Loading...
SEE REV1and2 APPROVED- PLN RAINBOW BLD2021-0756+Mechanical_Plan+3.11.2022_2.07.33_PM+2733189 - APPROVED21AMA01, Anthology of Edmonds BASED ONIMC2015 OSA & LOAD CALCULATION TABLE COMMERCIAL VENTILATION SECTION NOTE: THIS INFORMATION IS FOR CALCULATION & CODE REVIEW ONLY. REFER TO EQUIPMENT SCHEDULES& PLANS FOR EXACT UNIT OPERATION AND BALANCING RQUIREMENTS. EQUIPMENT SERVING SPACE ROOM NAME & NUMBER AREA (SF) TOTAL COOLING (MBH) SENSIBLE OGLING (MBH TOTAL HEATING (MBH) TOTAL OUTSIDE AIR CFM TOTAL EXHAUST AIR CFM ROOM TYPE DEFAULT OCCUPANCY CFM / PERSON OCCUPANT CFM CFM / SF SF CFM SUBTOT CFM AIR DISTRIBUTION CONFIGURATION Ez DS-1 P-Maint 233 18 Storage: Warehouse 0 0 0 0.06 13.98 14 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 233 18 DS-2 P-Laundry 399 105 Dry cleaners,Laundry: Coin -operated laundries 7,98 7.5 59.85 0.06 23.94 gq warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 399 105 DS-3 P-MDF 90 8 Storage: Warehouse 0 0 0 0.06 5.4 6 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 90 8 DS-4 P-Electrical 162 13 Storage: Warehouse 0 0 0 0.06 9.72 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 162 13 EWH-2 P-Vestibule 1401 12 Public Spaces: Corridors 0 0 0 0.06 8.4 9 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 140 12 EF-G1 P-Generator 300 23 Storage: Warehouse 0 0 0 0.06 18 18 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 300 23 EF-P1 P-Parking 21309 1599 Storage: Warehouse 0 0 0 0.06 1279 1279 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 21309 1599 P-Corridor 127 10 Public Spaces: Corridors 0 0 0 0.06 7.62 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 P-Meth 175 14 Storage: Warehouse 0 0 01 0.06 10.5 11 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 P-Boiler 298 23 Storage: Warehouse 01 0 0 0.06 17.88 18 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 P-Stor 230 181 IIStorage: Warehouse 01 01 01 0.06 13.8 14 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 830 1 65 FC-1A 1-Great Room 614 24.7 24.7 54.8 219 Hotels, Motels, Resorts, Dormitories: Lobbies/prefunction 18.42 7.5 138.15 0.06 36.84 175 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Bistro 995 319 Food and Beverage Service: Dining rooms 10 7.5 75 0.18 179.1 255 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Mail 266 20 Public Spaces: Corridors 0 0 0 0.06 15.96 16 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Vest 111 9 Public Spaces: Corridors 0 0 0 0.06 6.66 7 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Elev Lobby 285 23 Public Spaces: Corridors 0 0 0 0.06 17.1 18 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-RR 264 0 0 0 0 0 0 0 warm air from ceiling >= 15°F above s.t., ceiling return 0,8 Total 2535 590 FC-1B 1-Reception 168 19.4 19.4 24.1 45 Office Buildings: Reception areas 5.04 5 25.2 0.06 10.08 36 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Business Office Mgr 111 13 Office Buildings: Office space 0.555 5 2.775 0.06 6.66 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Area RR's 115 13 Office Buildings: Office space 0.575 51 2.875 0.06 6.91 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Exec Dir 132 15 Office Buildings: Office space 0.66 5 3.3 0.06 7.92 12 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Discovery/Conf 190 53 Office Buildings: Conference rooms 6 5 30 0.06 11.4 42 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Sales Mgr 109 13 Office Buildings: Office space 0.545 5 2.725 0.06 6.54 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Sales Mgr (s) 120 14 Office Buildings: Office space 0.6 5 3 0.06 7.2 11 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Employee Lounge 339 37 Office Buildings: Office space 1.695 5 8.475 0.06 20.34 29 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Admin 133 10 Public Spaces: Corridors 0 0 0 0.06 7.98 8 warm air from ceiling >= 15°F above s.t., ceiling return 0,8 1-Corridor 88 8 Public Spaces: Corridors 0 0 0 0.06 5.28 6 warm air from ceiling >= 15°F above s.t., ceiling return p,g Total 1505 221 FC-1C,1D 1-Dining 1443 25 25 57.1 888 Food and Beverage Service: Dining rooms 60 7.5 450 0.18 259.7 710 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 1443 888 FC-1E 1-Family Room 310 4.3 4.3 6.7 74 Office Buildings: Conference rooms 8 5 40 0.06 18.6 59 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 310 74 FC-1F 1-Kitchen 951 12.5 12.5 8.2 1 102 Office Buildings: Office space 4.755 5 23.775 0.06 57.06 81 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Beverage Station 154 18 Office Buildings: Office space 0.77 5 3.85 0.06 9.24 14 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Office 87 10 Office Buildings: Office space 0.435 5 2.175 0.06 5.22 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Dry Storage 184 15 Storage: Warehouse 0 0 0 0.06 11.04 12 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Trash Corridor 78 7 Public Spaces: Corridors 0 0 0 0.06 4.68 5 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Trash 621 5 Storage: Warehouse 0 0 0 0.06 3.72 q warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 1516 157 EWH-1 1-Riser 127 10 Storage: Warehouse 0 0 0 0.06 7.62 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 1705 172 1-Stor 175 14 Storage: Warehouse 0 0 0 0.06 10.5 11 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Trash Collection 596 45 Storage: Warehouse 0 0 0 0.061 35.76 36 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 1-Meth 95 8 Storage: Warehouse 0 0 0 0.06 5.7 6 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 866 67 EF-P2 1-Parking + Ramp 15101 1134 Storage: Warehouse 0 0 0 0.06 906.1 907 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 15101 1134 UH-1 1-Receiving 240 19 Storage: Warehouse 0 01 01 0.06 14.41 15 warm air from ceiling >= 15°F above s.t., ceiling return 0,8 Total 1 2851 23 FC-2 2-Corrdior/Elev Lobby 3486 18.5 18.5 18.6 263 Public Spaces: Corridors 0 0 0 0.06 209.2 210 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 2-Stor W 269 22 Storage: Warehouse 0 0 0 0.06 16.14 17 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 2-IDF/Elec W 82 7 Storage: Warehouse 0 0 0 0.06 4.92 5 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 2-Elec/IDF E 156 13 Storage: Warehouse 0 0 0 0.06 9.36 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 2-Stor E 131 10 Storage: Warehouse 0 0 0 0.06 7.86 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 2-Janitor 21 3 Storage: Warehouse 01 01 0 0.06 1.26 2 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 2-Trash 43 41 1 Storage: Warehouse 01 01 01 0.061 2.581 3 1 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total1 1 41881 1 1 1 322 FC-3 3-Corrdior/Elev Lobby 3486 18.5 18.5 18.6 263 Public Spaces: Corridors 0 0 0 0.06 209.2 210 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 3-Stor W 269 22 Storage: Warehouse 0 0 0 0.06 16.14 17 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 3-IDF W 82 7 Storage: Warehouse 0 0 0 0.06 4.92 5 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 3-Elec/IDF E 156 13 Storage: Warehouse 0 0 0 0.06 9.36 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 3-Stor E 131 10 Storage: Warehouse 0 0 0 0.06 7.86 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 3-Janitor 21 31 IIStorage: Warehouse 01 01 0 0.06 1.26 2 warm air from ceiling >= 15°F above s.t., ceiling return 0,8 3-Trash 43 4 Storage: Warehouse 0 0 0 0.06 2.58 3 warm a ir from ceiling >= 15°F above s.t., ceiling return p,g Total 4188 322 FC-4 4-Corrdior/Elev Lobby 3486 18.5 18.5 18.6 263 Public Spaces: Corridors 0 0 0 0.06 209.2 210 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 4-Stor W 269 22 Storage: Warehouse 0 0 0 0.06 16.14 17 warm air from ceiling >= 15°F above s.t., ceiling return 0,8 4-IDF W 82 7 Storage: Warehouse 0 0 0 0.06 4.92 5 warm air from ceiling >= 1S°F above s.t., ceiling return 0.8 4-Elec/IDF E 156 13 Storage: Warehouse 0 0 0 0.06 9.36 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 4-Stor E 131 10 Storage: Warehouse 0 0 0 0.06 7.86 8 warm air from ceiling >= 15°F above s.t., ceiling return 0,8 4-Janitor 21 3 Storage: Warehouse 0 0 0 0.06 1.26 2 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 4-Tra7h 43 41 1 Storage: Warehouse 01 01 01 0.061 2.581 3 1 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total1 1 41881 322 FC-5 5-Corrdior/Elev Lobby 3486 18.5 18.5 18.6 263 Public Spaces: Corridors 0 0 0 0.06 209.2 210 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-Stor W 269 22 Storage: Warehouse 0 0 0 0.06 16.14 17 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-IDF W 82 7 Storage: Warehouse 0 0 0 0.06 4.92 5 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-Elec/IDF E 156 13 Storage: Warehouse 0 0 0 0.06 9.36 10 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-Stor E 131 10 Storage: Warehouse 0 0 0 0.06 7.86 8 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-Janitor 21 3 Storage: Warehouse 0 0 0 0.06 1.26 2 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 5-Trash 43 4 Storage: Warehouse 01 01 01 0.061 2.581 3 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total1 41881 1 322 FC-6A 5-Salon 344 4.3 4.3 6.7 268 Specialty shops: Beauty and nail salons 8.6 20 172 0.12 41.28 214 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 344 268 FC-613 6-Corrdior/Elev Lobby 3179 15.5 15.5 24.7 239 Public Spaces: Corridors 0 0 0 0.06 190.7 191 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 6-IDF W 29 3 Storage: Warehouse 0 0 0 0.06 1.74 2 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 6-Elec/IDF E 111 9 Storage: Warehouse 0 0 0 0.06 6.66 7 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 6-RR's 170 0 0 0 0 0 0 0 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 6-Trash 431 4 Storage: Warehouse 0 0 0 0.06 2.58 3 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 3532 255 RTU-1 6-Fitness 729 15.1 12.2 18.2 305 Sports and Amusement: Health club/aerobics room 10 20 200 0.06 43.74 244 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 1 729 305 RTU-2 6-Theater/Community 1035 16.9 15 1 19.8 267 Hotels, Motels, Resorts, Dormitories: Multipurpose assembly 30 5 1501 0.06 62.1 213 warm air from ceiling >= 15°F above s.t., ceiling return 0.8 Total 1035 2671 MECHANICAL COMPLIANCE SUMMARY 2015 WSEC Compliance Forms for Commercial Buildings including Group R-. R3 & R4 o%er 3 stones and all RI Administered by: i'2022 NEEA, All rights reser%ed Project & Applicant Information Project Title Anthology of Edmonds - 2015 WSEC For Building Department Use: Date: Feb 09, 2022 Project Address 212W 72nd Ave W Edmonds, WA 98026 Applicant Name Aaron Prough Applicant Phone 208-493.0027 Applicant Email aprough(�1deengineering.nel For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport, a waenergycodes.com General OccupancJ All Group R - R2, R3 & R4 over 3 stories and all RI Ceneral Building Use'I) pe Multifamily/Residential Building Cond. Floor Area 164,000 General Project Types New Building New Building or Addition Mechanical ScopeMultiple Single Zonn Systems & Equipment Zone Systems &Equipment Alteration Mechanical Scope Project Cond. Floor Area 164,000 Floors Above Grade 6 Compliance Method I Cum linnet Method I - Gcncral Mechanical Project Description This will be a 7 story assisted living facility with 1 floor of parking below grade. Mechanical Compliance Scope and M1lethod Project TVp Mechanical Scope Economber Exception(s) A lied? DOAS Ventilation Prmided? Higher Equipment Efficiency Option Applied? P pp Equipment Efficiency Compliance Verification P COMPLIES COMPLIES New Building Single Zone Systems & Equipment No No YLs New Building Multiple Zone Systems & Equipment No Yes Yes Additional Efficiency Credits Included (AEC) Higher equipment efficiency and fan FEG Dedicated outside air system (DOHS) option Does building include occupancy classifications requiring DOAS? Yes Does project include DOAS equipment? Yes Based on project scope do TSPR requirements apply? No Do all sv stems comply with Appendix D standard reference design or qualify for an exception to FSPR? No Scope & Space Conditioning NEW BUILDING - SINGLE ZONE SYSTEMS & EQUIPMENT Com Scope & Space Conditioning NEW BUILDING - MULTIPLE ZONE SYSTEMS & EQUIPMENT Compliance Verification MECHANICAL LEGEND EQUIPMENT ® SUPPLY DIFFUSER dJ J J J J J FLEXIBLE DUCTWORK z RETURN GRILLE LINED DUCTWORK z EXHAUST GRILLE DEMO ROUND DUCTWORK BREAK OT THERMOSTAT TS TEMPERATURE SENSOR DUCTWORK BREAK SD SMOKE DETECTOR ❑ � � DUCTWORK RISE CO CO2 SENSOR DUCTWORK DROP EZE& MOTORIZED DAMPER SPIN -IN SUPPLY (WITH VOLUME BAROMETRIC DAMPER W- - FLODAMPER) MANUAL VOLUME DAMPER. SPIN -IN RETURN/EXHAUST (WITH VOLUME DAMPER) FS�E: COMBINATION SMOKE/FIRE DAMPER 45° SQUARE DUCT TAKE -OFF S RA FROM SQUARE DUCT F-� FIRE DAMPER �� 45° ROUND DUCT TAKE -OFF # S RA FROM SQUARE DUCT EQUIPMENT CALLOUT # 45° ROUND DUCT TAKE -OFF # 5�- RA FROM ROUND DUCT DETAIL CALLOUT TURNING VANE O TEMPERATURE GAUGE MITERED CORNER POINT OF CONNECTION RADIUS ELBOW 4I4- INTAKE OR EXHAUST DIRECTION OF AIRFLOW ABBREVIATIONS & DESCRIPTIONS AC AIR CONDITIONING HVAC HEATING, VENTILATING, AIR CONDITIONING AFF ABOVE FINISHED FLOOR KES KITCHEN EQUIPMENT SUPPLIER AHU AIR HANDLING UNIT KW KILOWATT BTU BRITISH THERMAL UNITS KWH KILOWATT HOUR BTUH BTU'S PER HOUR LAT LEAVING AIR TEMPERATURE CA COMBUSTION AIR CC COOLING COIL MAX MAXIMUM CFM CAP FOR FUTURE MCA MINIMUM CIRCUIT AMPS CFM CUBIC FEET PER MINUTE MOCP MAXIMUM OVERCURRENT PROTECTION CHILLED WATER RETURN MI MIN N MINIMUM CCHILLED WATER SUPPLY NC NOISE CRITERIA CLG LG CEILING NFPA NATIONAL FIRE PROTECTION ASSOCIATION CW COLD WATER NTS NOT TO SCALE DEG DEGREE OSA OUTSIDE AIR DIA DIAMETER PD PRESSURE DROP DB DRY BULB TEMPERATURE PH PHASE EA EXHAUST AIR PRV PRESSURE REDUCING VALVE EAT ENTERING AIR TEMPERATURE RA RETURN AIR RPM REVOLUTIONS PER MINUTE EER ENERGY EFFICIENCY RATIO RTU ROOFTOP UNIT ESP EXTERNAL STATIC PRESSURE SA SUPPLY AIR EWT ENTERING WATER TEMPERATURE SEER SEASONAL ENERGY EFFICIENCY RATIO FCO FLOOR CLEANOUT SFD/FSD COMBINATION SMOKE/FIRE DAMPER FD FIRE DAMPER SP STATIC PRESSURE FLA FULL LOAD AMPS SYM SYMBOL FLR FLOOR T&P TEMPERATURE AND PRESSURE FPM FEET PER MINUTE TEMP TEMPERATURE FT FEET TYP TYPICAL GA GAUGE GCO GRADE CLEANOUT UMC UNIFORM MECHANICAL CODE GPM GALLONS PER MINUTE UPC UNIFORM PLUMBING CODE HC HEATING COIL VTR VENT THROUGH ROOF HP HORSEPOWER V VOLTS IECC INTERNATIONAL ENERGY WB WET BULB CONSERVATION CODE W/ WITH GENERAL NOTES 1. PER WSEC C409.3.1, PROVIDE ENERGY USE MONITORING OF ALL EQUIPMENT USED TO PROVIDE HEATING, COOLING AND VENTILATION OF OCCUPIED SPACES. 2. SEE MECHANICAL SPECIFICATION SECTION 230593 (TESTING, ADJUSTING, BALANCING FOR HVAC) FOR COMMISSIONING REQUIREMENTS PER WSEC C408. 3. PER WSEC C103.6, MECHANICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY CLOSE OUT DOCUMENTS AND TRAINING OF OPERATIONS PERSONEL WHICH APPLY TO ANY MECHANICAL COMPONENTS, EQUIPMENT, AND SYSTEMS GOVERNED BY THE WSEC. 4. ALL DUCTWORK SHALL BE CONSTRUCTED AND SEALED PER 2015 IMC. ALL DUCTWORK SHALL BE LOW PRESSURE UNLESS NOTED OTHERWISE, PER WSEC C403.2.8.1. 5. SEE MECHANICAL SPECIFICATION SECTION 230700 (HVAC INSULATION) FOR DUCTWORK AND PIPING INSULATION REQUIRMENTS. HVAC SHEET LIST SHEET NUMBER SHEET NAME M0.0 HVAC COVER SHEET M2.0 HVAC PLAN - PARKING M2.1 HVAC PLAN - FIRST FLOOR M2.2 HVAC PLAN - SECOND FLOOR M2.3 HVAC PLAN - THIRD FLOOR M2.4 HVAC PLAN - FOURTH FLOOR M2.5 HVAC PLAN - FIFTH FLOOR M2.6 HVAC PLAN - SIXTH FLOOR M2.7 HVAC PLAN - ROOF M4.0 HVAC PLAN - ENLARGED UNITS M4.1 HVAC PLAN - ENLARGED UNITS M5.0 HVAC SCHEDULES M6.0 HVAC DETAILS M6.1 HVAC DETAILS M6.2 HVAC KITCHEN DETAILS M6.3 HVAC KITCHEN DETAILS M6.4 HVAC KITCHEN DETAILS M6.5 HVAC KITCHEN DETAILS M6.6 HVAC KITCHEN DETAILS M6.7 HVAC KITCHEN DETAILS M6.8 HVAC KITCHEN DETAILS M6.9 HVAC KITCHEN DETAILS M6.10 HVAC KITCHEN DETAILS M6.11 HVAC KITCHEN DETAILS M6.12 HVAC KITCHEN DETAILS M6.13 HVAC KITCHEN DETAILS M6.14 HVAC KITCHEN DETAILS �O OF WASk 41741 'GISTER�� \� FSS/oNAL �G 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.dcengineering.net Phone:208.288.2181 Project:21 AMA01 (D 04 O 00 0 Z z 0 = Q W o I.L � 0 0 LLJ 0 ; > J Q J _� 0 -0 O N 0 z m w Z N U (�I U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 B 10-28-21 CITY COMMENTS #02 C 02-08-22 CITY COMMENTS #03 HVAC COVER SHEET GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 NUMBER MO.0 7 1 HVAC PLAN - PARKING SCALE: 1/8" = 1'-0" 9 I I I HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED 10 12 13 RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. 0 HVAC KEYNOTES: 1. PROVIDE 18"x18" LOUVER IN DOOR. COORDINATE WITH ARCHITECTURAL. 2. ROUTE 4" DRYER EXHAUST FROM LAUNDRY ROOM TO EXTERIOR WALL. PROVIDE BOOSTER FAN DBF-1 AND DUCT CLEANOUT IN VERTICAL DRYER DUCT. TERMINATE AT EXTERIOR WITH VENT BOX. 3. PROVIDE CO AND NO2 SENSOR AT CEILING FOR PARKING GARAGE EXHAUST FAN (EF-P1) SPEED CONTROL. 4. MOUNT PARKING GARAGE VENTILATION FAN AS HIGH AS POSSIBLE. 5. ROUTE 3" SA�DUCTUP TO FIRE RISER ROOM ABOVE, AND TERMINATE ROXIMATELY 9'-0" AFF. C O OF WA Sk // 41741 (GIs TER���\� FSS/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. w w w. d(e ngin e ering. n e t Phone:208.288.2181 Project:21 AMA01 N CD 00 0') (n Z O a F--- Z z 0= Q 0 W Cn 0 LL 0 O 0 Z > > 10 J Q J 0 C: O N CI-4 0 i Z m I- Q LLJ Z o U aLU Q\ N U REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 E 03-07-22 CITY COMMENTS #05 HVAC PLAN — PARKING GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.0 1 2 3 4 5 6 7 8 9 10 12 13 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I uu w 7 PARKING GARAGE 11039 1 0 1 HVAC PLAN - 1ST FLOOR SCALE: 1/8" = 1'-0" nr nr nr 1E 1 3 SD-1, 12"0 400 CFM I I RG-2, 12"x12" 400 CFM EF 20 K2 6. SD-2, 8" 0 100 CFM HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. 0 HVAC KEYNOTES: 1. 14"x14" OSA UP IN MECHANICAL SHAFT ABOVE. PROVIDE FSD AS REQUIRED AT SHAFT PENETRATION. 2. 22"x20" OSA DUCT UP IN CHASE ABOVE. PROVIDE FIRE/SMOKE DAMPER AT CHASE WALL PENETRATION. 3. 34"x10" GREASE DUCT CONNECTION TO KITCHEN HOOD (BY KES). 4. 24"x12" OSA CONNECTION TO KITCHEN HOOD PLENUM (BY KES). 5. INSTALL GREASE DUCT PER 2015 IMC SECTION 506.3. DUCT SHALL BE MINIMUM GAUGE 18 STAINLESS STEEL. SLOPE DUCT BACK TO KITCHEN HOOD AT 1/4" PER FOOT. PROVIDE CLEANOUTS EVERY 20 FEET, AND WITHIN 10 FEET OF A CHANGE IN DIRECTION OVER 45 DEGREES PER 2015 IMC SECTION 506.3.8. PROVIDE ASTM E2336 APPROVED FYREWRAP ELITE DUCT WRAP OR APPROVED EQUAL. 6. PROVIDE HINGED WALL MOUNT FOR GREASE EXHAUST FAN. 7. PROVIDE FIRE/SMOKE DAMPER AT RATED WALL. PROVIDE ACCESS TO DAMPER. 8. PROVIDE CO AND NO2 SENSOR AT CEILING FOR PARKING GARAGE EXHAUST FAN (EF-P2) SPEED CONTROL. 9. PROVIDE MOTORIZED DAMPER ON THE RETURN AND OUTSIDE AIR DUCTS FOR ECONOMIZER OPERATION. 10. ROUTE 10" EA DUCT FROM TYPE II HOOD TO EXTERIOR WALL. SLOPE DUCT AT 1/4" PER FOOT BACK TO HOOD. 11. ROUTE GENERATOR EXHAUST FLUE TO EXTERIOR WALL AS REQUIRED. 12. SEE KITCHEN EQUIPMENT DRAWINGS FOR ELEVATION VIEW OF COOKLINE EQUIPMENT AND REQUIRED CLEARANCES. 13. PROVIDE STAINLESS STEEL WALL FLASHING THAT EXTENDS 18" MINIMUM IN ALL DIRECTIONS BEYOND THE TYPE 1 HOOD. COORDINATE WITH ARCHITECTURAL AND KITCHEN DRAWINGS. 14. WALL CONSTRUCTION SHALL BE LIMITED COMBUSTABLE TYPE, WITH METAL STUD FRAME AND 5/8" GYPBOARD. COORDINATE WITH ARCHITECTURAL AND KITCHEN DRAWINGS. C O OF WA Sk // I /� 41741 GISTER���\� Fss/oNAL �� 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering. net Phone:208.288.2181 Project:21 AMA01 Q0 N CD 00 O') (n Z O a F--- Z z O= Q 0 W Cn 0 LL 0 O 0 �LLJ Z_ > > 10 J Q J _� O -0 N 0 r` z m F— p LLJ Z ON U ~ Q LU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 B 10-28-21 CITY COMMENTS #02 E 03-07-22 CITY COMMENTS #05 HVAC PLAN — FIRST FLOOR GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.1 HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. 1 2 3 4 5 6 7 8 9 10 12 13 G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. 11 g 4 10 M4.0 M4.0 M4.0 M4.0 1 M4.1 4 M4.1 —OG --(:K) 6 0 t 3 ,s u J v 1 HVAC PLAN - 2ND FLOOR SCALE: 1/8" = V-0" 0 HVAC KEYNOTES: 1. 14"x14" OSA FROM LOWER LEVEL UP TO ROOF. 2. 26"x18" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 3. 14"x16" EA DUCT UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 4. 26"x16" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 5. PROVIDE FIRE/SMOKE DAMPER AT ALL SHAFT WALL/RATED WALL PENETRATIONS WITH ACCESS. 6. MECHANICAL CHASE FOR UNIT VENTING UP TO ROOF. SEE M4.0 FOR ENLARGED PLAN. C O OF WA Sk x/ 41741 GISTER���\� FSS�oNAL �� 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering. net Phone:208.288.2181 Project:21 AMA01 Q0 N CD 00 0') (n Z 0 a F--- Z z 0 Q 0 W Cn 0 LL 0 O 0 Z_ > > 10 J Q J 0 O (N Z m I- C:) LLJ Z o U aLU Q\ N U REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 C 02-08-22 CITY COMMENTS #03 HVAC PLAN — SECOND FLOOR GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.2 HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC 1 2 3 4 5 6 7 8 9 10 12 13 SCHEDULE ON M5.0 FOR DETAIL. 0 HVAC KEYNOTES: 1. 14"x14" OSA FROM LOWER LEVEL UP TO ROOF. 2. 26"x18" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 3. 14"x16" EA DUCT UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 4. 26"x16" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 5. PROVIDE FIRE/SMOKE DAMPER AT ALL SHAFT WALL/RATED WALL PENETRATIONS WITH ACCESS. I I I I I I 6 I I I I I I 3 ,s u J v t"4S 1 HVAC PLAN - 3RD FLOOR " I SCALE: 1/8" = 1'-0" I I I I I I I I I I 7 M4.0 C O OF WA Sk // 41741 GISTER���\� FSS/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering. net Phone:208.288.2181 Project:21 AMA01 Q0 N CD 00 0') (n Z p a F--- Z z_ O= Q W C 0 O 0 0 Z_ > > 10 J Q J O C: O N CI-4 0 i z m LLI Z o U aLU Q\ N U REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 HVAC PLAN — TH I RD FLOOR GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.3 12 M4.0 7 I I I I I I I I 0 1 HVAC PLAN - 4TH FLOOR SCALE: 1/8" = 1'-0" T 9 12 I I I 13 I I I I I I I I 8 M4.0 HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. 0 HVAC KEYNOTES: 1. 14"x14" OSA FROM LOWER LEVEL UP TO ROOF. 2. 26"x18" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 3. 14"x16" EA DUCT UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 4. 26"x16" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 5. PROVIDE FIRE/SMOKE DAMPER AT ALL SHAFT WALL/RATED WALL PENETRATIONS WITH ACCESS. C O OF WA Sk // 41741 GISTER���\� FSS/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering. net Phone:208.288.2181 Project:21 AMA01 Q0 N CD 00 0') (n Z p a F--- Z z 0= Q W C 0 O 0 0 Z_ > > 10 J Q J 0 O N Z m LLI Z o U aLU Q\ N U REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 HVAC PLAN — FOURTH FLOOR GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.4 1 2 3 4 5 6 7 8 9 10 12 13 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I i 1 HVAC PLAN - 5TH FLOOR SCALE: 1/8" = 1'-0" HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. 0 HVAC KEYNOTES: 1. 14"x14" OSA FROM LOWER LEVEL UP TO ROOF. 2. 26"x18" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 3. 14"x16" EA DUCT UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 4. 26"x16" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 5. PROVIDE FIRE/SMOKE DAMPER AT ALL SHAFT WALL/RATED WALL PENETRATIONS WITH ACCESS. C O OF WA Sk // I /� 41741 GISTER���\� Fss/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering. net Phone:208.288.2181 Project:21 AMA01 Q0 N CD 00 0') (n Z 0 a F--- Z z 0= Q 0 W Cn 0 LL 0 O 0 3: (D > > 10 J Q J 0 - O N i Z m I- C:) LLJ Z o U aLU Q\ N U REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 HVAC PLAN — FIFTH FLOOR GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.5 i ) HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED 1 2 3 4 5 6 7 8 9 10 12 13 RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. HVAC KEYNOTES: 1. 14"x14" OSA FROM LOWER LEVEL UP TO ROOF. 2. 26"x18" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. I I I I I I I I I I I 3. 14"x16" EA DUCT UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. 4. 26"x16" OSA UP AND DOWN IN MECHANICAL SHAFT. SEE UPPER AND LOWER HVAC PLANS FOR CONTINUATION. I I I I I I I I I I I 5. PROVIDE FIRE/SMOKE DAMPER AT ALL SHAFT WALL/RATED WALL PENETRATIONS WITH ACCESS. 6. EA DUCT PENETRATION UP THROUGH ROOF. SEAL WEATHER ® ® TIGHT AND TERMINATE WITH VENT CAP AND INSECT SCREEN. ®o o ®Lj o 1003 O J 7. ROUTE 3" EA DUCT DOWN TO PEDICURE CHAIR CONNECTION. SEE ARCHITECTURAL PLANS FOR DETAIL ON SALON EQUIPMENT. SD-2, 8" O 7-1 SD-2, 8" O PROVIDE BALANCE DAMPER IN VERTICAL DUCT, SET TO 50 CFM 200 CFM 200 CFM B MINIMUM PER IMC TABLE 403.3.1.1. � (TYP-6) ® ® 0 8. 18"x12" SA AND 26"x12" RA DUCT DROPS FROM RTU ABOVE. SEE no 'ILL J IL-Cl � IL-B5 ,�, IL-B1 A o EXTERIOR DECK HVAC ROOF PLAN FOR CONTINUATION. I I I I I I I I I I I 6 L = I I I I I I I I I I 0 1 HVAC PLAN - 6TH FLOOR SCALE: 1/8" = 1'-0" - ----(�C) (X) C O OF WA Sk // 41741 GISTER���\� Fss/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering. net Phone:208.288.2181 Project:21 AMA01 N CD 00 0') (n Z 0 a F--- Z z 0 Q 0 W Cn 0 LL 0 O 0 Z_ > > 10 J Q J 0 C: O N CI-4 0 i Z Go LLJ it Z C:) U) aLU Q\ N U REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 B 10-28-21 CITY COMMENTS #02 HVAC PLAN - SIXTH FLOOR GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.6 c c 1 2 3 4 5 6 7 8 0 1 HVAC PLAN - ROOF SCALE: 1/8" = 1'-0" 9 10 12 HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. 0 HVAC KEYNOTES: 13 1. ROUTE DUCT DOWN THROUGH ROOF INTO STAIRWAY. SEAL PENETRATION WEATHER TIGHT. 2. ROUTE DUCT DOWN THROUGH ROOF INTO MECHANICAL CHASE. SEE LOWER FLOORS FOR CONTINUATION. 3. EXHAUST DUCT ROOF PENETRATION. SEE LOWER FLOOR FOR CONTINUATION. 4. PROVIDE CLASS 1 MOTORIZED DAMPER PER WSEC C403.2.4.3. C O 0F WA Sk 41741 �� ��'VR�\) GIST\� Fss/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering. net Phone:208.288.2181 Project:21 AMA01 Q0 N O 00 0') 0 Z z 0= Q 0 W Cn 0 LL 0 O 0 3: z > > 10 J Q J 0 O N CI-4Z 0 m F— p LLl Z ON U ~ Q LU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 A 08-20-21 CITY COMMENTS #01 HVAC PLAN — ROOF GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M2.7 c J J J J 0 0 t 1 HVAC PLAN - I L-A-1 SCALE: 1/4" = 1'-0" g HVAC PLAN - IL-B-2 %J SCALE: 1/4" = V-0" 9 HVAC PLAN - IL-B-5 SCALE: 1/4" = 1'-0" 2 HVAC PLAN - IL-A-1 (TYPE A SCALE: 1/4" = 1'-0" 3 HVAC PLAN - I L-A-2 SCALE: 1/4" = 1'-0" CZ HVAC PLAN - IL-B-2 + DEN V SCALE: 1/4" = 1'-0" ol n HVAC PLAN - IL-B-6 V SCALE: 1/4" = 1'-0" L V 7 SG-1, 12"x6" 150 CFM 4 HVAC PLAN - IL-B-1 SCALE: 1/4" = 1'-0" 17 TA 6.0 2 8"x6" SA SG-1, 12"x6" 150 CFM 1 SG -1, 12"x6" 150 CFM --- T r— — 2 J 4" 0 EA 4 6"0 EA EF 14 L _ EF 8 L _ o REF. 7 HVAC PLAN - IL-B3 I SCALE: 1/4" = 1'-0" 11 HVAC PLAN - IL-C-1 (TYPE A SCALE: 1/4" = 1'-0" HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. HVAC KEYNOTES: 1. VTAC REAR ACCESS PANEL AND RETURN AIR GRILLE. SEE DETAIL 17/M6.0. 2. ROUTE 4" DRYER EXHAUST DUCT IN SOFFIT TO LOUVER AT EXTERIOR WALL. PROVIDE DRYER DUCT FLAP/BACKDRAFT AT TERMINATION WITHOUT ANY SCREENING. 3. ARCHITECT TO PROVIDE 1" UNDERCUT DOOR FOR RETURN AIR PATH. 4. ARCHITECT TO PROVIDE LOUVERED DOOR WITH MINIMUM 100 SQ IN OPEN SPACE. 5. ROUTE 4" EXHAUST DUCT UP IN CHASE TO ROOF. PROVIDE LOW PROFILE ROOF CAP WITHOUT ANY SCREENING. 6. ROUTE 4" EXHAUST DUCT UP IN CHASE TO ROOF. PROVIDE LOW PROFILE ROOF CAP WITH INSECT SCREENING. 7. AT SECOND AND THIRD FLOOR ONLY, PROVIDE FANTECH DEDPV-705 DRYER BOOSTER FAN IN ACCESSIBLE LOCATION. PROVIDE FANTECH DBLT42 LINT TRAP PRIOR TO BOOSTER FAN. 8. IN ROOMS 225 AND 325 ONLY, ROUTE EXHAUST UP IN CHASE TO ROOF, SAME AS UNIT TYPE IL-B2+DEN. SEE 6/M4.0. 8 HVAC PLAN - IL-B3 (TYPE A) SCALE: 1/4" = 1'-0" ol r) HVAC PLAN - I L-C-2 SCALE: 1/4" = 1'-0" C O OF WA Sk // 41741 ISTER���\� Fss/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering. net Phone:208.288.2181 Project:21 AMA01 N O 00 0') Z o 0 Z z 0 Q 0 3: W U) 0 O 0 0 Z > > 10 J Q J 0 O N f` Z m I- Q LLJ Z o U Q LU N U a REVISION DATE REASON FOR ISSUE 4 01-03-22 ADDENDUM #03 A 08-20-21 CITY COMMENTS #01 B 10-28-21 CITY COMMENTS #02 C 02-08-22 CITY COMMENTS #03 HVAC PLAN - ENLARGED UNITS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M4.0 0 1 HVAC PLAN - IL-C-3 SCALE: 1/4" = V-0" 4"Oi FA 4 HVAC PLAN - I L-C-5 (TYPE A SCALE: 1/4" = 1'-0" 0 HVAC PLAN - I L-C-4 SCALE: 1/4" = 1'-0" g HVAC PLAN - I L-B5 ALT ♦.i SCALE: 1/4" = 1'-0" CZ HVAC PLAN - I L-B6 ALT V SCALE: 1/4" = 1'-0" Q HVAC PLAN - IL-C-5 SCALE: 1/4" = V-0" HVAC GENERAL NOTES: G1. CONTRACTOR TO COORDINATE ALL EQUIPMENT LOCATIONS AND ROOF PENETRATIONS WITHIN THE SCOPE OF THIS PROJECT. PLUMBING VENTS, REGULATORS VENTS, FLUES, AND EXHAUST AIR OUTLETS TO BE KEPT A MINIMUM OF 10' AWAY FROM OUTSIDE AIR INTAKE LOCATIONS. G2. ALL SUPPLY, RETURN, AND OUTSIDE AIR DUCT TO BE INSULATED PER 2015 WSEC. G3. CONDUIT AND J-BOXES SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, THERMOSTATS AND WIRING SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. G4. RESIDENTIAL RANGE HOODS SHALL BE LISTED AND LABELED RECIRCULATION HOODS AND SHALL NOT EXHAUST TO EXTERIOR UNDER 2015 IMC SECTION 501.3, EXCEPTION #3. RESIDENT SUITE HVAC UNITS UTILIZE MECHANICAL VENTILATION. SEE VTAC SCHEDULE ON M5.0 FOR DETAIL. HVAC KEYNOTES: 1. VTAC REAR ACCESS PANEL AND RETURN AIR GRILLE. SEE DETAIL 17/M6.0. 2. ROUTE 4" DRYER EXHAUST DUCT IN SOFFIT TO LOUVER AT EXTERIOR WALL. PROVIDE DRYER DUCT FLAP/BACKDRAFT AT TERMINATION WITHOUT ANY SCREENING. 3. ARCHITECT TO PROVIDE 1" UNDERCUT DOOR FOR RETURN AIR PATH. 4. ARCHITECT TO PROVIDE LOUVERED DOOR WITH MINIMUM 100 SQ IN OPEN SPACE. -7 HVAC PLAN - IL-B-7 SCALE: 1/4" = 1'-0" �O of W Sk 41741 �'� GISTSR�� FSS/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.dcengineering.net Phone:208.288.2181 Project:21 AMA01 CD 04 O 00 M p n Z z O= Q W o O 0 0 LLI Z O ; J Q J O -0 Of p N — o i z m I— 0 W Z N U Q Q LU cv U a REVISION DATE REASON FOR ISSUE 4 01-03-22 ADDENDUM #03 A 08-20-21 CITY COMMENTS #01 B 10-28-21 CITY COMMENTS #02 HVAC PLAN - ENLARGED UNITS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SMIrRFMBER M r 0 0 L DUCTLESS SPLIT HEAT PUMP SCHEDULE EQUIPMENT NOMINAL TOTAL COOL/HEAT INDOOR UNIT MCA MANUFACTURER MODEL NO. SERVICE CAPACITY (MBH) MAX CFM SEER/HSPF DSO/DSI-1 MAINTENANCE 0008 1 TON 12.0 / 13.6 400 26.1 / 12.5 1.0 MITSUBISHI MSZ-FH12NA DSO/DSI-2 LAUNDRY 0004 1.5 TON 17.2 / 20.3 460 21.0 / 12.0 1.0 MITSUBISHI MSZ-FH18NA2 DSO/DSI-3 MDF 0003 1 TON 12.0 / 13.6 400 26.1 / 12.5 1.0 MITSUBISHI MSZ-FH12NA DSO/DSI-4 ELECTRICAL 0002 1.5 TON 17.2 / 20.3 460 21.0 / 12.0 1.0 MITSUBISHI MSZ-FH18NA2 ALTERNATE MANUFACTURERS: DAIKIN, FUJITSU, MITSUBISHI, SANYO NOTES: 1. PROVIDE UNIT WITH 7 DAY PROGRAMMABLE THERMOSTAT. 2. PROVIDE ALL ANCILLARY COMPONENTS REQUIRED FOR A FULL INSTALLATION. 3. INDOOR UNIT IS ELECTRICALLY CONNECTED TO AND POWERED BY THE OUTDOOR UNIT. ELECTRICAL REQUIREMENTS ARE COMBINED. 4. CAPACITIES ARE RATED AT ARI STANDARDS. 5. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCHES AND POWER WIRING. 6. PROVIDE MANUFACTURER'S CONDENSATE PUMP KIT AND ROUTE TO NEAREST LAVATORY/SINK TAILPIECE. 7. PROVIDE REFRIGERANT AND REFRIGERANT PIPING PER MANUFACTURER FOR FIELD CONDITIONS. WEIGHT VOLT.-PH.-CY. MCA MOCP 29 LBS 208V-1 PH-60 11 20 29 LBS 208V-1 PH-60 16 20 29 LBS 208V-1 PH-60 11 20 29 LBS 208V-1 PH-60 16 20 OUTDOOR UNIT MANUFACTURER MITSUBISHI MITSUBISHI MITSUBISHI MITSUBISHI MODEL WEIGHT NOTES MUZ-FH12NHA 83 LBS 1,2,3,4,5,6,7 MUZ-FH18NHA 124 LBS 1,2,3,4,5,6,7 MUZ-FH12NHA 83 LBS 1,2,3,4,5,6,7 MUZ-FH18NHA 124 LBS 1,2,3,4,5,6,7 FAN SCHEDULE EQUIPMENT MOTOR HEATING NO. SERVES TYPE - MOUNTING CFM STATIC PRESS. (IN.WC.) WATTS HP RPM VOLT.-PH.-CY. WATTS SONES WEIGHT MANUFACTURER MODEL CONTROL NOTES DBF-1 LAUNDRY - DRYER BOOSTER EXHAUST -DUCT 170 - 72 - - 120-1-60 - - - FANTECH DB4XT-705 PRESSURE SENSOR SWITCH 5 EF-1 UNIT RESTROOMS EXHAUST - CEILING 80 0.10 11.7 - 750 120-1-60 1300 1.5 20 LBS DELTA BREEZE DELTA RAD80 DUAL (LIGHT/HEAT) WALL SWITCH 1,2 EF-2 BOILER 0005 EXHAUST - CEILING 200 0.10 17.5 - - 120-1-60 - 1.0 15 LBS DELTA BREEZE PR0200 THERMOSTAT EF-3 LAUNDRY 0004 EXHAUST - CEILING 100 0.10 12.6 - - 120-1-60 - 1.5 15 LBS DELTA BREEZE GBR100H WALL SWITCH WITH HUMIDISTAT EF-4 PUBLIC RESTROOMS EXHAUST - CEILING 80 0.10 10.5 - - 120-1-60 - 0.8 15 LBS DELTA BREEZE GBR80 VIA LIGHTING SCHEDULE EF-5 TRASH ROOMS/STORAGE EXHAUST- CEILING 80 0.10 10.5 - - 120-1-60 - 0.8 15 LBS DELTA BREEZE GBR80 CONTINUOUS EF-6 SALON EXHAUST - ROOF 290 0.20 - 1/30 1550 120-1-60 - 4.9 50 LBS GREENHECK CUE-070-D VIA LIGHTING SCHEDULE EF-7 FITNESS EXHAUST - CEILING 300 0.10 41 - - 120-1-60 - 2.0 15 LBS DELTA BREEZE PR0300 VIA LIGHTING SCHEDULE EF-8 RESTROOM 1005 EXHAUST - CEILING 150 0.15 17.5 - - 120-1-60 - 1.0 15 LBS DELTA BREEZE PR0200 VIA LIGHTING SCHEDULE EF-G1 GENERATOR ROOM EXHAUST - SIDEWALL 600 0.125 135 1/20 - 120-1-60 - 4.9 - GREENHECK SE1-10-440-G GENERATOR CONTROL EF-K1 COM. KITCHEN HOOD TYPE I - SIDEWALL 4200 1.0 - 3 1434 208-3-60 - 24 200 LBS CAPTIVEAIRE DU180HFA KITCHEN HOOD 7, 8 EF-K2 COM. KITCHEN HOOD TYPE II - SIDEWALL 400 0.5 - 0.25 1493 208-1-60 - 9.1 54 LBS CAPTIVEAIRE DU12HFA DISHWASHER HOOD EF-P1 MECH 0009 EXHAUST - FLOOR 16,000 / 10,700 0.25 - 5.63 720 208-3-60 - 80 850 LBS GREENHECK QEID-27-95 CONTINUOUS/SENSORS 6, 8 EF-P2 MECH 1032 EXHAUST - FLOOR 12,000 / 8,000 0.25 - 5 1475 208-3-60 - 83 850 LBS GREENHECK QEID-22-80 CONTINUOUS/SENSORS 6,8 EF-P3 PARKING GARAGE CIRCULATION - CEILING 2100 - - - - 208-1-60 - - - GREENHECK GJI CONTINUOUS 3.OA MCA, 15A MOP Op TRASH COMPACTOR RM EXHAUST-SIDEWALL 300 0.10 - 1/30 1550 120-1-60 - 5.2 50 LBS GREENHECK CUE-070-D KITCHEN HOOD EPF-1 ELEVATOR PRESSURIZATION - ROOF 10,000 0.25 - 2.11 1740 208-3-60 - 450 LBS REVERSOMATIC RDD-24 FIRE ALARM NOTE 8,29 DEGREE BLADE ANGLE SF-1 ELEVATOR LOBBY SUPPLY - CEILING 50 0.10 11.0 - - 120-1-60 - 15 LBS PANASONIC FV-15NLFS1 VIA LIGHTING SCHEDULE SPF-1 WEST STAIRWAY PRESSURIZATION - ROOF 5,000 0.25 - 0.56 1740 208-3-60 - 450 LBS REVERSOMATIC RDD-24 FIRE ALARM 11 DEGREE BLADE ANGLE SPF-2 EAST STAIRWAY PRESSURIZATION - ROOF 5,000 0.25 - 0.56 1740 208-3-60 - 450 LBS REVERSOMATIC RDD-24 FIRE ALARM 11 DEGREE BLADE ANGLE TF-1 ELECT ROOMS TRANSFER - CEILING 50 0.10 10.5 - - 120-1-60 - 0.8 15 LBS DELTA BREEZE GBR80 THERMOSTAT ALTERNATE MANUFACTURERS: COOK, GREENHECK, PANASONIC, PENNBARRY, CARNES, ACME NOTES: 1. CONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR ALL CONTROLS. 2. SINGLE BLOWER VENTILATOR SHALL BE CEILING MOUNTED. FURNISH WITH CEILING GRILLE, AND BACKDRAFT DAMPER. 3. FAN SHALL BE CONTROLLED BY WALL THERMOSTAT, PROVIDED BY MECHANICAL CONTRACTOR, INSTALLED AND WIRED BY ELECTRICAL CONTRACTOR. 4. FURNISH WITH BACKDRAFT DAMPER. 5. MOUNT IN DESIGNATED AREA ABOVE DRYER. PROVIDE WITH ACCESS, BRACKET, AND HARDWARE. 6. PROVIDE WITH CO AND NO2 SENSOR EQUIPMENT AND ALL NECESSARY ACCESSORIES. 8. FANS EXCEDING 1.0 HP SHALL HAVE AN ENERGY EFFICIENCY CLASSIFICATION OF MORE THAN FEG 71 PER AMCA 205, AND FAN OPERATION SHALL BE WITHIN 10% OF THE LISTED EFFICENY, IN COMPLIANCE WITH WSEC SECTION C406.2.3 SUPPLY FAN T.S.P. EQUIPMENT OUTSIDE (IN. FAN NO. SERVICE LOCATION AIR (CFM) CFM W.C.) RPM HP MAU-1 KITCHEN HOOD ROOF 3360 3360 1.0 1604 3 MAKE-UP AIR UNIT SCHEDULE (BY KES) DIRECT GAS FIRED HEATING I DX COOLING 11 TOTAL SENSIBLE INPUT OUTPUT CAPACITY CAPACITY MBH MBH EFF. % (MBH) (MBH) E.A.T./L.A.T. SEER VOLT.-PH.-CY 225 206.7 92 47.5 47.4 80 / 66 14 208-3-60 ALTERNATE MANUFACTURERS: LENNOX, TRANE, YORK, CARRIER NOTES: 1. UNIT CAPACITIES RATED AT 100 FEET ELEVATION AND 85 DEGREES CONDENSER ENTERING AIR. 2. PROVIDE UNIT WITH FACTORY MOUNTED DISCONNECT AND GFI SERVICE OUTLET. 3. PROVIDE PREFABRICATED 14" ROOF CURB. 4. PROVIDE WITH SEISMIC CLIP. 5. PROVIDE UNIT WITH SPRING ISOLATORS. ELECTRICAL WEIGHT FLA MCA MOCP (LBS) MANUFACTURER MODEL NOTES 9.5 44.4 60 1567 CAPTIVEAIRE A2-D250-20D-MPU 1, 2, 3, 4, 5, 6, 7,8 ENERGY RECOVERY VENTILATOR SCHEDULE SUPPLY FAN EXHAUST FAN ENERGY RECOVERY ELECTRICAL SUMMER WINTER EQUIPMENT T.S.P.(IN. FAN T.S.P. (IN. FAN SUMMER WINTER ENTHALPY ENTHALPY NO. SERVICE LOCATION CFM W.C.) RPM HP CFM W.C.) RPM HP EAT/LAT EAT/LAT RECOVERY RECOVERY SONES VOLT.-PH.-CY. FLA MCA MOCP WEIGHT MANUFACTURER MODEL NOTES ERV-1 FC OSA / CORRIDOR EA ROOF 1050 0.75 1100 0.75 950 0.75 1140 1 0.75 85 / 77.8 23 / 51.8 67.5 54.6 13.2 208V-PH1-60 12.2 15 GREENHECK ECV-10H-VG-FM NOTES: 1. UNIT CONFIGURED TO SUPPLY 100% OSA EQUIPMENT NO. SERVICE SUPPLY CFM MIN. OSA CFM ESP (IN. W.C.) VERTI L PACKAGED TERMINAt SENSIBLE COOLI MBH EER HEATING MBH COP EAT PUMP SCHEDULE C. HEAT (kW) VOLT-PH-CY MCP MCA WEIGHT MANUFACTURER MODEL NOTES VTAC-1 STUDIO UNIT 490 60 0.3 9.0 11.5 8.2 4.0 2.1 208V-1PH-60 15 15 145 AMANA AVH093H VTAC-2 1-BEDROOM 490 60 0.3 11.0 11.5 10.5 4.0 2.8 208V-1 PH-60 20 19.9 150 AMANA AVH123H VTAC-3 2-BEDROOM 675 60 0.3 18.0 11.5 16.5 4.0 4.1 208V-1 PH-60 30 28.6 190 AMANA AVH183H NOTES: 1. PROVIDE WITH MERV-6 FILTER OR BETTER. E 2. PROVIDE WITH ARCHITECTURAL LOUVER, ACCESS PANEL/RETURN AIR GRILLE, AND ACCESSORY DRAIN PAN/KIT. DEDICATED OUTSIDE AIR SUPPLY UNIT SCHEDULE SENS COOLING OUTSIDE AIR HEATING ELECTRICAL EQUIPMENT NOMINAL CAPACITY MIN / MAX ENTERING AIR CAPACITY E.S.P. NO. SERVICE CAPACITY (MBH) CFM SEER/IEER DB/WB (MBH) (IN W.C.) MCA MOCP VOLT/PH/CY WEIGHT MANUFACTURER MODEL NOTES DOAS-1 CORRIDOR OSA 12 TONS 160.8 2200 / 4800 418.1 18.1 80/61.3 133 0.5 88.5 A 100 A 208V-3PH-60 3851 LBS CAPTIVEAIRE CASRTU4 1,2 1.' UMIT CONFIGURED TO SUPPLY T00% OSA. ' ' 2. FANS EXCEDING 1.0 HP SHALL HAVE AN ENERGY EFFICIENCY CLASSIFICATION OF MORE THAN FEG 71 PER AMCA 205, AND FAN OPERATION SHALL BE WITHIN 10% OF THE LISTED EFFICENY, IN COMPLIANCE WITH WSEC SECTION C406.2.3 ROOFTOP UNIT SCHEDULE COOLING HEATING ELECTRICAL EQUIPMENT SUPPLY AIR OUTSIDE AIR ENTERING AIR SENSIBLE MBH MBH POWER EXH. NO. SERVICE TONS (CFM) (CFM) E.S.P. (IN. W.C.) EER/SEER REFRIGERANT DB/WB MBH INPUT OUTPUT AFUE % VOLT/PH/CYC MCA MOCP MCA MOCP WEIGHT (LBS) MANUFACTURER MODEL OPTIONS RTU-1 FITNESS 3 1200 305 0.5 416.1 16.1 R-41 OA 80 / 61 24.5 79.2 64.2 81% 208/3/60 27 30 1.5 15 700 CARRIER 48GCEM04 1,2,3,4,5,6,7,8 RTU-2 THEATER 3 1200 270 0.5 416.1 16.1 R-41 OA 80 / 61 24.5 79.2 64.2 81% 208/3/60 27 30 1.5 15 700 CARRIER 48GCEM04 1,2,3,4,5,6,7,8 ALTERNATE MANUFACTURERS: LENNOX, TRANE, BRYANT, YORK, CARRIER, LUXAIRE. NOTES: 1. UNIT CAPACITIES RATED AT 600 FEET ELEVATION AND 80 DEGREES CONDENSER ENTERING AIR. 2. PROVIDE UNIT WITH FACTORY MOUNTED DISCONNECT AND GFI SERVICE OUTLET. 3. PROVIDE PREFABRICATED 14" ROOF CURB. 4. PROVIDE ECONOMIZER WITH FULL MODULATING POWER EXHAUST AND HIGH LIMIT SHUT OFF CONTROL PER WSEC C403.3.3.3. 5. PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT. 6. PROVIDE WITH SEISMIC CLIP. 7. PROVIDE UNIT WITH ALL CONTROLS AND SENSORS REQUIRED FOR ON DEMAND VENTILATION. 8. PROVIDE UNIT WITH FACTORY SMOKE DETECTOR, FIELD INSTALLED. AIR DISTRIBUTION DEVICES SIZE MOUNTING MATERIAL EQUIPMENT LAY -IN HARD MANUFACTUR NO. FACE NECK SIDEWALL CEILING CEILING DUCT FLOOR STEEL ALUMINUM ER MODEL NOTES SD-1 12"x12" SEE PLANS X X X TITUS TMS SD-2 24"x24" SEE PLANS X X X TITUS TMS SG-1 10"x6" SEE PLANS X X TITUS US30OFS SG-2 10"x6" SEE PLANS X X X TITUS US350FS RG-1 12"x12" SEE PLANS X X X TITUS 50F RG-2 24"x24" SEE PLANS X X X TITUS 50F TG-1 14"x10' SEE PLANS X X TITUS US350FS TG-2 24"x24" SEE PLANS X X X TITUS 50F EGA 24"x24" SEE PLANS X X X TITUS 50F ALTERNATE MANUFACTURERS: TITUS, PRICE, METAL-AIRE, NAILOR, CARNES, TUTTLE & BAILEY NOTES: 1. CONTRACTOR TO VERIFY AND PROVIDE ALL MOUNTING HARDWARE FOR APPLICABLE CEILING TYPES. 2. FINISH TO BE COORDINATED WITH ARCHITECT PRIOR TO SUBMITTAL. 3. NC VALUES NOT TO EXCEED 25. 4. NECK SIZE REFERS TO THE DUCT SIZE CONNECTION AT THE DIFFUSER OR GRILLE. 5. CONTRACTOR PROVIDED FACE DAMPER WHEN IN -LINE DUCT DAMPER IS NOT ACCESSIBLE. 6. CONTRACTOR TO PROVIDE TRANSITIONS FROM LEAD-IN DUCT SIZE TO NECK SIZE AS REQUIRED. ELECTRIC WALL HEATER SCHEDULE EQUIPMENT ELECTRIC NO. SERVICE CFM WATTS RPM MCA VOLT.-PH.-CY. WEIGHT EWH-1 SEE PLANS 100 750 1060 6.3 120V-1PH-60 10 LBS EWH-2 STAIRWAYS 100 1500 1060 12.5 120V-1PH-60 10 LBS ALTERNATE MANUFACTURERS: NOTES: 1. COORDINATE MOUNTING LOCATION WITH ALL OTHER DISCIPLINES. EQUIPMENT NO. KEY: �� (A), (B) (A A. FIRST LETTER: S-SUPPLY, R-RETURN, E-EXHAUST, T- TRANSFER SECOND LETTER: D-DIFFUSER, R-REGISTER, G-GRILLE B. DUCT NECK SIZE, UNLESS NOTED OTHERWISE C. CFM MANUFACTURER MODEL NOTES MARKEL E3055T2DWB MARKEL E3055T2DWB LOUVER SCHEDULE EQUIPMENT THICKNESS NO. SERVICE WIDTH HEIGHT FREE AREA (SQ. FT.) OF FRAME MATERIAL SCREEN MANUFACTURER MODEL NOTES L-1 FC-1C, FC-1D, FC-1E INTAKE 46" 46" 28" 28" 4.4 4.5 6" GALVANIZED STEEL MESH GREENHECK VCD-23 2000 CFM INTAKE, CLASS 1 MOTORIZED DAMPER. L-2 1ST FLOOR RELIEF 6" GALVANIZED STEEL MESH GREENHECK VCD-23 3600 CFM RELIEF, CLASS 1 MOTORIZED DAMPER L-3 FC-1E RELIEF 12" 12" 0.5 5" GALVANIZED STEEL MESH GREENHECK VCD-23 400 CFM RELIEF, CLASS 1 MOTORIZED DAMPER L-G1 GENERATOR INTAKE 24" 18" 3.00 5" ALUMINUM MESH RUSKIN CD355 1,2 L-R1 UNIT EXHAUST MANIFOLD 12" 11" - 5" POLY MESH XVENT MDEB-44-BR 1 L-R2 UNIT EXHAUST MANIFOLD 16" 12" - 5" POLY MESH XVENT THEB-444-BR 1 RL-1 TRASH CHUTE PENTHOUSE VENT 24" 16" - - ALUMINUM MESH GREENHECK WRH 3 ALTERNATE MANUFACTURERS: GREENHECK, RUSKIN, CESCO, L & D NOTES: 1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. 2. PROVIDE WITH RUSKIN MOTORIZED ACTUATOR, CONTROLLED TO OPEN WHEN EF-G1 IS ENERGIZED. 3. COORDINATE WITH ARCHITECTURAL FOR TRASH CHUTE ROOF EXTENSION SIZE. UNIT HEATER SCHEDULE EQUIPMENT AIRFLOW NO. MANUFACTURER MODEL FUEL INPUT (MBH) EFFICIENCY (CFM) VOLT/PH/CY WEIGHT NOTES UH-1 MODINE HHD-30 NATURAL GAS 30.0 82% 500 120V-1 PH-60 1 55 LBS FAN COIL SCHEDULE EQUIPMENT NO. AREA SERVED SUPPLY AIR (CFM) OUTSIDE AIR (CFM) EXTERNAL STATIC PRESS (IN. W.G.) HEATING COIL COOLING COIL ELECTRICAL WEIGHT MANUFACTURER MODEL NOTES MBH INPUT KW MBH REFRIG. VOLT.-PH.-CY. MCA MOP FC-1A BISTRO 1600 570 0.24 54.2 650 48.1 R41 OA 208V-1PH-60 3.1 15 110 LG ARNU483M3A4 1, 2, 3, 4, 5, 6, 7, 9 FC-1 B OFFICES 1200 240 0.24 40.6 450 36.2 R41 OA 208V-1 PH-60 2.9 15 100 LG ARNU363M3A4 1, 2, 3, 4, 5, 6, 9 FC-1C DINING 1600 450 0.24 54.2 650 48.1 R41 OA 208V-1PH-60 3.1 15 110 LG ARNU483M3A4 1, 2, 3, 4, 5, 6, 7, 8, 9 FC-1D DINING 1600 450 0.24 54.2 650 48.1 R41 OA 208V-1PH-60 3.1 15 110 LG ARNU483M3A4 1, 2, 3, 4, 5, 6, 7, 8, 9 FC-1E FAMILY RM 400 75 0.24 13.6 190 12.3 R41 OA 208V-1PH-60 2.0 15 67 LG ARNU123M3A4 1, 2, 3, 4, 5, 6, 8, 9 FC-1 F KITCHEN 1200 0 0.24 40.6 450 36.2 R41 OA 208V-1 PH-60 2.9 15 100 LG ARNU363M3A4 1, 2, 3, 4, 5, 6, 9 FC-2 2ND FLOOR 800 325 0.24 27.3 190 24.2 R41 OA 208V-1PH-60 2.0 15 70 LG ARNU243M3A4 1, 2, 3, 4, 5, 6, 9 FC-3 3RD FLOOR 800 325 0.24 27.3 190 24.2 R41 OA 208V-1PH-60 2.0 15 70 LG ARNU243M3A4 1, 2, 3, 4, 5, 6, 9 FC-4 4TH FLOOR 800 325 0.24 27.3 190 24.2 R41 OA 208V-1PH-60 2.0 15 70 LG ARNU243M3A4 1, 2, 3, 4, 5, 6, 9 FC-5 5TH FLOOR 800 325 0.24 27.3 190 24.2 R41 OA 208V-1 PH-60 2.0 15 70 LG ARNU243M3A4 1, 2, 3, 4, 5, 6, 9 FC-6A SALON 400 270 0.24 13.6 190 12.3 R41 OA 208V-1PH-60 2.0 15 67 LG ARNU123M3A4 1, 2, 3, 4, 5, 6, 9 FC-613 6TH FLOOR 800 255 0.24 27.3 190 24.2 R41 OA 208V-1PH-60 2.0 15 70 LG ARNU243M3A4 1, 2, 3, 4, 5, 6, 9 ALTERNATE MANUFACTURERS: LENNOX, TRANE, YORK NOTES: 1. PROVIDE UNIT WITH 7 DAY PROGRAMMABLE THERMOSTAT. 2. PROVIDE ALL ANCILLARY COMPONENTS REQUIRED FOR A FULL INSTALLATION. 3. PROVIDE WITH MEDIA FILTER. 4. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCHES AND POWER WIRING. 5. PROVIDE MANUFACTURER'S CONDENSATE PUMP KIT AND ROUTE TO NEAREST LAVATORY/SINK TAILPIECE. 6. PROVIDE MANUFACTURER'S LOW AMBIENT KIT FOR OPERATION DOWN TO 0°F. 7. PROVIDE ALL CONTROLS AND SENSORS REQUIRED FOR DEMAND CONTROL VENTILATION. 8. PROVIDE FAN COIL WITH MOTORIZED DAMPERS FOR ECONOMIZER OPERATION, WITH HIGH LIMIT SHUT-OFF CONTROL PER WSEC C403.3.3.3. 9. PROVIDE UNIT WITH MANUFACTURER DRIP PAN AD SECONDARY DRAINAGE. HEAT PUMP SCHEDULE EQUIPMENT NO. I TOTAL HEATING CORRESPONDING TOTAL COOLING CAPACITY UNIT CAPACITY (MBH) (MBH) FC-1A 50 56.5 SEER/EER 17 HSPF 9.5 ELECTRICAL SOUND dB 51 MANUFACTURER LG MODEL WEIGHT NOTES VOLT./PH/CY. MCA MOCP HP-1A 208V-1PH-60 30 50 ARUN048GSS4 207 1, 2, 3, 4, 5, 6 H PA B FC-1 B 39.5 44 17 9.0 208V-1 PH-60 25 40 50 LG ARU N036GSS4 160 1, 2, 3, 4, 5, 6 HPA C FC-1 C 50 56.5 17 9.5 208V-1 PH-60 30 50 51 LG ARUN048GSS4 207 1, 2, 3, 4, 5, 6 HPA D FC-1 D 50 56.5 17 9.5 208V-1 PH-60 30 50 51 LG ARUN048GSS4 207 1, 2, 3, 4, 5, 6 HPA E FC-1 E 24 27 15.8 8.6 208V-1 PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-1 F FC-1 F 39.5 44 17 9.0 208V-1 PH-60 25 40 50 LG ARUN036GSS4 160 1, 2, 3, 4, 5, 6 HP-2 FC-2 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-3 FC-3 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-4 FC-4 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-5 FC-5 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-6A FC-6A 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 HP-613 FC-6B 24 27 15.8 8.6 208V-1PH-60 20 30 50 LG ARUN024GSS4 160 1, 2, 3, 4, 5, 6 ALTERNATE MANUFACTURERS: LENNOX, TRANE, YORK NOTES: 1. PROVIDE ALL ANCILLARY COMPONENTS REQUIRED FOR A FULL INSTALLATION. 2. INDOOR UNIT IS ELECTRICALLY CONNECTED TO AND POWERED BY THE OUTDOOR UNIT. ELECTRICAL REQUIREMENTS ARE COMBINED. 3. CAPACITIES ARE RATED AT ARI STANDARDS. 4. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCHES AND POWER WIRING. 5. PROVIDE REFRIGERANT AND REFRIGERANT PIPING PER MANUFACTURER FOR FIELD CONDITIONS. 6. PROVIDE MANUFACTURER'S LOW AMBIENT KIT FOR OPERATION DOWN TO 0°F. NOTE: MECHANICAL EQUIPMENT SHALL EXCEDE THE WSEC EFFICIENCIES ON TABLES C403.2.3(1) THROUGH C403.2.3(9) BY 15% TO UTILIZE THE HIGH EFFICIENCY HVAC OPTION. C O 0F WA Sk 41741 ISTER���\� Fss/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering. net Phone:208.288.2181 Project:21 AMA01 Q0 N O 00 O') p Z z_ 0 = Q W C 0 0 O0 Z O > > 10 J Q J _� O � O N 0 I` z m F_ C:)LLI Z o U Q LU Q N U a REVISION DATE REASON FOR ISSUE 4 01-03-22 ADDENDUM #03 A 08-20-21 CITY COMMENTS #01 B 10-28-21 CITY COMMENTS #02 C 02-08-22 CITY COMMENTS #03 E 03-07-22 CITY COMMENTS #05 HVAC SCHEDULES GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M5.0 Q M MAIN AIR DUCT ACOUSTIC LINING LG,� RECTANGULAR �s WHERE MAIN AIR DUCT ISOLATION RAIL WITH 2" N MAIN DUCT > r o INDICATED SPRING DEFLECTION _ HAND SUPPLY ___________________ ASSEMBLY. FLEX DUCT, MAX. DUCT - o FLOW M LENGTH = 6'-0" DAMPER o �. O SECURE � — \ � � — — / NO EXPOSED Z � i AIR FLOW i LINER EDGES AIR FLOW — S�ONA� E� WIRE TO PRE -FABRICATED 03/07/2022 ETRUCTUR Oo \ RECTANGULAR TO CURB — — — — ROUND TRANSITION NAILER STRIP TAKE -OFF AIRFOIL SHAPED 90T 45T Y-FITTING SPIN COLLAR �� DUCT SEALER 745- BALANCING DAMPER w/ TURNING VANES LOCKING QUADRANT RIGID INSULATION MANUAL DAMPER CLAMP TAKE -OFF - RECTANGULAR MAIN MITERED ELBOW -RECTANGULAR COLLAR 45° BRANCH DUCT ROUND BRANCH FLASHING DRAW BAND SUPPORT FLEX DUCT BEND WITH WITH 1" WIDE SHEET METAL STRAP FLEXIBLE ROUND MANUAL DAMPER SILICONE DUCT ASVI rt SEALER (TYP) FLEX DUCT SIZE TO MATCH 23° INDICATED LENGTH ROOFING DIFFUSER NECK SIZE J 45° (6' 0" MAX.) �_`� 38 NORTHWEST DAVIS, SUITE 300 M S �,�5 PORTLAND, OR 97209 ROUND DUCT LEVELING 503.245.7100 �: ' NOTES: *EQUALS WIDTH OF BRANCH DUCT UP TO 12". W STRIP AS 1505 5TH AVE, SUITE 300 D 1. REFER TO SPECIFICATIONS FOR 12" FOR ALL BRANCH DUCTS LARGER THAN 2'-0" MIN REQUIRED SEATTLE, WA 98101 CEILING CEILING DIFFUSER LINING REQUIREMENTS. NOTE: SHOWN WITH AIR SCOOP FOR CLARITY, 12". BALANCING DAMPERS IF SINGLE BLADE 206.576.1600 45/90T 2. REFER TO SPECIFICATIONS FOR NOT ALL SPIN IN FITTINGS REQUIRE SCOOPS. AS SHOWN ON PLANS. DAMPER ROOF DECK DOUBLE WALL CONSTRUCTION SEE PLANS FOR SCOOP REQUIREMENTS. TEES RECTANGULAR RADIUSED ELBOWS - RECTANGULAR 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 1 TYPICAL DIFFUSER CONNECTION DETAIL 2SCALE:NTS TYPICAL SPIRAL DUCT FITTINGS SPIN IN DETAIL 4SCALE:NTS SQUARE DUCT TAKE OFF DETAIL 5 LOW PRESSURE RETANGULAR DUCT FITTINGS SPRING ISOLATION ROOF CURB SCALE:NTS 3SCALE:NTS SCALE: NTS 6SCALE:NTS © ANKROM MOISAN ARCHITECTS, INC. POWER SUPPLY CABLE NAIL OR SCREW TOP FIELD SUPPLIED MANUFACTURERS (2 EACH SIDE) FUSED ROOFTOP UNIT ECONOMIZER HOOD FASTENER ROUGH IN BOX \ DISCONNECT ROOFTOP EQUIPMENT SHEET METAL �� KNOCKOUT SWITCH — FOAM INSULATION, \ �� SEE ARCHITECTURAL PAINT FLAT BLACK ON SPONGE RUBBER GASKET PLANS FOR MONITOR LOUVER SIDE 00 �\� I EXHAUST FAN WITH BIRD SCREEN SUPPLIED AND WALL SHEET KNOCKOUT INSTALLED BY CONSTRUCTION METAL all, ° MECHANICAL PLENUM BII CONTRACTOR BIRDSCREEN DUCTWORK ce, SIDE i HEAVY -GAUGE STEEL CURB TO BACKDRAFT DRAIN LEDGE I \\ COUNTERFLASHING MATCH UNIT - SLOPE BASE OF DAMPER PROVIDED D C ENGINEERING � \ � / CURB TO MATCH ROOF SLOPE BY FAN ARCHITECTURA � MANUFACTURER are9 Careful listenin Dynamic solutions. LOUVER z I Lu z INSULATION www.drengineering.net SEAL ALL - j z w CANT STRIP CURB (SEE ARCH.) Phone:208.288.2181 Project:21AMA01 AROUND SEAL WATERTIGHT � FRONT ROOF CURB N 0 = WOOD NAILER of CD ROOFING �X ROOF PENETRATE BOTTOM FLASHING THROUGH CONTROL SUPPLY AIR DUCT ADDITIONAL SUPPORT X ROOF DECK WIRING TO TO BE CONTINUOUS FOAM FOR PLENUM FOR THROUGH WALL �� CONNECTION INDOOR CONDENSATE EDGE OF ROOF DECK OR WITH NO JOINTS CAULK CONNECTION THERMOSTAT TRAP AND DRAIN REQUIRED WATER TIGHT ALL AROUND O POWER SUPPLY T ISOMETRIC VIEW RETURN � 3"x3"x1/4" ANGLES ALL AIR DUCT SIDES BY MECH. CONTR.SPAN BETWEEN JOISTS 7 INTAKE/EXHAUST LOUVER DETAIL ELECTRIC WALL HEATER DETAIL 9 RTU DOWNFLOW DETAIL 10 ROOF CURB DETAIL 11 EXHAUST FAN DETAIL SCALE: NTS 8SCALE:NTS SCALE: NTS SCALE: NTS SCALE: NTS "S" JOINT OR FIRE RATED DUCTMATE, SLEEVE TO WALL DUCT. (TYPICAL TOxORGALVANIZED SLEEVE OUTDOOR 1/2" STEEL BANDING BOTH SIDES OF FIRE (FURNISHED WITH AT 10-1/2" OC. DAMPER.) DAMPER) REFER TO CONDENSIN DUCT SUPPORT ARCHITECTURAL G TO STRUCTURE DRAWINGS FOR COIL BANDING ROOF SLEEPER DWOOD CONDENSAT ONE PIECE ROLL PENETRATION E ROOF 3" LONGITUDINAL FORMED GALVANIZED RS RL DRAIN ROUTE RL— ROOF 1 LAYER "FIREBARRIER" STEEL FRAME RSPER PLANS - OVERLAP DUCT WRAP 15A BY 3M JUNCTION BOX LES EXHAUST FAN WITH BIRD DAMPER MOTOR/ DUCTLES DUCT SCREEN SUPPLIED AND 3 PERIMETER OPERATOR OVER CENTER LOCK S S OVERLAP SPLIT (ELECTRICALLY) INSTALLED BY WALL CAP SPLIT r MECHANICAL FLOOR/ROOF W/BACKDRAF BACKDRAFT CONTRACTOR DUCT ABOVE T EAS DAMPER PROVIDED b 4 n va b q b PA�71R _, CONDENSATE BY FAN DRAIN MANUFACTURER �� EF PROVIDE ROUND ROUTE PER PLANS COONDOENOSIN CV DUCT CONNECTION 00 WHERE SHOWN ON 1-1/2"xl-1/2"xl/8" T-STAT T-STAY T STAY T STAY COIL L_ EXHAUST FAN FLEXIBLE DRAWINGS GALVANIZED W/BACKDRAFT DUCT EXHAUST MOUNTING FRAME O WALL WEATHER PROOF FUSED DAMPER CONNECTION DUCT 6" MIN, 16" MAX (FURNISHED WITH DAMPER) 0 DISCONNECT 1-1/2" PROVIDE WITH CEILING CEILING WELDED CARBON 10-112" MANUFACTURERS NOTE: Z Z SPACIN GRILLE 1. FIRE/SMOKE DAMPER INSTALLATION SHALL MEET U.L. REQUIREMENTS. RS-RL= — ��P TYP ISOLATION 2. FIRE/SMOKE DAMPER BASED ON RUSKIN MODEL FSD60 OR APPROVED EQUAL. O = EXTERNAL WIRING STEEL GREASE DUCT SPACING FOR 2�^ 3. FURNISH COMPLETE WITH 120 VOLT DAMPER ACTUATOR FURNISHED TIGHT TO BUILDING BANDS MOUNTING KIT COMPLETE WITH SMOKE DAMPER FOR A UL RATED SMOKE DAMPER. CONCRETE PAD Q 4. SMOKE DAMPER SHALL BE ACTIVATED FROM SMOKE DETECTOR TO CLOSE NOTE: NOTE: 0 UPON SMOKE DETECTION. MAINTAIN MANUFACTURERS RECOMMENDED CLEARANCE REQUIREMENTS MAINTAIN MANUFACTURERS RECOMMENDED CLEARANCE REQUIREMENTS NOTE: FOLLOW MFG INSTALLATION GUIDE FOR COMPLETE 5. PROVIDE FAIL SAFE DESIGN WHICH WILL ENABLE THE DAMPER TO W (n DETAILS TO INSTALL FOR A 2 HOUR FIRE RESISTIVE RATING. AUTOMATICALLY CLOSE DUE TO LOSS OF POWER. 0 0 EXTERIOR SIDEWALL EXHAUST FAN DETAIL GREASE EXHAUST DUCT WRAP DETAIL EXHAUST FAN TYPICAL DETAIL FIRE SMOKE DAMPER DETAIL DUCTLESS SPLIT DETAIL 12SCALE:NTS 13SCALE:NTS 14SCALE: NITS 15SCALE:NTS 16SCALE: NITS �w z w BIRD SCREEN i > o LOUVERED PENTHOUSE Q J GRAVITY ROOF VENTILATOR O -0 (if EXPANSIO O N POWDER ACTUATED N SHIELD ti Z m PIN (IF ALLOWED BY CONCRET WASHER rn CODE) E SLAB BOTTOM CHORD OF STEEL JOIST STEEL BEAM BEAM z 0 U) CLAMP N Q Of Of USE THIS METHOD _ N U tl w Li Li WHENEVER DUCTS CAN 1" x 16 GA.— 1/2" ALL BE GROUPED 1/2" ALL T PREFABRICATED, STRAPS SHEET METAL THREAD ROD S 1PWJt�T THREAD ROD INSULATED FAN CURB, SCREWS DRAWINGS FOR MOUNT AND SECURE PER NUMBER & SIZE ARCHITECTURAL DETAILS. REVISION DATE REASON FOR ISSUE X f Y\ LA V_y 1 6-18-2021 ADDENDUM 1 DUCT DUCT -SEE DUCT DUCT DUCT ROOF B 10-28-21 CITY COMMENTS #02 PLAN FOR 11 SIZE Rough in Dimensions 44" H X 27-5/8" W SINGLE RECTANGULAR DUCT MULTIPLE DUCTS RUNS ON TRAPEZE HANGERS Approximate 2"x2"x3/16" ANGLE (WHERE NOTE: EXHAUST OR BACKDRAFT DAMPER AS Fasteners Locations Return CAULK LENGTH OF ANGLE DUCTS SHALL BE SUPPORTED AT FRESH AIR DUCT REQUIRED BY THE I.E.C.C. ' Air EXCEEDS 6 FT. USE NOT LESS THAN 10 FT O.C. INTERMEDIATE SUPPORT) _ PENTHOUSE ROOF VENTILATOR DETAIL Architectural WOOD BEAM 19 SCALE: 12" = V-0" Grille (See Page.10) DUCT RISER -SEE PLANS FOR SIZE NOTE: Filter SPXC Unit SHEET METAL SCREWS MOUNT AND SECURE TO EXTERIOR WALL 0 0 C 1-1/2" x 1-1/2" x WALL IN ACCORDANCE WITH INSTALLATION PROCEDURES 1/8" ANGLE BOTH 1 1l2" x 1 1l2" x 1l8" MANUFACTURERS Electrical SIDES OF DUCT ANGLE BOTH SIDES OF � Disconnect Tilt Sleeve 1/2 Bubble SECURE STRAP DUCT o to outside HANGERS TO FLOOR CURB m Q / Sleeve Seal STRUCTURE CY CY To Condensate 0 0 0 0 0 1 3 o Drain TURN STRAP — —MIN EF HVAC DETAILS Rear Access 1"xl8 GA STRAP SHEET ^ Panel Wall Sleeve 6" min. �� HANGERS UP THRU 30" 0 2 i ' (See Page.10) METAL SEAL HOLE w T— a m/n. 1"x1/8" > 30"QJ AT 10' O.C. AFTER DUCT HOLE IN STRUCTURAL Drain SCREWS i (3/4" MPT) ♦ \ / FLOOR r INSTALLATION EXHAUST DUCT NOTE: DUCT RISER FOR KITCHEN EXH. HOOD Factory Installed WITH RED LEAD APPLICATIONS, DUCT TO TRIM > Backdraft Damper on FIGURE 4 . DUCT -SEE AND OAKUM G M P/PERMIT SET J Electrical Service OSA Air Connection ♦ BE OF 16 GA. WELDED � Knockout A Note: PLANS FOR SIZE Side View "P" Trap is shown for illustration purposes only - It ROUND DUCT RISER SUPPORT CONSTUCTION U) (with "Rear Install" sleeve) may not be required by local codes. CAULK/SEAL WEATHER TIGHT c 0 E w VTAC DETAIL DUCT HANGER DETAIL 0 GREASE EXHAUST FAN SIDEWALL DETAIL DATE PROJECT NUMBER N o SCALE: NTS 18SCALE:NTS 2 SCALE: NTS 055.21.21 184470 N aa) S MBER co U M6.0 U 0 i J J J J 0 D 0 t L FOR QUESTI❑NS, CALL THE Idaho Mechanical REGI❑N 112 PHONE: (888) 388-0344 EMAIL: reg112@captiveaire,com FYI-TATT.S'T FAN rivmPMATTnAT — TnR-,5n9R4S,5 FAN MOTOR DISCHARGE WEIGHT UNIT TAG QTY FAN UNIT MODEL # MANUFACTURER CFM ESP RPM ENCL HP BHP PHASE VOLT FLA VEL❑CITY (LBS) S❑NES NO 3 EF-1 1 DU180HFA CAPTIVEAIRE 4200 1.000 1434 ❑DP,PREMIUM 3,000 2,0790 3 208 9.5 970 FPM 200 24 4 EF-2 1 DUI2HFA CAPTIVEAIRE 400 0.500 1493 TEA❑ -ECM 0.250 0.1320 1 208 1.9 284 FPM 54 9,1 rnivnF. Ars F R nF. TATT,.S FAN CONDENSER MAX FUSE MIN WIRE UNIT TAG FAN UNIT MODEL # NO TONNAGE VOLTAGE PHASE FREQUENCY MCA RLA SIZE SIZE SEER NO 1 3 208-230 3 PHASE 60 HZ 14.5 AMPS 11,9 AMPS 20 AMPS 14 AWG 14 2 MAU-1 A2-D,250-20D-MPU 2 5 208-230 3 PHASE 60 HZ 21.4 AMPS 1 17.4 AMPS 1 30 AMPS 10 AWG 14 MUA FAN INFORMATION — JOB#5098465 FAN MIN DESIGN MOTOR WEIGHT UNIT TAG QTY FAN UNIT MODEL # BLOWER H❑USING CFM CFM ESP RPM ENCL HP BHP PHASE VOLT FLA MCA M❑CP (LBS) S❑NES NO 2 MAU-1 1 A2-D,250-20D-MPU 20MF-2-MOD A2-D.250 2900 3360 1.000 1604 ❑DP,PREMIUM 3.000 2.1720 3 208 9.5 44.4A 60A 1568 16.2 rnu-,zS - TnR,#Sn 9 R4F5 C❑❑LING HEATING FAN COIL DESIGN UNIT TAG TYPE CFM N❑ ENTERING DB ENTERING LEAVING DB LEAVING WB ENTERING LEAVING FLUID FLOW PERCENT TOTAL SENSIBLE LATENT ENTERING DB LEAVING DB ENTERING LEAVING FLUID FLOW PERCENT STEAM TOTAL SENSIBLE TEMP WB TEMP TEMP TEMP FLUID TEMP FLUID TEMP RATE GLYCOL CAPACITY CAPACITY CAPACITY TEMP TEMP FLUID TEMP FLUID TEMP RATE GLYCOL PRESSURE CAPACITY CAPACITY 2 MAU-1 DX 3360 80,0°F 60.0°F 66,7°F 54,9°F --- --- --- --- 47.5 MBH 47.4 MBH 0.1 MBH --- --- --- --- --- --- --- --- --- (TA.S' FTR F. T) MA k F. —TTP A TR TTATTT(.S' ) FAN INPUT OUTPUT REQUIRED INPUT GAS BURNER UNIT TAG BTUs BTUs TEMP RISE PRESSURE GAS TYPE EFFICIENCY(%) NO 2 MAU-1 224939 206944 60°F 7 IN. W.C. - 14 IN, W,C, NATURAL 92 n0A.S'/RTTT FAN .S'rNF, nw,F, - .TnRA.Sn 9 R4F.5 FAN RETURN AX TOTAL WEIGHT UNIT TAG QTY D❑AS/RTU MODEL # MANUFACTURER BLOWER AIR CFM ❑UTSIDE CFM ESP HP BHP HAS VOLT MCA M❑CP (LBS) NO AIR CFM 1 D❑AS 1 CASRTU4-I.500-24-22T-D❑AS CAPTIVEAIRE 24P-4 0 4800 4800 0,500 5,000 1,8620 3 208 88,5A 100A 3851 nnA.': /IPTTT rnnT.TNr .S'rTiFnuT.F. COMPRESSOR OUTDOOR FAN IND❑❑R C❑IL REHEAT FAN ❑UTSIDE ❑UTSIDE MIXED AIR MIXED AIR LEAVING LEAVING LEAVING TOTAL SENSIBLE LATENT REHEAT REHEAT DESIRED MAX LEAVING M❑ISTURE UNIT TAG AIR AIR DB TEMP WB TEMP DB TEMP WB TEMP DP TEMP CAPACITY CAPACITY CAPACITY LEAVING LEAVING REHEAT REHEAT RELATIVE REMOVAL IEER NO TONNAGE VOLTAGE PHASE MOTOR MOTOR 0 MOTOR MOTOR QTY ROWS FACE AREA DB TEMP WB TEMP DB TEMP WB TEMP CAPACITY CAPACITY HUMIDITY RATE VOLTAGE FREQUENCY 1 D❑AS 22 190-240 3 200-240 3 60 1 3 5 25.3 SQFT 80,0°F 61,3°F 80,0°F 61,3°F 48.4°F 48,4°F 48,5°F 164.0 MBH 160.8 MBH 3.2 MBH 70,0°F 58,1°F 116.8 MBH 129.6 MBH 49 2.9 LBS/HR 18,1 nnA.S'/RTTT HF,ATTNG ,S'rNF,T)TTT,F FAN INPUT OUTPUT BURNER UNIT TAG BTUs BTUs TEMP RISE REQUIRED INPUT GAS PRESSURE GAS TYPE EFFICIENCY(%) NO 1 D❑AS 414548 331638 60°F 7 IN. W.C. - 14 IN. W.C. NATURAL 80 REVISIONS DESCRIPTION DATE: 0 0 0 0 00 I ' I 0 E 0 II I M IIII a U III N Ia� Li Q I I 2 w 0 N_ CD x co v co �= co00 s 00 v � d ui z O O = s a IQD 0 1 C ca 3 co Y a� L 0 fn 0 0 z L0 0 CU V1 L� Q 0 O Q 011 3 0 03 v1 (J') o Q 5 I I z 0 o cis LL] DATE: 8/2/2021 DWG.#: 5018465 D RABW1N Z K M SCALE: 3/4" = 1'-0" MASTER DRAWING SHEET NO. 1 �O `a i 41741 � FSS/oNAL 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 (D CV O rn O 0 Z z O = Q 0 3: w o LL o O 0 LLI 3: z O > > J Q J O -0 0f O N 0 ti Z m I— o W Z N U) Q Q LU (v U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 HVAC DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 S MBER M Air a 7 C c C C C C 0 FAN OPTTnN.S' FAN UNIT NO TAG QTY DESCRIPTI❑N 1 INLET PRESSURE GAUGE, 0-35", 1 IMANIFOLD PRESSURE GAUGE, 0 TO 10" WC, 1 FURNACE. 1 TOTAL CFM M❑NIT❑RING FOR D❑AS, 1 SINGLE POINT ELECTRICAL C❑NNECTI❑N FOR RTU. QNTY 1 750VA TRANSFORMER USED, IF A NON-DCV PREWIRE CONTROLS THIS UNIT, THE #28, #47, "MA", OR "E2" ❑PTI❑N PREWIRE MUST BE SELECTED, D❑ NOT PR❑VIDE SUPPLY STARTER IN PREWIRE, 1 CASLINK BUILDING M❑NIT❑RING SYSTEM - INTERNET OR CELLULAR C❑NNECTI❑N REQUIRED. 1 RTU SIZE 4 DOWN DISCHARGE, 1 2" MERV 13 FILTERS FOR SIZE 4 RTU, QTY 12. 1 2" MERV 8 FILTERS FOR SIZE 4 RTU. QTY 12. 1 D❑AS 1 OVERHEAT STAT. 1 VFD FACTORY MOUNTED AND WIRED IN C❑MMERCIAL CONTROL VESTIBULE FOR RTU, 1 22 TON MODULATING C❑❑LING ❑PTI❑N, 208/230V, R410A REFRIGERANT, VARIABLE SPEED COMPRESSOR, ECM C❑NDENSING FAN(S), 1 22 TON M❑DULATING REHEAT ❑PTI❑N, SPACE DEWP❑INT CONTROL. 1 RTU FIXED 100% ❑A INTAKE CONTROL, 1 RTU SIZE 4 NO RETURN, 1 SIZE 4 RTU CURB DUCT HANGER. 1 C❑MMERCIAL SMOKE DETECTOR/ALARM INTERL❑CK (SUPPLIED BY OTHERS). 1 CLOGGED FILTER SWITCH WITH N❑TIFICATI❑N ON HMI. 1 VAV PACKAGE W/ MANUAL/DDC CONTROL (571 VFD INCLUDED), 1 5 YEAR ENTIRE UNIT PARTS WARRANTY, 10 YEAR ENTIRE UNIT PARTS WARRANTY WITH REMOTE M❑NIT❑RING AND CAPTIVEAIRE SERVICE CONTRACT, 25 YEAR STAINLESS STEEL FURNACE PARTS WARRANTY (SEE ADDITI❑NAL DETAILS), 1 INLET PRESSURE GAUGE, 0-35", 1 MANIF❑LD PRESSURE GAUGE, -5 TO 15" WC. 1 M❑T❑RIZED BACKDRAFT DAMPER FOR A2-D H❑USING, MEETS AMCA CLASS 1A RATING, 1 TOTAL CFM M❑NIT❑RING FOR MUA UNITS, 1 VAV PACKAGE W/ MANUAL/DDC CONTROL (571 VFD INCLUDED), 1 SIZE 2 DIRECT FIRED HEATER LOW CFM PR❑FILE PACKAGE, USED ON HEATERS UNDER 2500 CFM. 2 MAU-1 1 VFD FACTORY MOUNTED AND WIRED IN C❑MMERCIAL CONTROL VESTIBULE FOR TEMPERED SUPPLY FAN. 1 8 TON 2 CIRCUIT (3/5) MODULAR PACKAGED C❑❑LING ❑PTI❑N FOR SIZE 2 DF/EH MUA (2,900 TO 4,800 CFM), 208V/23OV, 3 PHASE. C❑❑LING THERMOSTAT OR PROGRAMMABLE STAT REQUIRED FOR PROPER OPERATION, 1 DOWNTURN PLENUM FOR SIZE 2 DX C❑IL MODULE, 1 SINGLE P❑INT MPU C❑NNECTI❑N, 2 CONDENSERS, 1 2 YEAR PARTS WARRANTY. 1 GREASE BOX, 1 THROUGH WALL CURB MOUNT INSTALLATION, CURB HEIGHT MUST BE MINIMUM 9" TALLER THAN WALL THICKNESS FOR USE WITH A HINGE KIT. 1 WALL MOUNT C❑NSTRUCTI❑N 18/20 060 IS❑LATORS), 3HP MAX FOR WALL M❑UNTING, 1 SHIP LOOSE DISC❑NNECT FOR REMOTE MOUNT. 3 EF-1 1 FAN BASE CERAMIC SEAL — SHIP LOOSE — FOR GREASE DUCTS. 1 VAV PACKAGE W/ MANUAL CONTROL (VFD INCLUDED), 1 VFD FACTORY MOUNTED AND WIRED IN EXHAUST FAN, 1 VFD MOUNTING BRACKET FOR DU/DR 180 — 200. 1 EXHAUST FAN HEAT BAFFLE, 1 2 YEAR PARTS WARRANTY. 4 EF-2 1 ECM WIRING PACKAGE — EXHAUST — MANUAL OR 0-10VDC REFERENCE SPEED CONTROL —MSC— (TELC❑), CCW R❑TATI❑N, 1 I 12—BDD DAMPER, 1 THROUGH WALL CURB MOUNT INSTALLATION, CURB HEIGHT MUST BE MINIMUM 9" TALLER THAN WALL THICKNESS FOR USE WITH A HINGE KIT. 1 SHIP LOOSE DISC❑NNECT FOR REMOTE MOUNT, 1 SCR-12 BIRD SCREEN. 1 2 YEAR PARTS WARRANTY. FA N A rrF..,:�.S'nRTF..<' FAN UNIT NO TAG EXHAUST SUPPLY GREASE CUP GRAVITY DAMPER WALL MOUNT SIDE DISCHARGE GRAVITY DAMPER M❑T❑RIZED DAMPER WALL MOUNT 2 MAU-1 YES 3 EF-1 YES 4 EF-2 YES PTTRR FAN #3 DU180HFA — EXHAUST FAN (EF-1) 33 TOP VIEW NO O N TAG WEIGHT ITEM SIZE 1 # 1 D❑AS 179 LBS CURB 80,000"W X 111.000"L X 14.000"H ALONG WIDTH, RIGHT INSULATED 16 GAUGE. 2 # 2 MAU-1 107 LBS CURB 31,000"W X 79,000"L X 20.000"H ALONG WIDTH, RIGHT INSULATED, # 2 RAIL 6.000"W X 31.000"L X 20,000"H RIGHT. 3 # 3 EF-1 37 LBS CURB 26,500"W X 26.500"L X 20,000"H ALONG LENGTH, RIGHT VENTED HINGED. 4 # 4 EF-2 25 LBS CURB 17,500"W X 17,500"L X 20.000"H ALONG LENGTH, RIGHT VENTED. 37 3/8 28 FEATURES: - DIRECT DRIVE CONSTRUCTI❑N (N❑ BELTS/PULLEYS), - ROOF MOUNTED FANS, - RESTAURANT MODEL. - UL705 AND UL762 AND ULC-S645 - VARIABLE SPEED CONTROL. - INTERNAL WIRING. - THERMAL OVERLOAD PR❑TECTI❑N (SINGLE PHASE), - HIGH HEAT ❑PERATI❑N 300°F (149°C), - GREASE CLASSIFICATI❑N TESTING. - NEMA 3R SAFETY DISC❑NNECT SWITCH, NORMAL TEMPERATURE TEST /8 EXHAUST FAN MUST OPERATE C❑NTINU❑USLY WHILE EXHAUSTING AIR AT 300°F (149°C) UNTIL ALL FAN PARTS HAVE REACHED THERMAL EQUILIBRIUM, AND WITH❑UT ANY DETERIORATING EFFECTS TO THE FAN WHICH WOULD CAUSE UNSAFE ❑PERATI❑N. DUCTWORK BETWEEN EXHAUST RISER ON HOOD AND FAN (BY OTHERS). ABNORMAL FLARE—UP TEST EXHAUST FAN MUST OPERATE C❑NTINU❑USLY WHILE EXHAUSTING BURNING GREASE VAPORS AT 600'F (316`C) FOR A PERI❑D OF 15 MINUTES WITHOUT THE FAN BEC❑MING DAMAGED TO ANY EXTENT THAT COULD CAUSE AN UNSAFE C❑NDITI❑N. ❑PTI❑NS GREASE BOX. THROUGH WALL CURB MOUNT INSTALLATI❑N. CURB HEIGHT MUST BE MINIMUM 9" TALLER THAN WALL THICKNESS FOR USE WITH A HINGE KIT, WALL MOUNT CONSTRUCTI❑N 18/20 060 IS❑LATORS), 3HP MAX FOR WALL MOUNTING, SHIP LOOSE DISC❑NNECT FOR REMOTE MOUNT, FAN BASE CERAMIC SEAL — SHIP LOOSE — FOR GREASE DUCTS, VAV PACKAGE W/ MANUAL CONTROL (VFD INCLUDED), VFD FACTORY MOUNTED AND WIRED IN EXHAUST FAN, VFD MOUNTING BRACKET FOR DU/DR 180 — 200, EXHAUST FAN HEAT BAFFLE, 2 YEAR PARTS WARRANTY. E 26 1/2" VENTED CURB. '.0 GAUGE ,TEEL ❑NSTRUCTI❑N, R❑❑F ❑PENING / 26 DIMENSIONS, 26 PITCHED CURBS ARE AVAILABLE 0" FOR PITCHED ROOFS, 0° SPECIFY PITCH; 12" EXAMPLE: 7/12 PITCH = 30° SLOPE. REVISIONS DESCRIPTION DATE: 0 'I 0 U I I � I I ' I (a E 0 U ai I I II I co IIII Q U III � N m II I I cm J_ Q I I 2 w I N 0 L0 x Cam') �i 00 _= OC) 00 s 00 t� 00 O di z O O � I 00 1 (_v (a 3 m Y a� m U a� 0 0 2 z L0 C) (0 ClJ V1 L� Q 0 O Q R-1 3 0 73 U1 CF") O Q 5 W I z O (i� W DATE: 8/2/2021 DWG.#: 5018465 DRAW ZKM SCALE: 3/4" = 1 '-0" MASTER DRAWING SHEET NO. 2 i 41741 FSS/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. = �M ao$�� DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 (D CV O 00 CY) p 0 z z O= >Q 0 W o O 0 0 Lu z O LU > J Q J �_ 0 0f p N T — o ti i z m I— C:)W z C:) U) Q LU Q (v U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 S MBER M6.2 c C C C C 0 FAN #4 DUI2HFA - EXHAUST FAN (EF-2) W ❑PE CURB HEIC 22 TOP VIEW THROUGH WALL CURB INSTALLATION ALL SUBSTRATE. WALL OPENIN( 9' MIN FOR USE WITH HINGE KIT, THICKNESS, /2 :R (STEEL ZINC PLATED) SCREW SIZE 3/8' TYP. 1/4' PILOT HOLE, DETAIL A CURB, FEATURES: - DIRECT DRIVE CONSTRUCTION (N❑ BELTS/PULLEYS), - ROOF MOUNTED FANS, - UL705, - VARIABLE SPEED CONTROL, - INTERNAL WIRING, - THERMAL OVERLOAD PR❑TECTI❑N (SINGLE PHASE), - NEMA 3R SAFETY DISC❑NNECT SWITCH. ❑PTI❑NS ECM WIRING PACKAGE - EXHAUST - MANUAL OR 0-10VDC REFERENCE SPEED CONTROL -MSC- (TELC❑), CCW R❑TATI❑N, I 12-BDD DAMPER. THROUGH WALL CURB MOUNT INSTALLATI❑N, CURB HEIGHT MUST BE MINIMUM 9' TALLER THAN WALL THICKNESS FOR USE WITH A HINGE KIT. SHIP LOOSE DISC❑NNECT FOR REMOTE MOUNT. SCR-12 BIRD SCREEN, 2 YEAR PARTS WARRANTY, NOTE: GREASE EXHAUST FAN SHALL HAVE A CLEARANCE OF 18" MINIMUM TO COMBUSTABLE MATERIAL. VENTED CURB, '0 GAUGE TEEL ❑NSTRUCTI❑N, L�vGE, ROOF ❑PENING / 13 DIMENSI❑NS, 13 PITCHED CURBS ARE AVAILABLE 0# FOR PITCHED ROOFS, 0° SPECIFY PITCH: 12' EXAMPLE: 7/12 PITCH = 30° SLOPE, BACKDRAET DAMPER INSTALLATI❑N AIR FLOW n (ROOF ❑PENING), BACKDRAFT DAMPER, CLEARANCE C❑MBUSTIBL 0 FT. SERVICE CLEARANCE 3 FT. (,UMb UJ I IbLLJ 3 h I. C❑MBUSTIBLES 0 FT. TYPICAL DEAS/RTU REEF H0UNTING INSTALLATIEfJ IfJSTRUCTIONS 1, SECURE THE CURB TO THE ROOF FRAMING MEMBERS BY DRILLING 1/4" PIL❑T HOLES IN THE CURB FLANGES AT LOCATIONS SHOWN IN THE DIAGRAM BELOW. USING 3/8" X 2" ZINC PLATED STEEL LAG BOLTS, AND ZINC PLATED WASHERS, SCREW THROUGH THE CURB FLANGES AND INT❑ THE ROOF FRAMING MEMBERS. A MINIMUM OF (5) LAG BOLTS ON EACH SHORT SIDE, AND (7) LAG BOLTS ON EACH LONG SIDE IS REQUIRED. 21 SECURE THE UNIT BASE TO THE SIDE WALLS OF THE CURB USING (24) 1/4"-14 X 2" SELF —DRILLING, STEEL ZINC PLATED SCREWS. PRE —PUNCHED HOLES HAVE BEEN PROVIDED FOR EACH SCREW L❑CATION, D❑AS/RTU. DETAIL 2 cnnr, nrl / KTU TD CURB WALL PRE —PUNCHED > (4 SIDES). L,UI\BI 0 LONG OF CUf T SIDE JRB, TYR DETAIL 1 ANCE TO STIBLES 0 FT. SERVICE CLEARANCE 4 FT. CLEARANCE TO REVISIONS DESCRIPTION DATE: 0 'I O U � I I I 'I E 0 U U C I I II I IIII Q co III � N M I I II CM J_ Q I I 2 w N 0 L0 x v Cam') ci 00 .� 00 M 00 s 0o as w z O = s � I00 1 � T �L C� G CU M Y N N L U a� 0 0 2 Z LO C) (m Cu V1 d L� C� Q 0 CD Q 3 � 3 0F") o 7575 Q L�J I z � o o LLJ DATE: 8/2/2021 DWG.#: 5018465 DRABW1N ZKM SCALE: 3/4" = 1 '-0" MASTER DRAWING SHEET NO. 3 �O c)v W,a sv /j"" i 41741 FSS�oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 c0 CV O 00 M O Z z_ O= Q 0 3: W o LL o O 0 o 3: z O ; > J Q o O _0 0f Cn O N 0 z m I— C:)Lu Z C:) U) a� QLU (�I U LU REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 B 10-28-21 CITY COMMENTS #02 HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SMIMIMBER M6.3 FAN #1 CASRTU4—I.500-24-22T—D❑AS — HEATER (D❑AS) NOTES, LDUVE AIR If D❑ NOT OBSTRUCT ❑UTSIDE OR ❑UTSIDE AIR FAN. )DENOTES CORNER ROOF ❑PENING MUST BE 2' IN BOTH DIRECTI❑NS, AIR INLET, ❑UTSIDE AIR C❑IL WEIGHT. SMALLER THAN CURB DIMENSI❑NS )KN❑TE: SUPPLY DUCT MUST BE INSTALLED TO MEET SMACNA STANDARDS. A MINIMUM STRAIGHT DUCT LENGTH MUST BE MAINTAINED DOWNSTREAM OF UNIT DISCHARGE AS ❑UTLINED IN AMCA PUBLICATI❑N 201. WHEN USING RECTANGULAR DUCTWORK, ELBOWS MUST BE RADIUS THROAT, RADIUS BACK WITH TURNING VANES, FLEXIBLE DUCTWORK AND SQUARE THROAT/SQUARE BACK ELBOWS SHOULD NOT BE USED, ANY TRANSITI❑N AND/OR TURNS IN THE DUCTWORK WILL CAUSE SYSTEM EFFECT, SYSTEM EFFECT WILL DRASTICALLY INCREASE STATIC PRESSURE AND REDUCE AIRFL❑W, D❑ NOT RELY ON UNIT TO SUPPORT DUCT IN ANY WAY. FAILURE TO PROPERLY SIZE DUCTWORK MAY CAUSE SYSTEM EFFECTS AND REDUCE PERFORMANCE OF THE EQUIPMENT, SUGGESTED STRAIGHT DUCT SIZE IS 30,875' x 39,75'. ISCONNECT, 600 MBH PDRATDR 7Q'D). ,P DEPTH. REP ACC LIF (4 1202 LBS 1240 LBS 13 17 1/8' f— MIN, 30.875' 693 LBS 716 LBS ❑PTI❑NS 1. INLET PRESSURE GAUGE, 0-350. 2. MANIF❑LD PRESSURE GAUGE, 0 TO 10" WC, 1 FURNACE. 3. TOTAL CFM M❑NIT❑RING FOR D❑AS. 4, SINGLE P❑INT ELECTRICAL C❑NNECTI❑N FOR RTU, QNTY 1 750VA TRANSFORMER USED. IF A NON—DCV PREWIRE CONTROLS THIS UNIT, THE #28, #47, "MA", OR "E2" ❑PTI❑N PREWIRE MUST BE SELECTED, D❑ NOT PR❑VIDE SUPPLY STARTER IN PREWIRE, 5, CASLINK BUILDING M❑NIT❑RING SYSTEM — INTERNET OR CELLULAR C❑NNECTI❑N REQUIRED, 6. RTU SIZE 4 DOWN DISCHARGE. 7. 2" MERV 13 FILTERS FOR SIZE 4 RTU, QTY 12. 8. 2" MERV 8 FILTERS FOR SIZE 4 RTU. QTY 12. 9. OVERHEAT STAT, 10. VFD FACTORY MOUNTED AND WIRED IN C❑MMERCIAL CONTROL VESTIBULE FOR RTU, 11, 22 TON M❑DULATING C❑❑LING ❑PTI❑N, 208/23OV, R410A REFRIGERANT, VARIABLE SPEED COMPRESSOR, ECM C❑NDENSING FAN(S), 12. 22 TON M❑DULATING REHEAT ❑PTI❑N, SPACE DEWP❑INT CONTROL, 13, RTU FIXED 100% ❑A INTAKE CONTROL. 14. RTU SIZE 4 N❑ RETURN. 15, SIZE 4 RTU CURB DUCT HANGER. 16, C❑MMERCIAL SMOKE DETECTOR/ALARM INTERL❑CK (SUPPLIED BY OTHERS). 17. CLOGGED FILTER SWITCH WITH N❑TIFICATI❑N ON HMI. 18, VAV PACKAGE W/ MANUAL/DDC CONTROL (571 VFD INCLUDED), 19, 5 YEAR ENTIRE UNIT PARTS WARRANTY, 10 YEAR ENTIRE UNIT PARTS WARRANTY WITH REMOTE M❑NIT❑RING AND CAPTIVEAIRE SERVICE CONTRACT, 25 YEAR STAINLESS STEEL FURNACE PARTS WARRANTY (SEE ADDITI❑NAL DETAILS), REVISIONS DESCRIPTION DATE: 0 0 0 0 �I QD 3 0 > I I ' 0- I E 0 U U ai I I II �� IIII III N Ia� L J_ Q I I � w I N 0 x CD ti co co v S a� w z ® 0 o C CO ® CO co L c� C m 0 0 0 U O 0 O O Z 0 co CLJ L� Q 0 � o Q � 3 0 co 75 o E-- Q w 3 I z 0 o cis W DATE: 8/2/2021 DWG.#: 5018465 DRAWN Z K M BY: SCALE: 3/8" = 1 '-0" MASTER DRAWING SHEET NO. 5 �O oV WAs 41741 C; I � I � SS/pNqL EN 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineerinq.net Phone:208.288.2181 Project:21 AMA01 Q0 N O 00 p 0 Z z_ O = Q 0 W U7 0 LL o O 0 3: z O ; > 10 J Q J O � O N z co I— p W it Z C:) U) ~ Q LU N U a REVISION DATE REASON FOR ISSUE HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M6.4 c C C C 0 FAN #2 A2-D,250-20D-MPU - HEATER (MAU-1) 1, DIRECT GAS FIRED HEATED MAKE UP AIR UNIT WITH 20' MIXED FLOW DIRECT DRIVE FAN, 2. INTAKE HOOD WITH EZ FILTERS. 3. DOWN DISCHARGE - AIR FLOW RIGHT -> LEFT, 4. GAS PRESSURE GAUGE, 0-35', 2,5' DIAMETER, 1/4' THREAD SIZE, 5. GAS PRESSURE GAUGE, -5 TO +15 INCHES WC., 2,5' DIAMETER, 1/4' THREAD SIZE. 6. M❑T❑RIZED BACK DRAFT DAMPER 22.75' X 24' FOR SIZE 2 STANDARD & MODULAR HEATER UNITS W/EXTENDED SHAFT, STANDARD GALVANIZED C❑NSTRUCTI❑N, 3/4' REAR FLANGE, LOW LEAKAGE, LF120S ACTUATOR INCLUDED. 7. TOTAL CFM M❑NIT❑RING FOR MUA UNITS, USES +/- 15 PRESSURE TRANSDUCER, RIVET NUTS, 1/4' AIRFL❑W TUBING AND PUSH TO CONNECT FITTINGS, 8. VAV (VARIABLE -AIR -VOLUME) WIRING PACKAGE FOR C❑MMERCIAL FANS, MANUAL SPEED CONTROL VARIABLE FREQUENCY DRIVE INCLUDED, 9. PR❑FILE PLATE CONFIGURATI❑N FOR SIZE 2 DIRECT FIRED UNIT FOR LOW CFM APPLICATIONS. 10. VFD FACTORY MOUNTED AND WIRED IN UNIT CONTROL VESTIBULE. 11. 8 TON, DUAL CIRCUIT (3/5) MODULAR PACKAGED C❑❑LING ❑PTI❑N FOR SIZE 2 DF/EH MODULAR PACKAGED UNIT. INCLUDES CONDENSER, DX C❑IL, FILTER/DRYER KIT, THERMAL EXPANSI❑N VALVE, R410A REFRIGERANT, AND REFRIGERANT PIPING, (2,900 TO 4,800 CFM) WHEN ORDERED WITH ❑PP❑SITE AIRFL❑W CONDENSERS ACCESS AND C❑IL PIPING WILL REMAIN IN STANDARD P❑SITI❑N, DRAIN AND SLEDS WILL MOVE TO THE ❑PP❑SITE SIDE, ANY OTHER CHANGE WILL REQUIRE CLI. CONDENSERS REQUIRE SEPARATE 208V, 3 PHASE POWER SUPPLY UNLESS ORDERED WITH SINGLE P❑INT C❑NNECTI❑N. C❑IL = 3EZ1101D, 12, DOWNTURN PLENUM FOR SIZE 2 C❑❑LING C❑IL MODULE - REQUIRED FOR DOWN DISCHARGE C❑❑LING C❑IL APPLICATI❑NS. 13, SINGLE P❑INT MPU C❑NNECTI❑N, 2 CONDENSERS, 14, HINGED DOUBLE WALL INSULATED DOOR ASSEMBLY (BURNER/BL❑WER/MPU SECTI❑N), 15. 2 YEAR PARTS WARRANTY, SUPPLY SIDE HEATER INF❑RMATI❑N, )KNOTE; SUPPLY DUCT MUST BE INSTALLED TO MEET SMACNA STANDARDS, A MINIMUM STRAIGHT DUCT LENGTH MUST BE MAINTAINED DOWNSTREAM OF UNIT DISCHARGE AS ❑UTLINED IN AMCA PUBLICATI❑N 201. WHEN USING RECTANGULAR DUCTWORK, ELBOWS MUST WINTER TEMPERATURE = 33`F, TEMP. RISE = 60°F, BE RADIUS THROAT, RADIUS BACK WITH TURNING VANES. FLEXIBLE DUCTWORK AND SQUARE THROAT/SQUARE BACK ELBOWS SHOULD BTUs CALCULATED OFF ACTUAL AIR DENSITY, NOT BE USED. ANY TRANSITI❑N AND/OR TURNS IN THE DUCTWORK WILL CAUSE SYSTEM EFFECT, SYSTEM EFFECT WILL OUTPUT BTUs AT ALTITUDE OF 0.0 FT. = 208363, DRASTICALLY INCREASE STATIC PRESSURE AND REDUCE AIRFL❑W, D❑ NOT RELY ON UNIT TO SUPPORT DUCT IN ANY WAY. FAILURE INPUT BTUs AT ALTITUDE OF 0.0 FT, = 226481, TO PROPERLY SIZE DUCTWORK MAY CAUSE SYSTEM EFFECTS AND REDUCE PERFORMANCE OF THE EQUIPMENT, OUTPUT BTUs AT ALTITUDE OF 189 FT, = 206944. SUGGESTED STRAIGHT DUCT SIZE IS 20' x 20', INPUT BTUs AT ALTITUDE OF 189 FT, = 224939, LIFTING LUG, 1 9/16' 18' CURB OUTER WALL. 6' DISCHARGE OPENING, ® 22 3/8' LJ L 4 5/16' 47 1 3 3/4' T_ 20' EQUIPMENT Cam,.. , I - 31' — - I TYPICAL DRAIN TRAP INSTALL RECOMMENDED C❑❑LING C❑IL DRAIN TRAP C❑NFIGURATI❑N, NO UNI❑NS. 7" CLEAN OUT, F I~ 12' MIN. NOTES: 1) 1' DIAMETER PVC PIPE ONLY. 2) USE ONLY LOW PR❑FILE C❑UPLINGS, 3) ADD CLEAN OUT AS SHOWN. 6' MIN. 20" AIRFL❑W, C❑❑LING C❑IL MODULE, 1' MPT C❑NNECTI❑N FOR SS PITCHED DRAIN PAN, FLEX C❑NDUIT FOR FIELD WIRING, H L LL DIRECT FIRED (DF) PROFILE PLATE ASSEMBLY T DIRECT FIRED BURNERS SHALL HAVE PATENTED (US PATENT NO.: US6629523132), SELF—ADJUSTING PROFILE PLATES DESIGNED TO ENSURE PROPER AIR VELOCITY AND PRESSURE DROP ACROSS THE BURNER. PROFILE PLATES SHALL ALLOW BURNERS TO ACHIEVE CLEAN COMBUSTION BY LIMITING BY—PRODUCT LEVELS TO A MAXIMUM OF 5PPM OF CARBON MONOXIDE (CO), AND 0,5PPM OF NITROGEN DIOXIDE (N021)IRECT FIRED UNITS SHALL BE CONFIGURED WITH THE BLOWER MOUNTED DOWNSTREAM OF THE BURNER. THIS ARRANGEMENT WILL ENSURE A CONSISTENT AIRFLOW, REGARDLESS OF INLET AIR TEMPERATURE. APPLICATION, SPRING —LOADED BURNER PROFILE PLATES ARE ENGINEERED TO AUTOMATICALLY REACT TO THE MOMENTUM OF A FRESH AIR STREAM, WITHOUT THE NEED FOR ANY MOTORS OR ACTUATORS TO MECHANICALLY ADJUST THEM. WITH THIS FEATURE, ALL DF UNITS ARE DESIGNED FOR DEMAND CONTROL VENTILATION (DCV) REQUIREMENTS. CERTIFICATIONS, ALL PROFILE PLATE ASSEMBLIES SHALL BE INCLUDED IN THE DF UNIT'S ETL LISTING AND COMPLY WITH COMBINED SAFETY STANDARDS ANSI Z83.4 AND CSA 3.7 (NON —RECIRCULATING DF HEATERS) AND ANSI Z83.18 (RECIRCULATING DF HEATERS). GENERAL CONSTRUCTION, —PROFILE PLATES SHALL BE FORMED FROM G90 GALVANIZED STEEL. —PROFILE PLATES SHALL VARY IN SIZE PER UNIT, —PROFILE PLATES SHALL BE MOUNTED ALONG THE SAME PLANE AS THE DISCHARGE OF THE BURNER. —DESIGN SHALL INCORPORATE PROPERLY TORQUED, PERMANENTLY MOUNTED SPRING HINGES, —SPRING HINGES SHALL BE MADE FROM PLATED STEEL, REVISIONS DESCRIPTION DATE: 0 `I O I � I� I ' I CU E 0 U U m II II � I co IIII Q 0 III � N m I I II cm J_ < I I � w I N_ O L0 x v cam') V 00 .- s 00 w z O O = s � 00 0 1 c� �L C� G ca 3 co `1 N U a� 0 0 0 2 Z LO O CU V1 d L� od5 Q 0 (� CD Q 3 � 3 0F") O 75 L�J I C z � o o cis LL DATE: 8/2/2021 DWG.#: 5018465 DRAW ZKM SCALE: 3/4" = 1 '-0" MASTER DRAWING SHEET NO. 6 °`A''f 41741 � FSS/oNAL 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 (D CV O 00 CY) p 0 Z z_ O= Q 0 3: W 0 O O0 Lu 3: z O ; > J Q J O -0 0f p N — o i z m I— C:)W Z C:) U) Q Ir Q (v U a REVISION DATE REASON FOR ISSUE HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 S MBER M1 M6.5 C C' C C C r 0 D 0 L THE CADDY VENTILATOR TESTING, LISTING AND APPROVAL REFERENCES: NATIONAL FIRE PROTECTION ASSOCIATION IN ACCORDANCE WITH RECOMMENDATION OF NATIONAL FIRE PROTECTION ASSOCIATION'S NFPA NO. 96 "VAPOR REMOVAL FROM COOKING EQUIPMENT" NATIONAL SANITATION FOUNDATION STANDARD #2 - "FOOD SERVICE EQUIPMENT" ETL, INTERTEK TESTED UNDER STANDARD U.L. 710 "EXHAUST HOODS FOR COMMERCIAL COOKING EQUIPMENT". ETL LISTED UNDER CONTROL # 3177269 UNIFORM MECHANICAL CODE SECTION 507 - COMMERCIAL KITCHEN HOODS AND KITCHEN VENTILATION SYSTEMS THE BOCA NATIONAL MECHANICAL CODE CHAPTER 5 - KITCHEN EXHAUST EQUIPMENT STANDARD MECHANICAL CODE (SBCCI) SECTION 504 - COMMERCIAL HOODS UNIFORM BUILDING CODE (ICBO) INTERNATIONAL MECHANICAL CODE (IMC) SECTION 507 - COMMERCIAL KITCHEN HOODS EXCLUDES CODE #507.2.1.1, CONSULT FACTORY FOR COMPLIANCE OPTIONS. NOTE: K.E.C. MUST VERIFY THE EXACT DIMENSION OF THE COOKING EQUIPMENT FROM EITHER THE WALL OR FROM THE FRONT OF THE HOOD, SO CADDY MAY PROPERLY LOCATE THE FIRE PROTECTION NOZZLES AT TIME -OF -FABRICATION IN THE FACTORY. IF EQUIPMENT IS NOT LOCATED AS SHOWN AND THE DRAWING IS APPROVED FOR FABRICATION, THEN NOZZLES MUST BE RELOCATED AT THE EXPENSE OF OTHERS. CONTRACTOR NOTE: ALLOW SUFFICIENT ACCESS ON TOP OF VENTILATOR TO SERVICE COMPONENTS AND UTILITIES MAKE-UP AIR NOTE: AIR TEMPERATURE SHOULD RANGE FROM 60° TO 65°F, BUT MAY BE AS LOW AS 50' F DEPENDING ON AIR VOLUME, DISTRIBUTION, AND INTERNAL HEAT LOAD 9/16" HOLE FOR 1/2" THREADED ROD (RODS AND HARDWARE BY K.E.C.) 5'-0" V-6" (13) HANGER BRACKETS (SEE DETAIL A -A) STN.ISTL. GREASE CUP 112" DIA. BY 6-0" LONG PLATED STEEL HANGER RODS AND BOLTS FURNISHED BY K.E.C. 12 GA. STN. STL. HANGER BRACKETS FULLY WELDED TO VENTILATOR BY CADDY HANGER BRACKET DETAIL A -A SCALE: 1/4"=1" GENERAL CONTRACT CONDITIONS ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE WITH THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION. ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND ACKNOWLEDGED ON OUR STANDARD FORM. CADDY SMART HOOD EXHAUST AIR Z TEMP. SENSORS e • • t' '.d. -e. �d 3" n CADDY SMART HOOD CANOPY �D TEMP. SENSOR [ r r____________________________r r ,F -- ---------------- -------------- -------------- -------------------------- J, I 7'-6" 15'-0" — 16-0" PLAN SCALE: 1 /2"=1'-0" TOTAL EXHAUST: 4,200 C.F.M. TOTAL SUPPLY : 3,360 C.F.M. 10" X 34" EXHAUST DUCT 12" X 24" SUPPLY DUCTS 1 4,200 C.F.M. @ 1.40" S.P. 2 1,680 C.F.M. @ 0.20" S.P. 1 T l e 0 0 O O ITEM #75 DBL DECK COVN OVEN VULCAN VC66GD v ITEM #68 ITEM #70OII CHARBROILER o a LIFT OUT DOORS STEAMER CLEVELAND GARLAND ITEM #71 21CGA5 GTBG24-NR24 RANGE/ GRIDDLE ® ®®QQ GARLAND ® ® ITEM #66 EE� G60-6G24RR FRYER ITEM #69 = = - VULCAN REFRIGERATED BASE = = 1 GR35M ITEM #66.1 FILTRATION SYSTEM RANDELL == VULCAN 200485C — M F-1 ELEVATION SCALE: 1/2"=V-0" K.E.C. TO VERIFY ALL MAKES AND MODELS OF COOKING EQUIPMENT, REVIEW PLAN FOR PROPER LINE-UP PRIOR TO FABRICATION OF VENTILATORS, AND TO NOTIFY CADDY OF ANY CHANGES. ANSUL ENCLOSURE 40% OPEN STN./STL. PERFORATED DIFFUSER MINIMUM OVERHANG FROM EDGE OF COOKING EQUIPMENT TO END OF HOOD MUST BE 6" INSTALLATION INFORMATION ALLOW SUFFICIENT ACCESS TO BRING VENTILATOR INTO KITCHEN AREA MAXIMUM VENTILATOR DIMENSIONS 16-0" LONG x 5-0" WIDE x 28 1/2" HIGH ESTIMATED TOTAL HANGING WEIGHT: 1,500 LBS. VENTILATOR TO BE SHIPPED IN (2) UNITS. ALL PLUMBING AND ELECTRICAL DISCONNECTED FOR SHIPMENT. RECONNECTED IN FIELD BY PLUMBING AND ELECTRICAL CONTRACTORS. ELECTRICAL NOTES- 1 LIGHT FIXTURES, VAPORPROOF, U.L. LISTED, FURNISHED, INSTALLED AND WIRED TO J-BOX OD BY CADDY. 2, LIGHT SWITCH FOR LIGHT FIXTURE WITH 120 VOLTS A.C. SERVICE BY CADDY. LIGHT SWITCH (SMART HOOD KEYPAD) LOCATED IN REMOTE LOCATION. SECTION Z-Z GENERAL NOTES EXHAUST AIR REQUIREMENTS: 1. EXHAUST C.F.M. BASED ON 280 C.F.M. PER LINEAR FOOT. 2. EXHAUST STATIC PRESSURE IS 1.40" W.G. AT DUCT TAKE -OFF COLLAR. TOTAL DUCT STATIC MUST BE ADDED. STATIC BASED ON OPERATION AT MEAN SEA LEVEL. 3. DUCT SIZE BASED ON 1,800 F.P.M. EXHAUST FAN REQUIREMENTS: 1. EXHAUST FAN DISCHARGE SHOULD BE VERTICAL; AWAY FROM AIR INTAKES. FAN FURNISHED BY OTHERS. 2. EXHAUST FAN MUST BE FURNISHED WITH A MAGNETIC STARTER WITH 120 VOLT HOLDING COIL. STARTER FURNISHED BY OTHERS. MAKE-UP AIR REQUIREMENTS: 1. AIR EXHAUSTED FROM KITCHEN MUST BE REPLACED - WITH DISTRIBUTION CONTROLLED TO PROVIDE FOR TOTAL KITCHEN. VENTILATION AND TO ESTABLISH NECESSARY AIR PATTERNS FOR PROPER PERFORMANCE OF THE VENTILATORS. AIR DISTRIBUTION SYSTEMS SHALL BE IN ACCORDANCE WITH ALL GOVERNING CODES. 2. MAKE-UP AIR MUST BE TEMPERED -HEATED OR COOLED -CONSISTENT WITH THE STYLE OF HOOD, HEAT LOAD, CLIMATIC CONDITIONS AND APPLICABLE CODES- 3. FAN MUST BE FURNISHED WITH A MAGNETIC STARTER WITH 120 VOLT HOLDING COIL. STARTER FURNISHED BY OTHERS. INSTALLATION: 1. VENTILATORS TO BE INSTALLED IN ACCORDANCE WITH ALL CODES. CONTRACTORS MUST REVIEW APPLICABLE CODES WITH CODE AUTHORITIES BEFORE APPROVING DRAWINGS FOR FABRICATION. SPECIAL ATTENTION MUST BE GIVEN TO CODE REGULATIONS RELATIVE TO CLEARANCES FROM SURROUNDING COMBUSTIBLE CONSTRUCTION (WALL, CEILINGS, ETC.). 2. VENTILATORS ARE NOT TO BE INSTALLED IN AREAS MEANT TO HANDLE ENVIRONMENTAL AIR. 3. ALL DUCTWORK BEYOND VENTILATOR DUCT TAKE -OFF COLLAR TO BE PROVIDED AND INSTALLED BY OTHERS, IN ACCORDANCE WITH JURISDICTIONAL CODES. DUCTS MUST BE MECHANICALLY STRONG, GREASE AND WATER TIGHT. 4. MOUNTING RODS FURNISHED AND INSTALLED BY OTHERS. CONSTRUCTION: 1. VENTILATORS TO BE MANUFACTURED IN STRICT ACCORDANCE WITH CADDY SPECIFICATIONS. 2. VENTILATORS CONSTRUCTED OF 18 GA. STAINLESS STEEL. FIRE PROTECTION: 1. SURFACE FIRE PROTECTION PROVIDED AND INSTALLED BY CADDY (ANSUL R-102). 2. CAUTION: SURFACE FIRE PROTECTION SYSTEM INSTALLATION MUST -A BE COORDINATED WITH CADDY TO PREVENT SYSTEMS INTERFERENCE WITH VENTILATOR'S OPERATION/PERFORMANCE. IMPROPER INSTALLATION MAY VOID LISTINGS OF THE EQUIPMENT. 3. IMPORTANT NOTE NFPA 96 REQUIRES THAT ALL GAS AND ELECTRIC COOKING EQUIPMENT THAT IS PROTECTED BY A SURFACE FIRE PROTECTION SYSTEM MUST AUTOMATICALLY SHUT OFF UPON GH VELOCITY ACTIVATION OF THE SYSTEM. REASE EXTRACTOR / WOOLGUARD ELECTRICAL REQUIREMENTS: 1. LIGHT FIXTURE BULBS PROVIDED AND INSTALLED BY CADDY. MOVABLE N./STL. :EASE CUP 1 US N S F. Intertek NFPA® �O oH WASMi� I� 41741 �'�FSS�OrsA�R N L 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineerinn. net Phone:208.288.2181 Project:21 AMA01 Q0 N O TO\ v/ Cl) o z z_ O= >Q> W U) LL z O0 z O > > 10 J Q J o O -0 O N CI-4z 0 m F— C:) w z C:)U Q LU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M6.6 0 1 0 0 o a ITEM #75 CONVECTION OVEN VULCAN VC66GD J 0 o a TYPICAL WET CHEMICAL FIRE PROTECTION SYSTEM INTERLOCK (CONDUIT AND BOX BY E.C.) CABLE BY FIRE SYSTEM CONTRACTOR MANUAL PULL FIRE HVAC/MAKE-UP AIR AND GAS/ ELECTRICAL EQUIPMENT PROTECTION PANEL SHUTDOWN WHEN USING AN MECHANICAL GAS VALVE 1. CONNECT THE INCOMING LIVE LEAD (A) TO THE COMMON i (B) TERMINAL SWITCH. - - 2. CONNECT THE FIRE-STAT RELAY (B). w (A) BY E.C. 3. CONNECT THE SHUNT TRIP RELAY TO THE MICRO -SWITCH (C). NEUTRAL BY E.C. 1�. la 9- WHEN DETECTION LINES OR HAND "PULL" STATION ENERGIZE THE FIRE PROTECTION SYSTEM, THE MICRO -SWITCH REPOSITIONS TO: 1. ACTIVATE SHUNT TRIP CIRCUIT BREAKER, SHUTTING OFF FUEL AND POWER TO THE EQUIPMENT 2. TRANSFER POWER TO THE FIRE-STAT RELAY TO OPEN CONTACT TO SHUT DOWN HVAC UNIT (SUPPLY AIR). 3. DETECTION LINE WILL CLOSE MECHANICAL GAS VALVE o-F-- I I MICRO -SWITCH SPDT ----------n 2 Q 450°f 360° 3 ° 1 41 3 ITEM #68 ITEM #70 STEAMER CHARBROILER CLEVELAND GARLAND 21 CGA5 ®I I GTBG24-NR24 ITEM #69 REFRIGERATED BASE RANDELL 20048SC POWER TO COOKING EQUIPMENT ITEM #71 RANGE ®® 04 GARLAND 0 0 ® ITEM #66 G60-6G24RR FRYER VULCAN 1 GR35M ITEM #66.1 FILTRATION SYSTEM VULCAN MF-1 POWER TO COOKING EQUIPMENT i SHUNT TRIP CIRCUIT BREAKER IN ELECTRICAL PANEL BY E.C. OR LIDS BY UDS MANUFACTURER I , I , MECHANICAL CABLE ASSEMBLY MECHANICAL GAS VALVE (NORMALLY CLOSED) � I I , I II , I I TO NC OR NO �-------- y� SWITCH AS REQ'D I UQ BY ALARM ALARM IF ! REQ'D I MICRO -SWITCH 1 CABLE BY FIRE SYSTEM CONTRACTOR CONDUIT BY E.C. HVAC UNIT CONTROLPANEL ------- I I I I I I I 1 I I FIRE-STAT RELAY BY HVAC WIRING BETWEEN COMPONENTS BY E.C. (LOCATED IN PANEL) REMOTE PULL STATION A A ELECTRIC SNAP -ACTION B SWITCH BY CADDY ❑ ❑ D G�i I 3.0 GALLON 3.0 GALLON TANK TANK TANK/ENCLOSURE ASSEMBLIES DOUBLE TANK NITROGEN CARTRIDGE ANSUL R-102 3/3 SYSTEM_ FOR VENTILATOR ITEMS #76 PLENUM PROTECTION NOZZLE DUCT PROTECTION NOZZLE I I _ APPLIANCE PROTECTION J' REMOTE MANUAL NOZZLE PULL STATION ' HINGED STAINLESS STEEL SERVICE DOOR I _ AGENTTANK I _ OEM RELEASE/ BRACKET ASSEMBLY TYPICAL ANSUL R-102 SYSTEM LAYOUT ANSUL NOZZLE DATA FLOW POINTS MIN. -MAX. SYM QTY DESCRIPTION HEIGHT EACH ABOVE HAZARD 1 4 ANSUL #1 N 1 15"- 40" (CHARBROILER) 35"- 40" GRIDDLE 2 1 ANSUL #2W 2 3 1 ANSUL #3N 3 21 "-34" (FRYER) 4 2 ANSUL #1 F 1 40"-48" (RANGE) UOL 0 UNDERWRITERS LABORATORIES, INC TESTED UNDER STANDARD U.L. 300 "FIRE TESTING OF FIRE EXTINGUISHING SYSTEMS FOR PROTECTION OF RESTAURANT COOKING AREAS ". no NFPA" 41741 FSS/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. = �M ao$�� DC ENGINEERING Careful listening. Dynamic solutions. www.drengineering.net Phone:208.288.2181 Project:21 AMA01 CV O rn p n Z z 0= Q W o 0 OLLI Z O w > J / < J O (if � C: 0 N 0 I` z m W Z N U) Q LU Q cal U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 S MBER -mmIIIIIIEff- M6.7 C C C, C C r 9/16" HOLE FOR 1/2" THREADED ROD (RODS AND HARDWARE BY K.E.C.) 1/2" DIA. BY 6-0" LONG PLATED STEEL HANGER RODS AND BOLTS FURNISHED BY K.E.C. 12 GA. STN. STL. HANGER BRACKETS FULLY WELDED TO VENTILATOR BY CADDY HANGER BRACKET DETAIL A -A SCALE: 1 /4"=1 " GENERAL CONTRACT CONDITIONS ELECTRICAL WORK DONE BY CADDY CORPORATION IS EXECUTED IN COMPLIANCE WITH STANDARDS PUBLISHED BY THE UNDERWRITER'S LABORATORIES, INC. INSOFAR AS APPLICABLE WITH THE NATIONAL ELECTRICAL CODE (NEC). CADDY CORPORATION DOES NOT ACCEPT ANY RESPONSIBILITY FOR THE REQUIREMENTS OF ANY REGIONAL AND/OR LOCAL CODES THAT ADD OR DEVIATED FROM THE ACCEPTED STANDARDS OF THE ABOVE AGENCIES. ANY FIELD WORK RELATING TO THE MODIFICATION OF ELECTRIC OR PLUMBING SYSTEMS, TO MEET REGIONAL OR LOCAL CODE REQUIREMENTS, IS TO BE DONE BY OTHERS AND WITHOUT BACK CHARGES TO CADDY CORPORATION, UNLESS THESE CONDITIONS WERE PREVIOUSLY BROUGHT TO OUR ATTENTION AND ARE EXPRESSLY INCLUDED IN OUR WRITTEN QUOTATION. ALL WIRING AND PLUMBING AT THE JOB SITE IS THE RESPONSIBILITY OF OTHERS. EQUIPMENT WILL BE CONSTRUCTED IN ACCORDANCE WITH OUR DRAWING(S) WHICH MUST BE APPROVED PRIOR TO FABRICATION. ANY SUBSEQUENT CHANGES REQUIRED MUST BE SUBMITTED TO US IN WRITING AND ACKNOWLEDGED ON OUR STANDARD FORM. 4 Z 1/2" 0 DRAIN Z-0" 4'-0" 2'-0" �� Z 4'-0" IwW_1►1 SCALE: 1 /2"= V-0" TOTAL EXHAUST: 600 C.F.M. 7" X 7" EXHAUST DUCT 600 C.F.M. @ 0.50" S.P. 0 4'-0" V-8 1/2" 7" V-8 1/2" ELEVATION SCALE : 1/2"=T-0" (4) HANGER BRACKETS (SEE DETAIL A -A) 1/2" 0 DRAIN INSTALLATION INFORMATION ALLOW SUFFICIENT ACCESS TO BRING VENTILATOR TO BE SHIPPED IN (1) UNIT. VENTILATOR INTO KITCHEN AREA ALL PLUMBING AND ELECTRICAL DISCONNECT - MAXIMUM VENTILATOR DIMENSIONS TED FOR SHIPMENT. RECONNECTED IN FIELD 4'-0" LONG x 4'-0" WIDE x 28 1/2" HIGH BY PLUMBING AND ELECTRICAL CONTRACTORS. ESTIMATED HANGING WEIGHT: 220 LBS. 9'-2" FIN. CLG. HEIGHT [ ] VERIFY SECTION Z-Z SCALE: 3/4"=T-0" NOTES =ULL PERIMETER SUTTER 1/2" 0 DRAIN (INDIRECT WASTE) 1. AIR SYSTEMS SHALL NOT BE LIABLE FOR IMPROPER FUNCTION DUE TO CHANGE IN STATIC PRESSURE OR AIR VOLUMES SPECIFIED. 2. ALL DIMENSIONS TO BE VERIFIED IN FIELD BY OTHERS BEFORE VENTILATORS ARE RELEASED FOR MANUFACTURE. 3. INDICATE ALL BEAMS, COLUMNS, ETC. WHICH MAY CONFLICT WITH VENTILATOR OR EXHAUST OUTLET COLLAR(S) (INDICATE SIZE, LOCATION, AND HEIGHT ABOVE FINISHED FLOOR.) 4. INSTALLING CONTRACTOR SHALL CHECK ALL BUILDING ACCESS, ENTRANCE AND FIELD CONDITIONS TO ENSURE SUFFICIENT CLEARANCE TO ALLOW VENTILATOR SECTION(S) (SIZE(S) AS DIMENSIONED ON THIS DRAWING) TO BE BROUGHT INTO BUILDING AND INSTALLED ACCORDING TO AIR SYSTEMS RECOMMENDATIONS. 5. ALL EXHAUST DUCT COLLARS ARE INSIDE DIMENSIONS. 6. ALL DUCTWORK BEYOND THE VENTILATOR OR EXHAUST DUCT COLLAR(S) TO BE PROVIDED AND INSTALLED BY OTHERS IN ACCORDANCE WITH JURISDICTIONAL CODES, AND MUST BE MECHANICALLY STRONG, AND GREASE AND WATER TIGHT. 7. VENTILATOR(S) SHALL BE N.S.F. APPROVED AND SHALL BEAR N.S.F. LABELS VISIBLY AFFIXED TO EXTERIOR. 8. VENTILATORS CONSTRUCTED OF 18 GA. STAINLESS STEEL. THE CADDY VENTILATOR TESTING, LISTING AND APPROVAL REFERENCES: NATIONAL SANITATION FOUNDATION Standard #2 - "Food Service Equipment" REVISIONS I REV I DATE I BY I REMARKS I A 1 09/02/20 1 KCT I NO CHANGES TO THIS SHEET B 1 04/01/21 1 AKG I NO CHANGES TO THIS SHEET NSF CADDY CORPORATION I 509 SHARPTOWN ROAD, P.O. BOX 345 L(cc_= BRIDGEPORT, NJ 08014 TEL:(856) 467-4222 FAX:(856) 467-5511 WWW. CADDYCORP.COM EQUIPMENT SCHEDULE ATOW UN , 1.01 M bm.*] CADDY NO. 35332 ITEM NO. 30 JOB: CA VENTURES EDMONDS LOC: EDMONDS, WASHINGTON CUST: CUST#: DATE SCALE 08/08/2019 AS NOTED DWG# 35332 SHT 3 AK JJ_ DR BY APP'D BY W OF 7 � �N �O oV WASH �� 41741 Q 1 � 11', FSS/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineerinq.net Phone:208.288.2181 Project:21 AMA01 Q0 N O 00 O') p C] Z z O= >Q C] LU C 0 O 0 0 �LLI 0 > Z O > > 10 J Q J O N CI-4 0 Z m I— C:)LLJ �* Z o U) Q IY N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M6.8 C C C C r ) J J J J 0 D 0 L J D n INSTALLATION REQUIREMENTS 1. THERE SHALL BE NO SUBSTITUTIONS OF ANY COMPONENTS ON MELINK INTELLI-HOOD CONTROLS UNLESS APPROVED BY MELINK. 2. MELINK CERTIFIED STARTUP CONTRACTOR IS NOT RESPONSIBLE FOR HIGH VOLTAGE ELECTRICAL WIRING. 3. MELINK CERTIFIED STARTUP CONTRACTOR IS NOT RESPONSIBLE FOR INSTALLING LOW VOLTAGE CONTROL CABLES LONGER THAN 50', ONLY MELINK CABLES SHALL BE USED. 4. MELINK CERTIFIES STARTUP CONTRACTOR IS NOT RESPONSIBLE FOR INSTALLING LOW VOLTAGE CABLES IF ACCESS TO THE TOP OF THE HOOD IS LIMITED DUE TO OBSTRUCTIONS (LOW CEILING, DUCTWORK, PIPING, ETC.) CALL MELINK FOR MORE INSTRUCTIONS IF NECESSARY. 5. MELINK CERTIFIED STARTUP CONTRACTOR IS NOT RESPONSIBLE FOR INSTALLING ANY CONDUIT IF REQUIRED; OR MAKING ANY CEILING, FLOOR OR WALL PENETRATIONS. 6. MELINK INTELLI-HOOD LITERATURE WILL BE INCLUDED IN THE SHIPMENT OF EACH SYSTEM. CALL MELINK WITH ANY QUESTIONS @ 1-(513)-965-7300. 7. ALL MOTORS MUST BE 3 PHASE, INVERTER DUTY RATED AS SPECIFIED IN NEMA STANDARD MG 1 PART 31. 8, DV/DT FILTERS MUST BE USED WHEN THE DISTANCE FROM VFD TO FAN IS OVER 200' FOR 230V, 70' FOR 460V, OR 40' FOR 575V. 9. OPTION: MELINK RECOMMENDS A CERTIFIED AIR BALANCE ON THE KITCHEN VENTILATION SYSTEM FOR OPTIMAL ENERGY SAVINGS. AGENCY APPROVALS THE MELINK INTELLI-HOOD CONTROLS ARE UL & CUL LISTED, & CONFORM WITH ALL APPLICABLE CODES & STANDARDS INCLUDING: 1. UL710 - STANDARD FOR EXHAUST HOODS FOR COMMERCIAL COOKING EQUIPMENT 2. UL2017- STANDARD FOR GENERAL PURPOSE SIGNALING DEVICES AND SYSTEMS. 3. CE - MEETS REQUIREMENTS OF APPLICABLE EC DIRECTIVES 4. ROHS - MEETS THE RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE 2002l951EC 5. NFPA 96 - STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS 6. IMC - INTERNATIONAL MECHANICAL CODE 7. BOCA - BUILDING OFFICIALS CODE ADMINISTRATORS 8. SBCCI - SOUTHERN BUILDING CODE CONGRESS INTERNATIONAL 9. ICBO - INTERNATIONAL CONFERENCE OF BUILDING OFFICIALS LAYOUT SYMBOLS LEGEND iNTELLµloaa TOUCHPAD HC(01) ALC(01) APS(01) SIN ELL/-Hppp HOO D CONTROLLER AUXILIARY AUXILIARY POWER CONTROLLER SUPPLY SYSTEM CONTROLLER AUXILIARY TOUCHPAD 101 E -L T AIR PURGE OPTIC TEMP SENSOR TEMP SENSOR PASS PURGE UNIT PIPE SENSOR (VARIABLE SPEED) (AUTO ON/OFF) THROUGH VFD HP V/3 EF HOOD-# O SUPPLY EXHAUST SUPPLY EXHAUST VFD FAN FAN COLLAR COLLAR 1 PHASE POWER ------------ MELINK CONTROL CABLE 3 PHASE POWER IN - - - - LOW VOLTAGE CABLE 3 PHASE POWER OUT -- -- - - ETHERNET LINE SHEET INDEX SHEET # SHEET DISCRIPTION I # INTELLI-HOOD DRAWING SHEETS GENERAL COMPONENT 01 NOT SITE SPECIFIC SYSTEM CONTROLLEF VFD "VARIABLE FREQUENCY DRIVES" TO BE FIELD INSTALLED BY ELECTRI (REFER TO DETAIL 3 FOR SYSTEM CONTROLLI ( REFER TO DETAIL 4 FOR VFD POWE INTELLI-HOOD* oDR RETRO-FIT SCOPE OF WORK INi OPT;c SEN�v SEQUENCE OF OPERATION 1. PRESS THE FAN SWITCH ON THE TOUCHPAD TO TURN THE FANS ON IN THE AUTO MODE. A. SYSTEM CONTROLLER STARTS THE FANS AT MINIMUM SPEED AND AUTOMATICA'_LY ADJUSTS EXHAUST AIR FLOW BASED ON THE ACTUAL COOKING LOADS AS SENSED BY THE TEMPERATURE AND OPTIC SENSORS MOUNTED IN THE HOODS. (SYSTEM CONTROLLER WILL SEND A RUN COMMAND AND SPEED REFERENCE SIGNAL TO THE VARIABLE FREQUENCY DRIVES (VFD'S).) B. SYSTEM CONTROLLER WILL CONTROL MAKE UP AIR FAN VFD(S). SYSTEM CONTROLLER WILL SEND A 24VDC SIGNAL TO THE MUA UNIT TO ENERGIZE THE CONTROL CIRCUIT. IN THE EVENT THE MUA UNIT GOES INTO HEATING MODE, THE MUA UNIT WILL PROVIDE A DRY CLOSURE SIGNAL TO THE SYSTEM CONTROLLER TO INCREASE THE MINIMUM AIR FLOW ACROSS THE BURNER OR HEAT EXCHANGER. B. SYSTEM CONTROLLER WILL PROVIDE A STARTISTOP AND 0-10VDC OR 4-20MA SIGNAL TO THE BAS TO CONTROL MUA. 2. PRESS THE FAN SWITCH AGAIN TO TURN THE FANS OFF. 3. PRESS THE LIGHT SWITCH ON THE TOUCHPAD TO TURN THE HOOD LIGHTS ON. THE TERMINALS OF THE SYSTEM CONTROLLER OR AUXILIARY LIGHTS CONTROLLERS. (LIGHTS MAY BE OPERATED BY OTHER CONTROLS OR BAS.) 4. IF THE AUTO ON/OFF TEMP SENSOR DETECTS HEAT LEVELS ABOVE 90°F132°C WHEN THE FANS ARE NOT ON, THE FANS WILL TURN ON AUTOMATICALLY. 5. IN THE EVENT OF FIRE MODE, POWER IS TURNED OFF TO THE SYSTEM CONTROLLER, THE EXHAUST FAN VFD WILL RUN AT FULL SPEED, AND MUA VFD WILL STOP. SEE DETAIL 4. US PATENTS - 6,170,480 ; 7,048,199 ; 9,810,437 CANADA PATENT-297682 PLUG-N-PLAY CABLE CONNECTIONS GENERAL WIRING OVERVIEW. NOT SITE SPECIFIC F F F _________J L____J W W W' SYSTEM LAPTOP, CONTROLLER _J L_ AND/OR BAS ""-'"�" BACnet ( ) i i i L------------------- I O I I I OUCHPA --J I I AUX POWER SUPPLY i r--------------------------J I - -- AUX LIGHT HOOD 1 F HOOD2_HOOD 3 ONTROLLER ONTROLLE1CONTROLLERf 1CONTROLLE i i i I AUX � � I TOUCHPAD APUS, OPTICS, APUS, OPTICS, FTPUS, OPTICS, TEMP SENSORS TEMP SENS I TEMP SENSORS HOOD 4 CONTROLLE NOTE: CAN SPECIFY 1-30 HOOD CONTROLLERS PER SYSTEM CONTROLLER ELECTRICAL SCOPE OF WORK 1. INSTALL SYSTEM CONTROLLER(S) IN LOCATION DICTATED ON PRINTS OR COORDINATED WITH CUSTOMER. REFER TO SYSTEM LAYOUT(S), 2. INSTALL TOUCHPAD(S) ON WALLS OR HOODS AT LOCATIONS DESIGNATED ON PRINT OR COORDINATE WITH CUSTOMER. REFER TO SYSTEM LAYOUT(S). 3. INSTALL TOUCHPAD CABLE IN CONDUIT WHERE EXPOSED. 4. INSTALL THE VFDS (X) IN LOCATIONS DESIGNATED ON PRINTS OR LOCATION COORDINATED WITH CUSTOMER. REFER TO SYSTEM LAYOUT. 5- INSTALL ETHERNET CABLE FROM BUILDING NETWORK TO THE SYSTEM CONTROLLERS. REFER TO DETAIL 1. CONFIGURE THE BUILDING NETWORK TO ALLOW SYSTEM CONTROLLER TO COMMUNICATE WITH MELINK HEADQUATERS SECURE INTELLI-HOOD 3 SERVER. IF APPLICABLE, CONFIGURE THE BUILDING'S BACnet AUTOMATION SYSTEM TO COMMUNICATE WITH THE INTELLI-HOOD 3 SYSTEM CONTROLLER. 6- PULL AND CONNECT MELINK CONTROL WIRE FROM SYSTEM CONTROLLER(S) TO VFDS AND FROM VFD-TO-VFD. REFER TO SYSTEM LAYOUT(S)- 7, PULL SENSOR AND/OR VFD CABLES OVER 50 FEET AND ANY CABLES THAT REQUIRE FLOOR, CEILING, OR WALL PENETRATIONS. 8- WIRE THE SYSTEM CONTROLLER INSIDE THE INTELLI-HOOD CONTROL CABINET, OR OTHER SPECIFIED LOCATION, WITH AN INPUT OF 90/250VAC FROM A DEDICATED CIRCUIT. THIS CIRCUIT MUST LOSE POWER WHEN THE FIRE SUPPRESSION SYSTEM IS ACTIVATED. PURPOSE IS TO SHUT OFF HOOD LIGHTS AND SEND EXHAUST FANS TO FULL SPEED, THE OUTPUT WIRING TO BE CONNECTED TO THE HOOD LIGHTS (15 AMPS MAX). SEE DETAIL 3. 9- WIRE THE VARIABLE FREQUENCY DRIVES (VFD) INSIDE THE CONTROL CABINET, OR IN SPECIFIED LOCATION, BY CONNECTING 3-PHASE INPUT POWER FROM THE CIRCUIT BREAKERS. THE OUTPUT WIRING IS TO BE CONNECTED TO THE RESPECTIVE FAN MOTOR. THE OUTPUT WIRING FROM EACH VFD MUST BE RUN IN SEPARATE CONDUIT. SEE DETAIL 4. 10. WIRE A DEDICATED SINGLE PHASE CIRCUIT TO THE MUA UNIT TO ENERGIZE THE MUA CONTROLS. DO NOT USE VFD OUTPUT TO ENERGIZE THIS CIRCUIT. SEE DETAIL 6- 11. INSTALL LOW VOLTAGE WIRING FROM SYSTEM CONTROLLER TO MUA AND OR BMS. SEE DETAIL 5- MECHANICAL SCOPE OF WORK INSTALL ALL TEMPERATURE, OPTIC SENSORS, AND HOOD CONTROLLERS ON OR IN THE HOODS IN ACCORDANCE WITH THE MELINK INSTALLATION PROCEDURE, REFER TO SYSTEM LAYOUT(S). CONNECT CABLES TO THE SENSORS AND PULL CABLES FROM SENSORS TO THE SYSTEM CONTROLLERS, PULL AND CONNECT COMMUNICATION CABLE FROM SYSTEM CONTROLLER TO VFD'S EXCEPT CABLES DESIGNATED TO BE PULLED BY ELECTRICAL CONTRACTOR, 4. MAKE CABLE CONNECTIONS AT THE SYSTEM CONTROLLER, VERIFY CONTROL WIRING AND SYSTEM PROGRAMMING, AND VERIFY SYSTEM FUNCTIONALITY PER SEQUENCE OF OPERATION. 5, TRAIN OPERATORS AND/OR FACILITIES PERSONNEL FOR EACH SYSTEII. 6. SUBMIT INTELLI-HOOD START-UP REPORT TO CUSTOMERS, PLEASE CALL MELINK WITH ANY QUESTIONS 0 1-CALL MELINK WITH ANY QUESTIONS 1�513)-965-7300965-7300. �O oH WASMi� 41741 SS/OIVAL 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. AIIIIIIIIIIM45 DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineerinq.net Phone:208.288.2181 Project:21 AMA01 Q0 N O 00 p Z z_ O = >Q> C] LU U) 0 �o O0 Ld 3: z O ; > 10 J Q J _� O -0 O N ti z m w Z o U � rY Q N U 0- REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M6.9 J J J J J r GENERAL INSTALLATION OVERVIEW THREE PHASE BREAKER 230/480/600VAC VARIABLE FREQU DRIVE "VFD" EXHAUST FAN UNIT VARIABLE THREE PHASE POWER TO EXHAUST AND MUA FANS (OUTPUT POWER) IN SEPARATE CONDUIT 7474 I II I II I II I II I II I II I II I II I II I II I II I II I II I II I II I II I II II I II � II II r II I II 4 II II CONSTANT THREE PHASE POWER TO VFDS (INPUT POWER) IN SEPARATE CONDUIT I II ----------------------------- I II I II I II I II I ll WIRE LEGEND WIRING INSTALLATIONS MUST FOLLOW ALL LOCAL ELECTRICAL AND MECHANI CODE REQUIREMENTS 1 PHASE POWER 3 PHASE POWER IN (VFD) 3 PHASE POWER OUT (VFD) -------------- MELINK CONTROL CABLE ETHERNET CAT5E LINE - - - - - 18 GAUGE, 6 CONDUCTOR LOW VOLTAGE CABLE MUA FAN UNIT 4 I i I I I I I I 6:4 (1 �� NQo Uv I �O I I GENERAL COMPONENT OVERVIEW NOT SITE SPECIFIC I I I II I ---------------------J -------------------------------------1 � HOOD I i � ~�` I I---------•---------------•--•"--'--•----------•------•--•------------1 CONTROLLE --' Hc(oi) i i low ANSUL L THERNET/BAS TEMP SENSOR ' 120VAC SHUNT TRIP BACNET I/P (VARIABLE SPEED) SYSTEM POWER EQUIVALENT AIR PURGE UNIT v I CONTROLLER I I I I I I I I I I I PTIC SENSOR SINGLE PHASE BREAKER 120VAC I I I I iNretuxic� TOUCHPAD 4171. SS/OIVAL 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering.net Phone:208.288.2181 Project:21 AMA01 Q0 N CD CD 0') (n Z 0 F--- Z z O = Q w C 0 LL o O 0 0 3: Z_ O > > 10 J Q J O 0C) O N Z m I— p LL] Z ON U ~ Q LU Q N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M6.1 0 C C c C' C C C 0 J J J J J DETAIL 1: SYSTEM LITE CONTROLLER BASE BOARD o ®{nLelh-Hood 0 OY .0 A p 0 0 o 0 0 0 ®Itltt ill -Hood F 013 �r R. RE,.D -N 20�-NN 0 A) 2 HOOD NETWORK PORTS ARE INTERCHANGEABLE. ANY OF THEM CAN BE USED TO CONNECT HOOD CONTROLLERS OR TOUCHPADS IN A SERIES CHAIN. CABLE LENGTH LIMITATIONS DO APPLY. REFER TO THE INSTALLATION MANUAL. PORTS ARE POWER -LIMITED. B) 1 VFD PORT USED TO CONNECT AND COMMUNICATE WITH VFDS VIA SERIAL MODBUS PROTOCOL. C) ETHERNET PORT IS USED TO CONNECT THE SYSTEM CONTROLLER TO THE GLOBAL INTERNET SUCH THAT THE INTELLI-HOOD SYSTEM CAN COMMUNICATE WITH MELINK HEADQUARTERS. D) USB PORTS. USED FOR DATALOG THUMB DRIVE. IMPORTANT: USE THE CORRECT PORTS ON THE SYS-EM CCRTROLLER BASE BOARD DETAIL 2: HOOD CONTROLLER BOARD I I TEMPI OPTIC !APU I oTl I =^I PORTS G TEMP 0 PORTS TEMP 3 TEMP 4 NETWORK ADDRESS IMPORTANT: USE THE CORRECT PORTS ON THE HOOD CONTROLLER BOARDS A) 2 HOOD NETWORK PORTS ARE USED TO WIRE THE HOOD CONTROLLERS, AND OTHER HOOD NETWORK DEVICES IN SERIES FROM THE SYSTEM CONTROLLER. B) CABLES FROM THE OPTIC APUS ARE CONNECTED TO THE OPTIC APU PORTS. THESE PORTS ARE INTERCHANGEABLE. EMITTER OR RECEIVER CAN BE PLUGGED INTO EITHER ONE- C) 4 TEMPERATURE PORTS ARE USED TO CONNECT THE TEMPERATURE SENSORS. PORTS MAY BE USES FOR VARIOUS PURPOSES SUCH AS EXHAUST DUCT, EXHAUST CANOPY, OR SUPPLY AIR. FOR CORRECT OPERATION, THE CORRECT PROBE MUST BE CONNECTED TO THE CORRECT PORT AS DEFINED BY THE SYSTEM CONTROLLER PROGRAMMING CONFIGURATION. D) ROTARY DIALS ARE USED TO DEFINE THE HOOD CONTROLLER'S ADDRESS (1 TO 39). E) THE TERMINATION RESISTOR SHOULD BE SWITCHED ON FOR THE LAST HOOD NETWORK DEVICES IN A SERIES CHAIN. DETAIL 3: MELINK SYSTEM CONTROLLER WIRING POWER TO SYSTEM CONTROLLER. 90-250VAC -20AMP DEDICATED CIRCUIT. (7 70W POWER CONSUMPTION - SHUNT TRIP BREAKER OR FIRE SUPPRESSION RELAY -SHUNT TRIP BREAKER OR FIRE SUPPRESSION RELAY L N G L N G INPUT OUTPUT m uv ,z VNECT SINGLE PHASE INPUT WIRING (20A CIRCUIT) FROM HUNT TRIP BREAKER OR FIRE SUPPRESSION RELAY VTACTS OF EACH ANSUL SYSTEM THAT WILL SHUT OFF NER IN EVENT THE FIRE SUPPRESSION SYSTEM IS rIVATED. )NNECT OUTPUT WIRING TO HOOD LIGHTS (15A MAX.). 'VOLTAGE WILL MATCH INPUT LINE VOLTAGE. NOTE: ALLOWABLE WIRE SIZE IS 16AWG - 12AWG. DETAIL 4: POWERFLEX 4 VFD WIRING VFD CONTROL TERMINAL BLOCK O 1 O 1 O 1 O O LEAVE JUMPER IN PLACE r ` REMU'+E JUMPER FOR FOR EXHAUST FAN VFD SUPPLY FAN VFD IMPORTANT: IF THE FAN IS TO SHUT DOWN WHEN THE FIRE SUPPRESSION TRIPS, THE JUMPER BETWEEN TERMINALS 02 AND 05 MUST BE REMOVED. WHEN THE POWER TO THE I/O PROCESSOR IS SHUT OFF, IT WILL DISABLE THE FAN, VFD POWER TERMINAL BLOCK WL1 S_ TA.3 Ufjl VlT2 WT3 R+ R- 30 INPUT W)RING 30 OUTPUT WIRING I BREAKER PANEL TO FAN MOTOR (FIELD INSTALLED) (FIELD INSTALLED IN SEPARATE CONDUIT) A) VERIFY THAT VOLTAGE OF VARIABLE FREQUENCY DRIVE (VFD) IS SAME AS THE FAN MOTORS, I.E. 208/3 OR 460/3. ALSO VERIFY THAT THE HP RATING IS THE SAME OR GREATER THAT THE FAN MOTORS. I I I I I� YI B) INSTALL SEPARATE CONDUIT FOR OUTPUT WIRING FROM EACH VARIABLE FREQUENCY DRIVE (VFD) TO PREVENT I I I ELECTRICAL INTERFERENCE. I I I I l l l y M i C) CONNECT INPUT WIRING FROM BREAKER, OR EXISTING STARTER TO L1, L2, L3, AND GROUND. POWER 3-PHASE SUPPLY MOTOR D) CONNECT OUTPUT WIRING FROM T1, T2, T3 AND GROUND TO RESPECTIVE FAN MOTORS. E) IF THE FAN IS TO SHUT DOWN WHEN THE FIRE SUPPRESSION TRIPS, THE JUMPER BETWEEN TERMINALS 02 AND `1 _',RTANT: 05 MUST BE REMOVED. WHEN THE POWER TO THE 1/0 PROCESSOR IS SHUT OFF, IT WILL DISABLE THE FAN. ­-E IT == F I H ,f ; vgO Ev 0:3� (95 va o� On a� VFD INSTALLATION INSTRUCTIONS INPUT AC POWER A. CIRCUIT BREAKERS FEEDING THE VFD'S ARE RECOMMENDED TO BE FAST ACTING AND THERMAL -MAGNETIC. B. EACH VFD SHALL BE FED BY ITS OWN BREAKER- IF MULTIPLE VFD'S ARE COMBINED ON THE SAME CIRCUIT BREAKER, EACH VFD SHALL HAVE ITS OWN PROTECTION DEVICE (FUSES OR CIRCUIT BREAKER) C- INPUT AC LINE CONDUCTORS SHALL BE RUN IN CONDUIT FROM THE CIRCUIT BREAKER PANEL TO THE VFD- AC INPUT POWER TO MULTIPLE VFD'S MAY BE RUN IN A SINGLE CONDUIT. NOTE: DO NOT CONNECT AC LINE CONDUCTORS TO OUTPUT TERMINALS OF VFD- SEVERE DAMAGE WILL OCCUR - OUTPUT POWER A. MOTOR CONDUCTORS FROM EACH VFD TO ITS RESPECTIVE MOTOR MUST BE RUN IN A SEPERATE METALLIC CONDUIT SEPERATE FROM CONTROL WIRING AND INCOMING AC POWER TO AVOID NOISE BETWEEN VFDS. B. LOAD REACTORS SHAL BE REQUIRED IF THE DISTANCE BETWEEN THE VFD AND THE MOTOR EXCEEDS (200 FEET @ 208/23OV, 70 FEET @ 460/48OV, OR 40 FEET @ 575V) C. DV/DT FILTERS SHALL BE REQUIRED IF THE DISTANCE BETWEEN THE VFD AND THE MOTOR EXCEEDS 500 FEET. D. A CONTACTOR SHALL NOT BE INSTALLED BETWEEN THE VFD AND THE MOTOR. OPERATION OF SUCH A DEVICE WHILE THE VFD IS RUNNING CAN CAUSE POTENTIAL DAMAGE TO THE OUTPUT COMPONENTS OF THE VFD. E. WHEN A DISCONNECT SWITCH IS INSTALLED BETWEEN THE VFD AND THE MOTOR, IT SHALL ONLY BE OPERATED WHEN THE VFD HAS BEEN STOPPED. DETAIL 5: �Q0 WIRING TO MUA UNIT SYSTEM CONTROLLER MAKE UP AIR UNIT 110 TERMINALS CONTROL TERMINALS 24VDC OUT 1 8 MUA ON/OFF INPUT 24VDC COM 9 _ R1 R1 r R I ORY COM 17 I L-- R2 �iR2 - CALL FOR HEAT A) WHEN THE FANS ARE TURNED ON, THE SYSTEM CONTROLLER (TERMINALS 8 AND 9) WILL SEND 24VDC TO A RELAY. THE N.O. RELAY CONTACTS SHOULD BE WIRED TO THE MUA UNIT TO START THE UNIT. 0 B) WHEN IN HEAT MODE, THE MUA UNIT WILL ENERGIZE A RELAY TO PROVIDE A DRY CONTACT CLOSURE TO THE SYSTEM CONTROLLER (TERMINALS 16 AND 17). THIS 0 INPUT WILL SIGNAL THE SYSTEM CONTROLLER TO INCREASE THE MINIMUM FAN MrOre SPEED AND MAINTAIN THE PROPER AIRFLOW ACROSS THE BURNER OR HEAT EXCHANGER. 0 o O C) MUA CONTROL RELAYS ARE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR IF NOT PROVIDED BY MUA OEM. D) 18AWG SHIELDED, PLENUM -RATED CABLE IS TYPICALLY RECOMMENDED. TERMINALS WILL ACCEPT 12-20AWG WIRING. E) NOTE: RELAY TERMINALS HAVE A MAXIMUM CAPACITY OF 5A AT EITHER 120 OR 230VAC. DETAIL 6: SEPARATION OF MUA UNIT MOTOR AND CONTROLS CONNECT TYPICAL STARTER BLOWER T1 MOTOR 3 PHASE VFD OUTPUT - - - __0 M 1 CONNECTED TO MUA L BLOWER MOTOR ONLY - - - -p 230, 120, OR 24 V SINGLE PHASE - TO MUA DEDICATED C ONTROLS POWER FOR THE MUA - - - C ONTROLS CIRCUIT NEUTRAL A) WIRE THREE-PHASE OUTPUT POWER FROM THE MUA VFD TO THE MUA UNIT TO POWER THE BLOWER MOTOF. B) WIRE A DEDICATED SINGLE PHASE CIRCUIT TO THE MUA UNIT TO ENERGIZE THE MUA CONTROLS. ❑O NOT USE THE VFD OUTPUT TO ENERGIZE THIS CIRCUIT. C) ENSURE 115V CIRCUIT IS IN A SEPARATE CONDUIT FROM THE OUTPUT VOLTAGE OF THE VFD. D) IF A MOTOR STARTER IS PRESENT IN THE MUA UNIT, IT MAY BE REMOVED COMPLETELY IN SOME CASES DEPENDING ON THE CONTROLS SEQUENCE OF OPERATIONS. IF IT IS DESIRABLE TO LEAVE THE CONTACTOR IN PLACE, THEN THE OVERLOADS SHOULD BE REMOVED. MOST OVERLOADS ARE NOT COMPATIBLE WITH VFDS. DETAIL 6: WIRING FOR DIGI WIRELESS MODEM LITE SYSTEM CONTROLLER NETWORK CONNECTOR POWER TRANSFORMER K0 M DETAIL 8: NOT USED A) THE DIGI MODEM TRANSFORMERS RED AND BLACK WIRES WILL CONNECT TO THE BASE BOARD 1/0 TERMINALS (B) 10 AND 11 (PROGRAMMED FOR 24/7)- THIS WILL POWER THE MODEM. B) CONNECT THE SUPPLIED ETHERNET CABLE FROM THE DIGI MODEMS NETWORK CONNECTOR PORT TO THE BASE BOARD ETHERNET PORT (D) C) CONNECT THE SUPPLIED ANTENNAS TO THE WAN PRI AND WAN SEC CONNECTORS ON THE MODEM D) IN SYSTEM CONTROLLER PROGRAMMING, SET "USE DHCP' TO YES. E) ONCE A CONNECTION IS ESTABLISHED THE ABOUT SCREEN ON THE INTELLI-HOOD TOUCHPAD WILL ISSUE AN IP ADDRESS. C O F OWA Sk" v I,L 4171. SS/OIVAL 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. ,iIMMON DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering.net Phone:208.288.2181 Project:21 AMA01 Q0 N C) 00 p n Z z O = Q LU C LL z OLLI 0 0 3: z O W / 10 J Q J o O (N ti z m I— C:)LIJ Z C:)U D_ Q N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M6.11 c u c C' C C C r r------ I I I I I I I I I 1 I I I I I I I I I I 1 I I I I I 1 1 I 1 I I I I 1 I I I I I I 1 I 1 1 1 1 I I I I I I I I I BREAKER PANEL o0 0 120 OR 230 VAC SINGLE PHASE INPUT '-LIGHT OUTPUT POWER. SEE DETAIL 3, SHEET 2 WIRE HOOD LIGHTS OUTPUT TO LIGHTS CIRCUITS OF HOOD 76, INTELLI-HOOD n: TOUCHPAD TP(01) VARIABLE FREQUENCY LOCATED: TBD i o� �,r4l SHEET 3 CONTROL WIRING SCHEMATIC FOR SYSTEM CONTROLLER #1 ----� I I I 1 I I I I I I I I I I I I I I I I I I I I I I I I I n 1 ' EF-1 Q)n l� I I 5N, I Wzz�'�� SYSTEM CONTROLLERS DIGITAL AND/OR ANALOG I/O SEE DETAIL 5 ETHERNET INTERFACE SEE DETAIL 1 REQUEST FOR INFORMATION: 1. FAN HP AND VOLTAGE IS NEEDED TO COMPLETE THE DRAWING. 2. ARE MUA UNITS DIRECT -FIRED HEAT? VFD-01 5 HP VFD-41 208V/3 5 HP 208V/3 EF-1 MUA-1 HOOD-1 L__J VFD POWER WIRING REFER TO DETAIL 4 VFD OUTPUT POWER TO EACH FAN INDICATED. OUTPUT FILTERS MUST BE USED WHEN THE DISTANCE FROM VFD TO FAN IS OVER 200' FOR 230V, 70' FOR 460V, OR 40' FOR 575V. I I I I I I I I I I I I I I I I I I I I I I I I I I I I I L------------------------------------------------------ J IMPORTANT 120V POWER FOR MUA-1 MUA CONTROLS REFER TO DETAIL 6 ON SHEET 2 REQUEST FOR INFORMATION: TO B REAKFR INTERFACE WIRING TO THE SUPPLY AIR SYSTEM MUST BE DESIGNED. PANEL AT TIME OF DRAWING REQUEST, SUPPLY AIR METHOD AND EQUIPMENT INFORMATION WAS NOT PROVIDED. TO SYSTEM CONTROLLER--- 4 MUA TO BE CONNECTED TO MELINK SYSTEM CONTROLLER. FOR TERMINAL CONNECTION 'L REFER TO DETAIL 5 ON SHEET 2 �O oH WASMi� 41741 FSS/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineerinq.net Phone:208.288.2181 Project:21 AMA01 Q0 N 00 p n Z z_z O = Q W C 0 O O 0 LLI z O W / 10 J Q J o O -0 O N ti z m I— C:) w Z C:)U Q LU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M6.12 r 15'-4" 26 GA STUCCO ACRYLUME 4" TYP.� 7'-2" 2" AIR SPACE w L- - - - - BEL0065—EE 1 54 Ibs L -FT - - -^- - - 77- w Z r-10'J m FREEZER c� Q = W/FLOOR aI 00 w DIAMOND o o = ALUMINUM � _j TREAD PLATE Q X X X C� X X X X X X N K a K RAMP I I I I E {I o rn I JE3'-0"W 2'-1'x 6'-5" H � DOOR ; I � I - L_ ❑ APPROVED ❑ APPROVED AS NOTED ❑ REVISE & RESUBMIT 21 21" 7'-2" rJ----A 1 BEL0060—AM I 1 36 Ibs 1 L�� _ _j 350 COOLER W/FLOOR DIAMOND ALUMINUM TREAD PLATE XXXXXX X X X � RAMP I I I I I i E--] r�r iA I E iA I 3 -0 W / —2'-1" L2'-1" x 6'-5"H 2'-1" DOOR I 040 STUCCO ALUM SIGNATURE _ PRINT NAME DATE CLOSURE PANEL J w z a a- Lu o- 0 J U INSULATION R—VALUES PANEL TYPE COOLER FREEZER 4" WALLS, ROOFS & DOORS R-29 R-32 5" WALLS, ROOFS & DOORS R-36 R-40 FLOORS R-25 R-28 FREEZER DOOR DOOR FRAME KWHr/DAY 3.600 COOLER DOOR DOOR FRAME KWHr/DAY 1.584 ELECTRICAL DATA t9 = POINT OF ELECTRICAL CONNECTIONS. FREEZER CONDENSING UNIT: 208-234V/60/30 9.7/12.2/15.0 (RLA/MCA/MOP) EVAPORATOR: 208-230v/60/10 1.5/9.5 AMPS COOLER CONDENSING UNIT: 208-230V/60/30 5.2/7.6 15.0 (RLA/MCA/MOP) EVAPORATOR: 115v/60/10 0.6 AMPS WALK—IN DOORS: 115v/10 — 350w* -SPECIFICATIONS— BOX HEIGHT: FREEZER — 8'-6" OVERALL (T-10 1 4" INTERIOR) COOLER — 8'-6" OVERALL (7'-10 1/4" INTERIOR) CONSTRUCTION: FOAMED IN PLACE NSF LISTED, STANDARD NO. 7 INSULATION: 4" URETHANE, FINISHED PANEL UL CLASSIFIED FLAME SPREAD 20 CORE SMOKE DEVELOPED 250 INSTALLATION: INDOOR FLOOR: FREEZER - STANDARD W/36" DEEP INTERIOR RAMP & 3/4" PLYWOOD UNDERLAYMENT (SEE DETAILS) COOLER - STANDARD W 36" DEEP INTERIOR RAMP & 3/4" PLYWOOD UNDERLAYMENT DOOR HARDWARE POWER TO BE STUBBED OUT CEILING PANEL & ACCESSORIES: DRY CONTACT LEADS TO BE STUBBED OUT CEILING PANEL IN A SEPARATE STUB OUT (EACH DOOR) DEAD13OLT HANDLE W/KEYED CYLINDER LOCK, PADLOCK PROVISION & QUARTER TURN INSIDE RELEASE FRAME HEATER WIRE HYDRAULIC DOOR CLOSER IC+ WALK-IN DOOR CONTROLLER AND ALARM SYSTEM INCLUDING: INTEGRATED LIGHT SWITCH WITH AUTOMATIC LIGHT OFF AND 3-WAY & 4-WAY CAPABILITY TEMPERATURE MONITOR AND LOGGER WITH HIGH TEMP. AND LOW TEMP. VISUAL AND AUDIO ALARM F OR C TEMPERATURE SELECTION INTEGRATED DRY CONTACT FOR ALARM SIGNALING & POWER FAILURE (1A 0 24VAC, 1A 0 30VDC) DOOR AND WINDOW HEATER CONTROL (WHEN SO EQUIPPED) HACCP PREVIEW VIA ONBOARD LCD SCREEN HACCP DOWNLOAD VIA USB WIFI CONNECTIVITY (INTERNET ENABLED WIFI NETWORK NEEDED) BATTERY BACKUP TEMPERATURE ALARM NOTIFICATION VIA EMAIL &/OR EMAIL TO SMS TEXT MESSAGES POWER FAILURE NOTIFICATION VIA EMAIL &/OR EMAIL TO SMS TEXT MESSAGES (FOR THIS FEATURE TO WORK THE LOCAL WIFI NETWORK MUST BE POWER PROTECTED AND WORKING AT THE TIME OF POWER FAILURE EVENT) AUTOMATIC AND ON DEMAND TRANSMISSION OF HACCP DATA VIA EMAIL ADAPTIVE SETTINGS AIR TEMPERATURE PROBE DOOR SWITCH TO ENABLE DOOR AJAR ALARM, DOOR AJAR NOTIFICATION VIA EMAIL &/OR EMAIL TO SMS TEXT MESSAGES, AND AUTOMATIC LIGHTS ON WHEN DOOR OPENS KASON SCREW —IN VAPOR PROOF LIGHT FIXTURE W/8.5 WATT SYLVANIA LED BULB & GLOBE STRIP CURTAIN 3 — DENT #D-690—HDS SPRING LOADED CAM RISE HINGES HEATED VISION WINDOW (14" x 14") 3/16" DIAMOND ALUMINUM TREAD PLATE KICKPLATES 0 36" HIGH I/S & O/S DOOR & FRAME KASON #1825 PRESSURE RELIEF VENT (FREEZER DOOR ONLY) 2 PC. 12 GA STAINLESS STEEL DOOR LOCKING BAR ACCESSORIES: 2 — PCS. TRIM ANGLE (SHIPPED LOOSE) CLOSURE PANEL TO AN EXISTING CEILING (PER PLAN) HO 4 — 48" (181OLC) LED LIGHT FIXTURE(S) 0 40W EACH 2 — BAKELITE LABEL(S) (BLACK) "FREEZER", "COOLER METAL FINISHES: INTERIOR WALLS & CEILING — WHITE .040 STUCCO ALUMINUM EXPOSED EXTERIOR — .040 STUCCO ALUMINUM UNEXPOSED EXTERIOR — 26 GA STUCCO ACRYLUME EXTERIOR FLOOR & CEILING — 26 GA STUCCO ACRYLUME INTERIOR FLOOR — 1/8" DIAMOND ALUMINUM TREAD PLATE INTEGRAL REFRIGERATION: U.L. LISTED, AIR COOLED, OUTDOORS FREEZER CONDENSING UNIT: 1 — STD. PRE —ASSEMBLED REMOTE — HERMETIC —SCROLL 1.75 HP MODEL NO. FFAL—A17Z—TFC-075 (R-448A) CONDENSING UNIT DIMENSIONS: 24 9/101 x 21"W x 19 1/10"H EVAPORATOR: 1 — MODEL NO. BEL0065BS6EE W/E.C. MOTORS & I.R.C. COOLER CONDENSING UNIT: 1 — STD. PRE —ASSEMBLED REMOTE — HERMETIC —SCROLL 1.00 HP MODEL NO. FFAM—AlOZ—TFC-075 (R-448A) CONDENSING UNIT DIMENSIONS: 24 1/101 x 18 9/10"W x 16 3/10"H EVAPORATOR: 1 — MODEL NO BELOOfiOBSfiAM W/E C MOTORS & IR C 'NUIL: ADD WAIIAUL VUK LAUH AUUIIIUNAL LIUM1 hIxIUKL IN AUULSSUItILS. REFRIGERATION 2 — WINTERIZATION CONTROLS/LASA ACCESSORIES: 2 — COMPRESSOR COVERS 2 — COMPRESSOR MOUNTING STANDS NOTE: THE LARGEST DOOR PANEL ON THIS JOB IS 57.5" x 98 NOTE: THE LARGEST WALK—IN PANEL ON THIS JOB IS 46" x 128". CUSTOMER IS TO VERIFY THAT THIS PANEL SIZE WILL NOT CONFLICT WITH ANY JOB SITE RESTRICTIONS. NOTE: CUSTOMER IS TO VERIFY ALL DIMENSIONS, ITEM # SECTIONS, DETAILS AND SPECIFICATIONS 1) Please verify that door swing and location are correct. 5) Special note to General Contractor and his Sub Contractor for quarry tile or concrete wearing floors: the sheet metal panel facings may be susceptible to staining due to excessive moisture created by hydration 2) If this walk-in is to be installed in a depression, or quarry tile is to be of concrete type materials. Therefore, it is absolutely necessary that applied to the interior, depression depths or tile thickness must be each room be properly ventilated. Also note that special precautions specified to insure proper door height. must be taken when using muriotic acid due to effects hydrochloric acid fumes have on aluminum and stainless steel. 3) All site preparation, floor slab construction, plumbing, electrical 6) This drawing and information contained herein are the exclusive connections (including control wiring) by others. property of American Panel Corporation. It shall be returned to American Panel Corporation upon demand and shall not be reproduced 4) & Electrical: 115-60-1 required above latch side of each door, through in whole or part, disclosed to anyone else, or used without the written ceiling, to operate frame heater and light. consent of American Panel Corporation. 0 u4� 8'-6„ OVERALL BOX 6'-10" HEIGHT A. F. FREEZER DOOR ELEVATION INITIAL HERE TO VERIFY TILE, GROUT, & MASTIC THICKNESS • .•� ��.�,99! vvn / ❑ APPROVED ❑ APPROVED AS NOTED ❑ REVISE & RESUBMIT SIGNATURE _ PRINT NAME DATE COOLER DOOR ELEVATION WALL PANEL TILE/GROUT/MASTIC 5/8" TOTAL THICKNESS (BY OTHERS) 8'-6" OVERALL BOX 0" HEIGHT F. CLEARANCE BELOW EVAPORATOR FLOOR PANEL SECTION AT EVAPORATOR TYP. NSF APPROVED RADIUS F FLOOR PANEL �3/4" PLYWOOD EXISTING FLOOR SECTION K — K ROOF PANEL AMERICAN PANEL CORPORATION rican Panel 5800 S.E. 78th St. Ocala, Florida 34472 Ph. (352) 245-7055 Fax (352) 245-0726 ENGER ASSOCIATES [PROJECT: TURES - EDMONDS SENIOR LIVING - EDMONDS WA DRAWN BY: P.O. 7 21 DC MM PROPOSAL#: JOB#: SHEET "=1 ' —0" PD 187239 1 of 2 AT EVERY STUB OUT: SEALING AROUND THE EXTERIOR OF THE ELECTRICAL CONDUIT AND INSIDE OF THE CONDUIT AROUND THE WIRES MUST BE COMPLETED. `SEALING UNIT (BY E.C.) HEATED PRESSUREONE REQUIRED AT EVERY RELIEF VENTENTRANCE OF CONDUIT (AS REQUIRED)INTO CABINET. TE: WHEN CABINET IS BRING ELECTRIC V INTERNALLY WIREDOUTDOORS, SERVICE THROUGH WALL DOOR JAMBDO NOT PENETRATE CEILING. ENT CONDUIT (BY OTHERS) FIXTURE DOOR PLUG DOOR ELECTRICAL CONNECTION IF NOT VERIFIED TRIM ANGLE WILL BE BACK ORDERED, WHICH WILL NC UR ADDITIONAL FREIGHT BUILDING WALL CHARGES EXTERIOR [XXI_ WALL PANEL - METAL STRIP #80/4" PPH TEK SCREW TRIM ANGLE DETAIL #2 1) Please verify that door swing and location are correct. 5) Special note to General Contractor and his Sub Contractor for quarry tile or concrete wearing floors: the sheet metal panel facings may be susceptible to staining due to excessive moisture created by hydration 2) If this walk-in is to be installed in a depression, or quarry tile is to be of concrete type materials. Therefore, it is absolutely necessary that applied to the interior, depression depths or tile thickness must be each room be properly ventilated. Also note that special precautions specified to insure proper door height. must be taken when using muriotic acid due to effects hydrochloric acid fumes have on aluminum and stainless steel. 3) All site preparation, floor slab construction, plumbing, electrical 6) This drawing and information contained herein are the exclusive connections (including control wiring) by others- property of American Panel Corporation. It shall be returned to American Panel Corporation upon demand and shall not be reproduced 4) & Electrical: 115-60-1 required above latch side of each door, through in whole or part, disclosed to anyone else, or used without the written ceiling, to operate frame heater and light. consent of American Panel Corporation. 2-PCS LOCKING BAR LOCKING BAR DETAIL IF NOT VERIFIED CLOSURE PANEL WILL BE BACK ORDERED, WHICH WILL INCUR ADDITIONAL BUILDING STRUCTURE FREIGHT CHARGES ANCHOR TO CEILING I -•TOP CHANNEL AIR SPACE ABOVE -/ WALK-IN CLOSURE PANEL REQUIRES A 12" MINIMUM TO INSTALL ;IFY HGT. ANCHOR TO A.F.F. ROOF PANEL 8070M CHANNEL ROOF PANEL -WALL PANEL CLOSURE PANEL AMERICAN PANEL CORPORATION American Panel 5800 S.E. 78th St. Ocala, Florida 34472 Ph. (352) 245-7055 Fax (352) 245-0726 CUSTOMER: CLEVENGER ASSOCIATES PROJECT: CA VENTURES - EDMONDS SENIOR LIVING - EDMONDS WA DATE: DRAWN BY: P.O. 04 07 21 DC MM SCALE: PROPOSAL#: JOB#: SHEET 5 1 G"=1 ' —O" PD 187239 2 of 2 �O of TVASMi� 41741 �� ��'GISTER��� \� Fss/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering. net Phone:208.288.2181 Project:21 AMA01 Q0 N O 00 O') p Z z O = Q W Cn LL z O� Uj Z O > > J Q J O 0 10� Z DO O LLJ �* Z C:) ~ Q LU N U a REVISION DATE REASON FOR ISSUE 1 6-18-2021 ADDENDUM 1 HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M6.13 r c C' C C C r L0 M 66 J N J N J N O N M 00 `o 'c a� 1n c O > E o v w o a L aci 3 U B M 00 u > a) J V) v E 0 79 0 w A ELEVATION FS-1 SCALE: 1/2" = 1'-0" 0 r-C-'�ELEVATION (I)ELEVATION F ELEVATION FS 1 SCALE: 1/2" = 1'-0" FS-1 SCALE: 1/2" = 1'-0" EXHAUST HOOD WITH 3" FINISHED CEILING SHALL BE AID RADDICD nA1 cGAD ACT-3, MOUNTED AT 10'-0". SEE (a)ELEVATION FS-1 SCALE: 1/2" = 1'-0" D ELEVATION FS-1 SCALE: 112" = 1'-0" GUNIRAGIUK 0 � G w BUILDING WALL OPEN ---� FINISHED CEILING BUILDING BUILDING WALL WALL 94 (R) 97 97.1 000 COVE BASE BY GENERAL COVE BASE l F.S. CONTRACTOR BY GENERAL `�-� CONTRACTOR G ELEVATION_ H ELEVATION ELEVATION FS-1 SCALE: 1 10 FS-1 SCALE: 1/2" = 1'-0" FS-1 SCALE: 1/2" = 1'-0" CLEVENGER la//OCIkITE/ FOODSERVICE, BAKERY, 59W SARATOGA ROAD. SUITE 2A DUBUQUE, IOWA 52002 COMMISSARY AND LAUNDRY PHONE (563)5825109 DESIGN/ CONSULTING SEATTLE*CALIFORNIA*ILUNOIS*IOWA KINES INFO@CLEVENGERASSOC.COM NEW I WWWC EVE GIERASSCC.COM '4� KITCHEN & BISTRO EQUIPMENT SCHEDULE ITEM QTY DESCRIPTION 1 1 WALK-IN FREEZER / COOLER ASSEMBLY 2 1 EVAPORATOR COIL(COOLER) 3 1 COMPRESSOR REMOTE, AIR-COOLED 4 1 WALK-IN FREEZER / COOLER ASSEMBLY 5 1 EVAPORATOR COIL(FREEZER) 6 1 COMPRESSOR REMOTE, AIR-COOLED 7 8 WIRE SHELVING UNIT 8 2 WIRE SHELVING UNIT 8.1 2 WIRE SHELVING UNIT 8.2 1 WIRE SHELVING UNIT 9 1 SPARE NUMBER 10 1 SPARE NUMBER 11 1 SPARE NUMBER 12 2 FAUCET W/ WRIST HANDLES 13 1 THREE COMPARTMENT SINK 14 1 SHELVES WITH REMOVABLE HOOKS 15 3 HAND SINK WITH SOAP AND TOWEL DISPENSERS 16 1 CAN RACK 17 5 WIRE SHELVING UNIT 18 2 HIGH DENSITY SHELVING - STATIONARY 19 6 HIGH DENSITY SHELVING - MOBILE 20 1 SPARE NUMBER 21 2 HIGH DENSITY SHELVING SYSTEM - TRACK 22 1 SPARE NUMBER 23 1 SPARE NUMBER 24 1 UTILITY CART 25 1 WALL MOUNTED SHELF 26 1 DISHTABLE, STRAIGHT 27 1 DISHRACK DOLLY 28 1 DISHRACK DOLLY 29 1 DOOR TYPE DISHMACHINE - TALL 30 1 CONDENSATE HOOD 31 1 TRASH CAN WITH DOLLY 32 1 SOILED DISHTABLE 32.1 1 WASTE DRAIN, TWIST HANDLE 33 1 PRE -RINSE FAUCET 34 1 SLANTED RACK SHELF 35 1 FILTRATION SYSTEM (STEAMER) 36 1 HOSE REEL, ENCLOSED, STAINLESS STEEL 37 1 WATER CONTROL CABINET 38 1 SPARE NUMBER 39 1 SPARE NUMBER 40 1 FOOD PROCESSOR 41 1 SPARE NUMBER 42 1 FOOD SLICER 43 1 LOW VOLTAGE COOK & HOLD OVEN 44 1 CABINET, HOLDING 45 1 SPARE NUMBER 46 1 SPARE NUMBER 47 1 WORKTABLE W/ SINKS 48 1 FAUCET 49 1 SPARE NUMBER 50 1 MOP BUCKET AND RINGER 51 1 MOP SINK 52 1 SERVICE FAUCET 53 1 CB STARTER 4V 21X36X84 54 1 WALL MOUNTED FAUCET 55 3 INGREDIENT BIN 56 1 WORKTABLE W/ SINK 57 1 SPARE NUMBER 58 1 PLANETARY MIXERS 9 1 MIXE S A D 60 1 UNDERCOUNTER REFRIGERATOR 6 O E S E S 62 1 SPARE NUMBER 3 1 IC D E B E 64 1 UNDERCOUNTER FREEZER 65 1 POT & PAN SHELVING 66.1 1 FILTRATION SYSTEM 68 1 CONVECTION STEAMER 69 1 REFRIGERATED CHEF BASE 70 1 CHARBROILER 71 1 RANGE 6-BURNER W/24" GRIDDLE 72 1 POT FILLER 73 1 DUMP STATI N A L S S L L PANEL 75 1 DOUBLE DECK CONVECTION OVEN 76 1 TYPE 1 EXHAUST HOOD 77 1 FIRE SUPPRESSION SYSTEM 78 1 HEATED PLATE DISPENSER 79 1 MAGNETIC KNIFE HOLDER 80 1 CHEF'S COUNTER 80.1 1 DOUBLE OVERSHELF 81 2 DROP -IN SOUP WELL 82 2 FILL FAUCET 83 1 MICROWAVE OVEN 84 1 CONVEYOR TOASTER 85 2 OVERHEAD FOOD WARMER 86 1 HOT FOOD TABLE 87 1 REFRIGERATOR, SANDWICH/SALAD PREP 88 1 SPARE NUMBER 89 1 SODA & ICE BEVERAGE DISPENSER 90 1 BAG -IN -BOX SYSTEM 91 1 BEVERAGE COUNTER 92 1 HIGH VOLUME COFFEE DISPENSER 93 1 FILTER SYSTEM 94 1 REFRIGERATOR 95 1 ICE CUBER 95.1 1 ICE BIN 96 1 JUICE DISPENSER 97 1 ICE CREAM CABINET 97.1 1 DIPPERWELL B1 1 HIGH VOLUME COFFEE DISPENSER B2 1 SPARE NUMBER B3 1 DROP -IN SINK B4 1 FAUCET B5 1 SPARE NUMBER B6 1 REFRIGERATED SANDWICH PREP TABLE B7 1 REFRIGERATED DISPLAY CASE B8 1 SPARE NUMBER B9 1 HEAVY-DUTY BAGEL TOASTER B10 1 CASH REGISTER B11 1 NON REFRIGERATED DISPLAY CASE (COUNTERTOP) B12 1 SPARE NUMBER B13 1 TRASH CONTAINER B14 3 INDUCTION B15 1 ICE MAKER B16 1 SPARE NUMBER B17 1 SPARE NUMBER B18 1 SPARE NUMBER B19 1 SPARE NUMBER B20 1 SINGLE DOOR WINE COOLER B21 1 SINGLE DOOR BEER COOLER 2 I T TEM (ICE MAKER) B 3 1 PANINI PRESS 2 1 'bRnrRr,0TjNTER REFRIGERATOR B25 1 UNDER MOUNT SINK W/ KOHLER FAUCET K-7507 B25.1 1 FAUCET B26 1 SOAP DISPENSER B27 1 COUNTER TOP PAPER TOWEL DISPENSER C O �F WA Sk v II \ 041741 � ��'GISTER���\� FSS/oNAL � 03/07/2022 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. ,iMMOA DC ENGINEERING Careful listening. Dynamic solutions. www. dcengineering.net Phone:208.288.2181 Project:21 AMA01 Q0 N O 00 O') p C] Z z_ O = Q W C 0 O 0 0 z O > > 10 J Q J _� O -0 C:O (N 0 I` z m I— C:)LLJ z o U Q LU N U a REVISION DATE REASON FOR ISSUE B 10-28-21 CITY COMMENTS #02 HVAC KITCHEN DETAILS GMP/PERMIT SET DATE PROJECT NUMBER 05.21.21 184470 SHEET NUMBER M6.14