DEF SUB5 REVIEWED BLD2021-0088+FIRESTOPPING+2.15.2023_1.15.26_PM+3371360CATALYST°EFS°g5- a`°=°=,°°aa FIREST PP ITTAL CONSTRUCTION Job: Anthology of Edmonds 21200 72nd Ave W Edmonds WA, 98026 Submittal Package - Item # 1 Submittal Description Submittal includes: Firestopping Submittal EVIEWED BY OF EDMONDS Spec Section No: 07 84 00 Revision No: 2 Sent Date: 1 /3/23 Required Date: 1 /17/23 DEFERRED SUBMITTAL 2/15/2023 CITY OF EDMONDS DEVELOPMENT Submittal # 07 84 00 1.2 Action Action: A = Approved AN = Approved As Noted RR = Revise and Resubmit NOTE: Please strike out any rejected items and approve the balance as noted or submitted whenever possible Contractor Stamp Project Name CATALYST Anthology of Edmonds J❑ FOR APPROVAL ❑ FOR RECORD ❑ REVIEWED ❑ NOT REVIEWED BY Alex Dent DATE 1/3/23 SUBMITTAL# 078400 JOB# 21-18 Other/Comments: Architect Stamp Ankrom Moisan Architects, Inc. Contractor Submittal Review Project Name: Edmonds Senior Living Project Number: 184470 Submittal ID: 07 84 00-1.2 Firestop Received On: 01/03/23 Reviewed On: 01/05/23 Reviewed By: adrianal Action: pp No Exception Taken ❑ Revise and Resubmit ❑ Make Corrections Noted ❑ Submit Specified Item ❑ No Action Taken ❑ Rejected Review Is for the limited purpose of checking for the mnfonnan-with the information given antlthe design concept expressed In the Contract nocumenb, Reviewisnotcond—dfar the purpose of determining the accuracy antl completeness of other details sucM1 as dimensions antl quantities, or for substantiating the instructions for installation the all th performance of equipment or systems, of which remain responsibility of the Contractor p required by the --t, l no,, u—s. The Ar.11y rs review sAb not ,y b.Ne approval of safety precautions or, unless specifically stated by the Architect, of any construction means, methods, tecM1niques, sequences th procedures. p—bt. itacl's w shall not indicate approval of anassembly of ringt[M1eitemisa component. Corrections or comments made on shop drawings during this review do not relieve the Gontmcbr from wmpliance with the requirements of the plans antl specifications. _ = Specified = Technologies STI® Inc. January 3, 2023 Mr. John Duggan P: (206)793-6852 E.john@baffiertechnologiesinc.com Subject: UL Listed Mineral Wool in STI UL Systems Project: Anthology at Edmonds Contractor: Catalyst Construction Dear Mr. Duggan: 210 Evans Way Somerville, NJ 08876 USA Phone: (908) 526-8000 Fax: (908) 231-8415 Toll Free: (800) 992-1180 Email:techserv@stifirestop.com Website: www.stifirestop.com DC00323001 The question has been raised as to whether mineral wool batt insulation from any manufacturer could be used in STI's UL systems C-AJ-0014, W-L-0016, W-L-0035, C-AJ-1353, C-AJ-3154, W- L-3210, C-AJ-5087, C-AJ-8113, W-L-8003, W-L-8026, HW-D-0156 Please be advised that any UL Listed mineral wool batt insulation that meets the minimum requirements as specified in the above UL systems may be used. Such requirements include material type, physical properties, installation depth etc. Please reference the UL Fire Resistance Directory for specific system requirements. We trust this information will prove helpful. Should further questions develop, please do not hesitate to contact me. Sincerely, /L Cq, c .ror Clay Hensley (Ext. 1092) Fire Protection Engineer Specified Technologies Inc. Project Anthology of Edmonds Senior Living Date 11 /29/2022 Project Address 21200 72nd Avenue West Edmonds, Washington 98026 United States Submitted By Barrier Technologies Inc. - John Duggan Submitter Email John _ barriertechnologiesinc.com Submitter Phone 2067936852 Submitter Address 13003 55th Drive Northeast Marysville, Washington 98271 United States SPECIFIED TECHNOLOGIES INC. • SOMERVILLE, NJ 08876 USA • T: +1-908-526-8000 • F: +1-908-526-9623 • WWW.STIFIRESTOP.COM Table of Contents Systems 1 CAJO014 Max 8" diam. blank opening. Caulk and Backing. 3 Hr. 2 CAJO100 Max 8" diam. opening. Pillows from above or below or one side of wall. Pillows. 3 CAJO135 Max 4" (102 mm) diam. blank opening. Steel Sleeve. Intumescent FP Firestop Plug. 3 Hr. 4 WL0016 Max 4" Blank Opening. Steel Sleeve. 5 WL0034 Max 2" diam opening. Caulk and Walk. 6 WL0035 Max 3" diam opening. 7 CAJ1080 Max 30" Steel or Iron pipe, max 6" Copper pipe or tube, max 6" conduit, or max 4" EMT. Caulk Only. 8 CAJ 1353 Max 12" steel or iron pipe, max 4" copper pipe or tube, max 2" flexible steel pipe, max 6" conduit, max 4" EMT or flexible Steel conduit. Caulk only or caulk & backing options. 9 FC1074 Max. 4" steel, iron, or copper pipe, copper tube, max 2" flexible pipe, conduit, EMT, flexible conduit. Optional chase wall. Caulk only. 10 WL1042 Max 4" steel, iron, or copper pipe, copper tube, conduit, or EMT. Angle pipe option. Caulk only. 11 WL1049 Max 36" steel or iron pipe, 6" copper pipe/tube, 6" conduit, 4" EMT, or 1" flexible conduit. Angle pipe option. Sheet steel sleeve option. Point contact. Caulk only. 12 FC2032 Chase Wall Optional. Max. 2" PVC, CPVC, ABS (DWV or closed), PEX, RNC, ENT, 1" PB or PEX-AL-PEX. Caulk only. 13 FC2038 other Chase Wall. Max. 3" PVC or ABS pipe (DWV or closed), CPVC (closed), or RNC. Wrap Strip tuck in. Ipex. 14 FC2102 Chase wall. Max 3" PVC or ABS (DWV or closed), CPVC (closed), RNC or max 2" ENT. Caulk only. Ipex.¶¶ 15 FC2157 Chase Wall. Max 3" PVC or ABS (DWV or closed) or max 3" CPVC (closed). Caulk and walk. Optional branch pipe. 16 FC2319 Chase Wall. Multiple 1" PEX (closed) or 2" ENT. Caulk only. 17 FC2320 Shower or tub drain (1-1/2" PVC or ABS) with gypsum board or plywood patch. Caulk only. 1s FC2321 Chase Wall Optional. Max. 4" PVC, CPVC or ABS with max 4" PVC, CPVC or ABS sanitary tee and branch pipe. Wrap Strip or Factory Collar. 1g FC2322 Water closet with 4" ABS or PVC drain pipe with corresponding water closet flange. Caulk only. 20 WL2048 Max. 3" PVC, CPVC, ABS, or 2" FRPP (DWV or closed), 2" PVDF or 1" PP (closed), or 3" RNC. Wrap Strip Tuck -in. Optional sleeve. 21 WL2059 Max 4" PVC, CPVC, FRPP, ABS, PVDF or FRP DWV or closed) or RNC or HDPE. Wrap Strip Collar or Factory Collar. 22 WL2100 Max. 2" PVC, CPVC, 1-1/2" ABS (DWV or closed), 1" PB or PEX (closed). Caulk only. 23 WL2216 Plastic pipe coupling for max. 4" PVC, CPVC, or ABS pipe (DWV or closed) or RNC. Wrap Strip Collar. 24 WL2237 Max. 4" PVC, CPVC, or ABS pipe (DWV or closed) or RNC. Factory Collar. 25 WL2241 Max 2" PVC, CPVC pipe, max 1-1/2" ABS (vented or closed), max 1" PEX, max 3" PVC or CPVC pipe (closed). Caulk only. 26 WL2242 Multiple max 1" PVC, CPVC, PEX (closed), RNC or ENT. Caulk only. 27 WL2334 Angled Plastic Pipe. Max. 4" PVC, CPVC, or ABS (DWV or closed) or RNC. Wrap Strip Tuck -In and Steel Sleeve. 2s WL2493 RTC Factory Collar for 3" & 4" Plastic pipe coupling. PVC, CPVC, or ABS pipe (DWV or closed) or RNC. RTC Collar. 2s WL2496 Max 4" PVC, CPVC or ABS pipe or RNC. Eccentric Wrap Strip Collar. 30 WL2506 Max 4" PVC, CPVC, ABS (DWV or closed), RNC or 2" ENT. Metallic Sleeve. Wrap Strip Tuck -in. 31 WL2508 Max 2" PVC, CPVC, max 1-1/2" ABS, max 1" PEX, max 2" RNC or ENT. Angle pipe option. Sleeve. Caulk only. 32 WL2552 Max 3" PVC or ABS pipe with clean -out tee. Caulk only or putty. 33 CAJ3154 Electrical, Telephone or Data Cables (45% fill). Metallic or nonmetallic sleeve. Extended sleeve. Annular space between sleeve and opening. 2-1/2" concrete. Caulk or putty and backing material. 2, 3, 4 Hr. 34 FA3021 Telephone or Data Cables, max 1-1/2" OFR (max 100% visual fill). EZ-Path Kick -In Plate. Up to 2 Hr T Rating. 2, 3, and 4 Hr F Rating. 35 FA3026 Electrical, Telephone or Data Cables (max 100% visual fill). Steel sleeve. Conduit attachment plate. EZ Path. 36 FA3054 Electrical, Telephone or Data Cables (max 100% visual fill). 2-1/2" Concrete. EZ Path Series 44, 44+. 2, 3 & 4 Hr. 37 FC3010 Electrical, Telephone or Data Cables, Armored Cables or Metal Clad Cables (45% fill). Optional chase wall. Caulk only. 38 FC3103 Electrical, Telephone or Data Cables (max 100% visual fill). EZ Path 33 Series & Extension Module. Max three devices. 39 WL3036 Electrical, Telephone or Data Cables, Armored Cables or Metal Clad Cables (max 45% fill). Caulk only. 40 WL3169 Electrical, Telephone or Data Cables, Armored Cables or Metal Clad Cables (4-1/2" bundle). Caulk only. 41 WL3171 Single Electrical, Telephone or Data Cable, Armored Cable or Metal Clad Cable. Caulk only. 42 WL3210 Electrical, Telephone or Data Cables, Armored Cables, Metal Clad Cables or max 3/4" diam Copper Ground Wire (48% fill). Extended metallic sleeve. Caulk Only and Caulk & Backing Material. 43 WL3377 Electrical, Telephone or Data Cables (max 100% visual fill). EZ Path (Series 22, 33, 44, 44+). 1, 2, 3, & 4 Hr. 44 CLIV Electrical Boxes 45 CAJ5087 Max. 24" steel or iron pipe or 6" copper pipe/tube with max. 2" thick fiberglass or mineral fiber. Optional steel sleeve. Caulk & Backing. 46 FC5043 Max 4" steel or Iron pipe or 4" copper pipe ortubing with max 1-1/2" thick fiberglass. max 1" thick mineral wool or max 1" thick AB/PVC insulation. Caulk only. 47 WL5298 Max. 6" steel or iron pipe or 4" copper pipe/tube with max. 2" thick fiberglass or mineral fiber insulation. Caulk only. 48 WL5054 Max. 4" steel, iron, or copper pipe or copper tube with 3/4" or 1" thick AB/PVC. Caulk only. 49 WL5121 Max. 6" steel or iron pipe, 4" copper pipe/tube with max 2" thick fiberglass or mineral fiber. Caulk only. 5o FC7014 Chase wall optional. Max. 10" round steel duct. Caulk only. 51 FC7023 Max 64 sq in square or rectangular HVAC duct. Caulk only. 52 WL7019 Max. 10" (254mm) diam Steel Duct. Allows for wood stud wall option. Caulk only. 53 WL7025 Max. 100" x 100" (2.54 x 2.54 m)Steel Duct. Steel retaining angles. Caulk only. 54 WL7026 Max. 24" (610mm) diam Steel Duct. Caulk only. 55 WL7029 Max. 24" x 24" (610 x 610mm)Steel Duct. No retaining angles. Caulk only. 56 WL7136 Metallic strut, cable or rod service support. Caulk only. 57 WL7193 Tub and Shower Valve. Caulk only. 58 CAJ8093 Multiple metal pipes or conduits with optional pipe insulation, plastic pipes or conduits, steel ducts, busways, cables and cable trays. SpecSeal T Collar. 6 ft x 3 ft opening. Pillows. 59 CAJ8113 Multiple metal pipes or conduits with optional pipe insulation, plastic pipes or conduits, steel ducts, busways, cable trays, AC Line Sets. SpecSeal. 1024 sq in. opening. Caulk & Backing. 60 CAJ8114 Multiple metal/non-metallic conduits, cable trays, cables, or busways. SpecSeal T Collar. 1920 sq. in. opening. Mortar. 61 FC8021 Optional chase wall. Multiple AC Line Sets with 3/4" metal pipes, 1" AB/PVC, 1-1/4" PVC line, and thermostat wires. Caulk only. 62 FC8029 Optional chase wall. Rectangular hole. Multiple metal pipes/conduits, plastic pipes/conduits, and/or cables. Caulk only. 63 WL8003 Multiple max 3" steel, 2" iron or copper, 3" conduit/EMT, 2" PVC (closed). Optional 1" fiberglass. Cables. Caulk & Backing. Rectangular hole. AC Line Set with 1" metal pipe, 3/4" AB/PVC, and thermostat wire. Caulk only. 65 WL8026 Multiple bare or insulated (1" fiberglass, 2" MW, 3/4" AB/PVC, 3" cellular glass or calcium silicate) metal pipes, PVC/CPVC/RNC/ENT, OFR, 4" cable bundle, cable tray, busway, A/C Lineset, Duct. SpecSeal T Collar. 7 sq. ft. opening. Caulk & Backing. 66 WL8027 Rectangular hole. Multiple AC Line Sets with 1" metal pipe, 3/4" AB/PVC, and thermostat wires. Caulk only. 67 WL8028 Multiple AC Line Sets with 3/4" metal pipes, 1/2" fiberglass or 5/8" AB/PVC, 1-1/4" PVC, and thermostat wires. Wrap Strip Tuck -in. 68 BWS0020 Max 1/2" joint. Shaft Wall. Finished side only. 69 BWS0003 Max 3/4" joint. Caulk only. 7o HWD0041 Concrete or block wall to concrete slab. Max 1" joint. Caulk only. 3 HR. 71 HWS0043 Gypsum wall to concrete slab. Max 3/4" joint. 1 & 2 HR. Allows point contact. 72 HWD0079 Gypsum wall to concrete slab. Max 3/4" joint. Optional bond breaker tape. Optional sound isolation clips. 1 & 2 HR. Caulk only. M:17i Bill I-V Concrete or block wall to concrete slab. Max 2" joint. 4 HR. Caulk & Backing. 74 HWD0194 Gypsum shaft wall to concrete slab. Max 3/4" joint. Caulk only. Optional bond breaker tape. 1 & 2 HR. 75 HWD0780 Concrete or block wall to concrete slab. Max 1" joint. 2 HR. Caulk only. 76 WWD0004 Concrete or block wall to concrete or block wall. Max 1"joint. Caulk only. 3 HR. 77 WWS0052 Gypsum wall to concrete or block wall. Max 1"joint. 1, 2, 3, & 4 Hr. Caulk only. Product Data Sheets 1 ES Elastomeric Sealant 2 LCI Intumescent Sealant 3 WF Caulk 4 EZ-Path 22 5 EZ-Path 33 6 EZ-Path 44+ 7 EZ-Path Retrofit Device s LCC Collar s RTC Collar 10 SSC Collar 11 BLU2 Wrap Strip 12 RED Wrap Strip 13 SSB Pillows 14 SSP Putty Pads 15 Intumescent Firestop Plug 16 Roxul-Safe Safety Data Sheets 1 ES Elastomeric Sealant 2 LCI Intumescent Sealant 3 WF Caulk 4 EZ-Path 22 5 EZ-Path 33 6 EZ-Path 44+ 7 EZ-Path Retrofit Device s LCC Collar s RTC Collar 10 SSC Collar 11 BLU2 Wrap Strip 12 RED Wrap Strip 13 SSB Pillows 14 SSP Putty Pads 15 Intumescent Firestop Plug 16 Roxul-Safe Approval Information LEED 1 General LEED Letter v4 User Upload Documents 1 AS200 GREENGUARD Gold Certification 228368-420 (1).pdf 2 Dottie PDS.pdf 3 Dottie SDS.pdf 4 ES GREENGUARD Gold Certification 228584-420 (1).pdf 5 John Duggan - FIT Level 2 Exam - Completion Certificate (2020).pdf 6 LCI GREENGUARD Gold Certification 228370-420.pdf 7 STI-Warranty-Information.pdf s WF300 GREENGUARD Gold Certification 228583-420.pdf Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) 0 P. System No. C-AJ-0014 F Rating - 3 Hr. T Rating - 2 Hr. .............. .... ................ ......................... a ................... . ............:.:.... l l l l l l l l l l l l l l l .. .,--.. .� 1l1111111111111 �...� � � �..� � � �..� � � a� I A Section A -A 1 1. Floor or Wall Assembly -Min 4-1/2 in. thick lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 8 in. See Concrete Block (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Firestop System - The firestop system shall consist of the following: A. Packing Material - Min 1-1/2 in. thickness of min 6 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Sealant - Min 1 in. thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Reproduced 10nWaomervlle, NJ 08876 courtesy ounderwiteraborno L S 1 I ® Created or Revised: January 23, 2014 ® C-AJ-0014 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 1 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) MW System No. C-AJ-0100 F Rating - 2 Hr T Rating - 1-1/2 Hr rA Section A -A 1. Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or normal weight (100 to 150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 8 in See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers 2. Fill, Void and Cavity Material* - Pillows - Pillows tightly packed into the opening to a min compression of 30% and installed in accordance with manufacturer's instructions. Pillows to be installed vertically within opening in floor and horizontally within opening in wall. Pillows to be installed centered within floor or wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Pillows * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I Created or Revised: May 8, 2003 I CAJ0100 o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Webs itemww.stifirestop.com PAGE 1 OF 1 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. C-A►J-0135 F Rating - 3 Hr T Ratings - 0 and 1-1/4 Hr (See Item 2) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft 1. Floor or Wall Assembly -Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 4 in. (102 mm). See Concrete Blocks (CAZT) category in the Fire Resistance Directory for the names of manufacturers. 2. Steel Sleeve - Nom 2 or 4 in. (51 or 102 mm) diam Schedule 5 (or heavier) steel sleeve or nom 2 or 4 in. (51 or 102 mm) diam rigid steel conduit or electrical metallic tubing. Sleeve to be cast or grouted into floor or wall flush with floor or wall surfaces, or may extend up to 2 in. (51 mm) beyond the top surface of the floor or both wall surfaces. When sleeve extends beyond floor or wall surface, the T Rating is 0 hr. 3. Firestop System - The firestop system shall consist of the following: A. Fill, Void or Cavity Materials* - Plug - Nom 2 in. (51 mm) or 4 in. (102 mm) diam plug firmly installed within the sleeve on the top side of the floor or on each side of wall such that the outer circumference of the dome -shaped plugs is recessed '/2 in. (13 mm) from top end of sleeve in floors, or from both ends of sleeve in walls. SPECIFIED TECHNOLOGIES INC - SpecSeal Series FP Firestop Plug B. Fill, Void or Cavity Material* - Putty - Nom'/z in. (13 mm) diam bead of putty applied around periphery of the opening at the plug/sleeve interface. SPECIFIED TECHNOLOGIES INC - SpecSeal Putty C. Fill, Void or Cavity Material* -(Optional) -Sealant or Putty - Nom'/2 in. (13 mm) diam bead of putty may applied around periphery of opening at interface of sleeve with wall or floor surfaces. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, Pensil 300 Sealant, SpecSeal SIL300 Silicone Firestop Sealant, or SpecSeal Putty * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies odpun . o10U Evans niterWay Somerville, NJ 08876 Created or Revised: April 8, 2010 S T l a0 C-5 1 (800)992-1180 • (908)526-8000 •FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Webs PAGGEE 1 1 OF 1 Classified by Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-0016 ❑■�, ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 1 and 2 Hr (See Item 1) L Rating At Ambient - Less Than 1 CFM/sq ft FH Ratings - 1 and 2 Hr (See Item 1) L Rating At 400 F - Less Than 1 CFM/sq ft FTH Ratings - 1 and 2 Hr (See Item 1) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft A 2 3 rrrrrr r.-Y. rrrrrr r r r r r r r r r r r r r r r r r r rrr.--.rr r r r r r r 3B 3B 2 A 1A 1B Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400'Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 4 in. (102 mm). The hourly F and T Ratings of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Steel Sleeve - Cylindrical steel sleeve fabricated from min 0.013 in. (0.33 mm) thick sheet metal. Coil sheet metal to a diam less than circular cutouts in gypsum board. Insert coil through both sides of opening and allow sheet metal to uncoil against circular cutouts. Min 2 in. (51 mm) lap along longitudinal joint required. Sleeve may be installed flush with wall surfaces or may project up to 1 in. (25 mm) beyond each surface of the wall assembly. 2A. Alternate Steel Sleeve - As an alternate to Item 2, nom 4 in. (102 mm) diam (or smaller) rigid steel conduit or EMT friction fitted into wall opening. Sleeve may be installed flush with wall surfaces or may project up to 1 in. (25 mm) beyond each surface of the wall assembly. 3. Firestop System - The firestop system consists of the following items: A. Packing Material - Mineral wool batt insulation, nom 4 pcf (64 kg/m3), tightly -packed to full depth of sleeve less the required thickness of sealant. Mineral wool recessed from each side of wall as required to allow for sealant thickness. B. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) thickness of fill material applied within opening, flush with both ends of steel sleeve. Min 3/8 in. (10 mm) diam bead of sealant applied at the metal sleeve/gypsum board interface on both sides of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: Januany 23, 2014 T I ® 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com GE 11 OF61 Classified by Underwiters Laboratories, Inc. System No. W-L-0034 to ASTM/UL1479 (ASTM E814) F Ratings - 1 and 2 Hr (See Item 1) a . T Ratings - 1/2 and 1 Hr (See Item 1) � L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft LA Section A -A 1. Wall Assembly - The 1 or 2 h fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 2 in. (51 mm). The hourly F Rating of the firestop system is equal to the hourly assembly rating of the wall assembly in which it is installed. When installed in a 1 hr fire rated wall, the T Rating is 1/2 hr. When installed in a 2 hr fire rated wall, the T Rating is 1 hr. 1A. Wall Assembly - (Not Shown) - As an option to Item 1, the 1 or 2 hr fire rated gypsum board/steel stud shaft wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features: A. Steel Studs - "C-H" or "C-T shaped studs, min 2-1/2 in. (64 mm) wide by 1-1/2 in. (38 mm) deep, fabricated from min No. 25 gauge galv steel, spaced max 24 in. (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max diam of opening is 2 in. (51 mm). C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum board. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 2 in. (51 mm). The hourly F Rating of the firestop system is equal to the hourly assembly rating of the shaft wall assembly in which it is installed. When installed in a 1 hr fire rated shaft wall, the T Rating is 1/2 hr. When installed in a 2 hr fire rated shaft wall, the T Rating is 1 hr. 2. Fill, Void or Cavity Material* - Caulk or Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with each surface of the wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, LCI Sealant, LC150 Sealant, or SIL300 Silicone Firestop Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: February 17, 2010 1 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com GE 1 OF Classified by ❑� . ❑� Underwiters Laboratories, Inc. System No. W-L-0035 to ASTM/UL1479 (ASTM E814) F Ratings - 1 and 2 Hr (See Item 1) a T Ratings - 1 and 2 Hr (See Item 1) or L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft Section A -A 1. Wall Assembly - The 1 or 2 h fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 3 in. (76 mm). The hourly F and T Ratings of the firestop system are equal to the hourly assembly rating of the wall assembly in which it is installed. 1 A. Wall Assembly - (Not Shown) - As an option to Item 1, the 1 or 2 hr fire rated gypsum board/steel stud shaft wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features: A. Steel Studs - "C-H" or "C-T" shaped studs, min 2-1/2 in. (64 mm) wide by 1-1/2 in. (38 mm) deep, fabricated from min No. 25 gauge galv steel, spaced max 24 in. (610 mm) OC. B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max diam of opening is 3 in. (76 mm). C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum board. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 3 in. (76 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Packing Material - Mineral wool batt insulation, nom 4 pcf (64 kg/m3) density, compressed and tightly -packed into wall cavity and opening as a permanent form. The packing material thickness shall be 1/2 in. (13 mm) thicker than the depth of the stud cavity to ensure a compression -fit. The packing material is installed within the wall cavity by cutting a plug approximately 1 in. (25 mm) larger than the diameter of the opening in the gypsum board layers, compressing the edges of the plug as it is slid through the first opening, and positioning the mineral wool plug such that the edges of the plug extend approx 1/2 in. (13 mm) beyond the periphery of the opening. In 2 hr walls, additional 5/8 in. (16 mm) depth of mineral wool shall be packed tightly into the opening within the gypsum board. Packing material recessed from wall surface as required to accommodate required thickness of sealant (Item 3). 3. Fill, Void or Cavity Material* - Caulk or Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with each surface of the wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, LCI Sealant, LC150 Sealant, or SIL300 Silicone Firestop Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: Januany 23, 2014 @ W-L-003 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com GE 1 OF5 Classified b �. Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. C-AJ-1080 ,f. ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 3 Hr F Rating - 3 Hr T Rating - 0 Hr FT Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/sq ft FH Rating - 3 Hr L Rating At 400 F - Less Than 1 CFM/sq ft FTH Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft A 2 3B 3B 1 a a d a. a d . d 4 2 A Section A -A 1. Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 32 in. See Concrete Block (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Through Penetrants - One metallic pipe, conduit or tubing to be centered within the firestop system. The annular space shall range from min 0 in. (point contact) to max 2 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 30 in. diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 30 in. diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 4 in. diam (or smaller) electrical metallic tubing or nom 6 in. diam (or smaller) rigid galv steel conduit. D. Copper Tubing - Nom 6 in. diam (or smaller) Type M (or heavier) copper tubing. E. Copper Pipe - Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe. 3. Firestop System - The firestop system shall consist of the following: A. Packing Material - (Optional, Not Shown) - Mineral wool batt insulation, polyethylene backer rod or glass fiber batt insulation friction fitted into annular space. Packing material to be recessed from top surface of floor or both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Caulk - Min 1/2 in. thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. At point contact location, apply min 1/4 in. diam bead of sealant at the pipe/concrete interface on the top surface of the floor or both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. (such Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I Created or Revised: January 23, 2014 C-AJ-1080 I o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Webs ite:www.stifirestop.com PAGE 1 OF 1 Classified by n#fFM Underwiters Laboratories, Inc. �R_'�� ,_ to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. C-AJ-1353 �, ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 3 Hr F Rating - 3 Hr T Rating - 0 Hr FT Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/sq ft FH Rating - 3 Hr L Rating At 400 F - Less Than 1 CFM/sq ft FTH Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft A 3 2 4A 4B 2 ................. llll D v llll D llll v 4B 3 4 A Section A -A 1. Floor or Wall Assembly - Lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete floor or wall. Min thickness of concrete is shown in table in Item 4B. Floor may also be constructed of any min 6 in. (152 mm) thick hollow -core Precast Concrete Units*. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 14 in. (356 mm). Max diam of opening in floors constructed of hollow -core is 7 in. (178 mm). See Concrete Blocks (CAZT) or Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 2. Steel Sleeve - (Optional) - Nom 14 in. (356 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe or No. 26 ga (0.022 in. or 0.56 mm thick) sheet steel sleeve with square anchor flange spot welded to the sleeve at approx mid -height. Sleeve cast or grouted in place flush with floor or wall surfaces. Steel pipe sleeve may project a max of 2 in. (51 mm) beyond the floor or wall surfaces. 3. Through Penetrant - One metallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop system. The annular space between the pipe, conduit or tube and the periphery of the opening shall be min 0 in. ( point contact). The max annular space is 1 in. or 2 in. (25 or 51 mm) as shown in the table in Item 413 . Pipe, conduit or tube to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of metallic pipes, conduits and tubes may be used: A. Steel Pipe - Nom 12 in. (305 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or nom 4 in. (102 mm) diam (or smaller) flexible steel conduit. D. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. E. Copper Tube - Nom 4 in. (102 mm) diam (or smaller) Regular L (or heavier) copper tube. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 C-AJ STI® (800)992-1180 • (908)526-8000 *FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifrestop.coPAGElOF 2 3A. Through Penetrating Product* - Flexible Metal Piping - As an alternate to Item 3, one nom 2 in. (51 mm) diam (or smaller) flexible steel pipe (with or without plastic jacketing) to be installed either concentrically or eccentrically within the firestop system. The annular space between the pipe, conduit or tube and the periphery of the opening shall be min 0 in. ( 0 mm or point contact). The max annular space is 1 or 2 in. (25 or 51 mm) as shown in the table in Item 4B. Pipe to be rigidly supported on both sides of the floor or wall assembly. .61TdXr7_\����1►[61 GASTITE, DIV OF TITEFLEX WARD MFG L L C 4. Firestop System - The firestop system shall consist of the following: A. Packing Material - When required as shown in the table in Item 4B, min 4 pcf (64 kg/m3) mineral wool batt insulation compressed and tightly packed to min 2-1/4 in. (57 mm) thickness. Packing material recessed from top surface of floor or both surfaces of wall as required to accommodate fill material (Item 413). When packing material is shown as being optional, mineral wool or glass fiber insulation or polyethylene foam backer rod may be used as a permanent form to facilitate installation of the fill material. In floors constructed of hollow -core precast concrete units, packing material to be recessed from both top and bottom surfaces of floor, as required to accommodate fill material (Item 4B). When steel sleeve projects from top of floor or from both sides of wall, the thickness of mineral wool batt packing material should be increased by an amount equal to the distance that the sleeve extends past the floor or wall surface. B. Fill, Void or Cavity Material* - Sealant - Fill material applied within annulus, flush with top surface of floor assembly or top edge of steel sleeve. In walls and in floors constructed from hollow core precast concrete units, fill material applied symmetrically on both sides of assembly flush with wall/floor surfaces or both ends of steel sleeve. At point contact location, apply min 1/4 in. (6 mm) diam bead of fill material at pipe/concrete interface or pipe/steel sleeve interface on top surface of floor or both surfaces of wall or precast concrete units. The fill material thickness shall be as specified in the following table: Min Concrete Steel Max Packing Min Fill Thickness SleeveMaterial Annular Space, Material Thickness F Rating in. mm in. mm in. mm 2-1/2 (64) Optional 2 (51) Required 1/4 (6) 3 hr 4-1/2 (114) Optional 1 (25) Optional 1/2 (13) 2 hr SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 us S T I o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mai1:techserv@stifirestop.com • Webs ite:www.stifirestop.com PAGE 2 AGE2 353 OF 2 Classified by Underwriters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-C-1074 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 Hr and 2 Hr (See Item 1) F Ratings - 1 Hr and 2 Hr (See Item 1) T Ratings - 1/4, 1/2 and 1 Hr (See Item 2) FT Ratings - 1/4, 1/2 and 1 Hr (See Item 2) L Rating At Ambient - Less Than 1 CFM/sq ft FH Ratings - 1 Hr and 2 Hr (See Item 1) L Rating At 400 F - Less Than 1 CFM/sq ft FTH Ratings - 1/4, 1/2 and 1 Hr (See Item 2) L Rating At Ambient - Less Than 5.1 L/s/m2 L Rating At 400 F - Less Than 5.1 L/s/m2 Section A -A Floor -- Ceiling Assembly -- The 1 hr fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Designs in the UL Fire Resistance Directory. The 2 hr fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in Design Nos. L505, L511 or L536 in the UL Fire Resistance Directory. The F and FH Ratings of the firestop system are equal to the fire rating of the floor -ceiling assembly. The general construction features of the floor assembly are summarized below: A. Flooring System -- Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of opening to be max 1 in. (25 mm) larger than diam of pipe. As an alternate, the opening may be square -cut with a max dimension 1 in. (25 mm) greater than the diam of the pipe. B. Wood Joists -- Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* -- Thickness, type, number of layers and fasteners as required in the individual Floor -Ceiling Design. Diam of opening to be max 1 in. (25 mm) greater than diam of pipe. D. Furring Channel -- (Not Shown) -- In 2 hr fire -rated assemblies, resilient galv steel furring channels installed perpendicular to wood joists between base and face layers of gypsum board (Item C). Furring channels spaced max 24 in. (610 mm) OC with additional short lengths of furring channel installed adjacent to and max 3 in. (76 mm) from two opposing sides of penetrant. 1A. Chase Wall -- (Optional, Not Shown) -- The through penetrant (Item 2) may be routed through a single, double or staggered wood stud/gypsum board chase wall. Depth of chase wall stud cavity to be min 1 in. (25 mm) greater than the diameter of the through penetrant (Item 2). The chase wall shall include the following construction features: Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: May 18, 2022 us S T I o 74 1 (800)992-1180 • (908)526-8000 •FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGEAGE 1 1 OF 2 A. Studs -- Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate -- Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening is to be max 1 in. (25 mm) larger than diam of pipe. As an alternate, the opening may be square - cut with a max dimension 1 in. (25 mm) greater than the diam of the pipe. Plates may be discontinuous over opening, terminating at two opposing edges of opening. Max length of discontinuity is 5-1/2 in. (140 mm). C. Top Plate -- The single or double top plate shall consist of two nom 2 by 4 in. (51 by 102 mm), or one or two nom 2 by 6 in. (51 by 152 mm), or one or two sets of parallel 2 by 4 in. (51 by 102 mm), lumber plates, tightly butted. Diam of opening is to be max 1 in. (25 mm) larger than diam of pipe. As an alternate, the opening may be square -cut with a max dimension 1 in. (25 mm) greater than the diam of the pipe. Plates may be discontinuous over opening, terminating at two opposing edges of opening. Max length of discontinuity is 5-1/2 in. (140 mm). D. Steel Plate -- When lumber plates are discontinuous, nom 1-1/2 in. (38 mm) wide No. 20 gauge (or heavier) galv steel plates shall be installed to connect discontinuous lumber plates and to provide a form for the fill material. Steel plates sized to lap 2 in. (51 mm) onto each discontinuous lumber plate and secured to lumber plates with steel screws or nails. E. Gypsum Board* -- Min 1./2 in. thick, classified or unclassified, gypsum board. 2. Through Penetrant -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the opening. Annular space to be min 0 in. (point contact) to max 1 in. (0 to 25 mm). Penetrant to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of metallic pipe, conduit or tubing may be used: A. Steel Pipe -- Nom 4 in. (102 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe -- Nom 4 in. (102 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit -- Nom 4 in. (102 mm) diam (or smaller) steel conduit, steel electrical metallic tubing or flexible steel conduit. D. Copper Pipe or Tube -- Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe or Type L (or heavier) copper tube. The T, FT and FTH Ratings are 1/4 hr when copper pipe or tube is used in 1 hr fire -rated assemblies. The T, FT and FTH Ratings are 1/2 hr when copper pipe or tube is used in 2 hr fire -rated assemblies. When steel pipe, iron pipe, steel conduit or flexible metal piping (Item 2A) is used, T, FT and FTH Ratings are 1 hr. 2A. Through Penetrating Product* -- Flexible Metal Piping -- As an alternate to Item 2, one nom 2 in. (51 mm) diam (or smaller) steel flexible metal pipe to be installed either concentrically or eccentrically within the firestop system. Annular space to be min 0 in. (point contact) to max 1 in. (0 to 25 mm). Penetrant to be rigidly supported on both sides of floor -ceiling assembly. OMEGA FLEX INC GASTITE, DIV OF TITEFLEX WARD MFG L L C 3. Fill, Void or Cavity Material* -- Sealant -- Min 3/4 in. (19 mm) thickness of fill material applied within the annulus, flush with the top surface of the floor or sole plate. Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with bottom surface of ceiling or top plate. Min 1/4 in. (6 mm) diam bead of fill material applied at point contact location on the top surface of floor or sole plate and at the penetrant/ceiling or top plate interface. SPECIFIED TECHNOLOGIES INC -- SpecSeal LCI Sealant or Type WF300 Firestop Caulk * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S 1T I ® Created or Revised: May 18, 2022 U F-C-1074 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. W-L-1042 F Ratings - 1 and 2 Hr (See Item 1) T Rating - 1/4 Hr Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Diam of opening to be 1/2 to 1 in. (13 to 25 mm) larger than outside diam of through penetrant (Item 2). Max diam of opening is 5 in. (128 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant - One metallic pipe, conduit or tubing installed concentrically or eccentrically within the firestop system. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or tube to be rigidly supported on both sides of wall assembly. The annular space between the pipe, conduit or tube and periphery of the opening shall be min 0 in. (point contact) to max 1/2 in. (0 to 13 mm). The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 4 in. (102 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or steel conduit. D. Copper Tubing - Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube. E. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. 3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. At the point contact location or when the annulus between the through penetrant and wall is 1/8 in. (3 mm) or less, min 1/2 in. (13 mm) diam bead of fill material applied at the through penetrant/gypsum board interface. SPECIFIED TECHNOLOGIES INC - Type WF300 Caulk * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: Januany 23, 2014 �° GE 1 OF1 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com Classified by [oil If. 10 Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-1049 i .L' ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Rating - 1 and 2 Hr (See Item 1) T Rating - 0 Hr FT Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/sq ft FH Rating - 1 and 2 Hr (See Item 1) L Rating At 400 F - Less Than 1 CFM/sq ft FTH Rating - 0 Hr L Rating at Ambient - Less Than 5.1 L/S/m2 L Rating at 204°C - Less Than 5.1 L/S/m2 1 1B A 3 3 2 2 A Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, V300, U400, V400 or W400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. When steel studs are used and the diam of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed between the vertical studs and screw -attached to the steel studs at each end. The framed opening in the wall shall be 4 to 6 in. (102 to 152 mm) wider and 4 to 6 in. (102 to 152 mm) higher than the diam of the penetrating item such that, when the penetrating item is installed in the opening, a 2 to 3 in. (51 to 76 mm) clearance is present between the penetrating item and the framing on all four sides. B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, V300, U400, V400 or W400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 38 in. (965 mm) for steel stud walls. Max diam of opening is 14-1/2 in. (368 mm) for wood stud walls. The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. 1A. Metallic Sleeve - (Optional, Not Shown) - Cylindrical sleeve fabricated from min 0.016 in. (0.41 mm) to max 0.105 in. (2.7 mm) thick sheet steel. Length of steel sleeve to be equal to the thickness of wall. Longitudinal seam of sleeve welded or overlapped min 1 in. (25 mm). The ends of the steel sleeve shall be flush or recessed max 1/4 in. (6 mm) from wall surfaces. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 �IL Reproduced courtesy of Underwriters Laboratories, Inc. us Created or Revised: May 28, 2021 W-L 1 S I® 1T (800)992-1180 • (908)526-8000 •FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Webs PAGE 1 OF 2 OF 2. Through Penetrant - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. The annular space between pipe, conduit or tubing and periphery of opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 36 in. (914 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 36 in. (914 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or nom 4 in. (102 mm) diam (or smaller) flexible steel conduit. D. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. 2A. Through Penetrating Product* - Flexible Metal Piping - As an alternate to Item 2, one nom 2 in. (51 mm) diam (or smaller) steel flexible metal pipe to be installed either concentrically or eccentrically within the firestop system. The annular space between the pipe and the periphery of the opening shall be min 0 in. (point contact) to max 2 in. (51 mm). Pipe to be rigidly supported on both sides of the wall assembly. OMEGA FLEX INC GASTITE, DIV OF TITEFLEX WARD MFG L L C Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall. At point contact location between through penetrant and gypsum board, a min 3/8 in. (10 mm) diam bead of fill material shall be applied at the gypsum board/through penetrant interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. �� S T I o Created or Revised: May 28, 2021 us I PACE 2 OF 2 (800)992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com Classified by &FRU Underwiters Laboratories, Inc. System No. F-C-2032 to ASTM/UL1479 (ASTM E814) F Rating - 1 Hr T Ratings - 0, 1/4, 3/4 and 1 Hr (See Item 2) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft Section A -A 1. Floor - Ceiling Assembly - The 1 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction details of the floor -ceiling assembly are summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of floor opening is 4 in. (102 mm). B. Wood Joists - Nom 2 by 10 in. (51 by 254 mm) lumber joists spaced 16 in. (406 mm) OC with nom 1 by 3 in. (25 by 76 mm) lumber bridging and with ends firestopped. As an alternate to lumber joists, nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Furring Channels - (Not Shown) - Resilient galv steel furring installed perpendicular to wood joists (Item 1 B) between gypsum board (Item 1 D) and wood joists as required in the individual Floor -Ceiling Design. D. Gypsum Board* - Nom 4 ft (1.2 m) wide by 5/8 in. (16 mm) thick as specified in the individual Floor -Ceiling Design. Gypsum board secured to wood joists or furring channels as specified in the individual Floor -Ceiling Design. Max diam of ceiling opening is 4 in. (102 mm). 1.1 Chase Wall - (Optional. Not Shown) - The through penetrant (Item No. 2) may be routed through a fire rated or non fire rated single, double or staggered wood stud/gypsum board chase wall. When fire rated the chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or double 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. C. Top Plate - The double top plate shall consist of two nom 2 by 4 in. (51 by 102 mm) or 2 by 6 in. (51 by 152 mm) or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max diam of opening is 4 in. (102 mm). D. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as specified in individual Wall and Partition Design. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 AEReproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 @ F-C-2032 T I ® 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 2 2. Through -Penetrants - One nonmetallic pipe, conduit or tubing to be installed within the firestop system. Diam of openings hole -sawed through flooring system and through gypsum board ceiling to be 1/4 to 1-5/8 in. (6 to 41 mm) larger than the outside diam of through -penetrant. Pipe, conduit or tubing to be rigidly supported on both sides of the floor -ceiling assembly. The following types and sizes of nonmetallic pipes, conduits or tubing may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. The T Rating for the firestop system when this penetrant is used is 1 hr except that when nom diam of pipe exceeds 1 in. (25 mm), the T Rating is 1/4 hr. B. Rigid Nonmetallic Conduit (RNC)+ - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70). The T Rating for the firestop system when this penetrant is used is 1 hr except that when nom diam of pipe exceeds 1 in. (25 mm), the T Rating is 1/4 hr. C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) SDR 17 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. The T Rating for the firestop system when this penetrant is used is 1 hr except that when nom diam of pipe exceeds 1 in. (25 mm), the T Rating is 1/4 hr. D. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. The T Rating for the firestop system when this penetrant is used is 0 hr. E. Polybutylene (PB) Pipe - Nom 1 in. (25 mm) diam (or smaller) SDR 11 PB pipe for use in closed (process or supply) piping systems. The T Rating for the firestop system when this penetrant is used is 1 hr. F. Cross Linked Polyethylene Aluminum -Cross Linked Polyethylene (PEX AL-PEX) Tubing - Nom 1 in. (25 mm) diam (or smaller) SDR 5 PEX-AL-PEX tubing for use in closed (process or supply) piping systems. The T Rating for the firestop system when this penetrant is used is 3/4 hr. G. Cross Linked Polyethylene (PEX) Tubing - Nom 2 in. (51 mm) diam (or smaller) SDR 9 PEX tubing for use in closed (process or supply) piping systems. The T Rating for the firestop system when this penetrant is used is 1 hr. H. Electrical Nonmetallic Tubing (ENT)+ - Nom 2 in. (51 mm) diam (or smaller) PVC tubing installed in accordance with Article 331 of the National Electrical Code (NFPA No. 70). The T Rating for the firestop system when this penetrant is used is 1 hr except that when nom diam of tube exceeds 1 in. (25 mm), the T Rating is 1/4 hr. I. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 80 CPVC pipe for use in closed (process or supply) piping systems. When 2A, 2B, 2C, 2E, 2F, 2G, 2H or 21 is used, the annular space shall be min 0 in. (point contact) to max 1-5/8 in. (41 mm). When 2D is used, the annular space shall be min 0 in. (point contact) to max 1 in. (25 mm) except that when nom pipe diam exceeds 1-1/2 in. (38 mm), the max annular space is 5/8 in. (16 mm). 3. Fill, Void or Cavity Material* - Sealant - Min 3/4 in. (19 mm) thickness of fill material applied within annulus on top surface of floor. Min 5/8 in. (16 mm) thickness of fill material applied within annulus on bottom surface of ceiling or lower top plate of chase wall assembly. Additional fill material to be installed such that a min 1/8 in. (3 mm) crown is formed around the through penetrant on bottom surface of ceiling or lower plate of chase wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, r SpecSeal LCI Sealant, or Type WF300 Firestop Caulk +Bearing the UL Listing Mark *Bearing the UL Classification Marking Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. T Created or Revised: January 23, 2014 32 S T I O PAGE 2oOF 2 (800)992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com Classified by Underwiters Laboratories, Inc. to CAN/ULC S115 stem No. F-C-2038 F Rating - 1 Hr FT Rating - 1 Hr FH Rating - 1 Hr FTH Rating - 1 Hr System tested with a pressure differential of 50 Pa between the exposed and the unexposed surfaces with the higher pressure on the exposed side. 1. Floor -Ceiling Assembly - The 1 hr fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Designs in the UL Fire Resistance Directory, as summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of opening to be 13 to 16 mm (1/2 to 5/8 in.) larger than outside diam of through penetrant. Max diam of opening is 102 mm (4 in.). B. Wood Joists - Nom 254 mm (10 in.) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Floor -Ceiling Design. Diam of opening to be 13 to 16 mm (1/2 to 5/8 in.) larger than outside diam of through penetrant. Max diam of opening is 102 mm (4 in.). 2. Chase Wall - The through penetrant (Item 2) shall be routed through a 1 hr fire rated single, double or staggered wood stud/gypsum board chase wall. Depth of chase wall stud cavity to be min 13 mm (1/2 in.) greater than diameter of opening cut in sole and top plates to accommodate the through penetrant (Item 2). The chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Nom 51 by 102 mm (2 by 4 in.), 51 by 152 mm (2 by 6 in.) or double nom 51 by 102 mm (2 by 4 in.) lumber studs. B. Sole Plate - (Not Shown)- Nom 51 by 102 mm (2 by 4 in.), 51 by 152 mm (2 by 6 in.) or parallel 51 by 102 mm (2 by 4 in.) lumber plates, tightly butted. Diam of opening to be 13 to 16 mm (1/2 to 5/8 in.) larger than outside diam of through penetrant. Max diam of opening is 102 mm (4 in.). C. Top Plate - The double top plate shall consist of two nom 51 by 102 mm (2 by 4 in.), two nom 51 by 152 mm (2 by 6 in.) or two sets of parallel 51 by 102 mm (2 by 4 in.) lumber plates, tightly butted. Diam of opening to be 13 to 16 mm (1/2 to 5/8 in.) larger than outside diam of through penetrant. Max diam of opening is 102 mm (4 in.). D. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as specified in the individual Wall and Partition Design. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: March 14, 2014 S T I o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE AGEF-C1 38 1 OF 2 3. Through Penetrant - One nonmetallic pipe or conduit to be centered within the opening. Annular space between the pipe or conduit and the periphery of the opening shall be 6 to 8 mm (1/4 to 5/16 in.). Penetrant to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of nonmetallic pipe or conduit may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 76 mm (3 in.) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 76 mm (3 in.) diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit (RNC)+ - Nom 76 mm (3 in.) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA 70). D. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 76 mm (3 in.) diam (or smaller) solid or cellular core Schedule 40 ABS pipe for use in closed (process or supply) piping systems or vented (drain, waste or vent) piping systems. E. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 76 mm (3 in.) drain (or smaller) SDR 11 CPVC for use in closed (process or supply) piping systems. IPEX INC - AquaRise 4. Fill, Void or Cavity Material* - Wrap Strip - One layer wrapped around pipe and secured with complete wrap of aluminum foil tape. Wrap strip layer slid into opening such that the bottom edge of the wrap strip protrudes 6 mm (1/4 in.) from the bottom surface of the chase wall top plate. SPECIFIED TECHNOLOGIES INC - SpecSeal BLU or BLU2 Wrap Strip 5. Fill, Void or Cavity Material* - Sealant - Min 19 mm (3/4 in.) thickness of fill material applied within the annulus, flush with the top surface of the floor or the chase wall sole plate. Min 16 mm (5/8 in.) thickness of fill material applied within the annulus around the wrap strip, flush with the bottom surface of the chase wall top plate. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant, SpecSeal 100, 101, 102, 105, 120 or 129 Sealant, or Type WF300 Firestop Caulk +Bearing the UL Listing Mark * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I. Created or Revised: March 14, 2014 I (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 03F Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. F-C-2102 F Rating - 1 Hr T Rating - 0 Hr 1. Floor -Ceiling Assembly - The 1 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction details of the floor -ceiling assembly are summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max dimension of round or square opening is 4-1/2 in. (114 mm). B. Wood Joists - Nom 2 by 10 in. (51 by 254 mm) lumber joists spaced 16 in. (406 mm) OC with nom 1 by 3 in. (25 by 76 mm) lumber bridging and with ends firestopped. As an alternate to lumber joists, nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required with ends firestopped. C. Furring Channels - (Not Shown) - Resilient galv steel furring installed perpendicular to wood joists (Item 1 B) between gypsum board (Item 1 D) and wood joists as required in the individual Floor -Ceiling Design. D. Gypsum Board* - Nom 4 ft (1.2 m) wide by 5/8 in. (16 mm) thick as specified in the individual Floor -Ceiling Design. Gypsum board secured to wood joists or furring channels as specified in the individual Floor -Ceiling Design. 2. Chase Wall - The through penetrant (Item 3) shall be routed through a 1 hr fire rated single, double or staggered wood stud/gypsum board chase wall. Depth of chase wall stud cavity to be min 1/2 in. (13 mm) greater than diam of opening cut in sole and top plates to accommodate the through penetrant (Item 2). The chase wall shall be constructed of the materials and in the manner specified in individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs . B. Sole Plate - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening is to be 1/2 in. (13 mm) to 1 in. (25 mm) larger than diam of pipe. As an alternate, the opening may be square -cut with a max dimension 1/2 in. (13 mm) to 1 in. (25 mm) greater than the diam of the pipe. Plates may be discontinuous over opening, terminating at two opposing edges of opening. Max length of discontinuity is 4-1/2 in. (114 mm). Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: March 14, 2014 @ F-C-2102 S T I O ) ) E-Mail:techserv@stifirestop.com P PAGE 1 OF 2 (800)992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifiresto .com • Website:www.stifiresto .com C. Top Plate - The double top plate shall consist of two nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening is to be 1/2 in. (13 mm) to 1 in. (25 mm) larger than diam of pipe. As an alternate, the opening may be square -cut with a max dimension 1/2 in. (13 mm) to 1 in. (25 mm) greater than the diam of the pipe. Plates may be discontinuous over opening, terminating at two opposing edges of opening. Max length of discontinuity is 4-1/2 in. (114 mm). D. Steel Plate - (Not Shown) - When lumber plates are discontinuous, nom 1-1/2 in. (38 mm) wide No. 20 gauge (or heavier) galv steel plates shall be installed to connect discontinuous lumber plates and to provide a form for the fill material. Steel plates sized to lap 2 in. (51 mm) onto each discontinuous lumber plate and secured to lumber plates with steel screws or nails. E. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as specified in individual Wall and Partition Design. 3. Through Penetrants - One nonmetallic pipe or conduit to be installed approximately midway between wood joists. Pipe or conduit to be installed either concentrically or eccentrically within the firestop system. Dimensions of square or circular opening hole -sawed through flooring system to be 1/2 in. (13 mm) to 1 in. (25 mm) larger than the outside diam of through -penetrant. On the top surface of the floor, the annular space within the opening shall be a min 0 in. (point contact) to max 1 in. (25 mm). Diam of opening hole -sawed through top plates of chase wall assembly to be 1/2 in. (13 mm) to 1 in. (25 mm) larger than the outside diam of through penetrant. In top plates of chase wall assembly, the annular space within the opening shall be min 0 in. (point contact) to max 1/2 in. (13 mm). Pipe or conduit to be rigidly supported on both sides of the floor -ceiling assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Rigid Nonmetallic Conduit+ - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA No. 70). C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) SDR 17 CPVC pipe for use in closed (process or supply) piping systems. D. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. E. Electrical Nonmetallic Tubing (ENT)+ - Nom 2 in. (51 mm) diam (or smaller) PVC tubing installed in accordance with the National Electrical Code (NFPA No. 70). F. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) FLOWGUARD GOLD@ SDR11 CPVC for use in closed (process or supply) piping systems. G. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) BLAZEMASTER@ SDR13.5 CPVC for use in closed (process or supply) piping systems. H. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) SDR11 CPVC pipe for use in closed (process or supply) piping systems. IPEX INC - AquaRise 4. Fill, Void or Cavity Material* - Sealant - Min 3/4 in. (19 mm) thickness of fill material applied within annulus, flush with top surface of sole plate (Item 2B) . Min 5/8 in. (16 mm) thickness of fill material applied within annulus on lower top plate (Item 2C) . Additional fill material to be installed such that a min 1/4 in. (6 mm) bead is formed around the through penetrant on the top surface of sole plate and bottom surface of lower top plate. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant or Type WF300 Firestop Caulk +Bearing the UL Listing Mark *Bearing the UL Classification Marking Specified Technologies 10Evans Waomervlle, NJ 08876 Reproduced courtesy ounderwriteraborInc. S T I o Created or Revised: March 14, 2014 @ F-C-2102 I ( ) ( ) PAGE 2 OF 2 (800)992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. F-C-2157 F Rating - 1 Hr T Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft 1. Floor -Ceiling Assembly - Floor Assembly - The 1 hr fire rated wood truss or combination wood and steel truss Floor -Ceiling assembly shall be constructed of the materials and in the manner described in the individual L500 Series Design in the UL Fire Resistance Directory, as summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of opening shall be 1/2 in. to 1 in. (13 to 25 mm) larger than the outside diam of nonmetallic pipe (Items 3 and 4). B. Joists - Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and ends firestopped. C. Gypsum Board* - Nom 4 ft. (1.2 m) wide by 5/8 in. (16 mm) thick, attached as described in the individual Floor -Ceiling Design. 2. Chase Wall - The through -penetrant (Item No. 3) shall be routed through a single, double or staggered wood stud/gypsum board chase wall and shall include the following construction features: A. Studs - Nom 2 by 4 in. (51 by 102 mm) or 2 by 6 in. (51 by 152 mm) lumber studs. B. Sole Plate - Nom 2 by 4 in. (51 by 102 mm) or 2 by 6 in. (51 by 152 mm) lumber plates. Diam of opening or length of notch -out in sole plate to be 1/2 in. to 1 in. (13 to 25 mm) larger than outside diam of pipe. C. Top Plate - The single or double top plate shall consist of one or two nom 2 by 4 in. (51 by 102 mm) or 2 by 6 in. (51 by 152 mm) lumber plates. Diam of opening or length of notch -out in top plate to be 1/2 in. to 1 in. (13 to 25 mm) larger than outside diam of pipe. D. Gypsum Board* - Min 1/2 in. (13 mm) thick rated or nonrated gypsum board Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 S T Io AGE1 57 (800)992-1180 • (908)526-8000 •FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 2 3. Through Penetrant - One nonmetallic pipe to be installed within the firestop system. Pipe to be rigidly supported on both sides of floor -ceiling assembly. The annular space between pipe and periphery of opening shall be min 0 in. (point contact) to max 1/2 in. (0 to max 13 mm). The following types and sizes of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. B. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. 4. Branch Piping - (Optional)- One nonmetallic pipe to be connected to through penetrant (Item 3) and installed within opening in subfloor. The annular space between pipe and periphery of opening shall be min 0 in. (point contact) to max 1/2 in. (13 mm). The following types and sizes of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. B. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system.. 5. Fill, Void or Cavity Materials* - Caulk or Sealant - Min 3/4 in. (19 mm) thickness of caulk applied within annular space around perimeter of through penetrant (Item 3), flush with top surface of floor or sole plate and flush with bottom surface of top plate. Min 3/4 in. (19 mm) thickness of caulk applied within annular space around perimeter of branch piping (Item 4), flush with top surface of floor. Min 1/2 in. (13 mm) diam bead applied at the pipe/floor interface. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant or Type WF300 Firestop Caulk * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I Created or Revised: January 23, 2014 IF-C-2157 ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. F-C-2319 F Rating - 1 Hr T Rating - 1 Hr 1. Floor -Ceiling Assembly - The 1 hr fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Designs in the UL Fire Resistance Directory, as summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of floor opening to be min 1/2 in. (13 mm) to max 1 in. (25 mm) larger than outside diameter of individual or grouped penetrants. Max diam of opening is 3 in. (76 mm). B. Wood Joists - Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Floor -Ceiling Design. 2. Chase Wall - The through penetrant (Item 3) shall be routed through a 1 hr fire rated single, double or staggered wood stud/gypsum board chase wall. Depth of chase wall stud cavity to be min 1/2 in. (13 mm) greater than diameter of opening cut in sole and top plates to accommodate the through penetrant (Item 2). The chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Nom 2 by 4 in.(51 by 102 mm), 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm)or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening in sole plate to be min 1/2 in. (13 mm) to max 1 in. (25 mm) larger than outside diameter of individual or grouped penetrants. Max diam of opening is 3 in. (76 mm). C. Top Plate - The double top plate shall consist of two nom 2 by 4 in. (51 by 102 mm), two nom 2 by 6 in. (51 by 152 mm)or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening in top plate to be min 1/2 in. (13 mm) to max 1 in. (25 mm) larger than outside diameter of individual or grouped penetrants. Max diam of opening is 3 in. (76 mm). D. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as specified in the individual Wall and Partition Design. 3. Through Penetrants - One or more nonmetallic pipes, conduits or tubing to be installed either concentrically or eccentrically within the opening. Min space between pipes, conduits or tubes to be 0 in. Annular space between the pipes, conduits or tubing and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 1 in. (25 mm). Penetrants to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of nonmetallic pipe, conduits or tubing may be used: A. Cross Linked Polyethylene (PEX) Tubing - Nom 1 in. (25 mm) diam (or smaller) SDR9 PEX tubing for use in closed (process or supply) piping systems. B. Electrical Nonmetallic Tubing (ENT)+ - Nom 2 in. (51 mm) diam (or smaller) PVC tubing installed in accordance with Article 331 of the National Electrical Code (NFPA 70). 4. Fill, Void or Cavity Material* -Sealant -Min 3/4 in. (19 mm) thickness of fill material applied within the annulus, flush with the top surface of the floor or chase wall sole plate. Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with bottom surface of chase wall top plate. Min 3/8 in. (10 mm) diam bead of fill material applied at point contact location on the top surface of floor or sole plate and at the penetrant/chase wall top plate interface. SPECIFIED TECHNOLOGIES INC - Type WF300 Caulk * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. AP Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2007 S T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com AG 2319 PAGE 1 OF 1 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. F-C-2320 F Rating - 1 Hr T Rating - 1 Hr n 1. Floor -Ceiling Assembly - The 1 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Rectangular cutout in flooring to accommodate the bathtub drain piping (Item 2) to be max 8 by 12 in. (203 by 305 mm). Cutout to be patched on underside of subfloor using one layer of min 3/4 in. (19 mm) thick plywood or min 5/8 in. (16 mm) thick gypsum wallboard (Item 1 C) sized to lap min 2 in. (51 mm) beyond each edge of rectangular cutout. Diam of opening hole -sawed through patch to accommodate drain piping (Item 2) to be 1 in. (25 mm) larger than outside diam of drain piping and positioned such that drain piping is centered in opening. Patch split into two pieces at opening hole -sawed for bathtub drain piping. Two pieces positioned around drain piping, with cut edges tightly butted, and screw -attached to underside of subfloor with 1-1A in. (32 mm) long Type S steel screws spaced max 6 in. (152 mm) OC. B. Wood Joists* - Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* - Nom 4 ft (1.22 m) wide by 5/8 in. (16 mm) thick, attached as described in the individual Floor -Ceiling Design. 2. Drain Piping - Nom 1-1/2 in. (38 mm) diam (or smaller) Schedule 40 cellular or solid core polyvinyl chloride (PVC) or acrylonitrile butadiene styrene (ABS) pipe and drain fittings cemented together and provided with PVC or ABS bathtub waste/overflow fittings. The annular space shall be a min 3/8 in. (10 mm) to max 5/8 in. (16 mm). 3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) depth of fill material applied within annular space, flush with both surfaces of plywood or gypsum wallboard patch. SPECIFIED TECHNOLOGIES INC - Type WF300 Caulk * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 �° PAGE23OF1 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com Classified by Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-C-2321 ❑■ ; ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 1 and 2 Hr (See Item 1) FT Ratings - 1 and 2 Hr (See Item 1) L Rating At Ambient - Less Than 1 CFM/sq ft FH Ratings - 1 and 2 Hr (See Item 1) L Rating At 400 F - Less Than 1 CFM/sq ft FTH Ratings - 1 and 2 Hr (See Item 1) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft 4 5D 1A 3 5D 1B 1D 5A 5B System tested with a pressure differential of 2.5 Pa between the exposed and the unexposed surfaces with the higher pressure on the exposed side. 1. Floor -Ceiling Assembly - The 1 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The 2 hr fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in Design Nos. L505, L511 or L536 in the UL Fire Resistance Directory. The F, T, FT, FH and FTH Ratings of the firestop system are equal to the rating of the floor -ceiling assembly. The general construction features of the floor -ceiling assembly are summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of opening hole -sawed in flooring shall be min 1/2 in. (13 mm) to max 1 in. (25 mm) larger than diam of through penetrant (Item 3) or branch piping (Item 4). As an option, the opening for the branch piping (Item 4) may be rectangular, 8 by 12 in. (203 by 305 mm) max, for 1 hr rated assemblies only. Cutout to be patched on underside of subfloor using one layer of min 3/4 in. (19 mm) thick plywood or min 5/8 in. (16 mm) thick gypsum board (Item 1 D) sized to lap min 2 in. (51 mm) beyond each edge of rectangular cutout. Diam of opening hole sawed through patch to accommodate branch piping (Item 4) to be min 1/2 in. (13 mm) to max 1 in. (25 mm) larger than diam of branch piping. Patch split into two pieces at opening hole -sawed for branch piping. Two pieces positioned around branch piping, with cut edges tightly -butted, and screw attached to the underside of subfloor using 1-1A in. (32 mm) long Type S steel screws spaced max 6 in. (152 mm) OC. B. Wood Joists* - For 1 hr fire -rated floor -ceiling assemblies nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. For 2 hr fire -rated floor -ceiling assembly, nom 2 by 10 in. (51 by 254 mm) lumber joists spaced 16 in. (406 mm) OC with nom 1 by 3 in. (25 by 76 mm) lumber bridging with ends firestopped. C. Furring Channels - (Not Shown) - Resilient galv steel furring installed perpendicular to wood joists between first and second layers of gypsum board (Item 1 D) in 2 hr fire -rated assembly. D. Gypsum Board* - Nom 4 ft (1.22 m) wide by 5/8 in. (16 mm) thick as specified in the individual Floor -Ceiling Design. First layer of gypsum board nailed to wood joists. Second layer of gypsum board (2 hr fire -rated assembly) screw -attached to furring channels. Diam of opening shall be max 1/2 in. (13 mm) larger than nom diam of through penetrant (Item 3). Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. us Created or Revised: June 05, 2015 F-C-2321 T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 3 Chase Wall - (Optional, not shown) - The through -penetrant (Item 3) may be routed through a single, double or staggered wood stud/gypsum board chase wall which includes the following construction features: A. Studs - Nom 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate - Nom 2 by 6 in. (51 by 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening hole -sawed in sole plate to be min 1/2 in. (13 mm) to max 1 in. (25 mm) larger than diam of through penetrant (Item 3). C. Top Plate - The single or double top plate shall consist of one or two nom 2 by 6 in. (51 by 152 mm) or one or two sets of parallel nom 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening shall be min 1/2 in. (13 mm) to max 1 in. (25 mm) larger than diam of through penetrant (Item 3). D. Gypsum Board* - Min 1/2 in. (13 mm) thick rated or non -rated gypsum board. Through Penetrants - One nonmetallic pipe to be centered within the firestop system. Pipe to be rigidly supported on both sides of floor -ceiling assembly. The annular space between pipe and periphery of opening shall be min 0 in. (0 mm, point contact) to max 1/2 in. (13 mm). Pipe may be installed with continuous point contact where it passes through gypsum board ceiling. The following types and sizes of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping system. C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. Branch Piping - (Optional) -One nonmetallic pipe with or without nom 4 in. (102 mm) diam (or smaller) toilet flange (not shown) connected to through penetrant (Item 3) within concealed space above ceiling and centered within opening in subfloor. The annular space between pipe and periphery of opening shall be min 0 in. (0 mm, point contact) to max 1/2 in. (13 mm). Branch piping may terminate in a max 4 in. (102 mm) diam toilet flange that corresponds to the type of branch piping. The following types and sizes of nonmetallic pipes may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. B. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. Firestop System - The details of the firestop system shall be as follows: A. Fill, Void or Cavity Material* - Wrap Strip - Nom 1/8 (3 mm), 3/16 in. (5 mm) or 1/4 in. (6 mm) thick intumescent material faced on both sides with a plastic film, supplied in 1-1/2 in. or 2 in. (38 or 51 mm) wide strips. Nom 1-1/2 in. or 2 in. (38 or 51 mm) wide strips tightly wrapped around through penetrant (Item 3) with the edges butted against the underside of the gypsum board ceiling (Item 1 D) or top plate of chase wall (Item 2C) around the entire perimeter of the hole -sawed opening. For nom 1/2 in. to 2 in. (13 to 51 mm) diam pipes, a min of one layer of wrap strip is required. For nom 2-1/2 in. to nom 4 in. (64 to 102 mm) diam pipes, a min of two layers of wrap strip is required. Each layer of wrap strip to be installed with butted seams, butted seams in successive layers to be staggered or aligned. Wrap strip layer(s) secured together with masking tape. SPECIFIED TECHNOLOGIES INC - SpecSeal RED, RED2, BLU or BLU2 Wrap Strip Al. Fill, Void, or Cavity Material - Wrap Strip - (Not Shown) - As an alternate to Item 5A for nom 2 in., 3 in. and 4 in. (51, 76 and 102 mm) diam pipes, precut intumescent wrap strip faced on both sides with a plastic film sized to fit the OD of the pipe. The size of the intumescent wrap strip for each pipe size is tabulated below: Nom Pipe Diam, Wrap Strip Nom Pipe Diam, in mm thick x width x len ht in mm 2 (51) SSW125 1/8 x 1-1/2 x 8-1/8 6x38x206 3 (76) SSW250 1/4 x 1-1/2 x 12-1/8 6x38x308 4 (102) SSW375 3/8 x 1-1/2 x 16 10x38x406 SPECIFIED TECHNOLOGIES INC - SpecSeal SSW125, SSW250, or SSW375 Wrap Strip Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: June 05, 2015 us o� PAGE 23 F13 T I ® 800 992-1180 • 908 526-8000 9FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com B. Steel Collar - Collar fabricated from coils of precut 0.016 in. (0.4 mm) thick galv sheet steel available from wrap strip manufacturer. Collar shall be nom 1-1/2 in. or 2 in. (38 or 51 mm) deep dependent upon wrap strip width with 1 in. (25 mm) wide by 2 in. (51 mm) long anchor tabs for attachment to underside of ceiling or top plate. Retainer tabs, 3/4 in. (19 mm) wide tapering down to 1/4 in. (6 mm) wide and located opposite the anchor tabs, folded 90 degrees toward through penetrant surface to maintain the annular space and to retain the wrap strips. Collar wrapped around wrap strips and through -penetrant with a 1 in. (25 mm) wide overlap along its perimeter joint and secured with a min 1/2 in. (13 mm) wide by 0.028 in. (0.7 mm) thick stainless steel hose clamp at the mid -height of the steel collar. As an alternate to the steel hose clamp, the steel collar may be secured together by means of three No. 8 steel sheet metal screws. The length of the steel screws is dependent upon the number of layers of wrap strip used within the steel collar. For steel collars incorporating a single layer of wrap strip, the length of the steel screws shall be 1/4 in. (6 mm) long. For steel collars incorporating two or more layers of wrap strip, the length of the steel screws shall be 3/8 in. (10 mm) long. Collar secured to the bottom of ceiling with min 3/16 in. (5 mm) diam by 2 in. (51 mm) long toggle bolts in conjunction with min 1/4 in. (6 mm) by 1-1/4 in. (32 mm) diam steel fender washers. Collar secured to bottom of chase wall top plate with min 3/4 in. (19 mm) long steel wood screws in conjunction with min 1/4 in. (6 mm) by 1 in. (25 mm) diam steel fender washers, respectively. The number of screws is dependent upon the nom diam of the through penetrant. Two screws, symmetrically located, are required for nom 1/2 in. (13 mm) through 2 in. (51 mm) diam through -penetrants. Three screws, symmetrically located, are required for nom 2-1/2 in. (64 mm) and 3 in. (76 mm) diam through -penetrants. Four screws, symmetrically located, are required for nom 3-1/2 in. (89 mm) and 4 in. (102 mm) diam through -penetrants. Steel collar is not required to be installed around branch piping at the underside of the flooring. C. Firestop Device* - (Not Shown) -As an alternate to Items 5A and 5B for through -penetrant (Item 3), a firestop device consisting of a steel collar lined with intumescent material and sized to fit the specific diam of the nonmetallic pipe may be used. Firestop device to be installed on underside of ceiling or top plate in accordance with the accompanying installation instructions. When pipe is contained within the cavity of a wall, the minimum number of fasteners may be reduced. For nom 2 in. diam (or smaller) pipes, the minimum number of opposing fasteners is two. For nom 3 in. diam (or smaller) pipes, the minimum number of fasteners is three. SPECIFIED TECHNOLOGIES INC - SpecSeal Firestop Collar, SpecSeal LCC Collar or SpecSeal SSC Collar D. Fill, Void or Cavity Material* - Sealant - Min 3/4 in. (19 mm) thickness of fill material applied within annular space around perimeter of through penetrant (Item 3) and branch piping (Item 4), flush with top surface of floor or top of chase wall sole plate. Min 1/2 in. (13 mm) diam bead applied at point contact locations at pipe/floor interface and the pipe/plate interface. SPECIFIED TECHNOLOGIES INC - Type WF300 Caulk *Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Sa Created or Revised: June 05, 2015 TIo I C us F-C-2321 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com. Website:www.stifirestop.com PAGE 3 OF 3 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. F-C-2322 F Rating - 1 Hr T Rating - 1 Hr MR 1. Floor -Ceiling Assembly - The 1 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory, as summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of opening is 5 in. (127 mm). B. Wood Joists - Nom 2 by 10 in. (51 by 254 mm) lumber joists spaced 16 in. (406 mm) OC with nom 1 by 3 in. (25 by 76 mm) lumber bridging and with ends firestopped. As an alternate to lumber joists, nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists trusses or Structural Wood Members* with bridging as required with ends firestopped. C. Furring Channels - (Not Shown) - Resilient galv steel furring installed perpendicular to wood joists (Item 1 B) between gypsum board (Item 1 D) and wood joists as required in the individual Floor -Ceiling Design. D. Gypsum Board* - Nom 4 ft (1.22 mm) wide by 5/8 in. (16 mm) thick as specified in the individual Floor -Ceiling Design. Gypsum board secured to wood joists as specified in the individual Floor -Ceiling Design. 2. Closet Flange - Polyvinyl chloride (PVC) or acrylonitrile butadiene styrene (ABS) closet flange installed in hole -sawed opening in flooring system with flange secured to top of flooring with steel screws. Diam of circular opening through flooring (Item 1A) to be max 1/2 in. (13 mm) larger than outside diam of closet flange. 3. Drain Piping - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC or ABS drain piping and fittings. Short length of pipe with 90 degree elbow fitting cemented into bottom socket of closet flange. Drain piping to soil stack cemented into elbow. 4. Fill, Void or Cavity Material* - Sealant - Fill material forced into annulus between closet stub and periphery opening in flooring to max extent possible, flush with bottom surface of floor. Additional fill material to be installed such that a min 3/8 in. (10 mm) crown is formed around the closet stub on bottom surface of floor. SPECIFIED TECHNOLOGIES INC - Type WF300 Caulk 5. Water Closet - (Not Shown) - Floor mounted vitreous china water closet. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUIL Certification (such as Canada), respectively. IF Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 T I � 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com PAGE23OF1 Classified by ■ #� �xxx"�___ Underwiters Laboratories, Inc. T. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-2048 Q ,.,� ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1) T Ratings -1, 1-3/4 and 2 Hr (See Items 2 and 4A) FT Ratings - 1, 1-3/4 and 2 Hr (See Items 2 and 4A) L Rating At Ambient - Less Than 1 CFM/ft2 FH Ratings - 1 and 2 Hr (See Item 1) L Rating At 400°F - Less Than 1 CFM/ft2 FTH Ratings - 1, 1-3/4 and 2 Hr (See Items 2 and 4A) L Rating At Ambient - Less Than 5.1 L/s/m2 L Rating At 204°C - Less Than 5.1 L/s/m2 A 2 3 4A 2 4B 4 4B A 1B Section A -A System tested with a pressure differential of 2.5 Pa between the exposed and the unexposed surfaces with the higher pressure on the exposed side. 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, V300, U400, V400 or W400 Series Wall Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, V300, U400, V400 or W400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 5 in. (127 mm). The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. 2. Steel Sleeve (Optional) - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 (or thinner) steel pipe friction -fit into wall assembly, flush with both surfaces of wall. When steel sleeve is used, T, FT and FTH Ratings are 1 hr. 3. Through Penetrants - One nonmetallic pipe or conduit to be centered within the firestop system. The annular space shall be min 1/4 in. (6 mm) to max 1-1/4 in (32 mm). Pipe or conduit to be rigidly supported on both sides of the wall assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. �� �r Created or Revised: October 12, 2021 T I ® 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com GE 1 OF82 B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit+ - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA No. 70). D. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. E. Flame Retardant Polypropylene (FRPP) Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. F . Polypropylene (PP) Pipe - Nom 1 in. (25 mm) diam (or smaller) Schedule 80 PP pipe for use in closed (process or supply) piping systems . G. Polyvinylidene Fluoride (PVDF) Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVDF pipe for use in closed (process or supply) piping systems . 4. Firestop System - The firestop system shall consist of the following: A. Fill, Void or Cavity Material* - Wrap Strip - Nom 1/8 in. (3.2 mm) or 3/16 in. (4.8 mm) thick intumescent material faced on both sides with a plastic film, supplied in 2 in. (51 mm) wide strips or 1/8 or 1/4 in. (3.2 or 6 mm) thick intumescent material faced on both sides with a plastic film, supplied in 1-1/2 in. (38 mm) wide strips. Single layer of wrap strip wrapped around the through penetrant with the ends butted and held in place by means of foil tape. The wrap strip is slid along the through penetrant into annulus such that 1/4 in. (6 mm) of the wrap strip protrudes from the wall. One set of wrap strips to be installed on each side of wall. As an option when 1/8 in. (3.2 mm) thick wrap strip (BLU2) is used, the strips may be cut to a width of 1-1/2 in. (38 mm). The T, FT and FTH Ratings of the firestop system is dependent upon the hourly rating of the wall, the type of through penetrant and the type of wrap strip used as tabulated below: Type Of Throught Hourly Rating Type of Wrap Strip T, FT, FTH Penetrant of Wall Hr Ratin Hr PVC, CPVC, PVDF 1 SpecSeal BLU, SpecSeal BLU2 1 RNC PP or FRPP or SpecSeal RED RED2 ABS 1 SpecSeal BLU, SpecSeal BLU2 1 or SpecSeal RED RED2 PVC, CPVC, PVDF 2 SpecSeal BLU, SpecSeal BLU2 2 RNC PP or FRPP or SpecSeal RED RED2 ABS 2 SpecSeal BLU or 2 S ecSeal BLU2 ABS 2 SpecSeal RED, RED2 1-3/4 SPECIFIED TECHNOLOGIES INC - SpecSeal BLU Wrap Strip, SpecSeal BLU2 Wrap Strip or SpecSeal RED Wrap Strip, SpecSeal RED2 Wrap Strip B. Fill, Void or Cavity Material* - Sealant - When an annular space is present between the wrap strip and the edge of the opening, a min 5/8 in. (16 mm) depth of sealant shall be installed in the annular space flush with each surface of the wall. A min 1/4 in. (6 mm) diam bead of sealant shall be applied at the gypsum board/wrap strip interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant or SpecSeal SIL300 Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S 1 I ® Created or Revised: October 12, 2021 W-L-2048 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Webs ite:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. W-L-2059 F Ratings - 1 and 2 Hr (See Items 2 and 3) T Ratings - 3/4, 1, 1-1/2 and 2 Hr (See Items 2 and 3) L Rating At Ambient - 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft Section A -A RUN 1. Wall Assembly - The 1 or 2 h fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, U400 and V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1219 mm) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 5 in. (127 mm). 2. Through -Penetrants - One nonmetallic pipe or conduit to be centered within the firestop system. The annular space shall be max 1/4 in. (6 mm). Pipe or conduit to be rigidly supported on both sides of the wall assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 or 80 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. When Schedule 80 PVC pipe is used, the F and T Ratings are 1 hr. When Scheduled 80 PVC pipe is used in closed (process or supply) piping systems, the F and T Ratings are equal to the assembly rating of the wall in which it is installed. B. Rigid Nonmetallic Conduit+ - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 or 80 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70). When Schedule 80 PVC conduit is used, the F and T Ratings are 1 hr. C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems. D. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or foamed core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. E. Fire Retardant Polypropylene (FRPP) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. F. Polyvinylidene Fluoride (PVDF) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVDF pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. G. Fiberglass Reinforced Pipe (FRP) Pipe - Nom 4 in. (102 mm) diam (or smaller) glass fiber reinforced thermosetting resin pipe for use in closed (process or control) or vented (drain, waste or vent) piping systems. When FRP pipe is used, T Rating is 3/4 hr. H. High Density Polyethylene (HDPE) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 HDPE pipe for use in closed (process or supply) piping systems. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: November 27, 2012 W-L-2059 T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com . Webs ite:www.stifirestop.com PAGE 1 OF 2 Firestop System - The firestop system shall consist of the following: A. Fill, Void or Cavity Material* - Sealant - Fill material forced into annular space to max extent possible. Caulk shall be installed flush with both surfaces of wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102, 105, 120 or 129 Sealant, SpecSeal LCI Sealant, Pensil 300 Sealant or SpecSeal Series SIL300 Sealant B. Fill, Void or Cavity Material - Wrap Strip - Nom 1/8 or 3/16 in. (3.2 or 4.8 mm) thick intumescent material faced on both sides with a plastic film, supplied in 2 in. (51 mm) wide strips or nom 1/4 in. (6 mm) thick intumescent material faced on both sides with a plastic film, supplied in 1-1/2 in. (38 mm) wide strips. The layers of wrap strips are individually wrapped around the through -penetrant with ends butted and held in place with masking tape. Butted ends in successive layers shall be aligned. Fire Rating of Wall Hr Max Diam of Throught Penetrant in. mm No. of Wrap Strip Layers F Rating Hr T Rating Hr 1 1-1/2(38) 1 1 1 2 1-1/2(38) 1 2 1-1/2 1 2 (51) 1 1 1 2 2 (51) 1 2 1-1/2 1 3 (76) 2 1 1 2 3 (76) 2 2 2 1 4 (102) 3 1 1 2 4 (102) 3 2 2 Except as noted in Item 2, the F and T Rating of the firestop system is dependent upon the fire rating of wall, diam of through penetrant and the number of wrap strips as tabulated below: SPECIFIED TECHNOLOGIES INC - SpecSeal BLU Wrap Strip, SpecSeal BLU2 Wrap Strip or SpecSeal RED Wrap Strip C. Steel Collar - Collar fabricated from coils of precut 0.016 in. (0.4 mm) thick (30 MSG) galv sheet steel available from wrap strip manufacturer. Collar shall be min 1-1/2 in. (38 mm) deep with 1 in. (25 mm) wide by 2 in. (51 mm) long anchor tabs for securement to the concrete floor or wall. Retainer tabs, 3/4 in. (19 mm) wide tapering down to 1/4 in. (6 mm) wide and located opposite the anchor tabs, are folded 90 degree toward pipe surface to maintain the annular space around the pipe and to retain the wrap strips. Steel collar wrapped around wrap strips and pipe with a 1 in. (25 mm) wide overlap along its perimeter joint and secured together by means of a min 1/2 in. (13 mm) wide by 0.028 in. (0.7 mm) thick stainless steel hose clamp installed at mid -depth of the steel collar. As an alternate to the steel hose clamp, the steel collar may be secured together by means of three No. 8 by 1/4 in. (6 mm) long steel sheet metal screws when more than one layer of wrap strip is used. Wrap strip/collar assembly is slid along the through -penetrant until abuts the surface of the wall. Collar secured to wall by 1/8 in. (3.2 mm) diam by 1-3/4 in. (44 mm) long steel molly bolts in conjunction with 1-1/4 in. (32 mm) diam steel fender washers. The number of molly bolts used is dependent upon the nom diam of the through penetrant. Two molly bolts, symmetrically located, are required for nom 1-1/2 in. (38 mm) and 2 in. (51 mm) diam through penetrants. Three molly bolts, symmetrically located, are required for nom 2-1/2 in. (64 mm) and 3 in. (76 mm) diam through penetrants. Four molly bolts, symmetrically located, are required for nom 3-1/2 in. (89 mm) and 4 in. (102 mm) diam through penetrants. Steel collars are installed on each side of wall. D. Firestop Device* - (Optional, Not Shown) - As an alternate to Item 313 and 3C, galv steel collar lined with an intumescent material sized to fit the specific diam of the through -penetrant. Device shall be installed around through -penetrant in accordance with accompanying installation instructions. Device incorporates anchor tabs for securement to each surface of wall assembly by means of 1/8 in. (3 mm) diam by 1-3/4 in. (45 mm) long steel molly bolts in conjunction with 1/4 in. (6 mm) diam by 1-1/2 in. (38 mm) diam steel fender washers. SPECIFIED TECHNOLOGIES INC - SpecSeal Firestop Collar, SpecSeal LCC Collar or SpecSeal SSC Collar. When SpecSeal LCC Collar or SpecSeal SSC Collar are used, the max annular space shall be 1/8 in. (3 mm) for max 2-1/2 in. (64 mm) diam pipe and shall be max 1/4 in. (6 mm) for pipe larger than 2-1/2 in. (64 mm) diam. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. �� STI Created or Revised: November 27, 2012 IW-L-2059 o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com . Website:www.stifirestop.com PAGE 2 OF 2 Classified by FEU , Underwiters Laboratories, Inc. W'• to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-2100 0 . ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 0, 1/4 , 1 and 1-1/2 Hr (See Item 2) FT Ratings - 0, 1/4 , 1 and 1-1/2 Hr (See Item 2) FH Ratings - 1 and 2 Hr (See Item 1) FTH Ratings - 0, 1/4 , 1 and 1-1/2 Hr (See Item 2) A 1A 2 2 3 3 1B A Section A -A System tested with a pressure differential of 2.5 Pa between the exposed and the unexposed surfaces with the higher pressure on the exposed side. 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, V300,U400, V400 or W400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-5/8 in. (92 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1.2 m) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Design in the UL Fire Resistance Directory. Max diam of opening is 3-1/2 in. The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. 2. Nonmetallic Pipe - One nonmetallic pipe or tubing to be centered within the firestop system. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types of nonmetallic pipes or tubing may be used: A. Polybutylene Pipe - Nom 1 in (2 mm) diam (or smaller) SDR 11 (or heavier) polybutylene (PB) pipe for use in closed (process or supply) piping systems. A nom annular space of 1/4 in. (6 mm) is required within the firestop system. B. Cross Linked Polyethylene (PEX) Tubing - Nom 1 in. (2mm) diam (or smaller) SDR 9 PEX tubing for use in closed (process or supply) piping systems. A nom annular space of 1/4 in. (6 mm) is required within the firestop system. C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 1-1/2 in. (38 mm) diam (or smaller) Schedule 40 cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. The annular space shall be min 1/4 in. (6 mm) to max 1 in. (25 mm). Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. �� Created or Revised: October, 11 2021 us W-L-210 0 S T I o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 0 2 D. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. The annular space shall be min 0 in. (point contact) to max 1 in. (25 mm). E. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) SDR 17 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. The annular space shall be min 0 in. (point contact) to max 1 in. (25 mm). The hourly T, FT and FTH Ratings of the firestop system are dependent on the hourly fire rating of the wall assembly in which it is installed and the type of through penetrant, as shown in the table below: Rating OF Wall Hr Type Of Throught Penetrant T, FT, FTH Rating Hr 2 PB pipe 1-1/2 2 PEX tubing 1-1/2 2 PVC or CPVC pipe 1/4 2 ABS pipe 0 1 PB pipe 1 1 PEX tubing 1 1 PVC or CPVC pipe 1/4 1 ABS pipe 0 3. Fill, Void or Cavity Material" - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall. Additional fill material to be installed such that a min 1/4 in. thick crown is formed around the penetrating item. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant " Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: October, 11 2021 W-L-2100 T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) I-" System No. W-L-2216 F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 1 and 2 Hr (See Item 1) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood or steel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall or Partition Design. Diam of opening in wall to be max 1/2 in. (13 mm) larger than diam of pipe or conduit. The F and T Ratings of the firestop system are dependent on the hourly rating of the wall in which it is installed. 2. Nonmetallic Pipe - One nonmetallic pipe or conduit centered within the opening. Pipe to be rigidly supported on both sides of wall assembly. The following types and sizes of nonmetallic pipe or conduit may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in vented (drain, waste or vent) or closed (process or supply) piping systems. B. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core ABS pipe for use in vented (drain, waste or vent) or closed (process or supply) piping systems. C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR17 CPVC pipe for use in vented (drain, waste or vent) or closed (process or supply) piping systems. D. Rigid Nonmetallic Conduit+ - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA No. 70). 3. Nonmetallic Pipe Coupling - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC pipe coupling, nom 4 in. (102 mm) diam (or smaller) Schedule 40 ABS pipe coupling or nom 4 in. (102 mm) diam (or smaller) SDR17 CPVC coupling installed such that it is flush with one side of the wall and extending outward. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S 1 I ® Created or Revised: January 23, 2014 W-L-2216 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 2 4. Firestop System - The firestop system shall consist of the following: A. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) thickness or fill material applied within annulus, flush with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series 100, 102, 105, 120 or 129 Sealant, SpecSeal LCI Sealant, Pensil 300 Sealant or SpecSeal Series SIL300 Sealant B. Fill, Void or Cavity Material* - Wrap Strip - Nom 1/4 in. (6 mm) thick by 1-1/2 in. (38 mm) wide (RED), 1/8 in. (3.2 mm) thick by 1-1/2 in. (38 mm) wide (RED2), 3/16 in. (4.8 mm) thick by 2 in. (51 mm) wide (BLU), 1/8 in. (3.2 mm) thick by 2 in. (51 mm) wide (BLU2), intumescent strips faced on both sides with a plastic film. The layers of wrap strip are individually wrapped around the pipe coupler with the ends butted and held in place with masking tape. Butted ends in successive layers may be aligned or offset. The wrap strips installed around the pipe coupler are to be butted tightly against the outer surface of the wall. For nom 2 in. (51 mm) diam (or smaller) pipe coupler, apply min two layers of wrap strip. For nom 4 in. (102 mm) diam (or smaller) pipe coupler, apply min three layers of wrap strip. For the pipe or conduit on the side of the wall opposite the pipe coupler, the wrap strips shall be wrapped tightly around the pipe and butted tightly against the outer surface of the wall. For nom 2 in. (51 mm) diam (or smaller) pipes, apply min one layer of wrap strip. For nom 2-1/2 in. and 3 in. (64 and 76 mm) diam pipes, apply min two layers of wrap strip. For nom 3-1/2 in. and 4 in. (89 and 102 mm) diam pipes, apply min three layers of wrap strip. SPECIFIED TECHNOLOGIES INC - SpecSeal RED, RED2, BLU, or BLU2 Wrap Strip C. Steel Collar - Collar fabricated from coils of precut 0.016 in. (0.4 mm) thick (No. 30 MSG) galv sheet steel available from wrap strip manufacturer. Collar shall be nom 1-1/2 or 2 in. (38 or 51 mm) deep with 1 in. (25 mm) wide by 2 in. (51 mm) long anchor tabs for securement to the wall assembly. Retainer tabs, 3/4 in. (19 mm) wide tapering down to 3/8 in. (10 mm) wide and located opposite the anchor tabs, are folded 90 degrees toward through -penetrant surface to maintain the annular space around the through -penetrant and to retain the wrap strips. Steel collar wrapped around wrap strips and through -penetrant with a 1 in. (25 mm) wide overlap along its perimeter joint. Steel collar tightened around wrap strips and through -penetrant using min 1/2 in. (13 mm) wide by 0.028 in. (0.7 mm) thick stainless steel hose clamp installed at midheight of the collar. As an alternate to the steel hose clamp, the steel collar may be secured together by means of three No. 8 by 3/8 in. (10 mm) long steel sheet metal screws. Collar to be secured to gypsum wallboard surface with 1/8 in. (3.2 mm) diam by min 2-3/4 in. (70 mm) long steel molly -type wall anchors or toggle bolts in conjunction with min 1/4 in. by 1-1/4 in. (6 by 31 mm) steel fender washers. The number of hollow -wall anchors used is dependent upon the nom diam of the through -penetrant. Two hollow -wall anchors, symmetrically located, are required for nom 2 in. (51 mm) diam (or smaller) through -penetrants. Three hollow -wall anchors, symmetrically located, are required for nom 2-1/2 in. and 3 in. (64 and 76 mm) diam through -penetrants. Four hollow -wall anchors, symmetrically located, are required for nom 3-1/2 and 4 in. (89 and 102 mm) diam through -penetrants. +Bearing the UL Listing Mark * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I o Created or Revised: January 23, 2014 I ( ( GE 2 OF2 (800)992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com Classified by Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-2237 ❑■ ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 1 and 2 Hr (See Item 1) FT Ratings - 1 and 2 Hr (See Item 1) FH Ratings - 1 and 2 Hr (See Item 1) FTH Ratings - 1 and 2 Hr (See Item 1) rA 3B 313 00 0 00 00 2 Oo 2 3 LA 1 1B = - Section A -A 3B 1B System tested with a pressure differential of 2.5 Pa between the exposed and the unexposed surfaces with the higher pressure on the exposed side. 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, V300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm)lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-5/8 in. (92 mm) wide and spaced max 24 in.(610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Wall and Partition Designs. For nom 2-1/2 in. (64 mm) diam and smaller pipes and conduits, diam of opening shall be max 1/4 in. (6 mm) larger than nom pipe diam. For pipes and conduits greater than nom 2-1/2 in. (64 mm) diam of opening shall be max 1/2 in. (13 mm) larger than nom pipe diam. The hourly F, T, FT, FH and FTH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants - One nonmetallic pipe or conduit to be centered within opening with a max annular space between pipe or conduit and periphery of 1/8 in. (3.2 mm) for nom 2-1/2 in. (64 mm) diam and smaller pipes and conduits and 1/4 in. (6 mm) for pipes and conduits greater than 2-1/2 in. (64 mm) diam. Pipe or conduit to be rigidly supported on both sides of the wall assembly. The following types and sizes of nonmetallic pipes and conduits may be used. A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. D. Rigid Nonmetallic Conduit+ - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA 70). IF Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: October 12, 2021 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@restop.com • Website:www.stifirestop.com GE 1 OF2 3. Firestop System - The firestop system consists of the following: A. Fill, Void or Cavity Material* - Sealant - Min 1/4 in. (6 mm) thickness applied within annulus, flush with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant B. Firestop Device* - Galy steel collar lined with an intumescent material sized to fit the specific diam of the through penetrant. Device shall be installed around through penetrant in accordance with the accompanying installation instructions. Device incorporates anchor tabs for securement to both surfaces of wall assembly by means of 3/16 in. (4.8 mm) diam steel toggle bolts in conjunction with min 1-1/4 in. (32 mm) diam steel fender washers. SPECIFIED TECHNOLOGIES INC - SpecSeal LCC Collar or SpecSeal SSC Collar * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. +Bearing the UL Listing Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: October 12, 2021 us W-L-2237 T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. System No. W-L-2241 �� to ASTM/UL1479 (ASTM E814) F Ratings - 1 and 2 Hr (See Item 1) aVZ T Ratings - 0, 1/4, 1 and 1-3/4 Hr (See Item 2) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft 0 Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Diam of opening to be 1 in. to 1-1/8 in. (25 to 29 mm) larger than outside diam of pipe. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. When Item 2G or 2H is used, the hourly F Rating is 1 hr. 2. Through Penetrant - One nonmetallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop system. Pipe, conduit or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of nonmetallic pipes, conduits and tubes may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. Annular space shall be min 0 in. ( 0 mm, point contact) to max 1 in. (25 mm). B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) SDR 13.5 or Schedule 80 CPVC pipe for use in closed (process or supply) piping systems. Annular space shall be min 0 in. ( 0 mm, point contact) to max 1 in. (25 mm). C. Rigid Nonmetallic Conduit+ - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA 70). Annular space shall be min 0 in. ( 0 mm, point contact) to max 1 in. (25 mm). D. Electrical Nonmetallic Tubing+ - Nom 2 in. (51 mm) diam (or smaller) PVC tubing installed in accordance with Article 331 of the National Electrical Code (NFPA 70). Annular space shall be min 0 in. ( 0 mm, point contact) to max 1 in. (25 mm). E. Cross Linked Polyethylene (PEX) Tubing - Nom 1 in. (25 mm) diam (or smaller) SDR9 PEX tubing for use in closed (process or supply) piping systems. Annular space shall be min 0 in. ( 0 mm, point contact) to max 1 in. (25 mm). Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 �° GE 1 OF12 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com F. Acrylonitrile Butadiene Styrene (ABS) pipe - Nom 1-1/2 in. (38 mm) diam (or smaller) Schedule 40 solid -core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. Annular space shall be min 1/4 in. (6 mm) to max 3/4 in. (19 mm). G. Polyvinyl Chloride (PVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) piping systems. Annular space shall be min 0 in. (0 mm, point contact) to max 1 in. (25 mm). H. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) SDR 17 CPVC pipe for use in closed (process or supply) piping systems. Annular space shall be min 0 in. (0 mm, point contact) to max 1 in. (25 mm). When Item 2A or 2B is used, the T Rating is 1/4 hr. When Item 2C, 2D, or 2E is used, the T Rating is 1 hr and 1-3/4 hr for 1 hr and 2 hr fire rated walls, respectively. When Item 2F, 2G, or 2H is used, T Rating is 0 hr. 3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. At point contact location, min 1/4 in. (6 mm) diam bead of fill material applied at nonmetallic pipe/gypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant or Type WF300 Firestop Caulk (for wood studs only) * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I o Created or Revised: January 23, 2014 I ( ( GE 2 OF12 (800)992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com Classified by Underwiters Laboratories, Inc. System No. W-L-2242 to ASTM/UL1479 (ASTM E814) F Ratings - 1 and 2 Hr (See Item 1) ❑� T Ratings - 1 and 1-3/4 Hr (See Item 2) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft I 3 A 2 L— A Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-5/8 in. (92 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 3 in. (76 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant - One or more nonmetallic pipes, conduits or tubes to be bundled together and installed eccentrically or concentrically within the firestop system. Aggregate cross -sectional area of penetrants not to exceed 42 percent of the cross -sectional area of the opening. The annular space between the grounded pipes, conduits or tubes and the periphery of the opening shall be min 0 in. (point contact) to max 1 in. (25 mm). Separation between pipes, conduits or tubes to be min 0 in. (point contact) to max 1 in. (25 mm). Pipes, conduits or tubes to be rigidly supported on both sides of the wall assembly. The following types and sizes of nonmetallic pipes, conduits and tubes may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 1 in. (25 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 1 in. (25 mm) diam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit+ - Nom 1 in. (25 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA 70). D. Electrical Nonmetallic Tubing+ - Nom 1 in. (25 mm) diam (or smaller) PVC tubing installed in accordance with the National Electrical Code (NFPA 70). E. Cross Linked Polyethylene (PEX) Tubing - Nom 1 in. (25 mm) diam (or smaller) SDR9 PEX tubing for use in closed (process or supply) piping systems. The T Rating is 1 hr and 1-3/4 hr for 1 hr and 2 hr fire rated walls, respectively. 3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. Sealant to be forced into interstices between penetrants to max extent possible. At point contact location, min 1/4 in. (6 mm) diam bead of fill material applied at nonmetallic pipe/gypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant or Type WF300 Firestop Caulk (wood stud walls only) * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. AP Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: June 17, 2010 1 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com GE 1 OF Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. W-L-2334 F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 1/2 and 1 Hr (See Item 1) Section A -A ir. 1. Wall Assembly - The fire rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Wall and Partition Design. Diam of opening is max 1/2 in. (13 mm) larger than the outside diam of steel sleeve (Item 3A). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. The T Ratings are 1/2 and 1 hr when installed in 1 hr and 2 hr rated walls, respectively. 2. Through Penetrants - One nonmetallic pipe or conduit to be centered within the firestop system. Pipe or conduit to be rigidly supported on both sides of wall assembly. The pipe or conduit may be installed at an angle not greater than 45 degrees from perpendicular. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 (or heavier) solid core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. D. Rigid Nonmetallic Conduit+ - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70). Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I Created or Revised: January 23, 2014 I W-L-2334 o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 2 3. Firestop System - The firestop system shall consist of the following: A. Metallic Sleeve - Cylindrical sleeve fabricated from min 0.016 in. (0.4 mm) thick (30 gauge) galv sheet steel and having a min 1 in. (25 mm) lap along the longitudinal seam. Sleeve to extend a min of 2 in. (51 mm) beyond both sides of the wall. The inside diam of the sleeve shall be larger than outside diam of nonmetallic pipe or conduit such that an annular space will be present between the steel sleeve and the pipe around the entire circumference of the pipe to accommodate the layer(s) of wrap strips (Item 313). The annular space between the outside of the sleeve and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 1/2 in. (13 mm). B. Fill, Void or Cavity Materials* - Wrap Strip - Nom 1/8 or 3/16 in. (3.2 or 4.8 mm) thick intumescent material faced on both sides with plastic film, supplied in 2 in. (51 mm) wide strips or 1/4 in. (6 mm) thick intumescent material faced on both sides with plastic film, supplied in 1-1/2 in. (38 mm) wide strips. Strips tightly wrapped around nonmetallic pipe and slid into sleeve on both sides of wall such that the edges of the wrap strips are recessed 1/2 in. (13 mm) from the edges of the sleeve. For nom 1/2 in. (13 mm) to nom 1-1/2 in. (38 mm) diam pipes, a min of one layer of wrap strip is required. For nom 2 in. (51 mm) , 2-1/2 in. (64 mm) and 3 in. (76 mm) diam pipes, a min of two layers of wrap strip is required. For nom 3-1/2 in. (89 mm) and 4 in. (102 mm) diam pipes, a min of three layers of wrap strip is required. Each layer of wrap strip to be installed with butted seam with butted seams in successive layers aligned or offset. Wrap strip layers temporarily held in position with tape. A min 1/2 in. (13 mm) wide stainless steel band clamp shall be secured around the outside of the sleeve to tighten the sleeve over the center of the wrap strips at each end of the sleeve. SPECIFIED TECHNOLOGIES INC - SpecSeal RED Wrap Strip, SpecSeal BLU Wrap Strip or SpecSeal BLU2 Wrap Strip C. Fill, Void or Cavity Materials* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus between metallic sleeve and periphery of the opening, flush with both surfaces of wall assembly. Min 1/2 in. (13 mm) diam bead of caulk to be applied at the point contact location between the steel sleeve and the gypsum board. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. �� S T I q Created or Revised: January 23, 2014 I�° GE2OF2 � 800 992-1180 • 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. W-L-2493 F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 1 and 2 Hr (See Item 1) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft rA 0 0 0 O 413 A Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood or steel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall or Partition Design. Diam of opening in wall to be max 1/2 in. (13 mm) larger than diam of pipe or conduit. The F and T Ratings of the firestop system are equal to the hourly fire rating of the wall in which it is installed. 2. Nonmetallic Pipe - One nonmetallic pipe or conduit centered within the opening. Pipe to be rigidly supported on both sides of the wall assembly. The following types and sizes of nonmetallic pipe or conduit may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 3 in. or 4 in. (76 or 102 mm) diam solid or cellular core Schedule 40 polyvinyl chloride (PVC) pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. or 4 in. (76 or 102 mm) diam SDR 13.5 chlorinated polyvinyl chloride (CPVC) pipe for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit+ - Nom 3 in. or 4 in. (76 or 102 mm) diam Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA 70). D. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 3 in. or 4 in. (76 or 102 mm) diam solid or cellular core Schedule 40 acrylonitrile butadiene styrene (ABS) pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. 3. Nonmetallic Pipe Coupling - Nom 3 in. or 4 in. (76 or 102 mm) diam Schedule 40 PVC, Schedule 40 ABS or SDR13.5 CPVC coupling corresponding to pipe type installed such that the top of the coupling is flush with one side of the wall and extends outward. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 @ W-L-2493 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com GE 1 OF 4. Firestop System - The firestop system shall consist of the following: A. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) thickness of fill material applied within annulus, flush with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series 100, 102, 105, 120 or 129 Sealant, SpecSeal LCI Sealant, Pensil 300 Sealant, Type WF300 Firestop Caulk (1.1300 Walls Only) B. Firestop Device* - Firestop device consisting of an adjustable galv steel collar lined with an adjustable intumescent material sized to fit nom 3 in. and 4 in. (76 and 102 mm) diam pipes and corresponding couplings. Device shall be installed around through penetrant in accordance with the accompanying installation instructions. Device incorporates anchor tabs for attachment to both surfaces of gypsum board wall assembly by means of min 1/8 in. (3.2 mm) diam by min 2-3/4 in. (70 mm) long steel toggle bolts in conjunction with min 1/4 in. by 1-1/4 in. (6 by 32 mm) diam steel fender washers. Min four fasteners are required. SPECIFIED TECHNOLOGIES INC - SpecSeal Series RTC Range -Taking Firestop Collar C. Firestop Device* - (Optional, Not Shown) -As an alternate to Item 4B for the pipe or conduit (Item 2) on the side of the wall opposite the pipe coupler, a firestop device consisting of a steel collar lined with intumescent material and sized to fit the specific diam of the nonmetallic pipe may be used. Firestop device to be installed on the side of wall opposite the pipe coupler in accordance with the accompanying installation instructions. SPECIFIED TECHNOLOGIES INC - SpecSeal LCC Firestop Collar +Bearing the UL Listing Mark * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 ® W-L-2493 S T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 2 OF 2 Classified by n#�a Underwiters Laboratories, Inc. u--rpL to ASTM/UL1479 (ASTM E814) System No. W-L-2496 F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 1 and 2 Hr (See Item 1) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft �-a °C0 3C �'�n'`� 3 A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. OC (610 mm). B. Gypsum Board* - The gypsum wallboard type, thickness, number of layers and orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 5 in. (127 mm). The hourly F and T Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants - One nonmetallic pipe or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space between the pipe or conduit and the periphery of the opening shall be min 0 in. (0 mm, point contact) to a max 1/2 in. (13 mm). Pipe or conduit to be rigidly supported on both sides of wall. The following types and sizes of pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed (process or supply) or vented (drain, waste, or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR 13.5 CVPC pipe for use in closed (process or supply) piping systems. C. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular core or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. D. Rigid Nonmetallic Conduit+ - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code, (NFPA No. 70). 3. Firestop System - The firestop system shall consist of the following: A. Fill, Void or Cavity Material* - Sealant - Min 3/8 in. (10 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102, 105, 120 or 129 Sealant, SpecSeal LCI Sealant, Pensil 300 Silicone Sealant or SpecSeal Series SIL300 Sealant Ir Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: November 26, 2008 W-L-2496 T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com . Webs ite:www.stifirestop.corn PAGE 1 OF 2 B. Fill, Void or Cavity Material* - Wrap Strip - Nom 1/8 in. (3.2 mm) or 3/16 in. (4.8 mm) thick intumescent material faced on both sides with a plastic film, supplied in 1 1/2 in. or 2 in. (51 mm) wide strips or nom 1/4 in. (6 mm) thick intumescent material faced on both sides with a plastic film, supplied in 1-1/2 in. (38 mm) wide strips. For nom 1-1/2 in. (38 mm) and 2 in. (51 mm) diam pipes/conduits, a min of two layers of wrap strip are required. For nom 2-1/2 in. (64 mm) or 3 in. (76 mm) diam pipes/conduits, a min of three layers of wrap strip are required. For nom 3-1/2 in (89 mm) and 4 in. (102 mm) diam pipes/conduits, a min of four layers of wrap strip are required. The layers of wrap strip are to be eccentrically installed such that the layers do not completely encircle the penetrant. The layers are wrapped around the penetrant flush with both surfaces of the wall such that the ends butt up to the tangent of the periphery of the opening at the point contact location. Layers of wrap strip temporarily held in place with tape. SPECIFIED TECHNOLOGIES INC - SpecSeal RED Wrap Strip, SpecSeal BLU Wrap Strip or SpecSeal BLU2 Wrap Strip C. Steel Collar - Collar fabricated from coils of precut 0.016 in. (4 mm) thick (No. 30 MSG) galv sheet steel available from wrap strip manufacturer. Collar shall be nom 1-1/2 in. (38 mm) or 2 in. (51 mm) deep (dependent upon width of wrap strip) with min four 1 in. (25 mm) wide by 2 in. (51 mm) long anchor tabs for attachment to the wall. Retainer tabs, 3/4 in. (19 mm) wide tapering down to 3/8 in. (10 mm) wide and located opposite the anchor tabs, are folded 90 degree toward through -penetrant surface to maintain the annular space around the through -penetrant and to retain the wrap strips. Steel collar wrapped around wrap strips and through penetrant with a 1 in. (25 mm) wide overlap along its perimeter joint. Steel collar tightened around wrap strips and through penetrant using min 1/2 in. (13 mm) wide by 0.028 in. (7 mm) thick stainless steel hose clamp installed at midheight of the collar or using three symmetrically located No. 8 steel sheet metal screws. Collar secured to wall surface with 1/8 in. (3 mm) diam steel hollow wall anchors in conjunction with min 1 in. (25 mm) diam steel fender washers installed symmetrically opposite the point contact location. The number of fasteners used is dependent upon the nom diam of the through penetrant. Two fasteners, symmetrically located, are required for nom 1-1/2 in (38 mm) and 2 in. (51 mm) diam through penetrants. Three fasteners, symmetrically located, are required for nom 2-1/2 in. (64 mm) and 3 in. (76 mm) diam through penetrants. Five fasteners, symmetrically located, are required for nom 3-1/2 in. (89 mm) and 4 in. (102 mm) diam through penetrants. One collar is used on each side of the wall. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. +Bearing the UL Listing Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I. Created or Revised: November 26, 2008 I W-L-2496 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. W-L-2506 F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 1, 1-1/2 and 1-3/4 Hr (See Items 3) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft ram— A A U SECTION AA Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 5 in. (127 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Steel Sleeve - Cylindrical sleeve fabricated from 30 gauge (0.013 in. or 0.33 mm thick) sheet steel and having a min 1 in. (25 mm) lap along the longitudinal seam. Length of steel sleeve to be equal to thickness of wall. 3. Through Penetrants - One nonmetallic pipe or conduit to be centered within the firestop system. Pipe or conduit to be rigidly supported on both sides of the wall assembly. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit+ - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA No. 70). D. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. E. Electrical Nonmetallic Tubing (ENT)+ - Nom 2 in. (51 mm) diam (or smaller) corrugated wall ENT formed from PVC installed in accordance with the National Electrical Code (NFPA No. 70). The hourly T Rating is 1-3/4 hr when Item B, C, D, or E is used and 1-1/2 hr when Item A is used in 2 hr walls. The hourly T Rating is 1 hr in 1 hr rated walls. 4. Firestop System - The firestop system shall consist of the following: A. Fill, Void or Cavity Material* - Wrap Strip - Nom 1/8 in. (3.2 mm) or 3/16 in. (4.8 mm) thick intumescent material faced on both sides with a plastic film, supplied in 2 in. (51 mm) wide strips. Two layers of wrap strip individually wrapped around the through penetrant with the ends butted or continuously wrapped around the through penetrant and held in place by means of foil tape. The wrap strip is slid along the through penetrant into annulus such that the ends of the wrap strip are recessed 1/4 in. (6 mm) from each end of steel sleeve. One set of wrap strips to be installed on each side of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal BLU Wrap Strip or SpecSeal BLU2 Wrap Strip B. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) depth applied between wrap strip and periphery of opening on both sides of wall flush with ends of steel sleeve. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 @ GE 1 -2506 OF T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com Classified by Underwriters Laboratories, Inc. ❑MU9 to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 7s�+ t System No. W-L-2508 Oti: ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1) T Rating - 0 Hr FT Rating - 0 Hr FH Ratings - 1 and 2 Hr (See Item 1) FTH Rating - 0 Hr A 4 3 2 3 4 2 1 1B A Section A -A System tested with a pressure differential of 2.5 Pa between the exposed and the unexposed surfaces with the higher pressure on the exposed side. 1. Wall Assembly -- The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, V300, U400, V400 or W400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* -- Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Diam of opening to be 1 in. to 1-1/8 in. (25 to 29 mm) larger than outside diam of pipe. The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. 2. Steel Sleeve -- Cylindrical sleeve fabricated from 0.0165 in. (0.42 mm) thick galv sheet steel and having a min 2 in. (51 mm) lap along the longitudinal seam. Length of steel sleeve to be equal to or nom 2 in. (51 mm) longer than the thickness of wall. Sleeve installed by coiling the sheet steel to a diam smaller than the through opening, inserting the coil through the openings and releasing the coil to let it uncoil against the circular cutouts in the gypsum board layers. The ends of the steel sleeve shall be flush with or extend max 1 in. (25 mm) beyond each surface of the wall. 3. Through Penetrant -- One nonmetallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop system. Annular space to be min 1/4 in. (6 mm) to max 1 in. (25 mm). Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of nonmetallic pipes, conduits and tubes may be used: Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: October 11, 2021 T I @ GE 1 008 ® 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com A. Polyvinyl Chloride (PVC) Pipe -- Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe -- Nom 2 in. (51 mm) diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit+ -- Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA 70). D. Electrical Nonmetallic Tubing+ -- Nom 2 in. (51 mm) diam (or smaller) PVC tubing installed in accordance with the National Electrical Code (NFPA 70). E. Cross Linked Polyethylene (PEX) Tubing -- Nom 1 in. (25 mm) diam (or smaller) SDR9 PEX tubing for use in closed (process or supply) piping systems. F. Acrylonitrile Butadiene Styrene (ABS) Pipe -- Nom 1-1/2 in. (38 mm) diam (or smaller) Schedule 40 solid -core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. 4. Fill, Void or Cavity Material* -- Sealant -- Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with ends of steel sleeve. SPECIFIED TECHNOLOGIES INC -- SpecSeal LCI Sealant, SpecSeal Series SSS Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. us S 1 I ® Created or Revised: October 11, 2021 OF (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Webs itemww.stifirestop.com W-L-2 508ePAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. W-L-2552 F Rating - 1 Hr T Rating - 1 Hr a a SECTION A -A Wall Assembly - The 1 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - (Not Shown) - Wall framing to consist of min 2 by 6 in. (51 by 152 mm) wood or steel channel studs spaced in accordance with the individual U300, U400, or V400 Series Wall and Partition Designs. B. Batts and Blankets* - Glass fiber or mineral wool batt insulation placed to fill stud cavity containing nonmetallic DWV pipe with clean -out tee (Item 2). Glass fiber insulation to have a min density of 0.9 pcf (14 kg/m3) and a min R-13 thermal insulation rating. Mineral wool batt insulation to have a min density of 3 pcf (48 kg/m3). See Batts and Blankets (BKNV) Category in the Building Materials Directory and Batts and Blankets (BZJZ) Category in the Fire Resistance Directory for names of Classified Companies. C. Gypsum Board* - One layer of nom 5/8 in. (16 mm) thick gypsum board, as specified in the individual Wall and Partition Design. Max diam of opening is 5 in. (127 mm). 2. Piping System - One nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC or ABS pipe with PVC or ABS clean -out tee, with threaded plug, for use in vented (drain, waste or vent) piping system installed within stud cavity. The threaded PVC or ABS clean -out plug is to be centered behind opening in gypsum board. 3. Fill, Void or Cavity Material* - Putty or Sealant - Min 3/4 by 5/16 in. (19 by 8 mm) continuous band of putty or min 1/2 in. (13 mm) diam continuous bead of sealant applied as a gasket around perimeter of opening. SPECIFIED TECHNOLOGIES INC - SpecSeal Putty, SpecSeal SSS Series Sealant, SpecSeal LCI Sealant, Pensil 300 Sealant or Type WF300 Firestop Caulk (U300-Series Wall and Partition Designs only) 4. Cover Plate -Min 6-1/2 in. (165 mm) diam 24 gauge (or heavier) stainless steel cover plate secured to PVC or ABS clean -out plug with stainless steel screw through center of plate. Cover plate to be tightened squarely to wall and shall overlap surface of gypsum board min 3/4 in. (19 mm) around entire perimeter of opening. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: May 14, 2010 �° GE 1 OF1 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com Classified by ❑0 . % Underwriters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System NO. C-AJ-3154 .h�' ❑Ir .. ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 2, 3 and 4 Hr (See Item 5) F Ratings - 2, 3 and 4 Hr (See Item 5) T Ratings - 0, 1/2 and 2-3/4 Hr (See Item 5) FT Ratings - 0, 1/2 and 2-3/4 Hr (See Item 5) L Rating at Ambient - Less Than 1 CFM/sq ft (See Items 3 and 5) FH Ratings - 2, 3 and 4 Hr (See Item 5) L Rating at 400°F - Less Than 1 CFM/sq ft (See Items 3 and 5) FTH Ratings - 0, 1/2 and 2-3/4 Hr (See Item 5) L Rating at Ambient - Less Than 5.1 L/S/m2 (See Items 3 and 5) L Rating at 204°C - Less Than 5.1 L/S/m2 (See Items 3 and 5) A 5 5 5 1 2 2« lllllll lllllll lllllll " v it llll p V ' D a 3 A 3 4 Section A -A 1. Floor or Wall Assembly -- Min 2-1/2 in. (64 mm) or 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete blocks*. Floor may also be constructed of any UL Classified hollow -core Precast Concrete Units*. Max diam of opening is 10 in. (254 mm). See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 2. Sleeve -- (Optional) - Nom 6 in. (152 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe sleeve, nom 6 in. (152 mm) diam (or smaller) No. 26 ga (0.022 in. or 0.56 mm thick) sheet steel sleeve with square anchor flange spot welded to sleeve at approx mid -height or nom 6 in. (152 mm) diam (or smaller) Schedule 40 polyvinyl chloride (PVC) pipe sleeve cast or grouted into floor or wall flush with floor or wall surfaces. Steel pipe sleeve may be installed to project a max of 6 in. (152 mm) beyond the floor or wall surfaces. Steel sleeve to be supported on top side of floor and both sides of wall when not cast or grouted into floor. The annular space between sleeve and periphery of opening shall be min 0 in. (0 m, point contact) to max 3-3/8 in. (86 mm). 3. Cables -- Aggregate cross -sectional area of cables in sleeve to be max 45 percent of the cross -sectional area of the sleeve. See Item 5 for specific cable fill requirements. Tight bundle of cables to be installed in the steel sleeve. The annular space within the firestop system shall be a min of 0 in. (point contact) to a max of 2 in. (51 mm). In 4 hr fire rated assemblies, the annular space within the firestop system shall be a min of 1/4 in. (6 mm) to a max of 1 in. (25 mm). When L Ratings for penetrants are required, min separation between cables and between cables and periphery of opening or the sleeve is 1/8 in. (3 mm). Cables to be rigidly supported on both sides of the floor or wall assembly. Any combination of the following types and sizes of cables may be used: A. Max 400 pair No. 24 AWG (or smaller) copper conductor cable with polyvinyl chloride (PVC) or plenum -rated jacketing and insulation. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. C us Created or Revised: October 4, 2022 C- S T I re o (800)992-1180 • (908)526-8000 •FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGEGE 1 1 0F4 OF 2 B. Max 3/C No. 2/0 AWG (or smaller) aluminum or copper conductor service entrance cable with PVC insulation and jacket. C. Max 3/C No. 2/0 AWG (or smaller) copper conductor PVC jacketed aluminum clad or steel clad TECK 90 cable. D. Max 3/C No. 8 AWG (or smaller) nonmetallic sheathed (Romex) cable with copper conductors, PVC insulation and jacket. E. Max 1/C 1000 kcmil (or smaller) copper conductor power cable with XLPE or PVC insulation and XLPE or PVC jacket. F. Max RG59/U (or smaller) coaxial cable with fluorinated ethylene or plenum -rated insulation and jacketing. G. Max 62.5/48 fiber optic cable with PVC or plenum -rated insulation and jacketing. H. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with PVC or plenum -rated insulation and jacket. 3A. Through Penetrating Product* -- (Not Shown) - Max 4/C No. 2/0 AWG (or smaller) steel or aluminum Armored Cable+ or Metal Clad Cable+ with copper or aluminum conductors. Diam of cable bundle (Item 3) including armored cable not to exceed 4 in. (102 mm). Through penetrating product to be rigidly supported on both sides of a floor or wall assembly. AFC CABLE SYSTEMS INC 4. Packing Material -- Min 2, 3 or 4 in. (51, 76 or 102 mm) thickness of min 4 pcf (64 kg/m3) density mineral -wool batt insulation tightly packed into opening as a permanent form for 2, 3 or 4 hr fire rated assemblies, respectively . Packing material to be recessed from top edge of sleeve or from top surface of concrete in cast concrete floor assemblies to accommodate the required thickness of fill material. Packing material to be recessed from both edges of sleeve or from both surfaces of assembly in walls and in floor constructed with hollow -core precast concrete units to accommodate the required thickness of fill material. When the annular space between the sleeve and the periphery of the opening exceeds 2 in. (51 mm), mineral -wool batt insulation tightly packed to a 3 in. depth and recessed from the top surface of the floor or both surfaces of the wall in order to accommodate the required thickness of sealant (Item 5, not shown). Otherwise, packing material is optional in annular space between the sleeve and the periphery of the opening. 5. Fill, Void or Cavity Material* -- Sealant or Putty -- Min 1/2 in. (13 mm) thickness of sealant applied within the annulus between steel sleeve and periphery of the opening, flush with the top surface of the floor or both surfaces of the wall. Min 1/2 in. (13 mm) diam bead of sealant shall be applied at point contact locations between sleeve and concrete interface on top surface of floor or both surfaces of the wall. Min 1/2 in. (13 mm) thickness of fill material applied within the annulus for 2 and 3 hr F Ratings. Min 3/4 in. (19 mm) thickness of fill material applied with the annulus for 4 hr F Rating. In floors, fill material to be installed flush with top edge of sleeve or top surface of floor. In walls and in floor constructed of hollow -core precast concrete units, fill material to be installed flush with both ends of sleeve or both surfaces of assembly. F, T, FT, FH, and FTH Ratings of firestop system are dependent upon the through opening size, thickness of concrete, sleeve type and percent cable fill, as shown in the following table: Max Opening Diam Min Concrete Thickness Optional Sleeve T Cable Type Percent F Rating T, FT, FH, FTH Rating 6 in. (152mm) 2-1/2 in. (64mm) PVC A to H, 3A 37 2 hr 0 hr 6 in. (152mm) 2-1/2 in. (64mm) PVC H 45 2 hr 0 hr 6 in. (152mm) 2-1/2 in. (64mm) Steel A to H, 3A 37 2 hr 0 hr 6 in. (152mm) 2-1/2 in. (64mm) Steel H 45 2 hr 0 hr 6 in. (152mm) 4-1/2 in. (114mm) Steel A to H, 3A 34 3 hr 1/2 hr 6 in. (152mm) 4-1/2 in. (114mm) Steel H 45 3 hr 1/2 hr 2 in. (51 mm) 4-1/2 in. (114mm) Steel H 40 3 hr 2-3/4 hr 2 in. (51 mm) 4-1/2 in. (114mm) Steel H 40 4 hr 2-3/4 hr SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant. When min floor or wall thickness is 4-1/2 in. (114 mm), SpecSeal Putty may be used. L Ratings apply only when SpecSeal Series SSS or SpecSeal LCI Sealants are used. *Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc.VLS 1 I ® (800)992-1180 • (908)526-8000 • FAX ( Created or Revised: October 4, 2022 us C-AJ-3154 908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 OF 2 Classified by FEB] ❑� Underwiters Laboratories, Inc. _ to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-A-3021 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 2, 3 and 4 Hr (See Items 1 and 3) F Ratings - 2, 3 and 4 Hr (See Items 1 and 3) T Ratings - 1/4, 1/2, 1-3/4 and 2 Hr (See Items 1, 2, 3 and 4) FT Ratings - 1/4, 1/2, 1-3/4 and 2 Hr (See Items 1, 2, 3 and 4) L Rating At Ambient - Less Than 1, 1.3, 4 or 7 CFM/Device FH Ratings - 2, 3 and 4 Hr (See Items 1 and 3) Module (See Item 3) L Rating At 400 F - Less Than 1, 2 or 3 CFM/Device Module FTH Ratings - 1/4, 1/2, 1-3/4 and 2 Hr (See Items 1, 2, 3 and 4) (See Item 3) L Rating At Ambient - Less Than 1, 1.3, 4 or 7 CFM/Device Module (See Item 3) L Rating At 400 F - Less Than 1, 2 or 3 CFM/Device Module (See Item 3) 3 A 1 2 2 ,-- 3 a a A Section A -A 1. Floor Assembly - Reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. The min concrete thickness for a 2 hr F and FH Ratings and for a 1/4 hr T, FT and FTH Ratings is 2-1/2 in. (64 mm). The min concrete thickness for a 3 hr F and FH Ratings and for a 1/2 hr T, FT and FTH Ratings is 4-1/2 in. (114 mm). The min concrete thickness for a 4 hr F and FH Ratings and for a 1-3/4 hr or 2 hr T, FT and FTH Ratings is 6 in. (152 mm). Diam of opening to be 4 in. (102 mm). 2. Firestop Device* - One firestop device module centered within the opening. The firestop device module consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop device module to be installed in conjunction with kick -in plate in accordance with the accompanying installation instructions. Kick -in plate consists of steel plate with vertical flanges on the top surface and with spring steel locking clips and intumescent foam wedges on the bottom surface. Kick -in plate secured to firestop device module with steel set screws in each of the four vertical flanges. Device with kick -in plate inserted into 4 in. (102 mm) diam core hole from top of floor and pushed into opening until bottom of plate is flush with the top surface of the floor to lock the device in position. The firestop device module is to be installed with its ends projecting an equal distance above and below the floor surfaces. For 1-3/4 or 2 hr T, FT and FTH Ratings, the firestop device module is to be installed to project 6 in. (152 mm) above the floor and 4-1/2 in. (114 mm) into the floor. When the firestop device module is cast or grouted into the floor assembly the T, FT and FTH Ratings are 2 hr. SPECIFIED TECHNOLOGIES INC - EZ PATH Series 33 Fire Rated Pathway AP Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. �� us Created or Revised: January 23, 2014 F-A-3021 S T I o (800)992-1180 • (908)526-8000 9 FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Websitemww.stifirestop.com PAGE 1 OF 2 3. Cables - Cables may represent a 0 to 100 percent visual fill within the loading area for the firestop device module. Cables to be rigidly supported on both sides of the floor assembly. Any combination of the following types of cables may be used: A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) or plenum -rated jacketing and insulation. B. Max 750 kcmil single copper conductor power cable with XLPE jacket and insulation C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation. D. Max 3/C No. 2/0 AWG metal clad or armored cable with steel or aluminum jacket. E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket. F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation. G. Coaxial cable with fluorinated ethylene or PVC insulation and jacketing having a max diam of 5/8 in. (16 mm). H. Optical fiber cable with PVC or polyethylene (PE) jacket and insulation and having a max diam of 5/8 in. (16 mm). When Item 3A is used, the max size of cable for 1-3/4 hr or 2 hr T, FT and FTH Ratings is 100 pair. When Item 3A or 313 is used, an extension module (Item 4) is required to attain 1-3/4 hr or 2 hr T, FT and FTH Ratings. Otherwise, the T, FT and FTH Ratings are 1/2 hr. When Item 3A is used, the max size of cable is 200 pair for the 3 hr F and FH Ratings. Otherwise, the F and FH Ratings are 2 hr. The L Rating for each empty firestop device module is less than 1 cfm at ambient and at 400F. When Item 3A is used, the L Rating for each firestop device module with 100 percent visual cable fill is 4 cfm at ambient and 3 cfm at 400F. When Item 3F is used, the L Rating for each firestop device module with 100 percent visual cable fill is 1.3 cfm at ambient and less than 1 cfm at 400F. When Item 3G or 3H is used, the L Rating for each firestop device module with 100 percent visual cable fill is 7 cfm at ambient and 2 cfm at 400F. 4. Firestop Device" - Extension Module - (Optional, Not Shown) - Module attached to top of 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long firestop device (Item 2) to increase its length. Each module consists of a 3 by 3 by 6 in. (76 by 76 by 152 mm) long galv steel tube with an intumescent material lining. Extension module to be installed in accordance with the accompanying installation instructions. When Item 4 is used with Item 3A or 313, the T, FT and FTH Ratings are 1-3/4 or 2 hr dependent upon the use or non-use of the kick -in plate. SPECIFIED TECHNOLOGIES INC - EZ PATH Extension +Bearing the UL Listing Mark Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. �� S T I Created or Revised: January 23, 2014 us I F-A-3021 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-A-3026 ❑■ ; ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 2 Hr F Rating - 2 Hr T Rating - 1 Hr FT Rating - 1 Hr FH Rating - 2 Hr FTH Rating - 1 Hr 4 3 A 0 2 3 o 4 A Section A -A 1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Floor may also be constructed of any min 6 in. (152 mm) thick hollow -core Precast Concrete Units*. See Precast Concrete Units category (CFTV) in the Fire Resistance Directory for names of manufacturers. 2. Steel Sleeve - Nom 4 in. (102 mm) diam steel electrical metallic tubing (EMT), steel conduit, Schedule 5 (or heavier) steel pipe or rigid steel conduit cast or grouted into concrete floor. Sleeve to extend min 3/4 in. (19 mm) to max 2 in. (51 mm) from top surface of floor and installed flush with the bottom surface of the floor. 3. Firestop Device* - One firestop device module centered within the steel sleeve. The firestop device module consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop device module to be installed in accordance with the accompanying installation instructions. Firestop device module secured in place by means of split steel restraint plate sized to accommodate the firestop device module. Steel restraint plate provided with an intumescent gasket and sized to cover the space between the firestop device module and the steel sleeve. Steel restraint plate installed on top end of steel sleeve and secured to firestop device module and steel sleeve with steel set screws. The firestop device module is to be installed with its ends projecting an equal distance beyond each edge of the steel sleeve. SPECIFIED TECHNOLOGIES INC - EZ PATH Series 33 Fire Rated Pathway IF Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. us Created or Revised: January 23, 2014 T I �° PAGE3026 . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com OF2 4. Cables - The cables may represent a 0 to 100 percent visual fill within the loading area for the firestop device module. Cables to be rigidly supported on both sides of the floor assembly. Any combination of the following types of cables may be used: A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation or with plenum rated jacketing and insulation. B. Max 350 kcmil single copper conductor power cable with XLPE jacket and insulation. C. Max VC No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation. D. Max 3/C No. 10 AWG metal clad or armored cable with steel or aluminum jacket. E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket. F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation. G. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation. H. Max RG/U coaxial cable with fluorinated ethylene insulation and jacketing. I. Fiber optic cable with PVC or polyethylene (PE) jacket and insulation having a max diam of 5/8 in. (16 mm). J. Aluminum or steel armored optical fiber cables jacketed with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation having a max diam of 5/8 in. (16 mm). * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 t us S T I o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Websitemww.stifirestop.com AGE2 26 PAGE 2 OF 2 Classified by ❑■ ❑■ Underwiters Laboratories, Inc. IL to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-A-3054 ■ ❑r ,. ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 2, 3 and 4 Hr (See Items 1 and 4) F Ratings - 2, 3 and 4 Hr (See Items 1 and 4) T Ratings - 0 and 1/2 Hr (See Item 4) FT Ratings - 0 and 1/2 Hr (See Item 4) L Rating At Ambient - Less than 1 to 2.3 CFM/Device Module FH Ratings - 2, 3 and 4 Hr (See Items 1 and 4) (See Item 3) L Rating At 400 F - Less than 1 to 2.3 CFM/Device Module (See FTH Ratings - 0 and 1/2 Hr (See Item 4) Item 3) L Rating At Ambient - Less than 1 to 2.3 CFM/Device Module (See Item 3) L Rating At 400 F - Less than 1 to 2.3 CFM/Device Module (See Item 3) A 3 1 O O o' or 2 o G Lalw- A 4 Section A -A 1. Floor Assembly - Min 2-1/2 in (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete floor. Min 4 1/2 in. (114 mm) floor thickness required for 3 and 4 Hr F and FH Ratings. Floor may also be constructed of any UL Classified hollow -core Precast Concrete Units*. Diam of opening is 6 in. (152 mm). Steel sleeve (Item 2) is required for floors constructed of hollow -core Precast Units. See Precast Concrete Units (CFTV) category in the Fire Resistance Directory for names of manufacturers. 2. Steel Sleeve - (Optional) - Nom 6 in. (152 mm) diam Schedule 10 to Schedule 40 steel pipe or rigid steel conduit cast or grouted into concrete floor flush with floor surfaces. 3. Firestop Device* - The firestop device module consists of a 4 by 4 5/8 by 14 in. (102 by 118 by 356 mm) long galv steel tube with an intumescent material lining. Firestop device module to be installed in accordance with the accompanying installation instructions. Firestop device module secured in place by means of two "L" shaped steel floor brackets installed with gasket material supplied with the product. Each floor bracket is secured to the device module by means of an integral hook and eye window attachment. Floor brackets are secured together forming the rectangular floor plate by means of steel screws and nuts supplied with the product. Floor plate to be secured to the top surface of the floor through predrilled holes in the floor plate using nom 3/16 in. (4.8 mm) by min 1-1/4 in. (32 mm) long concrete screws. As an option, the device may be cast or grouted into floor assembly. When the device is cast or grouted in place, the split floor plate is optional. The L Ratings vary according to whether the device module is blank (no cables) or loaded (with cables) and which cable type and size is used, as tabulated below: Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. us Created or Revised: April 14, 2016 F-A-3054 S1 I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 1 OF 2 Device Cable Type L-Rating (CFM) Ambient 400 °F 0% - Less Than 1 Less Than 1 1-25% 4A-41 1.5 1.5 26-50% 4A-41 2.3 2.3 51-75% 4A-41 2.3 2.3 76-100% 4A-41 2.3 2.3 SPECIFIED TECHNOLOGIES INC - EZ PATH Series 44+ Fire Rated Pathway 3A. Firestop Device* - Extension Module - (Optional, Not Shown) - Module attached to ends of firestop device (Item 3) to increase its length to facilitate installation in thicker floors. Each module consists of a 4 by 4-5/8 by 6 in. (102 by 118 by 152 mm) long galv steel tube with an intumescent material lining. Extension module to be installed in accordance with the accompanying installation instructions. SPECIFIED TECHNOLOGIES INC - EZ PATH Series 44+ Extension 4. Cables - Cables may represent a 0 to max 100 percent visual fill within the loading area for the firestop device module. Cables to be rigidly supported on both sides of the floor assembly. Any combination of the following types of cables may be used: A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) or plenum -rated jacketing and insulation. B. Max 750 kcmil single copper conductor power cable with XLPE jacket and insulation C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation. D. Max 3/C No. 2/0 AWG metal clad or armored cable with steel or aluminum jacket. E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket. F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation. G. Coaxial cable with fluorinated ethylene or PVC insulation and jacketing having a max diam of 5/8 in. (16 mm). H. Optical fiber cable with PVC or polyethylene (PE) jacket and insulation and having a max diam of 5/8 in. (16 mm). I. Max RG6/U coaxial cable with fluorinated ethylene, polyethylene (PE), PVC or plenum rated jacketing and insulation. When Item 4A, 413, 4C, 4D, 4E or 41 is used, the max F and FH Ratings are 3 hr. When Item 4F, 4G, or 4H is used, the max F and FH Ratings are 4 hr. When cable fill within the device is min 0 percent (empty) to max 20 percent, the T, FT and FTH Ratings are 0 Hr. When cable fill within the device is greater than 20 percent, the T, FT and FTH Ratings are 1/2 Hr. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: April 14, 2016 us F-A-3054 T I ® (800)992-1180 • (908)526-8000 . FAX (908)231-8415 • E-Mail:techserv@stifirestop.com . Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-C-3010 ❑■ ; ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 1 Hr F Rating - 1 Hr T Ratings - 1 Hr FT Ratings - 1 Hr FH Rating - 1 Hr FTH Ratings - 1 Hr D 2 4 1B 4 2B 3 2C 1 1C 4 4 2D 2 1. Floor -Ceiling Assembly - The 1 hr fire -rated solid or trussed lumber joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory. The general construction features of the floor -ceiling assembly are summarized below: A. Wood Joists - Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. B. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of floor opening is 3 in. (76 mm). C. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as specified in the individual Floor -Ceiling Design. Max diam of opening is 3 in. (76 mm). 2. Chase Wall - (Optional) - The through penetrant (Item 3) may be routed through a single, double or staggered wood stud/gypsum board chase wall and shall include the following construction features: A. Studs - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate - Nom 2 by 4 in. (51 by 102 mm) or 2 by 6 in. (51 by 152 mm) lumber plates or double nom 2 by 4 in. (51 by 102 mm) lumber plates tightly butted together. Circular opening to be centered in sole plate. Sole plate to be min 1 in. (25 mm) wider than diam of opening. Max diam of opening in sole plate is 3 in. (76 mm). C. Top Plate - The single or double top plate shall consist of one or two nom 2 by 4 in. (51 by 102 mm) or nom 2 by 6 in. (51 by 152 mm) lumber plates or one or two sets of parallel nom 2 by 4 in. (51 by 102 mm) lumber plates tightly butted together. Circular opening to be centered in top plate. Top plate to be min 1 in. (25 mm) wider than diam of opening. Max diam of opening in top plate is 3 in. (76 mm). D. Gypsum Board* - Min 1/2 in. (13 mm) thick gypsum board. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: June 05, 2015 TI . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com 3. Cables - Aggregate cross -sectional area of cable in opening to be max 45 percent of the cross -sectional area of the opening. The annular space between the cable bundle and the periphery of the opening to be min 0 in. (point contact) to max 1 in. (0 to 25 mm). Cables to be rigidly supported on both sides of the floor -ceiling assembly. Any combination of the following types and sizes of copper conductor cables may be used: A. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket. B. Type RG 59/U coaxial cable with polyethylene (PE) insulation and PVC jacket. C. Max 3/C with ground 2/0 AWG aluminum conductor SER cable with PVC insulation and jacket. D. Max 3/C No. 8 AWG steel or aluminum jacketed metal clad or armored clad cable. E. Max 3/C No. 10 AWG with ground Type NM nonmetallic sheathed (Romex) cable with PVC insulation and jacket. 4. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) thickness of fill material applied around cable bundle within the annulus on top surface of chase wall sole plate or top surface of floor. Min 1/2 in. (13 mm) thickness of fill material applied within the annulus of the top plate flush with the bottom surface of the top plate or bottom surface of gypsum board. Min 1/2 in. (13 mm) bead of fill material applied at the cable/lumber plate or cable/floor or ceiling interfaces at point contact locations on both sides of assembly. SPECIFIED TECHNOLOGIES INC - Type WF300 Caulk *Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: June 05, 2015 us S T I o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Websitemww.stifirestop.AGEF-C2 PAGE 2 com 10 OF 2 Classified by Underwiters Laboratories, Inc. p❑� to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-C-3103 ❑■ . ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 1 Hr F Rating - 1 Hr T Rating - 3/4 Hr FT Rating - 3/4 Hr FH Rating - 1 Hr FTH Rating - 3/4 Hr 3 A 1 ® ° 2 2 1B ° 3 • A 1C 2A umo Section A -A 1. Floor -Ceiling Assembly - The 1 hr fire -rated solid or trussed lumber joist Floor -Ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor -Ceiling Designs in the UL Fire Resistance Directory, as summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Opening in flooring system to be max 1/4 in. (6 mm) larger then width and height dimensions of firestop device(s). B. Joists - Nom 10 in. (254 mm) deep (or deeper) lumber and steel joist, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* - Nom 4 ft (1.2 m) wide by 5/8 in. (16 mm) thick. Gypsum board directly attached to joists or attached to furring channels as specified in the individual Floor -Ceiling Design. Opening in gypsum board to be max 1/4 in. (6 mm) larger then width and height dimensions of firestop device(s). 2. Firestop Device* - One, two, or three firestop device modules ganged together. Each firestop device module consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop device modules to be installed in conjunction with Item 2A and in accordance with the accompanying installation instructions. The space between the firestop device module(s) and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 1/4 in. (6.4 mm). Firestop device module(s) secured in place by means of steel plates installed with gasketing material supplied with product. Steel plates installed on both sides of floor/ceiling and secured to each device by means of steel set screws provided with device. Each firestop device module and extension module (Item 2A) is to be installed with ends projecting an equal distance beyond each surface of the floor/ceiling assembly. SPECIFIED TECHNOLOGIES INC - EZ PATH Series 33 Fire Rated Pathway Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. �� us T I Created or Revised: January 23, 2014 F-C-3103 ® (800)992-1180 9 (908)526-8000 9 FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com 9 Webs ite:www.stifirestop.com PAGE 1 OF 2 2A. Firestop Device" - Extension Module - Module attached to ends of 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long firestop device (Item 3) to increase its length to facilitate installation in floor/ceiling. Each module consists of a 3 by 3 by 6 in. (76 by 76 by 152 mm) long galv steel tube with an intumescent material lining. Extension module to be installed in accordance with the accompanying installation instructions. Firestop device (Item 2) and extension module(s) secured in place by means of steel plates installed with gasketing material supplied with product. Steel plates installed on both sides of floor/ceiling and secured to each device or extension module(s) by means of steel set screws provided with plates. Firestop device and extension module(s) assembly to be installed with ends projecting an equal distance beyond each surface of the floor/ceiling assembly. SPECIFIED TECHNOLOGIES INC - EZ PATH Extension 3. Cables - The cables may represent a 0 to 100 percent visual fill within the loading area for each firestop device module. Cables to be rigidly supported on both sides of the floor/ceiling assembly. Any combination of the following types of cables may be used: A. Max 200 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation. B. Max 350 kcmil single copper conductor power cable with XLPE jacket and insulation. C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation. D. Max 3/C No. 10 AWG metal clad or armored cable with steel or aluminum jacket. E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket. F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation. G. Max RG/U coaxial cable with fluorinated ethylene insulation and jacketing. H. Fiber optic cable with PVC or polyethylene (PE) jacket and insulation having a max diam of 5/8 in. (16 mm). * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I o Created or Revised: January 23, 2014 I F-C-3103 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. W-L-3036 F Ratings - 1 and 2 Hr (See Item 1) T Rating - 1/2 Hr Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Diam of opening to be 1/2 to 1 in. (13 to 25 mm) larger than diam of cable bundle. Max diam of opening is 4 in. (102 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Cables - Aggregate cross sectional area of cable in opening to be max 45 percent of the cross -sectional area of the opening. The annular space between the cable bundle and the periphery of the opening shall be min 0 in. (point contact) to max 3/4 in. (0 to 19 mm). Cables to be rigidly supported on both sides of wall assembly. Any combination of the following types and sizes of copper conductor cables may be used: A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket. B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket. C. Type RG/U coaxial cable with polyethylene (PE) insulation and jacket. D. Fiber optic communication cable jacketed with PVC and having max OD of 5/8 in. (16 mm). E. Through Penetrating Products* - Max 3/C No. 8 AWG Metal -Clad Cable+. F. Max 3/C (with ground) (or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacket. G. Max 3/C (with ground) No. 2/0 AWG aluminum or copper conductor SER cable with PVC insulation and jacket. 3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. At the point contact location, min 1/2 in. (13 mm) diam bead of fill material applied at the cable bundle/gypsum board interface. SPECIFIED TECHNOLOGIES INC - Type WF300 Caulk * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. + Bearing the UL Listing Mark IF Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 �°stifirestop.com • Website:www.stifirestop.com GE 1 OF61 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery Classified by System No. W-L-3169 Underwiters Laboratories, Inc. F Ratings - 1 and 2 Hr (See Item 1) to ASTM/UL1479 (ASTM E814) T Ratings - 1/4 and 3/4 Hr (See Item 2A) . ■ Section A -A Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-5/8 in. (92 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 5 in. (127 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Cables - Max 4-1/2 in. diam tight bundle of cables to be installed eccentrically or concentrically within the opening. The annular space between the cables and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 1/2 in. (13 mm). Cable bundle to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of cables may be used: A. Max 200 pair No. 24 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) insulation and jacketing material. B. Max 1/C No. 350 kcmil (or smaller) copper conductor cable with cross -linked polyethylene (XLPE) jacket. C. Max 7/C No. 12 AWG (or smaller) copper conductor power and control cables with XLPE or PVC insulation with XLPE or PVC jacket. D. Max 3/C No. 2/0 AWG (or smaller) copper or aluminum conductor SER cables with PVC insulation and jacket. E. Max 3/C No. 2/0 AWG (or smaller) copper conductor PVC jacketed aluminum clad or steel clad TEK cable. F. Max 110/125 fiber optic (F.O.) cable with PVC insulation and jacket. G. Max 3/C with ground No. 8 AWG (or smaller) copper conductor NM cable (Romex) with PVC insulation and jacket. H. Max RG/U coaxial cable with fluorinated ethylene insulation and jacket. I. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with Hylar jacket and insulation. J. Max 4/C (with ground) No. 300 kcmil (or smaller) aluminum conductor SER cables with PVC insulation and jacket. 2A. Through Penetrating Product* - As an alternate to the cables (Item 2), max 4 in. (102 mm) diam tight bundle of max 4/C No. 2/0 AWG (or smaller) aluminum or steel Armored Cable+ or Metal Clad Cable+ installed within the opening. Annular space between through -penetrating products and periphery of opening to be min 0 in. (0 mm, point contact) to max 1 in. (25 mm). Through penetrating product rigidly supported on both sides of floor or wall assembly. When Armored Cable or Metal Clad Cable is used, T Rating is 1/4 hr. 3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. Sealant to be forced into interstices of cable bundle to max extent possible. At point contact location, min 1/4 in. (6 mm) diam bead of fill material applied at cable bundle/gypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. IF Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 �TI� (800)992-1180. (908)526-8000 •FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com GE 1 OF1 Classified by System No. W-L-3171 �2 L.�Underwiters Laboratories, Inc. F Ratings - 1 and 2 Hr (See Item 1) 1 to ASTM/UL1479 (ASTM E814) T Ratings - 1/4 and 3/4 Hr (See Item 2A) a FVk MW Section A -A Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 3-5/8 in. wide and spaced max 24 in. OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 1 in. larger than OD of cable (Item 2). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Cable - One cable to be installed eccentrically or concentrically within the opening. The annular space between the cable and the periphery of the opening shall be min 0 in. (point contact) to max 1 in. Cable to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of cable may be used: A. Max 200 pair No. 24 AWG (or smaller) copper conductor with polyvinyl chloride (PVC) insulation and jacketing material. B. Max 1/C No. 350 kcmil (or smaller) copper conductor cable with cross -linked polyethylene (XLPE) jacket. C. Max 7/C No. 12 AWG (or smaller) copper conductor power and control cables with XLPE or PVC insulation with XLPE or PVC jacket. D. Max 3/C No. 2/0 AWG (or smaller) copper or aluminum conductor SER cables with PVC insulation and jacket. E. Max 3/C No. 2/0 AWG (or smaller) copper conductor PVC jacketed aluminum clad or steel clad TEK cable. F. Max 110/125 fiber optic (F.O.) cable with PVC insulation and jacket. G. Max 3/C with ground No. 8 AWG (or smaller) copper conductor NM cable (Romex) with PVC insulation and jacket. H. Max RG/U coaxial cable with fluorinated ethylene insulation and jacket. I. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with Hylar jacket and insulation. 2A. Through Penetrating Product* - As an alternate to the cable (Item 2), one max 4/C No. 2/0 AWG (or smaller) aluminum or steel Armored Cable+ or Metal Clad Cable+ installed within the opening. Annular space between through -penetrating product and periphery of opening to be min 0 in. (point contact) to max 1 in. Through penetrating product rigidly supported on both sides of wall assembly. When Armored Cable or Metal Clad Cable is used, T Rating is 1/4 hr. AFC CABLE SYSTEMS INC Fill, Void or Cavity Material* - Sealant - Min 5/8 in. thickness of fill material applied within annulus, flush with both surfaces of wall assembly. At point contact location, min 1/4 in. diam bead of fill material applied at cable/gypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification such as Canada res ectivel . Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 �°stifirestop.com • Website:www.stifirestop.com GE 1 OF11 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery Classified by[oil {: 10 Underwriters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-3210 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1) T Rating - 3/4 Hr FT Rating - 3/4 Hr L Rating at Ambient - Less Than 1 CFM/sq ft (See Items 3 and 413) FH Ratings - 1 and 2 Hr (See Item 1) L Rating at 400°F - Less Than 1 CFM/sq ft (See Items 3 and 413) FTH Rating - 3/4 Hr L Rating at Ambient - Less Than 5.1 L/S/mZ (See Items 3 and 413) L Rating at 204°F - Less Than 5.1 L/S/m2 (See Items 3 and 413) A 1B 413 4B 2 3 .:.... 4A `::: 111 111 ,:, 111 111 111 111 3 111 111 :: 413 4A 1A 2 A Section A -A 1. Wall Assembly -- The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, V300, U400, V400, or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* -- Thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, V300, U400 , V400 or W400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 6-1/2 in. (165 mm) when sleeve (Item 2) is installed. Max diam of opening is 4 in. (102 mm) when sleeve is not used. The hourly F and FH rating of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. 2. Steel Sleeve -- (Optional) -- Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT), steel conduit, Schedule 5 (or heavier) steel pipe sleeve or min 0.016 in. thick (0.41 mm, No. 28 ga) galv steel sleeve installed flush with wall surfaces. The annular space between the steel sleeve and periphery of opening shall be min 0 in. (continuous point contact) to max 2 in. (51 mm). When Schedule 5 steel pipe or EMT is used, sleeve may be installed flush with or extend up to 18 in. (46 cm) beyond one or both wall surfaces. Steel sleeve may be installed at an angle not greater than 45 degrees from perpendicular. Schedule 5 steel pipe or EMT sleeves may extend continuously beyond one wall surface. Sleeve to be Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. C us Created or Revised: October 4, 2022 W-L-3210 S I 1 ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 2 rigidly supported when extending from the wall surfaces. 3. Cables -- Aggregate cross -sectional area of cables in opening when a steel sleeve (Item 2) is not used, or within steel sleeve to be max 48 percent of the aggregate cross -sectional area of the opening or sleeve. Cables to be bundled and rigidly supported on both sides of wall assembly. When the sleeve is installed, the annular space between the cables and the sleeve shall be min 0 in. (point contact) to max 1-1/2 in. (38 mm). When the sleeve (Item 2) is not used, the annular space between the cables and the opening shall be a min 0 in. (point contact) to a max 1/2 in. (13 mm). When L Ratings for penetrants are required, min separation between cables and between cables and periphery of opening or the sleeve os 1/8 in. (3 mm). Cable bundle, using cables described below, may penetrate the wall at an angle not greater than 45 degrees. Any combination of the following types and sizes of copper conductor cable may be used: A. Max 200 pair No. AWG (or smaller) copper conductor cable with polyvinyl chloride (PVC) or plenum -rated jacketing and insulation. B. Max 3/C No. 2/0 AWG (or smaller) aluminum or copper conductor service entrance cable with PVC insulation and jacket. C. Max 3/C No. 8 AWG (or smaller) nonmetallic sheathed (Romex) cable with copper conductors, PVC insulation and jacket. D. Max 7/C No. 2/0 AWG (or smaller) multiconductor power and control cables with XLPE or PVC insulation and XLPE or PVC jacket. E. Max RG/U (or smaller) coaxial cable with fluorinated ethylene or plenum -rated insulation and jacketing. F. Max 62.5/48 fiber optic cable with PVC or plenum -rated insulation and jacketing. G. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with PVC or plenum -rated insulation and jacket. H. Max 4/C No. 2/0 aluminum or copper conductor aluminum or steel Metal -Clad# or Armored -Clad# cable. I. Max 3/4-in. (19 mm) diam copper ground cable with or without a PVC jacket. 4. Firestop System -- The firestop system shall consist of the following: A. Packing Material -- When required (See table in Item 413), min 1 in. (25 mm) thickness of min 4.0 pcf (64 kg/m3) mineral wool batt insulation firmly packed into each end of sleeve (Item 2) as a permanent form. Packing material to be recessed from each end of sleeve as required to accommodate the required thickness of fill material. When the sleeve is not used, the packing material is not required. B. Fill, Void or Cavity Material* - Sealant or Putty -- When sleeve (Item 2) is used, fill material applied to appropriate thickness within steel sleeve as shown in the table below, flush with edges of steel sleeve on both surfaces of wall. Min 1/2 in. (13 mm) thickness of fill material installed into annular space between sleeve and wall flush with both surfaces of the wall. Min 1/2 in. (13 mm) diam bead of sealant or "rope" of putty shall be applied around the perimeter of the sleeve on each side of the wall when sleeve extends beyond surface of wall and is installed at continuous point contact. When sleeve is not used, a min 5/8 in. (16 mm) thickness of fill material shall be applied within the annulus, flush with both surfaces of the wall. At point contact location, apply min 1/4 in. (6 mm) diam bead of fill material at cable/gypsum board interface on both sides of the wall. Sealant or Putty Type Thickness, Packing Material In. mm Required SpecSeal Series SSS Sealant 1/2 in. (13) Yes or LCI Sealant SpecSeal Series SSS Sealant 1 in. (25) No or LCI Sealant SpecSeal Putty 1 in. (25) No SPECIFIED TECHNOLOGIES INC -- SpecSeal Series SSS Sealant, SpecSeal LCI Sealant or SpecSeal Putty L Ratings apply only when SpecSeal Series SSS or SpecSeal LCI Sealants are used. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: October 4, 2022 C u T I ® 800 992-1180.908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com GE20Fo2 Classified by HVa Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-3377 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1, 2, 3 and 4 Hr (See Items 1 and 3) F Ratings - 1, 2, 3 and 4 Hr (See Items 1 and 3) T Rating - 3/4, 1, 1-1/2 and 2 Hr (See Item 3) FT Rating - 3/4, 1, 1-1/2 and 2 Hr (See Item 3) L Rating At Ambient - Less than 1 to 7 CFM/Device Module (See FH Ratings - 1, 2, 3 and 4 Hr (See Items 1 and 3) Item 2) L Rating At Ambient - Less than 1 to 7 CFM/Device Module (See FTH Rating - 3/4, 1, 1-1/2 and 2 Hr (See Item 3) Item 2) L Rating At Ambient - Less than 1 to 7 CFM/Device Module (See Item 2) L Rating at 400 F - Less than 1 to 3 CFM/Device Module (See Item 2) A 3 1A 2 3 2 e e A 1B Section A -A B 1 2 3 3 2 B 1B Section B-B C 1 2 3 3 0 0 1B C Section C-C Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: S I April 14, 2016 W-L-3377 1 ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 3 1. Wall Assembly - The 1, 2, 3 or 4 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300, U400, V400 or W400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features: A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. See Table for opening sizes. The hourly F and FH Ratings are dependent upon the hourly rating of the wall in which it is installed. 2. Firestop Device* - Series 22 EZ Path device modules consist of a 1.4 by 1.4 by 10-1/2 in. (36 by 36 by 267 mm) long galv steel tube with an intumescent material lining. Series 33 EZ Path device modules consist of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Series 44+ EZ Path device modules consist of a 4 by 4-5/8 by 14 in. (102 by 118 by 356 mm) long galv steel tube with an intumescent material lining. Firestop device modules to be installed in accordance with the accompanying installation instructions. Firestop device modules secured in place by means of steel wall plates installed with gasketing material supplied with product. Steel wall plates installed on both sides of wall and secured to each device by means of steel screws provided with device. Firestop device module is to be installed with ends projecting an equal distance beyond each surface of the wall assembly. The annular space between the device and opening shall be min 0 in. (point contact) to max 1/8 in. (3 mm) for Series 22 device, max 1/2 in. (13 mm) for Series 33 device and max 1/4 in. (6 mm) for Series 44 device. The opening size and L Ratings for each device vary according to whether device module is blank (no cables) or loaded (with cables) and which cable type and size is used, as tabulated below: SPECIFIED TECHNOLOGIES INC - EZ PATH Series 22, 33 or 44+ Fire Rated Pathway Max Cable L-Rating (CFM) Opening Size Diam or Device Cable Fill Type Dimensions, in. (mm) Ambient 400' F Series 22 0% - 1.4 1.4 2 (51) or 1-3/4 x 1-3/4 44 x 44 Series 22 1-25% 3A Less Less 2 (51) or Than 1 Than 1 1-3/4 x 1-3/4 44 x 44 Series 22 26-50% 3A Less Less 2 (51) or Than 1 Than 1 1-3/4 x 1-3/4 44 x 44 Series 22 51-75% 3A Less Less 2 (51) or Than 1 Than 1 1-3/4 x 1-3/4 44 x 44 Series 22 76-100% 3A Less Less 2 (51) or Than 1 Than 1 1-3/4 x 1-3/4 44 x 44 Series 22 100% 3F Less Less 2 (51) or Than 1 Than 1 1-3/4 x 1-3/4 44 x 44 Series 33 0% _ Less Less 4 (102) or Than 1 Than 1 3-1/4 x 3-1/4 82 x 82 Series 33 100% 3A 4 3 4 (102) or 3-1/4 x 3-1/4 82 x 82 Series 33 100% 3F 1.3 Less 4 (102) or Than 1 3-1/4 x 3-1/4 82 x 82 Series 33 100% 7 2 or 3-10/4) 3H 3-1/4 x 82 x 82 Series 33 100% 31 1.8 1.8 (102) or 3-1/4 x 1x 82 Series 44+ 0% - Less Less 6 (152) or Than 1 Than 1 4-1/8 x 4-3/4 120 x 120 Series 44+ 1-25% 3A-31 1.5 1.5 6 (152) or 4-1/8 x 4-3/4 120 x 120 Series 44+ 26-50% 3A-31 2.3 2.3 6 (152) or 4-1/8 x 4-3/4 120 x 120 Series 44+ 51-75% 3A-31 2.3 2.3 4-1/8 x 4 152 or x 120 Series 44+ 76% 3A-31 2.3 2.3 6 (152) or 100% 4-1/8 x 4-3/4 120 x 120 Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. @ S T I Created or Revised: April 14, 2016 I W-L-3377 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 OF 3 2A. Firestop Device* - Extension Module - (Optional, Not Shown) - Module attached to ends of Series 33, Series 44+ firestop device (Item 2) to increase its length to facilitate installation in thicker walls. Each module consists of a galv steel tube with an intumescent material lining. Extension module to be installed in accordance with the accompanying installation instructions. When module is used, firestop device (Item 2) and extension module(s) secured in place by means of steel wall plates installed with gasketing material supplied with product. Steel wall plates installed on both sides of wall and secured to each device or extension module(s) by means of steel set screws provided with wall plates. Firestop device and extension module(s) assembly to be installed with ends projecting an equal distance beyond each surface of the wall assembly. SPECIFIED TECHNOLOGIES INC - EZ PATH Series 33 or Series 44+ Extension 3. Cables - Cables may represent a 0 to max 100 percent visual fill within the loading area for the firestop device module. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used: A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) or plenum -rated jacketing and insulation. B. Max 750 kcmil single copper conductor power cable with XLPE jacket and insulation C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation. D. Max 3/C No. 2/0 AWG metal clad or armored cable with steel or aluminum jacket. E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket. F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation. G. Coaxial cable with fluorinated ethylene or PVC insulation and jacketing having a max diam of 5/8 in. (16 mm). H. Optical fiber cable with PVC or polyethylene (PE) jacket and insulation and having a max diam of 5/8 in. (16 mm). I. Max RG6/U coaxial cable with fluorinated ethylene, polyethylene (PE), PVC or plenum rated jacketing and insulation. When Series 22 EZ Path device modules are used and when the hourly rating of the wall assembly is 1 hr, the T, FT and FTH Ratings are 3/4 hr except that for Items 3F, 3G and 3H, the T, FT and FTH Ratings are 1 hr. When the hourly fire rating of the wall assembly is 2 hr or greater, the T, FT and FTH Ratings are 3/4 hr when cables are installed. When no cables are installed within the device module, the T, FT and FTH Ratings are 1 hr in 1 hr walls and 1-1/2 hr for 2, 3 and 4 hr walls. When Item 3A, 313, 3C, 3D or 3E is used, the maximum F and FH Ratings are 2 hr. When max 200 pair No. 24 AWG telecommunication cable and/or 350 kcmil power cable is used or when Item 3F, 3G, 3H or 31 is used, the maximum F and FH Ratings are 4 hr. When Series 33 EZ Path device modules are used and when the hourly rating of the wall assembly is 1 hr, the T, FT and FTH Ratings are 3/4 hr. When the hourly fire rating of the wall assembly is greater than 1 hr, the T, FT and FTH Ratings are 314 hr when Item 3A, 313, 3C, 3D or 3E is used. Otherwise the T, FT and FTH Ratings are 1 hr. When Item 3A, 313, 3C, 3D or 3E is used, the maximum F and FH Ratings are 2 hr. When max 200 pair No. 24 AWG telecommunication cable is used or when Item 3F, 3G, 3H or 31 is used, the maximum F and FH Ratings are 4 hr. When Series 44 + EZ Path device modules are used and when Item 3A, 313, 3C, 3D or 3E is used, the max F and FH Ratings are 3 hr and the T, FT and FTH Ratings are 1 hr. When Item 3F or 3G is used, the max F and FH Ratings are 4 hr and the T, FT and FTH Ratings are 1-1/2 hr. When Item 3H or 31 is used, the max F and FH Ratings are 4 hr and the T, FT and FTH Ratings are 2 hr. When device empty, the T, FT and FTH Ratings are 1-1/2 Hr. +Bearing the UL Listing Mark * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: April 14, 2016 t YL us W-L-3377 T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Webs itemww.stifirestop.com PAGE 3 OF 3 Classified by p a Underwiters Laboratories, Inc. CLIVA14288 to ANSI/UL 1479 (ASTM E814) '' and ANSI/UL263 (ASTM E119) Wall -opening Protective Materials ❑� ti SpecSeal Power Shield Box Inserts, for use with flush device UL Listed Metallic Outlet Boxes without internal clamps installed with steel mud rings in framed wall assemblies. When protective material is used in outlet boxes on both sides of the wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. (610 mm) provided that the boxes are not installed back-to-back. Installation shall comply with the National Electrical Code (NFPA 70). The max outlet box dimensions, hourly rating, type of stud, use of stud cavity insulation and type of faceplate are tabulated below. Additional general construction features shall comply as follows: A. Studs - Unless otherwise specified, the minimum stud width is 3-1/2 in. (89 mm). B. Stud Cavity Insulation - Where indicated in the table below, stud cavity insulation to consist of min 3-1/2 in. (89 mm) thick fiberglass (min 0.5 pcf or 8 kg/m3) or mineral fiber (min 4 pcf or 64 kg/m3). Unless indicated as required, stud cavity insulation is optional. C. Wall Design - Stud composition is indicated in the table below. Wall construction shall comply with the individual U300, U400 or V400 Series Wall and Partition Design in the Fire Resistance Directory. D. Pad Dimensions - The minimum dimensions of the insert pad are shown in the table below. Pads may be cut to achieve dimensions shown in table and partial insert pads may be utilized. Product Max Outlet Box Outlet Outlet Pad Size, in. Rating, Stud Cavity Face Plate Putty Size in. mm Box Type Box Mfr mm hr Insulation Type Ball EP 23 2 x 3 x 2-1/4 - - 1-7/8 x 2-3/4 2 Steel No Steel - 51 x76x57 deep 48x70 EP 23 2 x 3 x 2-1/4 - - 1-7/8 x 2-3/4 2 Steel Yes Plastic - 51 x76x57 deep 48x70 EP 23 2 x 3 x 2-1/4 _ _ 1-7/8 x 2-3/4 1 Steel or Yes Plastic or - 51 x 76 x 57 deep48 x 70 Wood Steel EP 24 2-1/8 x 4 x 2-1/8 - - 1-7/8 x 3-3/4 2 Steel No Steel - 54 x 102 x 54 deep 48 x 95 EP 24 2-1/8 x 4 x 2-1/8 - - 1-7/8 x 3-3/4 2 Steel Yes Plastic - 54 x 102 x 54 deep 48 x 95 EP 24 2-1/8 x 4 x 2-1/8 _ _ 1-7/8 x 3-3/4 1 Steel or Yes Plastic or _ 54 x 102 x 54 deep48 x 95 Wood Steel EP 44 4 x 4 x 2-1/8 - - 3-3/4 x 3-3/4 2 Steel No Steel - 102 x 102 x 54 deep 95 x 95 EP 44 4 x 4 x 2-1/8 - - 3-3/4 x 3-3/4 2 Steel Yes Plastic - 102 x 102 x 54 deep 95 x 95 EP 44 4 x 4 x 2-1/8 _ _ 3-3/4 x 3-3/4 1 Steel or Yes Plastic or _ 102 x 102 x 54 dee 95 x 95 Wood Steel EP 45 4-11/16 x 4-11/16 x 2-1/8 _ _ 4-1/2 x 4-1/2 1 or 2 Steel or Yes Plastic or _ 119 x 119 x 54 deep114 x 114 Wood Steel EP 45 4-1/2 x 5 x 2-3/8 _ _ 4-1/2 x 4-1/2 1 or 2 Steel or Yes Plastic or _ 114 x 127 x 60 deep114 x 114 Wood Steel EP 45 4-1/2 x 14 x 2-1/2 _ _ 4-1/2 x 13-3/4 1 or 2 Steel or Yes Plastic or - 114 x 356 x 64 deep114 x 349 Wood Steel SpecSeal Putty Pads, for use with flush device UL Listed Metallic Outlet Boxes installed with steel mud rings or UL Listed Nonmetallic Outlet Boxes in framed wall assemblies. When protective material is used on outlet boxes on both sides of the wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. (610 mm) provided that the boxes are not installed back-to-back. Installation shall comply with the National Electrical Code (NFPA 70). Min 3/16 in. (5 mm) thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and to completely seal against the stud within the stud cavity. Adjoining pieces of moldable putty pads to be overlapped approx 1/2 in. (13 mm) at the seam. An additional 3/16 in. (5 mm) thickness of putty to be formed around the connector securing the end of each Type MC cable, electrical metallic tube (EMT) or conduit to the box. When nonmetallic box is used with Type NM cable, a 3/16 in. (5 mm) thickness of putty shall be formed around the cable at its connection to the box and extending a min of 1 in. (25 mm). The box composition, max device dimensions, hourly rating, type of stud and type of faceplate are tabulated below. Additional general construction features shall comply as follows: A. Studs - Unless otherwise specified, the minimum stud width is 3-1/2 in. (89 mm). B. Stud Cavity Insulation - Unless indicated as required, stud cavity insulation is optional and may consist of min 3-1/2 in. (89 mm) thick fiberglass (min 0.5 pcf or 8 kg/m3) or mineral fiber (min 4 pcf or 64 kg/m3). C. Wall Design - Stud composition is indicated in the table below. Wall construction shall comply with the individual U300, U400 or V400 Series Wall and Partition Design in the Fire Resistance Directory. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: October 30, 2013 T I ® 800 992-1180.908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 3 D. Metallic Outlet Boxes - Except as indicated in the table below, when steel outlet boxes are used and the boxes are interconnected by means of electrical metallic tube or conduit, a ball of putty is to be installed to plug the open end of each electrical metallic tube (EMT) or conduit within the outlet box. When MC cable is used and/or when the outlet boxes are not interconnected, the ball of putty is not required. E. Nonmetallic Outlet Boxes - The box manufacturer is indicated in the table below. Boxes shall bear a 2 hr rating under the "Outlet Boxes and Fittings Classified for Fire Resistance" category in the Fire Resistance Directory. Model Max Outlet Box Outlet Outlet Pad Size Rating, Stud Cavity Face Plate Putty in. mm Box TVpe Box Mfr in. mm hr Insulation TVpe Ball - 4 x 4 x 2-1/8 Steel N.A. - 1 Steel or - Steel No 102 x 102 x 54 deepWood - 4 x 4 x 2-1/8 Steel N.A. - 1 Steel or - Plastic Yes 102 x 102 x 54 deepWood _ 4-11/16 x 4-11/16 x 2-1/8 Steel N.A. - 1 or 2 Steel or Steel Yes 119 x 119 x 54 dee Wood - 4-1/2 x 5 x 2-3/8 Steel N.A. - 1 or 2 Steel or - Steel Yes 114 x 127 x 60 deepWood - 4-1/2 x 14 x 2-1/2 Steel N.A. - 1 or 2 Steel or - Steel Yes 114 x 127 x 60 deepWood - 3-3/4 x 4 x 3 Polyvinyl Lamson & Sessions 1 or 2 Wood - Plastic or N.A. 95 x 102 x 76 deep Chloride or Carton Steel _ 3-3/4 x 4 x 3 Phenolic Allied Moulded _ 1 or 2 Wood _ Plastic or N.A. 95 x 102 x 76 deep Prods Steel - 3-3/4 x 4 x 3 Polycarbonate Thomas & Betts - 1 or 2 Wood - Plastic or N.A. 95 x 102 x 76 deepSteel - 3-3/4 x 4 x 3 Phenolic Thomas & Betts - 1 or 2 Wood - Plastic or N.A. 95 x 102 x 76 deep Steel 2-1/4 x 3-3/4 x 2-3/4 Polyvinyl Pass & Seymour - 1 or 2 Wood _ Plastic or N.A. 57 x 95 x 70 deepChloride Steel SpecSeal Putty Pads , for use with maximum 4 by 4 by 2-1/8 in. (102 by 102 by 54 mm) deep flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and with steel faceplates in 1 hr or 2 hr fire rated gypsum board wall assemblies constructed with min 5-1/2 in. (140 mm) wide wood or steel studs and with stud cavities filled with fiberglass (nom 0.5 pcf or 8 kg/m3) or mineral fiber (nom 4 pcf or 64 kg/m3) insulation. When protective material is used on outlet boxes on both sides of the wall as directed, the boxes may be installed back-to-back provided that the boxes on opposite sides of the wall are not interconnected with conduit or, when interconnected, the open end of the conduit within the outlet box is filled with a ball of putty. Installation shall comply with the National Electrical Code (NFPA 70). Min 3/16 in. (5 mm) thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and to completely seal against the stud within the stud cavity. Adjoining pieces of moldable putty pads to be overlapped approx 1/2 in. (13 mm) at the seam. An additional 3/16 in. (5 mm) thickness of putty to be formed around the connector securing the end of each Type MC cable, electrical metallic tube (EMT) or conduit to the box. SpecSeal EP23, EP24 and EP44 Power Shield Box Inserts and SpecSeal Putty Pads, for use with maximum 4 by 4 by 1-1/2 or 2-1/8 in. (102 by 102 by 38 or 54 mm) deep flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and with steel or plastic faceplates in 1 hr or 2 hr fire rated gypsum board wall assemblies constructed with min 3-1/2 in. (89 mm) wide wood or steel studs. When both protective materials are used with outlet boxes on both sides of the wall as directed, the boxes may be installed back-to-back provided that the backs of the boxes are minimum 1/2 in. (13 mm) apart and provided that the boxes are not interconnected. Installation shall comply with the National Electrical Code (NFPA 70). Min 3/16 in. (5 mm) thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and to completely seal against the stud within the stud cavity. Adjoining pieces of moldable putty pads to be overlapped approx 1/2 in. (13 mm) at the seam. An additional 3/16 in. (5 mm) thickness of putty to be formed around the connector securing the end of each Type MC cable, electrical metallic tube (EMT) or conduit to the box. An insert pad shall be installed to completely cover the back inside surface of each outlet box. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I. Created or Revised: October 30, 2013 L IV I (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE OF 3 SpecSeal Putty Pads, for use with max 5 by 5 by 2 7/8 in. (127 by 127 by 73 mm) deep flush device UL Listed Metallic Outlet Boxes or UL Listed Communications -Circuit Accessories manufactured by Randl Industries Inc for use in 1 hr or 2 hr fire rated gypsum board wall assemblies framed with min 3-5/8 in. (92 mm) wide wood or steel studs and constructed as specified in the individual U300, U400, or V400 or W400 Series Wall and Partition Designs in the Fire Resistance Directory. Metallic outlet boxes to be provided with UL Listed Signal Appliance with steel cover plate manufactured by Cooper Wheelock Inc. Moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud unless otherwise noted) including nailing tabs and to completely seal against the stud within the stud cavity. Multiple moldable putty pads may be installed on an outlet box to attain the required minimum thickness of putty material. Additional putty material used to seal around each conduit and/or cable fitting on the exterior of each box. A min 3/16 in. (4.8 mm) thickness of putty material is required on the exterior surfaces of flush device boxes in 1 and 2 hr fire rated Wall and Partition Designs. When the moldable putty pad outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. (610 mm) provided that the outlet boxes are not installed back to back, except as noted. SpecSeal EP55 Power Shield Box Inserts, for use with max 5 by 5 by 2 7/8 in. (127 by 127 by 73 mm) deep flush device UL Listed Metallic Outlet Boxes or UL Listed Communications -Circuit Accessories manufactured by Randl Industries Inc for use in 1 hr or 2 hr fire rated gypsum board wall assemblies framed with min 3-5/8 in. (92 mm) wide wood or steel studs and constructed as specified in the individual U300, U400, or V400 or W400 Series Wall and Partition Designs in the Fire Resistance Directory. Metallic outlet boxes to be provided with UL Listed Signal Appliance with steel cover plate manufactured by Cooper Wheelock Inc. Power Shield Box Insert is to be applied to the back surface of the box and may be slit to accommodate communications -circuit accessories. When the Power Shield Box Insert is used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. (610 mm) provided that the outlet boxes are not installed back to back, except as noted. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. ST I Created or Revised: October 30, 2013 ® CLIV I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 3 OF 3 Classified by a Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System NO. C-/o►J-5087 �■ ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 2 Hr F Rating - 2 Hr T Rating - 1 Hr FT Rating - 1 Hr L Rating At Ambient - Less Than 1 CFM/sq ft FH Rating - 2 Hr L Rating At 400 F - Less Than 1 CFM/sq ft FTH Rating - 1 Hr L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft A 3 2 5B 5B 2 1 .. a. it 4 :: 3 5 A Section A -A 1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete floor or min 5 in. (127 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete wall. Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow -core Precast Concrete Units*. Wall may also be constructed of any UL Classified Concrete Blocks* Max diam of opening is 30 in. (762 mm). Max diam of opening in floor constructed of hollow -core precast concrete units is 7 in. (178 mm). See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 2. Steel Sleeve - (Optional) - Nominal 30 in. (762 mm) diam (or smaller) Sch 10 (or heavier) steel pipe sleeve or No. 26 ga (0.022 in. or 0.56 mm thick) sheet steel sleeve with square anchor flange spot welded to the sleeve at approx mid -height. Sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces. 3. Through Penetrants - One metallic pipe to be installed either concentrically or eccentrically within the firestop system. Pipe to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes may be used: A. Steel Pipe - Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 24 in. (610 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type M (or heavier) copper tubing. D. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. Ap Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. ST I Created or Revised: January 23, 2014 C-AJ-5087 I (800)992-1180 • (908)526-8000 • FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 1 OF 2 4. Pipe Coverings - One of the following types of pipe coverings shall be used: A. Pipe and Equipment Covering Materials* - Nom 2 in. (51 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. Annular space shall be min 1/2 in. (13 mm) thick to max 1-1/2 in. (38 mm). When the nom pipe diam is less than 2 in. (51 mm), annular space may be min 1/4 in. (6 mm). See Pipe and Equipment Covering -Materials (BRGU) category in Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. B. Pipe Covering Materials* - Nom 2 in. (51 mm) thick unlaced mineral fiber pipe insulation having a nom density of 3.5 pcf (56 kg/m3) (or heavier) and sized to the outside diam of pipe or tube. Pipe insulation secured with min No. 8 AWG steel win spaced max 12 in. (305 mm) OC. IIG MINWOOL L L C - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT or High Temperature Pipe Insulation Thermaloc C. Sheathing Material* - Used in conjunction with Item 4B . Foil-scrim-kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 4B) with the kraft side exposed. Longitudinal joints and transverse joints sealed with metal fasteners or butt tape. Annular space shall be min 1/2 in. (13 mm) thick to max 1-1/2 in. (38 mm). When the nom pipe diam is less than 2 in. (51 mm), annular space may be min 1/4 in. (6 mm). See Sheathing Materials* - (BVDV) category in the Building Materials Directory for names of manufacturers. Any sheathir material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 5. Firestop System - The firestop system shall consist of the following: A. Packing Material - Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation compressed and firml packed within annular space. Packing material to be recessed from top surface of floor or from both surfaces of wall to accommodate the required thickness of fill material (Item 5B). B. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. When min annular space is less than 1/2 in. (13 mm), fill material to be installed to min 1 in. (25 mm) thickness. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certificatic (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I. Created or Revised: January 23, 2014 us I C-AJ-5087 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Websitemww.stifirestop.com PAGE 2 OF 2 Classified by ❑N0 Underwiters Laboratories, Inc. 5, to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-C-5043 ❑■ ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings -1 and 2 Hr (See Items 1, 3A and 3D) F Ratings - 1 and 2 Hr (See Items 1, 3A and 3D) T Ratings - 3/4 and 1 Hr (See Item 3) FT Ratings - 3/4 and 1 Hr (See Item 3) L Rating At Ambient - Less Than 1 CFM/sq ft FH Ratings - 1 and 2 Hr (See Items 1, 3A and 3D) L Rating At 400 F - Less Than 1 CFM/sq ft FTH Ratings - 3/4 and 1 Hr (See Item 3) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft 2 A 1 4 3 4 2 1B I 3 �A 1C 4 Section A -A 1. Floor - Ceiling Assembly - The 1 hr fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Designs in the UL Fire Resistance Directory. The 2 hr fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in Design Nos. L505, L511 or L536 in the UL Fire Resistance Directory. The F Rating of the firestop system is equal to the fire rating of the floor -ceiling assembly. The general construction features of the floor assembly are summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of opening to be max 1 in. (25 mm) larger than diam of insulated pipe. As an alternate, the opening may be square -cut with a max dimension 1 in. (25 mm) greater than the diam of the insulated pipe. B. Wood Joists - Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Floor -Ceiling Design. Diam of opening is to be max 1 in. (25 mm) larger than diam of insulated metallic pipe. D. Furring Channel - (Not Shown) - In 2 hr fire -rated assemblies, resilient galv steel furring channels installed perpendicular to wood joists between base and face layers of gypsum board (Item C). Furring channels spaced max 24 in. (610 mm) OC with additional short lengths of furring channel installed adjacent to and max 3 in. (76 mm) from two opposing sides of penetrant. 1A. Chase Wall - (Optional, Not Shown) - The through penetrant (Item 2) may be routed through a 1 or 2 hr fire rated single, double or staggered wood stud/gypsum board chase wall. Depth of chase wall stud cavity to be min 1 in. (25 mm) greater than the diameter of the insulated pipe (Item 2). The chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. 3 Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 F-C-5043 T I (800)992-1180 9 (908)526-8000 9 FAX (908)231-8415 • E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 1 OF 3 B. Sole Plate - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 b7 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening is to be max 1 in. larger than diam of insulated metallic pipe. As an alternate for pipes insulated with max 1 in. (25 mm) thick glass fiber insulation (Item 3A), the opening may be square -cut with a max dimension 1 in. (25 mm) greater than the diam of the insulated pipe. Plates may be discontinuous over opening, terminating at two opposing edges of opening. Max length of discontinuity is 7 in. (178 mm). C. Top Plate - The double top plate shall consist of two nom 2 by 4 in. (51 by 102 mm), two nom 2 by 6 in. (51 by 152 mm) or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening is to be max 1 in. larger than diam of insulated metallic pipe. As an alternate for pipes insulated with max 1 in. (25 mm) thick glass fiber insulation (Item 3A), the opening may be square -cut with a max dimension 1 in. (25 mm) greater than the diam of the insulated pipe. Plates may be discontinuous over opening, terminating at two opposing edges of opening. Max length of discontinuity is 7 in. (178 mm). D. Steel Plate - (Not Shown) - When lumber plates are discontinuous, nom 1-1/2 in. (38 mm) wide No. 20 gauge (or heavier) galv steel plates shall be installed to connect discontinuous lumber plates and to provide a form for the fill material. Steel plates sized to lap 2 in. (51 mm) onto each discontinuous lumber plate and secured to lumber plates with steel screws or nails. E. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as specified in the individual Wall and Partition Design. 2. Through Penetrants - One metallic pipe or tubing to be installed either concentrically or eccentrically within the opening. Penetrants to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of metallic pipe or tubing may be used: A. Steel Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 4 in. (102 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Pipe or Tube - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe or Type L (or heavier) copper tube. 3. Pipe Covering* - One of the following types of pipe coverings may be used: A. Pipe and Equipment Covering Materials* - Nom 1 or 1-1/2 in. (25 or 38 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap tape. Transverse joints secured with metal fasteners or butt tape supplied with the product. The annular space between the insulated through penetrant and periphery of opening shall be min 0 in. (point contact) to max 1 in. (25 mm). When 1-1/2 in. (38 mm) thick insulation is used, max F Rating is 1 hr. When 1 in. (25 mm) thick insulation is used, max F Rating is 2 hr. See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used: B. Pipe Covering Materials* - Max 1 in. (25 mm) thick unfaced mineral fiber pipe insulation having a nom density of 3.5 pcf (56 kg/m3) (or heavier) and sized to the outside diam of pipe or tube. Pipe insulation secured with min No. 18 AWG steel wire spaced max 12 in. (305 mm) OC. The annular space between the insulated through penetrant and periphery of opening shall be min 0 in. (point contact) to max 1 in. (25 mm). IIG MINWOOL L L C - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT or High Temperature Pipe Insulation Thermaloc. C. Sheathing Material* - Used in conjunction with Item 3B. Foil-scrim-kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 3B) with the kraft side exposed. Longitudinal joints and transverse joints sealed with metal fasteners or butt tape. See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any sheathing material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 F-C-5043 T I ® (800)992-1180 • (908)526-8000 9 FAX (908)231-8415 • E-Mail:techserv@stifirestop.com . Website:www.stifirestop.com PAGE 2 OF 3 D. Tube Insulation - Plastics# - Nom 1 in. (25 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The annular space between the insulated through penetrant and periphery of opening shall be min 0 in. (point contact) to max 1 in. (25 mm). When AB/PVC insulation is used, max F Rating is 1 hr. See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. When Item 3A or 313 pipe covering is used, T Rating is 1 hr. When Item 3D pipe covering is used, T Rating is 3/4 hr. 4. Fill, Void or Cavity Material" - Sealant - Min 3/4 in. (19 mm) thickness of fill material applied within the annulus, flush with the top surface of the floor or sole plate. Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with bottom surface of ceiling or top plate. Min 1/4 in. (6 mm) diam bead of fill material applied at point contact location on the top surface of floor or sole plate and at the insulated metallic pipe/ceiling or top plate interface. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant or Type WF300 Firestop Caulk Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. #Bearing the UL Recognized Component Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 YL us F-C-5043 T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 3 OF 3 Classified by j,J�a .' Underwiters Laboratories, Inc. �., to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System NO. W-L-5298 0 Qn XAI ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 1 and 2 Hr (See Item 1) F Rating - 1 and 2 Hr (See Item 1) T Rating - 0 Hr FT Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/sq ft FH Rating - 1 and 2 Hr (See Item 1) L Rating At 400 F - Less Than 1 CFM/sq ft FTH Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft 4 A 4 2 3 2 3 1A 1B A Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wood studs consist of nom 2 by 4 in. (51 by 102 mm) lumber studs spaced 16 in. (406 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 12 in. (305 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant - One metallic pipe or tube to be installed eccentrically or concentrically within the firestop system. Pipe or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of metallic pipes and tubes may be used: A. Steel Pipe - Nom 6 in. (152 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 6 in. (152 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tube - Nom 4 in. (102 mm) diam (or smaller) Type M (or heavier) copper tube. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. us W-L-5298 ST I Created or Revised: February 07, 2017 I (800)992-1180 • (908)526-8000 • FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com 0 Website:www.stifirestop.com PAGE 1 OF 2 3. Pipe Coverings - One of the following types of pipe coverings shall be used: A. Pipe and Equipment Covering Materials* - Nom 2 in. (51 mm) thick hollow cylindrical heavy density (min 3.5 pcf) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap tape. Transverse joints secured with metal fasteners or butt tape supplied with the product. The annular space between the insulated through penetrant and periphery opening shall be min 0 in. (0 mm, point contact) to max 1-3/8 in. (35 mm). See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. B. Pipe Covering Materials* - Nom 2 in. (51 mm) thick unfaced mineral fiber pipe insulation sized to the outside diam of pipe or tube. Pipe insulation secured with min No. 8 AWG steel wire spaced max 12 in. (305 mm) OC. The annular space between the insulated through penetrant and periphery opening shall be min 0 in. (0 mm, point contact) to max 1-3/8 in. (3E mm). INDUSTRIAL INSULATION GROUP L L C - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT or High Temperature Pipe Insulation Thermaloc. C. Sheathing Material* - Used in conjunction with Item 3B. Foil-scrim-kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 3B) with the kraft side exposed. Longitudinal joints and transverse joints sealed with metal fasteners or butt tape. See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any sheathing material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. At point contact location, min 1 /4 in. (6 mm) diam bead of fill material applied at insulated metallic pipe/gypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - Type WF300 Caulk * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. STIR Created or Revised: February 07, 2017 us I:wW-L-5298 o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Websiteww.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. W-L-5054 F Ratings - 1 & 2 Hr. (See Item 1) T Ratings - 3/4 and 1 Hr. A 3 �A Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. O.C. with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-1/2 in. wide and spaced max 24 in. O.C. B. Gypsum Board* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 7-5/8 in. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant - One metallic pipe or tubing to be installed either concentrically or eccentrically within the firestop system. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used: A. Steel Pipe - Nom 4 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 4 in. diam (or smaller) cast or ductile iron pipe. C. Copper Tubing - Nom 4 in. diam (or smaller) Type L (or heavier) copper tubing. D. Copper Pipe - Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. 3. Tube Insulation - Plastics+ - Nom 3/4 in. or 1 in. thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The annular space between penetrating item and periphery of opening shall be min 0 in. (point contact) to max 1-1/2 in. When 1 in. thick AB/PVC insulation is used, T Rating is 3/4 hr. When 3/4 in. thick AB/PVC insulation is used, T Rating is 1 hr. See Plastics+ (QMFZ2) category in the Recognized Component Directory of names for manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. 4. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. Thickness of fill material applied within annulus, flush with both surfaces of wall. Min 1/4 in. diam bead of sealant to be applied at the point contact location between the AB/PVC insulation and the gypsum board. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: jANUARY 23, 2014 @ W-L-505 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com GE 1 OF1 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. W-L-5121 F Ratings - 1 and 2 Hr (See Item 1) T Ratina - 1 Hr 1 1B A Section A -A Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 3-5/8 in. wide and spaced max 24 in. OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 12 in. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant - One metallic pipe or tube to be installed eccentrically or concentrically within the firestop system. Pipe or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of metallic pipes and tubes may be used: A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 6 in. diam (or smaller) cast or ductile iron pipe. C. Copper Pipe - Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tube - Nom 4 in. diam (or smaller) Type L (or heavier) copper tube. 3. Pipe Coverings - One of the following types of pipe coverings shall be used: A. Pipe and Equipment Covering Materials* - Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap tape. Transverse joints secured with metal fasteners or butt tape supplied with the product. The annular space between the insulated through penetrant and periphery opening shall be min 0 in. (point contact) to max 1-1/2 in. See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. B. Pipe Covering Materials* - Nom 2 in. thick unfaced mineral fiber pipe insulation sized to the outside diam of pipe or tube. Pipe insulation secured with min No. 8 AWG steel wire spaced max 12 in. OC. The annular space between the insulated through penetrant and periphery opening shall be min 0 in. (point contact) to max 1-1/2 in. IIG MINWOOL L L C - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT or High Temperature Pipe Insulation Thermaloc. C. Sheathing Material* - Used in conjunction with Item 3B. Foil-scrim-kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 3B) with the kraft side exposed. Longitudinal joints and transverse joints sealed with metal fasteners or butt tape. See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any sheathing material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. thickness of fill material applied within annulus, flush with both surfaces of wall assembly. At point contact location, min 1/4 in. diam bead of fill material applied at insulated metallic pipe/gypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: jANUARY 23, 2014 �°stifirestop.com • Website:www.stifirestop.com GE 1 OF11 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery Classified by Underwiters Laboratories, Inc. ,� to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-C-7014 ■❑ ; ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 1 Hr F Rating - 1 Hr T Ratings - 1/4 and 1 Hr (See Item 2) FT Ratings - 1/4 and 1 Hr (See Item 2) L Rating At Ambient - Less Than 1 CFM/sq ft FH Rating - 1 Hr L Rating At 400 F - Less Than 1 CFM/sq ft FTH Ratings - 1/4 and 1 Hr (See Item 2) L Rating At Ambient - Less Than 5.1 L/s/m2 L Rating At 400 F - Less Than 5.1 L/s/m2 A 1 2 2 1B 3 1C 3 p` Section A -A 1. Floor - Ceiling Assembly - The 1 hr fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Designs in the UL Fire Resistance Directory, as summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Diam of opening is to be max 1 in. (25 mm) larger than diam of steel duct. B. Wood Joists - Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Floor -Ceiling Design. Diam of opening is to be max 1 in. (25 mm) larger than diam of steel duct. 1A. Chase Wall - (Optional, Not Shown) - The through penetrant (Item 2) may be routed through a single, double or staggered wood stud/gypsum board chase wall. Depth of chase wall stud cavity to be min 1/2 in. (13 mm) greater than diameter of opening cut in sole and top plates to accommodate the through penetrant (Item 2). The chase wall shall include the following construction features: A. Studs - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm)or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening is to be max 1 in. (25 mm) larger than diam of steel pipe. C. Top Plate - The single or double top plate shall consist of one or two nom 2 by 4 in (51 by 102 mm) or one or two nom 2 by 6 in. (51 by 152 mm) or one or two sets of parallel nom 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Diam of opening is to be max 1 in. (25 mm) larger than diam of steel duct. D. Gypsum Board* - Min 1/2 in. (13 mm) thick rated or nonrated gypsum board. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. �� us S T I Created or Revised: June 05, 2015 F-C-7014 I (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 2 2. Steel Duct -One nom 4 in. (102 mm) diam (or smaller) No. 30 GA (or heavier) steel duct or one nom 10 in. (254 mm) diam (or smaller) No. 28 GA (or heavier) steel duct to be installed either concentrically or eccentrically within the opening. Annular space to be min 0 in. (point contact) to max 1 in. (25 mm). Steel duct to be rigidly supported on both sides of floor -ceiling assembly. T, FT and FTH Ratings are 1 hr for nom 4 in. (102 mm) diam (or smaller) ducts. T, FT and FTH Ratings are 1/4 hr for ducts greater than nom 4 in. (102 mm) diam. 3. Fill, Void or Cavity Material" - Sealant - Min 3/4 in. (19 mm) thickness of fill material applied within the annulus, flush with the top surface of the floor or sole plate. Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with bottom surface of ceiling or top plate. Min 1/4 in. (6 mm) diam bead of fill material applied at point contact location on the top surface of floor or chase wall sole plate and at the penetrant/ceiling or chase wall top plate interface. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant or Type WF300 Firestop Caulk * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. ST I a Created or Revised: June 05, 2015 I@ PAGE 2 01 2 0 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com Classified by ❑� R1 Underwiters Laboratories, Inc. MV to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-C-7023 �■ ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 1 Hr F Rating - 1 Hr T Rating - 1/4 Hr FT Rating - 1/4 Hr L Rating At Ambient - Less Than 1 CFM/sq ft FH Rating - 1 Hr L Rating At 400 F - Less Than 1 CFM/sq ft FTH Rating - 1/4 Hr L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft 2 A 31A 3 ...................... ..................... 3 1B 2 A 1C 3 3 Section A -A 1. Floor -Ceiling Assembly - The 1 hr fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Designs in the UL Fire Resistance Directory, as summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Square or rectangular opening made to accommodate steel duct (Item 2) to be centered between wood joists. Max area of opening is 81 sq in. (0.05 m2). Length and width dimensions of opening to be max 1 in.(25 mm) larger than outside dimensions of steel duct. Long dimension of rectangular opening to be perpendicular to direction of wood joists. B. Wood Joists - Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Floor -Ceiling Design. Max area of opening in gypsum board ceiling is 100 sq in. (0.065 m2). Length and width dimensions of opening to be max 1 in. (25 mm) larger than outside dimensions of steel duct. 1 A. Chase Wall - (Optional, Not Shown) - The steel duct may be routed through a 1 hr fire rated single, double or staggered wood stud/gypsum board chase wall. Depth of chase wall stud cavity to be min 1/2 in. (13 mm) greater than width of opening cut in sole and top plates to accommodate the steel duct. The chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Nom 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate - Nom 2 by 6 in. (51 by 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max area of opening is 100 sq in. (0.065 m2). Length and width dimensions of opening to be max 1 in. (25 mm) larger than each side of steel duct. C. Top Plate - The double top plate shall consist of two nom 2 by 6 in. (51 by 152 mm) or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Length and width dimensions of opening to be max 1 in. (25 mm) larger than each side of steel duct. D. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as specified in the individual Wall and Partition Design. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I Created or Revised: January 23, 2014 F-C-7023 I reo (800)992-1180 • (908)526-8000 • FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 1 OF 2 2. Steel Duct - Square or rectangular duct formed from No. 28 gauge (or heavier) galvanized steel. Max cross -sectional area of duct to be 64 sq in. (0.04 m2) with a maximum dimension of 12 in. (305 mm). Annular space between the steel duct and the periphery of the opening shall be min 0 in. (point contact) to max 1 in. (25 mm). Steel duct to be rigidly supported on both sides of floor -ceiling assembly. 3. Fill, Void or Cavity Material* - Sealant - Min 3/4 in. (19 mm) thickness of fill material applied within the annulus, flush with the top surface of the floor or sole plate. Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with bottom surface of gypsum board ceiling or top plate. Min 1/4 in. (6 mm) diam bead of fill material applied at point contact location on the top surface of floor or chase wall sole plate and at the penetrant/ceiling or penetrant/chase wall top plate interface. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant or Type WF300 Firestop Caulk * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. F-CCreated or Revised: January 23, 2014 S 1T I. AGE2 23 (800)992-1180 • (908)526-8000 •FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Webs PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) A 3 2 System No. W-L-7019 F Ratings - 1 & 2 Hr (See Item 1) T Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. (51 by 102 mm) lumber end plates and cross braces. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 11 in.(279 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant - One nom 10 in. (254 mm) diam (or smaller) No. 28 MSG (or heavier) steel vent pipe to be installed either concentrically or eccentrically within the firestop system. The annular space between pipe and periphery of opening shall be min 0 in. (point contact) to max 1 in. (25 mm). Pipe to be rigidly supported on both sides of wall assembly. 3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall. At the point contact location between through penetrant and gypsum board, a min 3/8 in. (10 mm) diam bead of fill material shall be applied at the gypsum board/through penetrant interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant or Type WF300 Firestop Caulk (wood stud walls only). * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: October 28, 2009 �° GE 1 OF91 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com Classified by F!l Underwiters Laboratories, Inc. ,+� to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-7025 ❑■Ptzi ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1) T Rating - 1/2 Hr FT Rating - 1/2 Hr L Rating At Ambient - Less Than 1 CFM/sq ft FH Ratings - 1 and 2 Hr (See Item 1) L Rating At 400 F - Less Than 1 CFM/sq ft FTH Rating - 1/2 Hr L Rating At Ambient - Less Than 5.1 L/s/m3 L Rating At 204 C- Less Than 5.1 L/s/m3 1 A 1A 3B 3C 3B 1B A 2 Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400, V400 or W 400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of min 3-1/2 in. (89 mm) wide steel channel studs spaced max 24 in. (610 mm) OC. Additional steel studs shall be used to completely frame the opening. B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Design in the UL Fire Resistance Directory. Max area of opening is 73.7 sq ft (6.85 m2) with a max dimension of 104 in. (2.64 m). The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. 2. Steel Duct - Max 100 in. by 100 in. (2.54 by 2.54 m) No. 26 gauge (or heavier) galv steel duct to be installed either concentrically or eccentrically within the firestop system. The space between the steel duct and periphery of opening shall be min 0 in. ( 0 mm, point contact) to max 2 in. (51 mm). Steel duct to be rigidly supported on both sides of the wall assembly. 2A. Coated Ducts* - As an alternate to Item 2, max 60 by 60 in. (1524 by 1524 mm) steel duct coated with BW11 coating material. Duct sections shall be assembled using bolted flanges or SMACNA approved Transverse Joint Reinforcements. Annular space between duct and periphery of opening shall be shall be min Oin. (point contact) to max 2 in. (51 mm). Duct to be rigidly supported on both sides wall assembly. FIRESPRAY INTERNATIONAL LTD - FLAMEBAR BW11 fire rated ductwork IF Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: July 24, 2017 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@restop.com • Website:www.stifirestop.com GE 1 OF2 3. Firestop System - The firestop system shall consist of the following: A. Packing Material - (Optional, Not Shown) - Polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fitted into annular space. Packing material to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of fill material shall be applied at the point contact location between the steel duct and the gypsum board. For 2 hr Rated walls when LC150 or LE600 Sealant is used, fill material thickness installed to full depth of gypsum board layers on each side of wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, SpecSeal LCI Sealant, SpecSeal LC150 Sealant or SpecSeal LE 600 Sealant. C. Steel Retaining Angles - Min No. 16 gauge (0.059 in. or 15 mm) galv steel angles sized to lap steel duct a min of 2 in. (51 mm) and to lap wall surfaces a min of 1 in. (25 mm). Angles attached to steel duct on both sides of wall with min No. 10 by 1/2 in. (13 mm) long steel sheet metal screws located a max of 1 in. (25 mm) from each end of steel duct and spaced a max of 6 in. (152 mm) OC. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. At Created or Revised: July 24, 2017 IWW S T I o (800)992-1180 • (908)526-8000 9 FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Webs ite:www.stifirestop.com GE 2 OF 2 Classified by Underwiters Laboratories, Inc. ,� to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-7026 ❑■ ,,; ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1) T Rating - 0 Hr FT Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/sq ft FH Ratings - 1 and 2 Hr (See Item 1) L Rating At 400 F - Less Than 1 CFM/sq ft FTH Rating - 0 Hr L Rating At Ambient - Less Than 5.1 L/s/m2 L Rating At 204 C- Less Than 5.1 L/s/m2 A 1 3 3 2 3 1B A Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of min 3-1/2 in. (89 mm) wide steel channel studs spaced max 24 in. (610 mm) OC. When diam of opening exceeds width of stud cavity, additional lengths of steel stud installed to frame out opening around steel duct (Item 2). B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Design in the UL Fire Resistance Directory. Max diam of opening is 25-1/2 in. (648 mm). The hourly F and FH Rating of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. 2. Steel Duct - Max 24 in. (610 mm) diam No. 28 gauge (or heavier) galv steel vent duct or No. 26 gauge (or heavier) spiral wound galv steel duct. One steel duct to be installed either concentrically or eccentrically within the firestop system. An annular space of min 0 in. (point contact) to max 1-1/2 in. (38 mm) is required within the firestop system. Steel duct to be rigidly supported on both sides of the wall assembly. 2A. Coated Ducts* - As an alternate to Item 2, max 24 in. (610 mm) diam (or smaller) steel duct coated with BW11 coating material. Duct sections shall be assembled using bolted flanges or SMACNA approved Transverse Joint Reinforcements. One duct to be installed either concentrically or eccentrically within the firestop system. The annular space between the duct and the periphery of the opening shall be min 0 in. (point contact) to a max of 1-1/2 in. (38 mm). Duct to be rigidly supported on both sides o wall assembly. FIRESPRAY INTERNATIONAL LTD - FLAMEBAR BW11 fire rated ductwork Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: July 24, 2017 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com �° GE 1 OF2 3. Firestop System - The firestop system shall consist of the following: A. Packing Material - (Optional, Not Shown) - Polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fit into annular space for 2 hr rated wall assemblies only. Packing material to be recessed from both surfaces of wall to accommodate the required thickness of fill material (Item 313). B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of fill material shall be applied at the point contact location between the steel duct and the gypsum board. For 2 hr Rated walls when LC150 or LE600 Sealant is used, fill material thickness installed to full depth of gypsum board layers on each side of wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, SpecSeal LC150 Sealant, or SpecSeal LE600 Sealant * Indicates such products shall bear the UL or cUlL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. YLAt Il Created or Revised: July 24, 2017 W-L-7026 S T I o (800)992-1180 • (908)526-8000 9 FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-7029 ❑■ ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1) T Rating - 1/4 Hr FT Rating - 1/4 Hr FH Ratings - 1 and 2 Hr (See Item 1) FTH Rating - 1/4 Hr A 1 3B 1 2 3B I� 71 3B 1B A Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400, V400, or W400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of min 3-1/2 in. (89 mm) wide steel channel studs spaced max 24 in. (610 mm) OC. Additional steel studs shall be used to completely frame opening. B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Designs in the UL Fire Resistance Directory. Max area of opening is 690 sq in. (0.45 m2) with max dimension of 27 in. (686 mm). The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall in which it is installed. 2. Steel Duct - Max 24 by 24 in. (610 by 610 mm) No. 26 gauge (or heavier) steel duct to be installed within the opening. The annular space within the firestop system shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Steel duct to be rigidly supported on both sides of the wall assembly. 2A. Coated Ducts* - As an alternate to Item 2, max 24 by 24 in. (610 by 610 mm) steel duct coated with BW11 coating material. Duct sections shall be assembled using bolted flanges or SMACNA approved Transverse Joint Reinforcements. Annular space between duct and periphery of opening shall be shall be min 0 in. (point contact) to max 2 in. (51 mm). Duct to be rigidly supported on both sides of wall assembly. FIRESPRAY INTERNATIONAL LTD - FLAMEBAR BW11 fire rated ductwork Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. T I Created or Revised: July 24, 2017 . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com O° GE 1 OF2 3. Firestop System - The firestop system shall consist of the following: A. Packing Material - (Optional, Not Shown) - Mineral wool batt insulation, foam backer rod or glass fiber insulation installed as a permanent form to facilitate installation of fill material (Item 313). B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. Min 1/4 in. (6 mm) diam bead of fill material to be applied at point contact location between the steel duct and the gypsum board. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. ST I ao Created or Revised: July 24, 2017 YL us I W-L-7029 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. �+ to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-7136 ❑■ ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr (See Item 1) F Ratings - 1 and 2 Hr (See Item 1) T Rating - 0 Hr FT Rating - 0 Hr FH Ratings - 1 and 2 Hr (See Item 1) FTH Rating - 0 Hr A 1B 3 3 2 2 1A A Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - One or two layers of gypsum board, as specified in the individual Wall and Partition Design. Max diam of opening is 3-3/8 in. (86 mm). Max area of rectangular opening is 16.5 sq in. (106 cm2) with max dimension of 5 in. (127 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants - One metallic strut, cable or rod service support to be installed within the firestop system. An annular space of min 1/8 in. (3 mm) to max 7/8 in. (22 mm) is required within the firestop system. Strut, cable or rod service support to be rigidly supported on both sides of wall assembly. The strut, cable or rod service support may be installed at an angle not greater than 45 degrees from the perpendicular. The following types and sizes of metallic strut, cable or rod service support may be used: A. Steel Strut - Max 1-5/8 by 1-5/8 in. (41 by 41 mm) channel strut formed from min 0.105 in. (2.7 mm) thick galv or painted steel. B. Steel Strut - Max 3-1/4 by 1-5/8 in. (83 by 41 mm) H strut formed from min 0.105 in. (2.7 mm) thick galv or painted steel. C. Cable - Max 3/8 in. (9.5 mm) diam unjacketed galv steel cable. D. Threaded Rod - Max 5/8 in. (16 mm) diam galv steel threaded rod. 3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within the annulus and within the channel struts, flush with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, SpecSeal LC150 Sealant, SpecSeal LE600 Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. IF Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com �° GE 1 OF61 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) System No. W-L-7193 F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 1 and 2 Hr (See Item 1) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft 1. Wall Assembly - The fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing to consist of nom 2 by 6 in. (51 by 152 mm) (or larger) wood or steel channel studs or doubled or staggered nom 2 by 4 in. (51 by 102 mm) (or larger) wood studs spaced in accordance with the individual U300, U400, or V400 Series Wall and Partition Designs. B. Gypsum Board* - Thickness, type, number of layers, as specified in the individual Wall and Partition Design. Max diam of opening is 5 in. (127 mm). The hourly F and T Ratings are equal to the hourly rating of the wall assembly in which it is installed. 2. Tub and Shower Valve - Single -handled tub/shower valve assembly with nonmetallic/nonferrous and stainless steel materials connected to nom 1/2 in. (13 mm) cross -linked polyethylene (PEX), copper, brass, or iron supply pipes/tubes. Nom 7 in. (178 mm) stainless steel escutcheon plate to lap min 1 in. (25 mm) beyond periphery of opening. 3. Fill, Void or Cavity Material* - Sealant or Putty - Min 1/2 in. (13 mm) depth of fill material applied within opening flush with wall surface. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, SpecSeal LC150 Sealant, SpecSeal Series SIL300 Sealant, SpecSeal Putty, Pensil 300 Sealant, or Type WF300 Firestop Caulk (U300 Walls only) * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 �° GE 1 OF31 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com Classified by a' Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System NO. C-AJ-8093 ❑■ ANSI/U1-1479 (ASTM E814) CAN/ULC S115 F Ratings - 2 and 3 Hr (See Items 3, 4, 6 and 8) F Ratings - 2 and 3 Hr (See Items 3, 4, 6 and 8) T Ratings - 0, 1/4, 1/2, 3/4, 1-1/2 and 2 Hr (See Items 2 through FT Ratings - 0, 1/4, 1/2, 3/4, 1-1/2 and 2 Hr (See Items 2 through 9) 9) L Rating At Ambient - Less than 1, 1.6, and 3.2 CFM/sq ft (See FH Ratings - 2 and 3 Hr (See Items 3, 4, 6 and 8) Item 2, 4, 5, 6, 8 and 9B) L Rating at 400 F - Less than 1, 1.6, and 2 CFM/sq ft (See Item FTH Ratings - 0, 1/4, 1/2, 3/4, 1-1/2 and 2 Hr (See Items 2 2, 4, 5, 6, 8 and 9B) through 9) L Rating At Ambient - Less than 1, 1.6, and 3.2 CFM/sq ft (See Item 2, 4, 5, 6, 8 and 913) L Rating at 400 F - Less than 1, 1.6, and 2 CFM/sq ft (See Item 2, 4, 5, 6, 8 and 913) 5 0 2 9C 6A A A A A A A A I I I I0 1 . .................... . 9 ...................... ...... .a ............ ......... ..... a ...................... .. O O O 9 O 0 0 0 3 4 2 3 Section A -A A System tested with a pressure differential of 2.5 Pa between the exposed and the unexposed surfaces with the higher pressure on the exposed side. 1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max area of opening is 18 sq ft with a max single dim of 6 ft (1.6 m) When any dim exceeds 3 ft (0.76 m), see Item 9C. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Metallic Penetrants - One or more metallic pipes, conduits or tubes to be installed within the opening. Min 1/2 in. (13 mm) clearance between penetrants. Min clearance between penetrants and periphery of opening is 0 in. (point contact) (0 mm). Penetrants rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) electrical metallic tubing (EMT), or nom 4 in. (102 mm) diam (or smaller) steel Flexible Metal Conduit#. D. Copper Pipe or Tube - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe or Type M (or heavier) coppertube. Specified Technologies f0nWay Somerville, NJ 08876 nc Reproduced courtesy oUnderwiterbo Created or Revised: February 24, 2016 T I ® 800 992-1180 • 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@resop.com • Website:www.stifirestop.com AGE 1 OF 4 Type of Metallic Penetrant Max Diam of Throu ht Penetrant in. mm T Rating, Hr Steel or Iron Pipe, Conduit or Copper Pipe or Tube 12 (305) 1/4 Steel or Iron Pipe, Conduit or EMT 4 (102) 3/4 Steel or Iron Pipe, Conduit or EMT 2 (51) 2 The L Rating is Less than 1 CFM/sq ft at ambient and 400 F for metallic penetrants. Pipe Insulation - (Optional) - The following types of pipe insulations may be installed on one or more of the metallic pipes or tubing: A. Pipe and Equipment Covering Materials* - Max 2 in. (51 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 57 kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. B. Pipe Covering Materials* - Max 2 in. (51 mm) thick unfaced mineral fiber pipe insulation having a nom density of 3.5 pcf (57 kg/m3) (or heavier) and sized to the outside diam of the pipe or tube. Pipe insulation secured with min 8 AWG steel wire spaced max 12 in. (305 mm) OC. INDUSTRIAL INSULATION GROUP L L C - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT and High Temperature Pipe Insulation Thermaloc C. Sheathing Material* - Use in conjunction with Item 3B. Foil-scrim-kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 3B) with the kraft side exposed. Longitudinal and transverse joints sealed with metal fasteners or butt tape. See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any sheathing material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. D. Tube Insulation - Plastics## - Max 1 in. (25 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. When tube insulation is used, nom diam of copper pipe or tube shall not exceed 4 in. (102 mm). See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. E. Pipe Covering Materials*- Cellular Glass Insulation - Max 3 in. (76 mm) thick cellular glass units sized to the outside diam of the pipe or tube and supplied in nom 24 in. (610 mm) long half sections or nom 18 in. (457 mm) long segments. Pipe insulation installed on pipe in accordance with the manufacturer's instructions. PITTSBURGH CORNING CORP - FOAMGLAS F. Metal Jacket - Used in conjunction with Item 3E. Min 12 in. long jacket formed from min 0.010 in. (0.254 mm) thick aluminum sheet cut to wrap tightly around the pipe insulation with a min 2 in. (51 mm) lap and secured using bands and seals of a similar material or min No. 18 AWG steel tie wire. Bands or steel tie wire to be located within 2 in. (51 mm) of each end of the jacket and spaced max 10 in. (254 mm) OC. Jacket installed with edge abutting surface of fill material (Item 9A) on top surface of floor or both surfaces of wall. Metal jacket to be used in addition to any other jacketing material which may be required on the pipe covering. G. Pipe and Equipment Covering Materials* - Max 3 in. (76 mm) thick hollow cylindrical calcium silicate (min 10.0 pcf or 160 kg/m3) sized to the outside diam of the pipe or tube. Pipe insulation secured with min 8 AWG steel wire spaced max 12 in. (305 mm) OC. See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. When Items 3A or 3D are used, the F and FH Ratings are 2 hr. When other pipe covering materials are used, F and FH Ratings are 3 hr. When Item 3D is used, the T, FT and FTH Ratings are 3/4 hr. When other pipe covering materials are used, T, FT and FTH Ratings are 1-1/2 hr. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: February 24, 2016 us S T l a0 C-3 1 (800)992-1180 • (908)526-8000 •FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 2 OF 4. Nonmetallic Penetrants - One or more nonmetallic pipes, conduits or tubes to be installed within the opening. Min clearance between nonmetallic penetrants to be 1 in. (25 mm). Min clearance between nonmetallic and metallic penetrants to be 4 in. (102 mm) Min clearance between penetrants and periphery of opening is 0 in. (0 mm) (point contact). Penetrants rigidly supported on both sides of floor or wall assembly. The following types and sizes of nonmetallic pipes, conduits or tubing may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) solid or cellular core Schedule 40 PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. C. Rigid Nonmetallic Conduit+ - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA 70). D. Electrical Nonmetallic Tubing (ENT)+ - Nom 2 in. (51 mm) diam (or smaller) corrugated wall ENT formed of polyvinyl chloride (PVC) installed in accordance with the National Electrical Code (NFPA 70). E. Optical Fiber Raceway (OFR)+ - Nom 2 in. (51 mm) diam (or smaller) OFR formed of either polyvinyl chloride (PVC) or polyvinylidene fluoride (PVDF) installed in accordance with the National Electrical Code (NFPA 70). When Item 4 is used, the F, T, FT, FH and FTH Ratings of the firestop system are 2 hr. The L Rating is Less than 1 CFM/sq ft at ambient and 400 F. 5. Cables - Nom 4 in. (102 mm) diam (or smaller) tight bundle of cables. Cable bundle spaced min 4 in. (102 mm) from all other penetrants. Clearance between cable bundle and periphery of opening is 0 in. (0 mm) (point contact). Cable bundle rigidly supported on both sides of floor or wall assembly. The following types and sizes of cables may be used: A. Max 1/C - 350 kcmil cable with polyvinyl chloride (PVC), cross -linked polyethylene (XLPE) or plenum rated insulation and jacket. B. Max 7/C - No. 12 AWG cable with PVC -nylon insulation and PVC jacket. C. Max 100 pair - No. 24 AWG copper conductor telephone cable with PVC or plenum rated insulation and jacket. D. Max RG/U coaxial cables with fluorinated ethylene or plenum rated jacket and insulation. E. Multiple fiber optic cables with PVC or plenum rated insulation. F. Through Penetrating Products* - Max 2/C with ground No. 12 AWG Metal -Clad Cable+. AFC CABLE SYSTEMS INC When Item 5A or 5F is used, the T, FT and FTH Ratings are 1/2 hr. When other cables are used, T, FT and FTH Ratings are 3/4 hr. The L Rating is Less than 1.6 CFM/sq ft at ambient and 400 F. 6. Cable Tray - Max 30 in. (762 mm) wide by max 6 in. (152 mm) deep open ladder cable tray with channel -shaped side rails formed from min 0.060 in. (1.5 mm) thick (No. 16 MSG) galv steel or min 0.060 in. (1.5 mm) thick aluminum with rungs spaced max 9 in. (227 mm) OC. A max of two cable trays may be installed within the opening with a min separation of 8 in. (204 mm) between trays. The min space between the cable tray and the periphery of the opening is 0 in. (0 mm) (point contact). Cable trays to be rigidly supported on both sides of the floor or wall assembly. Aggregate cross -sectional area of cables in cable tray not to exceed 40 percent of the cross -sectional area of the cable tray based on a max 3 in. (76 mm) cable loading depth within tray. Any combination of the cable types specified in Item 5 may be used. When width of cable tray exceeds 18 in. (457 mm), the F and FH Ratings are 2 hr. The L Rating is 3.2 CFM/sq ft at ambient and 2 at 400 F when putty is used (See Item 9B). 7. Busway+ - (Not Shown) - Nom 19 in. (483 mm) wide (or smaller) by 5 in. (127 mm) deep "I" shaped aluminum enclosure containing factory -mounted copper bars rated for 600 V, 5000 A or aluminum bars rated for 600 V, 4000 A. A max two busways to be installed within the opening. The annular space between the busway and the periphery of the opening shall be a min 1/2 in. (13 mm) to a max 3-1/2 in. (89 mm). Busways spaced min 6 in. (152 mm) from all other penetrants. Busway to be rigidly supported on both sides of floor or wall assembly. The busway shall bear the UL Listing Mark and shall be installed in accordance with all provisions of the National Electrical Code, NFPA 70. When busway is used, the T, FT and FTH Ratings are 0 hr. 8. Steel Duct - (Not Shown) - Nom 18 in. (457 mm) diameter (or smaller) No. 28 GA (or heavier) steel duct installed within opening when opening contains no cable tray. A max of two steel ducts may be installed within the through -opening. Ducts to be spaced min 4 in. (102 mm) apart and min 8 in. (204 mm) from insulated penetrants and nonmetallic penetrants. The clearance between the steel duct and the periphery of the opening shall be min 0 in. (0 mm) (point contact). Steel ducts to be rigidly supported on both sides of floor or wall assembly. When steel duct is used, the F and FH Ratings are 2 hr and the T, FT and FTH Ratings are 0 hr. The L Rating is Less than 1 CFM/sq ft at ambient and 400 F. Specified Technologies 10nWaomervlle, NJ 08876 Reproduced courtesy ouderwiteraboroInc. Created or Revised: February 24, 2016 lit STIo R C-(800)992-1180 • (908)526-8000 •FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE GE 3 3 OF OF 4 9. Firestop System - The firestop system shall consist of the following items: A. Fill, Void or Cavity Materials* - Pillows - Nom 9 in. (227 mm) long by 4 to 6 in. (102 to 152 mm) wide by 1 to 3 in. (25 to 76 mm) thick plastic covered intumescent pillows. In floors, pillows to be installed lengthwise through opening and positioned to extend a maximum of 2-1/2 in. (64 mm) below the bottom plane of the floor. In walls, pillows to be installed lengthwise through opening and positioned to extend an equal distance from the approximate center line of the wall. Pillows tightly packed into the opening to fill the annular space between the annular space and the penetrating items. SPECIFIED TECHNOLOGIES INC - SpecSeal Firestop Pillows B. Fill, Void or Cavity Materials* - Sealant or Putty - Min 1/2 in. (13 mm) depth of fill material applied at point contact locations between penetrating items and periphery of opening. Additional fill material forced into interstices of grouped cables and grouped cables within cable trays. For L Ratings, apply nom 3/16 in. (4.8 mm) thick by 4-3/4 in. (121 mm) wide band of putty to top of cables in the cable tray. SPECIFIED TECHNOLOGIES INC - SpecSeal Series 100, 101, 102, 120, 129 or 105 Sealant, SpecSeal LCI Sealant, SpecSeal SIL300 Silicone Firestop Sealant, or SpecSeal Putty C. Wire Mesh - Nom 1 in. (25 mm) hexagonal wire mesh fabricated from min 20 ga galv steel wire cut to fit the contours of the penetrating items and the opening with a min 2 in. (51 mm) lap beyond the periphery of the opening. Wire mesh secured to both sides of floor or wall by means of 1/4 in. (6 mm) diam by 1-1/2 in. (38 mm) long steel concrete screws in conjunction with 1-1/4 in. (31 mm) diam steel fender washers spaced max 6 in. (152 mm) OC. Any joints within wire mesh shall overlap 2 in. (51 mm) and be secured together by means of No. 20 AWG steel wire spaced 6 in. (152 mm) OC. When both the length and width dimensions of the through opening are less than 36 in. (914 mm) and when the max space between penetrants or between the penetrant and the perimeter of the opening is less than 10 in. (254 mm), the wire mesh is optional. When the area of the opening exceeds 1296 sq in. (0.84 m2), the gauge of the steel wire mesh shall be increased to min 16 AWG. D. Steel Straps - (Not shown) - As an alternate to the wire mesh (Item 9C) in wall assemblies, min 1 in. (25 mm) wide by 0.015 in. (0.38 mm) thick steel banding straps sized to lap 2 in. (51 mm) beyond the periphery of the opening may be installed either horizontally or vertically between rows of penetrants with a max on center spacing of 4 in. (102 mm). Steel banding straps secured to concrete with 1/4 in. (6 mm) diam by 1-1/2 in. (38 mm) long steel concrete screws in conjunction with 1-1/4 in. (31 mm) diam steel fender washers. E. Steel Plate - (Not Shown) - As an alternate to Item 9C or 9D, min 28 GA (or heavier) steel plate sized to lap 2 in. (51 mm) beyond periphery of opening may be installed on minimum one side of floor or wall assembly on either side of assembly. Steel plate secured to concrete with 1/4 in. (6 mm) diam by 1-1/2 in. (38 mm) long steel concrete screws in conjunction with 1-1/4 in. (31 mm) diam steel fender washers. Fasteners spaced 1 in. (25 mm) from each corner and 8 in. (204 mm) center -to -center. When steel plate is used, the T, FT and FTH Ratings are 0 hr. * Bearing the UL Classification Marking #Bearing the UL Recognized Components Mark +Bearing the UL Listing Mark * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I o Created or Revised: February 24, 2016 us I C-AJ-8093 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 4 OF 4 Classified by N Laboratories, Inc.0Underwiters; to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. C-AJ-8113 ❑■ ? ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 2 Hr F Rating - 2 Hr T Rating - 0, 1/4, 1/2, 3/4 and 2 Hr (See Items 2 through 9) FT Rating - 0, 1/4, 1/2, 3/4 and 2 Hr (See Items 2 through 9) FH Rating - 2 Hr FTH Rating - 0, 1/4, 1/2, 3/4 and 2 Hr (See Items 2 through 9) A 10B 6 6 7 Y 5 10B 1 3 ................................................... .................................................................................................................................................................................................................... a . .. .............................. ......................... ........ ... .............. ° lllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllll ` 'a ' lllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllll '� . c 2 111 llllllllllllllllllllllllllllllllllllllllllllllllllllllllll. 10 4 7 5 10 Section A -A $ A 1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max area of opening is 1024 sq in. (0.66 m2) with a max height of 32 in. (813 mm) when installed in a wall or a max width of 32 in. (813 mm) when installed in a floor. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Metallic Penetrants - One or more metallic pipes, conduits or tubes to be installed within the opening. Annulus between penetrants is min 0 in. (point contact) to max 24 in. (609 mm). Annulus between penetrants and periphery of opening is 0 in. (point contact) to max 24 in. (609 mm). Penetrants rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) electrical metallic tubing (EMT), or nom 4 in. (102 mm) diam (or smaller) steel Flexible Metal Conduit#. D. Copper Pipe or Tube - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe or Type M (or heavier) coppertube. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Hit T I Created or Revised: May 12, 2017 WIW C-AJ S 8113 I (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Webs ite:www.stifirestop.com F PAGE 1 AGE 1 OF 4 Type of Metallic Penetrant Max Dim of Throught Penetrants, In. mm T Rating, Hr Steel or Iron Pipe, Conduit 12 (305) 0 Copper Pipe or Tube 6 (152) 0 Steel or Iron Pipe, Conduit or EMT 4 (102) 1/4 Steel or Iron Pipe, Conduit or EMT 2 (51) 1/2 Steel or Iron Pipe, Conduit or EMT 1(25) 3/4 3. Pipe Insulation - One or more max 4 in. (102 mm) metallic pipes or tubes may be insulated. Annulus between penetrants is min 0 in. (point contact) to max 24 in. (609 mm). Annulus between penetrants and periphery of opening is 0 in. (point contact) to max 24 in. (609 mm). The annular space between metallic pipes, conduit and tubes and insulated pipes and tubes shall be a min 1/2 in. (13 mm) to max 24 in. (609 mm). Penetrants rigidly supported on both sides of floor or wall assembly. The following types of pipe insulation may be used: A. Pipe and Equipment Covering Materials* - Nom 1 in. (25 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. When Item 3A is used, T Rating is 3/4 Hr. See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. B. Pipe Covering Materials* - Nom 2 in. (51 mm) thick unfaced mineral fiber pipe insulation having a nom density of 3.5 pcf (56 kg/m3) (or heavier) and sized to the outside diam of the pipe or tube. Pipe insulation secured with min 8 AWG steel wire spaced max 12 in. (305 mm) OC. When Item 3B is used, T Rating is 2 Hr. INDUSTRIAL INSULATION GROUP L L C - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT and High Temperature Pipe Insulation Thermaloc C. Sheathing Material* - Use in conjunction with Item 3B. Foil-scrim-kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 3B) with the kraft side exposed. Longitudinal and transverse joints sealed with metal fasteners or butt tape. See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any sheathing material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. D. Tube Insulation -Plastics## - Nom 3/4 in. (19 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. When Item 3D is used, T Rating is 1/2 Hr. See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. E. Pipe Covering Materials* - Cellular Glass Insulation - Nom 2 to 3 in. (51 to 76 mm) thick cellular glass units sized to the outside diam of the pipe or tube and supplied in nom 24 in. (610 mm) long half sections or nom 18 in.(457 mm) long segments. Pipe insulation installed on pipe in accordance with the manufacturer's instructions. When Item 3E is used, T Rating is 2 Hr. F. Metal Jacket - Used in conjunction with Item 3E. Min 12 in. (305 mm) long jacket formed from min 0.010 in. (0.25 mm) thick aluminum sheet cut to wrap tightly around the pipe insulation with a min 2 in. (51 mm) lap and secured using bands and seals of a similar material or min No. 18 AWG steel tie wire. Bands or steel tie wire to be located within 2 in. (51 mm) of each end of the jacket and spaced max 10 in. (254 mm) OC. Jacket installed with edge abutting surface of fill material (Item 9A) on top surface of floor or both surfaces of wall. Metal jacket to be used in addition to any other jacketing material which may be required on the pipe covering. G. Pipe and Equipment Covering Materials* - Nom 2 to 3 in. (51 to 76 mm) thick hollow cylindrical calcium silicate (min 14 pcf or 224 kg/m3) units sized to the outside diam of the pipe or tube. Pipe insulation secured with stainless steel bands or min 8 AWG stainless steel wire spaced max 12 in. (305 mm) OC. When Item 3G is used, T Rating is 2 Hr. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: May 12, 2017 STI0 C-3 1 (800)992-1180 • (908)526-8000 •FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE GE22 O OF 4 4. Nonmetallic Penetrants - One or more nonmetallic pipes, conduits or tubes to be installed within the opening. Annulus between penetrants and periphery of opening is min 1 in. (25 mm) to max 24 in. (609 mm). Separation between metallic and nonmetallic penetrants is min 6 in. (152 mm). Penetrants rigidly supported on both sides of floor or wall assembly. The following types and sizes of nonmetallic pipes, conduits or tubing may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) solid or cellular core Schedule 40 PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit+ - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA 70). D. Electrical Nonmetallic Tubing (ENT)+ - Nom 2 in. (51 mm) diam (or smaller) corrugated wall ENT formed of polyvinyl chloride (PVC) installed in accordance with the National Electrical Code (NFPA 70). E. Optical Fiber Raceway+ - Nom 2 in. (51 mm) diam (or smaller) optical fibner raceway (innerduct). Optical fiber raceway installed in accordance with Article 770 of the National Electrical Code (NFPA 70). When Item 4 is used, the T Rating of the firestop system is 2 hr. 5. Cables - Nom 4 in. (102 mm) diam (or smaller) tight bundle of cables. Annulus between cable bundle and periphery of opening is min 0 in. (point contact) to max 24 in. (609 mm). Separation between cable bundle and metallic or nonmetallic penetrants shall be min 6 in. (152 mm). Cable bundle rigidly supported on both sides of floor or wall assembly. The following types and sizes of cables may be used: A. Max 1/C - 1000 kcmil cable with polyvinyl chloride (PVC) or cross -linked polyethylene (XLPE) insulation and jacket. B. Max 7/C - No. 12 AWG cable with PVC -nylon insulation and PVC jacket. C. Max 400 pair - No. 24 AWG copper conductor telephone cable with PVC insulation and jacket. D. Max RG/U coaxial cables with fluorinated ethylene jacket and insulation. E. Multiple fiber optic cables with PVC insulation. F. Through Penetrating Products* - Max 4/C with ground No. 2/0 AWG Metal -Clad Cable+. AFC CABLE SYSTEMS INC When cables are used, T Rating is 1/2 hr. 6. Cable Tray - Max 30 in. (762 mm) wide by max 6 in. (152 mm) deep open ladder cable tray with channel -shaped side rails formed from min 0.060 in. (1.5 mm) thick (No. 16 MSG) galv steel or min 0.060 in. (1.5 mm) thick aluminum with rungs spaced max 9 in. (229 mm) OC. A max of two cable trays may be installed within the opening with a min vertical separation of 4 in. (102 mm) and a min horizontal separation of 1/4 in. (6 mm) between trays. Max vertical or horizontal separation is 24 in. (609 mm). Annulus between the cable tray and the periphery of the opening is min 0 in. (point contact) to max 24 in. (609 mm). Separation between cable tray and metallic or nonmetallic penetrants is min 6 in. (152 mm). Cable trays to be rigidly supported on both sides of the floor or wall assembly. Aggregate cross -sectional area of cables in cable tray not to exceed 40 percent of the cross -sectional area of the cable tray based on a max 3 in. (76 mm) cable loading depth within tray. Any combination of the cable types specified in Item 5 may be used. When cable tray is used, T Rating is 1/2 hr. 7. Busway+ - Nom 19 in. (483 mm) wide (or smaller) by 6 in. (152 mm) deep "I" shaped aluminum enclosure containing factory -mounted copper bars rated for 600 V, 5000 A or max 26 in. (660 mm) wide by max 6 in. (152 mm) deep "I" shaped aluminum enclosure containing factory -mounted aluminum bars rated for 600 V, 4000 A. A max of two busways may be installed within the opening with a min separation of 1 in. (25 mm) to max 24 in. (609 mm). The annular space between the busway and the periphery of the opening shall be a min 0 in. (point contact) to a max 24 in. (609 mm). Busways spaced min 6 in. (152 mm) from all other penetrants. Busway to be rigidly supported on both sides of floor or wall assembly. The busway shall bear the UL Listing Mark and shall be installed in accordance with all provisions of the National Electrical Code, NFPA 70. When busway is used, the T Rating is 1/4 hr. 8. Air Conditioning (AC) Line Set - One or more AC line sets installed within opening. Each AC line set consists of two pipes or tubes (Item 8A), tubing insulation (Item 8B) and a thermostat cable (Item 8C). The space between the AC line sets shall be min 2 in. (51 mm). The space between the AC line sets and the periphery of the opening shall be min 0 in. (point contact) to max 24 in. (609 mm). The AC line sets shall be spaced min 6 in. from uninsulated metallic penetrants and shall be rigidly supported on both sides of the floor or wall assembly. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. 113 ST I a Created or Revised: May 12, 2017 I@ AGE380F4 0 800 992-1180 • 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com 8A. Through Penetrant - A max of two pipes or tubes to be installed in each AC line set. Of the two pipes or tubes, only one may have a nom diam greater than 1/2 in. (13 mm). The following types and sizes of through penetrants may be used: A. Steel Pipe - Nom 1 in. (25 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 1 in. (25 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Pipe - Nom 1 in. (25 mm) diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tube - Nom 1 in. (25 mm) diam (or smaller) Type L (or heavier) copper tube. 8B. Tube Insulation - Plastics# - Nom 3/4 in. (19 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The tube insulation may be installed on one max 3/4 in. (19 mm) diam pipe or tube in each AC line set. The space between the insulated and uninsulated pipes or tubes within each AC line set shall be 0 in. (point contact). See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation meeting the above specifications and having a UL 94 Flammability Classification of 945VA may be used. 8C. Cable - One 4 pair No. 18 AWG (or smaller) thermostat cable with polyvinyl chloride (PVC) insulation and jacket materials may be installed with each AC line set. When Item 8 is used, the T Rating of the firestop system is 1/4 hr. 9. Steel Duct - (Not Shown) Nom 12 in. (305 mm) diameter (or smaller) No. 30 GA (or heavier) steel duct installed within opening when opening contains no cables or cable tray. A max of two steel ducts may be installed within the through -opening. Ducts to be spaced min 4 in. (102 mm) apart and min 8 in. (203 mm) from insulated penetrants and nonmetallic penetrants. Annulus between the steel duct and the periphery of the opening shall be min 0 in. (point contact) to max 24 in. (0 to 609 mm). Steel ducts to be rigidly supported on both sides of floor or wall assembly. When steel duct is used, the T Rating is 0 hr. 10. Firestop System - The firestop system shall consist of the following items: A. Packing Material - Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation tightly packed into opening. Packing material recessed from top surface of floor assembly or from both surfaces of wall or precast concrete units to accommodate the required thickness of fill material. B. Fill, Void or Cavity Materials" - Sealant - Min 1/2 in. (13 mm) depth of fill material applied within the annulus, flush with top surface of floor assembly or with both surfaces of the wall assembly. Additional fill material forced into interstices of grouped cables and grouped cables within cable trays. At point contact location between through penetrant and concrete, a min 3/8 in. (9.6 mm) diam of fill material shall be applied at through penetrant/concrete interface on top surface of floor or both surfaces of the wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. #Bearing the UL Recognized Components Mark +Bearing the UL Listing Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: May 12, 2017 STC-GE40 3 o (800)992-1180 • (908)526-8000 *FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 4 OF 4 Classified by Underwriters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) WN-1.4 System No. C-AJ-8114 F Rating - 2 Hr T Ratings - 0, 1/2, and 2 Hr (See Items 2 through 6) Section A -A 1. Floor or Wall Assembly -Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max area of opening is 1920 sq in. (1.2 m2) with a max dim of 48 in. (1.2 m). See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Metallic Conduits - One or more nom 6 in. (152 mm) diam (or smaller) rigid steel conduits, nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or nom 1 in. (25 mm) diam (or smaller) flexible steel conduits installed within the opening. Min space between conduits and periphery of opening is 1 in. (25 mm). Min space between conduits is 1 in. (25 mm). Conduit to be rigidly supported on both sides of floor or wall assembly. When metallic conduit is used, the T Rating is 1/2 hr. 3. Cables - Nom 4 in. (102 mm) diam (or smaller) tight bundle of cables. Cable bundle spaced min 6 in. (152 mm) from metallic conduits. Clearance between cable bundle and periphery of opening is min 2 in. (51 mm). Cable bundle rigidly supported on both sides of floor or wall assembly. The following types and sizes of cables may be used: A. Max VC - 350 kcmil cable with polyvinyl chloride (PVC) or cross -linked polyethylene (XLPE) insulation and jacket. B. Max 7/C - No. 12 AWG cable with PVC -nylon insulation and PVC jacket. C. Max 200 pair No. 24 AWG copper conductor cable with PVC insulation and jacket. D. Max RG/U coaxial cables with fluorinated ethylene jacket and insulation. E. Multiple fiber optic cables with PVC insulation. F. Through Penetrating Products* - Max 3/C with ground No. 12 AWG Metal -Clad Cable+. AFC CABLE SYSTEMS INC When cables are used, the T Rating is 0 hr. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: February 24, 2016 @ C-AJ-8114 S 1T I ® ( ) ( ) AGE 1 OF 2 (800)992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com 4. Cable Tray - Max 30 in. (762 mm) wide by 6 in. (152 mm) deep open ladder cable tray with channel -shaped side rails formed from min 0.060 in. (1.5 mm) thick (No. 16 GA) galv steel or min 0.060 in.(1.5 mm) thick aluminum with rungs spaced max 9 in. (227 mm) OC. A max of three cable trays may be installed within the opening with a min separation of 6 in. (152 mm) between cable trays and with a min separation distance of 6 in. (152 mm) from metallic conduits. The min space between the cable tray and the periphery of the opening is 2 in. (51 mm). Cable trays rigidly supported on both sides of floor or wall assembly. Aggregate cross -sectional area of cables in cable tray not to exceed 40 percent of the cross -sectional area of the cable tray based on a max 3 in. (76 mm) cable loading depth within the tray. Any combination of the cable types specified in Item 3 may be used. When cable tray is used, the T Rating is 0 hr. 5. Nonmetallic Conduits - One or more nonmetallic conduits spaced min 1 in. (25 mm) apart and 1 in. from periphery of opening. Min clearance between nonmetallic conduits and metallic conduits is 6 in. (152 mm). Penetrants rigidly supported on both sides of floor or wall assembly. Any of the following types and sizes may be used. A. Rigid Nonmetallic Conduit+ - Nom 2 in. (51 mm) diam (or smaller) PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA 70). B. Optical Fiber Raceway (OFR)+ - Nom 2 in. (51 mm) diam (or smaller) OFR formed of either polyvinyl chloride (PVC) or polyvinylidene fluoride (PVDF) installed in accordance with Article 770 of the National Electrical Code (NFPA 70). See Optical Fiber Raceway (QAZM) category in the Electrical Constructions Materials Directory for names of manufacturers. When nonmetallic conduit is used, the T Rating is 0 hr. 6. Busway+ - Nom 19 in. (483 mm) wide (or smaller) by 5 in. (127 mm) deep "I" shaped aluminum enclosure containing factory -mounted copper bars rated for 600 V, 5000 A or aluminum bars rated for 600 V, 4000 A. A max of two busways may be installed within the opening. The min space between the busway and the periphery of the opening is 2 in. Busways spaced min 6 in. (152 mm) from all other penetrants. Busway to be rigidly supported on both sides of floor or wall assembly. The busway shall bear the UL Listing Mark and shall be installed in accordance with all provisions of Article 364 of the National Electrical Code, NFPA 70. When busway is used, the T Rating is 0 hr. 7. Firestop System - The firestop system consists of the following items: A. Fill, Void or Cavity Material* - Putty or Sealant - (Not Shown) - Fill material forced into grouped cable interstices to max extent possible. SPECIFIED TECHNOLOGIES INC - SpecSeal Putty or SpecSeal 100, 101, 105, 120 or 129 Sealant B. Fill, Void or Cavity Material* - Wrap Strip - Nom 1/8 in. (3.2 mm) thick by 1-1/2 in. (38 mm) wide (RED2), nom 1/4 in. (6 mm) thick by 1-1/2 in. (38 mm) wide (RED), 3/16 in. (4.8 mm) by 2 in. (51 mm) wide (BLU) or 1/8 in. (3.2 mm) by 2 in. (51 mm) wide (BLU2) intumescent strips faced on both sides with a plastic film.. One layer of wrap strip installed in web sections of busway and wrapped around outer circumference of nonmetallic conduit. Wrap strip ends butted and held in place with aluminum foil tape. In floors, the bottom edge of wrap strip shall be recessed 1-1/2 in. from the bottom surface of the floor. In walls having a thickness of 5 in. or less, the wrap strip shall be centered at mid -depth of wall assembly. In walls having a thickness of greater than 5 in., the wrap strip shall be installed on both sides of the wall such that the exposed edge of wrap strip is recessed 1-1/4 in. from each side of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal BLU or BLU2 Wrap Strip or SpecSeal RED or RED2 Wrap Strip C. Forms - (Not Shown) - Used as a form to prevent leakage of fill material. Forms to be rigid sheet material cut to fit the contours of the penetrants and positioned on the bottom surface of floor or both sides of wall to accommodate the required thickness of fill material. Forms to be removed after fill material has cured. D. Fill, Void or Cavity Material* - Mortar - Min 3-1/2 in. (89 mm) thickness of fill material applied within annulus. Mortar to be mixed with water in accordance with the installation instructions provided with the product. When cable tray or cables are used, min thickness of mortar is 4-1/2 in. (114 mm). SPECIFIED TECHNOLOGIES INC - SpecSeal Mortar * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. #Bearing the UL Recognized Components Mark +Bearing the UL Listing Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S 1 I ® Created or Revised: February 24, 2016 C-AJ-8114 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Websitemww.stifirestop.com PAGE 2 OF 2 Classified by a Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-C-8021 ❑■ ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 1 Hr F Rating - 1 Hr T Ratings - 1/2 and 1 Hr (See Item 2) FT Ratings - 1/2 and 1 Hr (See Item 2) FH Rating - 1 Hr FTH Ratings -1/2 and 1 Hr (See Item 2) 2 4 A 1A 6 4 6 5 3 2 i 1C A Section A -A 1. Floor -Ceiling Assembly - The 1 hr fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Designs in the UL Fire Resistance Directory, as summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor -Ceiling Design. Max diam of opening is 4-1/2 in. (114 mm). B. Wood Joists - Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Floor -Ceiling Design. Max diam of opening is 4-1/2 in. (114 mm). 1A. Chase Wall - (Optional, Not Shown) - The through penetrant (Item 2) may be routed through a single, double or staggered wood stud/gypsum board chase wall. Depth of chase wall stud cavity to be min 1/2 in. (13 mm) greater than diameter of opening cut in sole and top plates to accommodate the through penetrant (Item 2). The chase wall shall include the following construction features: A. Studs - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max diam of opening is 4-1/2 in. (114 mm). C. Top Plate - The single or double top plate shall consist of one or two nom 2 by 4 in. (51 by 102 mm) or one or two nom 2 by 6 in. (51 by 152 mm) or one or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max diam of opening is 4-1/2 in. (114 mm). D. Gypsum Board* - Min 1/2 in. (13 mm) thick rated or nonrated gypsum board. 2. Through Penetrant - One or more metallic pipes, conduits or tubing to be installed either concentrically or eccentrically within the opening. Pipes, conduits or tubing to be spaced min 0 in. (0 mm) (point contact) to max 1 in. (25 mm) apart. The space between the pipes, conduits or tubing and the periphery of the opening shall be min 0 in. (0 mm) (point contact) to max 1 in. (25 mm). Penetrants to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of metallic pipe, conduits or tubing may be used: A. Steel Pipe - Nom 3/4 in. (19 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: June 05, 2015 810 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com �° PAGE F12 B. Iron Pipe - Nom 3/4 in. (19 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 3/4 in. (19 mm) diam (or smaller) steel conduit or steel electrical metallic tubing. D. Copper Pipe or Tube - Nom 3/4 in. (19 mm) diam (or smaller) Regular (or heavier) copper pipe or Type L (or heavier) copper tube. When metallic pipe, conduit or tubing without insulation is used, T, FT and FTH Ratings are 1/2 hr. Otherwise, T, FT and FTH Ratings are 1 hr. 3. Tube Insulation - Plastics# - Nom 1 in. (25 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. Tube insulation to be installed on a max of two metallic pipes or tubes. Insulated pipe or tubing to be spaced 0 in. (0 mm) (point contact) to 1 in. (25 mm) from other through penetrants (Items 2, 4 and 5). The space between the insulated pipe or tube and the periphery of the opening shall be min 0 in. (0 mm) (point contact) to max 1 in. (25 mm). See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. 4. Nonmetallic Through Penetrant - One nonmetallic pipe, conduit or tube to be installed within the firestop system. Pipe, conduit or tube to be spaced min 0 in. (0 mm) (point contact) to max 1 in. (25 mm) from the insulated through penetrants and min 1/2 in. (13 mm) to max 1 in. (25 mm) from non -insulated through penetrants. The space between the pipe, conduit or tube and the periphery of the opening shall be min 0 in. (0 mm) (point contact) to max 1 in. (25 mm). Pipe, conduit or tube to be rigidly supported on both sides of floor -ceiling assembly. One of the following types and sizes of nonmetallic through penetrants may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 1-1/4 in. (32 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in vented (drain, waste or vent) or closed (process or supply) piping system. B. Chlorinated Polyvinyl (CPVC) Pipe - Nom 1-1/4 in. (32 mm) diam (or smaller) SDR17 CPVC pipe for use in vented (drain, waste or vent) or closed (process or supply) piping system. C. Rigid Nonmetallic Conduit+ - Nom 1-1/4 in. (32 mm) diam (or smaller) PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA 70). D. Electrical Nonmetallic Tubing (ENT) - Nom 1-1/4 in. (32 mm) diam (or smaller) PVC tubing installed in accordance with Article 331 of the National Electrical Code (NFPA 70). E. Cross Linked Polyethylene (PEX) Tubing - Nom 1 in. (25 mm) diam (or smaller) SDR9 PEX tubing for use in closed (process or supply) piping systems. 5. Cables - Max two 4 pair No. 18 AWG (or smaller) cables with PVC insulation and jacketing. Cables to be spaced min 0 in. (0 mm) (point contact) to max 1 in. (25 mm) from the other through penetrants. The space between the cables and the periphery of the opening shall be min 0 in. (0 mm) (point contact) to max 1 in. (25 mm). Cables to be rigidly supported on both sides of the floor -ceiling assembly. 6. Fill, Void or Cavity Material* - Caulk or Sealant - Min 3/4 in. (19 mm) thickness of fill material applied within the annulus, flush with the top surface of the floor or sole plate. Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with bottom surface of ceiling or top plate. Additional fill material forced into grouped penetrant interstices to max extent possible. At point contact locations, min 1 /4 in. (6 mm) diam bead of fill material applied at grouped penetrant bundle/subfloor or sole plate interface and at grouped penetrant bundle/ceiling or top plate interface. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant or Type WF300 Caulk * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. #Bearing the UL Recognized Component Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: June 05, 2015 T I ® 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. L to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. F-C-8029 ❑■ ; ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating - 1 Hr F Rating - 1 Hr T Ratings - 1/2 and 3/4 Hr (See Item 2) FT Ratings - 1/2 and 3/4 Hr (See Item 2) L Rating At Ambient - Less Than 1 CFM/sq ft FH Rating - 1 Hr L Rating At 400 F - Less Than 1 CFM/sq ft FTH Ratings - 1/2 and 3/4 Hr (See Item 2) L Rating At Ambient - Less Than 1 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft 2A 2B C 3 1A A A 2 2B C 1B O 3 1B 1_�; 1C Section A -A 1. Floor -Ceiling Assembly - The 1 hr fire -rated wood joist floor -ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Designs in the UL Fire Resistance Directory, as summarized below: A. Flooring System - Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture` as specified in the individual Floor -Ceiling Design. Max area of rectangular opening cut in flooring is 43-1/2 sq in. (0.028 m2) with a max width dimension of 3 in. (76 mm) and with a max length dimension of 14-1/2 in. (368 mm). Longer dimension of rectangular opening to be perpendicular to wood joist direction. B. Wood Joists - Nom 10 in. (254 mm) deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* - Thickness, type, number of layers and fasteners as required in the individual Floor -Ceiling Design. Max area of rectangular opening cut in gypsum board ceiling is 43-1/2 sq in. (0.028 m2) with a max width dimension of 3 in. (76 mm) and with a max length dimension of 14-1/2 in. (368 mm). 1A. Chase Wall - (Optional, Not Shown) - The through penetrants (Item 2) may be routed through a 1 hr fire rated single, double or staggered wood stud/gypsum board chase wall. Depth of chase wall stud cavity to be min 1/2 in. (13 mm) greater than width of opening cut in sole and top plates to accommodate the through penetrants. The chase wall shall be constructed of the materials and in the manner specified in the individual U300 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or double nom 2 by 4 in. (51 by 102 mm) lumber studs. B. Sole Plate - Nom 2 by 4 in. (51 by 102 mm), 2 by 6 in. (51 by 152 mm) or parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max area of rectangular opening cut in sole plate is 43-1/2 sq in. (0.028 m2) with a max width dimension of 3 in. (76 mm) and with a max length dimension of 14-1/2 in. (368 mm). Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. us S T I Created or Revised: January 23, 2014 F-C-8029 I o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com 0 Website:www.stifirestop.com PAGE 1 OF 2 C. Top Plate - The double top plate shall consist of two nom 2 by 4 in. (51 by 102 mm), two nom 2 by 6 in. (51 by 152 mm) or two sets of parallel 2 by 4 in. (51 by 102 mm) lumber plates, tightly butted. Max area of rectangular opening cut in top plate is 43-1/2 sq in. (0.028 m2) with a max width dimension of 3 in. (76 mm) and with a max length dimension of 14-1/2 in. (368 mm). D. Gypsum Board* - Thickness, type, number of layers and fasteners shall be as specified in the individual Wall and Partition Design. 2. Through Penetrants - One or more metallic or nonmetallic pipes, conduits, tubing or cables to be installed either concentrically or eccentrically within the opening. Min separation between penetrants to be 1 in. (25 mm). Annular space between the penetrants and the periphery of the opening shall be min 0 in. (point contact) to max 1 in. (25 mm). Penetrants to be rigidly supported on both sides of floor -ceiling assembly. The following types and sizes of through penetrants may be used: A. Metallic Penetrants - The following types and sizes of metallic pipes, conduits or tubes may be used: Al. Steel Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. A2. Iron Pipe - Nom 2 in. (51 mm) diam (or smaller) cast or ductile iron pipe. A3. Copper Pipe or Tubing - - Nom 2 in. (51 mm) diam (or smaller) Type L (or heavier) copper tube or Regular (or heavier) copper pipe. A4. Conduit - Nom 2 in. (51 mm) diam (or smaller) rigid steel conduit, electrical metallic tubing (EMT) or flexible steel or aluminum conduit. B. Nonmetallic Penetrants - The following types and sizes of nonmetallic pipes, conduits or tubes may be used: B1. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B2. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) SDR11 CPVC pipe for use in closed (process or supply) piping systems. B3. Rigid Nonmetallic Conduit (RNC)+ - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA 70). B4. Electrical Nonmetallic Tubing (ENT)+ - Nom 2 in. (51 mm) diam (or smaller) PVC tubing installed in accordance with the National Electrical Code (NFPA 70). B5. Cross Linked Polyethylene (PEX) Tubing - Nom 1 in. (25 mm) diam (or smaller) SDR 9 PEX tubing for use in closed (process or supply) piping systems. C. Cables - The following types of cables may be used: Cl. Max 200 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with PVC insulation and jacketing. C2. Max 3/C No. 3/0 AWG (or smaller) aluminum or copper conductor SER cable with PVC insulation and jacketing. C3. Max 3/C with ground No. 8 AWG (or smaller) Type NM (Romex) nonmetallic sheathed cable with PVC insulation and jacketing. C4. Max 7/C No. 12 AWG (or smaller) power/control cables with PVC insulation and jacketing. C5. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with PVC insulation and jacketing. C6. Max RG/U coaxial cable with copper conductor and fluorinated ethylene insulation and jacket. C7. Max 4 pair No. 18 AWG (or smaller) copper conductor instrumentation cable with PVC insulation and jacketing. C8. Fiber optic cable with PVC insulation and jacketing. C9. Through -Penetrating Products* - Max 4/C with ground No. 2/0 AWG (or smaller) aluminum or copper conductor, aluminum or steel jacketed Metal -Clad+ or Armored -Clad+ cable. The T Rating is 3/4 hr unless copper pipe or tube is used. When copper pipe of tube is used, the hourly T Rating is 1/2 hr. 3. Fill, Void or Cavity Material* - Sealant - Min 3/4 in. (19 mm) thickness of fill material applied within the annulus, flush with the top surface of the floor or chase wall sole plate. Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with bottom surface of gypsum board ceiling or chase wall top plate. Min 1/4 in. (6 mm) diam bead of fill material applied at point contact location on the top surface of floor or chase wall sole plate and at the penetrant/ceiling or penetrant/chase wall top plate interface. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant or Type WF300 Firestop Caulk * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. +Bearing the UL Listing Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 F-C-8029 T I ® (800)992-1180 9 (908)526-8000 9 FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) N 3 System No. W-L-8003 (Formerly System No. 633) F Ratings - 1 and 2 Hr (See Item 1 B) T Rating - 0 Hr L Rating At Ambient - 8 CFM/sq ft L Rating At 400 F - Less Than 1 CFM/sq ft A Section A -A 1. Wall Assembly - The 1 or 2 h fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. In 2 h fire -rated assemblies, steel studs to be min 2-1/2 in. wide and spaced max 24 in. OC. In 1 h fire rated assemblies, steel studs to be min 3-5/8 in. wide and spaced 24 in. OC. Additional studs shall be installed horizontally in such a manner to form a nom 22-3/4 in. wide by 6 in. high opening. B. Gypsum Board* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. If the through penetrants are installed in a wood stud/gypsum board assembly, the max area of opening is 87 sq. in. with max dimension of 14-1/2 in. The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants - Four pipes, conduits or tubing to be installed within the opening. The space between pipes, conduits or tubing shall be a nom 1-7/8 in. The space between pipes, conduits or tubing and periphery of opening shall be min 5/8 in. to max 1-15/16 in. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of pipes, conduits or tubing may be used: A. Steel Pipe - Nom 3 in. diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 2 in. diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 3 in. diam (or smaller) steel electrical metallic tubing or steel conduit. D. Copper Tubing - Nom 2 in. diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe - Nom 2 in. diam (or smaller) Regular (or heavier) copper pipe. F. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. diam (or smaller) Schedule 40 PVC pipe for use in closed (process or supply) piping system. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S 1TI ® Created or Revised: January 2, 2009 W-L-8003 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 2 3. Pipe Covering - One of the following types of pipe coverings shall be used: A. Pipe and Equipment Covering - Marerials* - Nom 1 in. thick hollow cylindrical heavy density (min 3.5 pcf) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. The pipe covering may be installed on one of the metallic pipes or tubing having a nom diam of 2 in. or less. The insulated pipe or tubing shall be spaced a nom 1-7/8 in. from the other through -penetrants. The annular space between the insulated through penetrant and periphery of the opening shall be a nom 1 in. See Pipe and Equipment Covering - Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. B. Pipe Covering Materials* - Nom 1 in. thick unfaced mineral fiber pipe insulation sized to the outside diam of pipe or tube. Pipe insulation secured with min 8 AWG steel wire spaced max 12 in. OC. The insulated pipe or tubing shall be spaced a nom 1-7/8 in. from the other through -penetrants. The annular space between the insulated through penetrant and periphery of opening shall be a nom 1 in. IIG MINWOOL L L C - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT or High Temperature Pipe Insulation Thermaloc C. Sheathing Material* - (Not shown) - Used in conjunction with Item 3B. Foil-scrim-kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 3B) with the kraft side exposed. Longitudinal joints and transverse joints sealed with metal fasteners or butt tape. See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any sheathing material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4. Cables - Max six cables to be installed within the firestop system. Cables to be spaced 1-1/2 in. from the through -penetrants. The space between the cables and periphery of opening shall range from a min 1 in. to a max 2-7/8 in. Cables to be tightly bundled together and rigidly supported on both surfaces of wall. Any combination of the following types and sizes of copper conductor cables may be used: A. Max 25 pair No. 24 AWG (or smaller) telephone cables with polyvinyl chloride (PVC) insulation and jacket. B. Max 3/C (with ground) - No. 10 AWG (or smaller) nonmetallic sheathed ("Romex" ) cable with PVC insulation and jacket. C. Max 4 pair No. 18 AWG (or smaller) thermostat cables with PVC insulation and jacket. 5. Firestop System - The firestop system shall consist of the following: A. Packing Material - In 2 h fire -rated assemblies, min 2-1/2 in. thickness of min 6 pcf mineral wool batt insulation firmly packed into opening as a permanent form. In 1 h fire -rated assemblies, min 2-1/4 in. thickness of mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Caulk - Min 1-1/4 in. thickness of fill material applied within the annulus, on both surfaces of wall. Caulk to be forced into interstices of cable group to max extent possible. Additional caulk to be installed such that a min 1 in. is lapping beyond periphery of the opening. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I Created or Revised: January 2, 2009 I W-L-8003 o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) A 5 4 2 3 A System No. W-L-8025 F Ratings - 1 and 2 Hr (See Item 1) T Rating - 1/4 Hr Section A -A 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features. A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 3-1/2 in. (89 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant - A max of two pipes or tubes to be installed within the opening. Of the two pipes or tubes, only one may have a nom diam greater than 1/2 in. (13 mm). Annular space between pipes or tubing and periphery of opening shall be min 0 in. (point contact) to max 1-1/2 in. (38 mm). Separation between uninsulated pipes or tubes shall be min 0 in. (point contact) to max 1-1/2 in. (38 mm). Pipes or tubing to be rigidly supported on both sides of the wall assembly. The following types and sizes of through penetrants may be used: A. Steel Pipe - Nom 1 in. (25 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 1 in. (25 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Pipe - Nom 1 in. (25 mm) diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tube - Nom 1 in (25 mm) diam (or smaller) Type L (or heavier) copper tube. 3 Tube Insulation - Plastics# - Nom 3/4 in. (19 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The tube insulation may be installed on a max of one pipe or tube. The annular space between the insulated penetrating item and the periphery of the opening shall be min 0 in. (point contact) to max 1/2 in. (13 mm). The space between insulated and uninsulated pipes or tubing shall be 0 in. (point contact). See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. 4. Cable - One 4 pair No. 18 AWG (or smaller) thermostat cable with polyvinyl chloride (PVC) insulation and jacket materials. Cable to be spaced min 0 in. (point contact) to max 1/2 in. (13 mm) from the other penetrants. The space between the cable and the periphery of the opening shall be min 0 in. (point contact) to max 1/2 in. (13 mm). Cable to be rigidly supported on both sides of wall assembly. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 @ W-L-8025 T I ® 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Webs ite:www.stifirestop.corn GE 1 OF 2 5. Fill, Void or Cavity Material"- Sealant - Min 5/8 in (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. At point contact location, min 1/4 in. (6 mm) diam bead of fill material applied at through penetrant/gypsum board interface on both surfaces of wall. Additional fill material forced into grouped penetrant interstices to max extent possible. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant or Type WF300 Firestop Caulk (wood stud walls only). * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. #Bearing the UL Recognized Component Marking Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 W-L-8025 T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Webs ite:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ANSI/UL 1479 (ASTM E814) and CAN/ULC S115 System No. W-L-8026 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings - 1 and 2 Hr F Ratings - 1 and 2 Hr T Ratings - 0, 1/2, 1, 3/4 and 2 Hr (See Items 2, 3 and 4) FT Ratings - 0, 1/2, 1, 3/4 and 2 Hr (See Items 2, 3 and 4) FH Ratings - 1 and 2 Hr FTH Ratings - 0, 1/2, 1, 3/4 and 2 Hr (See Items 2, 3 and 4) p aection A -A 1. Wall Assembly - The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm). OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. Additional studs to be installed horizontally to form a rectangular box around the opening. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. When wood studs are used, interior of through opening to be lined with sheets of gypsum board around entire periphery to a total thickness of 5/8 in. (16 mm) or 1-1/4 in. (32 mm) for 1 or 2 hr wall assemblies, respectively. Max area of opening is 7 ft2 (0.66 m2)with a max height dimension of 32 in. (813 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Metallic Penetrants - One or more metallic pipes, conduits or tubes to be installed within the opening. Annulus between penetrants is min 0 in. (point contact) to max 24 in. (609 mm). Annulus between penetrants and periphery of opening is 0 in. (point contact) to max 24 in. (609 mm). Penetrants rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe - Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) electrical metallic tubing (EMT), or nom 4 in. (102 mm) diam (or smaller) steel Flexible Metal Conduit#. D Copper Pipe or Tube - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe or Type M (or heavier) copper tube. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: May 12, 2017 S T I o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com W-L-8026 PAGE 1 OF 4 Type of Max Diam of Through T Rating Hr Metallic Penetrant Penetrant in. mm Steel or Iron Pipe, 12 (305) 0 Conduit Copper Pipe or Tube 6 (152) 0 Steel or Iron Pipe, 4 (102) 1/4 Conduit or EMT Steel or Iron Pipe, 2 (51) 1/2 Conduit or EMT Steel or Iron Pipe, 1 (25) 3/4 Conduit or EMT Pipe Insulation - (Optional) - One or more max 4 in. (102 mm) metallic pipes or tubes may be insulated. Annulus between penetrants is min 0 in. (point contact) to max 26 in. (660 mm). Annulus between penetrants and periphery of opening is 0 in. (point contact) to max 24 in. (609 mm). The annular space between metallic pipes, conduit and tubes and insulated pipes and tubes shall be a min 1/2 in. (13 mm) to max 24 in. (609 mm). Penetrants rigidly supported on both sides of floor or wall assembly. The following types of pipe insulation may be used A. Pipe and Equipment Covering Materials* - Nom 1 in. (25 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. When Item 3A is used, T Rating is 3/4 Hr. See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. B. Pipe Covering Materials* - Nom 2 in. (51 mm) thick unfaced mineral fiber pipe insulation having a nom density of 3.5 pcf (56 kg/m3) (or heavier) and sized to the outside diam of the pipe or tube. Pipe insulation secured with min 8 AWG steel wire spaced max 12 in. (305 mm) OC. When Item 3B is used, T Rating is 2 Hr. INDUSTRIAL INSULATION GROUP L L C - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT and High Temperature Pipe Insulation Thermaloc C. Sheathing Material* - Use in conjunction with Item 3B. Foil-scrim-kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 3B) with the kraft side exposed. Longitudinal and transverse joints sealed with metal fasteners or butt tape. See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any sheathing material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. D Tube Insulation - Plastics# - Nom 3/4 in. (19 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. When Item 3D is used, T Rating is 1/2 Hr. See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. E Pipe Covering Materials* - Cellular Glass Insulation - Nom 2 to 3 in. (51 to 76 mm) thick cellular glass units sized to the outside diam of the pipe or tube and supplied in nom 24 in. (610 mm) long half sections or nom 18 in.(457 mm) long segments. Pipe insulation installed on pipe in accordance with the manufacturer's instructions. When Item 3E is used, T Rating is 2 Hr. PITTSBURGH CORNING CORP - FOAMGLAS F Metal Jacket - Used in conjunction with Item 3E. Min 12 in. (305 mm) long jacket formed from min 0.010 in. (0.25 mm) thick aluminum sheet cut to wrap tightly around the pipe insulation with a min 2 in. (51 mm) lap and secured using bands and seals of a similar material or min No. 18 AWG steel tie wire. Bands or steel tie wire to be located within 2 in. (51 mm) of each end of the jacket and spaced max 10 in. (254 mm) OC. Jacket installed with edge abutting surface of fill material (Item 9A) on both surfaces of wall. Metal jacket to be used in addition to any other jacketing material which may be required on the pipe covering. G. Pipe and Equipment Covering Materials* - Nom 2 to 3 in. (51 to 76 mm) thick hollow cylindrical calcium silicate (min 14 pcf or 224 kg/m3) units sized to the outside diam of the pipe or tube. Pipe insulation secured with stainless steel bands or min 8 AWG stainless steel wire spaced max 12 in. (305 mm) OC. When Item 3G is used, T Rating is 2 Hr. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: May 12, 2017 W-L-8026 T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 OF 4 4. Nonmetallic Penetrants - One or more nonmetallic pipes, conduits or tubes to be installed within the opening. Annulus between penetrants and periphery of opening is min 1 in. (25 mm) to max 24 in. (609 mm). Separation between metallic and nonmetallic penetrants is min 6 in. (152 mm). Penetrants rigidly supported on both sides of wall assembly. The following types and sizes of nonmetallic pipes, conduits or tubing may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) solid or cellular core Schedule 40 PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit+ - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA 70). D. Electrical Nonmetallic Tubing (ENT)+ - Nom 2 in. (51 mm) diam (or smaller) corrugated wall ENT formed of polyvinyl chloride (PVC) installed in accordance with the National Electrical Code (NFPA 70). E. Optical Fiber Raceway+ - Nom 2 in. (51 mm) diam (or smaller) optical fiber raceway (innerduct). Optical fiber raceway installed in accordance with the National Electrical Code (NFPA 70). When Item 4 is used, the T Rating of the firestop system is 2 hr. 5. Cables - Nom 4 in. (102 mm) diam (or smaller) tight bundle of cables. Annulus between cable bundle and periphery of opening is min 0 in. (point contact) to max 24 in. (609 mm). Separation between cable bundle and metallic or nonmetallic penetrants shall be min 6 in. (152 mm). Cable bundle rigidly supported on both sides of wall assembly. The following types and sizes of cables may be used: A. Max 1/C - 1000 kcmil cable with plenum rated, polyvinyl chloride (PVC) or cross -linked polyethylene (XLPE) insulation and jacket. B. Max 7/C - No. 12 AWG cable with PVC -nylon insulation and PVC jacket. C. Max 400 pair - No. 24 AWG copper conductor telephone cable with plenum rated or PVC insulation and jacket. D. Max RG/U coaxial cables with plenum rated or fluorinated ethylene jacket and insulation. E. Multiple fiber optic cables with plenum rated or PVC insulation. F. Through Penetrating Product" - Any cables, Armored Cable+ or Metal Clad Cable+ currently Classified under the Through Penetrating Product category. See Through Penetrating Product (XHLY) category in the Fire Resistance Directory for names of manufacturer. When cables are used, T Rating is 1/2 hr. 6. Cable Tray - Max 30 in. (762 mm) wide by max 6 in. (152 mm) deep open ladder cable tray with channel -shaped side rails formed from min 0.060 in. (1.5 mm) thick (No. 16 MSG) galv steel or min 0.060 in. (1.5 mm) thick aluminum with rungs spaced max 9 in. (229 mm) OC. A max of two cable trays may be installed within the opening with a min vertical separation of 4 in. (102 mm) and a min horizontal separation of 1/4 in. (6 mm) between trays. Max vertical or horizontal separation is 24 in. (609 mm). Annulus between the cable tray and the periphery of the opening is min 0 in. (point contact) to max 24 in. (609 mm). Separation between cable tray and metallic or nonmetallic penetrants is min 6 in. (152 mm). Cable trays to be rigidly supported on both sides of the wall assembly. Aggregate cross -sectional area of cables in cable tray not to exceed 40 percent of the cross -sectional area of the cable tray based on a max 3 in. (76 mm) cable loading depth within tray. Any combination of the cable types specified in Item 5 may be used. When cable tray is used, T Rating is 1/2 hr. 7. Busway+ - Nom 19 in. (483 mm) wide (or smaller) by 6 in. (152 mm) deep "I" shaped aluminum enclosure containing factory -mounted copper bars rated for 600 V, 5000 A or max 26 in. (660 mm) wide by max 6 in. (152 mm) deep "I" shaped aluminum enclosure containing factory -mounted aluminum bars rated for 600 V, 4000 A.. A max of two busways may be installed within the opening with a min separation of 1 in. (25 mm) to max 24 in. (609 mm). The annular space between the busway and the periphery of the opening shall be a min 0 in. (point contact) to a max 24 in. (609 mm). Busways spaced min 6 in. (152 mm) from all other penetrants. Busway to be rigidly supported on both sides of wall assembly. The busway shall bear the UL Listing Mark and shall be installed in accordance with all provisions of the National Electrical Code, NFPA 70. When busway is used, the T Rating is 1/4 hr. 8. Air Conditioning (AC) Line Set - One or more AC line sets installed within opening. Each AC line set consists of two pipes or tubes (Item 8A), tubing insulation (Item 8B) and a thermostat cable (Item 8C). The space between the AC line sets shall be min 2 in. (51 mm). The space between the AC line sets and the periphery of the opening shall be min 0 in. (point contact) to max 24 in. (609 mm). The AC line sets shall be spaced min 6 in. from uninsulated metallic penetrants and shall be rigidly supported on both sides of the wall assembly. Specified Technologies n 10nWay Somerville, NJ 08876 Reproduced courtesy ounderwiterLaboratories, nc Created or Revised: May 12, 2017 s T L 800 992-1180 • 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com GE 3 OF 4 8A. Through Penetrant - A max of two pipes or tubes to be installed in each AC line set. Of the two pipes or tubes, only one may have a nom diam greater than 1/2 in. (13 mm). The following types and sizes of through penetrants may be used: A. Steel Pipe - Nom 1 in. (25 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 1 in. (25 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Pipe - Nom 1 in. (25 mm) diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tube - Nom 1 in. (25 mm) diam (or smaller) Type L (or heavier) copper tube. 8B. Tube Insulation - Plastics# - Nom 3/4 in. (19 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The tube insulation may be installed on one max 3/4 in. (19 mm) diam pipe or tube in each AC line set. The space between the insulated and non -insulated pipes or tubes within each AC line set shall be 0 in. (point contact). See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation meeting the above specifications and having a UL 94 Flammability Classification of 945VA may be used. 8C. Cable - One 4 pair No. 18 AWG (or smaller) thermostat cable with polyvinyl chloride (PVC) insulation and jacket materials may be installed with each AC line set. When Item 8 is used, the T Rating of the firestop system is 1/4 hr. 9. Steel Duct - (Not Shown) - Nom 12 in. (305 mm) diameter (or smaller) No. 30 GA (or heavier) steel duct installed within opening when opening contains no cables or cable tray. A max of two steel ducts may be installed within the through -opening. Ducts to be spaced min 4 in. (102 mm) apart and min 8 in. (203 mm) from insulated penetrants and nonmetallic penetrants. Annulus between the steel duct and the periphery of the opening shall be min 0 in. (point contact) to max 24 in. (0 to 609 mm). Steel ducts to be rigidly supported on both sides of wall assembly. When steel duct is used, the T Rating is 0 hr. 10. Firestop System - The firestop system shall consist of the following items: A. Packing Material - Min 4 pcf (64 kg/m3) mineral wool batt insulation tightly packed into opening to full depth of the wall. Packing material recessed from both surfaces of wall to accommodate the required thickness of fill material. B. Fill, Void or Cavity Materials* -Sealant - Min 1/2 in. (13 mm) depth of fill material applied within the annulus, flush with both surfaces of the wall assembly. Additional fill material forced into interstices of grouped cables and grouped cables within cable trays. At point contact location between through penetrant and gypsum wallboard, a min 3/8 in. (10 mm) diam bead of fill material shall be applied at through penetrant/gypsum board interface on both surfaces of the wall. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. #Bearing the UL Recognized Components Mark +Bearing the UL Listing Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. ST I c Created or Revised: May 12, 2017 us I GE 4 OF4 (800)992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) --A System No. W-L-8027 F Ratings - 1 and 2 Hr (See Item 1) T Rating - 1/4 Hr Section A -A Wall Assembly - The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board" - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max area of opening is 30 sq in. (0.019 m2) with a max dimension of 10 in. (254 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Air Conditioning (AC) Line Set - One or more AC line sets installed eccentrically or concentrically within opening. Each AC line set consists of two pipes or tubes (Item 2A), tubing insulation (Item 213) and a thermostat cable (Item 2C). The space between the AC line sets shall be min 1/2 in. (13 mm) to max 3/4 in. (19 mm). The space between the AC line sets and the periphery of the opening shall be min 0 in. (point contact) to max 1 in. (25 mm). 2A. Through Penetrant - A max of two pipes or tubes to be installed in each AC line set. Of the two pipes or tubes, only one may have a nom diam greater than 1/2 in. (13 mm) Annular space between pipes or tubing and periphery of opening shall be min 0 in. (point contact) to max 1-1/2 in. (38 mm). Pipes or tubing to be rigidly supported on both sides of the wall assembly. The following types and sizes of through penetrants may be used: A. Steel Pipe - Nom 1 in. (25 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom. 1 in. (25 mm) diam (or smaller) cast or ductile iron pipe. C. Copper Pipe - Nom 1 in. (25 mm) diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tube - Nom. 1 in. (25 mm) diam (or smaller) Type L (or heavier) copper tube. 2B. Tube Insulation - Plastics# - Nom 3/4 in. (19 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The tube insulation may be installed on one max 1/2 in. (13 mm) diam pipe or tube in each AC line set. The annular space between the penetrating item and the periphery of the opening shall be min 0 in. (point contact) to max 1/2 in. (13 mm). The space between the pipes or tubing within each AC line set shall be 0 in. (point contact). See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S 1 I ® Created or Revised: January 23, 2014 W-L-8027 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Websitemww.stifirestop.com PAGE 1 OF 2 2C. Cable - One 4 pair No. 18 AWG (or smaller) thermostat cable with polyvinyl chloride (PVC) insulation and jacket materials may be installed with each AC line set. Cable to be spaced min 0 in (point contact) to max 1/2 in. (13 mm) from the other penetrants in each line set. The space between the cable and the periphery of the opening shall be min 0 in. (point contact) to max 1/2 in. (13 mm). Cable to be rigidly supported on both sides of wall assembly. 3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. At point contact location, min 1 /4 in. (6 mm) diam bead of fill material applied at through penetrant/gypsum board interface on both surfaces of wall. Additional fill material forced into grouped penetrant interstices to max extent possible. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant or Type WF300 Firestop Caulk (wood stud walls only). * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. # Bearing the UL Recognized Component Marking Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 ST I o (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com W-L-80 PAGE 2 OFF 2 Classified by Underwiters Laboratories, Inc. to ASTM/UL1479 (ASTM E814) A C 2B 3B 3 2A D ---- am -a 0 0 f System No. W-L-8028 0 F Ratings - 1 and 2 Hr T Rating - 3/4 Hr 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 4-1/2 in. (114 mm). The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Air Conditioning (AC) Line Set - AC line set consisting of multiple metallic pipes (Item 2A), nonmetallic pipes (Item 213), cables (Item 2C) and pipe insulation (Item 2D) bundled within the opening such that the aggregate cross -sectional area of the penetrants does not exceed 54 percent of the cross -sectional area of the wall opening. The annular space between the penetrants and the periphery of opening shall be min 1/4 in. (6 mm) to max 1 in. (25 mm). Penetrants to be rigidly supported on both sides of wall assembly. 2A. Metallic Pipes - The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 3/4 in. (19 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 3/4 in. (19 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 3/4 in (19 mm) diam (or smaller) steel conduit or EMT. D. Copper Pipe or Tube - Nom 3/4 (19 mm) diam (or smaller) Type L (or heavier) copper tube or Regular (or heavier) copper pipe. Allp Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 2, 2009 W-L-8028 T I ® (800)992-1180 • (908)526-8000 9 FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 1 OF 2 2B. Nonmetallic Pipes -A max of one nonmetallic pipe or conduit maybe used. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 1-1/4 in. (32 mm) diam (or smaller) Schedule 40 solid core PVC pipe for use in vented (drain, waste or vent) or closed (process or supply) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 1-1/4 in. (32 mm) diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit+ - Nom 1-1/4 in. (32 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA 70). 2C. Cables - Max 7/C No. 12 AWG (or smaller) multiconductor power and control cables; XLPE or PVC insulation with XLPE or PVC jacket or four pair No. 18 AWG (or smaller) thermostat cable with PVC insulation and jacket. 2D. Pipe Covering - The following types and sizes of pipe coverings may be used with the metallic pipes: A. Tube Insulation - Plastics# - Nom 5/8 in. (16 mm) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The tube insulation may be installed on a max of one pipe or tube. See Plastics (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. B. Pipe and Equipment Covering Materials* - Nom 1/2 in. (13 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap tape. Transverse joints secured with metal fasteners or butt tape supplied with the product. See Pipe and Equipment Covering Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. Firestop System - The details of the firestop system shall be as follows: A. Fill, Void or Cavity Material* - Wrap Strip - Nom 1/8 or 3/16 in. (3.2 or 4.8 mm) thick intumescent material faced on both sides with a plastic film, supplied in 2 in. (51 mm) wide strips, or nom 1/4 in. (6 mm) thick intumescent material faced on both sides with a plastic film, supplied in 1-1/2 in. (38 mm) wide strips. Single layer wrapped around penetrant bundle and secured with a single layer of foil tape. Wrap strip recessed within opening such that ends project a max 1/4 in. (6 mm) on each surface of the wall. SPECIFIED TECHNOLOGIES INC - SpecSeal RED Wrap Strip, SpecSeal BLU Wrap Strip or SpecSeal BLU2 Wrap Strip B. Fill, Void or Cavity Material* -Sealant -Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. Fill material forced into grouped penetrant interstices to max extent possible. A min 1/4 in. (6 mm) bead of fill material shall be applied at the wrap strip/gypsum board interface on both sides of the wall assembly. SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. + Bearing the UL Listing Mark # Bearing the UL Recognized Component Marking Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 2, 2009 W-L-8028 T I ® (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ANSI/UL 2079 System No. BW-S-0020 Assembly Ratings - 1 and 2 Hr (See Item 2) Joint Width - 1/2 In. Max L Rating At Ambient - Less Than 1 CFM/Lin Ft L Rating At 400 F - Less Than 1 CFM/Lin Ft 1. Floor Assembly -Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow -core Precast Concrete Units*. See Precast Concrete Units (CFTV) category in the Fire Resistance Directory for names of manufactures. 2. Wall Assembly - The 1 or 2 hr fire rated gypsum board/steel stud shaft wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory. In addition, the wall may incorporate a head -of -wall joint system constructed as specified in the HW Series Joint Systems in the UL Fire Resistance Directory. The wall shall include the following construction features: A. Steel Floor Runner - "J"-shaped runners, min 2-1/2 in. (64 mm) deep, with unequal legs of 1 in. (25 mm) and 2 in. (51 mm), fabricated from min 24 MSG galv steel. Runners positioned with short leg toward finished side of wall. Runners attached to structural supports with steel fasteners located not greater than 2 in. (51 mm) from ends and not greater than 24 in. (610 mm) OC. B. Studs - "C-H", "E" (back-to-back) or "C-7-shaped studs, min 2-1/2 in. (64 mm) deep, fabricated from min 25 MSG galv steel. Cut to lengths 3/8 to 1/2 in. (10 to 13 mm) less than floor -to -ceiling height and spaced 24 in. (610 mm) OC. C. Gypsum Board* - 1 in. (25 mm) thick gypsum liner panels and 1/2 in., 5/8 in. or 3/4 in. (13, 16 or 19 mm) thick gypsum panels installed as specified in the individual U400 or V400 Series shaft wall designs in the UL Fire Resistance Directory. The hourly fire rating of the joint system is equal to the hourly fire rating of the wall. 3. Fill, Void or Cavity Material* - Sealant - Max separation between top of floor and bottom of gypsum board on the finish side of wall is 1/2 in. (13 mm). Min 1/2 in. (13 mm) thickness of fill material installed on finish side of the wall between the bottom of the gypsum board and the top of the concrete floor, flush with surface of the finish side of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant, SpecSeal LCI Sealant, SpecSeal LC150 Sealant, Pensil 300 Sealant or SpecSeal Series SIL300 Silicone Firestop Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 Po0STIo (800)992-1180. (908)526-8000 9FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com 9 Webs ite:www.stifirestop.com E 1OF 1 Classified by Underwiters Laboratories, Inc. to ANSI/UL 2079 System No. BW-S-0003 Assembly Ratings - 1 and 2 Hr (See Item 2) L Rating At Ambient - Less Than 1 CFM/Lin Ft (See Item 313) L Rating At 400°F - Less Than 1 CFM/Lin Ft (See Item 313) Joint Width - 3/4 In. Max Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. Floor may also be constructed of any 6 in. (152 mm) thick UL Classified hollow -core Precast Concrete Units*. See Precast Concrete Units category in the Fire Resistance Directory for names of manufactures. Wall Assembly - The 1 or 2 h fire -rated gypsum board/steel stud wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall or Partition Design in the UL Fire Resistance Directory. In addition, the wall may incorporate a head -of -wall joint system constructed as specified in the HW Series Joint Systems in the UL Fire Resistance Directory. The wall shall include the following construction features: A. Steel Floor Runner - Floor runners of wall assembly shall consist of min No. 25 gauge galv steel channels sized to accommodate steel studs (Item 213). Floor runners to be provided with min 1-1/4 in. (32 mm) flanges. Runners secured with steel fasteners spaced 12 in. (305 mm) OC. B. Studs - Steel studs to be min 3-1/2 in. (89 mm) wide. Studs cut 1/2 to 3/4 in. (13 to 19 mm) less in length than assembly height with bottom nesting in, resting on and fastened to floor runner with sheet metal screws. Stud spacing not to exceed 24 in. (610 mm) OC. C. Gypsum Board* - Gypsum board installed to a min total thickness of 5/8 in. (16 mm) or 1-1A in. (32 mm) on each side of wall for a 1 or 2 hr fire rated wall, respectively. Wall to be constructed as specified in the individual U400 or V400 Series Design in the UL Fire Resistance Directory except that a max 3/4 in. (19 mm) gap shall be maintained between the bottom of the gypsum board and the top of the concrete floor. The hourly fire rating of the joint system is equal to the hourly fire rating of the wall. Joint System - Max separation between top of floor and bottom of gypsum board is 3/4 in. (19 mm). The joint system consists of a packing material and a fill material, as follows: A. Packing Material - (Optional, Not Shown) - Mineral wool batt insulation, polyethylene backer rod or glass fiber insulation firmly packed into the gap between the bottom of the gypsum board and the top of the concrete floor and recessed from each surface of the wall to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* -Sealant - Min 1/2 in. (13 mm) thickness of fill material installed on each side of the wall between the bottom of the gypsum board and the top of the concrete floor, flush with each surface of the wall. When mineral wool batt insulation is used as a packing material, min thickness of fill material on each side of the wall is 1/4 in. (6 mm). SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant, SpecSeal LCI Sealant, SpecSeal LC150 Sealant, Pensil 300 Sealant or SpecSeal Series SIL300. Note: L Ratings apply when SpecSeal ES Sealant is used. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S T I o Created or Revised: January 23, 2014 I ( ) ( ) E-Mail:techserv@stifirestop.com P @BW-S-0003 GE 1OF1 (800)992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifiresto .com • Website:www.stifiresto .com Classified by Underwiters Laboratories, Inc. to ANSI/UL 2079 System No. HW-D-0041 Assembly Rating - 3 Hr Nominal Joint Width - 1 In. L Rating At Ambient - Less Than 1 CFM/Lin Ft L Rating At 400°F - Less Than 1 CFM/Lin Ft Class II Movement Capabilities - 12.5% Compression Or Extension Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. Joint System - Max separation between bottom of floor and top of wall (at time of installation of joint system) is 1 in. (25 mm). The joint system is designed to accommodate a max 12.5 percent compression or extension, or max 25 percent in compression only, from its installed width. The joint system shall consist of the following: A. Packing Material - Open or closed cell polyethylene or polyurethane foam backer rod used as a form to prevent the leakage of fill material. Packing material to be recessed from both surfaces of the wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant * Indicates such products shall bear the UL or cUIL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 �° PAGE D1o041 OF 1 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com Classified by Underwiters Laboratories, Inc. &V:. to ANSI/UL 2079 and CAN/ULC S115 System No. HW-S-0043 ANSI/UL2079 CAN/ULC S115 Assembly Rating - 1 and 2 Hr (See Item 2) F Rating - 1 and 2 Hr (See Item 2) Joint Width - 3/4 In. Max FT Rating - (See Item 2) L Rating At Ambient - Less Than 1 CFM/lin ft FH Rating - 1 and 2 Hr (See Item 2) L Rating At 400 F - Less Than 1 CFM/lin ft FTH Rating - (See Item 2) Joint Width - 19 mm Max L Rating At Ambient - Less Than 1 L/s/m L Rating At 400 F - Less Than 1 L/s/m 1 F"__A � a a a a 1 3B 313 4; c c B L � - I - 1 SECTION A -A L►A a 313 1. Floor Assembly - Min 4-1/2 in. (114 mm) thick steel -reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. 2. Wall Assembly - The 1 hr or 2 hr fire rated gypsum board/steel stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Steel Floor and Ceiling Runners - Floor and ceiling runners of wall assembly shall consist of galv steel channels with min 1-1/4 in. (32 mm) long flanges sized to accommodate steel studs (Item 213). Ceiling runner secured to concrete floor with steel fasteners spaced max 24 in. (610 mm) OC. B. Studs - Steel studs to be min 3-1/2 in. (89 mm) wide. Studs cut 1/2 in. (13 mm) to 3/4 in. (19 mm) less in length than assembly height with bottom nesting in and resting on floor runner and with top nesting in ceiling runner. Stud spacing not to exceed 24 in. (610 mm) OC. C. Gypsum Board" - Gypsum board sheets installed to a min total thickness of 5/8 in. (16 mm) and 1-1A in. (32 mm) on each side of wall for 1 hr and 2 hr fire rated assemblies, respectively. Wall to be constructed as specified in the individual Wall and Partition Design in the UL Fire Resistance Directory. A max 3/4 in. (19 mm) gap shall be maintained between the top of the gypsum board and the bottom surface of the floor. The hourly rating of the joint system is dependent on the hourly fire rating of the wall assembly in which it is installed. AP Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: November 14, 2017 T I �° PAGE 1o043 . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com OF 2 Joint System - Max separation between bottom of floor and top gypsum board is 3/4 in. (19 mm). The joint system consists of the following: A. Forming Material - (Optional, Not Shown) - In 2 hr fire rated wall assemblies, polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fit into joint opening. B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within joint opening on both sides of wall, flush with both surfaces of wall. When no separation is present between the bottom of floor and top of gypsum board, a min 1/4 in. (6 mm) bead of sealant shall be applied at the floor/gypsum board interface on both sides of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. �r T Created or Revised: November 14, 2017 YL 043 ST�a P P PAGE 2oOF2 0 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com .com • Website:www.stifiresto .com Classified by Underwiters Laboratories, Inc. to ANSI/UL 2079 ❑� �■ System No. HW-D-0079 Assembly Ratings - 1 and 2 Hr (See Item 2) �■ :, Joint Width - 3/4 in. Maximum L Rating At Ambient - Less Than 1 CFM/Lin Ft L Rating At 400°F - Less Than 1 CFM/Lin Ft Class II Movement Capabilities - 25% Compression 1. Floor Assembly - Min 4-1/2 in. (114 mm) thick steel -reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. Floor may also be constructed of any min 6 in. thick (152 mm) UL Classified hollow -core Precast Concrete Units*. See Precast Concrete Units (CFTV) category in Fire Resistance Directory for names of manufacturers. 2. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Steel Floor and Ceiling Runners - Floor and ceiling runners of wall assembly shall consist of galv steel channels sized to accommodate steel studs (Item 213) with min 1-1/4 in. (32 mm) long flanges. Ceiling runner secured to concrete floor slab with steel masonry anchors spaced max 24 in. (610 mm) OC. Al. Light Gauge Framing* - Slotted Ceiling Runner - As an alternate to the ceiling runner in Item 2A, ceiling runner to consist of galv steel channel with slotted flanges sized to accommodate steel studs (Items 213). Ceiling runner secured to concrete floor slab with steel masonry anchors spaced max 24 in. (610 mm) OC. CALIFORNIA EXPANDED METAL PRODUCTS CO - CST BRADY CONSTRUCTION INNOVATIONS INC, DBA SLIPTRACK SYSTEMS - SLP-TRK MARINO/WARE, DIV OF WARE INDUSTRIES INC - Type SILT A2. Light Gauge Framing* - Vertical Deflection Ceiling Runner - As an alternate to the ceiling runner in Item 2A, vertical deflection ceiling runner to consist of galv steel channel with slotted vertical deflection clips mechanically fastened within runner. Slotted clip provided with step bushings for permanent fastening of steel studs. Flanges sized to accommodate steel studs (Item 213). Vertical deflection ceiling runner secured to concrete floor slab with steel masonry anchors spaced max 24 in. (610 mm) OC. THE STEEL NETWORK INC - VertiTrack VTD358, VTD400, VTD600 and VTD800 Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. S 1 I ® Created or Revised: November 17, 2017 @HW-D-0079 (800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 2 A3. Light Gauge Framing* - Notched Ceiling Runner - As an alternate to the ceiling runners in Items 2A through 2A3, notched ceiling runners to consist of C-shaped galv steel channel with notched return flanges sized to accommodate steel studs (Item 213). Notched ceiling runner secured to concrete floor slab with steel masonry anchors spaced max 24 in. (610 mm) OC. OLMAR SUPPLY INC - Type SCR A4. Steel Framing Members* - Sound Isolation Clips - (Not Shown) - As an alternate attachment means for the ceiling runner to the underside of the floor assembly, sound isolation clips installed in accordance with the accompanying installation instructions. Sound isolation clip installed through nom 1 in. (25 mm) diam hole in ceiling runner and attached to top of ceiling runner using four min No. 8 by 1/2 in. (13 mm) long self -tapping galv steel screws. Sound isolation clips to be installed adjacent to every stud location but not more than 24 in. (610 mm) OC and attached to the underside of floor assembly using min 3/16 in. (5 mm) diam by 2-1/2 in. (64 mm) long steel masonry anchors. PAC INTERNATIONAL INC - Type RSIC-U-HD B. Studs - Steel studs to be min 3-1/2 in. (89 mm) wide. Studs cut 1/2 in. (13 mm) to 3/4 in. (19 mm) less in length than assembly height with bottom nesting in and resting on floor runner and with top nesting in ceiling runner without attachment. When deflection channel (Item 3A) is used, steel studs attached to ceiling runner with sheet metal screws located 1/2 in. (13 mm) below the bottom of the deflection channel. When slotted ceiling runner (Item 2A2) is used, steel studs secured to slotted ceiling runner with No. 8 by 1/2 in. (13 mm) long wafer head steel screws at midheight of slot on each side of wall. When vertical deflection ceiling runner (Item 2A3) is used, steel studs secured to slotted vertical deflection clips, through bushings, with steel screws at midheight of each slot. Stud spacing not to exceed 24 in. (610 mm) OC. C. Gypsum Board* - Gypsum board sheets installed to a min total thickness of 5/8 in. (16 mm) and 1-1/4 in. (32 mm) on each side of wall for 1 and 2 hr fire rated assemblies, respectively. Wall to be constructed as specified in the individual Wall and Partition Design in the UL Fire Resistance Directory, except that a nom 3/4 in. (19 mm) gap shall be maintained between the top of the gypsum board and the bottom surface of the floor. In addition, the top row of screws shall be installed into the steel studs 1/2 to 1 in. (13 to 25 mm) below the bottom edge of the ceiling runner flange. The hourly fire rating of the joint system is dependent on the hourly fire rating of the wall assembly in which it is installed. 3. Joint System -Max separation between bottom of floor and top of wall is 3/4 in. (19 mm). The joint system is designed to accommodate a max 25 percent compression from its installed width.. The joint system consists of the following: A. Forming Material* - (Not Shown) - In 2 hr fire rated wall assemblies, polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fit into joint opening. When sound isolation clips (Item 2A5) are used to secure ceiling runner to underside of floor in 1 or 2 hr fire rated wall assemblies, the space between the top of the ceiling runner and the underside of the floor shall be tightly packed with mineral wool batt insulation. The forming material shall be recessed from each surface of wall to accommodate the required thickness of fill material. ROCK WOOL MANUFACTURING CO - Delta Safing ROCKWOOL MALAYSIA SDN BHD - Safe ROCKWOOL - Safe THERMAFIBER INC - Type SAF B. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) thickness of fill material applied within joint opening on both sides of wall, flush with both surfaces of wall. As an option in 1 hr fire rated walls, bond breaker tape applied to ceiling channel (Item 2A) prior to installation of fill material. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: November 17, 2017 @HW-D-0079 T I ® (800)992-1180 9 (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@stifirestop.com . Webs ite:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ANSI/UL 2079 System No. HW-D-0156 Assembly Rating - 4 Hr Nominal Joint Width - 2 in. L Rating At Ambient - Less Than 1 CFM/Lin Ft L Rating At 400°F - Less Than 1 CFM/Lin Ft Class II Movement Capabilities - 12.5% Compression or Extension 1. Floor Assembly - Min 5-1/2 in. (140 mm) thick steel reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3 ) structural concrete. 2. Wall Assembly -Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3 ) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. Joint System - Max width of joint (at time of installation of joint system) is 2 in. (51 mm). The joint system is designed to accommodate a max 12.5 percent compression or extension from its installed width. The joint system shall consist of forming and fill materials, as follows: A. Forming Material* - Min 4 pcf (64 kg/m3) mineral wool batt insulation installed in joint opening as a permanent form. Pieces of batt cut to min width of 5 in. (127 mm) and installed vertically, edge -first into joint opening, such that batt sections are compressed min 50 percent in thickness and that the compressed batt sections are recessed from each surface of the wall as required to accommodate the required thickness of fill material. Adjoining lengths of batt to be tightly butted with butted seams spaced min 16 in. (406 mm) apart along the length of the joint. IIG MINWOOL L L C - MinWool-1200 Safing JOHNS MANVILLE INTERNATIONAL INC - Safing ROCK WOOL MANUFACTURING CO - Delta Board ROCKWOOL MALAYSIA SDN BHD - SAFE ROCKWOOL - SAFE THERMAFIBER INC - Type SAF B. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) thickness of fill material applied within the joint on each side of wall, flush with wall surfaces. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: November 17, 2017 �° PAGE D1oOF 16 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com Classified by Underwiters Laboratories, Inc. to ANSI/UL 2079 System No. HW-D-0194 Assembly Ratings - 1 and 2 Hr (See Items 2 and 3B) Joint Width- 1 in. Max L Rating At Ambient - Less Than 1 CFM/Lin Ft (See Item 3B) L Rating At 400°F - Less Than 1 CFM/Lin Ft (See Item 3B) Class II Movement Capabilities-25 Percent Compression or Extension C 1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3 ) structural concrete. 2. Shaft Wall Assembly - With the exception of the ceiling runner, the 1 or 2 hr fire rated shaft wall assembly shall be constructed of the materials and in the manner described in the individual U400 or V400-Series Wall and Partition Design in the UL Fire Resistance Directory. The wall shall include the following construction features: A. Floor and Wall Runners - (Not Shown) - "J"-shaped runner, min 2-1/2 in. (64 mm) wide with unequal legs of 1 in. (25 mm) and 2 in. (51 mm), fabricated from min 24 MSG galv steel. Runners positioned with short leg toward finished side of wall. Runners attached to walls and floor with steel fasteners spaced max 24 in. (610 mm) OC. As an alternate to the "J"-shaped runner, a min 2-1/2 in. (64 mm) wide by 1 or 1-1/4 in. (25 or 32 mm) deep channel formed from min 24 MSG galv steel may be used for the floor runner. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. @HW-D-0194 Created or Revised: September 27, 2019�° PAGE 1 OF 2 T I ® 800 992-1180.908 526-8000 •FAX 908 231-8415 • E-Mail: tech sery stifirestop.com • Website:www.stifirestop.com B. Light Gauge Framing* - Slotted Ceiling Track - Slotted ceiling track shall consist of galv steel channels with slotted flanges. Slotted ceiling track sized to accommodate steel "C-H" studs (Items 2C). Attached to concrete at ceiling with steel fasteners spaced max 12 in. OC (305 mm). BRADY CONSTRUCTION INNOVATIONS INC, DBA SLIPTRACK SYSTEMS - SLP-TRK CALIFORNIA EXPANDED METAL PRODUCTS CO - CST CLARKDIETRICH BUILDING SYSTEMS - Type SILT, SLT-H MARINO/WARE, DIV OF WARE INDUSTRIES INC - Type SILT RAM SALES L L C - RAM Slotted Track SCAFCO STEEL STUD MANUFACTURING CO STEELER INC - Steeler Slotted Ceiling Runner TELLING INDUSTRIES L L C - True -Action Deflection Track C. Steel Studs - "C-H"-shaped steel studs to be min 2-1/2 in. (64 mm) wide and formed of min 24 MSG galv steel. Studs cut 1/2 to 3/4 in. (13 to 19 mm) less in length than assembly height with bottom nesting in and resting on floor runner and with top nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gypsum board liner panels (Item 2D), studs secured to flange of floor runner on finished side of wall only with No. 6 by 1/2 in. (13 mm) long self -drilling, self -tapping steel screws. Studs secured to flange of slotted ceiling track on finished side of wall only with No. 8 by 1/2 in. (13 mm) long self -drilling, self -tapping wafer head steel screws at slot midheight. D. Gypsum Board* - 1 in. (25 mm) thick by 24 in. (610 mm) wide gypsum board liner panels as specified in the individual U400 or V400-Series Wall and Partition Design. Panels cut 1 in. (25 mm) less in length than floor to ceiling height. Vertical edges inserted in "H"-shaped section of "C-H" studs. Free edge of end panels attached to long leg of "J" runner (Item 2A) with 1-5/8 in. (41 mm) long Type S steel screws spaced max 12 in. (305 mm) OC. E. Gypsum Board* - Gypsum board sheets, 1/2 or 5/8 in. (13 or 16 mm) thick, applied vertically or horizontally in one or two layers on finished side of wall as specified in the individual U400 or V400-Series Wall and Partition Design. A max 1 in. (25 mm) gap shall be maintained between the top of the gypsum board and the bottom surface of the concrete floor. The screws attaching the gypsum board layers to the C-H studs shall be located 1 in. (25 mm) below the bottom of the slotted ceiling track (Item 2C). No gypsum board attachment screws are to penetrate the slotted ceiling track. The hourly fire rating of the joint system is equal to the hourly fire rating of the wall. 3. Joint System - Max separation between bottom of floor and top of liner panel (Item 2D) and between bottom of floor and top of gypsum board sheets (Item 2E) at time of installation of joint system is 1 in. (25 mm). The joint system is designed to accommodate a maximum 25 percent compression or extension from its installed width. The joint system consists of bond breaker tape and sealant, as follows: A. Bond Breaker Tape - Polyethylene tape supplied in rolls. Tape applied to flanges of slotted ceiling track (Item 2D) to prevent bonding of the sealant at points other than the top and bottom of the linear gap. Bond breaker tape is optional when movement capability of the joint is limited to compression only. B. Fill, Void or Cavity Material* - Sealant - Min 1 in. (25 mm) depth of sealant to be installed to fill linear gap between top of gypsum board liner panel (Item 2D) and top inside surface of slotted ceiling track (Item 2B) prior to installation of gypsum board sheets on finished side of wall. For 1 hr fire rated walls, min 5/8 in. (16 mm) depth of sealant to be installed to fill linear gap between top of gypsum board sheet (Item 2E) and bottom of concrete floor. For 2 hr walls, min 1 in. (25 mm) depth of sealant to be installed to fill linear gap between top of gypsum board sheets (Item 2E) and bottom of concrete floor. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Elastomeric Sealant or SpecSeal LCI Sealant. L Ratings apply when SpecSeal ES Elastomeric Sealant is used. When SpecSeal LCI Sealant is used, the movement capability of the joint is limited to 25 percent in compression only. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. ST I Created or Revised: September 27, 2019 @HW-D-0194 I (800)992-1180 • (908)526-8000 • FAX (908)231-8415 9 E-Mail:techserv@stifirestop.com 9 Website:www.stifirestop.com PAGE 2 OF 2 Classified by Underwiters Laboratories, Inc. to ANSI/UL 2079 and CAN/ULC S115 System No. HW-D-0780 ❑■ ANSI/UL2079 CAN/ULC S115 Assembly Rating - 2 Hr F Rating - 2 Hr Max Joint Width - 1 In. FT Rating - 2 Hr Class II Movement Capabilities - 12.5% Compression or FH Rating - 2 Hr Extension L Rating At Ambient - Less Than 1 CFM/lin ft FTH Rating - 2 Hr L Rating At 400 F - Less Than 1 CFM/lin ft Max Joint Width - 25 mm Class II Movement Capabilities - 12.5% Compression or Extension L Rating At Ambient - Less Than 1.55 L/s/m L Rating At 204 C - Less Than 1.55 L/s/m 1 a a. 3B a a 2 1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. 2. Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 3. Joint System - Max separation between bottom of floor and top of wall (at time of installation of joint system) is 1 in. (25 mm). The joint system is designed to accommodate a max 12.5 percent compression or extension from its installed width. The joint system shall consist of the following: A. Forming Material - (Optional, Not Shown) - Open or closed cell polyethylene or polyurethane foam backer rod, mineral wool batt insulation or glass fiber insulation used as a form to prevent the leakage of fill material. Packing material to be recessed from both surfaces of the wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Sealant - Min 1/4 in. (6 mm) thickness of fill material applied within the joint, flush with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 18, 2017 D1OOF T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techserv@stifirestop.com 0 Website:www.stifirestop.com G PAGE 1 Classified by Underwiters Laboratories, Inc. to ANSI/UL 2079 System No. WW-D-0004 Assembly Rating - 3 Hr Nominal Joint Width - 1 In. L Rating At Ambient - Less Than 1 CFM/Lin Ft L Rating At 400°F - Less Than 1 CFM/Lin Ft Class II Movement Capabilities - 12.5% Compression Or Extension Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. Joint System - Max width of joint (at time of installation of joint system) is 1 in. (25 mm). The joint system is designed to accommodate a max 12.5 percent compression or extension from its installed width. The joint system shall consist of the following: A. Packing Material - Open or closed cell polyethylene or polyurethane foam backer rod used as a form to prevent the leakage of fill material. Packing material to be recessed from both surfaces of the wall as required to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) thickness of fill material applied within the joint, flush with both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: May 21, 2008 @0004 T I � 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com P GD-OF1 Classified by Underwiters Laboratories, Inc. to ANSI/UL 2079 System No. WW-S-0052 Assembly Rating - 1, 2, 3 and 4 Hr (See Items 2 and 313) Joint Width - 1 In. Max L Rating At Ambient - Less Than 1 CFM/lin ft L Rating At 400 °F - Less Than 1 CFM/lin ft Wall Assembly - The 1, 2, 3 or 4 hr fire -rated gypsum board/steel stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Steel studs to be min 3-1/2 in. (89 mm) wide by 1-1/4 in. (32 mm) deep corrosion protected min 25 MSG steel channels. Stud spacing not to exceed 24 in. (610 mm) OC. Stud installed nominally centered at joint location. B. Gypsum Board* - Gypsum board sheets installed to a min total thickness of 5/8 in. (16 mm), 1-1/4 in. (32 mm), 1-1/2 in. (38 mm) or 2 in. (51 mm) on each side of wall for 1, 2, 3 and 4 hr fire rated assemblies, respectively. Wall to be constructed in the individual U400 or V400 Series Design in the UL Fire Resistance Directory. The hourly rating of the joint system is dependent on the hourly fire rating of the wall assembly in which it is installed. Wall Assembly - Min 6 in. (152 mm) thick steel -reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. When the hourly rating is greater than 3 hr, the min thickness of the wall shall be 7-5/8 in. (194 mm) Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. Joint System - Max width of joint is 1 in. (25 mm). The joint system consists of the following: A. Forming Material - (Optional, Not Shown) - In 2, 3 or 4 hr fire rated wall assemblies, polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fit into joint opening, flush with both surfaces of wall. B. Fill, Void or Cavity Material* - Sealant - In 1 hr fire rated wall assemblies, min 5/8 in. (16 mm) thickness of fill material applied within joint opening. In 2, 3 or 4 hr fire rated wall assemblies, min 1 in. (25 mm) thickness of fill material applied within joint opening. Sealant applied on both sides of wall, flush with both surfaces of the wall. SPECIFIED TECHNOLOGIES INC - SpecSeal ES Sealant, Pensil 300 Sealant, SpecSeal Series SIL300 Sealant, SpecSeal LC150 or SpecSeal LE600 Sealant. Note: When SpecSeal LC150 or LE600 Sealant is used, the max assembly rating is 2 hr. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: January 23, 2014 �° PACE 1 OF@WW-S-001 T I . 800 992-1180. 908 526-8000 •FAX 908 231-8415 • E-Mail:techsery stifirestop.com • Website:www.stifirestop.com P R O D U C T D A T A S H E E T SpecSeal° ES Elastomeric Sealant SpecSeal° ES Elastomeric Sealant is a non -halogenated latex -based, highly elastomeric caulk designed to provide passive smoke and fire protection in construction joints. This material is also designed to restore sound attenuation properties to sound -rated ceilings and partitions. SpecSeal° ES Elastomeric Sealant is engineered to adhere to virtually all construction surfaces and may be applied using standard caulking equipment or by troweling. SpecSeal° ES Elastomeric Sealant dries to form a flexible shield against the propagation of fire. Its premium latex binder system is totally resistant to water and will not re -emulsify after drying. SpecSeal° ES Elastomeric Sealant contains no inorganic fibers, asbestos, or solvents. Applications SpecSeal° ES Elastomeric Sealant is designed primarily for the protection of construction joints. Specifications The fire protective sealant shall be a water -based, non -halogenated, elastomeric and shall contain no solvents, inorganic fibers, nor asbestos. The sealant shall dry to form a flexible, moisture resistant seal and shall adhere to all common construction surfaces. The sealant shall have demonstrated sound attentuation properties. The approved sealant shall be SpecSeal° ES Elastomeric Sealant. Specified Divisions Division 7 07 84 00 Firestopping Division 7 07 84 43 Joint Firestopping qW V Performance G�Pss�F,Fa When applied to a wet film FM thickness of 1 /4 in (6.3 mm) C to 1/2 in (12.5 mm) over aUS APPROVED appropriate backing materials, SpecSeal° ES Elastomeric Sealant has been successfully tested in one, two, three and four hourjoints when tested in accordance with UL2079 (ASTM E1966) and CAN/ULC S115. All tested systems have been cycled 500 times at total movement up to +/- 25%. Consult factory for individual system designs and application requirements. Limitations Features & Benefits • Water -based for easy installation & cleanup Non -halogenated • Thixotropic for high -build application • Auto bonding • Safe, no solvents, no asbestos, No PCBs, no inorganic fibers • Elastomeric • Water-resistant UL Certified • Acoustical sealant • Paintable when dry • Meets LEEDT"^ v3, v4, & v4.1 requirements. Low emitting materials credit. See general LEED letter for additional applicable credits. Use product as per manufacturer's instructions. Use only in applications per the manufacturer's published designs or specific recommendations. End user must ultimately determine the suitability of the product and/or design to his or her specific requirements and assumes responsibility for its use. PRODUCT CONTAINS WATER AND IS CONDUCTIVE UNTIL DRY. DO NOT APPLY IN THE PRESENCE OF EXPOSED OR ENERGIZED ELECTRICAL CONDUCTORS. This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product i0Tm for complete listings. (Firestop Systems). A& Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 2 h' STD® Technologies Inc. SpecSeal® ES Elastomeric Sealant • ZSFOD5032 24721 P R O D U C T D A T A S H E E T SpecSeal° ES Elastomeric Sealant Color Pale Blue or Red Solvent Content None Density/Weight per Gallon 12.1 lb/gal (1.45 kg/L) In Service Temperature Less than or equal to 185°F (85°C) Solids Content by Weight 80.7% Storage Temperature 40°F (4°C) to 95°F (35°C) Solids Content by Volume 73.0% Application Temperature 40°F (4°C) to 95°F (35°C) Flame Spread* 5 Drying Time Tack Free 2 Hours Dry through 5 to 7 days STC Rating Smoke Development* 5 62 (ASTM E90-04/ASTM C919) (Relates to Specific Construction) Mold & Fungus Growth Rating 0 VOC Content** 39 g/L (ASTM G21) Average Volume Shrinkage pH 7.5 o 31/o (ASTM C1241) Movement Capabilities*** +/- 25% For more information on Shelf Life Coverage product coverage see the From Date of Manufacture 24 months following documents for Linear Joint *Tested to ASTM E84 (UL723) at 14% surface coverage (modified test for sealants and caulks) **Per SCAQMD Rule 1168 (EPA Method 24) ***500 Cycles per UL2079, AC30 (ICBO) and ASTM E1399 ADependent on temperature and humidity Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestoD. com including Safety Data Sheets (SDS's). Precautionary Information Consult Safety Data Sheet (SDS) for additional information on the safe handling and disposal of this material. Wash areas of skin contact with soap and water. Avoid contact with eyes. Apply in areas with adequate ventilation. Availability SpecSeal° ES Elastomeric Sealant is available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800-992-1180 or visit www.stifirestop.com. ORDERING INFORMATION Catalog Number UPC Number Size (UOM) Qty. Case Qty. Weight (Each) ES100 730573081006 10.1 Oz Tube -18.2 cu in (300 ml) 1 12 1.08 Ibs (0.49 kg) ES10OR 730573081013 10.1 Oz Tube -18.2 cu in (300 ml) - Red 1 12 1.08 Ibs (0.49 kg) ES105 730573081051 5 Gallon Pail -1,155 cu in (19.0 liters) 1 N/A 63.30 Ibs (28.71 kg) ES105R 730573081068 5 Gallon Pail -1,155 cu in (19.0 liters) - Red 1 N/A 63.30 Ibs (28.71 kg) ES120 730573081037 20 Oz Sausage - 36 cu in (592 ml) 1 12 1.97 Ibs (0.89 kg) ES120R 730573081044 20 Oz Sausage - 36 cu in (592 ml) - Red 1 12 1.97 Ibs (0.89 kg) ES129 730573081297 29 Oz Tube - 52 cu in (858 ml) 1 12 3.05 Ibs (1.38 kg) ES129R 730573081310 29 Oz Tube - 52 cu in (858 ml) - Red 1 12 3.05 Ibs (1.38 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECHNICAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAL/WARRANTY MADE IN THE USA-©2021 SPECIFIED TECHNOLOGIES INC. Ifs Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com STISpecified SpecSeal® ES Elastomeric Sealant • ZSFOD5032 24721 ® Technologies Inc. IV MEMBER 2of2 P R 0 D U C S H- SpecSeal° LCI Intumescent Sealant SpecSeal° LCI Sealant is a versatile and economical intumescent sealant that has excellent caulking properties as well as high build properties on vertical or overhead surfaces. This single component sealant may be caulked (standard cartridge or bulk loaded), knifed or troweled. In addition, SpecSeal° LCI Sealant does not contain PCB's or asbestos. SpecSeal° LCI Sealant is storage stable (when stored according to the manufacturer's recommendations), and will not separate or shrink when dried (when applied according to the manufacturer's recommendations). SpecSeal° LCI Sealant will adhere to all common construction and penetrant materials and contains no solvents that might adversely effect plastic pipes or cable jackets. Applications SpecSeal° LCI Sealant has a broad application base designed to seal a wide variety of common penetrations and construction joints. Penetrant types include: Metallic penetrants (steel, iron, copper pipe, copper tubing, steel conduit and EMT) up to 36 in (914 mm) trade size; Non-metallic penetrants (Conduits & Tubing including PVC, CPVC, ABS, and PEX); Insulated pipes including heating, cooling, and condensation applications; Common electrical service and power distribution (service entrance, cable trays, busways), telephone, data, and TV cabling; Structural Steel and Metal Ductwork including HVAC, bath and dryer vents. This product is also used in conjunction with other SpecSeal° Products such as SpecSeal° Firestop Collars and Wrap Strips to protect larger plastic pipes. Specifications The firestopping sealant shall be a water-resistant, intumescent latex sealant. The sealant when exposed to high heat or flame shall exhibit a free expansion of up to 10 times its original volume. The firestopping sealant shall contain no water soluble nor hygroscopic ingredients and shall be acoustically tested. The sealant shall be UL Certified and/or FM approved and tested to the requirements of ASTM E814 (UL1479), CAN/ULC-S115 and shall meet Class A finish requirements when tested in accordance with ASTM E84 (UL723). Specified Divisions Division 7 078413 Penetration Firestopping Division 7 07 84 43 Joint Firestopping Division 22 22 00 00 Plumbing Division 23 23 00 00 HVAC Division 26 26 00 00 Electrical Performance SpecSeal° LCI Sealant is the basis for systems that meet the exacting criteria of ASTM E814 (UL1479), ASTM E1966 (UL2079) and CAN/ULC-S115 as well as to the time -temperature requirements of ASTM E119 (UL263). LCI provides up to a 4-hour fire rating for typical service penetrations through concrete or wood floors, concrete or masonry walls, as well as gypsum board walls. SpecSeal° LCI Sealant meets Class A finish requirements for Flame Spread and Smoke Development when tested in accordance with Features & Benefits • Economical: high performance without the high price • Highly intumescent: expands up to 10 times • Excellent smoke seal • Water resistant: will not re -emulsify when dry • Water -based for easy installation, cleanup, and disposal • Acoustically tested: reduces noise transmission • Safe, low VOC's, no asbestos, no PCBs, no inorganic fibers • Paintable when dry • Auto bonding • Non -halogenated • High solids formula - minimal shrinkage • Meets LEEDTM v3, v4, & v4.1 requirements. Low emitting materials credit. See general LEED letter for additional applicable credits. ASTM E84 (UL723). Meets or exceeds the requirements of ASTM �pss►F�F C834, Type C, Grade 0. SpecSeal° LCI Sealant is also acoustically u <�> u FBC -E. „S tested, demonstrating excellent sound attenuation properties. C o US APPROVED SYSTEM COMPATIBLE Intertek A& Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 3 STD® Technologies Inc. SpecSeal LCI Intumescent Sealant • ZSFOD5062 24721 P R 0 D U C S H — SpecSeal° LCI Intumescent Sealant Color Density/Weight per Gallon Solids Content by Weight Solids Content by Volume Flame Spread* Smoke Development* Mold & Fungus Growth Rating (ASTM G21) Movement Capabilities Coverage pH In Service Temperature Storage Temperature Applicaton Temperature STC Rating (ASTM E90-04/ASTM C919) VOC Content** Expansion Begins Average Volume Shrinkage (ASTM C1241) Volume Expansion Shelf Life From Date of Manufacture Red 12.3 lb/gal (1.47 kg/L) 80.0% 70.8% 0 0 0 33% Compression Only Class II For more information on product coverage see the following documents for Linear Joint & Penetration 9 Less than or equal to 185°F (85°C) 40°F (4°C) to 95°F (35°C) 35°F (2°C) to 100°F (38°C) 62 (Relates to Specific Construction) 26 g/L 350°F (177°C) 21.1 % 10x Free Expansion 24 months *Tested to ASTM E84 (UL723) at 14% surface coverage (modified test for sealants and caulks) **Per SCAQMD Rule 1168 (EPA Method 24) Limitations Use product as per manufacturer's instructions. Use only in applications per the manufacturer's published designs or specific recommendations. End user must ultimately determine the suitability of the product and/or design to his or her specific requirements and assumes responsibility for its use. PRODUCT CONTAINS WATER AND IS CONDUCTIVE UNTIL DRY. DO NOT APPLY IN THE PRESENCE OF EXPOSED OR ENERGIZED ELECTRICAL CONDUCTORS. This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. Maintenance No maintenance is normally required, however a periodic inspection of rated barriers is recommended to make sure that any new openings, modifications of previously installed firestops, or areas exhibiting physical damage, have been properly sealed or repaired. Subsequent sealing or repairs should be accomplished using SpecSeal° products per the original approved design. RETROFIT: When adding or removing penetrants, care should be taken to minimize damage to the seal. Reseal using SpecSeal® products per the approved design. NOTE: New penetrants of a different nature than the original design may require a totally new firestop design or extensive modifications to the existing design. Reseal all openings as per the requirements of the modified design. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product iOT1, for complete listings. (Firestop Systems). A& Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 3 SpecSeal LCI Intumescent Sealant • ZSFOD5062 24721 STD® Technologies Inc. P R 0 D U C S H - SpecSeal° LCI Intumescent Sealant Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information Consult Safety Data Sheet (SDS) for additional information on the safe handling and disposal of this material. Availability SpecSeal° LCI Sealant is available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800-992-1180 or visit www.stifirestop.com. Catalog Number LC1300 UPC Number 730573011706 Size 10.1 Oz Tube -18.2 cu in (300 ml) (UOM) Qty. 1 Case Qty. 12 Weight (Each) 1.05 Ibs (0.48 kg) L01305 730573011751 5 Gallon Pail - 1,155 cu in (19 liters) 1 1 61.39 Ibs (27.84 kg) LC1320 730573011720 20 Oz Sausage - 36 cu in (592 ml) 1 12 1.96 Ibs (0.89 kg) LC1329 730573011799 29 Oz Tube - 52.3 cu in (858 ml) 1 12 2.94 Ibs (1.33 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECHNICAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTORCOM/LEGAL/WARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER & I fI Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 3 of 3 Specified STD® Technologies Inc. SpecSeal LCI Intumescent Sealant • ZSFOD5062 24721 P R O D U C T D A T A S H E E T WF300 Intumescent Firestop Caulk WF300 Caulk is a latex based, high solids firestop caulk. This material, when properly installed, effectively seals penetration openings in wood frame construction against the spread of fire, smoke and combustion byproducts. WF300 Caulk is a single stage intumescent. When exposed to elevated temperatures, WF300 expands rapidly to seal off voids left by the burning or melting of combustible materials. WF300 Caulk is storage stable (when stored according to manufacturer's recommendations) and will not separate or shrink when dried. WF300 adheres tenaciously to common construction materials such as lumber and gypsum board as well as typical penetrant materials. Applications WF300 Caulk is used to seal through penetrations and gaps in fire resistance rated wood frame construction such as floor/ceilings and walls or partitions. Most common penetrating items were successfully tested with WF300. Specifications The firestopping sealant shall be a water-resistant, intumescent, latex sealant WF Firestop Caulk. The sealant when exposed to high heat or flame shall exhibit a free expansion of up to 5 times its original volume. The firestopping sealant shall contain no water soluble nor hygroscopic ingredients. The sealant shall be UL Certified and tested to the requirements of ASTM E814 (UL1479), CAN/ULC-S115 and shall meet Class A finish requirements when tested in accordance with ASTM E84 (UL723). Specified Divisions Division 7 078413 Penetration Firestopping Division 22 22 00 00 Plumbing Division 23 23 00 00 HVAC Division 26 26 00 00 Electrical Performance Features & Benefits Water based for easy installation, cleanup and disposal • Intumescent • Water-resistant, will not re -emulsify when dry Paintable when dry • Safe, no asbestos, no PCBs, no inorganic fibers • Auto bonding Non -halogenated • Meets LEEDTM v3 requirements. Low emitting materials credit. See general LEED letter for additional applicable credits. G�pSSIFj�O as U� �s SYSTEM COMPATIBLE WF300 Caulk is the basis for systems that meet the exacting criteria of ASTM E 814 (ANSI/UL1479), CAN/ULC-S115 as well as the time/temperature requirements of ASTM E119 (ANSI/UL263). UL Systems have been tested for wood frame construction and common penetrating items with ratings up to 2 hours. See UL Directory for system information. Limitations Use product as per manufacturer's instructions. Use only in applications per the manufacturer's published designs or specific recommendations. End user must ultimately determine the suitability of the product and/or design to his or her specific requirements and assumes responsibility for its use. PRODUCT CONTAINS WATER AND IS CONDUCTIVE UNTIL DRY. DO NOT APPLY IN THE PRESENCE OF EXPOSED OR ENERGIZED ELECTRICAL CONDUCTORS This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. Maintenance Inspection: Installations should be inspected periodically for subsequent damage. Any damage should be repaired using WF300 Caulk per the original approved design. & Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 2 STDSpecified WF300 Intumescent Firestop Caulk • ZSFOD5085 24721 ® Technologies Inc. P R O D U C T D A T A S H E E T WF300 Intumescent Firestop Caulk Color Red In Service Temperature Less than 185°F (85°C) Density/Weight per Gallon 10.2 Ibs/gal (1.22 kg/L) Storage Temperature 40°F (4°C) to 95°F (35°C) Solids Content by Weight 81% Application Temperature 35°F (2°C) to 100°F (38°C) Solids Content by Volume 77_6% STC Rating 61 (ASTM E90-04/ASTM C919) (Relates to Specific Construction) Flame Spread* 0 VOC Content** 53 g/L Smoke Development* 20 1 Expansion Begins 350°F (176°C) For more information on product Average Volume Shrinkage 23.5% Coverage coverage see the following documents (ASTM C1241) for Linear Joint & Penetration Volume Expansion 5x free expansion pH 7.4 to 8.4 Shelf Life From Date of 24 months Manufacture *Tested to ASTM E84 (UL723) at 14% surface coverage (modified test for sealants and caulks) **Per SCAQMD Rule 1168 (EPA Method 24) Retrofit: When adding or removing penetrants, care should be taken to minimize damage to the seal. Reseal using WF300 Caulk per the original approved design. NOTE: New penetrants of a different nature than the original design may require a totally new firestop design or extensive modifications to the existing design. Reseal all openings as per the requirements of the modified design. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product i0Tm for complete listings. (Firestop Systems). Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestoD. com including Safety Data Sheets (SDS's). Precautionary Information Consult Safety Data Sheet (SDS) for additional information on the safe handling and disposal of this material. Wash areas of skin contact with soap and water. Avoid contact with eyes. SEALANT IS CONDUCTIVE UNTIL DRY. Availability WF300 Caulk is available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800-992-1180 or visit www. stifirestop.com. Catalog Number UPC Number Size (UOM) Qty. Case Qty. Weight (Each) WF310 730573097106 10.1 Oz. Tube -18.2 cu. in. (300 ml) 1 12 0.95lbs (0.43 kg) WF320 730573097205 20 Oz. Sausage - 36 cu. in. (592 ml) 1 12 1.70 Ibs (0.77 kg) WF305 730573097052 5 Gallon Pail -1,155 cu. in. (19.0 liters) 1 N/A 54.30 Ibs (24.63 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECHNICAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED, IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAL/WARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER �✓ Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 2 STISpecified WF300 Intumescent Firestop Caulk • ZSFOD5085 24721 ® Technologies Inc. D A T A S H E E T EZ Path° Series 22 Fire Rated Pathway The EZ Path° Series 22 Fire Rated Pathway is a pathway device designed to allow cables to penetrate fire -rated walls without the need for firestopping. This device features a built-in fire sealing system that automatically adjusts to the amount of cables installed. Once installed in a fire barrier, cables can be easily added or removed at any time without the need to remove or reinstall firestopping materials. The EZ Path° Series 22 Fire Rated Pathway consists of an enclosed heavy gauge galvanized steel pathway lined with intumescent material engineered for rapid expansion when exposed to fire or high temperatures, quickly sealing the pathway and preventing the passage of flames and smoke. EZ Path° Series 22 Fire Rated Pathway is painted safety orange for easy identification. Its compact square profile allows a maximum number of cables to be installed in a relatively small area. The pathway measures approximately 1.5" x 1.5" (37 mm) and is 10.5" (267 mm) long. Applications EZ Path° Series 22 Fire Rated Pathway is designed for easy installation in walls. Tested and approved cable capacities range from 0 to 100% visual fill. EZ Path° Series 22 Fire Rated Pathway when installed with provided wall plates is designed for new cable installations. In these installations, the device does not require mechanical attachment to either the wall or the wall framing and may be installed after the wallboard has been installed. EZ Path° Series 22's split body design also allows the device to be easily disassembled and installed around previously installed cables in existing construction. EZ Path" Series 22 Fire Rated Pathway provides exceptional cable capacity. A single unit installed in a wall has an equal cable carrying capacity of a 2" (51 mm) diam sleeve utilizing typical putty firestop systems (35% cable loading). Specifications All data, video, and communications cable bundles shall utilize an enclosed fire -rated pathway device wherever said cables penetrate rated walls. The fire -rated pathway shall contain a built-in fire sealing system sufficient to maintain the hourly fire rating of the barrier being penetrated. The self- contained sealing system shall automatically adjust to the installed cable loading and shall permit cables to be installed, removed, or retrofitted without the need to remove or reinstall firestop materials. The pathway shall be UL Certified and tested to the requirements of ASTM E814 (UL1479) and CAN/ULC-S115. Features & Benefits • Easy to install • No firestopping required • Firestopped at all stages of use • UL rested - low leakage • UL Certified for the complete range of its capacity • Match the capacity of a 2" (51 mm) conduit • Acoustically tested Shell Composition 0.059" (1.5 mm) Galvinzed Steel Cable Loading Area 1-1/4 sq in (nom.) [8.06 sq cm] Allowable Cable Fill 0 to 100% Visual Fire Resistance Ratings 1, 2, 3 and 4 Hour Expansion Begins 350°F (177°C) Volume Expansion 30x Sample Cable Volume 15 (nom.) Cat 6 (0.236" OD) Specified Divisions Division 7 078413 Penetration Firestopping In Service Temperature -10°F (23°C) to 120°F (49°C) Division 26 26 00 00 Electrical Storage Temperature Less than 120°F (49°C) Division 27 27 00 00 Communications Shelf Life No Limit —� Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 2 p STD® Technologies Inc. EZ Path® Series 22 Fire Rated Pathway ZSFOD5087 24721 D A T A S H E E T EZ Path° Series 22 Fire Rated Pathway Performance VU SSIFj EZ Path° Series 22 Fire Rated Pathway is UL Tested and Certified in accordance with ASTM E814 U ■ us APPROVED (UL1479) and CAN/ULC-S115. Systems are available for common wall construction with ratings up toand including 4 hours. C Limitations This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. Cable Installation Cables may easily be added or removed at any time without removing or reinstalling the fire seal. Cables may be added individually or in bundles. Wrapping ends with a low -friction tape facilitates cable insertion. A self-adjusting cable throat automatically adjusts to accommodate the cable bundle as it passes through the pathway. Maintenance No maintenance of the pathway is normally required. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product iO!M for complete listings. (Firestop Systems). Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information The use of this device is subject to local, regional and national codes. Consult the local Building Code Official or Authority Having Jurisdiction regarding any regional or local requirements that might influence the selection or use of this product. Availability EZ Path° Products are available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800- 992-1180 or visit www.stifirestop.com. Catalog Number UPC Number Description (U0M) Qty. Case Qty. Weight (Each) EZD22 730573000229 Device, full kit includes wall plates and labels 1 6 1.91 Ibs (0.86 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECH N I CAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAL/WARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER _✓ Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 2 STDSpecified EZ Path® Series 22 Fire Rated Pathway • ZSFOD5087 24721 ® Technologies Inc. D A T A S H E E T EZ Path° Series 33 Fire Rated Pathway The EZ Path° Fire Rated Pathway is a pathway device designed to allow cables to penetrate fire -rated walls and floors without the need for firestoppil device features a built-in fire and smoke sealing system that automat adjusts to the amount of cables installed. Once installed in a fire barril can be easily added or removed at any time without the need to remo or reinstall firestopping materials. EZ Path° Series 33 Fire Rated Pathway consists of an enclosed heavy gauge galvanized steel pathway lined with intumescent material engineered for rapid expansion when exposed to fire or high temperatures, quickly sealing the pathway and preventing the passage of flames and smoke. EZ Path° Series 33 Fire Rated Pathway is painted safety orange for easy identification. Its compact square profile allows a maximum number of cables to be installed in a relatively small area. The pathway measures approximately 3" (76 mm) x 3" (76 mm) and is 10.5" (267 mm) long. Applications EZ Path° Series 33 Fire Rated Pathway is designed for easy installation in floors and walls. Tested and approved cable capacities range from 0 to 1 nno/-visual fill. EZ Path° Series 33 Fire Rated Pathway when installed with available wall plates is designed for new cable installations. In these installations, the device does not require mechanical attachment to either the wall or the wall framing and may be installed after the wallboard has been installed. EZ Paths° split body design also allows the device to be easily disassembled and installed around previously installed cables in existing construction. EZ Path° Series 33 Fire Rated Pathway provides exceptional cable capacity. A single unit installed in a wall exceeds the cable carrying capacity of a 4" (102 mm) sleeve utilizing typical putty firestop systems (35% cable loading). Multiple ganged devices utilizing available double, triple, four and seven gang wall plates provide additional capacity or segregation of cables by use, type, installer or vendor as desired. Specifications All data, video, and communications cable bundles shall utilize an enclosed fire -rated pathway device wherever said cables penetrate rated walls. The fire -rated pathway shall contain a built-in fire sealing system sufficient to maintain the hourly fire rating of the barrier being penetrated. The self-contained sealing system shall automatically adjust to the installed cable loading and shall permit cables to be installed, removed, or retrofitted without the need to remove or reinstall firestop materials. The pathway shall be UL Certified and/or FM Systems Approved and tested to the requirements of ASTM E814 (UL1479) and CAN/ULC-S115. Specified Divisions Division 7 078413 Penetration Firestopping Division 26 26 00 00 Electrical Division 27 27 00 00 Communications Features & Benefits • Easy to install • No firestopping required • Acoustically tested • Firestopped at all stages of use • UL tested - low leakage • UL Certified for the complete range of its capacity • Pathways can be ganged for additional capacity • Permits cable segregation by use, type, vendor • Match the capacity of a 4" (102 mm) conduit & Specified STD® Technologies Inc. Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 3 EZ Path' Series 33 Fire Rated Pathway • ZSFOD5079 24721 P R O D U C T D A T A S H E E T EZ-Path° Series 33 Fire Rated Pathway Shell Composition Cable Loading Area Allowable Cable Fill Fire Resistance Ratings Expansion Begins Volume Expansion Sample Cable Volume Cat 6 (0.236" OD) In Service Temperature Storage Temperature Shelf Life 0.059" (1.5 mm) Galvanized Steel 6 sq in (nom.) [39 sq cm] 0 to 100% Visual 1, 2, 3 and 4 Hour 350°F (177°C) 15x 88 (nom.) -10°F (-23°C) to 120°F (49°C) Less than 120°F (49°C) No Limit Performance G�PSSIFj�O EZ Path° is UL Tested and Certified in accordance with ASTM E814 (UL1479) and CAN/ULC-S115. U FM Systems are available for common floor and wall constructions with ratings up to and including 4 am C O us APPROVED hours. Limitations This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. Cable Installation Cables may easily be added or removed at any time without removing or reinstalling the fire seal. Cables may be added individually or in bundles. Wrapping ends with a low -friction tape facilitates cable insertion. A self-adjusting cable throat automatically adjusts to accommodate the cable bundle as it passes through the pathway. Maintenance No maintenance of the pathway is normally required. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product iOTm for complete listings. (Firestop Systems). Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). & Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 3 STD® Technologies Inc. EZ Path Series 33 Fire Rated Pathway • ZSFOD5079 24721 P R O D U C T D A T A S H E E T Precautionary Information The use of this device is subject to local, regional and national codes. Consult the local Building Code Official or Authority Having Jurisdiction regarding any regional or local requirements that might influence the selection or use of this product. Availability EZ-Path° Products are available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800- 992-1180 or visit www.stifirestop.com. Catalog Number UPC Number Description (UOM) Qty. Case Qty. Weight (Each) EZD33FWS 730573000045 Fire -Rated Pathway Device 1 6 2.70 Ibs (1.22 kg) EZDP33FWS 730573000342 Square Plate Kit - Device with square wall plates and labels 1 4 3.52 Ibs (1.60 kg) EZP133W 730573001332 Square Wall Plates with labels 1 1 0.81 Ibs (0.37 kg) EZDP133CWK 730573000359 Circular Plate Kit - Device with circular wall plates and labels 1 1 3.83 Ibs (1.74 kg) EZP133CW 730573001370 Circular Wall Plates with labels 1 1 0.82 Ibs (0.37 kg) EZDP133FK 730573008355 Kick in Floor Plate Kit - Device with split floor plate 1 1 3.53 Ibs (1.60 kg) EZP133K 730573008331 Kick -In Split Floor Plate 1 6 0.71 Ibs (0.32 kg) ORDERING INFORMATION•INSTALLATIONS EZDP33WR 730573005330 Retro-Fit Kit - Device with retro-fit wall mounting plates and labels 1 1 6.63 Ibs (3.01 kg) EZP133R 730573005354 Retro-Fit Mounting Plates with labels 1 1 3.57 Ibs (1.62 kg) EZDP133CAK 730573000366 Conduit Attachment Kit -Device 1 1 4.05 Ibs (1.84 kg) with conduit attachment plate and label EZP133CA 730573001387 Conduit Attachment Plate with label 1 1 0.86 Ibs (0.39 kg) ORDERING INFORMATIONINSTALLATION EZDP233GK 730573002353 Two -Gang Kit - Two (2) devices with two -gang plates and labels 1 1 6.48 Ibs (2.94 kg) EZP233W 730573002339 Two -Gang Wall Plates with labels 1 1 0.79 Ibs (0.36 kg) EZDP333GK 730573903353 Three -Gang Kit - Three (3) devices with three -gang plates and labels 1 1 9.10 Ibs (4.13 kg) EZP333W 730573003336 Three -Gang Wall Plates and labels 1 1 1.03 Ibs (0.47 kg) EZDP433GK 730573004357 Four -Gang Kit - Four (4) devices with four -gang plates and labels 1 1 13.06 Ibs (5.92 kg) EZP433W 730573004333 Four -Gang Wall Plates and labels 1 1 1.73 Ibs (0.78 kg) EZDP733GK 730573007358 Seven -Gang Kit - Seven (7) devices with seven -gang plates and labels 1 1 21.82 Ibs (9.90 kg) EZP733W 730573007334 Seven -Gang Wall Plates and labels 1 1 2.66 Ibs (1.21 kg) ORDERING INFORMATIONACCESSORIES EZD33E 730573000052 Extension Module 1 1 1.63 Ibs (0.74 kg) RCM33 730573009338 One Pair (2) Radius Control Modules 1 1 0.05 Ibs (0.02 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECH N I CAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAUWARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER & I fI Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 3 of 3 Specified STD® Technologies Inc. EZ Path' Series 33 Fire Rated Pathway • ZSFOD5079 24721 D A T S H E E- EZ Path° Series 44+ Fire Rated Pathway The EZ Path° Series 44+ Fire Rated Pathway is a pathway device designed to allow cables to penetrate fire -rated walls and floors without the need for firestopping. This device features a built-in fire and smoke sealing system that automatically adjusts to the amount of cables installed. Once installed in a fire barrier, cables can be easily added or removed at any time without the need to remove or reinstall firestopping materials. The EZ Path° Series 44+ Fire Rated Pathway consists of an enclosed heavy gauge galvanized steel pathway lined with intumescent material engineered for rapid expansion when exposed to fire or high temperatures, quickly sealing the pathway and preventing the passage of flames and smoke. EZ Path° Series 44+ Fire Rated Pathway is painted safety orange for easy identification. Its compact square profile allows a maximum number of cables to be installed in a relatively small area. The pathway measures approximately 4 in (101.6 mm) x 4-5/8 in (118 mm) and is 14 in (356 mm) long and can be increased by 6" (152 mm) for every Series 44+ Extension module (EZD44ES) installed. Applications EZ Path° Series 44+ Fire Rated Pathway is designed for easy installation in floors and walls. Tested and approved cable capacities range from 0 to 100% visual fill. EZ Path° Series 44+ Fire Rated Pathway when installed with available single wall plates is designed for new cable installations. In these installations, the device does not require mechanical attachment to either the wall or the wall framing and must be installed after the wallboard has been installed. Split floor plates and multi -gang wall and floor brackets permit installation around previously installed cables if so desired. These installations require mechanical attachment to the barrier. A list of available accessories along with their intended use is shown on page 2 under available components. EZ Path° Series 44+ Fire Rated Pathway Fire Rated Pathway provides exceptional cable capacity. A single unit installed in a wall exceeds the cable carrying capacity of a 6 in (152 mm) sleeve utilizing typical putty firestop systems (35% cable loading). Multiple ganged pathways utilizing available wall bracket kits provide additional capacity or segregation of cables by use, type, installer or vendor as desired. Shell Composition 0.059" (1.5 mm) Galvanized Steel Cable Loading Area 12.66 sq in (81.7 sq cm) 3-3/8" (86 mm) x 3-3/4" (95 mm) Allowable Cable Fill 0 to 100% Visual Fire Resistance Ratings 1, 2, 3 and 4 hour Expansion Begins 350°F (177°C) Volume Expansion 15x Sample Cable Volume - Cat 6 (0.236" OD) 210 (nom.) In Service Temperature -10°F (-23°C) to 120°F (49°C) Storage Temperature Less than 120°F (49°C) Shelf Life No Limit Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 3 STDh EZ Path' Series 44+ Fire Rated Pathway • ZSFOD5139 24721 ® Technologies Inc. D A T S H E E- EZ Path° Series 44+ Fire Rated Pathway Specifications All data, video, and communications cable bundles shall utilize an enclosed fire rated pathway device wherever said cables penetrate rated walls and floors. The fire - rated pathway shall contain a built-in fire sealing system sufficient to maintain the hourly fire rating of the barrier being penetrated. The self-contained sealing system shall automatically adjust to the installed cable loading and shall permit cables to be installed, removed, or retrofitted without the need to remove or reinstall firestop materials. The pathway shall be UL Certified and/or FM Systems Approved and tested to the requirements of ASTM E814 (UL1479) and CAN/ULC-S115. Specified Divisions Division 7 078413 Penetration Firestopping Division 26 26 00 00 Electrical Division 27 27 00 00 Communications Features & Benefits Easy to install No firestopping required Firestopped at all stages of use UL tested - low leakage Acoustically tested UL Certified for the complete range of its capacity Interlocking design for easy gang installations Permits cable segregation by use, type, vendor More than twice the capacity of EZ Path® 33 Performance G�pSSIFj�O EZ Path° Series 44+ Fire Rated Pathway is UL Tested and Certified in accordance with a FM ASTM E814 (UL1479) and CAN/ULC-S115. Systems are available for common floor and wall L C ®� US APPROVED constructions with ratings up to and including 4 hours. Limitations This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. Cable Installation Cables may easily be added or removed at any time without removing or reinstalling the fire seal. Cables may be added individually or in bundles. Wrapping ends with a low -friction tape facilitates cable insertion. A self-adjusting cable throat automatically adjusts to accommodate the cable bundle as it passes through the pathway. Maintenance No maintenance of the pathway is normally required. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product i0iM for complete listings. (Firestop Systems). Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information The use of this device is subject to local, regional and national codes. Consult the local Building Code Official or Authority Having Jurisdiction regarding any regional or local requirements that might influence the selection or use of this product. & Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 3 STDh EZ Path' Series 44+ Fire Rated Pathway ZSFOD5139 24721 ® Technologies Inc. D A T S H E E- EZ Path° Series 44+ Fire Rated Pathway Availability EZ Path" Products are available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800- 992-1180 or visit www.stifirestop.com. ORDERING INFORMATION Catalog Number UPC Number Description (UOM) Qty. Case Qty. Weight (Each) EZD44S2 730573001004 Fire -Rated Pathway Device 1 4 5.56 Ibs (2.52 kg) EZDP44S2 730573001066 Fire -Rated Pathway Kit - Device with wall plates and labels 1 1 7.92 Ibs (3.59 kg) EZP144W 730573001448 Single Wall Plates and Labels 1 1 2.11 Ibs (0.96 kg) EZDP144RS2 730573001073 Split Wall Plate - Device with split wall plate and labels 1 1 8.17 Ibs (3.70 kg) EZP144RS 730573001486 Split Wall Plate - Plate only 1 1 2.42 Ibs (1.10 kg) EZDP144FKS2 730573001080 Floor Kit - Device with floor plate 1 1 7.32 Ibs (3.32 kg) EZP144F 730573008348 Split Floor Plate - Plate only 1 1 1.50 Ibs (0.68 kg) ORDERING INFORMATION - GANG PLATES FOR WALLS EZP544W 730573005446 Multi -gang wall plate brackets for 1-5 devices 1 8 3.91 Ibs (1.77 kg) EZP544WD 730573005460 Multi -gang wall plate brackets for 2-10 devices 1 8 4.00 Ibs (1.81 kg) EZP644W 730573006481 Multi -gang wall plate brackets for 6 devices 1 8 4.40 Ibs (1.99 kg) EZP644WD 730573006573 Multi -gang wall plate brackets for 12 devices 1 8 4.80 Ibs (2.18 kg) EZP544WV 730573005477 Vertical Multi -Gang Wall Bracket Kit for 1-5 devices 1 1 7.00 Ibs (3.18 kg) ORDERING INF• ' •N - MODULAR FLOOR GRID SYSTEM EZDG444S2 730573001103 Single Bank Floor Grid - Four (4) Devices with floor frame 1 1 37.40 Ibs (16.96 kg) EZG444 730573004433 Single -Slot Frame for Four (4) Pathways 1 1 11.39 Ibs (5.17 kg) EZDG844S2 730573001110 Dual -slot Frame Kit with 8 Pathways - (Includes eight (8) 1 1 65.86 Ibs (29.87 kg) Series 44+ devices with EZG844) EZG844 730573008447 Dual -Slot Frame for Eight (8) Pathways 1 1 16.25 Ibs (7.37 kg) EZDG1644S2 730573001127 Quad -slot Frame Kit with 16 Pathways - (Includes sixteen 1 1 49.96 Ibs (22.66 kg) (16) Series 44+ devices with EZG1644) EZG1644 730573006443 Multi -Slot Frame for Sixteen (16) Pathways 1 1 26.59 Ibs (12.06 kg) EZG444CP 730573004494 Floor Grid Splice Plate Kit - includes plate and gasket 1 1 2.11 Ibs (0.95 kg) EZD444MBS2 730573001097 Single Bank of Devices - Four (4) Devices with hanger bracket 1 1 23.37 Ibs (10.60 kg) EZP444MB 730573004487 Hanger Bracket for Modular Floor Grid System 1 1 1.30 Ibs (0.59 kg) TRK444 730573004463 T-Rating Kit 1 1 15.36 Ibs (6.97 kg) ORDERING INFORMATIONACCESSORIES EZD44ES 730573000694 6" Extension Module - use with Series 44+ pathway ONLY 1 1 2.44 Ibs (1.11 kg) EZRCM44S 730573009345 Radius Control Module - one pair (2) for use 1 1 0.12 Ibs (0.05 kg) with Series 44+ pathway ONLY IMPORTANT NOTICE: ALL STATEMENTS, TECHNICAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAUWARRANTY IV MADE IN THE USA-©2021 SPECIFIED TECHNOLOGIES INC. MEMBER -� Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 3 of 3 EZ Path' Series 44+ Fire Rated Pathway • ZSFOD5139 24721 STIp ® Technologies Inc. P R O D U C T D A T A S H E E T EZ Path"' Retrofit Device (EZDR200 & EZDR400) The EZ Path° Retrofit Device is designed to restore the ratings for overfilled cable sleeve penetrations. The device features a built-in fire and smoke sealing system that can attach either to the sleeve or the barrier surface. The EZ Path° Retrofit Device consists of a heavy gauge galvanized steel housing containing intumescent materials that expand rapidly when exposed to fire or high temperatures to close off the void area. Its unique two-piece design quickly installs around cable bundles and extended sleeves and can even accommodate standard conduit bushings. The square device shape allows cable exit or entry from multiple directions.. Applications EZ Path° Retrofit Device restores non -compliant overfilled sleeve con( in walls and floors. Cable capacity ranges from 50 to 100% visual fill.1 piece split device facilitates installation around existing cable bundles. backplate attaches directly to the end of the steel sleeve. For flush-mcu, sleeves, mounting tabs allow for attachment to the substrate. EZ Path® Retrofit Devices are sized for 2 in (2.197 in [56 mm] to 2.375 in [60 mm] OD) and 4 in (4.500" [114 mm]) trade size EMT or rigid steel conduit sleeves or stubs. No additional putty or sealant is required. Existing putty or sealant may be left in place. Specifications All new data comm cable penetrations shall be routed through factory - supplied, maintenance -free, fire -rated pathway devices (Ex. EZ Path° Fire Rated Pathways). For existing sleeves where cable fill percentage exceeds listed system specifications, a factory -supplied, fire -rated retrofit device shall be installed. The device shall be a two-piece split design with intumescent materials and allow 50 to 100 percent visual fill. The device shall be UL Certified and tested to ASTM E814 (UL1479) and CAN/ULC-S115. Specified Divisions Division 7 078413 Penetration Firestopping Division 26 26 00 00 Electrical Division 27 27 00 00 Communications Performance EZ Path° Retrofit Device is UL Certified in accordance with ASTM E814 (UL1479) am G` pss�gFo and CAN/ULC-S115. Systems are available U for common floor and wall construction C O us with ratings up to and including 2 Hr. L Ratings range from less than 1 to 10.7 CFM dependent upon cable types, sizes, and configurations. Refer to UL System for more details. Features & Benefits • Easy to install • No additional firestopping required • Sized for 2 in (2.197 in [56 mm] to 2.375 in [60 mm] OD) and 4 in (4.500 in [114 mm]) trade size EMT or rigid steel conduit sleeves or stubs • 50% to 100% cable fill • Works with extended or flush sleeves • Bring overfilled sleeves back into code compliance Shell Composition 0.059" (1.5 mm) Thick Galvanized Steel Fire Ratings 1 or 2 Hours Expansion Begins 250°F (121°C) Allowable Cable Fill 50 to 100% In Service Temperature Less than 130°F (54°C) Shelf Life No Limit -� Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 2 STIh EZ Path' Retrofit Device (EZDR200 & EZDR400) • ZSFOD5321 24721 . Technologies Inc. P R O D U C T D A T A S H E E T EZ Path° Retrofit Device (EZDR200 & EZDR400) Limitations This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. Maintenance No maintenance of the pathway is normally required. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product iOlm for complete listings. (Firestop Systems). Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information The use of this device is subject to local, regional and national codes. Consult the local Building Code Official or Authority Having Jurisdiction regarding any regional or local requirements that might influence the selection or use of the product. Availability EZ Path° Products are available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800- 992-1180 or visit www.stifirestop.com. Catalog Number UPC Number Description (UOM) Qty. Case Qty. Weight (Each) EZDR200 730573002001 Retrofit Device for 2" (2-3/16" or 2-3/8" O.D.) Sleeves, One Pair (2) 1 4 2.83 Ibs (1.28 kg) EZDR400 730573004005 Retrofit Device for 4" (4-1/2" O.D.) Sleeves, One Pair (2) 1 4 4.81 Ibs (2.18 kg) EZPR150 730573002018 1-1/2" Adapter Plate for EZDR200, One Pair (2) 1 1 0.75 Ibs (0.34 kg) EZPR300 730573004012 3" Adapter Plate for EZDR400, One Pair (2) 1 1 1.25 Ibs (0.57 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECH N I CAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAUWARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER & Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 2 STDSpecified EZ Path'Retrofit Device (EZDR200 &EZDR400) • ZSFOD5321 24721 ® Technologies Inc. P R O D U C T D A T A S H E E T SpecSeal° LCC Firestop Collars The SpecSeal° LCC Collar is a factory -manufactured device designedto protect plastic pipes penetrating fire -rated walls and floors. Utilizing a heavy gauge galvanized metal collar to house a molded intumescent insert, the SpecSeal° LCC Firestop Collar is specifically sized to fit 1-1/2 in, 2 in, 3 in, and 4 in (38 mm, 51 mm, 76 mm and 102 mm) trade sized pipes. When exposed to temperatures in excess of 320°F (160°C), the SpecSeal° LCC Collar's molded insert begins to expand (intumesce) rapidly to form a dense, highly insulative char. Its free expansion ranges from 32x to 64x original (pre -expanded) volume. Expansion continues up to 1,000°F (538°C). Applications SpecSeal° LCC Collars are used to protect a variety of plastic pipes including PVC, PVC Foam Core (ccPVC), CPVC, RNC, PP, FRPP, FRP, HDPE, PE, PVDF, ABS and ABS Foam Core (ccABS) in both vented (DWV) and closed (electrical conduit and water supply) installations. SpecSeal° LCC Collars are suitable for use in all common constructions including concrete floors, concrete over steel deck, concrete walls, concrete block walls, gypsum board walls, as well as wood floor assemblies. Specifications The firestop system shall be a factory assembled firestop collar utilizing a molded, flexible intumescent insert. The intumescent insert shall provide a minimum of 30x free expansion and shall contain no water soluble expansion ingredients. The specified material shall be approved for a wide range of applications including PVC, PVC Foam Core (ccPVC), CPVC, RNC, PP, FRPP, FRP, HDPE, PE, PVDF, ABS and ABS Foam Core (ccABS) when used by itself or in combination with other products from the same manufacturer. The collar shall be UL Certified and tested to the requirements of ASTM E814 (UL1479) and CAN/ULC-S115. Specified Divisions Division 7 078413 Penetration Firestopping Division 22 22 00 00 Plumbing Performance FM am SpecSeal® LCC Collars are thebasis for systems that meet theC ®� us APPROVED exacting criteria of ASTM E814 (UL1479) and CAN/ULC-S115. Systems have been tested for all common forms of masonry construction and the most common plastic pipes with ratings up to two hours. Consult factory for information not available in the UL Online Certifications Directory/UL Product IQT" as of this printing. Limitations This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. Available Sizes F& j 1.5" (38 mm) 2" (51 mm) 3" (76 mm) 4" (102 mm) Shell Construction Galvanized Steel Expansion Begins 320°F (160°C) Volume Expansion 32 to 64x (free expansion) In Service Temperature Less Than 120°F (49°C) Shelf Life Features & Benefits No Limit • Rapid expansion - closes off burning pipes quickly • Small profile - use it in all the tight spots • Flexible & durable - no loose flakes (eye hazards) • Water resistant - no water soluble or hygroscopic ingredients • Economical - lower installed cost • High volume char - expands up to 60 times Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 2 STIp SpecSeal° LCC Firestop Collars • ZSFOD5064 24721 ® Technologies Inc. P R O D U C T D A T A S H E E T SpecSeal° LCC Firestop Collars Maintenance INSPECTION: Installations should be inspected periodically for subsequent damage. Any damage should be repaired using SpecSeal° products per the original approved design. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product 02A for complete listings. (Firestop Systems). Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information No unusual hazards are known or expected. Observe normal safety procedures during installation. Availability SpecSeal° Firestop Collars are available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800-992-1180 or visit www.stifirestop.com. Catalog Number UPC Number Description (UOM) Qty. Case Qty. Weight (Each) LCC150 730573039014 Firestop Collar for 1.5" (38 mm) Trade Size Plastic Pipe 1 6 0.22 Ibs (0.10 kg) LCC200 730573039021 Firestop Collar for 2.0" (51 mm) Trade Size Plastic Pipe 1 6 0.24 Ibs (0.11 kg) LCC300 730573039038 Firestop Collar for 3.0" (76 mm) Trade Size Plastic Pipe 1 6 0.46 Ibs (0.21 kg) LCC400 730573039045 Firestop Collar for 4.0" (102 mm) Trade Size Plastic Pipe 1 6 0.75 Ibs (0.34 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECHNICAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAL/WARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER �✓ Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 2 SpecSeal" LCC Firestop Collars • ZSFOD5064 24721 STISpecified ® Technologies Inc. J D U C S H E E T SpecSeal° Range -Taking Firestop Collars (RTC) SpecSeal° Range -Taking Firestop Collars (RTC) are factory - manufactured devices designed to seal plastic pipes penetrating through fire resistance rated walls and floors. SpecSeal° RTC Collars are comprised of a heavy gauge metal collar housing a molded intumescent insert. The adjustable collar is designed to allow a single collar to fit 3 in (89 mm) and 4 in (114 mm) trade size pipes and corresponding 3" (102 mm) and 4" (127 mm) couplings. When exposed to temperatures in excess of 320°F (160°C), the SpecSeal° Range -Taking Firestop Collars's molded insert begins to expand (intumesce) rapidly to form a dense, highly insulative char. Free expansion ranges from 32x to 64x original (pre -expanded) volume. Expansion continues up to 1,000°F (538°C). Applications SpecSeal° Range -Taking Firestop Collars are used to protect a variety of plastic pipes and couplings including PVC, PVC Cellular Core (ccPVC), CPVC, ABS, and ABS Cellular Core (ccABS) in both vented (DWV) and closed (electrical conduit (RNC) or water supply) installations. SpecSeal° Range - Taking Firestop Collars are suitable for use in all common constructions including concrete floors, concrete over steel deck, concrete walls, concrete block walls, gypsum board/stud walls, as well as wood floor/ceiling assemblies. Specifications The firestop system shall be a factory assembled firestop collar utilizing a molded, flexible intumescent insert. The intumescent insert shall provide a minimum of 30x free expansion and shall contain no water soluble expansion ingredients. The specified material shall be approved for a wide range of applications including PVC, PVC Foam Core (ccPVC), CPVC, RNC, PP, FRPP, FRP, HDPE, PE, PVDF, ABS and ABS Foam Core (ccABS) when used by itself or in combination with other products from the same manufacturer. The collar shall be UL Certified and tested to the requirements of ASTM E814 (UL1479) and CAN/ULC-S115. Specified Divisions Division 7 078413 Penetration Firestopping Division 22 22 00 00 Plumbing Performance SpecSeal° Range -Taking Firestop Collars are the basis for systems G�ssiF,Fo that meet the exacting criteria of am U ASTM E814 (UL1479) and CAN/ C o us ULC-S115. Systems have been tested for all common forms of construction and the most common plastic pipes and couplings with ratings up to two hours. Consult factory for more information or refer to the UL Online Certifications Directory/UL Product IQT to i Shell Construction Nom 22 GA galvanized steel (0.03" (0.76 mm) thick) Intumescent Insert Molded one piece 3" trade size pipe (89 mm) Sizes 3" trade size pipe fitting (102 mm) accommodated 4" trade size pipe (114 mm) 4" trade size pipe fitting (127 mm) Expansion Begins Volume Expansion In Service Temperature Shelf Life Features & Benefits 320°F (160°C) 32x to 64x (free expansion) Less than 120°F (49°C) No Limit • Adjustable - one collar fits 3" (89 mm) pipe, 3" (102 mm) coupling, 4" (114 mm) pipe, and 4" (127 mm) coupling • Rapid expansion - closes off burning pipes quickly • Small profile - use it in all the tight spots • Flexible & durable - no loose flakes (eye hazards) • Water resistant - no water soluble or hygroscopic ingredients • Economical - lower installed cost • High volume char - expands up to 60 times & Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 2 STLh SpecSearp' Range -Taking Firestop Collars (RTC) • ZSFOD5102 24721 Technologies Inc. P R 0 D U C D A T A S H E E T SpecSeal° Range -Taking Firestop Collars (RTC) Limitations This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. Maintenance INSPECTION: Installations should be inspected periodically for subsequent damage. Any damage should be repaired using SpecSeal° Firestop Products per the original approved design. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product iOTm for complete listings. (Firestop Systems). Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information No unusual hazards are known or expected. Observe normal safety procedures during installation. Availability SpecSeal° Range -Taking Firestop Collars are available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800-992-1180 or visit www.stifirestop.com. Catalog Number UPC Number Description (UOM) Qty. Case Qty. Weight (Each) RTC350 730573038352 Adjustable factory collar for 3" (89 mm) & 4" (114 mm) 1 6 0.80 Ibs (0.36 kg) pipe and associated couplings IMPORTANT NOTICE: ALL STATEMENTS, TECH N I CAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAL/WARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER �✓ Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 2 STISpecified SpecSeall Range -Taking Firestop Collars (RTC) • ZSFOD5102 24721 ® Technologies Inc. P R O D U C T D A T A S H E E T SpecSeal° Series SSC Firestop Collar The SpecSeal° Series SSC Collar is a factory -manufactured device designed to protect plastic pipes penetrating fire -rated walls and floors. Utilizing a heavy gauge galvanized metal collar to house a molded intumescent insert, the SpecSeal° Series SSC Firestop Collar is specifically sized to fit 1-1/2 in (38 mm), 2 in (51 mm), 3 in (76 mm), and 4 in (102 mm) trade sized pipes. When exposed to temperatures in excess of 320°F (160°C), the SpecSeal° Series SSC Collar's molded insert begins to expand (intumesce) rapidly to form a dense, highly insulative char. Its free expansion ranges from 32x to 64x original (pre -expanded) volume. Expansion continues up to 1,000°F (538°C). Applications SpecSeal° Series SSC Collars are used to protect a variety of plastic pipes including PVC, PVC Foam Core (ccPVC), CPVC, RNC, PP, FRPP, FRP, HDPE, PE, PVDF, ABS, ABS Foam Core (ccABS) and XFR 15-50 PVC in both vented (DWV) and closed (electrical conduit and water supply) installations. SpecSeal® Series SCC Collars are suitable for use in all common constructions including concrete floors, concrete over steel deck, concrete walls, concrete block walls, gypsum board walls, as well as wood floor assemblies. Specifications The firestop system shall be a factory assembled firestop collar utilizing a molded, flexible intumescent insert. The intumescent insert shall provide a minimum of 30x free expansion and shall contain no water soluble expansion ingredients. The specified material shall be approved for a wide range of applications including PVC, PVC Foam Core (ccPVC), CPVC, RNC, PP, FRPP, FRP, HDPE, PE, PVDF, ABS, ABS Foam Core (ccABS) and XFR 15-50 PVC when used by itself or in combination with other products from the same manufacturer. The collar shall be UL Certified and tested to the requirements of ASTM E814 (UL1479) and CAN/ULC-S115 at 50 PA (0.20 in of water). Availble Sizes Shell Construction Expansion Begins 1.5" (38mm) 2" (51mm) 3" (76mm) 4" (102mm) 6" (152mm) Galvanized Steel 320°F (160°C) Volume Expansion 32 to 64x (free expansion) Specified Divisions In Service Division 7 078413 Penetration Firestopping Temperature Less than 120°F (49°C) Division 22 22 00 00 Plumbing Shelf Life No Limit Performance SpecSeal° Series SSC Collars are the basis for �ssiF�F Features & Benefits systems that meet the exacting criteria of ASTM o �i Rapid expansion - closes off burning E814 (UL1479) and CAN/ULC-S115 at 50 PA am �'' us pipes quickly (0.20 in of water). Systems have been tested forC ® US Intertek • Small profile - use it in all the tight spots all common forms of masonry construction and • Flexible & durable - no loose flakes (eye the most common plastic pipes with ratings up to three hours. Consult factory for information not hazards) available in UL Online Certifications Directory/UL Product iQTm as of this printing. • Water resistant - no water soluble or hygroscopic ingredients Limitations • Economical - lower installed cost This product has been designed to be safe with plastics. It has been used extensively and • High volume char - expands up to 60 successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in times these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. -� Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 2 STIh SpecSeal" Series SSC Firestop Collar • ZSFOD5152 24721 . Technologies Inc. P R O D U C T D A T A S H E E T SpecSeal° Series SSC Firestop Collar Maintenance INSPECTION: Installations should be inspected periodically for subsequent damage. Any damage should be repaired using SpecSeal° products per the original approved design. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product 10111 for complete listings. (Firestop Systems). Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information No unusual hazards are known or expected. Observe normal safety procedures during installation. Availability SpecSeal° Firestop Collars are available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800-992-1180 or visit www.stifirestop.com. Catalog Number UPC Number Size (UOM) Qty. Case Qty. Weight (Each) SSC150 730573031506 Firestop Collar for 1.5" (38 mm) Trade Size Plastic Pipe 1 6 0.33 Ibs (0.15 kg) SSC200 730573032008 Firestop Collar for 2.0" (51 mm) Trade Size Plastic Pipe 1 6 0.38 Ibs (0.17 kg) SSC300 730573033005 Firestop Collar for 3.0" (76 mm) Trade Size Plastic Pipe 1 6 0.74 Ibs (0.33 kg) SSC400 730573034002 Firestop Collar for 4.0" (102 mm) Trade Size Plastic Pipe 1 6 1.07 Ibs (0.49 kg) SSC600 730573036006 Firestop Collar for 6.0" (152 mm) Trade Size Plastic Pipe 1 2 5.04 Ibs (2.29 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECH N I CAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAL/WARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER �✓ Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 2 STISpecified SpecSeal" Series SSC Firestop Collar • ZSFOD5152 24721 ® Technologies Inc. P R O D U C T D A T A S H E E- SpecSeal° SSW BLU/BLU2 Intumescent Wrap Strip SpecSeal° Wrap Strips are highly flexible, elastomeric strips designed to firestop combustible penetrations in fire -rated floors, floor/ceilings, and walls. Convenient 12 ft (3.7 m) rolls, or individually sized strips facilitate installation and minimize waste. These products utilize STI's fast responding intumescent technology, providing very responsive and highly directionalized expansion. Rapid expansion provides quick closure for burning combustible penetrants. When exposed to temperatures in excess of 250°F (121 °C), the SpecSeal° Wrap Strip begins to expand (intumesce) rapidly to form a dense, highly insulative char. Free expansion varies according to the grade utilized (See Table A). Expansion continues up to temperatures of 1,000°F (538°C). Applications SpecSeal° Wrap Strips are used for firestopping combustible penetrants such as nonmetallic pipes or pipe insulation. Installations were developed for both "tuck -in" applications (where strips are secured around the penetrant and slid into the opening) and restraining collar assemblies (for surface mounting). For larger openings or complex penetrant configurations, systems were developed utilizing wrap strips in conjunction with other SpecSeal° products. SpecSeal° Wrap Strips are suitable for use in all common forms of construction including concrete floors, concrete over steel deck, concrete walls, concrete block walls, gypsum board/stud walls, and wood floor/ceiling assemblies. Specifications The wrap strip material shall be a highly flexible, intumescent material. The wrap strip shall contain no water soluble expansion ingredients and provide a minimum of 20x free expansion. The intumescent wrap strip shall be faced on each side with plastic. The specified material shall be approved for a wide range of applications including combustible and noncombustible penetrants when used by itself or in combination with other products from the same manufacturer. The wrap strip shall be UL Certified and tested to the requirements of ASTM E814 (UL 1479), CAN/ULC-S115. Specified Divisions Division 7 078413 Penetration Firestopping Division 22 22 00 00 Plumbing Performance SpecSeal° Wrap Strips are the basis for systems that meet the exacting criteria of ASTM E814 (UL 1479), CAN/ULC-S115. Systems were tested for all common forms of construction and penetrants with ratings up to 4 hours (dependent upon grade of wrap strip utilized). Limitations Features & Benefits • Rapid expansion - closes off burning penetrants faster • High volume char - significant expansion seals off opening • Water-resistant - no soluble or hygroscopic ingredients • economical -12' (3.7 m) rolls or precut strips means no piecing, less waste • Highly flexible - no foil, easier to install • Versatile - performer for a wide range of complex applications G�pSSIFjFO c U L us APPROVED This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. M Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 3 STLp SpecSeal`p' SSW BLU/BLU2 Intumescent Wrap Strip ZSFOD5343 24721 Technologies Inc. P R O D U C T D A T A S H E E T SpecSeal° SSW BLU/BLU2 Intumescent Wrap Strip Maintenance Inspection: Installations should be inspected periodically for subsequent damage. Any damage should be repaired using SpecSeal° products per the original approved design. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product 1O1-14 for complete listings. (Firestop Systems). Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information Consult Safety Data Sheet (SDS) for additional information on the safe handling and disposal of this material. Wash areas of skin contact with soap and water. Avoid contact with eyes. Catalog Number SSWBLU SSWBLU2 SSWBLU220 SSWBLU230 SSWBLU240 Color Blue Blue Blue Blue Blue Thickness 3/16" 1/8" 1/8" 1/8" 1/8" (4.8 mm) (3.2 mm) (3.2 mm) (3.2 mm) (3.2 mm) Width 2 2" 1-1/2" 3" 4" (51 mm) (51 mm) (38 mm) (76 mm) (102 mm) Length (min.) 12' 12' 8" 11-1/4" 14-3/4" (3.7 m) (3.7 m) (203 mm) (286 mm) (375 mm) Weight (min.) 2.87 Ibs (1.30 kg) 1.71 Ibs (0.77 kg) 0.08 Ibs (0.04 kg) 0.22 Ibs (0.10 kg) 0.37 Ibs (0.17 kg) Expansion System Two -Stage Single -Stage Single -Stage Single -Stage Single -Stage 1st Stage 250°F Expansion Begins (121°C) 320°F 320' F 320' F 320' F 2"d Stage 350°F (160°C) (160°C) (160°C) (160°C) (177°C) Volume Expansion 20x to 30x 30x to 60x 30x to 60x 30x to 60x 30x to 60x Mold & Fungus Growth 0 0 0 0 0 Rating (ASTM G21) In Service Temperature Less than 130°F Less than 1307 Less than 1307 Less than 1307 Less than 1307 (54°C) (54°C) (54°C) (54°C) (54°C) Storage Less than 130°F Less than 1307 Less than 1307 Less than 1307 Less than 130°F Temperature (54°C) (54°C) (54°C) (54°C) (54°C) Shelf Life No Limit No Limit No Limit No Limit No Limit Oven Aging No Change No Change No Change No Change No Change 140°F (60°C) 140°F (60°C) 140°F (60°C) 140°F (60°C) 140°F (60°C) Humidity Exposure No Change No Change No Change No Change No Change 60°C (98% R.H.) 60°C (98% R.H.) 60°C (98% R.H.) 60°C (98% R.H.) 60°C (98% R.H.) UL Accelerating Aging Pass Pass Pass Pass Pass & Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 3 ® Technologies STDh Inc. SpecSeal`p' SSW BLU/BLU2 Intumescent Wrap Strip ZSFOD5343 24721 P R O D U C T D A T A S H E E T SpecSeal° SSW BLU/BLU2 Intumescent Wrap Strip .• STRIP. Wrap Strip � J � J � J � J � J � J � J � J � J � J Type ; m ; m ; m ; m ; m m m m m m m m 00 m m 4th 5th Trade Pipe OD 6th 7th 8th Size (in) 1st Layer 2nd Layer 3rd Layer Layer Layer Layer Layer Layer Total RC (in.) 1.5 1.9 6.8 7.1 6.8 7.1 7.9 8.3 2.0 2.375 8.3 8.7 8.3 8.7 9.5 9.9 2.5 2.875 9.9 10.3 10.7 11.5 20.6 21.8 11.9 12.8 3.0 3.5 11.8 12.2 12.6 13.4 24.3 25.5 13.9 14.7 3.5 4.0 13.4 13.7 14.1 14.9 14.9 16.1 42.4 44.8 16.3 17.5 4.0 4.5 14.9 15.3 15.7 16.5 16.5 17.7 47.1 49.5 17.9 19.1 6.0 6.625 21.6 22.0 22.4 23.2 23.2 24.3 134.3' 139.0' 24.7' 26.0' 8.0 8.625 27.9 28.3 28.7 29.5 29.5 30.6 30.2 31.8 232.52 240.32 31.12 32.82 10.0 10.75 34.6 35.0 35.3 36.1 36.1 37.3 36.9 38.5 357.43 367.23 38.03 39.63 12.0 12.75 40.8 41.2 41.6 42.4 42.4 43.6 43.2 44.8 44.0 45.9 - - - - - - 530.14 544.94 45.34 47.34 14.0 14.0 44.8 45.2 45.6 46.3 46.3 47.5 47.1 48.7 47.9 49.9 48.7 51.1 49.5 52.2 50.0 53.4 950.55 985.85 52.05 55.45 Requires 2 stacks of 3 layers of wrap strip and WSC8 restraining collar (4" depth). 2 Requires 2 stacks of 41ayers of wrap strip and WSC8 restraining collar (4" depth). 3 Requires 2-1/2 stacks of 4 layers of wrap strip and WSC12 restraining collar (5" depth). Requires 2-1/2 stacks of 5 layers of wrap strip and WSC12 restraining collar (5" depth). Requires 2-1/2 stacks of 8 layers of wrap strip and two layers of WSC12 restraining collar (F depth). Availability SpecSeal° Wrap Strips are available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800-992-1180 or visit www.stifirestop.com. ORDERING INFORMATION Catalog Number UPC Number Size (UOM) Qty. Case Qty. Weight (Each) SSWBLU 730573037010 12' (3.7 m) x 2" (51 mm) x 3/16" (4.8 mm) roll 1 8 2.87 Ibs (1.30 kg) SSWBLU2 730573037119 12' (3.7 m) x 2" (51 mm) x 1/8" (3.2 mm) roll 1 8 1.71 Ibs (0.77 kg) SSWRC 730573037508 2" (50.8 mm) width 30 Gauge Galvanized sheet metal restraining 1 1 6.47 Ibs (2.93 kg) collar for <<-4" (102 mm) trade size pipe, 25' (7.6 m) roll WSC-8 730573037539 4" (101.6 mm)width preformed restraining collar 1 1 1.51 Ibs (0.68 kg) for 6" (152 mm) and 8" (204 mm) trade size pipe WSC-12 730573037607 5" (127 mm) width preformed restraining collar 1 1 3.15 Ibs (1.43 kg) for 8" (204 mm) trade size pipe and larger PRECUT SSWBLU220 730573037201 Precut strip sized for 2" (51 mm) trade size pipe 1 100 0.08 Ibs (0.04 kg) SSWBLU230 730573037300 Precut strip sized for 3" (76 mm) trade size pipe 1 100 0.22 Ibs (0.10 kg) SSWBLU240 730573037409 Precut strip sized for 4" (102 mm) trade size pipe 1 100 0.37 Ibs (0.17 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECHNICAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTORCOM/LEGAL/WARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER �✓ Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 3 of 3 STISpecified SpecSeal`p' SSW BLU/BLU2 Intumescent Wrap Strip • ZSFOD5343 24721 ® Technologies Inc. P R O D U C T D A T A S H E E T SpecSeal° SSW RED/RED2 Intumescent Wrap Strip SpecSeal° Wrap Strips are highly flexible, elastomeric strips designed to firestop combustible penetrations in fire -rated floors, floor/ceilings, and walls. Convenient 12 ft (3.7 m) rolls, or individually sized strips facilitate installation and minimize waste. These products utilize STI's fast responding intumescent technology, providing very responsive and highly directionalized expansion. Rapid expansion provides quick closure for burning combustible penetrants. When exposed to temperatures in excess of 250°F (121 °C), the SpecSeal° Wrap Strip begins to expand (intumesce) rapidly to form a dense, highly insulative char. Free expansion varies according to the grade utilized (See Table A). Expansion continues up to temperatures of 1,000°F (538°C). Applications SpecSeal° Wrap Strips are used for firestopping combustible penetrants such as nonmetallic pipes or pipe insulation. Installations were developed for both "tuck -in" applications (where strips are secured around the penetrant and slid into the opening) and restraining collar assemblies (for surface mounting). For larger openings or complex penetrant configurations, systems were developed utilizing wrap strips in conjunction with other SpecSeal° products. SpecSeal° Wrap Strips are suitable for use in all common forms of construction including concrete floors, concrete over steel deck, concrete walls, concrete block walls, gypsum board/stud walls, and wood floor/ceiling assemblies. Specifications The wrap strip material shall be a highly flexible, intumescent material. The wrap strip shall contain no water soluble expansion ingredients and provide a minimum of 16x free expansion. The intumescent wrap strip shall be faced on each side with plastic. The specified material shall be approved for a wide range of applications including combustible and noncombustible penetrants when used by itself or in combination with other products from the same manufacturer. The wrap strip shall be UL Certified and tested to the requirements of ASTM E814 (UL 1479), CAN/ULC-S115. Specified Divisions Division 7 078413 Penetration Firestopping Division 22 22 00 00 Plumbing Performance SpecSeal° Wrap Strips are the basis for systems that meet the exacting criteria of ASTM E814 (UL 1479), CAN/ULC-S115. Systems were tested for all common forms of construction and penetrants with ratings up to 4 hours (dependent upon grade of wrap strip utilized). Limitations Features & Benefits • Rapid expansion - closes off burning penetrants faster • High volume char - significant expansion seals off opening • Water-resistant - no soluble or hygroscopic ingredients • Economical -12' (3.7 m) rolls or precut strips means no piecing, less waste • Highly flexible - No foil, easier to install • Versatile - performer for a wide range of complex applications G�p,SSIFj�O (91 W c ~' us C ®� US Intertek This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. A& Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 3 STDh SpecSeal" Series RED/RED2 Intumescent Wrap Strip • ZSFOD5344 24721 ® Technologies Inc. P R O D U C T D A T A S H E E T SpecSeal° SSW RED/RED2 Intumescent Wrap Strip Maintenance Inspection: Installations should be inspected periodically for subsequent damage. Any damage should be repaired using SpecSeal° products per the original approved design. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product iOlm for complete listings. (Firestop Systems). Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information Consult Safety Data Sheet (SDS) for additional information on the safe handling and disposal of this material. Wash areas of skin contact with soap and water. Avoid contact with eyes. Catalog Number SSWRED SSWRED2 Color Red Red Thickness 1/4" (6.4 mm) 1/8" (3.2 mm) Width 1-1/2" (38 mm) 1-1/2" (38 mm) Length (min.) 12' (3.7 m) 12' (3.7 m) Weight (min.) 2.92 Ibs (1.33 kg) 1.33 Ibs (0.60 kg) Expansion System Two -Stage Single -Stage 1st Stage Expansion Begins 250°F (121 °C) 2nd Stage 320°F (160°C) 350°F (177°C) Volume Expansion 16x to 24x 24x to 48x Mold & Fungus Growth Rating 0 0 (ASTM G21) In Service Temperature Storage Temperature Less than 130°F (54°C) Less than 130°F (54°C) Less than 130°F Less than 130°F (54°C) (54°C) Shelf Life No Limit Oven Aging No Change 140°F (60°C) Humidity Exposure No Change 60°C (98% R.H.) UL Accelerating Aging Pass No Limit No Change 140°F (60°C) No Change 60°C (98% R.H.) Pass & Specified STD® Technologies Inc. Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 3 SpecSeall Series RED/RED2 Intumescent Wrap Strip • ZSFOD5344 24721 P R O D U C T D A T A S H E E T SpecSeal° SSW RED/RED2 Intumescent Wrap Strip WRAP STRIP AND RESTRAINING COLLAR REQUIREMENTS T Wrap Strip o 0 0 0 0 0 0 0 0 0 Type Cf �uj � LU � Of Trade Pipe OD 1st Layer 2nd Layer 3rd Layer Total RC Size (in.) (in.) 1.5 1.9 6.8 7.5 - - 6.8 7.5 7.9 8.7 2.0 2.375 8.3 9.1 - - - - 8.3 9.1 9.5 10.3 2.5 2.875 9.9 10.7 10.7 12.3 - 20.6 22.9 11.9 13.6 3.0 3.5 11.8 12.6 12.6 14.1 - - 24.3 26.7 13.9 15.5 3.5 4.0 13.4 14.1 14.1 15.7 14.9 17.3 42.4 47.1 16.3 18.7 4.0 4.5 14.9 15.7 15.7 17.3 16.5 18.8 47.1 51.8 17.9 20.3 6.0 6.625 21.6 22.4 22.4 24.0 23.2 25.5 134.31 143.71 24.71 27.21 Requires 2 stacks of 3 layers of wrap strip and WSC8RED restraining collar (T depth). Availability SpecSeal° Wrap Strips are available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800-992-1180 or visit www.stifirestop.com. Catalog Number UPC Number Size (UOM) Qty. Case Qty. Weight (Each) SSWRED 730573037027 12' (3.7 m) x 1-1/2" (38 mm) x 1/4" (6.4 mm) roll 1 10 2.92 Ibs (1.33 kg) SSWRED2 730573037126 12' (3.7 m) x 1-1/2" (38 mm) x 1/8" (3.2 mm) roll 1 8 1.33 Ibs (0.60 kg) 2" (50.8 mm) width 30 Gauge Galvanized sheet metal restraining 5.19 Ibs SSWRC2 730573037522 1 1 collar for <<-4" (102 mm) trade size pipe, 25' (7.6 m) roll (2.35 kg) 3" (76.2 mm) width preformed restraining collar 1.42 Ibs WSC-BRED 730573037546 1 1 for 6" (152 mm) trade size pipe (0.64 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECHNICAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAL/WARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER �✓ Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 3 of 3 STISpecified ® Technologies Inc. SpecSeall Series RED/RED2 Intumescent Wrap Strip • ZSFOD5344 24721 P R O D U C T D A T A S H E E T SpecSeal° SSB Firestop Pillows SpecSeal° Firestop Pillows are through -penetration firestop products resembling small cushions or soft bricks. These intumescent and highly resilient pillows are installed in openings by compressing and stacking into the opening in a brick -like fashion. SpecSeal° Firestop Pillows consist of a mineral fiber core material sealed with a water-resistant intumescent membrane. This coated core material is then heat -sealed in a tough, nonirritating, fire - retardant poly bag. Applications SpecSeal° Firestop Pillows are designed for firestopping medium to large openings containing various penetrating items such as pipes, conduits, cables, insulated metal pipes, bus ducts and HVAC ducts. Pillows are particularly well suited for applications involving data, communications, power or control cables, innerducts and cable trays. This method of sealing offers easy retrofitting of cable installations without the need to damage the firestop seal. Difficult applications such as one-sided shaft wall installations and other applications where access is restricted to one side of the assembly may be easily firestopped with this material. Specifications The firestopping system shall utilize an intumescent pillow heat sealed in a fire -retardant poly bag. The firestop pillow shall consist of a monolithic (one piece) core that is encapsulated on all sides by a flexible intumescent coating and shall not contain any loose fiber fill. The pillow shall be UL Certified and/ or FM Systems Approved and tested to the requirements of ASTM E814 (UL1479) and CAN/ULC-S115. Specified Divisions Division 7 078413 Penetration Firestopping Division 22 22 00 00 Plumbing Division 23 23 00 00 HVAC Division 26 26 00 00 Electrical Performance SSB Pillows are the basis for systems that meet the exacting criteria of ASTMam V FME814(UL1479)andCAN/ C o US APPROVED ULC-S115 as well as the time -temperature requirements of ASTM E119 (UL263). Tested systems will provide up to 4-hour rating for penetrations through gypsum board, concrete, CMU, or concrete tilt -up walls, as well as concrete or concrete over steel deck floors. Additional systems have been tested up to 3-hours in gypsum board walls. AIR LEAKAGE: Tests conducted by Underwriters Laboratories for air leakage at ambient and elevated temperatures (400°F (204°C)) indicate that properly installed pillows seal penetrations virtually airtight. Color Density Flammability* Compression** Air Leakage In Service Temperature Storage Temperature STC Rating (ASTM E 90-40) L Rating (UL1479 and CAN/ULC-S115) VOC Content*** Shelf Life Red 4 pcf (64 kg/cu m) V-0 25% to 33% Less than 1 CFM/sq. ft. Less than 130°F (54°C) Less than 130°F (54°C) 60 (Relates to specific construction) Less than 1 CFM/sq. ft (Pillows Only) 0.00 Ibs/gal (0.0 g/L) No Limit *Outer poly bag **As installed ***Per SCAQMD Rule 1168 (EPA Method 24) Features & Benefits • Intumescent - expands in all directions for a tough, tight seal • Reinstallable for easy retrofitting of cables • Lightweight for ease of installation • Easier wire screen requirements for large openings and 3 to 4 hour ratings • Heat -sealed poly bag - strong & durable • No sewn seams to unravel or tear, no irritating fiberglass • Monolithic encapsulated core, no loose fill • No special tools required • Superior air leakage ratings & Specified STD® Technologies Inc. Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 2 SpecSeal`°' SSB Firestop Pillows • ZSFOD5023 24721 P R O D U C T D A T A S H E E T SpecSeal° SSB Firestop Pillows Limitations This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. Maintenance INSPECTION: Installations should be inspected periodically for subsequent damage. Replace any damaged pillows. RETROFIT: Cables may be added or replaced in previously sealed openings by removing the mesh (if present) and removing and replacing pillows as required. DO NOT WEAVE CABLES THROUGH WIRE MESH! Doing so may interfere with subsequent efforts to add or remove cables and may pose a safety hazard. Reinstall pillows and putty as required and then replace wire mesh. NOTE: Removal of cables may require the installation of additional pillows to fill the void created by removing the cables. Inspect pillows for excess compression. SpecSeal Firestop Pillows are designed to be very durable and highly resilient. Excessive handling or abuse may permanently compress the pillows. If pillows are too thin to apply pressure within the seal when installed, replace thin pillows or add additional new pillows as required. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product i0lm for complete listings. (Firestop Systems). Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information Consult Safety Data Sheet (SDS) for additional information on the safe handling and disposal of this material. Avoid damaging poly outer bag. Do not use damaged pillows. Availability SpecSeal° Firestop Pillows are available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800-992-1180 or visit www.stifirestop.com. Catalog Number UPC Number Size (UOM) Qty. Case Qty. Weight (Each) SS1314 730573061404 1" (25 mm) x 4" (101 mm) x 9" (225 mm) 1 20 0.19 Ibs (0.09 kg) SSB24 730573062401 2" (50 mm) x 4" (101 mm) x 9" (225 mm) 1 10 0.31 Ibs (0.14 kg) SSB26 730573062609 2" (50 x mm) x 6" (152 mm) x 9" (225 mm) 1 22 0.39 Ibs (0.18 kg) SSB36 730573063606 3" (76 x mm) x 6" (152 mm) x 9" (225 mm) 1 16 0.55 Ibs (0.25 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECH N I CAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAUWARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER & I fI Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 2 Specified STD® Technologies Inc. SpecSeal SSB Firestop Pillows • ZSFOD5023 24721 P R O D U C T D A T A S H E E T SpecSeal°SSP Putty & Putty Pads SpecSeal° SSP Putty is a non -hardening, intumescent compound designed to seal through -penetrations as well as certain membrane penetrations (med-gas valve box, tub & shower valve, clean -out tee) against the spread of fire, smoke and hot gasses. SpecSeal° Putty expands up to eight times its original size when exposed to high temperatures or flames. Requiring no tools, SpecSeal° SSP Putty is soft and pliable making it easy to install by hand packing into openings. Its aggressive adhesion makes it suitable for use with all common construction materials as well as cable jacketing and pipes. SpecSeal° Putty remains soft and easy to reuse or retrofit. SpecSeal° SSP Putty Pads provide this same level of protection in a release lined pad for easy application to electrical boxes or other penetrants. The pad is conveniently sized to fit a typical 1-1/2 in (38 mm) deep 4S box with no cutting or piecing required. Faced on both sides with a convenient poly liner, SpecSeal° Putty Pads are easily applied with no mess or excessive residue. Applications SpecSeal° SSP Putty and Putty Pads are used to seal through -penetrations as well as construction gaps and blank openings. SpecSeal° Putty Pads are used to seal around electrical boxes to reduce sound transmission (see Technical Update) and increase fire resistance. These pads also provide a metered method of application when sealing through -penetrations and in some applications, are used to provide a cushion to allow movement due to settling, expansion and contraction, or vibration. Specifications The firestopping putty shall be a one -part, two -stage intumescent, non -hardening compound. The putty, when exposed to high heat or flame shall be capable of expanding a minimum of five times. Range of continuing expansion shall be from 2307 to less than 1,000°F (110°C to less than 538°C). The putty shall be soft and pliable with aggressive adhesion and shall not contain any water-soluble intumescent ingredients. The putty shall be UL Certified and/or FM Systems Approved and tested to the requirements of ASTM E814 (UL1479), CAN/ULC-S115 and UL263 (ASTM E119, NFPA 251). Specified Divisions Division 7 078413 Penetration Firestopping Division 26 26 00 00 Electrical Division 27 27 00 00 Communications Performance SpecSeal° Putty and Putty G�pSSIFjFo Pads have been tested to U FM ASTM E814 UL1479 , CAN/as C O us ( ) APPROVED ULC-S115 and to UL263 (ASTM E119, NFPA251) and are Certified for up to 2 hours as a Wall Opening Protective Material for use with both metallic and nonmetallic outlet or switch boxes installed in gypsum wallboard assemblies (steel and wood stud assemblies). Boxes protected with SpecSeal° Putty Pads have been successfully tested with box spacing reduced to less than 16 in (406 mm). Color Odor Density Solids Content Mold & Fungus Growth Rating (ASTM G21) Volume Expansion Expansion Begins In Service Temperature Red None 1.45 kg/L (12.08 lb/gal) 100% Greater than 500% (free expansion) 230°F (110°C) 10°F (-23°C) to 120°F (49°C) Installation Temperature Less than 100°F (38°C) Storage Temperature Less than 100°F (38°C) STC Rating 62 (Relates to Specific (ASTM E 90-04/ASTM C919) Construction) VOC* 0 g/L Shelf Life No Limit *Per SCAQMD Rule 1168 (EPA Method 24) Features & Benefits • Non -hardening = easy retrofit • Endothermic fillers absorb heat & release water • Highly adhesive formula - stays put, allows movement • Soft & pliable for easy installation • No water-soluble expansion ingredients means better water resistance • Excellent sound attenuation properties • Reduces noise transmission Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 2 STDh SpecSeal" SSP Putty Pads • ZSFOD5010 24721 ® Technologies Inc. P R O D U C T D A T A S H E E T SpecSeal°SSP Putty & Putty Pads Limitations This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. Maintenance Installations should be inspected periodically for subsequent damage. Any damage should be repaired using SpecSeal° products per the original approved design. System Selection To find your firestop system or create a submittal, visit https://systems.stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product iOlm for complete listings. (Firestop Systems). Clean Up Remove excess material from all contact surfaces immediately. Clean hands or skin using a waterless hand cleaner. When using water -emulsifiable soaps, apply soap and work over areas of skin contact prior to applying water. Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information Consult Safety Data Sheet for additional information on the safe handling and disposal of this material. Wash areas of skin contact with soap and water. Avoid contact with eyes. DO NOT APPLY TO EXPOSED ELECTRICAL CONDUCTORS. Availability SpecSeal° Series SSP Putty is available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800-992-1180 or visit www.stifirestop.com. Catalog Number UPC Number Size (EOM) Qty. Case Qty. Weight (Each) SSP100 730573021002 36 in' (0.6 liter) bar 1 6 2.22 Ibs (1.01 kg) SSP28 730573021019 24 in3 (0.4liter) bar 1 1 1.42 Ibs (0.64 kg) SSP4S 730573022009 7.25" x 7.25" x 3/16" (184 x 184 x 4.8 mm) pad 1 20 0.64 Ibs (0.29 kg) SSP9S 730573023006 9.00" x 9.00" x 3/16" (229 x 229 x 4.8 mm) pad 1 20 0.85 Ibs (0.39 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECHNICAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED, IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAL/WARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER �✓ Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 2 of 2 Specified SpecSeal` SSP Putty Pads • ZSFOD5010 24721 STI® Technologies Inc. P R O D U C T D A T A S H E E T SpecSeal° FP Intumescent Firestop Plug SpecSeal° FP Intumescent Firestop Plugs are soft and supple, foam plugs molded from polyurethane. Plugs are conveniently sized to fit 2 in (51 mm) or 4 in (102 mm) diameter openings or sleeves fabricated from electrical metallic tubing (EMT). The intumescent plugs expand when exposed to heat to quickly close off around combustible jacketed cables. The SpecSeal° FP500D Firestop Plugs are conveniently sized to fit 5 in. (127 mm) diameter openings or steel sleeves. When exposed to heat they quickly close off 1-1 /2 in. or 2 in. Trade Size ABS, PVC, Steel or Iron drain pipes. Applications SpecSeal° FP Intumescent Firestop Plugs are designed for temporary or permanent sealing of single or grouped cables, metallic and non-metallic pipe penetrations, and blank openings through common construction such as concrete or gypsum board. Specifications The firestopping system shall utilize an intumescent foam plug having a nominal density of 19 pcf. The plug shall expand a minimum 10 times. The one-piece product shall be sized to fit the inside diameter of the opening or sleeve. The plug shall be UL Classified and tested to the requirements of ASTM E814 (UL1479) and CAN/ULC-S115. Specified Divisions Division 7 078413 Penetration Firestopping Division 22 22 00 00 Firestopping for Plumbing Division 26 26 00 00 Electrical Division 27 27 00 00 Communications Performance SpecSeal° FP Intumescent Firestop G�pSSIFjFo Plugs were tested to meet the exacting U criteria of ASTM E814 (UL1479) and alCuS CAN/ULC-S115. Tested systems were developed providing up to 2 hour ratings for penetrations of cables and blank openings through concrete and gypsum board/stud wall assemblies. SpecSeal° FP500D Intumescent Firestop Plugs have been tested in Firestop Systems. Tested systems were developed providing up to 2 hour ratings for penetrations of nonmetallic and metallic drain pipes in 5 in. diameter openings through concrete floors. 11 1 jm� Features & Benefits Intumescent - expands in all directions Reinstallable - easy retrofitting of cables Easy to install - no special tools required Soft and resilient foam - conforms to cable & pipe surfaces Paintable - can be painted to match surroundings A& Specified Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com 1 of 2 STDp SpecSeal`w FP Intumescent Firestop Plug ZSFOD5125 24721 ® Technologies Inc. P R O D U C T D A T A S H E E T SpecSeal° FP Intumescent Firestop Plug Limitations This product has been designed to be safe with plastics. It has been used extensively and successfully with various types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials, however, make it impossible to guarantee compatibility. STI strongly recommends that the user consults with the pipe, tubing, or cable manufacturer in question regarding any known sensitivities or potential restrictions before applying this product. Maintenance Installations should be inspected periodically for subsequent damage. Replace any damaged foam plugs. System Selection To find your firestop system or create a submittal, visit httpsWsystems. stifirestop.com/ to use System Search & Submittal Builder. You may also visit the UL Online Certifications Directory/UL Product iO!M for complete listings. (Firestop Systems). Color Red Density 19 pcf (304 kg/m3) 2" — 0.20 lb (91 g) Weight 4" — 0.50 lb (227 g) 5" — 0.50 lb (227 g) Expansion Begins 350°F (176°C) Volume Expansion 10x In Service Temperature Less than 130°F (54°C) Storage Temperature Less than 130°F (54°C) VOC Content N/A Shelf Life No Limit Technical Service Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL System designs suitable for submittal or specification purposes are available on request. A complete library of technical information is provided at the company's website www.stifirestop.com including Safety Data Sheets (SDS's). Precautionary Information No unusual hazards are known or expected. Observe normal safety procedures during installation. Availability SpecSeal° FP Intumescent Firestop Plugs are available from Specified Technologies Inc. (STI) authorized distributors. For additional purchasing and technical information or for the names and locations of the nearest representative and/or distributor, regarding this and other Specified Technology products, please call 1-800-992-1180 or visit www.stifirestop.com. Catalog Number UPC Number Description (UOM) Qty. Case Qty. Weight (Each) FP200 730573072029 Firestop Plug sized for 2 in. (51 mm) opening/sleeve 1 10 0.27 Ibs (0.12 kg) FP400 730573072043 Firestop Plug sized for 4 in. (102 mm) opening/sleeve 1 10 0.61 Ibs (0.28 kg) Firestop Plug sized for 5 in. (127 mm) opening/sleeve. 0.59 Ibs FP500D 730573072059 1 10 For sealing drain pipe penetrations in concrete floors only (0.27 kg) IMPORTANT NOTICE: ALL STATEMENTS, TECH N I CAL INFORMATION, AND RECOMMENDATIONS CONTAINED HEREIN ARE BASED UPON TESTING BELIEVED TO BE RELIABLE, BUT THE ACCURACY AND COMPLETENESS THEREOF IS NOT GUARANTEED. IV STI TYPICALLY WARRANTIES ITS PRODUCTS FOR ONE FULL YEAR. FOR COMPLETE DETAILS OF OUR STANDARD WARRANTY, PLEASE VISIT WWW.STIFIRESTOP.COM/LEGAUWARRANTY MADE IN THE USA - ©2021 SPECIFIED TECHNOLOGIES INC. MEMBER �✓ Specified Technologies Inc. • Somerville, NJ 08876 • Technical Service 1-800-992-1180 • www.stifirestop.com SpecSeal`w FP Intumescent Firestop Plug • ZSFOD5125 24721 2 of 2 STISpecified ® Technologies Inc. ROXUL SAFE° Product Description & Application Fire Safing Insulation ROXUL SAFE® is semi -rigid, mineral wool insulation approved for use in fire rated joints, through penetrations and perimeter fire containment systems. Performance Test Standard Compliance Mineral Fiber Block and Board Thermal Insulation Type IVA Compliant ASTM C612 MEA Approval, New York City Approval 339-97-M Reaction to Fire Flame spread index = 0 ; Smoke developed index = 0 ASTM E84 (UL 723) Flame spread index = 0 ; Smoke developed index = 0 CAN/ULC S102 Determination of Non Combustibility of Building Materials - Non Combustible CAN/ULC S114 Test for Non -Combustibility - Non Combustible ASTM E136 Fire Tests of Firestop Systems CAN/ULC S115 Fire Tests of Penetration Firestop Systems ASTM E814 (UL 1479) Tests for Fire Resistance of Building Joint Systems UL 2079 Perimeter Fire Barrier Systems ASTM E2307/E119 Smoulder Resistance - 0.01 % CAN/ULC S129 Consult UL, ULC and Intertek Directories for fire rated designs Density Actual Density - 4.5 Ibs/ft' (72 kg/m') ASTM C303 Corrosion Resistance Stress Corrosion Cracking Tendency of Austenitic Stainless Steel - Passed ASTM C795 Corrosion of Steel - Passed ASTM C665 Reaction to Moisture Moisture Sorption - 0.04% ASTM C1104 Determination of Fungi Resistance - Passed ASTM C1338 Thickness Product is available in 2", 3" and 4" (50.8mm, 76.2mm and 101.6mm) Dimensions 24"x48" (610mm x 1219mm) ��o Intertek LISTED NOTE: *Mast Format 1995 Edition **Master Format 2004 Edition. As ROXUL Inc has no control over installation design and workmanship, accessory materials or application Issued 09-02-16 conditions, ROXUL Inc. does not warranty the performance or results of any installation containing ROXUL Inc's products. ROXUL Inc's overall liability and the remedies available Supersedes 04-01-16 are limited by the general terms and conditions of sale. This warranty is in lieu of all other warranties and conditions expressed or implied, including the warranties of merchantability and fitness for a particular purpose. �N STI SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME Address: Business Phone: Emergency Phone: SpecSeal° ES Elastomeric Firestop Sealant Firestop and Sound Transmission None Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of Competent Person for Information on SDS: techserv(@stifirestop.com NOTE: ALL United States Occupational Safety and Health Administration Standard (29 CFR 1910.1200), U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7250 required information is included in appropriate sections based on the U.S. ANSI Z400.1-2010 format. This product has been classified in accordance with the hazard criteria of the countries listed above. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND JAPANESE JIS Z7253 LABELING AND CLASSIFICATION: This product has been classified per UN GHS Standards under U.S., Japanese and other applicable regulations that require Global Harmonization compliance. Classification: Carcinogenic Category 1, Eye Irritation Category 2A, Specific Target Organ Toxicity (Inhalation -Respiratory Irritation) Single Exposure Category 3 Signal Word: Warning Hazard Statements: H351: This product contains trace amounts of a suspected human carcinogen by inhalation: however, this hazard is not expected to be significant due to viscosity and consistency of the mixture. H319: Causes serious eye irritation. H335: May cause respiratory irritation. Precautionary Statements: Prevention: P201: Obtain special instructions before use. P202: Do not handle until all safety precautions have been read and understood. P261: Avoid breathing vapors, fume. P271: Use only in a well -ventilated area. P280: Wear protective gloves, clothing, eye protection and face protection. P284: Wear respiratory protection. Response: P308 + P313: IF exposed or concerned: Get medical advice/attention. P305 + P351 + P338: IF IN EYES: Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do. P337 + P313: If eye irritation persists: Get medical advice/attention. P304 + P340: If inhaled, remove victim to fresh air and keep at rest in a position comfortable for breathing. P312: Call a POISON CENTER or doctor if you feel unwell. P321: Specific treatment (remove from exposure and treat symptoms). Storage: P403 + P233 + P405: Store in a well -ventilated place. Keep container tightly closed. Store locked up. Disposal: P501: Dispose of contents/containers in accordance with all local, regional, national and international regulations. Hazard Symbols: GHS07, GHS08 f > 4> KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: Classified in accordance with ISHA Notice 2009-68. Under ISHA, no differences in classification are applicable. 3. COMPOSITION and INFORMATION ON INGREDIENTS Hazardous Components: Chemical Name CAS# Chinese IECSC Inventory Japanese ENCS# Korean ECL# wT� LABEL ELEMENTS GHS & Japanese JIS Z7253 Classification Korean ISHA Classification GHS Hazard Codes SELF CLASSIFICATION Titanium Dioxide 13463-67-7 Listed 1-558 KE-33390 0.05- GHS & JAPANESE JIS Z7253, KOREAN ISHA: 0.3 % Classification: Carcinogenic Cat. 2 Hazard Codes: H351 SELF CLASSIFICATION GHS & JAPANESE JIS Z7253, KOREAN ISHA: Crystalline Silica 14808-60-7 Listed 1-548 KE-29983 0.5- Classification: Carcinogenic Cat. 1, STOT (Inhalation -Lungs) RE Cat. 0 9� 2 Hazard Statement Codes: H350, H373 SDS0009 - SPECSEAO ES ELASTOMERIC FIRESTOP SEALANT SDS EFFECTIVE DATE: NOVEMBER 10, 2020 4. FIRST -AID MEASURES Skin Exposure: If adverse skin effects occur, discontinue use and flush contaminated area. Seek medical attention if adverse effect occurs after flushing. Inhalation: If fumes or vapors are inhaled, remove victim to fresh air. If necessary, use artificial respiration to support vital functions. Seek medical attention if adverse effect continues after removal to fresh air. Eve Exposure: If this product contaminates the eyes, rinse eyes under gently running water. Ingestion: If this product is swallowed, CALL PHYSICIAN OR POISON CONTROL CENTER FOR MOST CURRENT INFORMATION. If professional advice is not available, DO NOT INDUCE VOMITING. Never induce vomiting or give diluents (milk or water) to someone who is unconscious, having convulsions, or unable to swallow. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Pre-existing respiratory disorders may be aggravated by overexposures to this product. INDICATION OF IMMEDIATE MEDICAL ATTENTION AND SPECIAL TREATMENT IF NEEDED: Treat symptoms and eliminate exposure. 5. FIRE -FIGHTING MEASURES FLASH POINT: 302 °C (576 °F) AUTOIGNITION TEMPERATURE: Not available. FLAMMABLE LIMITS (in air by volume, %): Not applicable. FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. When involved in a fire, this material may decompose and produce irritating vapors and toxic gases Explosion Sensitivity to Mechanical Impact: Not sensitive. Explosion Sensitivity to Static Discharge: Not sensitive. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: No Special protective actions for fire-fighters are anticipated. 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Uncontrolled releases should be responded to by trained personnel using pre -planned procedures. Proper protective equipment should be used. Call CHEMTREC (1-800- 424-9300) for emergency assistance. Or if in Canada, call CANUTEC (613-996-6666). PERSONAL PROTECTIVE EQUIPMENT: Proper protective equipment should be used. Small Spills: Wear rubber gloves, splash goggles, and appropriate body protection. NFPA RATING Large Spills: Minimum Personal Protective Equipment should be rubber gloves, rubber boots, face shield �crmnaABwry METHODS FOR CLEAN-UP AND CONTAINMENT: Spills of this product present minimal hazard. 0 Small Spills: Small releases can be carefully swept up or cleaned up using a damp sponge or polypads. HEATH 2 O INSr AB uTY Large Spills: Access to the spill area should be restricted. For large spills, dike or otherwise contain spill and sweep -up or vacuum with non -sparking vacuum. All Spills: Place all spill residue in a double plastic bag or other containment and seal. Close off sewers and take other measures to protect human health and the environment as necessary. Rinse area with soap and water solution and follow with a water rinse.. ENVIRONMENTAL PRECAUTIONS: Avoid release to the environment. �TH� Hazard Scale: 0 = Minimal 1 = Slight 2 = Moderate 3 = Serious 4 = Severe 7. HANDLING and USE PRECAUTIONS FOR SAFE HANDLING: As with all chemicals, avoid getting this material ON YOU or IN YOU. Do not eat, drink, smoke, or apply cosmetics while handling this product. Wash hands thoroughly after handling this product or containers of this product. Avoid breathing fumes or vapors generated by this product. Use in a well -ventilated location. CONDITIONS FOR SAFE STORAGE: Store containers in a cool, dry location, away from direct sunlight, sources of intense heat. Do not store above 55°C (131 °F) SPECIFIC END USE(S): This product is for use as a sealant. Follow all industry standards for use of this product. SDS0009 - SPECSEAL® ES ELASTOMERIC FIRESTOP SEALANT SIDS EFFECTIVE DATE: NOVEMBER 10, 2020 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: Ventilation and Engineering Controls: Use with adequate ventilation to ensure exposure levels are maintained below the limits provided below (if applicable). Exhaust directly to the outside, taking necessary precautions for environmental protection. Workplace Exposure Limits/Control Parameters: CHEMICAL CAS # EXPOSURE LIMITS IN AIR NAME ACGIH-TLVs OSHA-PELs NIOSH-RELs NOSH OTHER TWA I STEL TWA STEL TWA STEL IDLH mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 Crystalline 14808-60-7 0.025 NE 0.05 mg/m3(resp. NE 0.05 (resp. NE 50 Carcinogen: IARC-1, MAK-1 Silica (Quartz) (resp. dust) dust) (respirable fraction), NOSH- fract.) Ca, NTP-K (respirable fraction), TLV-A2 Titanium 13463-67-7 10 NE 15 (total dust) NE See Pocket Guide 5000 Carcinogen: IARC-2B, MAK- Dioxide App. A (Ca) 3A, NIOSH-Ca; TLV-A3 NE = Not Established. See Section 16 for Definitions of Other Terms Used International Occupational Exposure Limits: Currently, the following additional exposure limit values have been established by various countries for the components of this mixture. More current limits may be available; individual countries should be consulted to determine if newer limits are available. CRYSTALLINE SILICA: TITANIUM DIOXIDE: Australia: TWA = 0.1 mg/m3, JUL 2008 ARAB Republic of Egypt: TWA = 15 mg/m3, JAN 1993 Belgium: TWA = 0.1 mg/m3 (resp. dust), MAR 2002 Austria: MAK-TMW = 5 mg/m3, KZW = 10 mg/m3, resp, 2007 Denmark: TWA = 0.1 mg/m3 (respirable), carc, MAY 2011 Belgium: TWA = 10 mg/m3, MAR 2002 Denmark: TWA = 0.1 mg/m3 (resp.), carc, MAY2011 Denmark: TWA = 6 mg(Ti)/m3, MAY 2011 Denmark: TWA = 0.3 mg/m3 (total), MAY 2011 France: VME = 10 mg/m3, FEB 2006 Finland: TWA = 0.05 mg/m3, resp. dust, SEP 2009 Germany: MAK = 1.5 mg/m3 (respirable), 2005 France: VME = 0.1 mg/m3, (resp), FEB 2006 Iceland: TWA = 6 mg(Ti)/m3, NOV 2011 Iceland: TWA = 0.1 mg/m3 (resp. dust), NOV 2011 Japan: OEL = 1 mg/m3 (resp. dust), 4 mg/m3 (total dust), MAY 2009 Japan: OEL-C = 0.03 mg/m3 (respirable), APR 2007 Korea: TWA = 10 mg/m3, 2006 Korea: TWA = 0.1 mg/m3, 2006 Mexico: TWA = 10 mg(Ti)/m3; STEL = 20 mg(Ti)/m3, 2004 Mexico: TWA = 0.1 mg/m3 (respirable), 2004 The Netherlands: MAC-TGG = 10 mg/m3, 2003 The Netherlands: MAC-TGG = 0.075 mg/m3, 2003 New Zealand: TWA = 10 mg/m3 (inspirable dust), JAN 2002 New Zealand: TWA = 0.2 mg/m3 (respirable dust), JAN 2002 Norway: TWA = 5 mg/m3, JAN 1999 Norway: TWA = 0.1 mg/m3 (resp. dust), JAN 1999 Peru: TWA = 10 mg/m3, JUL 2005 Norway: TWA = 0.3 mg/m3 (total dust), JAN 1999 Poland: MAC(TWA) = 10 mg(Ti)/m3, MAC(STEL) = 30 mg(Ti)/m3, JAN 1999 Peru: TWA = 0.05 mg/m3, JUL 2005 Russia: TWA = 10 mg/m3, JUN 2003 Russia: TWA = 1 mg/m3, STEL = 3 mg/m3, JUN 2003 Sweden: TWA = 5 mg/m3 (total dust), JUN 2005 Sweden: TWA = 0.1 mg/m3 (resp. dust), JUN 2005 Switzerland: MAK-W = 3 mg/m3, DEC 2006 Switzerland: MAK-W = 0.15 mg/m3, DEC 2006 Turkey: TWA = 15 mg/m3, JAN 1993 Thailand: TWA = 10 mg/m3 (resp. dust), JAN 1993 United Kingdom: TWA = 10 mg/m3 (inhal. dust), OCT 2007 Thailand: TWA = 30 mg/m3 (total dust), JAN 1993 United Kingdom: TWA = 4 mg/m3 (resp. dust), OCT 2007 United Kingdom: TWA = 0.1 mg/m3 (resp. dust), OCT 2007 In Argentina, Bulgaria, Colombia, Jordan, Singapore, Vietnam check ACGIH TLV In Argentina, Bulgaria, Colombia, Jordan, Singapore, Vietnam check ACGIH TLV PROTECTIVE EQUIPMENT: The following information on appropriate Personal Protective Equipment is provided to assist employers in complying with OSHA regulations found in 29 CFR Subpart I (beginning at 1910.132, including U.S. Federal OSHA Respiratory Protection (29 CFR 1910.134), OSHA Eye Protection 29 CFR 1910.133, OSHA Hard Protection 29 CFR 1910.138, OSHA Foot Protection 29 CFR 1910.136 and OSHA Body Protection 29 CFR1910.132), equivalent standards of Canada (including CSA Respiratory Standard Z94.4-02, Z94.3-M 1982, Industrial Eye and Face Protectors and CSA Standard Z195-02, Protective Footwear), or standards of Japan (including JIS T 8116:2005 for glove selection, JIS T 8150:2006 for respiratory PPE, JIS T 8147:2003 for eye protectors, and JIS T 8030:2005 for protective clothing). Please reference applicable regulations and standards for relevant details. Respiratory Protection: Maintain airborne contaminant concentrations below exposure limits listed above. For materials without listed exposure limits, minimize respiratory exposure. If necessary, use only respiratory protection authorized under appropriate regulations. Eve Protection: Wear splash goggles or safety glasses as appropriate for the task. Hand Protection: During manufacture or other similar operations, wear the appropriate hand protection for the process. Skin Protection: Use appropriate protective clothing. If necessary, refer to the U.S. OSHA Technical Manual (Section VII: Personal Protective Equipment) or other appropriate regulations. Full -body chemical protective clothing is recommended for emergency response procedures. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Paste. MOLECULAR FORMULA: Mixture. ODOR: Mild acrylic. FLAMMABLE LIMITS (in air by volume, %): Not applicable DECOMPOSITION TEMPERATURE: Not available. AUTOIGNITION TEMPERATURE: Not available. FREEZING/MELTING POINT: Not available. COLOR: Blue or Red MOLECULAR WEIGHT: Mixture. ODOR THRESHOLD: Not available. OXIDIZING PROPERTIES: Not applicable. PERCENT VOLATILE: 17-20 FLASH POINT: Not available. BOILING POINT: 100-105°C (212-221 °F) SDS0009 - SPECSEAL® ES ELASTOMERIC FIRESTOP SEALANT SIDS EFFECTIVE DATE: NOVEMBER 10, 2020 9. PHYSICAL and CHEMICAL PROPERTIES (Continued) VAPOR PRESSURE: Not available. SPECIFIC GRAVITY (water = 1): 1.2-20 gri VAPOR DENSITY (air = 1): Not available. CARB VOC: 3.04 wt % (calc.) EVAPORATION RATE (n-BuAc = 1): > 1 SCAQMD (U.S. EPA Method 24): 44 gm/L SOLUBILITY IN WATER: Dissolves when wet; insoluble when cured. SOLUBILITY IN SOLVENTS: Not available. COEFFICIENT WATER/OIL DISTRIBUTION: Not established. pH: Not available. HOW TO DETECT THIS SUBSTANCE (warningproperties in event of accidental release): The appearance may be characteristics to distinguish a release of this product. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is stable when properly stored at normal temperature and pressures (see Section 7, Handling and Storage). DECOMPOSITION PRODUCTS: Combustion: If exposed to extremely high temperatures, thermal decomposition may generate irritating fumes and toxic gases (e.g., calcium, carbon, magnesium and titanium oxides, and acrylic monomers). Hydrolysis: None known. MATERIALS WITH WHICH SUBSTANCE IS INCOMPATIBLE: This product is incompatible with strong oxidizers. POSSIBILITY OF HAZARDOUS POLYMERIZATION OR REACTION: Will not occur. CONDITIONS TO AVOID: Avoid exposure to or contact with extreme temperatures and incompatible chemicals. 11. TOXICOLOGICAL INFORMATION SYMPTOMS OF EXPOSURE BY ROUTE OF EXPOSURE: The health hazard information provided below is pertinent to employees using this product in an occupational setting. The following paragraphs describe the symptoms of exposure by route of exposure. Inhalation: Inhalation of fumes or vapors may cause irritation of the nose, throat, and lungs and cause coughing. Removal to fresh air should relieve symptoms. This product contains trace amounts of a suspected human carcinogen by inhalation; however, this hazard is not expected to be significant due to viscosity and consistency of the mixture. Contact with Skin or Eves: Direct eye contact may cause irritation, redness, and tearing from mechanical irritation. Prolonged or repeated skin exposures may cause dermatitis (dry red skin). Skin Absorption: Components are not known to be absorbed through intact skin. Ingestion: Ingestion is not a significant route of occupational exposure and is unlikely to occur. If this product is swallowed, irritation of the mouth, throat, esophagus and other tissues of the digestive system may occur. Symptoms of ingestion may include nausea, vomiting, and diarrhea. Infection: Accidental injection of this product, via laceration or puncture by a contaminated object can cause redness at the site of injection. Animal data for the Crystalline Silica component indicate that it may cause carcinogenic effects by this route of exposure. HEALTH EFFECTS OR RISKS FROM EXPOSURE: Exposure to this product may cause the following health effects: Acute: Inhalation of fumes or vapors may cause irritation of respiratory system. Eye contact may cause mechanical irritation. Chronic: Prolonged or repeated skin exposure may cause dermatitis (dry red skin). This product contains trace amounts of a suspected human carcinogen by inhalation; however, this hazard is not expected to be significant due to viscosity and consistency of the mixture. TARGET ORGANS: Acute: Skin, eyes, respiratory system. Chronic: Skin. TOXICITY DATA: Currently, the following toxicological data are available for components of 1 % or more concentration. Due to the large amount of data available Titanium Dioxide and Crystalline Silica components, only human data, LD50 Oral Rat and Mouse, LD50 Skin Rabbit and Rat, LC50 Inhalation Rat and Mouse, carcinogenic and mutation data are provided. IRRITANCY OF PRODUCT: Inhalation of fumes or vapors may cause respiratory irritation. Eye contact may cause irritation. Prolonged skin contact may cause irritation. SENSITIZATION OF PRODUCT: This product is not currently known to cause allergic skin or respiratory reaction. CARCINOGENIC POTENTIAL OF COMPONENTS: Components of this product are listed by agencies tracking the carcinogenic potential of chemical compounds, as follows: CRYSTALLINE SILICA: ACGIH-TLV-A2 (Suspected Human Carcinogen); ARC-1 (Carcinogenic to Humans); MAK-1 (Substances that Cause Cancer in Man and Can Be Assumed to Make a Significant Contribution to Cancer Risk); NIOSH- Ca (Potential Occupational Carcinogen with No Further Categorization); NTP-K (Known to Be a Human Carcinogen) TITANIUM DIOXIDE: ACGIH TLV-A3 (Confirmed Animal Carcinogen); IARC-3 (Unclassifiable as to Carcinogenicity in Humans); NIOSH-Ca (Potential Occupational Carcinogen, with No Further Categorization) The remaining components are not found on the following lists: U.S. EPA, U.S. NTP, U.S. OSHA, U.S. NIOSH, GERMAN MAK, IARC, or ACGIH and therefore is neither considered to be nor suspected to be a cancer -causing agent by these agencies. REPRODUCTIVE TOXICITY INFORMATION: Components of this product have no reported mutagenic, embryotoxic, teratogenic or reproductive toxicity. ACGIH BIOLOGICAL EXPOSURE INDICES (BEls): Currently, there are no ACGIH Biological Exposure Indices (BEls) determined for this material. DEGREE OF EFFECT TO THE HEALTH OF THE POLLUTING AGENT OF ENVIRONMENT OF WORK (per Mexican NOM-010 STPS-1999): 0 HAZARDOUS MATERIAL IDENTIFICATION SYSTEM HEALTH HAZARD (BLUE) 2' FLAMMABILITY HAZARD (RED) 0 PHYSICAL HAZARD (YELLOW) 0 PROTECTIVE EQUIPMENT EYES RESPIRATORY HANDS BODY SEE SECTIONS SEE SECTIONS For Routine Industrial Use and Handling Applications Hazard Scale: 0 = Minimal 1 = Slight 2 = Moderate 3 = Serious 4 = Severe ' = Chronic hazard SDS0009 - SPECSEAL® ES ELASTOMERIC FIRESTOP SEALANT SDS EFFECTIVE DATE: NOVEMBER 10, 2020 12. ECOLOGICAL INFORMATION ALL WORK PRACTICES MUST BE AIMED AT ELIMINATING ENVIRONMENTAL CONTAMINATION. MOBILITY: This product has not been tested for mobility in soil. PERSISTENCE AND BIODEGRADABILITY: This product has not been tested for persistence or biodegradability. The mineral components are not expected to biodegrade to great extent. BIO-ACCUMULATION POTENTIAL: This product has not been tested for bio-accumulation potential. ECOTOXICITY: This product has not been tested for aquatic or animal toxicity. All releases to terrestrial, atmospheric and aquatic environments should be avoided. OTHER ADVERSE EFFECTS: This material is not listed as having ozone depletion potential. ENVIRONMENTAL EXPOSURE CONTROLS: Controls should be engineered to prevent release to the environment, including procedures to prevent spills, atmospheric release and release to waterways. 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: It is the responsibility of the generator to determine at the time of disposal whether the product meets the criteria of a hazardous waste per regulations of the area in which the waste is generated and/or disposed of. Waste disposal must be in accordance with appropriate Federal, State, and local regulations. This product, if unaltered by use, may be disposed of by treatment at a permitted facility or as advised by your local hazardous waste regulatory authority. Shipment of wastes must be done with appropriately permitted and registered transporters. DISPOSAL CONTAINERS: Waste materials must be placed in and shipped in appropriate 5-gallon or 55-gallon poly or metal waste pails or drums. Permeable cardboard containers are not appropriate and should not be used. Ensure that any required marking or labeling of the containers be done to all applicable regulations. PRECAUTIONS TO BE FOLLOWED DURING WASTE HANDLING: Wear proper protective equipment when handling waste materials. U.S. EPA WASTE NUMBER: Not applicable. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. SDS0009 - SPECSEAL° ES ELASTOMERIC FIRESTOP SEALANT SDS EFFECTIVE DATE: NOVEMBER 10, 2020 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: This product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-21): ACUTE: Yes; CHRONIC: Yes; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): There are no specific Threshold Planning Quantities for components. The default Federal SIDS submission and inventory requirement filing threshold of 10,000 lb (4,540 kg) may apply, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: Components of this product are listed on the TSCA Inventory. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): The trace Crystalline Silica component (airborne, unbound particles of respirable size) and Titanium Dioxide are found on the Proposition 65 List of chemicals known to the state to cause cancer. However due to the form of the product, the Proposition 65 warning for these components is not applicable. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: This product would be categorized as a Controlled Product, D213 (Other Toxic Effects - Potential Carcinogenic Effect, Irritation) as per the Controlled Product Regulations. O CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: Components listed by CAS# are listed on the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: Components listed by CAS# are on the ENCS Inventory or are excepted. Japanese Ministry of Economy, Trade, and Industry (METI) Status: Components are not listed as Class I Specified Chemical Substances, Class II Specified Chemical Substances, or Designated Chemical Substances by the Japanese METI. Poisonous and Deleterious Substances Control Law: Components are not listed as a Specified Poisonous Substance under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existinq Chemicals List (ECL) Status: Components listed by CAS# are listed on the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: Components listed by CAS# are not listed on the Singapore List of Controlled Substances. Code of Practice on Pollution Control Requirements: The components identified by CAS# in Section 2 (Composition and Information on Ingredients) NOT are subject to the requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: Components listed by CAS# are listed on the Taiwan Existing Chemicals List. 16. OTHER INFORMATION REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: CHEMICAL SAFETY ASSOCIATES, Inc. • PO Box 1961, Hilo, HI 96721-1961 • (800) 441-3365 DATE OF PRINTING: November 12, 2020 REVISED: June 5, 2018 March 12,2020 November 10, 2020 REVISION DETAILS: Revised Proposition 65 statement. Revised hazard identification profile. Revised product information. SDS0009 - SPECSEAL® ES ELASTOMERIC FIRESTOP SEALANT SIDS EFFECTIVE DATE: NOVEMBER 10, 2020 Sn. SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: SpecSeal° LCI Intumescent Sealant RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME: Address: Business Phone: Emergency Phone: Firestop and Sound Transmission None Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of Competent Person for Information on SDS: techserv(cDstifirestop.com NOTE: ALL United States Occupational Safety and Health Administration Standard (29 CFR 1910.1200), U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7250 required information is included in appropriate sections based on the U.S. ANSI Z400.1-2010 format. This product has been classified in accordance with the hazard criteria of the countries listed above. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND JAPANESE JIS Z7253 LABELING AND CLASSIFICATION: This product has been classified per UN GHS Standards under U.S., Japanese and other applicable regulations that require Global Harmonization compliance. Classification: Carcinogenic Category 2, Eye Irritation Category 2A, Specific Target Organ Toxicity (Inhalation -Respiratory Irritation) Single Exposure Category 3 Signal Word: Warning Hazard Statements: H351: This product contains trace amounts of a suspected human carcinogen by inhalation: however, this hazard is not expected to be significant due to viscosity and consistency of the mixture. H319: Causes serious eye irritation. H335: May cause respiratory irritation. Precautionary Statements: Prevention: P201: Obtain special instructions before use. P202: Do not handle until all safety precautions have been read and understood. P261: Avoid breathing vapors, fume. P271: Use only in a well -ventilated area. P280: Wear protective gloves, clothing, eye protection and face protection. P284: Wear respiratory protection. Response: P308 + P313: IF exposed or concerned: Get medical advice/attention. P305 + P351 + P338: IF IN EYES: Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do. P337 + P313: If eye irritation persists: Get medical advice/attention. P304 + P340: If inhaled, remove victim to fresh air and keep at rest in a position comfortable for breathing. P312: Call a POISON CENTER or doctor if you feel unwell. P321: Specific treatment (remove from exposure and treat symptoms). Storage: P403 + P233 + P405: Store in a well -ventilated place. Keep container tightly closed. Store locked up. Disposal: P501: Dispose of contents/containers in accordance with all local, regional, national and international regulations. Hazard Symbols: GHS07, GHS08 t > 4> KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: Classified in accordance with ISHA Notice 2009- 68. Under ISHA, no differences in classification are applicable. 3. COMPOSITION and INFORMATION ON INGREDIENTS Hazardous Components: LABEL ELEMENTS Chemical Name CAS # Chinese IECSC Japanese ENCS # Korean ECL # Taiwan I WT°� GHS & Japanese JIS Z7253 Classification Inventory ECS Korean ISHA Classification GHS Hazard Codes SELF CLASSIFICATION Aluminum 21645-51-2 Listed 1-17 KE-00980 15-25% GHS & JAPANESE JIS Z7253, KOREAN ISHA: Classification: Eye Irritation Cat. 2A Trihydrate Hazard Codes: H319 SELF CLASSIFICATION Sulfuric Acid GHS & JAPANESE JIS Z7253, KOREAN ISHA: Compound with 12777-87-6 Not Listed Not Listed KE-32585 2-5% Graphite Classification: Carcinogenic Cat. 2 Hazard Codes: H351i SELF CLASSIFICATION GHS & JAPANESE JIS Z7253, KOREAN ISHA: Crystalline Silica 14808-60-7 Listed 1-548 KE-29983 0.1-0.2% Classification: Carcinogenic Cat. 1, STOT (Inhalation -Lungs) RE Cat. 2 Hazard Statement Codes: H350, H373 SDS0004 - SPECSEAL® LCI INTUMESCENT SEALANT SIDS EFFECTIVE DATE: AUGUST 11, 2020 PAGE 1 of 6 4. FIRST -AID MEASURES Skin Exposure: If adverse skin effects occur, discontinue use and flush contaminated area. Seek medical attention if adverse effect occurs after flushing. Inhalation: If fumes or vapors are inhaled, remove victim to fresh air. Eve Exposure: If this product contaminates the eyes, rinse eyes under gently running water. Ingestion: If this product is swallowed, CALL PHYSICIAN OR POISON CONTROL CENTER FOR MOST CURRENT INFORMATION. If professional advice is not available, DO NOT INDUCE VOMITING. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Pre-existing respiratory disorders may be aggravated by overexposures to this product. 5. FIRE -FIGHTING MEASURES FLASH POINT: 338 °C (640 °F) AUTOIGNITION TEMPERATURE: Not available. FLAMMABLE LIMITS (in air by volume, %): Not applicable. FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. When involved in a fire, this material may decompose and produce irritating vapors and toxic gases. Explosion Sensitivity to Mechanical Impact: Not sensitive. Explosion Sensitivity to Static Discharge: Not sensitive. NFPA RATING HEALTH INSTABILITY OTHER Hazard Scale: 0 = Minimal 1 = Slight 2 = Moderate 3 = Serious 4 = Severe SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: No special protective actions for fire-fighters are anticipated. 6. ACCIDENTAL RELEASE MEASURES PERSONAL PROTECTIVE EQUIPMENT: Proper protective equipment should be used. Small Spills: Wear rubber gloves, safety glasses. Large Spills: Minimum Personal Protection Equipment should be rubber gloves. METHODS FOR CLEAN-UP AND CONTAINMENT: Spills of this product present minimal hazard. Small Spills: Small releases can be carefully swept up or cleaned up using a damp sponge or polypads. Large Spills: Access to the spill area should be restricted. For large spills, dike or otherwise contain spill and sweep -up or vacuum with non -sparking vacuum. All Spills: Place all spill residue in a double plastic bag or other containment and seal. Close off sewers and take other measures to protect human health and the environment as necessary. Rinse area with soap and water solution and follow with a water rinse. Decontaminate the area thoroughly. Do not mix with wastes from other materials. Dispose of in accordance with applicable Federal, State, and local procedures (see Section 13, Disposal Considerations). For spills on water, contain, minimize dispersion and collect. Dispose of recovered material and report spill per regulatory requirements. ENVIRONMENTAL PRECAUTIONS: Avoid release to the environment. Run-off water may be contaminated by other materials and should be contained to prevent possible environmental damage. 7. HANDLING and USE PRECAUTIONS FOR SAFE HANDLING: As with all chemicals, avoid getting this material ON YOU or IN YOU. Do not eat, drink, smoke, or apply cosmetics while handling this product. Wash hands thoroughly after handling this product or containers of this product. Avoid breathing fumes or vapors generated by this product. Use in a well -ventilated location. CONDITIONS FOR SAFE STORAGE: Store containers in a cool, dry location, away from direct sunlight, sources of intense heat. Do not store above 55°C (131 °F) SPECIFIC END USE(S): This product is for use as a sealant. Follow all industry standards for use of this product. SDS0004 - SPECSEALO LCI INTUMESCENT SEALANT SDS EFFECTIVE DATE: AUGUST 11, 2020 PAGE 2 of 6 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: Ventilation and Engineering Controls: Use with adequate ventilation to ensure exposure levels are maintained below the limits provided below (if applicable). Exhaust directly to the outside, taking necessary precautions for environmental protection. Workplace Exposure Limits/Control Parameters: CHEMICAL CAS # EXPOSURE LIMITS IN AIR NAME ACGIH-TLVs OSHA-PELs NIOSH-RELs NIOSH OTHER TWA STEL TWA STEL TWA I STEL IDLH mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 Aluminum 21645-51-2 NE NE NE NE NE NE NE DFG MAKs: Trihydrate TWA = 4 mg/m3 (inhalable fraction); 1.5 mg/m3 (respirable fraction) DFG MAK Pregnancy Risk Classification: D Crystalline Silica 14808-60-7 0.025 NE 0.05 mg/m3 NE 0.05 (resp. NE 50 Carcinogen: IARC-1, MAK-1 (Quartz) (resp. (resp. dust) dust) (respirable fraction), NOSH -Ca, NTP- fract.) K (respirable fraction), TLV-A2 Sulfuric Acid 12777-87-6 NE NE NE NE NE NE NE NE Compound with Graphite NE = Not Established. See Section 16 for Definitions of Other Terms Used PROTECTIVE EQUIPMENT: The following information on appropriate Personal Protective Equipment is provided to assist employers in complying with OSHA regulations found in 29 CFR Subpart I (beginning at 1910.132, including U.S. Federal OSHA Respiratory Protection (29 CFR 1910.134), OSHA Eye Protection 29 CFR 1910.133, OSHA Hard Protection 29 CFR 1910.138, OSHA Foot Protection 29 CFR 1910.136 and OSHA Body Protection 29 CFR1910.132), equivalent standards of Canada (including CSA Respiratory Standard Z94.4-02, Z94.3-M1982, Industrial Eye and Face Protectors and CSA Standard Z195-02, Protective Footwear), or standards of Japan (including JIS T 8116:2005 for glove selection, JIS T 8150:2006 for respiratory PPE, JIS T 8147:2003 for eye protectors, and JIS T 8030:2005 for protective clothing). Please reference applicable regulations and standards for relevant details. Respiratory Protection: Maintain airborne contaminant concentrations below exposure limits listed above. For materials without listed exposure limits, minimize respiratory exposure. If necessary, use only respiratory protection authorized under appropriate regulations. Eve Protection: Wear splash goggles or safety glasses as appropriate for the task. Hand Protection: Wash hands and wrists before putting on and after removing gloves. During manufacture or other similar operations, wear the appropriate hand protection for the process. Skin Protection: Use appropriate protective clothing for the task (e.g., lab coat, etc.). If necessary, refer to the U.S. OSHA Technical Manual (Section VII: Personal Protective Equipment) or other appropriate regulations. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Paste. COLOR: Red MOLECULAR FORMULA: Mixture. MOLECULAR WEIGHT: Mixture. ODOR: Mild acrylic. ODOR THRESHOLD: Not available. FLAMMABLE LIMITS (in air by volume, %): Not applicable. OXIDIZING PROPERTIES: Not applicable. DECOMPOSITION TEMPERATURE: Not available. PERCENT VOLATILE: 22 AUTOIGNITION TEMPERATURE: Not available. FLASH POINT: Not available. FREEZING/MELTING POINT: Not available. BOILING POINT: > 1000C (> 212°F) VAPOR PRESSURE: Not available. SPECIFIC GRAVITY (water = 1): 1.38 VAPOR DENSITY (air = 1): Not available. CARB VOC: 0.2.29 wt % (calc.) EVAPORATION RATE (n-BuAc = 1): > 1 VOC (U.S. EPA Method 24): 26 gm/L SOLUBILITY IN WATER: Insoluble. SOLUBILITY IN SOLVENTS: Not available. COEFFICIENT WATER/OIL DISTRIBUTION: Not established. pH: Not available. HOW TO DETECT THIS SUBSTANCE (warning properties in event of accidental release): The appearance may be characteristics to distinguish a release of this product. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is stable when properly stored at normal temperature and pressures (see Section 7, Handling and Storage). DECOMPOSITION PRODUCTS: Combustion: If exposed to extremely high temperatures, thermal decomposition may generate irritating fumes and toxic gases (e.g., aluminum, calcium, carbon, and sulfur oxides, and acrylic monomers). Hydrolysis: None known. MATERIALS WITH WHICH SUBSTANCE IS INCOMPATIBLE: This product is incompatible with strong oxidizers. POSSIBILITY OF HAZARDOUS POLYMERIZATION OR REACTION: Will not occur. CONDITIONS TO AVOID: Avoid exposure to or contact with extreme temperatures and incompatible chemicals. SDS0004 - SPECSEAL® LCI INTUMESCENT SEALANT SDS EFFECTIVE DATE: AUGUST 11, 2020 PAGE 3 of 6 11. TOXICOLOGICAL INFORMATION Inhalation: Inhalation of fumes or vapors may cause Irritation of the nose, throat, and lungs and cause coughing. Removal to fresh air should relieve symptoms. The trace Crystalline Silica component is a known human carcinogen. Due to the form of this product, this hazard is not as significant as a powdered or solid products, however, all inhalation exposure must be avoided in order to mitigate carcinogenic potential. Contact with Skin or Eyes: Direct eye contact may cause irritation, redness, and tearing from mechanical irritation. Prolonged or repeated skin exposures may cause dermatitis (dry red skin). Skin Absorption: Components are not known to be absorbed through intact skin. Ingestion: Ingestion is not a significant route of occupational exposure and is unlikely to occur. Infection: Accidental injection of this product, via laceration or puncture by a contaminated object can cause redness at the site of injection. HEALTH EFFECTS OR RISKS FROM EXPOSURE: Exposure to this product may cause the following health effects: Acute: Inhalation of fumes or vapors may cause irritation of respiratory system. Eye contact may cause mechanical irritation. Chronic: Prolonged or repeated skin exposure may cause dermatitis (dry red skin). This product contains trace amounts of a suspected human carcinogen by inhalation: however, this hazard is not expected to be significant due to the viscosity and consistency of the mixture. HAZARDOUS MATERIAL IDENTIFICATION SYSTEM HEALTH HAZARD (BLUE) 1* FLAMMABILITY HAZARD (RED) 0 PHYSICAL HAZARD (YELLOW) 0 PROTECTIVE EQUIPMENT EYES RESPIRATORY HANDS BODY 9 SEE SECTION 8 J SEE SECTION 8 For Routine Industrial Use and Handling Applications Hazard Scale: 0 = Minimal 1 = Slight 2 = Moderate TARGET ORGANS: Acute: Skin, eyes, respiratory system. Chronic: Skin. 3 = Serious 4 = Severe ` = Chronic hazard not otherwise specified IRRITANCY OF PRODUCT: Inhalation of fumes or vapors may cause respiratory irritation. Eye contact may cause irritation. Prolonged skin contact may cause irritation. SENSITIZATION OF PRODUCT: This product is not currently known to cause allergic skin or respiratory reaction. CARCINOGENIC POTENTIAL OF COMPONENTS: Components of this product are listed by agencies tracking the carcinogenic potential of chemical compounds, as follows: CRYSTALLINE SILICA: ACGIH-TLV-A2 (Suspected Human Carcinogen); IARC-1 (Carcinogenic to Humans); MAK-1 (Substances that Cause Cancer in Man and Can Be Assumed to Make a Significant Contribution to Cancer Risk); NIOSH-Ca (Potential Occupational Carcinogen with No Further Categorization); NTP-K (Known to Be a Human Carcinogen) The remaining components are not found on the following lists: U.S. EPA, U.S. NTP, U.S. OSHA, U.S. NIOSH, GERMAN MAK, IARC, or ACGIH and therefore is neither considered to be nor suspected to be a cancer -causing agent by these agencies. REPRODUCTIVE TOXICITY INFORMATION: Components of this product have no reported mutagenic, embryotoxic, teratogenic or reproductive toxicity. ACGIH BIOLOGICAL EXPOSURE INDICES BIOLOGICAL EXPOSURE INDICES (BEIss : Currently, there are no ACGIH Biological Exposure Indices (BEls) determined for this material. DEGREE OF EFFECT TO THE HEALTH OF THE POLLUTING AGENT OF ENVIRONMENT OF WORK (per Mexican NOM- 010 STPS-1999): 0 12. ECOLOGICAL INFORMATION MOBILITY: This product has not been tested for mobility in soil. PERSISTENCE AND BIODEGRADABILITY: This product has not been tested for persistence or biodegradability. The mineral components are not expected to biodegrade to great extent. BIO-ACCUMULATION POTENTIAL: This product has not been tested for bio-accumulation potential. ECOTOXICITY: This product has not been tested for aquatic or animal toxicity. All releases to terrestrial, atmospheric and aquatic environments should be avoided. OTHER ADVERSE EFFECTS: This material is not listed as having ozone depletion potential. ENVIRONMENTAL EXPOSURE CONTROLS: Controls should be engineered to prevent release to the environment, including procedures to prevent spills, atmospheric release and release to waterways. 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: It is the responsibility of the generator to determine at the time of disposal whether the product meets the criteria of a hazardous waste per regulations of the area in which the waste is generated and/or disposed of. Waste disposal must be in accordance with appropriate Federal, State, and local regulations. DISPOSAL CONTAINERS: Waste materials must be placed in and shipped in appropriate 5-gallon or 55-gallon poly or metal waste pails or drums. PRECAUTIONS TO BE FOLLOWED DURING WASTE HANDLING: Wear proper protective equipment when handling waste materials. U.S. EPA WASTE NUMBER: Not applicable. SDS0004 - SPECSEAL® LCI INTUMESCENT SEALANT SIDS EFFECTIVE DATE: AUGUST 11, 2020 PAGE 4 of 6 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: This product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-21): ACUTE: Yes; CHRONIC: Yes; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): There are no specific Threshold Planning Quantities for components. The default Federal SIDS submission and inventory requirement filing threshold of 10,000 lb (4,540 kg) may apply, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: Components of this product are listed on the TSCA Inventory. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): The trace Crystalline Silica component (airborne, unbound particles of respirable size) is found on the Proposition 65 List of chemicals known to the state to cause cancer. Due to the form of the product, the Proposition 65 warning for this component is not applicable. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: This product would be categorized as a Controlled Product, D213 (Other Toxic Effects - Potential Carcinogenic Effect, Irritation) as per the Controlled Product Regulations. CHINESE REGULATIONS: O Chinese Inventory of Existing Chemical Substances Status: Components listed by CAS# are listed on the Chinese Inventory of Existing Chemical Substances (IECSC), or are not listed, per information in Section 2. JAPANESE REGULATIONS: Japanese ENCS: Components listed by CAS# are on the ENCS Inventory, are excepted, or are not listed, per information in Section 2. Japanese Ministry of Economy, Trade, and Industry (METI) Status: Components are not listed as Class I Specified Chemical Substances, Class II Specified Chemical Substances, or Designated Chemical Substances by the Japanese METI. Poisonous and Deleterious Substances Control Law: Components are not listed as a Specified Poisonous Substance under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: Components listed by CAS# are listed on the Korean ECL Inventory, or are not listed, per information in Section 2. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: Components listed by CAS# are not listed on the Singapore List of Controlled Substances. Code of Practice On Pollution Control Requirements: The components identified by CAS# in Section 2 (Composition and Information on Ingredients) NOT are subject to the requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: Components listed by CAS# are listed on the Taiwan Existing Chemicals List. SDS0004 - SPECSEAL® LCI INTUMESCENT SEALANT SIDS EFFECTIVE DATE: AUGUST 11, 2020 PAGE 5 of 6 16. OTHER INFORMATION REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: CHEMICAL SAFETY ASSOCIATES, Inc.. PO Box 1961, Hilo, HI 96721-1961 . (800) 441-3365 DATE OF PRINTING: August 12, 2020 REVISED: June 5, 2018 June 1, 2019 August 11, 2020 REVISION DETAILS: Revised Proposition 65 statement. Revised Hazards Identification profile. SDS0004 - SPECSEAL® LCI INTUMESCENT SEALANT SIDS EFFECTIVE DATE: AUGUST 11, 2020 PAGE 6 of 6 2V6 STI SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME: Address: Business Phone: Emergency Phone: Blazestop— WF300 Firestop Caulk Firestop and Sound Transmission None Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of Competent Person for Information on SDS: techserv(a)stifirestop.com NOTE: ALL United States Occupational Safety and Health Administration Standard (29 CFR 1910.1200), U.S. State equivalent Standards, Canadian WHIMS [Controlled Products Regulations], Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7250 required information is included in appropriate sections based on the U.S. ANSI Z400.1-2010 format. This product has been classified in accordance with the hazard criteria of the countries listed above. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND JAPANESE JIS Z7253 LABELING AND CLASSIFICATION: This product has been classified per UN GHS Standards under U.S., Japanese and other applicable regulations that require Global Harmonization compliance. Classification: Carcinogenic Category 2, Eye Irritation Category 2A, Specific Target Organ Toxicity (Inhalation -Respiratory Irritation) Single Exposure Category 3 Signal Word: Warning Hazard Statements: H351: Suspected of causing cancer. H319: Causes serious eye irritation. H335: May cause respiratory irritation. Precautionary Statements: Prevention: P201: Obtain special instructions before use. P202: Do not handle until all safety precautions have been read and understood. P261: Avoid breathing vapors, fume. P271: Use only outdoors or in a well -ventilated area. P280: Wear protective gloves, clothing, eye protection and face protection. P284: Wear respiratory protection. Response: P308 + P313: IF exposed or concerned: Get medical advice/attention. P305 + P351 + P338: IF IN EYES: Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do. P337 + P313: If eye irritation persists: Get medical advice/attention. P304 + P340: If inhaled, remove victim to fresh air and keep at rest in a position comfortable for breathing. P312: Call a POISON CENTER or doctor if you feel unwell. P321: Specific treatment (remove from exposure and treat symptoms). Storage: P403 + P233 + P405: Store in a well -ventilated place. Keep container tightly closed. Store locked up. Disposal: P501: Dispose of contents/containers in accordance with all local, regional, national and international regulations. Hazard Symbols: GHS07, GHS08 KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: Classified in accordance with ISHA Notice 2009-68. Under ISHA, no differences in classification are applicable. 3. COMPOSITION and INFORMATION ON INGREDIENTS Chinese LABEL ELEMENTS Chemical Name CAS # IECSC Japanese ENCS # Korean ECL Taiwan wT% GHS & Japanese JIS Z7253 Classification Inventory # NESCI ECS Korean ISHA Classification GHS Hazard Codes SELF & PUBLISHED CLASSIFICATION GHS & JAPANESE JIS Z7253, KOREAN ISHA: Classification: Flammable Liquid Cat. 3, Aspiration Mineral Spirits 64742-88-7 Listed Not Listed KE-31664 2-4% Hazard Cat. 1, STOT (Inhalation -Central Nervous System) RE Cat. 1 Hazard Statement Codes: H226, H304, H372 BlazestopT" WF300 Firestop Caulk SDS EFFECTIVE DATE: JUNE 5, 2018 PAGE 1 OF 7 3. COMPOSITION and INFORMATION ON INGREDIENTS (Continued) Chemical Name CAS # Chinese IECSC Inventory Japanese ENCS # Korean ECL # Taiwan NESCI ECS WT°/ LABELELEMENTS GHS & Japanese JIS Z7253 Classification Korean ISHA Classification GHS Hazard Codes Sulfuric Acid SELF CLASSIFICATION Compound with 12777-87-6 Not Listed Not Listed KE-32585 1-2 % GHS & JAPANESE JIS Z7253, KOREAN ISHA: Graphite Classification: Carcinogenic Cat. 2 Hazard Codes: H351i SELF CLASSIFICATION Crystalline Silica 14808-60-7 Listed 1-548 KE-29983 0.1-0.5% GHS & JAPANESE JIS Z7253, KOREAN ISHA: Classification: Carcinogenic Cat. 1, STOT (Inhalation -Lungs) RE Cat. 2 Hazard Statement Codes: H350, H373 4. FIRST -AID MEASURES Skin Exposure: If adverse skin effects occur, discontinue use and flush contaminated area. Seek medical attention if adverse effect occurs after flushing. Inhalation: If fumes or vapors are inhaled, remove victim to fresh air.. Eve Exposure: If this product contaminates the eyes, rinse eyes under gently running water. Use sufficient force to open eyelids and then "roll' eyes while flushing. Minimum flushing is for 20 minutes. The contaminated individual must seek medical attention if any adverse effect continues after rinsing. Ingestion: If this product is swallowed, CALL PHYSICIAN OR POISON CONTROL CENTER FOR MOST CURRENT INFORMATION. If professional advice is not available, DO NOT INDUCE VOMITING. Never induce vomiting or give diluents (milk or water) to someone who is unconscious, having convulsions, or unable to swallow. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Pre-existing respiratory disorders may be aggravated by overexposures to this product. INDICATION OF IMMEDIATE MEDICAL ATTENTION AND SPECIAL TREATMENT IF NEEDED: Treat symptoms and eliminate exposure. 5. FIRE -FIGHTING MEASURES FLASH POINT: 140 °C (284 °F) AUTOIGNITION TEMPERATURE: Not available. FLAMMABLE LIMITS (in air by volume, %): Not applicable. FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. When involved in a fire, this material may decompose and produce irritating vapors and toxic gases. Explosion Sensitivity to Mechanical Impact: Not sensitive. Explosion Sensitivity to Static Discharge: Not sensitive. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: No Special protective actions for fire-fighters are anticipated. HEALTH NFPA RATING OTHER INSTABILITY Hazard Scale: 0 = Minimal 1 = Slight 2 = Moderate 3 = Serious 4 = Severe 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Uncontrolled releases should be responded to by trained personnel using pre -planned procedures. Proper protective equipment should be used. Call CHEMTREC (1- 800-424-9300) for emergency assistance. Or if in Canada, call CANUTEC (613-996-6666 PERSONAL PROTECTIVE EQUIPMENT: Proper protective equipment should be used. Small Spills: Wear rubber gloves, splash goggles, and appropriate body protection. Large Spills: Minimum Personal Protective Equipment should be rubber gloves, rubber boots, face shield, METHODS FOR CLEAN-UP AND CONTAINMENT: Spills of this product present minimal hazard. Small Spills: Small releases can be carefully swept up or cleaned up using a damp sponge or polypads. Large Spills: Access to the spill area should be restricted. For large spills, dike or otherwise contain spill and sweep -up or vacuum with non -sparking vacuum. All Spills: Place all spill residue in a double plastic bag or other containment and seal. Rinse area with soap and water solution and follow with a water rinse. Do not mix with wastes from other materials. Dispose of in accordance with applicable Federal, State, and local procedures (see Section 13, Disposal Considerations). For spills on water, contain, minimize dispersion and collect. Dispose of recovered material and report spill per regulatory requirements. ENVIRONMENTAL PRECAUTIONS: Avoid release to the environment. Run-off water may be contaminated by other materials and should be contained to prevent possible environmental damage. BlazestopT" WF300 Firestop Caulk SIDS EFFECTIVE DATE: JUNE 5, 2018 PAGE 2 OF 7 7. HANDLING and STORAGE PRECAUTIONS FOR SAFE HANDLING: As with all chemicals, avoid getting this material ON YOU or IN YOU. Do not eat, drink, smoke, or apply cosmetics while handling this product. Wash hands thoroughly after handling this product or containers of this product. Avoid breathing fumes or vapors generated by this product. Use in a well -ventilated location. CONDITIONS FOR SAFE STORAGE: Store containers in a cool, dry location, away from direct sunlight, sources of intense heat. Do not store above 55°C (131 °F) SPECIFIC END USE(S): This product is for use as a sealant. Follow all industry standards for use of this product. PROTECTIVE PRACTICES DURING MAINTENANCE OF CONTAMINATED EQUIPMENT: Follow practices indicated in Section 6 (Accidental Release Measures). Make certain that application equipment is locked and tagged -out safely, if necessary. Collect all rinsates and dispose of according to applicable Federal, State, and local procedures. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: Ventilation and Engineering Controls: Use with adequate ventilation to ensure exposure levels are maintained below the limits provided below (if applicable). Exhaust directly to the outside, taking necessary precautions for environmental protection. Workplace Exposure Limits/Control Parameters: CHEMICAL CAS # EXPOSURE LIMITS IN AIR NAME ACGIH-TLVs OSHA-PELs NIOSH-RELs NOSH OTHER TWA STEL TWA STEL TWA F13TEL IDLH mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 g/m3 mg/m3 mg/m3 Crystalline 14808-60-7 0.025 NE 0.05 ma/m3(resp. NE 0.05 (resp. NE 50 Carcinogen: IARC-1, MAK-1 Silica (Quartz) (resp. dust) dust) (respirable fraction), fract.) NOSH -Ca, NTP-K (respirable fraction), TLV- A2 Mineral Spirits 64742-88-7 NE NE 2000 NE 350 1800 1100 Carcinogen: IARC-3 Exposure (ceiling) (based limits for 15 min. on 10% petroleum of LEL) distillates naphtha NE = Not Established. See Section 16 for Definitions of Other Terms Used International Occupational Exposure Limits: Currently, the following additional exposure limit values have been established by various countries for the components of this mixture. More current limits may be available; individual countries should be consulted to determine if newer limits are available. CRYSTALLINE SILICA: CRYSTALLINE SILICA (continued): Australia: TWA = 0.1 mg/m3, JUL 2008 Thailand: TWA = 10 mg/m3 (resp. dust), JAN 1993 Belgium: TWA = 0.1 mg/m' (resp. dust), MAR 2002 Thailand: TWA = 30 mg/m3 (total dust), JAN 1993 Denmark: TWA = 0.1 mg/m' (respirable), carc, MAY 2011 United Kingdom: TWA = 0.1 mg/m' (resp. dust), OCT 2007 Denmark: TWA = 0.1 mg/m' (resp.), carc, MAY2011 In Argentina, Bulgaria, Colombia, Jordan, Singapore, Vietnam check ACGIH TLV Denmark: TWA = 0.3 mg/m3 (total), MAY 2011 Finland: TWA = 0.05 mg/m3, resp. dust, SEP 2009 France: VME = 0.1 mg/m3, (resp), FEB 2006 Iceland: TWA = 0.1 mg/m3 (resp. dust), NOV 2011 Japan: OEL-C = 0.03 mg/m' (respirable), APR 2007 Korea: TWA = 0.1 mg/m3, 2006 Mexico: TWA = 0.1 mg/m' (respirable), 2004 The Netherlands: MAC-TGG = 0.075 mg/m', 2003 New Zealand: TWA = 0.2 mg/m3 (respirable dust), JAN 2002 Norway: TWA = 0.1 mg/m3 (resp. dust), JAN 1999 Norway: TWA = 0.3 mg/m3 (total dust), JAN 1999 Peru: TWA = 0.05 mg/m3, JUL 2005 Russia: TWA = 1 mg/m3, STEL = 3 mg/m', JUN 2003 Sweden: TWA = 0.1 mg/m' (resp. dust), JUN 2005 Switzerland: MAK-W = 0.15 mg/m', DEC 2006 PROTECTIVE EQUIPMENT: The following information on appropriate Personal Protective Equipment is provided to assist employers in complying with OSHA regulations found in 29 CFR Subpart I (beginning at 1910.132, including U.S. Federal OSHA Respiratory Protection (29 CFR 1910.134), OSHA Eye Protection 29 CFR 1910.133, OSHA Hard Protection 29 CFR 1910.138, OSHA Foot Protection 29 CFR 1910.136 and OSHA Body Protection 29 CFR1910.132), equivalent standards of Canada (including CSA Respiratory Standard Z94.4-02, Z94.3-M 1982, Industrial Eye and Face Protectors and CSA Standard Z195-02, Protective Footwear), or standards of Japan (including JIS T 8116:2005 for glove selection, JIS T 8150:2006 for respiratory PPE, JIS T 8147:2003 for eye protectors, and JIS T 8030:2005 for protective clothing). Please reference applicable regulations and standards for relevant details. Respiratory Protection: Maintain airborne contaminant concentrations below exposure limits listed above. For materials without listed exposure limits, minimize respiratory exposure. If necessary, use only respiratory protection authorized under appropriate regulations. Oxygen levels below 19.5% are considered IDLH by U.S. OSHA. In such atmospheres, use of a full-facepiece pressure/demand SCBA or a full facepiece, supplied air respirator with auxiliary self-contained air supply is required under U.S. OSHA's Respiratory Protection Standard (1910.134-1998). BlazestopT" WF300 Firestop Caulk SIDS EFFECTIVE DATE: JUNE 5, 2018 PAGE 3 OF 7 8. EXPOSURE CONTROLS - PERSONAL PROTECTION (continued) Eve Protection: Wear splash goggles or safety glasses as appropriate for the task. Hand Protection: Wash hands and wrists before putting on and after removing gloves. During manufacture or other similar operations, wear the appropriate hand protection for the process. Use double gloves for spill response, as stated in Section 6 (Accidental Release Measures) of this SDS. Because all gloves are to some extent permeable and their permeability increases with time, they should be changed regularly (hourly is preferable) or immediately if torn or punctured. If necessary refer to appropriate regulations. Skin Protection: Use appropriate protective clothing for the task (e.g., lab coat, etc.). If necessary, refer to the U.S. OSHA Technical Manual (Section VII: Personal Protective Equipment) or other appropriate regulations. Full -body chemical protective clothing is recommended for emergency response procedures. If a hazard of injury to the feet exists due to falling objects, rolling objects, where objects may pierce the soles of the feet or where employee's feet may be exposed to electrical hazards, use foot protection, as described in U.S. OSHA and Canadian Standards. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Paste. MOLECULAR FORMULA: Mixture. ODOR: Mild acrylic. FLAMMABLE LIMITS (in air by volume, %): Not applicable DECOMPOSITION TEMPERATURE: Not available. AUTOIGNITION TEMPERATURE: Not available. FREEZING/MELTING POINT: Not available. VAPOR PRESSURE: Not available. VAPOR DENSITY (air = 1): Not available. EVAPORATION RATE (n-BuAc = 1): > 1 SOLUBILITY IN WATER: Insoluble. COLOR: Red. MOLECULAR WEIGHT: Mixture. ODOR THRESHOLD: Not available. OXIDIZING PROPERTIES: Not applicable. PERCENT VOLATILE: 19-20 FLASH POINT: Not available. BOILING POINT: > 100°C (> 212T) SPECIFIC GRAVITY (water = 1): 1.18 g/mL CARB VOC: 0.36 wt % (calc.) SCAQMD (U.S. EPA Method 24): 53 gm/L SOLUBILITY IN SOLVENTS: Not available. COEFFICIENT WATER/OIL DISTRIBUTION: Not established. pH: Not available. HOW TO DETECT THIS SUBSTANCE (warning properties in event of accidental release): The appearance may be characteristics to distinguish a release of this product. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is stable when properly stored at normal temperature and pressures (see Section 7, Handling and Storage). DECOMPOSITION PRODUCTS: Combustion: If exposed to extremely high temperatures, thermal decomposition may generate irritating fumes and toxic gases. Hydrolysis: None known. MATERIALS WITH WHICH SUBSTANCE IS INCOMPATIBLE: This product is incompatible with strong oxidizers. POSSIBILITY OF HAZARDOUS POLYMERIZATION OR REACTION: Will not occur. CONDITIONS TO AVOID: Avoid exposure to or contact with extreme temperatures and incompatible chemicals. 11. TOXICOLOGICAL INFORMATION SYMPTOMS OF EXPOSURE BY ROUTE OF EXPOSURE: The health hazard information provided below is pertinent to employees using this product in an occupational setting. The following paragraphs describe the symptoms of exposure by route of exposure. Inhalation: Inhalation of fumes or vapors may cause irritation of the nose, throat, and lungs and cause coughing. Removal to fresh air should relieve symptoms. This product contains trace amounts of a suspected human carcinogen by inhalation: however, this hazard is not expected to be significant due to viscosity and consistency of the mixture. Contact with Skin or Eves: Direct eye contact may cause irritation, redness, and tearing from mechanical irritation. Prolonged or repeated skin exposures may cause dermatitis (dry red skin). Skin Absorption: Components are not known to be absorbed through intact skin. Ingestion: Ingestion is not a significant route of occupational exposure and is unlikely to occur. Infection: Accidental injection of this product, via laceration or puncture by a contaminated object can cause redness at the site of injection. Animal data for the Crystalline Silica component indicate that it may cause carcinogenic effects by this route of exposure. HEALTH EFFECTS OR RISKS FROM EXPOSURE: Exposure to this product may cause the following health effects: Acute: Inhalation of fumes or vapors may cause irritation of respiratory system. Eye contact may cause mechanical irritation. Chronic: Prolonged or repeated skin exposure may cause dermatitis (dry red skin). This product contains trace amounts of a suspected human carcinogen by inhalation: however, this hazard is not expected to be significant due to viscosity and consistency of the mixture. BlazestopT" WF300 Firestop Caulk SIDS EFFECTIVE DATE: JUNE 5, 20018 PAGE 4 OF 7 11. TOXICOLOGICAL INFORMATION (Continued) TARGET ORGANS: Acute: Skin, eyes, respiratory system. Chronic: Skin. TOXICITY DATA: Currently, the following toxicological data are available for components of 1 % or more concentration. MINERAL SPIRITS: TCLo (Inhalation -Rat) 275 mg/m'/6 hours/16 days -intermittent: Liver: changes in liver weight TCLo (Inhalation -Rat) 2200 mg/m'/6 hours/16 days -intermittent: Liver: other changes TCLo (Inhalation -Rat) 275 mg/m'/6 hours/16 days -intermittent: Nutritional and Gross Metabolic: weight loss or decreased weight gain TCLo (Inhalation -Rat) 138 mg/m3/6 hours/16 days -intermittent: Liver: changes in liver weight; Kidney/Ureter/Bladder: changes in kidney weight; Related to Chronic Data: changes in testicular weight TCLo (Inhalation -Rat) 550 mg/m'/6 hours/16 days -intermittent: Kidney/Ureter/Bladder: other changes in urine composition, changes in kidney weight; Reproductive: Paternal Effects: spermatogenesis (incl. genetic material, sperm morphology, motility, and count) TCLo (Inhalation -Rat) 2200 mg/m'/6 hours/16 days -intermittent: Sense Organs and Special Senses (Olfaction): effect, not otherwise specified TCLo (Inhalation -Rat) 2200 mg/m'/6 hours/16 days -intermittent: Related to Chronic Data: death TCLo (Inhalation -Rat) 550 mg/m'/6 hours/16 days -intermittent: Kidney/Ureter/Bladder: other changes TCLo (Inhalation -Rat) 550 mg/m'/6 hours/16 days -intermittent: Endocrine: thyroid tumors TCLo (Inhalation -Rat) 1100 mg/m'/6 hours/16 days -intermittent: Kidney/Ureter/Bladder: other changes, Kidney tumors TCLo (Inhalation -Rat) 138 mg/m3/91 days -intermittent: Liver: changes in liver weight; Kidney/Ureter/Bladder: changes in kidney weight; Related to Chronic Data: changes in testicular weight TCLo (Inhalation -Rat) 1100 mg/m3/91 days -intermittent: Liver: changes in liver weight; Kidney/Ureter/Bladder: changes in kidney weight TCLo (Inhalation -Rat) 550 mg/m3/91 days -intermittent: Kidney/Ureter/Bladder: changes in tubules (including acute renal failure, acute tubular necrosis), other changes TCLo (Inhalation -Rat) 550 mg/m3/2 years -intermittent: Endocrine: other changes, tumors TCLo (Inhalation -Rat) 2200 mg/m3/91 days -intermittent: Kidney/Ureter/Bladder: other changes TCLo (Inhalation -Mouse) 275 mg/m'/6 hours/16 days -intermittent: Liver: changes in liver weight TCLo (Inhalation -Mouse) 2200 mg/m'/6 hours/16 days -intermittent: Liver: other changes TCLo (Inhalation -Mouse) 138 mg/m3/6 hours/16 days -intermittent: Blood: changes in spleen TCLo (Inhalation -Mouse) 2200 1 1 days -intermittent: Liver: changes in liver weight; Reproductive: Paternal Effects: spermatogenesis (incl. genetic material, sperm morphology, motility, and count) TCLo (Inhalation -Mouse) 550 mg/m'/6 hours/16 days -intermittent: Nutritional and Gross Metabolic: weight loss or decreased weight gain TCLo (Inhalation -Mouse) 2200 mg/m'/6 hours/16 days -intermittent: Liver: tumors TCLo (Inhalation -Mouse) 1100 mg/m'/91 days -intermittent: Liver: changes in liver weight TCLo (Inhalation -Mouse) 2200 mg/m'/91 days -intermittent: Reproductive: Paternal Effects: spermatogenesis (incl. genetic material, sperm morphology, motility, and count) TCLo (Inhalation -Mouse) 2200 mg/m3/2 years -intermittent: Liver: other changes, tumors TCLo (Inhalation -Mouse) 1100 mg/m3/2 years -intermittent: Liver: other changes IRRITANCY OF PRODUCT: Inhalation of fumes or vapors may cause respiratory irritation. Eye contact may cause irritation. Prolonged skin contact may cause irritation. SENSITIZATION OF PRODUCT: This product is not currently known to cause allergic skin or respiratory reaction. CARCINOGENIC POTENTIAL OF COMPONENTS: Components of this product are listed by agencies tracking the carcinogenic potential of chemical compounds, as follows: EYES RESPIRATORY HANDS BODY 9 SEE SECTION 8 j SEE SECTION S For Routine Industrial Use and Handling Applications Hazard Scale: 0 = Minimal 1 = Slight 2 = Moderate 3 = Serious 4 = Severe * = Chronic hazard CRYSTALLINE SILICA: ACGIH-TLV-A2 (Suspected Human Carcinogen); ARC-1 (Carcinogenic to Humans); MAK-1 (Substances that Cause Cancer in Man and Can Be Assumed to Make a Significant Contribution to Cancer Risk); NIOSH-Ca (Potential Occupational Carcinogen with No Further Categorization); NTP-K (Known to Be a Human Carcinogen) MINERAL SPIRITS: ARC-3 (Unclassifiable as to Carcinogenicity in Humans) The remaining components are not found on the following lists: U.S. EPA, U.S. NTP, U.S. OSHA, U.S. NIOSH, GERMAN MAK, IARC, or ACGIH and therefore is neither considered to be nor suspected to be a cancer -causing agent by these agencies. REPRODUCTIVE TOXICITY INFORMATION: Components of this product have no reported mutagenic, embryotoxic, teratogenic or reproductive toxicity. ACGIH BIOLOGICAL EXPOSURE INDICES (BEls): Currently, there are no ACGIH Biological Exposure Indices (BEls) determined for this material. DEGREE OF EFFECT TO THE HEALTH OF THE POLLUTING AGENT OF ENVIRONMENT OF WORK (per Mexican NOM-010 STPS-1999): 0 12. ECOLOGICAL INFORMATION ALL WORK PRACTICES MUST BE AIMED AT ELIMINATING ENVIRONMENTAL CONTAMINATION. MOBILITY: This product has not been tested for mobility in soil. PERSISTENCE AND BIODEGRADABILITY: This product has not been tested for persistence or biodegradability. The mineral components are not expected to biodegrade to great extent. BIO-ACCUMULATION POTENTIAL: This product has not been tested for bio-accumulation potential. ECOTOXICITY: This product has not been tested for aquatic or animal toxicity. All releases to terrestrial, atmospheric and aquatic environments should be avoided. OTHER ADVERSE EFFECTS: This material is not listed as having ozone depletion potential. ENVIRONMENTAL EXPOSURE CONTROLS: Controls should be engineered to prevent release to the environment, including procedures to prevent spills, atmospheric release and release to waterways. BlazestopT" WF300 Firestop Caulk SDS EFFECTIVE DATE: JUNE 5, 20018 PAGE 5 OF 7 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: It is the responsibility of the generator to determine at the time of disposal whether the product meets the criteria of a hazardous waste per regulations of the area in which the waste is generated and/or disposed of. Waste disposal must be in accordance with appropriate Federal, State, and local regulations. This product, if unaltered by use, may be disposed of by treatment at a permitted facility or as advised by your local hazardous waste regulatory authority. Shipment of wastes must be done with appropriately permitted and registered transporters. DISPOSAL CONTAINERS: Waste materials must be placed in and shipped in appropriate 5-gallon or 55-gallon poly or metal waste pails or drums. Permeable cardboard containers are not appropriate and should not be used. Ensure that any required marking or labeling of the containers be done to all applicable regulations. PRECAUTIONS TO BE FOLLOWED DURING WASTE HANDLING: Wear proper protective equipment when handling waste materials. U.S. EPA WASTE NUMBER: Not applicable. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: This product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-21): ACUTE: Yes; CHRONIC: Yes; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): There are no specific Threshold Planning Quantities for components. The default Federal SDS submission and inventory requirement filing threshold of 10,000 lb (4,540 kg) may apply, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: Components of this product are listed on the TSCA Inventory. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): The trace Crystalline Silica component (airborne, unbound particles of respirable size) is found on the Proposition 65 List of chemicals known to the state to cause cancer. However due to the form of the product, the Proposition 65 warning for this component is not applicable. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: This product would be categorized as a Controlled Product, D213 (Other Toxic Effects - Potential Carcinogenic Effect, Irritation) as per the Controlled Product Regulations. CHINESE REGULATIONS: (D Chinese Inventory of Existing Chemical Substances Status: Components listed by CAS# are listed on the Chinese Inventory of Existing Chemical Substances (IECSC), or are not listed, per information in Section 2. JAPANESE REGULATIONS: Japanese ENCS: Components listed by CAS# are on the ENCS Inventory, are excepted, or are not listed, per information in Section 2. Japanese Ministry of Economy, Trade, and Industry (METI) Status: Components are not listed as Class I Specified Chemical Substances, Class II Specified Chemical Substances, or Designated Chemical Substances by the Japanese METI. Poisonous and Deleterious Substances Control Law: Components are not listed as a Specified Poisonous Substance under the Poisonous and Deleterious Substances Control Law. Blazestop'" WF300 Firestop Caulk SDS EFFECTIVE DATE: JUNE 5, 20018 PAGE 6 OF 7 15. REGULATORY INFORMATION (Continued) KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: Components listed by CAS# are listed on the Korean ECL Inventory, or are not listed, per information in Section 2. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: Components listed by CAS# are not listed on the Singapore List of Controlled Substances. Code of Practice on Pollution Control Requirements: The components identified by CAS# in Section 2 (Composition and Information on Ingredients) NOT are subject to the requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: Components listed by CAS# are listed on the Taiwan Existing Chemicals List. 16. OTHER INFORMATION REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: CHEMICAL SAFETY ASSOCIATES, Inc. • PO Box 1961, Hilo, HI 96721-1961 • (800) 441-3365 DATE OF PRINTING: July 6, 2018 REVISED: June 5, 2018 REVISION DETAILS: Revised proposition 65 statement. BlazestopT" WF300 Firestop Caulk SIDS EFFECTIVE DATE: JUNE 5, 20018 PAGE 7 OF 7 STI, SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, REACH, CLP 1272:2208 and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: EZ-Path21 Series 22 Pathway SYNONYMS: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME: Address: Business Phone: Emergency Phone: None Intumescent Sealing Devise Other than Relevant Use Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of Competent Person for Information on SDS: techservBstifirestoD.com ALL United States Occupational Safety and Health Administration (OSHA) Standard, 29 CFR Parts 1910, 1915, 1917, 1918 and 1926, and the U.S. OSHA Instruction CPL 02-02-079, July 9, 2015, U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], European Union REACH and CLP EC 1272/2008, Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7253 required information is included in appropriate sections based on the Global Harmonization Standard (GHS). This product has been classified in accordance with the hazard criteria of the countries listed above. This product is defined as an "Article" under the U.S. Federal OSHA Hazard Communication Standard (29 CFR 1910.1200), EU Directives, and the Canadian Workplace Hazardous Materials Standard. Refer to Section 15 (Regulatory Information) for specific regulatory citations. As articles, this product presents negligible health and physical hazards under reasonably anticipated circumstances of use. Subsequently, a Safety Data Sheet is not required under Standards cited above. This document is prepared to provide persons using this product with additional safety information. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND EU CLP REGULATION (EC) 1272/2008 LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under CLP Regulation (EC) 1272/2008. EU 67/548/EEC LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under European Community Council Directive 67/548/EEC or subsequent Directives. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. 3. COMPOSITION and INFORMATION ON INGREDIENTS This product is an article that does not contain any "Substances of Very High Concern". 4. FIRST -AID MEASURES DESCRIPTION OF FIRST AID MEASURES: This product is an article and under normal use conditions does not present health concerns. Skin Exposure: If mechanical irritation occurs, remove contaminated clothing and wash skin gently with soap and water. Inhalation: Not anticipated based on product form. Eve Exposure: If this product contaminated the eyes, rinse eyes under gently running water. Use sufficient force to open eyelids and the "roll" eyes while flushing. Minimum flushing is 20 minutes. Ingestion: Due to the form of the product, ingestion is unlikely. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: None known. INDICATION OF IMMEDIATE MEDICAL ATTENTION AND SPECIAL TREATMENT IF NEEDED: If any adverse reaction or discomfort continues from any of the above exposures, seek professional medical advice. EZPATH® SERIES 22 PATHWAY SDS EFFECTIVE DATE: MAY 5, 2017 Page 1 of 4 aI::aalei: IIILI10Lyi :7*9 FLASH POINT: Not determined. AUTOIGNITION TEMPERATURE: Not available. FLAMMABLE LIMITS (in air by volume, %): Not applicable. FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. When involved in a fire, this material may decompose and produce irritating vapors and toxic gases (e.g., carbon, nitrogen and metal oxides, phthalates, ammonia, formaldehyde, hydrogen cyanide, nitriles, isocyanates, nitrosamines, hydrogen chloride, and acrylic monomers). Explosion Sensitivity to Mechanical Impact or Static Discharge: Not sensitive. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: In large fires in poorly ventilated areas involving packaging materials respiratory protection / breathing apparatus may be required. [:�_Td61l174LIkIFTIM►Ti0*1 PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Under normal handling conditions an accidental release is highly unlikely. Uncontrolled releases should be responded to by trained personnel. PERSONAL PROTECTIVE EQUIPMENT: Use personal protection recommended in Section 8 of the SDS METHODS FOR CLEAN-UP AND CONTAINMENT: As the product is an article, chemical components will not be released, therefore, spills are not anticipated. ENVIRONMENTAL PRECAUTIONS: As the product is an article, chemical components will not be released, therefore, spills are not anticipated. REFERENCE TO OTHER SECTIONS: See information in Section 8 (Exposure Controls — Personal Protection) and Section 13 (Disposal Considerations) for additional information. 7. HANDLING and USE PRECAUTIONS FOR SAFE HANDLING: As the product is an article, no precautions are necessary during normal use conditions. Avoid touching heated product. CONDITIONS FOR SAFE STORAGE: Store this product in a cool, dry location, away from sources of intense heat. Store away from water, heat and flame. SPECIFIC END USE(S): This product is an article made of formed Steel with Intumescent Fire -Retardant Gaskets Follow all industry standards for use of this product. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: This product is an article. No chemical components will be released from this product. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Galvanized steel form lined with a rubberized solid. pH: Not applicable. MOLECULAR FORMULA: Mixture. COLOR: Orange ODOR: Not available. MOLECULAR WEIGHT: Mixture FLAMMABLE LIMITS (in air by volume, %): Not available. ODOR THRESHOLD: Not available DECOMPOSITION TEMPERATURE: Not available. OXIDIZING PROPERTIES: Not applicable AUTOIGNITION TEMPERATURE: Not available. PERCENT VOLATILE: 0 FREEZING/MELTING POINT: Not available. FLASH POINT: Not available. VAPOR PRESSURE: Not applicable. BOILING POINT: Not applicable VAPOR DENSITY (air = 1): Not applicable. SPECIFIC GRAVITY (water = 1): Not applicable. EVAPORATION RATE (n-BuAc = 1): Not applicable. CARB VOC: Not applicable. SOLUBILITY IN WATER: Insoluble. SCAQMD (U.S. EPA Method 24): Not applicable. COEFFICIENT WATER/OIL DISTRIBUTION: Not SOLUBILITY IN SOLVENTS: Not applicable. applicable. HOW TO DETECT THIS SUBSTANCE (warning properties in event of accidental release): This product is an article. No chemical components will be released from this product. EZPATH° SERIES 22 PATHWAY SDS EFFECTIVE DATE: MAY 5, 2017 Page 2 of 4 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is an article and stable when properly stored at normal temperature and pressures (see Section 7, Handling and Storage). DECOMPOSITION PRODUCTS: Combustion: If exposed to extremely high temperatures, thermal decomposition may generate irritating fumes and toxic gases (e.g., carbon, nitrogen and metal oxides, phthalates, ammonia, formaldehyde, hydrogen cyanide, nitriles, isocyanates, nitrosamines, hydrogen chloride, and acrylic monomers). Hydrolysis: None known. MATERIALS WITH WHICH SUBSTANCE IS INCOMPATIBLE: This product is incompatible with strong oxidizers. POSSIBILITY OF HAZARDOUS POLYMERIZATION OR REACTION: Will not occur. CONDITIONS TO AVOID: Avoid exposure to or contact with extreme temperatures and incompatible chemicals. 11. TOXICOLOGICAL INFORMATION This product is an article. No chemical components will be released from this product. 12. ECOLOGICAL INFORMATION This product is an article. No chemical components will be released from this product. 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: This product is an article. No chemical components will be released from this product. Dispose of in accordance with local, state, and federal laws and regulations. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. EUROPEAN AGREEMENT CONCERNING THE INTERNATIONAL CARRIAGE OF DANGEROUS GOODS BY ROAD A( DR): This product is not classified by the United Nations Economic Commission for Europe to be dangerous goods. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: As an article, this product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-211: ACUTE: No; CHRONIC: No; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): As an article, this product is not subject to Threshold Planning Quantities, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: This product is an article as defined by TSCA. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): No component is on the California Proposition 65 lists. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: As an article, this product is not subject the Controlled Product Regulations. EUROPEAN REGULATIONS: EZPATH® SERIES 22 PATHWAY SDS EFFECTIVE DATE: MAY 5, 2017 Page 3 of 4 15. REGULATORY INFORMATION (continued) Safety, Health, and Environmental Regulations/Legislation Specific for the Product This product is an article that does not contain any "Substances of Very High Concern". CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: As an article, this product is not subjected to requirements under the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: As an article, this product is not subjected to requirements under ENCS Inventory. Japanese Ministry of Economy, Trade, and Industry (METI) Status: As an article, this product is not subjected to requirements under the Japanese METI. Poisonous and Deleterious Substances Control Law: As an article, this product is not subjected to requirements under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: As an article, this product is not subjected to requirements under the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is not classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: As an article, this product is not subjected to requirements under the Singapore List of Controlled Substances. Code of Practice On Pollution Control Requirements: As an article, this product is not subjected to requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: As an article, this product is not subjected to requirements under the Taiwan Existing Chemicals List. 16. OTHER INFORMATION GLOBAL HARMONIZATION, U.S. OSHA, JAPANESE JIS Z7253, EU REACH AND CLIP REGULATION (EC)1272/2208 AND THE TAIWAN REGULATION OF LABELING AND HAZARD COMMUNICATION OF DANGEROUS AND HARMFUL MATERIALS: This product has been classified per GHS Standards under U.S., European, Japanese and Taiwanese regulations. This product is and article and is not required to be classified under any regulations. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. REVISION DETAILS: May 5, 2017: Up -date SDS to include EU REACH and CLP 1272 compliance. REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: Specified Technologies, Inc DATE OF PRINTING: June 27, 2017 REVISED: May 5, 2017 EZPATH® SERIES 22 PATHWAY SDS EFFECTIVE DATE: MAY 5, 2017 Page 4 of 4 STI, SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, REACH, CLP 1272:2208 and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: EZ-Path21 Series 33 Pathway SYNONYMS: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME: Address: Business Phone: Emergency Phone: None Intumescent Sealing Devise Other than Relevant Use Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of Competent Person for Information on SDS: techservBstifirestoD.com ALL United States Occupational Safety and Health Administration (OSHA) Standard, 29 CFR Parts 1910, 1915, 1917, 1918 and 1926, and the U.S. OSHA Instruction CPL 02-02-079, July 9, 2015, U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], European Union REACH and CLP EC 1272/2008, Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7253 required information is included in appropriate sections based on the Global Harmonization Standard (GHS). This product has been classified in accordance with the hazard criteria of the countries listed above. This product is defined as an "Article" under the U.S. Federal OSHA Hazard Communication Standard (29 CFR 1910.1200), EU Directives, and the Canadian Workplace Hazardous Materials Standard. Refer to Section 15 (Regulatory Information) for specific regulatory citations. As articles, this product presents negligible health and physical hazards under reasonably anticipated circumstances of use. Subsequently, a Safety Data Sheet is not required under Standards cited above. This document is prepared to provide persons using this product with additional safety information. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND EU CLP REGULATION (EC) 1272/2008 LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under CLP Regulation (EC) 1272/2008. EU 67/548/EEC LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under European Community Council Directive 67/548/EEC or subsequent Directives. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. 3. COMPOSITION and INFORMATION ON INGREDIENTS This product is an article that does not contain any "Substances of Very High Concern". 4. FIRST -AID MEASURES DESCRIPTION OF FIRST AID MEASURES: This product is an article and under normal use conditions does not present health concerns. Skin Exposure: If mechanical irritation occurs, remove contaminated clothing and wash skin gently with soap and water. Inhalation: Not anticipated based on product form. Eve Exposure: If this product contaminated the eyes, rinse eyes under gently running water. Use sufficient force to open eyelids and the "roll" eyes while flushing. Minimum flushing is 20 minutes. Ingestion: Due to the form of the product, ingestion is unlikely. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: None known. INDICATION OF IMMEDIATE MEDICAL ATTENTION AND SPECIAL TREATMENT IF NEEDED: If any adverse reaction or discomfort continues from any of the above exposures, seek professional medical advice. EZ-Path® Series 33 Pathway SDS EFFECTIVE DATE: MAY 5, 2017 Page 1 of 4 aI::aalei: IIILI10Lyi :7*9 FLASH POINT: Not determined. AUTOIGNITION TEMPERATURE: Not available. FLAMMABLE LIMITS (in air by volume, %): Not applicable. FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. When involved in a fire, this material may decompose and produce irritating vapors and toxic gases (e.g., carbon, nitrogen and metal oxides, phthalates, ammonia, formaldehyde, hydrogen cyanide, nitriles, isocyanates, nitrosamines, hydrogen chloride, and acrylic monomers). Explosion Sensitivity to Mechanical Impact or Static Discharge: Not sensitive. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: In large fires in poorly ventilated areas involving packaging materials respiratory protection / breathing apparatus may be required. [:�_Td61l174LIkIFTIM►Ti0*1 PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Under normal handling conditions an accidental release is highly unlikely. Uncontrolled releases should be responded to by trained personnel. PERSONAL PROTECTIVE EQUIPMENT: Use personal protection recommended in Section 8 of the SDS METHODS FOR CLEAN-UP AND CONTAINMENT: As the product is an article, chemical components will not be released, therefore, spills are not anticipated. ENVIRONMENTAL PRECAUTIONS: As the product is an article, chemical components will not be released, therefore, spills are not anticipated. REFERENCE TO OTHER SECTIONS: See information in Section 8 (Exposure Controls — Personal Protection) and Section 13 (Disposal Considerations) for additional information. 7. HANDLING and USE PRECAUTIONS FOR SAFE HANDLING: As the product is an article, no precautions are necessary during normal use conditions. Avoid touching heated product. CONDITIONS FOR SAFE STORAGE: Store this product in a cool, dry location, away from sources of intense heat. Store away from water, heat and flame. SPECIFIC END USE(S): This product is an article made of formed Steel with Intumescent Fire -Retardant Gaskets Follow all industry standards for use of this product. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: This product is an article. No chemical components will be released from this product. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Galvanized steel form lined with a rubberized solid. pH: Not applicable. MOLECULAR FORMULA: Mixture. COLOR: Orange ODOR: Not available. MOLECULAR WEIGHT: Mixture FLAMMABLE LIMITS (in air by volume, %): Not available. ODOR THRESHOLD: Not available DECOMPOSITION TEMPERATURE: Not available. OXIDIZING PROPERTIES: Not applicable AUTOIGNITION TEMPERATURE: Not available. PERCENT VOLATILE: 0 FREEZING/MELTING POINT: Not available. FLASH POINT: Not available. VAPOR PRESSURE: Not applicable. BOILING POINT: Not applicable VAPOR DENSITY (air = 1): Not applicable. SPECIFIC GRAVITY (water = 1): Not applicable. EVAPORATION RATE (n-BuAc = 1): Not applicable. CARB VOC: Not applicable. SOLUBILITY IN WATER: Insoluble. SCAQMD (U.S. EPA Method 24): Not applicable. COEFFICIENT WATER/OIL DISTRIBUTION: Not SOLUBILITY IN SOLVENTS: Not applicable. applicable. HOW TO DETECT THIS SUBSTANCE (warning properties in event of accidental release): This product is an article. No chemical components will be released from this product. EZ-Path' Series 33 Pathway SDS EFFECTIVE DATE: MAY 5, 2017 Page 2 of 4 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is an article and stable when properly stored at normal temperature and pressures (see Section 7, Handling and Storage). DECOMPOSITION PRODUCTS: Combustion: If exposed to extremely high temperatures, thermal decomposition may generate irritating fumes and toxic gases (e.g., carbon, nitrogen and metal oxides, phthalates, ammonia, formaldehyde, hydrogen cyanide, nitriles, isocyanates, nitrosamines, hydrogen chloride, and acrylic monomers). Hydrolysis: None known. MATERIALS WITH WHICH SUBSTANCE IS INCOMPATIBLE: This product is incompatible with strong oxidizers. POSSIBILITY OF HAZARDOUS POLYMERIZATION OR REACTION: Will not occur. CONDITIONS TO AVOID: Avoid exposure to or contact with extreme temperatures and incompatible chemicals. 11. TOXICOLOGICAL INFORMATION This product is an article. No chemical components will be released from this product. 12. ECOLOGICAL INFORMATION This product is an article. No chemical components will be released from this product. 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: This product is an article. No chemical components will be released from this product. Dispose of in accordance with local, state, and federal laws and regulations. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. EUROPEAN AGREEMENT CONCERNING THE INTERNATIONAL CARRIAGE OF DANGEROUS GOODS BY ROAD A( DR): This product is not classified by the United Nations Economic Commission for Europe to be dangerous goods. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: As an article, this product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-211: ACUTE: No; CHRONIC: No; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): As an article, this product is not subject to Threshold Planning Quantities, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: This product is an article as defined by TSCA. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): No component is on the California Proposition 65 lists. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: As an article, this product is not subject the Controlled Product Regulations. EUROPEAN REGULATIONS: EZ-Path® Series 33 Pathway SDS EFFECTIVE DATE: MAY 5, 2017 Page 3 of 4 15. REGULATORY INFORMATION (continued) Safety, Health, and Environmental Regulations/Legislation Specific for the Product This product is an article that does not contain any "Substances of Very High Concern". CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: As an article, this product is not subjected to requirements under the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: As an article, this product is not subjected to requirements under ENCS Inventory. Japanese Ministry of Economy, Trade, and Industry (METI) Status: As an article, this product is not subjected to requirements under the Japanese METI. Poisonous and Deleterious Substances Control Law: As an article, this product is not subjected to requirements under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: As an article, this product is not subjected to requirements under the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is not classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: As an article, this product is not subjected to requirements under the Singapore List of Controlled Substances. Code of Practice On Pollution Control Requirements: As an article, this product is not subjected to requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: As an article, this product is not subjected to requirements under the Taiwan Existing Chemicals List. 16. OTHER INFORMATION GLOBAL HARMONIZATION, U.S. OSHA, JAPANESE JIS Z7253, EU REACH AND CLIP REGULATION (EC)1272/2208 AND THE TAIWAN REGULATION OF LABELING AND HAZARD COMMUNICATION OF DANGEROUS AND HARMFUL MATERIALS: This product has been classified per GHS Standards under U.S., European, Japanese and Taiwanese regulations. This product is and article and is not required to be classified under any regulations. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. REVISION DETAILS: May 5, 2017: Up -date SDS to include EU REACH and CLP 1272 compliance. REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: Specified Technologies, Inc DATE OF PRINTING: July 11, 2017 REVISED: May 5, 2017 EZ-Path® Series 33 Pathway SIDS EFFECTIVE DATE: MAY 5, 2017 Page 4 of 4 STI, SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, REACH, CLP 1272:2208 and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: EZ-Path° Series 44+ Pathway SYNONYMS: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME: Address: Business Phone: Emergency Phone: None Intumescent Sealing Devise Other than Relevant Use Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of ComDetent Person for Information on SDS: techservBstifirestoo.com ALL United States Occupational Safety and Health Administration (OSHA) Standard, 29 CFR Parts 1910, 1915, 1917, 1918 and 1926, and the U.S. OSHA Instruction CPL 02-02-079, July 9, 2015, U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], European Union REACH and CLP EC 1272/2008, Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7253 required information is included in appropriate sections based on the Global Harmonization Standard (GHS). This product has been classified in accordance with the hazard criteria of the countries listed above. This product is defined as an "Article" under the U.S. Federal OSHA Hazard Communication Standard (29 CFR 1910.1200), EU Directives, and the Canadian Workplace Hazardous Materials Standard. Refer to Section 15 (Regulatory Information) for specific regulatory citations. As articles, this product presents negligible health and physical hazards under reasonably anticipated circumstances of use. Subsequently, a Safety Data Sheet is not required under Standards cited above. This document is prepared to provide persons using this product with additional safety information. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND EU CLP REGULATION (EC) 1272/2008 LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under CLP Regulation (EC) 1272/2008. EU 67/548/EEC LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under European Community Council Directive 67/548/EEC or subsequent Directives. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. 3. COMPOSITION and INFORMATION ON INGREDIENTS This product is an article that does not contain any "Substances of Very High Concern". 4. FIRST -AID MEASURES DESCRIPTION OF FIRST AID MEASURES: This product is an article and under normal use conditions does not present health concerns. Skin Exposure: If mechanical irritation occurs, remove contaminated clothing and wash skin gently with soap and water. Inhalation: Not anticipated based on product form. Eve Exposure: If this product contaminated the eyes, rinse eyes under gently running water. Use sufficient force to open eyelids and the "roll" eyes while flushing. Minimum flushing is 20 minutes. Ingestion: Due to the form of the product, ingestion is unlikely. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: None known. INDICATION OF IMMEDIATE MEDICAL ATTENTION AND SPECIAL TREATMENT IF NEEDED: If any adverse reaction or discomfort continues from any of the above exposures, seek professional medical advice. EZPATH® SERIES 44+ PATHWAY SIDS EFFECTIVE DATE: MAY 5, 2017 Page 1 of 4 41 a I N :a a lei : I I I LI 10 Lyi I :7*9 FLASH POINT: Not determined. AUTOIGNITION TEMPERATURE: Not available. FLAMMABLE LIMITS (in air by volume, %): Not applicable. FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. When involved in a fire, this material may decompose and produce irritating vapors and toxic gases (e.g., carbon, nitrogen and metal oxides, phthalates, ammonia, formaldehyde, hydrogen cyanide, nitriles, isocyanates, nitrosamines, hydrogen chloride, and acrylic monomers). Explosion Sensitivity to Mechanical Impact or Static Discharge: Not sensitive. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: In large fires in poorly ventilated areas involving packaging materials respiratory protection / breathing apparatus may be required. 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Under normal handling conditions an accidental release is highly unlikely. Uncontrolled releases should be responded to by trained personnel. PERSONAL PROTECTIVE EQUIPMENT: Use personal protection recommended in Section 8 of the SDS METHODS FOR CLEAN-UP AND CONTAINMENT: As the product is an article, chemical components will not be released, therefore, spills are not anticipated. ENVIRONMENTAL PRECAUTIONS: As the product is an article, chemical components will not be released, therefore, spills are not anticipated. REFERENCE TO OTHER SECTIONS: See information in Section 8 (Exposure Controls — Personal Protection) and Section 13 (Disposal Considerations) for additional information. 7. HANDLING and USE PRECAUTIONS FOR SAFE HANDLING: As the product is an article, no precautions are necessary during normal use conditions. Avoid touching heated product. CONDITIONS FOR SAFE STORAGE: Store this product in a cool, dry location, away from sources of intense heat. Store away from water, heat and flame. SPECIFIC END USE(S): This product is an article made of formed Steel with Intumescent Fire -Retardant Gaskets Follow all industry standards for use of this product. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: This product is an article. No chemical components will be released from this product. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Galvanized steel form lined with a rubberized solid. pH: Not applicable. MOLECULAR FORMULA: Mixture. COLOR: Orange ODOR: Not available. MOLECULAR WEIGHT: Mixture FLAMMABLE LIMITS (in air by volume, %): Not available. ODOR THRESHOLD: Not available DECOMPOSITION TEMPERATURE: Not available. OXIDIZING PROPERTIES: Not applicable AUTOIGNITION TEMPERATURE: Not available. PERCENT VOLATILE: 0 FREEZING/MELTING POINT: Not available. FLASH POINT: Not available. VAPOR PRESSURE: Not applicable. BOILING POINT: Not applicable VAPOR DENSITY (air = 1): Not applicable. SPECIFIC GRAVITY (water = 1): Not applicable. EVAPORATION RATE (n-BuAc = 1): Not applicable. CARB VOC: Not applicable. SOLUBILITY IN WATER: Insoluble. SCAQMD (U.S. EPA Method 24): Not applicable. COEFFICIENT WATER/OIL DISTRIBUTION: Not SOLUBILITY IN SOLVENTS: Not applicable. applicable. HOW TO DETECT THIS SUBSTANCE (warning properties in event of accidental release): This product is an article. No chemical components will be released from this product. EZPATH° SERIES 44+ PATHWAY SDS EFFECTIVE DATE: MAY 5, 2017 Page 2 of 4 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is an article and stable when properly stored at normal temperature and pressures (see Section 7, Handling and Storage). DECOMPOSITION PRODUCTS: Combustion: If exposed to extremely high temperatures, thermal decomposition may generate irritating fumes and toxic gases (e.g., carbon, nitrogen and metal oxides, phthalates, ammonia, formaldehyde, hydrogen cyanide, nitriles, isocyanates, nitrosamines, hydrogen chloride, and acrylic monomers). Hydrolysis: None known. MATERIALS WITH WHICH SUBSTANCE IS INCOMPATIBLE: This product is incompatible with strong oxidizers. POSSIBILITY OF HAZARDOUS POLYMERIZATION OR REACTION: Will not occur. CONDITIONS TO AVOID: Avoid exposure to or contact with extreme temperatures and incompatible chemicals. 11. TOXICOLOGICAL INFORMATION This product is an article. No chemical components will be released from this product. 12. ECOLOGICAL INFORMATION This product is an article. No chemical components will be released from this product. 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: This product is an article. No chemical components will be released from this product. Dispose of in accordance with local, state, and federal laws and regulations. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. EUROPEAN AGREEMENT CONCERNING THE INTERNATIONAL CARRIAGE OF DANGEROUS GOODS BY ROAD A( DR): This product is not classified by the United Nations Economic Commission for Europe to be dangerous goods. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: As an article, this product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-211: ACUTE: No; CHRONIC: No; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): As an article, this product is not subject to Threshold Planning Quantities, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: This product is an article as defined by TSCA. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): No component is on the California Proposition 65 lists. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: As an article, this product is not subject the Controlled Product Regulations. EUROPEAN REGULATIONS: EZPATH® SERIES 44+ PATHWAY SDS EFFECTIVE DATE: MAY 5, 2017 Page 3 of 4 15. REGULATORY INFORMATION (continued) Safety, Health, and Environmental Regulations/Legislation Specific for the Product This product is an article that does not contain any "Substances of Very High Concern". CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: As an article, this product is not subjected to requirements under the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: As an article, this product is not subjected to requirements under ENCS Inventory. Japanese Ministry of Economy, Trade, and Industry (METI) Status: As an article, this product is not subjected to requirements under the Japanese METI. Poisonous and Deleterious Substances Control Law: As an article, this product is not subjected to requirements under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: As an article, this product is not subjected to requirements under the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is not classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: As an article, this product is not subjected to requirements under the Singapore List of Controlled Substances. Code of Practice On Pollution Control Requirements: As an article, this product is not subjected to requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: As an article, this product is not subjected to requirements under the Taiwan Existing Chemicals List. 16. OTHER INFORMATION GLOBAL HARMONIZATION, U.S. OSHA, JAPANESE JIS Z7253, EU REACH AND CLP REGULATION (EC)1272/2208 AND THE TAIWAN REGULATION OF LABELING AND HAZARD COMMUNICATION OF DANGEROUS AND HARMFUL MATERIALS: This product has been classified per GHS Standards under U.S., European, Japanese and Taiwanese regulations. This product is and article and is not required to be classified under any regulations. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. REVISION DETAILS: May 5, 2017: Up -date SDS to include EU REACH and CLP 1272 compliance. REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: Specified Technologies, Inc DATE OF PRINTING: June 27, 2017 REVISED: May 5, 2017 EZPATH® SERIES 44+ PATHWAY SIDS EFFECTIVE DATE: MAY 5, 2017 Page 4 of 4 STI, SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, REACH, CLP 1272:2208 and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: EZ-Path°Retrofit Device SYNONYMS: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME: Address: Business Phone: Emergency Phone: None Intumescent Sealing Devise Other than Relevant Use Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of ComDetent Person for Information on SDS: techservBstifirestoo.com ALL United States Occupational Safety and Health Administration (OSHA) Standard, 29 CFR Parts 1910, 1915, 1917, 1918 and 1926, and the U.S. OSHA Instruction CPL 02-02-079, July 9, 2015, U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], European Union REACH and CLP EC 1272/2008, Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7253 required information is included in appropriate sections based on the Global Harmonization Standard (GHS). This product has been classified in accordance with the hazard criteria of the countries listed above. This product is defined as an "Article" under the U.S. Federal OSHA Hazard Communication Standard (29 CFR 1910.1200), EU Directives, and the Canadian Workplace Hazardous Materials Standard. Refer to Section 15 (Regulatory Information) for specific regulatory citations. As articles, this product presents negligible health and physical hazards under reasonably anticipated circumstances of use. Subsequently, a Safety Data Sheet is not required under Standards cited above. This document is prepared to provide persons using this product with additional safety information. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND EU CLP REGULATION (EC) 1272/2008 LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under CLP Regulation (EC) 1272/2008. EU 67/548/EEC LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under European Community Council Directive 67/548/EEC or subsequent Directives. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. 3. COMPOSITION and INFORMATION ON INGREDIENTS This product is an article that does not contain any "Substances of Very High Concern". 4. FIRST -AID MEASURES DESCRIPTION OF FIRST AID MEASURES: This product is an article and under normal use conditions does not present health concerns. Skin Exposure: If mechanical irritation occurs, remove contaminated clothing and wash skin gently with soap and water. Inhalation: Not anticipated based on product form. Eve Exposure: If this product contaminated the eyes, rinse eyes under gently running water. Use sufficient force to open eyelids and the "roll" eyes while flushing. Minimum flushing is 20 minutes. Ingestion: Due to the form of the product, ingestion is unlikely. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: None known. INDICATION OF IMMEDIATE MEDICAL ATTENTION AND SPECIAL TREATMENT IF NEEDED: If any adverse reaction or discomfort continues from any of the above exposures, seek professional medical advice. 5. FIRE -FIGHTING MEASURES FLASH POINT: Not determined. AUTOIGNITION TEMPERATURE: Not available. FLAMMABLE LIMITS (in air by volume, %): Not applicable. FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. When involved in a fire, this material may decompose and produce irritating vapors and toxic gases (e.g., carbon, nitrogen and metal oxides, phthalates, ammonia, formaldehyde, hydrogen cyanide, nitriles, isocyanates, nitrosamines, hydrogen chloride, and acrylic monomers). Explosion Sensitivity to Mechanical Impact or Static Discharge: Not sensitive. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: In large fires in poorly ventilated areas involving packaging materials respiratory protection / breathing apparatus may be required. EZ-Path®Retrofit Device SIDS EFFECTIVE DATE: MAY 5, 2017 Page 1 of 4 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Under normal handling conditions an accidental release is highly unlikely. Uncontrolled releases should be responded to by trained personnel. PERSONAL PROTECTIVE EQUIPMENT: Use personal protection recommended in Section 8 of the SDS METHODS FOR CLEAN-UP AND CONTAINMENT: As the product is an article, chemical components will not be released, therefore, spills are not anticipated. ENVIRONMENTAL PRECAUTIONS: As the product is an article, chemical components will not be released, therefore, spills are not anticipated. REFERENCE TO OTHER SECTIONS: See information in Section 8 (Exposure Controls — Personal Protection) and Section 13 (Disposal Considerations) for additional information. 7. HANDLING and USE PRECAUTIONS FOR SAFE HANDLING: As the product is an article, no precautions are necessary during normal use conditions. Avoid touching heated product. CONDITIONS FOR SAFE STORAGE: Store this product in a cool, dry location, away from sources of intense heat. Store away from water, heat and flame. SPECIFIC END USE(S): This product is an article made of formed Steel with Intumescent Fire -Retardant Gaskets Follow all industry standards for use of this product. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: This product is an article. No chemical components will be released from this product. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Galvanized steel form lined with a rubberized solid. pH: Not applicable. MOLECULAR FORMULA: Mixture. COLOR: Orange ODOR: Not available. MOLECULAR WEIGHT: Mixture FLAMMABLE LIMITS (in air by volume, %): Not available. ODOR THRESHOLD: Not available DECOMPOSITION TEMPERATURE: Not available. OXIDIZING PROPERTIES: Not applicable AUTOIGNITION TEMPERATURE: Not available. PERCENT VOLATILE: 0 FREEZING/MELTING POINT: Not available. FLASH POINT: Not available. VAPOR PRESSURE: Not applicable. BOILING POINT: Not applicable VAPOR DENSITY (air = 1): Not applicable. SPECIFIC GRAVITY (water = 1): Not applicable. EVAPORATION RATE (n-BuAc = 1): Not applicable. CARB VOC: Not applicable. SOLUBILITY IN WATER: Insoluble. SCAQMD (U.S. EPA Method 24): Not applicable. COEFFICIENT WATER/OIL DISTRIBUTION: Not SOLUBILITY IN SOLVENTS: Not applicable. applicable. HOW TO DETECT THIS SUBSTANCE (warning properties in event of accidental release): This product is an article. No chemical components will be released from this product. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is an article and stable when properly stored at normal temperature and pressures (see Section 7, Handling and Storage). DECOMPOSITION PRODUCTS: Combustion: If exposed to extremely high temperatures, thermal decomposition may generate irritating fumes and toxic gases (e.g., carbon, nitrogen and metal oxides, phthalates, ammonia, formaldehyde, hydrogen cyanide, nitriles, isocyanates, nitrosamines, hydrogen chloride, and acrylic monomers). Hydrolysis: None known. MATERIALS WITH WHICH SUBSTANCE IS INCOMPATIBLE: This product is incompatible with strong oxidizers. POSSIBILITY OF HAZARDOUS POLYMERIZATION OR REACTION: Will not occur. CONDITIONS TO AVOID: Avoid exposure to or contact with extreme temperatures and incompatible chemicals. 11. TOXICOLOGICAL INFORMATION This product is an article. No chemical components will be released from this product. 12. ECOLOGICAL INFORMATION This product is an article. No chemical components will be released from this product. 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: This product is an article. No chemical components will be released from this product. Dispose of in accordance with local, state, and federal laws and regulations. EZ-Path®Retrofit Device SDS EFFECTIVE DATE: MAY 5, 2017 Page 2 of 4 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. EUROPEAN AGREEMENT CONCERNING THE INTERNATIONAL CARRIAGE OF DANGEROUS GOODS BY ROAD ADR : This product is not classified by the United Nations Economic Commission for Europe to be dangerous goods. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: As an article, this product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-211: ACUTE: No; CHRONIC: No; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): As an article, this product is not subject to Threshold Planning Quantities, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: This product is an article as defined by TSCA. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): No component is on the California Proposition 65 lists. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: As an article, this product is not subject the Controlled Product Regulations. EUROPEAN REGULATIONS: Safety, Health, and Environmental Regulations/Legislation Specific for the Product This product is an article that does not contain any "Substances of Very High Concern". CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: As an article, this product is not subjected to requirements under the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: As an article, this product is not subjected to requirements under ENCS Inventory. Japanese Ministry of Economy, Trade, and Industry (METI) Status: As an article, this product is not subjected to requirements under the Japanese METI. Poisonous and Deleterious Substances Control Law: As an article, this product is not subjected to requirements under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: As an article, this product is not subjected to requirements under the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is not classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: As an article, this product is not subjected to requirements under the Singapore List of Controlled Substances. Code of Practice On Pollution Control Requirements: As an article, this product is not subjected to requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: As an article, this product is not subjected to requirements under the Taiwan Existing Chemicals List. EZ-Path®Retrofit Device SDS EFFECTIVE DATE: MAY 5, 2017 Page 3 of 4 16. OTHER INFORMATION GLOBAL HARMONIZATION, U.S. OSHA, JAPANESE JIS Z7253, EU REACH AND CLP REGULATION (EC) 1272/2208 AND THE TAIWAN REGULATION OF LABELING AND HAZARD COMMUNICATION OF DANGEROUS AND HARMFUL MATERIALS: This product has been classified per GHS Standards under U.S., European, Japanese and Taiwanese regulations. This product is and article and is not required to be classified under any regulations. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. REVISION DETAILS: May 5, 2017: Up -date SDS to include EU REACH and CLIP 1272 compliance. REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: Specified Technologies, Inc DATE OF PRINTING: June 27, 2017 REVISED: May 5, 2017 EZ-Path®Retrofit Device SDS EFFECTIVE DATE: MAY 5, 2017 Page 4 of 4 2V6 STI SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME Address: Business Phone: Emergency Phone: SpecSeal° LCC Intumescent FireStop Collars Firestop Device None Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of Competent Person for Information on SDS: techserv(a)stifirestop.com NOTE: ALL United States Occupational Safety and Health Administration Standard (29 CFR 1910.1200), U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7250 required information is included in appropriate sections based on the U.S. ANSI Z400.1-2010 format. This product has been classified in accordance with the hazard criteria of the countries listed above. This product is defined as an "Article' under the U.S. Federal OSHA Hazard Communication Standard (29 CFR 1910.1200), EU Directives, and the Canadian Workplace Hazardous Materials Standard. Refer to Section 15 (Regulatory Information) for specific regulatory citations. As articles, this product presents negligible health and physical hazards under reasonably anticipated circumstances of use. Subsequently, a Material Safety Data Sheet is not required under Standards cited above. This document is prepared to provide persons using this product with additional safety information. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND EU CLP REGULATION (EC) 1272/2008 LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under CLP Regulation (EC) 1272/2008. EU 67/548/EEC LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under European Community Council Directive 67/548/EEC or subsequent Directives. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. 3. COMPOSITION and INFORMATION ON INGREDIENTS This product is an article and as such no components of this product pose a hazard; no component information is given in this SDS. 4. FIRST -AID MEASURES Skin Exposure: As an article, no need for first aid is anticipated. Inhalation: As an article, no need for first aid is anticipated. Eve Exposure: As an article, no need for first aid is anticipated. Ingestion: As an article, no need for first aid is anticipated. 5. FIRE -FIGHTING MEASURES FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: No Special protective actions for fire-fighters are anticipated. SPECSEAL° LCC Intumescent FireStop Collars SDS EFFECTIVE DATE: MAY12,2017 PAGE 1 OF 4 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Not applicable. PERSONAL PROTECTIVE EQUIPMENT: Not applicable. METHODS FOR CLEAN-UP AND CONTAINMENT: Not applicable. ENVIRONMENTAL PRECAUTIONS: Not applicable. 7. HANDLING and STORAGE PRECAUTIONS FOR SAFE HANDLING: No special requirements. CONDITIONS FOR SAFE STORAGE: No special requirements. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: As an article which does not release or otherwise result in exposure to hazardous chemicals under normal use, no personal protective equipment (PPE) is required. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Galvanized metal ring liner with a solid. ODOR: Not available. FLAMMABLE LIMITS (in air by volume, %): Not available. DECOMPOSITION TEMPERATURE: Not available. AUTOIGNITION TEMPERATURE: Not available. FREEZING/MELTING POINT: Not available. VAPOR PRESSURE: Not applicable. VAPOR DENSITY (air = 1): Not applicable. EVAPORATION RATE (n-BuAc = 1): Not applicable. SOLUBILITY IN WATER: Insoluble. COEFFICIENT WATER/OIL DISTRIBUTION: Not established COLOR: Multiple. ODOR THRESHOLD: Not available. OXIDIZING PROPERTIES: Not applicable. PERCENT VOLATILE: 0 FLASH POINT: Not available. BOILING POINT: Not applicable. SPECIFIC GRAVITY (water = 1): Not applicable. CARB VOC: Not applicable. SCAQMD (U.S. EPA Method 24): Not applicable. SOLUBILITY IN SOLVENTS: Not applicable. pH: Not applicable. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is stable when properly stored at normal temperatures. 11. TOXICOLOGICAL INFORMATION SYMPTOMS OF EXPOSURE BY ROUTE OF EXPOSURE: Inhalation: Due to the form of the product, inhalation is unlikely. Contact with Skin or Eves: Due to the form of the product, contact with the eyes is unlikely Skin Absorption: Due to form of product, skin absorption is not a likely route of exposure. Ingestion: Ingestion is not a likely route of exposure, due to the form of the product. Infection: Injection is not likely, due to the form of the product. 12. ECOLOGICAL INFORMATION MOBILITY: As an article, this product will not be mobile in soil. PERSISTENCE AND BIODEGRADABILITY: No specific information is available regarding persistence and biodegradability. BIO-ACCUMULATION POTENTIAL: This product has not been tested for bio-accumulation potential. ECOTOXICITY: This product has not been tested for aquatic or animal toxicity. All releases to terrestrial, atmospheric and aquatic environments should be avoided. SPECSEAL° LCC Intumescent FireStop Collars SDS EFFECTIVE DATE: MAY12,2017 PAGE 2 OF 4 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: Waste disposal must be in accordance with appropriate Federal, State, and local regulations. U.S. EPA WASTE NUMBER: Not applicable. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: As an article, this product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-21): ACUTE: No; CHRONIC: No; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): As an article, this product is not subject to Threshold Planning Quantities, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: Components of this product are listed on the TSCA Inventory. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): No component is on the California Proposition 65 lists. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: As an article, this product is not subject the Controlled Product Regulations. CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: As an article, this product is not subjected to requirements under the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: As an article, this product is not subjected to requirements under ENCS Inventory. Japanese Ministry of Economy. Trade, and Industry (METI) Status: As an article, this product is not subjected to requirements under the Japanese METI. Poisonous and Deleterious Substances Control Law: As an article, this product is not subjected to requirements under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: As an article, this product is not subjected to requirements under the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is not classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: As an article, this product is not subjected to requirements under the Singapore List of Controlled Substances. Code of Practice on Pollution Control Requirements: As an article, this product is not subjected to requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: As an article, this product is not subjected to requirements under the Taiwan Existing Chemicals List. SPECSEAL° LCC Intumescent FireStop Collars SDS EFFECTIVE DATE: MAY12,2017 PAGE 3 OF 4 16. OTHER INFORMATION REVISION DETAILS: Updated May 12, 2017, no changes necessary. REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: CHEMICAL SAFETY ASSOCIATES, Inc. • PO Box 1961, Hilo, HI 96721-1961 • (800) 441-3365 DATE OF PRINTING: June 29, 2017 REVISION HISTORY: May 12,2017 SPECSEAL° LCC Intumescent FireStop Collars SIDS EFFECTIVE DATE: MAY12,2017 PAGE 4 OF 4 2V6 STI SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME Address: Business Phone: Emergency Phone: SpecSeal° RTC Range -Taking FireStop Collars Firestop Device None Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of ComDetent Person for Information on SDS: techsery anstifirestOD.com NOTE: ALL United States Occupational Safety and Health Administration Standard (29 CFR 1910.1200), U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7250 required information is included in appropriate sections based on the U.S. ANSI Z400.1-2010 format. This product has been classified in accordance with the hazard criteria of the countries listed above. This product is defined as an "Article" under the U.S. Federal OSHA Hazard Communication Standard (29 CFR 1910.1200), EU Directives, and the Canadian Workplace Hazardous Materials Standard. Refer to Section 15 (Regulatory Information) for specific regulatory citations. As articles, this product presents negligible health and physical hazards under reasonably anticipated circumstances of use. Subsequently, a Material Safety Data Sheet is not required under Standards cited above. This document is prepared to provide persons using this product with additional safety information. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND EU CLP REGULATION (EC) 1272/2008 LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under CLP Regulation (EC) 1272/2008. EU 67/548/EEC LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under European Community Council Directive 67/548/EEC or subsequent Directives. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. 3. COMPOSITION and INFORMATION ON INGREDIENTS This product is an article and as such no components of this product pose a hazard; no component information is given in this SDS. 4. FIRST -AID MEASURES Skin Exposure: As an article, no need for first aid is anticipated. Inhalation: As an article, no need for first aid is anticipated. Eve Exposure: As an article, no need for first aid is anticipated. Ingestion: As an article, no need for first aid is anticipated. 5. FIRE -FIGHTING MEASURES FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: No Special protective actions for fire-fighters are anticipated. SPECSEAL° RTC RANGE -TAKING FIRESTOP COLLARS SDS EFFECTIVE DATE: MAY12,2017 PAGE 1 OF 4 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Not applicable. PERSONAL PROTECTIVE EQUIPMENT: Not applicable. METHODS FOR CLEAN-UP AND CONTAINMENT: Not applicable. ENVIRONMENTAL PRECAUTIONS: Not applicable. 7. HANDLING and STORAGE PRECAUTIONS FOR SAFE HANDLING: No special requirements. CONDITIONS FOR SAFE STORAGE: No special requirements. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: As an article which does not release or otherwise result in exposure to hazardous chemicals under normal use, no personal protective equipment (PPE) is required. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Galvanized metal ring liner with a solid. ODOR: Not available. FLAMMABLE LIMITS (in air by volume, %): Not available. DECOMPOSITION TEMPERATURE: Not available. AUTOIGNITION TEMPERATURE: Not available. FREEZING/MELTING POINT: Not available. VAPOR PRESSURE: Not applicable. VAPOR DENSITY (air = 1): Not applicable. EVAPORATION RATE (n-BuAc = 1): Not applicable. SOLUBILITY IN WATER: Insoluble. COEFFICIENT WATER/OIL DISTRIBUTION: Not established COLOR: Multiple. ODOR THRESHOLD: Not available. OXIDIZING PROPERTIES: Not applicable. PERCENT VOLATILE: 0 FLASH POINT: Not available. BOILING POINT: Not applicable. SPECIFIC GRAVITY (water = 1): Not applicable. CARB VOC: Not applicable. SCAQMD (U.S. EPA Method 24): Not applicable. SOLUBILITY IN SOLVENTS: Not applicable. pH: Not applicable. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is stable when properly stored at normal temperatures. 11. TOXICOLOGICAL INFORMATION SYMPTOMS OF EXPOSURE BY ROUTE OF EXPOSURE: Inhalation: Due to the form of the product, inhalation is unlikely. Contact with Skin or Eves: Due to the form of the product, contact with the eyes is unlikely Skin Absorption: Due to form of product, skin absorption is not a likely route of exposure. Ingestion: Ingestion is not a likely route of exposure, due to the form of the product. Infection: Injection is not likely, due to the form of the product. 12. ECOLOGICAL INFORMATION MOBILITY: As an article, this product will not be mobile in soil. PERSISTENCE AND BIODEGRADABILITY: No specific information is available regarding persistence and biodegradability. BIO-ACCUMULATION POTENTIAL: This product has not been tested for bio-accumulation potential. ECOTOXICITY: This product has not been tested for aquatic or animal toxicity. All releases to terrestrial, atmospheric and aquatic environments should be avoided. SPECSEAL° RTC RANGE -TAKING FIRESTOP COLLARS SIDS EFFECTIVE DATE: MAY12,2017 PAGE 2 OF 4 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: Waste disposal must be in accordance with appropriate Federal, State, and local regulations. U.S. EPA WASTE NUMBER: Not applicable. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: As an article, this product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-21): ACUTE: No; CHRONIC: No; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): As an article, this product is not subject to Threshold Planning Quantities, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: Components of this product are listed on the TSCA Inventory. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): No component is on the California Proposition 65 lists. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: As an article, this product is not subject the Controlled Product Regulations. CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: As an article, this product is not subjected to requirements under the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: As an article, this product is not subjected to requirements under ENCS Inventory. Japanese Ministry of Economy. Trade, and Industry (METI) Status: As an article, this product is not subjected to requirements under the Japanese METI. Poisonous and Deleterious Substances Control Law: As an article, this product is not subjected to requirements under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: As an article, this product is not subjected to requirements under the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is not classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: As an article, this product is not subjected to requirements under the Singapore List of Controlled Substances. Code of Practice on Pollution Control Requirements: As an article, this product is not subjected to requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: As an article, this product is not subjected to requirements under the Taiwan Existing Chemicals List. SPECSEAL° RTC RANGE -TAKING FIRESTOP COLLARS SIDS EFFECTIVE DATE: MAY12,2017 PAGE 3 OF 4 16. OTHER INFORMATION REVISION DETAILS: Updated May 12, 2017, no changes necessary. REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: CHEMICAL SAFETY ASSOCIATES, Inc. • PO Box 1961, Hilo, HI 96721-1961 • (800) 441-3365 DATE OF PRINTING: June 29, 2017 REVISION HISTORY: May 12,2017 SPECSEA0 RTC RANGE -TAKING FIRESTOP COLLARS SDS EFFECTIVE DATE: MAY12,2017 PAGE 4 OF 4 2V6 STI SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME Address: Business Phone: Emergency Phone: SpecSeal° SCC FireStop Collars Firestop Device None Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of Competent Person for Information on SDS: techserv(a)stifirestop.com NOTE: ALL United States Occupational Safety and Health Administration Standard (29 CFR 1910.1200), U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7250 required information is included in appropriate sections based on the U.S. ANSI Z400.1-2010 format. This product has been classified in accordance with the hazard criteria of the countries listed above. This product is defined as an "Article' under the U.S. Federal OSHA Hazard Communication Standard (29 CFR 1910.1200), EU Directives, and the Canadian Workplace Hazardous Materials Standard. Refer to Section 15 (Regulatory Information) for specific regulatory citations. As articles, this product presents negligible health and physical hazards under reasonably anticipated circumstances of use. Subsequently, a Material Safety Data Sheet is not required under Standards cited above. This document is prepared to provide persons using this product with additional safety information. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND EU CLP REGULATION (EC) 1272/2008 LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under CLP Regulation (EC) 1272/2008. EU 67/548/EEC LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under European Community Council Directive 67/548/EEC or subsequent Directives. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. 3. COMPOSITION and INFORMATION ON INGREDIENTS This product is an article and as such no components of this product pose a hazard; no component information is given in this SDS. 4. FIRST -AID MEASURES Skin Exposure: As an article, no need for first aid is anticipated. Inhalation: As an article, no need for first aid is anticipated. Eve Exposure: As an article, no need for first aid is anticipated. Ingestion: As an article, no need for first aid is anticipated. 5. FIRE -FIGHTING MEASURES FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: No Special protective actions for fire-fighters are anticipated. SPECSEAL° SCC FireStop Collars SDS EFFECTIVE DATE: MAY12,2017 PAGE 1 OF 4 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Not applicable. PERSONAL PROTECTIVE EQUIPMENT: Not applicable. METHODS FOR CLEAN-UP AND CONTAINMENT: Not applicable. ENVIRONMENTAL PRECAUTIONS: Not applicable. 7. HANDLING and STORAGE PRECAUTIONS FOR SAFE HANDLING: No special requirements. CONDITIONS FOR SAFE STORAGE: No special requirements. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: As an article which does not release or otherwise result in exposure to hazardous chemicals under normal use, no personal protective equipment (PPE) is required. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Galvanized metal ring liner with a solid. ODOR: Not available. FLAMMABLE LIMITS (in air by volume, %): Not available. DECOMPOSITION TEMPERATURE: Not available. AUTOIGNITION TEMPERATURE: Not available. FREEZING/MELTING POINT: Not available. VAPOR PRESSURE: Not applicable. VAPOR DENSITY (air = 1): Not applicable. EVAPORATION RATE (n-BuAc = 1): Not applicable. SOLUBILITY IN WATER: Insoluble. COEFFICIENT WATER/OIL DISTRIBUTION: Not established COLOR: Multiple. ODOR THRESHOLD: Not available. OXIDIZING PROPERTIES: Not applicable. PERCENT VOLATILE: 0 FLASH POINT: Not available. BOILING POINT: Not applicable. SPECIFIC GRAVITY (water = 1): Not applicable. CARB VOC: Not applicable. SCAQMD (U.S. EPA Method 24): Not applicable. SOLUBILITY IN SOLVENTS: Not applicable. pH: Not applicable. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is stable when properly stored at normal temperatures. 11. TOXICOLOGICAL INFORMATION SYMPTOMS OF EXPOSURE BY ROUTE OF EXPOSURE: Inhalation: Due to the form of the product, inhalation is unlikely. Contact with Skin or Eves: Due to the form of the product, contact with the eyes is unlikely Skin Absorption: Due to form of product, skin absorption is not a likely route of exposure. Ingestion: Ingestion is not a likely route of exposure, due to the form of the product. Infection: Injection is not likely, due to the form of the product. 12. ECOLOGICAL INFORMATION MOBILITY: As an article, this product will not be mobile in soil. PERSISTENCE AND BIODEGRADABILITY: No specific information is available regarding persistence and biodegradability. BIO-ACCUMULATION POTENTIAL: This product has not been tested for bio-accumulation potential. ECOTOXICITY: This product has not been tested for aquatic or animal toxicity. All releases to terrestrial, atmospheric and aquatic environments should be avoided. SPECSEAL° SCC FireStop Collars SIDS EFFECTIVE DATE: MAY12,2017 PAGE 2 OF 4 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: Waste disposal must be in accordance with appropriate Federal, State, and local regulations. U.S. EPA WASTE NUMBER: Not applicable. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: As an article, this product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-21): ACUTE: No; CHRONIC: No; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): As an article, this product is not subject to Threshold Planning Quantities, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: Components of this product are listed on the TSCA Inventory. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): No component is on the California Proposition 65 lists. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: As an article, this product is not subject the Controlled Product Regulations. CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: As an article, this product is not subjected to requirements under the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: As an article, this product is not subjected to requirements under ENCS Inventory. Japanese Ministry of Economy. Trade, and Industry (METI) Status: As an article, this product is not subjected to requirements under the Japanese METI. Poisonous and Deleterious Substances Control Law: As an article, this product is not subjected to requirements under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: As an article, this product is not subjected to requirements under the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is not classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: As an article, this product is not subjected to requirements under the Singapore List of Controlled Substances. Code of Practice on Pollution Control Requirements: As an article, this product is not subjected to requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: As an article, this product is not subjected to requirements under the Taiwan Existing Chemicals List. SPECSEAL° SCC FireStop Collars SIDS EFFECTIVE DATE: MAY12,2017 PAGE 3 OF 4 16. OTHER INFORMATION REVISION DETAILS: Updated May 12, 2017, no changes necessary. REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: CHEMICAL SAFETY ASSOCIATES, Inc. • PO Box 1961, Hilo, HI 96721-1961 • (800) 441-3365 DATE OF PRINTING: June 29, 2017 REVISION HISTORY: May 12,2017 SPECSEAL° SCC FireStop Collars SDS EFFECTIVE DATE: MAY12,2017 PAGE 4 OF 4 �N/ STI. SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME: Address: Business Phone: Emergency Phone: SpecSeal° Intumescent Wrap Strips Blu 2 Firestop Device None Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (Collect-24 hrs) EMAIL of ComDetent Person for Information on SDS: techserv(a)stifirestOD.com NOTE: ALL United States Occupational Safety and Health Administration Standard (29 CFR 1910.1200), U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7250 required information is included in appropriate sections based on the U.S. ANSI Z400.1-2010 format. This product has been classified in accordance with the hazard criteria of the countries listed above. This product is defined as an "Article' under the U.S. Federal OSHA Hazard Communication Standard (29 CFR 1910.1200), EU Directives, and the Canadian Workplace Hazardous Materials Standard. Refer to Section 15 (Regulatory Information) for specific regulatory citations. As articles, this product presents negligible health and physical hazards under reasonably anticipated circumstances of use. Subsequently, a Material Safety Data Sheet is not required under Standards cited above. This document is prepared to provide persons using this product with additional safety information. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND EU CLP REGULATION (EC) 1272/2008 LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under CLP Regulation (EC) 1272/2008. EU 67/548/EEC LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under European Community Council Directive 67/548/EEC or subsequent Directives. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. 3. COMPOSITION and INFORMATION ON INGREDIENTS This product is an article and as such no components of this product pose a hazard; no component information is given in this SDS. 4. FIRST -AID MEASURES Skin Exposure: As an article, no need for first aid is anticipated. Inhalation: As an article, no need for first aid is anticipated. Eve Exposure: As an article, no need for first aid is anticipated. Ingestion: As an article, no need for first aid is anticipated. 5. FIRE -FIGHTING MEASURES FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: No Special protective actions for fire-fighters are anticipated. SPECSEAL° WRAP STRIPS BLU 2 SDS EFFECTIVE DATE: JULY 12, 2017 PAGE 1 OF 4 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Not applicable. PERSONAL PROTECTIVE EQUIPMENT: Not applicable. METHODS FOR CLEAN-UP AND CONTAINMENT: Not applicable. ENVIRONMENTAL PRECAUTIONS: Not applicable. 7. HANDLING and STORAGE PRECAUTIONS FOR SAFE HANDLING: No special requirements. CONDITIONS FOR SAFE STORAGE: No special requirements. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: As an article which does not release or otherwise result in exposure to hazardous chemicals under normal use, no personal protective equipment (PPE) is required. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Solid. ODOR: Not available. FLAMMABLE LIMITS (in air by volume, %): Not available. DECOMPOSITION TEMPERATURE: Not available. AUTOIGNITION TEMPERATURE: Not available. FREEZING/MELTING POINT: Not available. VAPOR PRESSURE: Not applicable. VAPOR DENSITY (air = 1): Not applicable. EVAPORATION RATE (n-BuAc = 1): Not applicable. SOLUBILITY IN WATER: Insoluble. COEFFICIENT WATER/OIL DISTRIBUTION: Not established COLOR: Black with Blue Label ODOR THRESHOLD: Not available. OXIDIZING PROPERTIES: Not applicable. PERCENT VOLATILE: 0 FLASH POINT: Not available. BOILING POINT: Not applicable. SPECIFIC GRAVITY (water = 1): Not applicable. CARB VOC: Not applicable. SCAQMD (U.S. EPA Method 24): Not applicable. SOLUBILITY IN SOLVENTS: Not applicable. pH: Not applicable. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is stable when properly stored at normal temperatures. 11. TOXICOLOGICAL INFORMATION SYMPTOMS OF EXPOSURE BY ROUTE OF EXPOSURE: Inhalation: Due to the form of the product, inhalation is unlikely. Contact with Skin or Eves: Due to the form of the product, contact with the eyes is unlikely Skin Absorption: Due to form of product, skin absorption is not a likely route of exposure. Ingestion: Ingestion is not a likely route of exposure, due to the form of the product. Infection: Injection is not likely, due to the form of the product. 12. ECOLOGICAL INFORMATION MOBILITY: As an article, this product will not be mobile in soil. PERSISTENCE AND BIODEGRADABILITY: No specific information is available regarding persistence and biodegradability. BIO-ACCUMULATION POTENTIAL: This product has not been tested for bio-accumulation potential. ECOTOXICITY: This product has not been tested for aquatic or animal toxicity. All releases to terrestrial, atmospheric and aquatic environments should be avoided. SPECSEAL° WRAP STRIPS BLU 2 SIDS EFFECTIVE DATE: JULY 12, 2017 PAGE 2 OF 4 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: Waste disposal must be in accordance with appropriate Federal, State, and local regulations. U.S. EPA WASTE NUMBER: Not applicable. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: As an article, this product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-21): ACUTE: No; CHRONIC: No; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): As an article, this product is not subject to Threshold Planning Quantities, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: Components of this product are listed on the TSCA Inventory. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): No component is on the California Proposition 65 lists. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: As an article, this product is not subject the Controlled Product Regulations. CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: As an article, this product is not subjected to requirements under the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: As an article, this product is not subjected to requirements under ENCS Inventory. Japanese Ministry of Economy, Trade, and Industry (METI) Status: As an article, this product is not subjected to requirements under the Japanese METI. Poisonous and Deleterious Substances Control Law: As an article, this product is not subjected to requirements under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: As an article, this product is not subjected to requirements under the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is not classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: As an article, this product is not subjected to requirements under the Singapore List of Controlled Substances. Code of Practice on Pollution Control Requirements: As an article, this product is not subjected to requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: As an article, this product is not subjected to requirements under the Taiwan Existing Chemicals List. SPECSEAL° WRAP STRIPS BLU 2 SIDS EFFECTIVE DATE: JULY 12, 2017 PAGE 3 OF 4 16. OTHER INFORMATION REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: CHEMICAL SAFETY ASSOCIATES, Inc. • PO Box 1961, Hilo, HI 96721-1961 • (800) 441-3365 DATE OF PRINTING: September 27, 2017 REVISED: July 12, 2017 REVISION DETAILS: Reviewed July 12, 2017, no changes. SPECSEAL° WRAP STRIPS BLU 2 SDS EFFECTIVE DATE: JULY 12, 2017 PAGE 4 OF 4 2V6 STI SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME: Address: Business Phone: Emergency Phone: SpecSeal° Red Wrap Strip Firestop Device None Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585(collect-24 hrs) EMAIL of COmDetent Person for Information on SDS: techsery anstifirestOD.com NOTE: ALL United States Occupational Safety and Health Administration Standard (29 CFR 1910.1200), U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7250 required information is included in appropriate sections based on the U.S. ANSI Z400.1-2010 format. This product has been classified in accordance with the hazard criteria of the countries listed above. This product is defined as an "Article" under the U.S. Federal OSHA Hazard Communication Standard (29 CFR 1910.1200), EU Directives, and the Canadian Workplace Hazardous Materials Standard. Refer to Section 15 (Regulatory Information) for specific regulatory citations. As articles, this product presents negligible health and physical hazards under reasonably anticipated circumstances of use. Subsequently, a Material Safety Data Sheet is not required under Standards cited above. This document is prepared to provide persons using this product with additional safety information. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND EU CLP REGULATION (EC) 1272/2008 LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under CLP Regulation (EC) 1272/2008. EU 67/548/EEC LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under European Community Council Directive 67/548/EEC or subsequent Directives. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. 3. COMPOSITION and INFORMATION ON INGREDIENTS This product is an article and as such no components of this product pose a hazard; no component information is given in this SDS. 4. FIRST -AID MEASURES Skin Exposure: As an article, no need for first aid is anticipated. Inhalation: As an article, no need for first aid is anticipated. Eve Exposure: As an article, no need for first aid is anticipated. Ingestion: As an article, no need for first aid is anticipated. 5. FIRE -FIGHTING MEASURES FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: No Special protective actions for fire-fighters are anticipated. SPECSEAL' RED WRAP STRIP SDS EFFECTIVE DATE: SEPTEMBER 7, 2017 PAGE 1 OF 4 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Not applicable. PERSONAL PROTECTIVE EQUIPMENT: Not applicable. METHODS FOR CLEAN-UP AND CONTAINMENT: Not applicable. ENVIRONMENTAL PRECAUTIONS: Not applicable. 7. HANDLING and STORAGE PRECAUTIONS FOR SAFE HANDLING: No special requirements. CONDITIONS FOR SAFE STORAGE: No special requirements. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: As an article which does not release or otherwise result in exposure to hazardous chemicals under normal use; no personal protective equipment (PPE) are required. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Solid. ODOR: Not available. FLAMMABLE LIMITS (in air by volume, %): Not available. DECOMPOSITION TEMPERATURE: Not available. AUTOIGNITION TEMPERATURE: Not available. FREEZING/MELTING POINT: Not applicable. VAPOR PRESSURE: Not applicable. VAPOR DENSITY (air = 1): Not applicable. EVAPORATION RATE (n-BuAc = 1): Not applicable. SOLUBILITY IN WATER: Insoluble. COEFFICIENT WATER/OIL DISTRIBUTION: Not applicable COLOR: Black with Red Label. ODOR THRESHOLD: Not available. OXIDIZING PROPERTIES: Not applicable. PERCENT VOLATILE: 0 FLASH POINT: Not available. BOILING POINT: Not applicable. SPECIFIC GRAVITY (water = 1): Not applicable. CARB VOC: Not applicable. SCAQMD (U.S. EPA Method 24): Not applicable. SOLUBILITY IN SOLVENTS: Not applicable. pH: Not applicable. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is stable when properly stored at normal temperatures. 11. TOXICOLOGICAL INFORMATION SYMPTOMS OF EXPOSURE BY ROUTE OF EXPOSURE: Inhalation: Due to the form of the product, inhalation is unlikely. Contact with Skin or Eves: Due to the form of the product, contact with the eyes is unlikely Skin Absorption: Due to form of product, skin absorption is not a likely route of exposure. Ingestion: Ingestion is not a likely route of exposure, due to the form of the product. Infection: Injection is not likely, due to the form of the product. 12. ECOLOGICAL INFORMATION MOBILITY: As an article, this product will not be mobile in soil. PERSISTENCE AND BIODEGRADABILITY: No specific information is available regarding persistence and biodegradability. BIO-ACCUMULATION POTENTIAL: This product has not been tested for bio-accumulation potential. ECOTOXICITY: This product has not been tested for aquatic or animal toxicity. All releases to terrestrial, atmospheric and aquatic environments should be avoided. SPECSEAL' RED WRAP STRIP SDS EFFECTIVE DATE: SEPTEMBER 7, 2017 PAGE 2 OF 4 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: Waste disposal must be in accordance with appropriate Federal, State, and local regulations. U.S. EPA WASTE NUMBER: Not applicable. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: As an article, this product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-21): ACUTE: No; CHRONIC: No; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): As an article, this product is not subject to Threshold Planning Quantities, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: Components of this product are listed on the TSCA Inventory. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): No component is on the California Proposition 65 lists. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: As an article, this product is not subject the Controlled Product Regulations. CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: As an article, this product is not subjected to requirements under the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: As an article, this product is not subjected to requirements under ENCS Inventory. Japanese Ministry of Economy, Trade, and Industry (METI) Status: As an article, this product is not subjected to requirements under the Japanese METI. JAPANESE REGULATIONS (continued): Poisonous and Deleterious Substances Control Law: As an article, this product is not subjected to requirements under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: As an article, this product is not subjected to requirements under the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is not classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: As an article, this product is not subjected to requirements under the Singapore List of Controlled Substances. Code of Practice on Pollution Control Requirements: As an article, this product is not subjected to requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: As an article, this product is not subjected to requirements under the Taiwan Existing Chemicals List. SPECSEA0 RED WRAP STRIP SDS EFFECTIVE DATE: SEPTEMBER 7, 2017 PAGE 3 OF 4 16. OTHER INFORMATION REVISION DETAILS: Reviewed September 7, 2017, no changes. REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: Specified Technologies Inc. DATE OF PRINTING: November 7, 2017 REVISED: September 7, 2017 SPECSEAL° RED WRAP STRIP SIDS EFFECTIVE DATE: SEPTEMBER 7, 2017 PAGE 4 OF 4 2V6 STI SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME Address: Business Phone: Emergency Phone: SpecSeal° FireStop Pillows Firestop and Sound Transmission None Specified Technologies Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of ComDetent Person for Information on SDS: techserv(a)stifirestOD.com NOTE: ALL United States Occupational Safety and Health Administration Standard (29 CFR 1910.1200), U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7250 required information is included in appropriate sections based on the U.S. ANSI Z400.1-2010 format. This product has been classified in accordance with the hazard criteria of the countries listed above. This product is defined as an "Article' under the U.S. Federal OSHA Hazard Communication Standard (29 CFR 1910.1200), EU Directives, and the Canadian Workplace Hazardous Materials Standard. Refer to Section 15 (Regulatory Information) for specific regulatory citations. As articles, this product presents negligible health and physical hazards under reasonably anticipated circumstances of use. Subsequently, a Material Safety Data Sheet is not required under Standards cited above. This document is prepared to provide persons using this product with additional safety information. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND EU CLP REGULATION (EC) 1272/2008 LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under CLP Regulation (EC) 1272/2008. EU 67/548/EEC LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under European Community Council Directive 67/548/EEC or subsequent Directives. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. 3. COMPOSITION and INFORMATION ON INGREDIENTS This product is an article and as such no components of this product pose a hazard; no component information is given in this SDS. 4. FIRST -AID MEASURES Skin Exposure: As an article, no need for first aid is anticipated. Inhalation: As an article, no need for first aid is anticipated. Eye Exposure: As an article, no need for first aid is anticipated. Ingestion: As an article, no need for first aid is anticipated. 5. FIRE -FIGHTING MEASURES FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: No Special protective actions for fire-fighters are anticipated. SPECSEAL° FIRESTOP PILLOWS SDS EFFECTIVE DATE: MAY 17, 2017 PAGE 1 OF 4 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Not applicable. PERSONAL PROTECTIVE EQUIPMENT: Not applicable. METHODS FOR CLEAN-UP AND CONTAINMENT: Not applicable. ENVIRONMENTAL PRECAUTIONS: Not applicable. 7. HANDLING and STORAGE PRECAUTIONS FOR SAFE HANDLING: No special requirements. CONDITIONS FOR SAFE STORAGE: No special requirements. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: As an article which does not release or otherwise result in exposure to hazardous chemicals under normal use, no personal protective equipment (PPE) is required. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Solid ODOR: Mild acrylic. FLAMMABLE LIMITS (in air by volume, %): Not applicable. DECOMPOSITION TEMPERATURE: Not available. AUTOIGNITION TEMPERATURE: Not available. FREEZING/MELTING POINT: Not applicable. VAPOR PRESSURE: Not applicable. VAPOR DENSITY (air = 1): Not applicable. EVAPORATION RATE (n-BuAc = 1): Not applicable. SOLUBILITY IN WATER: Not applicable. COEFFICIENT WATER/OIL DISTRIBUTION: Not established COLOR: Red ODOR THRESHOLD: Not available. OXIDIZING PROPERTIES: Not applicable. PERCENT VOLATILE FLASH POINT: Not available. BOILING POINT: Not applicable. SPECIFIC GRAVITY (water = 1): 0.1 CARB VOC: Not applicable. SCAQMD (U.S. EPA Method 24): Not applicable. SOLUBILITY IN SOLVENTS: Not applicable. PH: Not applicable. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is stable when properly stored at normal temperatures. 11. TOXICOLOGICAL INFORMATION SYMPTOMS OF EXPOSURE BY ROUTE OF EXPOSURE: Inhalation: Due to the form of the product, inhalation is unlikely. Contact with Skin or Eves: Due to the form of the product, contact with the eyes is unlikely Skin Absorption: Due to form of product, skin absorption is not a likely route of exposure. Ingestion: Ingestion is not a likely route of exposure, due to the form of the product. Infection: Injection is not likely, due to the form of the product. 12. ECOLOGICAL INFORMATION MOBILITY: This product has not been tested for mobility in soil. PERSISTENCE AND BIODEGRADABILITY: This product has not been tested for persistence or biodegradability. The mineral components are not expected to biodegrade to great extent. BIO-ACCUMULATION POTENTIAL: This product has not been tested for bio-accumulation potential. ECOTOXICITY: This product has not been tested for aquatic or animal toxicity. All releases to terrestrial, atmospheric and aquatic environments should be avoided. No aquatic toxicity data are available for components. SPECSEAL° FIRESTOP PILLOWS SDS EFFECTIVE DATE: MAY 17, 2017 PAGE 2 OF 4 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: Waste disposal must be in accordance with appropriate Federal, State, and local regulations. U.S. EPA WASTE NUMBER: Not applicable. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: Not applicable. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: As an article, this product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-21): ACUTE: No; CHRONIC: No; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): As an article, this product is not subject to Threshold Planning Quantities, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: Components of this product are listed on the TSCA Inventory. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): No component is on the California Proposition 65 lists. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: Components are not on the CEPA Priorities Substances Lists. Canadian WHMIS Classification and Symbols: As an article, this product is not subject the Controlled Product Regulations. CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: As an article, this product is not subjected to requirements under the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: As an article, this product is not subjected to requirements under ENCS Inventory. Japanese Ministry of Economy, Trade, and Industry (METI) Status: As an article, this product is not subjected to requirements under the Japanese METI. Poisonous and Deleterious Substances Control Law: As an article, this product is not subjected to requirements under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: As an article, this product is not subjected to requirements under the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is not classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: As an article, this product is not subjected to requirements under the Singapore List of Controlled Substances. Code of Practice on Pollution Control Requirements: As an article, this product is not subjected to requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: As an article, this product is not subjected to requirements under the Taiwan Existing Chemicals List. SPECSEAL° FIRESTOP PILLOWS SDS EFFECTIVE DATE: MAY 17, 2017 PAGE 3 OF 4 16. OTHER INFORMATION REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: Specified Technologies Inc DATE OF PRINTING: July 5, 2017 REVISED: May 17 , 2017 REVISION DETAILS: Reviewed May 17, 2017, no changes. SPECSEAL° FIRESTOP PILLOWS SDS EFFECTIVE DATE: MAY 17, 2017 PAGE 4 OF 4 STI. SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: SpecSeal® Firestop Putty/Putty Pads (SSP 100, SSP28, SS4S, SSP9S pads) RELEVANT USE of the SUBSTANCE: Firestop and Sound Transmission USES ADVISED AGAINST: none SUPPLIER/MANUFACTURER'S NAME: Specified Technologies, Inc. Address: 210 Evans Way, Somerville, New Jersey 08876 Business Phone: (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) Emergency Phone: U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (collect-24 hrs) EMAIL of Competent Person for Information on SIDS: techserv(cDstifirestop.com NOTE: ALL United States Occupational Safety and Health Administration Standard (29 CFR 1910.1200), U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7250 required information is included in appropriate sections based on the U.S. ANSI Z400.1-2010 format. This product has been classified in accordance with the hazard criteria of the countries listed above. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND JAPANESE JIS Z7253 LABELING AND CLASSIFICATION: This product has been classified per UN GHS Standards under U.S., Japanese and other applicable regulations that require Global Harmonization compliance. Classification: Carcinogenic Category 2, Germ Cell Mutagen Category 2, Acute Dermal Toxicity Category 5, Eye Irritation Category 2A, Skin Irritation Category 2, Skin Sensitization Category 1, Specific Target Organ Toxicity Repeated Exposure Category 2 Signal Word: Warning Hazard Statements: H351: This product contains trace amounts of a suspected human carcinogen by inhalation: however, this hazard is not expected to be significant due to viscosity and consistency of the mixture. H341: Suspected of causing genetic effects. H313: May be harmful in contact with skin. H315: Causes skin irritation. H317: May cause an allergic skin reaction. H319: Causes serious eye irritation. H373: May cause damage to organs through prolonged or repeated exposure. Precautionary Statements: Prevention: P201: Obtain special instructions before use. P202: Do not handle until all safety precautions have been read and understood. P260: Do not breathe vapors/fume. P271: Use only outdoors or in a well -ventilated area. P272: Contaminated work clothing should not be allowed out of the workplace. P280: Wear protective gloves, clothing, eye protection and face protection. Response: P308 + P313: IF exposed or concerned: Get medical advice/attention. P305 + P351 + P338: IF IN EYES: Rinse cautiously with water for several minutes. Remove contact lenses, if present and easy to do. P337 + P313: If eye irritation persists: Get medical advice/attention. P302 + P352: IF ON SKIN: Wash with plenty of soap and water. P333 + P313: If skin irritation or rash occurs: Get medical advice/attention. P312: Call a POISON CENTER or doctor if you feel unwell. P362 + P364: Take off contaminated clothing and wash it before reuse. P321: Specific treatment (remove from exposure and treat symptoms). Storage: P403 + P233 + P405: Store in a well -ventilated place. Keep container tightly closed. Store locked up. Disposal: P501: Dispose of contents/containers in accordance with all local, regional, national and international regulations. Hazard Symbols: GHS07, GHS08 <�> 4> KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: Classified in accordance with ISHA Notice 2009-68. Under ISHA, no differences in classification are applicable. SDS0002 - SPECSEALO SSP FIRESTOP PUTTY/PUTTY PADS SIDS EFFECTIVE DATE: JULY 1, 2020 PAGE 1 OF 13 3. COMPOSITION and INFORMATION ON INGREDIENTS Chinese LABEL ELEMENTS IECSC GHS & Japanese JIS Z7253 Classification Inventory Korean ISHA Classification GHS Chemical Name CAS # Japanese Korean Taiwan wTo� Hazard Codes ENCS # ECL # NESCI ECS KE-00980 SELF CLASSIFICATION Aluminum GHS & JAPANESE JIS Z7253, KOREAN ISHA: Trihydrate 21645-51-2 Listed 1-17 Listed 50-60% Classification: Eye Irritation Cat. 2A Hazard Codes: H319 Proprietary Listed Proprietary Proprietary Listed 20-30% Classification Not Applicable Polymer SELF CLASSIFICATION Formaldehyde GHS & JAPANESE JIS Z7253, KOREAN ISHA: Polymer with 35297-54-2 Listed Not Listed KE-17082 Listed 10-15% Classification: Acute Oral Toxicity Cat. 5, Skin Sensitization Ammonia and Cat. 1 B, STOT Re Cat. 3 Phenol Hazard Codes: H303, H317, H373 GHS & JAPANESE JIS Z7253, KOREAN ISHA: Classification: Mutagenic Cat. 2, Acute Oral Toxicity Cat. 3, Phenol 108-95-2 Listed 3-381 KE-28209 Listed 1-3% Acute Dermal Toxicity Cat. 3, Acute Inhalation Toxicity Cat. 3, Skin Corrosion Cat. 1 B, STOT RE Cat. 2 Hazard Codes: H341, H301 + H311 + H331, H314, H373 Sulfuric Acid SELF CLASSIFICATION Compound with GHS & JAPANESE JIS Z7253, KOREAN ISHA: Graphite 12777-87-6 Not Listed Not Listed KE-32585 Listed 2-5% Classification: Carcinogenic Cat. 2 Hazard Codes: H351i SELF CLASSIFICATION GHS & JAPANESE JIS Z7253, KOREAN ISHA: Crystalline Silica 14808-60-7 Listed 1-548 KE-29983 Listed Trace Classification: Carcinogenic Cat. 1, STOT (Inhalation -Lungs) RE Cat. 2 Hazard Statement Codes: H350, H373 GHS & JAPANESE JIS Z7253, KOREAN ISHA: Classification: Carcinogenic Cat. 2, Acute Oral Toxicity Cat. 3, Formaldehyde 50-00-0 Listed 2-482 KE-17074 Listed Trace Acute Dermal Toxicity Cat. 3, Acute Inhalation Toxicity Cat. 3, Skin Corrosion Cat. 1B, Skin Sensitization Cat. 1 Hazard Codes: H351, H301 + H311 + H331, H314, H317 Water and Other Balance Classification Trace Ingredients Not Applicable 4. FIRST -AID MEASURES DESCRIPTION OF FIRST AID MEASURES: Skin Exposure: If adverse skin effects occur, discontinue use and flush contaminated area. Seek medical attention if adverse effect occurs after flushing. Inhalation: If fumes or vapors are inhaled, remove victim to fresh air. Seek medical attention if adverse effect continues after removal to fresh air. Eye Exposure: If this product contaminates the eyes, rinse eyes under gently running water. Remove contact lenses if easy to do. Use sufficient force to open eyelids and then 'roll' eyes while flushing. Minimum flushing is for 20 minutes. The contaminated individual must seek medical attention if any adverse effect continues after rinsing. Ingestion: If this product is swallowed, CALL PHYSICIAN OR POISON CONTROL CENTER FOR MOST CURRENT INFORMATION. If professional advice is not available, DO NOT INDUCE VOMITING. Never induce vomiting or give diluents (milk or water) to someone who is unconscious, having convulsions, or unable to swallow. If victim is convulsing, maintain an open airway and obtain immediate medical attention. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: See Section 11. INDICATION OF IMMEDIATE MEDICAL ATTENTION AND SPECIAL TREATMENT IF NEEDED: Treat symptoms and eliminate exposure. SDS0002 - SPECSEAL® SSP FIRESTOP PUTTY/PUTTY PADS SIDS EFFECTIVE DATE: JULY 1, 2020 PAGE 2 OF 13 5. FIRE -FIGHTING MEASURES FLASH POINTAUTOIGNITION TEMPERATURE: Not determined.: Not available. NFPA RATING FLAMMABLE LIMITS (in air by volume, %): Not applicable. FLAMMABILITY FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. p UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to HEALTH 2 0 INSTABILITY be non-flammable and non-combustible. When involved in a fire, this material may decompose and produce irritating vapors and toxic gases Explosion Sensitivity to Mechanical Impact: Not sensitive. Explosion Sensitivity to Static Discharge: Not sensitive. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: No Special OTHER protective actions for fire-fighters are anticipated. Hazard Scale: 0 = Minimal 1 = Slight 2 = Moderate 3 = Serious 4 = Severe 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Uncontrolled releases should be responded to by trained personnel using pre -planned procedures. Proper protective equipment should be used. Call CHEMTREC (1800- 424-9300) for emergency assistance. Or if in Canada, call CANUTEC (613-996-6666). PERSONAL PROTECTIVE EQUIPMENT: Proper protective equipment should be used. Small Spills: Wear rubber gloves. Large Spills: Minimum Personal Protective Equipment should be rubber gloves, rubber boots, face shield. METHODS FOR CLEAN-UP AND CONTAINMENT: Spills of this product present minimal hazard. Small Spills: Small releases can be carefully swept up or cleaned up using a damp sponge or polypads. Large Spills: Access to the spill area should be restricted. For large spills, dike or otherwise contain spill and sweep -up or vacuum with non -sparking vacuum. All Spills: Place all spill residue in a double plastic bag or other containment and seal. Close off sewers and take other measures to protect human health and the environment as necessary. Rinse area with soap and water solution and follow with a water rinse. ENVIRONMENTAL PRECAUTIONS: Avoid release to the environment. 7. HANDLING and USE PRECAUTIONS FOR SAFE HANDLING: As with all chemicals, avoid getting this material ON YOU or IN YOU. Do not eat, drink, smoke, or apply cosmetics while handling this product. Wash hands thoroughly after handling this product or containers of this product. Avoid breathing fumes or vapors. Use in a well -ventilated location. CONDITIONS FOR SAFE STORAGE: Store containers in a cool, dry location, away from direct sunlight, sources of intense heat. SPECIFIC END USE(S): This product is for use as a sealant. Follow all industry standards for use of this product. PROTECTIVE PRACTICES DURING MAINTENANCE OF CONTAMINATED EQUIPMENT: Follow practices indicated in Section 6 (Accidental Release Measures). Make certain that application equipment is locked and tagged -out safely, if necessary. Collect all rinsates and dispose of according to applicable Federal, State, and local procedures. SDS0002 - SPECSEALO SSP FIRESTOP PUTTY/PUTTY PADS SIDS EFFECTIVE DATE: JULY 1, 2020 PAGE 3 OF 13 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: Ventilation and Engineering Controls: Use with adequate ventilation to ensure exposure levels are maintained below the limits provided below (if applicable). Exhaust directly to the outside, taking necessary precautions for environmental protection. Workplace Exposure Limits/Control Parameters: CHEMICAL NAME CAS # EXPOSURE LIMITS IN AIR ACGIH-TLVs OSHA-PELs NIOSH-RELs NIOSH OTHER TWA STEL TWA STEL TWA STEL IDLH mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 mg/m3 Aluminum 21645-51-2 NE NE NE NE NE NE NE DFG MAKs: Trihydrate TWA = 4 mg/m3 (inhalable fraction); 1.5 mg/m3 (respirable fraction) DFG MAK Pregnancy Risk Classification: D Crystalline Silica 14808-60-7 0.025 NE 30 mq/m3 (total dust) 0.05 NE 50, Ca Carcinogen: IARC-1, MAK-1 % S02 + 2 (Quartz) (resp. (resp. (respirable fraction), NOSH -Ca, NTP-K Tract.) 0.1 (vacated 1989 PEL) dust) (respirable fraction), TLV-A2 250 mppcf (resp. dust) %Si02+5 or 10 mq/m3 (resp. dust) 0.2%SO2+2 Formaldehyde 50-00-0 SEN 0.37 0.016 0.1 20 ppm DFG MAKs: (ceiling) ppm ppm, (Ca) TWA = 0.37 0.75 ppm 2 ppm 15 min. PEAK = 2-MAK 15-min average value, 1-hr interval, 4 per shift; 1 (ceiling) NIC: D-SEN, RSEN See 20 CFR See Pocket Guide Danger of Sensitization of the Skin 1910.1048(c) App. A DFG MAK Germ Cell Mutagen Category: 5 DFG MAK Pregnancy Risk Classification: C Carcinogen: EPA-131, IARC-1, MAK-4, NIOSH-Ca, NTP-K, OSHA -Ca, TLV-A2 Formaldehyde 35297-54-2 NE NE NE NE NE NE NE NE Polymer with Ammonia and Phenol Phenol 108-95-2 19 Skin 19 (skin) Skin 19 60 25 ppm DFG MAK: Skin (skin) (skin) (skin) Carcinogen: EPA -I, EPA-D, IARC-3, 15 min. MAK-313, TLV-A4 Proprietary Polymer NE NE NE NE NE NE NE NE Sulfuric Acid 12777-87-6 NE NE NE NE NE NE NE NE Compound with Graphite NE: Not Established. Ca: Carcinogen NIC: Notice of Intended Change DSEN: May Cause Dermal Sensitization. This notation is used to indicate the potential for dermal sensitization resulting from the interaction of an absorbed agent and ultraviolet light (i.e. photosensitization) RSEN: May Cause Respiratory Sensitization SEN: Confirmed Potential Worker Sensitization as a Result of Dermal Contact and/or Inhalation Exposure, Based on the Weight of Scientific Evidence See Section 16 for Definitions of Other Terms Used International Occupational Exposure Limits: Currently, the following additional exposure limit values have been established by various countries for the components of this mixture. More current limits may be available; individual countries should be consulted to determine if newer limits are available. SDS0002 - SPECSEAL® SSP FIRESTOP PUTTY/PUTTY PADS SDS EFFECTIVE DATE: JULY 1, 2020 PAGE 4 OF 13 ALUMINUM HYDROXIDE: Australia: TWA = 2 mg(AI)/m3, JUL 2008 Belgium: TWA = 2 mg(AI)/m3, MAR 2002 Finland: TWA = 2 mg(AI)/m3, NOV 2011 France: VME = 2 mg(AI)/m3, FEB 2006 Korea: TWA = 2 mg(AI)/m3, 2006 New Zealand: TWA = 2 mg(AI)/m3, JAN 2002 Russia: TWA = 6 mg/m3, JUN 2003 Sweden: TWA = 1 mg(AI)/m3, JUN 2005 Switzerland: MAK-W = 3 mg/m3, resp, JAN 2011 United Kingdom: TWA = 2 mg(AI)/m3, OCT 2007 In Argentina, Bulgaria, Colombia, Jordan, Singapore, Vietnam check ACGIH TLV CRYSTALLINE SILICA: Australia: TWA = 0.1 mg/m3, JUL 2008 Belgium: TWA = 0.1 mg/m3 (resp. dust), MAR 2002 Denmark: TWA = 0.1 mg/m3 (respirable), carc, MAY 2011 Denmark: TWA = 0.1 mg/m3 (resp.), carc, MAY2011 Denmark: TWA = 0.3 mg/m3 (total), MAY 2011 Finland: TWA = 0.05 mg/m3, resp. dust, SEP 2009 France: VME = 0.1 mg/m3, (resp), FEB 2006 Iceland: TWA = 0.1 mg/m3 (resp. dust), NOV 2011 Japan: OEL-C = 0.03 mg/m3 (respirable), APR 2007 Korea: TWA = 0.1 mg/m3, 2006 Mexico: TWA = 0.1 mg/m3 (respirable), 2004 The Netherlands: MAC-TGG = 0.075 mg/m3, 2003 New Zealand: TWA = 0.2 mg/m3 (respirable dust), JAN 2002 Norway: TWA = 0.1 mg/m3 (resp. dust), JAN 1999 Norway: TWA = 0.3 mg/m3 (total dust), JAN 1999 Peru: TWA = 0.05 mg/m3, JUL 2005 Russia: TWA = 1 mg/m3, STEL = 3 mg/m3, JUN 2003 Sweden: TWA = 0.1 mg/m3 (resp. dust), JUN 2005 Switzerland: MAK-W = 0.15 mg/m3, DEC 2006 Thailand: TWA = 10 mg/m3 (resp. dust), JAN 1993 Thailand: TWA = 30 mg/m3 (total dust), JAN 1993 United Kingdom: TWA = 0.1 mg/m3 (resp. dust), OCT 2007 In Argentina, Bulgaria, Colombia, Jordan, Singapore, Vietnam check ACGIH TLV FORMALDEHYDE: ARAB Republic of Egypt: TWA = 2 ppm (3 mg/m3), JAN 1993 Australia: TWA = 1 ppm (1.2 mg/m3), STEL = 2 ppm (2.5 mg/m3), Carcinogen, JUL 2008 Austria: MAK-TMW = 0.5 ppm (0.6 mg/m3); KZW = 0.5 ppm (0.6 mg/m3), skin, sen, 2007 Belgium: STEL = 0.3 ppm (0.38 mg/m3), MAR 2002 Denmark: CL = 0.3 ppm (0.4 mg/m3), carc, MAY 2011 Finland: TWA = 0.3 ppm (0.37 mg/m3), CL = 1 ppm (1.2 mg/m3), NOV 2011 France: VME = 0.5 ppm, VILE 1 ppm, C3 Carcinogen, FEB 2006 Germany: MAK = 0.3 ppm (0.37 mg/m3), 2011 Hungary: TWA = 0.6 mg/m3, STEL 0.6 mg/m3, Skin, SEP 2000 FORMALDEHYDE (continued): Iceland: TWA = 0.3 ppm (0.4 mg/m3), STEL 1 ppm (1.2 mg/m3), Sen, NOV 2011 Japan: OEL = 0.1 ppm (0.12 mg/m3), 2A Carc, A2 Sen, s1 Sen, MAY 2012 Japan: OEL = 0.2 ppm (0.24 mg/m3), MAY2012 Korea: TWA = 1 ppm (1.5 mg/m3), STEL = 2 ppm (3 mg/m3), 2006 Mexico: PEAK = 2 ppm (3 mg/m3), 2004 The Netherlands: MAC-TGG = 1.5 mg/m3, 2003 New Zealand: CL = 1 ppm (1.2 mg/m3), sen, JAN 2002 Norway: TWA = 0.5 ppm (0.6 mg/m3), JAN 1999 Peru: TWA STEL = 0,3 ppm (0,37 mg/m3), JUL 2005 The Philippines: TWA = 5 ppm (6 mg/m3), JAN 1993 Poland: MAC(TWA) = 0.5 mg/m3, MAC(STEL) = 1 mg/m3, JAN 1999 Russia: STEL = 0.5 mg/m3, Skin, JUN 2003 Sweden: TWA = 0.5 ppm (0.6 mg/m3), CL = 1 ppm (1.2 mg/m3), Carcinogen, Sen, JUN 2005 Switzerland: MAK-W = 0.3 ppm (0.37 mg/m3), KZG-W = 0.6 ppm (0.74 mg/m3), Carc 3, Sen, JAN 2011 Thailand: TWA = 3 ppm, STEL = 5 ppm, JAN 1993 Turkey: TWA = 5 ppm (6 mg/m3), JAN 1993 United Kingdom: TWA = 2 ppm (2.5 mg/m3); STEL 2 ppm (2.5 mg/m3), OCT 2007 In Argentina, Bulgaria, Colombia, Jordan, Singapore, Vietnam check ACGIH TLV PHENOL: ARAB Republic of Egypt: TWA = 5 ppm (19 mg/m3), Skin, JAN 1993 Australia: TWA = 1 ppm (4 mg/m3), JUL 2008 Austria: MAK-TMW = 2 ppm (7.8 mg/m3), skin, 2007 Denmark: TWA = 2 ppm (7.8 mg/m3), Skin, MAR 2002 Denmark: TWA = 1 ppm (4 mg/m3), skin, MAY 2011 EC: TWA = 7.8 mg/m3 (2 ppm), skin, JUN 2000 Finland: TWA = 2 ppm (8 mg/m3), STEL = 4 ppm (16 mg/m3), skin, NOV 2011 France: VME = 2 ppm (7.8 mg/m3), Skin, FEB 2006 Hungary: TWA = 7.8 mg/m3, STEL = 78 mg/m3, Skin, SEP 2000 Iceland: TWA = 1 ppm (4 mg/m3), skin, NOV 2011 Japan: OEL = 5 ppm (19 mg/m3), skin, MAY 2012 Korea: TWA = 5 ppm (19 mg/m3), skin, 2006 Mexico: TWA = 5 ppm (19 mg/m3); STEL = 10 ppm (38 mg/m3) (skin), 2004 The Netherlands: MAC-TGG = 8 mg/m3, Skin, 2003 New Zealand: TWA = 5 ppm (19 mg/m3), skin, JAN 2002 Norway: TWA = 1 ppm (4 mg/m3), JAN 1999 Peru: TWA = 5 ppm (19 mg/m3), JUL 2005 The Philippines: TWA = 5 ppm (10 mg/m3), Skin, JAN 1993 Poland: MAC(TWA) = 10 mg/m3, MAC(STEL) = 20 mg/m3, JAN 1999 Russia: TWA = 0.3 mg/m3, STEL = 1 mg/m3, Skin, JUN 2003 Sweden: TWA = 1 ppm (4 mg/m3); STEL = 2 ppm (8 mg/m3), Skin, JUN 2005 Switzerland: CL 5 ppm (19 mg/m3), skin, JAN 2011 Thailand: TWA = 5 ppm (19 mg/m3), JAN 1993 Turkey: TWA = 5 ppm (19 mg/m3), Skin, JAN 1993 United Kingdom: TWA = 2 ppm (7.8 mg/m3), skin, OCT2007 In Argentina, Bulgaria, Colombia, Jordan, Singapore, Vietnam check ACGIH TLV PROTECTIVE EQUIPMENT: The following information on appropriate Personal Protective Equipment is provided to assist employers in complying with OSHA regulations found in 29 CFR Subpart I (beginning at 1910.132, including U.S. Federal OSHA Respiratory Protection (29 CFR 1910.134), OSHA Eye Protection 29 CFR 1910.133, OSHA Hard Protection 29 CFR 1910.138, OSHA Foot Protection 29 CFR 1910.136 and OSHA Body Protection 29 CFR1910.132), equivalent standards of Canada (including CSA Respiratory Standard Z94.4-02, Z94.3-M1982, Industrial Eye and Face Protectors and CSA Standard Z195-02, Protective Footwear), or standards of Japan (including JIS T 8116:2005 for glove selection, JIS T 8150:2006 for respiratory PPE, JIS T 8147:2003 for eye protectors, and JIS T 8030:2005 for protective clothing). Please reference applicable regulations and standards for relevant details. Respiratory Protection: Maintain airborne contaminant concentrations below exposure limits listed above. For materials without listed exposure limits, minimize respiratory exposure. If necessary, use only respiratory protection authorized under appropriate regulations. Eve Protection: Wear splash goggles or safety glasses as appropriate for the task. Hand Protection: During manufacture or other similar operations, wear the appropriate hand protection for the process. Skin Protection: Use appropriate protective clothing. If necessary, refer to the U.S. OSHA Technical Manual (Section VII: Personal Protective Equipment) or other appropriate regulations. Full -body chemical protective clothing is recommended for emergency response procedures. 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Putty MOLECULAR FORMULA: Mixture. ODOR: Minimal. FLAMMABLE LIMITS (in air by volume. %): Not applicable DECOMPOSITION TEMPERATURE: Not available. AUTOIGNITION TEMPERATURE: Not available. FREEZING/MELTING POINT: Not available. COLOR: Red. MOLECULAR WEIGHT: Mixture. ODOR THRESHOLD: Not available. OXIDIZING PROPERTIES: Not applicable. PERCENT VOLATILE: Not available. FLASH POINT: Not available. BOILING POINT: Not available. SDS0002 - SPECSEAL® SSP FIRESTOP PUTTY/PUTTY PADS SIDS PAGE 5 OF 13 EFFECTIVE DATE: JULY 1, 2020 VAPOR PRESSURE: Not available. SPECIFIC GRAVITY (water = 1): 1.49 VAPOR DENSITY (air = 1): Not available. CARB VOC: Not available. EVAPORATION RATE (n-BUAC = 1): Not Applicable SCAQMD (U.S. EPA Method 24): Not available. SOLUBILITY IN WATER: Insoluble. SOLUBILITY IN SOLVENTS: Not available. COEFFICIENT WATER/OIL DISTRIBUTION: Not established. pH: Not available. HOW TO DETECT THIS SUBSTANCE (warning properties in event of accidental release): The appearance may be characteristics to distinguish a release of this product. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is stable when properly stored at normal temperature and pressures (see Section 7, Handling and Storage). DECOMPOSITION PRODUCTS: Combustion: If exposed to extremely high temperatures, thermal decomposition may generate irritating fumes and toxic gases Hydrolysis: None known. MATERIALS WITH WHICH SUBSTANCE IS INCOMPATIBLE: This product is incompatible with strong oxidizers. POSSIBILITY OF HAZARDOUS POLYMERIZATION OR REACTION: Will not occur. CONDITIONS TO AVOID: Avoid exposure to or contact with extreme temperatures and incompatible chemicals. 11. TOXICOLOGICAL INFORMATION SYMPTOMS OF EXPOSURE BY ROUTE OF EXPOSURE: The health hazar information provided below is pertinent to employees using this product in a occupational setting. The following paragraphs describe the symptoms c exposure by route of exposure. Inhalation: Inhalation of fumes or vapors if heated may cause irritation of the nose throat, and lungs and cause coughing. Removal to fresh air should reliev symptoms. The trace Crystalline Silica and Formaldehyde components are know human carcinogens. Due to the form of this product, this hazard is not as significar due to viscosity and consistency of the mixture. Contact with Skin or Eyes: Direct eye contact may cause irritation, redness, an tearing from mechanical irritation. Prolonged or repeated skin exposures may taus dermatitis (dry red skin). Skin Absorption: The Phenol component and trace Formaldehyde component can b absorbed through intact skin. Phenol in all forms (solid, solutions and vapor) i readily absorbed through the skin and can cause harmful effects if a large area c the skin is involved or if contact is prolonged. Due to the small amount of each ( these materials, the possibility of adverse effects is not expected to be significar however, skin contact should be avoided. Formaldehyde and Phenol can taus sensitization effects as described under `Sensitization Effect's'. SYMPTOMS OF EXPOSURE BY ROUTE OF EXPOSURE (continued): Ingestion: Ingestion is not a significant route of occupational exposure and is unlikel to occur. If this product is swallowed, irritation of the mouth, throat, esophagus an other tissues of the digestive system may occur. Symptoms of ingestion may includ nausea, vomiting, and diarrhea. Infection: Accidental injection of this product, via laceration or puncture by contaminated object can cause redness at the site of injection. HEALTH EFFECTS OR RISKS FROM EXPOSURE: Exposure to this Hazai Scale: 3 = Serious 0 4= = Severe ` = Chronic hazard Minimal 1 = Slight 2 = Moderate product cause the following health effects: HAZARDOUS MATERIAL IDENTIFICATION SYSTEM 2* HEALTH HAZARD (BLUE) FLAMMABILITY HAZARD 0 (RED) PHYSICAL HAZARD 0 (YELLOW) PROTECTIVE EQUIPMENT EYES RESPIRATORY HANDS BODY 9 SEE SECTION 8J SEE SECTION , For Routine Industrial Use and Handling Applications Acute: Inhalation of fumes or vapors may cause irritation of respiratory system. Eye contact may cause mechanical irritation. Eye contact with fumes can cause irritation. May be harmful if swallowed. Chronic: Prolonged or repeated skin exposure may cause dermatitis (dry red skin). TARGET ORGANS: Acute: Skin, eyes, respiratory system. Chronic: Skin. TOXICITY DATA: Currently, the following toxicological data are available for components of 1 % or more concentration. ALUMINUM TRIHYDRATE: TDLo (Oral -Child) 79 gm/kg/2 years -intermittent: Behavioral: changes in motor activity (specific assay), muscle contraction or spasticity; Musculoskeletal: osteomalacia TDLo (Oral -Child) 122 gm/kg/4 days: Gastrointestinal: other changes; Nutritional and Gross Metabolic: body temperature increase TDLo (Oral -Woman) 84 gm/kg: female 1-40 week(s) after conception: Reproductive: Effects on Newborn: physical TDLo (Oral -Infant) 68040 mg/kg/24 weeks -intermittent: Musculoskeletal: osteoporosis; Nutritional and Gross Metabolic: weight loss or decreased weight gain, changes in phosphorus SDS0002 - SPECSEAL® SSP FIRESTOP PUTTY/PUTTY PADS SDS EFFECTIVE DATE: JULY 1, 2020 PAGE 6 OF 13 TDLo (Oral -Woman) 73912.5 mg/kg/26 weeks -intermittent: Blood: changes in serum composition (e.g. TP, bilirubin, cholesterol); Musculoskeletal: osteoporosis; Nutritional and Gross: Metabolic: changes in phosphorus TDLo (Unreported -Infant) 39 gm/kg/24 days -intermittent: Musculoskeletal: osteomalacia TDLo (Oral -Rat) 15 mg/kg: Gastrointestinal: other changes TDLo (Oral -Rat) 8040 mg/kg/67 days -continuous: Blood: changes in serum composition (e.g. TP, bilirubin, cholesterol); Nutritional and Gross Metabolic: changes in phosphorus TDLo (Oral -Mouse) 80,880 mg/kg/23 weeks -continuous: Liver: other changes; Musculoskeletal: other changes; Nutritional and Gross Metabolic: changes in metals, not otherwise specified TDLo (Intraperitoneal-Rat) 150 mg/kg TDLo (Intraperitoneal-Rat) 6240 mg/kg/26 weeks -intermittent: Blood: pigmented or nucleated red blood cells; Nutritional and Gross Metabolic: weight loss or decreased weight gain, changes in iron TDLo (Intraperitoneal-Rat) 1920 mg/kg/8 weeks -intermittent: Blood: microcytosis with or without anemia TDLo (Intraperitoneal-Rat) 960 mg/kg/4 weeks -intermittent: Blood: changes in erythrocyte (RBC) count TDLo (Intraperitoneal-Rat) 1920 mg/kg/8 weeks -intermittent: Blood: microcytosis with or without anemia TDLo (Intraperitoneal-Rat) 960 mg/kg/4 weeks -intermittent: Blood: changes in erythrocyte (RBC) count PHENOL: LDLo (Oral -Human) 14 gm/kg: Behavioral: muscle weakness; Lungs, Thorax, or Respiration: cyanosis LDLo (Oral -Human) 140 mg/kg: Behavioral: hallucinations, distorted perceptions; Skin and Appendages: sweating LDLo (Oral -Infant) 10 mg/kg: Behavioral: muscle weakness; Lungs, Thorax, or Respiration: cyanosis TDLo (Parenteral-Man) 105.3 mg/kg: Peripheral Nerve and Sensation: sensory change involving peripheral nerve; Lungs, Thorax, or Respiration: dyspnea; Kidney/Ureter/Bladder: renal function tests depressed TDLo (Unreported -Man) 5714 pg/kg: Sense Organs and Special Senses (Olfaction): effect, not otherwise specified IC5o (In vitro -Human Liver) 3.02 mmol/U24 hours: In Vitro Toxicity Studies: cell viability (mitochondrial reductase assays): MITT, XTT, MTS, WSTs assays etc IC5o (In vitro -Human Liver) 9.67 mmol/L/24 hours: In Vitro Toxicity Studies: cell viability (mitochondrial reductase assays): MITT, XTT, MTS, WSTs assays etc IC5o (In vitro -Human Liver Tumor) 10 mmol/U24 hours: In Vitro Toxicity Studies: cell protein synthesis IC5o (In vitro -Human Liver Tumor) 3.47 mmol/U24 hours: In Vitro Toxicity Studies: cell membrane integrity: cytoplasmic enzymes leakage (lactate dehydrogenase, ATP enzymes etc.), cell viability (mitochondrial reductase assays): MITT, XTT, MTS, WSTs assays etc TOXICITY DATA (continued): IC5o (In vitro -Human Liver Tumor) 14.66 mmol/L/24 hours: In Vitro Toxicity Studies: cell membrane integrity: cytoplasmic enzymes leakage (lactate dehydrogenase, ATP enzymes etc.), cell viability (mitochondrial reductase assays): MITT, XTT, MTS, WSTs assays etc IC5o (In vitro -Human HeLa Cell) 100 mg/U24 hours: In Vitro Toxicity Studies: cell membrane integrity: cytoplasmic enzymes leakage (lactate dehydrogenase, ATP enzymes etc.) Open Irritation Test (Skin -Rabbit) 535 mg: Severe Standard Draize Test (Skin -Rabbit) 100 mg: Mild Standard Draize Test (Eye -Rabbit) 5 mg: Severe Standard Draize Test (Eye -Rabbit) 400 pU30 seconds: Severe Rinsed with Water (Eye -Rabbit) 5 mg/30 seconds: Mild LCw (Inhalation -Rat) 316 mg/m3 LC5o (Inhalation -Rat) 316 mg/m3/4 hours LC5o (Inhalation -Mouse) 177 mg/m3 LC5o (Inhalation -Mouse) 177 mg/m3/4 hours LD5o (Oral -Rat) 317 mg/kg: Behavioral: convulsions or effect on seizure threshold LD5o (Oral -Rat) 512 mg/kg LD5o (Oral -Mouse) 270 mg/kg LD5o (Oral -Mammal -Species Unspecified) 500 mg/kg LD5o (Skin -Rat) 1500 mg/kg LD5o (Skin -Rat) 669 mg/kg: Behavioral: tremor; Kidney/Ureter/Bladder: hematuria; Skin and Appendages: cutaneous sensitization, experimental (after topical exposure) LD5o (Skin -Rabbit) 630 mg/kg LD5o (Intraperitoneal-Rat) 127 mg/kg LD5o (Intraperitoneal-Mouse) 180 mg/kg LD5o (Subcutaneous -Rat) 300 mg/kg LD5o (Subcutaneous -Mouse) 344 mg/kg LD5o (Intravenous -Mouse) 112 mg/kg: Behavioral: tremor IGo (In vitro -Rat Liver) 1.12 mmol/L/24 hours: In Vitro Toxicity Studies: cell membrane integrity: cytoplasmic enzymes leakage (lactate dehydrogenase, ATP enzymes etc.), cell viability (mitochondrial reductase assays): MITT, XTT, MTS, WSTs assays etc IGo (In vitro -Rat Lung) 0.03 gm/U24 hours: In Vitro Toxicity Studies: cell membrane integrity (prelabeled cells): release of radioactive isotopes ([51Cr], [3H]-thymidine, [3H]-proline, [35S]- or [75Se]-methionine, 5-[1251]-2-deoxy-uridine) or fluorescent dyes (bis-carboxyethyl-carboxyfluorescein (BCECF) or calcein-AM) TIVIEQ IGo (In vitro -Rat Lung) 0.2 gm/L/24 hours: In Vitro Toxicity Studies: cell viability (mitochondrial reductase assays): MITT, XTT, MTS, WSTs assays etc IGo (In vitro -Chicken Neurons) 7470 pmol/L/21 hour In Vitro Toxicity Studies: cell viability (mitochondrial reductase assays): MITT, XTT, MTS, WSTs assays etc IGo (In vitro -Chicken Neurons) 1862 pmol/L/21 hours: In Vitro Toxicity Studies: cell viability (mitochondrial reductase assays): MITT, XTT, MTS, WSTs assays etc IGo (In vitro -Chicken Neurons) 614 pmol/L/20 hours: In Vitro Toxicity Studies: cell viability (Iysosomal damage): neutral red assay etc. IC5o (In vitro -Rat Liver) 3.3 mmol/L/24 hours: In Vitro Toxicity Studies: cell membrane integrity: cytoplasmic enzymes leakage (lactate dehydrogenase, ATP enzymes etc.), cell viability (mitochondrial reductase assays): MITT, XTT, MTS, WSTs assays etc. IC5o (In vitro -Rat Lung) 1 gm/U24 hours: In Vitro Toxicity Studies: cell viability (mitochondrial reductase assays): MITT, XTT, MTS, WSTs assays etc. IC5o (In vitro -Rat Lung) 0.36 gm/U24 hours: In Vitro Toxicity Studies: cell membrane integrity (prelabeled cells): release of radioactive isotopes ([51 Cr], [3H]-thymidine, [3H]-proline, [35S]- or [75Se]-methionine, 5-[1251]-2-deoxy-uridine) or fluorescent dyes (bis-carboxyethyl-carboxyfluorescein (BCECF) or calcein-AM) TDLo (Oral -Mouse) 2800 mg/kg/10 days -intermittent: Behavioral: tremor, ataxia TDLo (Skin -Mouse) 329 mg/kg/30 minutes: Skin and Appendages: primary irritation (after topical exposure); Biochemical: Metabolism (Intermediary): other, effect on inflammation or mediation of inflammation TDLo (Skin -Mouse) 88.9 pL/kg: Biochemical: Metabolism (Intermediary): effect on inflammation or mediation of inflammation TDLo (Skin -Mouse) 16 gm/kg/40 weeks -intermittent: Tumorigenic: carcinogenic by RTECS criteria; Skin and Appendages: tumors TDLo (Intraperitoneal-Rat) 650 mg/kg/17 days -intermittent: Blood: other changes TDLo (Intraperitoneal-Rat) 600 mg/kg: female 12-14 day(s) after conception: Reproductive: Effects on Embryo or Fetus: fetotoxicity (except death, e.g., stunted fetus) TDLo (Intraperitoneal-Mouse) 300 mg/kg: Nutritional and Gross Metabolic: body temperature decrease TDLo (Intraperitoneal-Mouse) 300 mg/kg: Immunological Including Allergic: hypersensitivity delayed TCLo (Inhalation -Rat) 110 mg/m3/4 hours: Behavioral: somnolence (general depressed activity); Blood: changes in serum composition (e.g. TP, bilirubin, cholesterol); Biochemical: Enzyme inhibition, induction, or change in blood or tissue levels: proteases TCLo (Inhalation -Rat) 150 ug/m3/8 hours/26 weeks -intermittent: Kidney/Ureter/Bladder: changes in tubules (including acute renal failure, acute tubular necrosis); Biochemical: Enzyme inhibition, induction, or change in blood or tissue levels: phosphatases TCLo (Inhalation -Rat) 5 mg/m3/4 hours/17 weeks -intermittent: Liver: liver function tests impaired; Endocrine: effect on menstrual cycle; Blood: changes in leukocyte (WBC) count TCLo (Inhalation -Rat) 100 pg/m3/24 hours/61 days -continuous: Behavioral: muscle contraction or spasticity; Blood: other changes; Biochemical: Enzyme inhibition, induction, or change in blood or tissue levels: true cholinesterase SDS0002 - SPECSEAL° SSP FIRESTOP PUTTY/PUTTY PADS SIDS EFFECTIVE DATE: JULY 1, 2020 PAGE 7 OF 13 TCLo (Inhalation -Rat) 0.5 mg/m3/4 hours/122 days -intermittent: Blood: changes in serum composition (e.g. TP, bilirubin, cholesterol); Biochemical: Enzyme inhibition, induction, or change in blood or tissue levels: multiple enzyme effects TCLo (Inhalation -Mouse) 15 ppm/6 minutes: Lungs, Thorax, or Respiration: respiratory depression LCLo (Inhalation -Rat) 232 mg/m3/ 4 hours LCLo (Inhalation -Mouse) 110 mg/m3/4 hours Mutation Test Systems -Not Otherwise Specified (Human HeLa cell) 17 mg/L Mutation Test Systems -Not Otherwise Specified (Human Lymphocyte) 5 pmol/L DNA Inhibition (Human HeLa Cell) 1 mmol/L Sister Chromatid Exchange (Human Lymphocyte) 5 pmol/L Cytogenetic Analysis (Human Cells -Not Otherwise Specified) 300 pmol/L/30 hours Mutation in Microorganisms (Bacteria -Salmonella typhimunum) 40 pmol/plate Mutation in Microorganisms (Mouse Lymphocyte) 300 mg/L Mutation in Microorganisms (Microorganism -Not Otherwise Specified) 200 mg/L/8 hours Sex Chromosome Loss and Non -Disjunction (Insect -Drosophila melanogasterOvary) 100 ppm Gene Conversion and Mitotic Recombination (Mold-Aspergillus nidulans) 15 pmol/L DNA Damage (Mammal -Species Unspecified Lymphocyte) 250 mmol/L Micronucleus Test (Oral -Mouse) 265 mg/kg Micronucleus Test (Intraperitoneal-Mouse) 265 mg/kg Micronucleus Test (Hamster Lung) 4 mmol/L Micronucleus Test (Hamster Ovary) 175 mg/L Micronucleus Test (Hamster Embryo) 500 mg/L/4 hours DNA Inhibition (Oral -Mouse) 20 gm/kg DNA Inhibition (Mouse Lymphocyte) 800 pmol/L DNA Inhibition (Hamster Lung) 1900 pmol/L Cytogenetic Analysis (Multiple Routes -Fish -Not Otherwise Specified) 300 nL/L Cytogenetic Analysis (Hamster Ovary) 2 gm/L Cytogenetic Analysis (Hamster Embryo) 100 pmol/L Unscheduled DNA Synthesis (Oral -Rat) 4 gm/kg Unscheduled DNA Synthesis (Hamster Embryo) 3 pmol/L DNA Damage (Mouse Lymphocyte) 1500 pmol/L Mutation Test Systems -Not Otherwise Specified (Mouse Cells -Not Otherwise Specified) 2500 pmol/L Mutation Test Systems -Not Otherwise Specified (Rabbit Bone Marrow) 250 pmol/L Mutation in Mammalian Somatic Cells (Mouse Lymphocyte Mouse Lymphocyte) 1890 pmol/L Mutation in Mammalian Somatic Cells (Hamster Embryo) 3 mmol/L Morphological Transformation (Hamster Embryo) 10 pmol/L Sister Chromatid Exchange (Hamster Ovary) 300 mg/L Sister Chromatid Exchange (Hamster Embryo) 1 mmol/L POLYBUTENE: TCLo (Inhalation -Rat) 700 mg/m3/7 hours/2 weeks -intermittent: Liver: changes in liver weight; Nutritional and Gross Metabolic: weight loss or decreased weight gain 11. TOXICOLOGICAL INFORMATION (Continued) IRRITANCY OF PRODUCT: Inhalation of fumes or vapors may cause respiratory irritation. Eye contact may cause irritation. Eye contact with fumes may cause irritation. Prolonged skin contact may cause irritation. CARCINOGENIC POTENTIAL OF COMPONENTS: Components of this product are listed by agencies tracking the carcinogenic potential of chemical compounds, as follows: CRYSTALLINE SILICA: ACGIH-TLV-A2 (Suspected Human Carcinogen); ARC-1 (Carcinogenic to Humans); MAK-1 (Substances that Cause Cancer in Man and Can Be Assumed to Make a Significant Contribution to Cancer Risk); NIOSH-Ca (Potential Occupational Carcinogen with No Further Categorization); NTP-K (Known to Be a Human Carcinogen) FORMALDEHYDE: ACGIH-TLV-A2 (Suspected Human Carcinogen); EPA-B1 (Probable Human Carcinogen -Limited Evidence of Carcinogenicity from Epidemiological Studies), ARC-1 (Carcinogenic to Humans); MAK-4 (Substances with Carcinogenic Potential for Which Genotoxicity Plays No or at Most a Minor Role. No significant contribution to human cancer risk is expected, provided the MAK value is observed.); NIOSH-Ca (Potential Occupational Carcinogen with No Further Categorization); NTP-K (Known to Be a Human Carcinogen); OSHA -Ca (Carcinogen Defined with No Further Categorization) PHENOL: ACGIH TLV-A4 (Not Classifiable as a Human Carcinogen); EPA -I (Data are Inadequate for an Assessment of Human Carcinogenic Potential); EPA-D (Not Classifiable as to Human Carcinogenicity); IARC-3 (Unclassifiable as to Carcinogenicity in Humans); MAK-3B (Substances for Which in vitro tests or animal studies have yielded evidence of carcinogenic effects that is not sufficient for classification of the substance in one of the other categories. Further studies are required before a final classification can be made.) The remaining components are not found on the following lists: U.S. EPA, U.S. NTP, U.S. OSHA, U.S. NIOSH, GERMAN MAK, IARC, or ACGIH and therefore is neither considered to be nor suspected to be a cancer -causing agent by these agencies. REPRODUCTIVE TOXICITY INFORMATION: This product is not expected or reported to cause human mutagenic, embryotoxic, teratogenic or reproductive toxicity effects. The following gives information on possible effects from components. Mutagenicity: Formaldehyde is considered mutagenic, based on positive results (e.g. chromosomal aberrations in lung cells) observed in studies with live animals. In occupational exposure studies, which are limited by such problems as low numbers of workers studied and mixed exposures, both positive and negative results (micronuclei, sister chromatid exchanges (SCEs), chromosome aberrations in lymphocytes or cheek and nose cells) and a negative result (abnormal sperm) were obtained.(19,44,46,81) However, positive results (SCEs in lymphocytes, DNA -protein crosslinks in lymphocytes) were obtained in 2 reasonably well-conducted studies. SDS0002 - SPECSEAL® SSP FIRESTOP PUTTY/PUTTY PADS SDS EFFECTIVE DATE: JULY 1, 2020 PAGE 8 OF 13 Embryotoxicity/Teratogenicity: No component is known to cause human embryotoxicity or teratogenicity. Animal studies are inconclusive or have not shown embryotoxicity or teratogenicity. Reproductive Toxicity: There is insufficient evidence to determine if Formaldehyde causes reproductive toxicity in humans. Despite limitations, the few animal studies available do not suggest that Formaldehyde exposure will affect fertility. ACGIH BIOLOGICAL EXPOSURE INDICES (BEls): Currently, there are no ACGIH Biological Exposure Indices (BEls) determined for this material. DEGREE OF EFFECT TO THE HEALTH OF THE POLLUTING AGENT OF ENVIRONMENT OF WORK (per Mexican NOM-010 STPS-1999): 0 12. ECOLOGICAL INFORMATION ALL WORK PRACTICES MUST BE AIMED AT ELIMINATING ENVIRONMENTAL CONTAMINATION. MOBILITY: This product has not been tested for mobility in soil. PERSISTENCE AND BIODEGRADABILITY: This product has not been tested for persistence or biodegradability. The mineral components are not expected to biodegrade to great extent. BIO-ACCUMULATION POTENTIAL: This product has not been tested for bio-accumulation potential. ECOTOXICITY: This product has not been tested for aquatic or animal toxicity. All releases to terrestrial, atmospheric and aquatic environments should be avoided. OTHER ADVERSE EFFECTS: This material is not listed as having ozone depletion potential. ENVIRONMENTAL EXPOSURE CONTROLS: Controls should be engineered to prevent release to the environment, including procedures to prevent spills, atmospheric release and release to waterways. 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: It is the responsibility of the generator to determine at the time of disposal whether the product meets the criteria of a hazardous waste per regulations of the area in which the waste is generated and/or disposed of. Waste disposal must be in accordance with appropriate Federal, State, National, International, and local regulations. This product, if unaltered by use, may be disposed of by treatment at a permitted facility or as advised by your local hazardous waste regulatory authority. Shipment of wastes must be done with appropriately permitted and registered transporters. DISPOSAL CONTAINERS: Waste materials must be placed in and shipped in appropriate 5-gallon or 55-gallon poly or metal waste pails or drums. Ensure that any required marking or labeling of the containers be done to all applicable regulations. PRECAUTIONS TO BE FOLLOWED DURING WASTE HANDLING: Wear proper protective equipment when handling waste materials. U.S. EPA WASTE NUMBER: Not applicable. SDS0002 - SPECSEAL® SSP FIRESTOP PUTTY/PUTTY PADS SIDS EFFECTIVE DATE: JULY 1, 2020 PAGE 9 OF 13 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. OFFICIAL MEXICAN STANDARD: REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: The components of this product are subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act as follows. CHEMICAL NAME SARA 302 (40 CFR 355, Appendix A) SARA 304 (40 CFR Table 302.4) SARA 313 (40 CFR 372.65) Formaldehyde Yes Yes Yes Phenol Yes Yes Yes U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-21): ACUTE: Yes; CHRONIC: Yes; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): Formaldehyde: 500 lb (27.2 kg); Phenol: 500 lb (27.2 kg) U.S. CERCLA Reportable Quantity (RQ): Formaldehyde: 100 lb (45.4 kg); Phenol: 1000 lb (454 kg) U.S. TSCA Inventory Status: Components of this product are listed on the TSCA Inventory. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): The Crystalline Silica and Formaldehyde (gas) components are on the California Proposition 65 lists. WARNING! This product contains compounds known to the State of California to cause Cancer. This product contains trace amounts of a suspected human carcinogen by inhalation; however, this hazard is not expected to be significant due to viscosity and consistency of the mixture. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: The Phenol and Formaldehyde components are on the CEPA Priorities Substances 2 List. Canadian WHMIS Classification and Symbols: This product would be categorized as a Controlled Product, D213 (Other Toxic Effects Potential Carcinogenic and Mutagenic Effect, Irritation, Skin Sensitization) as per the Controlled Product Regulations. CHINESE REGULATIONS: 0 Chinese Inventory of Existing Chemical Substances Status: Components listed by CAS# are listed on the Chinese Inventory of Existing Chemical Substances (IECSC), or are not listed, per information in Section 2. JAPANESE REGULATIONS: Japanese ENCS: Components listed by CAS# are on the ENCS Inventory, are excepted, or are not listed, per information in Section 2. Japanese Ministry of Economy, Trade, and Industry (METI) Status: Components are not listed as Class I Specified Chemical Substances, Class II Specified Chemical Substances, or Designated Chemical Substances by the Japanese METI. Poisonous and Deleterious Substances Control Law: Components are not listed as a Specified Poisonous Substance under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: Components listed by CAS# are listed on the Korean ECL Inventory, or are not listed, per information in Section 2. SDS0002 - SPECSEA0 SSP FIRESTOP PUTTY/PUTTY PADS EFFECTIVE DATE: JULY 1, 2020 PAGE 10 OF 13 MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: Components listed by CAS# are not listed on the Singapore List of Controlled Substances. Code of Practice on Pollution Control Requirements: The components identified by CAS# in Section 2 (Composition and Information on Ingredients) NOT are subject to the requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: Components listed by CAS# are listed on the Taiwan Existing Chemicals List. 16. OTHER INFORMATION REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification PREPARED BY: CHEMICAL SAFETY ASSOCIATES, Inc. • PO Box 1961, Hilo, HI 96721-1961 • (800) 441-3365 DATE OF PRINTING: July 1, 2020 REVISED: January 3, 2017 July 1, 2020 REVISION DETAILS: Reviewed January 3, 2017, no changes. Reviewed July 1, 2020, consolidated SSP Putty and SSP Putty Pads into single SIDS document. SDS0002 - SPECSEAL® SSP FIRESTOP PUTTY/PUTTY PADS EFFECTIVE DATE: JULY 1, 2020 PAGE 11 OF 13 DEFINITION OF TERMS A large number of abbreviations and acronyms appear on a SIDS. Some of these, which are commonly used, include the following: CAS #: This is the Chemical Abstract Service Number that uniquely identifies each constituent. FLAMMABILITY HAZARD (continued): 1 Slight Hazard: Materials that must be pre -heated before EXPOSURE LIMITS IN AIR: ignition can occur. Material requires considerable pre -heating, under all ambient temperature conditions before ignition and combustion can occur. This usually includes the following: Materials CEILING LEVEL: The concentration that shall not be exceeded during any part of the working that will burn in air when exposed to a temperature of 815.5°C (1500°F) for a period of 5 minutes exposure. or less; Liquids, solids and semisolids having a flash point at or above 93.3°C (200oF) (i.e. OSHA DFG MAKs: Federal Republic of Germany Maximum Concentration Values in the workplace. Class 11113); and Most ordinary combustible materials (e.g. wood, paper, etc.). 2 Moderate Hazard: Exposure limits are given as TWA (Time -Weighted Average) or PEAK (short-term exposure) values. Materials that must be moderately heated or exposed to relatively high ambient temperatures before DFG MAK Germ Cell Mutagen Categories: 1: Germ cell mutagens that have been shown to ignition can occur. Materials in this degree would not, under normal conditions, form hazardous increase the mutant frequency in the progeny of exposed humans. 2: Germ cell mutagens that have atmospheres in air, but under high ambient temperatures or moderate heating may release vapor been shown to increase the mutant frequency in the progeny of exposed mammals.3A: Substances in sufficient quantities to produce hazardous atmospheres with air. This usually includes the that have been shown to induce genetic damage in germ cells of human of animals, or which following: Liquids having a flash -point at or above 37.8°C (100°F); Solid materials in the form of produce mutagenic effects in somatic cells of mammals in vivo and have been shown to reach the course dusts that may burn rapidly but that generally do not form explosive atmospheres; 3 germ cells in an active form. 313: Substances that are suspected of being germ cell mutagens (continued): Solid materials in a fibrous or shredded form that may burn rapidly and create flash because of their genotoxic effects in mammalian somatic cell in vivo; in exceptional cases, fire hazards (e.g. cotton, sisal, hemp); and Solids and semisolids (e.g. viscous and slow flowing as substances for which there are no in vivo data, but that are clearly mutagenic in vitro and structurally asphalt) that readily give off flammable vapors. 3 Serious Hazard: Liquids and solids that can be related to known in vivo mutagens. 4: Not applicable (Category 4 carcinogenic substances are ignited under almost all ambient temperature conditions. Materials in this degree produce those with non-genotoxic mechanisms of action. By definition, germ cell mutagens are genotoxic. hazardous atmospheres with air under almost all ambient temperatures, or, unaffected by ambient Therefore, a Category 4 for germ cell mutagens cannot apply. At some time in the future, it is temperature, are readily ignited under almost all conditions. This usually includes the following: conceivable that a Category 4 could be established for genotoxic substances with primary targets Liquids having a flash point below 22.8°C (73°F) and having a boiling point at or above 38°C (100°F) other than DNA [e.g. purely aneugenic substances] if research results make this seem sensible.) 5: and those liquids having a flash point at or above 22.8°C (73°F) and below 37.8°C (100°F) (i.e. Germ cell mutagens, the potency of which is considered to be so low that, provided the MAK value OSHA Class IB and IC); Materials that on account of their physical form or environmental conditions is observed, their contribution to genetic risk for humans is expected not to be significant. can form explosive mixtures with air and are readily dispersed in air (e.g., dusts of combustible DFG MAK Pregnancy Risk Group Classification: Group A: A risk of damage to the developing solids, mists or droplets of flammable liquids); and Materials that burn extremely rapidly, usually by embryo or fetus has been unequivocally demonstrated. Exposure of pregnant women can lead to reason of self-contained oxygen (e.g. dry nitrocellulose and many organic peroxides). 4 Severe damage of the developing organism, even when MAK and BAT (Biological Tolerance Value for Hazard: Materials that will rapidly or completely vaporize at atmospheric pressure and normal Working Materials) values are observed. Group B: Currently available information indicates a risk ambient temperature or that are readily dispersed in air, and that will burn readily. This usually of damage to the developing embryo or fetus must be considered to be probable. Damage to the includes the following: Flammable gases; Flammable cryogenic materials; Any liquid or gaseous developing organism cannot be excluded when pregnant women are exposed, even when MAK material that is liquid while under pressure and has a flash point below 22.8°C (73°F) and a boiling and BAT values are observed. Group C: There is no reason to fear a risk of damage to the point below 37.8°C (100°F) (i.e. OSHA Class IA); and Materials that ignite spontaneously when developing embryo or fetus when MAK and BAT values are observed. Group D: Classification in exposed to air at a temperature of 54.4°C (130°F) or below (pyrophoric). one of the groups A—C is not yet possible because, although the data available may indicate a trend, PHYSICAL HAZARD: 0 Water Reactivity. Materials that do not react with water. Organic Peroxides: they are not sufficient for final evaluation. Materials that are normally stable, even under fire conditions and will not react with water. IDLH: Immediately Dangerous to Life and Health. This level represents a concentration from which Explosives: Substances that are Non -Explosive. Compressed Gases: No Rating. Pyrophorics: No one can escape within 30-minutes without suffering escape -preventing or permanent injury. LOO: Rating. Oxidizers: No 0 rating. Unstable Reactives: Substances that will not polymerize, Limit of Quantitation. decompose, condense, or self -react.). 1 Water Reactivity: Materials that change or decompose NE: Not Established. When no exposure guidelines are established, an entry of NE is made for upon exposure to moisture. Organic Peroxides: Materials that are normally stable, but can become reference. unstable at high temperatures and pressures. These materials may react with water, but will not NIC: Notice of Intended Change. release energy violently. Explosives: Division 1.5 & 1.6 explosives. Substances that are very NIOSH CEILING: The exposure that shall not be exceeded during any part of the workday. If insensitive explosives or that do not have a mass explosion hazard. Compressed Gases: Pressure instantaneous monitoring is not feasible, the ceiling shall be assumed as a 15-minute TWA below OSHA definition. Pyrophorics: No Rating. Oxidizers: Packaging Group III oxidizers; Solids: exposure (unless otherwise specified) that shall not be exceeded at any time during a workday. any material that in either concentration tested, exhibits a mean burning time less than or equal to NIOSH RELs: NIOSH's Recommended Exposure Limits. the mean burning time of a 3:7 potassium bromate/cellulose mixture and the criteria for Packing PEL: OSHA's Permissible Exposure Limits. This exposure value means exactly the same as a TLV, Group I and 11 are not met. Liquids: any material that exhibits a mean pressure rise time less than except that it is enforceable by OSHA. The OSHA Permissible Exposure Limits are based in the or equal to the pressure rise time of a 1:1 nitric acid (65%)/cellulose mixture and the criteria for 1989 PELs and the June, 1993 Air Contaminants Rule (Federal Register: 58: 35338-35351 and 58: Packing Group I and 11 are not met. Unstable Reactives: Substances that may decompose 40191). Both the current PELs and the vacated PELs are indicated. The phrase, 'Vacated 1989 condense, or self -react, but only under conditions of high temperature and/or pressure and have PEL" is placed next to the PEL that was vacated by Court Order. little or no potential to cause significant heat generation or explosion hazard. Substances that readily SKIN: Used when a there is a danger of cutaneous absorption. undergo hazardous polymerization in the absence of inhibitors. 2 Water Reactivity. Materials that STEL: Short Term Exposure Limit, usually a 15-minute time -weighted average (TWA) exposure may react violently with water. Organic Peroxides: Materials that, in themselves, are normally that should not be exceeded at any time during a workday, even if the 8-hr TWA is within the TLV- unstable and will readily undergo violent chemical change, but will not detonate. These materials TWA, PEL-TWA or REL-TWA. may also react violently with water. Explosives: Division 1.4 explosives. Explosive substances TLV: Threshold Limit Value. An airborne concentration of a substance that represents conditions where the explosive effects are largely confined to the package and no projection of fragments of under which it is generally believed that nearly all workers may be repeatedly exposed without appreciable size or range are expected. An external fire must not cause virtually instantaneous adverse effect. The duration must be considered, including the 8-hour. explosion of almost the entire contents of the package. Compressed Gases: Pressurized and meet TWA: Time Weighted Average exposure concentration for a conventional 8-hr (TLV, PEL) or up to OSHA definition but < 514.7 psi absolute at 21.1 °C (70°F) [500 psig]. Pyrophorics: No Rating. a 10-hr (REL) workday and a 40-hr workweek. WEEL: Workplace Environmental Exposure Limits Oxidizers: Packing Group 11 oxidizers. Solids: any material that, either in concentration tested, from the AIHA. exhibits a mean burning time of less than or equal to the mean burning time of a 2:3 potassium HAZARDOUS MATERIALS IDENTIFICATION SYSTEM HAZARD bromate/cellulose mixture and the criteria for Packing Group I are not met. Liquids: any material that exhibits a mean pressure rise time less than or equal to the pressure rise of a 1:1 aqueous RATINGS: This rating system was developed by the National Paint and Coating Association sodium chlorate solution (40%)/cellulose mixture and the criteria for Packing Group I are not met. and has been adopted by industry to identify the degree of chemical hazards. Reactives: Substances that may polymerize, decompose, condense, or self -react at ambient HEALTH HAZARD: 0 Minimal Hazard: No significant health risk, irritation of skin or eyes not temperature and/or pressure, but have a low potential (or low risk) for significant heat generation or anticipated. Skin Irritation: Essentially non -irritating. Mechanical irritation may occur. PII or Draize explosion. Substances that readily form peroxides upon exposure to air or oxygen at room = 0. Eye Irritation: Essentially non -irritating, minimal effects clearing in < 24 hours. Mechanical temperature. 3 Water Reactivity: Materials that may form explosive reactions with water. Organic irritation may occur. Draize = 0. Oral Toxicity LDso Rat: > 5000 mg/kg. Dermal Toxicity LDso Rat or Peroxides: Materials that are capable of detonation or explosive reaction, but require a strong Rabbit. > 2000 mg/kg. Inhalation Toxicity 4-hrs LCso Rat. > 20 mg/L. 1 Slight Hazard: Minor initiating source or must be heated under confinement before initiation; or materials that react reversible injury may occur; may irritate the stomach if swallowed; may defat the skin and explosively with water. Explosives: Division 1.3 explosives. Explosive substances that have a fire exacerbate existing dermatitis. Skin Irritation: Slightly or mildly irritating. PII or Draize > 0 < 5. Eye hazard and either a minor blast hazard or a minor projection hazard or both, but do not have a mass Irritation: Slightly to mildly irritating, but reversible within 7 days. Draize > 0 s 25. Oral Toxicity LDso explosion hazard. Compressed Gases: Rat: >500-0000mg/kg. Dermal Toxicity LDso Rat or Rabbit: > 1000-2000 mg/kg. Inhalation Toxicity Pressure z 514.7 psi absolute at 21.1°C (70oF) [500 psig]. Pyrophorics: No Rating. Oxidizers: LCso 4-hrs Rat: > 2-20 mg/L. 2 Moderate Hazard: Packing Group I oxidizers. Solids: any material that, in either concentration tested, exhibits a mean Temporary or transitory injury may Skin Irritation occur; prolonged exposure burning timeless than the mean burning time ofa 3:2 potassium bromate/cellulose mixture. Liquids: may affect the CNS.: Moderately irritating; primary any material that spontaneously ignites when mixed with cellulose in a 1:1 ratio, or which exhibits a irritant; sensitizer. PII or Draize z 5, with no destruction of dermal tissue. Eye Irritation: Moderately mean pressure rise time less than the pressure rise time of a 1:1 perchloric acid (50%)/cellulose to severely irritating; reversible corneal opacity; corneal involvement or irritation clearing in 8-21 mixture. Unstable Reactives: Substances that may polymerize, decompose, condense, or self -react days. Draize = 26-100, with reversible effects. Oral Toxicity LDso Rat: > 50-500 mg/kg. Dermal at ambient temperature and/or pressure and have a moderate potential (or moderate risk) to cause Toxicity LDso Rat or Rabbit: > 200-1000 mg/kg. Inhalation Toxicity LCso 4-hrs Rat > 0.5-2 mg/L. 3 significant heat generation or explosion. 4 Water Reactivity. Materials that react explosively with Serious Hazard: Major injury likely unless prompt action is taken and medical treatment is given; water without requiring heat or confinement. Organic Peroxides: Materials that are readily capable high level of toxicity; corrosive. Skin Irritation: Severely irritating and/or corrosive; may cause of detonation or explosive decomposition at normal temperature and pressures. Explosives: destruction of dermal tissue, skin burns, and dermal necrosis. PII or Draize > 5-8, with destruction Division 1.1 & 1.2 explosives. Explosive substances that have a mass explosion hazard or have a of tissue. Eye Irritation: Corrosive, irreversible destruction of ocular tissue; corneal involvement or projection hazard. A mass explosion is one that affects almost the entire load instantaneously. irritation persisting for more than 21 days. Draize > 80 with effects irreversible in 21 days. Oral Compressed Gases: No Rating. Pyrophorics: Add to the definition of Flammability 4. Oxidizers: No Toxicity LDso Rat. > 1-50 mg/kg. Dermal Toxicity LDso Rat or Rabbit. > 20-200 mg/kg. Inhalation 4 rating. Unstable Reactives: Substances that may polymerize, decompose, condense, or self -react Toxicity LCso 4-hrs Rat: > 0.05-0.5 mg/L. 4 Severe Hazard: Lifethreatening; major or permanent damage may result from single or repeated exposures; extremely toxic; irreversible injury may result from brief contact. Skin Irritation: Not appropriate. Do not rate as a 4, based on skin irritation alone. Eye Irritation: Not appropriate. Do not rate as a 4, based on eye irritation alone. Oral Toxicity LDso Rat: 5 1 mg/kg. Dermal Toxicity LDso Rat or Rabbit. 5 20 mg/kg. Inhalation Toxicity LCso 4-hrs Rat: 5 0.05 mg/L. FLAMMABILITY HAZARD: 0 Minimal Hazard: Materials that will not burn in air when exposure to a temperature of 815.5°C (1500°F) for a period of 5 minutes. HAZARDOUS MATERIALS IDENTIFICATION SYSTEM HAZARD RATINGS (continued): SDS0002 - SPECSEAL° SSP FIRESTOP PUTTY/PUTTY PADS EFFECTIVE DATE: JULY 1, 2020 PAGE 12 OF 13 at ambient temperature and/or pressure and have a high potential (or high risk) to cause significant ignite when exposed to air, Solids containing greater than 0.5% by weight of a flammable or heat generation or explosion. combustible solvent are rated by the closed cup flash point of the solvent. 4 Materials that will DEFINITION OF TERMS (Continued) NATIONAL FIRE PROTECTION ASSOCIATION HAZARD RATINGS: HEALTH HAZARD: 0 Materials that, under emergency conditions, would offer no hazard beyond that of ordinary combustible materials. Gases and vapors with an LC5o for acute inhalation toxicity greater than 10,000 ppm. Dusts and mists with an LC5o for acute inhalation toxicity greater than 200 mg/L. Materials with an LD5o for acute dermal toxicity greater than 2000 mg/kg. Materials with an LD5o for acute oral toxicity greater than 2000 mg/kg. Materials essentially non -irritating to the respiratory tract, eyes, and skin. 1 Materials that, under emergency conditions, can cause significant irritation. Gases and vapors with an LC5o for acute inhalation toxicity greater than 5,000 ppm but less than or equal to 10,000 ppm. Dusts and mists with an LCso for acute inhalation toxicity greater than 10 mg/L but less than or equal to 200 mg/L. Materials with an LD5o for acute dermal toxicity greater than 1000 mg/kg but less than or equal to 2000 mg/kg. Materials that slightly to moderately irritate the respiratory tract, eyes and skin. Materials with an LD5o for acute oral toxicity greater than 500 mg/kg but less than or equal to 2000 mg/kg. 2 Materials that, under emergency conditions, can cause temporary incapacitation or residual injury. Gases with an LC5o for acute inhalation toxicity greater than 3,000 ppm but less than or equal to 5,000 ppm. Any liquid whose saturated vapor concentration at 20°C (68°F) is equal to or greater than onefiffh its LC5o for acute inhalation toxicity, if its LC5o is less than or equal to 5000 ppm and that does not meet the criteria for either degree of hazard 3 or degree of hazard 4. Dusts and mists with an LC5o for acute inhalation toxicity greater than 2 mg/L but less than or equal to 10 mg/L. Materials with an LD5o for acute dermal toxicity greater than 200 mg/kg but less than or equal to 1000 mg/kg. Compressed liquefied gases with boiling points between -30oC (-22°F) and -55°C (66.5°F) that cause severe tissue damage, depending on duration of exposure. Materials that are respiratory irritants. Materials that cause severe, but reversible irritation to the eyes or are lachrymators. Materials that are primary skin irritants or sensitizers. Materials whose LD5o for acute oral toxicity is greater than 50 mg/kg but less than or equal to 500 mg/kg. 3 Materials that, under emergency conditions, can cause serious or permanent injury. Gases with an LCso for acute inhalation toxicity greater than 1,000 ppm but less than or equal to 3,000 ppm. Any liquid whose saturated vapor concentration at 20oC (68°F) is equal to or greater its LC5o for acute inhalation toxicity, if its LC5o is less than or equal to 3000 ppm and that does not meet the criteria for degree of hazard 4. Dusts and mists with an LC5o for acute inhalation toxicity greater than 0.5 mg/L but less than or equal to 2 mg/L. Materials with an LD5o for acute dermal toxicity greater than 40 mg/kg but less than or equal to 200 mg/kg. Materials that are corrosive to the respiratory tract. Materials that are corrosive to the eyes or cause irreversible corneal opacity. Materials corrosive to the skin. Cryogenic gases that cause frostbite and irreversible tissue damage. Compressed liquefied gases with boiling points below -55°C (-66.5°F) that cause frostbite and irreversible tissue damage. Materials with an LD5o for acute oral toxicity greater than 5 mg/kg but less than or equal to 50 mg/kg. HEALTH HAZARD (continued): 4 Materials that, under emergency conditions, can be lethal. Gases with an LC5o for acute inhalation toxicity less than or equal to 1,000 ppm. Any liquid whose saturated vapor concentration at 20oC (68°F) is equal to or greater than ten times its LC5o for acute inhalation toxicity, if its LC5o is less than or equal to 1000 ppm. Dusts and mists whose LC5o for acute inhalation toxicity is less than or equal to 0.5 mg/L. Materials whose LD5o for acute dermal toxicity is less than or equal to 40 mg/kg. Materials whose LD5o for acute oral toxicity is less than or equal to 5 mg/kg. FLAMMABILITY HAZARD: 0 Materials that will not bum under typical fire conditions, including intrinsically noncombustible materials such as concrete, stone, and sand. Materials that will not bum in air when exposed to a temperature of 816°C (1500°F) for a period of 5 minutes in according with Annex D of NFPA 704. 1 Materials that must be preheated before ignition can occur. Materials in this degree require considerable preheating, under all ambient temperature conditions, before ignition and combustion can occur: Materials that will bum in air when exposed to a temperature of 816°C (1500°F) for a period of 5 minutes in according with Annex D of NFPA 704. Liquids, solids, and semisolids having a flash point at or above 93.4°C (200°F) (i.e. Class 11113 liquids). Liquids with a flash point greater than 35°C (95°F) that do not sustain combustion when tested using the Method of Testing for Sustained Combustibility, per 49 CFR 173, Appendix H or the UN Recommendations on the Transport of Dangerous Goods, Model Regulations (current edition) and the related Manual of Tests and Criteria (current edition). Liquids with a flash point greater than 35°C (95°F) in a water - miscible solution or dispersion with a water noncombustible liquid/solid content of more than 85 % by weight. Liquids that have no fire point when tested by ASTM D 92, Standard Test Method for Flash and Fire Points by Cleveland Open Cup, up to the boiling point of the liquid or up to a temperature at which the sample being tested shows an obvious physical change. Combustible pellets with a representative diameter of greater than 2 mm (10 mesh). Most ordinary combustible materials. Solids containing greater than 0.5% by weight of a flammable or combustible solvent are rated by the closed cup flash point of the solvent. 2 Materials that must be moderately heated or exposed to relatively high ambient temperatures before ignition can occur. Materials in this degree would not under normal conditions form hazardous atmospheres with air, but under high ambient temperatures or under moderate heating could release vapor in sufficient quantities to produce hazardous atmospheres with air. Liquids having a flash point at or above 37.8°C (100°F) and below 93.4°C (200-F) (i.e. Class 11 and Class IIIA liquids.) Solid materials in the form of powders or coarse dusts of representative diameter between 420 microns (40 mesh) and 2 mm (10 mesh) that bum rapidly but that generally do not form explosive mixtures with air. Solid materials in fibrous or shredded form that burn rapidly and create flash fire hazards, such as cotton, sisal, and hemp. Solids and semisolids that readily give off flammable vapors. Solids containing greater than 0.5% by weight of a flammable or combustible solvent are rated by the closed cup flash point of the solvent. 3 Liquids and solids that can be ignited under almost all ambient temperature conditions. Materials in this degree produce hazardous atmospheres with air under almost all ambient temperatures or, though unaffected by ambient temperatures, are readily ignited under almost all conditions. Liquids having a flash point below 22.8°C (73°F) and having a boiling point at or above 37.8°C (100°F) and those liquids having a flash point at or above 22.8°C (73°F) and below 37.8°C (100°F) (i.e. Class IB and IC liquids). Materials that on account of their physical form or environmental conditions can form explosive mixtures with air and are readily dispersed in air. Flammable or combustible dusts with representative diameter less than 420 microns (40 mesh). NATIONAL FIRE PROTECTION ASSOCIATION HAZARD RATINGS (continued): Materials that bum with extreme rapidity, usually by reason of self-contained oxygen (e.g. dry nitrocellulose and many organic peroxides). Solids containing greater than 0.5% by weight of a flammable or combustible solvent are rated by the closed cup flash point of the solvent. Materials that will rapidly or completely vaporize at atmospheric pressure and normal ambient temperature or that are readily dispersed in air and will burn readily. Flammable gases. Flammable cryogenic materials. Any liquid or gaseous materials that is liquid while under pressure and has a flash point below 22.8°C (73°F) and a boiling point below 37.8°C (100°F) (i.e. Class IA liquids). Materials that rapidly or completely vaporize at atmospheric pressure and normal ambient temperature or that are readily dispersed in air and will burn readily: Flammable gases. Flammable cryogenic materials. Any liquid or gaseous materials that is liquid while under pressure and has a flash point below 22.8°C (73°F) and a boiling point below 37.8°C (100°F) (i.e. Class IA liquids). Materials that ignite when exposed to air. Solids containing greater than 0.5 percent by weight of a flammable or combustible solvent are rated by the closed cup flash point of the solvent. INSTABILITY HAZARD: 0 Materials that in themselves are normally stable, even under fire conditions: Materials that have an estimated instantaneous power density (product of heat of reaction and reaction rate) at 250°C (482°F) below 0.01 W/mL. Materials that do not exhibit an exotherm at temperatures less than or equal to 500°C (932°F) when tested by differential scanning calorimetry. 1 Materials that in themselves are normally stable, but that can become unstable at elevated temperatures and pressures: Materials that have an estimated instantaneous power density (product of heat of reaction and reaction rate) at 2500C (482°F) at or above 0.01 W/mL and below 10 W/mL. 2 Materials that readily undergo violent chemical change at elevated temperatures and pressures: Materials that have an estimated instantaneous power density (product of heat of reaction and reaction rate) at 2500C (482°F) at or above 10 W/mL and below 100W/mL. 3 Materials that in themselves are capable of detonation or explosive decomposition or explosive reaction, but that require a strong initiating source or that must be heated under confinement before initiation: Materials that have an estimated instantaneous power density (product of heat of reaction and reaction rate) at 250°C (482°F) at or above 100 W/mL and below 1000 W/mL. Materials that are sensitive to thermal or mechanical shock at elevated temperatures and pressures. 4 Materials that in themselves are readily capable of detonation or explosive decomposition or explosive reaction at normal temperatures and pressures: Materials that have an estimated instantaneous power density (product of heat of reaction and reaction rate) at 250°C (482°F) of 1000 W/mL or greater. Materials that are sensitive to localized thermal or mechanical shock at normal temperatures and pressures. FLAMMABILITY LIMITS IN AIR: Much of the information related to fire and explosion is derived from the National Fire Protection Association (NFPA). Flash Point: Minimum temperature at which a liquid gives off sufficient vapor to form an ignitable mixture with air near the surface of the liquid or within the test vessel used. Autoignition Temperature: Minimum temperature of a solid, liquid, orgas required to initiate orcause self -sustained combustion in air with no other source of ignition. LEL: Lowest concentration of a flammable vapor or gas/air mixture thatwill ignite and burn with a flame. UEL: Highest concentration of a flammable vapor or gas/air mixture that will ignite and burn with a flame. TOXICOLOGICAL INFORMATION: Human and Animal Toxicology: Possible health hazards as derived from human data, animal studies, or from the results of studies with similar compounds are presented. LD5o: Lethal Dose (solids & liquids) that kills 50% of the exposed animals. LC5o: Lethal Concentration (gases) that kills 50 % of the exposed animals. ppm: Concentration expressed in parts of material per million parts of air or water. mq/m3: Concentration expressed in weight of substance per volume of air. mg/kg: Quantity of material, by weight, administered to a test subject, based on their body weight in kg. TDLo: Lowest dose to cause a symptom. TCLo: Lowest concentration to cause a symptom. TDo, LDLo, and LDo, or TC, TCo, LCLo, and LCo: Lowest dose (or concentration) to cause lethal or toxic effects. Cancer Information: IARC: International Agency for Research on Cancer. NTP: National Toxicology Program. RTECS: Registry of Toxic Effects of Chemical Substances. IARC and NTP rate chemicals on a scale of decreasing potential to cause human cancer with rankings from 1 to 4. Subrankings (2A, 2B, etc.) are also used. Other Information: BEL ACGIH Biological Exposure Indices, represent the levels of determinants which are most likely to be observed in specimens collected from a healthy worker who has been exposed to chemicals to the same extent as a worker with inhalation exposure to the TLV. ECOLOGICAL INFORMATION: EC: Effect concentration in water. BCF: Bioconcentration Factor, which is used to determine if a substance will concentrate in life forms that consume contaminated plant or animal matter. TLm: Median threshold limit. log Kow or log Koc: Coefficient of Oil/Water Distribution is used to assess a substance's behavior in the environment. REGULATORY INFORMATION: U.S.: EPA: U.S. Environmental Protection Agency. ACGIH: American Conference of Governmental Industrial Hygienists, a professional association that establishes exposure limits. OSHA: U.S. Occupational Safety and Health Administration. NIOSH: National Institute of Occupational Safety and Health, which is the research arm of OSHA. DOT: U.S. Department of Transportation. SARA: Superfund Amendments and Reauthorization Act. TSCA: U.S. Toxic Substance Control Act. CERCLA: Comprehensive Environmental Response, Compensation, and Liability Act. Marine Pollutant status according to the DOT; CERCLA or Superfund; and various state regulations. This section also includes information on the precautionary warnings that appear on the material's package label. CANADA: WHMIS: Canadian Workplace Hazardous Materials Information System. TC: Transport Canada. DSUNDSL: Canadian Domestic/Non-Domestic Substances List. JAPAN: METI: Ministry of Economy, Trade and Industry. SDS0002 - SPECSEAL® SSP FIRESTOP PUTTY/PUTTY PADS EFFECTIVE DATE: JULY 1, 2020 PAGE 13 OF 13 2V6 STI SAFETY DATA SHEET Prepared to U.S. OSHA, CMA, ANSI, Canadian WHMIS, the Korean ISHA (Notice 2009-68), the Japanese Industrial Standard JIS Z 7250: 2000, Mexican NOM018-STPS 2000, SPRING Singapore, and the Global Harmonization Standard 1. IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY UNDERTAKING IDENTIFICATION OF THE MIXTURE TRADE/MATERIAL NAME: RELEVANT USE of the SUBSTANCE: USES ADVISED AGAINST: SUPPLIER/MANUFACTURER'S NAME Address: Business Phone: Emergency Phone: SpecSeal° Series FP Intumescent Firestop Plug Firestop Device None Specified Technologies, Inc. 210 Evans Way, Somerville, New Jersey 08876 (908) 526-8000 (8:00am to 5:00pm Eastern Standard Time) U.S., Canada: 1-800-255-3924 (24 hrs) International: +1-813-248-0585 (Collect-24 hrs) EMAIL of ComDetent Person for Information on SDS: techsery anstifirestOD.com NOTE: ALL United States Occupational Safety and Health Administration Standard (29 CFR 1910.1200), U.S. State equivalent Standards, Canadian WHMIS [Controlled Products Regulations], Mexican NOM018-STPS 2000, SPRING Singapore, and Japanese JIS Z7250 required information is included in appropriate sections based on the U.S. ANSI Z400.1-2010 format. This product has been classified in accordance with the hazard criteria of the countries listed above. This product is defined as an "Article" under the U.S. Federal OSHA Hazard Communication Standard (29 CFR 1910.1200), EU Directives, and the Canadian Workplace Hazardous Materials Standard. Refer to Section 15 (Regulatory Information) for specific regulatory citations. As articles, this product presents negligible health and physical hazards under reasonably anticipated circumstances of use. Subsequently, a Material Safety Data Sheet is not required under Standards cited above. This document is prepared to provide persons using this product with additional safety information. 2. HAZARD IDENTIFICATION GLOBAL HARMONIZATION AND EU CLP REGULATION (EC) 1272/2008 LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under CLP Regulation (EC) 1272/2008. EU 67/548/EEC LABELING AND CLASSIFICATION: This product is an article and is not required to be classified under European Community Council Directive 67/548/EEC or subsequent Directives. KOREAN ISHA (Notice 2009-68) LABELING AND CLASSIFICATION: As an article, this product is not subject to ISHA Notice 2009-68. 3. COMPOSITION and INFORMATION ON INGREDIENTS This product is an article and as such no components of this product pose a hazard; no component information is given in this SDS. 4. FIRST -AID MEASURES Skin Exposure: As an article, no need for first aid is anticipated. Inhalation: As an article, no need for first aid is anticipated. Eve Exposure: As an article, no need for first aid is anticipated. Ingestion: As an article, no need for first aid is anticipated. 5. FIRE -FIGHTING MEASURES FIRE EXTINGUISHING MEDIA: Use extinguishing materials suitable for the surrounding area. UNSUITABLE FIRE EXTINGUISHING MEDIA: None known. UNUSUAL FIRE AND EXPLOSION HAZARDS: This product is formulated to be non-flammable and non-combustible. SPECIAL PROTECTIVE ACTIONS FOR FIRE-FIGHTERS: No Special protective actions for fire-fighters are anticipated. SPECSEAL° SERIES FP INTUMESCENT FIRESTOP PLUG SDS EFFECTIVE DATE: JANUARY 23, 2017 PAGE 1 OF 5 6. ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS AND EMERGENCY PROCEDURES: Not applicable. PERSONAL PROTECTIVE EQUIPMENT: Not applicable. METHODS FOR CLEAN-UP AND CONTAINMENT: Not applicable. ENVIRONMENTAL PRECAUTIONS: Not applicable. 7. HANDLING and STORAGE PRECAUTIONS FOR SAFE HANDLING: No special requirements. CONDITIONS FOR SAFE STORAGE: No special requirements. 8. EXPOSURE CONTROLS - PERSONAL PROTECTION EXPOSURE LIMITS/CONTROL PARAMETERS: As an article which does not release or otherwise result in exposure to hazardous chemicals under normal use, no personal protective equipment (PPE) is required 9. PHYSICAL and CHEMICAL PROPERTIES FORM: Solid. ODOR: Not available. FLAMMABLE LIMITS (in air by volume, %): Not available. DECOMPOSITION TEMPERATURE: Not available. AUTOIGNITION TEMPERATURE: Not available. FREEZING/MELTING POINT: Not available. VAPOR PRESSURE: Not applicable. VAPOR DENSITY (air = 1): Not applicable. EVAPORATION RATE (n-BuAc = 1): Not applicable. SOLUBILITY IN WATER: Insoluble. COEFFICIENT WATER/OIL DISTRIBUTION: Not established COLOR: Red. ODOR THRESHOLD: Not available. OXIDIZING PROPERTIES: Not applicable. PERCENT VOLATILE: 0 FLASH POINT: Not available. BOILING POINT: Not applicable. SPECIFIC GRAVITY (water = 1): Not applicable. CARB VOC: Not applicable. SCAQMD (U.S. EPA Method 24): Not applicable. SOLUBILITY IN SOLVENTS: Not applicable. pH: Not applicable. 10. STABILITY and REACTIVITY CHEMICAL STABILITY: This product is stable when properly stored at normal temperatures. 11. TOXICOLOGICAL INFORMATION SYMPTOMS OF EXPOSURE BY ROUTE OF EXPOSURE: Inhalation: Due to the form of the product, inhalation is unlikely. Contact with Skin or Eyes: Due to the form of the product, contact with the eyes is unlikely. Skin Absorption: Due to form of product, skin absorption is not a likely route of exposure. Ingestion: Ingestion is not a likely route of exposure, due to the form of the product. Infection: Injection is not likely, due to the form of the product. 12. ECOLOGICAL INFORMATION MOBILITY: As an article, this product will not be mobile in soil. PERSISTENCE AND BIODEGRADABILITY: No specific information is available regarding persistence and biodegradability. BIO-ACCUMULATION POTENTIAL: This product has not been tested for bio-accumulation potential. ECOTOXICITY: This product has not been tested for aquatic or animal toxicity. All releases to terrestrial, atmospheric and aquatic environments should be avoided. SPECSEAL° SERIES FP INTUMESCENT FIRESTOP PLUG SIDS EFFECTIVE DATE: JANUARY 23, 2017 PAGE 2 OF 5 13. DISPOSAL CONSIDERATIONS DISPOSAL METHODS: Waste disposal must be in accordance with appropriate Federal, State, and local regulations. U.S. EPA WASTE NUMBER: Not applicable. 14. TRANSPORTATION INFORMATION U.S. DEPARTMENT OF TRANSPORTATION REGULATIONS: This product is not classified as dangerous goods, per U.S. DOT regulations, under 49 CFR 172.101. TRANSPORT CANADA TRANSPORTATION OF DANGEROUS GOODS REGULATIONS: This product is not classified as Dangerous Goods, per regulations of Transport Canada. INTERNATIONAL AIR TRANSPORT ASSOCIATION (IATA): This product is not classified as dangerous goods under rules of IATA. INTERNATIONAL MARITIME ORGANIZATION (IMO) DESIGNATION: This product is not classified as Dangerous Goods by the International Maritime Organization. OFFICIAL MEXICAN STANDARD; REGULATION FOR THE TRANSPORT OF DANGEROUS GOODS AND RESIDUES: This product is not classified as Dangerous Goods, per transport regulations of Mexico. SINGAPORE STANDARD 286: PART A: This product has no requirements under the Specification for Caution Labeling for Hazardous Substances, Part 4: Marking of Packages, Containers and Vehicles, as it does not meet the criteria for any hazard class under this regulation. TRANSPORT IN BULK ACCORDING TO THE IBC CODE: See the information under the individual jurisdiction listings for IBC information. ENVIRONMENTAL HAZARDS: This material does not meet the criteria of environmentally hazardous according to the criteria of the UN Model Regulations (as reflected in the IMDG Code, ADR, RID, and ADN) and is not listed in Annex III under MARPOL 73/78. 15. REGULATORY INFORMATION UNITED STATES REGULATIONS: U.S. SARA Reporting Requirements: As an article, this product is not subject to the reporting requirements of Sections 302, 304, and 313 of Title III of the Superfund Amendments and Reauthorization Act. U.S. SARA Hazard Categories (Section 311/312, 40 CFR 370-21): ACUTE: No; CHRONIC: No; FIRE: No; REACTIVE: No; SUDDEN RELEASE: No U.S. SARA Threshold Planning Quantity (TPQ): As an article, this product is not subject to Threshold Planning Quantities, per 40 CFR 370.20. U.S. CERCLA Reportable Quantity (RQ): Not applicable. U.S. TSCA Inventory Status: Components of this product are listed on the TSCA Inventory. California Safe Drinking Water and Toxic Enforcement Act (Proposition 65): No component is on the California Proposition 65 lists. CANADIAN REGULATIONS: Canadian DSL/NDSL Inventory Status: Components are on the DSL or NDSL Inventories. Canadian Environmental Protection Act (CEPA) Priorities Substances Lists: As a phthalate, the Undecyl Alcohol Phthalate component is regulated by the CEPA as a substance that may present, to individuals in Canada, the greatest potential for exposure; or is persistent or bioaccumulative in accordance with the regulations, and inherently toxic to human beings or to non -human organisms, as determined by laboratory or other studies.. Canadian WHMIS Classification and Symbols: As an article, this product is not subject the Controlled Product Regulations. CHINESE REGULATIONS: Chinese Inventory of Existing Chemical Substances Status: As an article, this product is not subjected to requirements under the Chinese Inventory of Existing Chemical Substances (IECSC). JAPANESE REGULATIONS: Japanese ENCS: As an article, this product is not subjected to requirements under ENCS Inventory. Japanese Ministry of Economy, Trade, and Industry (METI) Status: As an article, this product is not subjected to requirements under the Japanese METI. Poisonous and Deleterious Substances Control Law: As an article, this product is not subjected to requirements under the Poisonous and Deleterious Substances Control Law. KOREAN REGULATIONS: Korean Existing Chemicals List (ECL) Status: As an article, this product is not subjected to requirements under the Korean ECL Inventory. MEXICAN REGULATIONS: Mexican Workplace Regulations (NOM-018-STPS-2000): This product is not classified as hazardous. SINGAPORE REGULATIONS: List of Controlled Hazardous Substances: As an article, this product is not subjected to requirements under the Singapore List of Controlled Substances. Code of Practice on Pollution Control Requirements: As an article, this product is not subjected to requirements under the Singapore Code of Practice on Pollution Control. TAIWANESE REGULATIONS: Taiwan Existing Chemical Substances Inventory Status: As an article, this product is not subjected to requirements under the Taiwan Existing Chemicals List. SPECSEAL° SERIES FP INTUMESCENT FIRESTOP PLUG SIDS EFFECTIVE DATE: JANUARY 23, 2017 PAGE 3 OF 5 16. OTHER INFORMATION REVISION DETAILS: Reviewed January 23, 2017, no changes necessary. REFERENCES AND DATA SOURCES: Contact the supplier for information. METHODS OF EVALUATING INFORMATION FOR THE PURPOSE OF CLASSIFICATION: Criteria of the GHS were used for classification. PREPARED BY: CHEMICAL SAFETY ASSOCIATES, Inc. • PO Box 1961, Hilo, HI 96721-1961 • (800) 441-3365 DATE OF PRINTING: January 23, 2017 REVISED: January 23, 2017 DEFINITION OF TERMS A large number of abbreviations and acronyms appear on a BIDS. Some of these, which are commonly used, include the following: CAS #: This is the Chemical Abstract Service Number that uniquely identifies each constituent. HAZARDOUS MATERIALS IDENTIFICATION SYSTEM HAZARD EXPOSURE LIMITS IN AIR: RATINGS (continued): CEILING LEVEL: The concentration that shall not be exceeded during any part of the working FLAMMABILITY HAZARD (continued): 1 Slight Hazard: Materials that must be pre -heated before exposure. DFG MAKs: Federal Republic of Germany Maximum Concentration Values in the workplace. ignition can occur. Material requires considerable pre -heating, under all ambient temperature conditions before ignition and combustion can occur. This usually includes the following: Materials Exposure limits are given as TWA (Time -Weighted Average) or PEAK (short-term exposure) values. that will burn in air when exposed to a temperature of 815.5°C (1500°F) for a period of 5 minutes DFG MAK Germ Cell Mutagen Categories: 1: Germ cell mutagens that have been shown to or less; Liquids, solids and semisolids having a flash point at or above 93.3°C (200°F) (i.e. OSHA increase the mutant frequency in the progeny of exposed humans. 2: Germ cell mutagens that Class IIIB); and Most ordinary combustible materials (e.g. wood, paper, etc.). 2 Moderate Hazard: have been shown to increase the mutant frequency in the progeny of exposed mammals. 3A: Materials that must be moderately heated or exposed to relatively high ambient temperatures Substances that have been shown to induce genetic damage in germ cells of human of animals, before ignition can occur. Materials in this degree would not, under normal conditions, form or which produce mutagenic effects in somatic cells of mammals in vivo and have been shown to hazardous atmospheres in air, but under high ambient temperatures or moderate heating may reach the germ cells in an active form. 3B: Substances that are suspected of being germ cell release vapor in sufficient quantities to produce hazardous atmospheres with air. This usually mutagens because of their genotoxic effects in mammalian somatic cell in vivo; in exceptional includes the following: Liquids having a flash -point at or above 37.8°C (100°F); Solid materials in cases, substances for which there are no in vivo data, but that are clearly mutagenic in vitro and the form of course dusts that may burn rapidly but that generally do not form explosive structurally related to known in vivo mutagens. 4: Not applicable (Category 4 carcinogenic atmospheres; 3 (continued): Solid materials in a fibrous or shredded form that may burn rapidly substances are those with non-genotoxic mechanisms of action. By definition, germ cell mutagens and create flash fire hazards (e.g. cotton, sisal, hemp); and Solids and semisolids (e.g. viscous and are genotoxic. Therefore, a Category 4 for germ cell mutagens cannot apply. At some time in the slow flowing as asphalt) that readily give off flammable vapors. 3 Serious Hazard: Liquids and future, it is conceivable that a Category 4 could be established for genotoxic substances with solids that can be ignited under almost all ambient temperature conditions. Materials in this degree primary targets other than DNA [e.g. purely aneugenic substances] if research results make this produce hazardous atmospheres with air under almost all ambient temperatures, or, unaffected by seem sensible.) 5: Germ cell mutagens, the potency of which is considered to be so low that, ambient temperature, are readily ignited under almost all conditions. This usually includes the provided the MAK value is observed, their contribution to genetic risk for humans is expected not following: Liquids having a flash point below 22.8°C (73°F) and having a boiling point at or above to be significant. DFG MAK Pregnancy Risk Group Classification: Group A: A risk of damage to the developing 38°C (100°F) and those liquids having a flash point at or above 22.8°C (73°F) and below 37.8°C (100°F) (i.e. OSHA Class IB and IC); Materials that on account of their physical form or embryo or fetus has been unequivocally demonstrated. Exposure of pregnant women can lead to environmental conditions can form explosive mixtures with air and are readily dispersed in air (e.g., damage of the developing organism, even when MAK and BAT (Biological Tolerance Value for dusts of combustible solids, mists or droplets of flammable liquids); and Materials that burn Working Materials) values are observed. Group B: Currently available information indicates a risk extremely rapidly, usually by reason of self-contained oxygen (e.g. dry nitrocellulose and many of damage to the developing embryo or fetus must be considered to be probable. Damage to the organic peroxides). 4 Severe Hazard: Materials that will rapidly or completely vaporize at developing organism cannot be excluded when pregnant women are exposed, even when MAK atmospheric pressure and normal ambient temperature or that are readily dispersed in air, and that and BAT values are observed. Group C: There is no reason to fear a risk of damage to the will bum readily. This usually includes the following: Flammable gases; Flammable cryogenic developing embryo or fetus when MAK and BAT values are observed. Group D: Classification in materials; Any liquid or gaseous material that is liquid while under pressure and has a flash point one of the groups A-C is not yet possible because, although the data available may indicate a below 22.8°C (73°F) and a boiling point below 37.8°C (100°F) (i.e. OSHA Class IA); and Materials trend, they are not sufficient for final evaluation. that ignite spontaneously when exposed to air at a temperature of 54.4°C (130°F) or below IDLH: Immediately Dangerous to Life and Health. This level represents a concentration from which (pyrophoric). one can escape within 30-minutes without suffering escape -preventing or permanent injury. PHYSICAL HAZARD: 0 Water Reactivity: Materials that do not react with water. Organic Peroxides: LOQ: Limit of Quantitation. Materials that are normally stable, even under fire conditions and will not react with water. NE: Not Established. When no exposure guidelines are established, an entry of NE is made for Explosives: Substances that are Non -Explosive. Compressed Gases: No Rating. Pyrophorics: No reference. NIC: Notice of Intended Change. Rating. Oxidizers: No 0 rating. Unstable Reactives: Substances that will not polymerize, NIOSH CEILING: The exposure that shall not be exceeded during any part of the workday. If decompose, condense, or self -react.). 1 Water Reactivity. Materials that change or decompose upon exposure to moisture. Organic Peroxides: Materials that are normally stable, but can become instantaneous monitoring is not feasible, the ceiling shall be assumed as a 15-minute TWA unstable at high temperatures and pressures. These materials may react with water, but will not exposure (unless otherwise specified) that shall not be exceeded at any time during a workday. release energy violently. Explosives: Division 1.5 & 1.6 explosives. Substances that are very NIOSH RELs: NIOSH's Recommended Exposure Limits. insensitive explosives or that do not have a mass explosion hazard. Compressed Gases: Pressure PEL: OSHA's Permissible Exposure Limits. This exposure value means exactly the same as a below OSHA definition. Pyrophorics: No Rating. Oxidizers: Packaging Group III oxidizers; Solids: TLV, except that it is enforceable by OSHA. The OSHA Permissible Exposure Limits are based in any material that in either concentration tested, exhibits a mean burning time less than or equal to the 1989 PELs and the June, 1993 Air Contaminants Rule (Federal Register: 58: 35338-35351 and the mean burning time of a 3:7 potassium bromate/cellulose mixture and the criteria for Packing 58: 40191). Both the current PELs and the vacated PELs are indicated. The phrase, "Vacated 1989 Group I and II are not met. Liquids: any material that exhibits a mean pressure rise time less than PEL" is placed next to the PEL that was vacated by Court Order. or equal to the pressure rise time of a 1:1 nitric acid (65%)/cellulose mixture and the criteria for SKIN: Used when a there is a danger of cutaneous absorption. Packing Group I and II are not met. Unstable Reactives: Substances that may decompose STEL: Short Term Exposure Limit, usually a 15-minute time -weighted average (TWA) exposure condense, or self -react, but only under conditions of high temperature and/or pressure and have that should not be exceeded at any time during a workday, even if the 8-hr TWA is within the TLV- little or no potential to cause significant heat generation or explosion hazard. Substances that TWA, PEL-TWA or REL-TWA. readily undergo hazardous polymerization in the absence of inhibitors. 2 Water Reactivity. TLV: Threshold Limit Value. An airborne concentration of a substance that represents conditions Materials that may react violently with water. Organic Peroxides: Materials that, in themselves, are under which it is generally believed that nearly all workers may be repeatedly exposed without normally unstable and will readily undergo violent chemical change, but will not detonate. These adverse effect. The duration must be considered, including the 8-hour. materials may also react violently with water. Explosives: Division 1.4 explosives. Explosive TWA: Time Weighted Average exposure concentration for a conventional 8-hr (TLV, PEL) or up to substances where the explosive effects are largely confined to the package and no projection of a 10-hr (REL) workday and a 40-hr workweek. fragments of appreciable size or range are expected. An external fire must not cause virtually WEEL: Workplace Environmental Exposure Limits from the AIHA. instantaneous explosion of almost the entire contents of the package. Compressed Gases: HAZARDOUS MATERIALS IDENTIFICATION SYSTEM HAZARD Pressurized and meet OSHA definition but < 514.7 psi absolute at 21.1°C (70°F) [500 prig]. RATINGS: This rating system was developed by the National Paint and Coating Association and Pyrophorics: No Rating. Oxidizers: Packing Group II oxidizers. Solids: any material that, either in has been adopted by industry to identify the degree of chemical hazards. concentration tested, exhibits a mean burning time of less than or equal to the mean burning time HEALTH HAZARD: 0 Minimal Hazard: No significant health risk, irritation of skin or eyes not of a 2:3 potassium bromate/cellulose mixture and the criteria for Packing Group I are not met. anticipated. Skin Irritation: Essentially non -irritating. Mechanical irritation may occur. PII or Draize Liquids: any material that exhibits a mean pressure rise time less than or equal to the pressure rise = 0. Eye Irritation: Essentially non -irritating, minimal effects clearing in < 24 hours. Mechanical of a 1:1 aqueous sodium chlorate solution (40%)/cellulose mixture and the criteria for Packing irritation may occur. Draize = 0. Oral Toxicity LD5o Rat > 5000 mg/kg. Dermal Toxicity LD50 Rat or Group I are not met. Reactives: Substances that may polymerize, decompose, condense, or self - Rabbit: > 2000 mg/kg. Inhalation Toxicity 4-hrs LC5o Rat: > 20 mg/L. 1 Slight Hazard: Minor react at ambient temperature and/or pressure, but have a low potential (or low risk) for significant reversible injury may occur; may irritate the stomach if swallowed; may defat the skin and heat generation or explosion. Substances that readily form peroxides upon exposure to air or exacerbate existing dermatitis. Skin Irritation: Slightly or mildly irritating. PII or Draize > 0 < 5. Eye oxygen at room temperature. 3 Water Reactivity. Materials that may form explosive reactions with Irritation: Slightly to mildly irritating, but reversible within 7 days. Draize > 0 s 25. Oral Toxicity LD5o water. Organic Peroxides: Materials that are capable of detonation or explosive reaction, but Rat: > 500-5000 mg/kg. Dermal Toxicity LD5o Rat or Rabbit > 1000-2000 mg/kg. Inhalation require a strong initiating source or must be heated under confinement before initiation; or materials Toxicity LC5o 4-hrs Rat > 2-20 mg/L. 2 Moderate Hazard: Temporary or transitory injury may occur; that react explosively with water. Explosives: Division 1.3 explosives. Explosive substances that prolonged exposure may affect the CNS. Skin Irritation: Moderately irritating; primary irritant; have a fire hazard and either a minor blast hazard or a minor projection hazard or both, but do not sensitizer. PII or Draize a 5, with no destruction of dermal tissue. Eye Irritation: Moderately to have a mass explosion hazard. Compressed Gases: Pressure >- 514.7 psi absolute at 21.1°C severely irritating; reversible corneal opacity; corneal involvement or irritation clearing in 8-21 days. (70°F) [500 psig]. Pyrophorics: No Rating. Oxidizers: Packing Group I oxidizers. Solids: any Draize = 26-100, with reversible effects. Oral Toxicity LD5o Rat > 50-500 mg/kg. Dermal Toxicity material that, in either concentration tested, exhibits a mean burning time less than the mean LD50 Rat or Rabbit > 200-1000 mg/kg. Inhalation Toxicity LC5o 4-hrs Rat > 0.5-2 mg/L. 3 Serious burning time of a 3:2 potassium bromate/cellulose mixture. Liquids: any material that Hazard: Major injury likely unless prompt action is taken and medical treatment is given; high level spontaneously ignites when mixed with cellulose in a 1:1 ratio, or which exhibits a mean pressure of toxicity; corrosive. Skin Irritation: Severely irritating and/or corrosive; may cause destruction of rise time less than the pressure rise time of a 1:1 perchloric acid (50%)/cellulose mixture. Unstable dermal tissue, skin burns, and dermal necrosis. PII or Draize > 5-8, with destruction of tissue. Eye Reactives: Substances that may polymerize, decompose, condense, or self -react at ambient Irritation: Corrosive, irreversible destruction of ocular tissue; corneal involvement or irritation temperature and/or pressure and have a moderate potential (or moderate risk) to cause significant persisting for more than 21 days. Draize > 80 with effects irreversible in 21 days. Oral Toxicity LD5o heat generation or explosion. 4 Water Reactivity Materials that react explosively with water without Rat: > 1-50 mg/kg. Dermal Toxicity LD5o Rat or Rabbit > 20-200 mg/kg. Inhalation Toxicity LCW requiring heat or confinement. Organic Peroxides: Materials that are readily capable of detonation 4-hrs Rat: > 0.05-0.5 mg/L. 4 Severe Hazard: Life -threatening; major or permanent damage may or explosive decomposition at normal temperature and pressures. Explosives: Division 1.1 & 1.2 result from single or repeated exposures; extremely toxic; irreversible injury may result from brief explosives. Explosive substances that have a mass explosion hazard or have a projection hazard. contact. Skin Irritation: Not appropriate. Do not rate as a 4, based on skin irritation alone. Eye A mass explosion is one that affects almost the entire load instantaneously. Compressed Gases: Irritation: Not appropriate. Do not rate as a 4, based on eye irritation alone. Oral Toxicity LD5o Rat: No Rating. Pyrophorics: Add to the definition of Flammability 4. Oxidizers: No 4 rating. Unstable <- 1 mg/kg. Dermal Toxicity LD50 Rat or Rabbit <- 20 nri Inhalation Toxicity LC50 4-hrs Rat: <- Reactives: Substances that may polymerize, decompose, condense, or self -react at ambient 0.05 mg/L. temperature and/or pressure and have a high potential (or high risk) to cause significant heat FLAMMABILITY HAZARD: 0 Minimal Hazard: Materials that will not burn in air when exposure to generation or explosion. a temperature of 815.5°C (1500°F) for a period of 5 minutes. SPECSEAL® SERIES FP INTUMESCENT FIRESTOP PLUG SDS EFFECTIVE DATE: JANUARY 23, 2017 PAGE 4 OF 5 DEFINITION OF TE NATIONAL FIRE PROTECTION ASSOCIATION HAZARD RATINGS: HEALTH HAZARD: 0 Materials that, under emergency conditions, would offer no hazard beyond that of ordinary combustible materials. Gases and vapors with an LC5o for acute inhalation toxicity greater than 10,000 ppm. Dusts and mists with an LC5o for acute inhalation toxicity greater than 200 mg/L. Materials with an LD5o for acute dermal toxicity greater than 2000 mg/kg. Materials with an LD5o for acute oral toxicity greater than 2000 mg/kg. Materials essentially non -irritating to the respiratory tract, eyes, and skin. 1 Materials that, under emergency conditions, can cause significant irritation. Gases and vapors with an LC5o for acute inhalation toxicity greater than 5,000 ppm but less than or equal to 10,000 ppm. Dusts and mists with an LC50 for acute inhalation toxicity greater than 10 mg/L but less than or equal to 200 mg/L. Materials with an LD5o for acute dermal toxicity greater than 1000 mg/kg but less than or equal to 2000 mg/kg. Materials that slightly to moderately irritate the respiratory tract, eyes and skin. Materials with an LD5o for acute oral toxicity greater than 500 mg/kg but less than or equal to 2000 mg/kg. 2 Materials that, under emergency conditions, can cause temporary incapacitation or residual injury. Gases with an LC5o for acute inhalation toxicity greater than 3,000 ppm but less than or equal to 5,000 ppm. Any liquid whose saturated vapor concentration at 20°C (68°F) is equal to or greater than one -fifth its LC5o for acute inhalation toxicity, if its LC5o is less than or equal to 5000 ppm and that does not meet the criteria for either degree of hazard 3 or degree of hazard 4. Dusts and mists with an LC5o for acute inhalation toxicity greater than 2 mg/L but less than or equal to 10 mg/L. Materials with an LD5o for acute dermal toxicity greater than 200 mg/kg but less than or equal to 1000 mg/kg. Compressed liquefied gases with boiling points between -30°C (-22°F) and -55°C (-66.5°F) that cause severe tissue damage, depending on duration of exposure. Materials that are respiratory irritants. Materials that cause severe, but reversible irritation to the eyes or are lachrymators. Materials that are primary skin irritants or sensitizers. Materials whose LD5o for acute oral toxicity is greater than 50 mg/kg but less than or equal to 500 mg/kg. 3 Materials that, under emergency conditions, can cause serious or permanent injury. Gases with an LC5o for acute inhalation toxicity greater than 1,000 ppm but less than or equal to 3,000 ppm. Any liquid whose saturated vapor concentration at 20°C (68°F) is equal to or greater its LC5o for acute inhalation toxicity, if its LC5o is less than or equal to 3000 ppm and that does not meet the criteria for degree of hazard 4. Dusts and mists with an LC50 for acute inhalation toxicity greater than 0.5 mg/L but less than or equal to 2 mg/L. Materials with an LD5o for acute dermal toxicity greater than 40 mg/kg but less than or equal to 200 mg/kg. Materials that are corrosive to the respiratory tract. Materials that are corrosive to the eyes or cause irreversible corneal opacity. Materials corrosive to the skin. Cryogenic gases that cause frostbite and irreversible tissue damage. Compressed liquefied gases with boiling points below -55°C (- 66.5°F) that cause frostbite and irreversible tissue damage. Materials with an LD5o for acute oral toxicity greater than 5 mg/kg but less than or equal to 50 mg/kg. HEALTH HAZARD (continued): 4 Materials that, under emergency conditions, can be lethal. Gases with an LC5o for acute inhalation toxicity less than or equal to 1,000 ppm. Any liquid whose saturated vapor concentration at 20°C (68°F) is equal to or greater than ten times its LC5o for acute inhalation toxicity, if its LC5o is less than or equal to 1000 ppm. Dusts and mists whose LC50 for acute inhalation toxicity is less than or equal to 0.5 mg/L. Materials whose LD50 for acute dermal toxicity is less than or equal to 40 mg/kg. Materials whose LD5o for acute oral toxicity is less than or equal to 5 mg/kg. FLAMMABILITY HAZARD: 0 Materials that will not burn under typical fire conditions, including intrinsically noncombustible materials such as concrete, stone, and sand. Materials that will not burn in air when exposed to a temperature of 816°C (1500°F) for a period of 5 minutes in according with Annex D of NFPA 704. 1 Materials that must be preheated before ignition can occur. Materials in this degree require considerable preheating, under all ambient temperature conditions, before ignition and combustion can occur: Materials that will burn in air when exposed to a temperature of 816°C (1500°F) for a period of 5 minutes in according with Annex D of NFPA 704. Liquids, solids, and semisolids having a flash point at or above 93.4°C (200°F) (i.e. Class 1II13 liquids). Liquids with a flash point greater than 35°C (95°F) that do not sustain combustion when tested using the Method of Testing for Sustained Combustibility, per 49 CFR 173, Appendix H or the UN Recommendations on the Transport of Dangerous Goods, Model Regulations (current edition) and the related Manual of Tests and Criteria (current edition). Liquids with a flash point greater than 35°C (95°F) in a water - miscible solution or dispersion with a water non-combustible liquid/solid content of more than 85 % by weight. Liquids that have no fire point when tested by ASTM D 92, Standard Test Method for Flash and Fire Points by Cleveland Open Cup, up to the boiling point of the liquid or up to a temperature at which the sample being tested shows an obvious physical change. Combustible pellets with a representative diameter of greater than 2 mm (10 mesh). Most ordinary combustible materials. Solids containing greater than 0.5% by weight of a flammable or combustible solvent are rated by the closed cup flash point of the solvent. 2 Materials that must be moderately heated or exposed to relatively high ambient temperatures before ignition can occur. Materials in this degree would not under normal conditions form hazardous atmospheres with air, but under high ambient temperatures or under moderate heating could release vapor in sufficient quantities to produce hazardous atmospheres with air. Liquids having a flash point at or above 37.8°C (100°F) and below 93.4°C (200°F) (i.e. Class II and Class IIIA liquids.) Solid materials in the form of powders or coarse dusts of representative diameter between 420 microns (40 mesh) and 2 mm (10 mesh) that burn rapidly but that generally do not form explosive mixtures with air. Solid materials in fibrous or shredded form that burn rapidly and create flash fire hazards, such as cotton, sisal, and hemp. Solids and semisolids that readily give off flammable vapors. Solids containing greater than 0.5% by weight of a flammable or combustible solvent are rated by the closed cup flash point of the solvent. 3 Liquids and solids that can be ignited under almost all ambient temperature conditions. Materials in this degree produce hazardous atmospheres with air under almost all ambient temperatures or, though unaffected by ambient temperatures, are readily ignited under almost all conditions. Liquids having a flash point below 22.8°C (73°F) and having a boiling point at or above 37.8°C (100°F) and those liquids having a flash point at or above 22.8°C (73°F) and below 37.8°C (100°F) (i.e. Class IB and IC liquids). Materials that on account of their physical form or environmental conditions can form explosive mixtures with air and are readily dispersed in air. Flammable or combustible dusts with representative diameter less than 420 microns (40 mesh). RMS (Continued) NATIONAL FIRE PROTECTION ASSOCIATION HAZARD RATINGS (continued): FLAMMABILITY HAZARD (continued): Materials that burn with extreme rapidity, usually by reason of self-contained oxygen (e.g. dry nitrocellulose and many organic peroxides). Solids containing greater than 0.5% by weight of a flammable or combustible solvent are rated by the closed cup flash point of the solvent. Materials that will rapidly or completely vaporize at atmospheric pressure and normal ambient temperature or that are readily dispersed in air and will burn readily. Flammable gases. Flammable cryogenic materials. Any liquid or gaseous materials that is liquid while under pressure and has a flash point below 22.8°C (73°F) and a boiling point below 37.8°C (100°F) (i.e. Class IA liquids). Materials that ignite when exposed to air, Solids containing greater than 0.5% by weight of a flammable or combustible solvent are rated by the closed cup flash point of the solvent. 4 Materials that will rapidly or completely vaporize at atmospheric pressure and normal ambient temperature or that are readily dispersed in air and will burn readily: Flammable gases. Flammable cryogenic materials. Any liquid or gaseous materials that is liquid while under pressure and has a flash point below 22.8°C (73°F) and a boiling point below 37.8°C (1001F) (i.e. Class IA liquids). Materials that ignite when exposed to air. Solids containing greater than 0.5 percent by weight of a flammable or combustible solvent are rated by the closed cup flash point of the solvent. INSTABILITY HAZARD: 0 Materials that in themselves are normally stable, even under fire conditions: Materials that have an estimated instantaneous power density (product of heat of reaction and reaction rate) at 250°C (482°F) below 0.01 W/mL. Materials that do not exhibit an exotherm at temperatures less than or equal to 500°C (932°F) when tested by differential scanning calorimetry. 1 Materials that in themselves are normally stable, but that can become unstable at elevated temperatures and pressures: Materials that have an estimated instantaneous power density (product of heat of reaction and reaction rate) at 250°C (482°F) at or above 0.01 W/mL and below 10 W/mL. 2 Materials that readily undergo violent chemical change at elevated temperatures and pressures: Materials that have an estimated instantaneous power density (product of heat of reaction and reaction rate) at 250°C (482°F) at or above 10 W/mL and below 100W/mL. 3 Materials that in themselves are capable of detonation or explosive decomposition or explosive reaction, but that require a strong initiating source or that must be heated under confinement before initiation: Materials that have an estimated instantaneous power density (product of heat of reaction and reaction rate) at 250°C (482°F) at or above 100 W/mL and below 1000 W/mL. Materials that are sensitive to thermal or mechanical shock at elevated temperatures and pressures. 4 Materials that in themselves are readily capable of detonation or explosive decomposition or explosive reaction at normal temperatures and pressures: Materials that have an estimated instantaneous power density (product of heat of reaction and reaction rate) at 250°C (482°F) of 1000 W/mL or greater. Materials that are sensitive to localized thermal or mechanical shock at normal temperatures and pressures. FLAMMABILITY LIMITS IN AIR: Much of the information related to fire and explosion is derived from the National Fire Protection Association (NFPA). Flash Point: Minimum temperature at which a liquid gives off sufficient vapor to form an ignitable mixture with air near the surface of the liquid or within the test vessel used. Autoianition Temperature: Minimum temperature of a solid, liquid, or gas required to initiate or cause self -sustained combustion in air with no other source of ignition. LEL: Lowest concentration of a flammable vapor or gas/air mixture that will ignite and burn with a flame. UEL: Highest concentration of a flammable vapor or gas/air mixture that will ignite and burn with a flame. TOXICOLOGICAL INFORMATION: Human and Animal Toxicology: Possible health hazards as derived from human data, animal studies, or from the results of studies with similar compounds are presented. LD5o: Lethal Dose (solids & liquids) that kills 50 % of the exposed animals. LC5o: Lethal Concentration (gases) that kills 50 % of the exposed animals. ppm: Concentration expressed in parts of material per million parts of air or water. m /m3: Concentration expressed in weight of substance per volume of air. mg/ko: Quantity of material, by weight, administered to a test subject, based on their body weight in kg. TDLo: Lowest dose to cause a symptom. TCLo: Lowest concentration to cause a symptom. TDo, LDLo, and LDo, or TC, TCo, LCLo, and LCo: Lowest dose (or concentration) to cause lethal or toxic effects. Cancer Information: IARC: International Agency for Research on Cancer. NTP: National Toxicology Program. RTECS: Registry of Toxic Effects of Chemical Substances. IARC and NTP rate chemicals on a scale of decreasing potential to cause human cancer with rankings from 1 to 4. Subrankings (2A, 213, etc.) are also used. Other Information: BEL ACGIH Biological Exposure Indices, represent the levels of determinants which are most likely to be observed in specimens collected from a healthy worker who has been exposed to chemicals to the same extent as a worker with inhalation exposure to the TLV. ECOLOGICAL INFORMATION: EC: Effect concentration in water. BCF: Bi000ncentration Factor, which is used to determine if a substance will concentrate in life forms that consume contaminated plant or animal matter. TLm: Median threshold limit. log Kow or log Koc: Coefficient of Oil/Water Distribution is used to assess a substance's behavior in the environment. REGULATORY INFORMATION: U.S.: EPA: U.S. Environmental Protection Agency. ACGIH: American Conference of Governmental Industrial Hygienists, a professional association that establishes exposure limits. OSHA: U.S. Occupational Safety and Health Administration. NIOSH: National Institute of Occupational Safety and Health, which is the research arm of OSHA. DOT: U.S. Department of Transportation. SARA: Superfund Amendments and Reauthorization Act. TSCA: U.S. Toxic Substance Control Act. CERCLA: Comprehensive Environmental Response, Compensation, and Liability Act. Marine Pollutant status according to the DOT; CERCLA or Superfund; and various state regulations. This section also includes information on the precautionary warnings that appear on the material's packagelabel. CANADA: WHMIS: Canadian Workplace Hazardous Materials Information System. TC: Transport Canada. DSL/NDSL: Canadian Domestic/Non-Domestic Substances List. JAPAN: METI: Ministry of Economy, Trade and Industry. SPECSEAL° SERIES FP INTUMESCENT FIRESTOP PLUG SDS EFFECTIVE DATE: JANUARY 23, 2017 PAGE 5 OF 5 ROXUL Stone Wool Insulation Safety Data Sheet �} according to Hazardous Products Act and Controlled Products Regulations and 29 CFR § 1910.1200 The Better Insulation Revision date: February 5, 2015 Supersedes: February 13, 2014 Version: 1 SECTION 1: Identification of the substance/mixture and of the company/undertaking 1.1. Product identifier Product form Fibrous batt, blanket, or board. Name Stone Wool Insulation Product code AFB°, CAVITYROCK°, COMFORTBATTr', COMFORTBOARDTm, CURTAINROCK°, DRAINBOARD°, FIREWALL°, MONOBOARD°, ROCKBOARD, ROXUL Plus°, SAFE°, SAFEWSOUND°, TOPROCK° 1.2. Relevant identified uses of the substance or mixture and uses advised against 1.2.1. Relevant identified uses Use of the substance/preparation Commercial, industrial, and residential insulation 1.2.2. Uses advised against None known. 1.3. Details of the supplier of the safety data sheet ROXUL INC. 8024 Esquesing Line Milton, Ontario, Canada L9T 6W3 www.roxul.com Telephone: 1-800-265-6878 or +1-905-878-8474 Fax: +1-905-878-8077 1.4. Emergency telephone number Telephone: 1-800-265-6878 or 1-905-878-8474 (9:00 am to 5:00 pm ET) SECTION 2: Hazards identification 2.1. Classification of the substance or mixture WHMIS Classification Not controlled Classification according to 2012 29 CFR § 1910.1200 [OSHA GHS] Not classified Classification according to NMX-R-019-SCFI-2011 [Mexico GHS] Not classified Adverse physicochemical, human health and environmental effects This product may cause mechanical irritation to the eyes and skin. Temporary irritation of the upper respiratory tract (scratchy throat, coughing, congestion) may result from exposure to dusts and fibers in excess of applicable exposure limits. Pre-existing chronic eye, skin and respiratory conditions may temporarily worsen due to exposure to dusts and fibers. This product may cause allergy in sensitized individuals. There is insufficient evidence that synthetic mineral fibers cause respiratory disease in humans. Results from animal experiments have led to conservative classifications of certain synthetic mineral fibers as possible human carcinogens. Specifically, glass wool insulation is not classifiable as to their carcinogenicity to humans. 2.2. Label elements Labelling according to WHMIS : None Labelling according to 2012 29 CFR § 1910.1200 [OSHA GHS] Hazard pictograms (OSHA GHS) None Signal word (OSHA GHS) None Hazard statements (OSHA GHS) None Precautionary statements (OSHA GHS) None Feburary 5, 2015 EN (English) 1/8 Mineral Wool Insulation Safety Data Sheet according to Hazardous Products Act and Controlled Products Regulations and 29 CFR § 1910.1200 Labelling according to NMX-R-019-SCFI-2011 [Mexico GHS] Hazard pictograms (Mexico GHS) None Signal word (Mexico GHS) None Hazard statements (Mexico GHS) None Precautionary statements (Mexico GHS) None 2.3. Any hazards not otherwise classified None known. SECTION 3: Composition/information on ingredients 3.1. Substances Not applicable. 3.2. Mixtures Name Product Identifier (CASRN) Weight % Mineral wool fiber 65997-17-3 94-99% Phenol formaldehyde polymer 9003-35-4 <6% SECTION 4: First aid measures 4.1. Description of first aid measures First -aid measures after inhalation If irritation occurs, remove the affected person to fresh air. Drink water, and blow nose, to clear dusts and fibers from throat and nose. If irritation persists, consult a physician. First -aid measures after skin contact Rinse thoroughly under running water prior to washing with mild soap and water. Use a washcloth to help remove fibers. If irritation occurs, do not rub or scratch. If irritation persists, consult a physician. First -aid measures after eye contact If irritation occurs, hold eyelids apart and flush eyes with plenty of water for at least 15 minutes. Do not rub the eyes. Consult a physician if irritation persists. First -aid measures after ingestion Ingestion of this product is unlikely and not intended under normal conditions of use. DO NOT INDUCE VOMITING. Wash out mouth with water. Consult a physician if symptoms persist. 4.2. Most important symptoms and effects, both acute and delayed Symptoms/injuries after inhalation Temporary mechanical irritation of the upper respiratory tract (scratchy throat, coughing, congestion) may result from exposure to dusts and fibers in excess of applicable exposure limits. Pre-existing chronic eye, skin and respiratory conditions may temporarily worsen due to exposure to dusts and fibers. Symptoms/injuries after skin contact Dusts and fibers may cause irritation (itching) or redness to the skin. Pre-existing chronic eye, skin and respiratory conditions may temporarily worsen due to exposure to dusts and fibers. Symptoms/injuries after eye contact Dusts and fibers may cause irritation (itching) or redness to the eyes. Pre-existing chronic eye, skin and respiratory conditions may temporarily worsen due to exposure to dusts and fibers. Symptoms/injuries after ingestion Ingestion of this product is unlikely and not intended under normal conditions of use. Ingestion of this product may cause gastrointestinal irritation. 4.3. Indication of any immediate medical attention and special treatment needed Treat symptomatically. SECTION 5: Firefighting measures 5.1. Extinguishing media Suitable extinguishing media: Water, foam, carbon dioxide, or dry powder Unsuitable extinguishing media None known. 5.2. Special hazards arising from the substance or mixture Fire hazard This product is non-combustible and does not pose a fire hazard. However, packaging material may burn. Reactivity When mineral wool is heated above approximately 200°C (-392°F), binder components and decomposition gases are emitted from the binder, which can be detected by odor. 5.3. Advice for firefighters Protective equipment for firefighters Do not enter fire are without proper protective equipment, including NIOSH-approved self- contained breathing apparatus (SCBA). Observe normal fire fighting procedures. May 29, 2015 EN (English) 2/8 Mineral Wool Insulation Safety Data Sheet according to Hazardous Products Act and Controlled Products Regulations and 29 CFR § 1910.1200 SECTION 6: Accidental release measures 6.1. Personal precautions, protective equipment and emergency procedures 6.1.1. For non -emergency personnel Pick up large pieces and scoop up dusts and fibers after they have settled out of air. Wear protective equipment (see Section 8 of this Safety Data Sheet). 6.1.2. For emergency responders Protective equipment Ensure clean-up personnel wear appropriate personal protective equipment (see Section 8 of this Safety Data Sheet). Emergency procedures Isolate area. Evacuate non -essential personnel. Avoid inhalation of dusts. Avoid creating dust on clean-up of material. Responders and clean-up crews must be properly trained and must utilize appropriate personal protective equipments (see Section 8 of this Safety Data Sheet). If dry methods or compressed air are used to collect dust and fibers, all personnel in the area should wear OSHA -approved protective equipment (see Section 8 of this Safety Data Sheet). 6.2. Environmental precautions Do not flush down sewer or drainage systems, unless system is designed and permitted to handle such material. These materials will disperse and settle along the bottom of waterways and ponds. It cannot easily be removed once it is waterborne, but is considered non -hazardous in water. 6.3. Methods and material for containment and cleaning up For containment This material will settle out of air. If concentrated on land, it can be scooped up for disposal as non -hazardous waste. Methods for cleaning up Use OSHA -recommended work practices and protective equipment as described in Section 8 of this Safety Data Sheet. Avoid generating airborne dusts and fibers during cleanup. Do not use compressed air. Vacuum dusts and fibers. Place material in an appropriate container for disposal as non -hazardous waste. 6.4. Reference to other sections See Section 8 for personal protective equipment. See Section 13 for disposal considerations. SECTION 7: Handling and storage 7.1. Precautions for safe handling Precautions for safe handling Utilize OSHA -recommended work practices and protective equipment when fabricating, installing or removing the products (see Section 8 of this Safety Data Sheet). Unpack material at applicable site to avoid unnecessary handling of product. Keep work area clean. Avoid unnecessary handling of scrap material and debris by placing such materials in suitable containers, which should be kept as close to the work area as possible. Avoid generating dusts. Avoid excessive eye and skin contact with dusts and fibers. Use recommended cleanup procedures to avoid buildup of dusts and fibers in the work area. Hygiene measures Handle in accordance with good industrial hygiene and safety practice. Wash with soap and water before eating, drinking, smoking, or using toilet facilities. Remove fibers from the work clothes, before leaving work to reduce potential skin irritation. If working in a very dusty environment, it is advisable to shower and change clothes. 7.2. Conditions for safe storage, including any incompatibilities Technical measures: Ensure adequate ventilation. Storage condition(s) Keep material in original packaging until it is to be used. Store material to protect against adverse conditions including precipitation. Incompatible materials Hydrofluoric acid. 7.3. Specific end use(s) Commercial, industrial, residential, and marine insulation. SECTION 8: Exposure controls/personal protection 8.1. Control parameters Follow all applicable exposure limits. Local regulations may apply. ROXUL recommends that users of the products adhere to the OSHA - recommended PEL of 1 f/cc TWA (fibers longer than 5 pm with diameters less than 3pm). This recommended PEL, together with recommended work practices and personal protective equipment, were adopted in a Health and Safety Partnership Program (HSPP) agreement in 1999 between OSHA and the North American Insulation Manufacturers Association (NAIMA), of which ROXUL is a member. Adherence to the OSHA - recommended PEL, work practices and protective equipment in the HSPP is expected to provide appropriate protection against all inhalation - related health risks that may be associated with exposures to mineral wool fibers (ACGIH, 1997; NAIMA, 1999; OSHA, 1999; National Research Council, 2000; IARC, 2001), and to minimize eye and skin irritation. Reference Exposure Legal or Recommended Exposure Limit OSHA Synthetic Vitreous Fibers, >5 pm length, <3 pm 1 f/cc TWA (recommended) diameter Inert dust and particulates not otherwise regulated 15 mg/m3 TWA-PEL (total particulate) 5 mg/m3 TWA-PEL (respirable particulate) May 29, 2015 EN (English) 3/8 Mineral Wool Insulation Safety Data Sheet according to Hazardous Products Act and Controlled Products Regulations and 29 CFR § 1910.1200 Reference Exposure Legal or Recommended Exposure Limit ACGIH Synthetic Vitreous Fibers, >5 pm length, <3 pm 1 f/cc TWA (threshold limit value- TLV) diameter Particulates not otherwise classified, containing no asbestos and <1 % crystalline silica 10 mg/m3 TWA-TLV (inhalable particulate) 3 mg/m3 TWA-TLV (respirable particulate) 8.2. Exposure controls Appropriate engineering controls Ensure good ventilation. Where feasible, general dilution ventilation or local exhaust ventilation should be used as necessary to maintain exposures below applicable exposure limits. Dust collection systems should be used in cutting or machining operations and may be needed when using power tools. Local exhaust ventilation may be required if the method of use produces dust levels which exceed applicable exposure limits. A washing facility/water for eye and skin cleaning purposes should be present. In poorly ventilated areas when dusty conditions exist and/or dust levels exceed applicable exposure limits, wear a NIOSH certified dust respirator with an efficiency rating of N95 or higher, Personal protective equipment Gloves, safety glasses or goggles, protective clothing, respirator Hand protection Gloves. Eye protection Safety glasses or safety goggles with side shields. Skin and Body protection Appropriate protective clothing. Do not tape sleeves or pants at wrists or ankles. Respiratory protection In poorly ventilated areas when dusty conditions exists and/or dust levels exceed applicable exposure limits, wear a NIOSH certified dust respirator with an efficiency rating of N95 or higher. Use disposable face masks complying with NIOSH respirator standards, such as a 3M Model 8210 (or 8710) (3M Model 9900 in high humidity environments) or equivalent. For exposures up to five times the established exposure limits use a quarter -mask respirator, rated N95 or higher; and for exposures up to ten times the established exposure limits, use a half -mask respirator (e.g., MSA's DM-11, Racal's Delta N95, 3M's 8210), rated N95 or higher. For exposures up to 50 times the established exposure limits, use a full-faced respirator, rated N99 or higher. Environmental exposure controls Avoid release to the environment. SECTION 9: Physical and chemical properties 9.1. Information on basic physical and chemical properties Physical state Solid Color Grey, green, brown Odor May have slight resin odor Odor threshold Not applicable pH Not applicable Melting point Approximately 2150T (1177°C) Solidification point Data not available Boiling point Not applicable Flash point None Relative evaporation rate (butylacetate=1) Not applicable Flammability (solid, gas) Not applicable Explosive limits Not applicable Vapour pressure Not applicable Relative vapour density at 20 °C Not applicable Relative density Not applicable Solubility Insoluble in water Log Pow Not applicable Log Kow Not applicable Self ignition temperature Not applicable Decomposition temperature Not applicable Viscosity, kinematic Not applicable Viscosity, dynamic Not applicable Explosive properties Not applicable Oxidising properties Not applicable VOC Content less than Not applicable 9.2. Other information Upper flammable Limit Not applicable Lower Flammable Limit Not applicable Sensitivity to mechanical impact No data available Sensitivity to static discharge No data available May 29, 2015 EN (English) 4/8 Mineral Wool Insulation Safety Data Sheet according to Hazardous Products Act and Controlled Products Regulations and 29 CFR § 1910.1200 SECTION 10: Stability and reactivity 10.1. Reactivity This product is stable under the normal conditions of use. 10.2. Chemical stability This product is stable under the normal conditions of use. 10.3. Possibility of hazardous reactions Under normal conditions of storage and use, hazardous polymerization is not known to occur. 10.4. Conditions to avoid Avoid generation of dust. 10.5. Incompatible materials This product reacts with hydrofluoric acid. 10.6. Hazardous decomposition products Primary combustion products of the cured urea extended phenolic formaldehyde binder, when heated above 390°F (200°C), are carbon monoxide, carbon dioxide, ammonia, water and trace amounts of formaldehyde. Other undetermined compounds could be released in trace quantities. Emission usually only occurs during the first heating. The released gases may be irritating to the eyes, nose and throat during initial heat -up. Use appropriate respirators (air supplied) particularly in tightly confined or poorly ventilated areas during initial heat -up. SECTION 11: Toxicological information 11.1. Information on toxicological effects Routes of Entry Acute toxicity Ingredient data: Oral, dermal, inhalation, eye contact. No product data available. Name Product Identifier (CASRN) Route & Species Value (LD5o/LCso) Mineral wool fiber 65997-17-3 No data identified No data identified Phenol formaldehyde polymer 9003-35-4 Oral, rat >5000 mg/kg Dermal, rat >2000 mg/kg Skin corrosion/irritation Coarse fibers and dust from mineral wool products can cause irritation (itching, redness) of the skin. The itching and possible inflammation are a mechanical reaction to dust and coarse fibers (or more than about 5 pm in diameter) and are not damaging in the way chemical irritants may be. The symptoms generally abate within a short time after the end of exposure. When products are handled continually, the skin itching generally diminishes. Serious eye damage/irritation Coarse fibers and dust from mineral wool products can cause irritation (itching, redness) of the eyes. The itching and possible inflammation are a mechanical reaction to dust and coarse fibers (or more than about 5 pm in diameter) and are not damaging in the way chemical irritants may be. The symptoms generally abate within a short time after the end of exposure. Respiratory or skin sensitisation This product contains a component (phenol formaldehyde polymer) at >_1% that may cause allergy in sensitized individuals. Germ cell mutagenicity This product is not known to contain any components at >_0.1 % that has been shown to cause mutagenicity. Therefore, based upon the available data and the known hazards of the components, this product is not expected to be a mutagen. May 29, 2015 EN (English) 5/8 Mineral Wool Insulation Safety Data Sheet according to Hazardous Products Act and Controlled Products Regulations and 29 CFR § 1910.1200 Carcinogenicity In October 2001, IARC completed a re-evaluation of respirable mineral wool fibers and classified them in Group 3 (not classifiable as to their carcinogenicity to humans). A summary of the most important scientific studies appears below: Human data: The possible carcinogenic effects of exposure to mineral wool fibers have been evaluated in a number of epidemiological (human) studies. Most of the research, including large long-term studies of mineral wool production workers in the U.S. and Europe, has been sponsored or supported by the North American and International thermal insulation industries, including ROXUL INC. Published reports of the early results of these studies identified significantly elevated rates of respiratory cancer in several subcohorts of the worker populations under evaluation (e.g., Simonato et al., 1987; Enterline et al., 1987). However, the studies had several methodological limitations, including failure to control for confounding exposures to other possible causes of the elevated cancer risk, including tobacco use and occupational exposures to recognized carcinogens such as asbestos. For these reasons, the authors of these reports did not interpret the results as establishing an association between exposure to mineral wool fibers and an increased risk of cancer. Several of these earlier reports formed part of the basis for IARC's previous classification of mineral wool fibers in Group 2B (possibly carcinogenic to humans) (IARC, 1987). Follow-up studies, including case -control studies designed to exclude the contribution of confounding exposures to the cancer experience of the study populations, found no evidence that mineral wool fibers are associated with an increased cancer risk (Marsh et al., 1996; Wong et al., 1991; Kjaerheim et al., 2001). In announcing the new Group 3 classification for mineral wool fibers, IARC stated: "Epidemiologic studies published during the 15 years since the previous IARC Monographs review of these fibers in 1988 provide no evidence of increased risks of lung cancer or of mesothelioma (cancer of the lining of the body cavities) from occupational exposures during manufacture of these materials" (IARC, 2001). Animal data: Several studies of intraperitoneal injection of high doses of mineral wool fibers have produced significant increases in the incidence of mesothelioma (IARC, 2002). The intraperitoneal injection studies formed part of the basis for IARC's previous (IARC, 1987) Group 2B classification for mineral wool fibers. Leading scientists agree that intraperitoneal injection studies (i.e., surgical implantation or injection into the chest or abdomen) are the least relevant type of animal study for evaluating potential human risk for fiber exposures, because such studies bypass the animals' natural defense mechanisms and involve a type and pattern of exposure (implantation of a high dose early in life) that does not mimic human patterns of exposure (inhalation of much lower doses over a lifetime) (National Research Council, 2000). A well -designed long-term inhalation study in rats exposed to mineral wool fibers found no significant increase in lung tumor incidence, and no mesotheliomas (IARC, 2002). Likewise, in two intratracheal instillation studies of mineral wool fibers, no significant increase in the incidence of lung tumors or mesotheliomas was found (IARC, 2002). Inhalation studies are regarded as the most relevant type of animal data for evaluating potential human risk and intratracheal instillation studies while less relevant, are considered valuable for the initial screening of fibrous compounds (National Research Council, 2000). Thus, evaluating all the available animal studies in conjunction with the human data, IARC's most recent review finds "inadequate evidence overall for any cancer risk" from mineral wool fibers (IARC, 2001). Source Classification Description IARC Group 3 Insulation glass wool: Not classifiable as a human carcinogen. ACGIH Group A3 Confirmed animal carcinogen with unknown relevance to humans. OSHA Not established There is insufficient evidence that synthetic mineral fibers cause respiratory disease in humans. Results from animal experiments have led to conservative classifications of certain synthetic mineral fibers as possible human carcinogens. Specifically, insulation glass wool and continuous glass filament are not classifiable as to their carcinogenicity to humans. NTP Reasonably Certain Glass Wool Fibers (Inhalable) Anticipated To Be Human Carcinogens Reproductive toxicity This product is not known to contain any components at >_0.1 % that have been shown to cause reproductive toxicity. Therefore, based upon the available data and the known hazards of the components, this product is not expected to be a reproductive toxin. Teratogenicity/Embryotoxicity This product is not known to contain any components at >_0.1 % that have been shown to cause teratogenicity and/or embryotoxicity. Therefore, based upon the available data and the known hazards of the components, this product is not expected to be a teratogen/embryotoxin. Specific target organ toxicity (single exposure) Coarse fibers and dust from mineral wool products can cause temporary mechanical irritation in the upper respiratory tract (nose and throat). The itching and possible inflammation are a mechanical reaction to dust and coarse fibers (or more than about 5 pm in diameter) and are not damaging in the way chemical irritants may be. The symptoms generally abate within a short time after the end of exposure. May 29, 2015 EN (English) 6/8 Mineral Wool Insulation Safety Data Sheet according to Hazardous Products Act and Controlled Products Regulations and 29 CFR § 1910.1200 Specific target organ toxicity (repeated exposure) Aspiration hazard Potential Adverse human health effects and symptoms Toxicologically Synergistic Materials SECTION 12: Ecological information 12.1. Toxicity No information available. 12.2. Persistence and degradability No information available. 12.3. Bioaccumulative potential No information available. 12.4. Mobility in soil No information available. 12.5. Results of PBT and vPvB assessment No information available. This product is not known to contain any components at >_1.0% that have been shown to cause chronic toxic effects. Therefore, based upon the available data and the known hazards of the components, contact with this product is not expected to cause chronic toxic effects. This product is not an aspiration hazard. Effects of exposure may include irritation of the skin, and of the mucous membranes in the eyes and in the upper respiratory tract (nose and throat). None known. 12.6. Other adverse effects The products are stable, not expected to cause harm to animals, plants or fish, and have no other known adverse environmental effects. SECTION 13: Disposal considerations 13.1. Waste treatment methods Waste disposal recommendations The products, as supplied, are not expected to be a characteristic hazardous waste under RCRA if discarded. Product is not considered a hazardous waste. Dispose of waste material according to Federal, State, Provincial and Local environmental regulations. Comply with relevant regulations with regards to disposal, recycling, treatment, transportation and storage of contents and containers. SECTION 14: Transport information No special precautions. This product is not considered to be a hazardous material for transport. SECTION 15: Regulatory information 15.1. Safety, health and environmental regulations/legislation specific for the substance or mixture 15.1.1. National regulations USA This product has been classified in accordance with the 2012 hazard criteria of the OSHA's HCS and the SIDS contains all the information required by the 29 CFR § 1910.1200. Canada This product has been classified in accordance with the hazard criteria of the Controlled Products Regulations and the MSDS contains all the information required by the Controlled Products Regulations. Mexico : This product has been classified in accordance with NMX-R-019-SCFI-2011. All compounds in this product are listed in the Canada Domestic Substances List (DSL) and the US Toxic Substances Control Act (TSCA) Chemical Substance Inventory (1985). SECTION 16: Other information Date of Preparation : May 29, 2015 May 29, 2015 EN (English) 7/8 Mineral Wool Insulation Safety Data Sheet according to Hazardous Products Act and Controlled Products Regulations and 29 CFR § 1910.1200 Sources of Key data A complete copy of OSHA -recommended workplace practices and protective equipment when fabricating, installing or removing the products can be obtained from ROXUL INC. and is available on the OSHA website(http://www.osha.gov/SLTC/syntheticmineralfibers). IARC Monograph Man-made Vitreous Fibres, press release October 2001 Safety in the Use of Mineral and Synthetic Fibers, Occupational Safety and Health Series, International Labor Office. Information about "Health and Safety Research on Rock- and Slag -wool" can be obtained from the North American Insulation Manufacturers Association (NAIMA), 44 Canal Center Plaza, Suite 210, Alexandria, VA 22314, USA). Homepage: http://www.naima.org Complete citations, or copies of all references cited in this SIDS can be obtained from ROXUL INC. (See Section 1). Abbreviations and acronyms ACGIH —American Conference of Governmental Industrial Hygienists bw— body weight CASRN — Chemical Abstracts Service Registry Number CFR — US Code of Federal Regulations DSL — Canada Domestic Substances List GHS — Globally Harmonized System HCS — US Hazard Communication Standard IARC — International Agency for Research on Cancer LD50 — Acute lethal dose causing 50% lethality in animals (M)SDS — (Material) Safety Data Sheet NAIMA — North American Insulation Manufacturers Association NIOSH — National Institute of Occupational Safety and Health NTP — National Toxicology Program OSHA — Occupational Safety and Health Administration PEL — Permissible Exposure Limit SCBA — Self -Contained Breathing Apparatus TLV — Threshold Limit Value TSCA — US Toxic Substances Control Act TWA — Time -Weighted Average US — United States of America WHMIS —Workplace Hazardous Material Information System Disclaimer: The information contained herein is based upon data considered to be accurate. However, no warranty is expressed or implied regarding the accuracy of these data, the results to be obtained from the use thereof, or that any such use will not infringe upon any patent. This information is furnished as a guide only and upon the condition that the person receiving it shall make tests to determine the accuracy and suitability for his or her own purpose. No responsibility is assumed for injury or damage from the use of the products described herein. May 29, 2015 EN (English) 8/8 _ = Specified = Technologies STIo Inc. April 14, 2020 210 Evans Way Somerville, NJ 08876 USA Phone: (908) 526-8000 Fax: (908) 231-8415 Toll Free: (800) 992-1180 Email:techserv@stifirestop.com Website: www.stifirestop.com Subject: LEED@ information concerning SpecSeal@, EZ-Path@, EZ-Firestop@, SmokeBlock@ Caulk, FyreFlange@ and SpeedFlex@ Products To Whom It May Concern: Specified Technologies Inc. (STI) manufactures the SpecSeal@, EZ-Firestop@, SmokeBlock@ Caulk FyreFlange@ and SpeedFlex@ line of firestopping products as well as EZ-Path@. One or more STI products are being considered for use on your construction project. This letter provides information on using STI products to contribute to obtaining LEED credits. A product cannot be LEED certified, only the building can be LEED certified. Because an individual product cannot directly produce a LEED credit, it is not possible to determine the exact number of LEED credits that can be generated by using products manufactured by STI. STI firestop materials and pathway devices are high quality firestop products designed with the environment in mind. Wherever possible, formulations include material obtained from recycled sources and contain bio-based materials. STI takes steps to minimize or eliminate volatile organic compounds (VOC's). For all products, VOC content is far below the nationally recognized standards set forth by the South Coast Air Quality Management District Rule #1168 and Bay Area Air Quality Management District Regulation 8, Rule #51. Further, these products are nontoxic and do not contain asbestos, PCB's, lead, water-soluble intumescent ingredients, or halogens. Our attention to the environment does not end with the product. Strict and effective methods are employed to reduce packaging and promote the use of packaging with recycled material content. Packaging is also recyclable. Additionally, our manufacturing plants, warehouses and network of stocking distributers are strategically located to reduce environmental impact through reduction of transportation distances. The following two pages summarize LEED@ credits that may be applicable. Table One: LEED@ for New Construction and Major Renovations outlines various credits that may be available when using SpecSeal@, EZ-Firestop@, SmokeBlock@ Caulk, FyreFlange@ and SpeedFlex@ Products following this rating system. Table Two: Applicable Products, correlates the products to applicable LEED@ credits. Although these charts address LEED@ for New Construction and Major Renovations, the information contained within may be applied to any of the LEED@ rating systems currently in use. If there are further questions, please do not hesitate to contact us. Thank you for your interest in SpecSeal@, EZ-Path@, EZ-Firestop@, SmokeBlock@ Caulk, FyreFlange@ and SpeedFlex@ Products. Sincerely yours, George Gornick, LEED Green Associate Applications Engineer (Ext. 1013) 1 of 4 TABLE ONE: p RATING SYSTEM DESCRIPTION• - NEW CONSTRUCTION• - RENOVATIONS NC v4I Section How SpecSeal®, EZ-Firestop®, SmokeBlock® Caulk, Points Section Name / Title Intent FyreFlange® and SpeedFlex® Products Can Help Required Minimum Energy Performance To reduce the environmental and economic harms of excessive energy use by achieving a Use firestop products to seal openings to minimize airflow thereby reducing cycling of HVAC equipment. ;sscl minimum level of energy efficiency for the building and its systems. 1 - 20 Optimize Energy Performance To achieve increasing levels of energy performance beyond the prerequisite standard to reduce Use firestop products to seal openings to minimize airflow thereby reducing cycling of HVAC equipment. environmental and economic impacts associated with excessive energy use. 1 Sustainable Sites To assesssite conditions before design to evaluate sustainable options and inform related Use firestop products that are re -useable, retrofittable, with recycled content, with movement capability and can Site Assessment decisions about site desiqn. provide a W-Ratinq where applicable. MRp1 To reduce the waste that is generated by building occupants and hauled to and disposed of in Use firestop products: 1. Packaged in recyclable containers, Pre Req Required Storage and Collection of Recyclables landfills. 2. With recycled content, 3. That are re -useable and retrofittable. MRp2 Construction and Demolition Waste To reduce construction and demolition waste disposed of in landfills and incineration facilities by Use firestop products: 1. Packaged in recyclable containers, Pre Req Required Management Planning recovering, reusing, and recycling materials. 2. With recycled content, 3. That are re -useable and retrofittable. Building Life -Cycle Impact Reduction To encourage adaptive reuse and optimize the environmental performance of products and MRc1 2-5 Building Reuse —Maintain Interior Nonstructural Elements materials. Use firestop products that are re -useable and retrofittable. Building Product Disclosure MRc3 (1) 1 -2 and Optimization To increase demand for building products that incorporate bio-based materials, thereby reducing Use firestop products that contain bio-based materials. Responsible Sourcing of Raw Materials dependence on fossil fuels, a finite resource. - Bio-based materials Building Product Disclosure MRc3 (2) 1 -2 and Optimization To reuse building materials and products to reduce demand for virgin materials and reduce waste, Use firestop products that are re -useable and retrofittable. Responsible Sourcing of Raw Materials thereby lessening impacts associated with the extraction and processing of virgin resources. - Materials Reuse Building Product Disclosure MRc3 (3) 1 -2 and Optimization To increase demand for building products that incorporate recycled content materials, thereby Use firestop products with recycled content. Responsible Sourcing of Raw Materials reducing impacts resulting from extraction and processing of virgin materials. - Recvc/ed Content MRc4 Building Product Disclosure To reward project teams for selecting products for which the chemical ingredients in the product Health Product Declaration. The end use product has a published and complete Health Product Declaration with 1 -2 and Optimization are inventoried using an accepted methodology and for selecting products verified to minimize the full disclosure of known hazards in compliance with the Health Product Declaration open Standard. Option 1 - Material Ingredient Reporting use and generation of harmful substances. Contact Technical Service for HPD Document. Building Product Disclosure MRc4 and Optimization To reward project teams for selecting products for which the chemical ingredients in the product Use firestop products that comply with REACH and contains ingredients listed on the REACH Authorization List 1 -2 - Material Ingredient Optimization are inventoried using an accepted methodology and for selecting products verified to minimize the Option 2 International Alternative Compliance Path — use and generation of harmful substances. (Annex XIV), Restriction List (Annex XVII), and SVHC Candidate list. REACH Optimization Use firestop products manufactured within 100 miles of project location. Copy and paste MRc3 Building Product Disclosure To increase demand for building materials and products that are extracted, manufactured and https://Iogin.stifirestop.com/?button=llg into your browser to access LEED Credit Calculator to obtain distance 1 -2 and Optimization purchased within the region, thereby supporting the use of indigenous resources and reducing the verification. MRc4 - Regional Materials environmental impacts resulting from transportation. Due to the complexity of STI Firestop products, we are unable to indicate harvesting/extraction information, as the majority of our products are comprised of a multitude of individual ingredients from a wide variety of locations. Construction and Demolition Waste To reduce construction and demolition waste disposed of in landfills and incineration facilities by Use firestop materials: 1. Packaged in recyclable containers, MRc5 1-2 2. With recycled content, Management recovering, reusing, and recycling materials. 3. That are re -useable and retrofittable. EQp1 Required Minimum Indoor Air Quality Performance To contribute to the comfort and well-being of building occupants by establishing minimum Seal openings with firestop products to minimize non -design airflow and meet mechanical and natural ventilation Pre Req standards for indoor air quality (IAQ). system design requirements. EQp2 Required Environmental Tobacco Smoke (ETS) To prevent or minimize exposure of building occupants, indoor surfaces and ventilation air Seal openings with firestop products to minimize airflow. Pre Req Control distribution systems to environmental tobacco smoke (ETS). Use firestop products: 1. Encapsulate exposed fibers to reduce impact on IAQ. 2. Guard against mold growth and EQc1 1-2 Enhanced Indoor Air Quality Strategies To promote occupants' comfort, well-being, and productivity by improving indoor air quality. mildew by taking steps to minimize water infiltration to reduce impact on IAQ, 3. Seal openings to minimize airflow, control pollutant sources and interupt contamination pathways to help meet mechanical and natural ventilation system design requirements. Use firestop products (Architectural Sealants) with VOC under 250 g/L per SCAQMD Rule 1168 and tested to the EQc2 1-3 Low -Emitting Materials To reduce concentrations of chemical contaminants that can damage air quality, human health, California Department of Public Health (CDPH) Standard Method v1.2-2017 or CDPH Standard Method V1.1- - Adhesives and Sealants productivity, and the environment. 2010. Contact Technical Service for CDPH Certificate/Report. Use firestop products: 1. Encapsulate exposed fibers to reduce impact on IAQ. 2. Guard against mold growth and EQc3 1 Construction Indoor Air Quality Management To promote the well-being of construction workers and building occupants by minimizing indoor air mildew by taking steps to minimize water infiltration to reduce impact on IAQ, 3. Seal openings to minimize airflow, Plan quality (IAQ) problems associated with construction and renovation. control pollutant sources and interupt contamination pathways. Use firestop products (Architectural Sealants) with VOC under 250 /L. Use firestop products: 1. To seal openings to minimize airflow thereby reducing distribution of particulate matter EQc4 1-2 Indoor Air Quality Assessment To establish better quality indoor air in the building after construction and during occupancy. and pollutants. 2. Guard against mold growth and mildew by taking steps to minimize water infiltration to reduce Option 2 impact on IAQ, 3. Seal openings to minimize airflow, control pollutant sources and interupt contamination pathways. 4. (Architectural Sealants) with VOC values under 250 g/L per SCAQMD Rule 1168. EQc5 1 Thermal Comfort To promote occupants' productivity, comfort, and well-being by providing quality thermal comfort. Use firestop products and systems that seal openings to minimize airflow and that incorporate insulation materials offerinq thermal resistance. EQc9 1 Acoustic Performance To provide workspaces and classrooms that promote occupants' well-being, productivity, and Use firestop products with STC Value tested to ASTM E90 "Standard Test Method for Laboratory Measurement of communications through effective acoustic design. Airborne Sound Transmission Loss of Building Partitions and Elements". To provide design teams and projects the opportunity to achieve exceptional performance above Use firestop products: 1. Encapsulate exposed fibers to reduce impact on IAQ. 2. Guard against mold growth and INc1 1 - 5 Innovation the requirements set by the LEED Green Building Rating System and/or innovative performance in mildew by taking steps to minimize water infiltration to reduce impact on IAQ, 3. Use firestop products that Green Building categories not specifically addressed by the LEED Green Building Rating System accommodate future expansion, thereby eliminating shipping additional products to the project, reintroducing VOCs, and creating airborne contaminates when creating openings for new cables, etc. Use firestop products to earn bonus credit points (for credits received above) by achieving credits that have been RPc1 1 -4 Regional Priority To provide an incentive for the achievement of credits that address geographically specific designated as particularly important for your project's specific geographic location. environmental, social equity, and public health priorities. Regional priority credit lookup: https://www.usgbc.org/rpc 2 of 4 Rev.(4-14-2020) TABLE TWO: APPLICABLE PRODUCTS LEEDO For New Construction and Major Renovations v4.0/v4.1 SectioCredn: V4.0 / v4.1 RECYCLED VOC PRODUCT CONTENT CONTENT MRc3 (3) (EQc2AS200 6 Sw 6% post consumer MJJJJJJEJJE= JJJJEJJJJJJ 0% post industrial Cable Spray •. MJJJJJJEJJE= JJJJ � 0% post industrial Cast-in=111111011EM Noun W111111 Firestop Device FCloset i estopFGasket ' =111111EIIE= 1111E111111 Composite Sheet �Unnnn©=mmn� ©©©©®©©©©©© Cnnection Protection =..©©©©0©.©= ©...®©©©... 1111W111111 E BPowers ox Insertsld =111111MINEM ES Sealant •p consumer. M111111011EM 1111E111111 0% `ndWrapmicM01111110110M 1111M111111 TZ—Path Fire -Rated Pathways 22, 33, 44+ EZ Path =111111011E= 111IM111111 Devicetrofit EZ Path33NEZ,Smoke =011111101100 1111M111111 4NEZ Path T-REZ ng Kit =111111=11E= 11110111111 at . r =111111011w= 11110111111 Grommets • . Fast Tack Spray .0% 1111E111111 p industrialost Firestop Plug©©©©©©�©■©� ©©©©=©©©■©© ©©©©�©©■■©© FyreFlange . ■■©©©©�©■©� LC150 Sealant ©©©©©©©©©©© ;; ��consumer•®©©©©©,�,©©� • LCC Collars • LCI Sealant 6consumer 0% post industrial PEN200 % post consumer 0% post industrial Brackets Quick-Clip -BracketReady ®..©©©.�©.©� ©...®©..... Sleeve Ready Sleeve Split Sleeve r • ��������'©� ��������'�� RTC Collar r r • ■■©©©©®©■©� ©■■■�©■■■■■ Safing Spray 6consumer• 0% •. SIL3005% post consumer. % •. 3 of 4 LEGEND: N/A- Not Applicable Revised 4-14-2020 N N N V C Q U U Q O- U M M M U O C M V u7 U O U U U Q N Q U N U M U 7 U u7 U a7 U U U ' < < v) U U U C1 C1 CJ CJ Ci CJ CJ CJ Z a . w w cn g g 2 2 0 w w w w w w w w— tY OQ Z> Bio- Based Reach „ HPD CDPH % by Compliant weight 5% t i 5% post consumer < 47.0 g/L X X X X X 0 X X Y X X X X X X X X X X X 0% post industrial Not 0 < 2.0 g/L X X X 0 X Y X X X X CDPH X X X X X v Tested 0 26% X X 0 Y X X X X Not CDPH X X X X X 4 0 Tested 5% 5% post consumer 20.0 g/L X X X X X 0 X X Y v X X X X X X X X X X X 0% post industrial > v c 5% 5% post consumer 30.0 g/L X X X X X 0 X X Y i9 X X X X X X X X X X X 0% post industrial o a u o .w 0 0 g/L X X X X X 0 X Y X X X N/A X X X X X c � 10% Y a 0% post consumer 0 g/L X X X X X X 0 X X X Y 3 .a X X X X N/A X X X X X X 10% post industrial ° E o w 21% 21 % post consumer 0 g/L X X X X X X 0 X X X Y y 3 v X X X X N/A X X X X X X 0% post industrial o °° on v o 0 0 g/L X X X X 12 X X Y X N/A X 24 % £ 19 % post consumer 0 g/L X X X X X 0 X X Y\ X X X X N/A X X X X X 5% post industrial c £ 3 u Q 0 0 g/L X X X X X X 0 X X Y X X X X X X X X X X X 16% w 1 ° v v Not 6% post consumer 29.2 g/L X X X X X 0 X X Y ° 2 �w X X X X CDPH X X X X X X 10% post industrial ° v � c Tested 0 0 g/L X X X X 0 X X Y y Y o X N/A X v � � � Q t L 0 0 g/L X X X X 20 X X Y 3 X N/A X o v = w > ar a 0 0 g/L X X X X 20 X X Y X N/A X 0 0 g/L X X X 0 X Y N/A X 5% t 5% post consumer 53.0 g/L X X X X X 0 X X Y X X X X X X X X X X X 0% post industrial 4 of 4 LEGEND: N/A- Not Applicable Revised 4-14-2020 SpecSeal@ Series SpecSeal@ ASzoo Elastomeric Spray 228368-420 Certificate Number 01/27/2021 - 01/27/2022 Certificate Period Certified Status UL 2818 - 2o13 Gold Standard for Chemical Emissions for Building Materials, Finishes and Furnishings Building Construction Adhesives are tested in accordance with California Department of Public Health (CDPH) Standard Method V1.2-2017 in an Office and Classroom Environment. Product tested in accordance with UL 2821 test method to show compliance to emission limits on UL 2818. Section 7A and 7.2. UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively "Agreement'). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report in accordance with the terms of the Agreement. This Certificate is valid for the identified dates unless there is non-compliance with the Agreement. GREENGUARD Gold Certification Criteria for Building Products and Interior Finishes Maximum Allowable Criteria CAS Number Predicted Concentration Units TVOC (A) - 0.22 mg/m3 Formaldehyde 50-00-0 9 (7.3 ppb) µg/m3 Total Aldehydes (B) - 0.043 ppm 4-Phenylcyclohexene 4994-16-5 6.5 µg/m3 Particle Matter less than io µm (c) - 20 µg/m3 1-Methyl-2-pyrrolidi none (D) 872-50-4 16o µg/m3 1/2 CREL Individual VOCs (E) or 1/sooth TLV (A) Defined to be the total response of measured VOCs falling within the C6 — C16 range, with responses calibrated to a toluene surrogate. Maximum allowable predicted TVOC concentrations for GREENGUARD Gold (0.22 mg/m3) fall in the range of 0.5 mg/m3 or less, as specified in CDPH Standard Method v1.2. (B) The sum of all measured normal aldehydes from formaldehyde through nonanal, plus benzaldehyde, individually calibrated to a compound specific standard. Heptanal through nonanal are measured via TD/GC/MS analysis and the remaining aldehydes are measured using HPLC/UV analysis. (C) Particle emission requirement only applicable to HVAC Duct Products with exposed surface area in air streams (a forced air test with specific test method) and for wood finishing (sanding) systems. (D) Based on the CA Prop 65 Maximum Allowable Dose Level for inhalation of 3,200 jig/day and an inhalation rate of 20 m3/day (E) Allowable levels for chemicals not listed are derived from the lower of 1/2 the California Office of Environmental Health Hazard Assessment (OEHHA) Chronic Reference Exposure Level (CREL) as required per the CDPH/EHLB/Standard Method v1.2 and BIFMA level credit 7.6.2 and 1/100th of the Threshold Limit Value (TLV) industrial work place standard (Reference: American Conference of Government Industrial Hygienists, 6500 Glenway, Building D-7, and Cincinnati, OH 45211-4438). UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively "Agreement). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report in accordance with the terms of the Agreement. This Certificate is valid for the identified dates unless there is non-compliance with the Agreement. SpecSeal@ Series ES Elastomeric Firestop Sealant 228584-420 Certificate Number 01/27/2021 - 01/27/2022 Certificate Period Certified Status UL 2818 - 2o13 Gold Standard for Chemical Emissions for Building Materials, Finishes and Furnishings Building Construction Adhesives are tested in accordance with California Department of Public Health (CDPH) Standard Method V1.2-2017 in an Office and Classroom Environment. Product tested in accordance with UL 2821 test method to show compliance to emission limits on UL 2818. Section 7A and 7.2. UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively "Agreement'). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report in accordance with the terms of the Agreement. This Certificate is valid for the identified dates unless there is non-compliance with the Agreement. GREENGUARD Gold Certification Criteria for Building Products and Interior Finishes Maximum Allowable Criteria CAS Number Predicted Concentration Units TVOC (A) - 0.22 mg/m3 Formaldehyde 50-00-0 9 (7.3 ppb) µg/m3 Total Aldehydes (B) - 0.043 ppm 4-Phenylcyclohexene 4994-16-5 6.5 µg/m3 Particle Matter less than io µm (c) - 20 µg/m3 1-Methyl-2-pyrrolidi none (D) 872-50-4 16o µg/m3 1/2 CREL Individual VOCs (E) or 1/sooth TLV (A) Defined to be the total response of measured VOCs falling within the C6 — C16 range, with responses calibrated to a toluene surrogate. Maximum allowable predicted TVOC concentrations for GREENGUARD Gold (0.22 mg/m3) fall in the range of 0.5 mg/m3 or less, as specified in CDPH Standard Method v1.2. (B) The sum of all measured normal aldehydes from formaldehyde through nonanal, plus benzaldehyde, individually calibrated to a compound specific standard. Heptanal through nonanal are measured via TD/GC/MS analysis and the remaining aldehydes are measured using HPLC/UV analysis. (C) Particle emission requirement only applicable to HVAC Duct Products with exposed surface area in air streams (a forced air test with specific test method) and for wood finishing (sanding) systems. (D) Based on the CA Prop 65 Maximum Allowable Dose Level for inhalation of 3,200 jig/day and an inhalation rate of 20 m3/day (E) Allowable levels for chemicals not listed are derived from the lower of 1/2 the California Office of Environmental Health Hazard Assessment (OEHHA) Chronic Reference Exposure Level (CREL) as required per the CDPH/EHLB/Standard Method v1.2 and BIFMA level credit 7.6.2 and 1/100th of the Threshold Limit Value (TLV) industrial work place standard (Reference: American Conference of Government Industrial Hygienists, 6500 Glenway, Building D-7, and Cincinnati, OH 45211-4438). UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively "Agreement). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report in accordance with the terms of the Agreement. This Certificate is valid for the identified dates unless there is non-compliance with the Agreement. SpecSeal@ Series LCI Intumescent Firestop Sealant 228370-420 Certificate Number 01/27/2021 - 01/27/2022 Certificate Period Certified Status UL 2818 - 2o13 Gold Standard for Chemical Emissions for Building Materials, Finishes and Furnishings Building Construction Adhesives are tested in accordance with California Department of Public Health (CDPH) Standard Method V1.2-2017 in an Office and Classroom Environment. Product tested in accordance with UL 2821 test method to show compliance to emission limits on UL 2818. Section 7A and 7.2. UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively "Agreement'). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report in accordance with the terms of the Agreement. This Certificate is valid for the identified dates unless there is non-compliance with the Agreement. GREENGUARD Gold Certification Criteria for Building Products and Interior Finishes Maximum Allowable Criteria CAS Number Predicted Concentration Units TVOC (A) - 0.22 mg/m3 Formaldehyde 50-00-0 9 (7.3 ppb) µg/m3 Total Aldehydes (B) - 0.043 ppm 4-Phenylcyclohexene 4994-16-5 6.5 µg/m3 Particle Matter less than io µm (c) - 20 µg/m3 1-Methyl-2-pyrrolidi none (D) 872-50-4 16o µg/m3 1/2 CREL Individual VOCs (E) or 1/sooth TLV (A) Defined to be the total response of measured VOCs falling within the C6 — C16 range, with responses calibrated to a toluene surrogate. Maximum allowable predicted TVOC concentrations for GREENGUARD Gold (0.22 mg/m3) fall in the range of 0.5 mg/m3 or less, as specified in CDPH Standard Method v1.2. (B) The sum of all measured normal aldehydes from formaldehyde through nonanal, plus benzaldehyde, individually calibrated to a compound specific standard. Heptanal through nonanal are measured via TD/GC/MS analysis and the remaining aldehydes are measured using HPLC/UV analysis. (C) Particle emission requirement only applicable to HVAC Duct Products with exposed surface area in air streams (a forced air test with specific test method) and for wood finishing (sanding) systems. (D) Based on the CA Prop 65 Maximum Allowable Dose Level for inhalation of 3,200 jig/day and an inhalation rate of 20 m3/day (E) Allowable levels for chemicals not listed are derived from the lower of 1/2 the California Office of Environmental Health Hazard Assessment (OEHHA) Chronic Reference Exposure Level (CREL) as required per the CDPH/EHLB/Standard Method v1.2 and BIFMA level credit 7.6.2 and 1/100th of the Threshold Limit Value (TLV) industrial work place standard (Reference: American Conference of Government Industrial Hygienists, 6500 Glenway, Building D-7, and Cincinnati, OH 45211-4438). UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively "Agreement). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report in accordance with the terms of the Agreement. This Certificate is valid for the identified dates unless there is non-compliance with the Agreement. SpecSeal@ Series WF300 Intumescent Firestop Caulk 228583-420 Certificate Number 01/27/2021 - 01/27/2022 Certificate Period Certified Status UL 2818 - 2o13 Gold Standard for Chemical Emissions for Building Materials, Finishes and Furnishings Building Construction Adhesives are tested in accordance with California Department of Public Health (CDPH) Standard Method V1.2-2017 in an Office and Classroom Environment. Product tested in accordance with UL 2821 test method to show compliance to emission limits on UL 2818. Section 7A and 7.2. UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively "Agreement'). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report in accordance with the terms of the Agreement. This Certificate is valid for the identified dates unless there is non-compliance with the Agreement. GREENGUARD Gold Certification Criteria for Building Products and Interior Finishes Maximum Allowable Criteria CAS Number Predicted Concentration Units TVOC (A) - 0.22 mg/m3 Formaldehyde 50-00-0 9 (7.3 ppb) µg/m3 Total Aldehydes (B) - 0.043 ppm 4-Phenylcyclohexene 4994-16-5 6.5 µg/m3 Particle Matter less than io µm (c) - 20 µg/m3 1-Methyl-2-pyrrolidi none (D) 872-50-4 16o µg/m3 1/2 CREL Individual VOCs (E) or 1/sooth TLV (A) Defined to be the total response of measured VOCs falling within the C6 — C16 range, with responses calibrated to a toluene surrogate. Maximum allowable predicted TVOC concentrations for GREENGUARD Gold (0.22 mg/m3) fall in the range of 0.5 mg/m3 or less, as specified in CDPH Standard Method v1.2. (B) The sum of all measured normal aldehydes from formaldehyde through nonanal, plus benzaldehyde, individually calibrated to a compound specific standard. Heptanal through nonanal are measured via TD/GC/MS analysis and the remaining aldehydes are measured using HPLC/UV analysis. (C) Particle emission requirement only applicable to HVAC Duct Products with exposed surface area in air streams (a forced air test with specific test method) and for wood finishing (sanding) systems. (D) Based on the CA Prop 65 Maximum Allowable Dose Level for inhalation of 3,200 jig/day and an inhalation rate of 20 m3/day (E) Allowable levels for chemicals not listed are derived from the lower of 1/2 the California Office of Environmental Health Hazard Assessment (OEHHA) Chronic Reference Exposure Level (CREL) as required per the CDPH/EHLB/Standard Method v1.2 and BIFMA level credit 7.6.2 and 1/100th of the Threshold Limit Value (TLV) industrial work place standard (Reference: American Conference of Government Industrial Hygienists, 6500 Glenway, Building D-7, and Cincinnati, OH 45211-4438). UL investigated representative samples of the identified Product(s) to the identified Standard(s) or other requirements in accordance with the agreements and any applicable program service terms in place between UL and the Certificate Holder (collectively "Agreement). The Certificate Holder is authorized to use the UL Mark for the identified Product(s) manufactured at the production site(s) covered by the UL Test Report in accordance with the terms of the Agreement. This Certificate is valid for the identified dates unless there is non-compliance with the Agreement. CERTIFICATE OF ACHIEVEMENT PRESENTED TO: John Dug4 ia IN Mechanical Firestop Services LLC for attending the course Firestop Instructional Training Level 2 W cs Effective 02/20/2020, BICSI recognizes the above -named course for the following BICSI Continuing Education Credits CECs). Event ID: OV-STI-NJ-0220-3 BICSI CECs: 12 Course Number: FIT2 Learning Units: 16 LUIHSW non Continuing Education Provider 16 hours of continuing education Learning Objectives • To learn the requirements of compliance and be able to choose firestop systems and products to achieve that compliance. • To understand compartmentation and the role of through penetrations in barriers. • Understanding of the UL System approach to managing the firestop process and identify the components of a firestop system. • To identify various firestop products and their properties. • Recognize the requirements and correct use of products and materials for building design or renovation. Issued By: John Zalepka Training & Development Manager Specified Technologies Inc. August 10, 2020 This certificate expires 1 year from the Enrollment Date and not Completion Date & Specified STI Technologies Inc. on FIREST I THE FIRESTOR AUTHORITY LIMITED WARRANTY: WARRANTY INFORMATION STI warrants that its products will be free of defects for one year from the date of purchase. In the event a product does not conform to this warranty, the sole and exclusive remedy is, at STI's option, replacement of the product or refund of the purchase price. The warranty provided herein shall be void and of no effect in the event thatthe product is not installed in accordance with STI's published instructions, listed systems and applicable building and safety codes. THIS WARRANTY IS IN LIEU OF ALL OTHER REPRESENTATIONS AND EXPRESSED OR IMPLIED WARRANTIES (including the implied warranties of merchantability or fitness for a particular use) AND UNDER NO CIRCUMSTANCES SHALL STI BE LIABLE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES, INCLUDING, WITHOUT LIMITATION, ANY LOSS OF REVENUE, PROFIT OR USE. Prior to use, the user shall determine the suitability of the product for its intended use, and the user assumes all risks and liability for subsequent use. No person other than an officer of STI is authorized to bind STI to any other warranty for any product for which this warranty is issued. GARANTIA LIMITADA: Specified Technologies Inc. fabrica sus articulos de manera que esten fibres de defectos. Si se produce algun defecto en sus articulos (dentro de un intervalo de un ano), Specified Technologies Inc., tras la notificacion inmediata, cambiara o reparara, a discrecion suya, los articulos o reembolsara el precio de compra de cualquier producto que se demuestre esta defectuoso cuando se instala de conformidad con la recomendaciones publicadas de STI y en aplicaciones que STI haya considerado apropiadas Para este producto. LIMITACIONES y EXCLUSION ES: ESTA GARANTIA SUSTITUYE TODAS LAS DEMAS PRESENTACI ONES Y GARANTIAS EXPRESAS 0 IMPLICITAS (incluidas [as garantias implicitas de comerciabilidad o idoneidad de uso) Y BAJO NINGUNACIRCUNSTANCIASERA SPECIFIED TECHNOLOGIES INC. RESPONSABLE DE NINGUNAPERDIDAO DANO A LA PROPIEDAD INCIDENTAL 0 CONSECUENTE. GARANTIE LIMITEE : Specified Technologies Inc. fabrique ses merchandises de maniere a ce qu'elles soient sans defaut Dans l'eventualite d'un quelconque defaut de la merchandise durant la premiere annee, Specified Technologies Inc. s'engage, a son entiere discretion et sur notification rapide, a echanger ou reparer la marchandise ou a rembourser le prix d'achat de tout produit avere defectueux s'il a ete pose en conformite avec les conseils publies de STI et dans des applications que STI considere adaptees pour ledit produit. DIMITIES et EXCLUSIONS : LA PRESENTE GARANTIE REMPLACE TOUTE AUTRE REPRESENTATION ET GARANTIE EXPRESSE ET IMPLICITE (incluant les garanties implicites marchandes ou d'adaptabilite a un usage particulier) ET SPECIFIED TECHNOLOGIES INC. NE PEUT, EN AUCUNE CIRCONSTANCE ETRE TENUE RESPONSABLE DE QUELQUE DOMMAGE OU PERTE ACCESSOIRE, MATERIELLE OU INDIRECTE QUE CE SOIT. TOLL FREE: 1-800-992-1180 FIRESTOP WWW.STIFIRESTOP.COM THE FIRESTOP AUTHORITY AFBO Acoustical Fire B ROCKWOOL AFB° is a lightweight, acoustical fire batt stone wool insulation specifically designed for steel stud and wood stud interior wall and floor applications. Its superior sound absorbency and fire protection contribute to the overall comfort and safety of occupants. It provides increased density that reduces sound transmission. Greater noise control is further achieved when AFB® is part of the wall assembly along with gypsum boards and resilient channels. AFB® is non-combustible and will not develop toxic smoke or promote flame spread, even when directly exposed to fire. This helps to provide valuable extra time for people to reach safety and for fire services personnel to control the spread. It is a key component of fire -rated partitions. AFB° comes in a number of thicknesses to meet the requirements of both retrofit and new construction applications. Learn more at rockwool.com ROCKWOO A F B° Technical Data Sheet Batt Insulation 07210 & 09820* • Blanket Insulation 07 21 16** Acoustical Fire Batt Insulation Acoustical Blanket Insulation 09 81 16** ROCKWOOL AFB® is a mineral wool batt insulation for interior partitions in commercial constructions where superior fire resistance and acoustical performance are required. Mineral Fiber Thermal Insulation for Buildings, Type 1 Compliant CAN/ULC S702 Mineral Fiber Blanket Thermal Insulation, Type 1 Compliant ASTM C665 Compliance Mineral Fiber Blanket Thermal Insulation, Type 7 Compliant ASTM C553 MEA Approval, New York City Approval 338-97-M City of Los Angeles Approval RR 25444 Flame spread index = 0; Smoke developed index = 0 ASTM E84 (UL 723) Flame spread index = 0; Smoke developed index = 0 CAN/ULC S102 Reaction to Fire Determination of Non -combustibility of Building Materials - Non-combustible CAN/ULC S114 Behavior of materials at 750*C - Non-combustible ASTM E136 Smolder Resistance - 0.09% CAN/ULC S129 Nominal Density > 2.5 Ibs/ft3 (>40 kg/m3)t ASTM C303 Stress Corrosion Cracking Tendency of Austenitic Stainless Steel - Passed ASTM C795 Corrosion Resistance Corrosion of Steel - Passed ASTM C665 Air Erosion Maximum Air Velocity - 1000 fpm (5.08 m/s) UL 181 Thickness 1" through 4" (25.4 mm - 101.6 mm) in 1/2" increments as well as 5" (127 mm) and 6" (152.4 mm), Dimensions 15.25" x 47" (387 mm x 1194 mm), 16" x 48" (413 mm x 1219 mm), 19.2" x 47" (470 mm x 1194 mm), 23" x 47" (584 mm x 1194 mm), 24" x 48" (610 mm x 1219 mm) Thickness 125 Hz 250 Hz 500 Hz 1000 Hz 2000Hz 4000 Hz NRC ASTM C423 1.0" 0.14 0.25 0.65 0.9 1.01 1.01 0.7 1.5" 0.18 0.44 0.94 1.04 1.02 1.03 0.85 2" 0.28 0.6 1.09 1.09 1.05 1.07 0.95 Acoustical Performance 3" 0.52 0.96 1.18 1.07 1.05 1.05 1.05 4" 0.86 1.11 1.2 1.07 1.08 1.07 1.1 6" 1.11 1.28 1.15 1.06 1.03 1.01 1.15 ASTM E90 Please contact ROCKWOOL for STC ratings on tested wall assemblies Fire Rated Designs ULC Classification Code: BZJZC UL Classification Code: BZJZ ��Sslfl uson • • - • •regarding - - • • UL Declare. cum. ... stone ...... please - cus USA Specifications and Sizing NOTE: *Master Format 1995 Edition **Master Format 2004 Edition. As ROCKWOOL has no control over installation design and workmanship, accessory materials or application conditions, ROCKWOOL does not warranty the performance or results of any Issued 11/2022 installation containing ROCKWOOUs products. ROCKWOOUs overall liability and the remedies available are limited by the general Supersedes 01/2018 terms and conditions of sale. This warranty is in lieu of all other warranties and conditions expressed or implied, including the warranties of merchantability and fitness for a particular purpose. 'Density will change with thickness. Density is not a performance criteria but is commonly referred to when specifying insulation. Actual density is the true density of the insulation and Nominal density is the effective density of the insulation relative to a historic benchmark where the insulation contained 40% non -fibrous content also known as Shot (ASTM C612-99). Please contact ROCKWOOL for more information. ROCKWOOL Tel: Es-265-6g Line, Milton, 9 -0110 Tel: 800-265-6878 9Fax: 800-991-0110 rockwool.com Thermafiber° SAFB'" (Sound Attenuation Fire Blankets) are THERMAFIBER0 mineral wool batts designed to provide acoustical control and Ire protection in many UL°fire-rated wall and floor -ceiling assemblies. These products are non-combustible, moisture - SAFBTM resistant, non -corrosive, non -deteriorating, mildew -resistant, and MINERAL WOOL vermin -resistant. SAFBT' resists temperatures over 2,000 OF and can add points to STC for walls and floor -ceiling assemblies. SAFB'" can be installed in both steel stud and wood -framed construction. INSULATION Features • Exceptional sound and noise absorption • Adds STC value to wall and floor -ceiling assemblies • Provides fire containment in rated assemblies • Fire-resistant to temperatures above 2,000°F (1,093°C) • Minimum 70% recycled content' • Mold-resistant2 • Contributes to credits in several green building programs, such as LEED° and Green Globes® 2 Tested per ASTM C1338, Standard Test Method for Determining Fungi Resistance of Insulation Materials and Facings, ASTM International. Standards, Codes Compliance • NFPA 101, Class A -rated interior finish Physical Properties PROPERTY TEST METHOD VALUE Corrosion of Steel, ASTM C665 Type I Aluminum, and Copper Non -Combustibility ASTM E136 Non-combustible Non -Combustibility CAN/ULC S114 Complies Water Vapor Sorption ASTM C1104 Sorption less than 1 °i by volume Surface Burning ASTM E84 Flame Spread 0, Smoke Developed 0 Characteristics Surface Burning CAN/ULC S102 Flame Spread 0, Smoke Developed 0 Characteristics Acoustical Performance Noise Reduction Coefficients at Frequencies per ASTM C423 THICKNESS 125 HZ 250 HZ 500 HZ 1000 HZ 2000 HZ 4000 HZ NRC 2" 0.34 0.61 1.07 1.09 1.07 1.10 0.95 2.5 pcf 3" 0.51 0.99 1.18 1.03 0.99 0.96 1.05 Nominal Density 4" 0.83 1.19 1.27 1.12 1.12 1.13 1.20 6" 1.37 1.32 1.23 1.16 1.12 1.12 1.20 Availability NOMINAL DENSITY THICKNESS3 WIDTHS4 LENGTHS 2.5 pcf 1'i2`7' 15",16", 17", 23", 24", 25" 48" 4.0 pcf 1 " 15", 16", 17", 23", 24", 25" 48" Tolerances +1/4'-14- ±1i8° ±1i2^ Custom sizes are availble. Minimum ordering will apply. 3 Thicknesses are available in r-inch increments. 4 15-inch and 23-inch are recommended widths for wood -framed construction. Installation • Interior Stud Cavity - Friction -fit SAFB'" securely between studs. Butt ends of blankets closely together and fill all voids. • Creased SAFB'" - Using SAFB'" 1 inch wider than regular blankets, bow the blankets slightly to fit into stud cavity. Slit the blankets vertically 1 inch deep with a utility knife down the center. • Floor -Ceiling - Friction -fit SAFB'" securely between floor joints. • Ceiling Overlayment - Lay SAFB'" over ceiling panels, extending 48 inches beyond all partitions. Tightly fit around all hangers, obstructions, and penetrations. Product Options • Recycled Content Options',': • EPA Choice Fiber (U.S. Government Buildings) ....................................Minimum 75% • Standard Fiber................................................................................70°i Formaldehyde -free product available. See Owens Corning publication "Thermafiber° SAFBT' Formaldehyde -Free Mineral Wool Insulation Data Sheet" (Pub. No. 10022322) for more information. 5 Recycled content options other than standard must be specified at time of order. Product Data Sheet I Thermafiber® SAFB'" I September 2021 Environmental and Sustainability Owens Corning is a worldwide leader in building material systems, insulation, and composite solutions, delivering a broad range of high -quality products and services. Owens Corning is committed to driving sustainability by delivering solutions, transforming markets, and enhancing lives. More information can be found at www.owenscorning.com. Certifications and Sustainable Features • 'Verified by ICC-ES to contain a minimum of 70% recycled content. See ICC-ES Evaluation Report VAR-1025 at icc-es.org. • Environmental Product Declaration (EPD) has been certified by UL Environment. For more information, visit ul.com/epd. • SAFB'' products have a published Health Product Declaration (HPD). • This product receives SAFETY Act designation by the U.S. department of Homeland Security. For more information, visit safetyact.gov. u� CERTIFIED AVE "L Made in the USA Disclaimer of Liability Technical information contained herein is furnished without charge or obligation and is given and accepted at recipient's sole risk. Because conditions of use may vary and are beyond our control, Owens Corning makes no representation about, and is not responsible or liable for, the accuracy or reliability of data associated with particular uses of any product described herein. Owens Corning reserves the right to modify this document without prior notice. LEED® is a registered trademark of the U.S. Green Building Council. Green Globes® is a registered trademark of Green Building Initiative, Inc. UL® and the UL® logo are trademarks of UL LLC. Notes For additional information, refer to the Safe Use Instruction Sheet (SUIS) found in the SIDS Database via http://sds.owenscorning.com. THERMAFIBER, INC. ONE OWENS CORNING PARKWAY TOLEDO, OHIO, USA 43659 888-TFI B ERI 1834-23711 www.owenscorning.com/thermafiber Pub. No. 10021143-G. Printed in U.S.A. September 2021. The color PINK is a registered trademark of Owens Coming.© 2021 Owens Corning. All Rights Reserved. Mechanical Firestopping Material PRODUCT SPECIFICATION DRAWING Deck Penetration Sleeves Hydroflame Pro Series Sleeves CD Plate (optional) Safety Cap & Locator Whiskers Included (Shown with optional CD Plate) (OSHA Compliant Hole Cover) Non-Telesco0na Version ("-B") --T* See Dim "C" (Telescoping) *Note: a) Height range: 2-1/2" to 12". b) Height range: 2-1/2" to 7-3/4" ("-B" version). c) Both standard & "-B" style can be extended by adding sleeving extension. d) Sleeves with black Bases & black Locator Whiskers are for use with metallic penetrants. e) Sleeve with red Bases & red Locator Whiskers are for use with either metallic or non-metallic (plastic) penetrants. f) The use of the Locator Whiskers is optional. Dimension Chart Size Dim "A" Dim "B" Dim "C" Pipe Size HFP-1* 4-1/4" 3-314" 8" - 12" /2" - 1" HFP-2* 4-5/8" 3-7/8" 8" - 12" 1 Y<" - 2" HFP-3* 5-5/8" 5" 8" - 12" 2" - 3" HFP-4* 6-1/2' 1 6 8"-12' 1 3" - 4" HFP-6* 9-1/4" 1 8-7/8" 1 8" - 12" 1 5" - 6" Technical Data for HydroFlame Pro Firestop Device Product Test Criteria UL Fire Tested & Listed to UL1479 ASTM E814 & CAN/ULC S115 UL Ratings (consult individual product specs & UL Systems): "L": Yes; "F": 3 Hrs. typical; "W": Yes (UL system may require caulk) Intumescent Fire Wrap Physical Properties, Performance Contains no solvents or carcinogenic fillers Color: Gray/Black Material shelf/store life: Indefinite Heat Expansion begins: = 375°F (191 °C) Greatest Expansion: 575-F-1100-F (302-C - 59YC) Constrained Expansion: >_ 18 times volume Free Expansion: >_ 37 times volume Expansion after accelerated weathering (tested to UL 1479): Temperature aging: Pass - 270 days @ 158°F (70°C) High humidity aging: Pass - 180 days @ 97-100% humidity, 95°F (35°C) Application Temperature: Minimum 15°F (-9°C) / maximum 130°F (54°C) Temperature Resistance: Maximum 212°F (100°C) Surface Burning Indicates (Per ASTM E84/UL 723): Flame spread: 15 Smoke developed: 15 The HOLDRITE@ Hydroflame Pro Series Sleeving System consists of UL & cLIL listed assemblies that provide sleeving & firestop solutions for cast -in -place concrete floors. These sleeve products provide solutions for both metallic & non-metallic pipes, line -sets, cables, conduits, floor drains, tub drains, shower drains and toilet drains. For slabs 21/2" and thicker and for pipes, conduits & cables'/2" - 6" nominal; 2 & 3 hour UL Fire Ratings and T, L & W- ratings available. 50 Pa ratings available. See UL Fire Resistive Directory (R25101) for further details. Sleeves are easly adapted for use on Corrugated Metal Decking with the use of HoldRite's CD Plates. 16 models include: #HFP-P/M1 (B), #HFP-P/M2 (B), #HFP-P/M3 (B), #HFP-P/M4 (B) and #HFP-P/M6 (B). Tested to ASTM E90 standard test method for laboratory Measurement of Airborne Sound Transmission Loss in Building Partitions and Elements. Please see HOLDRITE Silencer Series brochure or appropriate testing reports for further information. Contact your HOLDRITE representative for any additional information. Product Information: • Material: Main Sleeve Body & Safety Cap: Polypropylene Mid -Body Seal: Thermoplastic Rubber (TPR); Mold & Fungus resistant per ASTM G-21. Locator Whiskers: Polypropylene Fire Ring: 24GA CRS Firestop Material: UL Listed Intumescent Composite Patented & Patents Pending • See Hydroflame Pro Series Installation Instructions, Best Practices documents and the latest UL Fire Resistive Directory file (R25101) for details. Aa�`• lsIFj4, TO CHANGE WITHOUT NOTICE. IT MAY NOT BE REPRODUCED IN (� Q PART OR WHOLE WITHOUT WRITTEN AUTHORIZATION. 4 �E UL tiS ,Vq Buy Ame,ca Act HOLDRITE" MAMi HVM 01-LAMI-Fm FBIG5. USAMEMBERPRO SERIES tI1IIIIp, 800-321-0316 OR 760-744-6944 / FAX: 760-744-0507 / WWW.HOLDRITE.COM SYSTWOOMPATIOU spec_HFP Series Sleeves, RevF, pg 1 of 2, 01-27-20 Product Submittal Job Name: Um ner: Mechanical Firestopping Material Deck Penetration Sleeves c+�'pSSlFj�O ,Vq 4 �c UL Us Buy Amex . Act FEW MADE IN USIA 9Y47EM CONiATBIE PRODUCT SPECIFICATION DRAWING Hydroflame Pro Series Sleeves, (cont.) Center to Center Dimensions Model #1 Model #2 Dim "A" HFP-P1 HFP-P1 3.76" HFP-P2 HFP-P2 3.96" HFP-P3 HFP-P3 4.96" HFP-P4 HFP-P4 6.25" HFP-P5 HFP-P5 8.00" HFP-P6 HFP-P6 8.88" HFP-M1 HFP-M1 3.76" HFP-M2 HFP-M2 3.96" HFP-M3 HFP-M3 4.96" HFP-M4 HFP-M4 6.25" HFP-M5 HFP-M5 8.00" HFP-M6 HFP-M6 8.88" HFP-P1 B HFP-P1 B 3.76" HFP-P2B HFP-P2B 3.96" HFP-P3B HFP-P3B 4.96" HFP-P4B HFP-P4B 6.25" HFP-P5B HFP-P5B 8.00" HFP-P6B HFP-P6B 8.88" HFP-M1 B HFP-M1 B 3.76" HFP-M2B HFP-M2B 3.96" HFP-M3B HFP-M3B 4.96" HFP-M4B HFP-M4B 6.25" HFP-M5B HFP-M5B 8.00" HFP-M6B HFP-M6B 8.88" TO CHANGE WITHOUT NOTICE. IT MAY NOT BE REPRODUCED IN PART OR WHOLE WITHOUT WRITTEN AUTHORIZATION. HOLORITE° MB HYO�ROFLAMET" MEMBER PRO 800-321-0316 OR 760-744-6944 / FAX:760-744-0507 / WWW.HOLDRITE.COM spec_HFP Series Sleeves, RevF, pg 2 of 2, 01-27-20 Mechanical Firestopping Material Deck Penetration Sleeves PRODUCT SPECIFICATION DRAWING Hydroflame Pro Series - Sleeve Extensions Sleeve Extension 5-5/16" Extends Sleeve Height (All Sizes) By Up To 4-3/4" The HOLDRITE® Hydroflame Pro Series "Sleeve Extensions" (#HFPE1 - #HFPE6) are available to fit a wide variety of Sleeve combinations, from 1" thru 6" sizes. Each extension adds up to 4-3/4" of height in 1/4" increments. No coupling is needed! Height markings are shown on each part, in both U.S. and metric. Product Information: • Material: Body: Polypropylene. Patented & Patents Pending. See Hydroflame Pro Series Installation Instructions, Best Practices documents and the latest UL Fire Resistive Directory file (R25101) for details. � S�JIi� O I TO CHANGE WITHOUT NOTICE. IT MAY NOT BE REPRODUCED IN PART OR WHOLE WITHOUT WRITTEN AUTHORIZATION. C �L us HOLDRITE' FM-u 1A Y 1] 1101-1-A M I_T"" rnwwvr.�nc �illlA PRO SERIES 800-321-0316 OR 760-744-6944 / FAX:760-744-0507 / WWW.HOLDRITE.COM spec_HFP Series, Sleeve Extensions, pg7 of 12_RevA Product Submittal I Job Name: ner: 10/19/2016 XHEZ.F-A-5043- Through- penetration Firestop Systems Deck Penetration Sleeves Mechanical Firestopping Material MENU Pace Bottom System No. F-A-5043 XH EZ. F-A-5043 Through -penetration Firestop Systems Design/System/Construction/Assembly Usage Disclaimer Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Certified products, equipment, system, devices, and materials. Authorities Having Jurisdiction should be consulted before construction. Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requirements. The published information cannot always address every construction nuance encountered in the field. When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction. Only products which bear UL's Mark are considered Certified. XHEZ - Through -penetration Firestop Systems XHEZ7 - Through -penetration Firestop Systems Certified for Canada See General Information for Through -penetration Firestop Systems See General Information for Through -penetration Firestop Systems Certified for Canada System No. F-A-5043 September 16, 2016 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings — 2 or 3 Hr (See Items 1 and 2) F Ratings — 2 or 3 Hr (See Items 1 and 2) T Ratings — 1-1/4 or 1-1/2 Hr (See Item 2) FT Ratings — 1-1/4 or 1-1/2 Hr (See Item 2) L Rating At Ambient — Less Than 1 CFM/ft2 FH Ratings — 2 or 3 Hr (See Items 1 and 2) L Rating At 400 F — Less Than 1 CFM/ft2 FTH Ratings — 1-1/4 or 1-1/2 Hr W Rating — Class 1 (see Item 4) L Rating At Ambient — Less Than 5.1 L/s/m2 L Rating At 400 F — Less Than 5.1 L/s/m2 http://database.ul .com/cgi-bin/XYV/tem plate/LlSEXT/1 F RAM E/showpage.htm I?name=XH EZ. F-A-5043&ccnshorttitl e=Through-penetration+Firestop+Systems... 1 /4 10/19/2016 XHEZ.F-A-5043- Through- penetration FirestopSystems Deck Penetration Sleeves Mechanical Firestopping Material MENU Configuration A Configuration B http://database.ul .com/cgi-bin/XYV/tem plate/LlSEXT/1 F RAM E/showpage.htm I?name=XH EZ. F-A-5043&ccnshorttitl e=Through-penetration+Fi restop+Systems... 214 10/19/2016 XHEZ.F-A-5043- Through- penetration Firestop Systems Deck Penetration Sleeves Mechanical Firestopping Material MENU 1. Floor Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. IA. Alternate Floor Assembly — (Not Shown) — The fire rated unprotected concrete and steel deck floor assembly shall be constructed of the material and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below: A. Concrete — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete, as measured from the top plane of the steel floor units. B. Steel Floor and Form Units* — Composite or non -composite max 3 in. (76 mm) deep galv steel fluted units as specified in the individual Floor -Ceiling Design. 2. Firestop Device* — Sleeve — Max 8 in. (203 mm) diam WD sleeve or Max 6 in. (152 mm) HFP Series cast in place firestop device permanently embedded during concrete placement in accordance with accompanying installation instructions. For HFP devices the optional accessories (not shown) includes a sleeve extension, deck adapter and/or water dam installed in accordance with installation instructions. The device shall be installed flush with top and bottom surfaces of floor. The devices are sized to accommodate the followinq nom pipe sizes: Nom Pipe Diam in. (mm) with (Item 4 below) Insulation Firestop Devices for Thickness will determine which Firestop Devices for Fluted Deck (Not device size to use. Concrete Slab Shown) 1/2 to 1 (13 to 25) HFP-P1, HFP-M1, HFP- add HFPCDI H2, HFP-P1B, HFP-M1B, HFP-H2B 1-1/4 to 2 (32 to 51) HFP-P2, HFP-M2, HFP- add HFPCD2 H3, HFP-P2B, HFP-M2B, HFP-H3B 2 to 3 (51 to 76) HFP-P3, HFP-M3, HFP- add HFPCD3 H4, HFP-P3B, HFP-M3B, HFP-H4B 3 to 4 (76 to 102) HFP-P4, HFP-M4, HFP- add HFPCD4 H5, HFP-P4B, HFP-M4B, HFP-H5B HFP-P6, HFP-P6B, HFP- add HFPCD6 M6, HFP-M6B, HFP-H7, HFP-H7B HFP Series devices do not reqire the use of Packing material (Item 5) or Sealant (Item 6) when sized according to manufacturer's instructions. SECURUS INC, DBA HOLDRITE — HFP-Px, HFP-Hx, HFP-PxB, HFP-HxB, HFP-Mx and HFP-MxB F Rating is limited to 2 hour when HFP-H series devices are used in Config A & all other HFP series devices hav a 3 hour F Rating and a 1-1/4 T Rating. Configuration B Note: F rating is limited to 2 hours when configuration B is used. 1. Floor Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. IA. Alternate Floor Assembly — (Not Shown) — The fire rated unprotected concrete and steel deck floor assembly shall be constructed of the material and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below: A. Concrete — Min 4-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete, as measured from the top plane of the steel floor units. B. Steel Floor and Form Units* — Composite or non -composite max 3 in. (76 mm) deep galv steel fluted units as specified in the individual Floor -Ceiling Design. 2. Firestop Device* — Sleeve — Max 8 in. (203 mm) diam cast in place Firestop device permanently embedded during concrete placement in accordance with accompanying installation instructions. The device shall be installed flush with top and bottom surfaces of floor. The devices are sized to accommodate the nom pipe sizes: SECURUS INC, DBA HOLDRITE — HydroFlame WD, CD Sleeve hftp://database.ul .com/cgi-bin/XYV/tem plate/LlSEXT/1 F RAM E/showpage.htm I?name=XH EZ. F-A-5043&ccnshorftitl e=Through-penetration+Firestop+Systems... 3/4 10/19/2016 XHEZ.F-A-5043- Through- penetration FirestopSystems Deck Penetration Sleeves Mechanical Firestopping Material MENU .5. Tnrougn-Penetrant — Une metallic pipe or tuDing to De centered witnln the tlrestop system. Pipe or tUDing to De rigidly supported on both sides of floor assembly. The following types of pipe or tubing may be used: A. Steel Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Copper Tubing — Nom 4 in. (102 mm) diam (or smaller) Type M (or heavier) copper tubing. C. Copper Pipe — Nom 4 in. (102) diam (or smaller) Regular (or heavy) copper pipe. D. Iron Pipe — Nom 4 in. (152 mm) diam (or smaller) cast or ductile iron pipe. 4. Pipe Covering* — Max 1-1/2 in. (38 mm) thick hollow cylindrical heavy density mineral fiber units with an all service jacket. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. A min annular space of 1/2 in. (13 mm) is required within the firestop system. See Pipe and Equipment Covering — Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. Note: Land W Rating only apply when pipe covering is 1/2 in. (13 mm) or less. 5. Packing Material — Min 3-3/4 in. (95 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form so that the width of the wool is compressed at least 50 percent. Packing material to be recessed from top surface of floor as required to accommodate the required thickness of fill material. Packing material is optional for HFP-Px, HFP-PxB, HFP-Mx, HFP-MxB series devices (See Item 2). 6. Fill, Void or Cavity Material* — Sealant — Min 1/4 in. (6 mm) thickness of sealant applied within the annulus, flush with the top surface of floor. When pipe covering (Item 4) thickness is greater than 1 in. (25 mm), the min thickness of sealant applied within the annulus shall be 1/2 in. (13 mm). Sealant is optional for HFP-Px, HFP-PxB, HFP-Mx, HFP-MxB series devices (See Item 2). 3M COMPANY 3M FIRE PROTECTION PRODUCTS — FB-1000NS, FB-1003SL, FB-3000 WT RECTORSEAL — Metacaulk 835+ or Biotherm 100 or 200 * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Last Updated on 2016-09-16 Questions? Print this page Terms of Use Page Top © 2016 UL LLC The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow -Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow -Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non - misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2016 UL LLC". http://database.ul .com/cgi-bin/XYV/tem plate/LlSEXT/1 F RAM E/showpage.htm I?name=XH EZ. F-A-5043&ccnshorttitl e=Through-penetration+Fi restop+Systems... 4/4 10/19/2016 XHEZ.F-A-2269- Through- penetration Firestop Systems Deck Penetration Sleeves Mechanical Firestopping Material MENU Pace Bottom System No. F-A-2269 XHEZ.F-A-2269 Through -penetration Firestop Systems Design/System/Construction/Assembly Usage Disclaimer Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Certified products, equipment, system, devices, and materials. Authorities Having Jurisdiction should be consulted before construction. Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requirements. The published information cannot always address every construction nuance encountered in the field. When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction. Only products which bear UL's Mark are considered Certified. XHEZ - Through -penetration Firestop Systems XHEZ7 - Through -penetration Firestop Systems Certified for Canada See General Information for Through -penetration Firestop Systems See General Information for Through -penetration Firestop Systems Certified for Canada System No. F-A-2269 September 12, 2016 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Ratings — 2 or 3 Hr (See Item 3) F Ratings — 2 or 3 Hr (See Item 3) T Ratings — 0 or 1/2 Hr (See Item 3) FT Ratings — 0 or 1/2 Hr (See Item 3) L Rating At Ambient — Less Than 1 CFM/sq ft FH Ratings — 2 or 3 Hr (See Item 3) L Rating At 400 F — Less Than 1 CFM/sq ft FTH Ratings — 0 or 1/2 Hr (See Item 3) W Rating — Class 1 L Rating At Ambient — Less Than 5.1 L/s/mz L Rating At 400 F — Less Than 5.1 L/s/m2 http://database.ul .com/cgi-bin/XYV/tem plate/LlSEXT/1 F RAM E/showpage.htm I?name=XH EZ. F-A-2269&ccnshorttitl e=Through-penetration+Firestop+Systems... 1 /3 Electrical Firestopping Material Firestop Submittal Package Anthology of Edmonds Project: Anthology of Edmonds Date: 2/14/2023 Submitted by: Charles Hodson Josh McCarver Rhema Electric This submittal is auto -generated based on user -selected inputs. Therefore, Hilti makes no representation as to the suitability of these systems for their intended use. Hilti Firestop Saving lives through innovation Hilti. Outperform. Outlast. and education Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com • en espanol 1-800-879-5000 • P.O. Box 21148, Tulsa, Oklahoma 74121 Hilti (Canada) Corp. 1-800-363-4458 www.hilti.ca • 2360 Meadowpine Blvd., Mississauga, Ontario L5N 6S2 Table Of Contents UL Listings F-A-2054(US Only)............................................................... 1 CP 680-P Cast -in firestop sleeve Product Data Sheet (US CA ENG) for CP 680 PX, P, and M .............................. 3 UL Certificate of Compliance for CP 680-P, CP 680-M, CP 680-PX Cast -in Firestop Devices and CP 681 Tub Box Kit........................................................... 4 Material Information Statement for Firestop Products ..................................... 5 VOC_SCAQMD and EPA24_CP680_EN.............................................. 6 System No. F-A-2054 Classified by Underwriters Laboratories, Inc. F Rating — 3 Hr to UL 1479 T Ratings — 0 and 3 Hr (See Item 3) L Rating (Without Movement) At Ambient — Less Than 1 CFM/sq ft (See Item 3 and Table 1) L Rating (Without Movement) At 400 F — Less Than 1 CFM/sq ft (See item 3 and Table 1) W Rating (Without Movement) — Class 1 (See Items 3, 4 and 4A) M RATING (Movement) — See Table 2 2 A A SECTION A -A 1. Floor Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. 1A. Floor Assembly - (Optional - Not Shown) — The fire rated unprotected concrete and steel floor assembly shall be constructed of the materials and in the manner specified in the individual D900 Series designs in the UL Fire Resistance Directory and as summarized below: A. Concrete — Min 4-1/2 in (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. B. Steel Floor and Form Units* — Composite or non -composite max 3 in. (76 mm) deep galv steel fluted units as specified in the individual Floor -Ceiling Design. 2. Firestop Device* — Cast in place firestop device permanently embedded during concrete placement or grouted in concrete assembly in accordance with accompanying installation instructions. The devices may extend a max 2 in. (51 mm) above the top surface of the concrete. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 680-75/2.5"N, CP 680-110/4"N, CP 680-160/6"N, CP 680-P 2", CP 680-P 3", CP 680-P 4", CP 680-P 6", CP 680-PX 2", CP 680-PX 3" 3. Through Penetrants — One nonmetallic pipe or conduit to be installed within the firestop system. Pipe or conduit to be rigidly supported on both sides of floor assembly. For W Rating with Water Barrier Module, pipe shall be installed from bottom of device. The following types and sizes of nonmetallic pipes or conduits may be used: A. Polyvinyl Chloride (PVC) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Pipe-Nom 6 in. (152 mm) diam (or smaller) SDR11 or SDR13.5 CPVC pipe for use in closed (process or supply) piping systems. C. Rigid Nonmetallic Conduit+ — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA No. 70). D. Cross Linked Polyethylene (PEX) Tubing — Nom 4 in. (102 mm) diam (or smaller) SDR 9 PEX tubing for use in closed (process or supply) piping systems. LO 0 N Q LL Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. Hilti Firesto Systems January 21,2020 p Y ms Page: 1 of 2 System No. F-A-2054 The firestop devices and nonmetallic penetrants shall be sized as follows in Table 1 below: Nom Pipe Diameter Firestop Device T Rating-Hr CP 680-75/2.5"N 1/2 in. to 2 in. (19 mm to 51 mm) CP 680-P 2" 3 CP 680-PX 2" CP 680-110/4"N CP 680-P 3" 3 in. (76 mm) 0 and 3+ CP 680-PX 3" CP 680-P 4" CP 680-110/4"N 4 in. (102 mm) 3 CP 680-P 4" CP 680-160/6"N 6 in. (152 mm) 0 CP 680-P 6" +3 hr T Rating applies when CP 680-P(X) 3" and CP 680-P 4" devices are used. 3 hr T Rating also applied when CP 680-110/4"N device is used provided that min 4 in. (102 mm) thickness of nom 4 pcf (64 kg.m3) mineral wool batt insulation tightly packed within annulus between pipe and wall of CP 680-110/4"N device. ++ L Rating applies only to CP 680-P(X) devices and only when the nom diam of pipe equals size of device (2 in. diam pipe in 2" device etc.) L Rating does not apply to CP 680N devices. +++ T Rating is 0 hr for firestop systems with M Rating (Movement) 4. Firestop Device — Top seal plug for use with CP 680-P(X) 2" device installed in accordance with the manufacturer's instructions. The Top Seal Plug is optional for nom 1-1/2 in. (38 mm) pipes and conduits. Top Seal Plugs are required for all pipes and conduits less than nom 1-1/2 in. (38 mm). W Rating applies only to the IPS Top Seal Plug and nom 2 in. diam penetrants and CPS Top Seal Plug for nom 1/2 to 2 in. (13 to 51 mm) diam penetrants. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — IPS and CPS Top Seal Plugs 4A. Firestop Device* - Water Barrier Module — (Optional, Not Shown) - Alternate to Top Seal Plug (Item 4). Applies to nom 2", 3", 4" and 6" water barrier modules used in combination with the CP 680-P(X) 2", CP 680-P(X) 3", CP 680-P 4" and CP 680-P 6" devices, respectively, and supplied by device manufacturer. Module is threaded onto top of device. W Rating applies only when water barrier module is used and nom diam of penetrant equals size of device. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — Water Barrier Module THE M RATING FOR THE FIRESTOP SYSTEM IS DEPENDENT ON THE VARIABLES AS NOTED IN TABLE 2 BELOW. Movement Penetrant NOMINAL Device Sealant L W Direction Item PENETRANT Size Movement Depth Rating Rating DIAMETER Y 3A 2 in. 2 in. 100% N/A N/A N/A Z 3A 2 in. 2 in. 3.21 in. N/A N/A N/A ** PERCENTAGE MOVEMENT BASED ON THE MINIMUM DISTANCE BETWEEN PENETRANT OD AND DEVICE ID. * INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR JURISDICTIONS EMPLOYING THE UL OR CUL CERTIFICATION (SUCH AS CANADA), RESPECTIVELY. Hilti Firestop Systems Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. January 21, 2020 LO 0 N Q LL Page: 2 of 2 E Product information CAST -IN FIRESTOP DEVICES (CP 680-P, CP 680-PX, AND CP 680-M) For use in Dust and fiber free environments such as hospitals, computer centers and laboratories Concrete floor assemblies rated up to 4 hours Product description A one-step cast -in firestop device for a variety of pipe materials and diameters Helps reduce labor costs and increase productivity Ready -to -use out of the package Internationally tested and approved by UL and FM Reduces the chance of project delays due to failed inspections Product features Quick and simple installation SpeedLine Alignment system promotes faster layout QuickTurn System creates fast, simple vertical connections Integrated moisture and smoke seal Innovative adapter for metal deck applications Installation and applications Concrete floors from 2.5" (63 mm) thickness for either flat concrete or concrete over metal deck CP 680-M: - Insulated and non -insulated metal pipes - EMT and electrical conduits - Cable bundles - Multiple pipes CP 680-P: Addresses all applications for CP 680-M as well as the following: - Plastic pipes such as PVC, CPVC, ABS, ENT and FRPP - Fresh and waste water pipes CP 680-PX: Addresses all applications for CP 680-P as well as the following: - XFR pipes Not suited for Areas with high condensation Outdoor areas Wall applications Installation and applications Notice Before handling, read Material Safety Data Sheet and product label for safe usage and health information. Instructions below are general guidelines — always refer to the applicable drawing in the UL Fire Resistance Directory or Hilti Firestop Systems Guide for complete installation information Instructions for use Before pouring concrete, secure the cover cap in place, thereby preventing the flow of concrete into the cast -in device Do not use for wall applications ' Hilti Firestop Hilti (Canada) Corp. Saving lives 1-800-363-4458 / through innovation www.hilti.ca and education CP 680-P and CP 680-M in CP 680-P and CP 680-M over CP 680-PX in concrete over CP 680-PX over metal deck concrete over wood forms metal deck wood forms Technical Data CP 680-P, CP 680-PX, and CP 680-M ID Footprint Opening required thru metal deck 2" 3-3/4" x 4-1/2" 3-1/2" diameter 3" 4-3/4" x 5-5/8" 4-1/2" diameter 4" 6-3/8" x 6-3/4" 5-1/2" diameter 6" 9" x 9-1/2" 7-1/2" diameter Expansion temperature 392°F (200eC) Expansion rate 1:50 (unrestrained) 1:30 (Load expansion, Load = 20g/cm3) Standard height 8" Temperature resistance Maximum 212OF (100°C) Color CP 680-P: red CP 680-M: black CP 680-PX: red Tested in accordance with • UL 1479 • ASTM E 814 • ASTM G21 • CAN/ULC-S115 Internationally tested and approved QSSIF/ FIRESTOP DEVICE FOR USE IN THROUGH VQA -PENETRATION FMC1 ucMC SEE UL FIRE RESISTANCE DIRECTORY IRE RE ISTANCEDI FBC- System Compatible L J SN76 APPROVED indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuarb Gold(@, BlazeMasterA and Corz,ho piping systems and products made with TempRiteA Technology .""The FBC System Compatible Logo, FBC'"", Flow - Guard Gold®, BlazeMasterOO, CorzahA, and TempRiteA are trademarks of Lubrizol Advanced Materials, Inc. or Its affiliates" E1©0N® CERTIFICATE OF COMPLIANCE Certificate Number 20150626-R15431 Report Reference R15431 Issue Date 2015-06-26 Issued to: Hilti, Inc, 5400 S 122ND East Ave Tulsa, OK 74146 This is to certify that Firestop Devices representative samples of CP 680-M 2 in., CP 680-M 3 in., CP 680-M 4 in., CP 680-M 6 in., CP 680-P 2 in., CP 680-P 3 in., CP 680-P 4 in., CP 680-P 6 in., CP 681 and CP 680-PX 2 in. and CP 680-PX 3 in. for use Through -Penetration Firestop Systems as currently described in the UL Fire Resistance Directory and the products Certified for Canada Directory. Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: ANSI/UL 1479, "Fire Tests of Through -Penetration Firestops." CAN/ULC-S115 "Standard Method of Fire Tests of Firestop Systems." Additional Information: See the UL Online Certifications Directory at www.ul.com/database for additional information Only those products bearing the UL Classification Mark for the U.S. and Canada should be considered as being covered by UL's Classification and Follow -Up Service and meeting the appropriate U.S. and Canadian requirements. The UL Classification Mark includes: the UL in a circle symbol: °r with the word "CLASSIFIED" (as shown); a control number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL's evaluation of the product; and the product category name (product identity) as indicated in the appropriate UL Directory. The UL Classification Mark for Canada includes: the UL Classification Mark for Canada: °L with the word "CLASSIFIED" (as shown); a control number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL's evaluation of the product; and the product category name (product identity) in English, French, or English/French as indicated in the appropriate UL Directory. Look for the UL Classification Mark on the product. �114i"r /1. 47`- William R. Carney, Director, North American Certification Programs UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at www.ul.comlcontactus Page 1 of 1 4 Material Information Statement Articles According to Regulation (EC) 1907/2006, Article 32 Revision: 04.08.2022 1.1 Product identifier Trade name: • Firestop Bandage CFS-B / CFS-CB / CP 646 • Firestop Back Pan Strip CFS-BPS • Firestop Block CFS-BL / CFS-BL P • Firestop Board CP 675 • Firestop Boot CFS-BO • Firestop Box Insert • Firestop Cable Collar CFS-CC / CFS-RCC / CFS-RCC EXT • Firestop Cable Module CFS-T • Firestop Cast -in device and accessories CP 680 / CP 681 / CFS-CID / CFS-CID MD P/M/ CFS-CID MD HS GUI / CFS- CID MD PLT W2/W3 / CFS-CID MD HS / CFS-CID ARB TE- Y / CFS-CID ARB TE-C • Firestop Coated Board CFS-CT B / CP670 / CP673 / CP676 • Firestop Collar CFS-C / CFS-C P • Firestop Collar CP 643 / CP 644 • Firestop Composite Sheet CFS-COS • Firestop Cord CFS-CO • Firestop Cushion CP 651N • Firestop Drop -In Device CFS-DID • Firestop Edge of Slab QuickSeal CFS-EOS QS • Firestop Endless Collar CFS-C EL • Firestop Filler Module CFS-T FB • Firestop Gangplate CFS-SL GP • Firestop Module Box CFS-MB / CP 657 • CFP-ES ENDO-SHIELD 1.2 Application of the listed articles Version: 23 • Firestop Plug CFS-PL / CP 658 • Firestop Plug Seal CFS-T RR / CFS-T RRS • Firestop Retrofit Sleeve CFS-SL RK • Firestop Sleeve CP 645 • Firestop Sleeve Kit CFS-SL SK • Firestop Modular Sleeves and accessories CFS-MSL / CFS- MSL GPP Pre -Installed Gang Plates / CFS-MSL FGR Floor Grids / CFS-MSL GCL (Ganging Clips) / CFS-MSL GPA Adjustable Gang Plates / CFS-MSL GPR Retrofit Gang Plates • Firestop Speed Sleeve CFS-SL / CFS-SL GA / CP 653 • Firestop Top Track Seal CFS-TTS • Firestop Top Track Seal CFS-TTS MD • Firestop Top Track Cover CFS-TTS MD C • Firestop Top Track Plug CFS-TTS MD P • Firestop Top Track Seal CFS-TTS 212 • Firestop Top Track Seal CFS-TTS R • Firestop Wedge Seal CFS-T WD120 • Firestop Wrap Strip CFS-W EL / SG / P / CP 648 • Foil Tapes CS -FT • Intumescent fagade cavity closer CP674 • Joint Sealing Tapes CS-JST • Mineral Wool • Mineral Wool Boards • Multifunctional Tapes CS-MFT • Pre -coated Mineral Wool Boards • Smoke & Acoustic Track Seal CS-TTS SA • Speed Plug CP 777 • Speed Strip CP 767 Construction industry. Refer to Hilti product literature, technical data sheets, 3rd party published listings and national approvals for specific application information. For more details, please contact your local Hilti organization through http://www.hilti.ciroup 1.3 Manufacturer / Supplier Hilti AG Feldkircherstr. 100 FL-9494 Schaan Liechtenstein Customer Service Phone +423 (0)844 84 84 85 Fax +423 (0)844 84 84 86 A Safety Data Sheet is not required due to the classification of these products as "articles" according to Regulation (EC) No. 1907/2006 of 18 December 2006 (EU) / 29CFR 1910.1200 (U.S.A.). Consequently, these products are exempted from CLP / OSHA Labeling and SIDS requirements. These data are based on our present knowledge. However, they shall not constitute a guarantee for any specific product features and shall not establish a legally valid contractual relationship. Informing department: chemicals.hse(a) hilti.com 5 L E G E N D Technical Services, Inc. W W VJ I o f] P, �l !� - f] r o ll () r o !7) 88 Empire Drive • St. Paul, Minnesota • 55103 (651) 642-1150 • fax (651) 642-1239 VOC Content Test Certificate April 12, 2011 Supplier: Hilti Entwicklungsgesellschaft mbH BU Chemicals Hiltistrasse 6 86916 Kaufering GERMANY Sample Description: Hilti CP 680 Assembly Date Tested: April 4, 2011 Test Method: SCAQMD method 304-91 "Determination of Volatile Organic Compounds (VOC) in Various Materials" as referenced by South Coast Air Quality Management District (SCAQMD) Rule 1168. The values also comply with the requirements of EPA test method #24. Test Data: Specification Product LEED 2009 (LEED 3.0) LEED 2.2 IEQ-4.1: Low -Emitting Materials — Adhesives and Sealants Hilti CP 680 Assembly Green Building Council of Australia Green Star Office Design 3.0, IEQ-13 Green Star Office Design 2.0, IEQ-13 Green Star Office Interiors 1.1, IEQ-11 Architectural Sealant; VOC Limit: 250 g/L Product contains: 1.4 g/L of VOC William Welbes Tom Barrett Vice President of Laboratory Operations Senior Chemist I