Approved FIR2024-0113+Fire_Alarm_PLAN_Calculations+11.19.2024_9.06.26_AM+4626719GENERAL NOTES: 1. SCOPE OF WORK: THIS PROJECT SHALL INCLUDE: FIRE ALARM REPLACEMENT OF EXISTING CONVENTIONAL FIRE ALARM SYSTEM IN EXISTING BUILDING(S). HALF OF THE BUILDING IS FULLY SPRINKLED AND HAS AN EXISTING FIRE ALARM SYSTEM WHICH WILL BE REPLACED WITH NEW ADDRESSABLE FIRE ALARM SYSTEM FOR SPRINKLER MONITORING AND OCCUPANT NOTIFICATION. PROVIDE AND INSTALL MANUAL PULL STATIONS, COMPLETE DETECTION COVERAGE AND OCCUPANT NOTIFICATION IN SECTION OF BUILDING WITHOUT FIRE SPRINKLER PROTECTION. 2. THESE DRAWINGS ARE DIAGRAMMATIC. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONS. 3. INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND ALL OTHER APPLICABLE CODES AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION. 4. WIRING DEPICTED ON THESE PLANS IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING CONSTRUCTION CONDITIONS ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS LONG AS NO 110V OR HIGHER VOLTAGE CABLES ARE IN THE SAME RACEWAY. 5. FIRE RATINGS SHALL BE MAINTAINED FOR ALL PENETRATIONS THROUGH FIRE -RATED CONSTRUCTION. 6. POWER FOR ALL FIRE ALARM PANELS AND FIRE ALARM POWER SUPPLIES MUST BE PROVIDED BY A DEDICATED AC BRANCH CIRCUIT. THE LOCATION OF THE BRANCH CIRCUIT BREAKER SHALL BE PERMANENTLY IDENTIFIED AT THE CONTROL UNIT, MECHANICALLY PROTECTED, ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL AND SHALL BE RED AND LABELED "FIRE ALARM CIRCUIT CONTROL" IN ACCORDANCE WITH NFPA 72. ELECTRICAL CONTRACTOR SHALL PERFORM LOAD CALCULATIONS TO DETERMINE SIZE OF WIRING AND BREAKERS FOR ALL FIRE ALARM AC BRANCH CIRCUITS BASED ON THE INFORMATION PROVIDED IN THE BATTERY CALCULATIONS FOR THE FIRE ALARM EQUIPMENT. 7. POWER -LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST REMAIN SEPARATED IN CABINET. ALL POWER -LIMITED CIRCUIT WIRING MUST REMAIN AT LEAST 0.25" AWAY FROM ANY NONPOWER-LIMITED CIRCUIT WIRING. FURTHERMORE, ALL POWER -LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST ENTER AND EXIT THE CABINET THROUGH DIFFERENT KNOCK OUTS AND/OR SEPARATE CONDUITS. 8. WHEN UTILIZING CLASS "A" CIRCUITS, SEPARATE OUTGOING AND RETURN CONDUCTORS OF CLASS "A" CIRCUITS BY A MINIMUM OF 12" WHERE RUN VERTICALLY AND 48" WHERE RUN HORIZONTALLY. 9. WHEN UTILIZING SHIELDED CABLE TIE SHIELDS THROUGH AND INSULATE AT EACH JUNCTION BOX. INSULATE AND TAPE BACK AT END. 10. ALL FIRE ALARM CABLING SHALL BE ACCEPTABLE TO THE FIRE ALARM EQUIPMENT MANUFACTURER FOR THE INTENDED PURPOSE. CABLES USED IN VERTICAL RUNS SHALL BE TYPE FPLP OR FPLR. CABLE SPLICES OR TERMINATIONS SHALL BE MADE IN LISTED FITTINGS, BOXES, ENCLOSURES, FIRE ALARM DEVICES, OR UTILIZATION EQUIPMENT. WHERE INSTALLED EXPOSED, CABLES SHALL BE ADEQUATELY SUPPORTED AND INSTALLED IN SUCH A WAY THAT MAXIMUM PROTECTION AGAINST PHYSICAL DAMAGE IS AFFORDED BY BUILDING CONSTRUCTION. WHERE LOCATED WITHIN 7 FT OF THE FLOOR, CABLES SHALL BE SECURELY FASTENED IN AN APPROVED MANNER AT INTERVALS OF NOT MORE THAN 18 IN. 11. SMOKE DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER CONSTRUCTION CLEAN-UP IS COMPLETED AND FINAL. 12. LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL DIFFUSERS. WALL -MOUNTED SMOKE DETECTORS SHALL BE LOCATED A MAXIMUM OF 12" FROM CEILING. 13. PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS. PROVIDE ALL REQUIRED SYNC MODULES. PROVIDE A MULTI -SYNC MODE SLAVE CONNECTION BETWEEN ALL SYNC MODULES. 14. VERIFY ALL FIELD SELECTABLE AUDIBILITY SETTINGS OF NOTIFICATION APPLIANCES WITH FIRE ALARM CONTRACTOR. 15. UPON COMPLETION OF THE FIRE ALARM SYSTEM INSTALLATION AND PROGRAMMING, THE INSTALLING CONTRACTOR SHALL PERFORM FINAL TESTING OF THE ENTIRE SYSTEM, PER ALL APPLICABLE CODES, AND SHALL COORDINATE AND PERFORM A FINAL FIRE ALARM SYSTEM INSPECTION. 16. PROVIDE OFF -SITE MONITORING AS REQUIRED BY THE INTERNATIONAL FIRE CODE, SECTION 907.6.6 AND THE LOCAL AUTHORITY HAVING JURISDICTION. 17. INSTALLING CONTRACTOR SHALL, PHYSICALLY, LABEL ALL INITIATING DEVICES AND NOTIFICATION APPLIANCE CIRCUIT END OF LINE (WHEN WIRING CLASS "B"). THESE LABELS SHALL BE IN PLACE PRIOR TO START-UP AND TESTING. 18. ROOMS CONTAINING CONTROLS FOR AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL ELEMENTS SHALL BE IDENTIFIED WITH PERMANENTLY MOUNTED SIGNS WITH LETTERING NOT LESS THAN 2 INCHES TALL WITH A PRINCIPAL STROKE OF NOT LESS THAN 3/8 INCH. LETTERS SHALL CONTRAST WITH BACKGROUND. CODE ANALYSIS BUILDING INFORMATION: A) OCCUPANCY CLASSIFICATION(S): B B) OCCUPANCY LOAD(S): 123 OCC C) SPRINKLERS: PARTIAL D) CONSTRUCTION TYPE: EXISTING E) BUILDING HEIGHT: 2 STORY + BASEMENT F) PROJECT SQUARE FOOTAGE: 20,067 S.F. 14,607 S.F. (SPRINKLED) 5,460 S.F. (NON SPRINKLED) G) APPLICABLE CODES: 2021 WASHINGTON STATE FIRE CODE 2021 INTERNATIONAL FIRE CODE 2019 WASHINGTON STATE FIRE ALARM CODE 2019 NFPA 72 2023 WASHINGTON STATE ELECTRICAL CODE 2023 NFPA 70 STATE AND LOCAL MARSHAL REGULATIONS H) CIRCUIT CLASSIFICATION: POWER LIMITED 1) PARCEL NUMBER: 0189258 RISK STEVES' EUROPE 130 4TH AVENUE NORTH EDMONDS, WA 98020 a�K m p emxY 0 N VICINITY MAP SCALE: sa DDn Ir/IT I nfl ATVnAI FACP PROJECT NAME: Required Standby Time: Required Alarm Time: System Manufacturer Battery Calculation RICK STEVES EUROPE 241 Hours 5 qutes Silent Knight 11/14/2024 AC Branch Current AC Branch Current: 3.30 Amps @ 120 VAC Maximum NAC Output Panel Max: 6.00 Amps Circuit Max: 3.00 Amps Regulated Load in Sta dby Regulated Load in ALARM Device Type Model Number of Devices Current (Amps) Total Current (Amps) Current (Amps) Total Current (Amps) FACP MAINBOARD 6808 1 0.190000 0.190000 0.250000 0.250000 ANNUNCIATOR 5860 1 0.020000 0.020000 0.025000 0.025000 SMOKE DETECTOR SK-PHOTO-W 41 0.000200 0.008200 0.004500 0.184500 HEAT DETECTOR SK-HEAT-W 2 0.000200 0.000400 0.004500 0.009000 MONITOR MODULE SK-MONITOR 6 0.000375 0.002250 0.000375 0.002250 RELAY MODULE SK-RELAY 9 0.000255 0.002295 0.000255 0.002295 PULL STATION SK-PULL-DA 8 0.000375 0.003000 0.000375 0.003000 FACP.O (See Voltage Drop Calculations) 0.000000 0.000000 0.000000 0.000000 FACP.1 (See Voltage FACP.2 (See Voltage FACP.3 (See Voltage Drop Drop Drop Calculations) Calculations) Calculations) 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 1.472000 0.981000 0.566000 1.472000 0.981000 0.566000 FACPA (See Voltage Drop Calculations) 0.000000 0.000000 0.000000 0.000000 FACP.5 (See Voltage Drop Calculations) 0.000000 0.000000 0.000000 0.000000 FACP.6 See Voltage Drop Calculations 0.000000 0.000000 0.000000 0.000000 Standby Total 0.226145 Alarm Total 3.495045 Battery Requirements Standby Load Current (Amps 0.226145 Required Standby Time in Hours X 24.000000 X 5.427480 Alarm Load Current (Amps) 3.495045 Required Alarm Time in Hours X 0.083333 X 0.291254 Total Ampere Hours Derating Factor (before derating factor) 5.718734 1.25 TOTAL AMPERE HOURS REQUIRED 7.148417 BATTERIES TO BE PROVIDED 2 - 12v 12 AH Point to Point NAC Voltage Drop Calculation 11/14/2024 Project Name IRICK STEVES EUROPE Circuit Number FACP.1 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 20 volts Gau e Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 3.00 amps Total Circuit Current 1.472 amps Spare Current Capacity 20% NAC ID 0.1. End of Line Voltage 17.39 volts Notification Appliance Manufacturer System Sensor Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop 0.1.1 P2RLED 135 0.189 20 20.22 0.181 0.89% 0.1.2 SRLED 15 0.018 41 19.90 0.504 2.47% 0.1.3 P2RLED 135 0.189 37 19.61 0.791 3.88% 0.1.4 P2RLED 135 0.189 62 19.20 1.201 5.89% 0.1.5 P2RLED 135 0.189 62 18.86 1.538 7.54% 0.1.6 P2RLED 15 SRLED 15 0.035 170 18.13 2.267 11.11 % 0.1.7 0.018 31 18.01 2.393 11.73% 0.1.8 P2RLED 15 0.035 13 17.96 2.445 11.98% 0.1.9 P2RLED 30 0.038 37 17.82 2.583 12.66% 0.1.10 SRLED 15 0.018 29 17.71 2.685 13.16% 0.1.11 P2RLED 135 0.189 42 17.57 2.828 13.86% 0.1.12 P2RLED 135 0.189 65 17.43 2.974 14.58% 0.1.13 P2RK 75 0.176 37 17.39 3.0141 14.77% Totals 1 1.472 1 646 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). FIRE ALARM SYMBOL LEGEND NOTE: ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT QTY SYMBOL DESCRIPTION MANUF. & PART # MOUNTING MOUNT IN 1 FACP FIRE ALARM CONTROL PANEL SILENT KNIGHT - 6808 WALL - TOP ® 66" CABINET INCLUDED 1 C 07M FIRE ALARM COMMUNICATOR TELGUARD - TG7 WALL - TOP ® 66" CABINET INCLUDED 1 DOC DOCUMENT BOX SPACE AGE ELEC. - SS000691 WALL - TOP @ 66" CABINET INCLUDED 1 FSA REMOTE ANNUNCIATOR SILENT KNIGHT - 5860 WALL - TOP @ 66" 4 SQ. DEEP W/ SINGLE GANG MUD RING - MOUNTED FLUSH 41 2 SMOKE DETECTOR - SENSOR SILENT KNIGHT - SK-PHOTO-W CEILING ON B300-6 BASE 41 SMOKE DETECTOR - BASE SILENT KNIGHT - B300-6 CEILING 4 SQ. DEEP W/ SINGLE GANG MUD RING - MOUNTED FLUSH 2 1 HEAT DETECTOR - SENSOR SILENT KNIGHT - SK-HEAT-W CEILING ON B300-6 BASE 2 HEAT DETECTOR - BASE SILENT KNIGHT - B300-6 CEILING 4 SQ. DEEP W/ SINGLE GANG MUD RING - MOUNTED FLUSH 6 MM MONITOR MODULE SILENT KNIGHT - SK-MONITOR FIELD VERIFY 4 SQ. DEEP - MOUNTED FLUSH 9 RM RELAY MODULE SILENT KNIGHT - SK-RELAY FIELD VERIFY 4 SQ. DEEP - MOUNTED FLUSH 8 © PULL STATION SILENT KNIGHT - SK-PULL-DA WALL @ 48" 4 SQ. DEEP W/ SINGLE GANG MUD RING - MOUNTED FLUSH 4 VS SPRINKLER VALVE TAMPER FIELD VERIFY BY OTHERS INSTALLED BY OTHERS 1 WF SPRINKLER WATERFLOW FIELD VERIFY BY OTHERS INSTALLED BY OTHERS 13H CEILING MOUNT HORN / STROBE SYSTEM SENSOR - PC2R(W)LED CEILING 4 SQ. DEEP W/ SINGLE GANG MUD RING - MOUNTED FLUSH 8 ;°; STROBE SYSTEM SENSOR - SR(W)LED WALL 80"-96" 4 SQ. DEEP W/ SINGLE GANG MUD RING - MOUNTED FLUSH 14 ;°; HORN / STROBE SYSTEM SENSOR - P2R(W)LED WALL 80"-96" 4 SQ. DEEP W/ SINGLE GANG MUD RING - MOUNTED FLUSH 1 wP HORN / STROBE (WEATHERPROOF) SYSTEM SENSOR - P2RK WALL 80"-96" 4 SQ. DEEP W/ SINGLE GANG MUD RING - MOUNTED FLUSH ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION O -DEVICE ADDRESS L1 SO01 OR M01 (L - DENOTES LOOP #) (S or M -DENOTES SENSOR OR MODULE #) E EXISTING AWG AMERICAN WIRE GAUGE G WITH GUARD TWP TWISTED PAIR P PENDENT MOUNT TWSP TWISTED SHIELDED PAIR R RESIDENTIAL 110V FPLP FIRE POWER LIMITED PLENUM 1-#16 2 TWP WIRE TYPE ABBREVIATED CONDUCTOR COUNT WIRE SIZE OF OMITTED ONLY 1 ACABLE BLES (INEEDED) S SOUNDER BASE FPLR FIRE POWER LIMITED RISER WP WEATHERPROOF STROBE, :°: 15 CANDELA 30 EOL END OF LINE RESISTOR EOLR END OF LINE RELAY 4" MIN 12" MAX CEILING -MOUNTED 4" MINA HEAT DETECTOR AUDIBLE/VISUAL NEVER AND/OR VISUAL HERE ONLY APPLIANCE O `WALL -MOUNTED HEAT DETECTOR FSA o® FACP SYSTEM a RECORDS. 80"-96" DOCUMENTS TO LOWEST PART OF LENS 66" TO 66" TO 66" TO FOP OF TOP OF TOP OF FSA FACP CABINET Point to Point NAC Voltage Drop Calculation 11/14/2024 Project Name IRICK STEVES EUROPE Circuit Number FACP.2 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 50 volts Gau e Per 1000 feet 14 3.07 Wire Gauge for balance of circuit 14 3.07 Max Output Current 3.00 amps Total Circuit Current 0.981 amps Spare Current Capacity 20% NAC ID 0.2. End of Line Voltage 19.34 volts Notification Appliance Manufacturer S stem Sensor Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop 0.2.1 P2RLED 135 1 0.1891 50 20.10 0.301 1.48% 0.2.2 SRLED 15 0.018 36 19.92 0.476 2.33% 0.2.3 P2RLED 135 0.189 31 19.78 0.624 3.06% 0.2.4 P2RLED 135 0.189 59 19.56 0.835 4.10% 0.2.5 P2RLED 135 0.189 41 19.46 0.935 4.58% 0.2.6 SRLED 15 19.38 1.019 5.00% 0.018 66 1 0.189 33 0.2.7 1 P2RLED 135 1 19.341 1.057 5.18% Totals 0.981 316 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). A/C SUPPLY OR RETURN DIFFUSER PENDANT MOUNTED- AUDIBLE/VISUAL APPLIANCES 36" MIN. I-� AUDIBLE -ONLY REMOTE ALARM CEILING MOUNTEDJ/ CEILING MOUNTED APPLIANCESM--INDICATOR SMOKE/HEAT AUDIBLE/VISUAL DETECTOR APPLIANCES DOOR WIDTH T LESS 3"� 6» MAGNETIC [ DOOR HOLDER 90" MIN. 10' MAX WHERE CEILING AFF HEIGHT ALLOWS FINISHED FLOOR FIRE ALARM DEVICE MOUNTING HEIGHTS SCALE: NOT TO SCALE Point to Point NAC Voltage Drop Calculation 11/14/2024 Project Name RICK STEVES EUROPE Circuit Number FACP.3 Nominal System Voltage 20.4 volts Wire Resistance Minimum Device Voltage Distance from source to 1st device 16.0 75 volts Gouge feet 14 Per 1000 3.07 Wire Gauge for balance of circuit 14 J 3.07 Max Output Current 3.00 amps Total Circuit Current 0.566 amps Spare Current Capacity 20% NAC ID 0.3. End of Line Voltage 19.62 volts Notification Appliance Manufacturer System Sensor Circuit is within limits Distance Circuit Device Device Previous Voltage Drop From Percent Identifier Type Current Device at Device Source Drop 0.3.1 PC2RLED 15 0.035 75 20.14 0.261 1.28% 0.3.2 SRLED 15 0.018 34 20.03 0.371 1.82% 0.3.3 PC2RLED 15 0.035 20 19.97 0.434 2.13% 0.3.4 PC2RLED 75 0.087 26 19.89 0.511 2.50% 0.3.5 PC2RLED 75 0.087 28 19.82 0.578 2.83% 0.3.6 PC2RLED 75 0.087 30 19.77 0.634 3.11 % 0.3.7 PC2RLED 15 0.035 40 19.71 0.687 3.37% 0.3.8 PC2RLED 30 0.038 28 19.68 0.719 3.52% 0.3.9 PC2RLED 30 0.038 28 19.66 0.743 3.64% 0.3.10 PC2RLED 15 0.035 33 19.64 0.765 3.75% 0.3.11 SRLED 15 0.018 19 19.63 0.773 3.79% 0.3.12 SRLED 15 0.018 18 19.62 0.779 3.82% 0.3.13 PC2RLED 15 0.035 22 19.62 0.784 3.84% Totals 0.566 401 Notes: Wire resistance is doubled in the calculations for two wires (Positive and Negative). The voltage calculated to the last device must not be lower than the manufactures listed minimum operating voltage (IE: rated operating voltage 16-33 VDC (24 VDC nominal)). 30' MAX 30' MAX AFF 5' MAX. --i FROM EXIT MANUAL 42"-48" PULL STATION F I R2024-0113 NOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST POINT OF DETECTOR 2" MAX WALL -MOUNTED SMOKE DETECTOR I SIDE WALL FINISHED WALL RECEIVED Nov 21 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Drawings reviewed by: Cory W. Haws, SET NICET Certification Fire Protection Engineering Technology Fire Alarm Systems - Level IV Cert. No. 112381 Exp 12/1/2025 shop drawings created by: ITS 5794 W.4600 So. Hooper, UT 84315 Office: 801.985.0410 V NICA %%W.Lrt�.Tf1 N W CD a o � 5 0 z Of o < a � 0 w w o 0 0 w N z 0 L o > W W O W W W V o� w mZ �o fn N CD CD Z Z OD N w COo = U = C,� z 3 w Ln awe > C N � , W H - Ln = Cal w m _ �0 o N ww � X � o0 U �wCn wm r\ Z 0 cn cN 2�a moo N N GNU I -Z z � ZQa CO LU 5 Q U LaJ _, UJ ` 0 u- � LOQw _ I- z L- Z W Q O M r NICET IV Fire Alarm Systems (41 V J Q V C W C) Z Z W W J Q J Q W LL Cory W. HaWs SET / Signature Date: 11/14/2024 Fire Protection Engineering Technology ��<(,Exp re Alarm Sys 81ert. No. Sys!em 12/1/2025 DRAWN CORY W. HAWS UNICAD JOB #24589 CHECKED CORY W. HAWS, SET NICET IV FAS 112381 DATE 11/14/2024 REVISION 0 SCALE 1/8"=V-0" FA-1 UP TO 1 ST FLOOR BASEMENT FIRE ALARM PLAN SCALE: 1/8"=1'-0" 0 4' 8' 16' (DEI FIRE ALARM RISER DIAGRAM SCHEMATIC: NO SCALE Approved Fire Marshal Chris Burt 11 /25/2024 SHEET NOTES: Oi EXISTING INITIATING DEVICE TO BE DEMOLISHED. INSTALLING CONTRACTOR SHALL REMOVE EXISTING DEVICES) AND WIRE NUT EXISTING CIRCUITING. BLANK PLATE EXISTING BACKBOX. O2 EXTEND EXISTING INITIATING DEVICE CIRCUIT TO NEW DEVICES. FIELD VERIFY EXACT CIRCUITING. MAINTAIN EXISTING WIRE GAUGE AND WIRING STYLE. O REPLACE EXISTING INITIATING DEVICE WITH NEW ADDRESSABLE DEVICE LIKE FOR LIKE. O ADDRESSABLE RELAY MODULE(S) AND MULTI -VOLTAGE CONTROL RELAY(S) PROVIDED FOR FIRE -SMOKE DAMPER CONTROL. INSTALLING CONTRACTOR SHALL FIELD VERIFY EXACT MOUNTING, CIRCUITING AND PROGRAMMING REQUIREMENTS. FIELD VERIFY EXACT QUANTITY AND LOCATIONS) WITH MECHANICAL DIVISION. O ADDRESSABLE RELAY MODULE(S) AND MULTI -VOLTAGE CONTROL RELAY(S) PROVIDED FOR DOOR HOLDER CONTROL. INSTALLING CONTRACTOR SHALL FIELD VERIFY EXACT MOUNTING, CIRCUITING AND PROGRAMMING REQUIREMENTS. FIELD VERIFY POWER SOURCE (24 VDC OR 120 VAC). USE MULTI -VOLTAGE CONTROL RELAY(S) IF REQUIRED. FIELD VERIFY EXACT QUANTITY AND LOCATION(S). O ADDRESSABLE MONITOR MODULE(S) PROVIDED TO MONITOR ALL WATER FLOW, PRESSURE SWITCHES, TAMPER SWITCHES AND POST INDICATING VALVES ASSOCIATED WITH THE FIRE SPRINKLER SYSTEM. INSTALLING CONTRACTOR SHALL FIELD VERIFY EXACT MOUNTING, CIRCUITING AND PROGRAMMING REQUIREMENTS. FIELD VERIFY EXACT QUANTITY AND LOCATION(S). O WHERE HOISTWAY(S) AND ELEVATOR CONTROL ROOM ARE PROTECTED WITH SPRINKLERS, PROVIDE HEAT DETECTOR(S) WITHIN 24" OF EACH SPRINKLER HEAD. HEAT DETECTORS SHALL HAVE A LOWER TEMPERATURE RATING THAN THE SPRINKLERS IN THE AREA AND BE MONITORED FOR INTEGRITY. O ADDRESSABLE RELAY MODULES (4) PROVIDED FOR THE ELEVATOR RECALL AND SHUT DOWN. TIE TO ELEVATOR EQUIPMENT ROOM DETECTOR(S), HOISTWAY DETECTOR(S) AND LOBBY DETECTOR(S) TO INITIATE RECALL AND SHUT DOWN. ADDRESSABLE MONITOR MODULE PROVIDED TO MONITOR THE CONTROL CIRCUIT TO THE ELEVATOR SHUNT TRIP BREAKER FOR THE PRESENCE OF OPERATING VOLTAGE. LOSS OF VOLTAGE SHALL CAUSE A SUPERVISORY SIGNAL AT THE CONTROL PANEL. FIELD VERIFY EXACT MOUNTING, CIRCUITING AND PROGRAMMING REQUIREMENTS. U Z z Z a � (/ ) Q LiOf (n J a LL Q Q J o 0 OPERATIONS D_ Q N U � W LJ Yof LQi LQ, U L¢i O >_ Q J Z Cn z MATRIX Q Q a Q `n z J z o Q o of of ~ X � O o Z af o t;Ld . LJ m z CD N J c? Cn J Z a J Z Q w a- ~ W U � Of D_12 Z ZQ � Z CD � O (n Lil U W = (n 2 Z O J J 0 Q Z Ld O Ld J Ld O > J Ld Q Q Z Q U m o of a m a m 0 m o Of a E LJ a- m Q w Q �_ Q Q w U L J C '� Cn Q L1J Q L LJ Q LLJ Q W Q L LJ Q L LJ Q ~ (/') ~ (n ~ (n ~ U) L LJ Q L LJ Q L LJ Q LJ Q Ld Q Ld N (n LJ w N U U U U z z z z w Cn o FIRE ALARM INPUT L� o a a a C) Q a C)���� Q a a a a a Of U SMOKE DETECTORS PULL STATIONS 1 PRIMARY RECALL FLR, ELEV LOBBY SMOKE DET ALTERNATE RECALL FLR, ELEV LOBBY SMOKE DET # # TOP OF ELEV SHAFT SMOKE DET 1 ELEVATOR EQUIPMENT ROOM SMOKE DET ELEVATOR EQUIPMENT ROOM HEAT DET TOP OF ELEV SHAFT HEAT DET WATERFLOW SWITCHES VALVE SUPERVISORY SWITCHES 1 1 FIRE ALARM AC POWER FAIL FIRE ALARM LOW BATTERY OPEN CIRCUIT GROUND FAULT NAC SHORT CIRCUIT 4 LOSS OF AC TO BUILDING __TT 1*1 1 RECEIVED Nov 21 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT Drawings reviewed by: Cory W. Haws, SET NICET Certification Fire Protection Engineering Technology Fire Alarm Systems - Level IV Cert. No. 112381 Exp 12/1/2025 shop drawings created by: IT= HoopSo. Hooper,er, UT UT 84315 Office: 801.985.0410 U NICADE 5 O z r O Q P a tU w_ W �j O LL_ M LJ (n N z O � o W W LU a. O DC LU LU LU F_ V Z LU a F_ 0 M r r- C] C] 0 N Q � N Q� Ln N m ­4- + X Q� a� a L V) V) N N N I"g,o Z O LU NICET IV Fire Alarm Systems �L' mZ Us (n fn (n H W W d U Z Z W z� a� 0 p 00 U = LLj Z p a N W H w� =o U p W W N L� CJ L� N p U W Z m LLj IL Z d aoam W z o = U N H v,—Z — p W o< W = ZOr W AWL, 0 o W ZZx O U U, U W � Z � DC a J a LU W LL F_ Z LU M LU U) a Cory W. HaWs SET / Signature Date: 11/14/2024 Fire Protection Engineering Technology \Fire Alarm Sys Cert. No. 11238181 Exp 12/1/2025 DRAWN CORY W. HAWS UNICAD JOB #24589 CHECKED CORY W. HAWS, SET NICET IV FAS 112381 DATE 11/14/2024 REVISION 0 SCALE j 1/8"=V-0" %%W.Lrt*xxiTMt FA-2 SHEET NOTES: N W CD H \ a 01 !l !1I/T nrrinr I I nrrinr FROM FACP NAC2 SLC CKT. IN BASEMENT DEMO TO FACP Pa O 1 TIFC #14/2 AWG DEMO EEXISTING CKT.. M22 STORAGE O TOILET (DEMO 15cd 0.2.RR 1 2 )d O 135cd RR OFFIC 9 02.3 COMPUTER RM. T11 n r-r-I n r OFFICE OFFI E 0.2.7 135cd 2 MO---- 1 0.2.5 135cd I OD40 3 NEW RR5cd 0.2.4 OFFICE OFFICE EMO n r- r- I n r- OFFICE OFFICE O TOILET nnnv N Itvvl�� #16/2 TWPq NEW CKT. OFFICE OFFICE ZD21 STORAGE D20 SLC CKT FROMTI Oi EXISTING INITIATING DEVICE TO BE DEMOLISHED. INSTALLING CONTRACTOR SHALL REMOVE EXISTING DEVICES) AND WIRE NUT EXISTING CIRCUITING. BLANK PLATE EXISTING BACKBOX. O2 EXTEND EXISTING INITIATING DEVICE CIRCUIT TO NEW DEVICES. FIELD VERIFY EXACT CIRCUITING. MAINTAIN EXISTING WIRE GAUGE AND WIRING STYLE. O REPLACE EXISTING INITIATING DEVICE WITH NEW ADDRESSABLE DEVICE LIKE FOR LIKE. O ADDRESSABLE RELAY MODULE(S) AND MULTI —VOLTAGE CONTROL RELAY(S) PROVIDED FOR FIRE —SMOKE DAMPER CONTROL. INSTALLING CONTRACTOR SHALL FIELD VERIFY EXACT MOUNTING, CIRCUITING AND PROGRAMMING REQUIREMENTS. FIELD VERIFY EXACT QUANTITY AND LOCATIONS) WITH MECHANICAL DIVISION. O ADDRESSABLE RELAY MODULE(S) AND MULTI —VOLTAGE CONTROL RELAY(S) PROVIDED FOR DOOR HOLDER CONTROL. INSTALLING CONTRACTOR SHALL FIELD VERIFY EXACT MOUNTING, CIRCUITING AND PROGRAMMING REQUIREMENTS. FIELD VERIFY POWER SOURCE (24 VDC OR 120 VAC). USE MULTI —VOLTAGE CONTROL RELAY(S) IF REQUIRED. FIELD VERIFY EXACT QUANTITY AND LOCATION(S). O ADDRESSABLE MONITOR MODULE(S) PROVIDED TO MONITOR ALL WATER FLOW, PRESSURE SWITCHES, TAMPER SWITCHES AND POST INDICATING VALVES ASSOCIATED WITH THE FIRE SPRINKLER SYSTEM. INSTALLING CONTRACTOR SHALL FIELD VERIFY EXACT MOUNTING, CIRCUITING AND PROGRAMMING REQUIREMENTS. FIELD VERIFY EXACT QUANTITY AND LOCATION(S). O WHERE HOISTWAY(S) AND ELEVATOR CONTROL ROOM ARE PROTECTED WITH SPRINKLERS, PROVIDE HEAT DETECTOR(S) WITHIN 24" OF EACH SPRINKLER HEAD. HEAT DETECTORS SHALL HAVE A LOWER TEMPERATURE RATING THAN THE SPRINKLERS IN THE AREA AND BE MONITORED FOR INTEGRITY. O ADDRESSABLE RELAY MODULES (4) PROVIDED FOR THE ELEVATOR RECALL AND SHUT DOWN. TIE TO ELEVATOR EQUIPMENT ROOM DETECTOR(S), HOISTWAY DETECTOR(S) AND LOBBY DETECTOR(S) TO INITIATE RECALL AND SHUT DOWN. ADDRESSABLE MONITOR MODULE PROVIDED TO MONITOR THE CONTROL CIRCUIT TO THE ELEVATOR SHUNT TRIP BREAKER FOR THE PRESENCE OF OPERATING VOLTAGE. LOSS OF VOLTAGE SHALL CAUSE A SUPERVISORY SIGNAL AT THE CONTROL PANEL. FIELD VERIFY EXACT MOUNTING, CIRCUITING AND PROGRAMMING REQUIREMENTS. D2 OFFIC 15c1 0.3.13 OFFICE KITCHEN D38 2 2 D37 30cd 0.3.7 0.3.8 15cd H H 14 D3 2 NEW CKT. FACE 2 D36 CTD. FR OFFICE nrrinr- 15i 0.3. 5cd ;FICE 0.11 I I NON SPRINKLED SECIION OF BUILDING. ALL CIRCUITS AND DEVICES IN THIS SIDE OF THE BUILDING ARE NEW. 5 0 Z Of 0 Q i= a � U w w 0 0 ILI_ 0 w cn N Z 0 o W W W a. O W W LU F_ V W Z W Q F_ O M r o� W mZ �s fn N 0 LLj o c.) z pp N z w Q 0s I 0C) U = cNo w � > = N Ln W H — Ln N w� 0 m Co W W X 9 o= U %) W CZ wm � Z 0 cn Cv N N =zo I ~ `n —z W Nouj z zo < co �W01 �^ �ZW [r W W Ln N N ?Zc (n U W Z Q J a. Q J Q W W LL J LL 0 Z N 06 F_ r FIRST FLOOR SECOND FLOOR RECEIVED(�Fire NICET IV\ Alarm Systems FIRE ALARM PLAN FIRE ALARM PLAN Nov 21 2024 > s 0 ONDS 4' 8' 16' » > » 0 4' 8' 16' SCALE: 1 /8 =1 —0 SCALE: 1 /8 =1 —0 CITY M E T SERVICES DEVELOPMENT SERVICES DEPARTMENT Ha s SET /Signature 11/14/2024 ection Engineering Technology e Alarm Sys em�ert. No. 112381 Exp 12/1/2025 Drawings reviewed by: DRAWN CORY W. HAWS U Cory W. Haws, SET NICAD JOB #24589 NICET Certification CHECKED CORY W. HAWS, SET Fire Protection Engineering Technology NICET IV FAS 112381 Fire Alarm Systems - Level IV DATE 11/14/2024 Cert. No. 112381 Exp 12/1/2025 REVISION o shop drawings SCALE 1/8"=1'-0" created by: ITS 5794 W.4600 So.VNICA Hooper, UT 8435 FA3 Office: 801.985.0410 _%%WAfl*xxiTMt a