REVIEWED BLD2022-1541+Energy_Code_Sheet_or_Envelope_Summary+11.11.2022_10.12.16_AM+32157852018 WSEC Compliance Forms for Commercial Buildings including Group R2, R3 & R4 over 3 stories and all RI
Administered by: 02022 NEEA, All rights reserved
Project & Applicant
Information
Project Title
Glacier Environmental Services Office Building - 2018 WSEC
For Building Department Use, I Date: Nov 11, 2022
REVIEWED
CITY OF EDMONDS
€auaDINCDEanRrmENr? RECEIVED
........ ............ .
BLD2022-1541 Nov 152022
DE' o°M H° S--
Project AddressBY
7509 212th Street SW
Edmonds, WA 98026
Applicant Name
Theresa Greene
Applicant Phone
425-830-3245
Applicant Email
tg.architect@comcast.net
For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com
General Occupancy
All Commercial
General Building Use Type
Office, Other
Building Cond. Floor Area
4,600
Project Scope
New Building
Space Conditioning Categories
Fully Conditioned
Project Cond. Floor Area
4,600
Floors Above Grade
2
Compliance Method
Compliance Method I - General
Envelope Project Description
New 2-Story Office Building
Envelope
Compliance
Scope
Scope
Space Conditioning Category
Compliance Method
WWR/SRR
per Category
UA Calculation Adjustment
Fenestration Alternates
Compliance Verification
and
Method
New Building
Fully Conditioned
Prescriptive
35.06% / 0%
None selected
No alternates selected
COMPLIES
Air Barrier Testing I Air barrier testing included in project scope I Air Barrier Comments
Project Title
Glacier Environmental Services Office Building - 2018 WSEC
Date
Nov 11, 2022
Scope & Space Conditioning
NEW BUILDING - FULLY CONDITIONED
Compliance Verification
COMPLIES
Window -to -wall Ratio
1 35.06% Skylight -to -roof -ratio 0%
1 Vertical Fenestration Alternate
No alternates selected
Opaque Envelope Assemblies
Insulation R-Values
Roof/Ceiling
Location in Documents
Assembly ID
Assembly Location
Cavity
o Continuous
( /o penetration)
2nd Layer
(MB Roof)
U-Factor
Net Area (SF)
Insulation entirely above deck
Levels of Insulation, Sheet A2.12, Section 6/A4.2
Table C402.1.4
Exterior
I R-38 (< 0.04%)
U-0.027
2,748
U-Factor Source: WSEC Appendix A
U-Factor Source Description:
Is this assembly exterior or interior?: Exterior
Walls
Location in Documents
Assembly ID
Assembly Location
Cavity
Continuous
(% penetration)
Insulated Wall
Furring
U-Factor
Net Area (SF)
Wood -framed and other -Commercial
Levels of Insulation, Sheet A2.12, Wall Sections, Sheet A4.2
Table C402.1.2
Exterior
R-21
R-0 (< 0.04%)
U-0.054
2,500
Which insulation code target does wall comply with?: R-21 Cavity + Intermediate Framing
U-Factor Source: WSEC Appendix A
U-Factor Source Description:
Wall Framing Type (Standard, Inter., Advanced): Intermediate
Framing Depth: 2x6
Framing Spacing: 16" o.c.
Is this assembly exterior or interior?: Exterior
Slab -on -grade Floors
Location in Documents
Assembly ID
Assembly Location
Slab Edge
Under Slab
F-Factor
Perimeter
Length (SF)
Unheated slab
Levels of Insulation, Sheet A2.12, Wall Sections, Sheet A4.2
Table C402.1.3
I At grade level
R-10
I R-0
F-0.54
212
Slab Insulation Method: 2 ft horizontal (no slab edge insulation)
F-Factor Source: WSEC Appendix A
F-Factor Source Description:
Fenestration & Opaque Door Assemblies
or
Insulation R-Values
Vertical Fenestration
Location in Documents
Assembly ID
Assembly Location
Orientation
Shading (PF)
Fenestration
SHGC
Fenestration
U-Factor
Rough
Opening (SF)
Fixed - Class AW or site built
I Levels of Insulation, Sheet A2.12, Schedules, Sheet A5.2
Table C402.4
I Exterior
South/East/West Facing
I PF < 0.2
1 SHGC-0.38
U-0.38
1,102
U-Factor & SHGC Source: WSEC Appendix A
U-Factor Source Description:
Is this assembly exterior or interior?: Exterior
Fixed - Class AW or site built
Levels of Insulation, Sheet A2.12, Schedules, Sheet A5.2
Table C402.4 Exterior
North Facing PF < 0.2
SHGC-0.51
I U-0.38
128
U-Factor & SHGC Source: WSEC Appendix A
U-Factor Source Description:
Is this assembly exterior or interior?: Exterior
Glazed Doors
Location in Documents
Assembly H)
Assemble Location
Orientation
Shading (PF)
Fenestration
SHGC
Fenestration
U-Factor
Rough
Opening (SF)
Swinging entrance door
Levels of Insulation, Sheet A2.12, Schedules, Sheet A5.2
Table C402.4
Exterior
South/East/West Facing
I PF < 0.2
SHGC-0.38
U-0.6
120
U-Factor & SHGC Source: WSEC Appendix A
U-Factor Source Description:
Is this assembly exterior or interior?: Exterior
Is this a public entrance door?: Yes
Door enclosed within a vestibule?: No vestibule