BLD2024-1467_Manufacturer_Specifications_and_Installation_Instructions_11.7.2024_8.38.34_AM_46063223 Product Specifications
Decibels([dB(A)]
Max @ 100% load
77
79
Min @ min load
56
60
Compressor
RLA
19
29
LRA
45
58.1
Condenser Fan Motor
Horsepower (HP)
1/6
1/3
FLA
1.0
2.5
Refrigeration System
Refrigerant Line Size'
Liquid Line Size (OD)
3/8"
3/8"
Suction Line Size (OD)
3/4"
7/8"
Refrigerant Connection Size
Liquid Valve Size (OD)
3/8"
3/8"
Suction Valve Size (OD)
3/4"
7/8"
Refrigerant Charge (R410-A, oz)
121
170
Expansion Device
EEV
EEV
Maximum Line Length
100 FT
100 FT
Maximum Elevation Difference
50 FT
50 FT
Operating Range
Cooling
40'F-125°F
Heating
5°F-86°F
Electrical Data
Voltage -Phase -Hz
208/230-1-60
208/230-1-60
Minimum Circuit Ampacity2
24.8
38.8
Max. Overcurrent Protection
40
60
Min/Max Volts
172V/270V
Weight
Net Weight (without packaging)
159
196
Gross Weight (including packaging)'
190
227
Dimensions
Unit L x W x H (in.)
29.1/8x29.1/8x24.15/16 29-1/8x29.1/8x33-3/16
Outdoor Coil
Net face area - sq.ft. Outer Coil
13.6
18.4
Tube diameter -in.
9/32" (7mm)
9/32" (7mm)
No.of rows
2
2
Fins per inch
17
19
Table 1
' Tested and rated in accordance with AHRI Standard 210/240.
s Wire size should be determined in accordance with National Electrical Codes;
extensive wire runs will require larger wire sizes.
3 Must use time -delay fuses or HACK -type circuit breakers of the same size as
noted.
' Weight values are estimated.
Always check the rating plate for electrical data on the unit being
installed.
1 • Unit is factory charged with refrigerant for 15' of V liquid line.
System charge must be adjusted per Installation Instructions Final
Charge Procedure.
• TXV is required at indoor unit to match our outdoor unit.