APPROVED BLD BLD2024-1451+Mechanical_Plan+11.4.2024_11.41.03_AM+4599916v 04 N OD N N DESCRIPTION OF OPERATIONS BELOW IS A REVISED DESCRIPTION OF OPERATIONS FOR THE EXISTING 6-PIPE HEAT RECOVERY CHILLER SYSTEM IN THE LEVEL 3 MECHANICAL PENTHOUSE AT SWEDISH EDMONDS. ALL SYSTEMS AND EQUIPMENT ARE EXISTING. HYDRONIC PIPING AND PIPING ACCESSORIES WILL BE ADDED OR ALTERED TO ACHIEVE THE FUNCTIONS DESCRIBED BELOW. REFER TO THE PIPING SYSTEM DETAILS 1-3 ON TF6.01 FOR VALVE, METER AND SENSOR NAMING CONVENTIONS. CHILLED WATER SYSTEM GENERAL DESCRIPTION: THE CHILLED WATER SYSTEM SUPPLIES CHILLED WATER TO THE HOSPITAL TO MEET THE MECHANICAL COOLING NEEDS. THE CHILLED WATER SYSTEM IS A VARIABLE PRIMARY FLOW SYSTEM. THE CHILLED WATER PUMPS (PUMPCHW001 - PUMPCHW004) ARE FURNISHED WITH VFDS TO MODULATE FLOW CAPACITY. THE COOLING NEEDS ARE MET BY THE THREE MODULAR CHILLERS (CHILR001 - CHILR003). OVERALL CHILLED WATER FLOW IS MEASURED DOWNSTREAM OF THE PUMPS AT FLOW METER FM-2. PUMPING LOGIC: VARIABLE PRIMARY FLOW LOGIC WILL BE IMPLEMENTED WHERE THE PUMPS MAINTAIN A REMOTE DP SETPOINT OF 10 PSID (ADJ) AT DP-4. THE MINIMUM FLOW BYPASS VALVE (CV-2) WILL MODULATE TO ENSURE A MINIMUM SYSTEM FLOW IS MAINTAINED BASED ON THE NUMBER OF ENABLED CHILLER MODULES (100 GPM PER MODULE). CHILLER FLOW: THE MINIMUM FLOW BYPASS VALVE (CV-2) AT THE END OF THE CHILLED WATER LOOP IN THE INTERSTITIAL SPACE ABOVE THE EMERGENCY DEPARTMENT WILL BE USED TO ENSURE MINIMUM SYSTEM FLOW IS MAINTAINED TO THE ACTIVE CHILLER MODULES. TO DO THIS A NEW PARALLEL DP SENSOR (DP-2) WILL NEED TO BE INSTALLED AND TIED INTO SIEMENS CONTROLS. THIS WILL BE PARALLEL TO THE CLIMACOOL FACTORY DP SENSOR ALREADY INSTALLED. WINTER OPERATION (OSA BELOW 50 DEG ADJ) A SINGLE CLIMACOOL MODULE WILL BE ENABLED (LEAD/LAG ROTATION BASED ON RUN HOURS AND OR OPERATOR PREFERENCE). THE MODULE WILL BE COMMANDED INTO COOLING MODE, WITH A CHILLED WATER SUPPLY TEMPERATURE SETPOINT OF 45 DEG F (ADJ). THE HEAT REJECTION TO MAINTAIN A SINGLE 40 TON COMPRESSOR WILL BE INITIATED AT AHUHRC BY MODULATING THE COOLING FLOW THROUGH THE EXHAUST AIR STREAM. THE COOLING FLOW THROUGH AHUHRC WILL MODULATE TO MAINTAIN A HEATING WATER SUPPLY TEMPERATURE OUT OF THE HEAT RECOVERY CHILLER AT 120 DEG F. IF THE LEAVING AIR TEMPERATURE FROM AHUHRC IS BELOW 55 DEG F (WITH STABLE CHW VALVE CONTROL) AND THE HEATING WATER SUPPLY TEMPERATURE OUT OF THE CHILLER IS BELOW 120 DEG F, THERE IS A NEED FOR ADDITIONAL COOLING LOAD. THAT WILL BE INITIATED BY UTILIZING THE HEAT FROM THE RETURN AIR STREAM IN AH0001. THE MIXED AIR TEMPERATURE SETPOINT FOR AH0001 WILL BE MODULATED TO MAINTAIN 120 DEG F LEAVING WATER TEMPERATURE AT TS-2. SUMMER OPERATION (OSA ABOVE 55 DEG ADJ, DEADBAND CONCEPT) FIRST STAGE: A SINGLE CLIMACOOL MODULE WILL BE ENABLED TO REJECT HEAT TO THE FLUID COOLER. THE AHUHRC HRC COIL WILL BE SET TO PROVIDE HEATING WATER TO THE EXHAUST AIR STREAM. A SECOND CHILLER MODULE WILL BE ENABLED IF THE CHILLED WATER SUPPLY TEMPERATURE IS 3 DEG F (ADJ) ABOVE THE SETPOINT (45 DEG F) FOR A DURATION OF 15 MINUTES (ADJ). SECOND STAGE: THE SECOND MODULE SHOULD BE SET TO REJECT HEAT TO THE FLUID COOLER LOOP WITH THE SIDE STREAM VALVES (CV-3 & CV-4) OPEN TO THE HEATING WATER LOOP (COOLING MODE). BOTH ACTIVE CHILLERS SHOULD RECEIVE THE SAME CHILLED WATER SUPPLY TEMPERATURE SETPOINT OF 45 DEG F. STAGING DOWN FROM 2 CHILLERS TO 1 CHILLER SHOULD BE BASED ON CAPACITY. EACH CHILLER MODULE HAS 2 COMPRESSORS AT 40 TONS PER MODULE. AS THE TOTAL COOLING LOAD DROPS BELOW 80 TONS (ADJ) FORA DURATION OF 15 MINUTES (ADJ) THE CHILLED WATER PLANT SHOULD STAGE DOWN TO 1 MODULE. SIMILARLY IF BOTH CHILLERS ARE OPERATING AT LESS THAN 50% OF THEIR FLA FOR A DURATION OF 15 MINUTES (ADJ) STAGING DOWN SHOULD OCCUR. HEATING WATER SYSTEM GENERAL DESCRIPTION: THE HEATING WATER SYSTEM UTILIZES LOW TEMPERATURE SUPPLY WATER OF 120°F FOR BUILDING HEAT. HEATING WATER SERVES THE HOSPITALS AIR HANDLING UNITS, TERMINAL UNITS, HYRDONIC UNIT HEATERS AND CABINET HEATERS. THE PRIMARY METHOD OF PRODUCING HEATING WATER IS VIA THE THREE HEAT RECOVERY CHILLER MODULES (CHILR001 - CHILR003). WHEN THESE CHILLERS CANNOT MEET THE HOSPITALS HEATING DEMAND, SUPPLMENTAL HEAT IS PROVIDED BY STEAM HEAT EXCHANGERS. OVERALL HEATING WATER FLOW IS MEASURED DOWNSTREAM OF THE PUMPS AND HEAT EXCHANGERS AT FLOW METER FM-3. PUMPING LOGIC: VARIABLE PRIMARY FLOW LOGIC WILL BE IMPLEMENTED WHERE THE PUMPS- (PUMPHW001 & PUMPHW002) MAINTAIN A REMOTE DP SETPOINT OF 10 PSID (ADJ) AT DP-5. THE MINIMUM FLOW BYPASS VALVE (CV-6) WILL MODULATE TO ENSURE A MINIMUM SYSTEM FLOW IS MAINTAINED IN HEAT RECOVERY MODE (YEAR ROUND). HEATING WATER SUPPLY TEMPERATURE CONTROL: THE FIRST STAGE OF HEATING IS BY THE HEAT RECOVERY CHILLERS. THE CONDENSER LOOP WILL BE CONTROLLED TO MAINTAIN A HIGHER FLOW RATE THAN THE HEATING LOOP AT ALL TIMES. THIS WILL ENSURE THE WARMEST WATER IS ALWAYS AVAILABLE TO THE HEATING COILS. IF TEMPERATURE SENSOR TS-9 IS AT THE 120 DEG F SETPOINT (WITH A DEADBAND) THEN VALVE CV-7 SHOULD BYPASS THE STEAM TO HOT WATER HEAT EXCHANGERS. IF TEMPERATURE SENSOR TS-9 IS BELOW 120 DEG F SETPOINT (WITH A DEADBAND) THEN VALVE CV-7 SHOULD CLOSE AND THE ENABLED HEAT EXCHANGER SHOULD MODULATE THE STEAM VALVE TO MAINTAIN THE LEAVING WATER SETPOINT OF 120 DEG F. CONDENSER WATER SYSTEM GENERAL DESCRIPTION: THE CONDENSER WATER SYSTEM INCLUDES A CLOSED CIRCUIT COOLING TOWER (CTWRO01), TWO CONDENSER WATER PUMPS (PUMPCTW001 & PUMPCTW002), AND CONDENSER WATER/ COOLING TOWER TREATMENT EQUIPMENT. THE FLUID COOLER FANS ARE EQUIPPED WITH VARIABLE FREQUENCY DRIVES ALLOWING FOR MODULATION TO MAINTAIN THE CONDENSER WATER TEMPERATURE SETPOINT. CONDENSER WATER TEMPERATURE & FLOW CONTROL: THE CONDENSER LOOP WILL BE USED YEAR ROUND IN COOLING MODE. ONE MODULE IS ALL THAT IS EXPECTED TO RUN IN WINTER OPERATION. DURING THE SUMMER MONTHS IF A SECOND MODULE IS ENABLED TO ENSURE THE CHILLED WATER SUPPLY TEMPERATURE SETPOINT IS MET, STAGING UP WILL BE PERFORMED BY THE CLIMACOOL MASTER CONTROLLER. THE CONDENSER WATER PUMPS (PUMPCTW001 & PUMPCTW002) WILL MAINTAIN 200 GPM (ADJ) WHEN ONE MODULE IS ACTIVE. WHEN TWO OR MORE MODULES ARE ACTIVE CONTROL TO 360 GPM (ADJ). THE FLUID COOLER BYPASS VALVE (CV-8) WILL BE USED AS THE PRIMARY PATH FOR REJECTING HEAT TO THE HEATING LOOP WHEN ONE MODULE IS ACTIVE. FIRST STAGE: DURING THE SUMMER OPERATING MODE, THE AHUHRC PICV WILL MODULATE THE HEATING FLOW TO MAINTAIN 120 DEG F LEAVING WATER TEMPERATURE. SECOND STAGE: FLUID COOLER BYPASS (CV-8) TO CLOSE. FLUID COOLER FANS TO MODULATE TO MAINTAIN 120 DEG F CONDENSER WATER TEMPERATURE LEAVING THE CHILLER AT TS-2. IF THE AHUHRC PICV IS FULLY OPEN AND THE CONDENSER LEAVING WATER TEMPERATURE (TS-2) EXCEEDS 120 DEG F, ADDITIONAL HEAT REJECTION IS AVAILABLE BY MODULATING THE CONDENSER LOOP BYPASS VALVE (CV-8) AND FLOWING THROUGH THE FLUID COOLER. IF THE FLUID COOLER BYPASS VALVE (CV-8) IS COMPLETELY CLOSED, AND THE LEAVING CONDENSER WATER TEMPERATURE (TS-2) EXCEEDS 120 DEG F ENABLE THE FLUID COOLER FAN AND MODULATE TO MAINTAIN 120 DEG F LEAVING WATER OUT OF THE CONDENSER LOOP FROM THE CLIMACOOL CHILLER AT TEMPERATURE SENSOR TS-2. FREEZE PROTECTION: AT OUTSIDE AIR TEMPERATURES BELOW 35 DEG F (ADJ) THE FLUID COOLER WILL NEED TO MAINTAIN A MINIMUM FLOW THROUGH THE FLUID COOLER (CTWR001) TO PREVENT FREEZING. MINIMUM FLOW TO BE INITIALLY SET AT 200 GPM (ADJ). BYPASS VALVE CV-8 IS CLOSED. NORMAL CONDITIONS CV-3 AND CV-4 CLOSED WITH CV-5 OPEN. IF CONDENSER ENTERING WATER TEMPERATURE (TS-1) IS BELOW 65 DEG F (ADJ). CV-3 AND CV-4 OPEN WITH CV-5 CLOSED. WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 37 DEG F (ADJ) FOR A PERIOD OF 15 MINUTES (ADJ) REVERT TO USING THE FLUID COOLER BYPASS VALVE (CV-8). THE BAS BYPASS VALVE LOGIC MUST ENSURE THIS MINIMUM FLOW IS MAINTAINED REGARDLESS OF TEMPERATURE LOGIC IMPLEMENTED. BAS ALARMING AND SAFETIES WILL BE USED TO ENSURE A MINIMUM FLOW RATE, AND ALSO A MINIMUM WATER TEMPERATURE (AT TEMPERATURE SENSOR TS-10) IS MAINTAINED. IF THE MINIMUM ENTERING WATER TEMPERATURE TO THE CHILLER DURING THIS FREEZE PROTECTION MODE IS OBSERVED, ALARMS SHOULD BE EMAILED TO FACILITY MAINTENANCE TO NOTIFY THEM THAT CHILLED WATER IS NOT AVAILABLE TO THEIR PROCESS COOLING. THE FLUID COOLER IS TO MAINTAIN THE ENTERING WATER TEMPERATURE TO THE CHILLER AT NO LOWER THAN 80 DEG F (ADJ) ALARM SHOULD BE SENT TO FACILITIES IF TEMPERATURE SENSOR TS-10 IS BELOW 50 DEG F (ADJ). EXHAUST FAN HEAT RECOVERY COIL (AHUHRC) GENERAL DESCRIPTION: DURING WINTER MONTHS THE EXHAUST FAN HEAT RECOVERY COIL WILL PROVIDE A FALSE LOAD TO THE EVAPORATOR SIDE OF THE CLIMACOOL CHILLERS. A PID LOOP AS SHOWN ON DETAIL 4 OF TF6.01 WILL MAINTAIN A LEAVING AIR TEMPERATURE SETPOINT OF 55 DEG F (ADJ). SIMILARLY IN THE SUMMER MONTHS (BASED ON OSA) HEATING WATER WILL BE MODULATED TO LOWER THE HEATING WATER SUPPLY TEMPERATURE TO MAINTAIN 120 DEG F OUT OF THE CHILLERS, WHICH WILL PROVIDE HEAT TO THE VAV BOXES, AND DOMESTIC WATER PRE -HEAT. DOMESTIC HOT WATER PREHEAT HEAT EXCHANGER (HEATXDW001) GENERAL DESCRIPTION: CONTROL THE PRE -HEAT TEMPERATURE TO 70 DEG F (ADJ) BY MODULATING THE HEATING WATER RETURN PRESSURE INDEPENDENT CONTROL VALVE AS SHOWN ON DETAIL 5 OF TF6.01. SYMBOL DESCRIPTION PIPING LEGEND ABBREVIATION SYMBOL DESCRIPTION ABBREVIATION IXj GATE VALVE GV ® SOLENOID VALVE SV �Q GLOBE VALVE GLV GAS COCK GC BALL VALVE - FULL PORTED BV TAT CIRCUIT SETTER VALVE CS PI'`I SILENT CHECK VALVE CV QO HORIZONTAL EXPANSION TANK HET ~O BUTTERFLY VALVE BFV O VERTICAL EXPANSION TANK VET BUTTERFLY VALVE W/ MEMORY STOP BFVM ® AIR SEPARATOR AIR SEP Kfkf\/\JN FLEXIBLE CONNECTION ® AIR PURGER AP ® SEDUCED PRESSURE BACKFLOW PREVENTER RPBP '1r❑ END SUCTION CENTRIFUGAL PUMP ES PUMP UNION UNION VERTICAL IN -LINE CENTRIFUGAL PUMP VI PUMP STRAINER STRN SUCTION DIFFUSER SUC DIFF �Ps PRESSURE RELIEF VALVE RV Q TEMERATURE GAUGE TG PRESSURE REDUCING VALVE PRV A COMPRESSED AIR PRESSURE / TEMPERATURE TAP P&T C CONDENSATE PIPING -T BULB WELL BW CHWS CHILLED WATER SUPPLY PIPING MANUALAIRVENT MAV - -CHWR- -CHILLED WATER RETURN PIPING Q AUTOMATIC AIR VENT AV CWS CONDENSER WATER SUPPPLY PIPING Q zZP$1 PRESSURE GAUGE PG - -CWR- - CONDENSER WATER RETURN PIPING �F=F THERMOMETER THERM G GAS PIPING 04, BALL VALVE W/ 3/4" HOSE ADAPTOR BV W/ HA L REFRIGERANT LIQUID LINE CONCENTRIC REDUCER CR S REFRIGERANT SUCTION LINE p ECCENTRIC REDUCER ER HWS HEATING WATER SUPPLY PIPING 0 TWO-WAY CONTROL VAVLE 2WAY - - - HWR - - - HEATING WATER RETURN PIPING f� ® THREE-WAY CONTROL VALVE 3WAY AIR SEPARATOR SCHEDULE UNIT NO. SYSTEM SERVED CHILLED WATER HEATING WATER CONDENSER WATER FLUID COOLER MFG & MODEL NO. SIZE AUTO AIR VENT DR (FT) B&G CSR 3" 1 B&G CSR 3" 1 B&G CSR 2" 1 SPIROTHERM VJR 3/4" N/A NOTES 1 1 2 1 ASPRT001 ASPRT002 ASPRT003 ASPRT004 NOTES: 1. EXISTING UNIT TO REMAIN. SCHEDULE PROVIDED BASED ON CONSTRUCTION DOCUMENTS DATED 06/10/14. 2. EXISTING UNIT TO BE RELOCATED. FLUID COOLER SCHEDULE UNIT COIL EAT FAN FAN SPRAY WT NO. MFG & MODEL NO. GPM DP FT EWT OF LWT OF DB °F WB OF CFM VOLT/PH HP PUMP HP LBS NOTES CTWR001 EVAPCO ATWB 9-7H8 360 5.8 114 94 88 69 29,520 460/3 7.5 2 15,990 1 NOTES: 1. EXISTING UNIT TO REMAIN. SCHEDULE PROVIDED BASED ON CONSTRUCTION DOCUMENTS DATED 06/10/14. UNIT L. SYSTEM SERVED MFR. & MODEL NO. PUMP SCHEDULPIE TYPE GPM DP FT IMP DIA IN HP RPM VOLT/PH WT LBS NOTES PUMPCHWO01 CHILLED WATER ARMSTRONG 43001VS VSC 300 45 5.39 5 2881 460/3 230 1 PUMPCHWO02 CHILLED WATER ARMSTRONG 43001VS VSC 300 45 5.39 5 2881 460/3 230 1 PUMPCHWO03 CHILLED WATER ARMSTRONG 43001VS VSC 600 60 6.19 15 2765 460/3 350 1 PUMPCHWO04 CHILLED WATER ARMSTRONG 43001VS VSC 600 60 6.19 15 2765 460/3 350 1 PUMPCTWO01 CONDENSER WATER ARMSTRONG 43001VS VSC 400 40 9.97 10 1800 460/3 527 1 PUMPCTWO02 CONDENSER WATER ARMSTRONG 43001VS VSC 400 40 9.97 10 1800 460/3 527 1 PUMPHWO01 HEATING WATER ARMSTRONG 43001VS VSC 200 60 9.48 7.5 1800 460/3 392 1 PUMPHW002 HEATING WATER ARMSTRONG 43001VS VSC 200 60 9.48 7.5 1800 460/3 392 1 NOTES: 1. EXISTING UNIT TO REMAIN. SCHEDULE PROVIDED BASED ON CONSTRUCTION DOCUMENTS DATED 06/10/14. UNIT AL NOM M CHILLED WATER HEAT RECOVERY CHILLER SCHEDULE HEATING WATER CONDENSER WATER WT NO. MFR. & MODEL NO. TONS DESIGN GPM MIN GPM DP FT EWT OF LWT OF DESIGN GPM DP FT LWT OF EWT OF DESIGN GPM MIN GPM DP FT LWT OF EWT OF NPLV VOLT/PH MCA LBS NOTES CHILHRO01 CLIMA COOL UCH-85AF 72 446 100 6 58 46 354 4 120 100 354 85 4 95 85 17.6 460/3 161.5 3,000 1,2 CHILHRO02 CLIMA COOL UCH-85AF 72 446 100 6 58 46 354 4 120 100 354 85 4 95 85 17.6 460/3 161.5 3,000 1,2 CHILHRO03 CLIMA COOL UCH-85AF 72 446 100 6 58 46 354 4 120 100 354 85 4 95 85 17.6 460/3 161.5 3,000 1,2 NOTES: 1. EXISTING UNIT TO REMAIN. SCHEDULE PROVIDED BASED ON CONSTRUCTION DOCUMENTS DATED 06/10/14. 2. DESIGN FLOW RATES ARE TOTAL SYSTEM FLOW WITH ALL THREE MODULES ACTIVE. MINIMUM FLOW RATES ARE BASED ON A SINGLE CHILLER MODULE. PRESSURE DROPS ARE FOR A SINGLE MODULE AT DESIGN FLOW ASSUMING ALL THREE MODULES ARE ACTIVE. ALL WORK SUBJECT TO FIELD INSPECTION FOR CODE COMPLIANCE APPROVED PLANS MUST BE ON JOB SITE PIPING GENERAL NOTES PIPING MATERIAL SCHEDULE PIPING SIZE MATERIAL JOINT 1/2"-2" COPPER TYPE L LEAD FREE SOLDER, PRESSED MECH JOINT HEATING HOT WATER 2-1/2" - 10" SCH 40 BLK STL, ASTM A53 A OR B GROOVED, FLANGED, BUTT WELDED 12"+ STD WT BLK STL, ASTM A53 A OR B GROOVED, FLANGED, BUTT WELDED 1/2"-2" COPPER TYPE L LEAD FREE SOLDER, PRESSED MECH JOINT CHILLED WATER 2-1/2" - 10" SCH 40 BLK STL, ASTM A53 A OR B GROOVED, FLANGED, BUTT WELDED 12"+ SCH 40 BLK STL, ASTM A53 A OR B GROOVED, FLANGED, BUTT WELDED 1/2"-2" COPPER TYPE L LEAD FREE SOLDER, PRESSED MECH JOINT CONDENSER WATER 2-1/2" - 10" SCH 40 BLK STL, ASTM A53 A OR B GROOVED, FLANGED, BUTT WELDED 12"+ STD WT BLK STL, ASTM A53 A OR B GROOVED, FLANGED, BUTT WELDED INDIRECT DRAIN 1/2" - 2-1/2" COPPER TYPE L LEAD FREE SOLDER, PRESSED MECH JOINT PIPING INSULATION SCHEDULE PIPING PIPE INSULATION INSULATION CONDUCTIVITY TYPE SIZE TYPE THICKNESS RANGE HEATING HOT WATER (105°-140°F) 1/2"-1-1/4" FIBERGLASS, ELASTOMERIC FOAM 1" 0.21 - 0.28 1-1/2"+ FIBERGLASS, ELASTOMERIC FOAM 1-1/2" 0.21 - 0.28 CHILLED WATER COOLING (40°-60°F) 1/2"-1-1/4" FIBERGLASS, ELASTOMERIC FOAM 1/2" 0.21 - 0.27 1-1/2"+ FIBERGLASS, ELASTOMERIC FOAM 1" 0.21 - 0.27 CONDENSER WATER (61°-104°F) ALL NOT REQUIRED CONDENSER WATER (40°-60°F) 1/2"-1-1/4" FIBERGLASS, ELASTOMERIC FOAM 1/2" 0.21 - 0.27 1-1/2"+ FIBERGLASS, ELASTOMERIC FOAM 1" 0.21 - 0.27 <1" FIBERGLASS, ELASTOMERIC FOAM 1/2" 0.20 - 0.26 CONDENSER WATER (<40°F) >1" AND <8" FIBERGLASS, ELASTOMERIC FOAM 1" 0.20 - 0.26 8" + FIBERGLASS, ELASTOMERIC FOAM 1-1/2" 0.20 - 0.26 1/2"-1-1/4" FIBERGLASS, ELASTOMERIC FOAM 1/2" 0.21 - 0.27 COIL CONDENSATE PIPING 1-1/2" + FIBERGLASS, ELASTOMERIC FOAM 1" 0.21 - 0.27 ALL PIPING INSULATION AND COVERINGS SHALL HAVE AN ASTM FLAME SPREAD RATING OF 25 OR LESS AND AN ASTM SMOKE DEVELOPED RATING OF 50 OR LESS. ELASTOMERIC INSULATIONS SHALL BE CLOSED CELL. ELASTOMERIC INSULATIONS WHICH MEET THESE RATINGS MAY BE USED AS A SUBSTITUTE FOR FIBERGLASS. PROVIDE A VAPOR BARRIER COVERING ON ALL CHILLED WATER PIPING AND COIL CONDENSATE PIPING INSULATION. PROVIDE A COVERING FOR ALL FIBERGLASS INSULATION WITHIN THE BUILDING. PROVIDE A VINYL JACKET FOR ALL INSULATION EXPOSED TO SIGHT WITHIN THE BUILDING EXCEPT MECHANICAL ROOMS. PROVIDE REMOVABLE LACED INSULATION PAD OVER ALL CONTROL VALVES, WHERE NOT LOCATED WITHIN A MECHANICAL ROOM. PROVIDE ALUMINUM JACKET ON ALL INSULATED PIPING OUTSIDE BUILDING. AT PIPE HANGERS PROVIDE RIGID INSULATION BETWEEN PIPE AND HANGER. 1. THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR EVERY OFFSET WHICH MAY BE REQUIRED. THE MECHANICAL CONTRACTOR IS TO COORDINATE WITH ALL OTHER TRADES AND IS TO VERIFY ALL CLEARANCES BEFORE COMMENCING WORK. 2. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE 2021 INTERNATIONAL BUILDING CODE (IBC), INTERNATIONAL MECHANICAL CODE (IMC), INTERNATIONAL ENERGY CODE (IEC) AND UNIFORM PLUMBING CODE (UPC) AS AMENDED BY THE STATE OF WASHINGTON AND LOCAL AUTHORITIES. 3. ALL PIPE SIZES NOTED ON DRAWINGS ARE MINIMUMS. 4. SLOPE ALL INDIRECT DRAINS AT 2% UNLESS OTHERWISE NOTED ON DRAWINGS. OBTAIN APPROVAL FROM THE CODE AUTHORITY BEFORE INSTALLING PIPING AT LESS THAN 2% (EVEN IF LESSER SLOPE IS INDICATED ON DRAWINGS). 5. HANGERS AND SUPPORTS FOR PIPING SHALL BE IN ACCORDANCE WITH THE 2021 IMC AND IBC AS AMENDED BY THE STATE OF WASHINGTON AND LOCAL AUTHORITIES. 6. PIPING PENETRATIONS OF FIRE RATED WALLS OR FLOORS SHALL BE SLEEVED AND FIRE STOPPED WITH LISTED MATERIALS SO AS TO MAINTAIN THE INTEGRITY AND RATING OF THE FLOOR OR WALL. 7. PROVIDE SHUT-OFF VALVES AT ALL EQUIPMENT CONNECTIONS. 8. PROVIDE UNION, GROOVED OR FLANGED CONNECTION AT EQUIPMENT FOR FUTURE REMOVAL AND SERVICING. 9. FOR CONDENSATE PIPING PROVIDE TRAPS WITH A MINIMUM SEAL 2" GREATER THAN THE FAN OPERATING STATIC PRESSURE AT ALL COOLING COIL CONNECTIONS. 10. PROVIDE MINIMUM 1"AIR BREAK FOR ALL CONDENSATE PIPE TERMINATIONS AT DRAINS. 11. PROVIDE DIELECTRIC CONNECTIONS BETWEEN DISSIMILAR METALS. LEGAL DESCRIPTION PARCEL NUMBER: 00580700002500 SOLNERS 5 ACRE TRACTS BLK 000 D-00 - N 1/2 OF TRS 27 & 28 & S 1/2 OF TRS 25 & 26 TGW TH PTN OF VAC 10TH ST SE (FORMERLY 216TH ST SW ADJ THRTO) & TGW TH PTN OF TR 29 SD PLAT LY WILY OF FDL - COM AT NWCOR SD TR 29 TH ELY ALG N BDY 42.12FT TO BEG OF LN HEREIN DESC TH SLY TAP 35.44FT FIR SW CR OF SD TR 29 AS MEAS ALG S BDY SD TR & TERM OF LN HEREIN DESC (PER CITY EDM BLA REC AF NO 199909155005) TITLE NAME COMPANY CONTACT LIST PHONE NUMBER EMAIL SENIOR PROJECT EXECUTIVE BREANNA LANGSTON MACDONALD MILLER 206-889-2792 BREANNA.LANGSTON@MACMILLER.COM PROJECT MANAGER MIRANDA ESPINELI MACDONALD MILLER 206-308-3411 MIRANDA.ESPINELI@MACMILLER.COM SMART BUILDINGS ANALYST JOSH DOERR MACDONALD MILLER 206-459-1801 JOSH.DOERR@MACMILLER.COM MECHANICAL DESIGN ENGINEER LUCAS OGILVIE MACDONALD MILLER 206-407-2662 LUCAS.OGILVIE@MACMILLER.COM ENGINEERING PRINCIPAL TODD BOVEY MACDONALD MILLER 206-379-1770 TODD.BOVEY@MACMILLER.COM HC PIPING SUPERINTENDENT JIM BERGAN MACDONALD MILLER 206-391-3614 JIM.BERGAN@MACMILLER.COM PIPING FOREMAN BRAD YOUNG MACDONALD MILLER 206-245-5725 BRAD.YOUNG@MACMILLER.COM SCOPE OF WORK THIS PROJECT INVOLVES HYDRONIC PIPING MODIFICATIONS AND CONTROLS UPGRADES TO THE EXISTING 6-PIPE HEAT RECOVERY CHILLER SYSTEM LOCATED ON THE THIRD FLOOR MECHANICAL ROOM. THE GOAL OF THIS PROJECT IS TO ALLOW THE EXISTING HEAT RECOVERY CHILLERS TO PROVIDE HEATING CAPACITY FOR THE HOSPITAL AND REDUCE RELIANCE ON STEAM. PIPING MODIFICATIONS, VALVES AND SENSOR ALTERATIONS PER DRAWINGS. DRAWING SHEET INDEX - FITTING NUMBER TITLE SCHEDULES - FITTING SITE PLAN PENTHOUSE MECHANICAL ROOM PARTIAL DEMO PLAN - FITTING PENTHOUSE MECHANICAL ROOM PARTIAL DEMO PLAN - FITTING DEMO RISERS & DIAGRAMS - FITTING PENTHOUSE MECHANICAL ROOM PARTIAL PLAN - FITTING PENTHOUSE MECHANICAL ROOM PARTIAL PLAN - FITTING RISERS & DIAGRAMS - FITTING DETAILS - FITTING TF0.01 TF0.01S DF2.03A DF2.0313 DF4.01 TF2.03A TF2.031B TF4.01 TM6.01 City Of Edmonds Building Department Work MECHANICAL, HYDRONIC PIPING Address 21601 76TH AVE W Owner : SWEDISH MED CNTR -------------- Approved Date 11/18/2024 Building Official � Eritl......................................................... BLD2024-1451 ..............................: Permit Number ne Ridge Park i i m F 201hh PI SW `; 3 s 3 3 5 m n a m "I St Sw Ch- ' lms216thSSW3exco 'a � b f x 9th St SW £ s f 220th St SW t < t25th PISW Sw Y w Coll"gt Pl- '� Middit S,.I 3 i 21CM St SW u _. < m 212th St SW ^ /212th St SW Seatlle 3 S Height -ISt nsw� a Ed-onds'Woodway a High School 215W St SW t a o a 9 4 y` 216th St SW 221"51 SW, 216th St SW SITE �5w -h Edm"nd, Hosoital+° 21Hh St SW s�f mth ct SK Qj" N MELOIIY Hill 220th St SW 220th St SW 220M St _ n v 222"d St SW s 22W St SW .� a 3 t222.dcfsw e 224th St SW " a JP 3 3 N UII�ITY MAP 11 /01 /2024 W H Q 66 Z O W > W LU H Q 0 Z O L > LU RECEIVED Nov 05 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT w rn VJ wQ CC) NQ>- I..L N� L.L w� Z Q wI v ) W 0 U' Z cJ0 (D 02 Z o v) 0 w � wz � J �� ou)>Q wo=� o w �o V) V) CV U0j V) ENGINEER: LAST REVISED: L OG I LV I E 11-01-2024 CHECKED BY: DATE PLOTTED: T BOVEY 11-01-2024 CAD: ISSUE DATE: M HAGBERG DRAWING NUMBER: D-3579-77243404-00 SHEET NUMBER: TFO.01 E z° la Friday, November 1, 2024 8:22:48 AM �. R Lit z C z i r f' a �I 1 • i L I qqq r .4 A w 1 `4V r � 45 r � 1 Li x, 93 ;8„ r� ROO C9, i s J:\7724\3404 - SMC Edmonds CBA Energy Upgrades\00\2 - Engineering\DWG\Shts\77243404TF0_01.dwg 1 J m o o m r z SMC EDMONDS CBA ENERGY UPGRADES — — — w Z = 00 O m p ° W - n SWEDISH EDMONDS - AMBULATORY CARE z A °m° m 21601 76TH AVE W o m p — — — — EDMONDS, WA98026 Duo — — — — r W\ MacDonald -Miller O p �zM 01 M Q r-Af �n SITE Pb-%iq z m � N — — — — — o ��a �o TY SOLUTION O O — — — — �$ 17930 Intl. Blvd. Suite 120, SeaTac, WA 98188 O o :(l z N C --Im D � � < N o Phone: 206-763-9400 www.macmiller.com O _1 < cf) m N m N m v o o REVISIONS: DATE REVISIONS: DATE ISO ISO ISSUED FOR PERMIT :'F w a FEC 2" FLUID COOLER BYPASS CV 2" BYPASS CV 3-WAY CWS/R MIXING CV 4" FLUID COOLER BYPASS 8" CWR 2" CWR DN TO HEATXDWO01 (TYP 2) 8" HHWS BELOW 8" HHWR 6" HHWR 8" HHWS/R CFF (BELOW) 3-WAY HHW MIXING CV ASPRT002 - 6" CHWR CFF (FUTURE PUMPS) �� I��ll l��ll ICI ICI ICI I nA VESTIBULE 0301.001 _�/I I\_ __/ — RAMP (1:20) p STAIR #1 0003.003 ml 2-1/2" CWS/R DN TO HEA RECOVERY COILS �lOw— TO EAT RECOVERY COILS li meld I I���mell `�J_ HtiWR DN • LEVEL 2 .,N• LEVEL 2, l - DN TO LEVEL 2 =1 8" CHWR MATCH LINE: 2.0313 MATCH LINE: 2.03A 8" CHWR (FUTURE) TAN KC H B001 C B A KEY NOTES 1. REMOVE AIR SEPARATOR ASPRT003 AND SAVE FOR RE -INSTALL. AIR SEPARATOR TO BE RE -INSTALLED WITH SIDE STREAM CONFIGURATION ON MAIN CONDENSER WATER RETURN LINE. 0 2E C o0 0 O U L O U U - E �E N _0_jW� O o� N O � O l) O 0 Q a I� co CD L)_ N C� D 0 L �a. �a 11 /01 /2024 I I I I I I I I Lu Q 0 66 z O w LU H Q z O LU RECEIVED Nov 05 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT z Q J O 75 W J coW � Q W Q � 0 ry QU pry n �O :5 Q O �J O ry rm J W Q z Q U W I z QU) Q m0 = F___ Uz U — C/)p W 0� w z o W 0- O W � U) C,0� o �— O Ov);Q p�LL Wpa� o UWtiz �o z_ W 2i W �� VJ VJ N LOU 0 v! ENGINEER: LAST REVISED: L OG I LV I E 11-01-2024 CHECKED BY: DATE PLOTTED: T BOVEY 11-01-2024 CAD: ISSUE DATE: M HAGBERG DRAWING NUMBER: D-3579-77243404-00 SHEET NUMBER: DF2.03A E 0 z T l0 KEY PLAN N 1/8" = V-0" n i i 'I i D C B A i i n q i 0 M 7 N ;H LINE: 2.0313 ;H LINE: 2.03A a 0 CN N W 7 N O N N E N z u 4.8 XA SHEET NOTES 1. NO DEMO SCOPE IN THIS AREA. KEY PLAN 00 02 E c oo Uo � L O U U ' 6 E ( J w O o N o o l) rn 0 p > co CD U_ N L CDa. �a 11 /01 /2024 LU Q 0 66 z 0 CO Lu LU 0 z 0 LU RECEIVED Nov 05 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Z J O 75 W p W J � � Q W � pQ ry QU �O :5 Q O O ry L.L W73 Q Z Q U W I Z QU Q UZ U U)O W 2i (D p2 z p W OW U) N � �— O� p�>a Wpa� U~0 Wiz 2i z- W VJ VJ N LOU 0- W O LL Q W D �U) VJ ENGINEER: LAST REVISED: L OG I LV I E 11-01-2024 CHECKED BY: DATE PLOTTED: T BOVEY 11-01-2024 CAD: ISSUE DATE: M HAGBERG DRAWING NUMBER: D-3579-77243404-00 SHEET NUMBER: DF2.03B i1/8" = 1'-0" I= 1' 0" I 0 co 7 N N co N N E 0 ROOF I r� -L--- 1--iF V V IN ----nL----------- OUT -- BASIN o� PUMP 0 SWEEP -n OUT 2/" I ASPRT004 I NO ISOLATION VAEVING ON SIDESTREAM 3/4" PIPING AAV I I I 8" I 1" CT EVAPORATION MAKE-UP—/ I I 112„ - - - - - - I 2" DRAIN 8" Ll - - - - - c -- - 2 r I i ei \� I 2" PREVIOUSLY \� FCV ES BASIN HEATER LOCATION CTWR001] 4" NC I FCV ES y Y2 Y�_� FILCS001 10" STANDPIPE WITH AUX 4" WASTE CONN (2 TYP) CR AUX EXHAUST AIR HEAT RECOVERY COILS AO FM-1 m PREHEAT DHW, SEE M7.04 — SPOOL PIECE FOR FUTURE WATER^n rTrr) 2" NC FILL BY BALL V 1 %4" PR REDUCIf 25 PSI 1 %4" B A PREVEN CR AFTER HEAT REJECTION AAV i ASPRT003 �I I 2 „�\ PENTHOUSE POTABLE COLD WATER, SEE M7.04 3 „ AHUHRC o `1� J* TS NO TS-2 I I II II I I II II I I" - - - - -H - - - - -H - - - - - � ­4111- -CHWR- - - I II II I �I I 2" I I NC I I II II I �1 I II II I I II II I FACTORY BYPASS I MODULE 1 II MODULE 2 II MODULE 3 1 �I SHIPPED LOOSE I II II „ CONTROLLED 1 11 II 1 8 BY CHILLER I II II L-----JL-----JL--- --J 1 11 CHIEHR001 CHILHR002 CHILHR003 DOMESTIC HOT WATER PREHEAT HEATXDW001 MAX UPPER LIMIT IS 135°F CHEMICAL TREATMENT FEED CONTROL PANEL (TYP) CHEMICAL PART OF CHEMICAL TREATMENT RETURN FEED CONTROL INSTALLATION 2 GPM FS S 3/4" BLEED �i SOLENOID I PSI i 3/4„ PS I Y4„ 2„ PSI I I` 2" n ,� CT CR ISOLATION VALVE MECHANICAL PENTHOUSE, SEE M7.02, C DOMESTIC WATER PRODUCTION AND (F HEATERS FOR STEAM AND STEAM BUILDING NO 4" 2„ CT BYPE VALVE M�� FCV POS FCV CT CS I SOLATI C Pos VALVE, CR TOWER AO FILL VALVE VFD BACKWASH FUTURE 1" CT MAKE-UP ISOLATION VALVE, NO 10 CR AO CR 8" PULSE OUTPUT FOR DDC, 3/4" WATER METER FOR LEAK DETECTION ro /2" (TYP) I 0 WASTEL n NC 1, ICE„—IL7JJ L04 P_ V —1 F i 2" NP HWR NP CWR 0 PENTHOUSE NOTE: CR FILSND001 PUMPCTW001 PUMPCTW002 TANKCTE001 FUTURE SEE M4.03 FOR FUTURE FILTER SPACE. CS 10"0 STANDPIPE WATER TIGHT SEAL AT 2" CHW BYPASS CV 4" 3-WAY CHW MIXING CV �t(XXXX� I I r 8„ 6„ 4" FUTURE 6" CFF*** TS TS 4" CFF WITH 4" WASTE ALL ROOF PENTHOUSE PIPE CONN (2 TYP) AND DRAIN LOCATIONS 0 n 0 8" ------T----- ----- ---------�--CHWR--��� I I I I I I I 1 7 6 1 4 I I (CR (CR (A0 TA f� G VFD VFD (CR (CR (A0 CA0 T 0 0 VFD VFD Eta PF_^ I TI I /11 I�` PUMPCHW004 PUMPCHW003 PUMPCHW002 PUMPCHW001 (600 GPM) (600 GPM) (220 GPM) (220 GPM) 4" CFF AAV 3" I i FM-3 3" 6„ I a — 3 STEAM —�---------------STEAMZ 4„ FCV TS - - - - - - - - - - - - - - - - - - - - - - - -�1 - - - - -41. ASPRT001 120°F IS 9kMLQ I L- — i NORMAL HIGH j j I I i HEATSBH1 FCV �j J AAV 100°F IS NORMAL I I ��I� I 3 I " FCV I�� I 8 1 " I NP II I 1 ���I�--�� HEATSBH2 VL_jHWRI I I HEATING WATER 4" JASPRT0021 I c j SAFETY RELIEF No I TO FLOOR TANKCHB001 4 4 TYP /2" eNo I I I I DRAIN (2 TYP) TANKCHE001 N NC U c 11Li i I I TANKCHB002 TANKHWE001 2" PICV DPS ��� FCV PIV) ��— DIPS WEST END OF INTERSTITIAL SPACE WEST END OF INTERSTITIAL SPACE HUMIDIFIER AH0001 COOLING COILS AH0001 HEATING COILS AH0001 SEE M9.01 FOR ADDITIONAL INFORMATION CONDENSER, CHILLED AND HEATING WATER SYSTEM DIAGRAM -DEMO NOT TO SCALE 3"_ TS "Z BYPASS I I FUTURE -AI II 1 1 CR CR � L � � I L — I AO AO II 1 VFD VFD 1 1 T LI L L � 1 PENTHOUSE PUMPH FPUMPHWO0211 00 n, 00 E W C o0 O V/ � U O U U i �Z �E � _j 0 o� N CD� �o 0 cn m a Q '6 mo U_ N L CDa. �a 11 /01 /2024 I I I I w 0 66 � z 0 L w w i o z 0 > w � I I RECEIVED Nov 05 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT r^ Lij V) ry i W 0U � Q i ry i O i Q J i m C ` � G W i NE z Q �/ w V Q (� Q m 0 vz O06 (D` Q VJ 0 i Z w w O N � � 0 O 0co>LL —Q� w0= �o O � w Uwtiz �— o w u) U^^ U^^ � IE ENGINEER: LAST REVISED: L OG I LV I E 11-01-2024 NE .11 CHECKED BY: DATE PLOTTED: T BOVEY 11-01-2024 CAD: ISSUE DATE: M HAGBERG DRAWING NUMBER: D-3579-77243404-00 i SHEET NUMBER: DF4.01 :'F 13I ` J TO LEVEL 2 1• X76l - DN TO LEVEL 2 =1 C(::B A ;H LINE: 2.0313 ;H LINE: � .03A HWR 2 co 00 E ^L U. m o _W z Q �_ m 5 E G � N - � C O N 0 OL> r c/) M O Q > I0 coO C.)=" _0 u o= Ia 11 /01 /2024 w Q 0 &j z O Ln w w H Q &5 z O Ln w RECEIVED Nov 05 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT z J n W J C� � Q W Q � 0 ry QU Or Q O �J O � (D rm J W75 Q z Q U W I z Q cn Q 00 0 _ Uz U U)O W 2i (D 02 z 0 W OW � U) N � O� 0U>Q W �a� � U W ~� r-z 2 z— ��� vJ ( VJCVcW W 0— W O LL 0 W D �U) V ) ENGINEER: LAST REVISED: L OGILVIE 11-01-2024 CHECKED BY: DATE PLOTTED: T BOVEY 11-01-2024 CAD: ISSUE DATE: M HAGBERG DRAWING NUMBER: D-3579-77243404-00 SHEET NUMBER: TF2.03A E z T l0 �i N KEY PLAN 1 1/8" = 1'-0" I (: D C B A 0 M 7 N a N cD N W 7 N O N N E N z u ,LL NEW TEMPERATURE SENSOR )) ON CONDENSER WATER SUPPLY NG FLUID COOLER. ;H LINE: 2.0313 ;H LINE: 2.03A 5 4.8 XA -(: 4 KEY PLAN 00 00 E O U Ale- 0 ' F (6 E -0 J O o N O � O l) O 0 mo U_ N L CDa. �a 11 /01 /2024 LU Q 0 66 z 0 U) LU z 0 LU RECEIVED Nov 05 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT W ry W Q pU Q� 0ry 0 �Q �� J (D L.L W73 Z Q W Q U) o� p UZ U)O p2 Zp Ow N p �Q< LU U LLJ �:'(.::)° VJ VJ N LOU ENGINEER: L OGILVIE CHECKED BY: T BOVEY CAD: M HAGBERG Z J n J Q ry Q n Lu O LL Q Lu D U) LAST REVISED: 11-01-2024 DATE PLOTTED: 11-01-2024 ISSUE DATE: DRAWING NUMBER: D-3579-77243404-00 SHEET NUMBER: TF2-03B i1/8" = 1'-0" I= 1' 0" I 0 co N I I , ROOF ------------ Li i V V IN ----nL-----------Jn OUT BASIN o PUMP TS-1 SWEEP n I ASPRT004 NO ISOLATION VALVING ON SIDESTREAM 3/4" PIPING AAV 4 I n 1 Y2„ MECHANICAL PENTHOUSE, SEE M7.02, DOMESTIC WATER PRODUCTION AND HEATERS FOR STEAM AND STEAM BUILDING 1" CT EVAPORATION MAKE-UP —/ CHEMICAL TREATMENT FEED CONTROL PANEL (TYP) CHEMICAL PART OF CHEMICAL TREATMENT RETURN FEED CONTROL INSTALLATION 2 GPM FS S I I 3/4" BLEED � i i SOLENOID C NO C 4"- CT CR ISOLATION VALVE FCV CV 2„ CT BYPA`. 130 ,� VALVE GPM` FCV POS FCv CT CS ISOLATIOI\ Pos VALVE, N FUTURE 1" CT MAKE-UP ISOLATION VALVE, NO 8" PULSE OUTPUT FOR DDC, 3/4" - WATER METER FOR LEAK DETECTION 2" NP HWR NP CWR O --- - - - - - - - PS - - - - - - - - - - 2„ DRAIN 8" 3/4„ I 13 „ OUT 2yTS I PS I /4 2 PS CR CR /2 (TYP) TOWER AO AO N0 2" PREVIOUSLY FCv ES FILL VALVE I BASIN HEATER NC 2P VFD VFD _ I LOCATION CTWR001 4" FCv ES BACKWASH WASTE NCB I J u PENTHOUSE 8" I I I I 4 I I PREHEAT DHW, _ SEE M7.04 AAV i I SPOOL PIECE TS 11 1 ASPRT003 FOR FUTURE WATER METER--,,""" I 6 TF6.01 2" NC INITIAL I a 2" FILL BYPASS BALL VALVE P 1 %4" PRESSURE REDUCING VALVE, N0 TF6.01 25 PSI NC NC 1 %4" BACKFLOW PREVENTER PENTHOUSE POTABLE COLD WATER, SEE M7.04 0° n Y2 FILCS001 NOTE: CR FILSND001 PUMPCTW001 PUMPCTWO02 TANKCTE001 FUTURE 10" STANDPIPE WITH AUX SEE M4.03 FOR CS 4" WASTE CONN (2 TYP) FUTURE FILTER SPACE. 10"0 STANDPIPE WATER TIGHT SEAL AT CR WITH 4" WASTE ALL ROOF PENTHOUSE PIPE AUX CONN (2 TYP) AND DRAIN LOCATIONS SEE DETAIL FOR CONTROL VALVE CONFIGURATION - - - - - - ---� 2------------ ---------- -----------------t r TS9-------- L_ - -r-� - ��1 1� — >— 1 Q I TS I -1AHUHRC I 0 ---� I n 1 TS-6 I E --- MODULATING CV I i TF6.01 i i I MAINTAINS 70°FATTS-11 I 1 TS-5- - - - - - - - - - - - - 0 I TS-3 I I LJ I_ - - - - - - - - - - - - - - - - - - - - I I-I---- - - - - - - - - - - - - - - - - - - - - - ----------------------1 FM-2 CHWR I I I DP-1 i 1 I -41 NEW CHW FLOW METER LOCATION iI I L-----------------------------------� 11 TS-2 I I 1 L----------------------------------------- � 1 i ---------------------------------------------� I I II II I „� I II II I 6 4 I II II DP-2 6" TS-1 I I I I I I F I --I _-- -fl _t � CHWR - - - (CR (CR � 1 I II II I (A0 I� �Ao T 0 2" I II II VFD VFD (CR (CR 1 1 I I CA0 (A0 °�1 I II II I I II II I FACTORY BYPASS I MODULE 1 II MODULE 2 II MODULE 3 SHIPPED LOOSE I II II CONTROLLED I II II 8" BY CHILLER I II II DOMESTIC HOT WATER PREHEAT HEATXDW001 CHILHR001 CHILHRO02 I CHILHR003 U AAV i I ASPRT001 TS I AAV i 8 8„ 6„ 4- 3" TS TS 4" FF Ej 1 PUMPCHW004 PUMPCHW003 (600 GPM) (600 GPM) 4" CFF 4„ FCV i HEATSBH1 3 FCV i NP I I I ���1 �' HEATSBH2 HWR Oz--���--- L_j II I I I I HEATING WATER 4" TS 3„ ASPRT002 I Imo♦ j SAFETY RELIEF TO NO /2 TANKCHB001 I I TYP " I I I DRAFNO(2 TYP) I TANKCHE001 I I I � N� NC 1 Ll 1~� I I I I HUMIDIFIER AH0001 COOLING COILS AH0001 HEATING COILS TANKCHB002 TANKHWE001 AH0001 SEE M9.01 FOR ADDITIONAL INFORMATION 3» STEAM - - - - - - - - - - ------------II-�1 1207 IS I I I NORMAL HIGH I I I II I I 1007 IS NORMAL -'� I I I I II �� II I I STEAM - FCV 3'° TS CR AO VFD 4'� �_Y BYPASS CR AO VFD PUMPH IPUMPHWO021 U VFD 1 I VFD 1 PUMPCHW002 PUMPCHW001 (220 GPM) (220 GPM) PENTHOUSE I I 11 /01 /2024 I I I I w Q 0 � z 0 w i w i o z 0 L > w RECEIVED Nov 05 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT W I i Q cn cn � op U p z Q � O ` Q(DG Q i Z p w O W oz i N oco) 0 ! O Q U) > Q U) F LL WQ= UUj �o W— w D C G O � CD O — � ' VJ VJ N �W LL �^ vJ ENGINEER: LAST REVISED: L OG I LV I E 11-01-2024 CHECKED BY: DATE PLOTTED: T BOVEY 11-01-2024 CAD: ISSUE DATE: M HAGBERG IE DRAWING NUMBER: D-3579-77243404-00 E SHEETNUMBFR: TF4.01 0 co 0 N E 0 WEST END OF INTERSTITIAL- SPACE FCV 2" PICV HIV) DPS 1 WEST END OF INTERSTITIAL SPACE CONDENSER, CHILLED AND HEATING WATER SYSTEM DIAGRAM NOT TO SCALE COPPER TUBE TO FLOOR DRAIN DI -ELECTRIC UNION AUTOMATIC AIR VENT PT PORT - AIR SEPARATOR CV-10 BUTTERFLY VALVE I I I I PT PORT BALL VALVE W/ 3/4" HOSE ADAPTER WATER FLOW TS-1 I (DP-1 TS-2 PUMPCTW002 PUMPCTW001 FM-1 BUTTERFLY VALVE MAIN LINE PIPE TO HHWR FROM HHWR W/MEMORY STOP COALESCING AIR SEPARATOR CONDENSER WATER SCHEMATIC SYSTEM DIAGRAM TF6.01 IN BY-PASS DETAIL TF6.01 (NEW CONDITIONS) N.T.S. N.T.S. P&T TAPS AT EACH CONN. (TYP.) MANUAL AIR VENT (TYP.) OUT TS-11 TEMP J SENSOR REDUCER (TYP.) IF REQUIRED 500-1500 DCW IN LLJ COLD OUT IN {�r-2 H H W IN HOUSEKEEPING PAD MODULATING PICV HHW OUT Qi \- 3/4" DRAIN (TYP.) BOLT EXCHANGER TO PAD AT EACH NOTE: BASE MOUNTING HOLE. PER PRVS TO BE RATED BELOW MAWP OF HX WITH STRUCTURAL REQUIREMENTS. CAPACITY OF 600 MBH OR MORE. PRV TO BE ASME RATED WITH AUTOMATIC RESET CAPABILITY. 5 PLATE/FRAME TF6.01 HEAT EXCHANGER DETAIL N.T.S. 2-WAY ISOLATION CV a" AUTO AIR VENT AT HIGH PT. (TYP 4) �' AA PIPE TO DRAIN HHWR HHWS CHWS CHWR a N 0 N O N PIPING REDUCER, TYP. %" BALL VALVE DRAIN W/ CAP u DRAIN THERMOMETER SHUT-OFF VALVE, TYP. P&T TAP, TYPICAL MANUAL AIR VENT ON HEADER TOP JPPER COIL LOWER COIL DRAIN PAN DRAIN PAN 3/" DRAIN FROM UPPER PAN TO LOWER PAN DEEP SEAL TRAP, DEPTH MIN 2x COOL AIR PRESSURE TS-9 TO CDWR CVV 3s FROM CDWR CV-4 TS-8 2 TF6.01 CV-1 CV-9 PUMPHWO02 PUMPHW001 TS-5 CHILRO01I CHILR0021 CHILRO03 TS-6 AHUHRC I 1 HEATXDWO01 I 1 AH0001 TS-7 CV-7 HEATSBH1 FLUID COOLER 4CV-8 I CTWRO01 BYPASS VALVE L2 VAVS nDP-5CV-61 MIN FLOW BYPASS HEATSBH2 HEATING WATER SCHEMATIC SYSTEM DIAGRAM (NEW CONDITIONS) N.T.S. CHILRO01 CHILRO02 CHILRO03 MIN FLOW BYPASS L00 00 E U. rn o Z Q m 5 O E G U U cc F— a) C O N /'R 0 cl O L> r W M O Q -> I0 coO C.)=" _0 u o= cr)a 11 /01 /2024 I I I I I w Q 0 z 0 W w w Q 0 z 0 Ln w RECEIVED Nov 05 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT W �� �//) V ry WQ 0 CU L.L ^V I..L O J (D� L.L W� z Q W I co 0 Uz U) O m W Z Ow co >N _ >< w Q � Q J� 0 Uw z � uw U) (n c v)� NW 0 ENGINEER: LAST REVISED: L OGILVIE 11-01-2024 CHECKED BY: DATE PLOTTED: T BOVEY 11-01-2024 CAD: ISSUE DATE: M HAGBERG DRAWING NUMBER: D-3579-77243404-00 SHEET NUMBER: TF6.01 AHUHRC COIL BANK CHILLED WATER SCHEMATIC SYSTEM DIAGRAM z TF6.01 W/ CHANGEOVER PIPING CONFIGURATION TF6.01 (NEW CONDITIONS) T N.T.S. N.T.S.