APPROVED RESUB1 FIR2024-0101+Drawings+11.7.2024_9.18.54_AM+4606486LISTINGS & STANDARDS
THIS WET CHEMICAL EXTINGUISHING SYSTEM IS ENGINEERED TO PROVIDE FIRE
PROTECTION FOR RESTAL RANT HOODS, DUCTS AND COOKING APPLIANCES, IS
UL SOD LISTED AND IS TO BE INSTALLED N ACCORDANCE WITH THE FOLLOWING
STANDARDS: Vim
•NFPAI7A 2017EDITION
. NFPA 10 2018 EDTION A
•NFPA96 2017EDITION NF
300
APPLICABLE CODES
NFPA 102018 EDITION
(6.6.2) MAXIMUM TRAVEL DISTANCE SHALL NOT EXCEED 30 FT (9.15DD) FROM THE
HAZARD TO THE EXTINGU ISHER(S)
NFPA 17A 201T EDITION
(5.2.1.1) MANUAL PULL STATIONS INSTALLED NO MORE THAN 48" AND NO LESS THAN 42"
ABOVETHEFLOOR
NFPA 96 2017 EDITION
(8.2.3) EXHAUST FANS & DAMPERS SHALL NOT BE REQUIRED TO SHUT DOWN ON
SYSTEM ACTUATION
(8.3.2) WHEN ITS FIRE -EXTINGUISHING SYSTEM DISCHARGES, MAKEUP AIR SUPPLIED
INTERNALLY TO A HOOD SHALL SHUT DOWN.
(10.4.1) UPON ACTIVATION OF ANY FIRE EXTINGUISHING SYSTEM FOR A COOKING
OPERATION, ALL SOURCES OF FUEL AND ELECTRICAL POWER THAT PRODUCE
HEAT TO ALL EQUIPMENT REQUIRING PROTECTION BY THAT SYSTEM SHALL
AUTOMATICALLY SHUT OFF.
(10.4.3) ANY GAS APPLIANCES NOT REQUIRING PROTECTION BUT LOCATED UNDER THE
SAME VENTALATING EQUIPMENT SHALL ALSO AUTOMATICALLY SHUT OFF UPON
ACTIVATION OF ANY EXTINGUISHING SYSTEM.
(10.4.4) SHUTOFF DEVICE SHALL REQUIRE MANUAL RESET.
(10.5.1.1) AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE LOCATED A MINIMUM OF
M (10 FT) AND A MAXIMUM OF 6 M (20 FT) FROM THE PROTECTED KITCHEN
APPLIANCES) WITHIN THE PATH OF EGRESS.
INSTALLATION REQUIREMENTS
1. ALL PIPE SHALL BE SCHEDULE 40 BLACK IRON. CHROME PLATED/SLEEVED WHERE
EXPOSED.
2. ALL CYLINDER SYSTEMS SHALL HAVE 3/8" SUPPLY LINES AND 3/3" BRANCH LINES.
3. ALL WIRE ROPE SHALL BE 1116" STAINLESS STEEL AND RUN THROUGH 1/2" EMT
CONDUIT.
C U L. LISTED CORNER PULLEYS REQUIRED WHENEVER THE STAINLESS STEEL CABLE
DIRECTION CHANGES.
5. ALL EQUIPMENT WITH FIRE PROTECTION MUST BE SECURED TO FLOOR. (NOT BY
STREIVOR)
6. SWIVEL ADAPTERS MAY BE ADDED TO NOZZLES FOR UP TO 30• ROTATION.
INSTALLATION NOTES:
• All piping is 3/8" Sch40 black pipe or equivalent.
• Fire system must connect to building fire alarm If present.
• Remote Manual Pull must be located in the path of egress
between loft and 20ft from the kitchen exhaust hood, mounted
42in to 48in from the finished floor, with a maximum 14in pull to
activate the system.
• Upon activation of the fire extinguishing system, all sources of fuel
& power to all appliance and outlets located under the ventilation
system, shall be shut down.
• Upon activation of the fire extinguishing system, Make up air
supply shall shut down.
• Upon activation of the fire extinguishing system, Exhaust air shall
stay on, OR turn on in the event it is in the off position.
• K-CLASS portable fire extinguisher to be located along the path of
egress within 30ft of the kitchen exhaust hood.
PULL STATION (#434618) DETECTORS (Series #435546ITerminal #435547)
CORNER PULLEY PROVIDED BY 4NG
OCTAGON -Y E.M.T. DETECTOR BRACKET
FIRE SUPPRESOX TO BE CONDUIT
ESSED OR TEMPERATURE RATED
STUBBED MIN. FUSIBLE LINK
FINISHED CEILIRFACE MOUNT
V J• STAINLESS
FINISHED CEILINGED PLASTIC ®� WIRE ROPE
ACE PLATE
SCISSOR -STYLE LINKAGERED PLASTICGONDU TBREAK ROD THE DETECTOR CONSISTS OF THREE BASIC COMPONENTS:
(RECESSED)DETECTOR BRACKET (#550676)
STAINLESS STEEL SCISSOR LINKAGE (#439515)
TEMPERATURE RATED FUSIBLE LINK (PART #439085 - #439089)
42.48"NOT PROVIDED BY STREIVOR
AF.F.
THE SCISSOR STYLE DETECTOR ALLOWS THE WIRE ROPE TO BE
STRUNG CONTINUOUSLY THROUGH THE DETECTION SYSTEM
FINISHED FLOOR ' RING CONDUIT AND BRACKETS FIRST, THEN THE DETECTOR LINKAGE
PULL HANDLE I ASSEMBLIES ARE CLIPPED ON LATER.
FIRE SYSTEM PIPING=3/8" BLACK PIPE
2.75
�R6EA'E \ ' /
ANSULR102 \/
PIPE & CONDUIT
BY ANSUL DISTRIBUTOR
MARK: H - 1 - SECTION 1
PLAN VIEW
�9.9 —7.645.0
15.5
45 DEG. 450 EG.
11FP o o CO
m M LO
N N �
148.0
MECHANICAL AUTOMAN (PART#79493)
FUSIBLE LINK
CONNECTION GAS VALVE
PULL STATION — CABLE CONNECTION
—18.0; 52.0�
2W
360 DEG. 61360 DEG. of
J J
a a_
A 33FP 11FP
2 FP 2 FP
25-351, 25-35" 35-4011 40-50' 40-50"
2.0 —' 1—
Range Cooking Surface:
36" w X 27" d
a -
x X
L x
a
x
CLASS K WET CHEM EXTINGUISHER
e e
3
SHALL BE INSTALLED 42-48" ABOVE
3
E 8
b t", 3
THE FINISHED FLOOR
' ' o
a
c �
X X
�� a �X
^
�X
c
tX
gt
Mai tp
U
ip
li LL L LL LL [7
LL' LL M
U LL O
MARK: H - 1 - SECTION 1
ELEVATION VIEW
ELECTRICAL
CONNECTIONS
MADE OUTSIDE OF
AUTOMAN
ELECTRICAL SWITCH (PART#551154)
COMMON (RED)
NO — NORMALLY
OPEN(BLACK)
N.
o NOS RMA
BROWN
ACTUATING PRESS CONNECTOR
ARM TIGHTLY AGAINST SWITCH
• OUANITITY:3
• SWITCHISRATEDAT25DVAC,2IARESISTME;
250 VAC 2 HP; 126 VAC, 1 HP
ALARM
COMMON (RED)
COM
NORMALLY
OPEN (BLACK)
N O r NORMALLY
CLOSED(BROWN)
ACTUATING
ARM
• OUANTITY:1
SWITCH IS RATED AT 28 VDC, EO mA
• FIRE SUPPRESSION SYSTEM TO BE FIELD WIRED INTO
BUILDING FIREALARM SYSTEM (BYOTHERS).
SYSTEM SHALL BE DESIGNED, INSTALLED, SERVICED
AND MAINTAINED IN ACCORDANCE WITH NFPA 17A,
NFPA 96, AND MANUFACTURER'S INSTRUCTIONS.
The addition of obstructions to spray Upon system activation the exhaust fan
,at"
ms from the cooking appliance nozzles shall remain on and the fuel, power, and
2.75 such as baffle plates, shelves, or any
modification shal not be permitted. make up air shall shut down.
Approved
DFM Chas Burt
South County Fire
Date: 11 /12/2024
ANSUL R-102 UL300 FIRE SYSTEM
1 N 6 GALLON SYSTEM
22 FLOW POINTS ALLOWED
15 FLOW POINTS USED
�-2.0
3.0 Tank & 1-Tank Enc.
Release
Building is alarmed
and tied into
suppression
system
Connection to
electrical shut
down upon
activation
REMOTE MANUAL
PULL STATION:
Shall be installed
42" - 48" above the
Finished floor and a
distance of at least
1 Oft from the hazard
but not more than
20ft. It shall be
installed in the path
Df exit and require a
maximum force of
40lbs and a
maximum
movement of 14" for
actuation.
DE
LU
J
UQ
Z UJ
ZN
Ow
Uw
WU
O
C Z
LLI Q
LL 0
a -
>CID U
_�00 � aj
Urn ;
Cn
J=)JCq
'ZI: co
QZYoq
/
W00 O
/
C/) :.E-
024-0101