RESUB 1-FIR2024-0086+Fire_Alarm_Equipment_Specification_Sheets+11.4.2024_10.43.46_AM+4599638
FIR2024-0086 RESUB Nov 04 2024 DEPARTMENT STERLINC.r COMMUNICATION TECHNOLOCIIES, INC.. Sterling Communication Technologies, Inc. Submittal TCN Edmonds Systems: Div. 28 FIRE ALARM SYSTEM August 5t", 2024 Submitted by: Joe Stevenson Sterling Communication Technologies, Inc. 18540 Apache Drive, Unit 100 Parker CO 80134 www.stercommtech.com (DPOTTER The Symbol of Protection Features • 10 Amp Power Supply • 3 Amps, regulated per NAC • 6 NACs Class B or 3 NACs Class A • 2 dry contact inputs • Fully programmable and monitored through control panel • Isolated P-Link repeater connection, Class A or B • Up to 31 power supplies per control panel with system wide sync • Quadrasync feature synchronizes strobes from AMSECO, Gentex, Cooper -Wheelock and System Sensor. Description The PSN-1000 series is a UL listed intelligent 10 amp notification power supply and P-Link (RS-485) repeater. The power supply connects to the P-Link bus from the control panel and is operated and supervised from the panel. The power supply may be installed 6,500 feet from the control panel. The PSN-1000 then repeats the P-Link communication for another 6,500 feet. The power supply has six (6) Class B or three (3) Class A power outputs. Each output is regulated and power limited with a 3 Amp maximum rating. In addition, the PSN-1000 has two (2) programmable dry contact inputs. The dry contact inputs are Class B, supervised inputs. The power supply operates on either 120 or 220 VAC power and has a regulated 24 VDC output. In addition, the panel can charge up to 55 AH batteries and will house 18 AH batteries. The cabinet is constructed out of 18 gauge cold rolled steel with a durable red powder coat finish. A standard Potter key lock is provided for securing the door. Electrical conduit knockouts are provided on the sides and top providing installers with multiple options for installing conduits and providing proper power separations. The PSN-1000 is a self contained intelligent power supply/P-Link repeater complete with cabinet. The PSN-1000E is the intelligent power supply/P-Link repeater with additional cabinet roomfor mounting stacker bracket modules including PAD 100-SLCE loop expanders. Both cabinets include space for 18 AH batteries. PSN-1000(E) Power Expander FM U` APPROVED 7165-0328:0195 S2930 Technical Specifications Size (H x W x D) PSN-1000: 16 3/4"x 161/8" x 3 1/2" PSN-1000 E: 26" x 17.6" x 3.75" Enclosure Sixteen (16) gauge sheet steel with hinged, locked doors 120 VAC at 50 HZ Power Input 240 VAC at 60 HZ 5.1 Amps/3.0 Amps max draw Current Standby 60 mA Alarm 200 mA Temperature 32' to 120°F, humidity 93% non -condensing IPA Series, AFC/ARC Series, PFC-4064, Compatible Panles P Series*, PFC-6000 Adressable Series* * Legacy Product The power supplies are programmed and controlled through the main control panel P-Link bus. The panel displays any troubles or off normal conditions of the power supply and the events are stored in the panel history buffer. Each output can be independently configured to provide one of four synchronization patterns, Amseco®, Gentex®, Cooper Wheelock® and System Sensor®. The ouputs can be also configured for constant power, resettable power, sounder base power, door holder power (with or without a low AC drop out), ANSI temporal Code 3, City Tie or be a releasing circuit for 24vdc solenoids. Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830032 - REV E • 04/20 PAGE 1 OF 2 (E)POTTER The Symbol of Protection PSN-1000(E) Intelligent Power Supply 0 n V 0 o U 0 El o 0 o O 0 • 6 Class B / 3 Class A NAC Circuits • 2 Input Monitoring Points (IDC) • P-Link Circuit Repeater 0 0 PSN-1000(E) Power Expander Potter Fire Alarm Control Panel Ordering Information Model Description Stock No. PSN-1000 Power Expander Standard Cabinet 3992662 PSN-1000(E) Power Expander Large Cabinet 3992665 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830032 - REV E • 04/20 PAGE 2 OF 2 (E)POTTER h The Symbol of Protection Features • Low profile, less than 2 inches with the base • Wide selectable sensitivity range of 1.1 to 3.5%/foot • Detector communicates sensitivity to control panel • UL listed smoke calibration and sensitivity • Optional locking tab to prevent unwanted removal • Simple DIP switch address setting, no programming tool required • Magnetic test switch • LED alarm indicator • Product includes 5-year warranty • UUKL Listed for Smoke Control • UL268 7th edition compliant Description The Photoelectric Smoke Detector is a listed Analog Addressable smoke detector compatible with fire alarm control panels that utilize the Potter Addressable Device (PAD) protocol. The PAD300-PD is a low profile smoke detector with a wide sensitivity range. The detector and base are made of a durable plastic in an off-white color to blend in with the ceiling. The PAD300-PD has a sensitivity range of 1.1 to 3.5 % per foot and is UL listed. The PAD300-PD features drift compensation and has built in dirty detector warning as well. The PAD300-PD and the control panel communicate over a proven and robust digital communication path and the system analyzes the information at the particular device. The total polling speed is less than five (5) seconds, well under the UL requirements. The detector is compatible with any of the PAD300 series detector bases and simply twists on. The PAD300-PD is addressed using DIP switches in the rear of the detector and can be easily programmed in the field without special tools. Setting the Address Each addressable device on the SLC loop must have a unique address from 1 to 127 to function properly. The address is set using DIP switches. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to SLC or device. Verify the following: 1. Power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. PAD300-PD Photoelectric Smoke Detector 0 0328-0541 Technical Specifications Operating Voltage 24 VDC Detector Current Draw 300 µA Alarm Indicator 1 LED Alarm Set -point Range 1.1 to 3.5%/ft (3.6 to 11%/m) Installation Temperature Range 32 to 120 ° F (0 to 49 ° C) Operating Relative Humidity 0% to 93% (Non -condensing) range Start-up Time Max. 1 sec. Maximum Number of Addresses 127 Per Loop Maximum Number of Lighted 30 Indicators in Alarm Per Loop Color Eggshell White Weight (without base) 9 1 g (3.2oz) Dimensions (without base) Height: 1.42 in (36mm) Diameter: 3.93 in (100 mm) Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830216 - REV B • 2/23 PAGE 1 OF 2 (E)POTTER The Symbol of Protection PAD300-PD Photoelectric Smoke Detector Air Velocity Ratings The PAD300-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute. The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD300-PD will operate even though the LED may not illuminate. Operation The PAD300-PD is an analog addressable detector that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel. The unit communicates with the control panel as it is polled. The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is in an active status. The polling LED can be turned off if desired for less conspicuous operation. The PAD300-PD with the PAD300-4DB or PAD300-6DB has a low profile of less than two (2) inches to blend into the surrounding environment. The detector includes an insect screen to prevent foreign objects from reaching the chamber and can be cleaned to restore operation of a dirty detector. Detector Sensitivity The PAD300-PD and the compatible control panel work in tandem to keep the sensitivity consistent. As the detector is installed over time, the detector compensates for the dirt in the unit until it is out of range. At that time, the panel will indicate a dirty detector. The detector will then have to be cleaned or replaced. The PAD300-PD can be programmed to provide a maintenance alert prior to reaching the dirty detector level which will allow for intervention prior to the detector going into trouble. This allows for detector replacement or cleaning prior to a nuisance trouble occurs. NOTE. As required by NFPA, do not install the detectors until all construction is complete and the work area has been thoroughly cleaned. If the detectors have been installed in a construction environment, they should be cleaned or replaced before the system is placed into service. Spacing The PAD300-PD is UL listed with a recommended maximum spacing of 30 feet. Refer to NFPA 72 for specific information regarding detector spacing, placement and special applications. Compatible Bases All bases will mount on a single gang, 3-1/2" octagon, 3-1/2" square, double gang, 4" octagon, 4" square, 50mm c/c, 60mm c/c and 70mm c/c boxes. Device Description Stock No. PAD300-4DB 4" Detector Base 3992781 PAD300-6DB 6" Detector Base 3992782 PAD300-IB 6" base with an isolator module included 3992783 PAD300-RB 6" base with one Form-C relay contact. 2A @ 30VDC, 0.5A @ 125VAC 13992784 PAD300-SB 6' base with sounder module included. Sound pattern is provided from external source 3992785 PAD300-LFSB 6" base with 520Hz sounder module included. Sound pattern is provided from external source 3992786 Ordering Information Model Description I Stock No. PAD300-PD Photoelectric Smoke Detector 13992775 Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com 8830216- REV B • 2/23 PAGE 2 OF 2 O,�� SYSTEM � SENSOR- L-Series and L-Series with LED Indoor Selectable Horns, Strobes and Horn Strobes System Sensor L-Series and L-Series with LED audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features • LED technology provides lower current draw • Digital Voltage Meter (DVM) diagnostic test points for Horn Strobes and Strobes • Common aesthetics across the L-Series platform • Standard and compact sizes • Tamper -resistant construction • Field -selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 • Field -selectable candela settings on ceiling units: 15, 30, 75, 95, 115, 150, and 177 • Rotary switches for candela, tone and volume selections • Mounting plate provides plug-in design for easier installation and shorting springs to check wiring continuity • Electrically compatible with legacy SpectrAlert, SpectrAlert Advance and L-series devices • Synchronization through use of UL approved power supplies that support System Sensor Sync protocol or System Sensor MDL3 Sync Module • Horns, Strobes and Horn Strobes listed for wall or ceiling use Agency Listings SIGNALING SIGNALING C �� US U� ULC FM a LISTED LISTED LISTED APPROVED Horn Strobes Horns: Horns: 3057072 7300-1653:0525 and Strobes: 54011 54011 FM23FPUS0195 7135-1653:0503 S5512, 54011 7135-16530526 The System Sensor L-Series and L-Series with LED platform offers the most versatile and easy -to -use line of horns, strobes, and horn strobes in the industry with lower current draw and modern aesthetics. LED lighting technology offers significantly lower current draw compared to older Xenon bulbs across a full candela range. This improves design flexibility for notification appliance circuits (NACs) while also reducing power supply requirements allowing for simpler and lower cost installations. Flexible design options meet virtually any application requirement: wall or ceiling mount, standard or compact sizes, red or white color choices, bezel kits for alternate markings and languages, and LED color lenses for distinctive visual signaling. In addition, installers can easily adapt devices using field selectable candela, tone and volume settings using rotary switches. The L-Series and L-Series with LED line is developed to simplify installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. The universal mounting plate includes an onboard shorting spring, so installers can test wiring continuity before the device is installed. In addition, the System Sensor L-Series with LED notification appliances offer a new diagnostic test point feature that allows you to measure device voltage with a digital voltage meter (DVM) without removing the appliance from the wall or ceiling. The DVM test points are discreetly located on the face of the notification appliance which enable faster troubleshooting and end of line (EOL) voltage checks while greatly reducing the risk of misplacing or damaging appliances during troubleshooting. AVDS916-01 • 10/03/2023 • Page 1 L-Series and L-Series with LED Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non -condensing Strobe Flash Rate 1 flash per second Nominal Voltage, LED Strobes and Horn Strobes Regulated 24 VDC Nominal Voltage, Horns Regulated 12 VDC or regulated 24 DC/FWR Operating Voltage Range, LED Strobes and Horn Strobes 16 to 33 V (24 V nominal) Operating Voltage Range, Horns 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG UUULC Current Draw Data, Horn Tones, and Sound Output Data Candela 16-33 Volts Rating Wall Ceiling Candela 15 18 18 Range 30 22 22 75 70 70 95 75 75 110 85 — 115 — 90 135 105 — 150 — 110 177 — 115 185 120 — 8-17.5 Volts 16-33 Volts Sound Pattern dB DC DC FWR Temporal High 39 44 54 Temporal Low 28 32 54 Non -Temporal High 43 47 54 Non -Temporal Low 29 32 54 3.1 KHz Temporal High 39 41 54 3.1 KHz Temporal Low 29 32 54 3.1 KHz Non -Temporal High 42 43 54 3.1 KHz Non -Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 Maximum Horn StrobeUUULC • .: Current Draw (mA RMS), Horn Strobe, Candela Range (15-185 cd) Sound Output (dBA) Switch Pos. Sound Pattern Volume Setting 15cd 30cd 75cd 95cd 16-33 Volts 110cd 115cd WALL CEILING 135cd WALL 150cd CEILING 177cd CEILING 185cd WALL 16-33V DC 1 Temporal High 35 38 87 92 94 120 189 189 190 190 87 2 Temporal Low 35 38 87 92 94 120 135 135 145 145 79 3 Non -Temporal High 50 52 87 92 94 120 127 127 135 135 87 4 Non -Temporal Low 35 38 87 92 94 120 125 125 130 130 79 5 3.1 KHz Temporal 3 High 35 38 87 89 91 115 155 155 165 165 86 6 3.1 KHz Temporal 3 Low 35 38 87 89 91 115 128 130 135 135 80 7 3.1 KHz Non -Temporal High 40 42 87 89 91 115 125 125 135 135 86 8 3.1 KHz Non -Temporal Low 35 38 87 89 91 115 120 120 130 130 80 AVDS916-01 • 10/03/2023 • Page 2 L-Series with LED Dimensions: Wall -Mounted Equipment 2.07 - 3.46" (53 mm) 1' 68 mm 00®00°0o (-316 00o0o00p0o00000 I oo00100°0°0 00°000°00527" 0 mm) 0 0 133.9 mm 19 ° 0 A0617-00 Compact Strobe, Horn Strobe for Wall A0613-00 Strobes, Horn Strobes for Walls 3.46" 88 mm 23.571.55" 32 mm (9.1 CM) (3.9 em) �O o 001010000000 UP + 0°0°0°0°0°0° °o°o°o°o°o°o° 5.38" 5.27^ o0000000ap000 (13.7 cm) O 133.9 mm°0°0°0°0°0°0 0p°o°o0o0Q0o0 O A0547-00 A0557-00 Compact Horn Compact Surface Mount Back Box for Walls (SBBGRL, SBBGWL) Horn 1.25.1 4.82" 32 mm (12.24 cm) (4.69 69 cm) 4 oDp ® o 58" O (14.68 cm) U�® ® r A0549-00 A0554-01 Surface Mount Back Box for Walls (SBBRUSBBWL) L-Series with LED Dimensions: Ceilina-Mounted Eauipment 6.83" diam. (173.5 mm) A0608-00 Strobes and Horn Strobes for Ceilings 6.92" A— (175. 2.5' (64 mm) O A0546-00 Surface Mount Back Box for Ceilings (SBBCRL, SBCWL) AVDS916-01 • 10/03/2023 • Page 3 L-Series with LED: Ordering Information L-Series with LED Horn Strobes LED Lenses P2RLED 2-Wire, Horn Strobe, Wall, Red LENS-A3 Lens LED Amber Wall/Ceiling P2RLED-B 2-Wire, Horn Strobe, Wall, Red, Bilingual LENS-B3 Lens LED Blue Wall/Ceiling P2WLED 2-Wire, Horn Strobe, Wall, White LENS-G3 Lens LED Green Wall/Ceiling P2WLED-B 2-Wire, Horn Strobe, Wall, White, Bilingual LENS-R3 Lens LED Red Wall/Ceiling P2GRLED 2-Wire, Compact Horn Strobe, Wall, Red Accessories P2GRLED-B 2-Wire, Compact Horn Strobe, Wall, Red, Bilingual TR-2 Universal Wall Trim Ring Red P2GWLED 2-Wire, Compact Horn Strobe, Wall, White TR-2W Universal Wall Trim Ring White P2GWLED-B 2-Wire, Compact Horn Strobe, Wall, White, SBBWL Wall Surface Mount Back Box, Red Bilingual SBBWL Wall Surface Mount Back Box, White P2RLED-P 2-Wire, Horn Strobe, Wall, Red, Plain SBBGRL Compact Wall Surface Mount Back Box, Red P2WLED-P 2-Wire, Horn Strobe, Wall, White, Plain SBBGWL Compact Wall Surface Mount Back Box, White P2RLED-SP 2-Wire, Horn Strobe, Wall, Red, FUEGO TRC-2 Universal Ceiling Trim Ring, Red P2WLED-SP 2-Wire, Horn Strobe, Wall, White, FUEGO TRC-2W Universal Ceiling Trim Ring, White PC2RLED 2-Wire, Horn Strobe, Ceiling, Red SBBCRL Ceiling Surface Mount Back Box, Red PC2RLED-B 2-Wire, Horn Strobe, Ceiling, Red, Bilingual SBBCWL Ceiling Surface Mount Back Box, White PC2WLED 2-Wire, Horn Strobe, Ceiling, White Bezelst PC2WLED-B 2-Wire, Horn Strobe, Ceiling, White, Bilingual BZR Wall Red Bezel Kit L-Series with LED Strobes BZW Wall White Bezel Kit SRLED Strobe, Wall, Red BZGR Compact Wall Red Bezel Kit SRLED-B Strobe, Wall, Red, Bilingual BZGW Compact Wall White Bezel Kit SWLED Strobe, Wall, White BZRC Horn Strobe Ceiling Red Bezel Kit SWLED-B Strobe, Wall, White, Bilingual BZWC Horn Strobe Ceiling White Bezel Kit SGRLED Strobe, Compact, Wall, Red SGRLED-B Strobe, Compact, Wall, Red, Bilingual Notes for L-Series With LED Horn Strobes and Strobes: SGWLED Strobe, Compact, Wall, White All -P models have a plain housing (no "FIRE" marking on cover). All -SP models have "FUEGO" marking on cover. SGWLED-B Strobe, Compact, Wall, White, Bilingual All -ALERT models have "ALERT' marking on cover. SRLED-P Strobe, Wall, Red, Plain All -B models have "FIRE/FEU" marking on cover for use in Canadian SWLED-P Strobe, Wall, White, Plain applications. SRLED-SP Strobe, Wall, Red, FUEGO Amber lenses are not for use in Canadian applications SWLED-CLR- Strobe, Wall, White, ALERT Notes for L-Series Horns: ALERT 'Horn -only models are listed for wall or ceiling use. SWLED-ALERT Strobe, Wall, White, ALERT, Amber Lens SCRLED Strobe, Ceiling, Red Notes for Bezels: SCRLED-B Strobe, Ceiling, Red, Bilingual tEach bezel pack ships in a package of 5. Add one of the following extensions for print/language options: -F (FIRE), -AL SCRLED-P Strobe, Ceiling, White, Plain (ALERT), -EV (EVAC), -AG (AGENT), -P (Plain), -FR (FEU), -PG (FOGO), -SP SCWLED Strobe, Ceiling, White (FUEGO), -SPE (FUEGO/FIRE). SCWLED-B Strobe, Ceiling, White, Bilingual SCWLED-P Strobe, Ceiling, White, Plain SCWLED-CLR- Strobe, Ceiling, White, ALERT ALERT L-Series Horns HRL" Horn, Red HRLA" Horn, Red, Plain, ULC HWL" Horn, White HWLA" Horn, White, Plain, ULC HGRL" Compact Horn, Red HGRLA* Compact Horn, Red, Plain, ULC HGWL" Compact Horn, White HGWLA' Compact Horn, White, Plain, ULC 3825 Ohio Avenue • St. Charles, IL 60174 USA System Sensor® is a registered trademark Phone: 800-SENSOR2 • Fax: 630-377-6495 of Honeywell international, Inc. www.systemsensor.com SYSTEM 3333 Unity Drive, Mississauga, ON L5L 3S6 Canada ©2023System Sensor. Phone: 800-SENSOR2 • Fax: 905 812 0771 Product specifications subject to change without notice visit systemsensoccom or current product information, including the latest version of this data sheet. SENSOR® www.systemsensor.ca nvoss,s-o, • 10/0/03/2023