RVWD BLD BLD2024-1421+Energy_Calculations+10.29.2024_6.50.54_AM+4586497.................. I ........... .................
Mechanical Compliance Summary REVIEWED 10/29/24, 7:50 AM
BY
CITY OF EDMONDS
MECHANICAL C MPLIANCE SUMMARY
UILDIN G DEPAR TMENT'
..........
..... ................. .......—
2021 WSEC Compliance Forms for Commercial Buildings including Group Rl, R2, and Group R3 & R4 over 3 stories Administered by: 02021 NEEA, All rights reserved
Project & Applicant
Information
Project Title
Edmonds Automotive - 2021 WSEC
For Building Department Use: Date, Oct 29, 2024
RECEIVED
Oct 29 2024
CITY OFEDMONDS BLD2024-1421
DEVELOPMENT SERVICES
DEPARTMENT
Project Address
2183RDAVE N
Edmonds, WA 98020
Applicant Name
Jacob Strobl
Applicant Phone
206-661-3622
Applicant Email
jacob@strobldesign.com
Mechanical Compliance Summary Scope - Compliance verification provided in this report is limited to code minimum efficiency requirements for mechanical equipment types
defined in Tables C403.3.2(1) through C403.3.2(16) of the 2021 WSEC-C. This includes efficiency multipliers for economizer exceptions. Performance criteria for additional
energy efficiency and load management measures ARE NOT included in this report. Additional documentation is required to demonstrate compliance with all other provisions of
the energy code, including better than code efficiency criteria for Section C406. For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or
via email at com.techsupport@waenergycodes.com.
General Occupancy
All Commercial
General Building
Services, Vehicle Maintenance
Building Cond.
1,850
Use Type(s)
Office, Other
Floor Area
Project Cond.
1,850
New
Floor Area
Building
Alteration
Multiple Zone Systems &
Floors Above
General Project Types
Alteration
or Addition
Mechanical
Equipment
Grade
1
Mechanical
Scope
Overall
General
Scope
Compliance Path
Prescriptive
Mechanical Project Description
Install a new bath exhaust fan, gas line to a tankless hot water heater, an air handler unit/heat pump of the heating in the
bathrooms/office, and a separate heat pump system to handle the garage bay to supply supplemental heating for comfort
Economizer
DOAS Ventilation
Equipment Efficiency
Mechanical
Project Type
Mechanical Scope
Exception(s)
Provided?
Compliance
Compliance
Applied?
Verification
Alteration
Multiple Zone Systems
Yes
No
COMPLIES
Scope and Method
& Equipment
Additional Energy
HVAC cooling equipment - 5-20% better than code efficiency & improved
Load Management
Efficiency
fan efficiency
Measures
No mechanical load management measures
Measures (AEM)
HVAC heating equipment - 5-20% better than code efficiency
(LDM)
included in project
Does building include occupancy classifications requiring DOAS?
Yes
Does project include DOAS equipment?
No
Do all systems comply with Appendix D
Based on project scope do TSPR requirements apply?
No
standard reference design or qualify for an
No
exception to TSPR?
Scope &Space Conditioning ALTERATION - MULTIPLE ZONE SYSTEMS & Compliance COMPLIES
EQUIPMENT Verification
Multiple Zone Air Systems Category - Heat pump, split & single package
Air Systems Summary Information
System/Equip ID
Supply Airflow
Control
Ventilation Standard
Ventilation CFM
Ventilation
Air Source
Paired with DOAS
Ventilation energy recovery
Energy Recovery
Efficiency (%)
HPl
Constant volume
IMC Natural Ventilation
HP2
Constant volume
IMC Natural Ventilation
Air Systems & Equipment - Cooling
Econo
Required
Required Part
Proposed
System/
Cooling System/Equip
Specific
Cooling
Exception
Cooling
Load Efficiency
Proposed
CE
Part
PL
Efficiency
Equip
Type
Type
Capacity
Multipliers
Efficiency
(Code Min +
Cooling
Units
Load
Units
Compliance
ID
(Btu/h)
(FUI14PLV)
(Code Min +
Econo)
Efficiency
Efficiency
Verification
Econo)
https://waenergycodes.com/print project_summary_form/mec?project_id=29751&form_version_id=24 Page 1 of 2
Mechanical Compliance Summary
10/29/24, 7:50 AM
HP2
Heat pump, air cooled
Split
34,400
0
0
14.3
0
169
SEER2
IEER
COMPLIES
system
Split
HPl
Heat pump, air cooled
20,200
0
0
14.3
0
19.4
SEER2
IEER
COMPLIES
system
Air Systems & Equipment - Heating
Cooling
System
Heat Pump
Capacity
Required Heat
Required
Proposed Heat
Proposed
Efficiency
/Equip
Heating
Specific
Heating Capacity
(Btu/h)
Pump
Low OSA
Pump
HPH
Low OSA
LTH
Compliance
ID
System/Equip Type
Type
(Btu/h)
(Identical to
Heating
Temp
Heating
Units
Temp
Units
Verification
Cooling
Efficiency
Efficiency
Efficiency
Efficiency
Table)
HP2
Heat pump, air cooled,
Split
36,600
34,400
7.5
0
9.1
HSPF2
COP
COMPLIES
heating
system
HP1
Heat pump, air cooled,
Split
23,000
20,200
7.5
0
10.3
HSPF2
COP
COMPLIES
heating
system
Air Systems & Equipment Details
System/Equip
Discrete Area(s) Served
Location In Project Documents - Plan/Detail #
System/Equip Compliance Path
ID
HPl
Storage/Service Repair Bays
ALL
General Prescriptive
Heating Section/Auxiliary Hearing Type: Other source
Economizer Compliance Method: Air -side economizer
provided
WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(2) Unitary Air -Cooled Heat
Pumps
WSEC Equip Efficiency Reference Table - Heating: Refer to Cooling Reference Table
HP2
Office/Business Occupancy I ALL
General Prescriptive
Heating Section/Auxiliary Heating Type: Other source
Economizer Compliance Method: Air -side economizer
provided
WSEC Equip Efficiency Reference Table - Cooling: Table C403.3.2(2) Unitary Air -Cooled Heat
Pumps
WSEC Equip Efficiency Reference Table - Heating: Refer to Cooling Reference Table
https://waenergycodes.com/print project_summary_form/mec?project_id=29751&form_version_id=24 Page 2 of 2