Loading...
REVIEWED RESUB1 FIR2023-0030+Life_Safety_Report+5.23.2023_8.26.51_AM+3562510RESUB May 23 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT REVIEWED united BUILDING & ENGINEERING SERVICES LLC FIR2023-0030 ANTHOLOGY AT EDMONDS SMOKE CONTROL REPORT BY CITY OF EDMONDS PRODUCED BY UNITED BUILDING AND ENGINEERING SERIVCES, LLC 1400 1121h Avenue SE, Suite 100 Bellevue, WA 98004 DATED April 1, 2023 united b 1. Introduction and Project Description The proposed project is a mid -rise apartment building located in Edmonds, Washington. The project consists of Type I -A and V-A construction. Five levels of Type V-A construction will be utilized as provided by Washington State Building Code Section 504.4.1. This project is not classified as a high rise as no occupiable floor is 75 feet or move above the average grade plane elevation. This project will contain stair and elevator pressurization. The project has been designed in accordance with IBC Chapter 7 for fire walls, fire barriers and partitions including exit stairs, corridors, exit passageways, mechanical shafts, etc. Structural members for the support of fire resistance -rated assemblies will be rated to the same degree as the assembly supported. In accordance with IBC Chapter 7, all openings in fire rated separation assemblies will be protected with approved opening protection to provide a rating compatible with the function of the element being penetrated. All means of egress will comply with the provisions of IBC Chapter 10 including applicable amendments by Edmonds. Final / full egress design is by the architect. Please reference the full building permit drawings for full information. We understand that means of egress sizing was calculated in accordance with IBC Section 1005.3.1 (no exceptions taken; is sized at 0.2 inches). With this understanding, emergency voice/alarm communication system (IFC907.2.2.2) is required for this project. To gain the fifth floor of Type V-A construction, the project will be utilizing the 2018 Washington State Building Code Amendment 504.4.1. The 2018 Washington State Building Code Amendment 504.4.1 states the following — "504.4.1 Stair enclosure pressurization increase. For Group R1 and R2 occupancies in buildings of Type VA construction equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1, the maximum number of stories permitted in Section 504.2 may be increased by one provided the interior exit stairways and ramps are pressurized in accordance with Section 909. Legally required standby power shall be provided for buildings constructed in compliance with this section and be connected to stairway shaft pressurization equipment, elevators and lifts used for accessible means of egress, hoistway pressurization equipment (if provided) and other life safety equipment as determined by the authority having jurisdiction. For the purposes of this section, legally required standby power shall comply with 2017 NEC Section 701.12, options (A), (8), (C), (D), (F), or (G) or subsequent revised section number(s)." All pertinent items as conveyed in this 2018 Washington State Building Code Amendment will be adhered to for this project. This report is the "Smoke Control Report" required by the City of Edmonds. This report is intended to describe, in conceptual terms, the scope of the proposed smoke control systems for the project, including United Building and Engineering Services, LLC 2 1 P a g e 1400 1121h Ave SE, Suite 100 Bellevue, WA 98004 united the applicable code sections, the design approach, goals of the system, smoke zones and general testing required of the proposed smoke control system. This report will document and communicate the overall approach to smoke management for the project. Smoke management, as described in this report, refers to the active and passive systems within the building that work together in such a manner so as to limit the migration of smoke from the zone of fire origin to surrounding areas within the building. As such, the proposed approach intends that occupants within the stairwells, and on other non -fire floors of the building, will not be exposed to harmful concentrations of smoke. This will be accomplished by showing compliance with the criteria for shaft pressurization and passive barriers as required by the Code. The design approach is not to perform a tenability study of the building. The purpose of the report is to provide a code analysis for the required smoke control system in the building. The work was performed by UNITED in accordance with the §909 of the 2018 International Building Code (IBC) and NFPA 92, Standard for Smoke Control Systems, 2021 Edition. The subsequent design of code compliant architectural/electrical/mechanical/fire alarm/sprinkler components sufficient to meet UNITED design is the responsibility of that architect/engineer/designer of record. The smoke control system assumes other life safety systems are maintained available and operational. The system design assumes as a minimum that the automatic sprinklers and fire detection/alarm systems will function as designed and that the fire resistive construction will be maintained in the building. Proper periodic inspection, testing, and maintenance of these systems is required per the appropriate codes and standards. For future tracking, revisions are indicated by underscored text to denote new wording (new wording) and strike- through text to denote deleted wording (deleted- • ^��' ^^). United Building and Engineering Services, LLC 3 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 Revision Histo Revision Changes Made Revised by Revised on 0 Smoke Control Report Bob Long 4/1/2023 This report may not be transmitted or distributed to any parties without the written approval of United Building and Engineering Services, LLC. At this time, this report is only transmitted to AMA Architects, Project Team and the City of Edmonds. All pertinent design information has been coordinated with the responsible design entity. Written By United Building and Engineering Services, LLC 1400 112th Ave SE, Suite 100 Bellevue, WA 98004 United Building and Engineering Services, LLC 4 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 unitod Applicable Codes The Anthology at Edmonds Apartment project will be located within the City of Edmonds, Washington where the following codes are currently enforced by the City of Edmonds. • 2018 ICC International Building Code (IBC) with Washington and Edmonds amendments 0 2018 ICC International Fire Code (IFC) with Washington and Edmonds amendments 0 2018 ICC International Mechanical Code (I MC) with Washington and Edmonds amendments • 2018 Uniform Plumbing Code (IPC) with Washington and Edmonds amendments • 2020 NFPA 70, National Electrical Code (NEC) with Washington and Edmonds amendments • 2018 Washington State Energy Code • 2019 NFPA 72, National Fire Alarm and Signaling Code • 2019 NFPA 80, Standard for Fire Doors and Other Opening Protectives • 2019 NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives • 2018 NFPA 3, Standard for Commissioning of Fire Protection and Life Safety Systems • 2018 NFPA 4, Standard for Integrated Fire Protection and Life Safety System Testing • 2019 NFPA 13, Standard for the Installation of Sprinkler Systems • 2019 NFPA 14, Standard for Installation of Standpipe and Hose Systems • 2019 ASME A17.1, Safety Code for Elevators and Escalators • Bellevue Fire Department Smoke Control Guidelines - Edmonds follows Bellevue smoke control standards - SMOKE CONTROL 02.14.2018.pdf (bellevuewa.gov) In addition to these code requirements, this analysis has been based, in part, on NFPA 92, Standard for Smoke Control Systems (2021 edition), the SFPE Handbook of Smoke Control Engineering (2012); and the SFPE Handbook of Fire Protection Engineers, 4th edition. The appropriate code section references for specific requirements are indicated in this analysis. Unless otherwise indicated, all code references contained herein are from the 2018 ICC International Building Code, as amended. This analysis does not include provisions from the Americans with Disabilities Act (ADA), ANSI A117.1, or any state or local design standard for accessibility. However, it is the project's intent to comply with all applicable accessibility requirements. United Building and Engineering Services, LLC 5 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united 11. Fire Protection and Life Safety Concepts The Anthology at Edmonds Apartment project will provide a level of fire protection and life safety for the occupants in accordance with an overall concept established for the project. The following goals serve as the basis for this overall fire protection and life safety concept: 1. Automatically detect all fire conditions. 2. Inform the building's occupants and the Fire Department of the condition. 3. Contain and control a developing fire condition and the smoke being produced until final resolution by responding emergency forces. 4. To provide for the safe evacuation of occupants. To achieve these goals, the following package of fire protection and life safety features will be provided: • Type I -A construction. • Type V-A construction. • 3-hour horizontal separation between Type I -A and V-A construction. • Complete automatic sprinkler protection throughout all areas. • Fire department standpipe systems. • Pressurized exit stairways and pressurized elevator shaft. • Smoke detection in select locations. • Occupant notification in accordance with IBC 907.2.9.1. • Fire department radio repeater and antenna system. • Automatic recall and emergency operation of elevators. • Standby and emergency power systems. • Electrical supervision and off -site alarm monitoring of sprinkler and fire alarm systems. • Portable fire extinguishers. This report is intended to present the smoke control approach for this project, as prescribed by the IBC. Specific design information regarding safety systems and associated features prescribed by the IBC will be prepared by others, including: United Building and Engineering Services, LLC 6 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united • Automatic fire sprinkler systems • Standpipe systems • Fire detection and alarm system • Fire-fighter's smoke control panel • In Building Radio Coverage • Portable fire extinguishers The following sections of this analysis provide additional details of the operation and design features of the fire and life safety systems to be provided for the proposed The Anthology at Edmonds Apartment project. A. Construction Classification The project will have Type I -A and V-A construction types; with a 3-hour horizontal assembly separating the two construction classifications in accordance with IBC § 510.2. Type I -A construction requires those levels to be designed with noncombustible structural elements throughout. The primary structural frame will be provided with a 3-hour fire -resistance rating and all floor construction and secondary members will have a fire resistance rating of 2- hours. Type V-A construction allows those levels to be constructed of protected wood framing. The primary structural frame will be provided with a 1-hour fire -resistance rating and all floor and roof construction and secondary members will have a fire resistance rating of 1-hour. In accordance with IBC 504.4.1 (WA), for R-2 occupancies of Type V-A construction and equipped throughout with an automatic sprinkler system, the maximum number of stories permitted in IBC § 504.2 may be increased by one provided the interior exit stairways are pressurized in accordance with IBC 909.20 and 909.11. As such, a total of five (5) stories are permitted above the 3-hour horizontal separation. All code required fire separations will be constructed of noncombustible materials and protected to provide the required fire -resistance rating as follows: • Sleeping unit separation: 1-hour fire partitions (IBC 708.1(1)) • Corridors: 1-hour fire partitions (IBC Table 1020.1) • Exit stairways: 2-hour fire barriers (IBC 1023.2) • Elevator hoistways: 2-hour fire barriers (IBC 713.4) Smoke barriers have been designed as required by Code by the architect and are fully reflected in the building permit plans. B. Automatic Sprinkler Systems All areas of The Anthology at Edmonds Apartment project, including the parking garage level, will be protected with hydraulically designed, electrically supervised and off -site monitored automatic sprinkler systems designed in accordance with NFPA 13-2019, Installation of Sprinkler Systems. Quick -response or residential automatic sprinklers will be installed in accordance with IBC 420.4. United Building and Engineering Services, LLC 7 1 P a g e 1400 1121h Ave SE, Suite 100 Bellevue, WA 98004 united In order to provide for annunciation of sprinkler system operation, electrically supervised control valves and water flow switches will be provided at the riser connection on each floor. Activation of any flow switch will initiate the appropriate voice/alarm messages and pressurized stairway and elevator sequences while simultaneously transmitting an alarm signal to the fire alarm annunciation and control panel and to the Fire Department via the off -site monitoring service. In the event that a sprinkler control valve is shut, a supervisory signal is transmitted to the fire alarm annunciation and control panel and to the off -site monitoring service. All of the alarm and supervisory circuitry itself will be electrically supervised so that any fault in the wiring results in a trouble signal being transmitted to the fire alarm annunciation and control panel(s) and to the off -site alarm monitoring service. The automatic fire sprinkler systems protecting the development will provide a proven level of performance in the areas of life safety, fire suppression, structural protection, and reduction of smoke development. C. Fire Department Standpipe System All building areas, including the parking garage level, will be provided with Class I standpipe systems designed in accordance with NFPA 14-2019, Installation of Standpipe and Hose Systems. A 2-1/2-inch standpipe hose connection will be provided in the following areas: • At each intermediate landing in every exit stairway • At the highest landing of one stairway, which will provide roof access. The hose connection will be located adjacent to the stair opening on the roof. • Where otherwise necessary such that all floor areas are within 200-foot travel distance to a protected hose connection. Such hose connections will be located in vertical exit enclosures or protected locations that are accessed through protected enclosures. • On the roof such that all portions of the roof are within 200 feet of hose travel distance from a standpipe hose connection. Hose connections will be at least 10 feet from the roof edge, skylight, light well, or similar openings unless protected by a 42-inch high guardrail or equivalent. All roof hose connections will be arranged to be operable without entering the building. Hose lines and nozzles for use by the building's occupants are not required by code and will not be provided. Each standpipe hose connection will be equipped with a cap and chain. The standpipe systems serving the project will be supplied via risers which also serve as the automatic sprinkler system risers. Shut-off valves and water -flow devices will be provided on each floor at the sprinkler system connection to each standpipe. The closing of any control valve will transmit a trouble signal to the fire alarm annunciation and control panel and the off -site monitoring service. United Building and Engineering Services, LLC 8 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united D. Fire Protection Water Supply We do not anticipate a fire pump being required (this work is by others). Further, since the building will not be classified as a high-rise building, a secondary water supply is not required and will not be provided. E. Portable Fire Extinguishers As an additional aid for control of incipient fire conditions, portable fire extinguishers of the appropriate size and type will be located throughout the project in accordance with IBC 906.1 and the requirements of NFPA 10-2019, Portable Fire Extinguishers. Portable fire extinguishers will be provided throughout the project (maximum floor area of 3,000 square feet per unit of A and maximum travel distance to extinguisher of 75 feet). F. Smoke and Heat Detection In addition to the automatic detection and annunciation provided by the automatic sprinkler system waterflow switches, smoke and heat detectors will be provided in the following areas: • Duct smoke detectors will be installed at each connection to a vertical duct or riser serving two or more stories from a return air duct or plenum of an air-conditioning system. (IMC 603.2.3) • Duct smoke detectors will be installed in the return air system where multiple air handling systems share common supply or return air ducts or plenums with a combined design capacity greater than 2,000 cfm. (IMC 603.2.2) • A smoke detector at the fire alarm annunciation and control panel and any auxiliary power supply(s). (IBC 907.4.1) • A smoke detector in each elevator machine room and in each elevator lobby in order to provide for elevator emergency return and firefighter's service. (IBC 3003.2) • A smoke detector within 5 feet of the entrance to each pressurized exit stairway on every floor. • Each sleeping unit will be provided with a single -station smoke alarm in every sleeping room and in the corridor(s) or area(s) leading to the sleeping rooms. Multiple smoke alarms with a sleeping unit will be interconnected. (IBC 907.2.11.2) • A fixed temperature heat detector will be located near each sprinkler located in an elevator hoistway or machine room. The heat detectors are designed to open a shunt trip device to disconnect main line power supply to the elevator equipment before sprinkler activation. (IBC 3005.5 & NFPA 72 6.16.4) Activation of sprinkler waterflow devices, heat detectors and smoke detectors, other than duct smoke detectors and single -station detectors, will initiate an alarm signal. Activation of a duct smoke detector will initiate a supervisory signal in accordance with IBC 907.3.1. G. Smoke Alarms Single station or multiple -station smoke alarms will be required in each residential dwelling unit in the following locations: United Building and Engineering Services, LLC 9 1 P a g e 1400 1121h Ave SE, Suite 100 Bellevue, WA 98004 united • On the ceiling or wall outside each sleeping area in the vicinity of bedrooms • In each room used for sleeping purposes These smoke alarms are not smoke control initiating devices. H. Fire Alarm Notification Appliances The following fire alarm notification appliances will be provided: • Audible - Speakers will be clearly audible throughout the building (including exterior areas of the building such as the pool deck and residential balconies) or on the floor of actuation with the capability of sounding a general alarm throughout the building by manual means from the fire command center • Visual - Visible notification appliances (i.e., strobes) will be required throughout the public areas of the building, designed and installed in accordance with NFPA 72. All dwelling units will be provided with the capability to support visible alarm notification appliances in accordance with Chapter 10 of ICC A117.1. Such capability will be permitted to include the potential for future interconnection of the building fire alarm system with the unit smoke alarms, replacement of audible appliances with combination audible/visible appliances, or future extension of the existing wiring from the unit smoke alarm locations to required locations for visible appliances. I. Through -Penetration Protection Penetrations into or through fire barriers, smoke barrier walls, fire partitions, floor, floor/ceiling assemblies, or the ceiling membrane of a roof/ceiling assembly, will be protected with an approved through - penetration firestop system in accordance with IBC Section 714. Fire and/or smoke dampers will be provided in duct and air -transfer openings as described in the following table. Fire dampers will have a 1%-hour rating and UL 555 Listed. Smoke dampers will have a Class II leakage rating and an elevated temperature rating of not less than 250°F and UL555S. Where both a fire and a smoke damper are required, the use of a combination fire/smoke damper is permitted. Combination fire and smoke dampers will be provided with an approved means of access, not affecting the integrity of the fire resistance -rated assemblies. Access shall be large enough to permit inspection and maintenance of the damper. Access doors shall have a permanent label with letters not less the % inch in height identifying FIRE/SMOKE DAMPER, SMOKE DAMPER, or FIRE DAMPER. Each damper shall have a separate permanent label with a distinct ID that corresponds with mechanical damper schedule and floor plans. In accordance with Washington State Building Code, Section 717.3.3.2 1, smoke dampers and combination fire/smoke dampers shall actuate upon initiation of a listed smoke detector or detectors in one of the following applicable methods: Smoke damper installed within a duct: Where a smoke damper is installed within a duct, a smoke detector shall be installed inside the duct or outside the duct with sampling tubes protruding into the duct. The detector or tubes within the duct shall be within 5 feet (1524 mm) of the damper. Air outlets and inlets shall not be located between the detector or tubes and the damper. The detector shall be listed for the air velocity, temperature, and humidity anticipated at the point where it is installed. Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum United Building and Engineering Services, LLC 10 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 unitod velocity to operate • Smoke damper installed above a smoke barrier door: Where a smoke damper is installed above smoke barrier doors in a smoke barrier, a spot -type detector shall be installed on either side of the smoke barrier door opening. The detector shall be listed for releasing service if used for direct interface with the damper • Smoke damper installed in air transfer opening: Where a smoke damper is installed within an air transfer opening in a wall, a spot -type detector shall be installed within 5 feet (1524 mm) horizontally of the damper. The detector shall be listed for releasing service if used for direct interface with the damper • Smoke damper installed in corridor wall or ceiling: Where a smoke damper is installed in a corridor wall or ceiling, the damper shall be permitted to be controlled by a smoke detection system installed in the corridor • Complete smoke detector coverage: Where a smoke detection system is installed in all areas served by the duct in which the damper will be located, the smoke dampers shall be permitted to be controlled by the smoke detection system United Building and Engineering Services, LLC 111 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 - . united SmokeFire Damper RequiredDamperYIN)Required Fire Barriers Yes No 717.5.2 Exceptions: 1. Fire damper not required when penetration is part of a listed assembly tested in accordance with ASTM E 119 or UL 263. 2. Fire damper not required when duct is part of a smoke control system and use of damper would interfere with operation of smoke control system. 3. Fire damper not required when duct is part of HVAC system, penetration is in 1-hour maximum fire barrier, building is sprinklered, duct is 26 gauges minimum, and is continuous from the air -handling appliance to air outlet and inlet terminals. Shaft Enclosures' Yes Yes 717.5.3 Exceptions: 1. Fire damper not required where steel exhausts extend at least 22 inches vertically in exhaust shafts and airflow is continuous'. 2. Fire damper not required where penetration is tested as part of listed assembly. 3. Fire damper and smoke damper not required where duct is part of smoke control system and damper would interfere with smoke control system operation. 4. Fire damper and smoke damper not required where penetration is in a parking garage shaft separated from other building shafts by 2-hour construction. 5. Smoke damper is not required in Group B occupancies protected by an NFPA 13 sprinkler system where the kitchen, clothes dryer, bathroom, and toilet room exhaust extend at least 22 inches vertically, are at least 0.019 wall thickness, and fans are installed on the upper terminus. Fans must be provided with emergency power systems in accordance with IBC maintain continuous upward airflow to the outside. Fire Partitions Yes No 717.5.4 Exceptions: 1. Fire damper not required in corridor walls in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.31.1 or 903.3.1.2 and the duct is protected as a through penetration in accordance with Section 714. 2. Fire damper not required where the duct is 100 square inches maximum, constructed of 0.0217-inch minimum thickness steel, does not have openings that connect the corridor with adjacent spaces, is installed above ceiling, does not terminate at fire -rated walls, and a 12-inch steel sleeve is provided in each duct opening that is secured on each side of the wall with ancillary space filled with mineral wool. - Note 1— Duct and air transfer openings are not permitted to penetrate the exit enclosures unless allowed by IBC Section 1022.4 J. Manual Fire Alarm Boxes Manual fire alarm boxes are not required in buildings that are equipped throughout with automatic sprinkler systems and where the occupant notification appliances will automatically activate upon sprinkler waterflow. As such, manual fire alarm boxes are not proposed to be provided. However, the applicable codes do require manual fire alarm boxes at select locations and one will be provided above the fire alarm annunciation and control panel in accordance with NFPA 72- 2019, 6.8.5.1.2. The manual fire alarm pull box is will be provided at the fire alarm panel where the fire alarm system utilizes automatic fire detectors or waterflow detection devices. This manual fire alarm box will be placed on a separate circuit which is not placed "on test" when the detection or sprinkler system is placed "on test." This manual fire alarm box will also be monitored by the supervising station. United Building and Engineering Services, LLC 12 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united K. Emergency Responder Radio Coverage An approved emergency responder radio coverage system will be provided to enhance the operation of the emergency services worker's radios in accordance with IFC 510. Typically, this type of system is designed to operate on a specific frequency programmed into all fire department radios. The radio system will be in service at all times. L. Exit Stairway Pressurization In addition to the effective means of smoke control provided by automatic sprinklers throughout The Anthology at Edmonds Apartment project, mechanical smoke -control consisting of stairway pressurization will be provided as required by IBC 504.4.1(WA). Refer to Section IV and V for a description of the proposed stairway pressurization systems. M. Elevator Pressurization Elevator pressurization will be provided in accordance with IBC Section 909.21 Refer to Section IV and V for a description of the proposed elevator pressurization systems. N. Smoke Control Wiring All smoke control wiring for power and control — regardless of voltage — shall be in raceways and 2-hour protected. Edmonds follows the Bellevue Smoke Control Guidelines with the only exception being that Edmonds does not recognize MC as a raceway as Bellevue does (Bellevue accepts this code reduction while Edmonds does not). O. Elevator Controls and Sizing Every group of elevators will have a smoke or heat detector located in each lobby on each floor level. Upon activation of a lobby or machine room smoke or heat detector, the elevator(s) served by that lobby or machine room will be recalled to the recall floor. In the event that the alarm is on the recall floor the elevators will be recalled to the alternate recall floor. Only the elevator(s) served by the affected lobby will be recalled. After returning to the designated level, the elevators will be rendered inoperable without the use of the fireman's key or until such time they are manually reset into the normal operating mode. Key operated recall switches will be provided near each elevator on each floor which permit the fire department to commandeer an elevator if necessary. Elevators and controls will be installed in accordance with the requirements of ASME A17.1-2019, Safety Code for Elevators and Escalators. In accordance with IBC 1009.2.1 and 1009.4, elevators will be provided with standby power. Standby power will be capable of manual transfer to all elevators in each bank. All elevators will automatically transfer to standby power in sequence, return to the designated level and disconnect from the standby power source. After all elevators have been returned to the designated level, at least one elevator in each bank will remain operable from the standby power source in accordance with IBC 3003.1.3. In accordance with IBC 3002.4, one elevator providing access to all floors will be of such size and United Building and Engineering Services, LLC 13 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united arrangement to accommodate an ambulance stretcher 24"x84" with not less than 5-inch radius corners, in the horizontal, open position and will be identified by the international symbol for EMS (star of life). P. Emergency and Standby Power A source of emergency and standby power will be provided for the following systems: Emergency Power • The fire alarm annunciation and control panel as well as all associated detection, supervision and notification devices. (IBC 907.6.2) • All designated emergency lighting and exit signage. (IBC 1008.3 and 1013.6.3) Emergency power will be provided by means of storage batteries in accordance with NEC 700.12(A). Standby Power • All exit stairway and elevator pressurization fans. (IBC 909.11) • Emergency responder radio system — 24 hours operation (IFC 510.4.2.3 Edmonds) • Elevators used as accessible means of egress. (IBC 1009.4 and 3003.1) Standby power will be provided in accordance with NEC Section 701.12. Option B (Generator) as approved by Edmonds and as listed per Washington State Building Code Section 504.4.1. The generator and transfer switch shall also be designed and installed in accordance with IBC Section 2702 and Bellevue Smoke Control Guidelines Section 6.7. Legally required standby power is provided for the smoke control system (as required by Washington State Building Code Section 504.4.1). Per IBC Section 2702.1.3 - Standby power systems shall automatically provide secondary power within 60 seconds after primary power is lost, unless specified otherwise in this code." Per Bellevue Smoke Control Guidelines Section 6.7 - Generator and transfer switch. The emergency generator set shall be in a separate room from the remainder of the building, the transfer switches, and from the normal power source. The rooms must feature 2-hour fire rated construction in high-rise and underground buildings, 1-hour fire rated in all other buildings. (Ref. IBC 2702.1.8, IBC 909.11, NFPA 110- 7.2.1.1). Q. Supervision To provide additional system reliability and rapid notification of the fire department, all fire protection devices are electronically supervised. The supervisory system is being designed to indicate three different signals: • Alarm • Supervisory • Trouble United Building and Engineering Services, LLC 14 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 An alarm signal is an indication that a fire or other emergency condition has been detected in the building. A supervisory signal is an indication that a required fire protection system is not in full working order such as a closed valve in the automatic sprinkler supply piping. A trouble signal is an indication that a portion of the fire protection system is not functioning properly such as problems associated with electrical wiring or devices. All signals are transmitted to the fire alarm annunciation and control panel and are supervised by the off - site alarm monitoring service. Signals from any automatic sprinkler waterflow device, smoke detector, or heat detector are considered an alarm condition by the off -site alarm monitoring service, and the fire department is immediately notified. United Building and Engineering Services, LLC 15 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united III. Smoke Control Narrative For The Anthology at Edmonds Apartment project, stair and elevator pressurization will be provided in accordance with IBC Section 909.20.5 and 909.21. CONTAM modeling will be utilized for sizing the stair and elevator pressurization fans. The general approach for smoke control for this project utilizes stair and elevator pressurization smoke control systems to help mitigate the possibility of vertical spread of smoke in the building. Each of the enclosed interior exit stairways along with the elevator shaft will be pressurized as the rational analysis for smoke control. This analysis is based on the other life safety systems being maintained, available and operational. The smoke control system assumes at minimum that the automatic sprinklers and fire detection/alarm system will function as designed and that the fire resistive construction will be maintained in the building. The intent of the stair and elevator pressurization requirements of the code is to utilize shaft pressurization systems that prevent smoke from entering the shaft. This is accomplished through the pressurization method of smoke -control which creates pressure differentials across the walls of vertical shafts on the fire floor, since infiltration through these shafts is the principle mechanism which allows smoke to move into upper floors. This will be accomplished in this project by mechanical pressurization of the exit stairways and elevator shaft. The general approach to automatic operation will include activation of the shaft pressurization fans along with the automatic closure of any protected openings which are required to close in the building. All stairwell and elevator pressurization fans are required to be equipped with a source of legally required standby power in accordance with NEC § 701.12, Option B. All stairwell and elevator pressurization fans are to be provided with variable frequency drives (VFD). All fans are required to be provided with at least 1.5 times the number of design belts with a minimum of 2. Supply inlets are required to be located to avoid the reintroduction of smoke. All pressurization fan components of the smoke control systems shall be rated for the anticipated exposure temperatures. All smoke control system power and control wiring are required to be in a 2-hour fire resistance rating (FRR) system in accordance with the IBC. The smoke control systems must be controlled by an Underwriters Laboratories (UL) UUKL listed firefighter's smoke control panel (FSCP) and (UL) UUKL listed fire alarm control panel (FACP). The stair and elevator pressurization system will be initiated upon activation of any of the following: general building alarm initiating device; manual pull station located at the FACP; any smoke/heat detection; and sprinkler waterflow within in the building. In addition, any HVAC systems supplying 2,000 CFM of air or more (or cumulative HVAC units serving the same common space supplying 2,000 CFM of air or more) will also shutdown. Finally, any activation of a smoke detector installed in the vicinity of any pressurization fan injection point shall result in the automatic shutdown of the corresponding pressurization fan. The following items are required for the smoke control system. For further information, refer to the "Smoke Control System Narrative" portion of this report. 1. A Rational Analysis, which provides the basis of design for the smoke control system is required, in accordance with 2018 IBC § 909.4. The Rational Analysis must address stack effect, temperature United Building and Engineering Services, LLC 16 1 P a g e 1400 1121h Ave SE, Suite 100 Bellevue, WA 98004 united effects of the fire, wind effects, HVAC system effects, climate, duration of operation, and the effect of open doors on the stair and elevator pressurization systems. 2. Legally Required Standby Power — The mechanical smoke control systems will be provided with legally required standby power in accordance with NEC § 701.12, Option B. 3. Protection of Smoke Control System Wiring — All wiring associated with smoke control systems, including all fire alarm component wiring utilized for activation and/or control, will be fully enclosed within continuous raceways in accordance with 2018 IBC § 909.12.1. In addition, all smoke control wiring (control and power — regardless of voltage) will be 2-hour protected. 4. Firefighter's Smoke Control Panel — A smoke control panel indicating the status and fault condition as well as manual control by emergency responders of the smoke control system will be provided. 5. Acceptance Testing — Before the mechanical equipment is approved, the system must be tested in the presence of the Building and Fire Code Official. A special inspection by a third party will be required prior to testing with the Building and Fire Code Official. The special inspector will develop a final Special Inspection Test Plan and will be an integral part of the acceptance of the smoke control systems. The smoke control system to be tested and a certificate of compliance be provided by the special inspector and responsible registered design professional certifying that the referenced property is in substantial compliance. The certificate must identify the company, designer, special inspector that performed the testing, name, date, and address of the property being tested. The following statement must be included, "I have reviewed the report and by personal knowledge and on -site observation certify that the smoke control system is in substantial compliance with the approved design documents, and to the best of my understanding complies with requirements of applicable codes as identified in the smoke control report." 6. The location of the main fire alarm control panel (FACP) and the firefighter's smoke control panel (FSCP) are located in a 2-hour rated room as approved by Edmonds. 7. The legally required standby power panel and ATS switch for the smoke control system is required to be 2-hour protected. 8. In general, smoke control power and control wiring will run horizontally in the concrete slabs (minimum 2" coverage) to gain the 2-hour rating protection. 9. Power and control wiring for each stair pressurization will run vertically in the stairwell enclosure (near the standpipe). Wiring for SPF-1 is only in the shaft for SPF-1; conversely, wiring for SPF-2 is only for SPF-2. As the stairwell enclosure is 2-hour rated construction, this will provide 2-hour rated protection for the vertical power and control wiring for the stair pressurization fans. As these electrical risers penetrate the roof, there will be only (at most) a 20-foot run -out on the roof (this will not be 2-hour protected on the roof). For the elevator pressurization fan, a 2-hour rated vertical shaft located near the elevator shaft will be coordinated with the architect for 2-hour protection of the power and control wiring to the elevator pressurization fan Active smoke control will be provided for the project by utilizing mechanical means to control smoke by creating pressure differentials across smoke zones. Each exit stair and elevator shaft will be considered a separate smoke control zone. Each stairway enclosure and elevator shaft will be separated from the remainder of the building by 2-hour fire barriers and will be mechanically pressurized to maintain the required pressure differentials. All other areas will be protected by Passive Methods such as smoke barrier construction. Passive Methods of smoke control will also be utilized for the spaces other than the pressurized exit stair and elevator shafts, as discussed in the sections that follow: • Parking Garage Levels — Each level of the parking garage is atmospherically connected. As United Building and Engineering Services, LLC 17 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 A united such the entire garage of each building will be treated as one passive smoke control zone. The garage will be separated from adjacent smoke zones by fire resistance -rated smoke barriers. Elevator Shafts— Elevator hoistways are provided. The hoistway will be of rated construction and considered as a passive zone. Residential Floors — Residential units and corridors are not required to be provided with a smoke control system and will be considered passive zones. Each residential unit will be separated from adjacent units by fire -resistance rated smoke barriers. These zones will be separated from adjacent smoke control zones by fire resistance -rated smoke barriers. Detection of smoke within a passive area or activation of sprinkler waterflow on the floor will activate the stair and elevator pressurization systems. Smoke management via passive smoke barriers will be achieved by providing effective compartmentation. According to Principles of Smoke Management by Klote and Milke — "Barriers with sufficient fire endurance to remain effective throughout afire exposure have a long history of providing protection against fire spread. In such fire compartmentation, the walls, partitions, floors, doors, and other barriers provide some level of smoke protection to spaces remote from the fire." Smoke Barriers will be tested in accordance with IBC § 909.5.2 United Building and Engineering Services, LLC 18 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united b IN. Smoke Control System Narrative A. Parking Garage Normal ventilation for the parking garage level will be provided in accordance with IBC 406.6.2 and IMC 404 by means of mechanical supply and exhaust activated by carbon monoxide detection. Manual override action of the garage ventilation is not required to be controlled via the firefighter smoke control panel. B. Exit Stairway Pressurization Systems To maintain tenable means of egress in the event of a fire, all exit stairways will be automatically pressurized in accordance with IBC 909.20.5. The stairways will be pressurized upon transmission of an alarm signal from a sprinkler waterflow switch or alarm -initiating smoke detector. Activation of a residential unit smoke detector will initiate a local alarm only and will not result in stairwell pressurization system activation. The stairways will be pressurized to a minimum of 0.10 inch of water and a maximum of 0.35 inch of water in the shaft relative to all floors, measured with all stairway doors closed under maximum anticipated stack pressures (and also door forces are not greater than 30# of door opening force). Manual controls for the stair pressurization systems will also be provided on the Firefighter's Smoke Control Panel located adjacent to the fire alarm annunciation and control panel. The stair pressurization fans will be provided with a primary and a secondary power supply. In the event of primary power failure, the stair pressurization fans will continue to be operational through the activation of the legally required standby power system. Variable frequency drives (VFDs) are to be provided on the stairwell pressurization fans to facilitate final balancing. VFD's will be mounted by the stair pressurization fans in weather proof rated enclosures. The VFD make and model are being finalized by the mechanical engineer. Should the VFDs selected rely on volatile memory, the VFDs will be provided with an uninterruptible power source (UPS). The UPS will allow for potential power surges and / or the transfer to secondary power to be absorbed by the system without corrupting the memory settings for the VFD. The VFD basis of design is an ABB ACH 580. The power and control wiring for pressurized stairways will be have 2-hour rated protection. C. Elevator Pressurization The elevator shaft will be automatically pressurized in accordance with IBC 909.20.5. The elevator shaft will be pressurized upon transmission of an alarm signal from a sprinkler waterflow switch or alarm -initiating smoke detector. Activation of a residential unit smoke detector will initiate a local alarm only and will not result in stairwell pressurization system activation. The elevator cars are only recalled on an elevator lobby smoke detector alarm. The elevator shaft will be pressurized to a minimum of 0.10 inch of water and a maximum of 0.25 inch of water in the shaft relative to the floor — except at the recall floor. Please see IBC Section 909.21.1 for all pertinent items. United Building and Engineering Services, LLC 19 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united Manual controls for the elevator pressurization system will also be provided on the Firefighter's Smoke Control Panel located adjacent to the fire alarm annunciation and control panel. The elevator pressurization fan will be provided with a primary and a secondary power supply. In the event of primary power failure, the elevator pressurization fan will continue to be operational through the activation of the legally required standby power system. Variable frequency drives (VFDs) are to be provided on the elevator pressurization fan to facilitate final balancing. VFD's will be mounted by the elevator pressurization fan in a weather proof rated enclosure. Should the VFDs selected rely on volatile memory, the VFDs will be provided with an uninterruptible power source (UPS). The UPS will allow for potential power surges and / or the transfer to secondary power to be absorbed by the system without corrupting the memory settings for the VFD. The VFD basis of design is an ABB ACH 580. The elevator pressurization fan would have (3) speeds. This for being able to properly balance the smoke control system (stair and elevator pressurization fan) for all scenarios — being primary recall, alternate recall and no -recall operations of the elevator pressurization fan. This would be accomplished by the following: • Speed 1 = Primary recall = Fire Alarm Output #1 — to VFD Input #1 = Distinct setting for VFD Fan speed for primary recall (VFD programming) — Allow balancing to balance the smoke control system to this scenario • Speed 2 = Alternate recall = Fire Alarm Output #2 — to VFD Input #2 = Distinct setting for VFD Fan speed for alternate recall (VFD programming) — Allow balancing to balance the smoke control system to this scenario Speed 3 = No recall = Fire Alarm Output #3 — to VFD Input #3 = Distinct setting for VFD Fan speed for No recall (VFD programming) — Allow balancing to balance the smoke control system to this scenario The power and control wiring for pressurized elevator shaft will be have 2-hour rated protection. D. Standby Power In accordance with IBC 909.11, all stairway and elevator pressurization systems will be provided with standby power. Standby power will be provided by means of a generator in accordance with NEC § 701.12, Option B. E. Marking and Identification of Equipment In accordance IBC 909.14 and NFPA 70 700.9, all portions of the stairway and elevator pressurization systems will be identified in the field. This includes all applicable junction boxes, control tubing, temperature control modules, relays, damper sensors, automatic door sensors and air movement sensors. All junction boxes and covers for the stairway and elevator pressurization systems (including all portions of the fire detection system which activate stairway and elevator pressurization) will be externally identifiable. The color of the markings will be orange with two grey bars. Please reference the Bellevue Smoke Control Guidelines Section 11.6 for additional details. F. Firefighter's Smoke Control Panel In accordance with IBC 909.16 and Section 9 of the Bellevue Smoke Control Guidelines, a Firefighter's Smoke Control Panel will be provided adjacent to the fire alarm annunciation and control panel for manual United Building and Engineering Services, LLC 20 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united control or override of automatic control for the stairway and elevator pressurization systems. The panel will be in accordance with IBC 909.16. All controls and indicators will be combined to control and indicate all elements of a single pressurization system as a unit, rather than controls for individual pieces of equipment and individual dampers. Each piece of equipment will be provided with status indicators on the Firefighter's Smoke Control Panel. This arrangement is permitted, with approval, by the Exceptions to IBC 909.16.2. Each control switch will activate and/or deactivate all applicable fans and will open and/or close all related dampers/doors serving the respective pressurization system. Pressurized stairways and elevator shaft will each have a single 3-position switch having settings of ON / AUTO / OFF. All dampers (at the stair and elevator pressurization fans) will be provided with OPEN / CLOSED / FAULT status indicator lights. All fans will be provided with ON / OFF / FAULT status indicator lights. All portions of the normal air handling systems and any other building systems that can adversely impact the smoke control operations will also be included in the automatic/manual overrides. When the control switches are in the CLOSED or OFF position (and also when the FSCP is switched to ON or OPEN), all dampers in the respective alarm zone typically fail closed. All manual controls will be arranged to override automatic sequences in accordance with IBC 909.16.3. The Anthology at Edmonds Apartment project pressurization systems are designed to involve an interface between the fire alarm annunciation and control panel and the Firefighter's Smoke Control Panel. All components utilized in this application have a UUKL listing under UL 864. IBC 909.12 intends that the panels used for activation and control of smoke control systems be listed under this classification. Full compliance with all applicable sections of the Bellevue Smoke Control Guidelines is required. G. Equipment and Ducts Mechanical equipment and ducts will be located outside the building or located within the shaft served by the equipment as required by IBC 909.20.6.1. Supply air for the variable frequency drive (VFD) pressurization fans will be taken directly from the outside. The intake opening for each fan will be a minimum distance of 20 feet from any air exhaust system or outlet so as to minimize the potential for introducing smoke or flame into the building, in accordance with IBC 909.10.3. Any duct system that is part of the pressurization system will be protected with the same fire- resistance rating as required for the shaft enclosure in accordance with IBC § 909.20.6.1. Ducts will be in accordance with § 909.10.2. Ducts serving pressurized shafts will not be tested in accordance with the performance criteria outlined in IBC § 909.10.2 as these ducts do not cross other smoke zones, or are essentially exterior to the building and part of the subject shaft. Any leakage from the duct into the shaft would continue to serve the subject shaft. Leakage from the pressurized shafts to the building is anticipated in accordance with IBC § 909.5. Measurement of prescribed pressure differentials between each shaft and all floors served will ensure the prescribed pressurization differentials are achieved. United Building and Engineering Services, LLC 211 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united Smoke control fan status ON/OFF/FAULT and supervision of power downstream of disconnects (i.e. presence of power downstream of all disconnects) will be provided. This will be accomplished by the provision of a contactor rated at fan voltage to provide N.O. dry contacts for power supervision. Fan differential pressure switches may also be used. Smoke control damper monitoring of fully-open/fault/fully -closed will be provided to report "damper open" and "damper closed" condition. This will be accomplished through the use of limit end -switches. All fire -smoke dampers, requiring status monitoring, will have an end -switch at both the full open and full closed positions. H. Fire Alarm System The smoke control system will be controlled by the fire alarm system that is installed in full accordance of IBC 907 and 909. The panel will be programmed to perform the weekly self -test of dedicated smoke control system elements. Any malfunction, or if the manual switches are set to off -normal position, will cause visible and audible signals at the smoke control panel which will send a trouble signal to the Central Station. Results of self -tests will be printed and maintained in the sprinkler riser room and will be accessible to inspection agencies. The smoke control panel will have the highest priority amongst the building system controls, whether or not smoke control has been initiated. All control systems must be supervised in accordance with § 907. The control system must comply with UL 864 (UUKL) and be listed as smoke control equipment. Positive confirmation of actuation, testing, manual override, and the presence of power downstream of a disconnect switches must be provided for all devices and equipment considered part of an active smoke control system. Additionally, a preprogrammed weekly test sequence must report abnormal conditions audibly, visually, and by printed report. Fans that are part of an active smoke control system must have pressure sensors, current switches, or other means of monitoring fan operation acceptable to the City of Edmonds. Dampers, if provided, must be monitored using end switches that are wired individually or in series indicating open and closed status of actual damper position. United Building and Engineering Services, LLC 22 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united V. Sequence of Operations A basic smoke control system sequence of operations is included in the Table below. The smoke control system sequence of operations involves closing fire -smoke dampers in smoke zone boundaries throughout the respective building, opening the motorized dampers and activate the stairwell and elevator pressurization fans based on a fire alarm condition in the respective building. Stair and elevator pressurization will also be initiated for a fire alarm condition anywhere in the respective building. Activation of a smoke detector installed in the vicinity of any pressurization fan air injection point will result in the automatic shutdown of said pressurization fan. a U V) LL O O ai — a, v, O a U o 0 to N +ai+ N LL LL O O Response a, a. ° 0 U Fire Alarm Initiating Device .I. o' a, o 'o Z3 a', Q w oC U Y cn Q C Q Corridor & Common Areas X X X X HVAC Detectors Stair & Elevator Pressurization Fans X I X Waterflow Switches All Areas / Levels X X X X Manual Manual Controls at FSCP Z X X X X #3 1 Protected openings include any fire doors or dampers held open by the fire alarm system. 2 Manual controls will be provided for active smoke control components. 3 Manual controls at the FSCP are annunciated as a supervisory signal Table: Smoke Control Sequence of Operations Elevator recall only occurs when the associated elevator lobby detector is activated for that specific elevator. Full central station monitoring is required for all points. The above table is a summary / general sequence of operations. United Building and Engineering Services, LLC 23 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 V1. System Commissioning and Periodic Testing All components of the smoke control system are required to be inspected and tested as part of the commissioning process. Prior to testing, a detailed test procedure is required to be submitted to Edmonds for review containing detailed checklists for all equipment. Commissioning of the building smoke control system shall be performed in accordance with IBC §909 after the system is installed and before the building is occupied. The commissioning must include the following: • All smoke control system components must be inspected to verify that the equipment is properly installed and that it is as specified in the design documents. Components that are specifically inspected include: o Fans and motors o Smoke Zone Boundary Doors o Fire/smoke dampers o Differential pressure transducers o Fire alarm control panel o Firefighter's control panel (FSCP) • The following additional inspections/tests are also required: o Ducts shall be inspected and pressure tested in accordance with SMACNA or equivalent methods. o Passive smoke barriers shall be inspected to verify theirintegrity. o Outside air inlets and outlets shall be inspected to verify that smoke is not reintroduced into the building. o Emergency power systems shall be inspected to verify that they are adequately separated from normal power systems. o All equipment items are inspected to verify that they are labeled consistent with the drawings and the firefighter's control panel. • Individual equipment components shall be individually tested to verify that they function properly. Proper function includes verifying airflow, current and voltage draw for fans and operation (open/close) for dampers and doors in smoke zone boundaries. • The performance of the entire smoke control system shall be tested. This testing must verify that the proper pressure differentials and door -opening forces are achieved. It also verifies that all appropriate fire alarm devices initiate smoke control and that the sequence of operations is in accordance with the design. The performance testing must be conducted with the pressurization systems activated in order to reflect maximum door overpressure conditions expected during actual operation. The sequence of testing must initiate the pressurization systems in order to achieve the required pressure differential across the stair and elevator doors and at each opening between smoke zones. • In order to account for the differences in construction, the initial testing of the pressurization fans should begin at the low set point on the variable speed drive. During the course of the testing, the fan capacity should be increased to achieve the specific air flows needed to obtain the required pressure differentials. The smoke control system to be tested and a certificate of compliance be provided by the special inspector and responsible registered design professional certifying that the referenced property is in substantial United Building and Engineering Services, LLC 24 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united compliance. The certificate must identify the company, designer, special inspector that performed the testing, name, date, and address of the property being tested. The following statement must be included, "I have reviewed the report and by personal knowledge and on -site observation certify that the smoke control system is in substantial compliance with the approved design documents, and to the best of my understanding complies with requirements of applicable codes as identified in the smoke control report." Upon completion of the commissioning, a complete sealed test report should be developed in accordance with IBC §909.18.8.3. Periodic testing is required to be performed semi-annually by persons thoroughly knowledgeable in the operation, testing, and maintenance of the smoke -control system in accordance with the 2018 International Fire Code (IFC) §909.20. The results of the tests shall be documented and the tests shall be conducted under standby and normal power. Operation of the correct outputs for each given input shall be verified by the periodic testing. Additionally, it is required by IBC §909.12 that the smoke control systems be controlled by an Underwriters Laboratories UUKL listed smoke control system. A UUKL listed system is required to perform a weekly self - test of the dedicated smoke control equipment including all smoke zone boundary doors, dampers, and any dedicated smoke control fans. Upon completion of the self -test, any door, fan, or damper that does not operate as required will constitute a test failure. Indication of a test failure must result in a latching trouble condition on the fire alarm control panel, and the trouble condition must be reported to the central station. The UUKL listed system shall be programmed to print a hard -copy report summarizing the results of the weekly self -test that clearly indicates whether the system passed or failed the test. United Building and Engineering Services, LLC 25 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 V11. Summary The Anthology at Edmonds Apartment project will provide a level of life safety and fire protection which meets or exceeds those levels of protection intended by the codes adopted and amended by the City of Edmonds, Washington. The following is a summarized list of the fire protection and life safety features proposed for the project. • Type I -A construction. • Type V-A construction. • 3-hour horizontal separation between Type I -A and V-A construction. • Complete automatic sprinkler protection throughout all areas. • Fire department standpipe systems. • Pressurized exit stairways and pressurized elevator shaft. • Smoke detection in select locations. • Occupant notification in accordance with IBC 907.2.9.1. • Fire department radio repeater and antenna system. • Automatic recall and emergency operation of elevators. • Standby and emergency power systems. • Electrical supervision and off -site alarm monitoring of sprinkler and fire alarm systems. • Portable fire extinguishers. This report is intended to present the smoke control approach for this project, as prescribed by the IBC. Specific design information regarding safety systems and associated features prescribed by the IBC will be prepared by others, including: • Automatic fire sprinkler systems • Standpipe systems • Fire detection and alarm system • Fire-fighter's smoke control panel • In Building Radio Coverage • Portable fire extinguishers United Building and Engineering Services, LLC 26 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united CONCLUSION This report depicts the smoke control system for The Anthology at Edmonds Apartment project. The design approach and calculations presented in this report follow the requirements of Section 909. Details of compliance are the responsibility of the Designers of Record and are shown on the Mechanical, Electrical, Fire Alarm, Sprinkler Riser Schematic and Architectural Drawings. Prepared by: UNITED BUILDING AND ENGINEERING SERVICES, LLC Timothy Mitchell, PE Senior Consultant April 1, 2023 Please address questions and correspondence to: Bob Long I Principal United Building and Engineering Services, LLC. 1400 112th Ave SE I Bellevue, WA 98004 Direct:425.591.4633 1 Mobile: 425.591.4633 Email: bob. long (a)unitedbes.com United Building and Engineering Services, LLC 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 Reviewed by: UNITED BUILDING AND ENGINEERING SERVICES, LLC Robert Long Principal April 1, 2023 271Page united APPENDIX SYSTEM IMPLEMENTATION REQUIREMENTS This section of the report is not intended to identify all requirements listed in Section 909, but is intended instead to highlight those areas of the design process where some care is required to ensure that the system design is adequately coordinated and in accordance with the requirements presented in Sections 909.10 through 909.17. All other requirements in § 909 will nevertheless apply. It is the responsibility of the Designer of Record pf that system to comply with these requirements. EQUIPMENT (909.10) Ducts, fans, and other equipment associated with the smoke control system must be separated from the remainder of the building or must be located outside. All equipment, including fans, ducts, and any balance dampers, must be suitable for their intended use and must be listed for the probable temperatures to which these components may be exposed. This temperature is permitted to be based on the sprinkler activation temperature. Proper listings for this equipment must be obtained and submitted during the Construction Phase prior to installation. Equipment shall be located so as to not expose uninvolved portions of the building to an additional fire hazard. Per 909.10.3, outside air inlets will be located a minimum distance of 20 feet from any air exhaust system or outlet, so as to minimize the potential for introducing smoke or flame into the building. Exhaust outlets shall be so located as to minimize reintroduction of smoke into the building and to limit exposure of the building or adjacent buildings to an additional fire hazard. Ducts - All ducts (including ducted shafts) must be capable of withstanding the maximum probable temperatures and pressures to which they will be exposed. Furthermore, the code requires ducts to be leak tested to 1.5 times the maximum design pressure in accordance with nationally -accepted practices. The maximum leakage during the pressure testing may not exceed five percent of the design flow rate. For this project, leakage testing will be performed on metal ductwork only, since other shafts will not be used as ducts. Fans - Supply fans serving the stairwell and elevator shafts will not have to be temperature rated, as they will never be exposed to elevated temperatures. In addition to these and other requirements in § 909.10, belt -driven fans must have 1.5 times the number of belts required for the listed design duty, with the minimum number of belts being two. Motors driving these fans must have a minimum service factor of 1.15. Calculations and manufacturer's fan curves must be obtained and submitted prior to installation. The fans will also be required to be supported and restrained by noncombustible supports attached to the structure. Supply air systems exceeding 2,000 CFM, will be provided with duct smoke detectors that will shut down the supply system, as required by code, except for supply systems that are part of the smoke control system. Duct smoke detectors shall be installed in all stairwell and elevator pressurization supply air systems, regardless of fan capacity. All duct smoke detectors are required to be supervised by the fire alarm control system. United Building and Engineering Services, LLC 28 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 Fire Dampers - Fire dampers will be provided as required by code. Fire dampers provided in openings in supply shafts will have a temperature rating of 160°F. Fire dampers provided in openings in exhaust shafts will have a temperature rating of 3507. Smoke Dampers - Smoke dampers, where installed in the supply or exhaust air systems, will operate per the smoke control sequence. Smoke Dampers in smoke barriers shall be protected with a minimum Class II, 250' F smoke damper having a UL 555S listing. Smoke damper monitoring and control requirements are summarized below: Dampers separating two passive zones: No end switches required No monitoring required by FSCP Dampers separating an active zone from a passive or active zone (discharge dampers at stair and elevator pressurization fans): • End switches required to verify "closed" position during UUKL weekly self- test. • Dampers will be monitored by the firefighter's smoke control panel (FSCP). Fault conditions will be indicated on smoke control panel for the applicable smoke zone if the damper does not close properly. • Control of individual dampers will not be provided. General control of all dampers will be provided in order to enable general shut down of air movement within the building. • Status monitored and indicated at the FSCP. • Manual control provided at the FSCP. Equipment Inlet and Outlets - Supply air shall be taken directly from an outside, uncontaminated source located a minimum distance of 20 feet from any air exhaust system or outlet so as to minimize the potential for introducing smoke or flame into the building. POWER SYSTEMS (909.11) Primary and secondary power will be required for this system as summarized in the Life Safety Features section of this report. Transfer to full emergency power must be automatic and must occur within 10 seconds of failure of primary power. The smoke control distribution power panel will be in a one -hour rated closet. Additionally, fire alarm, fire detection, and sprinkler supervisory systems cannot lose signal or must be capable of system restoration within ten seconds. United Building and Engineering Services, LLC 29 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united Elements of the smoke control system, which rely on volatile memory, must be supplied by an uninterruptible power source of sufficient duration to span a 15-minute interruption of primary power. DETECTION AND CONTROL SYSTEMS (909.12) The system will include a FSCP, per § 909.16, for manual observation and control of fans and dampers, which are a part of the smoke control system. Other building fans, not specifically mentioned as part of the smoke control system, will not be manually controllable from the smoke control panel. The smoke control system will be controlled by the fire alarm system. The panel will be programmed to perform the weekly self -test of dedicated smoke control system elements. Any malfunction, or if the manual switches are set to off -normal position, will cause visible and audible signals at the smoke control panel which will send a trouble signal to the Central Station. Results of self -tests will be printed and maintained in the sprinkler riser room and will be accessible to inspection agencies. The smoke control panel will have the highest priority amongst the building system controls, whether or not smoke control has been initiated. All control systems must be supervised in accordance with § 907. The control system must comply with UL 864 UUKL and be listed as smoke control equipment. Positive confirmation of actuation, testing, manual override, and the presence of power downstream of a disconnect switches must be provided for all devices and equipment considered part of an active smoke control system. Additionally, a preprogrammed weekly test sequence must report abnormal conditions audibly, visually, and by printed report. Fans that are part of an active smoke control system must have pressure sensors, current switches, or other means of monitoring fan operation acceptable to the City of Edmonds. Dampers, if provided, must be monitored using end switches that are wired individually or in series indicating open and closed status of actual damper position. Supervision of all active smoke control system components must be indicated at a UUKL Listed FSCP panel. All wiring, regardless of its voltage, must be fully enclosed within continuous conduits or raceways. This requirement applies to both electrical sub -systems and the fire alarm systems. All wiring serving the smoke control systems must be protected by 2-hour construction. MARKING AND IDENTIFICATION (909.14) During the construction phase, the detection and control systems are required to be clearly marked at all junctions, accesses, and terminations. This marking should be approved for its use by the Fire or Building Departments and in accordance with generally accepted practice. In addition, the Bellevue Smoke Control Guidelines Section 11.6 has additional requirements. FIREFIGHTER'S SMOKE CONTROL PANEL FSCP (909.16) The FSCP, will be located in a location as approved by Edmonds Fire Department. The FSCP will be provided per § 909.16, for manual observation and control of fans and dampers, which are a part of the smoke control system. The smoke control system will be controlled by the fire alarm system. The fire alarm system will be UUKL listed for smoke control application. The panel will be programmed to perform the weekly self -test of dedicated smoke control system elements. Any malfunction, or if the manual switches are set to off -normal position, will cause visible and audible signals at the smoke control United Building and Engineering Services, LLC 30 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united panel which will send a supervisory signal to the Central Monitoring Station. Results of self -tests will be printed and maintained in the Fire Command Room and will be accessible to inspection agencies. The FSCP will have the highest priority amongst the building system controls (except fire damper closure due to elevated temperature), whether or not smoke control has been initiated. SYSTEM RESPONSE TIME (909.17) Activation of the smoke control system must be initiated immediately after receipt of the appropriate automatic or manual activation command. The components must be activated in the sequence necessary to prevent physical damage of the equipment. The component response times should be similar to those response times listed below. The total response should not exceed 60 seconds, in accordance with standard practice. 1. Control air isolation valves - immediately. 2. Smoke damper closing - 15 seconds maximum. 3. Smoke damper opening - 15 seconds maximum. 4. Fans starting or energizing -15 seconds maximum. 5. Fans stopping or de -energizing - immediately. 6. Fan volume modulation - 30 seconds maximum. 7. Pressure control modulation - 15 seconds maximum. 8. Temperature control safety override - immediately. 9. Positive indication of system status - 15 seconds maximum. TESTING AND MAINTENANCE Prior to commissioning the smoke control system, detailed smoke control system testing scenarios should be developed by either the special inspector. The testing criteria should be reviewed by the City to ensure that the methods of testing are acceptable. TESTING PROCEDURES Three copies of a final document describing testing procedures of all active fire protection systems will be submitted to the City of Edmonds for review and comment as an electronic submittal. The preparation of the test procedures should be prepared by and coordinated through the respective Contractor and Engineer. CONTROL DIAGRAMS Three copies of the smoke management control diagrams should be submitted to the City of Edmonds prior to beginning testing of control equipment. SMOKE CONTROL SPECIAL INSPECTOR United Building and Engineering Services, LLC has been retained to perform Smoke Control Special Inspections to verify compliance with § 909.18. The smoke control system to be tested and a certificate of compliance be provided by the special inspector and responsible registered design professional certifying United Building and Engineering Services, LLC 31 1 P a g e 1400 1121h Ave SE, Suite 100 Bellevue, WA 98004 united that the referenced property is in substantial compliance. The certificate must identify the company, designer, special inspector that performed the testing, name, date, and address of the property being tested. The following statement must be included, "I have reviewed the report and by personal knowledge and on -site observation certify that the smoke control system is in substantial compliance with the approved design documents, and to the best of my understanding complies with requirements of applicable codes as identified in the smoke control report." PERIODIC OPERATION AND MAINTENANCE All active fire protection systems and devices will be regularly tested in accordance with applicable codes and standards by qualified individuals acceptable to the City of Edmonds. In accordance with § 909.12 the fire alarm/smoke control system will be programmed to automatically run a preprogrammed weekly test sequence on the smoke control system. This will include operation of the smoke control fans and dampers. Abnormal conditions will be reported audibly, visually, and by printer report. Per the Bellevue Smoke Control Guidelines —the system must be maintained in accordance with the manufacturer's instructions and 2018 IFC Sections 909.12 and 909.20.1 to 909.20.5. In addition, the Bellevue Fire Department Appendix E has additional requirements and standards. The following table provides guidance for implementation of selected aspects of Smoke Control Systems to be installed under the 2018 International Building Code, §909. The list is not intended to be a complete compilation of all requirements and resulting features. It is simply added detail about issues that are typically not well defined in smoke control system design documents and that have resulted in improper installations. United Building and Engineering Services, LLC 32 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united Code Reference Smoke Control System Feature Firefighter's Smoke Control Panel (FSCP) Configuration IBC §909.12 IBC • FACP shall be listed as smoke control equipment. — UL 864 UUKL §909.16.1 • Use of four status indicator lights (WHITE, RED, GREEN and AMBER) is specified by the 2018 IBC IBC §909.16.2 • The fire-fighter's control panel shall provide control capability over the complete smoke -control system equipment within the building asfollows: 1. ON -AUTO -OFF control over each individual piece of operating smoke control equipment that can also be controlled from other sources within the building. This includes stairway & elevator pressurization fans; and other operating equipment used or intended for smoke control purposes. 2. OPEN -AUTO -CLOSE control over individual dampers relating to smoke control and that are also controlled from other sources within the building. 3. ON -OFF or OPEN -CLOSE control over smoke control and other critical equipment associated with a fire or smoke emergency and that can only be controlled from the fire-fighter's control panel. Fire -Smoke Dampers (FSDs) IBC §717.3.2 FSDs must be Leakage Type II/250OF minimum. Detection and control system wiring IBC §909.12.1 • In addition to meeting requirements of NFPA 70, National Electric Code, all wiring, regardless of voltage, shall be fully enclosed within continuous raceways Power Systems IBC §909.11 The smoke control system shall be supplied with two sources of power. Primary power shall be the normal building power systems. Secondary power shall be from an approved standby source complying with NFPA 70, National Electric Code. The standby power source and its transfer switches shall be in a separate room from the normal power transformers and switch gear and shall be enclosed in a room constructed of not less than 1-hour fire - resistance rated fire barriers ventilated directly to and from the exterior. Power distribution from the two sources shall be by independent routes. Transfer to full standby power shall be automatic and within 60 seconds of failure of the primary power. The systems shall comply with the IBC or NFPA 70, National Electric Code. Verification IBC §909.12 The code requires methods of verification for actuation, testing, manual override, the presence of downstream power for all disconnects, and printed reports summarizing weekly preprogrammed tests accompanied by visual and audible signals if abnormal conditions exist. Air flow for pressurization fans must therefore be verified using pressure transducers listed for the intended ur ose or other approved means. Control Device Locations NFPA 72 (2010) Fire alarm control modules shall be located within 3-feet of the controlled circuit or §21.2.4 appliance. This rule applies to the following smoke control system components: • Building Management System (BMS) control unit • Fan controller (if the fan is controlled directly by the fire alarmsystem • The 3-foot rule may not apply to FSDs that fail -closed upon loss of power and have end switches to monitor their oosition. United Building and Engineering Services, LLC 33 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united Weekly Self -Test REFERENCES ASHRAE (2001), American Society for Heating Refrigeration and Air Conditioning Engineers, 2001 ASHRAE Handbook -Fundamentals, American Society for Heating Refrigeration and Air Conditioning Engineers, Atlanta, GA, 2001. Budnick, E. K. (1984), "Estimating Effectiveness of State -of -the -Art Detectors and Automatic Sprinklers on Life Safety in Residential Occupancies," NBSIR 84-2819, National Bureau of Standards, Gaithersburg, MD, January 1984. Evans, D. D., and Stroup, D. W. (1985), "Methods to Calculate the Response of Heat and Smoke Detectors Installed Below Large Unobstructed Ceilings," NBSIR 85-3167, National Bureau of Standards, Gaithersburg, M D, 1985. Geiman, J.A., and Gottuk, D.T. [2003], "Alarm Thresholds for Smoke Detector Modeling," Fire Safety Science — Proceedings of the Seventh International Symposium, 2003, pp. 197-208. Klote, J.H (2013), "Elevator Pressurization in Tall Buildings", International Journal of High -Rise Buildings, December 2013, Vol 2, No 4, pp 341-344. Klote, J. H. (1990), "Fire Experiments of Zoned Smoke Control at the Plaza Hotel in Washington, DC," ASHRAE Transactions, 92 (2), 1990, pp. 399-416. Klote, J. H., and Milke, J. A. (2002), Principles of Smoke Management, American Society for Heating Refrigeration and Air Conditioning Engineers, Atlanta, GA, 2002. Nelson, H. E. (1990), "FPETOOL: Fire Protection Engineering Tools for Hazard Evaluation," NISTIR 4380, National Institute of Standards and Technology, March 1990. Kung, Hsiang -Chang, et al. (1980), "Sprinkler Performance in Residential Fire Tests," prepared for the Federal Emergency Management Agency, United States Fire Administration 79019, Factory Mutual Research Corporation, Norwood, MA, December 1980. Tamaura, G. T. (1994), Smoke Movement and Control in High Rise Buildings, National Fire Protection Association, Quincy, MA, 1994. Walton, G. N. and Dols, Stuart (2005), "CONTAM 2.4 User Guide and Program Documentation," NISIR 7251, National Institute of Standards and Technology, November 2005. United Building and Engineering Services, LLC 34 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 unitod CONTAM MODEL RESULTS United Building and Engineering Services, LLC 35 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 Lik" qyunited �iNL �. FNGINEERINL 51 Estimates have been made for the actual leakage areas for various construction elements in the building based on the expected building construction. Final performance of the smoke control system should be evaluated in the "as built" condition during commissioning testing to ensure that the smoke control system is capable of providing the level of performance (i.e. pressure differentials and door opening forces at stair doors) suggested by this report. CONTAM Modeling or "hand calculations" can easily over -size or under- size fans due to assumptions for leakage rates. It is at least as equally important to take great care in selecting fans matched with VFD rated motors over a wide range of airflows while operating in stable fan regions. UNITED has performed computer modeling of airflow throughout the entire building using the computer model CONTAMW 3.1. Leakage values for average construction were evaluated. Additionally, the stair and elevator pressurization fans will be provided with variable frequency drives to facilitate final balancing. To clarify the meaning of "average" construction, values from Table 3.9 of the Handbook of Smoke Control Engineering are shown to indicate leakage areas per unit area for average construction. Additionally, the State of Washington has a requirement that the entire building envelope be leakage tested to confirm that the leakage rate of the building envelope does not exceed 0.25 cfm/ft2 at a pressure of 0.3 inches water gauge (2018 Washington Energy Code Section C402.4.1.2.3). These requirements further support that assumed construction for the building. Iahlr i 9: Flow Area. of AN: ll.and Floor. of( ,nui-dal Buildin;:.l %rea Ratio, Construction Element Leakage Leakage Arm per Unit Wall Area in,ift, fl'/ft' m'!m' Tight 72.10 5.0•10 5.0•10 Exterior building walls Average 2.5•10-2 1.7•10-4 1.7•10-4 (includes construdion crack and cracks around I.aosers) 5.0•10-2 3.5•10 33•104 windows and deo very Loose 1.7.10 1.2.10-3 12.10-; stairwell walls Tight 2.0.10-3 1A-10-5 1.4.10 I includes conswcuon cracks but not cracks Average 1.6.1(r2 1.1.1074 1.1•10-4 around w indows or doors) Loose 5.0.1(r2 3.5.10-4 3.5.I04 Elevator shaft walls Tight 2.6.le 1.8.1()4 1.8.1(p-4 t includes construction cracks but not cracks Average 1.2.10 8A.104 8A-lCr-4 around doors) Loose 2.6.10 1.8.10-3 1.8.10 Area Ratio' Construction Element Leakage Leakage Area per Unit Floor Area in'!ft' ft!ft m'im' Floors" Tight" 9.5•104 6.6.106 6.6.10_6 (includes censtruction cracks and gaps around Average 7.5.10 52.10' 52-10 5 penetrations) Loose" 2A-IP2 1.7.1(4 1.7.10-4 IThrdme in thu wMe arcix use wilh do Drat cquelkm. Flowarearuinsforflow ffib.wlofC- 0.65n10.3in.14,005Pe). Values R...d rmios based on preswvaeon mcwsurmnrnts m buildings by Tamura aM Nilsen 119661. Tenure and Stew t1976e: 19766: 1978) and Slow. eardon. anCheunF 119931. 'Floor Ieakaee does not-- for gaps that wn be belwern o floor end a cunein wall. Zucs canalx+laled from the ascrege fl«m lighmcss bnrcd on ranse of ughm«s of other canmrrion wmpmwnla. Future building modifications including tenant improvements may impact the performance of the smoke control system described in this report. Any substantial changes to the building should be reviewed for their potential impact on the smoke control system design. United Building and Engineering Services, LLC 36 1 P a g e 1400 1121h Ave SE, Suite 100 Bellevue, WA 98004 DESIGN CONSIDERATIONS IBC §909.4 specifies that design of smoke control systems should be based on a rational engineering analysis that must include consideration of stack effect, wind effects, and climate. Temperature effects associated with the fire and air movement caused by the building's HVAC systems must also be considered. Stack Effect Stack effect is a phenomenon which will induce an upward or downward air flow within buildings due to the temperature difference between a building's inside temperature and the outside ambient air temperature. Generally, when the ambient air temperature is colder than the building temperature, air will move upward through the building. This is commonly referred to as normal stack effect and will occur under winter conditions. When the ambient air temperature is warmer than the building temperature, air will move downward through the building. This is commonly referred to as reverse stack effect and will occur under summer conditions. The magnitude of the stack effect induced air flow is directly dependent on the magnitude of the temperature differential between the building and ambient, as well as the building's height. Examples of the stack effect are depicted in Figure 1. Note: Arrows indicate direction of air movement wi trai Pler Reverse Stack Effect Figure ]. Stack effect flows in a building. For the purposes of the analysis, the building is assumed to be at 68 'F. Climate data for the Seattle, Washington area was obtained from the SFPE Handbook of Smoke Control Engineering [SFPE, 20121. The design summer and winter conditions recommended by Tables 2.1 and 2.2 of the SFPE Handbook of Smoke Control Engineering were used in the analysis: Recommended design temperature (Winter): 24 °F Recommended design temperature (Summer): 85 °F The smoke control system was designed to satisfy the required pressure differences using static fan sizes at both the maximum and minimum ambient design temperatures. Wind The effect of wind on a building is a very complex phenomenon which is affected by building shape, United Building and Engineering Services, LLC 37 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united building height, and even other nearby buildings. Wind pressures can vary widely across each face of a building, making input of wind pressure into computer simulations difficult. Often, gross generalizations regarding wind pressures have to be made due to lack of available data. Also, the stairwells and elevator shafts are located interior to the building floor plate and would be minimally affected by wind (if any). However, the effects of 20 miles per hour (mph) wind from the southern direction (predominant direction for Seattle area) were included in the computer modeling. HVAC Systems Building HVAC systems in addition to those dedicated for smoke control purposes need to be evaluated for their contribution to smoke movement within a building. Of particular concern are those systems, which affect the pressure differentials of adjacent spaces. The parking garage ventilation fans were modeled as continuing to operate during a fire event. The HVAC systems serving the building areas were modeled as being required to shut down upon a fire alarm condition. Therefore, the ventilation system was not included in the air flow analysis. The interior environment for the computer modeling was as follows: Inside building temperature in summer and winter - 70°F Shaft summer temperature - 78°F Shaft winter temperature - 45°F Design Fire IBC §909.9 requires the design fire to be based on a rational analysis performed by a registered design professional and approved by the fire code official. A design fire, defined by a heat release rate, is used by fire protection engineers to calculate the exhaust capacities needed for atrium smoke control. The exhaust rate needed for atrium smoke control is a function of the air entrainment rate into the rising smoke plume (as well as the density of air at the temperature of the smoke layer). The air entrainment rate into the rising smoke plume is a function of the atrium height and the heat release rate of the fire. In the case of the proposed smoke control system, which is based on a pressure differential design objective, it is not the heat release rate of the fire that matters but the resulting fire compartment temperature. The minimum pressure differentials specified by code for sprinklered and non-sprinklered buildings implicitly consider the maximum compartment temperatures possible in these two different scenarios. For the same size fire (i.e. heat release rate), compartment temperatures can vary greatly depending on the geometry of the enclosure and construction materials used. The temperature of the fire compartment will dictate the buoyancy force of the hot gases. See below for an analysis of temperature effects. As a result of this analysis, the smoke control system design was not altered to accommodate for the temperature effects of a design fire. The 2018 IBC code required minimum design pressures (0.10 inches of water) used in the stairwell and elevator pressurization system design offers an additional safety factor for the design fire scenario. Temperature Effects IBC Section 909.4.2 requires that the buoyancy and expansion caused by the design fire be addressed. Both empirical and theoretical approaches may be taken in this endeavor. It is the intent of the code that the designer examines the potential impact of likely severe design fires on the particular fire protection United Building and Engineering Services, LLC 38 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 systems and passive barrier systems present in a building. Based upon the analysis, logical steps can then be taken to reduce the probability of smoke migration from the zone of fire origin to surrounding smoke zones. Empirical Data Tests conducted at the Plaza Apartments (Klote, 1990) support the notion that uncontrolled and unchecked production of hot gases (as might occur in an unsprinklered enclosure) creates the most severe conditions with respect to expansion of hot fire gases within the zone of origin. For sprinkler- controlled fire scenarios, the production of gases and smoke is dramatically reduced as a result of the cooling effects of water. Further, the heat release rates (HRR) of controlled fire scenarios are typically far less than those observed for similar uncontrolled fire scenarios, thereby limiting smoke production. Theoretical Effects of Buoyancy According to the principles of smoke control design, and documented in the Handbook of Smoke Control Engineering, buoyancy forces of heated gases are a direct result of the density differential between the heated and unheated or relatively unheated gases within a space. Equations 3.33, and 3.34 in Chapter 3 of the ASHRAE text can similarly be applied to arrive at the pressure difference between a room or series of rooms and surrounding spaces outside the space of fire origin. Assuming that the heated gases within the space will be cooled by sprinklers to some temperature below 350°F, application of the above equations demonstrates that only minor pressure differences, in the range of approximately 0.05 to 0.15 in. WC, will be achieved. It should be noted that for sprinkler -controlled fires, smoke temperatures of 165°F (the activating temperature of the sprinklers) are considered more realistic per NFPA 92, and even this value is considered somewhat conservative once the sprinkler system is activated and mixing and cooling effects are considered2. In either case, the larger the space, the greater the heat losses to the surroundings as the hot gas layer is diluted, and hence the smaller the pressure gradient. Table 1 lists a variety of pressure gradients for rooms and fires of varying sizes, as well as corresponding pressure gradients that would be anticipated. TABLE 1 - EFFECTS OF BUOYANCY ON PRESSURE GRADIENT' COMBUSTION GASES —TEMPERATURE AT PRESSURE DIFFERENCES (IN. WC) (ASSUMES ROOM CEILING 2F TEMPERATURE OF 682E 1,290°F (uncontrolled) 0.35 (assumes 35 ft. height of space) 350°F (sprinkler controlled) 0.15 (assumes 30 ft. height of space) 350°F (sprinkler controlled) 0.05 (assumes 10 ft. height of space) 165°F (sprinkler controlled) 0.07 (assumes 30 ft. height of space) 165°F (sprinkler controlled) 0.02 (assumes 10 ft. height of space) It is evident from the data in Table 1 that sprinkler controlled fires in spaces with lower ceiling heights generate very small pressure gradients in the area of fire origin as a result of buoyancy. Based on this data, it can be determined that buoyancy effects do not need to be considered in the stair and elevator United Building and Engineering Services, LLC 39 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 pressurization system modeling performed for this project. This analysis assumes that the maximum temperatures within the fire compartments will be less than 350°F since the building is fully sprinkler - protected. The ceiling heights will generally be about 13 ft (or less) and the pressurization systems will be designed to produce a minimum pressure difference of 0.10 in. WC, which will be greater than the maximum expected buoyancy induced pressure gradients within the room of fire origin. Theoretical Effects of Expansion Smoke movement can also be caused by expansion from the energy released by a fire. The degree to which expansion occurs and how the smoke migrates to adjacent spaces primarily depends on whether sprinklers activate and the nature and quantity of leakage paths between the room of fire origin and the adjacent spaces. The ratio of the volumetric flows into and out of the room of fire origin is expressed as a ratio of absolute temperatures as shown in Equation 3.28 (Chapter 3) of the ASHRAE text Handbook of Smoke Control Engineering. iI ` ill Till where 1 )llr = volumetric flow of smoke out of the fire compartment, cfin (nil/s), I111 = volumetric flow of air into the fire compartment, cfin (m1/s). Calculations using the above referenced equation demonstrate that for an unsprinklered fire having hot gas temperatures of approximately 1,110°F, the hot gases produced by the fire will expand to approximately three times their original volume.5 In comparison, for a sprinkler -controlled fire having gas temperatures of approximately 350°F, the gases will expand to approximately 1.5 times their original volume. As steps are taken to reduce the temperature of the hot gas layer, such as providing sprinklers that will discharge and control the fire, the effects of expansion on smoke migration can be all but eliminated. For these reasons, it was determined that the modeling performed for this analysis did not need to consider expansion effects. It should be noted that the pressure differences due to the rapid evaporation of water and creation of steam from water application on a fire were not included in the analysis. Tests have shown that under normal conditions of sprinkler operation, sprinklers are activated by the first flow of gases rising from the fire. Room temperature conditions are not hot enough at that point to cause an instantaneous evaporation of a large volume of water [Tamura, 1994]. Duration of Operation IBC Section 909.4.6 requires that all portions of the smoke control systems be capable of continued operation for not less than 20 min. In addition, the stair and elevator shafts will be enclosed with 2-hour fire -resistance (FRR) rated construction and will have 90 min. protected opening assemblies. The shaft pressurization and associated ducts, control wiring and power wiring will also be enclosed in 2-hour construction for separation from the rest of the building. United Building and Engineering Services, LLC 40 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united CONTAM MODEL ANALYSIS A model of The Anthology at Edmonds Apartment project was constructed using CONTAM 3.1c, a multizone building air flow and contaminant dispersal modeled developed at the National Institute of Standards and Technology (NIST). This program is recognized by leading fire protection engineering resources (NFPA 92 [2012], Principles of Smoke Management [Klote, Milke 2012]) as being appropriate for the design of pressurization smoke control systems. There are two primary reasons for using the computer model, CONTAM, as opposed to standard hand - calculations to evaluate the proposed smoke control system. As part of a rational analysis of the smoke control system, per IBC §909.4, CONTAM was used to evaluate the proposed smoke control system under different combinations of wind speed and outdoor temperatures, which could create pressure and airflow conditions within the building that cause smoke infiltration into the stairs, or elevator shafts. This evaluation would be extremely difficult to perform solely using hand calculation methods. The unpredictable nature of closing doors, limited air relief during smoke control system operation, and other items introduces significant complexity to the smoke control systems. Evaluating these features with hand calculations is not realistic. CONTAM Scenarios and Results A series of CONTAM simulations were conducted to evaluate the proposed smoke control system as part of the rational analysis defined by IBC §909.4. The proposed smoke control system is capable of maintaining conditions such that the interior exit stairways are pressurized to a minimum of 0.10 w.c. and a maximum of 0.35 w.c. in the shaft with respect to the building with all stairway doors closed under maximum anticipated stack and wind pressures and also maintain an elevator door pressure differential of a minimum 0.10 w.c. and a maximum of 0.25 w.c. across the elevator door. It is important to note that a differential pressure of 0.10 w.c. is sufficient to prevent the passage of smoke created from a sprinklered fire as shown in the "Design Fire" section of this report. CONTAM MODEL RESULTS This section describes the analysis of the smoke control systems using CONTAM and the results of the analysis. The following conditions were modeled as part of the CONTAM analysis: • The actual architectural configuration of The Anthology at Edmonds Apartment project • Leakages through different construction elements, including walls, floors, doors, and other air transfer openings United Building and Engineering Services, LLC 411 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united • Air flow locations and quantities matching the design for the smoke control system • Extreme weather conditions to account for stack effect and wind effect The results of the CONTAM computer modeling are presented at the end of this section in terms of the pressure differentials across residential floors and stair / elevator doors. The results were compared with the design criteria summarized in the following table: Smoke Control System Design Criteria Stairwell Pressurization System - Pressure difference to all floors 0.10 in. w.c. min. to 0.35 in. w.c. max. Elevator Pressurization System — Pressure Difference to all floors (except recall floor) 0.10 in. w.c. min. to 0.25 in. w.c. max The results of the CONTAM analysis depend on the leakage through different construction elements. The leakage factors used in the CONTAM model are based on the information in "Principals of Smoke Management" by John Klote and James Milke, which could be different from the leakage factors in the actual building. The actual performance of the smoke control system might change if the leakage of the actual building components differs from the leakages modeled in this analysis. Based on the results of the CONTAM modeling summarized in this section and subject to the limitations outlined in this analysis and referenced documents, the designed smoke control systems for The Anthology at Edmonds Apartment project is capable of meeting the design criteria outlined above. Smoke Control Svstems The smoke control systems for The Anthology at Edmonds Apartment project is based on developing pressure differences between stair / elevator shafts and adjacent spaces. The CONTAM model has been used to analyze the stair and elevator pressurization systems. The design of the smoke control systems is summarized below. A. Smoke Control System Modeling The smoke control systems have been evaluated under varying weather conditions. The results outlined at the end of this section are designed to both analyze the capabilities of the smoke control systems to achieve the design criteria and to provide guidance on the impact of various weather conditions on the pressure differentials in the building that can be used as part of the smoke control system testing. 1. CONTAM Model (CONTAM 3.1c) CONTAM is a computer program developed by the National Institute of Standards and Technology (NIST) for multi -zone indoor air quality and ventilation analysis that can calculate air flows and pressure differentials under a range of weather conditions. The CONTAM model works by dividing the space into multiple zones. Each zone is assumed to be well -mixed, meaning that the state properties (i.e. temperature) within each zone are uniform. Airflow between different zones driven by mechanical means, wind pressures, and buoyancy effects (induced by the United Building and Engineering Services, LLC 42 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united temperature difference between zones) are calculated by CONTAM. In this analysis, a CONTAM 3.1c model has been developed for The Anthology at Edmonds Apartment project from Level 1 to Roof (all levels). Each floor has been divided into multiple zones, including one zone for each of the vertical shafts, one zone for the corridor, one zone for the apartment units, etc. Zones are connected by flow paths described in the following section. 2. Building Leakage Building leakage was modeled as one-way flow using a power law relationship using a pressure exponent of 0.65. The effective leakage areas below are based on values found in "Principles of Smoke Management" by John Klote and James Milke. Since the final construction is not yet complete, the values chosen represent leakage looser than average. Construction Element Leakage Area Ratio - A/Aw Exterior walls 0.001 Corridor walls 0.0018 Stairwell walls 0.00035 Elevator walls 0.0015 3. Doors Doors were modeled as one-way flow using a power law relationship and a flow exponent of 0.65 consistent with the data source for the leakage area. Door leakage areas were based on "Principles of Smoke Management" by John Klote and James Milke: Construction Element Leakage Area Per Door (sq. ft.) Exterior doors 0.461 Residential doors 0.300 Stairwell doors 0.244 Elevator doors (open) 6.00 Elevator doors (closed) 0.37 The discharge coefficients used in the CONTAM model are based on the "Principles of Smoke Management" by John Klote and James Milke. 4. Other Openings United Building and Engineering Services, LLC 43 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united Other openings to the exterior within each of dwelling units, including operable windows, toilet exhausts, fireplace exhausts, range exhausts, dryer exhausts, and ventilation intakes, are accounted for in using loose leakage factors in the model. In addition, any variability caused by these openings will be compensated by a factor of safety of 25% used in the calculation of the required air flow rate. 5. Weather Conditions CONTAM is capable of incorporating the effects of weather on a building. Weather parameters include ambient temperature, barometric pressure, wind speed, and wind direction. The weather conditions used in the CONTAM model are as follows (previously described in our report). Season Outside Temperature (°F) Building Temperature (°F) Shaft Temperature (°F) Winter 24 70 45 Summer 85 70 78 Wind speed data is also taken from the 2013 ASHRAE Handbook of Fundamentals, and is based on the 1% extreme annual wind speed (20 mph). The worst -case wind speed direction was used, regardless of the prevailing wind direction presented in the data. 6. Air Handling Units The mechanical smoke control systems design for The Anthology at Edmonds Apartment project are modeled as "Air Handling Systems" in CONTAM. CONTAM has the capability of considering both the quantity and location of supply and exhaust that will be provided as part of the smoke control systems. All pressurization systems include a single injection point at the top of the shaft. Since the smoke control systems (potentially) have been over -designed to allow them to be properly balanced in the field to achieve the required pressure differences, the smoke control systems have been manually balanced in CONTAM within the designed fan capacities to achieve the required pressure differences. Note that the smoke control systems will need to be balanced in the field and may differ from the flow rates used in the model, because the actual leakage of the building elements may differ from those used in the CONTAM model. B. Design Scenarios The anticipated performance of the smoke control systems has been analyzed under extreme climate conditions. Four design scenarios have been analyzed as follows: United Building and Engineering Services, LLC 44 1 Page 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004 united Scenario Effective Season Wind Effect 1 Summer None 2 Summer 20 mph 3 Winter None 4 Winter 20 mph C. Analysis Results The air flows required to achieve proper pressurization of the stair and elevator shafts are shown in the table below. A factor of safety of 25% is included and will compensate for discrepancy between the estimated leakage factors and actual building leakage. Fans will have Variable Frequency Drives (VFD's) to provide the ability to adjust the airflow during final balancing and adjustments. Pressurized Shaft Required Airflow Rate at Top of Shaft (CFM) SPF-1 5,000 SPF-2 5,000 EPF-1 11,500 Elevator recall floors are as follows: o Primary Recall Floor = Level 1 o Alternate Recall Floor = Level 2 (this floor will also require a minimum 12 SF of free area relief) The stair and elevator fans are a utility set with a backward inclined fan wheel. This fan is classified as a non -overloading fan. We typically desire to have the fans final balanced for this project at or near 0.20" w.c. (this does yield higher CFM's than calculation at 0.10" w.c.). Beyond CONTAM modeling, this will be final balanced in the field under our direction and approval to operate per Code requirements in a manner that does not operate in any unstable conditions for the fan (RPM, amp, etc.). We recommend that a utility set fan (Greenheck USF) with backward inclined fan wheel to be used. Minimum external static pressure for sizing is 0.75" (we will want to review final mechanical design along with fan curves for the stair and elevator pressurization fans). In addition, each fan is provided with a VFD. The basis of design is an ABB ACH 580 in a NEMA-3R enclosure mounted by each stair and elevator pressurization fan. A final discussion is provided on the proper selection of the stair and elevator pressurization fans. The stair and elevator pressurization fans need to be carefully selected and matched with a United Building and Engineering Services, LLC 45 1 Page 1400 1121h Ave SE, Suite 100 Bellevue, WA 98004 united variable frequency to be able to work over a wide range of airflows without the fan operating in an unstable or improper area on the fan curve. As discussed in this report, CONTAM modeling or "hand calculations" can both as easily undersize or oversize smoke control fans because assumptions have to be made on leakage rates thru the various building structures. We believe in applying safety factors on the total airflow while equally applying our HVAC knowledge in the proper selection of fans that can operate without any issues over a wide range of airflows and matched with an appropriate variable frequency drive. Final balancing will then be utilized under our guidance to insure proper actual pressure differentials are utilized. IMPORTANT ADDITIONAL DESIGN CONSIDERATIONS: o All stair doors are to be supplied with Pemko adjustable door bottoms. Basis of design performance is a Pemko 4301_PKL Automatic Door Bottom o Elevator shaft is pressurized and is required to be airtight. All joints, edges, panels are to be fire caulked and sealed for this shaft. We assumed only a small amount of leakage via the elevator shaft o Elevator doors are to be installed in accordance with NFPA-252 to maintain the fire rating of the elevator door. This is also essential for smoke control as the maximum elevator door gap allowed is 3/8" (this helps also determine the elevator pressurization air leakage) o Elevator fronts are required to be sealed / fire caulked to sheetrock shaft o Stair shafts are also pressurized and are required to be airtight. All joints, edges, panels are to be fire caulked and sealed for these shafts o All shafts are indirectly pressurized. All joints, edges, panels are to be fire caulked and sealed for these shafts United Building and Engineering Services, LLC 46 1 P a g e 1400 112'h Ave SE, Suite 100 Bellevue, WA 98004