REVIEWED BLD2022-1541+Energy_Code_Sheet_Lighting+11.11.2022_10.12.16_AM+32157862018 WSEC Compliance Forms for Commercial Buildings including Group R2, R3 & R4 over 3 stories and all RI
Administered by: 02022 NEEA, All rights reserved
Project &Applicant
Information
Project Title
Glacier Environmental Services Office Building - 2018 WSEC
For Building Department Use: I Date: NOV ll, 2022
,
REVIEWED
BY
CITY OF EDMONDS
BUILDING DEPARTMENT' ".."..."..." RECEIVED
€.................. Nov 15 2022
BLD2022-1541 anOEEDMONDS
DEVELOFMENTSERVICES
Project Address
7509 212th Street SW
Edmonds, WA 98026
Applicant Name
Theresa Greene
Applicant Phone
425-830-3245
Applicant Email
tg.architect@comcast.net
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
General Occupancy
All Commercial
General Building Use Type
Office, Other
Building Cond. Floor Area
4,600
General Project Types
New Building
New Building or
Addition
Lighting Scope
Interior Lighting
Exterior Lighting
Alteration
Lighting Scope
Project Cond. Floor Area
4,600
Floors Above Grade
2
Compliance Method
Compliance Method 1 - General
Lighting Project Description
Lighting Compliance Scope
Project Type
Interior / Exterior
(Interior includes both interior & parking)
Luminaire Replacement Scope
Compliance Method
LPA Calculation
Adjustment
Compliance Verification
New Building
Interior Lighting
Space by space
No Calculation Adjustments selected
COMPLIES
and Method
New Building
Exterior Lighting
Not applicable to exterior
COMPLIES
Additional Efficiency
Options Included
Reduced lighting power density credit
Enhanced lighting controls credit
14F-
Projec Glacier Environmental Services Office Building - 2018 WSEC ate Nov 11, 2022
Lighting Power Calculation NEW BUILDING - INTERIOR LIGHTING Compliance Verification I COMPLIES
Compliance Method Space by space LPA Calculation Adjustment none
Interior Lighting Power Allowance - Space by Space
General Space Type
Specific Space Type
Ceiling
Height (Ft)
Gross Interior Area (SF)
LPA (Watts/SF)
Total Watts Allowed
(SF x LPA x 1)
Total Proposed Watts
(LPD + Display LPD)
Compliance Status
Atrium
Less than 40 ft ceiling
260
0.39
101
Copy/print room
272
0.31
84
Lounge/breakroom
General
288
0.59
170
Office
Enclosed > 250 sf
1,232
0.66
813
Office
Open plan
1,650
0.61
1,007
Restroom
General
346
0.63
218
Stairwell
General
324
0.49
159
Storage room
Less than 50 sf
84
0.51
43
Proposed Total LPD
1
2569
Totals 1
1 2,595
2,569
COMPLIES
Proposed Lighting Power Density
Fixture Type
Fixture ID
Quantity of
Fixtures (#F)
Watts or
Wattage Limit
per Fixture
(WpF)
Total Linear
Feet (LF)
Watts per Linear
Foot (WpLF)
Total Wafts
Proposed
(#F x WpF) or
(LF x WpLF)
Individual Fixtures
Direct / indirect pendant
Entry Pendant Light
6
40
240
Recessed downlight
6" Recessed Can Light
6
1 17
1
102
Recessed downlight
2X4 LED Recessed
30
1 53
1
1,590
Recessed downlight
2X4 LED Recessed
10
1 53
1
530
Wall -mounted
Restroom Lav Fixture
4
23
92
Other fixture type
Exit Sign w/90 minute Battery Backup
5
3
15
Proposed Total LPD
2569
Project Title
Glacier Environmental Services Office Building - 2018 WSEC ate Nov 11, 2022
Proposed Fixtures Details
NEW BUILDING - INTERIOR LIGHTING
Fixture Type/Application
Fixture ID
Location in Documents Lamp Type
New or
Existing -to -Remain
Individual Fixtures
Direct / indirect pendant
Entry Pendant Light
A2.32 LED
New
Fixture Description:
Are these fixtures located within a daylight zone?: Yes, controls provided
Daylight zone location(s): Sidelit daylight zones (primary and/or secondary)
Dimming method: Step dimming
Do these fixtures require specific application lighting controls?: None required
Recessed downlight
6" Recessed Can Light A2.31 & A2.32 LED
New
Fixture Description: 6" Recessed Can Light
Are these fixtures located within a daylight zone?: No
Do these fixtures require specific application lighting controls?: None required
Recessed downlight
2X4 LED Recessed A2.31 & A2.32 LED
New
Fixture Description: 2X4 LED Recessed Troffer
Are these fixtures located within a daylight zone?: Yes, controls provided
Daylight zone location(s): Sidelit daylight zones (primary and/or secondary)
Dimming method: Step dimming
Do these fixtures require specific application lighting controls?: None required
Recessed downlight
2X4 LED Recessed A2.31 & A2.32 LED
New
Fixture Description: 2X4 LED Recessed Troffer
Are these fixtures located within a daylight zone?: No
Do these fixtures require specific application lighting controls?: None required
Wall -mounted
Restroom Lav Fixture A2.31 & A2.32 LED
New
Fixture Description: Restroom Lav fixture
Are these fixtures located within a daylight zone?: No
Do these fixtures require specific application lighting controls?: None required
Other fixture type
I Exit Sign w/90 minute Battery Backup A2.31 & A2.32 LED
New
Fixture Description: Exit Light
Are these fixtures located within a daylight zone?: No
Do these fixtures require specific application lighting controls?: None required
91 Glacier Environmental Services Office Building - 2018 WSEC Date I Nov 41, 2022
Lighting Power Calculation EW BUIL G - EXTERIOR LIGHTING Compliance Verification I COMPLIES
Exterior Lighting Zone ZONE 3 Base Site Allowance 500
Exterior Tradable Lighting Power Allowance
Tradable Surface
Tradable Surface Sub -Type
Surface
Area (SF)
LPA
(Watts/SF)
Linear
Feet (LF)
LPA
(Watts/LF)
Total Watts Allowed
(LPA x SF) or
(LPA x LF)
Total Tradable
Proposed Watts
Tradable Compliance
Status
Building grounds
Landscaping
700
0.04
28
Building grounds
Walkways < 10 feet wide
212
0.60
127
Building entrances and exits
Entry canopies
1 168
1 0.40
1
67
Base Site Allowance
500
Totals
7221
444
1 COMPLIES
Proposed Tradable Lighting Power Density
Watts or
Total Watts
Fixture Type
Fixture ID
Tradable Surface Type
Quantity of
Wattage Limit
Total Linear
Watts per Linear
Proposed
Fixtures (#F)
per Fixture
Feet (LF)
Foot (WpLF)
(#F x WpF) or
(WpF)
(LF x WpLF)
Individual Fixtures
Canopy Entry Canopy Surface Mounted Fixture Building entrances and exits - Entry canopies 6 39 234
Wall -mounted Exterior Wall -Pack Building grounds - Walkways < 10 feet wide 5 30 150
Wall -mounted Exterior Wall -Pack Building grounds - Landscaping 2 30 60
Tradable Proposed Total 444