DNS RESUB2 BLD2021-0088+T SHEETS+12.28.2021_5.57.49_PM+2594904i c i c 11 TECHNOLOGY SHEET LIST Sheet Number Sheet Name S T T001 LOW VOLTAGE NARRATIVE T002 LOW VOLTAGE NARRATIVE T101 LEVEL 01 FLOOR PLAN T102 LEVEL 02 FLOOR PLAN T103 LEVEL 03 FLOOR PLAN T104 LEVEL 04 FLOOR PLAN T105 LEVEL 05 FLOOR PLAN T106 LEVEL 06 FLOOR PLAN T107 ROOF FLOOR PLAN T200P LEVEL P1 RCP T201 LEVEL 01 RCP T202 LEVEL 02 RCP T203 LEVEL 03 RCP T204 LEVEL 04 RCP T205 LEVEL 05 RCP T206 LEVEL 06 RCP T300 ENLARGED PLANS & ELEVATIONS T301 ENLARGED PLANS & ELEVATIONS T400 PATHWAY RISER DIAGRAM T401 CABLING RISER DIAGRAM T402 THEATER ROOM FLOW DIAGRAM T403 COMMON AREA SOUND SYSTEM FLOW DIAGRAM T500 DETAILS T501 DETAILS T502 DETAILS ABBREVATIONS A AMPERS N - NEUTRAL AC ABOVE CEILING NC - NORMALLY CLOSED AFC ABOVE FINISHED CEILING NIC - NOT IN CONTRACT AFF ABOVE FINISHED FLOOR NO - NORMALLY OPEN AHJ AUTHORITY HAVING JURISDICTION No. - NUMBER AWG AMERICAN WIRE GAUGE NTS - NOT TO SCALE BAS BUILDING AUTOMATED SYSTEMS NVR - NETWORK VIDEO RECORDER BMS BUILDING MANAGEMENT SYSTEMS OC - ON CENTER BDF BUILDING DISTRIBUTION FACILITY OD - OUTSIDE DIAMETER C CONDUIT OFCI - OWNERFURNUSHED, CONTRACTOR INSTALLED CAT CATALOG OFE - OWNER FURNISHED EQUIPMENT CATV COMMUNITY ANTENNA TELEVISION OFOI - OWNER FURNISHED, OWNER INSTALLED CB CIRCUIT BREAKER OSP - OUTSIDE PLANT CABLE CCTV CLOSED CIRCUIT TELEVISION PA - PUBLIC ADDRESS CER COMMUNICATIONS EQUIPMENT ROOM PB - PULL BOX CKT CIRCUIT PNL - PANEL CL CENTERLINE POE - POWER OVER ETHERNET CLG CEILING PR - PAIR COND CONDUCTOR PTZ - PAN/TILT/ZOOM CID CONSOLIDATION POINT REQ - REQUIREMENT CU COPPER RM - ROOM DIM DIMENSION SMF - SINGLE -MODE FIBER DWG DRAWING STP - SHIELDED TWISTED PAIR (E) EXIST/EXISTING XFRM - TRANSFORMER EC EMPTY CONDUIT TGB - TELECOMMUNICATIONS GROUNDING BAR EF ENTRANCE FACILITY TEL - TELECOMMUNICATIONS EM EMERGENCY TMGB - TELECOMMUNICATIONS MAIN GROUNDING BUSBAR ER EQUIPMENT ROOM TR - TELECOMMUNICATIONS ROOM EX EXISTING TSER - TELECOMMUNICATIONS SERIVE ENTRANCE ROOM F/UTP FOIL SCREENED TWISTED PAIR TSID - TELECOMMUNICATIONS SPACE IDENTIFICATION FA FIRE ALARM TS - TAMPER SWITCH FACP FIRE ALARM CONTROL PANEL TTB - TELECOMMUNICATIONS TERMINAL BOARD FOE FIBER OPTIC ENTRANCE TTC - TELECOMMUNICATIONS TERMINAL CABINET G GROUND TV - TELEVISION HC HUNG CEILING TYP - TYPICAL HZ HERTZ (U/)UTP - UNSHIELDED TWISTED PAIR HT HEIGHT/HIGH LION - UNLESS OTHERWISE NOTED ID INSIDE DIAMETER UPS - UNINTERRUPTIBLE POWER SUPPLY OF INTERMEDIATE DISTRIBUTION FRAME UTP - UNSHIELDED TWISTED PAIR JB JUNCTION BOX V - VOLTS LOMMF LASER OPTIMIZED MULTIMODE FIBER VA - VOLT-AMPERES LV LOW VOLTAGE VIF - VERIFY IN FIELD MAX MAXIMUM VM - VOLTIMETER MDF MAIN DISTRIBUTION FRAME VP - VAPOR PROOF MER MECHANICAL EQUIPMENT ROOM WAP - WIRELESS ACCESS POINT MH MANHOLE W - WATTS MIN MINIMUM WP - WATERPROOF MMF MULTIMODE FIBER WT - WATER TIGHT MPOE MINIMUM POINT OF ENTRY ZDF - ZONE DISTRIBUTION FACILITY MTD MOUNTED MTG MOUNTING AV SYMBOLS & CABLING REQUIREMENTS SP-1 IN -CEILING SPEAKER SP-2 IN -CEILING THEATER SPEAKER SP-3 IN -CEILING SURROUND SPEAKER SP-4 SURFACE MOUNT SPEAKER SW-1 SUBWOOFER SW-2 SUBWOOFER (RECESSED) MSC MOTORIZED SCREEN AV AUX VIDEO INPUT WALL PLATE CP AV CONTROL PANEL DEVICE LEGEND AC-X ACCESS CONTROL READER ACP ACCESS CONTROL PANEL ACS ACCESS CONTROL SERVER AO AUTO OPERATOR (BY OTHERS) ECP ELEVATOR CONTROL PANEL IC X INTERCOM STATION KP ALARM KEYPAD E FIRE RELAY (FOR LOCK RELEASE) LA LOCAL ALARM MC-X MAGNETIC CONTACT MD-X MOTION DETECTOR MH MAGNETIC HOLD OPEN MON VIDEO SURVEILLANCE NVR NETWORK VIDEO RECORDER PBX PUSH BUTTON PC PULL CORD RPT SKYNET REPEATER SBP SECURITY BADGE PRINTER SR SECURITY RISER LOCATION SI SIREN / SOUNDER ST STROBE UAP UNIT ACCESS PANEL WS WORKSTATION XLP LOCK POWER SUPPLY XCP CAMERA POWER SUPPLY XDP DEVICE POWER SUPPLY KKl<VSS CAMERA - FIXED C-X ) VSS CAMERA - PAN / TILT / ZOOM (PTZ) c-x VSS CAMERA - MULTI -SENSOR 360 DEGREE LOW VOLTAGE SYMBOL DESIGNATION WALL OUTLET SYSTEM TYPE xxx xx p xx" # OF DATA MOUNTING DROPS ELEVATION CEILING OUTLET SYSTEM TYPE xxx 1 # OF DATA DROPS FLOOR OUTLET 1 # OF DATA DROPS xxx SYSTEM TYPE DEVICE SYMBOL / TAG LEGEND F- DEVICE TYPE � w X XX ai XXX XXX LEVEL --J T QUANTITY DEVICE C-X DEVICE DETAIL DESIGNATION, REFER TO SECURITY DETAILS DEVICE AC-X DEVICE DETAIL DESIGNATION, REFER TO SECURITY DETAILS DEVICE TYPES: AC = ACCESS CONTROL C = VIDEO SURVEILLANCE IC = INTERCOM ID = INTRUSION DETECTION LOW VOLTAGE SYSTEM DESIGNATION SYSTEM NOTES AC ACCESS CONTROL ACP ALARM CONTROL PANEL ATM AUTOMATED TELLER MACHINE AVCAM AV IP CAMERA BAS BUILDING AUTOMATION SYSTEM CONNECTION POINT BMS BUILDING MANAGEMENT SYSTEM CONNECTION POINT CAM INDOOR - IP CAMERA CAM1 OUTDOOR - IP CAMERA CAM2 OUTDOOR - IP CAMERA CATV AV CATV CONNECTION POINT CID AV CONTROL PANEL DAS DISTRIBUTED ANTENNA SYSTEM - CELLULAR DS AV DIGITAL SIGNAGE ECP ELEVATOR CONTROL PANEL CONNECTION POINT ECS INDOOR EMERGENCY CALL STATION ECS1 OUTDOOR EMERGENCY CALL STATION ERK AV EQUIPMENT RACK ERRCS EMERGENCY RESPONSE RADIO COMMUNICATIONS SYSTEM ETU EMERGENCY TELEPHONE UNIT FCP FIRE CONTROL PANEL FPD AV FLAT PANEL DISPLAY IC INDOOR - IP INTERCOM IC1 OUTDOOR - IP INTERCOM IC2 OUTDOOR - IP INTERCOM LEC AVLECTURN LTC LIGHTING CONTROL SYSTEM CONNECTION POINT MIC AV IP MICROPHONE PRJ AV PROJECTOR RPT REPEATER RS AV ROOM SCHEDULING PANEL SCP SECURITY CONTROL PANEL TC TIME CLOCK VEN VENDING MACHINE CONNECTION POINT W WALL PHONE WAP 802.11 WIRELESS ACCESS POINT WAP1 802.11 WIRELESS ACCESS POINT CONDUIT PATHWAYS AND ENCLOSURES 1. GENERAL REQUIREMENTS a. REQUIREMENTS FOR CONDUITS AND BACK BOXES IN SPECIFICATION 27 05 33 COMMUNICATION CONDUITS AND BOXES SHALL BE FOLLOWED. PULL BOX SIZING GUIDE CONDUIT TRADE SIZE (IN.) PULL BOX WIDTH (IN.) PULL BOX LENGTH (IN.) PULL BOX DEPTH (IN.) PULL BOX WIDTH INCREASE FOR ADDITIONAL CONDUIT (IN.) 1 4 16 3 2 1 1 /4 6 20 3 3 1 1 /2 8 27 4 4 2 8 36 4 5 2 1 /2 10 42 5 6 3 12 48 5 6 3 1 /2 12 54 6 6 4 15 60 8 8 LOW VOLTAGE GENERAL NOTES ELECTRICAL NOTES 1. IT SHALL BE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR RISER POWER (EMERGENCY CIRCUIT) TO VERIFY THE APPLICABLE CODE VERSION WITH THE AUTHORITY HAVING JURISDICTION (AHJ) FOR ALL WORK PERFORMED. DIV 26 CONTRACTOR TO PROVIDE A HARD WIRED CONNECTION TO A O 120VAC 20A EMERGENCY CIRCUIT DEDICATED TO SECURITY IN EACH RISER 2. NOTIFY CONSULTANT OF ANY DISCREPANCIES BETWEEN THE EXISTING LOCATION WITHIN A 4"x4" BOX SURFACE MOUNTED 18" A.F.F. WITH WIRE ENDS CONDITIONS AND THE TELECOM DRAWINGS. OBTAIN CLARIFICATION TERMINATED AND INSULATED WITH WIRE NUTS. BEFORE PROCEEDING WITH WORK. RISER POWER (NON -EMERGENCY CIRCUIT) 3. A COPY OF THE SPECIFICATIONS AND DRAWINGS SHALL BE MAINTAINED AT THE JOB SITE AND SHALL BE PRESENTED UPON DIV 26 CONTRACTOR TO PROVIDE A HARD WIRED CONNECTION TO A 120VAC REQUEST. MAINTAIN DAILY MARKUPS OF ACTUAL INSTALLATION AND 2 20A NON -EMERGENCY CIRCUIT DEDICATED TO SECURITY IN EACH RISER LOCATION PRESENT FOR REVIEW DURING ALL SITE VISITS BY CONSULTANT. WITHIN A 4"x4" BOX SURFACE MOUNTED 18" A.F.F. WITH WIRE ENDS TERMINATED AND INSULATED WITH WIRE NUTS. 4. CABLE BUNDLING IS TO BE AVOIDED, ALL CABLES SHALL BE ALLOWED TO LAY NATURALLY IN CABLE TRAYS AND RUNWAYS. WHEN BUNDLING SECURITY CONTROL / EQUIPMENT ROOM POWER (UPS CIRCUIT) IS NECESSARY NO BUNDLE SHALL BE LARGER THAN 24 CABLES. DIV 26 CONTRACTOR TO PROVIDE A HARD WIRED CONNECTION TO A 120VAC 5. EXACT MOUNTING LOCATIONS AND HEIGHTS ARE FIELD 3 20A UNINTERRUPTIBLE POWER CIRCUIT DEDICATED TO SECURITY WITHIN A 4"x4" COORDINATION ISSUES. CONTRACTOR TO COORDINATE WITH BOX SURFACE MOUNTED BELOW THE FLOOR UNDER THE CONSOLE / RACK WITH EXISTING CONDITIONS ON SITE TO PROVIDE THE MOST AESTHETIC WIRE ENDS TERMINATED AND INSULATED WITH WIRE NUTS. APPEARANCE AND ALIGNMENT WITH NEARBY DEVICES. MAGNOTOMETER / X-RAY SCANNER POWER (EMERGENCY CIRCUIT) 6. TELECOMMUNICATIONS ROOM DIMENSIONS ON THE DRAWINGS HAVE BEEN TAKEN FOR THE ARCHITECTURAL DRAWINGS. THE SCALE OD DIV 26 CONTRACTOR SHALL PROVIDE AN UN -SWITCHED DUPLEX OUTLET THESE DRAWINGS ARE SUFFICIENTLY ACCURATE FOR DETERMINING 4 CONNECTED TO A 120VAC 20A EMERGENCY CIRCUIT DEDICATED TO SECURITY. THE THE LOCATION OF TELECOMMUNICATIONS INFRASTRUCTURE OUTLET SHALL BE FLUSH MOUNTED IN THE FLOOR. COMPONENTS, JUNCTION BOXES, OUTLET BOXES, RACEWAYS, RUNWAYS, PANELS, ETC. WHERE EXACT DIMENSIONS ARE INDICATED, EXTERIOR CAMERA POWER (EMERGENCY CIRCUIT) THE REFERENCE SURFACE SHALL BE THE FINAL FINISHED SURFACE INCLUDING ANY ACOUSTICAL TREATMENT. DIV 26 CONTRACTOR SHALL PROVIDE HARD WIRED CONNECTION TO A 120VA 5 20A EMERGENCY CIRCUIT DEDICATED TO SECURITY. THE CIRCUIT CONNECTION 7. ALL DIMENSIONS SHALL BE VERIFIED IN THE FIELD AND ANY SHALL BE PROVIDED WITHIN A 4"x4" BOX MOUNTED ABOVE ACCESSIBLE CEILING ON DEVIATIONS CAUSING CHANGES EXCEEDING 6 INCHES TO THE INTERIOR OF BUILDING WITH WIRE ENDS TERMINATED INSULATED WITH WIRE NUTS. INTENDED LOCATION OF MAJOR TELECOMMUNICATIONS MULTIPLE CONNECTIONS CAN BE BRANCHED OFF THIS CIRCUIT FOR ADDITIONAL INFRASTRUCTURE COMPONENTS SHALL BE COORDINATED WITH THE CAMERAS BUT SHALL NOT EXCEED 15 CONNECTIONS TOTAL. EACH CAMERAS ARCHITECT AND CONSULTANT PRIOR TO INSTALLATION. ACTUAL LOAD SHALL BE 1A AT 120VAC. 8. IT SHALL BE THE RESPONSIBILITY OF THE TELECOMMUNICATIONS POLE MOUNTED CAMERA POWER (EMERGENCY CIRCUIT) CONTRACTOR TO COORDINATE AND VERIFY SIGNAL/CONDUIT PATHWAYS WITH THE ELECTRICAL DRAWINGS. DIV 26 CONTRACTOR SHALL PROVIDE A HARD WIRED CONNECTION TO A 6 120VAC 20A EMERGENCY CIRCUIT DEDICATED TO SECURITY PROVIDED WITHIN A O 9. REFER TO DIVISION 27 SPECIFICATIONS FOR INSTALLATION NEMA 4X ENCLOSURE MOUNTED AT THE BASE OF THE POLE WITH WIRE ENDS REQUIREMENTS RELATED TO FLOOR BOXES, JUNCTION BOXES, TERMINATED AND INSULATED WITH WIRE NUTS. MULTIPLE CONNECTIONS CAN BE BONDING CONDUCTORS, BUSBARS, CONDUITS, CONDUIT BENDS, BRANCHED OFF THIS CIRCUIT FOR ADDITIONAL CAMERAS BUT SHALL NOT EXCEED RUNWAYS IN CORRIDORS, METALLIC ENCLOSURES. 15 CONNECTIONS TOTAL. EACH CAMERAS ACTUAL LOAD SHALL BE 1A AT 120VAC. 10.130ND ALL CONDUITS, CABLE TRAYS, AND JUNCTION BOXES IN DELAYED EXIT DEVICE POWER (NON -EMERGENCY CIRCUIT) TELECOMMUNICATIONS SPACES PER TIA-607 IN ADDITION TO ANY APPLICABLE CODE REQUIREMENTS. DIV 26 CONTRACTOR SHALL PROVIDE A HARD WIRED CONNECTION TO A 7 120VAC 20A NON -EMERGENCY CIRCUIT DEDICATED TO SECURITY AT DOORS O 11.PRIOR TO DRILLING OR CORING ANY CONCRETE, NEW OR EXISTING, UTILIZING DELAYED EXIT DEVICES PROVIDED WITHIN A 4"x4" BOX MOUNTED ABOVE REBAR AND PT TENDON SHALL BE LOCATED BY SCANNING. SHOP ACCESSIBLE CEILING ADJACENT TO THE DOOR WITH WIRE ENDS TERMINATED AND DRAWINGS SHOWING THE COORDINATED LOCATIONS OF THE OPENINGS INSULATED WITH WIRE NUTS. AND ANCHORS TO AVOID DAMAGING REBAR AND PT TENDONS SHALL BE SUBMITTED. CORING OF POST -TENSION CONCRETE IS NOT ELECTRIC EXIT DEVICE POWER (EMERGENCY CIRCUIT) PERMITTED WITHOUT THE REVIEW OF THE ARCHITECTS, DIV 26 CONTRACTOR SHALL PROVIDE A HARD WIRED CONNECTION TO A 12. ALL TELECOMMUNICATIONS RELATED FLOOR BOXES, POKE THRU 8 120VAC 20A EMERGENCY CIRCUIT DEDICATED TO SECURITY AT DOORS UTILIZING DEVICES, JUNCTION BOXES AND BACK BOXES SHOULD BE PROVIDED ELECTRIC EXIT DEVICES PROVIDED WITHIN A 4"x4" BOX MOUNTED ABOVE WITH AN EMPTY CONDUIT TO THE APPLICABLE TELECOM ROOM, ACCESSIBLE CEILING ADJACENT TO THE DOOR WITH WIRE ENDS TERMINATED AND CABLE TRAY, RUNWAY, PULL BOX, OR OPEN ACCESS CEILING AREA. INSULATED WITH WIRE NUTS. MULTIPLE CONNECTIONS CAN BE BRANCHED OFF THIS CIRCUIT FOR ADDITIONAL ELECTRIC EXIT DEVICES BUT SHALL NOT EXCEED 10 13. CONDUIT ROUTES ON THE TELECOM DRAWINGS SHOW ONLY CONNECTIONS TOTAL. EACH DEVICES ACTUAL LOAD SHALL BE 1.5A AT 120VAC. INTERCONNECTION BETWEEN THE TERMINATION POINTS AND APPROXIMATE ROUTES. THE EXACT ROUTE OF CONDUIT PATHWAYS SITE POWER (NON -EMERGENCY CIRCUIT) SHALL BE COORDINATED AND VERIFIED BY CONTRACTOR BASED ON FIELD CONDITIONS. DIV 26 CONTRACTOR SHALL PROVIDE A HARD WIRED CONNECTION TO A 9 120VAC 20A NON -EMERGENCY CIRCUIT DEDICATED TO SECURITY WIHIN A NEMA 4X O 14. CABLE PATHWAYS ON THE TELECOM DRAWINGS SHOW ONLY ENCLOSURE WITH WIRE ENDS TERMINATED AND INSULATED WITH WIRE NUTS. APPROXIMATE ROUTES. THE EXACT ROUTE OF PATHWAYS ARE TO BE COORDINATED AND VERIFIED BY CONTRACTOR BASED ON FILED SECURITY CONVENIENCE POWER (NON -EMERGENCY CIRCUIT) CONDITIONS. DIV 26 CONTRACTOR SHALL PROVIDE AN UN -SWITCHED DUPLEX OUTLET 15. THE METHOD OF INSTALLATION FOR ALL TELECOMMUNICATIONS <s> CONNECTED TO A 120VAC 20A NON -EMERGENCY CIRCUIT PROVIDED FLUSH IN WALL RELATED BACKBOXES IN WALLS AND THE METHOD FOR PASSAGE OF 18" A.F.F. CONDUIT AND RUNWAYS THROUGH ACOUSTICALLY SENSITIVE WALLS SHALL EB COORDINATED WITH THE ACOUSTICAL CONSULTANT OR ELEVATOR SECURITY EQUIPMENT POWER (NON -EMERGENCY CIRCUIT) OWNER PRIOR TO INSTALLATION. DIV 26 CONTRACTOR SHALL PROVIDE A HARD WIRED CONNECTIONS TO A 16. ALL TELECOMMUNICATIONS DEVICES SHALL BE SECURELY 11 120VAC 20A NON -EMERGENCY CIRCUIT DEDICATED TO SECURITY IN THE ELEVATOR MOUNTED PLUMB AND STRAIGHT TO WALLS, FLOORS, OR RACKS, PER MACHINE ROOM(S) AS INDICATED ON THE DRAWINGS. TYPICAL LOAD FOR EACH THE MANUFACTURER'S RECOMMENDED MOUNTING PRACTICE. CIRCUIT SHALL BE 10A. PROVIDE CONNECTION IN A SURFACE MOUNTED BOX MOUNTED AT 8' A.F.F. WITH WIRE ENDS TERMINATED AND INSULATED WITH WIRE 17. ALL CABLES SHALL BE RATED FOR THE ENVIRONMENT IN WHICH NUTS. THEY ARE INSTALLED. EMERGENCY CALL TOUCH PANEL POWER (EMERGENCY CIRCUIT) 18. CABLES INSTALLED IN ANY UNDERGROUND CONDUITS, INCLUDING UNDER OR WITHIN A SLAB ON GRADE, SHALL BE INDOOR/OUTDOOR DIV 26 CONTRACTOR SHALL PROVIDE AN UN -SWITCHED SINGLE GANG DUPLEX RATED. 12 RECEPTACLE CONNECTED TO A 120VAC 20A EMERGENCY CIRCUIT PROVIDED O FLUSH IN WALL AT 54" A.F.F TO CENTER. 19. INSTALL FIRESTOP ASSEMBLIES IN ALL THROUGH -SLAB OR THROUGH -WALL RATED BARRIER PENETRATIONS FOR THE EMERGENCY CALL REPEATER POWER (EMERGENCY CIRCUIT) INSTALLATION OF TELECOMMUNICATIONS CABLING AS REQUIRED TO MAINTAIN FIRE RATING OF PENETRATED SLAB OR WALL. REVIEW 13 DIV 26 CONTRACTOR TO PROVIDE AN UN -SWITCHED DUPLEX OUTLET CONNECTED TO DRAWINGS FOR PARTITION TYPE RATINGS. FIRESTOPPING SYSTEMS A DEDICATED 120V 20A EMERGENCY CIRCUIT, PROVIDED FLUSH IN WALL AT 841, A.F.F. USED FOR ALL PENETRATIONS SHALL BE A UL LISTED ASSEMBLY AND APPROVED BY APPLICABLE AUTHORITY HAVING JURISDICTION PRIOR EMERGENCY CALL ANCHOR POWER (EMERGENCY CIRCUIT) TO INSTALLATION. DIV 26 CONTRACTOR TO PROVIDE AN UN -SWITCHED DUPLEX OUTLET CONNECTED TO 20. SLEEVE ASSEMBLIES THAT PENETRATE RATED BARRIERS SHALL BE 14 A DEDICATED 120V 20A EMERGENCY CIRCUIT, PROVIDED AT 84" A.F.F. IN 3" DEEP PLASTIC EZ-PATH OR EQUAL ASSEMBLIES TO ALLOW FOR SIMPLE WEATHER PROOF ENCLOSURE. MAINTENANCE FREE RE-ENTRY WITHOUT DISTURBING SEALANT AND SHALL A PROVIDE SMOKE BARRIER IN ADDITION TO FIRE RATING. SUBWOOFER POWER (NON -EMERGENCY CIRCUIT) 21. ELECTRICAL FEEDS ARE NOT TO EB RIN PARALLEL WITH VIDEO, 15 DIV 26 CONTRACTOR TO PROVIDE AN UN -SWITCHED DUPLEX OUTLET CONNECTED TO A AUDIO, OR TELECOMMUNICATIONS CABLING OR RACEWAYS. IF DEDICATED 120V 20A NON -EMERGENCY CIRCUIT AT 18" A.F.F. ELECTRICAL FEED MUST BE RUN PARALLEL, A MINIMUM OF 6 INCHES OF SEPARATION SHALL BE MAINTAINED. PROJECTOR POWER (NON -EMERGENCY CIRCUIT) 22. POWER RECEPTACLES SHOWN ON TELECOMMUNICATIONS DIV 26 CONTRACTOR TO PROVIDE AN UN -SWITCHED DUPLEX OUTLET CONNECTED TO A DRAWINGS ARE DEDICATED TO SPECIFIC TELECOMMUNICATIONS 16 DEDICATED 120V 20A NON -EMERGENCY CIRCUIT ABOVE CEILING. O EQUIPMENT AND ARE SHOWN FOR REFERENCE ONLY. REFER TO ELECTRICAL DRAWINGS FOR ENGINEERED ELECTRICAL SYSTEM AND PROJECTOR SCREEN POWER (NON -EMERGENCY CIRCUIT) ADDITIONAL UTILITY POWER RECEPTACLES. DIV 26 CONTRACTOR TO PROVIDE AN UN -SWITCHED DUPLEX OUTLET CONNECTED TO A 17 23. THE FINISHES FOR ALL TELECOM COMPONENTS SHALL BE DEDICATED 120V 20A NON -EMERGENCY CIRCUIT ABOVE CEILING. SUBMITTED FOR REVIEW AND APPROVAL PRIOR TO PROCUREMENT. 24. TERMINATION OF OUTLETS IN ELEVATOR CONTROL AND ELEVATOR MACHINE ROOMS SHALL BE COORDINATED WITH ELEVATOR CONTRACTOR. ADDITIONAL SLACK MAY BE REQUIRED IN THESE LOCATIONS 25. DIRECT CONNECT FIELD ASSEMBLY OF EQUIPMENT TO NETWORK CABLING IS NOT PERMITTED. SECURITY CONDUIT AND WIRING NOTES 1.ALL CONDUIT AND BACKBOXES SHALL CONFORM TO BUILDING STANDARD ELECTRICAL SPECIFICATIONS. ALL CABLES SHALL BE PLENUM RATED WHERE REQUIRED. 2.ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED. SECURITY DEVICE NOTES 3.ALL CONDUIT USED IN POTENTIALLY DAMP OR WET LOCATIONS, EXPOSED 1.ALL DEVICES, WIRING, TERMINATION AND OTHER REQUIRED ROUGH -IN NOT OUTDOORS, OR IN HAZARDOUS AREAS SHALL BE INTERMEDIATE STELL CONDUIT DESIGNATED "AS BY OTHERS", ARE TO BE PROVIDED BY THE SECURITY (IMC). ALL EXTERIOR CONDUIT IN SLAB SHALL BE PVC. ALL CONDUIT OTHER THAN CONTRACTOR. SPECIFIED TO BE IMC OR PVC SHALL BE ELECTRICAL METALIC TUBING (EMT). 2.ALL SECURITY DEVICES PROVIDED BY THE SECURITY CONTRACTOR. 4.ALL CONDUIT SHALL BE ROUTED ABOVE CEILINGS, BELOW FLOORS, OR WITHIN WALLS. NO CONDUIT SHALL BE EXPOSED UNLESS APPROVED BY THE ARCHITECT. 5. PROVIDE PULL STRINGS IN ALL CONDUIT AND PULLBOXES AS REQUIRED. ALL CONDUITS SHALL BE PLASTIC BUSHING INSTALLED AT OPEN ENDS. 6. ALL BACKBOXES SHALL BE FLUSH MOUNTED UNLESS OTHERWISE NOTED. TALL BACKBOXES MOUNTED WITHIN FIRE RATED PARTITIONS SHALL MEET THE SECURITY GENERAL NOTES FIRE RATING OF THE PARTITION AS REQUIRED BY CODE. 1. DRAWINGS ARE NOT TO BE USED FOR ARCHITECTURAL OR 8. COORDINATE THE EXACT LOCATION OF ALL PULL AND BACKBOXES WITH ENGINEERING PURPOSES. THE SECURITY DRAWINGS SHOULD ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS. ONLY BE USED FOR SECURITY COORDINATION. 9.ALL JUNCTION AND PULLBOXES SHALL BE PROVIDED WITH ACCCOMPANYING BLANK 2.ALL MOUNTING SPECIFICS SHALL BE AS INDICATED IN THE LEGEND COVER PLATE. UNLESS OTHERWISE NOTED IN THE SECURITY DRAWINGS. MOUNTING CONDITIONS IDENTIFIED ON THE SECURITY DRAWINGS 10. JUNCTION BOXES LOCATED ABOVE DOORS WITH NO ACCESSIBLE CEILING SHALL SHALL TAKE PRECEDENCE OVER THE LEGEND DESCRIPTIONS. BE SECURED WITH TAMPER PROOF SCREWS. 3.VERIFY AND COORDINATE THE EXACT MOUNTING LOCATION OF 11. PROVIDE WATERTIGHT SEALING ASSEMBLIES WITH PRESSURE BUSHING AS ALL DEVICES PRIOR TO INSTALLATION. REQUIRED FOR EXTERIOR PENETRATIONS. 4. THE MOUNTING HEIGHTS ARE TO THE CENTERLINE OF THE DEVICE 12. JUNCTION AND PULLBOXES IN EXTERIOR LOCATIONS SHALL BE WATERPROOF. UNLESS OTHERWISE NOTED. 13. ALL CABLE RUNS IN CEILING AREAS WHERE CONDUIT OR CABLE TRAY IS NOT 5. THE SECURITY CONTRACTOR SHALL RESTORE CEILINGS AND SPECIFIED SHALL BE SUPPORTED WITH SIMILAR SUPPORT OR WITH THE USE WALLS AND ANY OTHER SURFACES AFFECTED BY HIS WORK WITH OF J-HOOKS AT S INTERVALS ABOVE CEILING TILES. LIKE MATERIALS TO MATCH EXISTING CONSTRUCTION UPON COMPLETION OF HIS WORK. 14. COORDINATE WITH DIV 26 FOR SECURITY DEVICE AND CONTROL PANEL POWER REQUIREMENTS. 6. FIRE STOPPING OF ALL PENETRATIONS SHALL BE PROVIDED BY THE SECURITY CONTRACTOR AS REQUIRED BY CODE. 15. WIRE SHEATH SHALL BE MAINTAINED TO FINAL TERMINATION. ALL TERMINATIONS SHALL MAINTAIN TWIST OF INDIVIDUAL PAIRS WIHTIN 0.5" OR LESS OF FINAL TALL DEVICES, WIRING, TERMINATIONS, AND OTHER REQUIRED TERMINATION. ALL WIRES SHALL BE LABELED WITHIN 6.5" OF FINAL TERMINATION. ROUGH -IN NOT DESIGNATED "BY OTHERS" ARE TO BE PROVIDED ALL LABELS SHALL BE MACHINE PRINTED OR STENCILED. NO HAND LETTERED BY THE SECURITY CONTRACTOR. LABELS SHALL BE USED. 8. COORDINATE ALL EXTERIOR CAMERA LOCATIONS WITH THE 16. ANY CONDUIT ROUTING SHOWN IS SCHEMATIC AND IS NOT INTENDED TO LANDSCAPE TO ENSURE THAT CAMERA VIEWS ARE NOT REPRESENT INSTALLED PATHS OR DISTANCES. ACTUAL ROUTING AND BOX OBSTRUCTED. LOCATIONS SHALL BE FIELD VERIFIED AND COORDINATED WITH OTHER DISCIPLINES BY THE INSTALLING CONTRACTOR. 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, LINCOLNSHIRE, IL 60069 TEL: 847-634-1200 m & R DESIGN FAX: 847-634-1201 SERVICES GROUP. LLC WWW.MANDR-DSG.COM N O CD z O Z z O = Q L U C6 0 LL z O0 LLI z_ O N > J > J p _ _ O I` z W Z O cn � Q N U REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 COVER SHEET GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER TOOO 1. OVERVIEW This document shall serve as the design criteria for all Anthology Senior Lifestyle projects. This includes the following systems: Structured Cabling, WIFI, Emergency Call, Video Surveillance, Access Control, and Audio -Video. Unless otherwise noted, any deviation or substitution will not be accepted. If any conflict arises between this low voltage design narrative and the contract drawings, the conflict must be brought to the attention of the Owner, GC, Architect and Low Voltage Consultant by the contractor(s). It is their responsibility to bring the conflict to the Owner, GC, Architect, and Low Voltage Consultant attention and obtain further clarification and/or instruction on how to proceed. This document is intended to provide a detailed account of the scope requirements. That said, the General Contractor and their subcontractors are expected to provide a reasonable amount of Design Assist to ownership/design team, as issues arise. 2. STRUCTURED CABLING 2.1.Dwelling Units • In each dwelling unit, every telecommunication outlet location shall have: • (1) Category 6 and (1) Quad -Shielded RG6 coaxial cable. • In all units, with the exception of MC and Studio units, these cables shall be run through the wall cavities without conduit and shall be coiled in the Unit Access Panel (UAP). • Each cable shall support a single jack —no 7-tapping" is permitted. • In each dwelling unit, with the exception of MC and Studio units, the Low Voltage Contractor (LVC) shall furnish: • (1) flush -mounted structured media box with door cover (Legrand Part Number(s) EN1200 or pre -approved equal). • The LVC will provide these boxes to the Electrical Contractor (EC) to install. • This box will serve as the unit's UAP. • The box shall not be installed on a demising wall and should be located in the entry closet, if possible. • The media box shall be installed at 60" AFF to the top of the box (verify with closet details). • EC to install duplex outlet in designated portion of UAP. • Each bedroom in each dwelling unit shall receive a telecommunications outlet. • MC and Studio units have only one combination outlet and those drops shall be home run from that location back to the nearest IDF. • In the dwelling units at the outlet location: • Each CAT-6 cable shall be terminated with a WHITE CAT-6 RJ-45 jack (terminated in EIA/TIA 568B). • Coaxial cable shall be terminated with a compression F-connector and attached to a modular jack. • The CAT-6 jacks and TV insert will share a single gang 2-port plate. • Terminations of the CAT-6 cables inside at the UAP shall be with male RJ45's, each cable shall have a minimum 18" service loop. • Terminations of the coax cables, in the UAP, shall be terminated with compression snap-n- seal connectors. Each cable shall have a minimum 18" service loop. • All cabling shall be labeled inside the UAP and at patch panel locations within the IDFs/MDF for easy tracing and identification. Labeling shall be printed wrap -around type. • Horizontal unit feed "Home Run" cabling shall consist of (1) Quad -shielded RG6 coax cable and (1) Category 6 cable. • Each dwelling unit shall receive an additional Category 6 for a PoE Wireless Access Point, additional detail on this requirement is provided in the WIFI section below. • See electrical drawings for typical power outlet locations. • All Category 6 cable shall be Hubbell Link Series Cable. All data jacks and patch panels shall be Hubbell NETSELECT connectivity. • EC to provide all pathways and/or sleeves for cabling between corridors/dwelling units and corridors/LV Closets and all boxes and trim rings for all LV outlets. • Contractor shall include Plenum cable if required by AHJ or in any plenum space. Highlight space after this bullet point. 2.2. Common Area Locations • All common area outlets shall have a minimum of (2) Category 6 data drops installed in either a standard wall jack or in modular furniture opening, regardless of what the drawings indicate. • Each Display or Digital Signage display shall have (1) Category 6 and (1) Quad -shielded RG6 coax cable ran from nearest data closet to each location. • Cables shall be terminated at both ends, data terminations in closet shall be on a patch panel. • LVC shall provide EC a rough -in box for these locations. This box shall be Strong (Snap - AV) part #SM-RBX-PRO-8. The EC shall install this box. • LVC shall include a 4-post equipment rack (Chatsworth QuadraRack or pre -approved equal) with horizontal and vertical cable management in the MDF/Server Room. Rack shall have ladder rack attached to the wall to allow for data cables to be neatly dressed into rack. • Other locations that shall require data include, but are not limited to: • Minimum of (6) data drops at each concierge/reception desk. • Minimum of (6) data drops in the Plant Ops/Maintenance Office • Minimum of (1) data drop at each intercom location (main entrance and the loading dock). • Minimum of (2) data drops at all Point of Sale (POS) locations. • Minimum of (1) data drop at Fitness Center equipment • Minimum of (4) drops for Fax Lines within Admin space, to be cross connected with POTS lines, provided by others, by LVC. • Elevators (for emergency phone lines) • Fire Alarm Panel (if AHJ requires) • EC to provide all pathways and/or sleeves for cabling between common areas/LV Closets and all boxes and trim rings for all LV outlets. 2.3. Closet Work • LVC shall furnish and install (1) 12-strand multimode OM3 fiber between the main Data Room and each IDF closet. • LVC shall terminate fiber with LC connectors to either a 1 RU Patch Panel or a wall mounted patch panel. • Fiber shall be run in innerduct or LVC may choose to use armored fiber. Highlight after • LVC Shall run (2) Category 6 cables between the main Data Room and each IDF closet. • These cables shall be punched down to patch panels. • LVC shall run (2) RG-11 coaxial cables between main Data Room and each IDF closet. • All RG6 homerun cables shall be terminated onto a modular patch panel. • LVC shall furnish and install 2-post 42RU open post racks in each IDF for patch panels and network equipment. • LVC to provide vertical and horizontal cable management, as well as cable management (ladder rack/tray). • EC shall provide (3) 4" conduits from the MDF to each IDF closet. • If the IDF's stack, (3) 4" sleeves between IDF closets is acceptable. • In any instance where the closets do not stack, there shall be full conduit between floors. • EC shall provide (4) 4" conduits from the property line into the MDF/Netpop. GC/EC to coordinate exact locations with Internet/TV providers. • LVC Shall furnish and install (1) APC SMT1500RM2UC UPS, (1) APC AP9631, and (1) APC AP9335TH, per data closet. LOW VOLTAGE NARRATIVE v5.0 3. WIFI 3.1.Wireless Access Points • LVC shall furnish all rough -in rings, tile brackets (if needed), cabling, related jacks, and installation labor for wireless access point locations, quantity and locations based on the Technology drawings. • Residential units, as indicated, will have an owner furnished wireless access point which will require a PoE network drop ran from this location back to the nearest IDF. • This outlet shall be located 84" AFF as indicated on the drawings. • EC shall provide a vertical single gang ring for these locations. • Each access point shall have (1) Category 6 data drop, terminated at nearest IDF/Data Closet. These drops shall be terminated onto patch panels. • LVC shall furnish and install (1) 1-ft Category 6 patch cord and (1) 7' Category 6 patch cord per access point. • Access points will be furnished by others but installed by LVC. • EC to provide all pathways and/or sleeves for cabling between corridors/dwelling units and corridors/LV Closets and all boxes and trim rings for all LV outlets. 4. EMERGENCY CALL 4.1.The Emergency Call system will be installed directly by Systems Technologies • Each residential unit shall (1) wireless pull cord per in -unit bathroom. • Common area restrooms and common area spaces shall have (1) wireless pull cord throughout per the Technology drawings. • Surface Mounted door contacts will be installed for monitoring purposes through the Emergency Call System. • EC shall be responsible for providing power to repeaters, per the Technology Drawings. • This outlet will be installed in a rough in box that shall be furnished and installed by the EC (p/n Leviton 001-47617-REB & 002-47617-HPC). • This box is NOT necessary if the repeater is located in IDF closets. • EC shall be responsible for furnishing and installing required rough -in back box for wireless pull cords (Arlington F101). EC to provide all pathways and/or sleeves for cabling between corridors/dwelling units and corridors/LV Closets and all boxes and trim rings for all LV outlets. 5. SECURITY 5.1.Video Surveillance • The video surveillance system will be furnished and installed by the owner's national integrator. GC shall manage their scope and be responsible to coordinate all work between their sub -contractors and the integrator's requirements. • Coverage areas of the video surveillance system include, but are not limited to: • Exterior Entrances/Exits • Reception • Elevator Lobbies • Elevator Cabs • Kitchen • The LVC shall furnish and install a Category 6 data drop for each camera identified on the Technology drawings. • EC to provide all pathways and/or sleeves for cabling between video surveillance camera locations/LV Closets. 5.2.Access Control • The access control system will be S2, consisting of HID Multi -Class card readers and HID Multi -Class reader with integral keypads. • Card Readers will be utilized at the following locations, per the technology drawings: • Main Entrance • Loading Dock • Amenity Spaces • Back of House Spaces • Provide long range vehicle reader and credentials, to be integrated with the access control system for entry into the parking garage. Vehicle detector loops, provided by others, shall be used for exiting the garage. • All residential units shall be accessed by key. • The LVC shall run one access control composite cable (West Penn #AC251822B or equal) from each card reader back to a consolidated location of controllers and power supplies located in the nearest IDF. • The Low Voltage contractor shall then run the individual cables at the door to each respective device. • The access control integrator will make final connections at the controllers, power supplies and doors. • GC shall have a certified representative available at the time of installation to assist with connections for door hardware to their power supplies (specifically but not limited to delayed egress, auto -operators, and sliding doors). • Recessed door contacts shall be installed on all exterior doors and the MC Suite/Stairwell Doors. • The EC shall furnish, install, and program an addressable relay from the building fire alarm system at each access control power supply location. If quantity required is unknown at time of bidding, GC to include all related costs for (10) addressable relays. • The EC shall furnish and install all conduit raceway, rough -in boxes, and hard -wired power connections (for power supplies, auto operators, etc.) at all common area doors with access control. • The GC is responsible to make sure all electronic door hardware is fully coordinated with Architect, access control integrator, and any other associated contractor and will ensure all parties are present for final connections and terminations to the associated hardware. 5.3.Intercom • Intercom substations shall be provided at the Main Entrance and Loading Dock. Intercom substations shall be Aiphone, Model JO-DV. • Intercom master station shall be provided at the Business Office. Intercom master station shall be Aiphone, Model JO-1 MDW. • Intercom system, cabling, installation, interfacing, final connections, and programming shall be completed by the LVC. LVC to assist in download and setup of intercom mobile app. 6. AUDIO-VISUAL 6.1.Theater • The LVC shall furnish and install the following equipment: • (1) Epson PowerLite L1060U WUXGA Projector w/4K Enhancement [white] • AV contractor will provide the proper lens based on where projector needs to be installed, as it relates to distance/height. • (1) Chief or Peerless Universal Ceiling Projector Mounting System • (1) Da-Lite Tensioned Advantage Electrol Projector Screen (Min size 57.5"x92" in 16:10 aspect ratio, HD Pro screen material, and must be ceiling mounted and flush with finished ceiling). • (5) In -Ceiling Speakers (Sonance 6.5" 2-way ceiling speaker or pre -approved equal) • (2) In -wall Powered Subwoofer (Sonance VP Series or similar) • (2) Surface Mount Program Audio Speakers (Crestron Saros SR4T-W-T or similar) • (1) Crestron 3-Series 4K DigitalMedia Pres. Sys (DMPS3-4K-250-C-AIRMEDIA) • (1) Crestron 4K Receiver & Room Controller (DM-RMC-4KZ-SCALER-C) • (1) Crestron 7" Touchscreen - (TSW-760-W-S) • (1) Crestron Digital Media Input Plate (DM-TX-200-C-2G) • (1) Network PoE Switch (sized appropriately) • (1) Sony Integrated A/V Receiver (STR-ZA1100ES) • (1) Sony Blu-ray Player (UBP-X1000ES) • (1) Apple TV Player • (1) Shure Wireless Receiver with Lavalier Microphone (SLX14/85) • (1) Listen Technologies Hearing Assistance Package (LS-70-216) • (4) Listen Technologies DSP Personal Receiver (LR-4200-216) • (4) Listen Technologies Intelligent Neck Loop (LA-430) • (1) 42RU A/V Cabinet with Locking Door (Lowell, Mid -Atlantic, or Approved equal) • Check with Interior Designer for color selection • If any component listed above has been replaced with a newer version, and it is available at the time of install, AV contractor shall provide the most current model available. • The LVC shall also furnish all related programming, misc. cables, and misc. hardware to provide a fully functional system. 6.2.Common Area Sound System • There shall be a background music sound system for the building. • All equipment will reside in the MDF/Main Data Room. • The LVC shall furnish and install 8-ohm and/or 70-volt speakers (assume a quantity of 32 in - ceiling speakers and 9 outdoor speakers) in the following locations: • Zone 1 — Dining 1007/Bistro 1002/Great Room 1001 x 10 • Zone 2 — Great Room Lobby/Elevator Lobby 1004 x 3 • Zone 3 — 6t" FL Exterior Deck x 8.1 landscape system • Outdoor zone speakers shall be Sonance Landscape series and must include a subwoofer. • The equipment for this system shall include, but not be limited to, the following: • (1) 8-Input/8-Zone Audio Mixer/Processor (QSC MP-M80) • (1) 8-channel 70v Audio Amplifier (QSC MP-A80V) • (1) Sonance LS4T SAT/LS12T SUB 8.1 SYS • (32) In -Ceiling Speakers + Installation Brackets (QSC AC-C6T/AC-MR6) • (8) Decora Style Audio Control Keypads located locally within each audio zone, with lockable covers. Every four keypads must be daisy chained. • (3) Sound Machine Media Players • (1) Network Switch (large enough for audio equipment ports) • (1) Swing Out Wall Rack with lockable Door • (2) Lowell 4-gang 1 RU rackmount panel (D4P-1 or approved equal) • (2) Lowell Rackmount Utility Shelves (US-110or approved equal) • (1) Power conditioner to support all rack equipment • (1) Lot rack vents, lacing bars, and any other rack accessory for a clean and organized installation. • (1) Lot 16/2 speaker cable • The LVC shall be responsible for installing and programming, the Sound Machine music source, furnished by the Owner within the AV rack, with network connection and 3.5mm audio jack, in the MDF. Complete all programming of common are sound system listed above for a complete and functioning system. Required streaming/licensing costs will be provided by owner/operator. 6.3.Displays/Digital Signage • The LVC shall furnish and install the following commercial display with mounting brackets. Displays shall have an Ethernet input connection: • Game/Amenity (65" 4K UHD LED TV) • Dining (75" 4K UHD LED TV) • Mail Room (49" 4K UHD LED TV) • Library/TV Alcove (49" 4K UHD LED TV) • Salons (65" 4K UHD LED TV) • Activity Room (65" 4K UHD LED TV) • Fitness (65" 4K UHD LED TV) • Bistro (75" 4K UHD LED TV) • Lounge/Activity (65" 4K UHD LED TV) • Community Room (75" 4K UHD LED TV) • Exterior Roof* (65" 4K UHD LED TV)* • Elevator Vestibules (1 per floor) (49" 4K UHD LED TV) • (1 Per lobby, per floor) • Elevator displays shall be mounted in landscape format. • *Outdoor TVs shall be Sunbrite Signature Series and soundbar with outdoor pedestal. GC shall be responsible for coordinating structural, electrical, and low -voltage requirements when final location is determined. 7. SUBMITTALS & SHOP DRAWINGS • General • The following Submittal and Shop drawing requirements apply to all low voltage systems described herein. • Submittals shall consist of product data, shop drawings, samples, and a detailed completion schedule. Partial submittals will not be accepted without prior written approval. • Submittals shall be furnished in electronic formats. • A letter of transmittal identifying the name of the Project, Contractor's name, date submitted for review, shall accompany submittals and a list of items transmitted. • Submittals must be complete and accurate. All submittals shall be in a similar format for ease of review. • Product data required as part of the submittal shall include the following: • Equipment schedules listing all System components, manufacturer, model number and the quantity of each. • General functional descriptions for each System. • Manufacturer's data specification sheets for all System components, including any warranty information (sheets containing more than one device or component model number shall be clearly marked to delineate items included in the Work). • A complete list of cable and wiring types, sizes, manufacturer, and model number. • A complete list of finishes and sample graphics, including custom artwork and custom graphics (if applicable). • List of parts inventories to provide manufacturer recommended service and maintenance of the Work. • Shop Drawings shall include the following: • Floor plan drawings indicating device locations with device make/model legends and wire runs. • System riser diagram with all devices, wire runs, and wire designations. • Schematic block diagrams for each System showing all equipment, interconnects, data flow, etc. • Wiring diagrams for each subsystem defining the interconnection of all inputs and outputs for all equipment. • Labeling/Tag-ID Plan. • Plans and elevations of the IDF and MDF closets showing all equipment locations, power supply locations, conduit, wire ways, wire molds, and all other equipment as well as Rack elevations. • It is the responsibility of Contractor to confirm all dimensions, quantities, and the coordination of materials and products supplied by Contractor with other trades. Approval of shop drawings containing errors does not relieve Contractor from making corrections at their expense. 8. RECORD DOCUMENTATION • Provide record "as -built" drawings upon substantial completion, no hand marked -up drawings will be acceptable. Initial draft of As -Built drawings is due at least (3) weeks prior to the TCO. All record drawings must be completed using AutoCAD, Revit, or equal. Submit (3) hard copies and an electronic copy. • Provide test and certification reports for all copper and fiber cabling with a Fluke DTX/DSX, or pre -approved alternate tester. 9. MISCELLANEOUS NOTES • All LV closet locations shall have proper exhaust and cooling accommodation to ensure the room temperature never exceeds 75 degrees. • All LV closets shall have Emergency Power circuits for use of special systems (minimum of 2 x 20-amp circuits per closet). • All LV closets shall receive VCT flooring. • All LV closets shall have 3/4" fire treated plywood provided by the GC. • All network switching equipment to be furnished and installed by Owner. • LVC shall provide all data and fiber patch cords for a complete structured cabling system. • Contractors shall be responsible for their own fire stopping of penetrations that have such a requirement. 10. UNIT PRICING The LVC shall provide unit pricing on the following: • LG/Samsung Commercial Smart Display (49" 4K UHD LED TV) $ • LG/Samsung Commercial Smart Display (65" 4K UHD LED TV) $ • LG/Samsung Commercial Smart Display (75" 4K UHD LED TV) $ • Commercial monitors provided must be capable of displaying video in portrait mode. • Includes Rough -In Box, Wall -Mount Bracket, & Installation. • 1-Port Data Drop (Cable/Jacks/Terminations/Labor/Testing) $ • 2-Port Data Drop (Cable/Jacks/Terminations/Labor/Testing) $ • Data+Coax Drop (Cable/Jacks/Terminations/Labor/Testing) $ 11. REQUIRED BIDDERS A minimum of two bidders are required by Anthology Senior Living for each project. Anthology Senior Living preferred bidders are indicated below, by Region. If there are questions regarding regional coverage, please contact preferred bidders or M&R Design Services Group for clarification. • Premier Technology Systems, L.L.0 (East /Midwest/Mid-Atlantic) Thomas G. Laird, Jr. Vice President - Sales tlaird6EDDtswired.com 724-916-2222xl3 Office 724-916-0099 Fax 412-874-0803 Mobile • The Cable Guy (West/Southeast) Tony Rocco Partner tonvroccoaazcableauv.com 602.422.9240 1 Office 602-559.9551 Direct 949.275.0122 Cell 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, LINCOLNSHIRE, IL 60069 TEL: 847-634-1200 m & R DESIGN FAX: 847-634-1201 SERVICES GROUP. LLC WWW.MANDR—DSG.COM Q0 N 0 00 rn O Z z 0 = Q L U Cn zz LL 0 0 >0. 0 z 0 > J > J 0 _ O ti z w Z o cn Q � Q N U REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LOW VOLTAGE NARRATIVE GMP / PERMIT SET DATE 05.21.2021 1 • 12. RESPONSIBILITY MATRIX Electrical Low Voltage Systems LVC Companies Access Control Notes Contractor Contractor Technologies Integrator Structured Cabling Units F&I telecommunication outlets (Cat 6 X and RG6 coaxial cable) Complete all terminations X Studio Units - Furnish flush mounted X structural media box (UAP) Studio Units - Install flush mounted X Box shall be installed at entry closet if structural media box (UAP) possible. 60" AFF to top of box. F&I duplex outlet in designated All cabling to be labeled inside UAP portion structural media box (UAP) X and at patch panel locations in IDF/MDF closets w/ printed labels. F&I pathway and/or sleeves for cabling between corridors/dwelling X units and corridors/LV Closets and all boxes and trim rings for all LV outlets Common Area Locations F&I telecommunication outlets (Cat 6 X See narrative for more information and RG6 coaxial cable) and locations. Complete all terminations X Furnish rough -in box for X display/digital signage display Install rough -in box for display/digital Box to have (1) Cat 6 and (1) coax signage display X cable. Should be terminated on both ends. Rack shall have horizontal and F&I 4-post equipment rack X vertical cable management. Shall have ladder rack attached to wall F&I pathway and/or sleeves for cabling between corridors/dwelling X units and corridors/LV Closets and all boxes and trim rings for all LV outlets Closet Work F&I fiber between main Data Room X and each IDF closet Coordinate power outlet locations X Terminate fiber to panels X F&I data cabling between main Data X Cables shall be punched down to Room and each IDF closet patch panels F&I coaxial cabling between main X Cables shall be terminated onto a Data Room and each IDF closet modular patch panel F&I 2-post 42RU racks in each IDF Provide vertical and horizontal cable closet X management, as well as cable management (ladder rack/tray) If IDF's stack, provide (3) 4" sleeves F&I conduit from MDF to each IDF X between IDF Closets. Where closets Closet. do not stack there should be full conduit between floors F&I conduits from property line to X Exact location to be coordinated by MDF/Netpop GC F&I (1) APC SMT1500RM2UC UPS, (1) F&I (see notes) in each data closet X APC AP9631, and (1) APC AP9335TH, per data closet Wi-Fi Wireless Access Points (WAP's) F&I all rough -in rings, tile brackets (if X In unit data for WAP to be at 84" needed), cabling, jacks, and boxes n F&I patch cords per access point X F&I separate vertical single gang ring X Install owner provided wireless X Wireless access points are furnished access point by Netrix F&I pathway and/or sleeves for cabling between corridors/dwelling X units and corridors/LV Closets and all boxes and trim rings for all LV outlets Emergency Call System F&I all pull cords X F&I all repeaters, head end X equipment and terminations F&I rough in back box for wireless X pull cords F&I surface mounted door contacts. X F&I power and rough in box for each X Box is not necessary if repeater is repeater located in IDF closets. F&I pathway and/or sleeves for cabling between corridors/dwelling X units and corridors/LV Closets and all boxes and trim rings for all LV outlets Video Surveillance F&I all cameras, monitors, cables, power, licensing, head end X equipment and terminations F&I Telecommunications outlet (Cat X Outlet to be PoE 6) for each camera F&I pathway and/or sleeves for cabling between corridors/dwelling X units and corridors/LV Closets and all boxes and trim rings for all LV outlets LOW VOLTAGE NARRATIVE v5.0 Access Control F&I card readers, power supplies, access control panels/enclosures, X Electronic Hardware to be provided head end and terminations for the S2 by Others. Solution F&I access control composite cable X from reader back to power supply Install individual cables at the door to X each respective device F&I recessed door contacts on all X exterior doors Stairwell Doors. Complete all terminations X Assist w/ connections for door hardware X F&I addressable relay from fire alarm system to each access control power X supply F&I conduit, rough in boxes and hard -wired connections at all X common area access control doors Intercom F&I intercom substations and master X stations. F&I telecommunications cabling (Cat X 6) to each intercom location. F&I conduit and rough in boxes at all X intercom locations. Audio -Visual F&I entire audio-visual system, to include cabling, for all common area X rooms and spaces F&I power and rough in box as X required for AV system Submittals & Shop Drawings Provide submittal and shop drawings X X X X as described within narrative. Record Documentation Provide record documents as X X X X described within narrative. Miscellaneous All low voltage closets shall have Emergency Power circuits for use of X special systems (minimum of 2 x 20-amp circuits per closet). Provide all data and fiber patch cords for a complete structured cabling X system. Provide fire stopping of penetrations X X X X that have such a requirement. 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, LINCOLNSHIRE, IL 60069 TEL: 847-634-1200 DESIGN FAX: 847-634-1201 WWW.MANDR-DSG.COM CD N O 00 M O 0 � Z Z O= >Q LU cn 0 LL Z O0 0 0 CD O N > J M J O _ O ti Z F_ O W Z N U) Q nl U REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LOW VOLTAGE NARRATIVE GMP / PERMIT SET DATE 05.21.2021 7 8 9 1 II C10 4CAM II120 10 12 13 MC-1 110: JII ui LEll IVI - 1 i I - H I -a r a 120" C-10 J — — — — — — — — — — — — — — — — — — —PARKING — — — — — — — — J I I I I GARAGE I 1039 I I I I I I I I I I I I I I I I I I I I I MECHANIC 1 2 I I I I I 1032 1 i i a a a a GENERATOR - I 1031 — I I I I I I I I I I I EXTERIOR 0 —I 1 2 3 4 5 6 7 8 9 UO 12 13 LEVEL 1 TECHNOLOGY FLOOR PLAN SCALE: 1/8" = V-0" .1.1 ��T01 10 k 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, A� LINCOLNSHIRE, IL 60069 I IrIT TEL: 847-634-1200 M & R DESIGN FAX: 847-634-1201 SERVICES GROUP, LLC WWW.MANDR—DSG.COM CV O 00 0) co z 0 11-- Z z O� Q W cn LL z O0 0 z O >> J m J O_ _ O ti z w Z N U) Q n1 U REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 01 FLOOR PLAN GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER T1 01 1 2 3 4 5 PC L- WAP 1 p 84" 1 AT 18 v " 1 CATV p� 18" 1 2 3 4 LEVEL 2 TECHNOLOGY FLOOR PLAN SCALE: 1/8" = 1'-0" 6 i 7 8 9 10 12 13 5 6 7 8 9 UO 12 13 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, A� LINCOLNSHIRE, IL 60069 I �IT TEL: 847-634-1200 M & R DESIGN FAX: 847-634-1201 S E? V I C E S G R O U P L L C WWW.MANDR-DSG.COM N O 00 m 0 0 � Z z O= Q Lu u6 0 LL z O 0 >. 0 z O >> J m J O _ O ti z C:)w U) Z Q N U REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 02 FLOOR PLAN GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER Tl 02 C 1 2 3 4 5 6 7 8 9 10 12 13 Kill -L 7RE F� . rrrm.-. ii 0. 1 FP MCA 1 1 84" 18" CATV IL-B5 314 I I I L 00 DW F -1 ■ UAP L L -1 L- -1 L�! R_E_F I - F WAP C�-CATV VL 84" 18" u 1 CA 18" AIL-B1 1312 0 UAP IF IL C2 II 3 6 CATV - 1-� - Pc I I - O O REF O O 00 R F •o a� PC PC O O PC r EF. 1661 ee I O O EF. 00 F F_ -1L I J _ I L I I C I ° I �, L �� L r I— L � L L-1 L -1UAP o L -1-1°� J -1 o DW ■ UAP ° �0 D UAP DW ■� UAP DW ■,. L_ L - 7LLL Pc IL B5 IL-B2 IL—B6 �IE Q 330 332 n 1 1 CATVB � I O O I O WAP >CA L84" 18' 1 11 1 CATV 1 CATV 01 1 1 CATV 1 >CATV 18, 18" ATVQ WAP CANS WAP 818' 84" 18" 18" 84" 84" PC Lj PC PC PC PC PC 1 :-11 WAP _ �.■_ r • CATV tk " I\WAP - T , I�� LE r J ■i� I ■ -.:� III. I�� I ww�. -�I ■ 1� �.S:yI11L w-i. �■� �.S:RED � CORRIDOR- I 1 1 _ CATVQ WAP CATV 8"- _ - 1 18" IL-C 306 L IL J J DW O'n UAP F_ _ L- J L J L J I J EF. O O 0o 1 18" CATV 1W I a m I\ ..I o N iY� v 1 1 I • � � I■ ICI I "� J � L J � J■ � L J UAP DW 0] UAP DW ■W E. 9 �I I fi IL-136 IL-136 J 336 338 CATV 1 CATV 1 1 1 18" CATV-4 WAP 18" C TVQ WAP 18" 84" 18" 84" PC PC PC C: 00 REF. 00 L L J � UAP pW 0�] IL-B6 � I J 340 CATV 18" CATV-4 WAP 18" 84" 1 2 3 4 5 6 7 8 9 10 12 13 LEVEL 3 TECHNOLOGY FLOOR PLAN SCALE: 1/8" = 11-0" 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, �� LINCOLNSHIRE, IL 60069 T E L: 847-634-1200 M & R DESIGN FAX: 847-634-1201 -'VICES ?VICES GROUP, LLC WWW.MANDR-DSG.COM Q0 N 0 00 o o Z z O � Q LU C 0 LL z Oz o z O N > J > J O _ � o ti z F_ o W z o cn Q � Q N 0 REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 03 FLOOR PLAN GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER T1 03 Q- 1 2 3 4 5 6 7 8 9 10 12 13 � h 1 11 -1 r T% 1 2 3 4 5 LEVEL 4 TECHNOLOGY FLOOR PLAN SCALE: 1/8" = 1'-0" 6 7 8 9 UO 12 13 GENERAL NOTES: 1. COORDINATE IN UNIT WAP DATA LOCATION WITH TV/DATA OUTLET. 2. COORDINATE ALL IN UNIT ANCHORS WITH TV/DATA OUTLET. 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, A� LINCOLNSHIRE, IL 60069 I �IT TEL: 847-634-1200 M & R DESIGN FAX: 847-634-1201 S E? V I C E S G R O U P L L C WWW.MANDR-DSG.COM N O 00 m 0 0 � Z z O= Q Lu u6 0 LL z O 0 >. 0 z O >> J m J O _ O ti z C:)w U) Z Q N U REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 04 FLOOR PLAN GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER Tl 04 2 3 4 I I I � I °OO r 17 OO 1 J C TV 1 L� 18"— 1 t WAP 1 p 84" CATV AT 18�r L UAP 1 � CATV 18" � F �I I r I �1 J 171 PC ( PC L C PC � PC L LJ J ° CATV UAP 1 18" 5 - CATvJ IL-131 1AP,r 4 520 i � F 7 PC ��v DWOO PC PC - PC I 52 F WAP 12 5 1 p 84" L CATV EF. 1 18" ■ PC � PC L-1 L L J 5 � 18" CATV 1 A 84" I L-B 1 WAP 1 524 PCFL O° DWOO -- 00 1 IPCI 1 1 H - - - - S —5 PC PC K — — T TV — 00 00 PC PC 00 PC 00 0 0 REF 526 O O R F I r EF. O O EF. C �o L L J J L L -1■ UAP ■ L � L J ■ L � L —1 UAP ° (° D UAP DW O J UAP DW O �■ DWI L L IL-�5 L— J Pc 5 8 I IL-B6 � '771 7771 —1 1X18" O ®30 O CO7' WAP >CATV CATV 84" 18' 1 1 1 1 1 CATV CATV 1 1 CATV 1 1� LWAP 1 CA 18�� 18" ATVQ WAP 18" CATV WAP or 8418" -- -- 18'. 84" ^^ 18' 84" ^^ 5 6 PC — 1 —CAN WAP pCA 84" 18" 1 CATV 18" DW C�0 � J - LL J J F� 0 LL JJ F-I o� ° L I REF UAP PC PC 7 8 9 10 12 13 I I W WAP ATV •, • , • •, • , • I■ I I • / • III _ • I , � Y I ■ i ,I ,q7 � I I F -1 Lam' y-1 L Ili1 �i4OYil� �. —,.�_ �i4:K{:i� —„� � .�1� !•11.: lsf w4alYJlUill CORRIDOR IF L 1 2 3 4 5 6 LEVEL 5 TECHNOLOGY FLOOR PLAN SCALE: 1/8" = 11-0" 1 1. 1 3 440 PC D ®F7 lPCFl PC I ° CATV 1 18 PC 00° r 00LeF CD Ito504PCF-J WAP 1 p 84" 3 4 7- J CATV F_ ,1 18" 1 18" UAP CATV � — — F 5 1 RAH 50 Pc I Q � PC O PC - I 71 L Jr4l � G ° J -- T CATV UAP 1 18" 6 �1 18" IL-B3 CATVJ L — —11 A 84" w502 WAP � J � O DW S -5 - - - - K ;, 00 pC 00 pC 00 pC 00 EF. O O EF. 0 0 EF. O O EF. 0 0 L J ■ L J L -1■ L -1UAP DW ° E UAP DW 0 ] J UAP L DW � ] L UAP DW EV I IL-B6 IL- 6 IL-136 540 J 53 J 536 J I O 10 I O 1 1 1 CATV p �1� 1 CATV 1 1� CATV 1 1� CATV 1 1� 18" Q CATVQ W P 18" CATV-4 WAP 18" Q C TV-4 WAP 18" CATV-4 WAP 18" 84" 18" 84" 18" 84" 18" 84" PC PC PC PC PC PC I I I I I I 7 8 9 10 12 13 GENERAL NOTES: 1. COORDINATE IN UNIT WAP DATA LOCATION WITH TV/DATA OUTLET. 2. COORDINATE ALL IN UNIT ANCHORS WITH TV/DATA OUTLET. 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, LINCOLNSHIREI IL 60069 T E L: 847-634-1200 M & R DESIGN FAX: 847-634-1201 -'VICES ?VICES GROUP, LLC WWW.MANDR-DSG.COM Q0 N O 00 0-) O Zz 0 = Q W v6 0 LL z O z �W Z 0 N > J > J 0 - O ti Z W Z o (n Q N U REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 05 FLOOR PLAN GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER Tl 05 (D- 1 2 3 4 5 6 7 8 9 10 12 13 PC PC 00 t PC PC coo O F_ 1--]00 1 PC 1 1 PC 1 WAP SCAT 1 1 60" LL TV CAN 1 1- 84" 18" CATV - -1 1 CATVWAP �ro-C WAP >CATV D 1 WAP I*CATV - PC - - - - - - - - - - - B 84" 18" , I PC Ra° 1R" EXTERIOR DECK_ 1 2 3 4 LEVEL 6 TECHNOLOGY FLOOR PLAN SCALE: 1 /8" = 1 I-0" GENERAL NOTES: 1. COORDINATE IN UNIT WAP DATA LOCATION WITH TV/DATA OUTLET. 2. COORDINATE ALL IN UNIT ANCHORS WITH TV/DATA OUTLET. SHEET NOTES: 1. 8 LANDSCAPE SPEAKERS AND SUBWOOFER LOCATIONS TO BE COORDINATED IN FIELD WITH FINAL LANDSCAPE DESIGN. 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, �� LINCOLNSHIRE, IL 60069 TEL: 847-634-1200 M & R DESIGN FAX: 847-634-1201 S E? V I C E S G R O U P L L C WWW.MANDR-DSG.COM Q0 N O 00 0-) O Zz O= Q Lu v6 0 LL z O0 >w. C) z O > J > J O- _ O ti z w Z o cn Q � Q N 0 REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 06 FLOOR PLAN GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER T1 06 T T 5 6 7 8 9 GARAGE EXTERIOR C 1 2 3 4 5 6 7 8 9 LEVEL 1 TECHNOLOGY REFLECTED CEILING PLAN SCALE: 1/8" = 1'-0" 10 12 i 13 GENERATOR 1031 _ L 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 © ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, A� LINCOLNSHIRE, IL 60069 I �IT TEL: 847-634-1200 M & R DESIGN FAX: 847-634-1201 S E? V I C E S G R O U P L L C WWW.MANDR-DSG.COM N O 00 m 0 0 � Z z O= >Q Lu (6 0 LL z O0 >. 0 z O > J m J O _ o ti z F- C:) w Z C:) U) Q N U REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 01 RCP GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER T201 C Q_ - 1 2 3 4 1 2 3 4 LEVEL 2 TECHNOLOGY REFLECTED CEILING PLAN SCALE: 1 /8" = 1'-0" 6 T7 8 9 10 5 12 13 u 5 6 7 8 9 10 12 13 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, �� LINCOLNSHIRE, IL 60069 TEL: 847-634-1200 M & R DESIGN FAX: 847-634-1201 SE?V IC ES GROU P, LL C. WWW.MANDR-DSG.COM Q0 N O 00 0-) 0 Z z O � Q Lu v6 0 LL z Oz >w. C) z O > J > J O- _ 0 ti z w Z o cn N U Q Q REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 02 RCP GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER T202 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, �� LINCOLNSHIRE, IL 60069 TEL: 847-634-1200 M & R DESIGN FAX: 847-634-1201 S E? V I C E S G R O U P L L C WWW.MANDR-DSG.COM Q0 N O 00 O-) O Zz 0 >Q W Cn 0 LL z 0 z C) z_ 0 N > J > J o ti z w Z o Cn N U Q Q REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 03 RCP GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER T203 C Q_ 1 2 3 4 5 6 7 8 9 10 12 13 1 2 3 4 5 6 7 8 9 UO 12 13 LEVEL 4 TECHNOLOGY REFLECTED CEILING PLAN SCALE: 1/8" = 1'-0" 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, �� LINCOLNSHIRE, IL 60069 TEL: 847-634-1200 M & R DESIGN FAX: 847-634-1201 S E? V I C E S G R O U P L L C WWW.MANDR-DSG.COM Q0 N O 00 0-) 0 Zz O = � a Lu v6 0 LL z Oz >w. C) z O > J > J 0 _ 0 ti z w Z o cn Q � Q N 0 REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 04 RCP GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER T204 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, �� LINCOLNSHIRE, IL 60069 TEL: 847-634-1200 M & R DESIGN FAX: 847-634-1201 S E? V I C E S G R O U P L L C WWW.MANDR-DSG.COM Q0 N O 00 O-) O Zz 0 >Q W Cn 0 LL z 0 z C) z_ 0 N > J > J o ti z w Z o Cn Q Q N U REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 05 RCP GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER T205 C 1 2 3 4 5 6 7 8 9 10 12 13 IL, C - 6�14 I CAM WAP p p 11 1 2 I I IL�-B1 =624 I I I TA1R 01 ST1— EZ T I RPT I I I K — — — 13751 — �, . 0 ❑ I I I -C2 LJ 26 IL B5, IL—B2 ILA$61:;e',, ' .R,; IL-B6 I L - - I I I I I I I I M -�- 4 - �- - - - 1 2 3 4 5 6 7 8 LEVEL 6 TECHNOLOGY REFLECTED CEILING PLAN SCALE: 1 /8" = 1 I-0" FA PT 13 Ll ❑ 4 u 1 O� QD I L—B6 640 7-7 38 NORTHWEST DAVIS, SUITE 300 PORTLAND, OR 97209 503.245.7100 1505 5TH AVE, SUITE 300 SEATTLE, WA 98101 206.576.1600 1014 HOWARD STREET SAN FRANCISCO, CA 94103 415.252.7063 ©ANKROM MOISAN ARCHITECTS, INC. 515 BOND ST, �� LINCOLNSHIRE, IL 60069 TEL: 847-634-1200 M & R DESIGN FAX: 847-634-1201 S E? V I C E S G R O U P L L C WWW.MANDR-DSG.COM Q0 N 0 00 0-) O Zz O= 2 Q Lu o LL z Oz Lu z O N > J > J 0 _ 4 O ti z w Z� U) av-- N U REVISION DATE REASON FOR ISSUE 04 08/20/21 OWNER REVISION #01 RESUB Dec 28 2021 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT BLD2021-0088 LEVEL 06 RCP GMP / PERMIT SET DATE 05.21.2021 SHEET NUMBER T206