Loading...
FIR2024-0114+Fire_Alarm_Equipment_Specification_Sheets+11.19.2024_10.17.51_AM+4627097Date: 11/18/2024 RED HAWK )� FIRE PROTECTION Customer: SCOTT'S ELECTRIC 23811 STATE ROUTE 2 MONROE, WA 98272 Job #: 390049 System Type: FAS PORTABLE Project: WOODWAY CENTER HS PORTABLE 4 9521 240TH ST SW EDMONDS, WA 98020 Material List of Data Sheets Item Manufacture Model Description 1 Silent Knight SK-PHOTO Intelligent Photo Smoke Detector w/ Base 2 Silent Knight SK-PULL-DA Addressable Manual Pull Station - Dual Action 3 STI STI-1130 Manual Pull Station Stopper Cover w/ Horn - Surface Mount 4 Ditek DTK-2MHLP24FWB 24VDC Surge Suppressor; 2pr, 14-30VDC, 16-22awg 5 System Sensor P2WL Wall Horn w/ Strobe, Multi-cd (15, 30, 75, 95, 110,135 or 185cd) This page intentionally left blank Honeywell SILENT* KNIGHT SK-PHOTO, SK-PHOTO-T, and SK-PHOTOR Intelligent Photoelectric Smoke Detectors The SK-PHOTO is a photoelectric smoke detector, the SK PHOTO-T is a photoelectric smoke detectorwith thermal and SK-PHOTOR is a photoelectric detector with remote test capability. These plug in smoke detectors, with integral communication, provide features that surpass conventional detectors and are for use with the Honeywell Silent Knight series fire alarm control panels (FACPs). F SK-PHOTO and SK-PHOTO-T are plug-in type smoke sensors that combine a photoelectric sensing chamber with addressable analog communications. Point ID capability allows each detector's address to be set with rotary address switches, providing exact detector locations for selective maintenance when chamber contamination reaches unacceptable levels. SK-PHOTO and SK-PHOTO-T have a unique optical sensing chamber that is engineered to sense smoke produced by a wide range of combustion sources. In the SK-PHOTO-T, dual electronic thermistors add 1350F (57°C) thermal technology to maximize detection. The SK-PHOTOR is a remote test capable detector for use with the DNR/ DNRW duct smoke detector (not included). COMPATIBILITY SK-Photo, and SK-Photo-T are compatible with the following detector bases: B21OLP: 6" base (included) B501: 2 wire base B224RB: Relay base B224BI: Isolator base FEATURES & BENEFITS • Sleek, low -profile design • Base included • Reliable analog communications for trouble -free operation • Age resistant polymer housing • Dual electronic thermistor design on the SK-Photo-T • Superior EMI resistance for reliability • Simple field cleaning for code compliance • Variety of mounting options to meet any application • Dual LED indicators for 3600 visibility • Detector transmits signal to indicate maintenance is required • Optional remote LED annunciator (System Sensor' PN RA100Z) SK-PHOTO (BASE INCLUDED) • Plug-in mounting provides ease of installation • Tamper -proof feature available on mounting bases • Listed for use in duct applications • Rotary address switches for fast installation • UL Listed • FM Approved SK-PHOTO, SK-PHOTO-T and SK-PHOTOR Technical Specifications ar*a ac3«om ata~ a... PHYSICAL Height: 2.0" (5.0 cm) Diameter:4.1" (10.4 cm) installed in B501 base ELECTRICAL Operating Voltage:15-32VDC Standby Current: 300 µA C 24VDC Maximum Alarm Current: 6.5mA C 24VDC max (with LED on) ENVIRONMENTAL Operating Temperature SK-Photo: 32' —120OF (0°C — 49°C) SK-Photo-T. 320 —100°F (0°C — 38°C) Humidity: 10%— 93% non -condensing OTHER RATINGS SK-Photo-TThermal: Fixed temperature set point 1350F (570C) Velocity: 0 — 4000 fpm (0 — 20 m/sec) INSTALLATION The SK-PHOTO and SK-PHOTO-T plug into a compatible Silent Knight series detector bases. The SK-PHOTOR is a remote test capable detector head included within the DNR (W) duct smoke detector. ORDERING INFORMATION SK-PHOTO: Photoelectric smoke detector SK-PHOTO-T. Photoelectric smoke detectorwith thermal (135°F fixed temperture) SK-PHOTOR: Photoelectric detector with remote test capability For more information Learn more about Honeywell Silent Knight and other products by visiting www.sitentknight.com Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472 800-328-0103 ACCESSORIES RA10OZ: Remote LED annunciator XR2B: Detector removal tool. A removal and replacement tool for SK series plug-in detectors. Includes the T55-127-000 M02-04-01: Detector test magnet. M02-09-00: Test magnet with telescoping handle XP-4: Extension Pole for XR2B. Extends from 5 — 15 ft. T55-127-000: Detector Removal Head BCK-20OB: Black Detector Kit. For SK series detectors COMPATIBILITY The SK-PHOTO, SK-PHOTO-T and SK-PHOTOR are compatible with the following Honeywell Silent Knight fire alarm control panels: 6820: Addressable fire alarm control panel 6820EVS: Addressable fire alarm control panel with an emergency mass notification system. 6808: Addressable fire alarm control panel 6700: Addressable fire alarm control panel 5700: Addressable fire alarm control panel 5808: Addressable fire alarm control panel 5820XL: Addressable fire alarm control panel 5820XL-EVS: Addressable fire alarm control panel with an emergency mass notification system. Doc 350118 1 Rev G 111/17 9 2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit www.siLentknight.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Silent Knight°, System Sensor' and Honeywell® are registered trademarks of Honeywell International, Inc. This document is not intended to be used for installation purposes. We try to keep our product information up -to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, call800-446-6444. Honeywell SA.EW' XMGNr Honeywell SILENT* KNIGHT SK-PULL-SA / SK-PULL-DA Intelligent Pull Stations The SK-PULL-SA is a single action pull station requiring only one motion to activate the station. The SK-PULL-DA is a dual action pull station requiring two motions to active the station. The SK-PULL-SA and SK-PULL-DA are for use with Honeywell Silent Knight Series fire control panel (FACP). Extremely easy to operate, the SK-PULL-DA and SK-PULL-SA provide a fast and practical means of manually initiating a fire alarm signal. The FACP recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. INSTALLATION The SK-PULL-SA and SK-PULL-DA can be surface mounted to an SB-1/0 surface back box or semi -flush mounted on a standard single -gang with a minimum depth of 2.13"(5.40 cm) or double gang or 4" (10.61 cm) square electrical box. You can also use the optional (System Sensor' PN BG-TR) trim ring if the station is being semi -flush mounted. FEATURES & BENEFITS • Installer can open station without causing an alarm condition • Dual -color LED is visible through handle of station blinks green to indicate normal operation and remains steady red in an alarm condition • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP Locks • Meets ADA requirement for 5 lbs maximum pull force to active • Meets the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls and operating mechanisms guidelines (Section 4.1.3[131) • Shell, door, and handle molded from durable LEXAN' �_l:C 111 14 g'71`11IIIIIIIIIIIIIIIII r SK-PULL-DA • Reliable analog communications for trouble -free operation • Braille text on station handle • Rotary address switches for fast installation • Handle latches in down position and the word Activated appears, clearly indicating the station has been pulled • UL Listed, including UL 38, Standard of Manually Actuated Signaling System • CSFM Listed • M EA Listed SK-PULL-SA / SK-PULL-DA Technical Specifications For a complete listing of all compliance approvals and certifications, please visit PHYSICAL ORDERING INFORMATION www.siLentknight.com. Dimensions: 5.5" H x 4" W x 1.45" D (14 x 10.2 x SK-Pull-SA: Single Action Pull Station 3.7cm) SK-Pull-DA: Dual Action Pull Station Microsoft, Windows, and the Windows Logo are Housing Material: LEXAN polycarbonate resin registered trademarks Bi-Colored LED: ACCESSORIES or trademarks of Blinking Green: Normal BG-TR: Optional trim ring. Microsoft Corporation. Steady Red: Alarm SB-1/0: Surface backbox, indoor/outdoor. Silent Knight°, System Switch: Single pole, single throw (SPST) normally * Unless otherwise noted, specifications apply to Sensor' and Honeywell® open (N/O) switch which closes upon activation of SK-Pull-SA and SK-Pull-DA are registered the pull station trademarks of Honeywell COMPATIBILITY International, Inc. ELECTRICAL The SK-PULL-SA AND SK-PULL-DA are This document is not Operating Voltage: 15 — 32VDC compatible with the following Honeywell Silent intended to be used for SLC Standby and Alarm Current: 350µA Knight fire alarm control panels: installation purposes. We z Wire Gauge: Up to 12AWG (3.1 mm) 6820: Addressable fire alarm control panel try to keep our product information up -to 6820EVS: Addressable fire alarm control panel date and accurate. We ENVIRONMENTAL with an emergency voice system. cannot cover all specific Operating Temperature: 320E— 120°F (0°C — 6808: Addressable fire alarm control panel applications or anticipate 49°C) 6700: Addressable fire alarm control panel all requirements. All specifications are subject Humidity: 10%— 93% non -condensing 5700: Addressable fire alarm control panel to change without notice. 5808: Addressable fire alarm control panel 582OXL: Addressable fire alarm control panel call80 -4466444.Support, ca11800-446-6444. 582OXL-EVS: Addressable fire alarm control panel with an emergency voice system For more information Learn more about Honeywell Silent Knight and other products by visiting www.sitentknight.com Honeywell Silent Knight 12 Clintonville Road Honeyne, Northford, CT 06472 Doc 350135 1 Rev E 11/17 ®silMqr, 800-328-0103 9 2017 Honeywell International Inc. XMGHiC STI STOPPER 110 LIFT HERE PRODUCT OVERVIEW nD STI-1100 ADA Compliant BSA SEE REVERSE FOR DETAILS This protective cover has been helping to stop false fire alarms around the world for more than 40 years, without restricting legitimate alarms. All models offer excellent protection against physical damage (both accidental and intentional) and several against severe environments both inside and out. It is ideal for schools, colleges, hospitals, nursing homes, stores, hotels and public buildings of almost every kind where there is a threat of false alarms. HOW IT WORKS Stopper II consists of a clear, tamperproof, tough polycarbonate shield and frame, but the line includes models with the option of a piezo horn, spacer, Form "C" dry relay contact and gaskets. The cover accommodates most manual pull stations. When the Stopper II with horn is lifted to gain access to the protected alarm, a piercing self- contained 95 or 105 dB warning horn (at one foot) sounds. Immediate attention is drawn to the area and a prankster will either run or be caught. The cover is connected to the frame by a cable. When the cover is lifted, it drops off of the frame and a horn will sound (models with horn) until the cover is snapped back onto the frame or for the life of the battery. KEY FEATURES General Information Proven effective for more than 40 years in helping stop false fire alarms without restricting legitimate alarms. Can be used as a guard against physical damage to a manual pull station, with or without the optional warning horn. Three year guarantee against breakage of polycarbonate in normal use (one year on electro mechanical and electronic components). Design Larger sizes and surface mounted pull stations accommodated with STI-3100 conduit spacer. Weather models have closed cell gaskets. The Stopper II design is a registered trademark of Safety Technology International, Inc. Construction UL Listed to U.S. and Canadian safety standards (also for custom labeling). Installation When covering a pull station outside, UL requires stations to be listed for outdoor use. Typical working properties of polycarbonate are -40° to 250oF (40° to 121°C). Electronics Power source is a 9V DC alkaline battery included on standard Stopper II (remote powered unit available). Options Optional horn has a choice of 95 or 105 dB at one foot. Standard red units have "In Case of Fire..." label unless specified with "no label" or "custom label" (extra charge for custom label). For more information, call 888-557-0558 or visit www.lifesafetycom.com LIFE SAFETY GCONSULTANTS STI Stopper II° Dimensions and Technical Information MODELS AVAILABLE Stopper II® Models Indoor Use STI-1100** With horn for flush mount STI-1130** With horn and spacer STI-1200** Without horn flush mount STI-1230** Without horn with spacer Weather Stopper® with gaskets (Indoor/Outdoor rated) STI-1150* Stopper II with horn flush mount STI-1155* Stopper II with horn and spacer STI-1250* STI-1200 flush mount and gasket STI-3150** STI-1200 with spacer and gaskets Accessories KIT-316 Louvers for STI-3100 KIT-1-119015 Two 3/32" Allen wrenches KIT-MO2002 Clear Frame for Stopper II Series STI-1102 Replacement horn for cover with alarm STI-1280 Backplate STI-3002 Weather gasket STI-3003 Conduit gasket STI-3004 Rigid conduit gasket STI-3100 2" conduit spacer with a frame, 1/2' or 3/4" conduit entry STI-3104 2" conduit spacer with 1/2" or 3/4" conduit entry (includes one 3/" conduit entry gasket) * Add -NR for no label on horn housing Add -CR for custom label on horn housing Add -FR for French labeling Add -ES for Spanish labeling * Available in a 6-pack (STI-1100 & STI-1130 also in a 12-pack) HORN COVER SIDE VIEW MODELS WITH HORN (STI-1100 Series) 5.34 in. 136mm) 3.175 in. (81i m) .5 in. _ IR— - (13 i m) 7.4 in. SPACER Yl 8.875 in. 2 Vf` 1774-1 (51 SIDE VIEW MODELS WITHOUT HORN (STI-3150 Series) APPROVALS & WARRANTY TESTING It has been tested and approved or listed by: UL/cUL Listed No. S2466 For fire alarm applications, UL38 requires outdoor listed stations for outdoor use State of California (obtain local fire marshal approval) MEA 49-00-E (STI-1200) Flush models ADA Compliant. Surface models ADA Compliant for operation (UL Certified No. S2466) Weather Stopper® versions designed to meet the requirements of IP54. The indoor/outdoor rated station covers, when mounted on a smooth surface, provide a rain tight seal similar to a 3R enclosure rating. WARRANTY Three year guarantee against breakage of polycarbonate in normal use (one year on electro mechanical and electronic components). IMPORTANT NOTICE Stopper II "FIRE" models are intended to be used in areas where the incidence of false fire alarms from manual pull stations is high or has proven to be a serious problem. Any disadvantage of this device is more than balanced when one considers the consequences of false fire alarms, especially if fire service personnel and equipment are responding to a false fire alarm when they are needed for a real fire somewhere else. Add to this the disruption to the facility when false alarms occur. If you have, or may have, a problem with false fire alarms or physical/weather damage to your fire alarm activation devices, the Stopper II could prove invaluable. *WARNINGAFor RC models: UL Listing does not permit relay contacts to connect to the fire alarm or a life safety function. The power supply for horns, according to UL Listing, cannot be connected to a UL Listed fire alarm system. For electrical specifications see install book. RC models contain one set of Form "C" dry contacts. Contacts rated 30 VAC/VDC 1 amp. EXTERNAL DIMENSIONS: • Flush 7.2 W x 10.2 H x 3.3 Din. (183x259x84mm) 3 in. 3.18 in. 4 in. (76mm 2.73 in. (81mm) 02mm) Sin. 2.32 in. (70mm) 5.5 in. (127mm) 1.61 in. (59mm) (41 mm) 78 in. (20mm) SPACER ADDS 6.81 in. 173mm) 2" DEPTH (50mm) ALL MODELS END VIEW • Surface 7.2 W x 10.2 H x 5.5 D in. (183x259x140mm) LIFE SAFETY 250 Palm Coast Parkway NE, Suite 607 # 323 Palm Coast, FL 32137 C O N S U L T A N T S Ph# (888) 557-0558 Fax# (616) 656-1807 DITEK's DTK-2MHLPF Seric— of low voltage surge protectors provide robust protection In a compact package. This series was designed to remove load instead of shorting to ground. Convenient field -replaceable modules offer ease of Installation, and the Snap -Track base system allows installers to protect multiple circuits while utilizing a common ground point. DTK-2MHLPF Series Modular Low Voltage Surge Protectors ve Product Features DTK-2MHLP 5F 12F 24F 36F 413F 75F > Protects (2) low voltage circuit pairs Service voltage: 5V 12V 24V 36V 48V 75V per module > Hybrid design utilizing SAD and GDT MCOV- 6V 18V 33V 48V 64V 90V technologies Clamping voltage: 6.8V 21 6V 39V 57V 76V 108V > Opens circuit when compromised Protection Modes: Common Mode (L-G) > Field -replaceable modular design with single point ground for fast and Surge Current Rating: 20.000A easy installation Max. Continuous 1A Six voltage configurations available Current: to protect various types of circuits Failure Mode: Open Circuit > Hardwired multi -base mounting system allows protection for up to (10) pairs with a common ground Mechanical Sivecifications > Suitable for use on both AC and DC Base Connection Method: Hardwired terminals. 30-12 AWG low voltage circuits Module Connection Method: Edge card into nxounling base Housing: ABS Applications Operating Temperature: -40°F - 158`F (40`C - 70'C) > Fire Alarm Panel SLC. PIV and IDC Maximum Humidity: 951/6 non -condensing Circuits Module Module with Base > Burglar Alarm Panel IDC Circuits Dimensions: 2.1' L x 1.4' 1h' x 1.9' H 3.25' L x II.5''A' x 2.6' H 4-20mA Current Loops (53 mm x 36 mm x 48 mm) 183 rrm x 38 mm x 66 mm) Weight: 1.2 oz (34 g) 2.8 oz (79 g) Accessories > To order module with base, add (tuallit' "Approvals VVB" to end of part number Certifications: UL497B > Test Module Kit, pin DTK-2MHLPTM Warranty: 10 Year Limited Warranty NFPA USTED DITEK Surge Protection, Largo, FL 33771 • Sa4&W.753.2345 &www.diteksugppmWAion.com • SPS• 100010.003 Rev 4 04121 E.n PWNA n no Owe NUr 10 a+wn nw to Mvsw a uano 1101 co*OAO WIN caopOrakn awven no vwDvoa ft aW u*drw a1 6004 b w owM409'I= b w* OF M rAvr~ Or M any •ton Or Orono* DITE Base Part Numbers and Dimensions DTK-2MHLPF Series Signaling Circuit Modular Surge Protectors DTK-MB10 2 3.25" H x 1.50" W (82.5 mm x 38.1 mm) DTK-2MB 4 3.25" H x 3.00" W (82.5 mm x 76.2 mm) DTK-3MB 6 3.25" H x 4 50" W (82.5 mm x 114.3 mm) DTK-4MB 8 3.25" H x 6.00- W (82.5 mm x 152.4 mm) DTK-5MB 10 3.25" H x 7.50' W (82.5 mm x 190.5 mm) DTK-2M.B DTK-3MB DTK-4?AB DTK-5MB DN-60918:B Indoor Selectable -Output Horns, Strobes, and Horn J Strobes for Wall Applications General The L-Series offers the most versatile and easy -to -use line of horns, strobes, and horn strobes in the industry with lower cur- rent draws and modern aesthetics. With white and red plastic housings, standard and small footprint devices, and plain, FIRE -printed devices, L-Series can meet virtually any applica- tion requirement. The L-Series product line of wall -mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually elim- inating costly and time-consuming ground faults. To further simplify installation and protect devices from con- struction damage, L-Series utilizes a universal mounting plate for all standard and compact models with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field -selectable candela set- tings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Features • Updated modern aesthetics. • Small profile devices for Horns and Horn Strobes. • Plug-in design with minimal intrusion into the back box. • Tamper -resistant construction. • Automatic selection of 12- or 24-volt operation at 15 and 30 candela. • Field -selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185. • Horn rated at 88+ dBA at 16 volts. • Rotary switch for horn tone and two volume selections. • Universal mounting plate for all standard and all compact wall units. • Mounting plate shorting spring checks wiring continuity. before device installation. • Electrically Compatible with legacy SpectrAlert® and SpectrAlert Advance devices. • Compatible with MDL3 sync module. • Listed for wall mounting only. Architectural/Engineering Specifications General: L-Series standard horns, strobes, and horn strobes shall mount to a standard 2" x 4" x "/8" back box, 4" x 4" x 11/2" back box, 4" octagon back box, or double -gang back box. L-Series compact products shall mount to a single -gang 2" x 4" x 17/8" back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard -size models and a separate universal mounting plate shall be used for mounting compact wall models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•CircuitTM Module accessory, shall be powered from a non -coded notifi- cation appliance circuit output and shall operate on a nominal N OTI F 1 E Re by Honeywell P2RL F F I.yam R� R3t y'� - E �� v i E P2GWL SGWL HWL 12 or 24 volts. When used with the Sync -Circuit Module, 12- volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated c appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full -wave rectified unaltered power supply. Strobes and horn strobes shall have field -select- able candela settings including 15, 30, 75, 95, 110, 135, and 185. Strobe. The strobe shall be a L-Series Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary -signaling notification appli- ance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/ reflector system. DN-60918:B • 5/19/17 — Page 1 of 4 Horn Strobe Combination. The horn strobe shall be a L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary -signaling notification appliance and comply with the Americans with Disabilities Act requirements for visi- ble signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non -temporal (contin- uous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non -coded power supply. Synchronization Module. The module shall be a Sync -Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while oper- ating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411/6" x 411/16" x 21/8" back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. PHYSICAL/ELECTRICAL SPECIFICATIONS • Standard Operating Temperature: 320F to 120°F (0°C to 49°C). • Humidity Range: 10 to 93% non -condensing. • Strobe Flash Rate: 1 flash per second. • Nominal Voltage: Regulated 12 DC or regulated 24 DC/ FWR1 (full wave rectified). • Operating Voltage Range2: 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal). • Operating Voltage Range: MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal). • Input Terminal Wire Gauge: 12 to 18 AWG. • Wall -Mount Dimensions (including lens): 5.6" L x 4.7" W x 1.25" D (143 mm L x 119 mm W x 32 mm D). • Compact Wall -Mount Dimensions (including lens): 5.26" L x 3.46" W x 1.93" D (133 mm L x 88 mm W x 49 mm D). • Horn Dimensions: 5.6" L x 4.7" W x 1.25" D (143 mm L x 119 mm W x 32 mm D). • Compact Horn Dimensions: 5.25" L x 3.45" W x 1.25" D (133mm L x 88mm W x 32mm D). NOTE. 1. Full Wave Rectified (FWR) voltage is a non -regulated, time - varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 cd and 30 cd. L-Series Drawings Compact Horn 3.46 1.25 0 00000 0 0000000000000 0000000000000 0000000000000 o000000000000 .27 00000000000 • 000000000000. 0000000000000 00000oo0o0a0o 0oi�l1�0�1p0�0 o 00�000000 0 Compact Combo 3.46 77�mnoo 5.27 Horn mo 47 .7 age 2 of 4 — DN-60918:B • 5/19/17 UL Current Draw Data UL MAX. HORN CURRENT DRAW (MA RMS) UL MAX. STROBE CURRENT DRAW (MA RMS) Candela 8-17.5 Volts 16-33 Volts DC DC FWR 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 185 N/A 222 257 The 3.1 k is the sound of the mini -horns. The EM (which stands for Electro-mechanical) is the sound of the SpectrAlert Advance line which uses an algorithm that hops frequencies between 2Hz and 4Hz. Sound Pattern dB 8-17.5 Volts 16-33 Volts DC DC FWR Temporal High 39 44 54 Temporal Low 28 32 54 Non -Temporal High 43 47 54 Non -Temporal Low 29 32 54 3.1 KHz Temporal High 39 41 54 3.1 KHz Temporal Low 29 32 54 3.1 KHz Non -Temporal High 42 43 54 3.1 KHz Non -Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL MAX. CURRENT DRAW (MA RMS), 2-WIRE HORN STROBE, CANDELA RANGE (15-115 CD) The 3.1 k is the sound of the mini -horns. The EM (which stands for Electro-mechanical) is the sound of the SpectrAlert Advance line which uses an algorithm that hops frequencies between 2Hz and 4Hz. DC Input: 8-17.5 Volts DC Input: 16-33 Volts FWR Input: 16 FWR 15 cd 30 cd 15 cd 30 cd 75 cd 95 cd 110 cd 135 cd 185 cd 15 cd 30 cd 75 cd 95 cd 110 cd 135 cd 185 cd Temporal High 98 158 54 74 121 142 162 196 245 83 107 156 177 198 234 287 Temporal Low 93 154 44 65 111 133 157 184 235 68 91 145 165 185 223 271 Non -Temporal High 106 166 73 94 139 160 182 211 262 111 135 185 207 230 264 316 Non-TemporalLow 93 156 51 71 119 139 162 190 239 79 104 157 175 197 235 283 3.1 K Temporal High 93 156 53 73 119 140 164 190 242 81 105 155 177 196 234 284 3.1 K Temporal Low 91 154 45 66 112 133 160 185 235 68 90 145 166 186 222 276 3.1K Non -Temporal High 99 162 69 90 135 157 175 208 261 104 131 177 204 230 264 326 3.1K Non -Temporal Low 93 156 52 72 119 138 162 192 242 77 102 156 177 199 234 291 DN-60918:B • 5/19/17 — Page 3 of 4 HORN TONES AND SOUND OUTPUT DATA: HORN AND HORN STROBE OUTPUT (DBA) The 3.1 k is the sound of the mini -horns. The EM (which stands for Electro-mechanical) is the sound of the SpectrAlert Advance line which uses an algorithm that hops frequencies between 2Hz and 4Hz. In the coded positions, temporal coding must be provided by the NAC. If the NAC voltage is held constant, the horn output will remain constantly on. Pos. Sound Pattern dB 8-17.5 Volts 16-33 Volts DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non -Temporal High 85 90 90 4 Non -Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non -Temporal High 84 89 89 8 3.1 KHz Non -Temporal Low 77 83 83 9t Coded High 85 90 90 10t 3.1 KHz Coded High 84 89 89 tSettings 9 and 10 are not available on the 2-wire horn strobes. Agency Listings and Approvals The listings and approvals below apply to L-series devices. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UUULC-Listed — S4011 Wall Horn Strobes — S5512 Wall Strobes — S5512 Wall Horns — S5512 Strobe -only ALERT devices • FM Approved (All except ALERT models) • CSFM Listed: 7135-1653:0503 (Wall Horns and Wall Horn Strobes), 7125-1653:0504 (Wall Strobes) Product Line Information WALL HORN STROBES P2WL(A)(-E)(-F), P2RL(A)(-E)(-F). 2-Wire, Horn Strobe (White, Red). P2GWL(A)(-E)(-F), P2GRL(A)(-E)(-F). 2-Wire, Compact Horn Strobe (White, Red). P2WL(A)-P, P2RL(A)-P. 2-Wire, Horn Strobe, Plain (White, Red). P2WL-SP, P2RL-SP. 2-Wire, Horn Strobe, FUEGO (White, Red). WALL STROBES SWL(A)(-E)(-F), SRL(A)(-E)(-F). Strobe, Red (White, Red). SGWL(A)(-E)(-F), SGRL(A)(-E)(-F). Compact Strobe (White, Red). SWL(A)-P, SRL(A)-P. Strobe, Plain (White, Red). SRL-SP. Strobe, FUEGO (Red). SWL-CLR-ALERT. Strobe, ALERT (White). SWL-ALERT. Strobe, Wall, Amber Lens, ALERT (White). HORNS HWL(A), HRL(A). Horn (White, Red). HGWL(A), HGRL(A). Compact Horn (White, Red). ACCESSORIES TR-2W, TR-2. Universal Wall Trim Ring (White, Red). SBBWL, SBBRL. Wall Surface Mount Back Box (White, Red). SBBGWL, SBBGRL. Compact Wall Surface Mount Back Box (White, Red). NOTE. `A" suffix indicates ULC-Listed model. ULC-listed devices include required French labeling. See Agency Listings for listing details. NOTE. `A" suffix indicates ULC-listed models, ULC models have FIRE/FEU marking on cover. NOTE. ULC-listed models add "-E" suffix for English only "FIRE" marking on cover. NOTE. ULC-listed models add "-F" suffix for French only "FEU" marking on cover. NOTIFIERO and SpectrAlertO are registered trademarks and Sync•CircuitTM is a trademark of Honeywell International Inc. ©2017 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. ISD 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. INGINMN6 & MhNUFUTUAW All specifications are subject to change without notice. QUALITY SYSTEMS For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 4 of 4 — DN-60918:6 • 5/19/17