REVIEWED RESUB4 BLD2021-0756+Energy_Calculations+2.9.2022_4.45.09_PM+26723832015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
Project: R E U B
Anthology of Edmonds - 2015 WSEC 21200 72nd Ave W gLD2021-0756 Feb 10 2022
Edmonds, WA 98026
CITY OF EDMONDS
DEVELOPMENT SERVICES DEPARTMENT Date: 2022-02-09
Applies
Code Section
Code Provision
Compliance Information Required In Permit
Location in
Building Department
Documentation
Documents
Notes
EQUIPMENT - SIZING, PERFORMANCE AND TYPE
NA
C403.1
Exempt process
Identify equipment to be used in
NA
equipment
manufacturing, industrial or commercial
processes that do not provide space
conditioning; identify provisions applicable to
this equipment per C403.1 exception
YES
C403.2.1
Load calculations
Provide load calculations performed per
M0.1
ASHRAE Std 183 or equivalent, using design
parameters per C302 and Appendix C;
include load adjustments to account for
energy recovery
YES
C403.2.2
Equipment and
Indicate that output capacities of heating and
M5.0
system sizing
cooling equipment and systems are no greater
than the smallest available equipment size that
exceeds the calculated loads; note exceptions
taken
YES
C403.2.3
HVAC equipment
Provide equipment schedules on plans or
M5.0
C403.2.3.2
performance
complete MECH-EQ forms indicating type,
C403.2.13.1
requirements
capacity, rated and WSEC minimum
(efficiency)
efficiencies for all heating and cooling
equipment; include supply and OSA cfms and
operating hours for all air systems; identify
heating and cooling equipment that does not
have a corresponding WSEC minimum
efficiency (manufacturer rated)
YES
C405.8
Electric motor
List all motors >_ 1/12 hp (that are not integral
M5.0
C403.2.14
efficiency
to a rated piece of equipment) in the
mechanical or electrical equipment schedules
on plans; indicate hp, rpm, number of poles
and rated efficiency, or exception applied
YES
For fractional hp fan motors (1/12 - 1 hp),
M5.0
indicate whether they are an electronically
commutated motor, have rated efficiency of
at least 70%, or exception taken
YES
C403.2.11.1
Fan power limitation
For all HVAC fan systems that provide
M5.0
heating and / or cooling, provide system total
nameplate hp in MECH-FANSYS-SUM form
NA
For all applicable HVAC systems with total
NA
fan motor hp > 5hp, verify fan system motor
hp or bhp complies with fan power limits per
equations in Table C403.2.11.1(1), provide
MECH-FANSYS form for each system
Page 1/17
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
NA
C403.2.11.2
Motor nameplate hp
For all applicable HVAC systems with total
NA
fan motor hp > 5hp, indicate fan motors
specified are the smallest available motor hp
size greater than fan bhp, note exceptions
taken
NA
C403.2.11.3
Fan efficiency
For all applicable HVAC systems with total
NA
fan motor hp > 5hp, identify in equipment
schedule all fans required to comply with fan
efficiency grade and indicate rated FEG is >_
67, or exception taken; indicate these fans are
sized so total efficiency is within 15% of the
fan maximum total efficiency
YES
C403.2.11.4
Group R occupancy
For all exhaust fans < 400 cfm in Group R
M5.0
exhaust fan efficacy
occupancies, indicate in equipment schedule
the fan flow rate and efficacy (cfm/watt), or
exception taken; refer to Table C403.2.11.4
(CE-57)
NA
C403.2.13
Variable flow
For fan motors > 7.5 hp, indicate method of
NA
capacity -
variable flow control (VSD or equivalent
fans
method) in equipment schedule, or exception
taken; for equivalent method for an HVAC
system refer to HVAC System Controls for
additional requirements
NA
C403.2.3
Maximum air cooled
For chilled water plants and buildings with >
chiller capacity
500 tons of cooling capacity, indicate air-
cooled chiller capacity is <_ 100 tons, or
exception taken
NA
C403.4
Large capacity
For buildings with >_ 300 tons of cooling
cooling systems
capacity, indicate method of multi -stage or
variable capacity control (VSD, multiple
staged compressors, or max capacity of any
single unit < 66% of the total)
NA
C403.2.3.1
Non-standard water-
For water-cooled centrifugal chillers not
cooled centrifugal
designed for operation at standard conditions,
chillers
provide calculations documenting maximum
full load and part load rated equipment
performance requirements
NA
C403.2.13.1
Centrifugal fan open-
For open -circuit centrifugal fan cooling
C403.4.3.2
circuit cooling towers
towers with >_ 1,100 gpm capacity, indicate
cooling towers comply with efficiency
requirements for axial fan open circuit
cooling towers
NA
C403.4.2
Large capacity boiler
For single boilers with > 500,000 Btu/h
C403.4.2.5
systems
capacity, indicate multi -stage or modulating
burner
NA
For boiler system (single or multiple) with >
1,000,000 Btu/h capacity, indicate turndown
ratio per Table C403.4.2.5 and method
(multiple single input boilers, modulating
boilers, or combination)
Page 2117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
NA
C403.2.13
Variable flow
For pump motors >_ 7.5 hp, indicate method
NA
capacity -
of variable flow control (VSD or equivalent
pumps
method) in equipment schedule, or exception
taken; for equivalent method for a hydronic
system refer to Hydronic System Controls for
additional requirements
NA
C403.2.3
Gas and oil -fired
For forced air furnaces with capacity >_
NA
forced air furnace
225,000 Btu/h and all unit heaters, indicate in
and unit heaters
equipment schedule intermittent ignition or
IID, flue or draft damper, and rated jacket
loss
NA
C403.2.4.8
Combustion heating
For combustion heating equipment with
NA
equipment
output capacity > 225,000 Btu/h, indicate
modulating or staged combustion control
NA
C403.2.3.3
Packaged electric
Verify all packaged electric equipment with >
heating / cooling
6,000 Btu/h cooling capacity and any amount
equipment
of heating is a heat pump; include in
equipment schedules
NA
C403.2.12
Heating outside a
Indicate systems providing heating in non -
building
enclosed outdoor occupied spaces are radiant
systems; refer to HVAC System Controls for
additional requirements
YES
C403.2.7.1
Kitchen exhaust
Indicate on plans the type, duty and exhaust
M6.1-M6.14
hoods
air rate of each kitchen hood, refer to HVAC
System Controls for additional requirements
YES
C403.2.4.3
Outdoor supply air,
Indicate locations of OSA intake, and exhaust
M2.0-M2.6
exhaust and relief
and relief outlet dampers on plans; indicate
dampers
whether dampers are Class 1 motorized, or
gravity and exception taken (include leakage
rating, cfm/sf); refer to HVAC System
Controls for additional requirements for OSA
dampers
YES
C403.2.4.3
Return air dampers
Indicate locations of return air dampers that
M2.0-M2.6
are integral to economizer operation; verify
dampers are motorized; indicate whether
dampers are Class 1, or within packaged
equipment eligible for leakage rating
exception (include leakage rating, cfm/sf)
YES
C403.2.4.3
Stairway and shaft
Indicate location of stairway and shaft vent
M2.0-M2.6
vent dampers
dampers on plans; verify dampers are Class 1
motorized; refer to HVAC System Controls
for additional requirements
NA
C403.2.4.4
Zone isolation
For systems serving areas > 25,000 sf or
NA
dampers
spanning more than one floor, that include
areas that are expected to be occupied non -
simultaneously; identify isolation zone areas
on plans and locations of associated isolation
dampers in HVAC distribution system; refer
to HVAC System Controls for additional
requirements
Page 3117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
NA
C403.2.3.4
Humidification
For cooling systems with humidification
NA
equipment that are also required to have air
economizer, indicate humidifier is adiabatic
(direct evaporative or fog atomization), or
exception taken
ADDITIONAL EFFICIENCY PACKAGE OPTION, MORE EFFICIENT HVAC EQUIPMENT & FAN PERFORMANCE - MUST COMPLY
WITH ALL 3 PROVISIONS TO BE ELIGIBLE
YES
C406.2.1
HVAC system
To comply with additional efficiency package
M0.1
C403.2.3
selection
option, calculate the percentage of heating and
cooling equipment in the project (based on
output capacity) that do not have a
corresponding WSEC listed efficiency; shall
be less than 10% to comply
YES
C406.2.2
Minimum equipment
To comply with additional efficiency package
M0.1
C403.2.3
efficiency
option, indicate that all listed heating and
cooling equipment have a rated efficiency that
exceeds WSEC listed efficiency by at least
15%
YES
C406.2.3
Minimum fan
To comply with additional efficiency package
M5.0
C403.2.11.3
efficiency
option, indicate rated FEG of stand alone fans
is >_ 71; indicate these fans are sized so the
fan efficiency at design conditions is within
10% of the maximum total or static efficiency
HVAC SYSTEM CONTROLS
YES
C403.2.4.1
Thermostatic controls
Indicate locations of thermostatic and
M2.0-M2.6
(thermostats and
humidity control devices and the zones they
humidistats)
serve on plans, including perimeter system
zones
NA
Where adjacent (neighboring) zones are
controlled by separate thermostats (including
perimeter systems used to offset heat gain or
loss), and are connected by permanent
openings > 10% of either zone sf area,
indicate controls configured to prevent
adjacent zones from operating in conflicting
modes (one in heat, other in cool); applies to
adjacent perimeter zones, adjacent
nonperimeter zones, and adjacent perimeter
and nonperimeter zones
NA
If applying Exception 2 to nonperimeter zones
adjacent to perimeter zones, indicate that
setpoints and deadband settings in these zones
are coordinated so cooling in a nonperimeter
zone does not occur until the temperature in
that zone is 5°F higher than the adjacent
perimeter zone temperature in heating
NA
C403.2.4.1.1
Heat pump
Indicate staged heating operation with
supplementary heat
compression as the first stage of heating and
supplemental heating controlled with outdoor
lock -out temperature set to 40°F or less
NA
C403.2.4.1.2
Deadband
Indicate zone thermostatic controls configured
with 5°F minimum deadband for systems that
control both heating and cooling
Page 4117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
NA
C403.2.4.1.3
Setpoint overlap
If separate heating and cooling systems with
restriction
separate thermostatic control devices are used
(thermostats)
to serve a zone, indicate locations of both
thermostatic control devices and the zone they
serve on plans
NA
Indicate a limit switch, mechanical stop or
DDC control with programming to prevent
simultaneous heating and cooling
NA
C403.2.4.2
Automatic setback
Indicate zone thermostatic controls configured
C403.2.4.2.1
and shutdown
with required automatic setback and manual
C403.2.4.2.2
override functions, setback temperatures, and
control method (automatic time clock or
programmable controls); note exceptions
taken
NA
C403.2.4.2.3
Automatic (optimum)
Indicate system controls that adjust equipment
start
start time required to bring each area served
up to design temperature just prior to
scheduled occupancy
YES
C403.2.4.3
Outdoor supply air
Indicate automatic controls configured to
M2.0-M2.6
dampers
close OSA damper during unoccupied
equipment operation; not including
economizer cooling, night flush or IMC
required OSA / exhaust
YES
C403.2.4.3
Stairway and shaft
Indicate method of activation of stairway and
M2.6-M2.7
vent dampers
shaft vent dampers (fire alarm or interruption
of power)
NA
C403.2.4.4
Zone isolation
For systems serving areas > 25,000 sf or
NA
controls
spanning more than one floor, that include
areas that are expected to be occupied non -
simultaneously; indicate controls that allow
for independent space conditioning of
isolation zones; or exception taken
NA
C403.2.12
Heating outside a
Indicate occupancy sensing or timer switch
building
controls configured to automatically shut off
heating system when area served is
unoccupied
NA
C403.2.4.5
Snow melt systems
Indicate automatic controls configured to shut
off system when pavement temperature
exceeds 50°F and no precipitation is falling,
and when outdoor air temperature exceeds
40°F
NA
C403.2.4.6
Freeze protection
Indicate automatic controls to shut off system
system controls
when outdoor temperature exceeds 40°F, or
conditions protect fluid from freezing
NA
C403.2.4.9
Group Rl hotel /
For hotels and motels with over 50 guest
NA
motel guest rooms
rooms, indicate automatic controls serving
guest rooms that are capable of setback
(heating) and set-up (cooling) of temperature
setpoint by at least 5°F; indicate control
method - activated by room entry or
occupancy sensor
Page 5117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
YES
C403.2.4.10
Group R2 / R3
For primary space conditioning system,
M4.0-M4.1
C403.2.4.11
dwelling units, Group
indicate 5-2 programmable thermostats
R2 sleeping units
capable of two setback periods per day; for all
thermostats indicate purpose (heating only,
cooling only, or both), required temperature
range and at minimum a 10°F deadband; or
exception taken
YES
C403.2.6
Ventilation
Indicate method of ventilation air delivery
M2.0-M2.6
C403.2.11.4
(natural or mechanical) for each zone
YES
If mechanically delivered, indicate that
M2.0-M2.6
systems are configured to provide not more
than 150% of, but at least the minimum
required volume of outdoor air to each zone
per IMC, ASHRAE 62.1 or other applicable
code (WAC, OSHA, etc); or exception taken
NA
If delivered via natural ventilation, identify
required elements per IMC including
minimum openable area to the outdoors or
qualifying adjoining spaces
NA
C403.2.6.2
Demand controlled
Identify spaces > 500 sf with occupant load >
NA
ventilation
25 people/1,000 sf per IMC; for each space
indicate whether it is served by an HVAC
system with total design OSA > 3,000 cfm,
and / or the system has airside economizer or
automatic modulating OSA damper; indicate
OSA controls are configured to provide
demand controlled ventilation or provide
supporting documentation for applied
exception
NA
C403.2.6.3
Occupancy sensors
For gyms, classrooms, auditoriums and
NA
conference rooms > 500 sf, indicate
occupancy -based OSA control when space is
unoccupied and method (closes OSA damper
or shuts -off equipment); or alternate means
provided to automatically reduce OSA when
space is partially occupied
NA
C403.2.6.4
Enclosed loading
For enclosed loading docks, indicate
C403.2.6.4.1
dock ventilation
ventilation / exhaust system method of
activation (gas detection system for CO and
NO2, or occupancy sensors), and control
method (staged or modulating)
YES
C403.2.6.4
Enclosed parking
For enclosed parking garages, indicate
M2.0-M2.1
C403.2.6.4.2
garage ventilation
ventilation / exhaust system activated by gas
detection system for CO and NO2, and
control method (staged or modulating); or
exception taken
YES
C403.2.7.1
Kitchen exhaust
Provide calculations that show a balanced
M2.1, M5.0
hoods
accounting of total kitchen exhaust (include
all hoods) with % of: supply air, transfer air
from adjacent spaces, and make-up air; if
applicable, indicate that direct make-up air to
each hood does not exceed 10% of hood
exhaust
Page 6117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
YES
For kitchens with total hood exhaust
M2.1, M5.0
exceeding 2,000 cfm, indicate exhaust air rate
per Table C403.2.7.1 and compliance method
(DCV, energy recovery, or transfer air that
would otherwise be exhausted)
NA
C403.2.7.2
Laboratory exhaust
Refer to Systems Requiring Energy Recovery
systems
for requirements
NA
C403.2.13
Variable flow
For HVAC fan motors >_ 7.5 hp, indicate
NA
capacity - HVAC
method of variable flow control (VSD, or
system fans
equivalent control method that reduces design
air volume by 50% at 1/3 static design
pressure); note exception taken
YES
C403.3.1
DX air handler
For DX air handlers with economizer and
M5.0
variable cooling
cooling capacity >_ 65,000 Btu/h, indicate
control
number of cooling stages provided and
(Under Integrated
method (multiple compressors and / or
Economizer)
variable speed compressors); indicate
minimum displacement (capacity reduction)
as % of full load
YES
Indicate control method (cooling capacity
M5.0
controlled in response to space temperature,
space temperature controlled by modulating
supply airflow, or both)
YES
C403.2.11.5
Fan airflow control
For DX air handling units with cooling
M5.0
capacity > 65,000 Btu/h and evaporative and
chilled water air handling units with fan >
0.25 hp, indicate whether system is single
zone or multiple zone and related control
method (cooling capacity controlled in
response to space temperature, space
temperature is controlled by modulating
supply airflow, or both)
YES
For mechanical cooling systems (includes DX
M5.0
and chilled water coils) that control cooling
capacity in response to space temperature -
Provide a minimum of two stages of fan
control; indicate minimum fan speed is <_
66% of full speed drawing <_ 40% of full
speed fan power during periods of low cooling
or ventilation only
YES
For other mechanical cooling systems
M5.0
(includes DX and chilled water coils) that
control space temperature by modulating
airflow (in lieu of, or in addition to,
controlling capacity in response to space
temperature) - Provide fan controls for
modulating supply airflow; indicate minimum
fan speed is <_ 50% of full speed drawing <_
30% of full speed fan power during periods of
low cooling or ventilation only; or exception
taken
Page 7117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
YES
C403.2.4.12
DDC system
Provide central and zone level DDC controls
SPECS
capabilities
as required based on system application,
capacity or size thresholds and other
qualification per Table C403.2.4.12.1
YES
Identify all DDC system input / output control
SPECS
points; indicate capability for trending and
graphical display
DUCTING SYSTEMS
YES
C403.2.8.1
Duct construction
Indicate on plans that all ductwork is
M2.0-M2.6
C403.2.8.3
constructed and sealed per IMC
YES
For OSA ductwork, also indicate on plans that
SPECS
ductwork meets air leakage requirements per
C402.5 and vapor retarder requirements per
the IBC
YES
C403.2.8.3
Duct pressure
Identify location of low, medium and high
M2.0-M2.6
classifications
pressure ductwork on plans
NA
C403.2.8.3.3
High pressure duct
Indicate high pressure duct leakage testing
NA
leakage test
requirements on plans; provide test results to
jurisdiction when completed
YES
C403.2.8.1
Duct insulation
For supply and return ductwork located in
SPECS
C403.2.8.2
unconditioned space or outdoors, indicate R-
value of insulation on ductwork on plans;
identify climate zone; note exceptions taken
YES
For supply ductwork located in conditioned
SPECS
space, identify if design supply temperature is
< 55°F or > 105°F and indicate R-value of
insulation on this ductwork on plans; note
exception taken
YES
For OSA ductwork, shafts and plenums,
SPECS
indicate R-value of insulation on these
elements on plans per Table C402.1.3 for
steel -framed walls; note exception taken
PIPING SYSTEMS
NA
C403.2.9
Piping insulation
Indicate design temperature range of fluid
conveyed in piping and thickness of insulation
(in inches) on hydronic piping plans; or
exception taken
NA
C403.2.9.1
Piping insulation
Indicate method of protection of pipe
exposed to weather
insulation from damage / degradation on
hydronic piping plans
ECONOMIZERS
YES
C403.3
Air economizer
Identify in equipment schedules on plans or in
M5.0
required
MECH-EQ forms all cooling systems
requiring air economizer controls
Page 8117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
YES
Provide MECH-ECONO form indicating
M5.0
systems utilizing air economizer exceptions,
including those with water -side economizer in
lieu of air economizer; indicate on plans
eligible exception(s) taken and measures to
comply with exception(s)
YES
C403.3.1
Integrated
Indicate air and water -side economizers are
M5.0
economizer operation
configured for partial cooling operation even
- air and water
where additional mechanical cooling is
required to meet the load
YES
C403.3.2
Economizer heating
Verify control method of HVAC systems with
SPECS
system impact - air
economizers does not increase building
and water
heating energy usage during normal operation
YES
C403.3.3.1
Air economizer
Indicate modulating OSA and return air
M5.0
capacity
dampers are configured to provide up to
100% OSA for cooling
YES
C403.3.1
Integrated air
Verify mechanical cooling controls are
M2.1
C403.3.3.2
economizer
interlocked with air economizer controls so
the outside air damper remains in 100% open
position when mechanical cooling is also
required to meet the cooling load, until the
leaving air temperature is < 45°F
YES
For systems with cooling capacity >_ 65,000
M5.0
Btu/h, verify that control of economizer
dampers is not based only on mixed air
temperature; or exception taken
YES
C403.3.3.3
Air economizer high
Indicate high limit shut-off control method
SPECS
limit controls
and required high limit per Table C403.3.3.3
NA
C403.3.4.1
Water economizer
For eligible systems where water -side
capacity
economizer may be provided in lieu of air
economizer, indicate system is capable of
100% design cooling capacity at 50°F db /
45°F wb OSA temperatures
NA
C403.3.4.2
Water economizer
Indicate pressure drop across precooling coils
maximum pressure
and heat exchangers in water economizer
drop
system do not exceed pressure drop limit
YES
C403.3.1
DX air handling
For DX air handlers with economizer and
SPECS
equipment control
cooling capacity >_ 65,000 Btu/h, refer to
HVAC System Controls for requirements
YES
C403.2.4.7
DX equipment
For DX air handlers with economizer and
SPECS
economizer fault
cooling capacity >_ 54,000 Btu/h, provide a
detection and
fault detection and diagnostics (FDD) system
diagnostics
to monitor economizer system operation and
report faults
SYSTEMS REQUIRING ENERGY RECOVERY
NA
C403.5.1
Energy recovery (ER)
For systems with design OSA > 5,000 cfm, or
NA
- ventilation / exhaust
design supply air cfm and % OSA exceeding
systems
the values in Tables C403.5.1(1) or (2),
indicate exhaust air ER method; or exception
taken with supporting calculations
Page 9117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
NA
For rooms served by multiple systems with
NA
aggregate design OSA > 5,000 cfm, or
aggregate design supply air cfm and % OSA
exceeding the values in Tables C403.5.1(1) or
(2), indicate exhaust air ER method; or
exception taken with supporting calculations
YES
Indicate ER rated effectiveness that increases
M5.0
OSA enthalpy by >_ 50% based on delta
between OSA and return air enthalpies at
design conditions
NA
C403.2.7.2
Laboratory exhaust
For buildings with total lab exhaust > 5,000
systems (energy
cfm, indicate method of energy recovery used
recovery)
to pre -condition laboratory make-up air; ER
effectiveness (min 25°F); or alternative
method per exception (VAV exhaust, semi -
conditioned makeup, or CERM calculation)
NA
C404.10.4
Pools and permanent
For buildings with pools or spas with water
(under
spas exhaust systems
surface area > 200 sf, indicate exhaust air ER
C404.11)
(energy recovery)
method and use of waste heat (preheat
ventilation air, pool water or service hot
water); or exception taken
NA
Indicate ER system has the rated effectiveness
and is configured to decrease the exhaust air
temperature at design conditions by >_ 36°F
NA
C403.5.2
Energy recovery -
For buildings with on -site steam heating
steam condensate
systems
systems, indicate condensate water ER
NA
For buildings that use off -site generated steam
where condensate is not returned to the
source, indicate on -site condensate water ER
YES
C403.5.3
Energy recovery -
For buildings with food service, meat or deli
M6.1-M6.14
cooler / freezer
departments that have >_ 500,000 Btu/h of
condensers
remote refrigeration capacity for coolers /
freezers, indicate condenser ER and use of
captured energy (service water heating, space
heating, or dehumidification reheating)
YES
For buildings with >_ 40,000 sf conditioned
M6.1-M6.14
floor area and with >_ 1,000,000 Btu/h of
remote refrigeration capacity for coolers /
freezers, indicate condenser ER and use of
captured energy for service water heating and
also for space heating, or dehumidification
reheating
NA
C403.5.4
Energy recovery -
For buildings with 24-hour operation and with
condenser systems
> 1,500,000 Btu/h of heat rejection capacity
and design service hot water load > 250,000
Btu/h, indicate condenser ER to pre -heat
service water; or exception taken. Provide
calculations showing the amount of recovered
heat that is utilized (60% of peak heat
rejection load or pre -heat service water to
85°F).
HYDRONIC SYSTEM CONTROLS
Page 10117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
NA
C403.2.13
Variable flow control
For hydronic system pump motors >_ 7.5 hp,
C403.4.2.7
-
indicate method of variable flow control
hydronic system
(VSD or equivalent method that requires
pumps
30% design wattage at 50% design fluid
flow); note exception taken
NA
Identify whether hydronic coils have DDC
controls and associated manner of pump
speed control (differential pressure, zone
hydronic demand, etc)
NA
C403.2.5
Hydronic system
For boilers that provide building heating,
C403.4.2.4
setback and part load
indicate controls that provide heating water
controls
temperature setback based on outdoor
temperature
NA
For heating and chilled water systems >
300,000 Btu/h, indicate systems are
configured to automatically reset supply water
temperature based upon demand; or exception
taken. If system pump motor hp > 3 hp, also
indicate controls automatically reduce flow by
> 50%.
NA
For chilled water systems (? 300,000 Btu/h,
pump motor hp ? 3 hp) that serve water-
cooled unitary air conditioners, indicate VSD
or staged pumps in chilled water system and
heat rejection loop that reduce pump flow so
that one control valve is nearly wide open, or
to maintain a minimum differential pressure;
or exception taken
NA
C403.4.2
Boiler sequencing
Indicate automatic controls that sequence
operation of multiple boilers
NA
C403.4.6
Hot gas bypass
For cooling equipment with hot gas bypass,
limitation
provide either multiple step unloading or
continuous capacity modulation; indicate
bypass capacity per Table C403.4.6
NA
C403.4.2.2
Two -pipe changeover
Indicate changeover deadband (min 15°F),
systems
heating / cooling mode scheduling and
changeover temperature range (limit 30°F)
NA
C403.4.2.6
Chiller / boiler plant
Indicate controls are configured to
pump isolation
automatically reduce overall plant flow and
shut-off flow through individual chillers and
boilers when not in use
NA
C403.2.13.1.
Heat rejection
For cooling towers with fan motors > 7.5 hp,
1
equipment - variable
indicate VSD and method to adjust fan speed
C403.4.3.1.1
flow control
(adjusted based on leaving fluid temperature
C403.4.3.1.2
or condenser temperature / pressure of heat
rejection device)
NA
For multiple -cell heat rejection equipment
with VSD, indicate controls that ramp all fans
in unison
NA
C403.4.3.3
Heat rejection
Indicate open -circuit cooling towers with
equipment - cooling
multiple pumps or VSD control are designed
tower flow turndown
so all cells can be run in parallel
Page 11117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
NA
C403.4.2.3.1
Water loop heat
Indicate capability of central equipment to
pump - deadband
provide minimum 20°F water supply
temperature deadband between heat rejection
and heat addition modes; or exception taken
NA
C403.4.2.3.2.
Water loop heat
Indicate type of cooling tower (open- or
1
pump - heat rejection
closed-circuit) in equipment schedule;
equipment, Zone 4
indicate method used to limit system heat loss
when heat rejection is not needed
NA
C403.4.2.3.2.
Water loop heat
For open- or closed-circuit cooling towers,
2
pump - heat rejection
provide a heat exchanger that separates the
equipment, Zone 5
cooling tower and heat pump loop
NA
C403.4.2.3.3
Water loop heat
For hydronic heat pump systems with total
pump - isolation
system power > 10 hp, indicate 2-way
valves
isolation valves on each heat pump and
variable flow system control
DEDICATED OUTDOOR AIR SYSTEMS (DOAS)
NA
C403.6
Dedicated outdoor air
For buildings with office, retail, education,
NA
C403.6.3
systems
library and fire station spaces, identify these
spaces on plans; indicate that ventilation air in
each occupied space is provided via a DOAS
system; or document compliance with
C403.6.3 Impracticality; or exception taken
(buildings complying with C402.4.1.4 or
C406.6 may not utilize exceptions)
YES
C403.6.1
Energy recovery
For all DOAS systems, indicate exhaust air
M5.0
ventilation with
ER method; or exception taken with
DOAS
supporting calculations. Indicate ER rated
effectiveness that increases OSA enthalpy by
> 50% based on delta between OSA and
return air enthalpies at design conditions.
YES
C403.6.2
Heating / cooling
Indicate equipment associated with the
SPECS
system
delivery of zone level heating and cooling
controls with DOAS
(fans, hydronic pumps, primary air dampers,
etc) are configured to shut off, and central
equipment is configured to turn down, when
there is no call for heating or cooling in the
zone they serve
NA
If applying Exception to heating / cooling fans
NA
used for air mixing in the space during
deadband periods, include fan watts per cfm
in equipment schedule
NA
C402.4.1.4
Increased prescriptive
Indicate that all occupied, conditioned spaces
C403.6
maximum vertical
are served by a DOAS per C403.6
fenestration area with
DOAS
ADDITIONAL EFFICIENCY PACKAGE OPTION, DEDICATED OUTSIDE AIR SYSTEMS (DOAS)
NA
C406.6
Building provided
To comply with additional efficiency package
LESS THAN 90%
with DOAS
option, indicate that 90% or more of all
occupied, conditioned spaces are served by a
DOAS per C403.6
MULTIPLE ZONE AIR SYSTEMS
Page 12117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
YES
C403.4.4
Air systems serving
Identify supply air systems serving multiple
M2.1-M2.6
multiple zones
zones and the zones they serve on plans;
indicate whether system is VAV and method
of primary air control; or provide supporting
documentation for applied exception to VAV
YES
C403.4.4
VAV systems serving
Provide equipment schedules on plans or
M5.0
multiple zones
MECH-EQ form that list all VAV air
terminals and types
NA
For each air terminal include: maximum
NA
airflow rates for primary supply air during
zone peak heating and zone peak cooling;
maximum airflow during reheating, recooling
or mixing; minimum airflow rate to maintain
required ventilation, and the basis for these
values; if IMC or ASHRAE 62.1 multiple
zone equation is basis for minimum flow
rates, provide calculation on plans
YES
C403.4.4.1
Single duct VAV
Indicate single duct terminal units are
M2.1-M2.6
terminal units
configured to reduce primary supply air
before reheating or recooling
NA
C403.4.4.2
Dual duct systems -
For systems with separate warm air and cool
NA
terminal units
air ducts, indicate terminal units are
configured to reduce the flow from one duct
to minimum before mixing with air from the
other duct
NA
C403.4.1.1
VAV system static
Indicate locations of duct static pressure
NA
C403.4.1.2
pressure sensors -
sensors on plans; include at least one sensor
sensors and DDC set
per major duct branch; verify controller
points
setpoint pressure at each sensor is <_ 1.2 inch
w.g.
NA
For systems with zone level DDC, indicate
NA
controls are configured to monitor zone
damper positions and reset static pressure
setpoint based on the zone requiring most
pressure; include control logic that
automatically detects and generates an alarm
if any zone excessively drives reset logic, and
allows building operators to exclude zones
from reset logic
NA
C403.4.4.3
Multiple -zone VAV
For systems with zone level DDC controls,
NA
system ventilation
indicate controls are configured to
optimization controls
automatically reduce outdoor airflow in
response to changes in system ventilation
efficiency; or exception taken
YES
C403.4.4.4
VAV system supply
Indicate controls automatically reset supply
SPECS
air reset
air temperature in response to building loads
or outdoor air temperature; or exception taken
MULTIPLE ZONE HVAC SYSTEMS, HIGH EFFICIENCY VAV - REQUIRED FOR SYSTEMS UTILIZING C403.6 DOAS EXCEPTION 2,
MUST COMPLY WITH ALL 16 PROVISIONS
NA
C403.7,
Air economizer
Indicate system is configured for 100% air
Item 1
economizer operation and complies with all
related economizer requirements per C403.3
(without economizer exceptions)
Page 13117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
NA
C403.7,
Direct digital controls
Provide DDC controls for all components of
Item 2
(DDC)
system; identify all DDC system input / output
control points; indicate capability for trending
and graphical display
NA
C403.7,
Outdoor airflow
For systems with minimum OSA > 2,500 cfm,
Item 3
measurement and
indicate outdoor airflow monitoring station
reduction
that measures OSA intake under all load
conditions; indicate control sequence that
increases or reduces system OSA cfm based
on VAV terminal feedback of ventilation
efficiency (per C403.4.4.3 without
exceptions) or DCV (per C403.2.6.2)
NA
C403.7,
Supply airflow
For systems with minimum OSA > 2,500 cfm,
Item 4
measurement
indicate supply airflow monitoring station
capable of measuring supply air delivered to
VAV terminals under all load conditions
NA
C403.7,
Zone isolation and
Verify maximum area served by a single
Item 5
maximum area served
HEVAV system is ? 50,000 sf, or one entire
floor, whichever is greater; in addition if a
system serves > 25,000 sf, that includes areas
that are expected to be occupied non -
simultaneously, indicate zone isolation
controls per C403.2.4.4
NA
C403.7,
Interior / exterior
Verify that VAV terminals serving interior
Item 6
zone design supply air
cooling driven loads are sized per design
temperature
supply air temperature that is 5°F higher than
VAV terminals serving exterior zones
NA
C403.7,
Maximum air
Identify air terminals with minimum primary
Item 7
terminal inlet velocity
airflow setpoints > 50% of maximum setpoint
in equipment schedule or MECH-EQ form;
indicate air terminal inlet velocity does not
exceed 900 fpm
NA
C403.7,
Sequence of
Indicate DDC system sequences of operation
Item 8
operation
are designed and configured per ASHRAE
GPC 36
NA
C403.7,
Maximum allowable
Verify fan system bhp is <_ 90% of the bhp
Item 9
system brake
limit per Option 2 equation in Table
horsepower
C403.2.11.1(1), provide MECH-FANSYS
form for each system
NA
C403.7,
Fan -powered terminal
Indicate all series and parallel terminal fans
Item 10
unit motor and
have electronically commutated motors;
control
indicate DDC control system is configured to
vary air terminal fan speed as a function of
the load; indicate fan speed during periods of
low heating, low cooling, or ventilation only is
< 66% of peak design air flow or provide
supporting documentation for applied
exception
NA
C403.7,
Application of single
Indicate VAV terminal types on plans; verify
Item 11
duct and fan -powered
fan -powered terminal units only serve
terminal units
perimeter zones with envelope loads; verify all
other zones are served by single duct terminal
units
Page 14117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
NA
C403.7,
Fan -powered terminal
Indicate DDC controls are configured to
Item 12
unit primary air reset
automatically reset the primary supply air cfm
setpoint of all fan -powered terminal units to
the minimum required to maintain ventilation
during occupied heating or deadband, based
upon the VAV air handling unit OSA
ventilation fraction
NA
C403.7,
High occupancy
For spaces > 150 sf with occupant density >_
Item 13
space controls
25 people / 1000 sf, indicate space is served
by a dedicated terminal unit with DCV control
that resets terminal unit ventilation setpoint;
also indicate occupancy sensor control that
automatically reduces minimum ventilation to
zero and sets back room heating and cooling
setpoints by >_ 5°F
NA
C403.7,
Dedicated HVAC
Item 14
systems
NA
C403.7,
Central plant
Item 15
efficiency
NA
NA
NA
C403.7,
Fault detection and
Item 16
diagnostics
HVAC EQUIPMENT ENERGY USE METERING
For server, electronic equipment, telecom or
similar spaces with cooling loads > 5 W/sf,
indicate spaces are served by independent
HVAC systems that are separate from
HPVAV systems serving rest of building;
indicate dedicated HVAC systems have air
economizer controls or energy recovery per
C403.3 Exception 9
Indicate whether systems are served by a high
efficiency heating water plant, or a high
efficiency chilled water plant
If complying via high efficiency heating water
plant: Indicate all VAV terminals have
hydronic heating coils served by heating water
system with either gas -fired boiler(s) with
thermal efficiency Z 90%, air -to -water heat
pumps, or heat recovery chillers
If complying via high efficiency chilled water
plant: Indicate all VAV air handlers have
cooling coils served by chillers with rated
IPLV efficiency that exceeds WSEC listed
IPLV by at least 25% per Table C403.2.3(7)
(note water-cooled IPLV is max, all others are
min); indicate smallest chiller or compressor
in plant is <_ 20% of total plant capacity, or
provide thermal storage sized for <_ 20% of
total plant capacity
Indicate DDC system includes a fault
detection and diagnostics (FDD) system
configured to monitor operation and provide
fault reporting of required parameters for all
VAV air handlers and VAV air terminal units
in the HPVAV system
Page 15117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
NA
C409.1
HVAC equipment
C409.3.1
energy use metering -
New Construction
and Large Additions
NA
C409.3.1
HVAC equipment
C409.5.1
energy use metering -
Alterations
For new buildings and additions > 50,000 sf, NA
verify energy use metering of all equipment
used to provide space heating and cooling,
dehumidification and ventilation will be
provided per C409; indicate equipment
eligible for exception
For new and replacement systems in buildings
that were constructed subject to the
requirements of this section, verify energy use
metering of all new and replacement
equipment used to provide space heating and
cooling, dehumidification and ventilation will
be provided per C409; indicate equipment
eligible for exception
NA
C409.3.1
HVAC equipment
For new systems in additions of any size to
C409.5.1
energy use metering -
buildings that were constructed subject to the
Small Additions
requirements of this section, verify energy use
metering of all new and replacement
equipment used to provide space heating and
cooling, dehumidification and ventilation will
be provided per C409; indicate equipment
eligible for exception
DOCUMENTATION AND SYSTEM SPECIFIC REQUIREMENT TO SUPPORT COMMISSIONING
YES
C408.2
Scope of mechanical
Indicate that all mechanical systems,
SPECS
systems
equipment, and controls for which the WSEC
commissioning
requires control functions and / or
configuration to perform specific functions
are required to be commissioned
YES For buildings with ? 240,000 Btu/h total SPECS
output cooling capacity or ? 300,000 Btu/h
total output heating capacity, indicate that all
mechanical systems regardless of individual
capacity are required to be commissioned; or
provide building heating / cooling capacity
calculation demonstrating eligibility for
exception
YES
C403.2.10
C408.1.1
C408.1.2
C408.1.4.2
C103.6
Commissioning
requirements in
construction
documents
Indicate in plans and specifications that Cx
per C408 is required for all applicable
mechanical systems
SPECS
YES
Include general summary with at a minimum
SPECS
of Items 1 thru 4 of the Cx plan per C408.1.2
including: narrative description of activities,
responsibilities of the Cx team, schedule of
activities including verification of project
close out documentation per C103.6, and
conflict of interest plan (if required)
YES
Include in general summary that a Cx project
SPECS
report or Compliance Checklist (Figure
C408.1.4.2) shall be completed by the
Certified Cx Professional and provided to the
owner prior to the final mechanical
inspection.
Page 16117
2015 WSEC Requirements for Commercial Buildings including Group R2, R3 & R4 over 3 stories & all R1 -- Administered by @2022 NEEA, All rights reserved
The following information is necessary to check a mechanical permit application for compliance with the mechanical systems and equipment requirements in the
Washington State Energy Code, Commercial Provisions.
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
NA
C408.2.2
Air system and
Indicate in plans that air and fluid flow rates
NA
hydronic system
shall be tested and balanced within the
balancing
tolerances defined in the specifications;
indicate systems shall be balanced in a manner
to first minimize throttling losses, then
adjusted to meet design flow conditions
YES
C408.2.2.1
Air system balancing
Indicate devices that provide the capability to
SPECS
devices
balance all supply air outlets, zone terminals
and air handling equipment requiring system
balancing
NA
C408.2.2.2
Hydronic system
Indicate devices that provide the capability to
balancing devices
isolate, balance and measure flow across all
hydronic equipment requiring system
balancing including heating and cooling coils
and pumps
YES
C408.2.3
Functional
Identify in plans and specifications the
SPECS
performance testing
intended operation of all equipment and
criteria
controls during all modes of operation,
including interfacing between new and
existing -to -remain systems
PROJECT CLOSE OUT DOCUMENTATION
YES
C103.6
Documentation and
Indicate in plans that project close out
SPECS
project close out
documentation and training of building
submittal
operations personnel is required for all
requirements
mechanical components, equipment and
systems governed by this code; indicate close
out documentation shall include: record
documents, O&M manuals, applicable WSEC
compliance forms and calculations
Page 17/17