Loading...
REVIEWED BLD2024-1455+WSEC+11.4.2024_4.22.34_PM+4601095BARRSN M P R (-)\/ I (\I G LIVESS HEATING AIR CONDITIONING ELECTRICAL ' PLUMBING 5100 Pacific Hwy #103, Ferndale, WA 98248 360-676-1131 • 800-328-7774 • fax 360-671-3713 RECEIVED Nov 05 2024 CITY OF EDMONDS DEVELOPMENT SERVICES Mechanical Repairs for Edmonds Hotel DEPARTMENT City of Edmonds Application ID: 1568265 2021 WSEC Compliance REVIEWED BY CITY OF EDMONDS BLD2024-1455 Per Table C403.3.2(4) proposed equipment exceeds values listed for PTHP Standard Size 9800 BTU PTHP cooling requires 11.6 EER, proposed PTHP is 12.52 EER 8500 BTU PTHP heating requires 3.25 COP, proposed PTHP is 3.51 TABLE C403.3.2(4) ELECTRICALLY OPERATED PACKAGED TERMINAL AIR CONDITIONERS. PACKAGED TERMINAL HEAT PUMPS. SINGLE -PACKAGE VERTICAL AIR CONDITIONERS, SINGLE -PACKAGE VERTICAL HEAT PUMPS. ROOM AIR CONDITIONERS AND ROOM AIR -CONDITIONER HEAT PUMPS —MINIMUM EFFICIENCY REDUIREMENTSc Equipment Typo Size Category Subcategory or Minimum Efficiency Test Procedure (Input) Rating Condition < 7.000 Btum 11.9 EER PTHP (cooling mode) Standard 95°F db/75'F wb AHRI 310/380 2 7.000 Btu/h and s 14 0 - (0 300 x Cap,1000) 15.000 Btu/h outdoor air, EER° size &gt. 15,000 Btufh 9.5 EER < 7.000 Btu/h 3.3 COP„ PTHP (heating 47`F db/43'F wb z 7.000 Btu/h ands 3 7 - (0 052 x Cap/1000) mode) Standard 15.000 Btu/h outdoor air COP, ° AHRI 3101380 size Sgt. 15,000 Btu/h 2 90 COP.,