Loading...
APPROVED PEER BLD FIR RESUB 3-BLD2022-0926+Structural Plans+11.2.2023_9.57.55_AM+3876593STRUCTURAL NOTES CODE All conditions, materials and construction shall conform to the code specified in the DESIGN CRITERIA, or other codes required by the governing jurisdiction. GEOTECHNICA L PA RA METERS Assumed soil parameters are specified in the DESIGN CRITERIA. Extend footings to undisturbed soil with a bearing capacity as specified in the DESIGN CRITERIA. Bottom of exterior footing shall be 1'-6" minimum below outside finished grade. BACICFILL shall be free draining and without organic material and debris from one of the following soil classes SM-SC, SM, SP, SW, GC, GM, GP, and GW. Unless noted otherwise. Do not backfill until all slabs and panels are constructed and/or installed and have reached a 7 day strength, otherwise provide temporary bracing to resist movement. There shall be no machine compaction on the retaining side of the structure for a distance equivalent to 2/3rds the wall height. PRE -CAST HOLLOW CORE SLABS All precast hollow core slabs are to be installed per the recommendations and specifications. The design of these panels shall resist the DESIGN LOADS. Notify this office of any conflicts prior to panel construction. MISCELLANEOUS The contractor shall verify dimensions and conditions at job site. The contractor shall provide temporary bracing as required until all permanent connections and stiffenings have been installed. Do not scale drawings. Pre -fabricated items to be handled and installed per manufacturer's TESTS AND INSPECTIONS INSPECTIONS PER IBC 110: Foundations, footings, underslab systems and framing are subject to inspection by the building official in accordance with IBC 110.3 the contractor shall coordinate all required inspections with the building official. In addition to inspections required by IBC 110, special inspections shall be done in accordance with the "statement of special inspections" per sections 1704 and 1705. SPECIAL INSPECTORS: Special inspectors shall be employed by the owner to provide special inspections for the project. A special inspector shall be a qualified person who works for an approved agency and demonstrates competence, to the satisfaction of the building official. The special inspector shall keep records of inspections and furnish them to the building official and the engineer of record on a regular basis. A final report documenting required special inspections and the correction of any discrepancies shall be provided prior to the completion of building finishes. Where fabrication of structural components and assemblies is being performed on the premises of a fabrication shop, special inspection of the fabricated items shall be required except where the fabricator is registered and approved to do such work without special inspection in accordance with IBC section 1704.2.2. Periodic inspection allows inspection at intervals necessary to confirm that work requiring special inspection is in compliance with requirements. Continuous special inspection requires that the inspector be on site at all times that work requiring special inspection is performed. Statement of special inspections per IBC sections 1704 and 1705: Special inspections are required by sections 1704, for the items summarized in the special inspection schedule located on this sheet: Special Inspections, Testing & Structural Observation Schedule INSPECTION ITEMS CONTINIUOLIS PERIODIC TESTING Soil & Foundations (IBC 1705.6) Observation and monitoring of excavation X Soil bearing verification X Backfill with native soil X Concrete Construction (IBC 1705.3) Reinforcing placement X Preparation of test specimens X X INSPECTION SCHEDULE NOTES: 1. Items marked with an "x" shall be inspected in accordance with IBC 1704 by a certified special inspector from an agency approved by the jurisdiction. 4. All welds shall be visually inspected. 5. All complete penetration welds shall be tested ultrasonically. 7. All complete penetration welds shall be tested ultrasonically. ❑ Submit Specific Item ❑ Rejected ❑ Revise and Resubmit ❑ Furnish with Corrections Noted ® Reviewed/No exception taken❑ Not Required/Not Reviewed This review is only for general conformance with the design concept of the Project and general compliance with the information given in the Contract Documents. Corrections or comments made on the shop drawings during this review do not relieve contractor from compliance with the requirements of the plans and specifications. Approval of the specific item shall not include approval of an assembly of which the item is a component. Contractor is responsible for dimensions to be confirmed and correlated at the job site; information that pertains solely to the fabrication processes or to the means, methods, techniques, sequences, and procedures of construction; coordination of his or her Work with that of other trades; and for performing all work in a safe and satisfactory manner. DAVID EVANS AND ASSOCIATES, INC. Date: 1/3/2024 Reviewed by: Alejandro Virgen CITY OF EDMONDS BUILDING DIVISION APPROVED PLAN Erize C&rfer 02/21/2024 CONCRETE CONCRETE REQUIREMENRS BY LOCATION: Pre -approved Mix Designs are listed in each section, this is not an endorsement of any company, we can add your equivalent mix designs to our list. W/C Ratio Design PSI Design Air Max Slump Footings & Slab on Grade 0.55 3000 1.5% 5" Miles Sand and Gravel Mix Design 18350FP W/C Ratio Design PSI Design Air Max Slump Walls (below grade) r 0.55 1 1 3000 1 1.5% 5" Miles Sand and Gravel Mix Design 18350FP W/C Ratio Design PSI Design Air Max Slump Walls (above grade) 0.55 3000 5.0% 5" Miles Sand and Gravel Mix Design 0250AC W/C Ratio Design PSI Design Air Max Slump Void Fill, Closure Pour, and 0.50 1 4000 1.5% 5" Slab (above grade) Miles Sand and Gravel Mix Design 1840OF6 W/0 Design PSI Panel Joint Gout Design Air Max Slum 0.40 L 1.5% Fluid Miles Sand and Gravel Mix Design 10600FG MD( DESIGN: Shall be based on field experience or trial mixtures in conformance with the specifications. Mix designs shall be submitted to the Building Official two weeks prior to their first use. MATERIAL REQUIREMENTS: Cement: ASTM C150 Admixtures: ACI 301 Aggregates: ASTM C33 Water: ASTM C94 PLACING REQUIREMENTS: PLACING Place concrete as nearly as practicable to its final position to avoid segregation. The free unconfined fall of the concrete shall not exceed 5 feet. DEBRIS: Remove all debris from forms prior to placing concrete. CONSOLIDATION: Consolidate concrete by suitable means. Thoroughly work concrete around embedded items and into corners of forms. CURING REQUIREMENTS: CURING: Concrete shall be maintained in a moist condition for a suitable period of time after placement. WEATHER CONDITIONS: Adequate precautions shall be taken during hot and cold weather in accordance with the specifications. INCLUDE THE FOLLIOWING TABLE 1705.3 ITEMS FOR PERIODIC SPECIAL INSPECTION: 5. VERIFY USE OF REQUIRED DESIGN MIX 12. INSPECT FORMWORK FOR SHAPE, LOCATION, AND DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED IN ADDITION TO PREPARATION OF TEST SPECIMENS, SPECIAL INSPECTION SHALL TEST CONCRETE TEMPERATURE, PERFORM AIR TEST, AND SLUMP. APPLY TO ALL 4 SIDES OF GRATE 5" x 5" x 8" ANGLE w/ %' HOLES AT 24" oc 8" O x 6" EXPANSION ANCHORS w/ 48" EMBEDMENT GRATE RETENTION CURB 4" 38-W-4 67M ears 12-318- D.C. z- 3M Cmn era a r o.c. z Heavy Duty Welded Steel Grating shall be as manufactured by Grating Pacific, Kent, WA 800-243-3939. Grating type; 38 - W - 4 Bar size: 5" x 8" Bearing Bar spacing: 28" Cross bar spacing: 4" Weight per SQ FT: 33,3psf Total Weight: 1840lbs Width (clear span): T-6" (F-Tspan) Length: 10'-0" Ends: open ends of grating shall be banded Finish: Hot Dipped Galvanized GRATE OVER OPENING N.T.S. GRTB REINFORCING BAR MATERIAL REQUIREMENT: REINFORCING BARS: Use deformed bars conforming to ASTM A615, grade 60, except as noted on the drawings. See applicable detail(s): RI WELDED WIRE FABRIC: Smooth fabric shall conform to ASTM A185. All WWF shall be 6x6 W2.9xW2.9 U.N.O. Lap reinforcemnt 8" minimum FA BRICATION AND PLACING REQUIREMENTS: BENDING: Bars shall be bent cold. Bars partially embedded in concrete shall not be field bent unless noted or shown otherwise or authorized by the engineer. PLACING Reinforcement shall be supported and tied to prevent displacement by construction loads or by placing of concrete. Maximum spacing of supports shall be T-6". CONCRETE COVER: Minimum concrete cover for reinf. Shall be as follows, unless noted otherwise: Concrete cast against earth 3" Concrete cast against forms and exposed to earth 2" WELDING Do not weld reinforcing bars. WET SETTINGS: Reinforcement anchor bolts, or any embedded item within the concrete, may not be set into the concrete after it has been poured within the forms. LAP SPLICES: Provide the following lap lengths: #4 bars 24" #5 bars 30" SHOP DRAWING REVIEW Once the contractor has completed his review, the Structural Engineer of Record (SER) will review the submittal for general conformance with the design concept and the contract documents for the building and will stamp the submittal accordingly. Redmarks or comments shall not be construed as relieving the contractor from compliance with the project plans and specifications. Once the contractor has completed his review, the Engineer of Record (EOR) will review the submittal for general conformance with the design concept and the contract documents for the building and will stamp the submittal accordingly. Redmarks or comments shall not be construed as relieving the contractor from compliance with the project plans and specifications. => HOLLOW CORE PANELS => REINFORCING STEEL => CONCRETE MIX DESIGN => VEHICLE GRATE The Engineer of Record will review shop drawings for design intent only. Verification of dimensions and quantities are the responsibility of the contractor. Components primarily designed by the Manufacturer shall be stamped by a licensed engineer. A cursory review for design loads used and their impact on the structure shall be performed. Shop drawings shall be reviewed and signed by the contractor prior to the Engineer's review. A copy shall be provided for the Engineers record as well as any plans required for signature. ,�"7�"0'144 rt LE A m"��"a' r� , �INE r+ �-7 In PANEL LOADING 1/8" _ V-0" PLAN INSTRUCTIONS READ THIS FIRST These plans are organized so that more detailed or specific information is found in the same way by following the direction shown below: GENERAL STRUCTURAL NOTES SCHEDULES, DETAILS and PLANS will often refer to GENERAL STRUCTURAL NOTES for more specific information. SCHEDULES DETAILS and PLANS will often refer to GENERAL STRUCTURAL NOTES and SCHEDULES for more specific information. DETAILS PLANS will often refer to GENERAL STRUCTURAL NOTES, SCHEDULES and DETAILS for more specific information. PLANS See the SYMBOL LEGEND as well as ABREVIATIONIS AND ACRONYMS for other additional information used on the PLANS. The term, TYPICAL (or TYP), used with a detail callout or plan note, indicates that the information specified shall apply in all similar conditions. IF YOU HA VEANY QUESTIONS OR CONCERNS CONTACT US IMMEDIA TEL Y! We can be reached immediately by phone: (425) 778-1023 For less pressing questions, email us: inbox@ssseng.com Please help us get to your plans by having this job number handy: s2301011 ABBREVIATIONS AND ACRONYMS BLK BLOCK EQ EQUAL SIM SIMILAR BLKG BLOCKING EXIST EXISTING STD STANDARD BTM BOTTOM FDN FOUNDATION STRUCT STRUCTURAL BRG BEARING FLR FLOOR THRU THROUGH BTWN BETWEEN FTG FOOTING TYP TYPICAL CLR CLEAR GR GRADE U.N.O. UNLESS NOTED CONIC CONCRETE HORIZ HORIZONTAL OTHERWISE CONT CONTINUOUS MAX MAXIMUM VERT VERTICAL CTR CENTER MFG MANUFACTURED w/ WITH DET DETAIL MIN MINIMUM w/o WITHOUT E.E. EACH END o/ OVER W / C WATER TO E.S. EACH SIDE cc ON CENTER CEMENT RATIO E.W. EACH WAY O.C. ON CENTER W.W.F. WELDED WIRE FABRIC EA EACH REINF REINFORCEMENT ELEV ELEVATION REQD REQUIRED EMBED EMBEDMENT SCHED SCHEDULE DESIGN CRITERIA Governing Code ACI 318-14 IBC 2018 Design Loads )rive Surface (w/ Fire Access) AASHTO HS-25 (Load Case 1) 45-K Outrigger (Load Case 2) -andscape Surface AASHTO HS-20 Soil Cover Soil Cover 1 7.5 ft Maximum Soil Cover Unit Weight 120 pcf Maximum 1 ft Minimum Geotechnical Soil Parameters Allowable Soil Bearing 1500O psf At -rest Earth Pressure 1 55 pcf Passive Earth Pressure 225 pcf Seismic Surcharge 14 H Coefficient of Friction 1 0.4 Geotechnical Report: Cobalt Geosciences Report #: N/A Date: 9/17/2020 BLD2022-0926 01 31 NA r*,q, ME 802 FA MA, VIA FA 11 0A 64, mw FA 16, 1 I ON ME' MiT4 L4 � I I'+ N NO NEEME SSS Number: s2301011 Project Name: Iron Vista Vault Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M c.n N O N O H b J `l' Lr) c.n N J W z E O V U U) 0 z to w V) O U O C N U) to O C LESL/£ Wq p9� �0 20 3373 IsTER� �sNONAt This space reserved for governing jurisdiction stamps RESUB Nov 02 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 1/24/2023 REVISED: 8/18/2023 st CLOSING POUR OR PANEL JOINTS GROUT SOLID CONTINUOUS BACKER ROD (TYPICAL) 16" THICK CAST -IN -PLACE SLAB (CLOSURE POUR), 4000 psi COMPRESSIVE STRENGTH 000 CAST -IN -PLACE SLAB #4 @ 12"oc AT TOP EACH WAY 1%" CLR ° d 000 8 d .4 d ° d g d ° f • — g .1 d ` it • • .. 1%" CLR J #5 @ 6"oc AT BOTTOM, LONGITUDINAL #4 @ 12"oc AT BOTTOM, TRANSVERSE REINF STD 900 HOOK INT MATCH HORIZ \ INTERSECTING GR BEAM REINF ALTERNATE EA BAR V-6" CORNER BAR @ ALL OUTER REINF REINFORCEMENT AT INTERSECTIONS N.T.S. PJA L_J N.T.S. N.T.S. RIBA GRT BACKFILL PER %/�%/ #4 STIRRUPS AT 12"0c #4 STIRRUPS AT 12"oc CIVIL DRAWINGS 1%" CLC, TYP i%" CLC, TYP - #5@8"oc #5@8"oc HORIZONTALLY HORIZONTALLY \ \ 10" WIDE x 30" (MIN) CONCRETE BEAM w/ (2) #5 CONT AT TOP & (3) #6 CONT AT BOTTOM, BOTTOM BARS SHALL TERMINATE WITH A STANDARD 0 HOOK OR EXTEND INTO DETAIL PAK, A MINIMUM OF 24" BAi PEf • GROUT FROM CLOSING POUR 10" T-0" RETAINING CURB @ PANEL ACCESS #5 CONT AROUND PERIMETER, TYP 7 •0 GROUT FROM 10" CLOSING POUR BACKFILL PER CIVIL rn"Trn Anr"IT"Ir nrn rT%ITi nr%rl wr"ITr VENT EXTENDED TO SURFACE I -AN I I-AINCL AU.EZ0 A 1 KINCC WALL PAK2 PANEL ACCESS AT KNEE WALL N.T.S. 24" 0 MAYTMI IM PE "ARS TO MAIN REINF rPENETRATION -0" PAST THE EDGE NGG WALL & REINF PER PLAN HORIZONTAL AND VERTICAL BARS SHALL BE WITHIN 6" OF THE EDGE OR ADDITIONAL BARS SHALL BE PROVIDED REINFORCEMENT AT PENETRATIONS N.T.S. N.T.S. VESA �_J N.T.S. PAK L N.T.S. RAPA RCT2 1 RETAINING CURB @PANEL ACCESS N.T.S. 10'-0" MIN. 40'-0" MAX 10'-0"+"T" MIN. 20'-0" MAX CJ SPACING 20'-0" MAX z� z i=� 0 o ZD BREAK EVERY OTHER WALL & REINF o 0 HORIZONTAL BAR PER PLAN o z U am V _ � o WOOD CHAMFER STRIP DEPTH SHALL BE 1%" THE WALL THICKNESS VERTICAL WALL CONTROL JOINT NOTES: 1. CONSTRUCTION JOINTS NEAREST TO A WALL CORNER OR A WALL TEE SHALL BE NO CLOSER THAN 10'-0" OR MORE THAN 20'-0" FROM THE CORNER. BASE SLAB C.J. NOT TO INCLUDE MORE THAN 400 S.F. JS� CONTROL JOINT SPACING N.T.S. CJSA To° #5 @ 24" oc 24" VOID DAM PER MANUF. GROUT FROM CLOSING POUR 1/4 x 3/8" BRG PER MANUF. 3" MIN. BRIG TOP OF WALL SUPPORTING PANEL (2) #5 CONT AROUND PERIMETER #5 @ 16" oc 34" WALL PER PLAN n""IM it nrn nl ""I TOP OF WALL PARALLEL PANELS (2) #5 CONT AROUND PERIMETER 2" J PAK2 PAK (2) #5 CONT AROUND WALL PER PERIMETER PLAN LAI 5-2" #5@8"oc LONGITUDINAL - EQ 10" EQ SEE PLAN FKWA KNEE WALL AT ACCESS (2) #5 CONT AROUND PERIMETER #5 @ 12" oc 10" (6 TOTAL) 34" ", TYP #5@10"oc CTR HORIZONTALLY #5 @ 12" oc VERTICALLY #5 @ 24" oc 10" (3 TOTAL) 3 "" • • �1 1 EQ 10" EQ SEE PLAN N.T.S. TSPA U N.T.S. TPPA U N.T.S. KWAP 8'-0" 4" RUBBER WATERSTOP #5@8"oc LONGITUDINAL — 3" F- CLR THICKENED J I EDGE FOOTING PER EQ 10" PLAN NOTE SEE PLAN WSP WALL SUPPORTING PANELS 2" CLR #5 @ 12" oc HORIZONTALLY #8@8"oc VERTICALLY #5 @ 16" oc Li"011 DOWELS w/ TEMBED SLAB ON GRADE SLOPE PER PLAN i 1� #4 @ 12"oc TRANSVERSE EQ 4" RUBBER WATERSTOP #5@8"oc LONGITUDINAL 3" 2" CLR #5@12"oc HORIZONTALLY #8@8"oc VERTICALLY #5 @ 16" oc Ll"011 DOWELS w/ TEMBED SLAB ON GRADE SLOPE PER PLAN THICKENED EDGE FOOTING PER EQ 10" PLAN KEY NOTE SEE PLAN — NPP WALL PARALLEL TO PANELS N.T.S. WSPA U N.T.S. WPPA NOTE: MAINTAIN CLEAR COVER PER STRUCTURAL NOTES SECTION "REINFORCING STEEL" CONC WALL & REINF / PER PLAN 5 -o SIZE &SPACE CORNER BARS TO 5' o" MATCH HORIZ. RIENF. WRC WALL REINFORCEMENT AT CORNERS N.T.S. WRCA SSS Number: s2301011 Project Name: Iron Vista Vault Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M c.n N O N O H 0 J 4=> w Ln LIn N J W z O V U ~ CD V7 W U) z w V) cc O U O C N cn V) O C N61 WA ,�� _o4�" zn 0 20 0373 t� ��` '� rsT° 1ss�s �ss�ONAI This space reserved for governing jurisdiction stamps RESUB Nov 02 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 1/24/2023 REVISED: 8/18/2023 S2 0 0 M c'V CU cn I CU U0I 00 0 M [V 2'-0" 11- 22'-11" -I- T-0" �- ----------------------------------------- — - — - — - — - I- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - I I I � II I II I WPP I KWA I � SLAB SLOPED I I I PER CNIL, TYP F- — — 7 -T it I II L J II 2'-6" I I I 1 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 11 - 3'-0" DETENTION VAULT FOOTING & BASE PLAN 1/4" = V-011 9T-10" 35'-0" THICKENED EDGE CONRETE SLAB: 12" THICK BENEATH THE WALLS AND 5" THICK AT THE CENTER OF THE SLAB. USE #4 @ 16"oc EACH WAY FOR SHRINKAGE AND TEMPERATURE REINFORCEMENT. REFER TO GENERAL STRUCTURAL NOTES FOR CONCRETE COVER REQUIREMENTS. REFERENCE CIVIL DRAWINGS FOR ELEVATION. 8'-0" - — - — - --�— — - — - — - — - —�— — - — - — - — - — - — - I F- — — — — — — — -1 1 --J C-------] I T-O" I L J 2'-6" 3'-0" 22' 11" -I 2'-0" I I � I II I � I I � I I � I SLAB SLOPED I 1 PER CIVIL, TYP I I I WPP I II 13'-10" 19'-10" SSS Number: s2301011 Project Name: Iron Vista Vault Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M c.n N O N O H 0 J w Lr) c.n N J w Z E O V V U) 0 Z � w V) O v O C N U) V) O C WA o4�0 zn 20 0373 t� 02 rsT "Z P 1ss�s �sS�ONAI. This space reserved for governing jurisdiction stamps RESUB Nov 02 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 1/24/2023 REVISED: 8/18/2023 S3 0 M cV cn I 00 0 M [V TPP 10" TSP BACKFILL: DO NOT BACKFILL UNTIL THE CLOSING POUR HAS REACHED THE 7 DAY STRENGTH. REFER TO STRUCTURAL NOTES FOR BACKFILL. - 0 0 0 0 0 0 0 0 O I O 0 0A..0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 d. °' d e CIP PRE CAST HOLLOW CORE PANELS, BIDDER DESIGNED. SEE DESIGN CRITERIA FOR LOADING REQUIREMENTS. °. — d. n ° d. a, Z Z Z Z Z Z ° . d Z Z Z Z Z Z Z Z Z W W W W W W .<. °. .° W W W W W W W W W J J J J J J A. J J J J J J J J J J J J J J J J J J J J J J J J W W W W W W T� W W W W W W W W W T� O a io io io io io io io io io io io io io io io ,d A. d PJ PANEL COVER: LIMITS AS TYP W DEFINED IN THE STRUCTURAL W WL NOTES "DESIGN CRITERIA" 0 0 0 0 O I 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W 0 0 0 0 0 0 ff TSP TYP 24'-0" DETENTION VAULT PANEL LAYOUT PLAN 1/4" = V-0" 4'-0" 16'-0" 95'-0" 96'-8" 36'-0" 10" 10" 1 0 6-0" 6-0" CJS TYP DETENTION VAULT WALL PLAN 1/4" = V-0" PAK 7'-0" 0 0 0 0 0 0 0 0 0 0 0 RCT1 W J W J W J W J W J W O a io W ¢ O a io W ¢ O a o W ¢ O a io W T� ¢ O a io 0 0 0 0 0 0 0 0 0 0 M 24'-0" REFERENCE CIVIL DRAWINGS FOR THE SIZE & RAP ELEVATION OF THE INLET AND OUTLET WALL PENETRATIONS. (TYPICAL AT "RAP") TYP 10" 16-0" 174" SSS Number: s2301011 Project Name: Iron Vista Vault Owner: LQH, Inc Project Location: 191xx 94th Ave W, Edmonds, WA Design Professional: LQH, Inc M c.n N O N O H 0 J O w Ll) c.n N J W Z E o I— 0 V_ H CC C t U) 0 z W 0 v 6 c U) V) 0 c LESLI£A 100373 f-isT��� fs')/ONAL��v�h�oti This space reserved for governing jurisdiction stamps RESUB Nov 02 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT ORIGIN DATE: 1/24/2023 REVISED: 7/25/2023 S4 0 M cV cn I 00 0 M [V