BLD2022-1319 TAB report40A- TESTING ANO C. SERVICES HOUSING HOPE ELC FIELD APARTMENTS 8215 236TH STREET SW EDMONDS, WA 98026 FINAL TAB REPORT ARCHITECT: DESIGNS NORTHWEST ARCHITECTS, INC. 26915 102ND DR NW, SUITE 201, STANWOOD, WA 98292 PROJECT NO: 2230199 DATE: 10/9/2024 TECHNICIAN: BRYCE HURLBUT MECHANICAL ENGINEER: ECOTOPE, INC. 1917 FIRST AVENUE, SUITE 300, SEATTLE, WA 98101 MECHANICAL CONTRACTOR: D. K. SYSTEMS, INC. 1355 BOUSLOG ROAD, BURLINGTON, WA 98233 10/09/2024 Page 1 of 102 AABC TAC SERVICES, LLC 16929 MAPLEWOOD LANE BOW, WA 98232 PH:(360) 255-5306 FAX:(360) 464-9973 ADMIN@TACSERVICESNW.COM AABC National Perfiormance Guaranty Pursuant to the agreement between TAC Services, LLC AABC Certified Testing & Balancing Agency and D. K. Systems, Inc. Client All systems shall be tested and balanced in accordance with the project plans and specifications and to the optimum performance capabilities of the equipment. Testing and balancing shall be done in accordance with the standards published by the Associated Air Balance Council. If the Agency listed above fails to comply with the specifications for any reason other than termination of business by the AABC agency or equipment malfunction or inadequacy which prevents proper balancing of the systems, AABC will investigate and, if warranted, will provide supervisory personnel to assist the member Agency to perform work in accordance with AABC Standards. This supervision will be provided at no additional cost to the building owner. This Guaranty is valid for one year from the date of submission of a test and balance report, provided the Agency is a current member of AABC, and may only be invoked in writing by the building owner, architect, or engineer of record. The Guaranty is limited to the terms and conditions as stated herein. Project Name Address Housing Hope ELC Field Apartments 8215 236th Street SW Edmonds, WA 98026 Name of Engineer Shanti Oram Engineering Firm Ecotope, Inc. Email Address shanti@ecotope.com Address 1917 First Avenue, Suite 300 Seattle, WA 98101 Date 10/9/2024 TBE # 08-02-04 By Robert R. Coallier AABC Certified TBE AABC Associated Air Balance Council 1518 K Street, N.W. Washington, D.C. 20005 202-737-0202 • Fax 202-638-4833 info@aabc.com • www.aabc.com 10/09/2024 Page 2 of 102 TESTING ANO Ca A~By SERVICES TABLE OF CONTENTS DESCRIPTION PAGE COVERPAGE------------------------------------------------------------------------------------------------------------ 1 AABC NATIONAL PERFORMANCE GUARANTY------------------------------------------------------------------------- 2 TABLE OF CONTENTS 3-4 TEST INSTRUMENT CALIBRATION DATES ------------------------------------------------------------------------------ 5 PR03ECTSUMMARY---------------------------------------------------------------------------------------------------- 6 LEGEND SHEET 7-9 EF-IDF-B •-------------------------------------------------------------------------------------------------------------- 10 EF-IDF-C •-------------------------------------------------------------------------------------------------------------- 11 EF-IDF-D •-------------------------------------------------------------------------------------------------------------- 12 EF-LAUND •-------------------------------------------------------------------------------------------------------------- 13 EF-MNT •-------------------------------------------------------------------------------------------------------------- 14 IHP-A2 •-------------------------------------------------------------------------------------------------------------- 15-16 IHP-A5 •-------------------------------------------------------------------------------------------------------------- 17-18 IHP-AI-A •-------------------------------------------------------------------------------------------------------------- 19 IHP-AI-B •-------------------------------------------------------------------------------------------------------------- 19 IHP-A3-A •-------------------------------------------------------------------------------------------------------------- 19 IHP-A3-B •-------------------------------------------------------------------------------------------------------------- 19 IHP-A4 •-------------------------------------------------------------------------------------------------------------- 20 IHP-IDF-A •-------------------------------------------------------------------------------------------------------------- 20 ERV-A1 •-------------------------------------------------------------------------------------------------------------- 21 ERV-A2 •-------------------------------------------------------------------------------------------------------------- 22-23 ERV-A3 •-------------------------------------------------------------------------------------------------------------- 24 UNIT B101 ------------------------------------------------------------------------------------------------------------ 25 UNIT B102 ------------------------------------------------------------------------------------------------------------ 26 UNIT B103 ------------------------------------------------------------------------------------------------------------ 27 UNIT B104 ------------------------------------------------------------------------------------------------------------ 28 UNIT C101 ------------------------------------------------------------------------------------------------------------ 29 UNIT C102 ------------------------------------------------------------------------------------------------------------ 30 UNIT C103 ------------------------------------------------------------------------------------------------------------ 31 UNIT C104 ------------------------------------------------------------------------------------------------------------ 32 UNIT D101 ------------------------------------------------------------------------------------------------------------ 33 UNIT D102 ------------------------------------------------------------------------------------------------------------ 34 UNIT D103 ------------------------------------------------------------------------------------------------------------ 35 UNIT D104 ------------------------------------------------------------------------------------------------------------ 36 UNIT D105 ------------------------------------------------------------------------------------------------------------ 37 UNIT D106 ------------------------------------------------------------------------------------------------------------ 38 UNIT A201 ------------------------------------------------------------------------------------------------------------ 39 UNIT A202 ------------------------------------------------------------------------------------------------------------ 40 UNIT A203 ------------------------------------------------------------------------------------------------------------ 41 UNIT A204 ------------------------------------------------------------------------------------------------------------ 42 10/09/2024 Page 3 of 102 STING AMC) Ca AABC TF SFRVICFS TABLE OF CONTENTS DESCRIPTION PAGE UNITA205------------------------------------------------------------------------------------------------------------ 43 UNITB201------------------------------------------------------------------------------------------------------------ 44 UNITB202------------------------------------------------------------------------------------------------------------ 45 UNITB203------------------------------------------------------------------------------------------------------------ 46 UNITB204------------------------------------------------------------------------------------------------------------ 47 UNITC201------------------------------------------------------------------------------------------------------------ 48 UNIT C202 49 UNITC203------------------------------------------------------------------------------------------------------------ 50 UNITC204------------------------------------------------------------------------------------------------------------ 51 UNITD201------------------------------------------------------------------------------------------------------------ 52 UNITD202------------------------------------------------------------------------------------------------------------ 53 UNIT D203 ------------------------------------------------------------------------------------------------------------ 54 UNIT D204 55 UNITD205------------------------------------------------------------------------------------------------------------ 56 UNIT D206 ------------------------------------------------------------------------------------------------------------ 57 UNIT A301 ------------------------------------------------------------------------------------------------------------ 58 UNIT A302 59 UNITA303------------------------------------------------------------------------------------------------------------ 60 UNIT A304 ------------------------------------------------------------------------------------------------------------ 61 UNIT A305 ------------------------------------------------------------------------------------------------------------ 62 UNIT B301 ------------------------------------------------------------------------------------------------------------ 63 UNIT B302 ------------------------------------------------------------------------------------------------------------ 64 UNIT B303 ------------------------------------------------------------------------------------------------------------ 65 UNIT B304 ------------------------------------------------------------------------------------------------------------ 66 UNIT C301 67 UNITC302------------------------------------------------------------------------------------------------------------ 68 UNITC303------------------------------------------------------------------------------------------------------------ 69 UNIT C304 ------------------------------------------------------------------------------------------------------------ 70 UNIT D301 ------------------------------------------------------------------------------------------------------------ 71 UNIT D302 ------------------------------------------------------------------------------------------------------------ 72 UNIT D303 ------------------------------------------------------------------------------------------------------------ 73 UNIT D304 ------------------------------------------------------------------------------------------------------------ 74 UNIT D305 ------------------------------------------------------------------------------------------------------------ 75 UNIT D306 ------------------------------------------------------------------------------------------------------------ 76 SCHEMATIC DIAGRAMS ------------------------------------------------------------------------------------------------ 77-93 FAN CURVES 94-102 10/09/2024 Page 4 of 102 4 TFSTING Am C. SERVICES TEST INSTRUMENT CALIBRATION DATES AA BC INSTRUMENT MANUFACTURER MODEL NO. SERIAL NO. CALIBRATION DATE DIGITAL FLOW CAPTURE HOOD ALNOR EBT-731 EBT732043039 10/16/2023 DIGITAL THERMOMETER (AIR) ALNOR EBT-731 EBT732043039 10/16/2023 DIGITAL VEL GRID ALNOR EBT-731 EBT732043039 10/16/2023 DIGITAL MANOMETER (AIR) ALNOR EBT-731 EBT732043039 10/16/2023 VANE ANEMOMETER ALNOR RVA-801 A06246 4/11/2024 HYDRONIC MANOMETER TELEMETRY S-DP-250 2200129B 6/25/2024 ULTRASONIC FLOW METER FUJI ELECTRIC SYS FSCS N9H1117T 5/3/2024 HUMIDITY SENSOR TELEMETRY PR-TH-1 2400217 7/19/2024 8" FLOW HOOD TELEMETRY CH-8D 2100134 6/25/2024 3 POUNDER FLOW HOOD TELEMETRY 3 POUNDER 2400272B 6/20/2024 PVF MODULE TELEMETRY S-PVF-1 2400075C 6/26/2024 DUCT AIR LEAKAGE TEST MACHINE ORIFLOW COBRA 10090501 N/A INFRARED CAMERA FLIR FLIR i7 601055235 N/A PITOT TUBE DWYER 160-12 N/A N/A PITOT TUBE DWYER 160-24 N/A N/A PITOT TUBE DWYER 160-36 N/A N/A PITOT TUBE DWYER 160-60 N/A N/A 10/09/2024 Page 5 of 102 4AC- TESTING ANn Ca SERVICES PROJECT SUMMARY AABC 1.0 THE ENVIRONMENTAL SYSTEMS WERE TESTED AND THE RESULTS ARE AS TABULATED ON THE ATTACHED DATA SHEETS 2.0 COMMENTS ON SPECIFIC EQUIPMENT IS INCLUDED UNDER REMARKS SECTION ON INDIVIDUAL DATA FORMS CONTAINED HEREIN. 10/09/2024 Page 6 of 102 4w- TURTING SIRVICI S AABC LEGEND SHEET AHU AIR HANDLING UNIT AC OR ACU AIR CONDITIONER UNIT ACCU AIR COOLED CONDENSING UNIT ADJ P.D. ADJUSTED PITCH DIAMETER AMP AMPERE AVG AVERAGE B.H.P. BRAKE HORSEPOWER C.D. CEILING DIFFUSER CFM CUBIC FEET PER MINUTE C.E. CEILING EXHAUST CH CHILLER CHWR CHILLED WATER RETURN CHW OR CHWS CHILLED WATER SUPPLY C.R. CEILING RETURN CT COOLING TOWER CWR CONDENSER WATER RETURN CW OR CWS CONDENSER WATER SUPPLY DB DRY BULB D.D. DIRECT DRIVE D.P. DIFFERENCE, NET DECREASE OR INCREASE DIA DIAMETER DISP DISPLACEMENT D.N.A. DATA NOT AVAILABLE D.N.L DATA NOT LISTED EAT ENTERING AIR TEMPERATURE EDC ELECTRIC DUCT COIL EDH ELECTRIC DUCT HEALER EF EXHAUST FAN EMCS ENERGY MANAGEMENT CONTROL SYSTEM (S) EWT ENTERING WATER TEMPERATURE FCU FAN COIL UNIT FH FUME HOOD FG FLOOR GRILLE F.E. FLOOR EXHAUST OR RETURN F.L.A FULL LOAD AMPERAGE FPB FAN POWERED BOX 10/09/2024 Page 7 of 102 4AA IL STING ANO C: %l Il V ICl 5 AABC FPM FEET PER MINUTE F.S. FLOOR SUPPLY F.S.R FLOOR SUPPLY REGISTER FT. HD FEET OF HEAD FTU FAN TERMINAL UNIT GPM GALLONS PER MINUTE GFH GAS FIRED HEATER HC HEATING COIL HEATER O.L. THERMAL OVERLOAD PROTECTION FOR MOTORS LOCATED AT THE MOTOR STARTER HEPA HIGH EFFICIENCY PARTICULATE AIR H.F. HEPA FILTER HOA HAND/OFF/AUTO SWITCH H.P. HORSEPOWER HPS HIGH PRESSURE STEAM HRC HEAT RECOVERY COIL OR HEAT RECLAIM COIL HVAC HEATING, VENTILATION AND AIR CONDITIONING HWR HOT WATER RETURN OR HEATING WATER RETURN HWS HOT WATER SUPPLY OR HEATING WATER SUPPLY HX HEAT EXCHANGER I.D. INSIDE DIAMETER LAT LEAVING AIR TEMPERATURE L.D. LINEAR SUPPLY DIFFUSER LPS LOW PRESSURE STEAM L.T. LIGHT TROFFER LWG LOW WALL GRILLE LWR LOW WALL RETURN LWT LEAVING WATER TEMPERATURE MAU/MUA MAKE UP AIR UNIT MBH 1,000 BTU'S PER HOUR N.A. NOT ACCESSIBLE N.I. NOT INSTALLED N.T. NOT TAKEN N.V.L NO VALID LOCATION N.Z. NOZZLE O.D. OUTSIDE DIAMETER OPEN NO TERMINAL DEVICE INSTALLED O.S.A. MIN OUTSIDE AIR MINIMUM OAT OUTSIDE AIR TEMPERATURE 10/09/2024 Page 8 of 102 4AP� TESTING ANO C■ SERVICES AABC PF POWER FACTOR PHC PREHEAT COIL PHC PHASE (S) PMP CIRCULATING PUMP P.P PERFORATED PLATE PSI POUNDS PER SQUARE INCH P.T. PITOT TRAVERSE RA RETURN AIR RF RETURN AIR FAN R.G. RETURN GRILLE RHC REHEAT COIL RPM REVOLUTIONS PER MINUTE SA SUPPLY AIR SAT SUPPLY AIR TEMPERATURE S.D. SUPPLY DIFFUSER SEF SMOKE EXHAUST FAN SF (AIR) SUPPLY FAN S.F. (ELECT) SERVICE FACTORS SHC STEAM HEATING COIL S.P. "W.C." STATIC PRESSURE RESISTANCE, MEASURED IN INCHES OF WATER COLUMN S.W.E. SIDEWALL EXHAUST S.W.R. SIDEWALL RETURN S.W.S. SIDEWALL SUPPLY TAB TESTING, ADJUSTING, AND BALANCING TSP TOTAL STATIC PRESSURE UH UNIT HEATER V VOLTS VAV VARIABLE AIR VOLUME VD VOLUME DAMPER VFD VARIABLE FREQUENCY DRIVE VP VELOCITY PRESSURE W WATTS WB WET BULB W.G. WATER GAUGE OF DEGREES FAHRENHEIT DP DIFFERENTIAL (DELTA) PRESSURE OR PRESSURE DROP DT DIFFERENTIAL (DELTA) TEMPERATURE, NET TEMPERATURE DECREASE OR INCREASE PSI POUNDS PER SQUARE INCH 10/09/2024 Page 9 of 102 40A- TESTING ANO Ca SERVICES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT ID EF-IDF-B UNIT DATA EQUIP. LOCATION CEILING AREA SERVED ELEC B122 MANUFACTURER GREENHECK MODEL NUMBER SP-A200-QD SERIAL NUMBER DESIGN CFM 23539850 150 FAN DATA ACTUAL CFM 151 T.S.P. "W.C. 0.30 DESIGN FAN RPM 750 TESTED FAN RPM MANUFACTURER UNABLE TO TEST GREENHECK • •• DATA HORSEPOWER 1/40 VOLTS 115 AMPS 0.46 SERVICE FACTOR 1.00 MOTOR RPM 900 SPEED VARIABLE PHASE / HZ 1/60 OVERLOAD SIZE THERMAL RHEOSTAT SETTING LOW AREA SERVED NO. CODE SIZE ELEC B122 El EG 6" AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN F. H. - 150 - 182 121% - 151 1010/0 EF-IDF-B 150 182 121% 151 1010/0 FORM: DIRECT DRIVE TEST DATA >2000 CFM 10/09/2024 Page 10 of 102 40A- TESTING ANO Ca SERVICES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT ID EF-IDF-C UNIT DATA EQUIP. LOCATION CEILING AREA SERVED ELEC C121 MANUFACTURER GREENHECK MODEL NUMBER SP-A200-QD SERIAL NUMBER DESIGN CFM 23539841 150 FAN DATA ACTUAL CFM 161 T.S.P. "W.C. 0.30 DESIGN FAN RPM 750 TESTED FAN RPM MANUFACTURER UNABLE TO TEST GREENHECK • •• DATA HORSEPOWER 1/40 VOLTS 115 AMPS 0.46 SERVICE FACTOR 1.00 MOTOR RPM 900 SPEED VARIABLE PHASE / HZ 1/60 OVERLOAD SIZE THERMAL SPEED SETTING LOW AREA SERVED NO. CODE SIZE ELEC C121 E1 EG 14X12 AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN 0.71 210 150 252 180 120% 225 161 107% EF-IDF-C 150 180 120% 161 107% UNIT IS SET TO ITS MINIMUM SPEED SETTING. FORM: DIRECT DRIVE TEST DATA >2000 CFM 10/09/2024 Page 11 of 102 40A- TESTING ANO Ca SERVICES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT ID EF-IDF-D UNIT DATA EQUIP. LOCATION CEILING AREA SERVED ELEC D122 MANUFACTURER GREENHECK MODEL NUMBER SP-A200-QD SERIAL NUMBER DESIGN CFM 23539849 150 FAN DATA ACTUAL CFM 164 T.S.P. "W.C. 0.30 DESIGN FAN RPM 750 TESTED FAN RPM MANUFACTURER UNABLE TO TEST GREENHECK • •• DATA HORSEPOWER 1/40 VOLTS 115 AMPS 0.46 SERVICE FACTOR 1.00 MOTOR RPM 900 SPEED VARIABLE PHASE / HZ 1/60 OVERLOAD SIZE THERMAL SPEED SETTING LOW AREA SERVED NO. CODE SIZE ELEC D122 El EG 6" AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN F. H. - 150 - 177 1180/0 - 164 1090/0 EF-IDF-D 150 177 1180/0 164 1090/0 UNIT IS SET TO ITS MINIMUM SPEED SETTING. FORM: DIRECT DRIVE TEST DATA >2000 CFM 10/09/2024 Page 12 of 102 40A- TESTING ANO Ca SERVICES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT ID EF-LAUND UNIT DATA EQUIP. LOCATION CEILING AREA SERVED LAUNDRY C122 MANUFACTURER PANASONIC MODEL NUMBER FV-0511VKS2 SERIAL NUMBER DESIGN CFM 30809M 50 FAN DATA ACTUAL CFM 53 T.S.P. "W.C. 0.10 DESIGN FAN RPM NOT GIVEN TESTED FAN RPM MANUFACTURER UNABLE TO TEST PANASONIC • •• DATA HORSEPOWER low VOLTS 120 AMPS 0.27 SERVICE FACTOR 1.00 MOTOR RPM VARIABLE SPEED 3SPEED PHASE / HZ 1/60 OVERLOAD SIZE THERMAL SPEED SETTING 50 CFM AREA SERVED NO. CODE SIZE LAUND C122 E1 EG 1OX10 AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN F. H. - 50 - 116 232% - 53 106% EF-LAUND 50 116 232% 53 106% FORM: DIRECT DRIVE TEST DATA >2000 CFM 10/09/2024 Page 13 of 102 40A- TESTING ANO Ca SERVICES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT ID EF-MNT UNIT DATA EQUIP. LOCATION CEILING AREA SERVED MAINT C123 MANUFACTURER GREENHECK MODEL NUMBER SP-A390-QD SERIAL NUMBER DESIGN CFM 23705785 200 FAN DATA ACTUAL CFM 358 T.S.P. "W.C. 0.33 DESIGN FAN RPM 927 TESTED FAN RPM MANUFACTURER UNABLE TO TEST MCMILLAN • •• DATA HORSEPOWER 1/12 VOLTS 115 AMPS 1.42 SERVICE FACTOR 1.00 MOTOR RPM 1350 SPEED SINGLE PHASE / HZ 1/60 OVERLOAD SIZE THERMAL RHEOSTAT SETTING NONE PROVIDED AREA SERVED NO. CODE SIZE MAINT C123 E1 EG 14X12 AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN F. H. - 200 - 358 179% - 358 179% EF-MNT 200 358 179% 358 179% UNABLE TO LOCATE ANY SPEED CONTROLLER FOR THIS FAN. NO OBJECTIONABLE NOISE OR DRAFTS OBSERVED. FORM: DIRECT DRIVE TEST DATA >2000 CFM 10/09/2024 Page 14 of 102 4- TESTING AND 1:.. SERVICES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT IHP-A5 • PROPERTY OFFICE, SECURE FILE, COPY/WORK, CONSULTATION AA BC = UNIT ID IHP-A5 I EQUIP. LOCATION CEILING AREA SERVED PROPERTY OFFICE MANUFACTURER MITSUBISHI MODEL # SEZ-KD12NA4 RIAL # i DESIGN CFM 16M01762 300 ACTUAL CFM 284 ESP 0.20 TESTED SPEED HIGH TESTED SETTING MANUFACTURER MODE: 8 SETTING: 3 MITSUBISHI MOTOR DATA HORSE POWER 96 W VOLTS 208 AMPS 0.72 SERVICE FACTOR 1.00 MOTOR RPM VARIABLE SPEED 3SPEED PHASE / HZ 1/60 HEATER SIZE THERMAL AREA SERVED NO. CODE SIZE PROP OFF A102 I S5 12X12 AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN F.H. - 75 80 107% 68 910/0 SERV OFF A106 2 S5 12X12 F.H. - 75 65 87% 68 910/0 SERV OFF A107 3 S5 12X12 F.H. - 75 44 590/0 68 910/0 SERV OFF A112 4 S5 12X12 F.H. - 75 61 81% 80 107% SUPPLY 300 250 83% 284 95% UNIT IS SET TO ITS MAXIMUM SPEED SETTING. FORM: FCU- VRF DUCTED- NO OSA- NO VAV- DIRECT DRIVE- TEST DATA 10/09/2024 Page 15 of 102 40A- TESTING AND U. SERVICES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT IHP-AS • PROPERTY OFFICE, SECURE FILE, COPY/WORK, CONSULTATION lqw AA BC AREA SERVED NO. CODE SIZE AK DESIGN FPM CFM INITIAL FPM CFM % OF DESIGN FINAL FPM CFM 7DESIGN FORM ID: VELOCITY TEST SHEET 10/09/2024 Page 16 of 102 4- TESTING AND 1:.. SERVICES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT IHP-A5 • PROPERTY OFFICE, SECURE FILE, COPY/WORK, CONSULTATION AA BC = UNIT ID IHP-A5 I EQUIP. LOCATION CEILING AREA SERVED PROPERTY OFFICE MANUFACTURER MITSUBISHI MODEL # SEZ-KD09NA4 RIAL # i DESIGN CFM 3XM22068 250 ACTUAL CFM 243 ESP 0.20 TESTED SPEED HIGH TESTED SETTING MANUFACTURER MODE: 8 SETTING: 3 MITSUBISHI MOTOR DATA HORSE POWER 96 W VOLTS 208 AMPS 0.59 SERVICE FACTOR 1.00 MOTOR RPM VARIABLE SPEED 3SPEED PHASE / HZ 1/60 HEATER SIZE THERMAL AREA SERVED NO. CODE SIZE PROP OFF A103 I S5 12X12 AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN F.H. - 100 63 63% 90 900/0 SECURE A104 2 S5 12X12 F.H. - 50 50 1000/0 51 102% COPY A105 3 S5 12X12 F.H. - 50 44 88% 51 102% CUNSULT A108 4 S5 12X12 F.H. - 50 47 94% 51 102% SUPPLY 250 204 82% 243 97% UNIT IS SET TO ITS MAXIMUM SPEED SETTING. FORM: FCU- VRF DUCTED- NO OSA- NO VAV- DIRECT DRIVE- TEST DATA 10/09/2024 Page 17 of 102 40A- TESTING AND U. SERVICES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT IHP-AS • PROPERTY OFFICE, SECURE FILE, COPY/WORK, CONSULTATION lqw AA BC AREA SERVED NO. CODE SIZE AK DESIGN FPM CFM INITIAL FPM CFM % OF DESIGN FINAL FPM CFM 7DESIGN FORM ID: VELOCITY TEST SHEET 10/09/2024 Page 18 of 102 40A- TESTING ANO Ca SERVICES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT IHP-Al-A, B, IHP-A3-A, B • COMMUNITY A101, MULTIPURPOSE Alll AABC UNIT ID IHP-Al-A UNIT IHP-Al-B DATA IHP-A3-A IHP-A3-B EQUIP. LOCATION WALL WALL WALL WALL AREA SERVED COMMUNITY A101 COMMUNITY A101 MULTIPURPOSE Alll MULTIPURPOSE A111 MANUFACTURER MITSUBISHI MITSUBISHI MITSUBISHI MITSUBISHI MODEL NUMBER MSZ-GS12NA MSZ-GS12NA MSZ-GS12NA MSZ-GS12NA SERIAL NUMBER DESIGN CFM 2ZE11560 134/160/222/307/381 31E15224 FAN 134/160/222/307/381 DATA 2ZE07413 134/160/222/307/381 2ZE06731 134/160/222/307/381 ACTUAL CFM 134/160/222/307/381 134/160/222/307/381 134/160/222/307/381 134/160/222/307/381 TESTED SPEED MANUFACTURER HIGH MITSUBISHI HIGH MOTOR MITSUBISHI DATA HIGH MITSUBISHI HIGH MITSUBISHI HORSE POWER 0.04 0.04 0.04 0.04 NAMEPLATE VOLTS 208-230 208-230 208-230 208-230 NAMEPLATE AMPS 0.25 0.25 0.25 0.25 SERVICE FACTOR 1.00 1.00 1.00 1.00 MOTOR RPM VARIABLE VARIABLE VARIABLE VARIABLE SPEED 5 SPEED 5 SPEED 5 SPEED 5 SPEED PHASE / HZ 1/60 1/60 1/60 1/60 OVERLOAD RATING THERMAL AREA SERVED NO. CODE SIZE THERMAL THERMAL THERMAL AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN DUCTLESS FORM: FCU & AC- NO OSA- DUCTLESS- DIRECT DRIVE- TEST DATA 10/09/2024 Page 19 of 102 40A- TESTING ANO Ca SERVICES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT IHP-A4, IHP-IDF-A • CORRIDOR A100, ELECTRIC A124 AABC UNIT ID IHP-A4 UNIT DATA IHP-IDF-A EQUIP. LOCATION CEILING CASSETTE WALL AREA SERVED CORRIDOR A100 ELEC A124 MANUFACTURER MITSUBISHI MITSUBISHI MODEL NUMBER SLZ-KF09NA PKA-Al2LA1 SERIAL NUMBER DESIGN CFM 2YM05068 230/265/300 FAN 36MO1164 DATA 265/290/325/385 ACTUAL CFM 230/265/300 265/290/325/385 TESTED SPEED MANUFACTURER HIGH MITSUBISHI MOTOR HIGH DATA MITSUBISHI HORSE POWER 50 W 0.04 NAMEPLATE VOLTS 208-230 208-230 NAMEPLATE AMPS 0.20 0.55 SERVICE FACTOR 1.00 1.00 MOTOR RPM VARIABLE VARIABLE SPEED 3 SPEED 3 SPEED PHASE / HZ 1/60 1/60 OVERLOAD RATING THERMAL AREA SERVED NO. CODE SIZE THERMAL AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN DUCTLESS FORM: FCU & AC- NO OSA- DUCTLESS- DIRECT DRIVE- TEST DATA 10/09/2024 Page 20 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-Al SUPPLY ERV-Al EXHAUST EQUIP. LOCATION LVL 1 BLDG A CEILING LVL 1 BLDG A CEILING AREA SERVED COMMUNITY A101 COMM A101/ STOR A123 MANUFACTURER GREENHECK GREENHECK MODEL NUMBER MINICORE-5-VG-F MINICORE-5-VG-F SERIAL NUMBER 23800619 • 23800619 DESIGN CFM 200 200 ACTUAL CFM 216 197 T.S.P. "W.C. 0.50 0.50 TESTED SPEED VARIABLE VARIABLE STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER GREENHECK GREENHECK HORSEPOWER 1/4 1/4 NAMEPLATE VOLTS 208 208 TESTED VOLTS 210 210 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.1 1.1 MOTOR RPM 1725 1725 SPEED VARIABLE VARIABLE PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED NO. COMMUNITY A101 1 THERMAL THERMAL CODE SIZE AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN S2 12X8 F.H. - 200 108 54% 216 1080/0 SUPPLY 200 108 54% 216 1080/0 COMMUNITY A101 E1 R2 12X8 F.H. - 100 77 77% 152 152% STOR A123 E2 R3 6X6 F.H. - 50 21 42% 45 900/0 EXHAUST 150 98 65% 197 131% UNIT DOES NOT HAVE INDEPENDENT SPEED CONTROL FOR SUPPLY/ EXHAUST MOTORS. NO NOISE ISSUES OR DRAFTS OBSERVED. UNIT RUNS AT A LOWER SPEED AND THEN RAMPS UP TO BALANCED SPEED WHEN CO2 SENSOR IS ACTIVATED. (FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 21 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-2 (SUPPLY) ERV-2 (EXHAUST) EQUIP. LOCATION BLDG A LVL 1 CEILING BLDG A LVL 1 CEILING AREA SERVED BLDG A LVL 1 OFFICES BLDG A LVL 1 OFFICES MANUFACTURER GREENHECK GREENHECK MODEL NUMBER MINICORE-5-VG-F MINICORE-5-VG-F SERIAL NUMBER 23800620 • 23800620 DESIGN CFM 300 200 ACTUAL CFM 307 199 T.S.P. "W.C. 0.50 0.50 TESTED SPEED 6.7 VDC 3.8 VDC STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER GREENHECK GREENHECK HORSEPOWER 1/4 1/4 NAMEPLATE VOLTS 208 208 TESTED VOLTS 210 210 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.0 0.9 MOTOR RPM 1725 1725 SPEED VARIABLE VARIABLE PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED CONSULT A108 NO. 1 THERMAL CODE SIZE S6 6X6 AK F.H. • FPM CFM - 25 THERMAL OF FPM CFM DESIGN 37 148% FPM CFM 25 OF DESIGN 1000/0 COPY/ WRK A105 2 S6 6X6 F.H. - 25 22 88% 24 96% SECURE FILE A014 3 S6 6X6 F.H. - 25 36 144% 24 96% PROP OFFICE A103 4 S6 6X6 F.H. - 25 39 156% 24 96% CORRIDOR A100 5 S4 12X12 F.H. - 100 85 85% 103 103% SERVICES OFF A112 6 S6 6X6 F.H. - 25 40 160% 24 96% SERVICES OFF A107 7 S6 6X6 F.H. - 25 21 84% 25 1000/0 SERVICES OFF A106 8 S6 6X6 F.H. - 25 21 84% 25 1000/0 PROPERTY OFF A102 9 S6 6X6 F.H. - 25 35 140% 33 132% SUPPLY 300 336 112% 307 102% BALANCING DAMPER FOR SUPPLY OUTLET #9 IS IN A FULL CLOSED POSITION, NO NOISE OR DRAFTS OBSERVED. FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 22 of 102 •rA PROJECT: LOCATION: PROJECT NO: CONTACT: SYSTEM: AREA SERVED: AREA SERVED NO. CODE SIZE AK DESIGN INITIAL Oho OF FINAL Oho OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN REMARKS: 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-1 (SUPPLY) ERV-1 (EXHAUST) EQUIP. LOCATION BLDG A LVL 1 CEILING BLDG A LVL 1 CEILING AREA SERVED BLDG A LVL 1 MULTI Alll BLDG A LVL 1 MULTI A111 MANUFACTURER GREENHECK GREENHECK MODEL NUMBER MINICORE-5-VG-F MINICORE-5-VG-F SERIAL NUMBER 23800621 • 23800621 DESIGN CFM 300 300 ACTUAL CFM 322 320 T.S.P. "W.C. 0.50 0.50 TESTED SPEED VARIABLE VARIABLE STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER GREENHECK GREENHECK HORSEPOWER 1/4 1/4 NAMEPLATE VOLTS 208 208 TESTED VOLTS 210 210 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.2 1.2 MOTOR RPM 1725 1725 SPEED VARIABLE VARIABLE PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED NO. MULTI Alll 1 THERMAL THERMAL CODE SIZE AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN S2 12X8 F.H. - 300 65 22% 322 107% SUPPLY 300 65 22% 322 107% TOILET A113 E1 R3 6X6 F.H. - 75 26 35% 73 97% MULTI Alll E2 R2 12X6 F.H. - 200 44 22% 215 108% STORAGE A114 E3 R3 6X6 F.H. - 25 10 40% 32 128% EXHAUST 300 80 27% 320 107% (BALANCING DAMPER FOR EXHAUST REGISTER #E3 IS IN A FULL CLOSED POSITION, NO NOISE OR DRAFTS OBSERVED. UNIT RUNS AT A LOWER SPEED AND THEN RAMPS UP TO BALANCED SPEED WHEN CO2 SENSOR IS ACTIVATED. (FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 24 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B101 SUPPLY ERV-RES B101 EXHAUST EQUIP. LOCATION BLDG B LVL 1 UNIT B101 BLDG B LVL 1 UNIT B101 AREA SERVED UNIT B101 UNIT B101 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 90 90 ACTUAL CFM 94 92 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 80CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.0 1.1 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG B LVL 1 B101 NO. 1 THERMAL CODE SIZE S1 4" AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 22 OF DESIGN 1100/0 BLDG B LVL 1 B101 2 S1 4" F.H. - 20 27 135% 20 1000/0 BLDG B LVL 1 B101 3 S1 4" F.H. - 20 26 130% 21 1050/0 BLDG B LVL 1 B101 4 S1 4" F.H. - 30 22 73% 31 103% SUPPLY 90 100 1110/0 94 104% BLDG B LVL 1 B101 E1 Rl 6" F.H. - 40 47 1180/0 40 1000/0 BLDG B LVL 1 B101 E2 Rl 6" F.H. - 50 45 900/0 52 104% EXHAUST 90 92 102% 92 102% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 25 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B102 SUPPLY ERV-RES B102 EXHAUST EQUIP. LOCATION BLDG B LVL 1 UNIT B102 BLDG B LVL 1 UNIT B102 AREA SERVED UNIT B102 UNIT B102 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 74 71 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG B LVL 1 B102 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 23 1150/0 FPM CFM 20 OF DESIGN 1000/0 BLDG B LVL 1 B102 2 S1 4" F.H. - 20 28 140% 22 1100/0 BLDG B LVL 1 B102 3 Sl 4" F.H. - 30 25 83% 32 107% SUPPLY 70 76 1090/0 74 106% BLDG B LVL 1 B102 E1 Rl 4" F.H. - 70 63 900/0 71 1010/0 EXHAUST 70 63 900/0 71 1010/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 26 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B103 SUPPLY ERV-RES B103 EXHAUST EQUIP. LOCATION BLDG B LVL 1 UNIT B103 BLDG B LVL 1 UNIT B103 AREA SERVED UNIT B103 UNIT B103 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 50 50 ACTUAL CFM 51 49 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 50 CFM 60CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.7 0.7 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED NO. BLDG B LVL 1 B103 1 THERMAL THERMAL CODE SIZE AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN Sl 4" F.H. - 20 26 130% 21 1050/0 BLDG B LVL 1 B103 2 Sl 4" F.H. - 30 28 93% 30 1000/0 SUPPLY 50 54 1080/0 51 102% BLDG B LVL 1 B103 E1 Rl 4" F.H. - 50 47 94% 49 98% EXHAUST 50 47 94% 49 98% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 27 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B104 SUPPLY ERV-RES B104 EXHAUST EQUIP. LOCATION BLDG B LVL 1 UNIT B104 BLDG B LVL 1 UNIT B104 AREA SERVED UNIT B104 UNIT B104 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 50 50 ACTUAL CFM 53 49 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 50 CFM 60CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.7 0.7 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED NO. BLDG B LVL 1 B104 1 THERMAL THERMAL CODE SIZE AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN Sl 4" F.H. - 20 26 130% 22 1100/0 BLDG B LVL 1 B104 2 Sl 4" F.H. - 30 29 97% 31 103% SUPPLY 50 55 1100/0 53 106% BLDG B LVL 1 B104 E1 Rl 6" F.H. - 50 43 86% 49 98% EXHAUST 50 43 86% 49 98% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 28 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C101 SUPPLY ERV-RES C101 EXHAUST EQUIP. LOCATION BLDG C LVL 1 UNIT C101 BLDG C LVL 1 UNIT C101 AREA SERVED UNIT C101 UNIT C101 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31101 • 31101 DESIGN CFM 70 70 ACTUAL CFM 76 74 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 1 C101 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 29 145% FPM CFM 22 OF DESIGN 1100/0 BLDG C LVL 1 C101 2 S1 6X4 F.H. - 20 26 130% 21 1050/0 BLDG C LVL 1 C101 3 S1 6X4 F.H. - 30 27 900/0 33 1100/0 SUPPLY 70 82 117% 76 1090/0 BLDG C LVL 1 C101 E1 Rl 6X6 F.H. - 70 55 79% 74 106% EXHAUST 70 55 1 79% 74 1 106% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 29 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C102 SUPPLY ERV-RES C102 EXHAUST EQUIP. LOCATION BLDG C LVL 1 UNIT C102 BLDG C LVL 1 UNIT C102 AREA SERVED UNIT C102 UNIT C102 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31101 • 31101 DESIGN CFM 70 70 ACTUAL CFM 74 72 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 1 C102 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 21 OF DESIGN 1050/0 BLDG C LVL 1 C102 2 S1 6X4 F.H. - 20 27 135% 21 1050/0 BLDG C LVL 1 C102 3 S1 6X4 F.H. - 30 31 103% 32 107% SUPPLY 70 84 120% 74 106% BLDG C LVL 1 C102 E1 Rl 6X6 F.H. - 70 83 1190/0 72 103% EXHAUST 70 83 1 119% 72 1 1030/ FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 30 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C103 SUPPLY ERV-RES C103 EXHAUST EQUIP. LOCATION BLDG C LVL 1 UNIT C103 BLDG C LVL 1 UNIT C103 AREA SERVED UNIT C103 UNIT C103 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 74 70 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 80CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.0 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 1 C103 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 28 140% FPM CFM 21 OF DESIGN 1050/0 BLDG C LVL 1 C103 2 S1 6X4 F.H. - 20 26 130% 21 1050/0 BLDG C LVL 1 C103 3 S1 6X4 F.H. - 30 31 103% 32 107% SUPPLY 70 85 121% 74 106% BLDG C LVL 1 C103 E1 Rl 6X6 F.H. - 70 83 1190/0 70 1000/0 EXHAUST 70 83 1 119% 70 1 1000/ FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 31 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C104 SUPPLY ERV-RES C104 EXHAUST EQUIP. LOCATION BLDG C LVL 1 UNIT C104 BLDG C LVL 1 UNIT C104 AREA SERVED UNIT C104 UNIT C014 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31101 • 31101 DESIGN CFM 90 90 ACTUAL CFM 94 95 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 80CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.0 1.1 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 1 C104 NO. 1 THERMAL CODE SIZE S1 6X4 AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 24 120% FPM CFM 20 OF DESIGN 1000/0 BLDG C LVL 1 C104 2 S1 6X4 F.H. - 20 23 1150/0 21 1050/0 BLDG C LVL 1 C104 3 S1 6X4 F.H. - 20 28 140% 21 1050/0 BLDG C LVL 1 C104 4 S1 6X4 F.H. - 30 51 170% 32 107% SUPPLY 90 126 140% 94 104% BLDG C LVL 1 C104 E1 Rl 6X6 F.H. - 40 55 138% 42 105% BLDG C LVL 1 C104 E2 Rl 6X6 F.H. - 50 57 114% 53 106% EXHAUST 90 112 124% 95 106% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 32 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D101 SUPPLY ERV-RES D101 EXHAUST EQUIP. LOCATION BLDG D LVL 1 UNIT D101 BLDG D LVL 1 UNIT D101 AREA SERVED UNIT D101 UNIT D101 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 60 50 ACTUAL CFM 62 51 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 50 CFM 50 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.7 0.7 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED NO. BLDG D LVL 1 D101 1 THERMAL THERMAL CODE SIZE AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN Sl 4" F.H. - 30 35 117% 31 103% BLDG D LVL 1 D101 2 Sl 4" F.H. - 30 37 123% 31 103% SUPPLY 60 72 120% 62 103% BLDG D LVL 1 D101 E1 Rl 6" F.H. - 50 82 164% 51 102% EXHAUST 50 82 164% 51 102% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 33 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D102 SUPPLY ERV-RES D102 EXHAUST EQUIP. LOCATION BLDG D LVL 1 UNIT D102 BLDG D LVL 1 UNIT D102 AREA SERVED UNIT D102 UNIT D102 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 74 68 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 1 D102 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 27 135% FPM CFM 20 OF DESIGN 1000/0 BLDG D LVL 1 D102 2 S1 4" F.H. - 20 28 140% 22 1100/0 BLDG D LVL 1 D102 3 Sl 4" F.H. - 30 23 77% 32 107% SUPPLY 70 78 1110/0 74 106% BLDG D LVL 1 D102 E1 Rl 6" F.H. - 70 96 137% 68 97% EXHAUST 70 96 1 137% 68 1 97% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 34 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D103 SUPPLY ERV-RES D103 EXHAUST EQUIP. LOCATION BLDG D LVL 1 UNIT D103 BLDG D LVL 1 UNIT D103 AREA SERVED UNIT D103 UNIT D103 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 74 72 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 1 D103 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 17 850/0 FPM CFM 20 OF DESIGN 1000/0 BLDG D LVL 1 D103 2 S1 4" F.H. - 20 25 125% 22 1100/0 BLDG D LVL 1 D103 3 Sl 4" F.H. - 30 32 107% 32 107% SUPPLY 70 74 106% 74 106% BLDG D LVL 1 D103 E1 Rl 6" F.H. - 70 62 89% 72 103% EXHAUST 70 62 1 89% 72 1 1030/ FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 35 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D104 SUPPLY ERV-RES D104 EXHAUST EQUIP. LOCATION BLDG D LVL 1 UNIT D104 BLDG D LVL 1 UNIT D104 AREA SERVED UNIT D104 UNIT D104 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 73 69 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 1 D104 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 21 OF DESIGN 1050/0 BLDG D LVL 1 D104 2 S1 4" F.H. - 20 27 135% 21 1050/0 BLDG D LVL 1 D104 3 Sl 4" F.H. - 30 24 80% 31 103% SUPPLY 70 76 1090/0 73 104% BLDG D LVL 1 D104 E1 Rl 6" F.H. - 70 98 140% 69 990/0 EXHAUST 70 98 1 140% 69 1 99% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 36 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D105 SUPPLY ERV-RES D105 EXHAUST EQUIP. LOCATION BLDG D LVL 1 UNIT D105 BLDG D LVL 1 UNIT D105 AREA SERVED UNIT D105 UNIT D105 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 74 71 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 1 D105 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 21 OF DESIGN 1050/0 BLDG D LVL 1 D105 2 S1 4" F.H. - 20 28 140% 21 1050/0 BLDG D LVL 1 D105 3 Sl 6" F.H. - 30 22 73% 32 107% SUPPLY 70 76 1090/0 74 106% BLDG D LVL 1 D105 E1 Rl 6" F.H. - 70 82 117% 71 1010/0 EXHAUST 70 82 1 117% 71 1 1010/ FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 37 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D106 SUPPLY ERV-RES D106 EXHAUST EQUIP. LOCATION BLDG D LVL 1 UNIT D106 BLDG D LVL 1 UNIT D106 AREA SERVED UNIT D106 UNIT D106 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 90 90 ACTUAL CFM 95 93 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 90 CFM 100 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.2 1.3 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 1 D106 NO. 1 THERMAL CODE SIZE S1 4" AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 28 140% FPM CFM 21 OF DESIGN 1050/0 BLDG D LVL 1 D106 2 S1 4" F.H. - 20 28 140% 21 1050/0 BLDG D LVL 1 D106 3 S1 4" F.H. - 20 18 900/0 22 1100/0 BLDG D LVL 1 D106 4 S1 4" F.H. - 30 42 140% 31 103% SUPPLY 90 116 129% 95 106% BLDG D LVL 1 D106 E1 Rl 6" F.H. - 50 51 102% 51 102% BLDG D LVL 1 D106 E2 Rl 6" F.H. - 40 42 1050/0 42 105% EXHAUST 90 93 103% 93 103% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 38 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES A201 SUPPLY ERV-RES A201 EXHAUST EQUIP. LOCATION BLDG A LVL 2 UNIT A201 BLDG A LVL 2 UNIT A201 AREA SERVED UNIT A201 UNIT A201 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 90 90 ACTUAL CFM 92 97 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 80CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.1 1.2 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG A LVL 2 A201 NO. 1 THERMAL CODE SIZE S1 6X4 AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 20 OF DESIGN 1000/0 BLDG A LVL 2 A201 2 S1 6X4 F.H. - 20 23 1150/0 21 1050/0 BLDG A LVL 2 A201 3 S1 6X4 F.H. - 20 24 120% 20 1000/0 BLDG A LVL 2 A201 4 S1 6X4 F.H. - 30 26 87% 31 103% SUPPLY 90 98 1090/0 92 102% BLDG A LVL 2 A201 E1 Rl 6X6 F.H. - 40 53 133% 44 1100/0 BLDG A LVL 2 A201 E2 Rl 6X6 F.H. - 50 41 82% 53 106% EXHAUST 90 94 104% 97 108% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 39 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES A202 SUPPLY ERV-RES A202 EXHAUST EQUIP. LOCATION BLDG A LVL 2 UNIT A202 BLDG A LVL 2 UNIT A202 AREA SERVED UNIT A202 UNIT A202 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 73 73 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG A LVL 2 A202 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 27 135% FPM CFM 21 OF DESIGN 1050/0 BLDG A LVL 2 A202 2 S1 6X4 F.H. - 20 24 120% 22 1100/0 BLDG A LVL 2 A202 3 S1 6X4 F.H. - 30 26 87% 30 1000/0 SUPPLY 70 77 1100/0 73 104% BLDG A LVL 2 A202 E1 Rl 6X6 F.H. - 70 65 93% 73 104% EXHAUST 70 65 1 93% 73 1 1040/ FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 40 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES A203 SUPPLY ERV-RES A203 EXHAUST EQUIP. LOCATION BLDG A LVL 2 UNIT A203 BLDG A LVL 2 UNIT A203 AREA SERVED UNIT A203 UNIT A203 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 72 69 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 60CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG A LVL 2 A203 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 22 OF DESIGN 1100/0 BLDG A LVL 2 A203 2 S1 6X4 F.H. - 20 24 120% 20 1000/0 BLDG A LVL 2 A203 3 S1 6X4 F.H. - 30 23 77% 30 1000/0 SUPPLY 70 73 104% 72 103% BLDG A LVL 2 A203 E1 Rl 6X6 F.H. - 70 59 84% 69 990/0 EXHAUST 70 59 1 84% 69 1 99% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 41 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES A204 SUPPLY ERV-RES A204 EXHAUST EQUIP. LOCATION BLDG A LVL 2 UNIT A204 BLDG A LVL 2 UNIT A204 AREA SERVED UNIT A204 UNIT A204 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 73 69 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 60CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG A LVL 2 A204 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 22 OF DESIGN 1100/0 BLDG A LVL 2 A204 2 S1 6X4 F.H. - 20 25 125% 20 1000/0 BLDG A LVL 2 A204 3 S1 6X4 F.H. - 30 21 70% 31 103% SUPPLY 70 72 103% 73 104% BLDG A LVL 2 A204 E1 Rl 6X6 F.H. - 70 82 117% 69 990/0 EXHAUST 70 82 1 117% 69 1 99% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 42 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES A205 SUPPLY ERV-RES A205 EXHAUST EQUIP. LOCATION BLDG A LVL 2 UNIT A205 BLDG A LVL 2 UNIT A205 AREA SERVED UNIT A205 UNIT A205 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 90 90 ACTUAL CFM 97 89 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.9 1.2 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG A LVL 2 A205 NO. 1 THERMAL CODE SIZE S1 6X4 AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 21 OF DESIGN 1050/0 BLDG A LVL 2 A205 2 S1 6X4 F.H. - 20 24 120% 22 1100/0 BLDG A LVL 2 A205 3 S1 6X4 F.H. - 20 24 120% 21 1050/0 BLDG A LVL 2 A205 4 S1 6X4 F.H. - 30 26 87% 33 1100/0 SUPPLY 90 100 1110/0 97 1080/0 BLDG A LVL 2 A205 E1 Rl 6X6 F.H. - 40 52 130% 42 105% BLDG A LVL 2 A205 E2 Rl 6X6 F.H. - 50 40 80% 47 94% EXHAUST 90 92 102% 89 990/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 43 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B201 SUPPLY ERV-RES B201 EXHAUST EQUIP. LOCATION BLDG B LVL 2 UNIT B201 BLDG B LVL 2 UNIT B201 AREA SERVED UNIT B201 UNIT B201 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 90 90 ACTUAL CFM 93 91 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 80CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.0 1.1 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG B LVL 2 B201 NO. 1 THERMAL CODE SIZE S1 4" AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 29 145% FPM CFM 20 OF DESIGN 1000/0 BLDG B LVL 2 B201 2 S1 4" F.H. - 20 25 125% 20 1000/0 BLDG B LVL 2 B201 3 S1 4" F.H. - 20 24 120% 22 1100/0 BLDG B LVL 2 B201 4 S1 4" F.H. - 30 22 73% 31 103% SUPPLY 90 100 1110/0 93 103% BLDG B LVL 2 B201 E1 Rl 6" F.H. - 40 48 120% 42 105% BLDG B LVL 2 B201 E2 Rl 6" F.H. - 50 45 900/0 49 98% EXHAUST 90 93 103% 91 1010/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 44 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B202 SUPPLY ERV-RES B202 EXHAUST EQUIP. LOCATION BLDG B LVL 2 UNIT B202 BLDG B LVL 2 UNIT B202 AREA SERVED UNIT B202 UNIT B202 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 71 73 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 60CFM 80CFM STATIC SETTING N. /APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.7 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG B LVL 2 B202 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 20 OF DESIGN 1000/0 BLDG B LVL 2 B202 2 S1 4" F.H. - 20 27 135% 20 1000/0 BLDG B LVL 2 B202 3 Sl 4" F.H. - 30 22 73% 31 103% SUPPLY 70 74 106% 71 1010/0 BLDG B LVL 2 B202 E1 Rl 6" F.H. - 70 62 89% 73 104% EXHAUST 70 62 89% 73 104% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 45 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B203 SUPPLY ERV-RES B203 EXHAUST EQUIP. LOCATION BLDG B LVL 2 UNIT B203 BLDG B LVL 2 UNIT B203 AREA SERVED UNIT B203 UNIT B203 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 50 50 ACTUAL CFM 52 51 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 50 CFM 60CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED NO. BLDG B LVL 2 B203 1 THERMAL THERMAL CODE SIZE AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN Sl 4" F.H. - 20 28 140% 20 1000/0 BLDG B LVL 2 B203 2 Sl 4" F.H. - 30 26 87% 32 107% SUPPLY 50 54 1080/0 52 104% BLDG B LVL 2 B203 E1 Rl 4" F.H. - 50 45 900/0 51 102% EXHAUST 50 45 900/0 51 102% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 46 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B204 SUPPLY ERV-RES B204 EXHAUST EQUIP. LOCATION BLDG B LVL 2 UNIT B204 BLDG B LVL 2 UNIT B204 AREA SERVED UNIT B204 UNIT B204 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 50 50 ACTUAL CFM 54 52 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 50 CFM 50 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.7 0.7 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED NO. BLDG B LVL 2 B204 1 THERMAL THERMAL CODE SIZE AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN Sl 4" F.H. - 20 26 130% 21 1050/0 BLDG B LVL 2 B204 2 Sl 4" F.H. - 30 28 93% 33 1100/0 SUPPLY 50 54 1080/0 54 1080/0 BLDG B LVL 2 B204 E1 Rl 4" F.H. - 50 63 126% 52 104% EXHAUST 50 63 126% 52 104% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 47 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C201 SUPPLY ERV-RES C201 EXHAUST EQUIP. LOCATION BLDG C LVL 2 UNIT C201 BLDG C LVL 2 UNIT C201 AREA SERVED UNIT C201 UNIT C201 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 74 77 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.9 1.0 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 2 C201 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 21 OF DESIGN 1050/0 BLDG C LVL 2 C201 2 S1 6X4 F.H. - 20 26 130% 20 1000/0 BLDG C LVL 2 C201 3 S1 6X4 F.H. - 30 27 900/0 33 1100/0 SUPPLY 70 78 1110/0 74 106% BLDG C LVL 2 C201 E1 Rl 6X6 F.H. - 70 61 87% 77 1100/0 EXHAUST 70 61 87% 77 1100/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 48 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C202 SUPPLY ERV-RES C202 EXHAUST EQUIP. LOCATION BLDG C LVL 2 UNIT C202 BLDG C LVL 2 UNIT C202 AREA SERVED UNIT C202 UNIT C202 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 75 68 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 2 C202 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 22 OF DESIGN 1100/0 BLDG C LVL 2 C202 2 S1 6X4 F.H. - 20 25 125% 20 1000/0 BLDG C LVL 2 C202 3 S1 6X4 F.H. - 30 24 80% 33 1100/0 SUPPLY 70 75 107% 75 107% BLDG C LVL 2 C202 E1 Rl 6X6 F.H. - 70 56 80% 68 97% EXHAUST 70 56 80% 68 97% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 49 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C203 SUPPLY ERV-RES C203 EXHAUST EQUIP. LOCATION BLDG C LVL 2 UNIT C203 BLDG C LVL 2 UNIT C203 AREA SERVED UNIT C203 UNIT C203 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31023 • 31023 DESIGN CFM 70 70 ACTUAL CFM 74 69 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.9 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 2 C203 NO. 1 THERMAL CODE SIZE AK 51 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 28 140% FPM CFM 21 OF DESIGN 1050/0 BLDG C LVL 2 C203 2 S1 6X4 F.H. - 20 25 125% 20 1000/0 BLDG C LVL 2 C203 3 S1 6X4 F.H. - 30 26 87% 33 1100/0 SUPPLY 70 79 113% 74 106% BLDG C LVL 2 C203 E1 Rl 6X6 F.H. - 70 61 87% 69 990/0 EXHAUST 70 61 87% 69 990/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 50 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C204 SUPPLY ERV-RES C204 EXHAUST EQUIP. LOCATION BLDG C LVL 2 UNIT C204 BLDG C LVL 2 UNIT C204 AREA SERVED UNIT C204 UNIT C204 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 90 90 ACTUAL CFM 94 94 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 80CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.1 1.1 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 2 C204 NO. 1 THERMAL CODE SIZE S1 6X4 AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 22 OF DESIGN 1100/0 BLDG C LVL 2 C204 2 S1 6X4 F.H. - 20 26 130% 20 1000/0 BLDG C LVL 2 C204 3 S1 6X4 F.H. - 20 24 120% 21 1050/0 BLDG C LVL 2 C204 4 S1 6X4 F.H. - 30 28 93% 31 103% SUPPLY 90 103 114% 94 104% BLDG C LVL 2 C204 E1 Rl 6X6 F.H. - 40 52 130% 44 1100/0 BLDG C LVL 2 C204 E2 Rl 6X6 F.H. - 50 54 1080/0 50 1000/0 EXHAUST 90 106 1180/0 94 104% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 51 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D201 SUPPLY ERV-RES D201 EXHAUST EQUIP. LOCATION BLDG D LVL 2 UNIT D201 BLDG D LVL 2 UNIT D201 AREA SERVED UNIT D201 UNIT D201 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31101 • 31101 DESIGN CFM 70 70 ACTUAL CFM 74 72 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 2 D201 NO. 1 THERMAL CODE SIZE AK S1 6X4 4" • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 21 OF DESIGN 1050/0 BLDG D LVL 2 D201 2 S1 6X4 4" - 20 28 140% 22 1100/0 BLDG D LVL 2 D201 3 S1 6X4 6" - 30 23 77% 31 103% SUPPLY 70 77 1100/0 74 106% BLDG D LVL 2 D201 E1 Rl 6X6 6" - 70 64 910/0 72 103% EXHAUST 70 64 910/0 72 103% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 52 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D202 SUPPLY ERV-RES D202 EXHAUST EQUIP. LOCATION BLDG D LVL 2 UNIT D202 BLDG D LVL 2 UNIT D202 AREA SERVED UNIT D202 UNIT D202 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 74 70 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 2 D202 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 24 120% FPM CFM 20 OF DESIGN 1000/0 BLDG D LVL 2 D202 2 S1 4" F.H. - 20 27 135% 22 1100/0 BLDG D LVL 2 D202 3 Sl 6" F.H. - 30 28 93% 32 107% SUPPLY 70 79 113% 74 106% BLDG D LVL 2 D202 E1 Rl 6" F.H. - 70 81 116% 70 1000/0 EXHAUST 70 81 1 116% 70 1 1000/ FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 53 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D203 SUPPLY ERV-RES D203 EXHAUST EQUIP. LOCATION BLDG D LVL 2 UNIT D203 BLDG D LVL 2 UNIT D203 AREA SERVED UNIT D203 UNIT D203 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31101 • 31101 DESIGN CFM 70 70 ACTUAL CFM 74 69 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 2 D203 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 29 145% FPM CFM 21 OF DESIGN 1050/0 BLDG D LVL 2 D203 2 S1 4" F.H. - 20 26 130% 21 1050/0 BLDG D LVL 2 D203 3 Sl 6" F.H. - 30 26 87% 32 107% SUPPLY 70 81 116% 74 106% BLDG D LVL 2 D203 E1 Rl 6" F.H. - 70 60 86% 69 990/0 EXHAUST 70 60 1 86% 69 1 99% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 54 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D204 SUPPLY ERV-RES D204 EXHAUST EQUIP. LOCATION BLDG D LVL 2 UNIT D204 BLDG D LVL 2 UNIT D204 AREA SERVED UNIT D204 UNIT D204 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 75 73 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 2 D204 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 22 OF DESIGN 1100/0 BLDG D LVL 2 D204 2 S1 4" F.H. - 20 27 135% 22 1100/0 BLDG D LVL 2 D204 3 Sl 6" F.H. - 30 28 93% 31 103% SUPPLY 70 80 114% 75 107% BLDG D LVL 2 D204 E1 Rl 6" F.H. - 70 66 94% 73 104% EXHAUST 70 66 1 94% 73 1 1040/ FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 55 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D205 SUPPLY ERV-RES D205 EXHAUST EQUIP. LOCATION BLDG D LVL 2 UNIT D205 BLDG D LVL 2 UNIT D205 AREA SERVED UNIT D205 UNIT D205 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 75 71 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 2 D205 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 21 OF DESIGN 1050/0 BLDG D LVL 2 D205 2 S1 4" F.H. - 20 27 135% 22 1100/0 BLDG D LVL 2 D205 3 Sl 6" F.H. - 30 29 97% 32 107% SUPPLY 70 82 117% 75 107% BLDG D LVL 2 D205 E1 Rl 6" F.H. - 70 83 1190/0 71 1010/0 EXHAUST 70 83 1 119% 71 1 1010/ FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 56 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D206 SUPPLY ERV-RES D206 EXHAUST EQUIP. LOCATION BLDG D LVL 2 UNIT D206 BLDG D LVL 2 UNIT D206 AREA SERVED UNIT D206 UNIT D206 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 90 90 ACTUAL CFM 95 90 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 90 CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.2 1.2 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 2 D206 NO. 1 THERMAL CODE SIZE S1 4" AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 21 OF DESIGN 1050/0 BLDG D LVL 2 D206 2 S1 4" F.H. - 20 28 140% 21 1050/0 BLDG D LVL 2 D206 3 S1 4" F.H. - 20 27 135% 22 1100/0 BLDG D LVL 2 D206 4 S1 4" F.H. - 30 26 87% 31 103% SUPPLY 90 107 1190/0 95 106% BLDG D LVL 2 D206 E1 Rl 6" F.H. - 50 45 900/0 48 96% BLDG D LVL 2 D206 E2 Rl 6" F.H. - 40 46 1150/0 42 105% EXHAUST 90 91 1010/0 90 1000/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 57 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES A301 SUPPLY ERV-RES A301 EXHAUST EQUIP. LOCATION BLDG A LVL 3 UNIT A301 BLDG A LVL 3 UNIT A301 AREA SERVED UNIT A301 UNIT A301 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31101 • 31101 DESIGN CFM 90 90 ACTUAL CFM 93 93 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 80CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.1 1.2 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG A LVL 3 A301 NO. 1 THERMAL CODE SIZE S1 6X4 AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 21 OF DESIGN 1050/0 BLDG A LVL 3 A301 2 S1 6X4 F.H. - 20 23 1150/0 20 1000/0 BLDG A LVL 3 A301 3 S1 6X4 F.H. - 20 24 120% 21 1050/0 BLDG A LVL 3 A301 4 S1 6X4 F.H. - 30 26 87% 31 103% SUPPLY 90 98 1090/0 93 103% BLDG A LVL 3 A301 E1 Rl 6X6 F.H. - 40 53 133% 42 105% BLDG A LVL 3 A301 E2 Rl 6X6 F.H. - 50 41 82% 51 102% EXHAUST 90 94 104% 93 103% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 58 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES A302 SUPPLY ERV-RES A302 EXHAUST EQUIP. LOCATION BLDG A LVL 3 UNIT A302 BLDG A LVL 3 UNIT A302 AREA SERVED UNIT A302 UNIT A302 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 74 70 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 60CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG A LVL 3 A302 NO. 1 THERMAL CODE SIZE AK 51 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 27 135% FPM CFM 21 OF DESIGN 1050/0 BLDG A LVL 3 A302 2 S1 6X4 F.H. - 20 24 120% 20 1000/0 BLDG A LVL 3 A302 3 S1 6X4 F.H. - 30 26 87% 33 1100/0 SUPPLY 70 77 1100/0 74 106% BLDG A LVL 3 A302 E1 Rl 6X6 F.H. - 70 85 121% 70 1000/0 EXHAUST 70 85 121% 70 1000/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 59 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES A303 SUPPLY ERV-RES A303 EXHAUST EQUIP. LOCATION BLDG A LVL 3 UNIT A303 BLDG A LVL 3 UNIT A303 AREA SERVED UNIT A303 UNIT A303 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 73 73 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 60CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.7 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG A LVL 3 A303 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 20 OF DESIGN 1000/0 BLDG A LVL 3 A303 2 S1 6X4 F.H. - 20 26 130% 20 1000/0 BLDG A LVL 3 A303 3 S1 6X4 F.H. - 30 23 77% 33 1100/0 SUPPLY 70 74 106% 73 104% BLDG A LVL 3 A303 E1 Rl 6X6 F.H. - 70 84 120% 73 104% EXHAUST 70 84 120% 73 104% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 60 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES A304 SUPPLY ERV-RES A304 EXHAUST EQUIP. LOCATION BLDG A LVL 3 UNIT A304 BLDG A LVL 3 UNIT A304 AREA SERVED UNIT A304 UNIT A304 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31101 • 31101 DESIGN CFM 70 70 ACTUAL CFM 73 70 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 60CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG A LVL 3 A304 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 28 140% FPM CFM 22 OF DESIGN 1100/0 BLDG A LVL 3 A304 2 S1 6X4 F.H. - 20 24 120% 20 1000/0 BLDG A LVL 3 A304 3 S1 6X4 F.H. - 30 23 77% 31 103% SUPPLY 70 75 107% 73 104% BLDG A LVL 3 A304 E1 Rl 6X6 F.H. - 70 82 117% 70 1000/0 EXHAUST 70 82 117% 70 1000/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 61 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES A035 SUPPLY ERV-RES A305 EXHAUST EQUIP. LOCATION BLDG A LVL 3 UNIT A305 BLDG A LVL 3 UNIT A305 AREA SERVED UNIT A305 UNIT A305 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31101 • 31101 DESIGN CFM 90 90 ACTUAL CFM 20 93 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 80CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.1 1.2 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG A LVL 3 A305 NO. 1 THERMAL CODE SIZE S1 6X4 AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 24 120% FPM CFM 20 OF DESIGN 1000/0 BLDG A LVL 3 A305 2 S1 6X4 F.H. - 20 26 130% 21 1050/0 BLDG A LVL 3 A305 3 S1 6X4 F.H. - 20 25 125% 20 1000/0 BLDG A LVL 3 A305 4 S1 6X4 F.H. - 30 22 73% 32 107% SUPPLY 90 97 1080/0 93 103% BLDG A LVL 3 A305 E1 Rl 6X6 F.H. - 40 53 133% 41 103% BLDG A LVL 3 A305 E2 Rl 6X6 F.H. - 50 42 84% 52 104% EXHAUST 90 95 106% 93 103% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 62 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B301 SUPPLY ERV-RES B301 EXHAUST EQUIP. LOCATION BLDG B LVL 3 UNIT B301 BLDG B LVL 3 UNIT B301 AREA SERVED UNIT B301 UNIT B301 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 90 90 ACTUAL CFM 91 90 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 90 CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.1 1.1 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG B LVL 3 B301 NO. 1 THERMAL CODE SIZE S1 4" AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 20 OF DESIGN 1000/0 BLDG B LVL 3 B301 2 S1 4" F.H. - 20 27 135% 21 1050/0 BLDG B LVL 3 B301 3 S1 4" F.H. - 20 24 120% 21 1050/0 BLDG B LVL 3 B301 4 S1 4" F.H. - 30 24 80% 29 97% SUPPLY 90 101 112% 91 1010/0 BLDG B LVL 3 B301 E1 Rl 6" F.H. - 40 46 1150/0 42 105% BLDG B LVL 3 B301 E2 Rl 6" F.H. - 50 47 94% 48 96% EXHAUST 90 93 103% 90 1000/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 63 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B302 SUPPLY ERV-RES B302 EXHAUST EQUIP. LOCATION BLDG B LVL 3 UNIT B302 BLDG B LVL 3 UNIT B302 AREA SERVED UNIT B302 UNIT B302 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 71 71 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 60CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 1.0 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG B LVL 3 B302 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 27 135% FPM CFM 20 OF DESIGN 1000/0 BLDG B LVL 3 B302 2 S1 4" F.H. - 20 24 120% 20 1000/0 BLDG B LVL 3 B302 3 Sl 4" F.H. - 30 26 87% 31 103% SUPPLY 70 77 1100/0 71 1010/0 BLDG B LVL 3 B302 E1 Rl 6" F.H. - 70 61 87% 71 1010/0 EXHAUST 70 61 87% 71 1010/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 64 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B303 SUPPLY ERV-RES B303 EXHAUST EQUIP. LOCATION BLDG B LVL 3 UNIT B303 BLDG B LVL 3 UNIT B303 AREA SERVED UNIT B303 UNIT B303 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 50 50 ACTUAL CFM 51 50 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 50 CFM 50 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.7 0.7 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED NO. BLDG B LVL 3 B303 1 THERMAL THERMAL CODE SIZE AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN Sl 4" F.H. - 20 26 130% 20 1000/0 BLDG B LVL 3 B303 2 Sl 4" F.H. - 30 28 93% 31 103% SUPPLY 50 54 1080/0 51 102% BLDG B LVL 3 B303 E1 Rl 4" F.H. - 50 62 124% 50 1000/0 EXHAUST 50 62 124% 50 1000/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 65 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES B304 SUPPLY ERV-RES B304 EXHAUST EQUIP. LOCATION BLDG B LVL 3 UNIT B304 BLDG B LVL 3 UNIT B304 AREA SERVED UNIT B304 UNIT B304 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 50 50 ACTUAL CFM 52 49 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 50 CFM 50 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED NO. BLDG B LVL 3 B304 1 THERMAL THERMAL CODE SIZE AK • OF OF FPM CFM FPM CFM DESIGN FPM CFM DESIGN Sl 4" F.H. - 20 26 130% 20 1000/0 BLDG B LVL 3 B304 2 Sl 4" F.H. - 30 27 900/0 32 107% SUPPLY 50 53 106% 52 104% BLDG B LVL 3 B304 E1 Rl 4" F.H. - 50 59 1180/0 49 98% EXHAUST 50 59 1180/0 49 98% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 66 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C301 SUPPLY ERV-RES C301 EXHAUST EQUIP. LOCATION BLDG C LVL 3 UNIT C301 BLDG C LVL 3 UNIT C301 AREA SERVED UNIT C301 UNIT C301 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 73 70 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 3 C301 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 20 OF DESIGN 1000/0 BLDG C LVL 3 C301 2 S1 6X4 F.H. - 20 26 130% 20 1000/0 BLDG C LVL 3 C301 3 S1 6X4 F.H. - 30 27 900/0 33 1100/0 SUPPLY 70 78 1110/0 73 104% BLDG C LVL 3 C301 E1 Rl 6X6 F.H. - 70 85 121% 70 1000/0 EXHAUST 70 85 121% 70 1000/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 67 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C302 SUPPLY ERV-RES C302 EXHAUST EQUIP. LOCATION BLDG C LVL 3 UNIT C302 BLDG C LVL 3 UNIT C302 AREA SERVED UNIT C302 UNIT C302 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31023 • 31023 DESIGN CFM 70 70 ACTUAL CFM 75 75 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.9 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 3 C302 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 20 OF DESIGN 1000/0 BLDG C LVL 3 C302 2 S1 6X4 F.H. - 20 26 130% 22 1100/0 BLDG C LVL 3 C302 3 S1 6X4 F.H. - 30 24 80% 33 1100/0 SUPPLY 70 75 107% 75 107% BLDG C LVL 3 C302 E1 Rl 6X6 F.H. - 70 83 1190/0 75 107% EXHAUST 70 83 1190/0 75 107% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 68 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C303 SUPPLY ERV-RES C303 EXHAUST EQUIP. LOCATION BLDG C LVL 3 UNIT C303 BLDG C LVL 3 UNIT C303 AREA SERVED UNIT C303 UNIT C303 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 75 73 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.9 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 3 C303 NO. 1 THERMAL CODE SIZE AK S1 6X4 F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 22 OF DESIGN 1100/0 BLDG C LVL 3 C303 2 S1 6X4 F.H. - 20 24 120% 21 1050/0 BLDG C LVL 3 C303 3 S1 6X4 F.H. - 30 27 900/0 32 107% SUPPLY 70 76 1090/0 75 107% BLDG C LVL 3 C303 E1 Rl 6X6 F.H. - 70 92 131% 73 104% EXHAUST 70 92 131% 73 104% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 69 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES C304 SUPPLY ERV-RES C304 EXHAUST EQUIP. LOCATION BLDG C LVL 3 UNIT C304 BLDG C LVL 3 UNIT C304 AREA SERVED UNIT C304 UNIT C304 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31023 • 31023 DESIGN CFM 90 90 ACTUAL CFM 90 92 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 90 CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.2 1.2 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG C LVL 3 C304 NO. 1 THERMAL CODE SIZE S1 6X4 AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 20 OF DESIGN 1000/0 BLDG C LVL 3 C304 2 S1 6X4 F.H. - 20 27 135% 20 1000/0 BLDG C LVL 3 C304 3 S1 6X4 F.H. - 20 24 120% 19 950/0 BLDG C LVL 3 C304 4 S1 6X4 F.H. - 30 26 87% 31 103% SUPPLY 90 103 114% 90 1000/0 BLDG C LVL 3 C304 E1 Rl 6X6 F.H. - 40 33 83% 43 108% BLDG C LVL 3 C304 E2 Rl 6X6 F.H. - 50 62 124% 49 98% EXHAUST 90 95 106% 92 102% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 70 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D301 SUPPLY ERV-RES D301 EXHAUST EQUIP. LOCATION BLDG D LVL 3 UNIT D301 BLDG D LVL 3 UNIT D301 AREA SERVED UNIT D301 UNIT D301 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31023 • 31023 DESIGN CFM 70 70 ACTUAL CFM 71 73 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 3 D301 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 25 125% FPM CFM 20 OF DESIGN 1000/0 BLDG D LVL 3 D301 2 S1 4" F.H. - 20 28 140% 20 1000/0 BLDG D LVL 3 D301 3 Sl 6" F.H. - 30 24 80% 31 103% SUPPLY 70 77 1100/0 71 1010/0 BLDG D LVL 3 D301 E1 Rl 6" F.H. - 70 82 117% 73 104% EXHAUST 70 82 117% 73 104% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 71 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D302 SUPPLY ERV-RES D302 EXHAUST EQUIP. LOCATION BLDG D LVL 3 UNIT D302 BLDG D LVL 3 UNIT D302 AREA SERVED UNIT D302 UNIT D302 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 71 68 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 120 120 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 3 D302 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 26 130% FPM CFM 21 OF DESIGN 1050/0 BLDG D LVL 3 D302 2 S1 4" F.H. - 20 28 140% 19 950/0 BLDG D LVL 3 D302 3 Sl 6" F.H. - 30 23 77% 31 103% SUPPLY 70 77 1100/0 71 1010/0 BLDG D LVL 3 D302 E1 Rl 6" F.H. - 70 79 113% 68 97% EXHAUST 70 79 113% 68 97% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 72 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D303 SUPPLY ERV-RES D303 EXHAUST EQUIP. LOCATION BLDG D LVL 3 UNIT D303 BLDG D LVL 3 UNIT D303 AREA SERVED UNIT D303 UNIT D303 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 70 69 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 3 D303 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 28 140% FPM CFM 19 OF DESIGN 950/0 BLDG D LVL 3 D303 2 S1 4" F.H. - 20 24 120% 21 1050/0 BLDG D LVL 3 D303 3 Sl 6" F.H. - 30 26 87% 30 1000/0 SUPPLY 70 78 1110/0 70 1000/0 BLDG D LVL 3 D303 E1 Rl 6" F.H. - 70 81 116% 69 990/0 EXHAUST 70 81 116% 69 990/0 FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 73 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D304 SUPPLY ERV-RES D304 EXHAUST EQUIP. LOCATION BLDG D LVL 3 UNIT D304 BLDG D LVL 3 UNIT D304 AREA SERVED UNIT D304 UNIT D304 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31023 • 31023 DESIGN CFM 70 70 ACTUAL CFM 74 68 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 70 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.8 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 3 D304 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 23 1150/0 FPM CFM 21 OF DESIGN 1050/0 BLDG D LVL 3 D304 2 S1 4" F.H. - 20 27 135% 20 1000/0 BLDG D LVL 3 D304 3 Sl 6" F.H. - 30 26 87% 33 1100/0 SUPPLY 70 76 1090/0 74 106% BLDG D LVL 3 D304 E1 Rl 6" F.H. - 70 79 113% 68 97% EXHAUST 70 79 113% 68 97% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 74 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D305 SUPPLY ERV-RES D305 EXHAUST EQUIP. LOCATION BLDG D LVL 3 UNIT D305 BLDG D LVL 3 UNIT D305 AREA SERVED UNIT D305 UNIT D305 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 70 70 ACTUAL CFM 72 72 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 70 CFM 80CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 121 121 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 0.8 0.9 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 3 D305 NO. 1 THERMAL CODE SIZE AK S1 4" F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 28 140% FPM CFM 20 OF DESIGN 1000/0 BLDG D LVL 3 D305 2 S1 4" F.H. - 20 24 120% 21 1050/0 BLDG D LVL 3 D305 3 Sl 6" F.H. - 30 26 87% 31 103% SUPPLY 70 78 1110/0 72 103% BLDG D LVL 3 D305 E1 Rl 6" F.H. - 70 60 86% 72 103% EXHAUST 70 60 86% 72 103% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 75 of 102 40A- TESTING ANO Ca SERV•CES • • • HOUSING HOPE ELC FIELD APARTMENTS • • EDMONDS, WA ••• • 2230199 • BRYCEHURLBUT AABC UNIT DATA UNIT ID ERV-RES D306 SUPPLY ERV-RES D306 EXHAUST EQUIP. LOCATION BLDG D LVL 3 UNIT D306 BLDG D LVL 3 UNIT D306 AREA SERVED UNIT D306 UNIT D306 MANUFACTURER PANASONIC PANASONIC MODEL NUMBER FV-10VE2 FV-10VE2 SERIAL NUMBER 31012 • 31012 DESIGN CFM 90 90 ACTUAL CFM 93 86 T.S.P. "W.C. 0.40 0.40 TESTED SPEED 90 CFM 90 CFM STATIC SETTING N. / APPL. MOTOR DATA N. / APPL. MANUFACTURER PANASONIC PANASONIC HORSEPOWER 68 W 68 W NAMEPLATE VOLTS 120 120 TESTED VOLTS 119 119 NAMEPLATE AMPS 1.7 1.7 TESTED AMPS 1.1 1.1 MOTOR RPM VARIABLE VARIABLE SPEED 6 SPEED 6 SPEED PHASE / HZ 1/60 1/60 OVERLOAD SIZE AREA SERVED BLDG D LVL 3 D306 NO. 1 THERMAL CODE SIZE S1 4" AK F.H. • FPM CFM - 20 THERMAL OF FPM CFM DESIGN 27 135% FPM CFM 20 OF DESIGN 1000/0 BLDG D LVL 3 D306 2 S1 4" F.H. - 20 26 130% 21 1050/0 BLDG D LVL 3 D306 3 S1 4" F.H. - 20 25 125% 21 1050/0 BLDG D LVL 3 D306 4 S1 6" F.H. - 30 22 73% 31 103% SUPPLY 90 100 1110/0 93 103% BLDG D LVL 3 D306 E1 Rl 6" F.H. - 50 44 88% 47 94% BLDG D LVL 3 D306 E2 Rl 6" F.H. - 40 47 1180/0 39 98% EXHAUST 90 91 1010/0 86 96% FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA 10/09/2024 Page 76 of 102 GENERAL NOTES AW\ HOUSING HOPE 1. we keep hope alive LACES ALL. NDNLDNDITIOONED �� SPACES ALL E lxspLAEG .INS T""Tp l o) l a) 10 11 12 11 WITH IM INGM ININVFlNllGLAL.L UHONO 7 7 s WITH INO THHERMAL BRIDGING. S. FINEITIAUTaIANirvo,ELECTRAcTE FN DESIGNS cnEciiprve To lN000Rn AP G Doethwest PINES °UNIITS SHALL RE CONCEALED CEILINGN. WALL OR lrvO SURFACE .—.---.—.—. .—---.—.— .—.—.—.—.---.—.——.—.—.—.—.—. —. .—.—.— ARCHITECTS UIHANICAL CONTRACTOR SHALL ___ ___ _ _ IN TL REDpIRED FOR A a� EH -FIRE IIII DHopES MOTORD PUMPS ALL MANUFANS. Fa ET 12 j rocxlxaw MRF xisFxj IIII IIIII E\ OPE CLEARAN DES wR1ACTURE auTF`ra H"En"RE ° H I� ox-NOF ox RonFRT EEINF"si'sF N EII IF j GroaFT TLL BE LOCATED AWAY nT c IryasF Pr - PROVIDED.TATS SECURE OUR ESFOR w 'A - IIII FALSE RE DIINGS UCH ASSUNLIGOPERABLE 0 CUP'6F URN 91110 E G. AIpTE MINALLOCATIONSASSHOWNARE OitDINATE E%ACi LOCATIONS OF AIR ELEMERMENiS WGHHTS PIPING STRUCTURAL EQUIPMENT ® ® IIII CTUR, .BL,ecs o,F , CORRIDORoETC 577 j 05k�� Y 35F S15F� MF eNs»yR�N 7. PROVIDE I All MANUAL VOLUME DAMPERS ON IANCINCH DUGOR ATS TO PROVIIEE MEANDEVICES OF FAR AS POSSIBLE FR. . AIR EGUIREp !� ° FFICE F E .RUNRY IIII .a CTO BE PYE CATIONS FRVIiFs; ERNIIEllIPEl WITH REMOTE IFFs [-a7Fn[ UP H� SHALL �RS (YOUNG REGULATOR TYPE) CI ANYFLEEISLEDUCTWORKRUNSSHALL R. NOTALLEp WIT IN LENGTH ANpsHALL BE rvoTE.p RN 6H NO NINKpR SHARP B --- SENDSRpRNs - --- --- --- — --- — — — --- m E. NCLUDETpRNNGVANESGNALL REGTAN6pLAR pUGT ELBOWS ,U WHERE POSSIBLE ARCIDUTILIZING)])9U -,�.. j ' ' YEN}l _ — __$ - pEGREE ELBpWG W TH ppGTLENGTH wETWTERTHENOFLESSTHAN� L IIIII, ; o DIAMETER (OR EDpIVAIENT DWMETER) III III III: CONERACi RsxALLCGGRpNATEW Ll RD ITEDT TO MEET THE C E A A NC � � 0 v o RMINATIONS MEETTHECLEARANDE9 I IIIIII W w HANICAH CODE°TO OPERABLE NAL _ „ A � IIII o oa pMESTrvTAKEGANpMEpnAN AL w = C CO Z W CD N -4 CD m _IIII �- o -,.-'-�--- ------ I IIIIIII N OC - —1 U Q N NFD =1 O J cFIBLE1 cF331BLEl 3sIIII IIII � Lu � m o _ o -I aFv sF sareF = to❑F. _- CONSTRUCTION IIII II .o II DOCUMENTS 77A❑ j - � III ISSUE OATS JAN. 3, 2023 o ❑ jI DID TI � it RFVUR.NwCHEDpLE FlRE RIBFR III .III ) IIIII U6I1413023 CCpM�rRESU o a III=IIIII HELI ) owx wFe��HPwH) III11I FIRE RISER B B` 27 F7 CHro„3CP3 RFIC36 IF I11=1 � HEYPUN - - - - =1 - - --- _--jll� D DOOR -III 0 R R R III CONTENTS MECHANICAL - - = FLOOR PLAN - 20 23 24 - H 25 == LEVEL 1 - \� =III— I I I I 1 BUILDING A& B II -II =III= CHEIRED OR—, PROJECT NO 2027037.00 MECHANICAL FLOOR PLAN - LEVEL 1 - BLDG A & B N� M2.11 rre-r-o• 1 2 ` aaJ o ou :W\ HOUSING GENERAL NOTES I HOPE we keep trope alive 1. ALL A ALL. F , ,2 2. REFRIGERANT PIPING SHALL BE INSULATED1 INCLUDING CONTIN TLAD LRIDGNG. Ii LSLV,.<r/�SIR RTS WITH SUPPO 'DGO, ESIGNS co TiONNSIPAND CONDENSATE PPINc k n — — ---- — — — — — — — — — — — — — LhwC BT I. EDNONS To NO..R HEAT / ARCHITECTS • REMREPIND WALL ORACEILING (NO SUURFACE EXHAFUNSFTALOUVERI I I{ NGI BID 9 "CALCOORDINATE PROVOISION OCONTRACT"F ALL REQUIRED I y R EQUIPMENT LOCATED lJtllJ 111 ABOVE CEILINGS, INCLUDING BUT NOT p-MAI A. I \ LIMITED TO HEAT PUMPS BALANCING M LAMPDEVICESD. ANDDD MPENE T y,uxrez ancF � i Ec OPE RoCFROM�000ESFOREQUIPM NTARE° o FAINSE EADINGsSUCHASOPERABLEA i • :: e^ wB. GT UNIGHT. TC. ARE ID li E. AIR OPPRERMINALLOCATIONS OCA o aA SHO INTS LIGHTS PIPINGS, EQUIPMENFAL - AUNG -x°Ew U.SFpTvpF6 BLY TEEM AUND S LLLL�®� ELEMENTS LIGHTS UND ❑ ® N �95F71 BE1IPFB 7. LL BRANCH DUCTS TO ROVIDE MEANS OF _ ® :.BIDER :.BEoFB I BALANCING FOR AL RMINA LUN oSSU EFMPoaMRTEMIPAL a,-x1l.o'ROBOF I°E _-----_- - - - - ---------- RED RED R BERVED. NY i0 III IN ACCESSIBLE LGCATIONS i BHALL BE EOUIPED R REMOTE HEAVY METALRIGIDa- -- -- ADTBATDRB YDBNGREGBATDRTYPE' RDNNDDNDTBDNLY C. ANY FLEXIBLE BUCTw.RR RUNS SHALL r HOT EXCEEDBINLENGTHANDBHALLBE FOR DRYER EXHAUST. II IIIIIII II IIIIIII I m INSTALL. WITH NO RN, OR I PaoVDELOUVEREDDOOR a+ W SENDS"RNs. DRYER'ENTUPToaooF D. N NING VANES ON ALL RM INAH Vk FURRED OEXHAU T //�� E rvcuinR°uGTELeows. WALL(2.e)TYPB) iii a— N 3 DEGRE ELBOWS WIiTH' ouaj'zINGTH so O I— w cn III EXHAUST DUCT A uP TO RooF CONTRACTOR ET NTAKE ARE DPS IN 1 III=III uol) 0 0 �B mA REEFER LENGTH I'r°TArcELOU ER BETWEEN THEN of LESS THAN zR METER (OR EOuIvuENT DwMETER� DRYER MANE UP AIR = o ,,. CONTRACT TO`ENSLCooaowATE WITH TArcE LOUVER O NECT TO ErvsuREAU EznnusT IN BE LA _____ _____ - r----v TERMINATIONS MEET THE CLEARANCES o o ; W 'M REDUIRED INTxE2nie IUTERAALE AL I p i oMEGn'R INGGDETDGPERABLE I IIIIIII i� J l� (9 OPENINGS, INTAKES, AND MECHANICAL r - � EQUIPMENT. 1 _ W o-------------- ------ - - -- ------ - ----I N EuFB B6oEB �EoEB BuFB BoEB ruLE J d D 2 W Q -97=- - - - ❑ _ CONSTRUCTION DOCUMENTS g.,.II a JAN.3, 2023 NECH Hk esf ER KEYPILAN D1i0 EH -FIRE F I uxptian .---.--—.---.— — — — OSI,A/2028 CCD Wt LL �T � ROVIDE LOUVERED DOOR �5 16 17 16 19 20 CONTENTS °0 IJ.J MECHANICAL - FLOOR PLAN - LEVEL 1- BUILDING C & D CHECKED Ch.- NO 2021031.00 ANICAL FLOOR PLAN - LEVEL 1 - BLDG C & D NE)M n ME CH2.1 2 N O (0o m m Co O O � O N GENERAL NOTES B. EFRIGERANTLPIPI GS ALL BE INSULATED INCLUOIING CONTIRUSOUN INSULATION AT SUPPORTS WITH NO THERMAL BRIG ING. REFR CON ECTiONS, ANo CONDENSATE PIPING AND x cepN3 TO IN D00R HEAT PUMPS UNITSL BE CONCEALED BEHINDWALLOR CLEILING (NO SURFACE 4. A COORDINATE PROVISION OF ALL REQUIRED R EQUIPMENT LOCATED CEILINGS IN. LLIIM ITED TOO EAT P MLPSIBAANCINGT DEVICES, M OTORIZED DAMPERS, FIRE T ALL CLEARANCES FORE"U'p XEUM AR'ED E. THERMOSTATSSNiNL SOILIRCESEFOR WINDOWS o'RECTAUNUlGHT IF A. AIR TERMINAL LOCATIONS AS SHOWN ARE RDINATEEEXACT LLOCATTIIONS. FLAIR COORDINATE WITH cFILINGS, STRUCTURAL ELEM ENTS LIGHTS PIPING, EQUIPMENT, ETC ALL BNCRHRCPER.LEIAVIPOF BALVOLUME A.A"NULNCING TOVLUMSHALL PROVIDE 'AMCIPER'CA BE FAR AS POSSIBLE FROM AIR T MR"U"RED e EDLIPEO WITH EOOLocano 6 ACTUATORS rOUNG REcUATOR TVPE) DE6 IN LENGTTH ANios LBE �NSTALLE� WITH NO KINK OR SHARP CRN R. INCLUDE TUUING VANES ON ALL RECTAN=R DUCTNG 12) SB ELBOWS lo. WHERE DEGREE s wiTxl .LOT LENGTH BETWEEN EQUIVALENT DIAMETER) 11. DIAMETER SHALL OOR ORDINATE WITH ARCHITECT ALL EXHA EST aFRul'RED 11 DECLINATIONS IEIII R INTERNATIONALS EENINGS, IN`ASES,A OPERABLE EQUIPMENT. �� T Y AkF\ HOUSING L� chwest J ARCHITECTS EGOTOPE r�n�><rrru•Ior■n� 41 I sB� Ds1412023 CCDBDI �o MSD4 0 0 20 21 22 225 23 24 25 o0 CONTENTS MECHANICAL - FLOOR PLAN - LEVEL 2 - I BUILDING A & B n MECHANICAL FLOOR PLAN - LEVEL 2 - BLDG A & B PROJECT NO 2021031.00 N� ^A 2,2 cQ o CDm ON 0 o� 0 N GENERAL NU ES 1. ALL IUINGKENSUFRIRANTLBATEO i0E B. 2. REFRIGERANT PIPING SHALL BE INSULA TED NOLDOONTINUISOUN INBMlATION AT EUPP= NO THERMAL IRILDI IN. B. HELP FINE ELE.TNICA CONNETIONSANAND CONNECTIONS TO°INOOOPHEATPING BEHIND WAIL oR CEILING (No SURFACE MOUNTING < RUINATEEROVVIISION OCONTRACTORF ALL RENT EOCAEE. AlllllPANCEILINGS, INCLUDING BUi Noi TED LIMITED T M HEAT ZEMPSA, SEIANCING CA.PERS AND ENGLEETHAT ALL MANUFACTURER MHE RENRoNoPOU"EAE s AWAY FROM FALSE WINDOWSANY POTENTIAL SUCH ns OPERABLE S. S AS SHO OXIMA ELOCONTRACTT1Rss AWN ARE RAL ETERMINALEMENTS, WITH PIPING, QUIPMENT, ETC 1. PROVIDE MANUAL VOLUMER—EMEnns OF uLGNIALANEl CINO FIR ALLTG cR VOLUMFAR AS NSI9LE5 ROMLAIR TEL0RM, AL As SERVED AN,VOLUMEREouIREo TO BE SHALL EAEOOIPEA WITH REMOTECATIONs ACTUATORS (YOUNG REGULATOR TYPE) S.NOT o V IN LENGTH AND SHALL BE INSTALLED WITH NO KINKOR SHARP IUES. NCLDTURNING VANES ON ALL DUCT ws DEGREE ertlNLENGTH 9010. wHD BETWEEN THEN THAN 2. 11. 2NTRACToa SHALL COORDINATE W, H ARCHITECT TO ENSURE ALL EXHAUST RE_F'MEET EENAICLEARANCES DNTNTRTOA MECHANICAL CODE INTAKESA MANICAL KIPMENT. T T f Y Y 15 16 17 18 19 20 21 AkF\ HOUSING I unoc DESIGNS thwest ARCHITECTS EGOTOPE file° W ° a_ U 3 0 2 Z o 0J W Z W w C/) LLa O J a = wQ CONSTRUCTION DOCUMENTS ISSUE DATE JAN. 3, 2023 [ascription r�orsn a/zon cc° mt °0 IJ.J MECHANICAL - FLOOR PLAN - LEVEL 2 - BUILDING C & D MECHANICAL FLOOR PLAN - LEVEL 2 - BLDG C & D N�4) M 2.22 N O (0o m m N 0 o� O N GENERAL NOTES 1. RKIIN NON pONUITIONNEDSPACES ED C. WITH IM INIMUMt PIIPINGHINSULATION NT S WITH NO TTHHERMALNBRIDGING? 3. SUPPORTS WITH PIPING, ELECTRICAL A NO UNNECTIONS OIIN� ORTH pTPlx BEHIND PUMNDI GALL OR CE'HNG(NG SURFACE MOU4. MECHANICAL CONTRACTORALL SHAAREQUIRED ACCESS PANELS FOR EQUIPMENT LOCATED ABOVE CEILINGS INCLUDING A UT N OF PUMPS BALA MI NO DEVICES MOTORIZED DAMPERSCFI E CLEARANCES FOR EQUIPM NTRETHAT ALL MANU 'A CTURER ET ARE P"DEDD s.FROM ANY EFALSE READINGSNTIAL souIDEswRwAr UGH AS OPERABLE ATMIACISSS. AIR TERMINAL LOCATIONSAPR ORMINALSWCoNT SHALL ITHACEILING9?SOTRUCTURAL ELEMiS, LIGHTS PIPING, EQUIPMENT, ]. ETC. MANUAVow.E OAEEE GN OF OR DUCTS TO ED M AM B=G TOR ALL TERMINAL DEVICES. VOLUME DAMPERS SHALL 11 LOCATED AS FAR AS POSSIBLE FROM AIR TERMINAL TO BE ED INLACCESSIBLLE LOCATTIIONS D SHALL BE aSS(YOUNNG REGUL TOR TYPE) S. ACTUATORS LEXTELE OUCT"RK RUNS SHALL NOT EXCEED B IN LENGTH AND SHALL BE INSTALLED WITH NO RINK OR SHARP SENDSOLURNS INCLUDE TURNING VANES IN ALL RECTANGSEABUIIID. OSIBLLBOIUTLZING(2) SO DEGREE ELBOWS WITH ILIT LENGTH BETWEEN THEN o' LESS THAN . OIA ETER(OREQUIVALENTDIAMETER) it OCHRECTTO ENSD EOALLL EIXHAUSTITH RMIINATIONS MEET THE CLEARANCES REQU INTERNATIONAL AGE,INCAKES,A D MECHANICALT. EQUIPMEN I (D--- - jt`!'� - - - - II �:� II ,0 ■■�::►�•'�[� a 'I .� AkF\ HOUSING L� chwest J ARCHITECTS EGOTOPE =11ai12nrua001N� ON1412023 GDDD01 KEYPLAN MSNB Ir77o I a a 20 21 22 22.5 23 24 25 NNTENTS MECHANICAL - FLOOR PLAN - LEVEL 3 - BUILDING A & B n MECHANICAL FLOOR PLAN - LEVEL 3 - BLDG A & B PROJECT NO 2021031.00 NE) ^A 2,3 N O (0o m m NN O O � O N GENERALNOTES 1. ALL Iry NONLpONUITIGNRENU E. WITH IMINIMUM1 PIPING INSULATION LATER UDRTS WITH NO THE RMFL BR_BNG? ]. SUPPORTS RIEC "i.ANIoc'oN"N.'RAT' CORRECT To INDOOR HEniPIN PUMPS UNITS ORAL BE CONCEALED BEHIND WA I MD GURFACE MOUNT A. MECHANI CONTRACTOR SHALLDOOR ALL UWED PROVISIONACCESS PAN ELS FOR pUIPM ENT LOCATED ABOVE CEILINGS, INCLU DING BUT NOT ING DEVICESi MOTORIZED DAPUMPSMPERSBALANCFIRE DAMPERS IF— AND FANG.ENMURETPAT ALL M AN U FAIT FOR E.U'PM°ENT ARED FROM All SFALSE READINGSHALL SRIAOO LCH AS OPERABLE WINDOWS DECT SUNLIGHT ETC . B. AIR TE MINAL LOCATIONS ASSHOWNARE AppCOORDINATE RMENLSWITHCoNT Te IILINGSIPING,ETRRIUCTURAL ELEMI. OVIDE MANUAL VOLUME DAMPERS ON ALL BRAN PDUCT-01ROVIDEMPARS.F BALANCING FOR ALL TERMINAL DEVICES. VOLUME IAIIIRIIHALLIELIIATEIAI SERVED AN'RED ED IN ACCEeBRIBLE ME LOCAS RETIONS 'HALL BERs (YOUNG REGULAPOR TYPE) B. LEIIBLE DUCTWORKLENGTH RUNS 'HALL NOTAND SHALL BE INSTALLED WITH NO KINK OR SHARP 'I. INCLUDE III. O881BEE ABOIO UTILIZING (2) BO DEGREE EI111111TH DUCT LENGTH DIAMETER (OR EQUIVALENT oNMETER) 11. RClnreC: OENSUREA LEXHAUATlTH RMINATIONS MEET THECLEARANCES REDO E 2111 INTERNATIONAL nTO P.AALE GCaNTAKES A D MECHANICAL ECUIPMEN T. =1I HOUSING HOPE i I w keeM none aRVe DESIGNS LID VVBS west ARCHITECTS Q EGOT OPE cly Nae Euulaeal aarsax 8985E u 15 16 17 18 19 20 21 a N3 O H 2 Z Lu U' J N Z W � N ILL o �a T 111 � DOCUMENTS � � °0 IJ.J NTENTS MECHANICAL - FLOOR PLAN - LEVEL 3 - BUILDING C & D n MECHANICAL FLOOR PLAN - LEVEL 3 - BLDG C & D NE) M 2.32 IQ O o CD m W N W � O O � N � j I , I � I I I I I � I I i AkV\ HOUSING L� chwest J ARCHITECTS EGOTOPE Ill a 3 O H 2 Zoo 0 J m 3 Z W w N o �a Q. r�n�irrru•ior■n� I � � 1 j' oo11412023 cco ao1 D I !-ii HYPIAN 20 21 22 225 23 24 25 00NiENi5 MECHANICAL - ROOFPLAN- BUILDING A & B MECHANICAL ROOF PLAN - BLDG A & B NO 2021031.00 ,A1 N�D M 2.41 U Q Q HOUSING HOPE w keep hope alive . DE S CICT ARCHHITTEE ARCTS EGO OPE wry Nae w m (L cl) 3 O F- = Q Z o 0 0 J m CWC C Ap O AWL O � O N -ja W Q CONSTRUCTION DOCUMENTS ISSUECATEJAN.3,2023 �\ 1\U/� aruoalzaza cco aot IJ ICJ ED CONTENTS MECHANICAL - ROOFPLAN- BUILDING C & D U ME CHANICAL ROOF PLAN - BLDG C & D N� PROJECT NO 2021031.00 M2.42 �� CD � 01 N 0 o IN) 0 N I of 22 225 &MECHANICAL TYPICAL UNIT PLAN -1BD MIRRORED va•-v-o• II O O1'�1�' — s EXxADBTDN 0 22.5 23 n MECHANICAL TYPICAL UNIT PLAN - 1BD -UNIT B203 U va = r-o GENERAL NOTES - TYPICAL UNIT PLANS 1. G'G FOesA"SE REALIN.B EDOF AS OPEHAD E WINGOWS, DIECT 2. ON RIGCTWORK OEOUIPMENT CATIONS ARE APPROXIMAITEi COINTRASCORS BHALALHNALSE OUST ROUTING COORDINATEB ENLGHTINGNPIR T IPPING ETTE C. OFALL "V�C. DAMRANCH DUCTS SUCH a. RIGID METAL OAL THAT EVERY IUCTIGISHALL AE USED FOR ALL VENTILATION. (NO FLEX S. CONLOTSTRACTORTO EN8U EXHAUST TERMINATIONS IN UINITSEM EIET THE C EARTo C,ANSEERA BS REQUIRED IN THE 2SIX INTERLE o CAL EQUIPMENT. A. RDINATERFINAL DIFINTAKES AND IFFUSERS AND ELEVATI GRILLE LOCATIONS WITH ARCHIT1."TU EL (MI SIZE ]BkSB•) IN CEILLINGEF6 R MAIINTENAHo VENTNC RAND FEACH TU RE NEE%HAILS F ERv UNIT. E. IN EACH i LIVING SPACE AND BEDROOM. REEEREUCE xeAT LOAD CALCuL IS. PR DOORS ii AM ING. REFERENCIE ATR�CTFRAL PLANBFOR FO WITHIN DETAILS12. DROPPED CEIRIN OR AND SOFFITS. CAL I�TONEERENIRIECTUREPINSFHTRINAI. RFCEACHTTALLAOR DEAILS.PLANS 1S. CHN IF DOMESTIC HO011 TO BE A MINIMUM OF TOO FM. REF CH FOR DETAILS SHEET NOTES AkIF\ HOUSING I HOPE we keep hope alive DE I S R llo_BF A ARCHCHITECEC TS EGOTOPE W ° a N 3 O H = OZ o 0 J Z WILL w � U Q O Ja 2 wQ CONSTRUCTION DOCUMENTS CONTENTS MECHANICAL TYPICAL UNIT PLANS -1BD CHECKEO -- NO 2021031.00 M5.01 AW\ HOUSING GENERAL NOTES - TYPICAL UNIT PLANS I HOPE we keep hope alive POTENTIAL SE RECIN SG SUCH AS -AD E WINDOWS, DIRECT LOCATIONS 2. ALL EQUIPMENT CATIONS ARE SHALL JFINALSE DUCT PIRATE. T a OEDED, AND E NARO COORDINATECOICONTRACTORS ROUTING AS COO OF ALL HVRAAD ELCEM ENT: WITH aRUCTURnneun Hen aPIPINGC. ETCbERa ou Au BRANCH S. NCH ou Ts sucH AIR FOR DoE"G N S LID we s t ARCHITECTS 4. RIGID METAL OUCTIGISHALLA E USED ALL VENTILATION. (NO FLEX DU1. CTS) SHALL TH ARCHITECT TO EN " RE ALL EMEIET EXHAUST TERMINATIONS IN UCTOR NITS THE C EARANCES REQUIRED IN OPENINGe, A. RDTHE 'X INTERHITINATERFINALINTAKES AND HDIFFUSERANICAL S AND I GRILLED LOCATIONS WITH COORDINATE a AL RCP. QELEVATouRE \ 1. cEouripEFsa moiniEnnH. VENTnc Rnno FEACH arcx uEeS GFERvunR. EL IOF SIZE UNIT. MN S. COVE HEATERS TO BE PROVIDE LATious FORRSGING. A IC AT ALL'NT'P'PP DOORSITYWITHIN OPE y Nae mBOXEDCUT RRETO BE I 9 LED CEINGING.EFERECE EUPROVAL OFORMNTIS ANOFFTe0CEPC CAL SOG. INAL LOCATION PENDINGFURTHER IPMENT EA+M Lieu aats�x ^ \\// \I. ROINATION. REFERENCE ARCHITECTURAL FOR DETAILS. DOMESTIC HO011 TO BE A MINIMUM OF IN�� P'NNFGRDESHEET NOTEST. NTC �N ERV INTAKE, ERV EXHAUST, AND RANGE HOOD _4 aeoo.-AGGRNE`GATE 50 CFM 56,03E FFR AIR. OF TIE OPENINGS NEG.aHALNGTECEEQ,MpaGIN.NA SO w ° 2 a //) 3 (06 O" = pZ fD CO C) J oN Z w A V) LL N 1 UQ O a ry = wQ CONSTRUCTION DOCUMENTS ISSUE e JAN. 3, 2023 MHEG 0 OMQ2023 GGGao, 22.5 23 MECHANICAL n MECHANICAL TYPICAL UNIT PLAN - 1BD -UNIT B303 p TYPICAL UNIT -0' PLANS-1 BD NO 2021031.00 M 5.02 �� CD � 00 N O O A C) N ( 22 22.5 23 MECHANICAL TYPICAL UNIT PLAN-1BD.ADA-B 2 GENERAL NOTES - TYPICAL UNIT PLANS ONEIGHi FG CFAL SE REAUINGC "LOCATED GUCN AS GPERAB E WINGOWS, UIRECi 2. G EQUIPMENT CATIONS ARE ANARO PROV a ONNIERAO ORS SNFTLHNALME DUCT B ENLGHTINGNPIR T IPPING ETTE C. OFALL "V�C. DAMRANCH OUCTS SUCH a. RIGID METAL UAL THAT EVERY IUCTIGISHALL AE USED FOR ALL VENTILATION. (NO FLEX 1. CONLOTSTRACTORTO EN8U EXHAUST TERMINATIONS IN UINITSEM EIET THE C EARTo C,ANCEERA BS REOUIREU IN THE 2SIX INTERLE o CAL EQUIPMENT. A. RDINATERFINAL DIFINTAKES AND IFFUSERS AND GRILLE LOCATIONS WITH ARCHIT "TU 1. EL (MI SIZE ]BkSB•) IN CEILLINGEF6 R MAIINTENAHo VENTNC RAND FEACH TU RE NEE%HA113 F ENV UNIT. S. LIN EACH FOR SPACE AND BEDROOM. IS. PREEREU RECE xeAT Lone CALCu ALLPTTPR DOORS 12 UNIT ERVARE BOXED CUT TO BE REFERENCIIN OR AND SOFFITSE ATRCTFRAL PLANRFOR FO WITHIN GETS'LL3. CAL I�TONEERENIRIECTUREPINSFHTRINAI. RFCEACHTTALLAOR DEAILS.PLANS 1S. CHN IF DOMESTIC HO011 TO BE A MINIMUM OF ISO FM. REF ARCH FORDETAILS NOTES AkIF\ HOUSING I HOPE we keep hope alive I S R LID _BF A ARCHCHITECEC TS EGOTOPE W ° a N 3 O H = OZ o 0 J Z WILL w � U Q O Ja 2 wQ CONSTRUCTION DOCUMENTS -Erg CONTENTS MECHANICAL TYPICAL UNIT PLANS - 1 BD.ADA NO 2021031.00 M5.03 �� CD � WN O O � O N 20 21 MECHANICAL TYPICAL UNIT PLAN - 213D MIRRORED 23 24 n MECHANICAL TYPICAL UNIT PLAN - 2BD va•=v-o• GENERAL NOTES - TYPICAL UNIT PLANS SE M"TT' 'FALLREAUINGS SCIA'UCH AS OPERAS ANYE WINGOWS, DIRECT 2. POTENTIAL ON RIGLL CTWORK AL CEOUIPMENT CATIONS ARE APPROREINATEXIROUTINGMAITEi COINTRACNAL CORS aHALATIONS AL HNALIZE DUCT ROUTING CooB E, LINEFDFDGHTINGNPIINUALIPPING ETTE C. OFALL "VRANCH DUCTS SUCH THATN BE a. RIGID METAL DEVERY IUCTIGISHALL AE USED FOR ALL VENTILATION. (NO FLEX 1. CONLOTSTRACTOR EXHAUST TERMINATIONS IN UINITSEM EIET THE CALOOD,CLEARANC'ERAES RETHE 2SIX INTERQUIRED IN CAL EQUIPMENT. A. RDINATERFINAL DIFLED INTAKES AND IFFUSERS AND ELEVATI GRILLE LOCATIONS WITH ARCHIT1."TU EL (MI SIZE 28k3e•1 IN CEILLINGEF6 R MAIINTENAHo VENTNC RAND FEACH TU RE NEE%HAILS F ERV UNIT. S. LIN EACH roaBEING. NGSPACE AND BEDROOM. REEEREUCE xeATLOAC CALCu IS. PR ALLPTTPR DOORS ii M IN.REFERECIET�LPNRFREAGNARETTRALAoGTS'LaFOR . CAL I�TONEERENIRIECTUREPINSFHTRINAI. RFCEACHTTALLAOR DEAILS.PLANS 1S. CHN IF DOMESTIC HO011 TO BE A MINIMUM OF ISO FM. REF CH FORDETAILS NOTES AkIF\ HOUSING I HOPE — keep hope alive I S R LID _BF A ARCHCHITECEC TS EGOTOPE W ° a N 3 O H = OZ o 0 J Z WILL w � U Q O Ja 2 wQ CONSTRUCTION DOCUMENTS CONTENTS MECHANICAL TYPICAL UNIT PLANS -2BD NO 2021031.00 M 5.04 AW\ HOUSING GENERAL NOTES - TYPICAL UNIT PLANS I HOPE we keep hope alive NC,TRREADINGS SCERINDOWS,DIRECT OS FOFnLSE SUCHAS ORAS E W NLIGCTWORK CEDUIP M ENT 2. CATIONS ARE ANpRO PIRATE.SHALLJFINALSE DUCT T a I O COIN TRACTORS ROUTING Go" NEEDED, ANCC OR aAcirLOCATI LOCATIONS xvnc eLeRrnENTs wlix CEMAN ERe ON ALLB GUCTs sucx BRANCH THAT EVERYAIR CHDE I EC S LID _BF AR ARCHITECTS C — RIGID OIUCTINGISHALLA E USED FOR ALL VENTILATION. (NO FLEX CT1. RA SHALL TH ARCHITECT TO ENSURE ALL EM TERMINATIONSCTOR EIET THE CLEARANCTo C 'ERAES REQUIRED ITHE N EXHAUST IN UNITS A. OPENINGe, RD'X INTER NATIONAL MECHANICALINATERINTAIE1 AN'FINALLIFFANSMECHANICALERQS ANDI GRILLEDO OLOCATIONS WITH IT cING a AL RCP. QELEVATDNRE \ 1. EL IMINS¢E Nexse•11n cRoorvpEFsaurnoiniEnnF. VENTnc Rnno FH aPcx uEeX GFERvunR. S. COVE HEATERS LIN EACH LIVINGSPACE AND BEDROOM. QLo DGALCU RV ARE TO HIN THE OPE .. e" ,DVNp Bc RI-REIGTO BOXED ivae ceDervccaSTRUCTURAL LFR E,ANTI . cauDOMCAL IRIECTUREPINSFTRIUAIN. REFERENCE ACHTTALLAOR DEAIILS. DSTOBEAMINIMUMOF,BBCFM.REFn Q ..o r.su .....,. o 2 TES T. —11All , Nr �AN ERV (TAKE, ERV ExxAusr, AND RANGE xGGQ o.AGIIEIA mlWT. BXVGGNSHEETEN RANGTGGELQGONNE OT AR NESHALNOT EXGEEDISO GOIN. IANY 3 f I` W m sC CFM a N 3 aI O H� 2 0 w cQo CD CO 0Z C7 J w Co N Z W V) O Ja 2 w Q 16 �� CONSTRUCTION MECHANICAL TYPICAL UNIT PLAN - 2BD 1 114' - 1'-0' - UNITS D105 D205 & D305 DOCUMENTS ISSUE DATE JAN. 3, 2023 FEII C_ ngion OelT SUB CCDOO, MECHANICAL TYPICAL UNIT PLANS -2BD NO 2021031.00 M5.05 �� CD � ON 0 o 4�- 0 N I I v 24 25 n MECHANICA t PICAL UNIT PLAN - 3BD MIRRORED 6 n MECHANICAL TYPICAL UNIT PLAN - 3BD u0 O GENERAL NOTES - TYPICAL UNIT PLANS NNLIGHT AOR FAL BE READINGS GUCH AS OPERABLE WINDOWS, DIRECT 2. p EpUIPMENT CATIONS AREANNTE IMAVa CNN FaFCT.RIsIALLJFINALIZE DO T ROUTINNEE BE D B EDNALIGHLTOTINGMLADOING TCION9 PECN ALDL xVeANOH OUOTS SUCH 4. RIGID METAL DIUCTINGISHALLABE USEDLFOR ALLVENTILATION.(NO FLEX DUCTS) 1. CTOR SHALL TH ARCHITECT TO ENSURE ALL EITAUIT RMINATIONS IN UNITS MEIET THE CLEARANCES REOUIED IN THE 2R",NTER 'CAL CODE EL' S. EIINATERFINALDL RCPIENUGLERSAND'LEVAIGRILLELOCATIONGWITH ARC HIT].'CTUA soNlEL (MIN SIZE 20'xUe"( IN CEILLING FOR MAINT ENANC NE " FOOD VENT OVERSIZED TUTUREREM U MOVAL'AHAUOF ERV UNIT. SIS. ED. EACH inTEA s FoaNG SPACE AND BEDROOM. CODES ii RAAI ING. REFERENALLCEHSB ToT RUINTERIORCTU PAT PLANSI FOR RETAILS. FOR ME GHANIGAL IRPIEATIONOREFE"`NTS ANRENCE ARCHRreCTTURAL P NET FOR DETAILS. FOR1S. GFM OF DOMESTIC HOODS TO BEA MINIMUM OF 100 CHM. REF ARCH PLANS DETAILS NOTES AkF\ HOUSING I HOPE — keep hope alive DE I S R LID_ST A ARCHCHITECEC TS EGOTOPE W ° a N 3 O H = OZ o 0 J Z W ON LL � U Q O Ja 2 W Q CONSTRUCTION DOCUMENTS CONTENTS MECHANICAL TYPICAL UNIT PLANS-3BD PROJECT NO 2021031.00 IHIIT M5.06 AW\ HOUSING GENERAL NOTES - TYPICAL UNIT PLANS I HOPE . keephopealive 2. POTENTIAL SE RECIN SG SUCH AS -AD E WINDOWS, DIRECT ALL EQUIPMENT ATIONS CATIONS ARE ANARO PIRATE.SHALLJFINALSE DUCT T a OEDED, AND S. COIN TRACTORS ROUTING AS COO OF ALL HVRAAD ELCEM ENT: WITH NCH ou Ts sucH aRUCTURnneun Hen aPIPINGC. ETCbEae ou Au BRANCH AIR FOR DoE"G N S LID we s t ARCHITECTS 4. RIGID METAL DUCTIGISHALLA E USED ALL VENTILATION. (NO FLEX DU1. CTS) TH ARCHITECT TO ENSURE ALL SHALL INITSEM A. EXHAUST TERMINATIONS IN UCTOR EIET THE CLEARANC'ERAES REQUIRED ITHE N OPENINGe, RD'X INTERHITINATERFINALINTAKES AND HDIFFUSERANICAL S AND I GRILLED LOCATIONS WITH COORDINATE a AL acP. QELEVATouRE \ 1. S. cEouripEFsa"C'Ennnc Rnnlo FH arcx uEeS GFERvunR. EL �OF SIZE UNIT. MN COV1B. PREREAEHEAT Long PROVIDE LATious FORRSGING. A AT ALL'NT'P'PP DOORS BOXED CUT AM ING. REFERENCE STPROVIDEDFORRUCTURAL ETAIMECHANICILLS.12. DROPPED CEIRIN OR AND SOFFITS To OPE I'll In' y Nae .uM,�eu aats�x 11 EQUIPMENT ANDFU RDINATION. RE ERIENCEI NAL ARCHI ECTTURALENDING PLANS FOR DHETAILS. FOR1S. CHN IF DOMESTIC HO011 TO BE A MINIMUM OF WO FM. PLANS DETAILS NOTES4 NTET� ERV INTAKE, ERV EXHAUST AND RANGE HOOD S 8 V CONNIESCHON TO RANGE HOOD. CONTRACTOR TO FIELD ONN— AILTHROUGH THE HR=lRANE SHALL NOT EXCEED GO, N ANY a N 3 (06 ow o fD Q) J o C) aGFM F. Z w o N U a �m = wQ ,ER -RE mC CONSTRUCTION k, DOCUMENTS e2 e M 2 1 4 so 2R'FM ISSUE e JAN. 3, 2023 REVISION SCHEDULE —'MEG q o SODFM oQF 40'FM ® a Da a oza GGQDD, aGFM CONTENTS MECHANICAL TYPICAL UNIT — — — — — — PLANS -3BD MECHANICAL TYPICAL UNIT PLAN - 3BD MIRRORED -UNITS C204 & C304 2 1/4'- 1'-0' MECHANICAL TYPICAL UNIT PLAN - 3BD MIRRORED - UNITS A201 & 1 -0. 01 UNNSR OHEC— ETND 2o2ia3,.0a IHIII M5.07 �� CD � NN O O � O N u 15 16 24 25 n MECHANICAL TYPICAL UNIT PLAN - 3BD.ADA-B n MECHANICAL TYPICAL UNIT PLAN - 3BD.ADA-A ia•=r-o• ( 1/4•=1-0• GENERAL NOTES - TYPICAL UNIT PLANS NNLIGHi FOR FAL BE REAUIMAT GB SUCH AB OPERABLE WIN OOWS, UIECT 2. U EQUIPMENT LOCATIONS AREAPPROXIMATE. NNTE IMAVR CONTRACTORS SHALL HNAL¢E OG WITH ?cT ROUTINB AS NEEDED E�LIGHANUALTING PBALANRNALING ET'oGACON9 DEAL xVAG ELEMENTS WITH AM ON ALL eANOH DUCTS SUCH THAT EVERY ASENCED 4. RIGID METAL UIUCTINGISHALLABE USEDLFOR ALLVENTILATION.(NO FLEX DUCTS) 1. CTOR SHALL TH ARCHITECT TO ENSURE ALL EXHAUST TERMINATIONS IN UNITS MEIET THE CLEARANCES REQU RED IN THE 2C",NTBR 'CAL GORE EL, B. HINATERFINALDL DOEIEN SLERBAND'LEVAIGRILLELOCATIONBWITH ARC HIT].'CTUA soNlEL (MIN SIZE 20'x3e"( IN CEILLING FOR MAiNT ENANC V'DE " FOOD VENT OVERSIZED TUITIUREREM U MOVALEXHAUOF ERV UNIT. S. EACH IN EACH NINsPACE AND BEDROOM. DOORS ii NAAI ING. REFERENCEHST RUCTU RAL�PLANSI FOR DETAILS. FOR ME CHANICAL IRCIEATIONOREFEELNTB ANRENCE ARCHRreCTTURAL P NO FOR oETAILB. FOR1S. GFM OF DOMESTIC HOODS TO BEA MINIMUM OF 100 CFM. NET ARCH PLANS DETAILS NOTES AkF\ HOUSING I HOPE we keep hope alive IGNI LID _BF ARCHITECTS EGOTOPE W ° a N 3 O H = OZ o 0 J Z WLL w � U Q O J a 2 wQ CONSTRUCTION DOCUMENTS CONTENTS MECHANICAL TYPICAL UNIT PLANS - 3BD.ADA NO 2021031.00 M5.08 IQ O CD W W N O O � O N — Hom, SO a / 0 11 7 (ABOVE) ENLARGED PLAN SHEET NOTES GENERAL NOTES - ENLARGED PLANS POTENTIAL SOURCES FOR FALSE READINGS SUCH AS OPERABLE WINDOWS UIRECT SUNLIGHT, ETC. ALL CU T III T III T III T III T III eoDIRMENTLQQATIQNBaRBaRRRQxIMATe.DQNTRAQTQRBsxALLHNAH EDDDTRQDTIx G°QRDIxATE FOR MECHANICAL EQI I 3. OVIDEMANUAL BALANCING WITH ARCHITECT ONAALL1 BRANCH DUES SUCH THAT EVERY AIR TERMINAL CELEMENTS N BEEBA ANCEEBTRUCTURE LIGHTING PIPING ETC oN. RRO ILL E. DUCT" E. ONS IN UNITS MEET THE CLEARANCES REQUIRED IN THE 201R INTERNATIONAL ARIOR4 RIGID METALL CO ETO OPERA LEEo ENIN S INTAKES AND MECHANicu BID,FMEN aTl E. 7. °OVINE ANEUNFFTEo, OVERSEEI ACc SS PANEL(MIN SIZE 28.361 iN CEIiiNCR oa MAINTENANCE FNo FUTURE REMOVAL of ERv UNIT. oVIDE IC UNDERCUT AT ALL INTERIOR DOORS. I AD IORIAN OF "IPTHICKNES AND 9HAEDBE CONTINUOUS WITHOBT CPENINDS FROM TH°EPA�,RHHANOL'NGAp Piu cE OR EEOuiFMENT TO THE AIR OUTLET AND INLET HERMINALSSLOCATED ON THE OPPOSITE SIDE OF THE WALL ASSEMBLY. AkF\ HOUSING I HOPE wD keep hope alive DESIGNS LID_XF ARCHITECTS EGOTOPE ::Le° CONSTRUCTION DOCUMENTS IB.1111-r .— A ImA MECHANICAL ENGLARGED PLAN - BUILDING A CHECKED OR—, PROJECT NO 2021031.00 M 5.09 LNGREENHECK Building Value in Air. Supply Fan Charts And Performance Printed Date: 10/18/2023 Job: Housing Hope Edmonds Mark: ERV-Al Model: Minicore-54G-F Supply Total Volume External SP Total SP RPM Operating Motor Fan (CFM) (in. wg) (in. wg) Power (hp) Qty size Qty Type Drive -Type 200 0.5 0.512 987 0.08 1 1/4 1 Forward Curve Direct Pressure .. Weatherhood Filter Damper External Total 0.012 - 0.5 0.512 i, 1.0 m 0.8 3 c E 0.6 Q) N a 0.4 m 0 F 0.2 0.0 0 1 2 3 4 5 Volume (CFM) x 100 0 Operating Bhp point 0 Operating point at Total External TP Fan curve - - - System curve ------- Brake horsepower curve Supply Fan 8) � T' a r m c A� ----- o ` �4 ---- -------- - 6 0.6 0.5 0.4 Q t 0.3 3 0 d N 0.2 m m` A 0.0 7 \\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj CAPS 4.42.1122 Generated WNYW� *zgdorse.com Page 4 of 34 Page 94 of 10 LNGREENHECK Building Value in Air. Supply Fan Charts And Performance Printed Date: 10/18/2023 Job: Housing Hope Edmonds Mark: ERV-A2 Model: Minicore-54G-F Supply Total Volume External SP Total SP Operating Motor Fan Qty size Qty Type Drive -Type (CFM) (in. wg) (in. wg) RPM Power (hp) 300 0.5 0.526 1060 0.11 1 1/4 1 Forward Curve Direct Pressure .. Weatherhood Filter Damper External Total 0.026 - 0.5 0.526 AccordanceSound Performance in Sound Power by Octave Band Lwa dBA Sones 62.5 125 250 500 1000 2000 4000 8000 79.2 78.4 72.6 65.6 66 63.7 61.7 56.5 1 72 1 60.5 1 10.7 Supply Fan 1.2 1.0 m 0.8 3 c E 0.6 N a 0.4 m 0 t- 0.2 00 0.6 0.5 0.4 Q 0.3 3 O d 0.2 m` 0.1 0.0 0 1 2 3 4 5 6 7 8 Volume (CFM) x 100 0 Operating Bhp point 0 Operating point at Total External TP Fan curve - - - System curve ------- Brake horsepower curve �O 60 m a m t ti c - A, v -" o -- o \\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj CAPS 4.42.1122 Generated s� z(�dorse.com Pa e 15 of 34 P ge 95 of 1 o g LNGREENHECK Building Value in Air. Supply Fan Charts And Performance Printed Date: 10/18/2023 Job: Housing Hope Edmonds Mark: ERV-A3 Model: Minicore-54G-F Supply Total Volume External SP Total SP Operating Motor Fan Qty iz Qty Type Drive -Type (CFM) (in. wg) (in. wg) RPM Power (hp) 300 0.5 0.526 1060 0.11 1 1/4 1 Forward Curve Direct Pressure .. Weatherhood Filter Damper External Total 0.026 - 0.5 0.526 AccordanceSound Performance in Sound Power by Octave Band Lwa dBA Sones 62.5 125 250 500 1000 2000 4000 8000 79.2 78.4 72.6 65.6 66 63.7 61.7 56.5 1 72 1 60.5 1 10.7 Supply Fan 1.2 1.0 m 0.8 3 c E 0.6 N a 0.4 m - t- 0.2 00 0.6 0.5 0.4 Q 0.3 3 O d 0.2 m` 0.1 0.0 0 1 2 3 4 5 6 7 8 Volume (CFM) x 100 0 Operating Bhp point 0 Operating point at Total External TP Fan curve - - - System curve ------- Brake horsepower curve �O a� m a m t N C - A LU -" " o \\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj CAPS 4.42.1122 Generated s� z(�dorse.com Pa e 26 of 34 P ge 96 of 1 o g nA Energy Recovery Ventilator 0 Specification Submittal Data / Panasonic ERV Description Ceiling or wall mount Cold Climate Energy Recovery Ventilator (ERV) provides a tempered air supply, humidity control, and a balanced amount of exhaust to help maintain balanced, positive or negative pressure throughout the home. The Panasonic Intelli-Balance ERV is engineered for use in any North America climate zone. Version 2 includes new Hi/Lo Occupant Controlled Boost Capability. Built-in ASHRAE 62.2 Timing function helps ensure code compliance. Motor/Blower: • ERV shall have Hil Speed Occupant Controlled Boost Capability • Two (2) enclosed DC brushless motors rated for continuous run. • ERV Supply and Exhaust ventilation rates shall be manually adjustable for 50-60-70-80- 90-100 CFM. • Power rating shall be 120 volts and 60 Hz. • Motor equipped with thermal cut-off fuse control. • Removable, permanently lubricated, plug—in motor. Housing: • 22 gauge galvanized steel body. • Four 4" or 6" intake and exhaust ducts. • Built in damper on Outdoor Air (OA) closes during defrost function when the outdoor temperature is too cold. • Filters on supply and exhaust air extend the life of the ERV core. • (4) Pressure ports allow for easy airflow verification. • Pre -drilled mounting bracket can accommodate 16", 19", or 24" on center. Maintenance: • MERV 8 filter included; MERV 8 (FV- FL0810VE1) and optional MERV 13 (FV- FL1310VE1) replacements available. • Unobtrusive alarm notifies owner for filter check and maintenance. Warranty: • DC Motors: 6 years from original purchase date IF All Parts: 3 Years from original purchase date. Architectural Specifications: ERV shall be ceiling or wall mount type with built-in speed selectors for both Supply and Exhaust air. Select from 50/60/70/80/90/100 CFM. ERV shall have 100 Net CFM on the exhaust ports and 100 Net CFM on the supply ports as tested in accordance with HVI 915 and 916 standards at 0.1 static pressure in inches water gauge. ERV shall have 100 Net CFM on the exhaust ports and Net 100 CFM on the supply ports at 0.4" w.g. static pressure. ERV shall have Hil Speed Occupant Controlled Boost Capability. Power consumption shall be no greater than 81 watts at 0.1 " w.g. and 100 watts at 0.4" w.g. static pressure. Apparent Sensible Effectiveness for heating shall be no less than 84% at 53 CFM net air flow under 32°F (0°C) as tested in accordance with CSA-C439. Total Recovery Efficiency for cooling shall be no less than 60% at 49 CFM net air flow under 95°F (35°C). The supply port damper shall close when outdoor temperatures are < 14°F (-10°C) to prevent freezing of the core. The (2) motors shall be totally enclosed DC brushless motors rated for continuous run. DC motor speed shall automatically increase when the fan senses static pressure to maintain selected CFM. ERV shall incorporate an ASHRAE 62.2 Intermittent Timing function for code compliance. ERV shall have standby/low speed to high speed control airflow capability as desired by occupant. Power rating shall be 120v/60Hz. Duct diameters shall be no less than 4". ERV can be used to comply with ASHRAE 62.2, LEED, IAP, California Title-24, and WA Energy Code ERV Core Technology: • Indoor and outdoor air passes through Panasonic's capillary core technology. This process tempers supply air while transferring moisture and energy. • Built in Frost Prevention Mode prevents the core from freezing. Frost Prevention Mode is intuitive and operates without homeowner intervention. • Core material permeated with anti -mold treatment. For complete Installation Instructions visit us.panasonic.com/ventfans FV-10VE2 Temperate Climate ERV FV-10VE2 optional E tenor Wall cap (see next page) DC Motor Technology When the ERV senses static pressure, its speed is automatically increased to ensure that the desired CFM is not compromised. Model Quantity Comments Project: Location: Architect: Engineer: Contractor: Submitted by: Date: Panasonic Life Solutions Company of America IAQ Division Two Riverfront Plaza Newark, NJ 07102 us.panasonic.com/ventfans Vi c U� us Page 2024 Panasonic ee.nrien Page 97 of 102 IAQ19203ST r7 LMGREENHECK Building Value in Air. Model: SP-A390 Ceiling Exhaust Fan Standard Construction Features: - Corrosion resistant galvanized steel scroll and housing - Sound absorbing insulation - White designer non -yellowing grille - Rectangular outlet duct collar with integral spring loaded backdraft damper - Double inlet forward curved wheel - Plug type disconnect - Adjustable mounting brackets - Field rotatable discharge Selected Options & Accessories: Motor rated for continuous use Motor with Thermal Overload Motor with CSA Approval Motor with 40 Degree C Ambient Temperature UL/cUL 507 Listed - Electric Fan Solid State Speed Control, 6 Amp, Shipped Loose Isolation Kit, (PN: VI KIT-SP/CSP), Shipped Loose Adjustable easy installation mounting bracket Standard Grille Polypropylene Wheel Material Dimensional Quantity 1 Weight w/o Acc's (lb) 24 Weight w/ Acc's (lb) 26 Performance Requested Volume (CFM) 200 Actual Volume (CFM) 200 Total External SP (in. wg) 0.325 Fan RPM 927 " FLA (A) 1.42 Elevation (ft) 433 Airstream Temp.(F) 70 Air Density (lb/ft3) 0.074 Sones 2.0 Motor Motor Mounted Yes " Input Watts (W) 135 Voltage/Cycle/Phase 115/60/1 Enclosure ODP M 0.5 m 0.3 rn U) a> 0.2 76 U) 0.1 M Printed Date: 10/19/2023 Job: Housing Hope Edmonds Mark: EF-MNT Model: SP-A390 15.5 14.938 6.75 00 O 13.375 e� �o 1/4 in. threaded rod (field provided) 14 11.875 Vibration Isolators (from manufacturer) 8 1 MOUNTING BRACKET 11.25 $ 8 FR M - o a� �o 0 c° 30 60 90 120 150 180 210 240 270 300 Volume (CFM) 0 Operating point at Total External SP Fan curve -- - - System curve Notes: All dimensions shown are in units of in. *FLA is approximate and will vary slightly with the motor. Sones - calculated using AMCA 301 at 5 ft ** Wattage is shown at free air. Wattage is approximate and may vary between motors. WORLDWIDE CERTIFIED RRTIRGf Cimca \\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj CAPS 4.42.1122 Generated s� z(�dorse.com Pa e 1 of 4 P ge 98 of 1 o g LMGREENHECK Building Value in Air. Model: SP-A200 Ceiling Exhaust Fan Standard Construction Features: - Corrosion resistant galvanized steel scroll and housing - Sound absorbing insulation - White designer non -yellowing grille - Rectangular outlet duct collar with integral spring loaded backdraft damper - Double inlet forward curved wheel - Plug type disconnect - Adjustable mounting brackets - Field rotatable discharge Selected Options & Accessories: Motor rated for continuous use Motor with Thermal Overload Motor with CSA Approval Motor with 40 Degree C Ambient Temperature UL/cUL 507 Listed - Electric Fan Solid State Speed Control, 6 Amp, Shipped Loose Isolation Kit, (PN: VI KIT-SP/CSP), Shipped Loose Adjustable easy installation mounting bracket Energy Star Certified Standard Grille Polypropylene Wheel Material Can Be Used to Comply with: ASHRAE 62.2, California Title 24, and Washington State Energy Code Dimensional Quantity 1 0.6 Weight w/o Acc's (lb) 24 Weight w/ Acc's (lb) 26 0.5 Performance Requested Volume (CFM) 150 Actual Volume (CFM) 150 Total External SP (in. wg) 0.3 Fan RPM 750 FLA (A) 0.46 Elevation (ft) 433 Airstream Temp.(F) 70 Air Density (lb/ft3) 0.074 Sones 1.5 Motor Motor Mounted Yes " Input Watts (W) 30 Voltage/Cycle/Phase 115/60/1 Enclosure ODP W 0.3 rn U) a> 0.2 .6 rn 0.1 0 Printed Date: 10/19/2023 Job: Housing Hope Edmonds Mark: EF-IDF-B Model: SP-A200 15.5 14.938 6.75 00 O 13.375 e� �o 1/4 in. threaded rod (field provided) 14 11.875 Vibration Isolators (from manufacturer) 8 1 MOUNTING BRACKET 11.25 $ 8 O ----------------- I m 0 c' 0 0 30 60 90 120 150 180 210 240 Volume (CFM) Operating point at Total External SP - Fan curve - System curve Notes: All dimensions shown are in units of in. *FLA is approximate and will vary slightly with the motor. Sones - calculated using AMCA 301 at 5 ft ** Wattage is approximate and may vary between motors. A RTCla WORLDWIDE CERTIFIED RRTIRGf \\orca\Public\Stephen\�/w1injobs\Housing Hope Edmonds.gfcj CAPS 4.42.1122 Generated sz(�dorse.com Page 99 of 162 Page 2 of 4 LMGREENHECK Building Value in Air. Model: SP-A200 Ceiling Exhaust Fan Standard Construction Features: - Corrosion resistant galvanized steel scroll and housing - Sound absorbing insulation - White designer non -yellowing grille - Rectangular outlet duct collar with integral spring loaded backdraft damper - Double inlet forward curved wheel - Plug type disconnect - Adjustable mounting brackets - Field rotatable discharge Selected Options & Accessories: Motor rated for continuous use Motor with Thermal Overload Motor with CSA Approval Motor with 40 Degree C Ambient Temperature UL/cUL 507 Listed - Electric Fan Solid State Speed Control, 6 Amp, Shipped Loose Isolation Kit, (PN: VI KIT-SP/CSP), Shipped Loose Adjustable easy installation mounting bracket Energy Star Certified Standard Grille Polypropylene Wheel Material Can Be Used to Comply with: ASHRAE 62.2, California Title 24, and Washington State Energy Code Dimensional Quantity 1 0.6 Weight w/o Acc's (lb) 24 Weight w/ Acc's (lb) 26 0.5 Performance Requested Volume (CFM) 150 Actual Volume (CFM) 150 Total External SP (in. wg) 0.3 Fan RPM 750 FLA (A) 0.46 Elevation (ft) 433 Airstream Temp.(F) 70 Air Density (lb/ft3) 0.074 Sones 1.5 Motor Motor Mounted Yes " Input Watts (W) 30 Voltage/Cycle/Phase 115/60/1 Enclosure ODP W 0.3 rn U) a> 0.2 .6 rn 0.1 0 Printed Date: 10/19/2023 Job: Housing Hope Edmonds Mark: EF-IDF-C Model: SP-A200 15.5 14.938 6.75 00 O 13.375 e� �o 1/4 in. threaded rod (field provided) 14 11.875 Vibration Isolators (from manufacturer) 8 1 MOUNTING BRACKET 11.25 $ 8 O ----------------- I m 0 c' 0 0 30 60 90 120 150 180 210 240 Volume (CFM) Operating point at Total External SP - Fan curve - System curve Notes: All dimensions shown are in units of in. *FLA is approximate and will vary slightly with the motor. Sones - calculated using AMCA 301 at 5 ft ** Wattage is approximate and may vary between motors. A RTCla WORLDWIDE CERTIFIED RRTIRGf \\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj CAPS 4.42.1122 Generatedff `�nz02 dorse.com Page 1 0 of 1 Page 3 of 4 LMGREENHECK Building Value in Air. Model: SP-A200 Ceiling Exhaust Fan Standard Construction Features: - Corrosion resistant galvanized steel scroll and housing - Sound absorbing insulation - White designer non -yellowing grille - Rectangular outlet duct collar with integral spring loaded backdraft damper - Double inlet forward curved wheel - Plug type disconnect - Adjustable mounting brackets - Field rotatable discharge Selected Options & Accessories: Motor rated for continuous use Motor with Thermal Overload Motor with CSA Approval Motor with 40 Degree C Ambient Temperature UL/cUL 507 Listed - Electric Fan Solid State Speed Control, 6 Amp, Shipped Loose Isolation Kit, (PN: VI KIT-SP/CSP), Shipped Loose Adjustable easy installation mounting bracket Energy Star Certified Standard Grille Polypropylene Wheel Material Can Be Used to Comply with: ASHRAE 62.2, California Title 24, and Washington State Energy Code Dimensional Quantity 1 0.6 Weight w/o Acc's (lb) 24 Weight w/ Acc's (lb) 26 0.5 Performance Requested Volume (CFM) 150 Actual Volume (CFM) 150 Total External SP (in. wg) 0.3 Fan RPM 750 FLA (A) 0.46 Elevation (ft) 433 Airstream Temp.(F) 70 Air Density (lb/ft3) 0.074 Sones 1.5 Motor Motor Mounted Yes " Input Watts (W) 30 Voltage/Cycle/Phase 115/60/1 Enclosure ODP W 0.3 rn U) a> 0.2 .6 rn 0.1 0 Printed Date: 10/19/2023 Job: Housing Hope Edmonds Mark: EF-IDF-D Model: SP-A200 15.5 14.938 6.75 00 O 13.375 e� �o 1/4 in. threaded rod (field provided) 14 11.875 Vibration Isolators (from manufacturer) 8 1 MOUNTING BRACKET 11.25 $ 8 O ----------------- I m 0 c' 0 0 30 60 90 120 150 180 210 240 Volume (CFM) Operating point at Total External SP - Fan curve - System curve Notes: All dimensions shown are in units of in. *FLA is approximate and will vary slightly with the motor. Sones - calculated using AMCA 301 at 5 ft ** Wattage is approximate and may vary between motors. A RTCla WORLDWIDE CERTIFIED RRTIRGf \\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj CAPS 4.42.1122 Generatedff `�nz02 dorse.com Page 1 1 of 1 Page 4 of 4 wh _n-er G reeo4;decr VENTILATION: FAN Specification Submittal Data / Panasonic Ventilation Fan Description Customizable ceiling mount ventilating fan, low sone and rated for continuous operation. ENERGY STAR® rated and certified by the Home Ventilating Institute (HVI). Evaluated by the Underwriters Laboratories and conforms to both UL and cUL standards. Motor/Blower: • Enclosed brushless ECM smart motor technology rated for continuous operation • Adjustable ventilation rates at 50 — 80 —110 CFM • Power rating of 120 volts and 60 Hz • UL and cUL listed for tub/shower enclosure when GFCI protected. • Motor equipped with thermal cutoff fuse • Removable permanently lubricated plug-in motor Housing: • Environmentally friendly 26 gauge Zinc -Aluminum -Magnesium (ZAM) housing • Integrated dual 4" or 6" diameter duct adapter • Built-in damper reduces back draft and helps with blower door testing • Built-in metal flange provides blocking for penetrations through drywall as an Air Barrier, and assists with the decrease in leakage in the Building Envelope during blower door testing • Suitable for installation in ceilings insulated up to R60 • Articulating and expandable installation bracket up to 24" Grille: • Attractive design using Poly Pro material • Attaches directly to housing with torsion springs • Includes a motion sensor cap for use as a cover when the motion sensor Plug 'n Play'" module has not been selected Warranty: • ECM Motor: 6 Years from original purchase date • ALL Parts: 3 Years from original purchase date Architectural Specifications: Customizable ceiling mount ventilation fan, ENERGY STAR® rated with multi -speed control (0, 30-100 CFM, in 10 CFM increments) and a built-in high/low adjustable time delay activated by a wall switch, SmartAction Motion Sensor Plug 'N Play- module or Condensation Sensor Plug 'N Play'" module. Features a built-in speed selector. Select from 50/80/110 CFM with <0.3 sone as certified by the Home Ventilating Institute (HVI) at 0.1 w.g. with 51 /80/110 CFM and no more than 0.4/0.5/0.8 sones at 0.25 w.g. and 5189/108 CFM at 0.375 w.g. Power Consumption shall be no greater than 3.1 /5.1 /9.9 watts at 0.1 w.g. and 6.2/9.6/15.4 watts at 0.25 w.g. and 9.6/13.4/20.0 watts at 0.375 w.g. ENERGY STAR® rated with efficiency of no less than 16.2/15.7/11.1 CFM/ watt at 0.1 w.g. and 8.3/8.3/7.1 CFM/watt at 0.25 w.g. and 5.3/5.9/5.4 CFM/watt at 0.375 w.g. The motor shall be enclosed with brushless ECM motor engineered to run continuously. ECM motor speed shall automatically increase when the fan senses static pressure to maintain selected CFM. Power rating shall be 120v/60Hz. Duct diameter shall be no less than 4", inclusive of an integrated dual 4" or 6" duct adapter. Plug 'N Play" modules provide up to two additional features. Select from Condensation Sensor, and SmartAction Motion Sensor. Fan shall be RoHS Compliant and UL and cUL listed for tub/shower enclosure when GFCI protected. Also suitable for installation in ceilings insulated up to R60. Fan can be used to comply with ASHRAE 62.2, LEED, ENERGY STAR®, IAP, EarthCraft, California Title-24 and WA Ventilation Code. isECM Motor Technology: When fan senses static pressure, its speed is automatically increased to ensure that the desired CFM is not compromised, which allows the fan to perform as rated. (P FV-0511 VKS2 Built -In Self Adjusting Airflow Capability FV-0511VKS2 Model Quantity Comments Project: Location: Architect: Engineer: Contractor: Submitted by: Date: For complete Installation Instructions visit us.panasonic.com/ventfans Ceiling Radiation Damper: WhisperGreen Select— is UL listed for use with the Panasonic Ceiling Radl WOV202"del #: PC-RD05C5, sold separately). Page 102 of 102