS ARE CENTERED ON THE CLOSEST WALL, UNO. DEPTH MAXIMUM INSIDE OF CLOSET IS 24", UNO. 12. CORRIDORS TO BE 6'-0" MINIMUM CLEAR, TYP. 13. CORRIDOR HANDRAILS SEE SHEETA11.02 FOR DETAILS 9/10 14. SEE EXTERIOR ELEVATION SHEETS A3.11-A3.12 FOR EXTERIOR WINDOW TAGS 15. ALL CORRIDOR AND UNIT DEMINSING WALLS TO BE 2X6 INTERIOR WALL ASSEMBLY'6B.1' U.N.O. 1/8" = 1'-0" PROJECT 01F Plan set for Smoke Control only. 9281 OF YA 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. Q0 (V O 00 M z V� 0 Z z O 0 V w o z z LL O OJ o O 0 z O ; �00 J00 o O� O N O 0 co 1 = 4t Z ON z � QN aws REVISION DATE REASON FOR ISSUE 1 06.18.21 Addendum #01 3 08.10.21 Acc Review #01 A 08.20.21 City Comments #01 C 02.08.22 City Comments #03 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT LEVEL 6 FLOOR PLAN CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 SHEET NUMBER A2*06 1 2 3 4 5 6 7 8 9 10 12 13 I I I I I I I I I I I I �I 3 A4.02 2 A3.12 I i I i i 12'-11 10'-0" MIN CLR FR ROOF PLAN 1 /8" = 1'-0" GENERAL NOTES - ROOF PLANS 1. REFER TO SHEET A0.01 FOR'PROJECT NOTES' APPLICABLE TO ALL PORTIONS OF THE WORK. 2. SEE SHEETA0.31 FOR HORIZONTAL ASSEMBLIES. 3. PROVIDE ROOFING MANUFACTURER'S STANDARD WALKWAY PADS BETWEEN ALL ROOF HATCHES, ROOF ACCESS DOORS, AND ROOFTOP EQUIPMENT AND AROUND PERIMETER OF ALL ROOFTOP EQUIPMENT. 4. PROVIDE POSITIVE ROOF SLOPE TO DRAIN AT MINIMUM SLOPE OF 1/4" PER FOOT MEASURED ALONG VALLEYS, UNLESS NOTED OTHERWISE. S. ROOF PENETRATIONS SHOWN ARE SCHEMATIC IN NATURE; COORDINATE ACTUAL SIZE, TYPE AND LOCATION OF EQUIPMENT. CURBS, AND ANY OTHER ROOF PENETRATIONS THAT MAY BE REQUIRED TO SUPPORT, SECURE OR FLASH ROOFTOP EQUIPMENT. 6. VERIFY AND COORDINATE SLAB PENETRATIONS INCLUDING SLEEVES & BLOCKOUTS AS REQUIRED FOR PLUMBING, MECHANICAL, ELECTRICAL, ETC. NOTIFY ARCHITECT OF ANY CONFLICTS OR DISCREPENCIES. 7. COMPLY WITH THE MOST STRINGENT OF SMACNA, NRCA OR MANUFACTURERS' REQUIREMENTS FOR FLASHINGS, COPINGS AND OTHER SHEET METAL CONSTRUCTION. 8. VERIFY ROOFING MANUFACTURERS MINIMUM REQUIREMENTS FOR LAPPING OF ALL MATERIALS. BRING CONFLICTS WITH ARCHITECTURAL DETAILS TO THE ATTENTION OF THE ARCHITECT PRIOR TO INSTALLATION. 9. REFER TO DETAILS FOR TOP OF PARAPET DATUMS. 10. SEE MEP AND LANDSCAPE DRAWINGS FOR ROOFTOP FURNISHINGS, EQUIPMENT AND PENETRATIONS. 11. VERIFY THAT BUILDING APPURTENANCES COMPRISE NO MORE THAN 20% OF BUILDING SURFACE AREA ABOVE THE MAXIMUM HEIGHT PER ECDC 16.06.020.B. ROOF PLAN LEGEND MECHANICAL EQUIPMENT & DUCTING, LOCATION ARE APPROXIMATE; GC TO COORDIANTE EXACT LOCATIONS IN FIELD (SEE MECH) Plan set for Smok ntrol PROJECT 9281 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. (V O 00 z 0 L7 Z z O 0 V w o z z LL 0 OJ o � 0 0 z O ; �00 J C) o O� O N J o 0co Z N z Of � QN aws REVISION DATE REASON FOR ISSUE 1 06.18.21 Addendum #01 2 07.6.21 Addendum #02 A 08.20.21 City Comments #01 4 01.03.22 Addendum #03 5 03.14.22 CONSTRUCTION SET RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ROOF PLAN CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 21AMA01, Anthology of Edmonds BASED ONIMC2015 OSA & LOAD CALCULATION TABLE COMMERCIAL VENTILATION SECTION NOTE: THIS INFORMATION IS FOR CALCULATION & CODE REVIEW ONLY. REFER TO EQUIPMENT SCHEDULES& PLANS FOR EXACT UNIT OPERATION AND BALANCING RQUIREMENTS. EQUIPMENT SERVING SPACE ROOM NAME & NUMBER AREA (SF) TOTAL COOLING (MgH) SENSIBLE COOLING (MBH) TOTAL HEATING (MBH) TOTAL OUTSIDE AIR (CFM) TOTAL EXHAUST AIR (CFM) ROOM TYPE DEFAULT OCCUPANCY CFM / PERSON OCCUPANT CFM CFM / SF SF CFM SUB CFMM AIR DISTRIBUTION CONFIGURATION Ez DS-1 P-Maint 233 18 Storage: Warehouse 0 0 0 0.06 13.98 14 warm air from ceiling>= 15°F above s.t., ceiling return 0.8 Total 233 18 DS-2 P-Laundry Y 399 105 Dr cleaners, Coin -operated laundries Y Y� P 7.98 7.5 59.85 0.06 23.94 84 warm air from ceiling >= 15°F above s.t., ceiling return g g 0.8 Total 399 105 DS-3 P-MDF 90 8 Storage: Warehouse 0 0 0 0.06 5.4 6 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 90 8 DS-4 P-Electrical 162 13 Storage: Warehouse 0 0 0 0.06 9.72 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 162 13 EWH-2 P-Vestibule 140 12 Public Spaces: Corridors 0 0 0 0.06 8.41 9 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 140 12 EF-G1 P-Generator 300 23 Storage: Warehouse 0 0 0 0.06 18 18 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 300 23 EF-P1 P-Parking 21309 1599 Storage: Warehouse 0 01 0 0.06 1279 1279 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 21309 1599 P-Corridor 127 10 Public Spaces: Corridors 0 0 0 0.06 7.62 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 P-Mech 175 14 Storage: Warehouse 0 0 0 0.06 10.5 11 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 P-Boiler 298 23 Storage: Warehouse 0 0 0 0.06 17.88 18 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 P-Stor 230 18 Storage: Warehouse 0 0 0 0.06 13.8 14 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 1 830 65 FC-1A 1-Great Room 614 24.7 24.7 54.8 219 Hotels, Motels, Resorts, Dormitories: Lobbies/prefunction 18.42 7.5 138.15 0.06 36.84 175 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Bistro 995 319 Food and Beverage Service: Dining rooms 10 7.5 75 0.18 179.1 255 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Mail 266 20 Public Spaces: Corridors 0 0 0 0.06 15.96 16 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Vest 111 9 Public Spaces: Corridors 0 0 0 0.06 6.66 7 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Elev Lobby 285 23 Public Spaces: Corridors 0 0 0 0.06 17.1 18 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-RR 2641 0 0 0 0 0 0 0 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 2535 590 FC-113 1-Reception 168 19.4 19.4 24.1 45 Office Buildings: Reception areas 5.04 5 25.2 0.06 10.08 36 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Business Office Mgr 111 13 Office Buildings: Office space 0.555 5 2.775 0.06 6.66 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Area RR's 115 13 Office Buildings: Office space 0.575 5 2.875 0.06 6.9 30 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Exec Dir 132 15 Office Buildings: Office space 0.66 5 3.3 0.06 7.92 12 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Discovery/Conf 190 53 Office Buildings: Conference rooms 6 5 30 0.06 11.4 42 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Sales Mgr g 109 13 Office Buildings: Offices ace g P 0.545 5 2.725 0.06 6.54 10 warm air from ceiling >= 15°F above s.t., ceiling return g g 0.8 1-Sales Mgr (s) 120 14 Office Buildings: Office space 0.6 5 3 0.06 7.2 11 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Employee Lounge 339 37 Office Buildings: Office space 1.695 5 8.475 0.06 20.34 29 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Admin 133 10 Public Spaces: Corridors 0 0 0 0.06 7.98 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Corridor 88 8 Public Spaces: Corridors 0 0 0 0.06 5.28 6 warm air from ceiling>= 15°F above s.t., ceiling return 0,8 Total 1505 221 FC-1C,1D 1-Dining 1443 25 25 57.1 888 Food and Beverage Service: Dining rooms 60 7.5 450 0.18 259.7 710 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 1443 888 FC-1E 1-Family Room 310 4.3 4.3 6.7 74 Office Buildings: Conference rooms 8 5 40 0.06 18.6 59 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 310 74 FC-1F 1-Kitchen 951 12.5 12.5 8.2 102 Office Buildings: Office space 4.755 5 23.775 0.06 57.06 81 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Beverage Station 154 18 Office Buildings: Office space 0.77 5 3.85 0.06 9.24 14 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Office 87 10 Office Buildings: Office space 0.435 5 2.175 0.06 5.22 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Dr Storage Y g 184 15 Storage: Warehouse g 0 0 0 0.06 11.04 12 warm air from ceiling >= 15°F above s.t., ceiling return g g 0.8 1-Trash Corridor 78 7 Public Spaces: Corridors 0 0 0 0.06 4.68 5 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Trash 62 5 Storage: Warehouse 0 0 0 0.06 3.72 4 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 1516 157 EWH-1 1-Riser 127 10 Storage: Warehouse 0 0 0 0.06 7.62 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 1705 172 1-Stor 175 14 Storage: Warehouse 0 01 0 0.06 10.5 11 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Trash Collection 596 45 Storage: Warehouse 0 0 0 0.06 35.76 36 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Mech 95 8 Storage: Warehouse 0 0 0 0.06 5.7 6 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 866 67 EF-P2 1-Parking+ Ramp 15101 1134 Storage: Warehouse 0 0 0 0.06 906.1 907 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 15101 1134 UH-1 1-Receiving 240 19 1Storage: Warehouse 0 0 01 0.06 14.4 15 warm air from ceiling >= 15°F above s.t., ceiling return 0,8 Total 285 23 FC-2 2-Corrdior/Elev Lobby 3486 18.5 18.5 18.6 1 263 Public Spaces: Corridors 0 0 0 0.06 209.2 210 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 2-Stor W 269 22 Storage: Warehouse 0 0 0 0.06 16.14 17 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 2-IDF/Elec W 82 7 Storage: Warehouse 0 0 0 0.06 4.92 5 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 2-Elec/IDF E 156 13 Storage: Warehouse 0 0 0 0.06 9.36 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 2-Stor E 131 10 Storage: Warehouse 0 0 0 0.06 7.86 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 2-Janitor 21 3 Storage: Warehouse 0 0 0 0.06 1.26 2 warm air from ceiling>= 15°F above s.t., ceiling return 0.8 2-Trash 1 431 41 1 Storage: Warehouse 01 01 01 0.061 2.581 3 warm air from ceiling >= 15°F above s.t., ceiling return 0,8 Total 1 1 41881 1 1 1 322 FC-3 3-Corrdior/Elev Lobby 3486 18.5 18.5 18.6 263 Public Spaces: Corridors 0 0 0 0.06 209.2 210 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 3-Stor W 269 22 Storage: Warehouse 0 0 0 0.06 16.14 17 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 3-IDF W 82 7 Storage: Warehouse 0 0 0 0.06 4.92 5 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 3-Elec/IDF E 156 13 Storage: Warehouse 0 0 0 0.06 9.36 30 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 3-Stor E 131 10 Storage: Warehouse 0 0 0 0.06 7.86 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 3-Janitor 21 3 Storage: Warehouse 01 01 0 0.06 1.26 2 warm air from ceiling >= 15°F above s.t., ceiling return 0,8 3-Trash 1 431 4 Storage: Warehouse 01 01 01 0.061 2.58 3 warm air from ceiling >= 15°F above s.t., ceiling return O,g Total1 1 41881 1 1 322 FC-4 4-Corrdior/Elev Lobby 3486 18.5 18.5 18.6 263 Public Spaces: Corridors 0 0 0 0.06 209.2 210 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 4-Stor (W) 269 22 Storage: Warehouse 0 0 0 0.06 16.14 17 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 4-IDF W 82 7 Storage: Warehouse 0 0 0 0.06 4.92 5 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 4-Elec/IDF E 156 13 Storage: Warehouse 0 0 0 0.06 9.36 30 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 4-Stor E 131 10 Storage: Warehouse 0 0 0 0.06 7.86 8 warm air from ceiling >= 15°F above s.t., ceiling return 0,8 4-Janitor 1 21 31 Storage: Warehouse 0 0 01 0.06 1.26 2 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 4-Trash 1 431 1 41 1 Storage: Warehouse 0 0 01 0.061 2.581 3 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total1 1 41881 1 322 FC-5 5-Corrdior/Elev Lobby 3486 18.5 18.5 18.6 263 Public Spaces: Corridors 0 0 0 0.06 209.2 210 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-Stor (W) 269 22 Storage: Warehouse 0 0 0 0.06 16.14 17 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-IDF (W) 82 7 Storage: Warehouse 0 0 0 0.06 4.92 5 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-Elec/IDF E 156 13 Storage: Warehouse 0 0 0 0.06 9.36 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-Stor E 131 10 Storage: Warehouse 0 0 0 0.06 7.86 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-Janitor 21 3 Storage: Warehouse 0 0 0 0.06 1.26 2 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-Trash 431 1 41 1 Storage: Warehouse 01 01 01 0.061 2.581 3 1warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total1 1 41881 1 322 FC-6A 6-Salon 344 4.3 4.3 6.7 268 Specialty shops: Beauty and nail salons 8.6 20 172 0.12 41.28 214 warm air from ceiling>= 15°F above s.t., ceiling return 0.8 Total 344 268 FC-66 6-Corrdior/Elev Lobby 3179 15.5 15.5 24.7 239 Public Spaces: Corridors 0 0 0 0.06 190.7 191 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 6-IDF (W) 29 3 Storage: Warehouse 0 0 0 0.06 1.74 2 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 6-Elec/IDF E 111 9 Storage: Warehouse 0 0 0 0.06 6.66 7 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 6-RR's 170 0 1 0 01 0 0 0 0 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 6-Trash 43 4 Storage: Warehouse 0 0 0 0.06 2.58 3 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 3532 255 RTU-1 6-Fitness 729 15.1 12.2 18.2 305 Sports and Amusement: Health club/aerobics room 10 20 200 0.06 43.74 244 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 729 305 RTU-2 6-Theater/Community 1035 16.9 15 19.8 267Y Hotels, Motels, Resorts, Dormitories: Multipurpose assembl 30 5 150 0.06 62.1 213 warm air from cell >= 15°F above s.t., ceiling return g g 0.8 Total 1035 267 MECHANICAL COMPLIANCE SUMMARY _015 \VSIi(' ('umplianx Form; for ('unnnareial Budding, including Group R'. R3 & R 1 over 3 stories and all RI Administered h\ 1'2021- NI. FA. All ncht, te.cn c.l I'ruji ct .\ \pplir:uu lulb 11"at ion Project Title Anthology of Edmonds - 2015 WSEC For Building Department Use: Date: h e1) 09. 21122 Project Address 21200 72nd Ave W Edmonds, WA 98026 :Applicant Name Aaron Prough Applicant Phone 208.493.0027 Applicant Email aproughL!deenginecring.net For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport(a:,wacnergycodes.com General (kcupanc) All Group R - 112, R3 & R4 over 3 storm and all RI General Building Use Type Multifamily. Residential Building Cond. floor Area 164,OW General Project Types New Building Ncw Building or Addition Mechanical Scope P Single Zone Systems & Equipment Multiple Zone Systems & Equipment Alteration Mechanical Scope Project Cond. Floor Area 164,000 Floors Above Grade 6 Compliance Method Compliance Method I - General Mechanical Project Description This will be a 7 story assisted living facility with I floor of parking below grade. 1echanical Compliance Scope and Method Project Type MecYaaieal Scope Economizer Exception(s) Applied? DOAS Ventilation Provided? Higher Equipment Option Applied? Efficiency OP PP Equipment Efficiency Compliance Verlilcation P COMPLIES COMPLIES New Building Single Zone Systems & Equipment No No Yk�s New Building Multiple Zone Systems & Equipment No Ycs Yes Additional Efficiency Credits Included (AEC) Higberequipment efficiency and fan FEG Dedicated outside air sxstem (DOHS) option Dues building include occupancy classifications requiring DOAS? Yes Dues project include DOAS equipment? Yes Based on project scope do TSPR requirements apply:' No Do all sxstems comply with Appendix D standard reference design or qualift for an exception to TSPR? No Scope & Space Conditioning NEW BUILDING - SINGLE ZONE SYSTEMS & EQUIPMENT Compliance Verification COMPLIES Scope & Space Conditioning NEW BUILDING - MULTIPLE ZONE SYSTEMS & EQUIPMENT Compliance Verification COMPLIES MECHANICAL LEGEND EQUIPMENT ® SUPPLY DIFFUSER dJ J J J J J FLEXIBLE DUCTWORK Z RETURN GRILLE LINED DUCTWORK Z EXHAUST GRILLE DEMO ROUND DUCTWORK BREAK �T THERMOSTAT TS TEMPERATURE SENSOR DUCTWORK BREAK SD SMOKE DETECTOR FM & DUCTWORK RISE CO CO2 SENSOR 11 El 1:16) DUCTWORK DROP L� MOTORIZED DAMPER SPIN -IN SUPPLY (WITH VOLUME BAROMETRIC DAMPER FLOW DAMPER) MANUAL VOLUME DAMPER. SPIN -IN RETURN/EXHAUST (WITH VOLUME DAMPER) HS COMBINATION SMOKE/FIRE DAMPER $� 45° SQUARE DUCT TAKE -OFF SA-- RA FROM SQUARE DUCT F�[ FIRE DAMPER 45° ROUND DUCT TAKE -OFF # SIX RA FROM SQUARE DUCT EQUIPMENT CALLOUT # 45° ROUND DUCT TAKE -OFF # Sly - RA FROM ROUND DUCT DETAIL CALLOUT TURNING VANE O TEMPERATURE GAUGE MITERED CORNER POINT OF CONNECTION RADIUS ELBOW �-� INTAKE OR EXHAUST DIRECTION OF AIRFLOW ABBREVIATIONS & DESCRIPTIONS AC AIR CONDITIONING HVAC HEATING, VENTILATING, AIR CONDITIONING AFF ABOVE FINISHED FLOOR KES KITCHEN EQUIPMENT SUPPLIER AHU AIR HANDLING UNIT KW KILOWATT BTU BRITISH THERMAL UNITS KWH KILOWATT HOUR BTUH BTU'S PER HOUR LAT LEAVING AIR TEMPERATURE CA COMBUSTION AIR CC COOLING COIL MAX MAXIMUM CFF CAP FOR FUTURE MCA MINIMUM CIRCUIT AMPS CFM CUBIC FEET PER MINUTE MOCP MAXIMUM OVERCURRENT PROTECTION CHWR CHILLED WATER RETURN MIN MINIMUM CHWS CHILLED WATER SUPPLY NC NOISE CRITERIA CLG CEILING NFPA NATIONAL FIRE PROTECTION ASSOCIATION CW COLD WATER NTS NOT TO SCALE DEG DEGREE OSA OUTSIDE AIR DIA DIAMETER PD PRESSURE DROP DB DRY BULB TEMPERATURE PH PHASE EA EXHAUST AIR PRV PRESSURE REDUCING VALVE EAT ENTERING AIR TEMPERATURE RA RETURN AIR RPM REVOLUTIONS PER MINUTE EER ENERGY EFFICIENCY RATIO RTU ROOFTOP UNIT ESP EXTERNAL STATIC PRESSURE SA SUPPLY AIR EWT ENTERING WATER TEMPERATURE SEER SEASONAL ENERGY EFFICIENCY RATIO FCO FLOOR CLEANOUT SFD/FSD COMBINATION SMOKE/FIRE DAMPER FD FIRE DAMPER SP STATIC PRESSURE FLA FULL LOAD AMPS SYM SYMBOL FLR FLOOR T&P TEMPERATURE AND PRESSURE FPM FEET PER MINUTE TEMP TEMPERATURE FT FEET TYP TYPICAL GA GAUGE GAO GRADE CLEANOUT UMC UNIFORM MECHANICAL CODE GPM GALLONS PER MINUTE UPC UNIFORM PLUMBING CODE HC HEATING COIL VTR VENT THROUGH ROOF HP HORSEPOWER V VOLTS IECC INTERNATIONAL ENERGY WB WET BULB CONSERVATION CODE W/ WITH GENERAL NOTES 1. PER WSEC C409.3.1, PROVIDE ENERGY USE MONITORING OF ALL EQUIPMENT USED TO PROVIDE HEATING, COOLING AND VENTILATION OF OCCUPIED SPACES. 2. SEE MECHANICAL SPECIFICATION SECTION 230593 (TESTING, ADJUSTING, BALANCING FOR HVAC) FOR COMMISSIONING REQUIREMENTS PER WSEC C408. 3. PER WSEC C103.6, MECHANICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY CLOSE OUT DOCUMENTS AND TRAINING OF OPERATIONS PERSONEL WHICH APPLY TO ANY MECHANICAL COMPONENTS, EQUIPMENT, AND SYSTEMS GOVERNED BY THE WSEC. 4. ALL DUCTWORK SHALL BE CONSTRUCTED AND SEALED PER 2015 IMC. ALL DUCTWORK SHALL BE LOW PRESSURE UNLESS NOTED OTHERWISE, PER WSEC C403.2.8.1. 5. SEE MECHANICAL SPECIFICATION SECTION 230700 (HVAC INSULATION) FOR DUCTWORK AND PIPING INSULATION REQUIRMENTS. HVAC SHEET LIST SHEET NUMBER SHEET NAME M0.0 HVAC COVER SHEET M2.0 HVAC PLAN - PARKING M2.1 HVAC PLAN - FIRST FLOOR M2.2 HVAC PLAN - SECOND FLOOR M2.3 HVAC PLAN - THIRD FLOOR M2.4 HVAC PLAN - FOURTH FLOOR M2.5 HVAC PLAN - FIFTH FLOOR M2.6 HVAC PLAN - SIXTH FLOOR M2.7 HVAC PLAN - ROOF M4.0 HVAC PLAN - ENLARGED UNITS M4.1 HVAC PLAN - ENLARGED UNITS M5.0 I HVAC SCHEDULES M6.0 HVAC DETAILS M6.1 HVAC DETAILS M6.2 HVAC KITCHEN DETAILS M6.3 HVAC KITCHEN DETAILS M6.4 HVAC KITCHEN DETAILS M6.5 HVAC KITCHEN DETAILS M6.6 HVAC KITCHEN DETAILS M6.7 HVAC KITCHEN DETAILS M6.8 HVAC KITCHEN DETAILS M6.9 HVAC KITCHEN DETAILS M6.10 HVAC KITCHEN DETAILS M6.11 HVAC KITCHEN DETAILS M6.12 HVAC KITCHEN DETAILS M6.13 HVAC KITCHEN DETAILS M6.14 HVAC KITCHEN DETAILS Plan set for Smoke Control only. tA �O OF WAS -O 41741 GISTER SS/ONAL 02/17/2023 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.di:engineering.net Phone:208.288.2181 Project:21 AMA01 N O 00 Cn Z 0 Z Z O= Q W o LL Z 0 0 Ld 0 3: Z 0 > > (� J Q J �_ 0 O-e 0 N _ 0 F- O Z m w � Z o U Q U � QN 0- REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 B 10-28-21 CITY COMMENTS #02 C 02-08-22 CITY COMMENTS #03 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT HVAC COVER SHEET CONSTRUCTION SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M0.0 c 7 1 HVAC PLAN - PARKING SCALE: 1/8" = V-0" 9 10 12 _ HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. HVAC KEYNOTES: 1. PROVIDE 18"x18" LOUVER IN DOOR. COORDINATE WITH ARCHITECTURAL. 2. ROUTE 4" DRYER EXHAUST FROM LAUNDRY ROOM TO EXTERIOR WALL. PROVIDE BOOSTER FAN DBF-1 AND DUCT CLEANOUT IN VERTICAL DRYER DUCT. TERMINATE AT EXTERIOR WITH VENT BOX. 3. PROVIDE CO AND NO2 SENSOR AT CEILING FOR PARKING GARAGE EXHAUST FAN (EF-P1) SPEED CONTROL. 4. MOUNT PARKING GARAGE VENTILATION FAN AS HIGH AS POSSIBLE. 5. ROUTE 3" SA DUCT UP TO FIRE RISER ROOM ABOVE, AND TERMINATE AT APPROXIMATELY 9'-0" AFF. 6. EXHAUST FAN IS INTENDED TO BE CEILING MOUNTED WITH MANUFACTURER'S VIBRATION ISOLATION KIT. Plan set for Smoke Control only. pF WA,g I -o 41741 GISTER� SS/ONAL 02/17/2023 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. v1ww. drengineerinn. net Phone:208.288.2181 Project:21 AMA01 N CD 00 M Cn Z 0 0 F___ Zz 0= >Q 0 W C 0 LL o 0 0 �LLJ Z O > > J Q J 0 o N _ _o CD*� H CD w m Z N U Q Q LU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 E 03-07-22 CITY COMMENTS #05 18 08-29-22 RFI#133 19 08-29-22 RFI#131 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT HVAC PLAN - PARKING CONSTRUCTION SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.0 c 1 2 3 4 5 6 7 8 9 10 12 13 I PARKING GARAGE 1039 I I I I I i I I 0 1 HVAC PLAN - 1 ST FLOOR SCALE: 1/8" = 1'-0" RG-2, 18" O 1150 CFM 9 46"x28" OSA V-22"x SA SD-1, 12"0 400 CFM I RG-2, 12"x12" E 400 CFM 4 EF 20 K2 6. SD-2, 8" O 100 CFM HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. HVAC KEYNOTES: 1. 14"x14" OSA UP IN MECHANICAL SHAFT ABOVE. PROVIDE FSD AS REQUIRED AT SHAFT PENETRATION. 2. 22"x20" OSA DUCT UP IN CHASE ABOVE. PROVIDE FIRE/SMOKE DAMPER AT CHASE WALL PENETRATION. 3. 34"x10" GREASE DUCT CONNECTION TO KITCHEN HOOD (BY KES). 4. 24"x12" OSA CONNECTION TO KITCHEN HOOD PLENUM (BY KES). 5. INSTALL GREASE DUCT PER 2015 IMC SECTION 506.3. DUCT SHALL BE MINIMUM GAUGE 18 STAINLESS STEEL. SLOPE DUCT BACK TO KITCHEN HOOD AT 1/4" PER FOOT. PROVIDE CLEANOUTS EVERY 20 FEET, AND WITHIN 10 FEET OF A CHANGE IN DIRECTION OVER 45 DEGREES PER 2015 IMC SECTION 506.3.8. PROVIDE ASTM E2336 APPROVED FYREWRAP ELITE DUCT WRAP OR APPROVED EQUAL. 6. PROVIDE HINGED WALL MOUNT FOR GREASE EXHAUST FAN. 7. PROVIDE FIRE/SMOKE DAMPER AT RATED WALL. PROVIDE ACCESS TO DAMPER. 8. PROVIDE CO AND NO2 SENSOR AT CEILING FOR PARKING GARAGE EXHAUST FAN (EF-P2) SPEED CONTROL. 9. PROVIDE MOTORIZED DAMPER ON THE RETURN AND OUTSIDE AIR DUCTS FOR ECONOMIZER OPERATION. 10. ROUTE 10" EA DUCT FROM TYPE II HOOD TO EXTERIOR WALL. SLOPE DUCT AT 1/4" PER FOOT BACK TO HOOD. 11. CONNECT TO GENERATOR EXHAUST SILENCER WITH A 6" STEEL FLUE, PER MANUFACTURER INSTRUCTIONS, AND ROUTE TO EXTERIOR WALL. PROVIDE MANUFACTURER'S WALL THIMBLE KIT FOR TERMINATION AT EXTERIOR WALL. 12. SEE KITCHEN EQUIPMENT DRAWINGS FOR ELEVATION VIEW OF COOKLINE EQUIPMENT AND REQUIRED CLEARANCES. 13. PROVIDE STAINLESS STEEL WALL FLASHING THAT EXTENDS 18" MINIMUM IN ALL DIRECTIONS BEYOND THE TYPE 1 HOOD. COORDINATE WITH ARCHITECTURAL AND KITCHEN DRAWINGS. 14. WALL CONSTRUCTION SHALL BE LIMITED COMBUSTABLE TYPE, WITH METAL STUD FRAME AND 5/8" GYPBOARD. COORDINATE WITH ARCHITECTURAL AND KITCHEN DRAWINGS. 15. 3" SA DUCT FROM BELOW. ROUTE TO EXTERIOR WALL AS SHOWN AND TERMINATE WITH VENT BOX AND INSECT SCREEN AT APPROX. 9'-0" AFF. 16. PROVIDE 36"x30" FRAMED OPENING IN CMU WALL FOR GENERATOR INTAKE AIR. PROVIDE METAL GRATE COVERING TO PROHIBIT ENTRY, VANDALISM, AND PESTS. 17. TERMINATE UNIT HEATER INTAKE COMBUSTION AIR AT THIS LOCATION WITH MANUFACTURER'S WALL VENT. 18. TERMINATE UNIT HEATER EXHAUST AIR AT THIS LOCATION WITH MANUFACTURER'S WALL VENT. 19. MOUNT EQUIPMENT ON THE WALL, AS HIGH AS POSSIBLE, WITH MANUFACTURER'S WALL MOUNT KIT. MAINTAIN MANUFACTURER'S CLEARANCES. Plan set for Smoke Control only. oy WA,g I -0 41741 ISTER� ss��NALww 02/17/2023 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.dcengineerinn. net Phone:208.288.2181 Project:21 AMA01 O N O 00 O p 0 z z_ O= >Q 0 W U) 0 LL z O2 O z O > > J Q J _� OT 0 i C O 0 CD*k F— CD LLI m z N U Q Q LU N U a REVISION DATE REASON FOR ISSUE 14 06-27-22 RFI#53 16 08-16-22 RFI#108 18 08-29-22 RFI#133 19 08-29-22 RFI#131 22 09-29-22 RFI#149 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT HVAC PLAN - FIRST FLOOR CONSTRUCTION SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.1 r ) 0 0 L ,3 D D 1 M4.1 3 M4.0 HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. 1 2 3 4 5 6 7 8 9 10 12 13 G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. 11 g 4 10 M4.0 M4.0 M4.0 M4.0 5 1 HVAC PLAN - 2ND FLOOR SCALE: 1/8" = V-0" --F 0 HVAC KEYNOTES: 1. 14"x14" OSA FROM LOWER LEVEL UP TO ROOF. 2. 26"x18" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 3. 14"x16" EA DUCT UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 4. 26"x16" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 5. PROVIDE FIRE/SMOKE DAMPER AT ALL SHAFT WALL/RATED WALL PENETRATIONS WITH ACCESS. 6. MECHANICAL CHASE FOR UNIT VENTING UP TO ROOF. SEE M4.0 FOR ENLARGED PLAN. 7. MOUNT RADIANT HEATERS ON THE BOTTOM OF CANOPY STRUCTURE AT A 45 DEGREE ANGLE. MAINTAIN MANUFACTURER'S CLEARANCES TO COMBUSTABLE MATERIALS. COORDINATE EXACT LOCATIONS WITH CANOPY STRUCTURAL 8. PROVIDE LOUVER L-4 FOR SMOKE CONTROL RELIEF ON THE ALTERNATE RECALL LEVEL 2. PROVIDE A CLASS 1 MOTORIZED DAMPER, FED WITH STANDBY POWER FROM THE GENERATOR, WITH OPEN/CLOSE INDICATOR SWITCHES FOR FIRE ALARM MONITORING. DAMPER SHALL FAIL OPEN. Plan set for Smoke Control only. <O pF WASI�/ r-b . 41741 <C/ Sl7 �ER����� N L 05/17/2023 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineerinq.net Phone:208.288.2181 Project:21 AMA01 N CD 00 M 0 0 Zz 0= < 0 W C 0 L,L O 0 0 > > J Q J 0 _ - o N 0 H CD w *� CDm Z N U Q QLU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 C 02-08-22 CITY COMMENTS #03 12-30-22 CCD 003 F 05-12/23 SMOKE CONTROL REVISIONS-ASI 009 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT HVAC PLAN - SECOND FLOOR CONSTRUCTION SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.2 c HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC 1 2 3 4 5 6 7 8 9 10 12 13 SCHEDULE ON M5.0 FOR DETAIL. HVAC KEYNOTES: 1. 14"x14" OSA FROM LOWER LEVEL UP TO ROOF. 2. 26"x18" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 3. 14"x16" EA DUCT UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 4. 26"x16" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 5. PROVIDE FIRE/SMOKE DAMPER AT ALL SHAFT WALL/RATED WALL PENETRATIONS WITH ACCESS. e"S I HVAC PLAN - 3RD FLOOR " I SCALE: 1/8" = 1'-0" Plan set for Smoke Control only. �� of wA s jj /� -0 41741 GISTER� SS/ONAL 02/17/2023 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. v1ww. drengineerinn. net Phone:208.288.2181 Project:21 AMA01 N CD 00 M Cn Z 0 C) F--- Z z 0= Q W C 0 LL O 0 0 > > J Q J 0 _ O N 0 H CD w m o U) Z N Q Q LU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT HVAC PLAN - THIRD FLOOR CONSTRUCTION SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.3 HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC 1 2 3 4 5 6 7 8 9 10 12 13 SCHEDULE ON M5.0 FOR DETAIL. HVAC KEYNOTES: 1. 14"x14" OSA FROM LOWER LEVEL UP TO ROOF. 2. 26"x18" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 3. 14"x16" EA DUCT UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 4. 26"x16" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER 5 6 AND LOWER HVAC PLANS FOR CONTINUATION. M4.1 M4.1 5. PROVIDE FIRE/SMOKE DAMPER AT ALL SHAFT WALL/RATED WALL PENETRATIONS WITH ACCESS. 8 M4.0 4D1 HVAC PLAN - 4TH FLOOR SCALE: 1/8" = 1'-0" L M Plan set for Smoke Control only. WAst�/ -0 41741 GISTER� SS/ONAL 02/17/2023 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. v1ww. drengineerinn. net Phone:208.288.2181 Project:21 AMA01 N CD 00 M Cn Z 0 0 Zz 0= Q W C 0 LL O 0 0 > > J Q J 0 _ o N 0 H CD w m o U) Z N Q Q LU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT HVAC PLAN - FOURTH FLOOR CONSTRUCTION SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.4 c ll 1 2 3 4 5 6 7 8 9 10 12 13 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 1 HVAC PLAN - 5TH FLOOR SCALE: 1/8" = 1'-0" 3 M4.1 HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. HVAC KEYNOTES: 1. 14"x14" OSA FROM LOWER LEVEL UP TO ROOF. 2. 26"x18" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 3. 14"x16" EA DUCT UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 4. 26"x16" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 5. PROVIDE FIRE/SMOKE DAMPER AT ALL SHAFT WALL/RATED WALL PENETRATIONS WITH ACCESS. Plan set for Smoke Control only. �� of wA -0 41741 GISTF SS/ONAL 02/17/2023 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions v1ww. drengineerinn. net Phone:208.288.2181 Project:21 AMA01 N CD 00 M Cn Z 0 0 Zz 0= >Q 0 W C 0 LL 0 0 0 Z O > > J Q J 0 _ - o N 0 CD*� H CD w m Z N U Q Q LU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT HVAC PLAN - FIFTH FLOOR CONSTRUCTION SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.5 HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED 1 2 3 4 5 6 7 8 9 10 12 13 RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. HVAC KEYNOTES: I I I I I I I I I I I I O t I I I I I I I I I I I M ,3 D ll L c c ()1 HVAC PLAN - 6TH FLOOR SCALE: 1/8" = V-0" 1. 14"x14" OSA FROM LOWER LEVEL UP TO ROOF. 2. 26"x18" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 3. 14"x16" EA DUCT UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 4. 26"x16" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 5. PROVIDE FIRE/SMOKE DAMPER AT ALL SHAFT WALL/RATED WALL PENETRATIONS WITH ACCESS. 6. EA DUCT PENETRATION UP THROUGH ROOF. SEAL WEATHER TIGHT AND TERMINATE WITH VENT CAP AND INSECT SCREEN. 7. ROUTE 3" EA DUCT DOWN TO PEDICURE CHAIR CONNECTION. SEE ARCHITECTURAL PLANS FOR DETAIL ON SALON EQUIPMENT. PROVIDE BALANCE DAMPER IN VERTICAL DUCT, SET TO 50 CFM MINIMUM PER IMC TABLE 403.3.1.1. 8. 18"x12" SA AND 26"x12" RA DUCT DROPS FROM RTU ABOVE. SEE HVAC ROOF PLAN FOR CONTINUATION. Plan set for Smoke Control only. OF WAS /� -o 41741 GISTF NAL 02/17/2023 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions v1ww. drengineerinn. net Phone:208.288.2181 Project:21 AMA01 N CD 00 M 0 0 Zz 0= >Q 0 W C 0 LL 0 0 0 �LLJ > > J Q J 0 _ o N 0 CD wH m Z N U Q Q LU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 B 10-28-21 CITY COMMENTS #02 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT HVAC PLAN - SIXTH FLOOR CONSTRUCTION SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.6 r U c 1 2 3 4 5 6 7 8 9 10 12 13 I 0 1 HVAC PLAN - ROOF SCALE: 1/8" = 1'-0" HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. HVAC KEYNOTES: 1. ROUTE DUCT DOWN THROUGH ROOF INTO STAIRWAY. SEAL PENETRATION WEATHER TIGHT. 2. ROUTE DUCT DOWN THROUGH ROOF INTO MECHANICAL CHASE. SEE LOWER FLOORS FOR CONTINUATION. 3. EXHAUST DUCT ROOF PENETRATION. SEE LOWER FLOOR FOR CONTINUATION. 4. PROVIDE 24"x24" CLASS 1 MOTORIZED DAMPER PER WSEC C403.2.4.3. BASIS OF DESIGN TO BE GREENHECK VCD-23 WITH OPTIONAL OCI SWITCH FOR MONITORING DAMPER POSITION. 5. ACTUATOR SHALL BE 120V, AND FAIL OPEN. PROVIDE 36"x36" CLASS 1 MOTORIZED DAMPER PER WSEC TIONAL OCI SWITCH FOR MONITORING DAMPER POSITION. ACTUATOR SHALL BE 120V, AND FAIL OPEN. Plan set for Smoke Control only. �O of wA,3 r-b' 41741 �<C/ '[STER��� \� ASS/0NAL NC� 05/17/2023 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineerinq.net Phone:208.288.2181 Project:21 AMA01 N CD 00 M 0 0 Zz 0= >Q 0 W C 0 LL 0 0 0 Z O > > J Q J 0 _ - o N 0 CD LL m CD*� Z N U Q QLU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 F 05-12/23 SMOKE CONTROL REVISIONS-ASI 009 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT HVAC PLAN - ROOF CONSTRUCTION SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.7 C C, 0 c C c r u L c c I 0 0 L a J D 0 DUCTLESS SPLIT HEAT PUMP SCHEDULE EQUIPMENT NO. SERVICE NOMINAL CAPACITY TOTAL COOL/HEAT (MBH) MAX CFM SEER/HSPF INDOOR UNIT OUTDOOR UNIT NOTES MCA MANUFACTURER MODEL WEIGHT VOLT.-PH.-CY. MCA MOCP MANUFACTURER MODEL WEIGHT DSO/DSI-1 MAINTENANCE 0008 1 TON 12.0 / 13.6 400 26.1 / 12.5 1.0 MITSUBISHI MSZ-FH12NA 29 LBS 208V-1PH-60 11 20 MITSUBISHI MUZ-FH12NHA 83 LBS 1,2,3,4,5,6,7 DSO/DSI-2 LAUNDRY 0004 1.5 TON 17.2 / 20.3 460 21.0 / 12.0 1.0 MITSUBISHI MSZ-FH18NA2 29 LBS 208V-1PH-60 16 20 MITSUBISHI MUZ-FH18NHA 124 LBS 1,2,3,4,5,6,7 DSO/DSI-3 MDF 0003 1 TON 12.0 / 13.6 400 26.1 / 12.5 1.0 MITSUBISHI MSZ-FH12NA 29 LBS 208V-1PH-60 11 20 MITSUBISHI MUZ-FH12NHA 83 LBS 1,2,3,4,5,6,7 DSO/DSI-4 ELECTRICAL 0002 1.5 TON 17.2 / 20.3 460 21.0 / 12.0 1.0 MITSUBISHI MSZ-FH18NA2 29 LBS 208V-1PH-60 16 20 MITSUBISHI MUZ-FH18NHA 124 LBS 1,2,3,4,5,6,7 ALTERNATE MANUFACTURERS: DAIKIN, FUJITSU, MITSUBISHI, SANYO NOTES: 1. PROVIDE UNIT WITH 7 DAY PROGRAMMABLE THERMOSTAT. 2. PROVIDE ALL ANCILLARY COMPONENTS REQUIRED FOR A FULL INSTALLATION. 3. INDOOR UNIT IS ELECTRICALLY CONNECTED TO AND POWERED BY THE OUTDOOR UNIT. ELECTRICAL REQUIREMENTS ARE COMBINED. 4. CAPACITIES ARE RATED AT ARI STANDARDS. 5. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCHES AND POWER WIRING. 6. PROVIDE MANUFACTURER'S CONDENSATE PUMP KIT AND ROUTE TO NEAREST LAVATORY/SINK TAILPIECE. 7. PROVIDE REFRIGERANT AND REFRIGERANT PIPING PER MANUFACTURER FOR FIELD CONDITIONS. FAN SCHEDULE EQUIPMENT NO. SERVES TYPE - MOUNTING CFM STATIC PRESS. (IN.WC.) MOTOR HEATING WATTS SONES WEIGHT MANUFACTURER MODEL CONTROL NOTES WATTS HP RPM VOLT.-PH.-CY. DBF-1 LAUNDRY - DRYER BOOSTER EXHAUST - DUCT 170 - 72 - - 120-1-60 - - - FANTECH DB4XT-705 PRESSURE SENSOR SWITCH 5 EF-1 UNIT RESTROOMS EXHAUST - CEILING 80 0.10 11.7 - 750 120-1-60 1300 1.5 20 LBS DELTA BREEZE DELTA RAD80 DUAL (LIGHT/HEAT) WALL SWITCH 1,2 EF-2 BOILER 0005 EXHAUST - CEILING 200 0.10 17.5 - - 120-1-60 - 1.0 15 LBS DELTA BREEZE PR0200 THERMOSTAT EF-3 LAUNDRY 0004 EXHAUST - CEILING 100 0.10 12.6 - - 120-1-60 - 1.5 15 LBS DELTA BREEZE GBR100H WALL SWITCH WITH HUMIDISTAT EF-4 PUBLIC RESTROOMS EXHAUST - CEILING 80 0.10 10.5 - - 120-1-60 - 0.8 15 LBS DELTA BREEZE GBR80 VIA LIGHTING SCHEDULE EF-5 TRASH ROOMS/STORAGE EXHAUST - CEILING 80 0.10 10.5 - - 120-1-60 - 0.8 15 LBS DELTA BREEZE GBR80 CONTINUOUS EF-6 SALON EXHAUST - ROOF 290 0.20 - 1/30 1550 120-1-60 - 4.9 50 LBS GREENHECK CUE-070-D VIA LIGHTING SCHEDULE EF-7 FITNESS EXHAUST - CEILING 300 0.10 41 - - 120-1-60 - 2.0 15 LBS DELTA BREEZE PR0300 VIA LIGHTING SCHEDULE EF-8 RESTROOM 1005 EXHAUST - CEILING 150 0.15 17.5 - - 120-1-60 - 1.0 15 LBS DELTA BREEZE PR0200 VIA LIGHTING SCHEDULE EF-G1 GENERATOR ROOM EXHAUST - SIDEWALL 4800 0.10 - 3/4 - 120-1-60 - 17.4 - GREENHECK SE1-18-429-A7X-QD GENERATOR CONTROL EF-K1 COM. KITCHEN HOOD TYPE I - SIDEWALL 4200 1.0 - 3 1434 208-3-60 - 24 200 LBS CAPTIVEAIRE DU180HFA KITCHEN HOOD 7,8 EF-K2 COM. KITCHEN HOOD TYPE II - SIDEWALL 400 0.5 - 0.25 1493 208-1-60 - 9.1 54 LBS CAPTIVEAIRE DU12HFA DISHWASHER HOOD EF-P1 MECH 0009 EXHAUST - FLOOR 16,000 / 10,700 0.25 - 5.63 720 208-3-60 - 80 850 LBS GREENHECK QEID-27-95 CONTINUOUS/SENSORS 6,8 EF-P2 MECH 1032 EXHAUST - FLOOR 12,000 / 8,000 0.25 - 5 1475 208-3-60 - 83 850 LBS GREENHECK QEID-22-80 CONTINUOUS/SENSORS 6,8 EF-P3 PARKING GARAGE CIRCULATION - CEILING 2100 - - - - 208-1-60 - - - GREENHECK GJI CONTINUOUS 3.OA MCA, 15A MOP EPF-1 ELEVATOR PRESSURIZATION - ROOF 11,500 0.75 - 3 - 208-3-60 - 500 LBS REVERSOMATIC RDD-33 FIRE ALARM NOTE 8, 9,10, 29 DEGREE BLADE ANGLE SPF-1 WEST STAIRWAY PRESSURIZATION - ROOF 5,000 0.5 - 1 - 208-3-60 - 450 LBS REVERSOMATIC RDD-24 FIRE ALARM NOTE 9, 10, 13 DEGREE BLADE ANGLE SPF-2 EAST STAIRWAY PRESSURIZATION - ROOF 5,000 0.5 - 1 - 208-3-60 - 450 LBS REVERSOMATIC RDD-24 FIRE ALARM NOTE 9, 10, 13 DEGREE BLADE ANGLE NOTES: 1. CONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR ALL CONTROLS. 2. SINGLE BLOWER VENTILATOR SHALL BE CEILING MOUNTED. FURNISH WITH CEILING GRILLE, AND BACKDRAFT DAMPER. 3. FAN SHALL BE CONTROLLED BY WALL THERMOSTAT, PROVIDED BY MECHANICAL CONTRACTOR, INSTALLED AND WIRED BY ELECTRICAL CONTRACTOR. 4. FURNISH WITH BACKDRAFT DAMPER. 5. MOUNT IN DESIGNATED AREA ABOVE DRYER. PROVIDE WITH ACCESS, BRACKET, AND HARDWARE. 6. PROVIDE WITH CO AND NO2 SENSOR EQUIPMENT AND ALL NECESSARY ACCESSORIES. 7. GREASE EXHAUST FAN SHALL BE INSTALLED TO PROVIDE 18" MINIMUM TO COMBUSTABLE MATERIALS. 8. FANS EXCEDING 1.0 HP SHALL HAVE AN ENERGY EFFICIENCY CLASSIFICATION OF MORE THAN FEG 71 PER AMCA 205, AND FAN OPERATION SHALL BE WITHIN 9. PROVIDE VARIABLE FREQUENCY DRIVE WITH FAN. BASIS OF DESIGN - DANFOSS VLT. 10. PROVIDE GREENHECK VCD-23 WITH 120V FAIL OPEN ACTUATOR AND OCI SWITCH. MAKE-UP AIR UNIT SCHEDULE (BY KES) SUPPLY FAN DIRECT GAS FIRED HEATING DX COOLING ELECTRICAL T.S.P. TOTAL SENSIBLE EQUIPMENT OUTSIDE (IN. FAN INPUT OUTPUT CAPACITY CAPACITY WEIGHT NO. SERVICE LOCATION AIR (CFM) CFM W.C.) RPM HP MBH 225 MBH EFF. % (MBH) 47.5 (MBH) 47.4 E.A.T./L.A.T. SEER VOLT.-PH.-CY. FLA MCA MOCP (LBS) MANUFACTURER MODEL NOTES MAU-1 KITCHEN HOOD ROOF 3360 3360 1.0 1604 3 206.7 92 80 / 66 14 208-3-60 9.5 44.4 60 1567 CAPTIVEAIRE A2-D250-20D-MPU 1, 2, 3, 4, 5, 6, 7,8 ALTERNATE MANUFACTURERS: LENNOX, TRANE, YORK, CARRIER NOTES: 1. UNIT CAPACITIES RATED AT 100 FEET ELEVATION AND 85 DEGREES CONDENSER ENTERING AIR. 2. PROVIDE UNIT WITH FACTORY MOUNTED DISCONNECT AND GFI SERVICE OUTLET. 3. PROVIDE PREFABRICATED 14" ROOF CURB. 4. PROVIDE WITH SEISMIC CLIP. 5. PROVIDE UNIT WITH SPRING ISOLATORS. 6. PROVIDE UNIT WITH FACTORY SMOKE DETECTOR, FEILD INSTALLED. 7. FANS EXCEDING 1.0 HP SHALL HAVE AN ENERGY EFFICIENCY CLASSIFICATION OF MORE THAN FEG 71 PER AMCA 205, AND FAN OPERATION SHALL BE WITHIN 10% OF THE LISTED EFFICENY, IN COMPLIANCE WITH WSEC SECTION C406.2.3 ENERGY RECOVERY VENTILATOR SCHEDULE SUPPLY FAN EXHAUST FAN ENERGY RECOVERY ELECTRICAL SUMMER WINTER EQUIPMENT T.S.P.(IN. FAN T.S.P. (IN. FAN SUMMER WINTER ENTHALPY ENTHALPY NO. SERVICE LOCATION CFM W.C.) RPM HP CFM W.C.) RPM HP EAT/LAT EAT/LAT RECOVERY RECOVERY SONES VOLT.-PH.-CY. FLA MCA MOCP WEIGHT MANUFACTURER MODEL NOTES ERV-1 FC OSA / CORRIDOR EA ROOF 1050 1 0.75 1 1100 0.75 950 0.75 1140 1 0.75 85 / 77.8 23 / 51.8 67.5 54.6 13.2 208V-PH1-60 12.2 15 GREENHECK ECV-10H-VG-FM NOTES: 1. UNIT CONFIGURED TO SUPPLY 100% OSA. VERTICAL PACKAGED TERMINAL HEAT PUMP SCHEDULE EQUIPMENT SENSIBLE COOLING NO. SERVICE SUPPLY CFM MIN. OSA CFM ESP (IN. W.C.) MBH EER HEATING MBH COP ELEC. HEAT (kW) VOLT-PH-CY MCP MCA WEIGHT MANUFACTURER MODEL NOTES VTAC-1 STUDIO UNIT 490 60 0.3 9.0 11.5 8.2 4.0 2.1 208V-1PH-60 15 15 145 AMANA AVH093H VTAC-2 1-BEDROOM 490 60 0.3 11.0 11.5 10.5 4.0 2.8 208V-1PH-60 20 19.9 150 AMANA AVH123H VTAC-3 2-BEDROOM 675 60 0.3 18.0 11.5 16.5 4.0 4.1 208V-1PH-60 30 28.6 190 AMANA AVH183H NOTES: 1. PROVIDE WITH MERV-6 FILTER OR BETTER. 2. PROVIDE WITH ARCHITECTURAL LOUVER, ACCESS PANEL/RETURN AIR GRILLE, AND ACCESSORY DRAIN PAN/KIT. DEDICATED OUTSIDE AIR SUPPLY UNIT SCHEDULE SENS COOLING OUTSIDE AIR HEATING ELECTRICAL EQUIPMENT NOMINAL CAPACITY MIN / MAX ENTERING AIR CAPACITY E.S.P. NO. SERVICE CAPACITY (MBH) CFM SEER/IEER DB/WB (MBH) (IN W.C.) MCA MOCP VOLT/PH/CY WEIGHT MANUFACTURER MODEL NOTES DOAS-1 CORRIDOR OSA 12 TONS 1 160.8 2200 / 4800 418.1 18.1 80/61.3 133 0.5 88.5 A 100 A 208V-3PH-60 3851 LBS CAPTIVEAIRE CASRTU4 1,2 NOTES: 1. UNIT CONFIGURED TO SUPPLY 100% OSA. 2. FANS EXCEDING 1.0 HP SHALL HAVE AN ENERGY EFFICIENCY CLASSIFICATION OF MORE THAN FEG 71 PER AMCA 205, AND FAN OPERATION SHALL BE WITHIN 10% OF THE LISTED EFFICENY, IN COMPLIANCE WITH WSEC SECTION C406.2.3 ROOFTOP UNIT SCHEDULE EQUIPMENT NO. SERVICE TONS SUPPLY AIR (CFM) OUTSIDE AIR (CFM) E.S.P. (IN. W.C.) COOLING ENTERING AIR SENSIBLE EER/SEER REFRIGERANT DB/WB MBH HEATING ELECTRICAL WEIGHT (LBS) MANUFACTURER MODEL OPTIONS MBH INPUT MBH OUTPUT AFUE % VOLT/PH/CYC MCA MOCP POWER EXH. MCA MOCP RTU-1 FITNESS 3 1200 305 0.5 416.1 16.1 R-41 OA 80 / 61 24.5 79.2 64.2 81 % 208/3/60 27 30 1.5 15 700 CARRIER 48GCEM04 1,2,3,4,5,6,7,8 RTU-2 THEATER 3 1200 270 0.5 416.1 16.1 R-41 OA 80 / 61 24.5 79.2 64.2 81 % 208/3/60 27 30 1.5 15 700 CARRIER 48GCEM04 1,2,3,4,5,6,7,8 ALTERNATE MANUFACTURERS: LENNOX, TRANE, BRYANT, YORK, CARRIER, LUXAIRE. NOTES: 1. UNIT CAPACITIES RATED AT 600 FEET ELEVATION AND 80 DEGREES CONDENSER ENTERING AIR. 2. PROVIDE UNIT WITH FACTORY MOUNTED DISCONNECT AND GFI SERVICE OUTLET. 3. PROVIDE PREFABRICATED 14" ROOF CURB. 4. PROVIDE ECONOMIZER WITH FULL MODULATING POWER EXHAUST AND HIGH LIMIT SHUT OFF CONTROL PER WSEC C403.3.3.3. 5. PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT. 6. PROVIDE WITH SEISMIC CLIP. 7. PROVIDE UNIT WITH ALL CONTROLS AND SENSORS REQUIRED FOR ON DEMAND VENTILATION. 8. PROVIDE UNIT WITH FACTORY SMOKE DETECTOR, FIELD INSTALLED. NOTE: MECHANICAL EQUIPMENT SHALL EXCEDE THE WSEC EFFICIENCIES ON TABLES C403.2.3(1) THROUGH C403.2.3(9) BY 15% TO UTILIZE THE HIGH EFFICIENCY HVAC OPTION. AIR DISTRIBUTION DEVICES EQUIPMENT NO. SIZE MOUNTING MATERIAL MANUFACTUR ER MODEL NOTES FACE NECK SIDEWALL LAY -IN CEILING HARD CEILING DUCT FLOOR STEEL ALUMINUM SD-1 12"x12" SEE PLANS X X X TITUS TMS SD-2 24"x24" SEE PLANS X X X TITUS TMS SG-1 10"x6" SEE PLANS X X TITUS US30OFS SG-2 10"x6" SEE PLANS X X X TITUS US350FS RG-1 12"x12" SEE PLANS X X X TITUS 50F RG-2 24"x24" SEE PLANS X X X TITUS 50F TG-1 14"x10' SEE PLANS X X X X X TITUS TITUS US350FS 50F TG-2 24"x24" SEE PLANS EG-1 24"x24" SEE PLANS X X X TITUS 5OF ALTERNATE MANUFACTURERS: TITUS, PRICE, METAL-AIRE, NAILOR, CARNES, TUTTLE & BAILEY NOTES: 1. CONTRACTOR TO VERIFY AND PROVIDE ALL MOUNTING HARDWARE FOR APPLICABLE CEILING TYPES. 2. FINISH TO BE COORDINATED WITH ARCHITECT PRIOR TO SUBMITTAL. 3. NC VALUES NOT TO EXCEED 25. 4. NECK SIZE REFERS TO THE DUCT SIZE CONNECTION AT THE DIFFUSER OR GRILLE. 5. CONTRACTOR PROVIDED FACE DAMPER WHEN IN -LINE DUCT DAMPER IS NOT ACCESSIBLE. 6. CONTRACTOR TO PROVIDE TRANSITIONS FROM LEAD-IN DUCT SIZE TO NECK SIZE AS REQUIRED. ELECTRIC WALL HEATER SCHEDULE EQUIPMENT NO. KEY: �_— (A), (B) (C) A. FIRST LETTER: S-SUPPLY, R-RETURN, E-EXHAUST, T- TRANSFER SECOND LETTER: D-DIFFUSER, R-REGISTER, G-GRILLE B. DUCT NECK SIZE, UNLESS NOTED OTHERWISE C. CFM EQUIPMENT ELECTRIC NO. SERVICE CFM WATTS RPM MCA VOLT.-PH.-CY. WEIGHT MANUFACTURER MODEL NOTES EWH-1 SEE PLANS 100 750 1060 6.3 120V-1 PH-60 10 LBS MARKEL E3055T2DWB EWH-2 STAIRWAYS 100 1500 1060 12.5 120V-1 PH-60 10 LBS MARKEL E3055T2DWB ALTERNATE MANUFACTURERS: NOTES: 1. COORDINATE MOUNTING LOCATION WITH ALL OTHER DISCIPLINES. LOUVER SCHEDULE EQUIPMENT THICKNESS NO. SERVICE WIDTH HEIGHT FREE AREA (SQ. FT.) OF FRAME MATERIAL SCREEN MANUFACTURER MODEL NOTES L-1 L-2 FC-1C, FC-1D, FC-1E INTAKE 46" 28" 4.4 6" GALVANIZED STEEL MESH GREENHECK VCD-23 2000 CFM INTAKE, CLASS 1 MOTORIZED DAMPER. 1ST FLOOR RELIEF 46" 28" 4.5 6" GALVANIZED STEEL MESH GREENHECK VCD-23 3600 CFM RELIEF, CLASS 1 MOTORIZED DAMPER I E L H N C C- 3 0 F R I C S 1 O R AM R L-4 FIRE ALARM 50" 72" 12 6" ALUMINUM MESH GREENHECK ECD-601 4 L-P1 PARKING EXHAUST RELIEF 42" 42" 6.0 6" ALUMINUM MESH RUSKIN CD355 1 L-R1 UNIT EXHAUST MANIFOLD 12" 11" - 5" POLY MESH XVENT MDEB-44-BR 1 L-R2 UNIT EXHAUST MANIFOLD 16" 12" - 5" POLY MESH XVENT THEB-444-BR 1 RL-1 TRASH CHUTE PENTHOUSE VENT 24" 16" - - ALUMINUM MESH GREENHECK WRH 3 ALTERNATE MANUFACTURERS: GREENHECK, RUSKIN, CESCO, L & D NOTES: 1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. 2. PROVIDE WITH RUSKIN MOTORIZED ACTUATOR, CONTROLLED TO OPEN WHEN EF-G1 IS ENERGIZED. 4. SMOKE CONTROL RELIEF DAMPER. PROVIDE CLASS 1 MOTORIZED DAMPER, RUSKIN CBD2 BACKDRAFT DAMPER, AND STANDBY POWER FROM GENERATOR. UNIT HEATER SCHEDULE EQUIPMENT NO. MANUFACTURER MODEL FUEL INPUT EFFICIENCY AIRFLOW (CFM) VOLT/PH/CY MCA MOCP WEIGHT NOTES UH-1 MODINE HHD-30 NATURAL GAS 30.0 MBH 82% 500 120V-1PH-60 - - 55 LBS RH-1,2,3,4 GREAT LAKES RADIANT BAH-35-C-17 ELECTRIC 1750 WATTS - - 240V-1 PH-60 7.0 A 15 A 13 LBS CCD 003 FAN COIL SCHEDULE EXTERNAL HEATING COIL COOLING COIL ELECTRICAL EQUIPMENT AREA SUPPLY OUTSIDE STATIC PRESS NO. SERVED AIR (CFM) AIR (CFM) (IN. W.G.) MBH INPUT KW MBH REFRIG. VOLT.-PH.-CY. MCA MOP WEIGHT MANUFACTURER MODEL NOTES FC-1A BISTRO 1600 570 0.24 54.2 650 48.1 R410A 208V-1PH-60 3.1 15 110 LG ARNU483M3A4 1, 2, 3, 4, 5, 6, 7, 9 FC-1 B OFFICES 1200 240 0.24 40.6 450 36.2 R410A 208V-1 PH-60 2.9 15 100 LG ARNU363M3A4 1, 2, 3, 4, 5, 6, 9 FC-1C DINING 1600 450 0.24 54.2 650 48.1 R41OA 208V-1PH-60 3.1 15 110 LG ARNU483M3A4 1, 2, 3, 4, 5, 6, 7, 8, 9 FC-1D DINING 1600 450 0.24 54.2 650 48.1 R410A 208V-1PH-60 3.1 15 110 LG ARNU483M3A4 1, 2, 3, 4, 5, 6, 7, 8, 9 FC-1E FAMILY RM 400 75 0.24 13.6 190 12.3 R410A 208V-1PH-60 2.0 15 67 LG ARNU123M3A4 1, 2, 3, 4, 5, 6, 8, 9 FC-1 F KITCHEN 1200 0 0.24 40.6 450 36.2 R410A 208V-1 PH-60 2.9 15 100 LG ARNU363M3A4 1, 2, 3, 4, 5, 6, 9 FC-2 2ND FLOOR 800 325 0.24 27.3 190 24.2 R410A 208V-1PH-60 2.0 15 70 LG ARNU243M3A4 1, 2, 3, 4, 5, 6, 9 FC-3 3RD FLOOR 800 325 0.24 27.3 190 24.2 R410A 208V-1 PH-60 2.0 15 70 LG ARNU243M3A4 1, 2, 3, 4, 5, 6, 9 FC-4 4TH FLOOR 800 325 0.24 27.3 190 24.2 R410A 208V-1 PH-60 2.0 15 70 LG ARNU243M3A4 1, 2, 3, 4, 5, 6, 9 FC-5 5TH FLOOR 800 325 0.24 27.3 190 24.2 R410A 208V-1 PH-60 2.0 15 70 LG ARNU243M3A4 1, 2, 3, 4, 5, 6, 9 FC-6A SALON 400 270 0.24 13.6 190 12.3 R410A 208V-1PH-60 2.0 15 67 LG ARNU123M3A4 1, 2, 3, 4, 5, 6, 9 FC-613 6TH FLOOR 800 255 0.24 27.3 190 24.2 R410A 208V-1 PH-60 2.0 15 70 LG ARNU243M3A4 1, 2, 3, 4, 5, 6, 9 ALTERNATE MANUFACTURERS: LENNOX, TRANE, YORK NOTES- 1 . PROVIDE UNIT WITH 7 DAY PROGRAMMABLE THERMOSTAT. 2. PROVIDE ALL ANCILLARY COMPONENTS REQUIRED FOR A FULL INSTALLATION. 3. PROVIDE WITH MEDIA FILTER. 4. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCHES AND POWER WIRING. 5. PROVIDE MANUFACTURER'S CONDENSATE PUMP KIT AND ROUTE TO NEAREST LAVATORY/SINK TAILPIECE. 6. PROVIDE MANUFACTURER'S LOW AMBIENT KIT FOR OPERATION DOWN TO 0°F. 7. PROVIDE ALL CONTROLS AND SENSORS REQUIRED FOR DEMAND CONTROL VENTILATION. 8. PROVIDE FAN COIL WITH MOTORIZED DAMPERS FOR ECONOMIZER OPERATION, WITH HIGH LIMIT SHUT-OFF CONTROL PER WSEC C403.3.3.3. 9. PROVIDE UNIT WITH MANUFACTURER DRIP PAN AD SECONDARY DRAINAGE. HEAT PUMP SCHEDULE EQUIPMENT NO. CORRESPONDING UNIT TOTAL COOLING CAPACITY (MBH) TOTAL HEATING CAPACITY (MBH) SEER/EER 17 HSPF 9.5 ELECTRICAL SOUND dB 51 MANUFACTURER LG MODEL ARUN048GSS4 WEIGHT 207 NOTES 1, 2, 3, 4, 5, 6 VOLT./PH/CY. 208V-1PH-60 MCA 30 MOCP 50 HP-1A FC-1A 50 56.5 HP-1 B FC-1 B 39.5 44 17 9.0 208V-1 PH-60 25 40 50 LG ARUN036GSS4 160 1, 2, 3, 4, 5, 6 HPA C FC-1 C 50 56.5 17 9.5 208V-1 PH-60 30 50 51 LG ARUN048GSS4 207 1, 2, 3, 4, 5, 6 HP-1 D FC-1 D 50 56.5 17 9.5 208V-1 PH-60 30 50 51 LG ARUN048GSS4 207 1, 2, 3, 4, 5, 6 HP-1 E FC-1 E 24 27 15.8 8.6 208V-1 PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-1 F FICA F 39.5 44 17 9.0 208V-1 PH-60 25 40 50 LG ARUN036GSS4 160 1, 2, 3, 4, 5, 6 HP-2 FC-2 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-3 FC-3 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-4 FC-4 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-5 FC-5 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-6A FC-6A 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-6B FC-6B 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 ALTERNATE MANUFACTURERS: LENNOX, TRANE, YORK NOTES: 1. PROVIDE ALL ANCILLARY COMPONENTS REQUIRED FOR A FULL INSTALLATION. 2. INDOOR UNIT IS ELECTRICALLY CONNECTED TO AND POWERED BY THE OUTDOOR UNIT. ELECTRICAL REQUIREMENTS ARE COMBINED. 3. CAPACITIES ARE RATED AT ARI STANDARDS. 4. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCHES AND POWER WIRING. 5. PROVIDE REFRIGERANT AND REFRIGERANT PIPING PER MANUFACTURER FOR FIELD CONDITIONS. 6. PROVIDE MANUFACTURER'S LOW AMBIENT KIT FOR OPERATION DOWN TO 0°F. Plan set for Smoke Control only. �O of wA,3 r-b' 41741 �<C/ �Z'rISTER�� \� AS8/0NAL EN 05/17/2023 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.d(engineerinq.net Phone:208.288.2181 Project:21 AMA01 N CD 00 M 0 0 Z z 0 = >Q 0 W C 0 LL O 0 0 0 Z O � > J Q J _� 0 rn T 0 i C O F_ CD LLl DOo Z N U LU Q Q N U a REVISION DATE REASON FOR ISSUE E 03-07-22 CITY COMMENTS #05 14 06-27-22 RFI#53 19 08-29-22 RFI#131 12-30-22 CCD 003 F 05-12/23 SMOKE CONTROL REVISIONS-ASI 009 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT HVAC SCHEDULES CONSTRUCTION SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M5.0 GENERALNOTES ABBREVIATIONS ELECTRICAL LEGEND (LEGEND IS GENERAL IN NATURE. NOT ALL OF THE SYMBOLS SHOWN ARE USED IN THIS PROJECT.) (RE: ALL ELECTRICAL SHEETS) A AMPERES POWER LIGHTING (SEE LUMINAIRE SCHEDULE FOR EXACT MISCELLANEOUS SWITCHES ONE LINE AC ABOVE COUNTER REQUIREMENTS) 1. ALL ELECTRICAL EQUIPMENT AND SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL AC ABOVE FINISHED FLOOR SIMPLEX OUTLET. +18" AFF UNO. SINGLE FACE EXIT SIGN. CEILING MOUNTED. O JUNCTION BOX. S# SWITCH. TYPE AS INDICATED. +46"AFF, UNO. CODE, INTERNATIONAL FIRE CODE, AND ALL OTHER STATE AFG ABOVE FINISHED GRADE 0 DUPLEX OUTLET. +18" AFF UNO. ® DOUBLE FACE EXIT SIGN. CEILING MOUNTED. 2 DOUBLE POLE BRANCH AND LOCAL CODES. CONTRACTOR SHALL IMMEDIATELY AF AMPERE FRAME Q JUNCTION BOX, WALL MOUNTED. 3 3-WAY PANEL BRANCH PANEL. NOTIFY ENGINEER IN WRITING IF PORTIONS OF THE DESIGN AHJ AUTHORITY HAVING JURISDICTION I DUPLEX OUTLET. MOUNTED ABOVE COUNTER UNO. 4 4-WAY ****** SET OR FIELD CONDITIONS DO NOT MEET REQUIRED CODES. AT AMP TRIP DUPLEX OUTLET. +18" AFF UNO WITH GROUND SINGLE FACE EXIT SIGN. WALL MOUNTED. � THERMOSTAT. +56" AFF UNO. UNIT CONTROLLED D DIMMER INDICATED. 2. PROVIDE FIRESTOPPING FOR ALL FLOOR AND FIREWALL AWG AMERICAN WIRE GAUGE 0 FAULT INTERRUPTION PROTECTION. DOUBLE FACE EXIT SIGN. WALL MOUNTED. F CEILING FAN CONTROLLER HP HORSE POWER RATED PENETRATIONS FROM ELECTRICAL DEVICE, RACEWAY, AND CABLE PENETRATIONS. SEE ARCHITECTURAL DRAWINGS FOR BW BLANKET WARMER � DUPLEX OUTLET. MOUNTED ABOVE COUNTER UNO SURFACE MOUNTED PANELBOARD/ENCLOSURE. � K KEYED FIREWALL LOCATIONS. C CONDUIT WITH GROUND FAULT INTERRUPTION PROTECTION. SINGLE FACE COMBO EXIT SIGN / EMERGENCY LUMINAIRE. WALL MOUNTED. SEE SCHEDULE FOR TYPE. LV LOW VOLTAGE � A CIRCUIT BREAKER. SIZE AND TYPE 3. FIRE ALARM SYSTEM IS DESIGN BUILD BY ELECTRICAL CB CIRCUIT BREAKER SWITCHED DUPLEX OUTLET. +18" AFF UNO. FLUSH MOUNTED PANELBOARD/ENCLOSURE. � M MOMENTARY CONTACT / I AS SPECIFIED. CONTRACTOR AND SHALL BE INSTALLED IN ACCORDANCE CC CRASH CART DUPLEX ISOLATED GROUND OUTLET. � ARROW INDICATES DIRECTION TO BE SEE SCHEDULE FOR TYPE. MM MANUAL MOTOR STARTER WITH NFPA 72 AND ALL OTHER STATE AND LOCAL CODES. CKT CIRCUIT +18" AFF UNO. SHOWN ON SIGN. OS OCCUPANCY SENSOR PROVIDE AND INSTALL CONDUIT AND CONDUCTORS FOR ALL FIRE ALARM DEVICES REQUIRED BY LOCAL AUTHORITY CL CRITICAL LOAD DUPLEX ISOLATED GROUND OUTLET. � LIGHT FIXTURE. AM MECHANICAL EQUIPMENT SYMBOL (RE: MECHANICAL DRAWINGS FOR EXACT LOCATION P PILOT LIGHT T 15 MINUTE TIMER I 30AF CIRCUIT BREAKER. FRAME SIZE AF ( ) AND TRIP PLUG/RATING AT 3 POLE, ( ), CM CEILING MOUNTED � COUNTER # / 30AT / UNO. HAVING JURISDICTION, INCLUDING BUT NOT LIMITED TO HVAC MOUNTED ABOVE UNO. LIGHT FIXTURE. OF UNITS). TO THERMAL OVERLOAD SHUTDOWN, FIRE ALARM CONTROL PANEL, INITIATING AND CO CONDUIT ONLY, PROVIDE PULL -LINE DUPLEX 20A OUTLET. +18" AFF UNO. INDICATES FIXTURE TYPE. REFER TO LUMINARE V VOLUME CONTROL ANNUNCIATING CIRCUITS. FIELD INSPECTION IS REQUIRED TO D MECHANICAL DUCT -MOUNTED DEVICE LIGHT FIXTURE. F#W SCHEDULE. VS VACANCY SENSOR VERIFY THIS INFORMATION PRIOR TO BID. DC DIRECT CURRENT DUPLEX 20A OUTLET. MOUNTED ABOVE COUNTER UNO. a SUPERSCRIPT INDICATES LIGHTS 15A FUSE. SIZE AND TYPE AS 4. PROVIDE AND INSTALL 3/4" CONDUIT WITH BUSHING AND PULL DET DETAIL TO BE SWITCHED TOGETHER SPECIFIED, CIRCUITING SYMBOLS CORD TO ABOVE ACCESSIBLE CEILING, UNLESS NOTED E EMERGENCY/CRITICAL CARE DUPLEX OUTLET WITH USB PORT. +18" AFF UNO. SUSPENDED LIGHT FIXTURE. PROVIDE FUSE FOR EACH POLE, 3 OTHERWISE FOR DATA, TELEPHONE, AND TELEVISION (E) EXISTING WALL MOUNTED FIXTURE. %MULTI -LEVEL SWITCHING, TO MEET LIGHT POLE, UNO. DEVICES. DATA, TELEPHONE, AND TELEVISION CABLING ARE EF EXHAUST FAN SINGLE 20A OUTLET. +18" AFF UNO. CONDUIT STUBBED, CAPPED, AND REDUCTION LEVELS PER ENERGY CODE AS NOT PROVIDED UNDER THIS CONTRACT. WALL SCONCE FIXTURE. MARKED WITH PULL CORD. SHOWN. PROVIDE ADDITIONAL OR STEP- 30A INTERRUPTER SWITCH. SIZE AS 5. EMERGENCY LIGHTING SYMBOLS ARE SHADED ON THE EL EMERGENCY LIGHT FOURPLEX OUTLET. +18" AFF UNO. DIMMING BALLASTS WHERE REQUIRED. INDICATED, 3 POLE, UNO. LIGHTING PLANS. EMERGENCY SOURCE SHALL BE BATTERY EWC ELECTRIC WATER COOLER FOURPLEX OUTLET. MOUNTED ABOVE WALL PACK FIXTURE. CONDUIT UP. BACKED DRIVER WITH MINIMUM OF 1400 LUMEN OUTPUT FOR EWH ELECTRIC WATER HEATER COUNTER UNO. OCCUPANCY SENSOR. CEILING MOUNTED. A 90 MINUTE PERIOD, UNLESS NOTED OTHERWISE. PROVIDE F FUSE UNDERCABINET MOUNTED FIXTURE. CONDUIT DOWN. UNSWITCHED CONDUCTORS FOR CHARGING CIRCUIT AS FACP FIRE ALARM CONTROL PANEL FOURPLEX ISOLATED GROUND OUTLET+18" AFF UNO. .F-vv TRACKLIGHT. -� X-# HOMERUN. PANEL AND CIRCUIT AS P 4 . . PHOTOCELLWALL MOUNTED REQUIRED. FUSED SWITCH. SWITCH SIZE (AS) & 6. ALL WIRING DEVICES SHALL BE OF THE SAME MANUFACTURER FVNR FULL VOLTAGE NON -REVERSING FOURPLEX ISOLATED GROUND OUTLET. MOUNTED © PENDANT LIGHT FIXTURE. INDICATED. 30AS 30AF FUSE SIZE (AF) AS INDICATED, 3 AND SHALL MATCH THROUGHOUT. COVER PLATES SHALL BE G/GND GROUND ABOVE COUNTER UNO. CIRCUIT CONCEALED IN CEILING OR P O PHOTOCELL. CEILING MOUNTED. POLE, UNO. STAINLESS AND DEVICES SHALL BE COORDINATED WITH THE GFI GROUND FAULT INTERRUPTION SPECIAL PURPOSE OUTLET. VERIFY SIZE AND TYPE ROUND DECORATIVE LIGHT FIXTURE. WALL. I, TIMECLOCK. WALL MOUNTED. ARCHITECT. GFP GROUND FAULT PROTECTION WITH EQUIPMENT SUPPLIER. SURFACE MOUNT C YYY 7. DESIGN OF ELECTRICAL REQUIREMENTS IS BASED ON H HEAT CONNECTION POINT TO EQUIPMENT SPECIFIED, Q RECESSED LIGHT FIXTURE. CIRCUIT CONCEALED IN FLOOR OR SINGLE BUTTON, WALL MOUNTED MECHANICAL EQUIPMENT SPECIFIED. ELECTRICAL HH HANDHOLE FURNISHED, AND INSTALLED UNDER OTHER SECTIONS. UNDERGROUND. _ 4 PUSHBUTTON. MOUNT AT SWITCH HEIGHT UNO. CONTRACTOR SHALL COORDINATE WITH MECHANICAL HOA HAND OFF AUTO ELECTRICAL CONTRACTOR TO SUPPLY RACEWAY AND � RECESSED WALL WASH LIGHT FIXTURE. DRAW OUT CIRCUIT BREAKER FRAME CONTRACTOR IF EQUIPMENT PURCHASED IS DIFFERENT FROM HID HIGH INTENSITY DISCHARGE CONDUCTORS AND MAKE FINAL CONNECTION TO ® o0 THREE BUTTON, WALL MOUNTED PUSHBUTTON. (AF) SIZE AND TRIP PLUG RATING THAT SPECIFIED STILL MEETS DESIGN INTENT, INCLUDING BUT EQUIPMENT UNDER THIS SECTION, UNO. PORCELAIN LAMP HOLDER. GROUNDING MOUNT AT SWITCH HEIGHT UNO. �/ (AT), 3 POLE, UNO. NOT LIMITED TO OVER -CURRENT PROTECTION, LOCAL DISCONNECTING MEANS, AND WIRE SIZING. HP HVAC HOUSE PHONE HEATING, VENTILATING, & AIR CONDITIONING ® DUPLEX OUTLET. FLUSH, FLOOR MOUNTED WITH (� WALL MOUNTED PORCELAIN LAMP HOLDER. CONDUCTOR SIZE / ® MOTOR STARTER/CONTACTOR. 8. IT SHALL BE CONTRACTORS RESPONSIBILITY TO VERIFY TYPE I IONIZATION BRASS COVER PLATE. DUPLEX SWITCHED OUTLET. FLUSH, FLOOR MOUNTED CEILING FAN. X"-X#X X#XG INDIVIDUAL BREAKER FRAME (AF) OF CEILING SYSTEMS AND TO FURNISH APPROVED LIGHTING ID IN -DUCT ® � COMBINATION STARTER AND DISCONNECT. 1 FIXTURES OF THE TYPE REQUIRED FOR MOUNTING IN SUBJECT CEILING. WHERE FIXTURES ARE RECESSED IN IC IG INTERRUPTING CAPACITY ISOLATED GROUND ® WITH BRASS COVER PLATE. DUPLEX ISOLATED GROUND OUTLET. FLUSH, FLOOR CEILING FAN WITH LIGHT KIT. RACEWAY SIZE ' -CONDUCTOR SIZE CONDUCTOR QUANTITY X D NON -FUSED DISCONNECT SWITCH. SIZE AS / / SIZE AND TRIP PLUG RATING (AT), NEMA 1 UNO, 3 POLE UNO. PLASTER OR DRYWALL CEILINGS, THEY SHALL BE COMPLETE MOUNTED WITH BRASS COVER PLATE. INDICATED, NEMA 1 UNO, 3 POLE UNO. WITH NECESSARY MOUNTING HARDWARE AND PLASTER J/JB JUNCTION BOX OUTLET. FLUSH, FLOOR MOUNTED WITH FRAMES. KW KILOWATT ® BRASS COVER PLATE. BRASS O e 0 POLE LIGHT 1 HEAD ROUND WITH POLE. 9. ALL RECESSED LIGHTING FIXTURES, SPEAKERS, KWH KILOWATT HOUR OHO POLE LIGHT 2 HEAD ROUND WITH POLE. CIRCUIT SHALL CONSIST OF 3/4"-2#12,1#12G UNLESS F X FUSED DISCONNECT SWITCH. SIZE AS O METER. RECEPTACLES, SWITCHES, ETC., MOUNTED IN THE FIRE M MAGNETIC CONTACTOR COIL ®❑ SPECIAL PURPOSE OUTLET. FLUSH, FLOOR MOUNTED NOTED OTHERWISE. INDICATED, NEMA 1 UNO, 3 POLE UNO. RATED CEILINGS OR WALLS SHALL BE ENCLOSED WITH AN MB MAIN BREAKER WITH BRASS COVER PLATE. -0 POLE LIGHT 1 HEAD SQUARE WITH POLE. AM AMMETER. APPROVED ENCLOSURE CARRYING THE SAME FIRE RATING AS MCC MOTOR CONTROL CENTER MOTOR CONNECTION. RE: MECHANCIAL CONTRACTOR SHALL ROUTE CIRCUIT HOMERUN THE CEILING OR WALL BY THIS CONTRACTOR. MLO MAIN LUGS ONLY EQUIPMENT SCHEDULE ❑-❑ POLE LIGHT 2 HEAD SQUARE WITH POLE. FROM DEVICE NEAREST THE PANEL. VM VOLTMETER. 10. ALL COMMUNICATIONS CONDUIT SHALL BE 3/4" UNO. MS MOTOR STARTER O BOLLARD LIGHT. 0 ADA DOOR CHIME/STROBE ❑K KIRK KEY LOCK. MOUNTING H E I H T DETAIL HEIGHTS MH MANHOLE MW MICROWAVE DECORATIVE POST -TOP LIGHT. � GFP GROUND FAULT PROTECTION. SHEET INDEX N NEUTRAL FIRE ALARM -< SPOT/FLOOD LIGHT. NC NCL NORMALLY CLOSED NON CRITICAL LOAD Sp O SMOKE DETECTOR, ADDRESSABLE, CEILING V-1-11 EMERGENCY EGRESS LIGHT. WALL MOUNTED. TVSS TRANSIENT VOLTAGE SURGE SUPRESSION. E0.00 ELECTRICAL COVER SHEET NEC NATIONAL ELECTRICAL CODE MOUNTED, UNO. pZ11 EMERGENCY EGRESS LIGHT. CEILING MOUNTED. ST SHUNT TRIP COIL. E0. 2 EL CTRI AL I C N R MP IA C E1.00 ELECTRICAL SITE PLAN NIC NOT IN CONTRACTNO CO CARBON MONOXIDE DETECTOR. KWH KILOWATT HOUR METER. NORMALLY OPEN KEYED NOTES COMMUNICATIONS E1.01 PHOTOMETRIC PLAN - SITE & LEVEL 1 E1.02 PHOTOMETRIC PLAN - LEVEL P1 NTS NOT TO SCALE FSD FIRE/SMOKE DAMPER A. 1. 48" AFF MEASURED FROM THE TOP OF THE KVAR KILOVAR DEMAND METER. E1.03 TYP. CORRIDOR & UNIT PHOTOMETRIC PLANS OL OS OVERLOAD OCCUPANCY SENSOR F L-177 IF�FF�F OUTLET BOX. TEST TEST BLOCK. E2.00 ELECTRICAL LIGHTING PLAN - LEVEL P1 OFCI OWNER FURNISHED CONTRACTOR INSTALLED SD LOW FREQUENCY SOUNDER W/ 177CD STROBE MOUNTED TO THE CEILING. ]Z COMMUNICATION OUTLET LOCATED AT 18" AFF UNO. 2. 46" AFF MEASURED FROM THE TOP OF THE E2.01 ELECTRICAL LIGHTING PLAN - LEVEL 1 E2.02 ELECTRICAL LIGHTING PLAN -LEVEL 2 P PHOTO S PROVIDE AND INSTALL 4" SQUARE, DEEP JUNCTION BOX WITH SINGLE GANG MUD RING � � OUTLET BOX WHERE LOCATED ABOVE SOLID BASE CABINET THAT ALLOWS OVERHEAD SERVICE DROP. PC PHOTOCELL E2.03 ELECTRICAL LIGHTING PLAN -LEVEL 3 F L F J a p ❑i ® ❑ PARALLEL (SIDE) APPROACH. APPLIES IN E2.04 ELECTRICAL LIGHTING PLAN -LEVEL 4 PVC RCPT POLYVINYL CHLORIDE RECEPTACLE SD LOW FREQUENCY SOUNDER. COMMUNICATION OUTLET. FLUSH, FLOOR MOUNTED. ❑v O � � TYPE B/FHA UNITS ONLY. a GENERATOR SET. MAIN BREAKER E2.05 ELECTRICAL LIGHTING PLAN -LEVEL 5 (R) RELOCATED S P I* S# � z z OF SIZE E2.06 ELECTRICAL LIGHTING PLAN -LEVEL 6 AUDIBLE /VISUAL HORN -STROBE SMOKE TELEVISION OUTLET LOCATED AT 18" AFF UNO. 3. 44" AFF MEASURED FROM THE TOP THE OUTLET BOX WHERE LOCATED ABOVE INDICATED. E2.10 ELECTRICAL POWER PLAN - LEVEL P1 (RE) ) REF REPLACED REFRIGERATOR F 177 DETECTION DEVICE. CEILING MOUNTED, UNO. PROVIDE AND INSTALL AS A RECESSED OUTLET. PANEL U ADA AT Lu J - � OPEN-FACED CABINET. APPLIES IN TYPE A TRANSFER SWITCH. E2.11 ELECTRICAL POWER PLAN - LEVEL 1 SPST SINGLE POLE SINGLE THROW NUMBER INDICATES CANDELA OF DEVICE. � FLOOR MOUNTED FLUSH TELEVISION OUTLET COUNTER MAX CO z �o Q Q CO UNITS AND COMMON AREAS ONLY. E2.12 ELECTRICAL POWER PLAN -LEVEL 2 VISUAL STROBE - SMOKE DETECTION DEVICE. . , . - � o_ GUTTER. E2.13 ELECTRICAL POWER PLAN - LEVEL 3 TIC TDR TIME CLOCK TIME DELAY RELAY F 177 CEILING MOUNTED, UNO. SO SPEAKER. CEILING MOUNTED WITH BACKBOX. v L F- - o - I� k�k IC is C 4. OUTLET ABOVE BASE CABINET IN 'U' SHAPED KITCHEN TO BE PROVIDED AT E2.14 ELECTRICAL POWER PLAN -LEVEL 4 p z O METER AND BASE. E2.15 ELECTRICAL POWER PLAN LEVEL 5 TJB TERMINAL JUNCTION BOX 11 _ VISUAL STROBE -SMOKE DETECTION DEVICE. (S� SPEAKER. WALL MOUNTED WITH BACKBOX +80" UNO. 0 " MINIMUM OF 36" FROM A CORNER. (MAY - TSP TWISTED SHIELDED PAIR WALL MOUNTED, UNO. Y °r° REQUIRE ADDITIONAL OUTLETS BEYOND NEUTRA 0 NEUTRAL. E2.16 ELECTRICAL POWER PLAN -LEVEL 6 TTB TELEPHONE TERMINAL BOARD FIRE WATER FLOW BELL WIRELESS PULL CORD. ARLINGTON F101 LOCATED FINISH FLOOR THOSE REQUIRED BY CODE). E2.17 ELECTRICAL POWER PLAN - ROOF E2.20 ELECTRICAL ENLARGED UNITS TVSS TRANSIENT VOLTAGE SURGE SUPPRESSER ADDRESSABLE MANUAL PULL STATION �P AT 48" AFF TO CENTER OF BOX. NO CONDUIT REQUIRED. B. LOCATED NO LESS THAN 15"AFF MEASURED PM POWER MONITORING E2.21 ELECTRICAL ENLARGED UNITS TYP TYPICAL FROM THE BOTTOM OF THE OUTLET BOX. UH UNIT HEATER AIM ADDRESSABLE INTERFACE MODULE Fps CAMERA. WALL MOUNTED AT 96" AFF UNO. PROVIDE E2.22 ELECTRICAL ENLARGED KITCHEN PLANS &SCHEDULE UNO UNLESS NOTED OTHERWISE 4" SQUARE, DEEP JUNCTION BOX WITH SINGLE GANG C. OUTLETS AND SWITCHES OVER COUNTERS, E2.30 SPECIAL SYSTEMS POWER PLAN - P1 V VOLT ANN ANNUNCIATOR PANEL MUD RING AND 3/4"CONDUIT TO THE NEAREST IDF. 8" TO CENTER OF BOX ABOVE COUNTERS, E2.31 SPECIAL SYSTEMS POWER PLAN - LEVEL 1 OR 10" TO TOP OF BOX ABOVE COUNTER. E2.32 SPECIAL SYSTEMS POWER PLAN - LEVEL 2 VA VOLT AMPERE ® ADDRESSABLE RELAY MODULE UNIT ACCESS PANEL. LOW VOLTAGE CONTRACTOR [UAP] E2.33 SPECIAL SYSTEMS POWER PLAN - LEVEL 3 WG PROVIDE PROTECTIVE WIRE GUARD (LVC)PROVIDED ELECTRICAL CONTRACTOR E2.34 SPECIAL SYSTEMS POWER PLAN - LEVEL 4 WP WEATHER PROOF/NEMA 3R FS FLOW SWITCH INSTALLED. MOUNTED AT 60" AFF TO TOP. XFMR TRANSFORMER COORDINATE WITH LVC FOR REQUIREMENTS. Q E2.35 SPECIAL SYSTEMS POWER PLAN - LEVEL 5 E2.36 SPECIAL SYSTEMS POWER PLAN - LEVEL 6 TS TAMPER SWITCH E3.00 ELECTRICAL SCHEDULES E3.01 ELECTRICAL SCHEDULES KNO KNOX BOX E4.00 ONE -LINE DIAGRAM (MDP-1) E4.01 ONE -LINE DIAGRAM (MDP-2) DH DOOR HOLD E5.00 ELECTRICAL DETAILS HD HEAT DETECTOR NOTE: PROVIDE AND INSTALL 3/4" CONDUIT WITH BUSHING AND PULL CORD TO ABOVE ACCESSIBLE CEILING, UNLESS NOTED OTHERWISE FOR DATA, TELEPHONE, AND TELEVISION DEVICES. DATA, TELEPHONE, AND TELEVISION CABLING ARE NOT PROVIDED UNDER THIS CONTRACT. Plan set for Smoke Control only. PN A. G , ASly o IFS FG S/DNAL EN 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 N O 00 d) O Z z O= Q W o LL z O0 0 z O N > J > J _� O -0 � O 0 0 Il z m F_ W p Z oN U ~ � Q LU N U a REVISIO N DATE REASON FOR ISSUE 5 03/14/22 Construction Set RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL COVER SHEET CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 ISHEET NUMBER -,oil EO.00 E co M 1J J _u 1 ELECTRICAL RICAL ITE PLAN NORTH N POWER FOR TO i SNOPUD ;UCTION. ORMER SITE GENERAL NOTES 1. CONTRACTOR SHALL CONTACT UNDERGROUND UTILITY LOCATING SERVICE PRIOR TO EXCAVATION FOR ELECTRICAL WORK. 2. CONTRACTOR IS RESPONSIBLE FOR COORDINATION WITH ALL OTHER SITE DISCIPLINES INCLUDING BUT NOT LIMITED TO TRADES ASSOCIATED WITH WATER, SEWER, AND GAS INSTALLATIONS. 3. ELECTRICAL CONTRACTOR SHALL COORDINATE UTILITY WORK REQUIRED BY SERVING UTILITY AND SHALL FORWARD SERVING UTILITY WORK ORDER INVOICE TO OWNER FOR PAYMENT BY OWNER. 4. ROUTE ALL EXTERIOR LIGHTING (INCLUDING SOFFIT AND AREA LIGHTING SHOWN ON SHEET E2.01) THROUGH A LIGHTING CONTROL PANEL. LOCATE LIGHTING CONTROL PANEL IN IDF ROOM 1018. PROVIDE PHOTO -CELL ON ROOF. REFER TO SHEET E5.00/3. 5 MDP-1 & 2 DIMENIONS ARE BASED ON EATON POW-R-LINE C. AUTOMATIC TRANSFER SWITCH DIMENSIONS ARE BASED ON GENERAC. PRIOR TO ORDERING FINAL EQUIPMENT, CONFIRM PHYSICAL DIMENSIONS AND THE SPACE REQUIREMENTS. NOTIFY DESIGN TEAM OF ANY CONFLICTS. 6 REFER TO SHEET E3.00 FOR LUMINAIRE SCHEDULE. KEYED NOTES 0 1 APPROXIMATE ROUTING/LOCATION OF SERVING UTILITY PRIMARY UNDERGROUND CONDUIT/CONDUCTORS. SHOWN FOR REFERENCE ONLY. PRIMARY CONDUIT, CONDUCTORS AND TERMINATIONS BY SERVING UTILITY. 2 NEW TRANSFORMER AND PAD BY SERVING UTILITY. COORDINATE WITH SERVING UTILITY, AS REQUIRED, FOR CONSTRUCTION SCHEDULE. 3 COORDINATE CONCRETE BASE AND PAD FOR GENERATOR WITH GENERAL CONTRACTOR PRIOR TO CONDUIT INSTALLATION AND GENERATOR PLACEMENT. 4 REFER TO SHEET E4.00 AND E4.01, ONE -LINE DIAGRAM, FOR CONDUIT AND WIRE REQUIREMENTS. 5 REFER TO DETAIL 6, SHEET E5.00, FOR TYPICAL TRENCHING DETAIL. 6 APPROXIMATE LOCATION OF TELEPHONE TERMINAL BOARD IN MDF 003. COORDINATE PRIOR TO CONDUIT INSTALLATION AND GENERATOR PLACEMENT. 7 PROVIDE (2) 4"CO WITH PULL CORD FOR TELEPHONE SERVICE CABLE. VERIFY EXACT LOCATION OF CONDUIT WITH TELEPHONE COMPANY. CONTRACTOR TO COORDINATE MAIN TELECOM CONNECTION ON NEW POWER POLE FOR ALL REQUIREMENTS. Plan set for Smoke Control only. p,N­ G ASy� G cn o - o 7 Z -o 3 �F F� SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 (N CD 00 d-) O Zz O= >Q L U cn 0 LL z O0 0 z_ O N > J > J O N _ 0 z m F_ w o Z oN U ~ � Q Q LU N U a REVISIO N DATE REASON FOR ISSUE 4 1/03/22 Addendum #03 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL SITE PLAN CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 SHEET NUMBER "Oil E1.00 1 2 3 4 4 ELECTRICAL POWER PLAN - LEVEL P1 SCALE: 1/8" = V-0" f 6 T7 8 9 10 12 13 5 NORTH i GENERAL POWER NOTES 1. NUMBER ADJACENT TO DEVICE OR HOME RUN INDICATES POLE POSITION WITHIN PANEL TO WHICH DEVICE SHALL BE CIRCUITED. 2. SEE SHEET E3.00-E3.01 FOR PANEL SCHEDULES. 3 CONTRACTOR TO VERIFY ALL CONDUCTOR SIZES FOR VOLTAGE DROP. KEYED NOTES O 1 CONNECT DOUBLE ELECTRICAL VEHICLE CHARGER PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE AND INSTALL JUNCTION BOX ON WALL AT +48" AFF WITH 1 "C, 3#8, 1#8G FROM PANEL INDICATED. 2 PROVIDE AND INSTALL JUNCTION BOX ON WALL AT +48" AFF FOR FUTURE ELECTRIC VEHICLE CHARGER. PROVIDE AND INSTALL 1"C WITH PULL CORD FROM PANEL PP. PROVIDE COVER PLATE AND LABEL "FUTURE ELECTRICAL CAR CHARGER" 3 INDOOR UNIT IS POWERED FROM THE OUTDOOR UNIT. COORDINATE WITH MECHANICAL FOR REQUIREMENTS. 4 PROVIDE 30W PER FOOT HEAT TRACE. COORDINATE WITH MECHANICAL FOR DETAILS. Plan set for Smoke Control only. PN A. G ASy� � cP A' FG1 SS/ONAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 CD N CD 00 z O Zz O = Q L U cn 0 LL z Oz 0 z_ O N > J > J O N _ 0 z m F- w o oN U ~ Z Q � Q LU N U a REVISIO N DATE REASON FOR ISSUE 1 6/18/21 Addendum #1 4 1/03/22 Addendum #03 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL POWER PLAN — LEVEL P1 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 SHEET NUMBER �111 E2.1 0 1 2 3 4 I I I I I I I 5 I I I I I 1 LLLL; I KIL SCALE: 1/8" = V-0" 7 I 8 I I 9 10 12 13 GENERAL POWER NOTES 1. NUMBER ADJACENT TO DEVICE OR HOME RUN INDICATES POLE POSITION WITHIN PANEL TO WHICH DEVICE SHALL BE CIRCUITED. 2. SEE SHEET E3.00-E3.01 FOR PANEL SCHEDULES. 3 CONTRACTOR TO VERIFY ALL CONDUCTOR SIZES FOR VOLTAGE DROP. � ■ ■"■ KEYED NOTES # 1 FAN IS POWERED AND CONTROLLED BY THE ROOM R ILIGHTING. 1-25 FRI 1P-25 2 FIRE SMOKE DAMPER, ROUTE CIRCUIT THROUGH J-BOX IN 9 ROOM 1018 FOR FIRE ALARM CONNECTION. I I I c� 0 0 0 � � o Cl) N CO L0 (O L U a U 0- � 0- CO m m m # vvv S=1==1 u1 ID 7 O 11 r- 11 P-5 I 1 P-22 GENERATOR 1031 14171M 1E 1F 9 (D `�to CV (D L?o (� o C d �o �Cit �o N N N U U U � M � M M NORTH Plan set for Smoke Control only. p,N • G AS G cP f 3/0NAL EN 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.dcengineering.net Phone:208.288.2181 Project:21 AMA01 N 00 M O 0 � Z _z O= Q W (n LL Z O0 z O > 10 J co J �_ O O N 0 F— o Z in W � Z N Cn ~ Q LU N U a REVISIO N DATE REASON FOR ISSUE 4 1/03/22 Addendum #03 5 03/14/22 Construction Set RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL POWER PLAN — LEVEL 1 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 r 1 2 3 4 5 6 7 I I I I I I I I I I I I I 4 ELECTRICAL POWER PLAN - LEVEL 2 SCALE: 1/8" = 1'-0" u 8 9 12 I I SEE SHEETS E2.20 AND E2.21 FOR ENLARGED UNIT PLANS SEE SHEETS E2.20 AND E2.21 FOR ENLARGED UNIT PLANS NORTH O GENERAL POWER NOTES 1. NUMBER ADJACENT TO DEVICE OR HOME RUN INDICATES POLE POSITION WITHIN PANEL TO WHICH DEVICE SHALL BE CIRCUITED. 2. SEE SHEET E3.00-E3.01 FOR PANEL SCHEDULES. 3 CONTRACTOR TO VERIFY ALL CONDUCTOR SIZES FOR VOLTAGE DROP. KEYED NOTES O 1 MOUNT RECEPTACLE 6" BELOW COUNTER TOP. 2 SURFACE MOUNTED WATERPROOF RECEPTACLE. MOUNT 6" BELOW CANOPY ROOF. 3 WEATHERPROOF KEYED SWITCH WITH STRING LIGHTS LABEL. Q 4 WEATHERPROOF KEYED SWITCH WITH LABEL FOR CCD 003 CORRESPONDING LABEL ON HEATER. 5 PROVIDE AND INSTALL 1/2" CONDUIT WITH PULLCORD TO FACP, AS REQUIRED, FOR SMOKE CONTROL LOUVER. Q COORDINATE SPECIFIC REQUIREMENTS WITH FIRE ALARM O 6 ELECTRICAL CONDUIT AND CONDUCTORS, ASSOCIATED 8 WITH L-4, TO BE ROUTED IN 2-HOUR SHAFT. Plan set for Smoke Control only. p,N G SNiti 9 z A pFGIS FSS/DNAL ENG\� 05/17/23 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.dcengineering.net Phone:208.288.2181 Project:21 AMA01 N 00 M O 0 � Z z 0= >Q 0 W cn 0 LL z 0 0 0 Z_ 0 N > J � J C: O N TC14— o O z m W � Z N � LU Q LU N U REVISIO N DATE REASON FOR ISSUE 6 02/15/23 SMOKE CONTROL REVISIONS 03/09/23 AS1007 8 05/17/23 SMOKE CONTROL REVISIONS RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL POWER PLAN — LEVEL 2 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 SHEET NUMBER E2.12 5 6 7 SEE SHEETS E2.00 AND E2.21 FOR ENLARGED UNIT PLANS. ITU ❑I ❑ �d I -C1 El IL-B5 IL-B6 16 314 jL 310 F DW____j - F1 DW o DW F o 00° � I - - - - JJ JJ I I 00 - - J IL O O REF REF O O REF IREF]LO 0 0 0 0 - 0 0LL SF SP1 IL- 1 jo 3 0 DW jREF.. I I I I F- T --------------- Tt 3P-5 II F ILL uj 0 324 _ � � 3 OOW 000 - -- 0 I I I I I I I W;- i-7 i- - RAF - - o D I '77 I IL-C2 IL-B 326 328 I I I 4 ELECTRICAL POWER PLAN - LEVEL 3 SCALE: 1/8" = 1'-0" — 3P-5,1-I�TR — F DW F IL-B2 ❑ 3❑❑ CP1-7 3P-7 TR 00 EF. O O �EF..[ 00 REF. < � I � J II L DW DW -B6 DW -7- E IL-B6 336 IL-1136 1 334 1 332 1 I I � I SEE SHEETS E2.00 AND E2.21 FOR ENLARGED UNIT PLANS. 10 12 TIL-C3 306 F® J7L 302 0 I n I I I I I I I I I I I I I I I 3P-7 STAIR - 02 ST2-03 1E 3P-EWR 0 0 O EF. O O EF. 0 - DW IL 6 DW I 8 I 3 Lp NORTH P GENERAL POWER NOTES 1. NUMBER ADJACENT TO DEVICE OR HOME RUN INDICATES POLE POSITION WITHIN PANEL TO WHICH DEVICE SHALL BE CIRCUITED. 2. SEE SHEET E3.00-E3.01 FOR PANEL SCHEDULES. 3 CONTRACTOR TO VERIFY ALL CONDUCTOR SIZES FOR VOLTAGE DROP. KEYED NOTES O Plan set for Smoke Control only. p,N - G AS G cP A' A �F FGI EEE� SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.dcengineering.net Phone:208.288.2181 Project:21 AMA01 N 00 0) o Z_z O= Q W cn LL z O0 z_ O > 10 J co J o� �0') p N T — o F— z m O W � Z N U Q LU Q N U a REVISIO N DATE REASON FOR ISSUE 1 6/18/21 Addendum #1 4 1/03/22 Addendum #03 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL POWER PLAN — LEVEL 3 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 SHEET NUMBER E2.13 1 2 3 4 5 6 7 ( 8 9 10 12 13 SEE SHEETS E2.20 AND E2.21 FOR ENLARGED UNIT PLANS. L 4 ELECTRICAL POWER PLAN - LEVEL 4 I SCALE: 1/8" = V-0" f SEE SHEETS E2.20 AND E2.21 FOR ENLARGED UNIT PLANS NORTH GENERAL POWER NOTES 1. NUMBER ADJACENT TO DEVICE OR HOME RUN INDICATES POLE POSITION WITHIN PANEL TO WHICH DEVICE SHALL BE CIRCUITED. 2. SEE SHEET E3.00-E3.01 FOR PANEL SCHEDULES. 3 CONTRACTOR TO VERIFY ALL CONDUCTOR SIZES FOR VOLTAGE DROP. KEYED NOTES O Plan set for Smoke Control only. p,N - G ASy� G cn - o z A' FG1 ERE SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 Q0 (N CD 00 d-) O Zz O= >Q W cn 0 LL z Oz 0 z_ O N > J > J O N _ 0 z m F- w o oN U ~ Z Q � Q LU N U a REVISIO N DATE REASON FOR ISSUE 1 6/18/21 Addendum #1 4 1/03/22 Addendum #03 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL POWER PLAN — LEVEL 4 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 GENERAL POWER NOTES 1. NUMBER ADJACENT TO DEVICE OR HOME RUN INDICATES POLE POSITION WITHIN PANEL TO WHICH DEVICE SHALL BE CIRCUITED. 2. SEE SHEET E3.00-E3.01 FOR PANEL SCHEDULES. 1 2 3 4 5 6 7 8 9 10 12 13 3 CONTRACTOR TO VERIFY ALL CONDUCTOR SIZES FOR VOLTAGE DROP. KEYED NOTES O 4 ELECTRICAL POWER PLAN - LEVEL 5 I SCALE: 1/8" = 1'-0" R r JO L E M U) U) C CU J .0 C J 0 n L+ rn nn Aklf rn n4 SEE SHEETS E2.00 AND E2.21 FOR ENLARGED UNIT PLANS. NORTH Plan set for Smoke Control only. p,N - G AS � cP A' FG1 ERE SS/ONAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 Q0 (N CD 00 d-) O Zz O = >Q W o LL z Oz 0 z_ O N > J > J O N _ 0 z m F- w o oN U ~ Z Q Q LU N U a REVISIO N DATE REASON FOR ISSUE 1 6/18/21 Addendum #1 4 1/03/22 Addendum #03 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL POWER PLAN - LEVEL 5 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 1 2 3 4 5 6 7 8 9 10 12 13 I I I I I I I I I I I oi ELECTRICAL POWER PLAN - LEVEL 6 SCALE: 1/8" = 1'-0" R r JO L E M U) U) C CU J .0 a. J 0 n SEE SHEETS E2.20 AND E2.21 FOR ENLARGED UNIT PLANS SEE SHEETS E2.00 AND FOR ENLARGED UNIT P ID NORTH GENERAL POWER NOTES 1. NUMBER ADJACENT TO DEVICE OR HOME RUN INDICATES POLE POSITION WITHIN PANEL TO WHICH DEVICE SHALL BE CIRCUITED. 2. SEE SHEET E3.00-E3.01 FOR PANEL SCHEDULES. 3 CONTRACTOR TO VERIFY ALL CONDUCTOR SIZES FOR VOLTAGE DROP. KEYED NOTES O 1 COORDINATE SALON ELECTRICAL REQUIREMENTS WITH SALON EQUIPMENT PROVIDER. 2 FAN IS POWERED AND CONTROLLED BY THE ROOM LIGHTING. 3 FIRE SMOKE DAMPER, ROUTE CIRCUIT THROUGH J-BOX IN ROOM 6002 FOR FIRE ALARM CONNECTION. Plan set for Smoke Control only. p,N - G AS � cP A' FG1 ERE SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 N CD 00 z O Zz Q W o LL z O 0 >w. 0 z O > J > J _ O N 0 z m F- o w Z oN U ~ � Q Q LU N U a REVISIO N DATE REASON FOR ISSUE 1 6/18/21 Addendum #1 4 1/03/22 Addendum #03 5 03/14/22 Construction Set RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL POWER PLAN - LEVEL 6 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 r GENERAL POWER NOTES 1. NUMBER ADJACENT TO DEVICE OR HOME RUN INDICATES POLE POSITION WITHIN PANEL TO WHICH DEVICE SHALL BE CIRCUITED. 2. SEE SHEET E3.00-E3.01 FOR PANEL SCHEDULES. 3 CONTRACTOR TO VERIFY ALL CONDUCTOR SIZES FOR VOLTAGE DROP. T 2 3 4 5 6 7 8 9 10 12 13 KEYED NOTES G) 1 ELECTRICAL AND FIRE ALARM CONDUIT AND CONDUCTORS, QASSOCIATED WITH EPF-1, TO BE ROUTED IN 2-HOUR SHAFT. 4 ELECTRICAL POWER PLAN - ROOF I SCALE: 1/8" = V-0" NORTH Plan set for Smoke Control only. PN A G Niti 9 P � � Sco SS/ONAL ENG 05/17/23 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 Q0 (N CD 00 d-) O Zz O= Q L U cn 0 LL z Oz z_ O N > J > J _ O N 0 z m F- o w Z oN U ~ � Q Q LU N U a REVISIO N DATE REASON FOR ISSUE 1 6/18/21 Addendum #1 4 1/03/22 Addendum #03 03/09/23 AS1007 SMOKE CONTROL 8 05/17/23 REVISIONS RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL POWER PLAN — ROOF CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 SHEET NUMBER �111 E2.17 1 2 T 4 5 6 T 8 9 10 12 13 i i 4 SPECIAL SYSTEMS POWER PLAN - LEVEL P1 SCALE: 1/8" = V-0" E NORTH CH) GENERAL SPECIAL SYSTEMS NOTES 1. ROUTE ALL COMMUNICATIONS CABLING ABOVE ACCESSIBLE CEILIG IN CORRIDORS. KEYED NOTES O 1 MOUNT RECEPTACLES TO CABLE TRAY DIRECTLY ABOVE EQUIPMENT, COORDINATE WITH LOW VOLTAGE CONTRACTOR FOR MOUNTING LOCATION. 2 4-4" CONDUITS TO PROPERTY LINE FOR INCOMMING COMMUNICATIONS SERVICES. COORDINATE WITH PROVIDERS FOR LOCATIONS. 3 3-4" SLEEVES BETWEEN COMMUNICATIONS ROOMS. PROVIDE FIRE STOPPING AS REQUIRED. REFER TO SHEET T400. 4 SEE SHEET T500 FOR CONDUIT REQUIREMENTS. 5 Plan set for Smoke Control only. p,N - G AS � cP A' FG1 ERE SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 N O 00 d) O Zz O= Q L U cn 0 LL z O z 0 z_ O N > J > J O N _ 0 z m F- w o Z oN U ~ � Q Q LU N U a REVISIO N DATE REASON FOR ISSUE RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SPECIAL SYSTEMS POWER PLAN - P1 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 1 2 3 4 5 6 I I I I I I I I I I I I I I I 1 I RISER ROOM 0 H0 I I I I I I MAW I so I 0 I I I I PARKING GARAGE 1039 10 0 3 IC AC-4E o ca �Z I I I I I I I I Z I I 7 8 9 10 12 I I I I I I I I I I 13 O - - O I !I I I I I I I I I I I I�EO III I I I I 0 MECHANICAL�------�-----�----------�----------T �-----------�----------� 1032 r — I i I i I I I I I I I I I I a a a a b - GENERATOR PARKING GARAGE RAMP 1040 I fi I— — — — — — — — — — — — — —---- - -61 a 1 SPECIAL SYSTEMS POWER PLAN - LEVEL 1 SCALE: 1/8" = 1'-0" R r JO L E M U) U) CU J .0 C J E n0 J Y I ill I I I J I i I TRASH COLLECTION I I - -i WF2 NORTH GENERAL SPECIAL SYSTEMS NOTES 1. ROUTE ALL COMMUNICATIONS CABLING ABOVE ACCESSIBLE CEILIG IN CORRIDORS. KEYED NOTES 1 MOUNT RECEPTACLES TO CABLE TRAY DIRECTLY ABOVE EQUIPMENT, COORDINATE WITH LOW VOLTAGE CONTRACTOR FOR MOUNTING LOCATION. 2 3-4" SLEEVES BETWEEN COMMUNICATIONS ROOMS. PROVIDE FIRE STOPPING AS REQUIRED. REFER TO SHEET T400. 3 SEE SHEET T500 FOR CONDUIT REQUIREMENTS. Plan set for Smoke Control only. 0 p,N - G AS � cP A' FG1 ERE SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 CD (N CD 00 d-) O Z z O � Q W C 0 LL z O z >w. 0 z O > J > J _� O O N r1_ z m LIJ p Z o U � Q LU N U a REVISIO N DATE REASON FOR ISSUE RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SPECIAL SYSTEMS POWER PLAN - LEVEL 1 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 1 2 3 4 55 6 7 4 SPECIAL SYSTEMS POWER PLAN - LEVEL 2 SCALE: 1/8" = V-0" R 8 i L� rn nn AAlf rn n4 JLL JI ILL 1 J LL.LV !'%I V V LL.L FOR ENLARGED UNIT PLANS 9 10 12 13 V NORTH GENERAL SPECIAL SYSTEMS NOTES 1. ROUTE ALL COMMUNICATIONS CABLING ABOVE ACCESSIBLE CEILIG IN CORRIDORS. KEYED NOTES O 1 MOUNT RECEPTACLES TO CABLE TRAY DIRECTLY ABOVE EQUIPMENT, COORDINATE WITH LOW VOLTAGE CONTRACTOR FOR MOUNTING LOCATION. 2 3-4" SLEEVES BETWEEN COMMUNICATIONS ROOMS. PROVIDE FIRE STOPPING AS REQUIRED. REFER TO SHEET T400. Plan set for Smoke Control only. p,N - G AS � cP A' FG1 ERE SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 CD (N CD 00 d-) O Zz O= Q o� LU C 0 LL z o0 >w.0 z o >� J > J O N _ 0 z m F- w o Z oN U ~ � Q Q LU N U a REVISIO N DATE REASON FOR ISSUE RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SPECIAL SYSTEMS POWER PLAN - LEVEL 2 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 1 2 3 4 O 6 70 8 O 10 12 13 c+rr C�LJrrTC� rn nn Anln rn nn 4 SPECIAL SYSTEMS POWER PLAN - LEVEL 3 SCALE: 1/8" = 1'-0" R J JI ILL I J LL.VV f INV LL.L I FOR ENLARGED UNIT PLANS. NORTH GENERAL SPECIAL SYSTEMS NOTES 1. ROUTE ALL COMMUNICATIONS CABLING ABOVE ACCESSIBLE CEILIG IN CORRIDORS. KEYED NOTES 1 MOUNT RECEPTACLES TO CABLE TRAY DIRECTLY ABOVE EQUIPMENT, COORDINATE WITH LOW VOLTAGE CONTRACTOR FOR MOUNTING LOCATION. 2 3-4" SLEEVES BETWEEN COMMUNICATIONS ROOMS. PROVIDE FIRE STOPPING AS REQUIRED. REFER TO SHEET T400. Plan set for Smoke Control only. of p,N - G AS � cP A' o �F FBI ERE SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 (N CD 00 d-) O Zz O= Q o� LU C 0 LL z o0 �LL] z o >� J > J O N _ 0 z m F- w o Z oN U ~ � Q Q LU N U a REVISIO N DATE REASON FOR ISSUE RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SPECIAL SYSTEMS POWER PLAN - LEVEL 3 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 1 2 3 4 5 6 I I I I I I II I I I I I IL-Cl 41 --AL 416 F-1 I II I I I 111-411 42 II I n Ea I I 422 I I - —II I II I I II Il fi C IL-B1 424 ' — 1 i i 0 I 7 F I I I I IL-C2 IL-1135 ' IL-1132 426 m 428 430 7 8 SEE SHEETS E2.20 AND E2.21 FOR ENLARGED UNIT PLANS. IL-1135 IL-1131 414 412 I 0 —3 L --i L L /N� I 1� �I IL-1136 IL-1136 432 434 I SEE SHEETS E2.20 AND E2.21 FOR ENLARGED UNIT PLANS T 9 I IL-1136 IL-B1 410 408 ❑ I CORRIDOR 4100 IL-B6 436 �I I IL-B6 438 I I 4 IL-05 (TYPE A) 404 I IL-1133 (TYPE A) 402 I IL-B6 440 SPECIAL SYSTEMS POWER PLAN - LEVEL 4 \ SCALE: 1/8" = 1'-0" NORTH R 13 GENERAL SPECIAL SYSTEMS NOTES 1. ROUTE ALL COMMUNICATIONS CABLING ABOVE ACCESSIBLE CEILIG IN CORRIDORS. KEYED NOTES 1 MOUNT RECEPTACLES TO CABLE TRAY DIRECTLY ABOVE EQUIPMENT, COORDINATE WITH LOW VOLTAGE CONTRACTOR FOR MOUNTING LOCATION. 2 3-4" SLEEVES BETWEEN COMMUNICATIONS ROOMS. PROVIDE FIRE STOPPING AS REQUIRED. REFER TO SHEET T400. Plan set for Smoke Control only. of p,N - G AS � cP A' o �F FBI ERE SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 (N CD 00 d-) O Zz O = Q L U v6 0 LL z �Lu z O > J ns J O N _ 0 z m F- Lu o Z oN U ~ � Q LU N U a REVISIO N DATE REASON FOR ISSUE RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SPECIAL SYSTEMS POWER PLAN - LEVEL 4 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 1 2 3 4 5 6 7 8 9 10 12 13 4 SPECIAL SYSTEMS POWER PLAN - LEVEL 5 SCALE: 1/8" = 1'-0" R OCC OLJCCTO C7 00 A KIM C7 71l SEE SHEETS E2.00 AND E2.21 FOR ENLARGED UNIT PLANS. NORTH GENERAL SPECIAL SYSTEMS NOTES 1. ROUTE ALL COMMUNICATIONS CABLING ABOVE ACCESSIBLE CEILIG IN CORRIDORS. KEYED NOTES 1 MOUNT RECEPTACLES TO CABLE TRAY DIRECTLY ABOVE EQUIPMENT, COORDINATE WITH LOW VOLTAGE CONTRACTOR FOR MOUNTING LOCATION. 2 3-4" SLEEVES BETWEEN COMMUNICATIONS ROOMS. PROVIDE FIRE STOPPING AS REQUIRED. REFER TO SHEET T400. Plan set for Smoke Control only. of p,N - G AS � cP A' o �F FBI ERE SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 (N CD 00 d-) O Zz O= >Q W cn 0 LL z 0 0 z_ O N > J > J O N _ 0 z m F- w o Z oN U ~ � Q Q LU N U a REVISIO N DATE REASON FOR ISSUE RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SPECIAL SYSTEMS POWER PLAN - LEVEL 5 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 1 SPECIAL SYSTEMS POWER PLAN - LEVEL SCALE: 1/8" = 1'-0" R 7 i 9 T10 12 13 8 - - ILL I V -- -- I - 1 FOR ENLARGED UNIT PLANS NORTH GENERAL SPECIAL SYSTEMS NOTES 1. ROUTE ALL COMMUNICATIONS CABLING ABOVE ACCESSIBLE CEILIG IN CORRIDORS. KEYED NOTES 1 RECEPTACLE TO BE MOUNTED ABOVE CEILING. COORDINATE WITH LOW VOLTAGE CONTRACTOR FOR MOUNTING LOCATION. 2 4-SQUARE DEEP BOX/2-GANG MUDRING WITH 3/4" CONDUIT TO ACCESSIBLE CEILING FOR AV PANEL. 3 4-SQUARE DEEP BOX/2-GANG MUDRING WITH 3/4" CONDUIT TO ACCESSIBLE CEILING FOR CONTROL PANEL. 4 MOUNT RECEPTACLES TO CABLE TRAY DIRECTLY ABOVE EQUIPMENT, COORDINATE WITH LOW VOLTAGE CONTRACTOR FOR MOUNTING LOCATION. 5 3-4" SLEEVES BETWEEN COMMUNICATIONS ROOMS. PROVIDE FIRE STOPPING AS REQUIRED. REFER TO SHEET T400. Plan set for Smoke Control only. of p,N - G AS � cP A' o �F FBI ERE SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 (N CD 00 d-) O Zz O= Q o� LU C 0 LL z o0 >w.0 z o >� J > J O N _ 0 z m F- w o Z oN U ~ � Q Q LU N U a REVISIO N DATE REASON FOR ISSUE RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT SPECIAL SYSTEMS POWER PLAN - LEVEL 6 CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 SHEET NUMBER E2.36 )711 r L r� :h :O >D L 7 E M U) U) N C f0 J JJ J .0 C J 0 n L ASI I CCD ASI I z ASI ( z CCD ASI 00 ASI 00 PTACLES 2640 VA 220-44 10kVA @ 100%, ELSE @ 50% 2640 VA H - PROVIDE HACR TYPE BREAKER 157442 VA 220-60 100% 157442 VA R LARGEST MOT.: 3840 12822 VA 220-50 100%+ LARGEST x 25% 13782 VA KITCHEN # OF KIT. UNITS: 0 OVA 220-56 SEE LOAD CACULATIONS, SHEET E7.6 PANELBOARD SCHEDULE PANEL: IL VOLTAGE: 208/120V PHASE 3 WIRE:4 AMPERE RATING: 100A SC RATING: 42K A.I.C. MAIN: MAIN LUG ENTRY: MOUNTING: SURFACE LOADS: Amps VA PHASE A: 29 3456 PHASE B: 22 2648 PHASE C: 20 2459 TOTAL: 8563 LOAD TYPES: 1 = LIGHTING 2 = RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN REMARKS: LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) 324 LTS - LVL P1 PARKING 1 20 1 1 A 2 20 1 1 LTS - LVL P1 STOR, BOILER, LAUNDRY 728 405 LTS -LVLI PARKING 1 20 1 3 B 4 20 1 1 LTS LVL P1 & LVL 1 VEST., CORRIDOR 200 200 LTS - BLDG EXTERIOR 1 20 1 5 C 6 20 1 1 LTS - LVL 2 VEST, CORRIDOR 1242 150 LTS - COURTYARD WALL SCONCES 1 20 1 7 A 8 20 1 1 LT - LVL VE T,. CORRIDOR 1182 SPARE 20 1 9 B 10 20 1 1 LTS -LVL 2-3 1248 SPARE 20 1 11 C 12 20 1 1 LTS -LVL 1 1017 SPARE 20 1 13 1 A 14 20 1 1 LTS - LVL 1 COMMON AREAS 1072 • SPARE 30 2 15 B 16 20 1 1 LTS - LVL 1 COMMON AREAS 795 SPARE - - 17 C 18 20 1 SPARE 7 SPARE 30 2 19 A 20 20 1 SPARE SPARE - - 21 B 22 20 1 SPARE SPARE 20 1 23 C 24 20 1 SPARE SPARE 20 1 25 A 26 20 1 SPARE SPARE 20 1 27 B 28 20 1 SPARE SPARE 20 1 29 C 30 20 1 SPARE SPARE 20 1 31 A 32 20 1 SPARE SPARE 20 1 33 B 34 20 1 SPARE SPARE 20 1 35 C 36 20 1 SPARE SPARE 20 1 1 1 37 1 A 3 SPARE SPARE 20 1 39 Bttft- SPARESPARE 20 1 41 C- SPARE RFI 30 �Q —CCD 00: ---:: - A PTACLES IR LARGEST MOT.: 0 PHASE C: 113 13600 OVA 220-44 10kVA @ 100%, ELSE @ 50% 0 VA H - PROVIDE HACR TYPE BREAKER OVA 220-60 100% 0 VA OVA 220-50 100%+ LARGEST x 25% 0 VA PANELBOARD SCHEDULE LUAUJ: VA PHASE A: 178 21382 PHASE B: 214 25712 PHASE C: 155 18634 TOTAL: 65728 LUAU I TYCJ: -I = LINK I INI 2 = RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN KCIVIAKNJ: LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED 1080 RE - RI ER ROOM,PARKING 2 20 1 1 A 2 20 1 1 2 1 SPARE 180 REC- MECHANICAL 2 20 1 3 B 4 20 1 2 SPARE 180 REC-GENERATOR 2 20 1 5 C 6 20 1 2 SPARE SPARE 20 1 7 A 8 20 1 2 SPARE SPARE 20 1 9 B 10 20 1 2 REC - 1ST FLOOR WALL MOUNT TV's SPARE 20 1 11 C 12 20 1 SPARE 900 REC - SALES MANAGER 2 20 1 13 A 14 20 1 SPARE 540 REC - EXEC DIR 2 20 1 15 B 16 20 1 3 EF-T1 TRASH COMPACTOR SPARE 20 1 17 C 18 20 1 3 WATER COOLER ASI 0 94 720 REC- RECEPTION, BUSINESS OFFICE 2 20 1 19 A 20 20 1 2 REC- RR 1005.1006,1019A,1026 900 REC - DISCOVERY/CONF 2 20 1 21 B 22 20 1 1 2 REC - RE EIV, CORR, TRASH, EF-5, E 720 RE - MAIL, ELEV LOBBY, CORRIDOR 2 20 1 23 C 24 20 1 1 2 REC - DRY STOR 1080 REC - DINING 2 20 1 25 A 26 20 1 2 REC - FAMILY ROOM REFRIGERATOF 360 REC- DINING 2 20 1 27 B 28 20 1 2 REC- FAMILY ROOM MICROWAVE SPARE 20 1 29 C 30 20 1 2 REC - FAMILY ROOM Q SPARE 20 1 31 A 1 32 20 1 3 EWH-1 RISER ROOM 1034 \SI 007 SPARE 20 1 33 B 34 20 1 SPARE SPARE 20 1 35 C 36 15 2 4 FC-1E 3324 UH-1 3 40 3 37 A 38 4 3324 -= 3 — — 39 B 40 15 4 FC-1F Q7 3324 3 41 C 42 4 1200 REC - EMP. LOUNGE REFRIGERATOR 5 20 1 43 A 44 20 1 SPARE 1000 REC- EMP LOUNGE MICROWAVE 1 5 1 20 1 45 B 46 30 2 4 HP-1E 360 REC - EMP LOUNGE COUNTER 2 20 1 47 C 48 — — 4 — SPARE 20 1 49 A 50 40 2 4 HP-1F SPARE 20 1 51 B 52 — -- 4 — SPARE 20 1 53 C 54 20 1 SPARE SPARE 20 1 1 55 A 56 30 3 3 EF-P2 3120 HP-1C 4 50 2 57 B 58 -- -- 3 — 3120 *** 4 * 59 C 60 -- -- 3 — AS I 034 3120 HP-1D 4 50 2 61 A 20 1 3 IDF 1018-SPECIAL SYSTEMS 3120 *** 4 * * 63 B 20 1 3 IDF 2006- SPECIAL SYSTEMS 2080 HP-2 4 30 2 65 C 20 1 3 IDF 2002 - SPECIAL SYSTEMS N64 2080 * 4 * 67 A 20 1 SPARE 2080 HP-3 4 30 2 69 B 20 1 SPARE 2080 *4 71 C 20 1 SPARE SPARE 20 1 73 A 74 20 1 SPARE SPARE 20 1 75 B 76 20 1 SPARE SPARE 20 1 77 C 78 20 1 SPARE ASI 0 SPARE 20 1 79 A 80 20 1 1 1 1 SPARE SPARE 20 1 81 B 82 20 1 1 1 1 SPARE -TACLES 12826 VA 220-44 10kVA @ 100%, ELSE @ 50% 11413 VA H - PROVIDE HACR TYPE BREAKER 19522 VA 220-60 100% 19522 VA R LARGEST MOT.: 3600 31180 VA 220-50 100%+ LARGEST x 25% 32080 VA Q720 PHASE A: 617 74098 PHASE B: 581 69754 PHASE C: 577 69215 TOTAL: 213067 LOAD (VA) LOAD SERVED 1260 REC - CORRIDOR 6000 1260 REC - CORRIDOR 5000 1080 REC - CORRIDOR 4000 1080 REC - CORRIDOR 3000 1080 REC - CORRIDOR 2000 720 FC-1A, 1B *** 1920 IDF 6002 - SPECIAL SYSTEMS S1 007 192n I InF M09-pvFr.IAI CYATFMA PANELBOARD SCHEDULE 1 = LIUH I INU KtMAKKS: 2 = RECEPTACLES NOTE #1 - PROVIDE "RED" HANDLE AND CONNECT TO FIRE ALARM SYSTEM 3 = MISC NOTE #2 - DENOTES SHUNT TRIP BREAKER 4 = MOTOR 5 = KITCHEN LOAD AMPS/ CKT CKT AMPS/ LOAD NOTE TYPE POLES NO PHASE NO POLES TYPE I NOTE I LOAD SERVED 2 20 1 1 1 1 A 1 2 20 1 1 3 1 1 WH-1, WH-2, WH-3, FUTURE IDF 2006 - SPECIAL SYSTEMS CP-1 L LSI 500 If-- go-67—AS I 1920 1 DF 6011 - SPECIAL SYSTEMS 1 3 20 1 1 1 27 1 B 28 1 20 1 1 3 1 1 MDF 0003 - SPECIAL SYSTEMS 1920 I Q 1920 IDF 6011 - SPECIAL SYSTEMS 3 20 1 29 C 30 20 1 3 MDF 0003 - SPECIAL SYSTEMS 1920 OAD ASI 007 1920 IDF 5002 - SPECIAL SYSTEMS 3 20 1 31 A 32 20 1 3 MDF 0003 - SPECIAL SYSTEMS 1920 (VA) 1920 1920 1920 Q 1920 IDF 5006-SPECIAL SYSTEMS 3 20 1 39 B 40 20 1 SPARE 1808 ASI 007 1920 IDF 5006-SPECIAL SYSTEMS 3 20 1 41 C 42 20 1 SPARE 1800 1920 1920 Q 1920 1920 ASI 007 1920 IDF 4002-SPECIAL SYSTEMS 3 20 1 49 A 50 15 2 4 720 720 720 Q 720 —CCD 003 1920 DF 4006 - SPECIAL SYSTEMS 3 20 1 57 B 58 20 1 4 TF-1, EF-5 1 ST, 2ND, 3RD, 4TH FLOOR 137 360 360 R M 2 20 1 59 C 60 20 1 4 - -5 5 , 105 42 500 Q SPARE 20 1 61 A 62 20 1 SPARE 1920 IDF 3002-SPECIAL SYSTEMS 3 20 1 63 B 64 20 1 SPARE �+ AS1 007 1920 DF 3002-SPECIAL SYSTEMS 3 20 1 65 C 66 20 1 SPARE 1260 1 REC - CORRIDOR 3000 1 1 2 1 20 1 1 1 31 1 A 1 32 1 20 1 1 1 3 1 1 OF 3002 - SPECIAL SYSTEMS 500 600 REC - FITNESS CROSSTRAINER 3 20 1 33 B 34 20 1 3 IDF 4006 -SPECIAL SYSTEMS 500 600 REC - FITNESS TREADMILL 3 20 1 35 C 36 20 1 3 IDF 4002 -SPECIAL SYSTEMS 500 �100RF1 30'AS7Q 1007 'ztiv An ASI C 7OADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 6149 VA 210-19 125% 7686 VA E - DENOTES EXISTING BREAKER TO REMAIN. RECEPTACLES 3420 VA 220-44 10kVA @ 100%, ELSE @ 50% 3420 VA N - DENOTES NEW BREAKER REQUIRED. MISC. 14030 VA 220-60 100% 14030 VA R- DENOTES TO REUSE EXISTING BREAKER. MOTOR LARGEST MOT.: 17640 17640 VA 220-50 100%+ LARGEST x 25% 22050 VA H - PROVIDE HACR RATED BREAKER KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 114 A 131 A 1920 IDF 5002-SPECIAL SYSTEMS 3 20 1 33 B 34 20 1 3 STOR. 4004-SPECIAL SYSTEMS 1920 1920 IDF 5002-SPECIAL SYSTEMS 3 20 1 35 C 36 20 1 3 STOR. 3004-SPECIAL SYSTEMS 1920 540 REC: RECEPTION DESK 2 20 1 37 A 38 20 1 3 FIRE SMOKE DAMPERS 540 1920 IDF 5006 -SPECIAL SYSTEMS 3 20 1 43 A 44 20 1 3 GENERATOR BLOCK HEATER 1600 1920 IDF 4002 -SPECIAL SYSTEMS 3 20 1 45 B 46 20 1 3 GENERATOR BATTERY CHARGER 200 360 REC: DINING 1007 2 20 1 47 C 48 20 1 2 REC -GENERATOR SERVICE 160 1920 IDF 4002-SPECIAL SYSTEMS 3 20 1 51 B 52 — — 4 — 720 1920 IDF 4006 -SPECIAL SYSTEMS 3 20 1 53 C 54 15 2 4 FGS, 6B 460 1920 IDF 4006 -SPECIAL SYSTEMS 3 20 1 55 A 56 — — 4 — 460 SI 007 0 LSI-005 PTACLES 7560 VA 220-44 10kVA @ 100%, ELSE @ 50% 7560 VA H - PROVIDE HACR RATED BREAKER 81620 VA 220-60 100% 81620 VA S - PROVIDE SHUNT TRIP BREAKER R LARGEST MOT.: 2928 7010 VA 220-50 100%+ LARGEST x 25% 7742 VA L FI 1 007 1 007 LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 0 VA 210-19 125% 0 VA E -DENOTES EXISTING BREAKER TO REMAIN. RECEPTACLES 540 VA 220-44 tOkVA @ 10000/a, ELSE @ 50% 540 VA N -DENOTES NEW BREAKER REQUIRED. MISC. 1605 VA 220-60 100% 1605 VA R -DENOTES TO REUSE EXISTING BREAKER. MOTOR LARGEST MOT.: 0 VA 220-50 100%+ LARGEST x 25% 5400 VA H -PROVIDE HACR RATED BREAKER KITCHEN # OF KIT. UNITS: 36 122835 VA 220-56 79843 VA S -PROVIDE SHUNT TRIP BREAKER TOTAL 347 A 243 A ANTHOLOGY OF EDMONDS LUMINAIRE DESCRIPTION MANUFACTURER CATALOG NUMBER LAMPS INPUT WATTS VOLTAGE MOUNTING NOTE COMMENTS EX1 EXIT SIGNS NORA NX-603-LED/R W/WET LOCATION OPTION NEG-60 LED 2 MVOLT SURFACE EXIT 61 15" PUCK LIGHT THOMAS LIGHTING CL781434 WHITE FINISH LED 30 120 SURFACE COMMON AREA CORRIDORS B2 5" PUCK LIGHT ELK LIGHTING MLE1200-5-30, WHITE FINISH,3000K LED 9 120 SURFACE CORRIDORS, COMMON AREAS GL1 2x2 LAY -IN METALUX 22FPX42-L835 LED 41.5 MVOLT RECESSED OFFICES. KITCHEN, BOH GL2 2x2 LAY -IN METALUX 22FPX-21-L835 LED 21.5 MVOLT RECESSED OFFICES. KITCHEN, BOH PD1 DECORATIVE PENDANT KUZCO MINA PENDANT KZC610336 LED 8 120V PENDANT GREAT ROOM FIREPLACE PD2 DECORATIVE CHANELIER TECH LINGER 18-LIGHT CHANDELIER 700LNG 18 B LED930 LED 80 120V PENDANT GREAT ROOM SITTING AREA PD3 DECORATIVE PENDANT TECH ORBEL ROUND PENDANT 700 TD OBLR R LED930 (1) LED BI-PIN G9 5 120V PENDANT GREAT ROOM RECEPTION PD4 DECORATIVE PENDANT ARTCRAFT LUGANO MULIT-LIGHT PENDANT ACRP313896 (3) 43W A19 LED 18 120V PENDANT MAIL PD5 DECORATIVE PENDANT NEMO CROWN PLANA LINEA PENDANT NIL457374 (10) 3W G9 LED 30 120V PENDANT BISTRO BANQUETTE PD6 DECORATIVE PENDANT PETITE FRITURE VERTIGO PENDANT BIS615410 (1) 53W A19 LED 6 24V PENDANT BISTRO BAR PD7 DECORATIVE PENDANT SERENA &LILY SANTA BARBARA PENDANT LA-H72-06 (1) 60W A19 LED 9 120V PENDANT DINING HOST PD8 DECORATIVE PENDANT SERENA &LILY SANTA BARBARA ROUND PENDANT LA-H82 (1) 60W A19 LED 9 120V PENDANT DINING HOST PD9 DECORATIVE PENDANT SERENA &LILY HEADLANDS PENDANT LA-H104-04 (1) 60W A19 LED 9 120V PENDANT DINING HOST PD10 DECORATIVE PENDANT POTTERY BARN FLORA RATTAN (1) 60W A19 LED 9 120V PENDANT DINING HOST PD11 DECORATIVE PENDANT dweLED LIGHTING LOLLI PENDANT UU572120 LED 6.5 120V PENDANT DINING NORTH FEATURE WALL PD12 DECORATIVE PENDANT MODERN FORMS COSMIC CHANDELIER MFR617499 (7) 7W LED 49 120V PENDANT DINING SOUTH FEATURE WALL PD13 DECORATIVE PENDANT AFX APEX PENDANT AFX APP1932LAJUDES-JT LED 42 120V PENDANT FAMILY PD14 DECORATIVE PENDANT AQUA CREATIONS TE LED PENDANT AQUY19970 LED 13.5 120V PENDANT DISCOVER/CONFERENCE PD15 DECORATIVE PENDANT KENNETH COBONPUE C U C ME ROUND PENDANT HIV130273 (1) 60W A19 LED 9 120V PENDANT SALON RECEPTION DESK PD16 DECORATIVE PENDANT SHADES OF LIGHT FLEMING CEILING LIGHT FM20084 ZM (4) 60W El LED 36 120V PENDANT SALON PEDICURE STATION PD17 DECORATIVE PENDANT AQUA CREATIONS M LED PENDANT AQUY19940 LED 35 120V PENDANT COMMUNITY ROOM, ACTIVITY PD18 DECORATIVE PENDANT QUOIZEL ROMAIN MINI PENDANT RM11509EK (1) 75W A19 LED 12 120V PENDANT COMMUNITY ROOM KITCHEN ISLAND SM1 DECORATIVE FLUSH BETHEL INTERNATIONAL FLUSH MOUNT LG03 (3) A19 LED 20 120V FLUSH CORRIDOR GENERAL ACCENT SM2 DECORATIVE SEMI -FLUSH MINKA LAVERY SEMI -FLUSH MOUNT 4107-66 LED 14 120V SEMI -FLUSH CORRIDOR GENERAL ACCENT S1 4' WRAP METALUX 4VT2-LD5-4-DR-UNV-L835-CD1-WL-U LED 30 MVOLT SURFACE STAIRS S2 2' WRAP METALUX 2VT2-LD5-2-DR-UNV-L835-CD1-WL-U LED 17 MVOLT SURFACE ELEVATOR PIT S3 4'SUSPENDED KUZCO VEGA MINOR LED LINEAR BLACK KUZP266423 LED 32 MVOLT SUSPENDED SALON S4 4' STRIP METALUX 4SNLED-LD5-52SL-SLW-UNV-L835-CD1-U LED 52 MVOLT SURFACE JANITOR, IDF, ELEC, MECH, TRASH U1 LED TAPE LIGHT NORA NUTP51-930 LED 2.7/FT 24V SURFACE COVES, UNDER BAR U2 RECESSED WALL WASH MARK SPRLED-LOP-13FT-RLP-G9-80CR1-35K400LMF-MINI-MVOLT LED 3.4/FT MVOLT RECESSED GREAT ROOM V1 DECORATIVE VANITY JUSTICE DESIGN GROUP FUSION ELEVATE MATTE BLACK JDGP268764 LED 22 120V WALL RESTROOM 1005 & 1006 V2 DECORATIVE VANITY ROGUE DECOR FIREFLY MULTI BATHROOM VANITY LIGHT ROG858700 LED 22.5 120V WALL RESTROOM 1019A & 1025A WD2 DECORATIVE SCONCE GEORGE KOVACS FABRIC WALL SCONCE (BRONZE W/OFF-WHITE) UU169009 (1) A19 LED 6 120V SCONCE UNIT ENTRY UNIT LIGHTING UA 7" PUCK LIGHT ALLADIN KYD-08E-15-WH LED 15 120V SURFACE UNITS UB 13" PUCK LIGHT ALLADIN KYD-13E-25-WH LED 25 120V SURFACE UNITS UC UNDER CABINET AMERICAN ALC2-18 LED 6 120V SURFACE UNITS UNDER CABINET LID 2' VANITY PROGRESS P2159-09 (3) 100W A19 LED 36 120V WALL UNIT BATHROOMS LIE CLOSET LIGHT LITHONIA FMMCL 840 PIR LED 10.4 120V WALL UNIT CLOSETS OF EXTERIOR SCONCE NUVO 62-1142 LED 10 120V WALL UNITS EXTERIOR 1. Design is based on first named manufacturer. 2. Contractor shall provide and coordinate all fixture mounting accessories. 3. Contractor to coordinate final color with owner prior to ordering. 4. Contractor to coordinate finish colors of luminaires in wood ceiling with Architect. 5. Provide hower approved fixture equal to A fixture. ANTHOLOGY OF EDMONDS (OUTDOOR) LUMINAIRE DESCRIPTION MANUFACTURER CATALOG NUMBER LAMPS INPUT WATTS VOLTAGE MOUNTING NOTE COMMENTS RR1 RECESSED CAN LITHONIA LDN6 40/15 L06AR LSS MVOLT GZ10 LED 20.5 MVOLT RECESSED EXTERIOR BUILDING RR1 E RECESSED CAN W/EMERGENCY LITHONIA LDN6 40/15 L06AR LSS MVOLT GZ10 EL LED 20.5 MVOLT RECESSED EXTERIOR BUILDING SL1 LED PARKING GARAGE LIGHT LITHONIA VCPG LED V4 P1 40K 80CRI TSM MVOLT SRM DDBXD LED 27 MVOLT SURFACE PARKING GARAGE SL1E LED PARKING GARAGE LIGHT W/ EMERGENCY LITHONIA VCPG LED V4 P1 40K 80CR1 T5M MVOLT SRM E8WC DDBXD LED 27 MVOLT SURFACE PARKING GARAGE SM3 EXTERIOR MAIN ENTRY FRACTAL PC010107-BC LED 67 MVOLT SURFACE EXTERIOR MAIN ENTRY SM4 EXTERIOR MAIN ENTRY FRACTAL PC010105-BC LED 47 MVOLT SURFACE EXTERIOR MAIN ENTRY WD1 EXTERIOR SCONCE NUVO 62-1142 LED 10 120V SCONCE COURTYARD WD3 NOT USED WL1 EXTERIOR LED WALLPACK LITHONIA WSR LED P1 40K SR2 MVOLT PE DBLXD LED 19.6 MVOLT WALL PARKING GARAGE WL1E EXTERIOR LED WALLPACK W/ EMERGENCY LITHONIA WSR LED P1 40K SR2 MVOLT PE E20WC DLXD LED 19.6 MVOLT WALL EXTERIOR BUILDING Plan set for Smoke Control only. LL RFI-055 N p,N G Sy, ,9 co o N (C) Z A FSS/ONAL ENO'\ 05/17/23 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 N 0 00 Z z O = Q W (n 0 LL z O0 0 z O Q> > J > J _� O -0 _ O z m W Z o U) � Q LU Q\ N U a REVISIO N DATE REASON FOR ISSUE 04/03/23 RF1250 7 04/04/23 HEATER SUBSTITUTION 05/05/23 RF1304 8 05/17/23 SMOKE CONTROL REVISIONS RES U 6 May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL SCHEDULES CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 SHEET NUMBER �111 E3.00 E PANELBOARD SCHEDULE PANEL: I2A VOLTAGE: 208/120V PHASE: 3 WIRE: 4 AMPERE RATING: 600A SC RATING: 22K A.I.0 MAIN: MAIN LUG ENTRY: MOUNTING:SURFACE LOADS AMPS VA PHASE A: 0 0 PHASE B: 0 0 PHASE C: 0 0 TOTAL: 0 LOAD TYPES: 1 = LIGHTING 2 = RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN REMARKS: SEE LOAD CACULATIONS, THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) ROOM 208 IL-B1 3 125 2 1 A 2 125 2 3 ROOM 214 IL-135 3 * 3 B 4 * 3 ROOM 210 IL-136 3 125 2 5 C 6 125 2 3 ROOM 216 IL-Cl ••• 3 * * 7 A 8 * * 3 *** ROOM 211 IL-136 1 3 125 2 1 9 B 10 125 2 3 ROOM 218 IL-C3 * 3 * 11 C 12 * 3 ROOM 212 IL-131 3 125 2 13 A 14 125 2 3 ROOM 220 IL-131 * 3 * 15 B 16 * 3 ROOM 213 IL-C4 3 125 2 17 C 18 125 2 3 ROOM 222 IL-A2 * 3 19 A 20 * 3 SPARE 20 1 21 B 22 125 2 3 ROOM 223 IL-132 + DEN SPARE 20 1 23 C 24 3 SPARE 20 1 25 A 26 125 2 3 ROOM 224 IL-131 SPARE 20 1 27 B 28 3 SPARE 20 1 29 C 30 125 2 3 ROOM 225 IL-132 SPARE 20 1 31 A 32 * 3 SPARE 20 1 33 B 34 125 2 SPARE SPARE 20 1 35 C 36 SPARE 20 1 37 A 38 20 1 SPARE SPARE 20 1 39 B 40 1 20 1 1 1 SPARE SPARE 201 1 1 41 C f 42 1 20 1 1 1 SPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 0 VA 210-19 125% 0 VA H - PROVIDE HACR RATED BREAKER RECEPTACLES 0 VA 220-44 10kVA @ 100%, ELSE @ 50% 0 VA MISC. 0 VA 220-60 100% 0 VA MOTOR LARGEST MOT.: 0 VA 220-50 100% + LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 0 A 0 A PANELBOARD SCHEDULE PANEL: 12B VOLTAGE: 208/120V PHASE: 3 WIRE: 4 AMPERE RATING: 600A SC RATING: 22K A.I.0 MAIN: MAIN LUG ENTRY: MOUNTING: SURFACE LOADS AMPS VA PHASE A: 0 0 PHASE B: 0 0 PHASE C: 0 0 TOTAL: 0 LOAD TYPES: 1 = LIGHTING 2 = RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN REMARKS: SEE LOAD CACULATIONS, THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) ROOM 230 IL-132 3 125 2 1 A 2 125 2 3 ROOM 206 IL-C3 ••• 3 * * 3 B 4 * * 3 *** ROOM 232 IL-66 3 125 2 5 C 6 125 2 3 ROOM 226 IL-C2 3 7 A 8 3 ROOM 234 IL-136 3 125 2 9 B 10 125 2 3 ROOM 228 IL-135 * 3 11 C 12 3 * ROOM 236 IL-136 3 125 2 13 A 14 20 1 SPARE ' 3 15 B 16 20 1 SPARE ROOM 238 IL-136 3 125 2 17 C 18 20 1 SPARE * 3 19 A 20 20 1 ISPARE ROOM 240 IL-66 3 125 2 21 B 22 20 1 SPARE ' 3 23 C 24 20 1 SPARE ROOM 201 IL-513 3 125 2 25 A 26 20 1 SPARE * 3 27 B 28 20 1 SPARE ROOM 202 IL-133 (TYPE A) 3 125 2 29 C 30 20 1 SPARE ' 3 31 A 32 20 1 SPARE ROOM 203 IL-A1 (TYPE A) 3 125 2 33 B 34 20 1 SPARE * 3 35 C 36 1 20 1 1 1 SPARE ROOM 204 IL-05 (TYPE A) 3 125 2 37 A 38 20 1 SPARE * 3 39 B 40 20 1 SPARE SPARE 20 1 41 C 42 20 1 SPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 0 VA 210-19 125% 0 VA H - PROVIDE HACR RATED BREAKER RECEPTACLES 0 VA 220-44 10kVA @ 100%, ELSE @ 50% 0 VA MISC, 0 VA 220-60 100% 0 VA MOTOR LARGEST MOT.: 0 VA 220-50 100%+ LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 0 A 0 A PANELBOARD SCHEDULE PANEL: I3A VOLTAGE: 208/120V PHASE: 3 WIRE: 4 AMPERE RATING: 600A SC RATING: 22K A.I.0 MAIN: MAIN LUG ENTRY: MOUNTING: SURFACE LOADS: AMPS VA PHASE A: 0 0 PHASE B: 0 0 PHASE C: 0 0 TOTAL: 0 LOAD TYPES: 1 = LIGHTING 2 = RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN REMARKS: SEE LOAD CACULATIONS, THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) ROOM 308 IL-B1 3 125 2 1 A 2 125 2 3 ROOM 314 IL-85 3 3 B 4 3 ROOM 310 IL-136 3 125 2 5 C 6 125 2 3 ROOM 316 IL-Cl 3 7 A 8 3 ROOM 311 IL-137 3 125 2 9 B 10 125 2 3 ROOM 318 IL-C3 * 3 * 11 C 12 * 3 ROOM 312 IL-131 3 125 2 13 A 14 125 2 3 ROOM 320 IL-131 * 3 * 15 B 16 * 3 ROOM 313 IL-C4 3 125 2 17 C 18 125 2 3 ROOM 322 ILL-A2 * 3 * 19 A 20 * 3 SPARE 20 1 21 B 22 125 1 2 1 3 ROOM 323 IL-132 + DEN SPARE 20 1 23 C 24 * 3 SPARE 20 1 25 A 26 125 2 3 ROOM 324 IL-B1 SPARE 20 1 1 27 1 B 28 * 3 SPARE 20 1 29 C 30 125 2 3 ROOM 325 IL-132 SPARE 20 1 31 A 32 * 3 SPARE 20 1 33 B 34 125 2 SPARE SPARE 20 1 35 C 36 SPARE 20 1 37 A 38 20 1 SPARE SPARE 20 1 39 B 40 20 1 SPARE SPARE 20 1 41 C 42 20 1 SPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 0 VA 210-19 125% 0 VA H - PROVIDE HACR RATED BREAKER RECEPTACLES 0 VA 220-44 10kVA @ 100%, ELSE @ 50% 0 VA MISC. 0 VA 220-60 100% 0 VA MOTOR LARGEST MOT.: 0 VA 220-50 100% + LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 0 A 0 A PANELBOARD SCHEDULE PANEL: 13B VOLTAGE: 208/120V PHASE: 3 WIRE: 4 AMPERE RATING: 600A SC RATING: 22K A.I.0 MAIN: MAIN LUG ENTRY: MOUNTING: SURFACE LOADS AMPS VA PHASE A: 0 0 PHASE B: 0 0 PHASE C: 0 0 TOTAL: 0 LOAD TYPES: 1 = LIGHTING 2 = RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN REMARKS: SEE LOAD CACULATIONS, THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) ROOM 330 IL-132 1 3 125 2 1 A 2 125 2 3 ROOM 306 IL-C3 3 * 3 B 4 * 3 ROOM 332 IL-136 3 125 2 5 C 6 125 2 3 ROOM 336 IL-C2 **• 3 * * 7 A 8 * * 3 *** ROOM 334 IL-66 3 125 2 9 B 10 125 2 1 3 ROOM 328 IL-65 * 3 * 11 C 12 * 3 ROOM 336 IL-136 3 125 2 13 A 14 125 2 SPARE *** 3 * * 15 B 16 * *** ROOM 338 IL-66 3 125 2 17 C 18 20 1 SPARE * 3 * 19 A 20 20 1 SPARE ROOM 340 IL-136 3 125 2 1 21 1 6 1 22 20 1 SPARE *** 3 * * 23 C 24 20 1 SPARE ROOM 301 IL-62 3 125 2 25 A 1 26 20 1 SPARE * 3 * 27 B 28 20 1 SPARE ROOM 302 IL-133 3 125 2 29 C 30 20 1 SPARE * 3 * 31 A 32 20 1 SPARE ROOM 303 IL -Al 3 125 2 33 B 34 20 1 SPARE * 3 * 35 C 36 20 1 SPARE ROOM 304 IL -Al 3 125 2 37 A 38 20 1 SPARE * 3 * 39 B 40 20 1 SPARE SPARE 20 1 1 41 C 42 20 1 SPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 0 VA 210-19 125% 0 VA H - PROVIDE HACR RATED BREAKER RECEPTACLES 0 VA 220-44 10kVA @ 100%, ELSE @ 50% 0 VA MISC. 0 VA 220-60 100% 0 VA MOTOR LARGEST MOT.: 0 VA 220-50 100% + LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 0 A 0 A PANELBOARD SCHEDULE PANEL: I4A VOLTAGE: 208/120V PHASE: 3 WIRE: 4 AMPERE RATING: 600A SC RATING: 22K A.I.0 MAIN: MAIN LUG ENTRY: MOUNTING: SURFACE LOADS AMPS VA PHASE A: 0 0 PHASE B: 0 0 PHASE C: 0 0 TOTAL: 0 LOAD TYPES. 1 = LIGHTING 2 = RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN REMARKS. SEE LOAD CACULATIONS, THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) ROOM 408 IL-B1 3 125 2 1 A 2 125 2 3 ROOM 414 IL-135 3 3 B 4 3 ROOM 410 IL-136 3 125 2 5 C 6 125 2 3 ROOM 416 IL-Cl 3 * 7 A 8 * 3 ROOM 411 IL-137 3 125 2 9 B 10 125 2 3 ROOM 418 IL-C3 * 3 * 11 C 12 * 3 ROOM 412 IL-131 3 125 2 13 A 14 125 2 3 ROOM 420 IL-131 *** 3 * 15 B 16 * 3 *** ROOM 413 IL-C4 3 125 2 17 C 18 125 2 3 ROOM 422 IL-A2 * 3 * 19 A 20 * 3 SPARE 1 1 20 1 21 B 22 125 2 3 1 ROOM 423 IL-132 + DEN SPARE 20 1 23 C 24 * 3 SPARE 20 1 25 A 26 125 2 3 ROOM 424 IL-131 SPARE 20 1 27 B 28 * 3 SPARE 20 1 29 C 30 125 2 3 ROOM 425 IL-132 SPARE 20 1 31 A 32 * 3 SPARE 1 1 20 1 33 B 34 125 2 SPARE SPARE 20 1 35 C 36 SPARE 20 1 37 A 38 20 1 SPARE SPARE 20 1 39 B 40 20 1 SPARE SPARE 20 1 41 C 42 20 1 SPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 0 VA 210-19 125% 0 VA H - PROVIDE HACR RATED BREAKER RECEPTACLES 0 VA 220-44 10kVA @ 100%, ELSE @ 50% 0 VA MISC. 0 VA 220-60 100% 0 VA MOTOR LARGEST MOT.: 0 VA 220-50 100% + LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 0 A 0 A '12A LOAD CALC' PANEL LOAD CALCULATION OPTIONAL METHOD NEC 220.80 UNIT CONNEC TED LOADS (F ER NEC 220.8 (C)) UNIT TYPE # OF UNITS UNIT LOAD KVA ( ) LOAD BY UNIT TYPE(KVA) ILF 1-BDRM/1-BATH 10 24.2 242.4 ILF 2-BDRM/2-BATH 3 13 26.2 78.6 TOTAL: TOTAL PANEL CONNECTED UNIT LOAD: 321.1 KVA DIVERSITY FACTOR: 41 % OPTIONAL CALCULATED LOAD: 131.6 KVA CORE CALCULATED LOAD KVA OPTIONAL CALCULATED LOAD: 131.6 KVA 365 A '1213 LOAD CALC' PANEL LOAD CALCULATION OPTIONAL METHOD NEC 220.80 UNIT CONNECTED LOADS (F ER NEC 220.8 (C)) UNIT TYPE # OF UNITS UNIT LOAD (KVA) LOAD BY UNIT TYPE(KVA) ILF 1-BDRM/1-BATH 10 24.2 242.4 ILF 2-BDRM/2-BATH 3 13 26.2 78.6 TOTAL: TOTAL PANEL CONNECTED UNIT LOAD: 321.1 KVA DIVERSITY FACTOR: 41 % OPTIONAL CALCULATED LOAD: 131.6 KVA CORE CALCULATED LOAD KVA OPTIONAL CALCULATED LOAD71 131.6 KVA 365 A '13A LOAD CALC' PANEL LOAD CALCULATION OPTIONAL METHOD NEC 220.80 UNIT CONNEC TED LOADS (F ER NEC 220.8 (C)) UNIT TYPE # OF UNITS UNIT LOAD KVA ( ) LOAD BY UNIT TYPE(KVA) ILF 1-BDRM/1-BATH 10 24.2 242.4 ILF 2-BDRM/2-BATH 1 3 13 26.2 78.6 TOTAL: TOTAL PANEL CONNECTED UNIT LOAD: 321.1 KVA DIVERSITY FACTOR: 41 % OPTIONAL CALCULATED LOAD: 131.6 KVA CORE CALCULATED LOAD KVA OPTIONAL CALCULATED LOAD: 131.6 KVA 365 A '1313 LOAD CALC' PANEL LOAD CALCULATION OPTIONAL METHOD NEC 220.80 UNIT CONNECTED LOADS (PER NEC 220.8 (C)) UNIT TYPE # OF UNITS UNIT LOAD (KVA) LOTYPE(KVA)UNIT ILF 1-BDRM/1-BATH 10 24.2 242.4 ILF 2-BDRM/2-BATH 3 13 26.2 78.6 TOTAL: TOTAL PANEL CONNECTED UNIT LOAD: 321.1 KVA DIVERSITY FACTOR: 41 % OPTIONAL CALCULATED LOAD: 131.6 KVA CORE CALCULATED LOAD KVA OPTIONAL CALCULATED LOAD: 131.6 KVA 365 A '14A LOAD CALC ' PANEL LOAD CALCULATION OPTIONAL METHOD NEC 220.80 UNIT CONNEC TED LOADS (F ER NEC 220.8 (C)) UNIT TYPE # OF UNITS UNIT LOAD KVA ( ) LOAD BY UNIT TYPE(KVA) ILF 1-BDRM/1-BATH 10 24.2 242.4 ILF 2-BDRM/2-BATH 3 13 26.2 78.6 TOTAL: TOTAL PANEL CONNECTED UNIT LOAD: 321.1 KVA DIVERSITY FACTOR: 41 % OPTIONAL CALCULATED LOAD: 131.6 KVA CORE CALCULATED LOAD KVA OPTIONAL CALCULATED LOAD: 131.6 KVA 365 A PANELBOARD SCHEDULE PANEL: I4B VOLTAGE: 208/120V PHASE: 3 WIRE: 4 AMPERE RATING: 600A SC RATING: 22K A.I.0 MAIN: MAIN LUG ENTRY: MOUNTING: SURFACE LOADS AMPS VA PHASE A: 0 0 PHASE B: 0 0 PHASE C: 0 0 TOTAL: 0 LOAD TYPES: 1 = LIGHTING 2- RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN REMARKS: SEE LOAD CACULATIONS, THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) ROOM 430 IL-132 3 125 2 1 A 2 125 2 3 ROOM 406 IL-C3 3 * 3 B 4 * 3 ROOM 432 IL-136 3 125 2 5 C 6 125 2 3 ROOM 426 IL-C2 **• 3 * 7 A 8 * 3 *** ROOM 434 IL-136 3 125 2 9 B 10 125 2 3 ROOM 428 IL-135 * 3 11 C 12 3 ROOM 436 IL-136 3 125 2 13 A 14 125 2 SPARE * 3 * 15 B 16 ROOM 438 IL-136 3 125 2 17 C 18 20 1 SPARE * 3 19 A 20 20 1 SPARE ROOM 440 IL-66 3 125 2 21 B 22 20 1 SPARE * 3 * 23 C 1 24 20 1 SPARE ROOM 401 IL-135 3 125 2 25 A 26 20 1 SPARE * 3 * 27 B 28 20 1 SPARE ROOM 402 IL-133 (TYPE A) 3 125 2 29 C 30 20 1 SPARE * 3 * 31 A 32 20 1 SPARE ROOM 403 IL -Al (TYPE A) 3 125 2 33 B 34 20 1 SPARE * 3 35 C 36 20 1 SPARE ROOM 404 IL-05 (TYPE A) 3 125 2 37 A 38 20 1 SPARE * 3 * 39 B 40 1 20 1 1 1 1 ISPARE SPARE 20 1 1 41 1 C 42 1 20 1 1 1 1 ISPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 0 VA 210-19 125% 0 VA H - PROVIDE HACR RATED BREAKER RECEPTACLES 0 VA 220-44 10kVA @ 100%, ELSE @ 50% 0 VA MISC. 0 VA 220-60 100% 0 VA MOTOR LARGEST MOT.: 0 VA 220-50 100% + LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 0 A 0 A PANELBOARD SCHEDULE PANEL: 15A VOLTAGE: 208/120V PHASE: 3 WIRE: 4 AMPERE RATING: 600A SC RATING: 22K A.I.0 MAIN: MAIN LUG ENTRY: MOUNTING: SURFACE LOADS: AMPS VA PHASE A: 0 0 PHASE B: 0 0 PHASE C: 0 0 TOTAL: 0 LOAD TYPES: 1 = LIGHTING 2 = RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN REMARKS: SEE LOAD CACULATIONS, THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) ROOM 508 IL-61 3 125 2 1 A 2 125 1 2 1 3 ROOM 514 IL-62 ••• 3 * 3 B 4 * 3 ••• ROOM 510 IL-136 3 125 2 5 C 6 125 2 3 ROOM 516 IL-Cl 3 7 A 8 3 * ROOM 511 IL-137 3 125 2 1 9 B 10 125 2 3 1 ROOM 518 IL-C3 ' 3 11 C 12 * 3 ROOM 512 IL-131 3 125 2 13 A 14 125 1 2 3 ROOM 520 IL-131 * 3 15 B 16 3 * ROOM 513 IL-C4 3 125 2 17 C 18 125 2 3 ROOM 522 IL-A2 ' 3 19 A 20 3 ' SPARE 1 20 1 1 21 B 22 125 2 1 3 1 1 ROOM 523 IL-132 + DEN SPARE 20 1 23 C 24 3 * SPARE 20 1 25 A 1 26 125 2 3 ROOM 524 IL-61 SPARE 20 1 27 B 28 3 ' SPARE 20 1 29 C 30 125 2 3 ROOM 525 IL-132 SPARE 20 1 31 A 32 3 * SPARE 20 1 1 33 B 34 125 2 1 SPARE SPARE 20 1 35 C 36 * SPARE 20 1 37 A 38 20 1 SPARE SPARE 20 1 39 B 40 20 1 SPARE SPARE 20 1 41 C 42 20 1 ISPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 0 VA 210-19 125% 0 VA H - PROVIDE HACR RATED BREAKER RECEPTACLES 0 VA 220-44 10kVA @ 100%, ELSE @ 50% 0 VA MISC. 0 VA 220-60 100% 0 VA MOTOR LARGEST MOT.: 0 VA 220-50 100%+ LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 0 A 0 A PANELBOARD SCHEDULE PANEL: I5B VOLTAGE: 208/120V PHASE: 3 WIRE: 4 AMPERE RATING: 600A SC RATING: 22K A.I.0 MAIN: MAIN LUG ENTRY: MOUNTING: SURFACE LOADS: AMPS VA PHASE A: 0 0 PHASE B: 0 0 PHASE C: 0 0 TOTAL: 0 LOAD TYPES: 1 = LIGHTING 2- RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN REMARKS: SEE LOAD CACULATIONS, THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) ROOM 530 IL-132 3 125 2 1 A 2 125 2 ROOM 506 IL-C3 3 3 B 4 ROOM 532 IL-136 3 125 2 5 C 6 125 2 ROOM 526 IL-C2 3 7 A 8 ROOM 534 IL-136 3 125 2 9 1B 10 125 2 ROOM 528 IL-135 * 3 * 11 C 12 ROOM 536 IL-136 3 125 2 13 A 14 125 2 SPARE * 3 * 15 B 16 ROOM 538 IL-136 3 125 2 17 C 18 20 1 SPARE * 3 * 19 A 20 20 1 ISPARE ROOM 540 IL-136 3 125 1 2 1 21 1 B 22 20 1 SPARE * 3 * 23 C 24 1 20 1 SPARE ROOM 501 IL-135 3 125 2 25 A 26 20 1 SPARE * 3 * 27 B 28 20 1 SPARE ROOM 502 IL-133 3 125 2 29 C 30 20 1 SPARE * 3 * 31 A 32 20 1 1 SPARE ROOM 503 IL -Al 3 125 2 33 B 34 20 1 SPARE * 3 * 35 C 36 20 1 SPARE ROOM 504 IL-05 3 38 20 1 SPARE *** 3 �2L4 �!B 40 20 1 SPARE SPARE 42 20 1 SPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 0 VA 210-19 125% 0 VA H - PROVIDE HACR RATED BREAKER RECEPTACLES 0 VA 220-44 10kVA @ 100%, ELSE @ 50% 0 VA MISC. 0 VA 220-60 100% 0 VA MOTOR LARGEST MOT.: 0 VA 220-50 100% + LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 0 A 0 A PANELBOARD SCHEDULE PANEL: 16A VOLTAGE: 208/120V PHASE: 3 WIRE: 4 AMPERE RATING: 600A SC RATING: 22K A.I.0 MAIN: MAIN LUG ENTRY: MOUNTING: SURFACE LOADS AMPS VA PHASE A: 0 0 PHASE B: 0 0 PHASE C: 0 0 TOTAL: 0 LOAD TYPES: 1 = LIGHTING 2 = RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN REMARKS: SEE LOAD CACULATIONS, THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) ROOM 611 IL-66 3 125 2 1 A 1 2 125 1 2 1 3 ROOM 620 IL-B1 3 3 B 4 3 ROOM 612 IL-B1 3 125 2 5 C 6 125 2 3 ROOM 622 IL-A2 **• 3 * * 7 A 8 * * 3 *** ROOM 613 IL-C4 3 125 2 9 B 10 125 2 3 ROOM 623 IL-62 * 3 11 C 12 3 ROOM 614 IL-135 3 125 2 13 A 14 125 2 3 ROOM 624 IL-131 *** 3 15 B 16 3 *** ROOM 616 IL-Cl 3 125 2 17 C 18 125 2 3 ROOM 625 BL-B2 * 3 19 A 20 3 ROOM 618 IL-C3 3 125 2 21 B 22 125 2 SPARE *** 3 23 C 24 *** SPARE 20 1 1 1 25 A 26 20 1 SPARE SPARE 20 1 27 B 28 20 1 SPARE SPARE 20 1 29 C 30 20 1 SPARE SPARE 20 1 31 A 32 20 1 SPARE SPARE 20 1 33 B 34 20 1 SPARE SPARE 1 35 C 36 20 1 SPARE SPARE J12 1 37 A 38 20 1 SPARE SPARE 1 39 B 40 20 1 SPARESPARE 1 41 C 42 20 1 SPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 0 VA 210-19 125% 0 VA H - PROVIDE HACR RATED BREAKER RECEPTACLES 0 VA 220-44 10kVA @ 100%, ELSE @ 50% 0 VA MISC. 0 VA 220-60 100% 0 VA MOTOR LARGEST MOT.: 0 VA 220-50 100%+ LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 0 A 0 A PANELBOARD SCHEDULE PANEL: I6B VOLTAGE: 208/120V PHASE: 3 WIRE: 4 AMPERE RATING: 600A SC RATING: 22K A.I.0 MAIN: MAIN LUG ENTRY: MOUNTING: SURFACE LOADS: AMPS VA PHASE A: 0 0 PHASE B: 0 0 PHASE C: 0 0 TOTAL: 0 LOAD TYPES: 1 = LIGHTING 2 = RECEPTACLES 3 = MISC 4 = MOTOR 5 = KITCHEN REMARKS: SEE LOAD CACULATIONS, THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) ROOM 636 IL-136 3 125 2 1 A 2 125 2 3 ROOM 632 IL-B6 3 3 B 4 3 ROOM 638 IL-136 3 125 2 5 C 6 125 2 3 ROOM 634 IL-136 3 7 A 8 * 3 ROOM 640 IL-136 3 125 2 9 B 10 125 2 SPARE * 3 * 11 C 12 ROOM 601 IL-B5 3 125 2 13 A 14 20 1 SPARE *** 3 * 15 B 16 20 1 SPARE ROOM 602 IL-133 (TYP A) 3 125 2 17 C 18 20 1 SPARE * 3 * 19 A 20 20 1 1 SPARE ROOM 603 IL -Al (TYPE A) 1 3 125 1 2 1 21 B 22 20 1 1 ISPARE * 3 * 23 C 24 20 1 SPARE ROOM 604 IL-Cl (TYPE A) 3 125 2 25 A 26 20 1 SPARE * 3 * 27 B 28 20 1 SPARE ROOM 626 IL-C2 3 125 2 29 C 30 20 1 SPARE * 3 * 31 A 32 20 1 SPARE ROOM 628 IL-BS 13 125 2 1 33 B 34 20 1 SPARE * 3 * 35 C 36 20 1 SPARE ROOM 630 IL-132 3 125 2 37 A 38 20 1 SPARE * 3 * 39 B 40 20 1 SPARE SPARE 20 1 41 C 42 20 1 SPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 0 VA 210-19 125% 0 VA H - PROVIDE HACR RATED BREAKER RECEPTACLES 0 VA 220-44 10kVA @ 100%, ELSE @ 50% 0 VA MISC. 0 VA 220-60 100% 0 VA MOTOR LARGEST MOT.: 0 VA 220-50 100% + LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 0 A 0 A '1413 LOAD CALC' PANEL LOAD CALCULATION OPTIONAL METHOD NEC 220.80 UNIT CONNEC TED LOADS (F ER NEC 220.8 (C)) UNIT TYPE # OF UNITS UNIT LOAD KVA ) ( LOAD BY UNIT TYPE(KVA) ILF 1-BDRM/1-BATH 10 24.2 242.4 ILF 2-BDRM/2-BATH 3 13 26.2 78.6 TOTAL: TOTAL PANEL CONNECTED UNIT LOAD: 321.1 KVA DIVERSITY FACTOR: 41 % OPTIONAL CALCULATED LOAD: 131.6 KVA CORE CALCULATED LOAD KVA OPTIONAL CALCULATED LOAD: 131.E KVA 365 A '15A LOAD CALC ' PANEL LOAD CALCULATION OPTIONAL METHOD NEC 220.80 UNIT CONNEC TED LOADS (F ER NEC 220.8 (C)) UNIT TYPE # OF UNITS UNIT LOAD (KVA) LOAD BY UNIT TYPE(KVA) ILF 1-BDRM/1-BATH 10 24.2 242.4 ILF 2-BDRM/2-BATH 3 13 26.2 78.6 TOTAL: TOTAL PANEL CONNECTED UNIT LOAD: 321.1 KVA DIVERSITY FACTOR: 41 % OPTIONAL CALCULATED LOAD: 131.6 KVA CORE CALCULATED LOAD .KVA OPTIONAL CALCULATED LOAD: 131.6 KVA 365 A '1513 LOAD CALC' PANEL LOAD CALCULATION OPTIONAL METHOD NEC 220.80 UNIT CONNEC TED LOADS (F ER NEC 220.8 (C)) UNIT TYPE # OF UNITS UNIT LOAD (KVA) LOAD BY UNIT TYPE(KVA) ILF 1-BDRM/1-BATH 10 24.2 242.4 ILF 2-BDRM/2-BATH 3 13 26.2 78.6 TOTAL: TOTAL PANEL CONNECTED UNIT LOAD: 321.1 KVA DIVERSITY FACTOR:=131.6KVA OPTIONAL CALCULATED LOAD: CORE CALCULATED LOAD KVA OPTIONAL CALCULATED LOAD: 131.6 KVA 365 A '16A LOAD CALC' PANEL LOAD CALCULATION OPTIONAL METHOD NEC 220.80 UNIT CONNECTED LOADS (PER NEC 220.8 (C)) UNIT TYPE # OF UNITS UNIT LOAD (KVA) LOAD ( UNIT TYPE (KVA) ILF 1-BDRM/1-BATH 8 24.2 193.9 ILF 2-BDRM/2-BATH 2 10 26.2 52.4 TOTAL: TOTAL PANEL CONNECTED UNIT LOAD: 246.4 KVA DIVERSITY FACTOR: 43% OPTIONAL CALCULATED LOAD: 105.9 KVA CORE CALCULATED LOAD KVA OPTIONAL CALCULATED LOAD: 105.9 KVA 294 A '1613 LOAD CALC' PANEL LOAD CALCULATION OPTIONAL METHOD NEC 220.80 UNIT CONNECTED LOADS (F ER NEC 220.8 (C)) UNIT TYPE # OF UNITS UNIT LOAD (KVA) LOAD BY UNIT TYPE (KVA) ILF 1-BDRM/1-BATH 10 24.2 242.4 ILF 2-BDRM/2-BATH 1 2 12 26.2 52.4 TOTAL: TOTAL PANEL CONNECTED UNIT LOAD: 294.8 KVA DIVERSITY FACTOR: 41 % OPTIONAL CALCULATED LOAD: 120.9 KVA CORE CALCULATED LOAD .KVA OPTIONAL CALCULATED LOAD: 120.9 KVA 336 A PANELBOARD SCHEDULE PANEL: ILF-1 Bd1 Bth/Studio VOLTAGE: 208/120V PHASE: 1 1 WIRE: 3 AMPERE RATING: 125A SC RATING: 1OK A.I.C. MAIN: MAIN LUG OR MAIN BREAKER ENTRY: MOUNTING: FLUSH OR SURFACE LOADS: AMPS VA PHASE A: 118 14110 PHASE B: 118 14200 TOTAL: 28310 LOAD TYPES: 1 = LIGHTING 2 = RECEPTACLES 3 = MISC 4-MOTOR 5 - KITCHEN REMARKS: SEE LOAD CALCS THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) 600 LIGHTS, EFs, DBF-1 A,B 1 15 1 1 A 2 20 1 2 REC-DISHWASHER/DISPOSAL 1500 1080 REC-LIVING ROOM A 2 15 1 3 B 4 1 3 H HEAT/LIGHT/FAN IN BATH 1500 1500 REC-BATH 2 20 1 5 A 6 2 3 H LIVING ROOM VTAC-2 1400 4000 RANGE 2 40 2 7 B 8 - 3 H --- 1400 P15 4000 --- 2 - - 9 A 10 1 2 A REC-KITCHEN #2 360 1500 MICROWAVE A 2 20 1 11 B 12 1 2 A REC-BEDROOM 720 1500 REC-KITCHEN #1 A 2 20 1 13 A 14 20 1 1 1 3 H BDRM EWH-1 750 1500 CLOTHES WASHER A 2 20 1 15 B 16 20 1 SPARE 2500 CLOTHES DRYER 12 1 30 2 17 1 A 18 20 1 SPARE 2500 --- 2 - 19 B 20 20 1 SPARE SPARE 27-1 1 21 A 22 20 1 SPARE SPARE I 1 1 20 1 1 1 23 1 B 24 20 1 SPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 600 VA 210-19 125% 750 VA A- PROVIDE AFCI TYPE CIRCUIT BREAKER RECEPTACLES 22660 VA 220-44 10kVA @ 100%, ELSE @ 50% 16330 VA B - PROVIDE DBF-1 ON 1ST & 2ND FLR UNITS ONLY MISC. 5050 VA 220-60 100% 5050 VA H - PROVIDE HACR RATED BREAKER MOTOR LARGEST MOT.: 0 VA 220-50 100% , LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: 0 VA 220-56 0 VA TOTAL 118 A 92 A APARTMENT TYPE: I 'IL-1Bd1BthLoadCalc' 'ILF-1Bd1Bth Load Calc' (OPTIONAL METHOD, NEC 220.30) CONNECTED LOAD VA (A) 1.TWO SMALL APPLIANCE CIRCUITS 3000 LAUNDRY BRANCH CIRCUIT 1500 2. GENERAL LIGHTING & SQ.FT: 526 1578 RECEPTACLES (3 VA/ SQ. FT.) 3. APPLIANCES: MICROWAVE 1500 RANGE 8000 DRYER 5000 DISHWASHER 864 4. MOTORS GARBAGE DISPOSAL 0 SUBTOTAL: 21442 a 10000 REMAINDER @ 40% 4577 SUBTOTAL: 14577 g LARGEST OF HEATING AND A/C 2800 TOTAL LOAD: 17377 VA 84 AMPS Lp PANELBOARD SCHEDULE PANEL: ILF-2Bd2Bth VOLTAGE: 208/120V PHASE: 1 WIRE: 3 AMPERE RATING: 125A SC RATING: 10K A.I.C. MAIN: MAIN LUG OR MAIN BREAKER ENTRY: MOUNTING: FLUSH OR SURFACE LOADS: AMPS VA PHASE A: 153 18398 PHASE B: 147 17600 TOTAL: 35998 LOAD TYPES: 1 - LIGHTING 2 - RECEPTACLES 3 - MISC 4-MOTOR 5 - KITCHEN REMARKS: SEE LOAD CALCS THIS SHEET LOAD (VA) LOAD SERVED NOTE LOAD TYPE AMPS/ POLES CKT NO PHASE CKT NO AMPS/ POLES LOAD TYPE NOTE LOAD SERVED LOAD (VA) 768 LIGHTS, Efs, DBF-1 A,B 1 15 1 1 A 2 20 1 2 REC-DISHWASHER/DISPOSAL 1500 1080 REC-LIVING ROOM A 2 15 1 3 B 4 20 1 3 HEAT/LIGHT/FAN IN BATH 1500 1500 REC-BATH 2 20 1 5 A 6 30 2 3 H LIVING ROOM VTAC-3 2050 4000 RANGE 2 40 2 7 B 8 - - 3 H --- 2050 4000 --- 2 - 9 A 10 20 1 2 A REC-KITCHEN #2 360 1500 MICROWAVE A 2 20 1 1 11 B 12 15 1 2 A REC-BEDROOM 720 1500 REC-KITCHEN #1 A 2 20 1 13 A 14 20 1 3 H BDRM EWH-1 750 1500 CLOTHES WASHER A 2 20 1 15 B 16 20 1 SPARE 2500 CLOTHES DRYER 2 30 2 17 A 18 15 1 2 A REC-BEDROOM 720 2500 --- 2 - - 19 B 20 20 1 3 HEAT/LIGHT/FAN IN BATH 1500 1250 BEDRM PTAC-1 H 3 20 1 21 A 22 20 1 2 REC-BATH 1500 1250 --- H 3 20 1 23 B 24 20 1 ISPARE LOADING BY TYPE CONNECTED NEC CODE DEMAND FACTOR DEMAND NOTES: LIGHTING 768 VA 210-19 125% 960 VA A- PROVIDE AFCI TYPE CIRCUIT BREAKER RECEPTACLES 24880 VA 220-44 10kVA @ 100%, ELSE @ 50% 17440 VA B - PROVIDE DBF-1 ON 1ST & 2ND FLR UNITS ONLY MISC. 10350 VA 220-60 100% 10350 VA H - PROVIDE HACR RATED BREAKER MOTOR LARGEST MOT.: 0 VA 220-50 100% + LARGEST x 25% 0 VA KITCHEN # OF KIT. UNITS: OVA 220-56 0 VA TOTAL 150 A 120 A APARTMENT TYPE: I 'IL -2Bd2Bth Load Calc' 'ILF-213d213th Load Calc' (OPTIONAL METHOD, NEC 220.30) CONNECTED LOAD VA (A) 13WO SMALL APPLIANCE CIRCUITS 3000 LAUNDRY BRANCH CIRCUIT 1500 2. GENERAL LIGHTING & SQ.FT: 750 2250 RECEPTACLES (3 VA/ SQ. FT.) 3. APPLIANCES: MICROWAVE 1500 RANGE 8000 DRYER 5000 DISHWASHER 864 4. MOTORS GARBAGE DISPOSAL 0 SUBTOTAL: 22114 a 10000 REMAINDER @ 40% 4846 SUBTOTAL: 14846 g LARGEST OF HEATING AND A/C 4100 TOTAL LOAD: 18946 VA 91 AMPS A Plan set for Smoke Control only. p,N • G ASy� G O = z A � FGI E Fs3/0NAL ENG\� 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. ��12 1p�� =it Mw DC ENGINEERING Careful listening. Dynamic solutions. www.dcengineering.net Phone:208.288.2181 Project:21 AMA01 (.O 04 0 TOT 0) Cl) O Z_z O_ W (n 70 O0 Z J> J o O 01-0 p N � 0 J O L m W � Z 04W Q LU 04 U a REVISIO N DATE REASON FOR ISSUE 5 03/14/22 Construction Set RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ELECTRICAL SCHEDULES CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 SHEET NUMBER E3.01 COPPER ALUMINUM CONDUCTOR/ RACEWAY TAG Conduit Conductor Conduit Conductor [2000S] * EA. W/4#400KCM I L * EA. W/4#500KCM I L [2500S] * EA. W/4#500KCM I L * EA. W/4#600KCM I L [3000S] * EA. W/4#500KCM I L * EA. W/4#600KCM I L [4000S] * EA. W/4#750KCMIL * EA. W/4#1000KCMIL [100N] 1-1/2" 4#2, 1#8G 2" 4#1/0, 1#6G [125N] 2" 4#11 1#6G 2" 4#1/0, 1#4G [150N] 2" 4#1/0, 1#6G 2" 4#2/0, 1#4G [175N] 2" 4#2/0, 1#6G 2-1/2" 4#3/0, 1#4G [200N] 2-1/2" 4#3/0, 1#6G 2-1/2" 4#4/0, 1#4G [225N] 2-1/2" 4#4/0, 1#4G 3" 4#250KCMIL, 1#2G [250N] 3" 4#250KCMIL, 1#4G 3" 4#350KCMIL, 1#2G [300N] 3" 4#300KCMIL, 1#4G 3-1/2" 4#400KCMIL, 1#2G [350N] 3-1/2" 4#400KCMIL, 1#3G 4" 4#600KCMIL, 1#1G [400N] 3-1/2" 4#500KCMIL, 1#3G (2)2-1/2 it EA. W/4#4/0, 1#1G [500N] (2)2-1/2 EA. W/4#4/0, 1#2G (2)3 EA. W/4#300KCMIL, 1#1/0G [600N] (2)3 11 EA. W/4#300KCMIL, 1#1G (3)3 EA. W/4#250KCMIL, 1#2/OG [800N] (2)3-1/2 EA. W/4#500KCMIL, 1#1/0G (3)3 EA. W/4#350KCMIL, 1#3/OG [1000N] (3)3-1/2 EA. W/4#400KCMIL, 1#2/OG (3)4 EA. W/4#600KCMIL, 1#4/OG [1200N] 4 3it EA. W/4#350KCMIL, 1#3/OG (4)4 EA. W/4#500KCMIL, 1#250G [1600N] (5)3-1/2 EA. W/4#400KCMIL, 1#4/OG 5 4 EA. W/4#600KCMIL, 1#350G [2000N] (6)3-1/2 EA. W/4#400KCMIL, 1#250G 7 4" EA. W/4#500KCMIL, 1#40OG [2500N] 7 4 EA. W/4#500KCMIL, 1#350G g 4 EA. W/4#600KCMIL, 1#60OG [20] 3/4" 3#12, 1#12G 3/4" 3#10, 1#10G [30] 3/4" 3#10, 1#10G 3/4" 3#8, 1#8G [40] 3/4" 3#8, 1#10G 1" 3#6, 1#8G [50] 1" 3#6, 1#10G 1-1/4" 3#41 1#8G [60] 1" 3#6, 1#10G 1-1/4" 3#4, 1#8G [70] 1-1/4" 3#41 1#8G 1-1/4" 3#3, 1#6G [80] 1-1/4" 3#3, 1#8G 1-1/4" 3#21 1#6G [90] 1-1/4" 3#2, 1#8G 1-1/2" 3#1, 1#6G [100] 1-1/4" 3#21 1#8G 1-1/2" 3#1/0, 1#6G [125] 1-1/4" 3#11 1#6G 2" 3#1/0, 1#4G [150] 1-1/2" 3#1/0, 1#6G 2" 3#2/0, 1#4G [175] 2" 3#2/0, 1#6G 2" 3#3/0, 1#4G F_ [200] 2" 3#3/0, 1#6G 2-1/2" 3#4/0, 1#4G * Coordinate with PNM. Final conduit size must be coordinated with PNM prior to purchase and installation. ►�i •- r.in 0 Q O O � Q m J z m z Q 2 Cn Q Of Of (D J w 0w o w LU z z � w z Of cn o O (D (D 0 Oo> op oW (fa_ J O Cl) ow � �w F_ � m ::) �#W MO -O MO MO FINISHED FLOOR (38'x5/8" ROD ELECTRODES GROUNDING DETAIL KEYED NOTES: 1. LIFER GROUND TO BE 20' OF #4 AWG COPPER OR 1/2" MINIMUM DIAMETER STEEL REINFORCING BAR PER NEC ARTICLE 250.52. GROUNDING DETAIL L NTS E co Cn Cn J JJ J 0 GROUNDING BUSHING TYPICAL LINO LIFER GROUND #4 COPPER 20' UFER GROUNDING DETAIL GENERAL NOTES: 1. ALL CONDUCTORS SHALL BE IN EMT CONDUIT UNLESS NOTED OTHERWISE. ALL CONDUITS SHALL HAVE A GROUNDING BUSHING AT EACH END. 2. ALL CONNECTIONS SHALL BE EXOTHERMIC WELD, LISTED PRESSURE CONNECTORS, LISTED CLAMPS OR OTHER LISTED MEANS. COORDINATE WITH SNOHOMISH COUNTY PUD ELECTRIC REQUIREMENTS FOR CONDUIT, TRENCHING AND BACKFILL. CONDUCTORS PROVIDED BY SNOHOMISH COUNTY PUD SNOHOMISH COUNTY PUD ELECTRIC CABINET MDP-1 DEMAND LOAD CALCULATION CONNECTED CALCULATIONS: Non dwelling space calculated demand load= LIGHTING 20425 RECEPTACLE 55979 MISC. 321268 MECHANICAL/MOTOR 111634.1 KITCHEN 99072 ELEVATOR #2 435320 CONCRETE PADNAULT PER SNOHOMISH COUNTY PUD REQUIREMENTS PROVIDE UNDER THIS CONTRACT, OLD CASTLE, INC OR EQUAL. SNOHOMISH COUNTY TRANSFORMER SEE SITE PLAN 0 0 EMERGENCY GENSET. MUST COME ONLINE WITHIN 10 SECONDS SERVICE 14 I "" RECEPTACLE SP1-6 3/4"C. �"� 13 12 — 0OGROUND PER 14 NEC 250 BATTERY CHARGER SP14 1 "C. ENGINE BLOCK HEATER, SP1-2 Non Dwelling Calculated Demand Load is arrived upon by summing the following: Lighting Load @ 125% 401585 VA 1 ST 1 OkVA of Rec. @ 100% remainder @ 50% 50979 VA Miscellaneous Loads @ 100% 321268 VA Largest Motor @ 125% 54150 Remainder of Motor Load @ 100% 111634 VA Kitchen @ 65% 64397 VA SUM of non living space calculated demand load 1004013 VA Load WA 1004 AMP 2787 TOTAL DEMAND LOAD AT 120/208V 3-PHASE KVA 1004 AMPS 2787 1-1/2" CONDUIT FOR CONTROLAND MONITORING 13 SIGNALS 30OKW GENERATOR 208V 3 PHASE, 4W 60Hz, DIESEL — 16 r— I PROVIDED SECONDARY CONNECTION CABINET, ,S 2 I� TERMINAL CABINET I 4 6 8 [3000S] TO MDP-2 (REFER TO DWG. E4.01) """ PROVIDED CABLE TRAY RACEWAY, GROUND ROD AND CONDUCTOR TO NEUTRAL BUS AND CASE GROUND, PER SNOHOMISH COUNTY PUD REQUIREMENTS. 1 I O _ I I 3000A 18 _ MAIN 1 3P KR `— 01 NEUT.BUS 600 AMP, 3 POLE LIFE SAFETY AUTOMATIC TRANSFER SWITCH #ATS1 NEMA 1 [400N] [40ON] GROUND PER NEC [800N] I I 80ON] I 800 AMP, 3 POLE - STANDBY AUTOMATIC TRANSFER SWITCH #ATS2 NEMA 1 GROUND PER NEC [40ON] [80ON] 400A -) 800A 3P 1 3P GROUND - PER NEC 250. RE: DETAIL ON SHEET E4.00 FIRE/LIFE SAFETY EMERGENCY PANEL LOCATED IN MAIN ELECTRICAL RM. 0002 16 PANEL FI G ELEVATOR #1 9 19 PANEL SP1 800A MC� MAIN ELEC. RM. 0002 STANDBY -BACKUP POWER PANEL PANEL PANEL 11 PANEL PANEL PANEL PANEL PANEL PP 1P 3P 6L 6P 6M1 600A 100A 20OA 100A 100A 200A OA T [60ON] 1 [10ON] 20ON] [10ON] [20ON] [20ON] [40ON] 600A "� 100A 3P J 3P ELEVATOR #2 200A 3P 100A 3P 200A 200A 3P 400A 3P 175A ST SPACE 3P 3P 3P 3000 AMP RATED BUS OMAIN DISTRIBUTION PANEL #1 (MDP-1) 3000A, 208Y/120 VOLT, 3 PHASE, 4 WIRE 100,000 AIC RATED NEMA 1 RATED PANEL 3 MDP-1 ONE -LINE POWER DISTRIBUTION DIAGRAM SCALE: N.T.S. GENERAL NOTES: A. SNOHOMISH COUNTY PUD REQUIRES GENERATORS TO BE CONNECTED USING A PERMANENTLY INSTALLED OPEN -TRANSITION (BREAK -BEFORE -MAKE) TRANSFER SWITCH PER PAGE 63 OF THE PNM ELECTRICAL SERVICE GUIDE. THE TRANSFER SWITCH MUST BE USED TO DISCONNECT ALL UNGROUNDED CONDUCTORS CONNECTED TO THE PGE SYSTEM PRIOR TO CONNECTING THE GENERATOR TO THE CUSTOMER'S ELECTRICAL SYSTEM. B. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR TRENCHING, BACKFILLING, COMPACTION, CONDUIT, TRANFORMER PADS OR VAULTS, AND ANY OTHER REQUIREMENTS TO COMPLETE THE UNDERGROUND SERVICE PER SNOHOMISH COUNTY PUD SERVICE REQUIREMENTS MANUAL. KEYED NOTES: 0 1. 4 INCH HIGH CONCRETE HOUSEKEEPING PAD UNDER SWITCHBOARD. COORDINATE WITH GENERAL CONTRACTOR. 2. CURRENT TRANSFORMER/TERMINAL CABINET PER THE MOST RECENT EDITION OF SNOHOMISH COUNTY PUD SERVICE REQUIREMENTS. 3. CONFIRM UTILITY TRANSFORMER IMPEDANCE. UTILITY TO PROVIDE AVAILABLE FAULT CURRENT. 4. ALL PRIMARY AND SECONDARY CONDUIT, TRENCHING AND BACKFILL, INCLUDING PULL VAULTS, AND CONDUCTORS ARE UNDER THIS CONTRACT, TO INCLUDE TERMINAL LUGS FOR UTILITY CONNECTION. VERIFY REQUIREMENTS WITH SNOHOMISH COUNTY PUD. TRENCHING AND BACKFILL BY GENERAL CONTRACTOR. COORDINATE WITH GENERAL CONTRACTOR. 5. SERVING UTILITY - SNOHOMISH COUNTY PUD. COORDINATE ALL REQUIREMENTS OF SNOHOMISH COUNTY PUD. REFER TO INSTALLATION REQUIREMENTS MANUAL LATEST EDITION. 6. UTILITY SERVICE FEEDERS WITHIN BUILDING FOOTPRINT TO BE INSTALLED BELOW SLAB, ENCASED WITH MINIMUM OF 6" CONCRETE ABOVE. VERIFY WITH AHJ. 7. USE SERIES RATED SWITCHES, BREAKERS AND RELATED EQUIPMENT. USE NEXT HIGHER AIC RATING THAN CALCULATED. 8. INSTALL WARNING RIBBON PER NEC. 9. VERIFY MOTOR SIZE, REQUIRED CIRCUIT BREAKER AND CONDUCTOR SIZE WITH ELEVATOR MANUFACTURER PRIOR TO ORDERING SWITCH GEAR AND CONDUCTOR MATERIAL. PER NEC. 10. USE COPPER CONDUCTORS AT ELEVATOR AS REQUIRED BY ELEVATOR MANUFACTURER. USE FULL SIZE GROUND. 11. STANDBY DIESEL GENERATOR, BASIS OF DESIGN: CUMMINS MODEL DFEJ 60HZ, 300 KW RATED, 208 VOLT, 3 PHASE, BASE MOUNT UL142 FUEL TANK, 693 GAL. NOMINAL 24 HOUR RUN TIME @G 100% LOAD. PROVIDE SEISMIC ATTACHMENT TO CONCRETE BASE, FUEL FILTER, ENGINE BLOCK HEATER, 10 AMP BATTERY CHARGER, REMOTE CONTROL PANEL AND EMERGENCY STOP, WITH LOW FUEL WARNING. PROVIDE WITH (1) 800 AMP AND (1) 600 AMP CIRCUIT BREAKER. PROVIDE WITH REMOTE ANNUNCIATOR AND ALARM HORN WITH (2) GENERATOR AUTOMATIC TRANSFER SWITCHES. AUTOMATIC TRANSFER SWITCH TO BE GROUNDED PER NEC ART. 250.30. 12. CONCRETE BASE FOR GENERATOR TO BE DESIGNED BY STRUCTURAL ENGINEER TO MATCH GENERATOR BEING USED. CONCRETE PAD DESIGNED AND PROVIDED BY OTHERS. COORDINATE WITH GENERAL CONTRACTOR AND ARCHITECT. 13. GENERATOR CONTROL WIRING METHODS SHALL BE INSTALLED PER NEC 695.14. 14. BOND GENERATOR CASING TO GROUND. DO NOT BOND EQUIPMENT NEUTRAUGROUND AT ENGINE GENERATOR. 15. NOT USED 16. WHERE ROUTED THRU THE BUILDING, THE CONDUCTORS SHALL BE PROTECTED 2 HOUR FIRE RATED PER NEC. 17. PROVIDE ELEVATOR DELAY RELAY TO BE INSTALLED IN THE ATS WHICH SERVES THE ELEVATORS. PROVIDE THREE (3) CONDUCTORS FROM THE ATS TO THE ELEVATOR MOTORS PER MANUFACTURER'S RECOMMENDATIONS. 18. PROVIDE BREAKER WITH ARCH ENERGEY REDUCTION PER NEC 240.87. 19. PROVIDE EATON ELEVATOR CONTROL ES SWITCH DISCONNECT, COORDINATE REQUIREMENTS WITH ELEVATOR SUPPLIER FOR COMPLETE INSTALLATION. COORDINATE SHUNT TRIP OPERATION WITH FIRE ALARM INSTALLER. Plan set for Smoke Control only. p,N • G ASy7 G FGI SS/ONAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.dcengineering.net Phone:208.288.2181 Project:21 AMA01 CD N O 00 M O Z _Z O= Q W (6 0 LL Z O0 LLI O > J co J �_ O O N — o o Z m W � Z N `/) Q LU Q N U a REVISIO N DATE REASON FOR ISSUE 1 6/18/21 Addendum #1 RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ONE —LINE DIAGRAM (MDP-1) CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 SHEET NUMBER E4.00 MDP -2 LOAD CALCULATION DEMAND LOAD CALCULATIONS: Dwelling space calculated demand load= Panel Connected Load (VA) # of units factor Total Connected METER DISTRIBUTION PANEL 'MDP' 12A 1 BDRM 10 242420 2BDRM 3 0.41 78642 TOTAL 13 Load kVA 132 AMP 365 12B 1 BDRM 10 242420 2BDRM 3 0.41 78642 TOTAL 13 Load kVA 132 AMP 365 13A 1 BDRM 10 242420 2BDRM 3 0.41 78642 TOTAL 13 Load kVA 132 AMP 365 13B 1 BDRM 10 242420 2BDRM 3 0.41 78642 TOTAL 13 Load kVA 132 AMP 365 14A 1 BDRM 10 242420 2BDRM 3 0.41 78642 TOTAL 13 Load kVA 132 AMP 365 14B 1 BDRM 10 242420 2BDRM 3 0.41 78642 TOTAL 13 Load kVA 132 AMP 365 15A 1 BDRM 10 242420 2BDRM 3 0.41 78642 TOTAL 13 Load kVA 132 AMP 365 15B 1 BDRM 10 242420 2BDRM 3 0.41 78642 TOTAL 13 Load kVA 132 AMP 365 16A 1 BDRM 8 193936 2BDRM 3 0.42 78642 TOTAL 11 Load kVA 114 AMP 318 16B 1 BDRM 10 242420 2BDRM 2 0.41 52428 TOTAL 12 Load kVA 121 AMP 336 TOTAL 1 BDRM 100 2424200 2BDRM 28 0.23 733992 TOTAL 128 TOTAL DEMAND LOAD AT 120/208V 3-PHASE Load kVA 726 AMP 2016 7 E co M J 11 J 0 COPPER ALUMINUM CONDUCTOR/ RACEWAY TAG Conduit Conductor Conduit Conductor [2000S] * EA. W/4#400KCM I L * EA. W/4#500KCM I L [2500S] * EA. W/4#500KCM I L * EA. W/4#600KCM I L [3000S] * EA. W/4#500KCM I L * EA. W/4#600KCM I L [4000S] * EA. W/4#750KCM I L * EA. W/4#1000KCM I L [100N] 1-1/2" 4#21 1#8G 2" 4#1/0, 1#6G [125N] 2" 4#1, 1#6G 2" 4#1/0, 1#4G [150N] 2" 4#1/0, 1#6G 2" 4#2/0, 1#4G [ 175 N] 2" 4#2/0, 1#6G 2-1/2" 4#3/0, 1#4G [200N] 2-1/2" 4#3/0, 1#6G 2-1/2" 4#4/0, 1#4G [225N] 2-1/2" 4#4/0, 1#4G 3" 4#250KCMIL, 1#2G [250N] 3" 4#250KCM I L, 1#4G 3" 4#350KCM I L, 1#2G [300N] 3" 4#300KCM I L, 1#4G 3-1/2" 4#400KCM I L, 1#2G [350N] 3-1/2" 4#400KCM I L, 1#3G 4" 4#600KCM I L, 1#1G [400N] 3-1/2" 4#500KCMIL, 1#3G (2)2-1/2 If EA. W/4#4/0, 1#1G [500N] 2 2-1 2" EA. W/4#4/0, 1#2G 2 311 EA. W/4#300KCMIL, 1#1/OG [600N] (2)3 11 EA. W/4#300KCMIL, 1#1G (3)3 If EA. W/4#250KCMIL, 1#2/OG [800N] 2 3-1 2" EA. W/4#500KCMIL, 1#1/OG 3 311 EA. W/4#350KCMIL, 1#3/OG [1000N] 3 3-1/2 If EA. W/4#400KCMIL, 1#2/OG (3)4 If EA. W/4#600KCMIL, 1#4/OG [1200N] 4 311 EA. W/4#350KCMIL, 1#3/OG (4)4 It EA. W/4#500KCMIL, 1#250G [1600N] 5 3-1/2 If EA. W/4#400KCMIL, 1#4/OG (5)4 If EA. W/4#600KCMIL, 1#350G [2000N] (6)3-1/2 EA. W/4#400KCM I L, 1#250G (7)4 If EA. W/4#500KCM I L, 1#4000 [2500N] (7)4 11 EA. W/4#500KCM I L, 1#350G (8)4 It EA. W/4#600KCM I L, 1#60OG [20] 3/4" 3#121 1#12G 3/4" 3#10, 1#10G [30] 3/4" 3#101? 1#10G 3/4" 3#8, 1#8G [40] 3/4" 3#8, 1#10G 1" 3#6, 1#8G [50] 1" 3#6, 1#10G 1-1/4" 3#41 1#8G [60] 1" 3#61 1#10G 1-1/4" 3#4, 1#8G [70] 1-1/4" 3#41 1#8G 1-1/4" 3#3, 1#6G [80] 1-1/4" 3#3, 1#8G 1-1/4" 3#2, 1#6G [90] 1-1/4" 3#21 1#8G 1-1/2" 3#11 1#6G [100] 1-1/4" 3#2, 1#8G 1-1/2" 3#1/0, 1#6G [125] 1-1/4" 3#11 1#6G 2" 3#1/0, 1#4G [150] 1-1/2" 3#1/0, 1#6G 2" 3#2/0, 1#4G [175] 2" 3#2/0, 1#6G 2" 3#3/0, 1#4G F_ [200] 1 2" 3#3/0, 1#6G 2-1/2" 3#4/0, 1#4G * Coordinate with PNM. Final conduit size must be coordinated with PNM prior to purchase and installation. GENERAL NOTES: A. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR TRENCHING, BACKFILLING, COMPACTION, CONDUIT, TRANFORMER PADS OR VAULTS, AND ANY OTHER REQUIREMENTS TO COMPLETE THE UNDERGROUND SERVICE PER SNOHOMISH COUNTY PUD SERVICE REQUIREMENTS MANUAL, KEYED NOTES: 1. 4 INCH HIGH CONCRETE HOUSEKEEPING PAD UNDER SWITCHBOARD. COORDINATE WITH GENERAL CONTRACTOR. 2. CURRENT TRANSFORMER/TERMINAL CABINET PER THE MOST RECENT EDITION OF SNOHOMISH COUNTY PUD SERVICE REQUIREMENTS. 3. CONFIRM UTILITY TRANSFORMER IMPEDANCE. UTILITY TO PROVIDE AVAILABLE FAULT CURRENT. 4. ALL PRIMARY AND SECONDARY CONDUIT, TRENCHING AND BACKFILL, NCLUDING PULL VAULTS, AND CONDUCTORS ARE UNDER THIS CONTRACT, TO INCLUDE TERMINAL LUGS FOR UTILITY CONNECTION. VERIFY REQUIREMENTS WITH SNOHOMISH COUNTY PUD. TRENCHING AND BACKEIEE BY GENERAL CONTRACTOR. COORDINATE WITH GENERAL CONTRACTOR. 5. SERVING UTILITY - SNOHOMISH COUNTY PUD. COORDINATE ALL REQUIREMENTS. REFER TO INSTALLATION REQUIREMENTS MANUAL LATEST EDITION. 6. UTILITY SERVICE FEEDERS WITHIN BUILDING FOOTPRINT TO BE INSTALLED BELOW SLAB, ENCASED WITH MINIMUM OF 6" CONCRETE ABOVE. VERIFY WITH AHJ. 7. USE SERIES RATED SWITCHES, BREAKERS AND RELATED EQUIPMENT. USE NEXT HIGHER NO RATING THAN CALCULATED, 8. INSTALL WARNING RIBBON PER NEC. 9. PROVIDE BREAKER WITH ARC ENERGY REDUCTION PER NEC 240.87 FROM SECONDARY CONNECTION CABINET, SCC-1. REFER TO DWG. E4.00 [2500S] [60ON] [600N] [60ON] [60ON] [60ONI [60ON] [60ON] [600N] [60ON] [60ON] PANEL UNIT PANELS UNITS 6th LEVEL [125] 25A TYPICAL OF (11) TYPICAL S NGLE PHA E PANEL UNIT PANELS UNITS 6th LEVEL [125] 25A TYPICAL OF (12) TYPICAL S NGLE PHA E PANEL UNIT PANELS UNITS 5th LEVEL [125] 25A TYPICAL OF (13) TYPICAL S NGLE PHA E PANEL UNIT PANELS UNITS 5th LEVEL TYPICAL OF [125] 125A (13) TYPICAL S NGLE PHA E PANEL UNIT PANELS UNITS 4th LEVEL [125] 125A TYPICAL OF (13) TYPICAL S NGLE PHA E PANEL UNIT PANELS UNITS 4th LEVEL TYPICAL OF [125] 125A (13) TYPICAL S NGLE PHA E PANEL UNIT PANELS UNITS 3rd LEVEL [125] 125A TYPICAL OF TYPICAL S NGLE PHA E (13) PANEL UNIT PANELS UNITS 3rd LEVEL [125] 125A TYPICAL OF (13) [YPICAL S NGLE PHA E PANEL UNIT PANELS UNITS 2nd LEVEL [125] 25A TYPICAL OF (13) 1YPICAL S NGLE PHA E PANEL UNIT PANELS UNITS 2nd LEVEL TYPICAL OF [125] 125A (13) TYPICAL S NGLE PHA E 5— O - SNOHOMISH COUNTY PUD INSTALLATION O O MANUAL FOR REQUIRED M 2500A MAI BRKR CONDITIONS. 600A 3P 600A 3P 1 91301 I I NEUT. BUS FULL BUS 600A 31 600A 31 600A 3P 600A 3P 600A 3P 60OA 3P 2400 AMP RATED BUS GROUND PER NEC 250. RE: DETAIL ON SHEET E5.00 600A 3P 600A 3P SPACE 3P MAIN DISTRIBUTION PANEL #2 (MDP-2) 2500A, 208Y/120 VOLT, 3 PHASE, 4 WIRE, 100,000 NC NEMA 1 RATED PANEL O MDP-2 ONE -LINE POWER DISTRIBUTION DIAGRAM SCALE: N.T.S. Plan set for Smoke Control only. p,N G ASyX G cn O O A' o �F FBI ERE SS/DNAL ENG 04/13/22 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 N 0 00 d) O Z Z O = � a W C LL Z O0 Z O > J > J _� O -0 1 O 0 0 Il Z m W p Z o U � Q LU N U a REVISIO N DATE REASON FOR ISSUE RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ONE —LINE DIAGRAM (MDP-2) CONSTRUCTION SET DATE PROJECT NUMBER 03/14/2022 184470 l-_ - '-- _ uu ILI­ J-- - --� - I ._ ----- - .----- - a�u _-k�..1 �I � i- �. � Q L� cm 1 � (m 2th St SW L�1 i 4 � S I C FIRE ALARM VICINITY MAP N SCHEMATIC: NOT TO SCALE � U _ U INi C14 to z W Z o Z Z Z 0 Z 0 = U _ _ O CV O U Cn L L_ U Cn L.� U fn W 2 (.� J Q M U_ U_ Cq t= O O 0:f Z Z Z J CC 4J Z p 04 CV W N N N Cn O O = U U N (n (n N p O Z Q H U C 0 W 0 W W Q H Cn Q I- [n Z OQQ W W W W �' C=7 J C=> J C7 J E E W ZO Li W Z of W Q L H Cn H (n IZ 0- UJ CL a_ U U N Z O Z O O O O J J O 0- a- U Q Z Z (n fn N Z Q W Z ¢ L� Z Q N M 0 � � � Q Q O Q 0 ¢ 0 J LU_ LNi W Z O O O = 2 2 W W Z LQ� J Q Q W Q W Z Z Z U<- Z Z Z O Z O O of of Q 2 2 O O C7 C� C 7 J Q a Q J Q Q Q Z C7 CL U Q Cr OR J Q Z Z IQi Z IQi Z LE Z Z O Z O Z O Cn (n W Z Q L� Z Q W Z LQ, L 1- Z Q W 2 Q I- N Q H N J W J J J J J CV O O OPERATIONS U W Q U W O O O O O Z Z Z Z Z O 2 CD 2 CD U Z Z Z O N O O H Q W W ,� Q O Q o o o Z O O I- o H o J �_ J J 0 0 0 Q LI..I W MATRIX Q L.� H �_ o Z J J Z O Z Q _ of _ W _ of (n (n __J _J W Q ¢ w O N O CD O Q Q H J (n W J W J W Z Q N O W Z C 7 Q Z (n (n 3 N N _� J ~ W W W (/') N W (n O p Z > Q J C� Cn J Q J ~ C,L < Cn N N (n N (n W W W W W �' of _ _ Q LU Li CL L� W L� J J W C) M W U m Ln J Z Q Q W L.I..I LII W W W Q Lnn Ln Cn (nLIJ N (n f� Q H Q H O O O Z O Z O Z O LL O W O LL O O W O W H X LIJQ Q C� Q (n Ld J _J of of W W H Q N Z O C' O N W W (n U (n Z Z Q Cn N Z a_ CL a_ J J O W W W W W H H H W C) W C) W CL W W W W W W Z O Z O W Z_ (n _J (n N W tY (n H Q W W Z Q J J W W W O a_ Z J J J p J > J J W M > � J m Q Z � U � Z Q ¢ U Cn Q W W W � W � O H O H O H Q >> Q J J J J J J W � Q Q Q W O O O O O O W W W W m m _ m W cr L L1 � W Q Q � L.� Q O > Q Q Q Q Q W _J W J W O LL1 W O U LL. L.L. LL. � a_ CL CL CL CL a- CL a- Y Y U N O CL 0 O O Q a- ZD O o W H M_ >> W W � 0 U L L_ W W Q Q > W > W >> W H Cn H [n J W [� J 2i W p p p Z Z Z Z Z Z Z Z Z ElfW () (n Q ZD Q Z3 N Z Q H ZD Q Q Cn J Q J W O Z Z Z Z Z H (n H (n J W J W J W Z Z Z W >� ¢ Q Q >Q > LLI Y O LL > W > LL > Q Li Q Li Q Li Q Li Q Li Q Li Q Li Q Li Q Li N N J Q W W W W W W W ~ ~ ~ ~ W W W W W W W W W W W Q Q W J N Cn W W W W W W W W W W W W W W W H Q H Q H Q H Q H Q H Q � (n M (n (n (n H Q H Q H Q H Q H Q O O O O F_ Q H Q H Q H Q H Q O O O Cn (/) W W W W (n H Q H Q H Q H Q H Q H Q H Q H Q H Q H Q H Q H Q H Q H Q w � CO Z > > > > > > F- Z Z Z z > I- > > > > ZD > > � > I- > � > W Z W Z W z W (n O (n O (n O z W > > > > > > > > > > > > > > FIRE ALARM INPUT o a ¢ ¢ ¢ a a ¢ a ¢ ¢ a U) czn Lnn can ¢ ¢ ¢ a a v C L o> 0 0 0 U o¢ Q¢ a a a a a Q¢ Q¢ a a SYSTEM NORMAL # # # SMOKE DETECTORS # # # # # # # # # # # # # HEAT DETECTORS i i # i # • i i i i # • • # • PULL STATIONS i • # # # # # # # # # # # # # # # PRIMARY RECALL FLR, ELEV LOBBY SMOKE DIET # # # i # # • # # # # # i # • # # i ALTERNATE RECALL FLR, ELEV LOBBY SMOKE DIET # # # # # # # # # # # # # # # TOP OF ELEV SHAFT SMOKE DIET # # # # # # # # # # # # # # # # # # # # ELEVATOR EQUIPMENT ROOM SMOKE DIET i i • i • # • # • # # i # # i # # • # ELEVATOR EQUIPMENT ROOM HEAT DET # # # # # # # # # # # # # # WATERFLOW SWITCHES # # # # # # # # # # # # # # # # # VALVE SUPERVISORY SWITCHES i # • i DUCT DETECTORS ON RTU # # # # ! # DUCT DETECTORS ON SPF STAIR 01 # # # # # # # # DUCT DETECTORS ON SPF STAIR 02 # # # # # # # DUCT DETECTORS ON EPF # # # # # # # # FAN SWITCH OVERRIDE SET TO "ON" AT FSCP i i • i i i i # # # # FAN SWITCH OVERRIDE SET TO "OFF" AT FSCP # # # # # # # # # TWO-WAY COMMUNICATION LOSS OF COMMUNICATION # # # # TWO-WAY COMMUNICATION LOSS OF POWER i # • i VFD FAULT STAIR 01 # # # # # • VFD FAULT STAIR 02 # # # # # • VFD FAULT ELEVATOR # # # # # FAN PROPER OPERATION STAIR 01 # # # # # # FAN PROPER OPERATION STAIR 02 FAN PROPER OPERATION ELEVATOR # # # # # FAN POWER ON STAIR 01 # # # # # # FAN POWER ON STAIR 02 FAN POWER ON ELEVATOR # # # # ! # FAN POWER OFF STAIR 01 # # # # # # FAN POWER OFF STAIR 02 # # # # # FAN POWER OFF ELEVATOR # # # # # # SMOKE CONTROL RELIEF LOUVER L-4 OPEN i i • i i # SMOKE CONTROL RELIEF LOUVER L-4 CLOSED # # # FIRE ALARM AC POWER FAIL # # # FIRE ALARM LOW BATTERY OPEN CIRCUIT # # # # GROUND FAULT # • NAC SHORT CIRCUIT # # # 1# LOSS OF AC TO BUILDING # # # # #7 QTY SYMBOL DESCRIPTION MANUFACTURER MODEL BACKBOX MOUNTING HEIGHT GENERAL NOTES. 1 FACP R ALARM ANEL MIRCOM FX-4003-12N ROD BY PROVIDED " A.F.F.CONTRL TO 1. SCOPE OF WORK: THIS PROJECT SHALL INCLUDE THE INSTALLATION OF A NEW 11 BPSx BOOSTER POWER POTTER PSN106 PROVIDED BY FIELD DETERMINE ADDRESSABLE FIRE ALARM SYSTEM IN A NEW APARTMENT BUILDING WITH A SUPPLY POTTER PARKING GARAGE. FIRE ALARM SYSTEM SHALL ACTIVATE SMOKE CONTROL SYSTEM 1 FCC FIRE RE ALARM COMMUNICATOR AES 7707 PROVIDED BYES A DETERMINE AS REQUIRED. 1 DOC Q DOCUMENT SPACE AGE SS000689 N/A FIELD DETERMINE 2• THESE DRAWINGS ARE DIAGRAMMATIC. REFER TO THE ARCHITECTURAL DRAWINGS ENCLOSURE FOR EXACT DIMENSIONS. 1 FSCP CONTROL PANELOKE KIRKLAND - PROVIDEDBY TO" A.F.F. 3. INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND ALL OTHER APPLICABLE 1 WA TWO-WAY COMM. RATH 2500-205FM PROVIDED BY ss" A.F.F.CODES AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION. BASE STATION RATH TO TOP 1 PRINT FIRE ALARM SYSTEM MIRCOM PTR-2000-1 4. WIRING DEPICTED ON THESE PLANS IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY PRINTER DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING 113 PHOTOELECTRIC MICRON MIX-4010-ISO 4S DEEP BETWEEN 4-12 CONSTRUCTION CONDITIONS ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA `=/p SMOKE DETECTOR W/3-0 RING OF CEILING SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS DUCT TYPE PROVIDED BY OTHERS LONG AS NO 110V OR HIGHER VOLTAGE CABLES ARE IN THE SAME RACEWAY. 5 S SMOKE DETECTOR 2 Fi O SPOT TYPE MIRCOM MIX-4030 4S DEEP BETWEEN R 12 5. FIRE RATINGS SHALL BE MAINTAINED FOR ALL PENETRATIONS THROUGH FIRE -RATED HEAT DETECTOR W/3-0 RING OF CEILING CONSTRUCTION. 1 0 MANUAL PULL MIRCOM MPS-802MP 4S DEEP R NG 0"CENTER 6. POWER FOR ALL FIRE ALARM PANELS AND FIRE ALARM POWER SUPPLIES MUST BE ADDRESSABLE MINI PROVIDED BY A DEDICATED AC BRANCH CIRCUIT. THE LOCATION OF THE BRANCH INPUT MODULE MIRCOM MIX-4041 FIELD DETERMINE FIELD DETERMINE CIRCUIT BREAKER SHALL BE PERMANENTLY IDENTIFIED AT THE CONTROL UNIT, MECHANICALLY PROTECTED, ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL AND 3 ® IMPUTE MODULE MIRCOM MIX-4040 4S DEEP FIELD DETERMINE SHALL BE RED AND LABELED "FIRE ALARM CIRCUIT CONTROL" IN ACCORDANCE ADDRESSABLE WITH NFPA 72. ELECTRICAL CONTRACTOR SHALL PERFORM LOAD CALCULATIONS TO 13 ® 2 INPUT MODULE MIRCOM MIX-4040 4S DEEP FIELD DETERMINE DETERMINE SIZE OF WIRING AND BREAKERS FOR ALL FIRE ALARM AC BRANCH ADDRESSABLE CIRCUITS BASED ON THE INFORMATION PROVIDED IN THE BATTERY CALCULATIONS 32 ® OUTPUT MODULE MIRCOM MIX-4045 4S DEEP FIELD DETERMINE FOR THE FIRE ALARM EQUIPMENT. IN/OUT MODULE MIRCOM MIX-4045 4S DEEP FIELD DETERMINE 7, POWER -LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST REMAIN SEPARATED SPRINKLER PROVIDED BY OTHERS IN CABINET. ALL POWER -LIMITED CIRCUIT WIRING MUST REMAIN AT LEAST 0.25" 1 © WATERFLOW AWAY FROM ANY NONPOWER-LIMITED CIRCUIT WIRING. FURTHERMORE, ALL SPRINKLER PROVIDED BY OTHERS POWER -LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST ENTER AND EXIT 3 ® TAMPER SWITCH THE CABINET THROUGH DIFFERENT KNOCK OUTS AND/OR SEPARATE CONDUITS. 1 ® APR SWI CH HI/LOW PROVIDED BY OTHERS "A" 8. WHEN UTILIZING CLASS CIRCUITS, SEPARATE OUTGOING AND RETURN 1 LT SPRINKLER ROOM PROVIDED BY OTHERS CONDUCTORS OF CLASS "A" CIRCUITS BY A MINIMUM OF 12" WHERE RUN LOW TEMPERATURE VERTICALLY AND 48 WHERE RUN HORIZONTALLY. 0 KEY SWITCH MIRCOM - 4S DEEP R NG FIELD DETERMINE 9, WHEN UTILIZING SHIELDED CABLE TIE SHIELDS THROUGH AND INSULATE AT EACH o Plv INDICATOR PROVIDED BY OTHERS JUNCTION BOX. INSULATE AND TAPE BACK AT END. 4 TAMPER SWITCH NOTIFICATION HORN/STROBE WHEELOCK ELHSW 4S DEEP W/1G RING 84" A.F.F. TO CENTER 10. ALL FIRE ALARM CABLING SHALL BE ACCEPTABLE TO THE FIRE ALARM EQUIPMENT MANUFACTURER FOR THE INTENDED PURPOSE. CABLES USED IN VERTICAL RUNS CEILINNOTIFIG MOUNT SHALL BE TYPE FPLP OR FPLR. CABLE SPLICES OR TERMINATIONS SHALL BE MADE 78 HORN/STROBE WHEELOCK ELHTWC 4S DEEP CEILING IN LISTED FITTINGS, BOXES, ENCLOSURES, FIRE ALARM DEVICES, OR UTILIZATION WPBBS BY HELD DETERMINE EQUIPMENT. WHERE INSTALLED EXPOSED, CABLES SHALL BE ADEQUATELY 2 Q NOTIFICATION WHEELOCK ASWP2475WFR WHEELOCK O FANSE D SUPPORTED AND INSTALLED IN SUCH A WAY THAT MAXIMUM PROTECTION AGAINST 45 NOTIFICATON WHEELOCK ELSTW 4S DEEP 84" A.F.F. PHYSICAL DAMAGE IS AFFORDED BY BUILDING CONSTRUCTION. WHERE LOCATED STROBE ONLY W/1G RING TO CENTER WITHIN 7 FT OF THE FLOOR, CABLES SHALL BE SECURELY FASTENED IN AN 22 �Cm NEILING MOUNT OTIFICATION WHEELOCK ELSTWC 4S DEEP CEILING APPROVED MANNER AT INTERVALS OF NOT MORE THAN 18 IN. 21 NOTIFI ATION WHEELOCK ELFHSW 4S DEEP 84" A.F.F. 11. SMOKE DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER CONSTRUCTION HORN- �Q W/1G RING TO CENTER CLEAN-UP IS COMPLETED AND FINAL. o 41 NOTIFI ATION WHEELOCK ELFHSWC 4S DEEP CEILING 12. LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL 182 H N W FIRTI N WHEELOCK ELFHNW 4S DEEP 84" A.F.F. DIFFUSERS. WALL -MOUNTED SMOKE DETECTORS SHALL BE LOCATED A MAXIMUM OF HORN QNLX W/1G RING TO CENTER 12 FROM CEILING. 0 101, LOW WhQUENUT NOTIFCATI N HORN ONLY WHEELOCK ELFHNWC 4S DEEP CEILING 13. PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS. PROVIDED BY A.F.F. PROVIDE ALL REQUIRED SYNC MODULES. PROVIDE A MULTI -SYNC MODE SLAVE 1 ® CAL STATIONMM� BATH 2100-95sSSRC2 o" CONNECTION BETWEEN ALL SYNC MODULES. 5 ® TWO-WAY COMM. STATION 2100-95sSSRC2 PROVIDED BY RAT T"UTCL OTON 14. VERIFY ALL FIELD SELECTABLE AUDIBILITY SETTINGS OF NOTIFICATION APPLIANCES AS REQ. J ❑ PERTINENT JUNCTION BOX LOCATE AS REQUIRED -- NOT ALL J-BOXES APPEAR ON PLANS WITH FIRE ALARM CONTRACTOR. END OF LINE 15. UPON COMPLETION OF THE FIRE ALARM SYSTEM INSTALLATION AND PROGRAMMING, -wwL- RESISTOR THE INSTALLING CONTRACTOR SHALL PERFORM FINAL TESTING OF THE ENTIRE SYSTEM, PER ALL APPLICABLE CODES, AND SHALL COORDINATE AND PERFORM A FINAL FIRE ALARM SYSTEM INSPECTION. 16. PROVIDE OFF -SITE MONITORING AS REQUIRED BY THE INTERNATIONAL FIRE CODE, SECTION 907.6.6 AND THE LOCAL AUTHORITY HAVING JURISDICTION. 17. INSTALLING CONTRACTOR SHALL, PHYSICALLY, LABEL ALL INITIATING DEVICES AND NOTIFICATION APPLIANCE CIRCUIT END OF LINE (WHEN WIRING CLASS "B"). THESE LABELS SHALL BE IN PLACE PRIOR TO START-UP AND TESTING. 18. ROOMS CONTAINING CONTROLS FOR AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL ELEMENTS SHALL BE IDENTIFIED WITH PERMANENTLY MOUNTED SIGNS WITH LETTERING NOT LESS THAN 2 INCHES TALL WITH A PRINCIPAL STROKE OF NOT LESS THAN 3/8 INCH. LETTERS SHALL CONTRAST WITH BACKGROUND. WIRE LEGEND SYM DESCRIPTION WIRE LEGEND COLOUR CIRCUIT TYPE WINDY CITY GENESIS SOUTHWIRE WEST PENN A 1 PAIR 14AWG FIRE RATED CABLE RED AUDIBLE/VISUAL CIRCUIT 7613 4511 G50032 60991 B B 2 COND. 16AWG OAS FIRE RATED CABLE RED BUS/RS485 CIRCUIT (FAA) 76132 4606 G50013 60994B Dx 1 PAIR 16AWG FIRE RATED CABLE RED SLC/DATA CIRCUIT 7613 4511 G50032 60991 B Sx 1 PAIR 14AWG FIRE RATED CABLE RED AUDIBLE/VISUAL CIRCUIT 7613 4511 G50032 60991 B P 1 PAIR 16AWG FIRE RATED CABLE RED GENERIC POWER 7613 4511 G50032 60991 B Zx 1 PAIR 16AWG FIRE RATED CABLE RED CONVENTIONAL DEVICE CIRCUIT 7613 4511 G50032 60991 B WIRE RUN IN 2-HOUR RATED PATHWAY IN CONDUIT WIRE RUN IN CONDUIT NOTES 1 "e" IN FRONT OF LETTER SIGNIFIES CIRCUIT CABLE EXISTING, TO REMAIN AND MAY DIFFER FROM SPECIFIED CALLOUT. 2 = HASH MARK QUANTITY SIGNIFIES QUANTITY OF DESCRIBED WIRE 3 ALL WIRE PERMITTED, FURNISHED AND INSTALLED BY RHEMA ELECTRIC AS A JOINT VENTURE. 4 WIRE MANUFACTURER IS FOR REFERENCE ONLY. ENSURE PROPER CROSS REFERENCE WHEN USING DIFFERENT MANUFACTURER. 5 BY DEFAULT-WASHINGTON ALARM SPECIFIES FPLP WIRING. ELECTRICAL CONTRACTOR SHALL ENSURE CABLE TYPE CONSISTENT WITH NEC REQUIREMENTS. 6 STRIPING -WHEN APPLICABLE -IS NOT REQUIRED AND IS RECOMMENDED FOR EASE OF CIRCUIT IDENTIFICATION. ALL CIRCUITRY SHALL BE UNIQUELY AND LOGICALLY LABELED. 7 ALL FIRE ALARM WIRING TYPES SHALL MAINTAIN SEPARATION FROM EACH OTHER, AND FROM AC CIRCUITRY. 4" MIN 12" MAX 4" MI A/C SUPPLY OR RETURN DIFFUSER PENDANT MOUNTED f AUDIBLE/VISUAL CEILING APPLIANCES 36" MIN. AUDIBLE/VISUAL AUDIBLE -ONLY REMOTE ALARM CEILING MOUNTED CEILING MOUNTED NEVER AND/OR VISUAL APPLIANCES INDICATOR SMOKE/HEAT AUDIBLE/VISUAL HERE ONLY APPLIANCE 0 o DETECTOR APPLIANCES WALL -MOUNTED HEAT DETECTOR DOOR WIDTH 4" LESS 3� FSA MAGNETIC Rd 30' DOOR FACP SYSTEM HOLDER AI a RECORDS. 80"-96" 90" MIN. 10' MAX DOCUMENTS TO LOWEST WHERE CEILING AFF PART OF LENS HEIGHT ALLOWS I E= 5' MAX. CEILING -MOUNTED HEAT DETECTOR 66" TO 66" TO 66" TO TOP OF TOP OF TOP OF FSA FACP CABINET FINISHED FLOOR FIRE ALARM DEVICE MOUNTING HEIGHTS SCALE: NOT TO SCALE FROM EXIT MANUAL 42"-48" PULL STATION NOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST POINT OF DETECTOR 12" MAX "WALL -MOUNTED SMOKE DETECTOR MAX SIDE WALL 30' MAX AFF FINISHED WALL Plan set for Smoke Control only. WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.corr WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 R ES U BM ITTA L 3/20/2023 R ES U BMITTAL 5/1 /2023 RESUBMITTAL Sheet Title FIRE ALARM NOTES WESUB L E G E N P23 2023 FEDMONDS DEVELOPMENT SERVICES DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA 1 000 0 2023, WASHINGTON ALARM 120 VAC (DEDICATED CKT.) TRIGGER & SYNC CIRCUIT TO BPS4A NO CONDUIT IN BOTTOM OF CAN NO CONDUIT IN BOTTOM OF CAN Plan set for Smoke Control only. I I WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.co WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 RESUBMITTAL 3/20/2023 RESUBMITTAL 5/ 1 /2023 RESUBMITTAL Sheet Title FIRE ALARM RISER RESUB D I A G R KMMO 3 DEVELOPMENT SERVICES DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA2001 0 2023, WASHINGTON ALARM TRIGGER & SYNC CIRCUIT FROM BPS313 ON FA2.01 NO CONDUIT IN BOTTOM OF CAN 15CD 15CD 150CD 15CD 13 S6A1-14 S6A1-15 S6A1-16 Plan set for Smoke Control only. WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.co WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 RESUBMITTAL 3/20/2023 RESUBMITTAL 5/ 1 /2023 RESUBMITTAL Sheet Title FIRE ALARM RISER RESUB D I A G R KMMO 3 DEVELOPMENT SERVICES DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA2002 0 2023, WASHINGTON ALARM 14111%,, M i room » FX-4000 Battery Calculation Program PROJECT NAME: ADDRESS: COMPANYNAME PREPARED BY: 9 1 FX-4000 Node # Panel Model FX-4003-12N / FX-4003-12NXT Main Chassis, no display (12 Amp) QTY Panel Adder Loops - MIX-4000 Devices (MGC, Requires MP Firmware) AL B2CN-960ISO Dua Ml Analog Loops (MIX-4000) w/ MP Firmware Pre -loaded 2 ALCN-960D Quad Analog Loops (MIX-4000) w/ MP Firmware Pre -loaded Panel Adder Modules Pq1FDX-008 / FDX-008KI HOA/Fan Damper Control Module IPS-2424DS 24 Programmable Input Switches Module RM-1008A 8 Relay Circuit Module 11 ISGM-1004A 4 Indicating Circuit Module Dialer / City Tie Modules �1 UDACT-300A Dialer Module Disolav Adder Modules = IDSPL-42ODS Narrow Display Intelligent Sensors & Modules - MIX-4000 (MGC, Requires MP Firmware) 113 MIX-4010-ISO Addressable Photo Sensor w/ Isolator 2 MIX-4030-ISO Addressable Tri-Heat Sensor w/ Isolator 16 1 IMIX-4040 Addressable Dual Input Monitor Module, latching 32 J IMIX-4045 Addressable Dual Relay Module Intelligent Manual Stations - MIX-4000 (MGC, Requires MP Firmware) MPS-802MP Addressable Two Stage Dual Action Manual Station (ULC) Intelligent Sensors & Modules - System Sensor (CLIP/AP) Intelligent Manual Stations - System Sensor (CLIP/AP) 24 Enter Number of Standby Hours 30 Enter Alarm Period in Minutes 1.2 Enter Battery Derating All Current in Amos Standby Alarm Current Current 0,310000 0,733000 0,4000001 0,426000 0,4000001 0,426000 0,015000 0.035000 0.005000 0,022000 0.025000 0150000 0.060000 0,258000 0.045000 0.120000 0.024000 0 025000 0,018080 0.018080 0,000320 0.000320 0,052800 0.052800 0.048000 0.048000 0.002000 0.002000 Total Standby Current in Amps 1.ao52oo Total Alarm Current in Amps 2.316200 Battery Capacity Requirement (Ah) a1.ss Recommended Mircom Batteries (x2) BAT-12va2A Mircom Technologies hereby disclaims all warranties relating to this software utility, whether expressed or implied, including without limitation any implied warranties of merchantability or fitness for a particular purpose. Mircom Technologies cannot and will not assume, accept or be liable for any special, incidental, consequential, indirect or similar claims, losses or damages for any reason whatsoever. Use of this Software Utility shall be deemed acceptance of these terms. It is the sole responsibility of the user to ascertain the accuracy and the reliability of any and all information generated or provided by this software utility and to ensure maximum current levels for control units have not been exceeded BPS1A Battery Calculation PROJECT NAME: ANTHOLOGY OF EDMONDS Required Standby Time: 241 Hours Required Alarm Time: 51 Minutes System Manufacturer Potter 2/8/2023 AC Branch Current AC Branch Current: 2.00 Amps ® 120V Maximum NAC Output Panel Max: 10.00 Amps Circuit Max: 2.50 Amps Regulated Load in Standby Device Type Model Number of Devices Current Am s Total Current (Amps) BPS1A MAINBOARD PSN-106 1 X 0.075000 = 0.075000 TOTAL STANDBY LOAD 0.075000 Regulated Load in ALARM Device Type Model Number of Devices Current (Amps) Total Current (Amps) BPS1A MAINBOARD S1A1 (See Voltage Drop Calculations) S1A2 (See Voltage Drop Calculations) S1A3 (See Voltage Drop Calculations) S1A4 (See Voltage Drop Calculations) SIIA5 (See Voltage Drop Calculations) S1A6 See Voltage Drop Calculations PSN-106 1 X 0.075000 = 0.075000 0.822000 = 0.822000 0.574000 = 0.574000 1.040000 = 1.040000 0.044000 = 0.044000 1.338000 = 1.338000 0.278000 = 0.278000 TOTAL ALARM LOAD 4.171000 Battery Requirements Standby Load Current (Amps) Required Standby Time in Hours 0.075000 X 24.00000 = 1.800000 Alarm Load Current (Amps) Required Alarm Time in Hours 4.171000 X 0.083333 = 0.347583 Total Ampere Hours before derating factor Derating Factor X 2.147583 1.2 TOTAL AMPERE HOURS REQUIRED = 2.577100 BATTERIES TO BE PROVIDED 2 - 12v 7 AH BPS2A Battery Calculation PROJECT NAME: ANTHOLOGY OF EDMONDS Required Standby Time: 24 Hours Required Alarm Time: 5 Minutes System Manufacturer Potter 2/8/2023 AC Branch Current AC Branch Current: 2.00 Amps ® 120V Maximum NAC Output Panel Max: 10.00 Amps Circuit Max: 2.50 Amps Regulated Load in Standby Device Type Model ber Current of vices (Amps) NFe Total Current (Amps) BPS2A MAINBOARD PSN-106 X 0.075000 = 0.075000 TOTAL STANDBY LOAD 0.075000 Regulated Load in ALARM Device Type Model Number of Devices Current Am s Total Current (Amps) BPS2A MAINBOARD S2A1 (See Voltage Drop Calculations) S2A2 (See Voltage Drop Calculations) S2A3 (See Voltage Drop Calculations) S2A4 See Voltage Drop Calculations S2A5 (See Voltage Drop Calculations) S2A6 See Voltage Drop Calculations PSN-106 1 X 0.075000 = 0.075000 0.828000 = 0.828000 0.480000 = 0.480000 1.268000 = 1.268000 1.078000 = 1.078000 0.536000 = 0.536000 0.000000 = 0.000000 TOTAL ALARM LOAD 4.265000 Battery Requirements Standby Load Current (Amps) Required Standby Time in Hours 0.075000 X 24.00000 = 1.800000 Alarm Load Current (Amps) Required Alarm Time in Hours 4.265000 X 0.083333 = 0.355417 Total Ampere Hours before derating factor Dera-ring Factor X 2.155417 1.2 TOTAL AMPERE HOURS REQUIRED = 2.586500 BATTERIES TO BE PROVIDED 2 - 12v 7 AH BPS2B Battery Calculation PROJECT NAME: ANTHOLOGY OF EDMONDS Required Standby Time: 241 Hours Required Alarm Time: 51 Minutes System Manufacturer Potter 2/8/2023 AC Branch Current AC Branch Current: 2.00 Amps 0 120V Maximum NAC Output Panel Max: 10.00 Amps Circuit Max: 2.50 Amps Regulated Load in Standby Device Type Model Number of Devices Current (Amps) Total Current (Amps) BPS2B MAINBOARD PSN-106 1 X 0.075000 = 0.075000 TOTAL STANDBY LOAD 0.075000 Regulated Load in ALARM Device Type Model Number of Devices Current Am s Total Current (Amps) BPS28 MAINBOARD S2B1 (See Voltage Drop Calculations) S2B2 (See Voltage Drop Calculations) S2B3 (See Voltage Drop Calculations) S2B4 (See Voltage Drop Calculations) S2B5 (See Voltage Drop Calculations) S2B6 See Voltage Drop Calculations PSN-106 1 X 0.075000 = 0.075000 0.784000 = 0.784000 0.882000 = 0.882000 0.784000 = 0.784000 0.000000 = 0.000000 0.000000 = 0.000000 0.000000 = 0.000000 TOTAL ALARM LOAD 2.525000 Battery Requirements Standby Load Current (Amps) Required Standby Time in Hours 0.075000 X 24.00000 = 1.800000 Alarm Load Current (Amps) Required Alarm Time in Hours 2.525000 X 0.083333 = 0.210417 Total Ampere Hours before derating factor Derating Factor X 2.010417 1.2 TOTAL AMPERE HOURS REQUIRED = 2.412500 BATTERIES TO BE PROVIDED 2 - 12v 7 AH BPS3A Battery Calculation PROJECT NAME: ANTHOLOGY OF EDMONDS Required Standby Time: 241 Hours Required Alarm Time: 51 Minutes System Manufacturer Potter 2/8/2023 AC Branch Current AC Branch Current: 2.00 Amps @ 120V Maximum NAC Output Panel Max: 10.00 Amps Circuit Max: 2.50 Amps Regulate Load in Standby Device Type Model Number of Devices Current Am s Total Current (Amps) BPS3A MAINBOARD PSN-106 1 X 0.075000 = 0.075000 TOTAL STANDBY LOAD 0.075000 Regulated Load in ALARM Device Type Model Number of Devices Current Am s Total Current (Amps) BPS3A MAINBOARD S3A1 (See Voltage Drop Calculations) S3A2 (See Voltage Drop Calculations) S3A3 (See Voltage Drop Calculations) S3A4 (See Voltage Drop Calculations) S3A5 (See Voltage Drop Calculations) S3A6 See Voltage Drop Calculations PSN-106 1 X 0.075000 = 0.075000 0.828000 = 0.828000 0.000000 = 0.000000 0.784000 = 0.784000 1.078000 = 1.078000 0.00000011 0.000000 0.000000T-=T 0.000000 TOTAL ALARM LOAD 2.765000 Battery Requirements Standby Load Current (Amps) Required Standby Time in Hours 0.075000 X 24.00000 = 1.800000 Alarm Load Current (Amps) Required Alarm Time in Hours 2.765000 X 0.083333 = 0.230417 Total Ampere Hours before derating factor Derating Factor X 2.030417 1.2 TOTAL AMPERE HOURS REQUIRED = 2.436500 BATTERIES TO BE PROVIDED 2 - 12v 7 AH BPS3B Battery Calculation PROJECT NAME: ANTHOLOGY OF EDMONDS Required Standby Time: 241 Hours Required Alarm Time: 51 Minutes System Manufacturer Potter 2/8/2023 AC Branch Current AC Branch Current: 2.00 Amps @ 120V Maximum NAC Output Panel Max: 10.00 Amps Circuit Max: 2.50 Amps Regulated Load in Standby Device Type Model Number of Devices Current (Amps) Total Current (Amps) BPS38 MAINBOARD PSN-106 1 X 0.075000 = 0.075000 TOTAL STANDBY LOAD 0.075000 Regulated Load in ALARM Device Type Model Number of Devices Current (Amps) Total Current (Amps) BPS3B MAINBOARD S3B1 (See Voltage Drop Calculations) S3B2 (See Voltage Drop Calculations) S3B3 (See Voltage Drop Calculations) S3B4 See Voltage Drop Calculations S3B5 (See Voltage Drop Calculations) S3B6 See Voltage Drop Calculations PSN-106 1 X 0.075000 = 0.075000 1.078000 = 1 A780 00 0.882000 = 0.882000 0.784000 = 0.784000 0.000000 = 0.000000 0.000000 = 0.000000 0.000000 = 0.000000 TOTAL ALARM LOAD 2.819000 Battery Requirements Standby Load Current (Amps) Required Standby Time in Hours 0.075000 X 24.00000 = 1.800000 Alarm Load Current (Amps) Required Alarm Time in Hours 2.819000 X 0.083333 = 0.234917 Total Ampere Hours before derating factor Derating Factor X 2.034917 1.2 TOTAL AMPERE HOURS REQUIRED = 2.441900 BATTERIES TO BE PROVIDED 2 - 12v 7 AH BPS4A Battery Calculation PROJECT NAME: ANTHOLOGY OF EDMONDS Required Standby Time: 24 Hours Required Alarm Time: 5 Minutes System Manufacturer Potter 2/8/2023 AC Branch Current AC Branch Current: 2.00 Amps @ 120V Maximum NAC Output Panel Max: 10.00 Amps Circuit Max: 2.50 Amps Regulated Load in Standby Device Type _T Model Number of Devices Current (Amps) Total Current (Amps) BPS4A MAINBOARD PSN-106 1 X 0.075000 = 0.075000 TOTAL STANDBY LOAD 0.075000 Regulated Load in ALARM Device Type Model Number of Devices Current (Amps) Total Current (Amps) 8PS4A MAINBOARD S4A1 (See Voltage Drop Calculations) S4A2 (See Voltage Drop Calculations) S4A3 (See Voltage Drop Calculations) S4A4 (See Voltage Drop Calculations) S4A5 (See Voltage Drop Calculations) S4A6 See Voltage Drop Calculations PSN-106 1 X 0.075000 = 0.075000 0.828000 0.828000 = 0.000000 = 0.000000 1.268000 = 1.268000 1.078000 = 1.078000 0.000000 = 0.000000 0.000000 = 0.000000 TOTAL ALARM LOAD 3.249000 Battery Requirements Standby Load Current (Amps) Required Standby Time in Hours 0.075000 X 24.00000 = 1.800000 Alarm Load Current (Amps) Required Alarm Time in Hours 3.249000 X 0.083333 = 0.270750 Total Ampere Hours before derating factor Derating Factor X 2.070750 1.2 TOTAL AMPERE HOURS REQUIRED = 2.484900 BATTERIES TO BE PROVIDED 2 - 12v 7 AH BPS4B Battery Calculation PROJECT NAME: ANTHOLOGY OF EDMONDS Required Standby Time: 241 Hours Required Alarm Time: 51 Minutes System Manufacturer Potter 2/8/2023 AC Branch Current AC Branch Current: 2.00 Amps @ 120V Maximum NAC Output Panel Max: 10.00 Amps Circuit Max: 2.50 Amps Regulated Load in Standby Device Type Model Number of Devices Current (Amps) Total Current (Amps) BPS48 MAINBOARD PSN-106 1 X 0.075000 = 0.075000 TOTAL STANDBY LOAD 0.075000 Regulated Load in ALARM Device Type Model Number of Devices Current (Amps) Total Current (Amps) BPS4B MAINBOARD S461 (See Voltage Drop Calculations) S462 (See Voltage Drop Calculations) S463 (See Voltage Drop Calculations) S464 (See Voltage Drop Calculations) S465 (See Voltage Drop Calculations) S4B6 See Voltage Drop Calculations PSN-106 1 X 0.075000 = 0.075000 1.078000 = 1.078000 0.882000 = 0.882000 0.784000 = 0.784000 0.000000 = 0.000000 0.000000 = 0.000000 0.00000011 0.000000 TOTAL ALARM LOAD 2.819000 Battery Requirements Standby Load Current (Amps) Required Standby Time in Hours 0.075000 X 24.00000 = 1.800000 Alarm Load Current (Amps) Required Alarm Time in Hours 2.819000 X 0.083333 = 0.234917 Total Ampere Hours before derating factor Derating Factor X 2. 334 117 1.2 TOTAL AMPERE HOURS REQUIRED = 2.441900 BATTERIES TO BE PROVIDED 2 - 12v 7 AH BPS5A Battery Calculation PROJECT NAME: ANTHOLOGY OF EDMONDS Required Standby Time: 241 Hours Required Alarm Time: 51 Minutes System Manufacturer Potter 2/8/2023 AC Branch Current AC Branch Current: 2.00 Amps @ 120V Maximum NAC Output Panel Max: 10.00 Amps Circuit Max: 2.50 Amps Regulated Load in Standby Device Type Model Number Current of Devices Am s Total Current (Amps) BPS5A MAINBOARD PSN-106 1 X 0.075000 = 0.075000 TOTAL STANDBY LOAD 0.075000 Regulated Load in ALARM Device Type Model Number of Devices Current (Amps Total Current (Amps) BPS5A MAINBOARD S5A1 (See Voltage Drop Calculations) S5A2 (See Voltage Drop Calculations) S5A3 (See Voltage Drop Calculations) S5A4 See Voltage Drop Calculations S5A5 (See Voltage Drop Calculations) S5A6 See Voltage Drop Calculations PSN-106 1 X 0.075000 = 0.075000 0.828000 = 0.828000 0.000000 = 0.000000 0.784000 = 0.784000 1.078000 = 1.078000 0.000000 = 0.000000 0.000000 = 0.000000 TOTAL ALARM LOAD 2.765000 Battery Requirements Standby Load Current (Amps) Required Standby Time in Hours 0.075000 X 24.00000 = 1.800000 Alarm Load Current (Amps) Required Alarm Time in Hours 2.765000 X 0.083333 = 0.230417 Total Ampere Hours before derating factor Derating Factor X T. 330 117 1.2 TOTAL AMPERE HOURS REQUIRED = 2.436500 BATTERIES TO BE PROVIDED 2 - 12v 7 AH BPS5B Battery Calculation PROJECT NAME: ANTHOLOGY OF EDMONDS Required Standby Time: 241 Hours Required Alarm Time: 5 Minutes System Manufacturer Potter 2/8/2023 AC Branch Current AC Branch Current: 2.00 Amps ® 120V Maximum NAC Output Panel Max: 10.00 Amps Circuit Max: 2.50 Amps Regulated Load in Standby Device Type Model Number of Devices Current Am s Total Current (Amps) BPS56 MAINBOARD PSN-106 1 X 0.075000 = 0.075000 TOTAL STANDBY LOAD 0.075000 Regulated Load in ALARM Device Type Model Number of Devices Current (Amps) Total Current (Amps) BPS5B MAINBOARD S561 (See Voltage Drop Calculations) S562 (See Voltage Drop Calculations) S563 (See Voltage Drop Calculations) S584 (See Voltage Drop Calculations) S585 (See Voltage Drop Calculations) S5B6 See Voltage Drop Calculations PSN-106 1 X 0.075000 = 0.075000 1.078000 1.078000 = 0.882000 = 0.882000 0.784000 = 0.784000 0.000000 = 0.000000 0.000000 = 0.000000 0.000000 = 0.000000 TOTAL ALARM LOAD 2.819000 Battery Requirements Standby Load Current (Amps) Required Standby Time in Hours 0.075000 X 24.00000 = 1.800000 Alarm Load Current (Amps) Required Alarm Time in Hours 2.819000 X 0.083333 = 0.234917 Total Ampere Hours before derating factor Derating Factor X 2.034917 1.2 TOTAL AMPERE HOURS REQUIRED = 2.441900 BATTERIES TO BE PROVIDED 2 - 12v 7 AH BPS6A Battery Calculation PROJECT NAME: ANTHOLOGY OF EDMONDS Required Standby Time: 24 Hours Required Alarm Time: 5 Minutes System Manufacturer Potter 2/9/2023 AC Branch Current AC Branch Current: 2.00 Amps @ 120V Maximum NAC Output Panel Max: 10.00 Amps Circuit Max: 2.50 Amps Regulated Load in Standby Device Type Model Number of Devices Current (AMPS) Total Current (Amps) 8PS6A MAINBOARD PSN-106 1 X 0.075000 = 0.075000 TOTAL STANDBY LOAD 0.075000 Regulated Load in ALARM Device Type Model Number of Devices Current (Amps Total Current (Amps) BPS6A MAINBOARD S6A1 (See Voltage Drop Calculations) S6A2 (See Voltage Drop Calculations) S6A3 See Voltage Drop Calculations) S6A4 See Voltage Drop Calculations) S6A5 (See Voltage Drop Calculations) S6A6 See Voltage Drop Calculations PSN-106 1 X 0.075000 = 0.075000 0.581000 = 0.581000 0.743000 = 0.743000 1.268000 = 1.268000 0.686000 = 0.686000 0.000000 = 0.000000 0.000000 = 0.000000 TOTAL ALARM LOAD 3.353000 Battery Requirements Standby Load Current (Amps) Required Standby Time in Hours 0.075000 X 24.00000 = 1.800000 Alarm Load Current (Amps) Required Alarm Time in Hours 3.353000 X 0.083333 = 0.279417 Total Ampere Hours before derating factor Dera Ing Factor X 2.079417 1.2 TOTAL AMPERE HOURS REQUIRED = 2.495300 BATTERIES TO BE PROVIDED 2 - 12v 7 AH BPS6B Battery Calculation PROJECT NAME: ANTHOLOGY OF EDMONDS Required Standby Time: 24 Hours Required Alarm Time: 5 Minutes System Manufacturer Potter 2/8/2023 AC Branch Current AC Branch Current: 2.00 Amps ® 120V Maximum NAC Output Panel Max: 10.00 Amps Circuit Max: 2.50 Amps Regulated Load in Standby Device Type Model Number of Devices Current Am s Total Current (Amps) BPS6B MAINBOARD PSN-106 1 X 0.075000 = 0.075000 TOTAL STANDBY LOAD 0.075000 Regulated Load in ALARM Device Type Model Number of Devices Current Am s Total Current (Amps) BPS6B MAINBOARD S6B1 See Voltage Drop Calculations) S6B2 (See Voltage Drop Calculations) S6B3 (See Voltage Drop Calculations) S6B4 See Voltage Drop Calculations S6B5 (See Voltage Drop Calculations) S686 See Voltage Drop Calculations PSN-106 1 X 0.075000 = 0.075000 0.784000 = 0.784000 0.882000 = 0.882000 0.784000 = 0.784000 0.000000 = 0.000000 0.000000 = 0.000000 0.000000 = 0.000000 TOTAL ALARM LOAD 2.525000 Battery Requirements Standby Load Current (Amps) Required Standby Time in Hours 0.075000 X 24.00000 = 1.800000 Alarm Load Current (Amps) Required Alarm Time in Hours 2.525000 X 0.083333 = 0.210417 Total Ampere Hours before derating factor Dera Ing Factor X 2.010417 1.2 TOTAL AMPERE HOURS REQUIRED = 2.412500 BATTERIES TO BE PROVIDE - Tian set Tor iz:imoKe luontroi only. WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.corr WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 R ES U BM ITTA L 3/20/2023 R ES U BMITTAL 5/1 /2023 RESUBMITTAL Sheet Title FIRE ALARM CALC1,bPJAWNS May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA3,901 0 2023, WASHINGTON ALARM Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name ANTHOLOGY OF EDMONDS Circuit Number S1A1 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts 110 feet Gauge Per 1000 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.822 amps Spare Current Capacity 20% End of Line Voltage 19.02 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S1A1-1 ELHSC 177 0.208 110 19.84 0.555 2.72% S1A1-2 ELSTC 75 0.060 46 19.67 0.729 3.57% S1A1-3 ELSTC 15 0.022 18 19.61 0.790 3.87% S1A1-4 ELHSC 75 0.077 34 19.50 0.901 4.42% S1A1-5 ELSTC 15 0.022 18 19.45 0.951 4.66% S1A1-6 JELSTC 15 0.022 14 19.41 0.988 4.85% S1A1-7 ELHSC 30 0.046 43 19.301 1.097 5.38% S1A1-8 ELSTC 15 0.022 19 19.26 1.139 5.59% S1A1-9 ELSTC 30 0.030 26 19.21 1.194 5.85% S1A1-10 ELHSC 110 0.109 41 19.13 1.273 6.24% SlA1-11 ELSTC 15 0.022 36 19.08 1.318 6.46% SlA1-12 ELSTC 15 0.022 21 19.06 1.342 6.58% SlA1-13 ELSTC 110 0.086 23 19.04 1.364 6.69% SlA1-14 ELHSC 15 0.037 27 19.02 1.376 6.75% S1A1-15 ELHSC 15 0.037 20 19.02 1.381 6.77% Totals 0.822 1 496 Notes: Vire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name ANTHOLOGY OF EDMONDS Circuit Number S1A2 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts Gauge Per 1000 170 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.574 amps Spare Current Capacity 20% End of Line Voltage 19.27 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S1A2-1 ELHSC 110 0.109 0.030 170 19.80 0.599 34 19.70 0.696 2.94% 3.41% S1A2-2 ELSTC 30 S1A2-3 ELHSC 30 0.046 31 19.62 0.779 3.82% S1A2-4 ELHSC 30 0.046 28 19.55 0.846 4.15% S1A2-5 ELSTC 15 0.022 27 19.50 0.903 4.43% S1A2-6 ELHSC 15 0.037 19 19.46 0.940 4.61% S1A2-7 ELSTC 15 0.022 22 19.42 0.979 4.80% S1A2-8 ELHSC 75 0.077 30 19.37 1.027 5.03% SIIA2-9 ELSTC 30 0.030 47 19.32 1.080 5.30% S1A2-10 ELHSC 30 0.046 32 19.291 1.111 5.447. S1A2-11 ELHSC 110 1 0.109 26 19.271 1.128 5.53% Totals 0.574 466 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S1A3 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts Gauge Per 1000 70 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 1.040 amps Spare Current Capacity 20% End of Line Voltage 19.22 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S1A3-1 ELHSC 177 0.208 70 19.951 54 19.68 0.447 0.723 2.19% 3.547o S1A3-2 ELHSC 177 0.208 S 1 A3-3 ELHSC 177 0.208 57 19.46 0.941 4.61 % S1A3-4 ELHSC 177 0.208 1 0.208 63 64 19.30 19.22 1.102 1.184 5.40% 5.80% S1A3-5 ELHSC 177 Totals 1.040 1 308 Notes: Vire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name ANTHOLOGY OF EDMONDS Circuit Number S1A4 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts Gauge Per 1000 216 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.044 amps Spare Current Capacity 20% End of Line Voltage 20.31 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S1A4-1 I ELST 15 0.0221 216 20.34 0.058 0.29% S1A4-2 I ELST 15 0.0221 201 20.31 0.086 0.42% Totals 0.044 1 417 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S1A5 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 35 volts feet Gauge 14 Per 1000 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 1.338 amps Spare Current Capacity 20% End of Line Voltage 17.33 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S1A5-1 I ELSTC 30 0.030 35 20.11 0.288 1.41% S1A5-2 ELHSC 177 0.208 53 19.69 0.713 3.50% S1 A5-3 ELHSC 177 0.208 70 19.21 1.186 5.81 % S1A5-4 ELHSC 177 0.208 70 18.83 1.569 7.69% S1A5-5 ELSTC 30 0.030 50 18.62 1.779 8.72% S1A5-6 ELHSC 177 0.208 230 17.70 2.703 13.25% S1A5-7 ELHSC 177 0.208 50 17.56 2.840 13.92% S1A5-8 ELST 30 0.030 51 17.49 2.914 14.29% S1A5-9 ELHSC 177 0.208 120 17.33 3.068 15.04% Totals 1.338 729 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S1A6 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 198 volts feet Gauge 14 Per 1000 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.278 amps Spare Current Capacity 20% End of Line Voltage 19.96 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S1A6-1 ELHS 30 0.046 198 20.06 20.05 0.338 0.352 1.66% 1.73% S1A6-2 ELHS 15 0.037 10 S1A6-3 ELHSC 30 0.046 24 1 20.02 0.381 1.87% S1A6-4 ELST 15 0.022 24 20.00 0.403 1.98% S1A6-5 ELST 15 0.022 21 19.98 0.419 2.06% S1A6-6 ELHS 15 0.037 22 19.97 0.433 2.12% S1A6-7 ELHS 30 0.046 10 19.96 0.438 2.15% S1A6-8 ELST 15 0.022 34 19.96 0.442 2.17% Totals 0.278 343 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S2A1 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 45 volts feet Gauge Per 1000 3.07 M14 Vire Gauge for balance of circuit 3.07 Max Output Current 2.50 amps Total Circuit Current 0.828 amps Spare Current Capacity 20% End of Line Voltage 18.72 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S2A1-1 ELSTC 15 0.022 45 20.17 0.229 1.12% S2A1-2 ELST 30 0.030 30 20.02 0.377 1.85% S2A1-3 ELST 15 0.022 22 19.92 0.482 2.36% S2A1-4 ELHSC 15 0.037 25 19.80 0.598 2.93% S2A1-5 ELHSC 177 0.208 52 19.57 0.827 4.05% S2A1-6 ELHSC 15 0.037 52 19.41 0.989 4.85% S2A1-7 ELST 75 0.060 44 19.28 1.117 5.47% S2A1-8 ELHSC 15 0.037 26 19.22 1.183 5.80% S2A1-9 ELST 15 0.022 38 19.13 1.270 6.23% S2A1-10 ELHSC 15 0.037 32 19.06 1.339 6.57% S2A1-11 ELHSC 15 0.037 48 18.97 1.433 7.02% S2A1-12 ELHSC 15 0.037 52 18.88 1.522 7.46% S2A1-13 ELHSC 15 0.037 52 18.80 1.599 7.84% S2A1-14 ELHSC 150 0.146 52 18.74 1.664 8.16% S2A1-15 ELHSC 15 0.037 0.022 48 16 18.72 18.72 1.682 1.684 8.24% 8.25% S2A1-16 ELST 15 Totals 0.828 634 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S2A2 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts Gauge Per 1000 50 feet 1 14 3.07 Wire Gauge for balance of circuit 1 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.480 amps Spare Current Capacity 207. End of Line Voltage 20.25 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S2A2-1 ASWP-24MCWH 185 0.480 50 20.25 0.147 0.72% Totals 1 0.480 1 50 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name ANTHOLOGY OF EDMONDS Circuit Number S2A3 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 22 volts Gauge Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 1.268 amps Spare Current Capacity 20% End of Line Voltage 19.08 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S2A3-1 ELST 15 0.022 22 20.23 0.171 0.84% S2A3-2 ELFHS 110 0.164 21 20.07 0.332 1.63% S2A3-3 ELFHN 0.098 34 19.84 0.558 2.73% S2A3-4 ELFHN 0.098 10 19.78 0.618 3.03% S2A3-5 ELFHS 110 0.164 65 19.43 0.972 4.76% S2A3-6 ELFHS 110 0.164 10 19.38 1.016 4.98% S2A3-7 ELST 15 0.022 22 19.31 1.092 5.35% S2A3-8 ELST 15 0.022 22 19.24 1.164 5.71 % S2A3-9 ELFHS 110 0.164 26 19.15 1.246 6.11 % S2A3-10 ELFHS 110 0.164 25 19.10 1.300 6.37% S2A3-11 ELFHS 110 0.164 0.022 10 29 19.09 19.08 1.311 1.315 6.43% 6.45% S2A3-12 ELST 15 Totals 1.268 296 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S2A4 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 82 volts Gau a Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 1.078 amps Spare Current Capacity 20% End of Line Voltage 19.09 volts Notification Appliance Manufacturer 1 Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S2A4-1 ELFHN 0.0981 0.098 82 24 19.86 0.543 2.66% S2A4-2 ELFHN 19.71 0.687 3.37% S2A4-3 ELFHN 0.098 16 19.63 0.774 3.79% S2A4-4 ELFHN 0.098 30 19.48 0.918 4.50% S2A4-5 ELFHN 0.098 18 19.41 0.994 4.87% S2A4-6 ELFHN 0.098 34 19.28 1.1171 5.47% S2A4-7 ELFHN 0.098 10 19.25 1.147 5.62% S2A4-8 ELFHN 0.098 34 19.17 1.229 6.02% S2A4-9 ELFHN 0.098 18 19.14 1.261 6.18% S2A4-10 ELFHN ELFHN 0.098 0.098 35 19.10 1.303 6.39% S2A4-11 10 19.09 1.309 6.42% Totals 1.078 311 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal . Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S2A5 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 158 volts Gauge Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.536 amps Spare Current Capacity 20% End of Line Voltage 19.74 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S2A5-1 ELST 15 0.022 158 24 19.88 0.520 2.55% S2A5-2 ELFHS 110 0.164 19.80 0.596 2.92% S2A5-3 ELFHS 110 0.164 23 19.75 0.645 3.16% S2A5-4 ELFHS 110 0.164 10 19.74 0.657 3.22% S2A5-5 ELST 15 0.022 19 19.74 0.659 3.23% Totals 1 0.536 1 234 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name ANTHOLOGY OF EDMONDS Circuit Number S3A1 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 45 volts feet Gauge Per 1000 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.828 amps Spare Current Capacity 20% End of Line Voltage 18.72 volts Notification Appliance Manufacturer Wheelock Circuit is within limits J Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S3A1-1 ELSTC 15 0.022 45 20.17 0.229 1.12% SW -2 ELST 30 0.030 30 20.02 0.377 1.85% SW -3 ELST 15 0.022 22 19.92 0.482 2.36% SW -4 ELHSC 15 0.037 25 19.80 0.598 2.93% SW -5 ELHSC 177 0.208 52 19.57 0.827 4.05% SW -6 ELHSC 15 0.037 52 19.41 0.9891 4.85% SW -7 ELST 75 0.060 44 19.28 1.117 5.47% SW -8 ELHSC 15 0.037 26 19.22 1.183 5.80% SW -9 ELST 15 0.022 38 19.13 1.270 6.23% S3A1-10 ELHSC 15 0.037 32 19.06 1.339 6.57% SW -11 ELHSC 15 0.037 48 18.97 1.433 7.02% S3A1-12 ELHSC 15 0.037 52 18.88 1.522 7.46% S3A1-13 ELHSC 15 0.037 52 18.80 1.599 7.84% S3A1-14 ELHSC 150 0.146 52 18.74 1.664 8.16% S3A1-15 ELHSC 15 0.037 48 18.72 1.682 8.24% SW -16 ELST 15 0.022 16 18.72 1.684 8.25% Totals 0.828 1 634 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S3A3 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 22 volts Gau a Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.784 amps Spare Current Capacity 20% End of Line Voltage 19.81 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S3A3-1 ELFHN 0.098 0.098 22 21 20.29 20.21 0.106 0.194 0.52% 0.95% S3A3-2 ELFHN S3A3-3 ELFHN 0.098 0.098 34 10 20.08 20.05 0.317 0.347 1.55% 1.70% S3A3-4 ELFHN S3A3-5 ELFHN 0.098 65 19.90 0.504 2.47% S3A3-6 ELFHN 0.098 29 19.84 0.556 2.73% S3A3-7 ELFHN ELFHN 0.098 25 19.81 19.81 0.586 0.592 2.87% 2.90% S3A3-8 0.098 10 Totals 0.784 1 216 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S3A4 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 82 volts feet Gauge Per 1000 14 3.07 Wire Gauge for balance of circuit 14 J 3.07 Max Output Current 2.50 amps Total Circuit Current 1.078 amps Spare Current Capacity 20% End of Line Voltage 1 19.091 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S3A4-1 ELFHN ELFHN 0.098 0.098 82 19.86 19.71 19.63 0.543 0.687 0.774 2.66% 3.37% 3.79% S3A4-2 24 16 S3A4-3 ELFHN 0.098 S3A4-4 ELFHN 0.098 30 19.48 0.918 4.50% S3A4-5 ELFHN 0.098 18 19.41 0.994 4.87% S3A4-6 ELFHN 0.098 34 19.28 1.117 5.47% S3A4-7 ELFHN 0.098 10 19.25 1.147 5.62% S3A4-8 ELFHN 0.098 34 19.17 1.229 6.02% S3A4-9 ELFHN 0.098 0.098 18 35 19.14 19.101 1.261 1.303 6.18% 6.39% S3A4-10 ELFHN ELFHN S3A4-11 0.098 10 19.091 1.309 6.42% Totals 1.078 1 311 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name ANTHOLOGY OF EDMONDS Circuit Number S361 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 164 volts Gauge Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 1.078 amps Spare Current Capacity 20% End of Line Voltage 18.61 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S3B1-1 ELFHN 0.098 164 23 19.31 1 19.18 1.086 5.32% S3B1-2 ELFHN 0.098 1.224 6.00% S3B1-3 ELFHN 0.098 10 19.12 1.278 6.26% S381-4 ELFHN 0.098 26 19.00 1.403 6.88% S381-5 ELFHN 0.098 24 18.90 1.504 7.37% S381-6 ELFHN 0.098 16 18.84 1.562 7.66% S3B1-7 ELFHN 0.098 30 18.75 1.652 8.10% S3B1-8 ELFHN 0.098 19 18.70 1.698 8.32% S3B1-9 ELFHN 0.098 0.098 31 22 18.65 18.62 1.754 1.780 8.60% 8.73% S3B1-10 ELFHN S3B1 -111 ELFHN 1 0.098 18 1 18.61 1.791 8.78% Totals 1.078 1 383 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name ANTHOLOGY OF EDMONDS Circuit Number S262 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts Gauge Per 1000 155 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.882 amps Spare Current Capacity 20% End of Line Voltage 19.14 volts Notification Appliance Manufacturer Wheelock Circuit is within limits J Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S282-1 ELFHN 0.0981 0.098 155 19.56 10 19.51 0.839 0.888 4.11% 4.35% S2B2-2 ELFHN S2B2-3 ELFHN 0.098 30 19.39 1.014 4.97% S2B2-4 ELFHN 0.098 10 19.35 1.050 5.15% S2B2-5 ELFHN 0.098 28 19.27 1.134 5.56% S282-6 ELFHN 0.098 16 19.23 1.173 5.75% S262-7 ELFHN 0.098 0.098 30 17 19.17 19.15 1.227 1.247 6.01 % 6.11 % S262-8 ELFHN S21132-9 ELFHN 0.098 24 19.14 1.262 6.19% Totals 0.882 320 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S363 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts Gauge Per 1000 110 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.784 amps Spare Current Capacity 20% End of Line Voltage 19.56 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S383-1 ELFHN 0.098 0.098 110 19.87 10 19.83 0.530 2.60% S3B3-2 ELFHN 0.572 2.80% S3B3-3 ELFHN 0.098 29 19.72 0.676 3.32% S3B3-4 ELFHN 0.098 10 19.69 0.706 3.46% S3B3-5 ELFHN 0.098 29 19.62 0.776 3.80% S3B3-6 ELFHN 0.098 10 19.61 0.794 3.89% S3B3-7 ELFHN 0.098 29 19.57 0.829 4.06% S383-8 ELFHN 0.098 10 19.56 0.835 4.09% Totals 0.784 1 237 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name ANTHOLOGY OF EDMONDS Circuit Number S4A1 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts 45 feet Gauge Per 1000 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.828 amps Spare Current Capacity 20% End of Line Voltage 18.72 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S4A1-1 ELSTC 15 0.022 45 20.17 0.229 1.12% S01-2 ELST 30 0.030 30 20.02 0.377 1.85% S4A1-3 ELST 15 0.022 22 19.92 0.482 2.36% S4A1-4 ELHSC 15 0.037 25 19.80 0.598 2.93% S4A1-5 ELHSC 177 0.208 52 19.57 0.827 4.05% S4A1-6 ELHSC 15 0.037 52 19.41 0.989 4.85% S4A1-7 ELST 75 0.060 44 19.28 1.117 5.47% S4A1-8 ELHSC 15 0.037 26 19.22 1.183 5.80% S4A1-9 ELST 15 0.022 38 19.13 1.270 6.23% S01-10 ELHSC 15 0.037 32 19.06 1.339 6.57% S4A1-11 ELHSC 15 0.037 48 18.97 1.433 7.02% S01-12 ELHSC 15 0.037 52 18.88 1.522 7.46% S01-13 ELHSC 15 0.037 52 18.80 1.599 7.847o S01-14 ELHSC 150 0.146 52 18.74 1.664 8.16% S01-15 ELHSC 15 0.037 48 18.72 1.682 8.247o S01-16 ELST 15 0.022 16 18.72 1.684 8.25% Totals 0.828 1 634 Notes: Vire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S4A3 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts Gauge 22 feet 14 Per 1000 3.07 Vire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 1.268 amps Spare Current Capacity 20% End of Line Voltage 19.08 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S4A3-1 ELST 15 0.022 22 20.23 0.171 0.847* S4A3-2 ELFHS 110 0.164 21 20.07 0.332 1.63% S4A3-3 ELFHN 0.098 34 19.84 0.558 2.73% S4A3-4 ELFHN 0.098 10 19.78 0.618 3.03% S4A3-5 ELFHS 110 0.164 65 19.43 0.972 4.76% S4A3-6 ELFHS 110 0.164 10 19.38 1.016 4.98% S4A3-7 ELST 15 0.022 22 19.31 1.092 5.35% S4A3-8 ELST 15 0.022 22 19.24 1.164 5.71 % S4A3-9 ELFHS 110 0.164 26 19.15 1.246 6.11 % S4A3-10 ELFHS 110 0.164 25 19.10 1.300 6.37% S03-11 ELFHS 110 0.164 10 19.09 1.311 6.43% S4A3-12 ELST 15 0.022 29 19.08 1.315 6.45% Totals 1.268 1 296 Notes: Vire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S4A4 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts Gauge 82 feet 14 Per 1000 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 1.078 amps Spare Current Capacity 20% End of Line Voltage 19.09 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S4A4-1 ELFHN 0.098 0.098 0.098 82 24 16 19.86 19.71 19.63 0.543 0.687 0.774 2.66% 3.37% 3.79% S4A4-2 ELFHN S4A4-3 ELFHN S4A4-4 ELFHN 0.098 30 19.48 0.918 4.50% S4A4-5 ELFHN 0.098 18 19.41 0.994 4.87% S4A4-6 ELFHN 0.098 34 19.28 1.117 5.47% S4A4-7 ELFHN 0.098 10 19.25 1.147 5.62% S4A4-8 ELFHN ELFHN ELFHN ELFHN 0.098 34 19.17 1.229 6.02% S4A4-9 0.098 18 19.14 1.261 6.18% S4A4-10 0.098 35 19.10 1.303 6.39% S4A4-11 0.098 10 19.09 1.309 6.42% Totals 1.078 1 311 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Plan set for Smoke Control only. WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.corr WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 R ES U BM ITTA L 3/20/2023 R ES U BMITTAL 5/1 /2023 RESUBMITTAL Sheet Title FIRE ALARM CALC1,bPJAWNS May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA3,002 0 2023, WASHINGTON ALARM Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S4B1 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 164 volts feet Gauge Per 1000 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 1.078 amps Spare Current Capacity 20% End of Line Voltage 18.61 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S461-1 ELFHN 0.098 164 19.31 1.086 5.32% S461-2 ELFHN 0.098 23 19.18 1.224 6.00% S461-3 ELFHN 0.098 10 19.12 1.278 6.26% S461-4 ELFHN 0.098 26 19.00 1.403 6.88% S461-5 ELFHN 0.098 24 18.90 1.504 7.37% S461-6 ELFHN 0.098 16 18.84 1.562 7.66% S461-7 ELFHN 0.098 30 18.75 1.652 8.10% S461-8 ELFHN 0.098 19 18.70 1.698 8.32% S461-9 ELFHN 0.098 31 18.65 1.754 8.60% S461-10 ELFHN 0.098 22 18.62 1.780 8.73% S461-11 ELFHN 0.098 18 18.61 1.791 8.78% Totals 1.078 383 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number IS482 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 155 volts feet Gauge 14 Per 1000 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.882 amps Spare Current Capacity 20% End of Line Voltage 19.14 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S4B2-1 ELFHN 0.098 155 10 30 10 19.56 19.51 19.39 19.35 0.839 0.888 1.014 1.050 4.11% 4.35% 4.97% 5.15% S462-2 ELFHN 0.098 S462-3 ELFHN 0.098 S462-4 ELFHN 0.098 S462-5 ELFHN 0.098 28 19.27 1.134 5.56% S462-6 ELFHN 0.098 16 19.23 1.173 5.75% S462-7 ELFHN 0.098 30 19.17 1.227 6.01 % S462-8 ELFHN 0.098 17 19.15 1.247 6.11 % S462-9 ELFHN 0.098 24 19.14 1.262 6.19% Totals 1 0.882 320 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S463 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 110 volts Gauge feet 14 Per 1000 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.784 amps Spare Current Capacity 207. End of Line Voltage 19.56 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S463-1 ELFHN 0.098 0.098 110 10 1 19.87 0.530 2.60% S463-2 ELFHN 19.83 0.572 2.80% S463-3 ELFHN 0.098 29 19.72 0.676 3.32% S463-4 ELFHN 0.098 10 19.69 0.706 3.46% S463-5 ELFHN 0.098 29 19.62 0.776 3.80% S463-6 ELFHN 0.098 10 19.61 0.794 3.89% S463-7 ELFHN ELFHN 0.098 0.098 29 19.57 0.829 4.06% S463-8 10 19.56 0.835 4.09% Totals 0.784 1 237 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S5A1 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 45 volts Gauge Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.828 amps Spare Current Capacity 20% End of Line Voltage 18.72 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S5A1-1 ELSTC 15 0.022 45 20.17 0.229 1.12% S5A1-2 ELST 30 0.030 30 20.02 0.377 1.85% S5A1-3 ELST 15 0.022 22 19.92 0.482 2.36% S5A1-4 ELHSC 15 0.037 25 19.80 0.598 2.93% S5A1-5 ELHSC 177 0.208 52 19.57 0.827 4.05% S5A1-6 ELHSC 15 0.037 52 19.41 0.989 4.85% S5A1-7 ELST 75 0.060 44 19.28 1.117 5.47% S5A1-8 ELHSC 15 0.037 26 19.22 1.183 5.80% S5A1-9 ELST 15 0.022 38 19.13 1.270 6.23% S5A1-10 ELHSC 15 0.037 32 19.06 1.339 6.57% S5A1-11 ELHSC 15 0.037 48 18.97 1.433 7.02% S5A1-12 ELHSC 15 0.037 52 18.88 1.522 7.46% S5A1-13 ELHSC 15 0.037 52 18.80 1.599 7.84% S5A1-14 ELHSC 150 0.146 52 18.74 1.664 8.16% S5A1-15 ELHSC 15 0.037 48 18.72 1.682 8.24% S5A1-16 ELST 15 1 0.0221 16 18.72 1.684 8.25% Totals 0.828 1 634 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S5A3 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 22 volts Gau a Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.784 amps Spare Current Capacity 20% End of Line Voltage 19.81 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S5A3-1 ELFHN 0.098 22 20.29 0.106 0.52% S5A3-2 ELFHN 0.098 21 20.21 0.194 0.95% S5A3-3 ELFHN 0.098 34 20.08 0.317 1.55% S5A3-4 ELFHN 0.098 10 20.05 0.347 1.70% S5A3-5 ELFHN 0.098 65 19.90 0.504 2.47% S5A3-6 ELFHN 0.098 29 19.84 0.556 2.73% S5A3-7 ELFHN 0.098 25 19.81 0.586 2.87% S5A3-8 ELFHN 0.098 10 19.81 0.592 2.90% Totals 0.784 1 216 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S5A4 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 82 volts Gauge Per 1000 feet 1 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 1.078 amps Spare Current Capacity 20% End of Line Voltage 19.09 volts Notification Appliance Manufacturer Wheelock Circuit is within limits J Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S5A4-1 ELFHN 0.0981 0.098 82 24 19.86 19.71 0.5431 2.66% S5A4-2 ELFHN 0.687 3.37% S5A4-3 ELFHN 0.098 16 19.63 0.774 3.79% S5A4-4 ELFHN 0.098 30 19.48 0.918 4.50% S5A4-5 ELFHN 0.098 18 19.41 0.994 4.87% S5A4-6 ELFHN 0.098 34 19.28 1.117 5.47% S5A4-7 ELFHN 0.098 10 19.25 1.147 5.62% S5A4-8 ELFHN 0.098 34 19.17 1.229 6.02% S5A4-9 ELFHN 0.098 18 19.14 1.261 6.18% S5A4-10 ELFHN 0.098 35 19.10 1.303 6.39% S5A4-11 ELFHN 0.098 10 19.09 1.309 6.42% Totals 1.078 311 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S561 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 164 volts Gauge feet 14 Per 1000 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 1.078 amps Spare Current Capacity 20% End of Line Voltage 18.61 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S5B1-1 ELFHN 0.098 164 19.31 1.086 5.32% S581-2 ELFHN 0.098 23 19.18 1.224 6.00% S581-3 ELFHN 0.098 10 19.12 1.278 6.26% S581-4 ELFHN 0.098 26 19.00 1.403 6.88% S5B1-5 ELFHN 0.098 24 18.90 1.504 7.37% S5B1-6 ELFHN 0.098 16 18.84 1.562 7.66% S5B1-7 ELFHN 0.098 30 18.75 1.652 8.10% S5B1-8 ELFHN 0.098 0.098 19 31 18.70 18.65 1.698 1.754 8.32% 8.60% S5B1-9 ELFHN S5B1-10 ELFHN ELFHN 0.098 22 18.621 1.780 8.73% S561-11 0.098 18 18.611 1.791 8.78% Totals 1.078 1 383 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name ANTHOLOGY OF EDMONDS Circuit Number S562 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 155 volts Gau a Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.882 amps Spare Current Capacity 20% End of Line Voltage 19.14 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S562-1 ELFHN 0.098 155 19.56 0.839 4.11% S562-2 ELFHN 0.098 0.098 10 30 19.51 19.39 0.888 1.014 4.35% 4.97% S562-3 ELFHN S562-4 ELFHN 0.098 0.098 10 28 19.35 19.27 1.050 1.134 5.15% 5.56% S562-5 ELFHN S562-6 I ELFHN 0.098 16 19.23 1.173 5.75% S5B2-7 ELFHN 0.098 30 19.17 1.227 6.01 % S5B2-8 ELFHN 0.098 0.098 17 24 19.15 19.14 1.247 1.262 6.11 % 6.19% S562-9 ELFHN Totals 0.882 320 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name ANTHOLOGY OF EDMONDS Circuit Number S563 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 110 volts Go u a Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.784 amps Spare Current Capacity 20% End of Line Voltage 19.56 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S5B3-1 ELFHN 0.098 0.098 110 10 19.87 0.530 2.60% S5B3-2 ELFHN 19.83 0.572 2.80% S5B3-3 ELFHN 0.098 29 19.72 0.676 3.32% S5B3-4 ELFHN 0.098 10 19.69 0.706 3.46% S563-5 ELFHN 0.098 29 19.62 0.776 3.80% S563-6 ELFHN 0.098 10 19.61 0.794 3.89% S563-7 ELFHN 0.098 29 19.57 0.829 4.06% S583-8 ELFHN 0.098 10 19.56 0.835 4.09% Totals 0.784 1 237 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/9/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S6A1 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage 16.0 volts Gauge Per 1000 Distance from source to 1st device 23 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.581 amps Spare Current Capacity 20% End of Line Voltage 19.07 volts Notification Appliance Manufacturer 1 Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S6A1-1 ELSTC 15 0.0221 23 20.32 40 20.18 0.082 0.40% S6A1-2 ELSTC 15 0.022 0.219 1.08% S6A1-3 ELSTC 15 0.022 50 20.02 0.384 1.88% S6A1-4 ELST 15 0.022 23 19.94 0.457 2.247. S6A1-5 ELHSC 15 0.037 19 19.89 0.514 2.52% S6A1-6 ELHSC 15 0.037 55 19.73 0.668 3.28% S6A1-7 ELST 15 0.022 46 19.61 0.787 3.86% S6A1-8 ELHSC 15 0.037 26 19.55 0.850 4.17% S6A1-9 ELST 15 0.022 33 19.48 0.923 4.52% S6A1-10 ELST 15 0.022 33 19.41 0.992 4.86% S6A1-11 ELHSC 15 0.037 27 19.36 1.044 5.12% S6A1-12 ELHSC 15 0.037 48 19.27 1.126 5.52% S6A1-13 ELHSC 15 0.037 0.037 52 52 19.20 19.13 1.203 1.269 5.90% 6.22% S6A1-14 ELHSC 15 S6A1-15 ELHSC 150 0.146 0.022 52 48 19.08 19.07 1.323 1.329 6.48% 6.51 % S6A1-16 ELST 15 Totals 0.581 1 627 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC 73-inflo Point NAL; voltage Drop Ualculation Project Name ANTHOLOGY OF EDMONDS Circuit Number S6A2 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage 16.0 volts Gauge Per 1000 Distance from source to 1st device 47 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.743 amps Spare Current Capacity 20% End of Line Voltage 19.80 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S6A2-1 ELHS 110 0.109 47 20.19 0.214 1.05% S6A2-2 ELHSC 75 0.077 37 20.04 0.358 1.76% S6A2-3 ELHS 75 0.077 63 19.83 0.574 2.81 % S6A2-4 ASWP-24MCWH 185 0.480 10 19.80 0.603 2.96% Totals 0.743 157 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S6A3 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 22 volts Gauge Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 1.268 amps Spare Current Capacity 20% End of Line Voltage 19.08 volts Notification Appliance Manufacturer Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S6A3-1 ELST 15 0.022 0.164 22 21 20.23 20.07 0.171 0.84% S6A3-2 ELFHS 110 0.332 1.63% S6A3-3 ELFHN 0.098 34 19.84 0.558 2.73% S6A3-4 ELFHN 0.098 10 19.78 0.618 3.03% S6A3-5 ELFHS 110 0.164 65 19.43 0.972 4.76% S6A3-6 ELFHS 110 0.164 10 19.38 1.016 4.98% S6A3-7 ELST 15 0.022 22 19.31 1.092 5.35% S6A3-8 ELST 15 0.022 22 19.24 1.164 5.71 % S6A3-9 ELFHS 110 0.164 26 19.15 1.246 6.11 % S6A3-10 ELFHS 110 0.164 25 19.10 1.300 6.37% S6A3-11 ELFHS 110 0.164 10 19.091 1.311 6.43% S6A3-121 ELST 15 0.022 29 19.081 1.315 6.45% Totals 1.268 296 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number S6A4 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 106 volts Gauge Per 1000 feet 1 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.686 amps Spare Current Capacity 20% End of Line Voltage 19.66 volts Notification Appliance Manufacturer 1 Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S6A4-1 ELFHN 0.0981 0.098 106 18 19.95 19.89 0.446 2.19% S6A4-2 ELFHN 0.511 2.51 % S6A4-3 ELFHN 0.098 35 19.78 0.617 3.02% S6A4-4 ELFHN 0.098 10 19.76 0.641 3.147. S6A4-5 ELFHN 0.098 36 19.69 0.706 3.46% S6A4-6 ELFHN 0.098 23 19.67 0.733 3.60% S6A4-7 ELFHN 0.098 10 19.661 0.740 3.63% Totals 0.686 1 238 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number IS681 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts Gauge 199 feet 14 Per 1000 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.784 amps Spare Current Capacity 20% End of Line Voltage 19.05 volts Notification Appliance Manufacturer 1 Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S661-1 ELFHN 0.0981 199 19.44 0.958 4.70% S6131-2 ELFHN 0.098 0.098 24 16 19.34 19.28 1.059 1.117 5.19% 5.47% S6131-3 ELFHN S6131-4 ELFHN 0.098 30 19.19 1.207 5.92% S6131-5 ELFHN 0.098 19 19.15 1.253 6.14% S6131-6 ELFHN 0.098 31 19.09 1.309 6.42% S6131-7 ELFHN ELFHN 0.098 22 19.06 1.335 6.55% S661-8 0.098 18 1 U5 1.346 6.60% Totals 0.784 359 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number IS682 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts Gauge 155 feet 14 Per 1000 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.882 amps Spare Current Capacity 20% End of Line Voltage 19.14 volts Notification Appliance Manufacturer 1 Wheelock Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S6132-1 ELFHN 0.098 0.098 155 10 19.56 19.51 0.839 0.888 4.11% 4.35% S6B2-2 ELFHN S6132-3 ELFHN 0.098 0.098 0.098 0.098 30 10 28 16 19.39 19.35 19.27 19.23 1.014 1.050 1.134 1.173 4.97% 5.15% 5.56% 5.75% S6132-4 ELFHN S662-5 ELFHN S6132-6 ELFHN ELFHN ELFHN I ELFHN S6132-7 0.098 30 19.17 1.227 6.01 % S6132-8 0.098 17 19.15 1.247 6.11 % S662-9 0.098 24 19.14 1.262 6.19% Totals 0.882 1 320 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Point to Point NAC Voltage Drop Calculation 2/8/2023 Project Name JANTHOLOGY OF EDMONDS Circuit Number IS683 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 volts Gauge Per 1000 110 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 2.50 amps Total Circuit Current 0.784 amps Spare Current Capacity 20% End of Line Voltage 19.56 volts Notification Appliance Manufacturer 1 Wheelock Circuit is within limits I Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop S6133-1 ELFHN 0.098 0.098 110 10 19.87 19.83 0.530 0.572 2.60% 2.80% S6133-2 ELFHN S6133-3 ELFHN 0.098 29 19.72 0.676 3.32% S6133-4 ELFHN 0.098 10 19.69 0.706 3.46% S6133-5 ELFHN 0.098 29 19.62 0.776 3.80% S6B3-6 ELFHN 0.098 0.098 10 29 19.61 19.57 0.794 0.829 3.89% 4.06% S6133-7 ELFHN ELFHN S663-8 0.098 10 19.56 0.835 4.09% Totals 0.784 1 237 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). Plan set for Smoke Control only. WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.corr WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 R ES U BM ITTA L 3/20/2023 R ES U BMITTAL 5/1 /2023 RESUBMITTAL Sheet Title FIRE ALARM CALC1,bPJAWNS May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA3003 0 2023, WASHINGTON ALARM 1 2 3 4 5 6 7 8 9 10 12 13 A-77 BML C D E FD3 S1A6 G H J K 77. L PROJECT NORTH FIRE ALARM/TWC SYSTEM: PARKING LEVEL PLAN 1 SCALE: 1 /8" = 1' Plan set for Smoke Control only. BOILER 12'-5 14'-4 23'-3 27'-3 13'-8 9'-5 1 /2" 1 /2" 6'-2" 13'-0" 18'-6" 1 /2" 28'_g" 1 /2" 3/4» 3/4" 23,_7„ FA & WC CIRCUITS HOM RUN TO HEAD ENDS IN RISER 1 2" EMT ALL TWC CONDUIT RUNS TW1=16GA 4C FPLR, WHITE JACKET 3 4» EMT TYP ALL FA CONDUIT RUNS TW2=CAT5, PLEASE DON'T USE BLUE OR WHITE S1A5=(2) 14GA THHN TW1 O S1A6=(2) 14GA THHN � O 0 0 O 0 0 0 0 0 0 MAINT. I '`• ' D3 0008 STOR. .' S1A6 0007 7 S1 A5-5 S1A5-1 cM S1 A5 177CD 30CD 27 -6" CM TWO HASH MARKS � r� D3 ALL NOTIFICATION DEVICES, INDICATE DOUBLE THE � WALL OR CEILING 4S DEEP BOX. REQUIRE NO RING CONDUCTORS FOR THIS WIRE DESIGNATION S1A6 S1 5-2 S1 A5-3 S1 A5-4 '. S1 A5 S1 A5 S1 A5 ''� cM cM cM a ?. cV I 34' 8'- 0" 34' TWO WAY COMM &FIR ALARM CONDUITS DON INTERSECT T N „I � � TW1 �� �� V STIBULE 0006 DESIGNATION NUMB S S R D3 A5 A6 S S1A6-8 D3 15CD D3-004 ENTER SHAFT AND PROVIDE BOX -LOCATE HEAT DETECTOR(S) W/IN 24" OF SPRINKLER HEAD (FIELD VERIFY LOCATION O '' � o \ N D3 J IDENTIFIER SUBJECT TO CHANGE UPON FULL ENGINEERI G O _ M TER CALL D3 i PUSH BUTTON MUST BEAT S1 17 5-6 CD S1A6-1 D3-001 30CD H D3 S1 A6 S1A6-2 LA U N D O S1A6-3 0004 30CD 3 1 A6 °M S1 S1A6-6 S1A6-7 15CD 30CD s J D3 D3-003 D3 3 6 +48" A.F.F. � I \ ' 1 S1A6-4 D3 A6 15CD ELECTRICAL � WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.co WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue 8. Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 R ES U BM ITTA L 3/20/2023 R ES U BMITTAL 5/ 1 /2023 RESU BMITTAL Sheet Title FIRE ALARM/ TWC S1� DRAWIFIA�a 3 DEVELOPMENT SERVICES DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA4000 0 2023, WASHINGTON ALARM 1 2 3 4 5 6D 7 8 9 10 12 12'-5 14'-4 23'-3 27'-3 13'-8 9'-5 1 /2" 1 /2- 6'-2" 13'-0" 18'-6" 1 /2„ 28'-6" 1 /2„ 3/4„ 3/4' 23'-7„ 71 IC) 1 O I0 17 �P 3/4" - aa� N � SP o F D4 4-008 S1A3 S1A4 4-007 D4 N T Sl UN PS1A O ERUN �:TL T -1 Z PAINTE� lei_ — DED IN SLAB ED JACKET S1 — 14GA THHN i =-41 D5 D6 D7 D8 D9 D10 D11 D12 S1A2 00 v ATA-4, S1 A MERUN T ISER , S1 A ISO I ROO I D4 a a S1A4 i m_ 2 2 A3 S aM aM AIM v v P v Lr AB D4 Sl A3 S1 A4 S1 3 4" EMT CONDUIT I D4A1 S1A1-1 cm GR AT ROOM 1001 00 S1A1 S1A1-10 M110CD BI TRO 1 02 o ® 0 �D4 S1A1 ® S1 Al D4 S1A1-2 75CD �-M g�A1 Fc MAIL 0 1 A 1003 Y 4 15fD4 - SIAI S1A1- C RD CM 110CC 1 22 30CD D4 Sl Al Al D4 SAL S MG TORA TORA 1007A 1007B EWSTmSlAl-l1 15CD 1 1 S1A2-1 DINING 1007 5 6 9 , S1A2-11 110CD CM FQ 4-020 1D c S1 A2 D4 S1A2-10 30CD �' 0 005 006 CON R EMBEDDED INS 4-004 3 4" EM D4=16GA 3-1 DATA-2 ERUN FACP 3 4" D4=1 EMT, CONDUI C FPLR, RED JACKET 1A3=(2) 14GA T 1A4=(2) 14GA T RUN EMBEDDED I HN HN SLAB ACKET P 17 D4 CDIN 3 4" E U EMBEDDED 110CD S1A2 �C 4M16GA I" EMT, CONDU T FPLR, REDI 3=() 14G 4=( ) 1413 U E BEDDE ACKE THH THH IN SL H B 1D4GA THHN 1 D4=16G 2C FPLR, RED ❑ LR, RE JAC ETI BEVERAGE 4-019 10 D4 KITCH S1 A2 S1A4 � EF ' D4 A0 RR 1006 4 0 I ' O EN'S R S1C 1 1005 cM 15CD , 1 10 0 oc 1 �022 � -02 FC FAMILY ROOM N � - D S oM 30 D4 1008 I I I PAINT, T P ORDISCO 1 o2oA _5 T T 12 H F91 8 SlA2 S1A2- cM 15CD ❑ S1 A2 o ` 0 cm30CD4 2 RATE FT S1 A2 CV 3 D4 S1A1 ELEV. NAITING ® CM 4 D4 "C S1 Z 3-2 USINESS OFF E ADMIN CDaI S1A = C30CD (n `L_ D4 S1A1 0 ELEV — Tw ELEV — 1 OM CALL STATIONS M G R 1027 ® 0 10 2 TO LEVEL 2, 4.02 17 S1A4 CD SlAl R 1021 CM cM O D 10� 1 slum S1A1 75CD c S1A1-6 15CD ,�, FC 4 016 S1A D4 1 B 1 23 1A1-8 - RR 1019A 1A1 E P Y CD 7 LOU 1019 S1 15 1c14 D S Al (TOTAL 6) S1Al-15 15CD RECEIVING D4 1 1017 0 1 1 A2--- ORRQ 15 D 1016 S1A2-8 75CD M COLLECTION 1030 -1 TO L 2, SEE 4.03 -0 FO SHT 1 o I N N CD SASH 1015 1A1 D4 I I I 2 � DATA-2 TO/FROM P1, SEE FA4.00 DATA 2 SEE F EXEC DIR. 1025 No Slope DN SALES MG 1024 1018 Q Z MOP 3NK Z o D LE I ° ® MoNo Bus j STAIR —' I UP P D2 S 1 Z o1 PD 0: ROOMAND LEVEL THE WEST ST 2 SLAB. RWELL SHALL BE LOCATED IN THE S1A3-3 177CD D4 S1 A3 S1 A4 S 1 N A3-4 17CD D4 S1 A3 S1 A4 2 ROOM LE D4 S1 A4 TN BETWEEN THE MAIN ELECTRICAL AND THEEASTSTAIRWELL SHALL BE LOCATED IN T EL 2 SLAB. dE I I I I I I P D4 S1 A4 0 D N 0 0 P S 1 P A3-5 7CD o 10 N S1A4-1 MECHAN 5 S1A4 2 S1A1 S 48tNERATOR 1031 1032 1 q D S 4-030 0 0 NORTH FIRE ALARM: LEVEL 1 PLAN SCALE: 1 /8" = 1' Plan set for Smoke Control only. WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.cory WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 RESUBMITTAL 3/20/2023 R ES U BMITTAL 5/1 /2023 RESUBMITTAL Sheet Title FIRE ALARM/ TWC SWIM O 3 DRAWIi�Y DEVELOPMENT SERVICES DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA4,001 0 2023, WASHINGTON ALARM 1 2 3 4 5 6 T 8 9 10 12 13 WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.cory WA Lic: WASHIA1282C LJ L B L� J�> I Project Title I L 11 L4 ANTHOLOGY OF EDMONDS , �] Q I 21200 72ND AVE W C EDMONDS, WA 98026 �F D Project Numbers 21836-1 Issue & Revision Dates El 2/9/2023 RO-INITIAL DESIGN E 2/22/2023 RESUBMITTAL 3/20/2023 RESUBMITTAL 5/1 /2023 RESUBMITTAL1-1 . 11 [_� Ii i. . 4 F El Grl r H MEER _,Q, 5 21 J K Sheet Title FIRE ALARM/ L TWC SWEM DRAWIi�� O 3 DEVELOPMENT SERVICES DEPARTMENT M NORTH F IRE ALARM: LEVEL 2 PLAN Prepared By Nicet Review 1 SCALE: 1 /8" - 1' B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number Plan set for Smoke ControlFA4*02 only. 0 2023, WASHINGTON ALARM 12'-5 5/8» 14'-4 1 /2" 6'-2" 13'-0" 18'-6" 23'-3 1 �2» 28'-6" 27'-3 1 /2» 13'-8 3/4» 9'-5 3/4" 23'-7" S2Aal S2A4-1 O S2A4-7 IL—C3 ❑ 218 H S2B1 S2B1 H O RUN S2 11 S10CD 5- cD�L—C1 TYPE S2A5-2 � 216 110CD S2A5 S A5 IL—B5 214 S2A4 IL—B1 212 H S2A4 S2A4-9 H H S2A4-6 IL—B6 210 IL—B1 208 M. H S2A4 2A4 S2A4-3 S2A4 H IL � H 206 S B SZB1 P B S 1-2 WASHINGTON ALARM P: 360.733.133 1420 King St, Ste 1 2 3 4 5 6 7 8 9 10 12 13 Bellingham, WA, 9822 www.washingtonalarm.co WA Lic: WASHIA1282C r L] L A B10 Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W C EDMONDS, WA 98026 13 D Project Numbers 21836-1 Issue 8� Revision Dates 2/9/2023 RO-INITIAL DESIGN E 2/22/2023 RESUBMITTAL 3/20/2023 RESUBMITTAL Ll 5/1 /2023 RESUBMITTALUN LLVL&LI F rQ G H J K Sheet Title F1 Ell FIRE ALARM/ El El F-1 L TWC SW DRAWIi�Y O 3 DEVELOPMENT SERVICES DEPARTMENT M NORTH F IRE ALARM: LEVEL 3 PLAN Prepared By Nicet Review 1 SCALE: 1 /8" - 1' B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number Plan set for Smoke ControlFA4*03 only. ® 2023, WASHINGTON ALARM 12'-5 14'-4 23'-3 27'-3 13'-8 9'-5 5�8» 1 �2„ 6'-2" 13'-0" 18'-6" 1 �2„ 2g'-6" 1 �2„ 3�4„ 3�4„ 23'-7„ CLR IL—C3 � IL—Cl IL—B5 IL—B1 6 IL—B1 318 316 314 312 �3—io:E S3AaiH S3A4-1 S3A4-7 S3B1 S3B1-4 H H H S3A4-6 "3A4 S3A4-3 S3A4 S H H B1 2 " IL—C3 S3B1 ❑ H S 1-5 S3B1- H 361-1 S3 1 HOM UN S3A4 S3A4 S3A4 � " 306 S361 S3B1 BP 3B H H S 53A4-9 ❑ S3A4-5 361 u S3A4-8 c � S3A4-4 ❑� ❑ � S3B1-6 " ° S3A4 rn `''� �IL o o o o �%v ° S3B1 � 0 15CD S3A1 177CD S3A1 1.4 H S3A4-1 S3A1 15CD S3A1 S3A4 cM 6-008 cM 6-007 6-005 6-004 cM1 D S3 OMERUN �j � � SP 3100 SP p SP ' BP A cfl U p6 SP p6 SP 6-00 361 ° S3A1-7 � 15CD STOR. ❑ � S3 3005 o 0 Qa Ds S3A1-2 S3 S3B1-8 " s EIE 30CD 3A1 ❑ O� � ❑� ELEV. T TWC 30�® ER SUPPLY, SEE FA4.01 15CD ❑ 1:1 ° S3A3-8 F"A. I L— B 1 ❑ 6-006 S3A3-7 " J A N 320 S3B1 -010 D6 03 Ds O I L— 1 � s P TW1 ao S3A6- I L— C 4 " S3A6- I L— B 7 30 0 \ S3 �TlV�O6""3A6-1HOMERU3A115 S3A6 S3A6 S3A6 S3A6 " H 6-001 LH S3A6 S3A6-2 S3A6 3P53A T 2 S A6-6 6-002 S3A3 IL—A2 SP ELEV O ERUNT�L�� 1 E D6 s 6-003 6-oil I L— B 2 + MA TER 1 2 3 4 6 9 10 12 13 5 7 8 WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.cory WA Lic: WASHIA1282C A Lij —1 416 Project Title ANTHOLOGY OF F7 r==1 17. 6 EDMONDS 21200 72ND AVE W C EDMONDS, WA 98026 p Project Numbers 21836-1 El 1:1 t� Issue 8� Revision Dates 2/9/2023 RO-INITIAL DESIGN E 2/22/2023 RESUBMITTAL 3/20/2023 RESUBMITTAL 5/1 /2023 RESUBMITTALAl F G H J K Sheet Title FIRE ALARM/ L TWC SW DRAWIi�� O 3 DEVELOPMENT SERVICES DEPARTMENT M NORTH F IRE ALARM: LEVEL 4 PLAN Prepared By Nicet Review 1 SCALE: 1 /8" - 1' B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number Plan set for Smoke ControlFA4*04 only. ® 2023, WASHINGTON ALARM 190'-4 12'-5 '— ,— 5�g„ ,— '— '- 5�8„ 1 /2„ 6,-2" 13'-0" 18'-6" 1 /2„ 2g'-6" 1/2') 3/4» 3/4>, 23'-7„ IL—B5 414 S4A4-11 H H S4A4-1 IL—B1 412 IL—B6 410 A4_� I L— B 1 418 S ❑ " S4B1 S4B1-4 S H H S4B1- B1-2 IL—C1 S4B1-1 �� S461 " S4B1 BPS4g OM UN S4A4 " S4A4 S4A4-9 H H S4A4-6 ❑ "4A4 H S4A4 S4A4-5 S4A4-3 " S4A4 IL—C3 S " 406 " 1-5 S4B1 4B1 o S4B1 o u H S4A4-8 ° c S4A4-4 � S4A1 0 15CD S4A1 15CD S4A1 1.4 H S4A4-1 15CD S4A4 S4A1 cM 7-004 cM1 4 OMERUN N I 7_008 CM CM 7-005 �j T7700 P D SBA P D7 P D7 461 ° S4A1-7 El 15CD STOR. 4005 ❑ � ° a 4 ° 54A1-2 S4 N � co 54A3-12 30CD 15CD 3 S4B1-8 " 4A1 L-1t4A ❑ ❑ ❑� ELEV. WAi3rlN TO TWC 4000 POWER SUPPLY, SEE FA4.01 1111 15CD El ° S4A3-11 110CD L— B 1 42o S4B1 10 ❑ 7-006 D7 TW1 J A N 4003 D7 S4A3-10 110CD � Q I L— C 5 1 2 3 4 5 6 7 8 9 10 12 13 0 9 0 0 WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.corr WA Lic: WASHIA1282C Lj L Lj _1 A/�j�i 11_j j 71 14 B Project Title ANTHOLOGY OF EDMONDS (0 cXj 21200 72ND AVE W C EDMONDS, WA 98026ppoi PM I IF Project Numbers 21836-1 L:j j �j ILL]. Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN E 2/22/2023 RESUBMITTAL 3/20/2023 RESUBMITTAL Pi 5/1 /2023 RESUBMITTAL If] IL F LLJ G H J K Sheet Title FIRE ALARM/ L TWC SW DRAWIi�Y O 3 DEVELOPMENT SERVICES DEPARTMENT M NORTH F IRE ALARM: LEVEL 5 PLAN Prepared By Nicet Review 1 SCALE: 1 /8" - 1' B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number Plan set for Smoke ControlFA4.05 only. ® 2023, WASHINGTON ALARM 12'-5 14'-4 23'-3 27'-3 13'-8 9'-5 5/8„ 1 /2„ 6,-2" 13'-0" 18'-6" 1 /2,� Zg'-6" 1/2') 3�4» 3�4» 23'-7„ IL—Cl IL—B2 IL—B1 IL—B6 I —B1 516 514 S5Aal S5A4-1 512 510 S5A4-7 —508 L— C3 518 ❑ "S S5B1 S5B1-4 H S H " S5B1- B1 2 H 5B1-1 S5 S5B1 S5B1 BP 1 HOM 5B UN S5A4 S5A4 S5A4-9 S5A4-6 ❑ S5A4 S5A4-5 5A4 S5A4-3 " S5A4 IL—C3 " S 1-5 5B1 S5B1 S5B1-6 " o S5B1 o u H S5A4-8 `--' �IL o �%v c � o S5A4-4 ° ° ❑ S5A4 O� � 6' � S5A1 0 15CD S5A1 15CD S5A1 1.3 H S5A4-1 15CD S5A1 S5A4 °A1 8-008 8-005 8-004 cM1 D 5 OMERUN N I 8 00 D5 P D P B P A co D5 P 561 ° S5A1-7 � 15CD STOR. ❑ 5005 ° a 4 ° S5A1-2 30CD S5 in 1 S5B1-8 " 5A1 U ❑ ELEV. WAI��I�P+��N TO TWC 5000 SEE FA4 OPLY 5004 S5A3-8 FIA L— B 1 El 8-006 J A N S5A3-7 " 520 S5B1 -010 �0,' 15C 6 S 8-Oil O S5A6 A6-6 H " S5A6- S5A6-4 S5A6 513 " H5A6-1 �5A6 �/IERU S5A6 S5A6 S5A6-2 D5 TW1 T 2 ELEV — ELEV — 1 MA TER CALL 15CD 1 TA. 5A1 5A1 03 D5 -D8 �, 8-001 i � S P 8-002 E D5 S 8-003 2- OUR _ � I L— 5 50 S5A3 "S5A3-6 00 p \ N S5A6- H � L— A 2 522 BPS5 x ❑ S5B1-9 H ° � _B6 D11 NORTH FIRE ALARM: LEVEL 6 PLAN SCALE: 1 /8" = 1' NORTH =TAI L (I Plan set for Smoke Control only. WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.cory WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 R ES U BMITTAL 3/20/2023 R ES U BMITTAL 5/1 /2023 RESUBMITTAL Sheet Title FIRE ALARM/ TWC SWIM O 3 DRAWIi�Y DEVELOPMENT SERVICES DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA4.06 0 2023, WASHINGTON ALARM NORTH FIRE ALARM: ROOF PLAN SCALE: 1 /8" = 1' Plan set for Smoke Control only. WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.cory WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 R ES U BMITTAL 3/20/2023 R ES U BMITTAL 5/1 /2023 RESUBMITTAL Sheet Title FIRE ALARM/ TWC SWIM O 3 DRAWIi�Y DEVELOPMENT SERVICES DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA4*07 0 2023, WASHINGTON ALARM STAIR - 1 ELEVATOR STAIR - 2 PRESS. FAN PRESS. FAN PRESS. FAN — — — TLTT- U — — — AUTO � ---AUTO ---� I I I I I 1 T OFF ON I I OFF ON I I OFF ON 5I I I I I I I I I I I I I I I I I I I I I I 1 I qD I I FAULT OFF ON I I FAULT OFF ON I I FAULT OFF ON I L_====____:� L_=========J L====::___� FIRE FIGHTER'S SMOKE CONTROL PANEL WO POWER ON SYSTEM NORMAL ® ELEV LOBBY SMOKE ® STAIR SMOKE ® OTHER SMOKE ® WATER FLOW ® HEAT DETECTOR ® MANUAL STATION SYSTEM FAULT DUCT DETECTOR SPRINKLER SUPERVISORY POWER DISCONNECT DISCHARGE DAMPER I 1 OPEN I ® 1 j CLOSED j I 1 j FAULT j 0 LAMP TEST (0 LAMP TEST Plan set for Smoke Control only. WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.co WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 RESUBMITTAL 3/20/2023 RESUBMITTAL 5/ 1 /2023 RESUBMITTAL Sheet Title FIRE FIGHTER'S SMOKERESUB 3 2023 C O N T MONDS DEVELOPMENT SERVICES PANEL DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA5.00 0 2023, WASHINGTON ALARM TWO-WAY COMMUNICATION SYSTEM SCOPE OF WORK S1 S2 PUSH FOR HELP r o-s s. r. a. i t LOCATION FLOOR PERSONS ABLE TO USE THE EXIT STAIRWAY DO SO AS SOON AS POSSIBLE, UNLESS THEY ARE ASSISTING OTHERS. AFTER ACTIVATING THE TWO—WAY EMERGENCY COMMUNICATION SYSTEM, WAIT HERE FOR ASSISTANCE. EMERGENCY COMMUNICATION r*.a s. ro.i. so%i r i rs* i° TWO-WAY COMMUNICATION SIGNAGE SCHEMATIC: NOT TO SCALE CABLE TYPES: RATH SYSTEMS Source Circuit Circuit Type Circuit Abbr Wiring Style Symbol Type Description Gauge RATH Power Indicating Z Class B Fire Alarm 18/2 SOL JKT FPLR 1 M RL RED #18 RATH S 22 AWG 2 Pair Bare Copper, Overall Shielded #22 Emergency Communication Plenum RATH RP700094 OR EQUAL 2500-21OFM$ Two -Way Class B Two -Way System 11 RATH Power T 18 AWG 2 CONDUCTOR FPLP, RED #18 $ TWO-WAY IN -BUILDING WIRED EMERGENCY COMMUNICATION SYSTEMS THAT ARE INSTALLED WHERE THE BUILDING HAS LESS THAN 2-HOUR FIRE -RATED CONSTRUCTION SHALL HAVE A PATHWAY SURVIVABILITY OF LEVEL 1,2, OR 3. NFPA 72 (2016) 24.3.14.7. ROOF TV o EMERGENCY PHONE 1T LEVEL 1s • Iola. EMERGENCY PHONE 1T LEVEL 1s EMERGENCY PHONE LEVEL4 1T 1S O EMERGENCY PHONE 1T LEVEL3 1S o EMERGENCY PHONE LEVEL2 1T Fire alarm cabling and terminations others ,_ PLY LOW VOLTAGE POWERSUPPLY / 2500-PWR24U 8 /Addressable/ /Fire Alarm 2Palr-Twisted 24-22 AWG Ao j Module Cabling run per floor PowE.� P /(Provided by others)/ Dedicated analog telephone line (POTS) or 1 Pair, 18 AWG cabling. VOIP interface device Homerun each call station. • • SMARTRESCUE BASE STATION 50/eOFh LEVEL 1 1s O EMERGENCY PHONE LEVEL 2 EMERGENCY COMMUNICATIONS RISER DIAGRAM SCHEMATIC: NOT TO SCALE THE SCOPE OF THIS PROJECT IS TO PROVIDE AN EMERGENCY TWO-WAY COMMUNICATION SYSTEM FOR THE ELEVATOR LOBBIES OF A 5 STORY OFFICE BUILDING. THE PROJECT CONSISTS OF THE FOLLOWING: • MASTER TWO-WAY COMMUNICATION SYSTEM LOCATED IN VESTIBULE 101. • SIGNAGE WILL BE PROVIDED FOR OCCUPANT INSTRUCTION AND DIRECTIONS ON EACH LEVEL. • CALL STATIONS PROVIDED IN THE ELEVATOR LOBBY PER LEVEL (ON LEVELS 2-5). TWO-WAY COMMUNICATION SYSTEM INSTALLATION NOTES INSTALLATION NOTES: 1. ALL WIRING AND CABLING ASSOCIATED WITH THE TWO—WAY COMMUNICATION SYSTEM SHALL BE INSTALLED IN 2HR FIRE RATED ENCLOSURE OR PATHWAY. 2. ARCHITECT TO PROVIDE THE APPROPRIATE SIGNAGE AT EACH TWO—WAY COMMUNICATION CALL STATION AND AT THE MASTER CALL CENTER. 3. THE MAXIMUM DISTANCE BETWEEN EACH OF THE CALL STATIONS AND THE MASTER CALL CENTER CAN NOT EXCEED 325 FEET. 4. MOUNT CALL CENTER AT NO MORE THAN 48" FROM FINISHED FLOOR. 5. CONNECT POTS TELEPHONE LINE TO MASTER CONTROLLER 6. ALL 120VAC CIRCUITS SHALL BE ON EMERGENCY GENERATOR POWER MEMBRANE PENETRATIONS. MEMBRANE PENETRATIONS SHALL COMPLY WITH SECTION 713.3.1. WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE A FIRE —RESISTANCE RATING, RECESSED FIXTURES SHALL BE INSTALLED SUCH THAT THE REQUIRED FIRE —RESISTANCE WILL NOT BE REDUCED. EXCEPTIONS: 1. MEMBRANE PENETRATIONS OF MAXIMUM 2—HOUR FIRE —RESISTANCE —RATED WALLS AND PARTITIONS BY STEEL ELECTRICAL BOXES THAT DO NOT EXCEED 16 SQUARE INCHES (0.0103 M`2) IN AREA, PROVIDED THE AGGREGATE AREA OF THE OPENINGS THROUGH THE MEMBRANE DOES NOT EXCEED 100 SQUARE INCHES (0.0645 M-2) IN ANY 100 SQUARE FEET (9.29 M^2) OF WALL AREA. THE ANNULAR SPACE BETWEEN THE WALL MEMBRANE AND THE BOX SHALL NOT EXCEED 1 /8 INCH (3.1 MM). SUCH BOXES ON OPPOSITE SIDES OF THE WALL OR PARTITION SHALL BE SEPARATED BY ONE OF THE FOLLOWING: 1.1. BY A HORIZONTAL DISTANCE OF NOT LESS THAN 24 INCHES (610 MM) WHERE THE WALL OR PARTITION IS CONSTRUCTED WITH INDIVIDUAL NONCOMMUNICATING STUD CAVITIES; 1.2. BY A HORIZONTAL DISTANCE OF NOT LESS THAN THE DEPTH OF THE WALL CAVITY WHERE THE WALL CAVITY IS FILLED WITH CELLULOSE LOOSE -FILL, ROCKWOOL OR SLAG MINERAL WOOL INSULATION; 1.3. BY SOLID FIREBLOCKING IN ACCORDANCE WITH SECTION 717.2.1; 1.4. BY PROTECTING BOTH OUTLET BOXES WITH LISTED PUTTY PADS; OR 1.5. BY OTHER LISTED MATERIALS AND METHODS. = x o m J Z = J J U TWO-WAY COMMUNICATION 2 g U z Q OPERATIONS Ckf W N J W O g C..)o MATRIX U Z w 0 � Q Z N x O m x O m Q M UU _J J J U J J U In J O Q O W U Q Q � W J W C) Q 1­__U Q U M Q Q Q Q Q Q O ¢ J U U U U U U (D TWO—WAY COMM. INPUT Q Q 0 N Q Q CD .� Z RING UP TO 5 TIMES f RING UP TO 10 TIMES • CALL FROM CALL BOX # ! CALL BOX HAS BEEN RECEIVED • i RECEIVED CALL FROM COMMAND CENTER CALL ON HOLD ! ! ANNUNCIATE AT COMMAND CENTER SOLID RED LIGHT • TROUBLE i MULTIPLE CALLS ! i PAUSED ALL OTHER CALL(S) OF THESEM PPHUN B�JI [O1 , PRESS RED LIGHT � Plan set for Smoke Control only. WASHINGTON ALARM P: 360.733.133 1420 King St, Ste Bellingham, WA, 9822 www.washingtonalarm.corr WA Lic: WASHIA1282C Project Title ANTHOLOGY OF EDMONDS 21200 72ND AVE W EDMONDS, WA 98026 Project Numbers 21836-1 Issue & Revision Dates 2/9/2023 RO-INITIAL DESIGN 2/22/2023 R ES U BM ITTA L 3/20/2023 R ES U BMITTAL 5/ l /2023 RESU BMITTAL Sheet Title TWO—WAY COMNZESUB �'ay 23 2023 D ETA I L CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Prepared By Nicet Review B. Haws Brady B. Haws 138751 Expires 5/1/25 Sheet Number FA6000 0 2023, WASHINGTON ALARM