APPROVED BLD APRVD WC3-BLD2022-0527 Westgate Station II - Shoring Design PlansGENERAL SHORING NOTES (THESE NOTES ARE TYPICAL UNLESS NOTED OR DETAILED OTHERWISE ON DRAWINGS) CODE ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (IBC), 2018 EDITION. SPECIFICATIONS AND STANDARDS WHERE REFERENCED ON THE DRAWINGS ARE TO BE THE LATEST EDITION. STATEMENT OF SPECIAL INSPECTIONS SPECIAL INSPECTIONS ARE REQUIRED AS INDICATED IN THE FOLLOWING TABLE. THE CONTRACTOR SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND OWNER PRIOR TO COMMENCEMENT OF WORK IN ACCORDANCE WITH SECTION 1704.4 OF THE IBC. SPECIAL INSPECTION OPERATION CONT PERIODIC REMARKS SOILS PILE INSTALLATION X GEOTECH ENGINEER GRADING AND EXCAVATION X GEOTECH ENGINEER ANCHOR INSTALLATION X GEOTECH ENGINEER ANCHOR TESTING X GEOTECH ENGINEER NOTE: ALL ITEMS MARKED WITH AN "X" SHALL BE INSPECTED IN ACCORDANCE WITH IBC CHAPTER 17. SPECIAL INSPECTION SHALL BE PERFORMED BY A QUALIFIED TESTING AGENCY DESIGNATED BY THE OWNER. THE ARCHITECT, STRUCTURAL ENGINEER, AND BUILDING OFFICIAL SHALL BE FURNISHED WITH COPIES OF ALL RESULTS. ANY INSPECTION FAILING TO MEET THE PROJECT SPECIFICATIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE DESIGN TEAM. SHOP DRAWINGS SHOP DRAWINGS FOR THE FOLLOWING ITEMS SHALL BE SUBMITTED TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW PRIOR TO FABRICATION: 1. SOLDIER PILES 3. GROUT MIX DESIGN 2. ANCHORS 4. CONCRETE MIX SHOP DRAWINGS SHALL BE REVIEWED, REVISED AS REQUIRED FOR FIELD CONDITIONS, AND DATE STAMPED BY THE CONTRACTOR PRIOR TO REVIEW BY THE ENGINEER. CONTRACTOR SHALL PROVIDE (3) SETS OF SHOP DRAWINGS FOR ENGINEER'S REVIEW. ALLOW TWO WEEKS FOR SHOP DRAWING APPROVAL BY ENGINEER. ENGINEER'S SHOP DRAWING REVIEW IS FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT AND CONTRACT DOCUMENTS. MARKINGS OR COMMENTS SHALL NOT BE CONSTRUED AS RELIEVING THE CONTRACTOR FROM COMPLIANCE WITH THE PROJECT PLANS AND SPECIFICATIONS. THE CONTRACTOR REMAINS RESPONSIBLE FOR DETAILS AND ACCURACY, FOR CONFORMING AND CORRELATING ALL QUANTITIES AND DIMENSIONS, FOR SELECTING FABRICATION PROCESSES, FOR TECHNIQUES OF ASSEMBLY, AND FOR PERFORMING THE WORK IN A SAFE MANNER. ENGINEER'S SHOP DRAWING REVIEW OF STRUCTURAL COMPONENTS DESIGNED BY OTHERS IS FOR LOADS IMPOSED ON THE BASIC STRUCTURE. THE COMPONENT DESIGNER IS RESPONSIBLE FOR CODE CONFORMANCE AND ALL CONNECTIONS TO THE BASIC STRUCTURE. SHOP DRAWINGS SHALL INDICATE MAGNITUDE AND DIRECTION OF THE LOADS IMPOSED ON THE BASIC STRUCTURE AND SHALL BE STAMPED & SIGNED BY A PROFESSIONAL ENGINEER REGISTERED IN THE SAME STATE AS THE PROJECT. FABRICATION SHALL BEGIN ONLY AFTER SHOP DRAWINGS BEARING THE STAMP AND SIGNATURE OF THE PROJECT ARCHITECT, ENGINEER OF RECORD, AND CONTRACTOR HAVE BEEN RECEIVED. STRUCTURAL STEEL STRUCTURAL STEEL DESIGN, FABRICATION AND ERECTION SHALL BE IN ACCORDANCE WITH THE AISC "SPECIFICATION FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS", LATEST EDITION. WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992, Fy = 50 KSI. PLATES, ANGLES, CHANNELS, AND RODS SHALL CONFORM TO ASTM A36, Fy = 36 KSI. STRUCTURAL TUBING SHALL CONFORM TO ASTM A500 GRADE B, Fy = 46 KSI. STEEL PIPE SHALL CONFORM TO ASTM A53 GRADE B, Fy = 35 KSI. BOLTS CONNECTING STEEL MEMBERS SHALL CONFORM TO ASTM A325-N. BOLTS SHALL BE 3/4"0 MINIMUM, UNO ANCHOR BOLTS SHALL CONFORM TO ASTM A307. CONTRACTOR SHALL PROVIDE CONNECTION ADJUSTMENT TOLERANCES TO SATISFY THE REQUIREMENTS OF AISC MANUAL OF STEEL CONSTRUCTION. UNLESS SPECIFIED AS STAINLESS STEEL, ALL STEEL MEMBERS, SHAPES, BOLTS, AND ACCESSORIES EXPOSED TO WEATHER SHALL BE HOT DIP GALVANIZED. WELDING WELDING SHALL CONFORM TO AWS "STRUCTURAL WELDING CODE", LATEST EDITION. ALL WELDING SHALL BE DONE WITH 70 KSI LOW HYDROGEN ELECTRODES. WHERE NOT CALLED OUT, MINIMUM FILLET WELD SIZE SHALL BE PER TABLE 5.8 IN AWS D1.1, LATEST EDITION. WELDING OF REINFORCING BARS SHALL NOT BE PERMITTED UNLESS SPECIFICALLY CALLED OUT ON DRAWINGS OR APPROVED BY STRUCTURAL ENGINEER. WELDING OF GRADE 60 REINFORCING BARS SHALL BE PERFORMED USING LOW HYDROGEN ELECTRODES. WELDING OF GRADE 40 REINFORCING BARS SHALL BE PERFORMED USING E70XX ELECTRODES. SEE REINFORCING NOTES FOR MATERIAL REQUIREMENTS OF WELDED BARS. WELDING WITHIN 4" OF COLD BENDS IN REINFORCING BARS IS NOT PERMITTED. ALL WELDING SHALL BE DONE BY WASHINGTON ASSOCIATION OF BUILDING OFFICIALS (WABO) CERTIFIED WELDERS. UTILITY LOCATION/EXISTING CONDITIONS THE LOCATIONS OF EXISTING UTILITIES AND SITE FEATURES SHOWN HEREON HAVE BEEN FURNISHED BY OTHERS BY FIELD SURVEY OR OBTAINED FROM AVAILABLE RECORDS AND SHOULD THEREFORE BE CONSIDERED APPROXIMATE ONLY AND NOT NECESSARILY COMPLETE. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO INDEPENDENTLY VERIFY THE ACCURACY OF ALL UTILITY LOCATIONS SHOWN AND TO FURTHER DISCOVER AND PROTECT ANY OTHER UTILITIES NOT SHOWN HEREON WHICH MAY BE AFFECTED BY THE IMPLEMENTATION OF THIS PLAN. CG ENGINEERING ASSUMES NO RESPONSIBILITY FOR THE COMPLETENESS OR ACCURACY OF THE EXISTING UTILITIES AND SITE FEATURES PRESENTED ON THESE DRAWINGS. CONTRACTOR SHALL LOCATE AND PROTECT ALL UTILITIES DURING CONSTRUCTION AND SHALL CONTACT THE UNDERGROUND UTILITIES LOCATION SERVICE (1-800-424-5555) AT LEAST 48 HOURS PRIOR TO CONSTRUCTION. CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE PROJECT SITE BEFORE STARTING WORK AND SHALL NOTIFY THE ENGINEER OF ANY DISCREPANCIES. IF THE ACTUAL FIELD VERIFIED LOCATION OF UTILITIES COULD RESULT IN A CONFLICT WITH THE SHORING, THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY. PRIOR TO CONSTRUCTION, CONTRACTOR SHALL VERIFY THAT OVERHEAD OBSTRUCTIONS, INCLUDING ELECTRICAL LINES, DO NOT INTERFERE WITH USE OF THE CONTRACTOR'S DRILLING EQUIPMENT. COORDINATE AND ARRANGE FOR ALL UTILITY RELOCATIONS AND/OR SERVICE INTERRUPTIONS WITH THE AFFECTED OWNERS AND APPROPRIATE UTILITY COMPANIES. INTERRUPTIONS TO EXISTING UTILITIES SHALL BE MADE ONLY WITH THE WRITTEN APPROVAL OF THE AUTHORITIES GOVERNING SAID UTILITIES AND WITH A MINIMUM 48 HOURS ADVANCE NOTICE. EXISTING UTILITY LINES IN SERVICE WHICH ARE DAMAGED DUE TO CONSTRUCTION WORK SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE AND INSPECTED AND ACCEPTED BY OWNER'S REPRESENTATIVE PRIOR TO BACKFILLING. NE 1/4, SECTION 36, TOWNSHIP 27 NORTH, RANGE 3 EAST, W.M. EROSION AND SEDIMENTATION CONTROL ALL DISTURBED SOIL AREAS SHALL BE SEEDED OR STABILIZED BY OTHER ACCEPTABLE METHODS FOR THE PREVENTION OF ON -SITE EROSION AFTER THE COMPLETION OF CONSTRUCTION. THE CONTRACTOR SHALL KEEP OFF -SITE STREETS CLEAN AT ALL TIMES BY SWEEPING. WASHING OF STREETS WILL NOT BE ALLOWED WITHOUT PRIOR APPROVAL. REFER TO CIVIL DRAWINGS FOR ADDITIONAL EROSION CONTROL INFORMATION. TEMPORARY SHORING CONTRACTOR SHALL BE RESPONSIBLE FOR AND SHALL INSTALL AND MAINTAIN TEMPORARY SHORING AND BRACING IN ADDITION TO SHORING SHOWN ON THESE PLANS AS NECESSARY TO PROTECT WORKERS, EXISTING BUILDINGS, STREETS, WALKWAYS, UTILITIES AND OTHER EXISTING AND PROPOSED IMPROVEMENTS AND EXCAVATIONS AGAINST LOSS OF GROUND OR CAVING EMBANKMENTS. CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR REMOVAL OF ANY TEMPORARY SHORING AND BRACING, AS REQUIRED. FOUNDATIONS: SOLDIER PILES SOILS REPORT: REPORT NO: 1156720 PREPARED BY: NELSON GEOTECHNICAL ASSOCIATES DATED: APRIL 14, 2020 REFER TO SOIL PRESSURE DIAGRAMS ON THIS SHEET FOR DESIGN EARTH PRESSURES. ALLOWABLE GROUTED ANCHOR COHESION IN COMPETENT SOIL = 1500 PSF CONCRETE/GROUT ALL CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF CHAPTER 19 OF THE INTERNATIONAL BUILDING CODE. CONCRETE STRENGTHS SHALL BE VERIFIED BY 28-DAY STANDARD CYLINDER TESTS, UNLESS APPROVED OTHERWISE. GROUT STRENGTHS SHALL BE VERIFIED BY 2-INCH CUBE TESTS PER ASTM C109. CONCRETE MIX DESIGNS SHALL CONFORM TO THE UNIFORM BUILDING CODE. COMPRESSIVE STRENGTH AT 28 DAYS SHALL BE AS FOLLOWS: SOLDIER PILE CONCRETE ABOVE GRADE: LEAN CONCRETE f'c = 500 PSI BELOW GRADE: LEAN CONCRETE f'c = 2500 PSI GROUTED ANCHOR GROUTED ANCHOR f'c = 3000 PSI MIN GROUTED ANCHORS GROUTED ANCHORS SHALL BE MANUFACTURED BY DYWIDAG SYSTEMS INTERNATIONAL OR ENGINEER APPROVED EQUAL. ANCHORS SHALL BE FACTORY DOUBLE CORROSION PROTECTED. REFER TO ANCHOR SCHEDULE FOR GROUTED DIAMETER AND ANCHOR ROD DIAMETER. ANCHOR RODS SHALL CONFORM TO ASTM A722, fu = 150 KSI ALL ANCHORS SHALL BE LOCKED OFF PER THE ANCHOR SCHEDULE PILE CORROSION PROTECTION PILES SHALL BE PAINTED TO PROTECT AGAINST CORROSION. BEFORE APPLYING PAINT PILES SHALL BE CLEAN AND FREE OF RUST OR DEBRIS. PAINTING SHALL CONSIST OF AN ORGANIC ZINC PRIMER COAT NOT LESS THAN 2.5 MILS DRY FILM THICKNESS. TOP COAT SHALL CONSIST OF AN EPDXY PAINT NOT LESS THAN 3.0 MILS DRY FILM THICKNESS. PILES SHALL BE PAINTED TO T-0" BELOW GRADE MINIMUM. ANY SCUFF MARKS OR SCRATCHES THAT OCCUR DURING CONSTRUCTION SHALL BE REPAIRED WITH A FIELD APPLIED EPDXY PAINT. TIMBER LAGGING/SAWN LUMBER SAWN LUMBER SHALL CONFORM TO GRADING AND DRESSING RULES, WEST COAST LUMBER INSPECTION BUREAU (WCLIB), LATEST EDITION. LUMBER SHALL BE THE GRADE LISTED BELOW: ALL LAGGING SHALL BE TREATED WITH ACZA WOOD PRESERVATIVE TREATMENT WITH 0.4 LBS/CU FT. ANY LAGGING FIELD CUT SHALL HAVE ACZA TREATMENT FIELD APPLIED TO THE CUT END. 4x LAGGING SHALL HAVE A MINIMUM ALLOWABLE BENDING STRESS Fb = 900 PSI. 6x AND 8x LAGGING SHALL HAVE A MINIMUM ALLOWABLE BENDING STRESS, Fb = 875 PSI ANCHOR TESTING EACH GROUND ANCHOR SHALL BE TESTED. THE MAXIMUM TEST LOAD SHALL NOT EXCEED THE MANUFACTURER RECOMMENDED MAXIMUM LOAD. TENDON ANCHORS SHALL BE LOADED SIMULTANEOUSLY TO THE ENTIRE TENDON. STRESSING OF A SINGLE ELEMENT OF MULTI -ELEMENT TENDONS WILL NOT BE PERMITTED. A DIAL GAUGE OR VERNIER SCALE CAPABLE OF MEASURING TO 0.001 INCHES SHALL BE USED TO MEASURE THE GROUND ANCHOR MOVEMENT. THE MOVEMENT MEASURING DEVICE SHALL HAVE A MINIMUM TRAVEL EQUAL TO THE THEORETICAL ELASTIC ELONGATION OF THE TOTAL ANCHOR LENGTH AT THE MAXIMUM TEST LOAD PLUS 1 INCH. THE DIAL GAUGE OR VERNIER SCALE SHALL BE SUPPORTED INDEPENDENT OF THE JACKING SYSTEM & RETAINED STRUCTURE & SHALL BE ALIGNED SO THAT ITS AXIS IS WITHIN 5° FROM THE AXIS OF THE GROUND ANCHOR. A HYDRAULIC JACK OR RAM SHALL BE USED TO APPLY THE TEST LOAD. THE JACK & PRESSURE GAUGE SHALL BE CALIBRATED BY AN INDEPENDENT TESTING LABORATORY AS A UNIT. THE PRESSURE GAUGE SHALL BE GRADUATED IN 100 PSI INCREMENTS OR LESS. THE RAM TRAVEL OF THE JACK SHALL NOT BE LESS THAN THE THEORETICAL ELASTIC ELONGATION OF THE TOTAL ANCHOR LENGTH AT THE MAXIMUM TEST LOAD PLUS 1 INCH. THE JACK SHALL BE INDEPENDENTLY SUPPORTED & CENTERED OVER THE ANCHOR SO THAT THE ANCHOR DOES NOT CARRY THE WEIGHT OF THE JACK. ANCHOR LOAD TEST AT LEAST (2) ANCHOR SHALL BE PERFORMANCE TESTED TO 200% OF THE DESIGN LOAD. ANCHORS TO BE TESTED SHALL BE SELECTED BY THE GEOTECHNICAL ENGINEER. ADDITIONAL ANCHOR TESTS MAY BE REQUIRED AT THE REQUEST OF THE GEOTECHNICAL SPECIAL INSPECTOR. CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLATION OF WHALERS IF REQUIRED TO LIMIT PILE DEFLECTION DURING TESTING. THE PERFORMANCE TEST SHALL BE COMPLETED BY INCREMENTALLY LOADING THE GROUND ANCHOR IN ACCORDANCE WITH THE FOLLOWING TABLE. ANCHOR LOADING ANCHOR UNLOADING LOAD HOLD TIME LOAD HOLD TIME ALIGNMENT LOAD 1 MINUTE 175% DESIGN LOAD UNTIL STABLE 25% DESIGN LOAD 5 MINUTES 150% DESIGN LOAD UNTIL STABLE 50% DESIGN LOAD 5 MINUTES 125% DESIGN LOAD UNTIL STABLE 75% DESIGN LOAD 5 MINUTES 100% DESIGN LOAD UNTIL STABLE 100% DESIGN LOAD 5 MINUTES 75% DESIGN LOAD UNTIL STABLE 125% DESIGN LOAD 5 MINUTES 50% DESIGN LOAD UNTIL STABLE 150% DESIGN LOAD 5 MINUTES 25% DESIGN LOAD UNTIL STABLE 175% DESIGN LOAD 5 MINUTES ALIGNMENT LOAD UNTIL STABLE 200% DESIGN LOAD 60 MINUTES THE ALIGNMENT LOAD (AL) SHOULD BE THE MINIMUM LOAD REQUIRED TO ALIGN THE TESTING APPARATUS & SHOULD NOT EXCEED 5% OF THE DESIGN LOAD. DIAL GAUGES SHOULD BE SET TO ZERO AFTER THE ALIGNMENT LOAD HAS BEEN APPLIED. A CREEP TEST SHALL BE PERFORMED DURING THE 200% DL HOLD TIME. ANCHOR MOVEMENT DURING THE CREEP TEST SHALL BE MEASURED & RECORDED AT 1, 2, 3, 5, 6, 10, 20, 30, 40, 50 & 60 MINUTES OF ELAPSED TIME FROM WHEN THE LOAD INCREMENT WAS APPLIED. ANCHOR PROOF TEST ALL OTHER ANCHORS SHALL BE PROOF TESTED TO 130% OF THE DESIGN LOAD BY INCREMENTALLY LOADING THE ANCHORS IN ACCORDANCE WITH THE FOLLOWING SCHEDULE. AT LOAD INCREMENTS OTHER THAN THE MAXIMUM TEST LOAD THE LOAD SHALL BE HELD LONG ENOUGH TO OBTAIN A STABLE READING. ANCHOR LOADING LOAD HOLD TIME 25% DESIGN LOAD UNTIL STABLE 50% DESIGN LOAD UNTIL STABLE 75% DESIGN LOAD UNTIL STABLE 100% DESIGN LOAD UNTIL STABLE 130% DESIGN LOAD 10 MINUTES THE ALIGNMENT LOAD (AL) SHOULD BE THE MINIMUM LOAD REQUIRED TO ALIGN THE TESTING APPARATUS & SHOULD NOT EXCEED 5% OF THE DESIGN LOAD. DIAL GAUGES SHOULD BE SET TO ZERO AFTER THE ALIGNMENT LOAD HAS BEEN APPLIED. THE MAXIMUM TEST LOAD SHALL BE HELD PER THE SCHEDULE. THE LOAD HOLD PERIOD SHALL START AS SOON AS THE MAXIMUM TEST LOAD IS APPLIED & THE ANCHOR MOVEMENT SHALL BE RECORDED AT 1, 2, 3, 5, 6, & 10 MINUTES. IF THE TOTAL ANCHOR MOVEMENT EXCEEDS 0.04 INCHES, THE MAXIMUM TEST LOAD SHALL BE HELD FOR AN ADDITIONAL 50 MINUTES & ANCHOR MOVEMENT SHALL BE RECORDED AT 20, 30, 50 & 60 MINUTES. IF ANCHOR FAILS IN CREEP, RETESTING WILL NOT BE ALLOWED. ACCEPTABLE ANCHOR TESTS A LOAD TESTED OR PROOF TESTED ANCHOR WITH A 10 MINUTE HOLD CREEP TEST IS CONSIDERED ACCEPTABLE WHEN: THE ANCHOR CARRIES THE MAXIMUM TEST LOAD WITH LESS THAN 0.04" OF MOVEMENT BETWEEN THE 1 & 10 MINUTE READINGS. A LOAD TEST OR PROOF TESTED ANCHOR WITH A 60 MINUTE HOLD CREEP TEST IS CONSIDERED ACCEPTABLE WHEN: THE ANCHOR CARRIES THE MAXIMUM TEST LOAD WITH LESS THAN 0.08" OF MOVEMENT PER LOG CYCLE OF THE TIME & THE CREEP RATE IS LINEAR OR DECREASING. IN ADDITION TO THE ABOVE, A TESTED ANCHOR SHALL NOT EXPERIENCE A PULLOUT FAILURE AT THE MAXIMUM TEST LOAD. A PULLOUT FAILURE IS DEFINED AS THE LOAD AT WHICH ATTEMPTS TO INCREASE THE TEST LOAD RESULT IN CONTINUED PULLOUT MOVEMENT OF THE TEST ANCHOR. ANCHORS THAT HAVE CREEP RATES GREATER THAN SPECIFIED CAN BE INCORPORATED IN THE FINISHED WORK AT A LOAD EQUAL TO 1/2 OF THE FAILURE LOAD. THE FAILURE LOAD IS THE MAXIMUM LOAD CARRIED BY THE ANCHOR AFTER THE LOAD HAS BEEN ALLOWED TO STABILIZE FOR 10 MINUTES. IF AN ANCHOR FAILS, THE CONTRACTOR SHALL BE RESPONSIBLE TO MODIFY THE DESIGN AND/OR THE INSTALLATION METHODS USED IN CONSTRUCTION. ANY MODIFICATIONS BY THE CONTRACTOR THAT REQUIRE CHANGES TO THE STRUCTURE SHALL HAVE PRIOR APPROVAL PER THE ENGINEER. PROCEDURE/CONSTRUCTION SEQUENCING: PRECONSTRUCTION MEETING CONTRACTOR SHALL CALL THE ENGINEERING INSPECTION LINE TO SET UP A PRECONSTRUCTION MEETING PRIOR TO ANY SITE WORK. CONCRETE PLACEMENT CONCRETE SHALL NOT BE ALLOWED TO FREE -FALL TO THE BOTTOM OF THE DRILLED HOLE, BUT SHALL EITHER BE TREMIED OR PUMPED INTO THE HOLE. LAGGING TIMBER LAGGING SHALL BE INSTALLED AT SHORING WALLS. VOIDS BETWEEN LAGGING AND SOIL SHALL BE BACKFILLED IMMEDIATELY AFTER LAGGING INSTALLATION. DRAINAGE BEHIND THE WALL MUST BE MAINTAINED. IT IS THE CONTRACTOR'S RESPONSIBILITY TO LIMIT THE AMOUNT OF EXPOSED SOIL WITHOUT LAGGING TO AVOID LOSS OF SOIL. NO MORE THAN 4 FEET OF EXCAVATION SHALL BE EXPOSED BEFORE INSTALLING LAGGING. EXCAVATIONS SHALL NOT REMAIN UNLAGGED OVERNIGHT. GENERAL STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL, CIVIL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS FOR COMPATIBILITY BEFORE PROCEEDING. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT BEFORE PROCEEDING. CONTRACTOR TO SEE ARCHITECTURAL, CIVIL, ELECTRICAL AND MECHANICAL DRAWINGS FOR SIZE AND LOCATION OF PIPE, VENT, DUCT AND OTHER OPENINGS AND DETAILS NOT SHOWN ON THESE DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR ERECTION STABILITY AND TEMPORARY SHORING AS NECESSARY UNTIL PERMANENT SUPPORT AND STIFFENING ARE INSTALLED. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL NOT SATISFY THIS REQUIREMENT. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF A SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND THE STRUCTURAL ENGINEER. Secial Insections reuired for thisro!ect: 8H PSI SUI AC PRESS 45 PASSIVE EARTH PRESSURE = 200 PCF OVER 2 PILE DIA INCLUDES A 1.5 FACTOR OF SAFETY EARTH PRESSURE DIAGRAM (NO TIEBACI SCALE: NTS 2 ANCHOR PER OPLAN 8H PSF SEISMICSURCHARGE(PERMANENT) 45 PCF ACTIVE PRESSURE65 ACTIVE CATCHMENT WALL PRESSURE100 PCF PCF AT REST II II PASSIVE EARTH II II PRESSURE = 200 PRESSURE PCF OVER 2 PILE DIA INCLUDES A 1.5 FACTOR OF SAFETY EARTH PRESSURE DIAGRAM (1 TIEBACK) SCALE: NTS i pp '1 p J 1 : ■ . NMI M ■ mom NMI M ■ mom NMI M ■ mom NMI IN ■ M ■ mom ■I■ ■ M ■ mom ■ MA ■ . The following documentation shall be available on ■ site for the building inspector: • SPCCIAL INSPCCTION ■ ■ ■ I I I I ■ 1 i OPERATION SOILS CONT PERIODIC REMARKS SHORWG X GEOTECH ENGINEER I XCAVATION & I -ILL X GEOTECH ENGINEER CONCRETE REINFORCING PLACEMENT x ANCHOR BOLTS x HOLDOWN PLACEMENT X CONCRETE TEST SPECIMENS x CONCRETE PLACEMENT x ADHESIVE ANCHORS x IF USED EXPANSION ANCHORS X IF USED EMBEDDED PLATES I x NOTE: ALL ITEMS MARKED WITH AN "X- SHALL BE INSPECTED IN ACCORDANCE WJTH IBC CHAPTER 17, SPECIAL IN P I P R F 1 A Y R T 5 ECT ON SHALL BE PE ME BY A OVALJ JED TESTING AGENCY DESIGNATED B THE OWNER, HE ARCHITECT, STRUCTURAL ENGINEER, AND BUILDING OFFICIAL SHALL BE FURNISHED WITH COPIES OF ALL RESULTS. ANY INSPECTION FAILING TO MEET THE PROTECT SPECIFICATIONS SHALL BE IMMEDIATELY BROUGH' TO THE ATTENTION OF THE DESJGN TEAM ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE APPROVED PLANS MUST BE ON JOB SITE ■ '■ 0 COE APPROVED ARCHITECTURAL PLAN SET ■ • ■ ■ 0 COE APPROVED STRUCTURAL PLAN SET ; ■ [:]COE REVIEWED CALCULATION PACKET ■ 1 ' ENERGY CREDIT WORKSHEET - SITE PLAN - ■ ■ 1 : � CIVIL PLAN - ■ Shoring Design plan sheets CITY OF EDMONDS BUILDING DEPARTMENT 2021 ■ 16 BLD2022-0527 PLAN REVIEW ACCEPTANCE FOR COMPLIANCE WITH THE APPLICABLE CONSTRUCTION CODES IDENTIFIED BELOW. ® BUILDING ® STRUCTURAL ❑ MECHANICAL ❑ PLUMBING ❑ ELECTRICAL ®ENERGY ® ACCESSIBILITY ❑ FIRE PLAN REVIEW ACCEPTANCE OF DOCUMENTS DOES NOT AUTHORIZE CONSTRUCTION TO PROCEED IN VIOLATION OF ANY FEDERAL, STATE, OR LOCAL REGULATIONS. BY:_41a� � ' )ATE:11/1512023 WEzi► uuHzi► uuut uunSULTANTS, INC. RECEIVED 6/1/2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT 4M ENGINEERING, 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 ��JTHy�'i OF WAShrl� �a V"A � ONAL �;4 J Q H H Z O_ cop D W N O U) oC W w 0 a 0�/ 28122 Y Q DESIGN: CCC DRAWN: ATD CHECK: MTM JOB NO: 19440.10 DATE: 03/28/22 N a p : 00 V Q Q Z 0 �--' Q 0 W 0 T_ 0 LJ (0 0 �j 0 W SHEET: V 0 Z V Z SH1m1 Id a z NE 1/4, SECTION 36, TOWNSHIP 27 NORTH, RANGE 3 EAST, W.M. vs "lol 0 / C I 00937900000700 h I I o° Q CITY BANK 3 4 352 I I 24 25 / � / 350 I I P34 I I I EX ° M ° H ° TOP 352.85 I I /� 23 / 348 I I 0000/ �,/ / / / / I INV 345.71 AB / � 19 / / / P33 J � 1 346 I I � / / / / SH3.1 344 I I 18 °P� / , `�' I ,, G� ��•V � // � P30 P31 3 342 /C? 27033600101500 00937900000600 /4 16 /// / / / /P 9 1 1 I ILo CITY BANK ,/ A15 / / , , / PeaK. o SH3.1 SH3.1 ,► / / I cv pG� SANDRA L. GREEN Lc j � / // // / 8 � / / I � 11 � / , 14 13 / �/ // // // / P27 / / OLYMPIC VIEW AND SEWER DISTRICT (3) PILES / / I SEWER EASEMENT 00, @ 8'0° (16-0") '�/ / EASEMENT PER PLAT 50' P.U.D. NO. 1 OF / / /���10 �// // // P23 // P24 /�---� �) SNOHOMISH COUNTY TRANSMISSION LINE //' / i/ /' p // /' // a // // 1 ` I EASEMENT PER A.F. 1�, /136 / I // / — / I 1 I I oG N0. 2027210 / .�///// ®�� _ 221 I �'"�50' PRIVATE � DRAINAGE EASEMENT II A7 ///' I / <1 / FOR LOTS 1 THROUGH 2 / / / / / / / �— P2o / 8 PER PLAT �♦ 19 Typ W 2\� °11 � / ��/ //// / / // �� /�� P17 / � _ J48 TIEBACKS SH4. // QF 41 r9a a,� / /�//// / // / _---346— % /�3 ° 4 / / r / / 44 a4 15 tio$,-344-- /2 a e // / / // S@q' /' //----342- ---------------------------- .,roan,• <.CuCii rh i <�iipU2y»TOP 338.45 r$ v7C INV • EX. l EASE NO. . 8 SAN. SEWER _ I / ` ss III 340 PROPOSED BUILDING FFE I � —P5 P4— — — I - P cJ TYP W/O TIEBACKS P3 a y (P1 a o as a / / a SHORING PLAN SCALE: 1" = 10' 10 0 5 10 PLAN REVIEW ACCEPTANCE FOR COMPLIANCE WITH THE APPLICABLE CONSTRUCTION CODES IDENTIFIED BELOW. ® BUILDING ® STRUCTURAL ❑ MECHANICAL ❑ PLUMBING ❑ ELECTRICAL ® ENERGY ® ACCESSIBILITY ❑ FIRE PLAN REVIEW ACCEPTANCE OF DOCUMENTS DOES NOT AUTHORIZE CONSTRUCTION TO PROCEED IN VIOLATION OF ANY FEDERAL, STATE, OR LOCAL REGULATIONS. BY: _/�a<���' )ATE:11 /15/2023 WEi i cuAJ I cuut cuwSULTANTS, INC. la 20 RECEIVED 6/l/2022 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT = (> 4m ENGINEERING, 250 4TH AVE. S., SUITE 200 EDMONDS, WASHINGTON 98020 PHONE (425) 778-8500 FAX (425) 778-5536 o 7w ON L W 28122 J z � O m N H U � U W Lu 0 d N N C) ---- m 0 Q DESIGN: CCC DRAWN: ATD CHECK: MTM JOB NO: 19440.10 DATE: 03/28/22 T— N O: a Il'— V Q 0 Q Z O W M Q La 0 C7 Z H Ir- O W ( 0 0) LLI SHEET: SH201