Loading...
Fire Alarm Information Guide - City of Edmonds Fire Marshal Office 07.10.24City of Edmonds Fire Marshal's Office FIRE ALARM INFORMATION GUIDE PURPOSE This document provides fire alarm designers, installers, plan reviewers, inspectors, and building owners with important information regarding fire alarm installation requirements within the city of Edmonds. It is intended to provide consistency between all parties during plan design, submittal, review, installation, inspection and testing of new and existing fire sprinkler systems. SCOPE The information contained within this document details some of the Edmonds Community and Development Code (ECDC) amendments to the International Fire Code. It may also contain some of the provisions found in the International Fire Code, NFPA Standards, Washington Administrative Code, and the Revised Code of Washington. Nothing in this document shall prevent the fire code official from modifying these requirements as necessary, based on circumstances, to provide an acceptable level of protection. This document is a summary of requirements found in various codes, standards, and laws. It is not a complete list of permit or code requirements and should not be used as a substitute for applicable laws and regulations. It is the responsibility of the design and installation professional to ensure all codes, laws and regulations are followed. DESIGN AND INSTALLATION 1. Where an existing building or suite provided with a fire alarm system, fire detection system, or supervised sprinkler system undergoes an alteration, repair, modification, change of use or occupancy, or where a fire alarm control panel is installed, replaced or upgraded, all fire alarm initiation and notification devices located within the entire building shall be required to meet both the currently adopted IFC and NFPA 72 National Fire Alarm and Signaling Code unless otherwise approved by the fire code official. (ECDC 19.25.035 D) 2. When a building is required to be equipped with a fire alarm system, the system shall provide protection throughout the structure or as approved by the fire code official. (ECDC 19.25.035 D) SOUTH COUNTY FIRE 12425 Meridian Avenue South, Everett, WA 98208 (425) 551-1264 I Prevention@SouthSnoFire.org SERVING THE CITIES OF • BRIER • EDMONDS • LYNNWOOD • MILL CREEK • MOUNTLAKE TERRACE 3. All construction documents shall be reviewed by a NICET III, an ESA/NTS Certified Fire Alarm Designer (CFAD) Level III Fire in fire alarms, or a licensed professional engineer (PE) in Washington prior to being submitted for permitting. The reviewing professional shall submit a stamped, signed, and dated letter; or a verification method approved by the local authority having jurisdiction indicating the system has been reviewed and meets or exceeds the design requirements of the state of Washington and the local jurisdiction (effective July 1, 2018). (2021 IFC 907.11.2) 4. All inspection, testing, maintenance, and programing not defined as "electrical construction trade" by chapter 19.28 RCW shall be completed by a NICET II or ESA/NTS Certified Fire Alarm Technician (CFAT) Level II Fire in fire alarms (effective July 1, 2018). (2021 IFC 907.8.4.1) 5. The installation, upgrade, or replacement of an existing fire alarm control panel (FACP) shall require that all fire alarm system components meet both the currently adopted IFC and NFPA 72 National Fire Alarm and Signaling Code. Exception: FACP replacement of the same make and model as the existing panel. (ECDC 19.25.035 D) 6. Systems and their components shall be listed and approved for the purpose for which they are installed. All new alarm systems shall be addressable, and each device shall have its own address and shall annunciate individual addresses to an approved central station. All new FACPs shall be installed in the fire riser room and have signage stating "Fire Alarm" or "Fire Alarm Control Panel" affixed to the outside of the door. Signs shall be red, with two-inch white letters. (ECDC 19.25.35 D) 7. All means of communication between the FACP, and the central station shall be of a method approved by the fire code official and be provided with a minimum of 24 hours' standby power. Only components that are serviceable by a fire alarm technician shall be part of the means of communication located on the protected premises. The fire code official shall maintain a list of approved communication means. (EDCD 19.25.035 D) 8. Detection shall be provided in all R1 and R2 occupancy buildings with common hallways and at the top of stairways unless otherwise approved by the fire code official. (ECDC 19.25.035) 9. FACPs shall be provided with an approved Knox key box for access. (2021 IFC 506.1) 10. Duct smoke detectors shall be connected to the FACP and report as a supervisory signal. (ECDC 19.25.035 D) City of Edmonds Fire Marshal's Office — Fire Alarm Information Guide Page 2 of 3 11.At least one audio/visual notification device shall be installed on the exterior of the building facing fire department arrival. One visual notification device shall be required to be located at the exterior entrance to a fire alarm control panel room as approved by the fire code official. (ECDC 19.25.035) 12.Testing Maintenance. Service providers hired by the building owner are responsible for electronically submitting completed annual confidence test reports of fire alarm systems, sprinkler systems, fire pumps, suppression systems, and standpipes to the appropriate fire prevention offices' online reporting system within 14 days of the completed inspection. (ECDC 19.25.035 D) Created 07-10-2024 City of Edmonds Fire Marshal's Office — Fire Alarm Information Guide Page 3 of 3