RESUB 2-FIR2024-0095+Applicant_Response+11.4.2024_7.44.54_AM+4598920Please see next page for range with back shelf coverage for a captive aire tank system. This is page 21 of the manual.
The coverage listed (shelf is less than 12", nozzle is 30-50" from cooking surface, nozzle spacing less than 36").
If you need any more assistance please call me 206-482-8858
Darin Wall
RESUB
Nov 04 2024
CITY OF EDMONDS
DEVE-MENTSE-CES
F I R2024-0095
Table 6 - Appliance with Back Shelf 4 nozzles per tank (20 flow points), 36" nozzle spacing
Hazard
Fuel Source
Maximum Depth of
Maximum Length of
Maximum Height
Cooking Surfaces
Cooking Surfaces
of Fuel
Less than 12" Back Shelf
Gas or Electric
30" deep
Unlimited
N/A
12" Back Shelf
Gas or Electric
30" deep
Unlimited
N/A
Shelves or protrusions from appliances measuring 6" or less are not considered shelves, standard
overlapping coverage applies. Refer to Table 3 on page 19.
Shelves or obstructions greater than 6" and up to 12" require 4 nozzles per tank, 36" nozzle spacing.
Shelves exactly at 12" depth require 35" distance from nozzle tip to cooking surface. Shelves less than
12" may use nozzle distance from cooking surface of 35" to 50", every effort should be taken to mini-
mize nozzle spray pattern obstruction with the shelf.
Figure 22 - Appliance with Back Shelf Options
15" 15"
Less than 12" 35" -' 50"
_Maximum
Overhang
Cooking Appliance
Hazard
Height
and
ght
RESUB
Nov 04 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
21