DNS INCLUDED IN CIVILS APPROVED RESUB1 BLD2022-1323+VAULT Plan+1.26.2023_12.26.59_AM+3334575_DEA ReviewedGeneral Structural Notes THE FOLLOWING APPLY UNLESS SHOWN OTHERWISE ON THE DRAWINGS CRITERIA 1. ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (2018 EDITION). 2. DESIGN LOADING CRITERIA: DRIVE AISLE PASSENGER VEHICLES . . . . . . . . . . . . . . . . . . . . . . . 40 PSF CONCENTRATED VEHICLE LOAD AASHTO HS-20 CONCENTRATED LADDER TRUCK LOAD (TOTAL VEHICLE/OUTRIGGER). 75 KIP/45 KIP SEE PLANS FOR ADDITIONAL LOADING CRITERIA 3. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL DRAWINGS FOR BIDDING AND CONSTRUCTION. ARCHITECTURAL DRAWINGS ARE THE PRIME CONTRACT DRAWINGS. ANY DISCREPANCIES FOUND AMONG THE DRAWINGS, THE SPECIFICATION, THESE GENERAL NOTES AND THE SITE CONDITIONS SHALL BE REPORTED TO THE ARCHITECT, WHO SHALL CORRECT SUCH DISCREPANCY IN WRITING. ANY WORK DONE BY THE GENERAL CONTRACTOR AFTER DISCOVERY OF SUCH DISCREPANCY SHALL BE DONE AT THE GENERAL CONTRACTOR'S RISK. 4. PRIMARY STRUCTURAL ELEMENTS NOT DIMENSIONED ON THE STRUCTURAL PLANS AND DETAILS SHALL BE LOCATED BY THE CIVIL PLANS AND DETAILS. VERTICAL DIMENSION CONTROL IS DEFINED BY THE CIVIL PLANS. DETAILING AND SHOP DRAWING PRODUCTION FOR STRUCTURAL ELEMENTS WILL REQUIRE DIMENSIONAL INFORMATION CONTAINED IN BOTH ARCHITECTURAL AND STRUCTURAL DRAWINGS. 5. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AND THE METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES REQUIRED TO PERFORM THE CONTRACTORS WORK. THE STRUCTURAL ENGINEER HAS NO OVERALL SUPERVISORY AUTHORITY OR ACTUAL AND/OR DIRECT RESPONSIBILITY FOR THE SPECIFIC WORKING CONDITIONS AT THE SITE AND/OR FOR ANY HAZARDS RESULTING FROM THE ACTIONS OF ANY TRADE CONTRACTOR. THE STRUCTURAL ENGINEER HAS NO DUTY TO INSPECT, SUPERVISE, NOTE, CORRECT, OR REPORT ANY HEALTH OR SAFETY DEFICIENCIES TO THE OWNER, CONTRACTORS, OR OTHER ENTITIES OR PERSONS AT THE PROJECT SITE. 6. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR THE STRUCTURE AND STRUCTURAL COMPONENTS UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH THE PLANS. CONFORM TO ASCE 37-14 "DESIGN LOADS ON STRUCTURES DURING CONSTRUCTION". 7. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY WILL NOT SATISFY THIS REQUIREMENT. 8. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND THE STRUCTURAL ENGINEER. ALL TYPICAL NOTES AND DETAILS SHOWN ON DRAWINGS SHALL APPLY, UNLESS NOTED OTHERWISE. TYPICAL DETAILS MAY NOT NECESSARILY BE INDICATED ON THE PLANS BUT SHALL STILL APPLY AS SHOWN OR DESCRIBED IN THE DETAILS. WHERE TYPICAL DETAILS ARE NOTED ON THE PLANS, THE SPECIFIED TYPICAL DETAIL SHALL BE USED. WHERE NO TYPICAL DETAIL IS NOTED, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO CHOOSE THE APPROPRIATE TYPICAL DETAIL FROM THOSE PROVIDED OR REQUEST ADDITIONAL INFORMATION. THE CONTRACTOR SHALL SUBMIT ALL PROPOSED ALTERNATE TYPICAL DETAILS TO THOSE PROVIDED WITH RELATED CALCULATIONS TO THE ENGINEER FOR APPROVAL PRIOR TO SHOP DRAWING PRODUCTION AND FIELD USE. 9. ALL STRUCTURAL SYSTEMS, WHICH ARE TO BE COMPOSED OF COMPONENTS TO BE FIELD ERECTED, SHALL BE SUPERVISED BY THE SUPPLIER DURING MANUFACTURING, DELIVERY, HANDLING, STORAGE AND ERECTION IN ACCORDANCE WITH INSTRUCTIONS PREPARED BY THE SUPPLIER. 10.SHOP DRAWINGS FOR THE FOLLOWING ITEMS SHALL BE SUBMITTED TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW PRIOR TO FABRICATION OF THESE ITEMS. PRECAST CONCRETE MEMBERS REINFORCING STEEL (FOR BOTH CONCRETE AND MASONRY CONSTRUCTION) MANUFACTURED LUMBER (PSL'S, LSL'S, LVL'S) CONTRACTOR SHALL SUBMIT WALL ELEVATION DRAWINGS OF AT LEAST 1/8" = 1'-011 SCALE INDICATING LOCATIONS OF CONNECTION EMBEDMENT'S AND WALL OPENINGS FOR REVIEW PRIOR TO CONSTRUCTION. CONTRACTOR SHALL COORDINATE WALL ELEVATION DRAWINGS WITH REINFORCEMENT SHOP DRAWINGS. APPROVED SETS OF ALL SHOP DRAWINGS SHALL ALSO BE SUBMITTED TO THE BUILDING DEPARTMENT. 11.SHOP DRAWING REVIEW: DIMENSIONS AND QUANTITIES ARE NOT REVIEWED BY THE ENGINEER OF RECORD, THEREFORE MUST BE VERIFIED BY THE CONTRACTOR. CONTRACTOR SHALL REVIEW AND STAMP DRAWINGS PRIOR TO REVIEW BY ENGINEER OF RECORD. CONTRACTOR SHALL REVIEW DRAWINGS FOR CONFORMANCE WITH THE MEANS, METHODS, TECHNIQUES, SEQUENCES AND OPERATIONS OF CONSTRUCTION, AND ALL SAFETY PRECAUTIONS AND PROGRAMS INCIDENTAL THERETO. SUBMITTALS SHALL INCLUDE A REPRODUCIBLE AND ONE COPY; REPRODUCIBLE WILL BE MARKED AND RETURNED WITHIN TWO WEEKS OF RECEIPT WITH A NOTATION INDICATING THAT THE SUBMITTAL HAS BEEN FOUND TO BE IN GENERAL CONFORMANCE WITH THE DESIGN OF THE BUILDING. THE SUBMITTED ITEMS SHALL NOT BE INSTALLED UNTIL THEY HAVE BEEN APPROVED BY THE BUILDING OFFICIAL. SHOP DRAWING SUBMITTALS PROCESSED BY THE ENGINEER ARE NOT CHANGE ORDERS. THE PURPOSE OF SHOP DRAWING SUBMITTALS BY THE CONTRACTOR IS TO DEMONSTRATE TO THE ENGINEER THAT THE CONTRACTOR UNDERSTANDS THE DESIGN CONCEPT, BY INDICATING WHICH MATERIAL IS INTENDED TO BE FURNISHED AND INSTALLED AND BY DETAILING THE INTENDED FABRICATION AND INSTALLATION METHODS. IF DEVIATIONS, DISCREPANCIES, OR CONFLICTS BETWEEN SHOP DRAWING SUBMITTALS AND THE CONTRACT DOCUMENTS ARE DISCOVERED EITHER PRIOR TO OR AFTER SHOP DRAWING SUBMITTALS ARE PROCESSED BY THE ENGINEER, THE DESIGN DRAWINGS AND SPECIFICATIONS SHALL CONTROL AND SHALL BE FOLLOWED. 12.SHOP DRAWINGS OF DESIGN BUILD COMPONENTS INCLUDING CANOPIES, BALCONIES, COLD FORM STEEL FRAMING, TEMPORARY SHORING, CURTAIN WALL SYSTEMS, SKYLIGHT FRAMES, PREFABRICATED STAIR SYSTEMS, EXTERIOR CLADDING, AND PRE-ENGINEERED SYSTEMS SHALL BE STAMPED AND SIGNED BY A STRUCTURAL ENGINEER LICENSED IN THE STATE OF WASHINGTON. SHOP DRAWINGS SHALL BE APPROVED BY THE COMPONENT DESIGNER PRIOR TO REVIEW OF THE ARCHITECT OR ENGINEER OF RECORD FOR GENERAL CONFORMANCE WITH THE DESIGN OF THE BUILDING. THE COMPONENT DESIGNER IS RESPONSIBLE FOR CODE CONFORMANCE AND ALL NECESSARY CONNECTIONS NOT SPECIFICALLY CALLED OUT ON ARCHITECTURAL OR STRUCTURAL DRAWINGS. SHOP DRAWINGS SHALL INDICATE MAGNITUDE AND DIRECTION OF ALL LOADS IMPOSED ON BASIC STRUCTURE. DESIGN CALCULATIONS SHALL BE SUBMITTED WITH THE SHOP DRAWINGS. QUALITY ASSURANCE 13.SPECIAL INSPECTION SHALL BE PROVIDED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND SECTIONS 110 AND 1705 OF THE INTERNATIONAL BUILDING CODE BY A QUALIFIED TESTING AGENCY DESIGNATED BY THE ARCHITECT, AND RETAINED BY THE BUILDING OWNER. THE ARCHITECT, STRUCTURAL ENGINEER, AND BUILDING DEPARTMENT SHALL BE FURNISHED WITH COPIES OF ALL INSPECTION AND TEST RESULTS. SPECIAL INSPECTION OF THE FOLLOWING TYPES OF CONSTRUCTION IS REQUIRED UNLESS NOTED OTHERWISE. CONCRETE CONSTRUCTION PRECAST CONCRETE ERECTION PER TABLE 1705.3 PER TABLE 1705.3 PERIODIC INSPECTION: INSPECTION SHALL BE PERFORMED AT INTERVALS NECESSARY TO CONFIRM THAT WORK REQUIRING SPECIAL INSPECTION IS IN COMPLIANCE WITH REQUIREMENTS. CONTINUOUS INSPECTION: INSPECTOR SHALL BE ONSITE AND OBSERVE THE WORK REQUIRING INSPECTION AT ALL TIMES THAT WORK IS PERFORMED. GEOTECHNICAL 14.FOUNDATION NOTES: SUBGRADE PREPARATION INCLUDING DRAINAGE, EXCAVATION, COMPACTION, AND FILLING REQUIREMENTS, SHALL CONFORM STRICTLY WITH RECOMMENDATIONS GIVEN IN THE SOILS REPORT OR AS DIRECTED BY THE SOILS ENGINEER. FOOTINGS SHALL BEAR ON SOLID UNDISTURBED EARTH OR COMPACTED STRUCTURAL FILL AT LEAST 18" BELOW LOWEST ADJACENT FINISHED GRADE. FOOTING DEPTHS/ELEVATIONS SHOWN ON PLANS (OR IN DETAILS) ARE MINIMUM AND FOR GUIDANCE ONLY; THE ACTUAL ELEVATIONS OF FOOTINGS MUST BE ESTABLISHED BY THE CONTRACTOR IN THE FIELD WORKING WITH THE TESTING LAB AND SOILS ENGINEER. BACKFILL BEHIND ALL RETAINING WALLS WITH FREE DRAINING GRANULAR FILL AND PROVIDE FOR SUBSURFACE DRAINAGE AS NOTED IN THE SOILS REPORT. ALLOWABLE SOIL PRESSURE (NATIVE SOILS) 4000 PSF LATERAL EARTH PRESSURE (RESTRAINED/UNRESTRAINED) . . . . . . 50 PCF/35 PCF ALLOWABLE PASSIVE EARTH PRESSURE (FS OF 1.5 INCLUDED) . . . . . . 250 PCF COEFFICIENT OF FRICTION (FS OF 1.5 INCLUDED) . 0.3 SEISMI SC URCHARGE PRESSURE (RESTRAINED%UNRESTRAINED) .14H PSF 7H PSF BUILDING SURCHARGE PRESSURE . . . . . . . . . . . . . . . . . .272 PSF/FT SOILS REPORT REFERENCE: RILEY GROUP PROJECT NO. 2021-319-1 DATED JUNE 171 2021 CONCRETE 15.CONCRETE SHALL BE MIXED, PROPORTIONED, CONVEYED AND PLACED IN ACCORDANCE WITH ACI 301, INCLUDING TESTING PROCEDURES. CONCRETE SHALL ATTAIN A 28-DAY STRENGTH OF f'c = 31000 PSI AND MIX SHALL CONTAIN NOT LESS THAN 5-1/2 SACKS OF CEMENT PER CUBIC YARD AND SHALL BE PROPORTIONED TO PRODUCE A SLUMP OF 5" OR LESS. REQUIRED CONCRETE STRENGTH IS BASED ON THE DURABILITY REQUIREMENTS OF SECTION 1904 OF THE IBC. DESIGN STRENGTH IS f'c = 21500 PSI. 16.A CONCRETE PERFORMANCE MIX SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER AND THE BUILDING DEPARTMENT FOR APPROVAL TWO WEEKS PRIOR TO PLACING ANY CONCRETE. THE PERFORMANCE MIX SHALL INCLUDE THE AMOUNTS OF CEMENT, FINE AND COARSE AGGREGATE, WATER AND ADMIXTURES AS WELL AS THE WATER CEMENT RATIO, SLUMP, CONCRETE YIELD AND SUBSTANTIATING STRENGTH DATA IN ACCORDANCE WITH ACI 318-14, SECTIONS 26.4.3 AND 26.4.4. THE USE OF A PERFORMANCE MIX REQUIRES BATCH PLANT INSPECTION, THE COST OF WHICH SHALL BE PAID BY THE GENERAL CONTRACTOR. REVIEW OF MIX SUBMITTALS BY THE ENGINEER OF RECORD INDICATES ONLY THAT INFORMATION PRESENTED CONFORMS GENERALLY WITH CONTRACT DOCUMENTS. CONTRACTOR OR SUPPLIER MAINTAINS FULL RESPONSIBILITY FOR SPECIFIED PERFORMANCE. 17.ALL CONCRETE WITH SURFACES EXPOSED TO WEATHER OR STANDING WATER SHALL BE AIR -ENTRAINED WITH AN AIR -ENTRAINING AGENT CONFORMING TO ASTM C2601 C494, AND C618. TOTAL AIR CONTENT FOR FROST -RESISTANT CONCRETE SHALL BE IN ACCORDANCE WITH ACI 318-14, TABLE 19.3.2.1 MODERATE EXPOSURE, F1. 18.REINFORCING STEEL SHALL CONFORM TO ASTM A615 (INCLUDING SUPPLEMENT S1) , GRADE 60, FY = 60,000 PSI. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185. SPIRAL REINFORCEMENT SHALL BE DEFORMED WIRE CONFORMING TO ASTM A615, GRADE 60, FY = 601000 PSI. 19.DETAILING OF REINFORCING STEEL (INCLUDING HOOKS AND BENDS) SHALL BE IN ACCORDANCE WITH ACI 315R-18 AND 318-14. LAP ALL CONTINUOUS REINFORCEMENT #5 AND SMALLER 40 BAR DIAMETERS OR 2'-0" MINIMUM. PROVIDE CORNER BARS AT ALL WALL AND FOOTING INTERSECTIONS. LAP CORNER BARS #5 AND SMALLER 40 BAR DIAMETERS OR 2'-0" MINIMUM. LAPS OF LARGER BARS SHALL BE MADE IN ACCORDANCE WITH ACI 318-14, CLASS B. LAP ADJACENT MATS OF WELDED WIRE FABRIC A MINIMUM OF 8" AT SIDES AND ENDS. NO BARS PARTIALLY EMBEDDED IN HARDENED CONCRETE SHALL BE FIELD BENT UNLESS SPECIFICALLY SO DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER. 20.CONCRETE PROTECTION (COVER) FOR REINFORCING STEEL SHALL BE AS FOLLOWS: FOOTINGS AND OTHER UNFORMED SURFACES CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 311 FORMED SURFACES EXPOSED TO EARTH OR WEATHER (#6 BARS OR LARGER). . . . 2" FORMED SURFACES EXPOSED TO EARTH OR WEATHER (#5 BARS OR SMALLER) . 1-1/211 21.CONCRETE WALL REINFORCING --PROVIDE THE FOLLOWING UNLESS DETAILED OTHERWISE: 8" WALLS #4 @ 12 HORIZ. #4 @ 18 VERTICAL 1 CURTAIN 10" WALLS #4 @ 18 HORIZ. #4 @ 18 VERTICAL 2 CURTAINS 22.CAST-IN-PLACE CONCRETE: SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND DIMENSIONS OF DOOR AND WINDOW OPENINGS IN ALL CONCRETE WALLS. SEE MECHANICAL DRAWINGS FOR SIZE AND LOCATION OF MISCELLANEOUS MECHANICAL OPENINGS THROUGH CONCRETE WALLS. SEE ARCHITECTURAL DRAWINGS FOR ALL GROOVES, NOTCHES, CHAMFERS, FEATURE STRIPS, COLOR, TEXTURE, AND OTHER FINISH DETAILS AT ALL EXPOSED CONCRETE SURFACES, BOTH CAST -IN -PLACE AND PRECAST. 23.PRECAST PRESTRESSED CONCRETE UNITS SHALL BE DESIGNED BY THE MANUFACTURER FOR THE LOADS AND SPANS SHOWN ON THE PLANS. MANUFACTURER SHALL DESIGN FOR SPECIAL CONDITIONS AT OPENINGS AND BLOCK -OUTS SHOWN ON STRUCTURAL, ARCHITECTURAL AND MECHANICAL DRAWINGS. DESIGN AND FABRICATION SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S PUBLISHED SPECIFICATIONS FOR THE UNIT FURNISHED AND ACI STANDARD 318-14. SUBMIT COMPLETE DESIGN CALCULATIONS AND SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. ALL SUBMITTALS SHALL BEAR THE STAMP AND SIGNATURE OF A REGISTERED PROFESSIONAL ENGINEER, STATE OF WASHINGTON. PRECAST CONCRETE MEMBERS SHALL BE ADEQUATELY BRACED UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH THE PLANS. CONTRACTOR SHALL PROVIDE ANY EXTRA REINFORCEMENT, INSERTS, LIFTING DEVICES, PRESTRESSING, ETC., REQUIRED FOR HANDLING AND ERECTION. 24.NON-SHRINK GROUT SHALL BE FURNISHED BY AN APPROVED MANUFACTURER AND SHALL BE MIXED AND PLACED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S PUBLISHED RECOMMENDATIONS. GROUT STRENGTH SHALL BE AT LEAST EQUAL TO THE MATERIAL ON WHICH IT IS PLACED (3000 PSI MINIMUM). AM 0 Submit Specific Item ❑ Rejected ❑ Revise and Resubmit PQ Furnish with Corrections Noted 0 Reviewed ❑ Not Required/Not Reviewed This review is only for general conformance with the design concept of the Project and general compliance with the information given in the Contract Documents. Corrections or comments made on the shop drawings during this review do not relieve contractor from compliance with the requirements of the plans and specifications. Approval of the specific item shall not include approval of an assembly of which the item is a component. Contractor is responsible for dimensions to be confirmed and correlated at the job site; information that pertains solely to the fabrication processes or to the means, methods, techniques, sequences, and procedures of construction; coordination of his or her Work with that of other trades; and for performing all work in a safe and satisfactory manner. DAVID EVANS AND ASSOCIATES, INC. Date: 3/15/23 Reviewed by: Mike Schumann HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360.629.3441 P.O. Box 1270 10031 SR 532, Suite B Sl_.od. WA 98292 www.de1lgnsow.cow 10 L ENONEMN SEATTLE 2124 Third Avenue, Suite 100 Seattle, WA 98121 TACOMA 934 Broadway, Suite 100 Tacoma, WA 98402 CENTRAL WASHINGTON 206.443.6212 414 N Pearl Street, Suite 8 ssfengineers.com Ellensburg, WA 98926 Copyright 2022 Swenson Say Faget - All Rights Reserved co N 0 00 UUrn am Cn O CO 0 o Q LU w C') J Z LU co FEEw Cn � w VCN O 0 00 LUN Pek��i�§ET ISSUE DATE: SEPTEMBER 30, 2022 REVISION SCHEDULE Rev # Date I Description 2 01-04-23 1 Permit Resubmittal RESUB 1 /26/2023 CONTENTS: CITY OF EDMONDS DEVELOPMENT G E N E RALICES STRUCTURAL NOTES SCALE: DRAWN: DJN CHECKED: RHR PROJECT NO: 12034-2021-01 SHEET: Simi 0 0 N 8/S3.1 1011 CONIC. WALL A 6/S3.1 PROVIDE REINF. PER 10/S3.1 POUR SLOTS PER 3/S3.1 �)Ili, PLAN MANUF. TYP. El 11 11 El El 11 11 El El 11 11 El El 11 11 El El 11 11 El El 11 El Ll El El Ll Ll El El Ll Ll El El El 11 11 11 11 11 11 11 11 11 11 11 11 11 El El 11 11 El El 11 11 El El 11 11 El EI 11 11 El El 11 11 El El 11 11 El El 11 11 El El 0 0 11 El 11 11 El El 11 11 El El 11 11 El El 11 11 El El 11 � � I � E] _ � � ❑❑o❑ ❑o❑❑ ❑o❑❑ > o /S3.1 ❑❑❑ LILIL- E3 ❑ ❑ 1 ❑ ❑ 1 ❑ ❑ 1 ❑ ❑ 1 ❑ ❑ 1 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 11 i ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 1 ❑ ❑ 1 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 1 ❑ ❑ ❑ ❑ 11 11 `t ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 1[10 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ PIPE Plan Notes 7/S3.1 1 �SEE CIVILRE NFORCEDMENT AROURAWINGS aJQ'PC'IVETRATIONSFrtF4ETERS, LOCATIONS, AND INVERTS. SE�S3.1�R ADDITIONAL Wi flLET 2. 3" TOPPING SLAB WITH #4 @ 12" ON CENTER EACH WAY PLACED AT THE MID -DEPTH OF THE SLAB. 3. ALL FOOTINGS SHALL BEAR ON DENSE UNDISTRURBED SOILS OR ON STRUCTURAL FILL PLACED AND COMPACTED PER GEOTECHNICAL RECOMMENDATIONS. ALLOWABLE BEARING PRESSURE SHALL BE FIELD VERIFIED PRIOR TO CONSTRUCTION. 4. HOLLOW CORE PLANKS SHALL BE DESIGNED TO SUPPORT LOADS IN EXCESS OF AASHTO HS20 AND ABLE TO SUPPORT A TOTAL LADDER TRUCK LOAD OF 75,000 LBS AND AN OUTRIGGER LOAD 45,000 LBS. 5. SEE PLANK MANUFACTURES PLACEMENT PLAN FOR INSTALLATION REQUIREMENTS. 2 J J O r CU 6/S3.1 , o 220'-0" 10" SLAB ON GRADE W/#5@12"oc. E.W. BOT J J Q O CD CU z CD U < 3/S3.1 6/S3.1 10/S3.1 > 24" 0 OPNG. TO ACCEPT RISER LADDER RING & LOCKING SOLID MANHOLE COVER PER CIVIL DWG'S. TYP. REFER TO 5/S3.1 FOR CURB SUPPORT OF 12%" x 48" HOLLOW CORE PLANK, TYP. (by others) auTt Lid Framing Plan Scale: 3/32" = V-011 8" CONC. WALL Vault Foundation Plan � Scale: 3/32" = V-0" � _7 BLOCKOUT IN EDGE CELL OF THE PLANK AS SHOWN 8/S3.1 1011 CONC. WALL 6/S3.1 2/S3.1 AW\ HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360. 629. 3441 P.O. Box 1270 10031 SR 532, Snite B Stanwood, WA 98292 www.designsnw.com 10 L ENONEMN SEATTLE 2124 Third Avenue, Suite 100 Seattle, WA 98121 TACOMA 934 Broadway, Suite 100 Tacoma, WA 98402 CENTRAL WASHINGTON 206.443.6212 414 N Pearl Street, Suite 8 ssfengineers.com Ellensburg, WA 98926 Copyright 2022 Swenson Say Faget - All Rights Reserved c0 N O 00 LUO-) a O 0 0 0 LU LU Z LU FC0 EE 1-- W LLI C/) LL M U) V CN O J M N Ln LU N 00 PEAMW§ET ISSUE DATE: SEPTEMBER 30, 2022 REVISION SCHEDULE Rev # Date I Description 2 01-04-23 1 Permit Resubmittal RESUB 1 /26/2023 CONTENTS: CITY OF EDMONDS DEVELOPMENT VAULT KANS SCALE: DRAWN: DJN CHECKED: RHR PROJECT NO: 12034-2021-01 SHEET: S2ml POUR SLOT PER PLANK MANUFACTURER CORNER BARS TO CORNER BARS TO HOLLOW CORE PLANK CORNER BARS TO MATCH CROSS WALL CORNER BARS TO MATCH CROSS WALL PER MANUFACTURER MATCH EXTERIOR HORIZ. REINF. MATCH HORIZ. REINF. HORIZ. REINF. HORIZ. REINF. (alt. hooks) VOID DAM PER (3)#5 CONT. ------------------ PLANK MFR. 2-2 #5 x 6 F_ EA. VOID HOLLOW CORE PLANK GROUT JOINT W/ POUR SLOT (2 min. PER MANUFACTURER 311 per plank) ADDITIONAL VERT. BARS T TYP. CORNER BARS: 24 ADDITIONAL VERT. BARS TYP. CORNER BARS: 24 BEARING STRIP PER min. PLANK MANUFACTURER 2 #5 HORZ @ TOP OF WALL (2)#5 ) 'Doo'"'00 N F NF 2'-011 TYP. AT VOIDS W/ POUR #5 x 3'-011 @ 18"oc AT CROSS WALL CROSS WALL SLOTS. (6" at other voids) CENTER OF WALL W/ STD HOOK IN CLOSURE CONT. BACKER ROD IF REQD CONCRETE WALL PER PLAN REINF w/ #4 @ 18"oc H.E.F., 1v/ 1 " I INSIDE FACE \/� OUTSIDE FACE MS Double Curtain Single Curtain #4 @ 10" oc V.O.F NOTE: SEE PLANK MANUFACTURER'S PLACEMENT PLANS FOR FINAL BEARING WIDTH Typical Corner Bars at Concrete Yp Walls and Footings 9 Hollow Core Edge Bearing 9 9 on Exterior Wall 3 Hollow Core Plank -to -Plank Grout Joint 4 COORDINATE ANY REQUIRED EMBEDS OR ANCHORAGE (1)#5 HORZ ABOVE AND ADD (1)#5 VERT FULL HEIGHT EA SIDE OF MANHOLE COVER PER W/ MANHOLE COVER MFR., TYP. BELOW OPENING OPENING FOR EACH PAIR 0 HOLLOW CORE PLANK GROUT EDGE VOID SOLID WITH CLOSURE POUR PLAN. CLIP CONNECTIONS 8" TYP VERT BARS CUT PER MANUFACTURER PER SUPPLIER FINISH GRADE EL. '\\\ #5 HAIRPIN w/ 14" WIDTH PER CIVIL OUTSIDE FACE \\ INSIDE FACE 2 AND 1811 LONG TAILS @ EA MS VOID BLOCKOUT „ „ CONT. PL 1/4 x3 W/ ty j\\jam\\\j\\\� %/// CONCRETE WALL PER PLAN REINF w/ (3)#5 CONT. 1/2"0 x 4" W.H.S. @ 24"oc 3„ \/\\�/\\//\\/\ #6 DOWELS @ 10" oc. \� j/ #4 @ 18"oc H.E.F., #4 @ 12"oc V.I.F, & #4 @ 10" oc V.O.F X/ #5 CONT. WITHIN EDGE (2)#5 HORZ @ TOP OF WALL BLOCKOUT �////\/ \\\/�\%�\\\�\ % SLAB ON GRADE VOID OF PLANK AS REQ D FOR COVER /\// \\/ PER PLAN (1)#5 x 4'-0" DIAG EA BACKING ROD AS REQ'D. #5 x 3-0" @ 18"oc AT r ti L J\ %// CORNERCENTER CONCRETE WALL PER /STD #4 CONT. PLAN REINF w/ HOOK INOCL SURE s #4 @ 18"oc H.E.F., 1 j\\/// /iN/,� /. 2'-01, V . F #4 @ 10" oc V.O. F #5 @ 12"oc E.W. CTRD. 2 8" THICK CONCRETE WALL CONN. PER 3/S3.1 2 INSIDE FACE \ OUTSIDE FACE MS PER 10/S3.1 MS HOLLOW CORE PLANK PER PLANK MFR. Curb at Grated Opening 5 p 9 6 Wall Reinforcing at T 9 Yp Pipe p Penetration 7 Hollow Core Edge Parallel to Exterior Concrete Wall 9 (5)#5 TOP AND BOT FINISH GRADE 11 SECTION , (4)#6 PLANK DOWELS PLACED AT THE TRANSVERSE z Q I 1 I I I I I (4)#6 PLANK DOWELS PLACED AT THE MID -DEPTH MID -DEPTH OF THE SLAB (4)#5 TOP AND BOT EA SIDE w — < � - - I I OF THE SLAB OF MANHOLE OPENING > CD TOP OF SLAB o I I I ' 45..32 r CV •� I I I I I I •• 45..03 ............ .._.. —7----r- -i----T— --- — 00 •• (5)#5 TOP AND BOT (2)#5HORZATTOPWALL I I TRANSVERSE I I I I 8" CONCRETE WALL REINF w/ ' I I I I I #4 @ 12"oc HORIZ. AND #5 - (4)#5 TOP AND BOT EA SIDE "oc VERT. CENTERED IN o I I ( I I I OF MANHOLE OPENING WALL. #5 FTG-TO-WALL DOWEL I / \ I c CENTERED IN WALL. MATCH / \ I VERT REINF SPACING. I I NOTE: • EXTEND 2'-6" INTO WALL SEE FOUNDATION PLAN FOR 5% SLOPE TO FOOTING DIMENSIONS SEDIMENT COLLECTION • 449.03' Q0 ............. ------ -- — -- —� -------- c� Section 24" 0 OPENING ACCOMMODATE TO MANHOLE plan (1)#6 AT THE MID -DEPTH OF THE SLAB 10 20'-0" 1/2"= V-0" 12 Cast -In -Place Slab at Manhole Vault Section AW\ HOUSING HOPE we keep hope alive DESIGNS northwest ARCHITECTS 360.629.3441 100001110 P.O. Box 1270 10031 SR 532, Snite B Stanwood, WA 98292 www.design s nw. com SEATTLE 2124 Third Avenue, Suite 100 Seattle, WA 98121 TACOMA 934 Broadway, Suite 100 Tacoma, WA 98402 CENTRAL WASHINGTON 206.443.6212 414 N Pearl Street, Suite 8 ssfengineers.com Ellensburg, WA 98926 Copyright 2022 Swenson Say Faget - All Rights Reserved co N 0 00 Ujrn om O F 0 Z z 0 Q LU w C� J 0 z LU F- w L F- F- Vm O M N LU Q 00 N ao PEfk'M'fi'§ET ISSUE DATE: SEPTEMBER 30, 2022 REVISION SCHEDULE Rev # Date Description 2 01-04-23 Permit Resubmittal RESUB 1 /26/2023 CONTENTS: CITY OF EDMONDS DEVELOPMENT ICES Vault Seciions and Details SCALE: DRAWN: DJN CHECKED: RHR PROJECT NO: 12034-2021-01 SHEET: S3ml