Shen-Federman Residence_Drainage Report_Civil Engineering Solutions_Dated 03.29.2023 (1)CIVIL ENGINEERING
MR 1-5 Storm Drainage Summary
Shen/Federman Residence
23310 Humber Lane
Edmonds, WA 98020
Parcel I D : 00 571300101000
4,455 sf new & replaced impervious
March 29, 2023
SOILS ....................glacial till
STORM DISCHARGE ......... basic dispersion
Coauthored by
Stephenie Seawall, civil engineer
Duffy Ellis, P.E.
Page 1 of 9
MR1-5 Drainage Report
23310 Humber Lane
Edmonds, WA 98020
3/29/2023 CES #2070
S O L U T 1 0 N S
General:
This site's proposed impervious area is below 5,000 sf, site is subject to minimum
requirements MR1-5 identified below. Reference attached Edmonds Addendum Figure
3.1.
MR1 = Preparation of Storm Water Site
See C2.0 Drainage Plan
Plans
MR2 = Construction Storm Water Pollution
See CSWPPP included with this
Prevention Plan
submittal. Also see sheet C1.0
TESCP in the civil plan set.
MR3 = Source Control of Pollution
See C1.0 for Temporary Erosion &
Sediment Control. Also see the
CSWPPP document prepared for this
project.
MR4 = Preservation of Natural Drainage
This suburban lot and surrounding
Systems and Outfalls
area have a moderate topographic tilt
toward the west. There are no natural
drainage systems. City storm is
available across the street, but would
require a pump system to make this
solution work. It is unknown what this
existing house does with stormwater.
We discuss MR4 in more depth on
page 6.
MR5 = On -site Stormwater Management
Basic dispersion is proposed for the
roof and driveway areas. Infiltration is
not recommended into the glacial till
soil.
See specific MR5 discussion of each
BMP on pages 6 and 7 of this report.
See the Infiltration report in the
appendix.
MR6 = Runoff Treatment
N/A, project under 5,000 sf
MR7 = Flow Control
N/A, project under 5,000 sf
MR8 = Wetlands Protection
N/A, project under 5,000 sf
MR9 = Operations and Maintenance
N/A, project under 5,000 sf
Page 2 of 9
MR1-5 Drainage Report
23310 Humber Lane
Edmonds, WA 98020
3/29/2023 CES #2070
CIVIL FNGINFFRING
Street View
Vicinity Map
� I
i rr� -
+Southwest
County Park '
J
iget Sound ��Jrj
f
l 99;
Edmonds L _
4n
Shen/Federman /'_ip
Wood I — r Mountlak
S -� Terrace
I Lake
B+Jli.yn
Page 3 of 9
MR1-5 Drainage Report
23310 Humber Lane
Edmonds, WA 98020
3/29/2023 CES #2070
SO_LU_T10NS
Background:
A new single-family two-story house is proposed on this lot adjacent to the east border of
Woodway. Subject lot slopes down to the west at an average grade of 7%. Soil is glacial
till and not great for infiltration. See soil summary below for full explanation.
This lot falls within the Deer Creek drainage basin which is tributary to Lake Washington.
The total new or replaced impervious area is under 5,000 sf including all roof area and
on -site driveway. See exact areas in the appendix.
Soils and Infiltration Feasibility:
Conclusion sourced from the geotech report (see appendix for report)... Soil is glacial till.
During our January 18, 2023 site visit, we assessed the subsurface conditions in
two test holes located... Published geologic maps indicate that the site and
surrounding area are underlain by glacial till, a glacially -compressed mixture of
gravel, silt, and fine-grained sand. The natural soil conditions encountered in the
test holes consist of topsoil overlying weathered, slightly gravelly, silty sand.
Beneath this thin weathered layer is dense, slightly gravelly, silty sand that has
been glacially compressed, and which is referred to as glacial till. This is
consistent with the mapped geology for the area. A layer of fill was encountered
over the native soils in the western test hole (Test Pit 2). We expect that fill may
be encountered elsewhere around the existing house, resulting from the
excavation and grading that occurred during the original site development.
The test holes were conducted following several months of wet weather. Shallow
seepage perched on top of the glacial till, which is relatively impervious, was
observed. This is a common occurrence in the Pacific Northwest on properties
where glacial till or other impervious soils lie close to the ground surface...
Considering the observed soil conditions and the presence of seasonal shallow
perched groundwater, it is our professional opinion that infiltration of
concentrated storm water runoff is infeasible for this site. Attempting to infiltrate
or disperse stormwater on the site would only increase the potential for surface
and subsurface drainage problems on neighboring properties.
Page 4 of 9
MR1-5 Drainage Report
23310 Humber Lane
Edmonds, WA 98020
3/29/2023 CES #2070
CIVIL ENGINEERING
Existing Drainage Pattern narrative:
It is unknown what the existing house does with its stormwater. (Normally houses built in
this era splash -blocked their water.) See downstream map below, assuming water is not
pumped up to the existing city storm (which would also end up in Deer Creek).
Washi
Existing Impervious area:
3,800 sf
Proposed Impervious area:
< 5,000 sf
See impervious spreadsheet in appendix for breakdown
Page 5 of 9
MR1-5 Drainage Report
23310 Humber Lane
Edmonds, WA 98020
3/29/2023 CES #2070
S O L U T I O N S
MR 4 Preservation of Natural Drainage Systems and Outfalls
MR#4 Definition
Natural drainage patterns shall be maintained, and discharges from the project site shall
occur at the natural location, to the maximum extent practicable. The manner by which
runoff is discharged from the project site must not cause a significant adverse impact to
downstream receiving waters and downgradient properties. All outfalls require energy
dissipation. (ref. DOE Manual, 1-2.5.4)
Response:
There are no well-defined natural outfalls and natural drainage systems to
release to on this urban lot. The "natural" place to discharge stormwater for this
lot is basic dispersion, which is proposed for the roof and driveway. See the map
on previous page.
MR#4 Objective
To preserve and utilize natural drainage systems to the fullest extent because of the
multiple stormwater benefits these systems provide; and to prevent erosion at and
downstream of the discharge location. (ref. DOE Manual, 1-2.5.4)
Response:
Basic Dispersion is proposed for the roof and driveway. See the maps on
previous page.
MR#4 Supplemental Guidelines
Creating new drainage patterns results in more site disturbance and more potential for
erosion and sedimentation during and after construction. Creating new discharge points
can create significant stream channel erosion problems as the receiving water body
typically must adjust to the new flows. Diversions can cause greater impacts than would
otherwise occur by discharging runoff at the natural location. (ref. DOE Manual, 1-2.5.4)
Response:
This project should in no way cause adverse problems mentioned above which
are more potential issues related to larger projects as opposed to urban single
family.
Page 6 of 9
MR1-5 Drainage Report
23310 Humber Lane
Edmonds, WA 98020
3/29/2023 CES #2070
S_ O L _U_ T_I O N_S_
MR 5 Proposed On -site Stormwater management:
The List Approach (List #1) selection process was applied to site:
Lawn and Landscaped Areas:
• Post -Construction Soil Quality and Depth in accordance with BMP T5.13 in
Chapter 5 of Volume V of the DOE Manual. Compost -Amended Soil is required
and proposed.
Roofs:
• Full Dispersion:
Not feasible:
A minimum native vegetative flowpath length of 100 lineal feet is not achievable.
• Downspout Full Infiltration:
Full Infiltration is not recommended. Dense glacial till soil. Project geotech, Marc
McGinnis, PE, does not advise infiltration due to the till soil with shallow
groundwater.
• Bio-retention / Raingarden:
Not advised in light of the dense till native soils. There would be a concern about
chronic standing water problem especially during the rainy season.
• Downspout Dispersion:
Proposed for roof and driveway, using the calculation 10 LF / 700 sf tributary
area.
The tributary area is around 3,300 sf (= 3,094 sf roof — 400 sf splash -blocked +
582 sf exposed driveway), so we used the maximum allowed 3,500 sf --> 50 LF
trench.
• PTC
No connection to city storm proposed.
Other Hard Surfaces (i.e. Driveway):
• Full Dispersion serving driveway:
Not feasible:
a minimum native vegetative flowpath length of 100 lineal feet is not even close
to being achievable.
• Permeable Pavement Driveway
Infiltration is not recommended. Dense glacial till soil. Project geotech, Marc
McGinnis, PE, does not advise infiltration due to the till soil with shallow
groundwater. In this case the driveway is tilting down toward the house, another
reason not to attempt driveway infiltration.
Page 7 of 9
MR1-5 Drainage Report
23310 Humber Lane
Edmonds, WA 98020
3/29/2023 CES #2070
CIVIL ENGINEERING
• Bioretention
On this driveway it is impossible to site a rain garden due to the south -to -north
slope of the front yard, and the underground utilities.
Sheet Flow Dispersion serving driveway
Impossible to ever use this BMP on urban lots. You can't achieve the minimum
25' flowpath required between trench and ROW; reference DOE Figure V-5.3.2.
MR6 Runoff Treatment
N/A — Project under 5,000 sf
MR7 Flow Control
N/A — Project under 5,000 sf
Page 8 of 9
MR1-5 Drainage Report
23310 Humber Lane
Edmonds, WA 98020
3/29/2023 CES #2070
CIVIL ENGINEERING
APPENDIX
• Impervious Area Spreadsheet
• Figure 3.1 — Flow Chart for Determining Requirements for Development
• Geotechnical Report, Geotech Consultants, Inc., January 2023
Attached separately
• CSWPPP (sourced from Bellevue, WA)
Page 9 of 9
MR1-5 Drainage Report
23310 Humber Lane
Edmonds, WA 98020
3/29/2023 CES #2070
Impervious Area Spreadsheet (Stormwater)
Shen/Federman Residence - 23310 Humber Lane, Edmonds, WA 98020
Site Area
12,600
sf
0.289
acres
Existing impervious area
Existing imprevious area to be demo'ed
3,595
sf
Existing imprevious area to remain
205
sf
total existing impervious =
3,800
sf
Existing vegetated area
8,800
sf
Proposed Impervious Area (on -site)
Roof
3,094
sf
Exposed driveway, on -site
582
sf
Exposed front/side walkway
779
sf
total new + replaced impervious =
4,455
sf
Existing imprevious area to remain
205
sf
Total proposed impervious =
4,660
sf
Proposed vegetated area
7,940
sf
Does the project result in 2,000 square feet, or greater, of new plus replaced hard surface area?
OR
Does the land disturbing activity total 7,000 square feet or greater?
Yes No
Minimum Requirements No. 1 through 5 apply I Minimum Requirement No. 2 applies
Next Question
IF
Does the project add 5,000 square feet or more of new plus replaced hard surfaces?
OR
Convert 0.75 acres or more of vegetation to lawn or landscaped areas?
OR
Convert 2.5 acres or more of native vegetation to pasture?
No
Yes
Is this a road related project?
All Minimum Requirements
apply to the new and replaced
hard surfaces and converted
vegetation areas.
All Minimum Requirements
apply to the new hard surfaces
and converted vegetation areas.
Yes
No
Yes
Does the project add
5,000 square feet or No
more of new hard
surfaces?
Yes
Do new hard surfaces add 50% or
more to the existing hard surfaces
within the project limits?
No
Figure 3.1. Flow Chart for Determining Requirements for Development.
No additional
requirements.
8 3. APPLICABILITY OF THE MINIMUM REQUIREMENTS
OEOTECH
CONSULTANTS, INC_
Bernard Shen & Catherine Federman
417 N.W. 32"d Street
Seattle, Washington 98177
via email: bernard8shen(aMotmail.cam & cefer8(a-hotmail.com
Subject: Geotechnical Report
Proposed New Residence
23310 Humber Lane
Edmonds, Washington
Greetings:
2401 1 Oth Ave E
Seattle, Washington 98102
(425)747-5618
January 19, 2023
J N 23011
This report presents our geotechnical conclusions related to the planned redevelopment of the
subject property. On January 18, 2023, the undersigned principal geotechnical engineer visited the
subject site to assess both the surface and subsurface conditions. In addition to this work, we have
reviewed published geologic maps, as well as the mapping by the Natural Resources Conservation
Service (NRCS).
Based on the information provided by Patricia Brennan Architects, the existing residence will be
demolished and be replaced with a new home having a larger footprint. The west wall of the new
house will be close to the western extent of the existing residence, and the new house's footprint
will extend eastward from the existing. The new home will be two stories in height. No basement
or deep below -grade spaces will be included.
SITE CONDITIONS
The existing house is one story in height and is centrally located on the lot. A paved driveway
extends from Humber Lane through the southern portion of the property to the garage located in the
south end of the current residence. The remainder of the property is covered primarily with grass,
with some landscape beds. There are two small detached sheds located in the southwestern
portion of the lot.
There are no steep slopes on, or near, the subject property. Consistent with the neighboring
properties, the natural ground surface slopes only gently downward toward the west from the edge
of Humber Lane. It appears that a storm sewer and associated catch basins are located along the
western edge of paved portion of Humber Lane.
The neighboring properties are similarly developed with one-story homes.
During our January 18, 2023 site visit, we assessed the subsurface conditions in two test holes
located as indicated on the attached Site Exploration Plan. Logs of the test pits are also attached.
Published geologic maps indicate that the site and surrounding area are underlain by glacial till, a
glacially -compressed mixture of gravel, silt, and fine-grained sand. The natural soil conditions
encountered in the test holes consist of topsoil overlying weathered, slightly gravelly, silty sand.
GEOTECH CONSULTANTS, INC.
Shen & Federman A 23011
January 19, 2023 Page 2
Beneath this thin weathered layer is dense, slightly gravelly, silty sand that has been glacially
compressed, and which is referred to as glacial till. This is consistent with the mapped geology for
the area. A layer of fill was encountered over the native soils in the western test hole (Test Pit 2).
We expect that fill may be encountered elsewhere around the existing house, resulting from the
excavation and grading that occurred during the original site development.
The test holes were conducted following several months of wet weather. Shallow seepage perched
on top of the glacial till, which is relatively impervious, was observed. This is a common occurrence
in the Pacific Northwest on properties where glacial till or other impervious soils lie close to the
ground surface.
CONCLUSIONS AND RECOMMENDATIONS
Based on the conditions observed in the test holes, it is our professional opinion that conventional
foundations can be utilized for the proposed residence. All footing areas will have to be excavated
down to the dense, native, glacially -compressed soil. It is possible that this may require
overexcavation below the planned footing grades. We recommend that the footings be excavated
using a smooth bucket, in order to prevent the subgrade disturbance that can result from the teeth
on an excavator's bucket. Where overexcavation below the planned footing grades is necessary,
the additional excavation can be backfilled to the planned footing grade using compacted quarry
spalls or railroad ballast rock. In wet conditions, the footing subgrades should be protected with a
layer of clean crushed gravel, in order to prevent disturbance and softening of the bearing soils
during the placement of foundation forms and rebar.
There are no geologically critical areas on, or near, the site. The potential for future slope
movement is nonexistent and the glacially -compressed soils do not present a seismic hazard.
No significant retaining walls are expected for the new project.
The erosion control measures needed during the site development will depend heavily on the
weather conditions that are encountered. We anticipate that a silt fence will be needed around
the downslope sides of any cleared areas until house excavation is are lowered below the
surrounding grades. Cut slopes and soil stockpiles should be covered with plastic during wet
weather. Following rough grading, it may be necessary to mulch or hydroseed bare areas
that will not be immediately covered with landscaping or an impervious surface. As with
most projects, it may be necessary to implement additional erosion control measures to
address site and weather conditions during the earthwork and construction.
If crawl spaces or interior slab floors are lower than the surrounding grade, footing drains should be
provided. A typical footing drain detail is attached. Given the impermeable nature of the dense
soils, it is not uncommon for shallow seepage to enter crawl spaces. As a result, it would be
prudent to provide a layer of gravel and perforated pipes under the vapor retarder/barrier, in
addition to the perimeter footing drains.
SEISMIC CONSIDERATIONS
In accordance with the International Building Code (IBC), the site class within 100 feet of the ground
surface is best represented by Site Class Type D (stiff soil).
GEOTECH CONSULTANTS, INC.
Shen & Federman JN 23011
January 19, 2023 Page 3
The IBC and ASCE 7 require that the potential for liquefaction (soil strength loss) be evaluated for
the peak ground acceleration of the Maximum Considered Earthquake (MCE), which has a
probability of occurring once in 2,475 years (2 percent probability of occurring in a 50-year period).
The dense, glacially -compressed soil that will support the foundations is not susceptible to seismic
liquefaction under the ground motions of the MCE.
CONVENTIONAL FOUNDATIONS
The proposed residence can be supported on conventional continuous and spread footings bearing
on undisturbed, dense soil, or on compacted crushed rock structural fill placed above this
competent native soil. Prior to placing structural fill beneath foundations, the excavation should be
observed by the geotechnical engineer or building inspector to document that adequate bearing
soils have been exposed.
We recommend that continuous and individual spread footings have minimum widths of 12 and 16
inches, respectively. Exterior footings should also be bottomed at least 18 inches below the lowest
adjacent finish ground surface for protection against frost and erosion. The local building codes
should be reviewed to determine if different footing widths or embedment depths are required.
Footing subgrades must be cleaned of loose or disturbed soil prior to pouring concrete. Depending
upon site and equipment constraints, this may require removing the disturbed soil by hand.
Depending on the encountered soil conditions, overexcavation may be required below the footings
to expose competent native soil. Unless lean concrete is used to fill an overexcavated hole, the
overexcavation must be at least as wide at the bottom as the sum of the depth of the
overexcavation and the footing width. For example, an overexcavation extending 2 feet below the
bottom of a 2-foot-wide footing must be at least 4 feet wide at the base of the excavation. If lean
concrete is used, the overexcavation need only extend 6 inches beyond the edges of the footing.
An allowable bearing pressure of 2,500 pounds per square foot (psf) is appropriate for footings
supported on competent native soil. A one-third increase in this design bearing pressure can be
used when considering short-term wind or seismic loads. For the above design criteria, it is
anticipated that the total post -construction settlement of footings founded on competent native soil
will be less than one inch, with differential settlements on the order of one -half -inch in a distance of
25 feet along a continuous footing with a uniform load.
Lateral loads due to wind or seismic forces may be resisted by friction between the foundation and
the bearing soil, or by passive earth pressure acting on the vertical, embedded portions of the
foundation. For the latter condition, the foundation must be either poured directly against relatively
level, undisturbed soil or be surrounded by level, well -compacted fill. We recommend using the
following ultimate values for the foundation's resistance to lateral loading:
PARAMETER ULTIMATE
VALUE
Coefficient of Friction 0.40
Passive Earth Pressure 300 pcf
Where: pcf is Pounds per Cubic Foot, and Passive Earth
Pressure is computed using the Equivalent Fluid Density.
GEOTECH CONSULTANTS, INC.
Shen & Federman JN 23011
January 19, 2023 Page 4
If the ground in front of a foundation is loose or sloping, the passive earth pressure given above will
not be appropriate. The above ultimate values for passive earth pressure and coefficient of friction
do not include a safety factor.
EVALUATION OF INFILTRATION FEASIBILITY
The dense soil known to underlie this area, and which was observed in the test holes is glacially
compressed. Our review of published geologic maps confirms that the near -surface geologic unit in
this area is glacial till (aka hardpan), which is consistent with the observed soil conditions. There
are no large or continuous pore spaces in the glacial till soils that can transmit water. This soil is
essentially impermeable, preventing downward percolation of water, which often causes a perched
water table to form following extended heavy rainfall. A 1997 study published by U.S. Geologic
Survey (USGS) in cooperation with the Washington Department of Ecology (WDOE) determined the
infiltration capacity of various Washington till soils to vary between 0.0005 and 0.005 inches/hour.
We have found similar extremely low infiltration rates in Pilot Infiltration Tests (PITS) our firm has
conducted in glacial till soils. Often, the impermeable nature of the glacial till causes a shallow
seasonal perched water table to form where the ground surface is not covered by an impervious
layer. This is a common problem in the wet season throughout the Pacific Northwest, and shallow
seepage is evident in the test pits conducted on the site.
Our review of the Web Soil Survey website run by the Natural Resources Conservation Service
(NRCS) indicates that the soil mapping is Alderwood-Urban land complex. This is consistent with
the soil conditions observed in the test pit. The following information is from the Web Soil Survey,
and also indicates that the limiting layer has a very low permeability, far below what is allowed for
design of infiltration systems.
5—Alderwood-Urban land complex, 2 to 8 percent slopes
Map Unit Composition
• Alderwood and similar soils: 60 percent
• Urban land: 25 percent
• Minor components: 15 percent
• Estimates are based on observations, descriptions, and transects of the mapunit.
Properties and qualities
• Slope: 2 to 8 percent
• Depth to restrictive feature: 20 to 40 inches to densic material
• Drainage class: Moderately well drained
• Capacity of the most limiting layer to transmit water (Ksat): Very low to moderately low
(0.00 to 0.06 in/hr)
• Depth to water table: About 18 to 36 inches
• Frequency of flooding: None
• Frequency of ponding: None
• Available water supply, 0 to 60 inches: Low (about 3.0 inches)
Considering the observed soil conditions and the presence of seasonal shallow perched
groundwater, it is our professional opinion that infiltration of concentrated storm water runoff is
infeasible for this site. Attempting to infiltrate or disperse stormwater on the site would only
increase the potential for surface and subsurface drainage problems on neighboring properties.
GEOTECH CONSULTANTS, INC.
Shen & Federman
January 19, 2023
Please contact us if you have any questions regarding this report.
Respectfully submitted,
GEOTECH CONSULTANTS, INC.
��-G R- McGI,�,
e OF WASy� '1'lcP
AL
1 /19/2023
Marc R. McGinnis, P.E.
Principal
Attachments: Vicinity Map, Site Exploration Plan, Test Pit Logs, Footing Drain Detail
cc: Patricia Brennan Architects
via email. office(a�.patriciabrennanarchitects.com
MRM:kg
J N 23011
Page 5
GEOTECH CONSULTANTS, INC.
GEOTECH
CONSULTANTS, INC.
(Source: Microsoft MapPoint, 2013)
VICINITY MAP
23310 Humber Lane
Edmonds, Washington
Job No: Date: Plate:
23011 Jan.2023 I 1
Legend:
TP-1 Test Hole Location
GEOTECH
CONSULTANTS, INC.
SITE EXPLORATION PLAN
23310 Humber Lane
Edmonds, Washington
Job No: Date: Plate:
23011 Jan. 2023 No Scale 1 2
TEST PIT 1
Depth feet
Soil Description
0 — 1.0
Crushed Rock over Topsoil
1.0 — 2.0
Orangish-bro.°, n. slightly gravelly. silty SAND. fine-grained, very
moist. loose
2.0 — 3.0
Grayish-bro�,,.rn, slightly gravelly, silty SAND, fine-grained, very
moist, dense Glacial Till)
Test Hole v,as terminated at a depth of 3.0 feet on January 17, 2023.
Perched ground ,ater seepage ,%as observed at 2.0 feet.
TEST PIT 2
Depth feet
Soil Description
0-2.0
Bro-:,,m, slightly gravelly, silty SAND. fine-grained. very moist. loose
i FILLI
2.0 — 2.5
Old Topsoil
2.5 — 3.5
Orangish-bro,.,:,n, slightly gravelly, silty SAND, fine-grained, very
moist. loose
3.5
Grayish-bro,.^:,n, slightly gravelly, silty SAND, fine-grained, very
moist, dense iGlacial Till)
Test Hole ✓as terminated at a depth of 3.5 feet on January 18, 2023.
Perched ground,• ater seepage was encountered at a depth of 3.5 feet.
GEOTECH
CONSULTANTS, INC.
TEST PIT LOGS
23310 Humber Lane
Edmonds, Washington
Job No: Date: Plate:
23011 Jan.2023 1 1 3
Slope backfill away from
foundation. Provide surface
drains where necessary.
4" min.
Tightline Roof Drain
(Do not connect to footing drain)
Backfill
(See text for
requirements)
O
c�
Nonwoven Geotextile
Filter Fabric
O
LL
Possible Slab
oo.a�-000.a� 000.a�0 .00a
°
o°<
0 0 0 0 0 "Oo�
oO oO oO oO oOo oo.00a 0'0�
o O ° Q' aQ o
0
O L�IL)00(�
�-o o�
000
4" Perforated Hard PVC Pipe
(Invert at least 6 inches below
slab or crawl space. Slope to
drain to appropriate outfall.
Place holes downward.)
a.o.o 0 o.a.o-a o a.o:o-o 0 o.a:o-o 0 o.a
00° ` oO' 00 ` oO' 0o0 ` 00, 0000°°
boa 0'o a�oa 0 0000�00 0 000�00 0 000�c
o,00q °o
°
Vapor Retarder/Barrier and
Capillary Break/Drainage Layer
(Refer to Report text)
NOTES:
(1) In crawl spaces, provide an outlet drain to prevent buildup of water that
bypasses the perimeter footing drains.
(2) Refer to report text for additional drainage, waterproofing, and slab considerations.
GEOTECH
CONSULTANTS, INC.
TYPICAL FOOTING DRAIN
23310 Humber Lane
Edmonds, Washington
Job No: Date: Plate. 4
23011 Jan.2023