RVWD BLD BLD2024-1278+Structural_PLANS+9.27.2024_12.23.02_PM+4528589STRUCTURAL NOTES O GI (THESE NOTES ARE TYPICAL UNLESS NOTED OR DETAILED OTHERWISE ON DRAWINGS) CODE ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (IBC), 2021 EDITION. SPECIFICATIONS AND STANDARDS WHERE REFERENCED ON THE DRAWINGS ARE TO BE THE LATEST EDITION. DESIGN LOADS DEAD LOADS: ROOF 15 PSF FLOOR 15 PSF LIVE LOADS: ROOF (SNOW LOAD) 25 PSF RESIDENTIAL 40 PSF DECK 60 PSF EARTHQUAKE LOADS: EQUIVALENT LATERAL FORCE PROCEDURE PER ASCE 7-16 SECTION 12.8. SITE CLASS D (DEFAULT) SHORT PERIOD SPECTRAL RESPONSE ACCEL (SS) 1.293 ONE SECOND SPECTRAL RESPONSE ACCEL (SI) 0.456 SHORT PERIOD DESIGN SPECTRAL RESPONSE ACCEL (SDS) 1.034 ONE SECOND DESIGN SPECTRAL RESPONSE ACCEL (SDI) 0.561 RISK CATEGORY II SEISMIC IMPORTANCE FACTOR (IE) 1.0 SEISMIC DESIGN CATEGORY D BASIC SEISMIC FORCE -RESISTING -SYSTEM WOOD SHEATHED SHEAR WALLS RESPONSE MODIFICATION FACTOR, (R) 6.5 REDUNDANCY FACTOR (p) 1.0 SEISMIC RESPONSE COEFFICIENT (CS) 0.159 W = TOTAL SEISMIC DEAD LO�D AS DEFINED PER ASCE 7-16 SECTION 12.7.2. DS R I BASE SHEAR (V), V = CSW = W WIND LOADS: BASIC WIND SPEED (3 SECOND GUST) 97 MPH EXPOSURE B KZT 1.35 SEE PLANS FOR ADDITIONAL DESIGN LOADS. STATEMENT OF SPECIAL INSPECTIONS SPECIAL INSPECTIONS ARE REQUIRED AS INDICATED IN THE FOLLOWING TABLE. THE CONTRACTOR SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND OWNER PRIOR TO COMMENCEMENT OF WORK IN ACCORDANCE WITH SECTION 1704.4 OF THE IBC. STRUCTURAL OBSERVATION OF THE STRUCTURAL SYSTEM BY THE ENGINEER IS NOT REQUIRED. FREQUENCY AND DISTRIBUTION OF REPORTS - INSPECTION REPORTS SHALL BE PROVIDED FOR EACH DAY ON SITE BY SPECIAL INSPECTOR. STRUCTURAL OBSERVATION REPORTS SHALL BE PROVIDED AFTER EACH OBSERVATION. REPORTS SHALL BE DISTRIBUTED TO THE CONTRACTOR, ARCHITECT, ENGINEER AND BUILDING OFFICIAL. SPECIAL INSPECTION OPERATION CONT PERIODIC REMARKS SOILS FOUNDATION BEARING CAPACITY VERIFICATION X NOTE: ALL ITEMS MARKED WITH AN "X" SHALL BE INSPECTED IN ACCORDANCE WITH IBC CHAPTER 17. SPECIAL INSPECTION SHALL BE PERFORMED BY A QUALIFIED TESTING AGENCY DESIGNATED BY THE OWNER. THE ARCHITECT, STRUCTURAL ENGINEER, AND BUILDING OFFICIAL SHALL BE FURNISHED WITH COPIES OF ALL RESULTS. ANY INSPECTION FAILING TO MEET THE PROJECT SPECIFICATIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE DESIGN TEAM. DEFERRED APPROVAL ITEMS SUBMITTAL DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE ARCHITECT OR ENGINEER OF RECORD WHO SHALL REVIEW THEM AND INDICATE THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND THAT THEY HAVE BEEN FOUND TO BE IN GENERAL CONFORMANCE WITH THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN AND SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING OFFICIAL. DEFERRED SUBMITTALS SHALL BE STAMPED AND SIGNED BY A PROFESSIONAL ENGINEER REGISTERED IN THE SAME STATE AS THE PROJECT. i��;,�► IeUI�Jy_Ii���1:���1titL�I�l��li�)��yx. FOUNDATIONS: SPREAD FOOTINGS SOILS REPORT: NOT AVAILABLE AT TIME OF DESIGN ALLOWABLE SOIL PRESSURE: 1500 PSF (ASSUMED) FOOTINGS SHALL BEAR ON FIRM UNDISTURBED EARTH OR 12" OF COMPACTED STRUCTURAL FILL AS REQUIRED AND AT LEAST 18" BELOW ADJACENT EXTERIOR GRADE. ANY FOOTING ELEVATIONS SHOWN IN THE DRAWINGS REPRESENT MINIMUM DEPTHS AND ARE FOR BIDDING ONLY. ACTUAL FOOTING ELEVATIONS ARE SUBJECT TO SITE CONDITIONS AND MUST THEREFORE BE ESTABLISHED BY THE CONTRACTOR. FOOTINGS SHALL BE CENTERED BELOW COLUMNS OR WALLS ABOVE, UNLESS NOTED OTHERWISE. IMPORTED STRUCTURAL FILL AND BACKFILL MATERIAL SHOULD CONSIST OF CLEAN, WELL GRADED GRANULAR MATERIAL FREE OF DEBRIS OR ORGANICS WITH A MAXIMUM PARTICLE DIAMETER OF THREE INCHES AND NO MORE THAN 10% FINES (PASSING THE #200 SIEVE). FILL AND BACKFILL MATERIAL SHOULD BE PLACED IN LEVEL LIFTS NOT EXCEEDING TWELVE (12") INCHES IN LOOSE THICKNESS AND COMPACTED TO A MINIMUM OF 95% OF ITS MAXIMUM DRY DENSITY AS DETERMINED BY ASTM TEST METHOD D1557. BACKFILL BEHIND ALL RETAINING WALLS WITH WELL -DRAINING, GRANULAR FILL AND PROVIDE FOR SUBSURFACE DRAINAGE. PROVIDE DAMPPROOFING AT EXTERIOR FACE OF ALL FOUNDATION WALLS EXPOSED TO EARTH PER ARCHITECTURAL SPECIFICATIONS. EXCAVATIONS AND DRAINAGE INSTALLATION SHALL BE OBSERVED BY A SOILS ENGINEER RETAINED BY THE OWNER. IF EXCAVATION SHOWS SOIL CONDITIONS TO BE OTHER THAN THOSE ASSUMED ABOVE NOTIFY THE STRUCTURAL ENGINEER FOR POSSIBLE FOUNDATION REDESIGN. ,Ko7►ldialtl: ALL CONCRETE SHALL BE MIXED, PROPORTIONED, CONVEYED, AND PLACED IN ACCORDANCE WITH CHAPTER 26 OF ACI 318 AND THE AMERICAN CONCRETE INSTITUTE'S SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301). ALL CONCRETE SHALL BE STONE -AGGREGATE CONCRETE HAVING A UNIT WEIGHT OF APPROXIMATELY 150 POUNDS PER CUBIC FOOT. CONCRETE STRENGTHS AT 28 DAYS (f'c) AND MIX CRITERIA SHALL BE AS FOLLOWS: MAXIMUM MIN CEMENT TYPE OF CONSTRUCTION f'c* WATER/CEMENT CONTENT PER CUBIC MAXIMUM SHRINKAGE STRAIN RATIO YARD STRUCTURAL SLAB 3000 PSI 0.50 5 1/2 SACK N/A GRADE BEAM 3000 PSI 0.50 5 1/2 SACK N/A WALLS 3000 PSI 0.50 5 1/2 SACK N/A THE MINIMUM AMOUNT OF CEMENT LISTED ABOVE MAY BE CHANGED IF A CONCRETE PERFORMANCE MIX IS SUBMITTED TO THE ENGINEER AND THE BUILDING DEPARTMENT FOR APPROVAL TWO WEEKS PRIOR TO PLACING ANY CONCRETE. THE PERFORMANCE MIX SHALL INCLUDE THE AMOUNTS OF CEMENT, FINE AND COARSE AGGREGATE, WATER, AND ADMIXTURES AS WELL AS THE WATER -CEMENT RATIO, SLUMP, CONCRETE YIELD, AND SUBSTANTIATING STRENGTH DATA IN ACCORDANCE WITH CHAPTER 26 OF ACI 318. ALL CONCRETE EXPOSED TO WEATHER OR TO FREEZING TEMPERATURES SHALL BE AIR -ENTRAINED IN ACCORDANCE WITH ACI 318 TABLE 19.3.3.1 FOR MODERATE EXPOSURE CLASS F1. *PROVIDE Pc SPECIFIED IN TABLE FOR DURABILITY REQUIREMENTS. 2500 PSI CONCRETE MEETS STRENGTH REQUIREMENTS, THEREFORE SPECIAL INSPECTION IS NOT REQUIRED. REINFORCING STEEL REINFORCING STEEL SHALL BE DEFORMED BILLET STEEL CONFORMING TO ASTM A615, AND SHALL BE GRADE 60 (Fy = 60,000 PSI), UNLESS NOTED OTHERWISE. GRADE 60 REINFORCING BARS INDICATED ON DRAWINGS TO BE WELDED SHALL CONFORM TO ASTM A706. REINFORCING COMPLYING WITH ASTM A615 MAY BE WELDED IF MATERIAL PROPERTY REPORTS INDICATING CONFORMANCE WITH WELDING PROCEDURES SPECIFIED IN AWS D1.4 ARE SUBMITTED. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. PROVIDE WELDED WIRE FABRIC IN SHEETS NOT ROLLS. LAP WELDED WIRE FABRIC 12" AT SIDES AND ENDS. REINFORCING STEEL SHALL BE DETAILED INCLUDING HOOKS AND BENDS IN ACCORDANCE WITH ACI SP-66 AND ACI 318, LATEST EDITIONS. UNLESS OTHERWISE NOTED, REINFORCING SPLICE LENGTHS AND DEVELOPMENT LENGTHS SHALL BE PER SCHEDULE. REINFORCING SHALL BE PLACED AND ADEQUATELY SUPPORTED PRIOR TO PLACING CONCRETE. WET -SETTING EMBEDDED ITEMS IS NOT ALLOWED WITHOUT PRIOR ENGINEER APPROVAL. BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL NOT BE FIELD BENT UNLESS SO DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER. REFER TO CHAPTER 25 OF ACI 318 FOR OTHER REINFORCING STEEL REQUIREMENTS. MINIMUM LAPS AND EMBEDMENT UNLESS OTHERWISE NOTED, REINFORCING SPLICE LENGTHS AND DEVELOPMENT LENGTHS SHALL BE AS TABULATED BELOW: f'c = 2500 PSI DEVELOPMENT LENGTH LAP SPLICE BAR TENSION COMPRESSION TENSION COMPRESSION SIZE TOP BARS OTHER BARS ALL BARS TOP BARS OTHER BARS ALL BARS #3 24 18 9 30 23 12 #4 31 24 12 41 31 15 #5 39 30 15 51 39 19 #6 47 36 18 61 47 23 #7 68 53 21 89 68 27 #8 1 78 60 24 102 78 30 NOTE: 1. ALL LENGTHS ARE IN INCHES. 2. ALL LAP SPLICES ARE CLASS B. 3. "TOP BARS" ARE HORIZONTAL REINFORCEMENT PLACED SUCH THAT MORE THAN 12 INCHES OF CONCRETE IS CAST IN THE MEMBER BELOW THE BAR. CONCRETE COVER ON REINFORCING CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3" CONCRETE EXPOSED TO EARTH AND WEATHER: #6 BARS AND LARGER 2" #5 BARS AND SMALLER 1 1/2" CONCRETE NOT EXPOSED TO EARTH OR WEATHER: SLABS, WALLS AND JOISTS 3/4" COLUMN TIES OR SPIRALS AND BEAM STIRRUPS 1 1/2" CONCRETE GENERAL NOTES VERTICAL BARS SHALL START FROM TOP OF FOOTING. HORIZONTAL BARS SHALL START A DISTANCE OF 1/2 THE NORMAL BAR SPACING FROM TOP OF FOOTING AND TOP OF FRAMED SLABS. IN ADDITION, THERE SHALL BE A HORIZONTAL BAR AT A MAXIMUM OF 3" FROM TOP OF WALL AND BOTTOM OF FRAMED SLABS. PROVIDE CORNER BARS TO MATCH THE HORIZONTAL REINFORCING WITH TENSION LAP SPLICE AT EACH SIDE PER TABLE, OR BEND ONE SIDE OVER TO PROVIDE TENSION LAP. PROVIDE CONTROL OR CONSTRUCTION JOINTS IN SLABS ON GRADE TO BREAK UP SLAB INTO RECTANGULAR AREAS OF NOT MORE THAN 400 SQUARE FEET EACH. AREAS TO BE AS SQUARE AS PRACTICAL AND HAVE NO ACUTE ANGLES. JOINT LOCATIONS TO BE APPROVED BY THE ARCHITECT. ALL CONSTRUCTION JOINTS SHALL BE THOROUGHLY CLEANED AND PROPERLY PREPARED IMMEDIATELY PRIOR TO POURING OF CONCRETE. DOWEL STEEL SHALL BE THE SAME SIZE AND SPACING AS MAIN REINFORCING DETAILED BEYOND JOINT. SEE ARCHITECTURAL DRAWINGS AND MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND DIMENSIONS OF OPENINGS IN CONCRETE WALLS, FLOORS AND ROOF. UNLESS INDICATED OTHERWISE, REINFORCE AROUND OPENINGS GREATER THAN 12" IN EITHER DIRECTION WITH (2) #5 EACH SIDE AND (1) #5 x 4'-0" DIAGONAL AT EACH CORNER. EXTEND BARS 2'-0" BEYOND EDGE OF OPENING. IF T-0" IS UNAVAILABLE, EXTEND AS FAR AS POSSIBLE AND HOOK. HOOK ALL REINFORCING INTERRUPTED BY OPENINGS. BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL NOT BE FIELD BENT UNLESS SO DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER. SEE ARCHITECTURAL DRAWINGS FOR ALL GROOVES, NOTCHES, CHAMFERS, FEATURE STRIPS, COLOR, TEXTURE AND OTHER FINISH DETAILS AT ALL EXPOSED CONCRETE SURFACES. PROVIDE 3/4" CHAMFER AT ALL CORNERS EXCEPT AS NOTED. LUMBER ALL GRADES SPECIFIED ARE MINIMUM GRADES REQUIRED. ALL LUMBER SHALL BE IN ACCORDANCE WITH WWPA GRADING RULES, KILN -DRIED TO MC 19 AND OF THE FOLLOWING MINIMUM STANDARDS: SIZE CLASSIFICATION SPECIES GRADE Fb (PSI) Fc (PSI) LIGHT FRAMING (STUDS) HEM -FIR STUD 675 800 2x JOISTS AND PLANKS HEM -FIR #2 850 - PLATES AND BLOCKING HEM -FIR #2 850 - 6x AND LARGER BEAMS AND STRINGERS DOUG-FIR #2 875 - 4x AND SMALLER BEAMS AND STRINGERS HEM -FIR #2 850 - ALL POSTS AND TIMBERS DOUG-FIR #1 1200 1000 REFER TO PLAN NOTES, SCHEDULES, AND DETAILS FOR MORE SPECIFIC LUMBER SIZE AND GRADE REQUIREMENTS UNLESS NOTED OTHERWISE IN THE PLANS, ALL WOOD AND WOOD -BASED MEMBERS EXPOSED TO WEATHER OR IN CONTACT WITH CONCRETE, MASONRY, OR WITHIN 8" OF SOIL SHALL BE PRESERVATIVE -TREATED BY VACUUM -PRESSURE IMPREGNATION IN ACCORDANCE WITH AWPA STANDARD U1. NAILS, BOLTS, AND METAL CONNECTORS FOR WOOD ALL NAILS SHALL CONFORM TO THE STANDARDS SET FORTH BY THE NATIONAL DESIGN STANDARDS (NDS) FOR WOOD CONSTRUCTION, LATEST EDITION. NAILING NOT SPECIFIED SHALL BE PER IBC TABLE 2304.10.2 NAILING SCHEDULE. ALL NAILS CALLED OUT ON PLANS SHALL BE COMMON NAILS UNLESS NOTED OTHERWISE AND SHALL MEET OR EXCEED THE FOLLOWING MINIMUM GUIDELINES: NAIL SHANK 0 MIN LENGTH 8d COMMON 0.1310 2 1/2" SHANK 10d COMMON 0.1480 3" SHANK 12d COMMON 0.1480 3 1/4" SHANK 16d COMMON 0.1620 3 1/2" SHANK 10d BOX NAILS MAY BE SUBSTITUTED FOR 8d COMMON NAILS WITH NO CHANGE IN NAIL SPACING. FRAMING MEMBERS MAY BE NAILED WITH 16d SINKERS (0.148" 0 x 3 1/4"), BUT ONLY 16d COMMON NAILS SHALL BE USED WHERE 16d NAILS ARE INDICATED IN THIS DRAWING SET. ENGINEER MAY APPROVE OTHER NAILS IF NAIL LABELS ARE SUBMITTED TO ENGINEER PRIOR TO START OF CONSTRUCTION. ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG SCREWS BEARING ON WOOD. LEAD HOLES FOR LAG BOLTS SHALL BE BORED FOR THE SHANK AND THREADED PORTIONS PER NDS 12.1.4.2. CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE" BY SIMPSON COMPANY, CATALOG TO BE THE LATEST EDITION, OR ENGINEER APPROVED EQUAL. CONNECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND WITH THE NUMBER AND SIZE OF FASTENERS AS SPECIFIED BY THE MANUFACTURER. WHERE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE ONE-HALF OF THE NAILS, SCREWS, OR BOLTS IN EACH MEMBER. INSTALL SOLID BLOCKING AT ALL BEARING POINTS. ALL SHIMS SHALL BE SEASONED, DRIED, AND THE SAME GRADE (MINIMUM) AS MEMBERS CONNECTED. GALVANIZATION UNLESS NOTED OTHERWISE, STEEL CONNECTORS IN CONTACT WITH TREATED WOOD SHALL BE GALVANIZED ACCORDING TO THE FOLLOWING TABLE: GALVANIZATION UNTREATED WOOD CCA-C SBX ACQ-C ACQ-D CBA-A CA-B OTHER BORATE ACZA OTHER PT WOOD G90 X X X G185 X X X X X X HDG X X X X X X STT300 X X X X X X X X G90 = 0.90 OZ. OF ZINC PER SQUARE FOOT OF AREA G185 = 1.85 OZ. OF ZINC PER SQUARE FOOT OF AREA HDG = HOT DIP GALVANIZED SST300 = TYPE 316L STAINLESS STEEL RATED SHEATHING RATED SHEATHING SHALL BE GRADE C-D INT-APA WITH EXTERIOR GLUE OR OSB SHEATHING WITH EXTERIOR GLUE IN CONFORMANCE WITH IBC STANDARD 2303.1.5. TIMBERSTRAND, MICROLLAM, AND PARALLAM MEMBERS FABRICATED IN CONFORMANCE WITH THE INTERNATIONAL CODE COUNCIL EVALUATION SERVICE (ICC-ES) REPORT NO. ESR-1387 OR CCMC REPORT NO. 12627-R, 08675-R, AND 11161-R. EACH MEMBER SHALL BE IDENTIFIED BY A STAMP INDICATING THE PRODUCT TYPE AND GRADE, ICC-ES OR CCMC REPORT NUMBER, MANUFACTURER'S NAME, PLANT NUMBER AND INDEPENDENT INSPECTION AGENCY'S LOGO. FABRICATOR SHALL BE CERTIFIED. MEMBERS SHALL MEET THE FOLLOWING MINIMUM STANDARDS: SIZE CLASSIFICATION SPECIES GRADE Fb (PSI) Fv (PSI Fc (PSI) BEAMS & POSTS (d < 9 1/2") LSL 1.3E 1,700 425 1,835 RIMS & BEAMS (d >_ 9 1/2") LSL 1.55E 2,325 310 - BEAMS & POSTS LVL 2.0E 2,600 285 2,510 POSTS (d < 9 1/2") PSL 1.8E 2,400 190 2,500 BEAMS (d >_ 9 1/2") PSL 2.0E 2,900 290 - TIMBERSTRAND, MICROLLAM, AND UNTREATED PARALLAM MEMBERS ARE INTENDED FOR DRY -USE APPLICATIONS. UNLESS NOTED OTHERWISE, ENGINEERED WOOD BEAMS EXPOSED TO WEATHER SHALL BE TREATED PER MANUFACTURER'S RECOMMENDATIONS. GLUE -LAMINATED TIMBER GLUE -LAMINATED TIMBER SHALL BE DOUGLAS FIR, FABRICATED IN CONFORMANCE WITH ANSI/AITC STANDARD A190.1, LATEST EDITION. EACH MEMBER SHALL BEAR AN AITC IDENTIFICATION MARK AND SHALL BE ACCOMPANIED BY AN AITC CERTIFICATE OF CONFORMANCE. FABRICATOR SHALL BE CERTIFIED. MEMBERS SHALL BE OF THE FOLLOWING MINIMUM STANDARDS: SPAN COMBINATION Fb SIMPLE SPAN BEAMS 24F-V4 2400 PSI CANTILEVER OR MULTI -SPAN BEAMS 24F-V8 2400 PSI TYPICAL FRAMING NOTES 1. BEARING WALL FRAMING 2x STUDS @ 16" OC FOR ALL SHEAR AND/OR BEARING WALLS UNO REFER TO FRAMING PLAN NOTES FOR TYPICAL DOOR & WINDOW HEADERS NOT CALLED OUT ON THE PLANS. HEADERS SHALL BE SUPPORTED BY A MINIMUM OF (1) CRIPPLE AND (1) FULL HEIGHT STUD UNO. COLUMNS BELOW FLUSH MULTIPLE JOIST BEAMS SHALL BE EQUAL IN WIDTH TO THE BEAM. ALL COLUMNS NOT CALLED OUT OTHERWISE SHALL BE TWO STUDS. 2. WALL BASE PLATE ON CONCRETE WALL PLATES BEARING ON CONCRETE SHALL BE PRESSURE -TREATED. FOR ALL EXTERIOR AND INTERIOR WALLS, BOLT PLATES OR SILLS TO CONCRETE STEM WALLS OR THICKENED SLAB FOOTINGS WITH 5/8 INCH DIAMETER ANCHOR BOLTS WITH 7 INCH MINIMUM EMBEDMENT. PLACE AT 5'-0" OC MAXIMUM FOR SHEAR WALLS, AND AT 6'-0" OC FOR BEARING WALLS AND OTHER PARTITIONS. USE MINIMUM OF TWO ANCHOR BOLTS PER SILL AND PLACE ONE WITHIN 12 INCHES OF END OF PLATES, TYPICAL UNLESS NOTED OR DETAILED OTHERWISE. REFER TO SHEAR WALL SCHEDULE. AT ALL SILL PLATE ANCHOR BOLTS, CONTRACTOR SHALL INSTALL 1/4" x 3" x 3" FLAT PLATE WASHERS. INTERIOR NON-STRUCTURAL WALLS MAY BE ANCHORED TO CONCRETE SLAB -ON -GRADE WITH 1/4" x 3" POWDER ACTUATED FASTENERS WITH 3/4" WASHERS AT 16" OC AND WITHIN 6" OF END OF PLATES. 3. ROOF AND FLOOR FRAMING PROVIDE 1 1/2" FULL DEPTH BLOCKING FOR JOISTS AND RAFTERS AT ALL SUPPORTS AND AT 8'-0" OC MAXIMUM UNO. INTERMEDIATE 8'-0" OC BLOCKING NOT REQ'D IF GWB CEILING IS INSTALLED DIRECTLYTO UNDERSIDE OF FRAMING. PROVIDE TRUSS BLOCKING PANELS FOR ROOF TRUSSES AT SUPPORTS AND SHEAR WALLS, AND WHERE INDICATED ON PLANS AND DETAILS. 4. DIAPHRAGM NAILING ALL SHEAR WALLS, FLOOR AND ROOF DIAPHRAGM NAILINGS SHALL BE AS CALLED OUT ON SCHEDULES OR ON THE PLANS. EXTERIOR WALLS NOT INDICATED AS SHEAR WALLS SHALL BE SHEATHED AND NAILED TO SUPPORTING FRAMING WITH 8d NAILS AT 6" OC AT ALL PANEL EDGES AND 12" OC AT ALL INTERMEDIATE SUPPORTS. THE USE OF NAIL GUNS WILL BE APPROVED IF NAILING INTO THE DIAPHRAGMS CAN BE INSTALLED FLUSH WITH FACE OF SHEATHING. NAIL PENETRATIONS GREATER THAN 1/16" ARE NOT ACCEPTABLE. 5. ALLOWABLE STUD AND PLATE PENETRATIONS CUTTING AND/OR NOTCHING OF WOOD STUDS OR PLATES SHALL NOT EXCEED 25% OF THE STUD/PLATE WIDTH IN EXTERIOR AND BEARING WALLS AND SHALL NOT EXCEED 40% OF THE STUD/PLATE WIDTH IN ANY NON -BEARING PARTITIONS. BORED HOLE DIAMETER IS LIMITED TO 40% OF STUD/PLATE WIDTH IN ANY STUD AND MAY BE 60% IN NONBEARING PARTITIONS OR IF STUD IS DOUBLED. MAINTAIN 5/8" MINIMUM EDGE DISTANCE FROM HOLE EDGE. 6. GYPSUM WALLBOARD NAILING ALL GYPSUM WALLBOARD SHALL BE NAILED TO ALL STUDS AND TOP AND BOTTOM PLATES WITH 6d COOLER NAILS OR NO. 13 GAUGE x 1 5/8" @ 7" OC (5d COOLER NAILS FOR 1/2 INCH GYPSUM SHEATHING). TYPICAL UNLESS NOTED OTHERWISE. INSTALLATION OF GWB SHALL BE SUCH THAT JOINTS ARE STAGGERED ON EACH SIDE OF A SINGLE WALL. EXISTING BUILDING CONTRACTOR SHALL VERIFY ALL DIMENSIONS, MEMBER SIZES AND CONDITIONS OF THE EXISTING BUILDING DEPICTED IN THE DRAWINGS, AND NOTIFY THE STRUCTURAL ENGINEER OF ANY DISCREPANCIES FOR POSSIBLE REDESIGN. CONTRACTOR RESPONSIBLE FOR COMPLETELY SEALING ALL AREAS WHERE EXISTING ROOF MATERIAL IS PENETRATED OR REMOVED. PROVIDE WATER PROOFING AS REQUIRED BY THE ARCH. GENERAL STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS FOR COMPATIBILITY BEFORE PROCEEDING. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT BEFORE PROCEEDING. CONTRACTOR TO SEE ARCHITECTURAL DRAWINGS FOR SIZE AND LOCATION OF PIPE, VENT, DUCT AND OTHER OPENINGS AND DETAILS NOT SHOWN ON THESE DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR ERECTION STABILITY AND TEMPORARY SHORING AS NECESSARY UNTIL PERMANENT SUPPORT AND STIFFENING ARE INSTALLED. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL NOT SATISFY THIS REQUIREMENT. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF A SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND THE STRUCTURAL ENGINEER. LE 0 0 0 0 0 0 0 0 0 0 0 0 0 000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 L REVIEWED BY CITY OF EDMONDS BUILDING DEPARTMENT ENGINES RING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 r�viOTl�y WAS# 7�, 46548 �16NAL J Q F- F- Z O_ m D_ N D' ~ O (n W w Q d 09116124 Ldrlj 00 Q C rn O Y D' a DESIGN: BTJ DRAWN: JEG CHECK: JGG JOB NO: 24292.10 DATE: 09/1 8/24 RECEIVED Sep 30 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2024-1278 M w w ~ LaU J (o O 0 cv Z CL 0 Z w 00 0 x 0) u'0a Q La J 3 uj D J 11 X w o U w w � z H (o O /�/ Z U r 0 LL w La V SHEET: STRUCTURAL NOTES O G (THESE NOTES ARE TYPICAL UNLESS NOTED OR DETAILED OTHERWISE ON DRAWINGS) LEGEND DEFINITION SYMBOL DEFINITION NATIVE SOIL==�=�=� SYMBOL DIRECTION OF FRAMING — — — — — EXTENT OF 10 FRAMING GRANULAR FILL COLUMNS STRUCTURAL STEEL P COLUMN BEARING RATED SHEATHING ON BEAM BEAM CONTINUOUS tb SHEAR WALL OVER SUPPORT SWX (SEE SCHEDULE) COLUMN MARK CONCRETE WALL (SEE SCHEDULE) BEARING STUD FOOTING MARK WALL (SEE SCHEDULE) O HOLDOWN MARK NON -BEARING STUD WALL (SEE SCHEDULE) BEARING STUD HANGER MARK O SHEAR WALL (SEE SCHEDULE) NON -BEARING FLAG NOTE STUD SHEAR WALL (SEE PLAN NOTES) STEEL MOMENT CMU WALL FRAME CONN. P,V� ABBREVIATIONS (A) ABOVE ANCHOR BOLT HORIZ HORIZONTAL AB KIP KING POST ALT ALTERNATE ARCH ARCHITECT KSI KIPS PER SQUARE INCH MECHANICAL MECH (B) BELOW MF MOMENT FRAME BLKG BLOCKING NS NEAR SIDE BM BEAM OC ON CENTER BOT BOTTOM OPP OPPOSITE PLATE PLACES POUNDS PER SQUARE INCH BTWN BETWEEN PL CJP COMPLETE JOINT PENETRATION PLCS CLR CLEAR PSI CMU CONCRETE MASONRY UNIT PSF POUNDS PER SQUARE FOOT COL COLUMN P/T POST TENSIONED CONIC CONCRETE PT PRESSURE TREATED CONN CONNECTION REINF REINFORCING CONT CONTINUOUS REQ'D REQUIRED DBL DIET DOUBLE DETAIL SCHED SCHEDULE SIM SIMILAR DIM DIMENSION SOG SLAB ON GRADE EA EACH STD STANDARD ELEV ELEVATION SW SHEAR WALL EXIST EXISTING TOC TOP OF CONCRETE EXP EXPANSION TOS TOP OF STEEL TOP OF WALL FLR FLOOR TOW FDN FOUNDATION FOOTING TYP TYPICAL FTG UNO UNLESS NOTED OTHERWISE FS FAR SIDE FULL HEIGHT GLUE -LAMINATED BEAM VFY VERIFY FH VIF VERIFY IN FIELD GLB VERT VERTICAL EN G INEE RING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 t�65 0�'9 ONAL '';4 J H H Z 2 O m F CL N U � W Lu 0 d Y Q 09115124 DESIGN: BTJ DRAWN: JEG CHECK: JGG JOB NO: 24292.10 DATE: 09/1 8/24 RECEIVED Sep 30 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2024-1278 m w w U ~ w � co O U cv z CL O Z w 00 o x a) J � O Q Q La J U :D J x � o U w w z 0 z U 0 w IM SHEET: Slm2 C G 4'-5 1/2" Ilk r- I I I I VERIFY/PROVIDE T-0 x T-0" x 10" CONIC FTG W/ (4) #3 EA WAY BOT, TYP (3) PLACES FOUNDATION PLAN (SLAB ON GRADE SCALE: 1/4" = V-0" 2'-0" 0 2'-0" FOUNDATION PLAN NOTES: 1. REFER TO SHEETS S4.1 FOR FOUNDATION DETAILS. 2. EXTERIOR FOOTINGS SHALL BEAR A MIN OF V-6" BELOW ADJACENT GRADE. 3. FOOTINGS AND SLAB ON GRADE SHALL BEAR ON FIRM NATIVE SOIL OR COMPACTED STRUCTURAL FILL. 4. PLACE ALL REINFORCEMENT PER THE STRUCTURAL NOTES AND FOUNDATION DETAILS. REFER TO SHEET S1.1 FOR ADDITIONAL CONCRETE DETAILING REQUIREMENTS. 5. HOLDOWNS ARE SHOWN ON THE FRAMING PLANS. REFER TO HOLDOWN SCHEDULE ON SHEET S3.1 FOR HOLDOWN TYPES AND FRAMING PLANS FOR HOLDOWN ANCHOR BOLT LOCATIONS. 6. REFER TO FRAMING PLANS AND SHEAR WALL SCHEDULE ON SHEET S3.1 FOR LOCATION OF SHEAR WALL ANCHOR BOLTS. ANCHORAGE AT NON -SHEAR WALLS SHALL BE PER STRUCTURAL NOTES. 7. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, WALL LOCATIONS, AND CONCRETE ROUGH OPENINGS WITH ARCHITECTURAL DRAWINGS AND NOTIFY ALL PARTIES OF ANY DISCREPANCIES. AF�f6` vaJ�� 4 HUC HANGER J N d N cn �c. m x w Q a ACn A � O 3 112" x 9 1/2" PSL ri n N c-I x 2x12 HF#2 @ 24" OC 3 ATTACH KING POST W/ CCQ POST CAP & (2) A35 BOT, TYP EA END OF RIDGE BEAM 2x12 HF#2 @ 24" OC 5 CV 4t L.L m x N u LL 2 m x V) VERIFY/PROVIDE 48 HF#2 HDR SUPPORTED BY (2) 2x STUDS EA END VERIFY/PROVIDE SW6 SHEATHING & NAILING PER SCHED AT ALL WALLS WEST EXTERIOR WALLS AT THIS LEVEL A CS16 STRAP ON TOP OF SHEATHING INTO 4x BLKG AT EA SIDE W/ (26) 8d COMMON NAILS @ EA END (15" LONG). ADD NAILS @ 12" OC IN BETWEEN THE ENDS EXIST FLOOR JOISTS ,,r- EXIST RAFTERS ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 J (2) Q UPPER FLOOR FRAMING PLAN ROOF FRAMING PLAN SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0" Z �� �� �� 116 �� ��116 O 4 -0 2 -0 0 2'-0" 4'- 2 -0 0 2 -0 4'- 0 TYPICAL FLOOR FRAMING PLAN NOTES: TYPICAL ROOF FRAMING PLAN NOTES: r ~ 1. REFER TO SHEETS S5.1 FOR TYPICAL FLOOR FRAMING DETAILS. REFER TO SHEET S3.1 FOR SCHEDULES. 1. REFER TO SHEET S6.1 FOR TYPICAL ROOF FRAMING DETAILS. REFER TO SHEET S3.1 FOR SCHEDULES. O 0 ry- Ld 2. FLOOR SHEATHING SHALL BE 3/4" PI 48/24 WITH 10d COMMON NAILS SPACED AT 6" OC AT ALL 2. ROOF SHEATHING SHALL BE 1/2" PI 40/20 WITH 8d COMMON NAILS SPACED AT 6" OC AT ALL 0 a DIAPHRAGM BOUNDARIES, PANEL EDGES AND SHEAR WALLS AND 12" OC AT INTERMEDIATE FRAMING. DIAPHRAGM BOUNDARIES, PANEL EDGES, SHEAR WALLS, COLLECTOR TRUSSES, AND BLOCKING OR REFER TO DETAIL 2/S5.1 FOR SHEATHING LAYOUT AND NAILING. TRUSS BLOCKING PANELS INDICATED ON PLANS. NAILING AT INTERMEDIATE FRAMING SHALL BE 8d COMMON NAILS @ 12" OC. REFER TO DETAIL 2/S5.1 FOR SHEATHING LAYOUT AND NAILING. W 3. COLUMNS NOT OTHERWISE SHOWN OR CALLED OUT ON PLAN SHALL BE (2) 2x STUDS. I-_ 00 3. COLUMNS AND BEARING WALLS SHOWN ON PLANS SHALL BE CONTINUED DOWN TO THE Q 4. UNLESS NOTED OTHERWISE, ALL STUDS SHALL BE HF STUD GRADE AND SPACED AT 16" OC. FOUNDATION UNLESS CARRIED BY A BEAM BELOW. PROVIDE SOLID BLOCKING IN JOIST SPACE BELOW 0 m ALL COLUMNS. 0 5. REFER TO DETAIL 3/S5.1 FOR CONSTRUCTION OF MULTIPLE STUD COLUMNS. V 4. WALLS SHOWN ON THE FRAMING PLANS ARE WALLS BELOW THE FRAMING LEVELS INDICATED. Q HOLDOWNS SHALL BE PLACED AT THE BASE OF THE WALLS SHOWN. Q 5. COLUMNS NOT OTHERWISE SHOWN OR CALLED OUT ON PLAN SHALL BE (2) 2x STUDS. EXTERIOR HEADERS SHALL BE SUPPORTED BY A MINIMUM OF (1) CRIPPLE STUD AND (1) KING STUD. 6. UNLESS NOTED OTHERWISE, ALL STUDS SHALL BE HF STUD GRADE AND SPACED AT 16" OC. 7. REFER TO DETAIL 3/S5.1 FOR CONSTRUCTION OF MULTIPLE STUD COLUMNS. 8. BEAMS SHOWN ON ROOF FRAMING PLAN SHALL BE ABOVE DOUBLE TOP PLATE UNLESS USED AS A DOOR OR WINDOW HEADER. 0'�Aw•lit" OF WAs� "i�465 5 t �IONAL 09/18/24 DESIGN: BTJ DRAWN: JEG CHECK: JGG JOB NO: 24292.10 DATE: 09/18/24 RECEIVED Sep 30 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2024-1278 W o w Ld � Z W Q CD U J N D Q w CL 0000 Dorn ZI..� w Q 0 LL. (n cy-„� 0 V) QO J La X W o 0 Z Z Z 0 D 0 Quo OZ U W Li- Q ! Z SHEET: S2.1 1 4= <> 4m ENGINES RING TYPE APA-RATED ADJOINING PANEL NAILING BLOCK CONN TO NAILING TO BOLT FOUNDATION TO SLAB OR CAPACITY HOEDOWN SCHEDULE MIN CHORD ANCHOR BOLT C GI "All CORNER BARS x Q "A" lk MAY BE SUBSTITUTED FOR ALL 90° HOOKED BARS — STD 90° HOOK TYP UNO UNO, VERT CORNER BARS SHALL BE SAME SIZE TABULATED FOR MIN WALL REINF FOR THICKER WALL — "A" = SPLICE LENGTH SEE NOTES, DETAILS, OR PLANS FOR (1) #4 VERT REQ'D REINF. ALL BARS TO BE CONT OR SPLICED PER STRUCTURAL NOTES STD 180° HOOK HORIZ CORNER BARS OF SIZE AND SPACING TO MATCH (2) #4 VERT REINF OF THINNER WALL PLACE VERT REINF OUTSIDE EXCEPT AS OTHERWISE NOTED OR SHOWN "A" TYPICAL CONCRETE WALL REINFORCING DETAIL SCALE: NTS I 4"0 PERFORATED PVC PIPE PER LOCAL CODES WITH 6" OF 3/4"-1" WASHED ROCK ALL AROUND, WRAPPED IN NON -WOVEN GEOTEXTILE FABRIC. SLOPE TO DRAIN 1/8" PER V-0" MIN. TURN DOWN PERFORATIONS AS SHOWN Q O o°° O° O °0 000 0 O °U o0 ° O0 0 0 0 ° 00°° O 000O 0 0 00 Q LINE OF MAX EXCAVATION. 0 IF SOIL IS OVER EXCAVATED, , 1 REPLACE WITH LEAN MIX CONCRETE NOTE: RAISE STEM WALL AS REQ'D AT PERIMETER AREAS WHERE NEEDED DUE TO CIVIL GRADES. STUD WALL PER FRAMING PLAN NOTES SHEATHING AND NAILING PER PLAN AND SHEAR WALL SCHEDULE x z_Q 00 N PAVING OR FINISHED GRADE PER ARCH DRAWINGS 000 0.° 00 O O ° 0 900.00 °' 0 Z Oo O°0 °0 00Oo 0 o °o °00 0°0 °0°° 00 ° ° o 0 0 O o o° o0 1 III. FOOTING DRAIN (OPTIONAL) ; FIRM BEARING SOIL I OR COMPACTED J STRUCTURAL FILL TYPICAL FOOTING DRAIN (OPTIONAL SCALE: 1" = V-0" SILL PL AND AB DIA AND SPACING PER SHEAR WALL SCHED (2) #4 CONT TOP #4 @ 12" OC EA WAY CENTERED IN WALL U ALT HOOK ol SIZE & REINF ol AS SHOWN PER PLAN TYPICAL STEM WALL DETAIL SCALE: 1" = V-0" ENGINEERING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 ►' AwTxt; wOF 1PAs$ 446Ets �IONAL 0910124 W Q C Ql O Y Q DESIGN: BTJ DRAWN: JEG CHECK: JGG JOB NO: 24292.10 DATE: 09/18/24 RECEIVED Sep 30 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2024-1278 W Q QLa (o ~ 0 _J N W z a- O 0 W 00 Z (n O LLJ � -a J O W F_ J XV a W W 0 0 z z �- cO 0 ZD a � o O U T­ Lw L.L. SHEET: S4.1 O GI STAGGER NAILS ON EA SIDE OF PANEL JOINT AS REQUIRED PER SHEAR WALL SCHED -n-------r- - 1.1 II II 1.1 II II HEADER PER PLAN II II I I II II I I I.1 I•I •11 II II I CRIPPLE STUDS PER I I I I I I I 11 I I PLAN; DO NOT CUT I . 1 I I I I I AWAY MATERIAL FROM CRIPPLE STUDS 11 1 I 1.1 1.1 1 1• 11• II II 1• I I I I II I I II I I I •I 1• I FULL -HEIGHT IIII I l i I I I •I I I I I HOLDOWN CHORD IIII I.1 I•I I I I•I 11.11 II II 1' I II IIII IIII II.11 II II II II II II I.I 1� I II I II I II illi II II 1 •I I.I I I•I I I�i ICI i' I I I IIII IIII II.11 II II II II II II I.I I II I II I II illi i•i II i�i II i�i I• 1 •I I.I 1 I i• I I I II II II II I •I I li AB W/ SIMPSON BP I PL WASHER, TYP I I I•I I •I I I I I•I I I I I II II I• I •i I, I ii PT SILL PL PER SHEAR II I I I I •1 1 1I A I I WALL SCHED I•I I• I 1.1 1------- --jiJ1 I I � � III III II _ CONCRETE FOOTING OR P/T SLAB NOTES: 1. REFER TO STRUCTURAL NOTES FOR ADDITIONAL INFORMATION. 2. FOR SHEAR WALLS WHERE NO HOLDOWNS ARE SPECIFIED THE FIRST AB SHALL BE LOCATED NOT MORE THAN V-0" AND NOT LESS THAN (7) BOLT DIAMETERS FROM END OF WALL. TYPICAL SHEAR WALL DETAIL SCALE: 3/4" = 1'-0" --------------------------------T-n 1.1 1.1 1.1 1.1 1 1.1 II II II II 111 II II II i1 11� II II II II II II II 111 II II II II 111 I•I I'I I'I I•I 11. II I II II II 1I II I FRAMING AT ADJOINING I I 11•I I I PANEL EDGES PER SHEAR I I 1 1 1 II II 11 I'I WALL SCHED 1 I II iI I 111 II II II 11 11�1 II 11 11 11 ill II II II II I'I ICI ICI 1, II II II II II I.1 ICI ICI II II II II II II II II II II II II II II II 1.1 ICI ICI 11 II II 11 II II II II II II II II II II II 1.1 ICI ICI II II II II II II II II II II II II II II II I'I ICI ICI II 11 11 -_ 11 11 _1L------J_L 11 1211 ------ II II I II II 11 11 11 11 II 11 11 1L__ - 1L� __1 A�1 AB SIZE AND SPACING PER PLAN AND SHEAR WALL SCHEDULE, TYP RIM BOARD OR BLOCKING Il C� -111-111--111-11I--111-11I- EDGE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES, TYP 0.131"0 x 3" NAILS @ 9" OC (2) ROWS OF 0.131" 0 x 3" NAILS @ 9" OC STUD WALL PER FRAMING PLAN NOTES, TYP PANEL EDGE NAILING PER SHEAR WALL SCHEDULE, TYP PANEL EDGE NAILING INTO HOLDOWN CHORDS, TYP INTERMEDIATE NAILING @ 12" OC SHEATHING PER PLAN AND SHEAR WALL SCHEDULE HOLDOWN CHORD PER SCHEDULE. REFER TO TYPICAL BUILT-UP COLUMN DETAIL ADDITIONAL END STUD IF REQUIRED TO PROVIDE COUNTERSINK FOR HOLDOWN BOLTS HOLDOWN ANCHORAGE PER PLAN AND SCHEDULE SIMPSON CNW COUPLER 1/2" TO NUT W/ SIZE TO MATCH SHEATHED EDGE HOLDOWN ANCHORAGE PANELEDGE NAILING PER SHEAR WALL SCHED CONTINUE HOLDOWN CHORD TO FOUNDATION CONCRETE STEM WALL CONCRETE FOOTING EDGE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES, TYP SHEATHING (OR GWB) AND NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES, TYP A. CORNER INTERSECTION B.'T' INTERSECTION TYPICAL WALL INTERSECTION DETAIL SCALE: 1" = V-0" PLATE WASHER PER SHEAR WALL SCHED SECTION A -A SCALE: 1 1/2" = V-0" 2x6 STUD @ 2x4 CROSS WALL 2x8 STUD @ 2x6 CROSS WALL EDGE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES, TYP 0.131"0 x 3" NAILS @ 9" OC STUD WALL PER FRAMING PLAN NOTES, TYP SHEATHING (OR GWB) AND NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES, TYP NOTE: STAGGER SHEATHING AS SHOWN. INTERMEDIATE FRAMING MEMBERS SHEATHING PANEL, TYP II II I II , 2x OR 3x BLOCKING ONLY IF BLOCKED DIAPHRAGM IS SPECIFIED FRAMING MEMBERS W/ SPACING PER PLAN CONTINUOUS PANEL EDGES II II I I II II I I II II SUPPORTED PANEL EDGES II II I II II II II _JL_J� DIAPHRAGM BOUNDARY (SHEAR WALL, BEAM, OR DRAG STRUT) TYPICAL FLOOR/ ROOF SHEATHING DETAIL SCALE: NTS (2) ROWS OF (8) 0.131" 0 x 3" 2 1/4" END NAILS @ 3" OC EA SIDE OF ILIDISTANCE, TYP SPLICE AND (2) @ 9" OC ELSEWHERE W/ 1 1/2" EDGE DISTANCE 3" OC SPACING TOPCHORD SPLICE AT LOCATIONS WHERE IT IS NOT POSSIBLE BOTTOM TO INSTALL THE SPECIFIED 0.131" 0 CHORD SPLICE NAILS, THE CONTRACTOR SHALL SPLICE INSTALL SIMPSON CS20 STRAPS EA SIDE OF WALL AT SPLICE. INSTALL EA STRAP W/ (12) 10d AT EA END. WHERE BOTH PLATES ARE CUT, INSTALL CS20 STRAPS AT EA PLATE AND EA SIDE OF THE WALL. J11" 6'-0" MIN BETWEEN SPLICES SPLICES TO OCCUR AT CENTER OF VERTICAL STUDS TOP CHORD SPLICE BOTTOM CHORD SPLICE TYPICAL TOP PLATE SPLICE DETAIL 4 SCALE: NOTE: SUPPORTS AT SOLID POSTS S I M BEAM PER F AND SCHEE SIMPSON LTP2 A35 FRAN ANCHOR EACH. OF BI SOLID OR MULT STUD COLUMN PER F,_ BEAM PARALLEL TO STUD WALL WIDTH, MIN UNO BEAM PER PLAN AND SCHEDULE SIMPSON A35 EACH SIDE OF BEAM o� cc J w 0 SOLID STUD COLU,.,,. , ADJACENT NAILS IN A ROW ARE TO BE DRIVEN FROM OPPOSITE SIDES, TYP FOR 2x4 STUDS, PROVIDE SINGLE ROW OF NAILS STAGGERED EA SIDE WITH 1 1/2" EDGE DISTANCE. FOR 2x6 STUDS, PROVIDE (2) ROWS OF NAILS SPACED AT 2 1/2" W/ 1 1/2" EDGE DISTANCE 9" OC MAX SPACING BETWEEN ADJACENT NAILS IN A ROW 0.131"0 x 3" NAILS, TYP (5) STUDS MAX TO BE USED FOR BUILT-UP COLUMNS TYPICAL BUILT-UP STUD COLUMN DETAIL SCALE: 1" = 1'-0" SIMPSON A35 (ONLY REQUIRED AT EXTERIOR HEADERS GREATER THAN 6' SPAN) JOIST DIRECTION PER PLAN STUD WALL FLKFLivuil,.uL/AK i u i uu vvALL TYPICAL FLUSH BEAM SUPPORT DETAILS SCALE: 1" = V-0" STUD WALL (6) 0.131"0 x 3" NAILS TYPICAL STUDS NAILING PER TYP BUILT-UP STUD COLUMN DETAIL TYP DOUBLE TOP PLATE BEAM OR HEADER PER PLAN AND NOTES AT HOLDOWNS: PROVIDE FULL HT CRIPPLE STUDS PER PLAN HOLDOWN CHORDS PER HD SCHED. AND COLUMN SCHEDULE OTHERWISE: (1) 2x FULL HT OR STRUCTURAL NOTES TYPICAL HEADER DETAIL SCALE: 1" = V-0" J Q �zz Q o�0 N O F- z O O O z z O a O Cr_ Ln 0 O 0 a CHORD SIZE PER HOLDOWN SCHEDULE SIMPSON STRAP WITH FASTENERS PER HOLDOWN SCHEDULE INSTALL MAX NAILING INTO RIM OR BLOCKING WHERE POSSIBLE JOIST DIRECTION PER PLAN FILL JOIST SPACE WITH FULL DEPTH BLOCKING TO MATCH DIMENSIONS OF STUD COLUMN ABOVE TYPICAL STRAP HOLDOWN DETAIL SCALE: 1" = V-0" ENGINES RING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 r1�THI' wof wAs$ 48548 _ NAL 09116124 J Q z O_ I__ N D_ D' ~ u (n W w Q a rlj Q rH O Y D' a DESIGN: BTJ DRAWN: JEG CHECK: JGG JOB NO: 24292.10 DATE: 09/1 8/24 RECEIVED Sep 30 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2024-1278 w W LJ Q C0 U J N Z CL O La 00 0 0:� 0) N O La J Q W X J W Ld 0 Z c ado U y:IIIIINIIII�� S5ml O G SHEATHING AND NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES BREAK SHEATHING \ AT PLATE UNO 2x CONTINUOUS RIM SILL PLATE NAILING PER SHEAR WALL SCHEDULE BREAK SHEATHING AT PLATE UNO _ PANEL EDGE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES NOTE: NON -SHEAR WALL NAILING SHALL BE PER IBC TABLE 2304.9 A. TYPICAL FRAMING STUD WALL PER FRAMING PLAN NOTES SILL PLATE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES SHEATHING AND NAILING PER PLAN WOOD JOISTS PER PLAN AND SCHEDULE 2x4 BLOCKING AT SHEAR WALLS ONLY SHEATHING AND NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES 2x CONTINUOUS RIM BREAK SHEATHING AT RIM AND PROVIDE PANEL NAILING EA SIDE OF JOINT PER SW SCHED PANEL EDGE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES STUD WALL PER FRAMING PLAN NOTES SILL PLATE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES SHEATHING AND NAILING PER PLAN JOISTS PER PLAN AND SCHEDULE B. ALTERNATIVE SHEAR WALL FRAMING SHEATHING AND NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES TYPICAL STUD WALL FRAMING DETAIL - EXTERIOR WALL PERPENDICULAR TO JOISTS SCALE: 1" = V-0" BREAK SHEATHING \ AT PLATE UNO 2x CONTINUOUS RIM SIMPSON LTP4 OR A35 FRAMING ANCHOR PER SW SCHED. (CONTRACTOR OPTION) BREAK SHEATHING AT PLATE UNO PANEL EDGE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES (4) 0.148" x 3" NAILS TOP & BOT III I II II II II DBL 2x BLKG STUD WALL PER FRAMING PLAN NOTES SILL PLATE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES SHEATHING AND NAILING PER PLAN WOOD JOISTS PER PLAN AND SCHEDULE C. ALTERNATIVE SHEAR WALL FRAMING 2x6 HF PARAPET STUDS @ 24" OC SISTERED TO EXIST JOISTS SHEATHING & NAILING PER PLAN AND SHEAR WALL SCHED OR STRUCTURAL NOTES SILL PLATE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES 2x BLKG 2x FULL DEPTH BLKG SILL PLATE NAILING PER SHEAR WALL SCHEDULE PER ARCH TYPICAL STUD WALL FRAMING DETAIL SCALE: 1" = V-0" ENGINES RING, 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 STUD WALL PER FLOOR DIAPHRAGM FRAMING PLAN NOTES BOUNDARY EDGE NAILING SHEATHING AND 2x FULL NAILING PER PLAN DEPTH BLKG AND SHEAR WALL SILL PLATE NAILING SCHEDULE OR PER PLAN AND SHEAR SHEATHING AND STRUCTURAL NOTES WALL SCHEDULE OR NAILING PER PLAN STRUCTURAL NOTES 10d NAILS @ 6" OC DBL RIM PER PLAN ml P- Aw 0WA 1 `Cs'Cz INVERTED LUS HANGER EA JOIST SILL PLATE NAILING PER E� SHEAR WALL SCHEDULE SIMPSON H2.5A TIE EACH JOIST 465 ti ` UL 2x4 BLOCKING s`SI0 PER ARCH EXIST BEAM 09118/ 24 PER PLAN TYPICAL STUD WALL FRAMING DETAIL SCALE: 1" = V-0" STUD WALL PER FRAMING PLAN NOTES SILL PLATE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES SHEATHING AND NAILING PER PLAN SIMPSON H2.5A TIE EACH JOIST 2x4 BLOCKING EXIST BEAM PER PLAN EX SECTION SCALE: 1" = V-0" STUD WALL PER FRAMING PLAN NOTES SILL PLATE NAILING PER PLAN AND SHEAR WALL SCHEDULE OR STRUCTURAL NOTES EXIST SHEATHING EXIST JOIST PER PLAN JOIST PER PLAN W/ (2) 1/4" 0 x 3 1/2" SDS SCREWS @ 12" OC EXIST WOOD STUD WALL LL I I— 00 a C O 09 DESIGN: BTJ DRAWN: JEG CHECK: JGG JOB NO: 24292.10 DATE: 09/18/24 RECEIVED Sep 30 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2024-1278 V/ J Q W 0 U w Q co USN C� w� 0000 Z ui O -a a �J� J w U L.L_ 0 Iw W Z 0 F- (o 0 0 z 0 w < U o w U- SHEET: S5m2 DIAPHRAGM BOUNDARY NAILING PER ROOF FRAMING PLAN NOTES FULL DEPTH BLKG RIPPED TO MATCH SLOPE OF ROOF PROVIDE BOUNDARY NAILING AT TOP PLATE PER SHEAR WALL SCHEDULE SHEATHING AND NAILING PER PLAN AND SHEAR WALL SCHEDULE ROOF SHEATHING AND NAILING PER ROOF FRAMING PLAN NOTES ROOF RAFTERS PER PLAN 2x4 BLKG W/ SILL PL NAILING PER SHEAR WALL SCHED SIMPSON H2.5A TIE STUD WALL FRAMING PER PLAN NOTES TYPICAL RAFTER SUPPORT DETAIL SCALE: 1" = V-0" DIAPHRAGM BOUNDARY NAILING PER ROOF FRAMING PLAN NOTES 2x4 FLAT OUTLOOKER @ 24" OC, 24" MAX OVERHANG 2x FULL DEPTH RIM. NOTCH AT OUTLOOKERS 2x FULL DEPTH BLKG @ 4'-0" OC SHEATHING PER PLAN & SHEAR WALL SCHEDULE SIMPSON A35 CLIPS @ 24" OC (4) 10d NAILS @ BLKG ROOF SHEATHING & NAILING PER ROOF FRAMING PLAN NOTES ROOF JOIST PER PLAN (3) 10d NAILS EA END A34 CLIP EA BLOCK FULL -HEIGHT STUD WALL PER PLAN & NOTES ROOF RAFTER CONNECTION (NON -BEARING' SCALE: 1" = V-0" ROOF VENTILATION Plr ll A Il l`1 I SECTION AT ROOF RIDGE BEAM SCALE: 1" = 1'-0" NOTCH BLKG FOR VENTILATION PER ARCH DIAPHRAGM BOUNDARY NAILING PER ROOF FRAMING PLAN NOTES NOTCH RAFTER AT OUTLOOKER (2" MIN DEPTH) FULL DEPTH BLKG RIPPED TO MATCH SLOPE OF ROOF ROOF SHEATHING AND NAILING PER ROOF FRAMING PLAN NOTES LPT4 @ 24" OC ROOF RAFTERS PER PLAN SIMPSON HU FACEMOUNT HANGER W/ SLOPED SEAT BEAM PER PLAN TYPICAL RAFTER SUPPORT DETAIL SCALE: 1" = V-0" SHEATHING AND NAILING PER ROOF FRAMING PLAN NOTES 2x6 HF LEDGER W/ (2) 0.162" x 3 1/2" NAILS @ 12" OC INTO BLKG PROVIDED BETWEEN STUDS ROOF RAFTER PER PLAN EXIST WOOD STUD WALL PER PLAN 2x6 HF BLKG SLOPED TO MATCH LOWER ROOF PROFILE RAFTER DETAIL AT LOWER ROOF SCALE: 1" = V-0" ENGINES RING 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 0 �vAwTln- �' og WAsp sv 46548 NAL 09116124 W a C Ql O Y D' a DESIGN: BTJ DRAWN: JEG CHECK: JGG JOB NO: 24292.10 DATE: 09/1 8/24 RECEIVED Sep 30 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2024-1278 V) Q W W U w J co U N Z CL O (� w 00 Z 0 x O) (n O L, J a Q W X w J LLJ W Z LL. � 0 Z � 0 0 w < U w SHEET: s6mi