BLD2022-1319 TAB report40A-
TESTING ANO C.
SERVICES
HOUSING HOPE ELC FIELD APARTMENTS
8215 236TH STREET SW
EDMONDS, WA 98026
FINAL TAB REPORT
ARCHITECT:
DESIGNS NORTHWEST ARCHITECTS, INC.
26915 102ND DR NW, SUITE 201, STANWOOD, WA 98292
PROJECT NO: 2230199
DATE: 10/9/2024
TECHNICIAN: BRYCE HURLBUT
MECHANICAL ENGINEER:
ECOTOPE, INC.
1917 FIRST AVENUE, SUITE 300, SEATTLE, WA 98101
MECHANICAL CONTRACTOR:
D. K. SYSTEMS, INC.
1355 BOUSLOG ROAD, BURLINGTON, WA 98233
10/09/2024
Page 1 of 102
AABC
TAC SERVICES, LLC
16929 MAPLEWOOD LANE
BOW, WA 98232
PH:(360) 255-5306
FAX:(360) 464-9973
ADMIN@TACSERVICESNW.COM
AABC National
Perfiormance Guaranty
Pursuant to the agreement between
TAC Services, LLC
AABC Certified Testing & Balancing Agency
and D. K. Systems, Inc.
Client
All systems shall be tested and balanced in accordance with the project plans and specifications
and to the optimum performance capabilities of the equipment. Testing and balancing shall be done
in accordance with the standards published by the Associated Air Balance Council.
If the Agency listed above fails to comply with the specifications for any reason other than
termination of business by the AABC agency or equipment malfunction or inadequacy which
prevents proper balancing of the systems, AABC will investigate and, if warranted, will provide
supervisory personnel to assist the member Agency to perform work in accordance with AABC
Standards. This supervision will be provided at no additional cost to the building owner.
This Guaranty is valid for one year from the date of submission of a test and balance report,
provided the Agency is a current member of AABC, and may only be invoked in writing by the building
owner, architect, or engineer of record. The Guaranty is limited to the terms and conditions as stated
herein.
Project Name
Address
Housing Hope ELC Field Apartments
8215 236th Street SW
Edmonds, WA 98026
Name of Engineer Shanti Oram
Engineering Firm Ecotope, Inc.
Email Address shanti@ecotope.com
Address 1917 First Avenue, Suite 300
Seattle, WA 98101
Date 10/9/2024
TBE # 08-02-04
By Robert R. Coallier
AABC Certified TBE
AABC
Associated Air
Balance Council
1518 K Street, N.W.
Washington, D.C. 20005
202-737-0202 • Fax 202-638-4833
info@aabc.com • www.aabc.com
10/09/2024
Page 2 of 102
TESTING ANO Ca A~By
SERVICES
TABLE OF CONTENTS
DESCRIPTION
PAGE
COVERPAGE------------------------------------------------------------------------------------------------------------
1
AABC NATIONAL PERFORMANCE GUARANTY-------------------------------------------------------------------------
2
TABLE OF CONTENTS
3-4
TEST INSTRUMENT CALIBRATION DATES
------------------------------------------------------------------------------
5
PR03ECTSUMMARY----------------------------------------------------------------------------------------------------
6
LEGEND SHEET
7-9
EF-IDF-B
•--------------------------------------------------------------------------------------------------------------
10
EF-IDF-C
•--------------------------------------------------------------------------------------------------------------
11
EF-IDF-D
•--------------------------------------------------------------------------------------------------------------
12
EF-LAUND
•--------------------------------------------------------------------------------------------------------------
13
EF-MNT
•--------------------------------------------------------------------------------------------------------------
14
IHP-A2
•--------------------------------------------------------------------------------------------------------------
15-16
IHP-A5
•--------------------------------------------------------------------------------------------------------------
17-18
IHP-AI-A
•--------------------------------------------------------------------------------------------------------------
19
IHP-AI-B
•--------------------------------------------------------------------------------------------------------------
19
IHP-A3-A
•--------------------------------------------------------------------------------------------------------------
19
IHP-A3-B
•--------------------------------------------------------------------------------------------------------------
19
IHP-A4
•--------------------------------------------------------------------------------------------------------------
20
IHP-IDF-A
•--------------------------------------------------------------------------------------------------------------
20
ERV-A1
•--------------------------------------------------------------------------------------------------------------
21
ERV-A2
•--------------------------------------------------------------------------------------------------------------
22-23
ERV-A3
•--------------------------------------------------------------------------------------------------------------
24
UNIT B101
------------------------------------------------------------------------------------------------------------
25
UNIT B102
------------------------------------------------------------------------------------------------------------
26
UNIT B103
------------------------------------------------------------------------------------------------------------
27
UNIT B104
------------------------------------------------------------------------------------------------------------
28
UNIT C101
------------------------------------------------------------------------------------------------------------
29
UNIT C102
------------------------------------------------------------------------------------------------------------
30
UNIT C103
------------------------------------------------------------------------------------------------------------
31
UNIT C104
------------------------------------------------------------------------------------------------------------
32
UNIT D101
------------------------------------------------------------------------------------------------------------
33
UNIT D102
------------------------------------------------------------------------------------------------------------
34
UNIT D103
------------------------------------------------------------------------------------------------------------
35
UNIT D104
------------------------------------------------------------------------------------------------------------
36
UNIT D105
------------------------------------------------------------------------------------------------------------
37
UNIT D106
------------------------------------------------------------------------------------------------------------
38
UNIT A201
------------------------------------------------------------------------------------------------------------
39
UNIT A202
------------------------------------------------------------------------------------------------------------
40
UNIT A203
------------------------------------------------------------------------------------------------------------
41
UNIT A204
------------------------------------------------------------------------------------------------------------
42
10/09/2024
Page 3 of 102
STING AMC) Ca AABC
TF
SFRVICFS
TABLE OF CONTENTS
DESCRIPTION
PAGE
UNITA205------------------------------------------------------------------------------------------------------------
43
UNITB201------------------------------------------------------------------------------------------------------------
44
UNITB202------------------------------------------------------------------------------------------------------------
45
UNITB203------------------------------------------------------------------------------------------------------------
46
UNITB204------------------------------------------------------------------------------------------------------------
47
UNITC201------------------------------------------------------------------------------------------------------------
48
UNIT C202
49
UNITC203------------------------------------------------------------------------------------------------------------
50
UNITC204------------------------------------------------------------------------------------------------------------
51
UNITD201------------------------------------------------------------------------------------------------------------
52
UNITD202------------------------------------------------------------------------------------------------------------
53
UNIT D203 ------------------------------------------------------------------------------------------------------------
54
UNIT D204
55
UNITD205------------------------------------------------------------------------------------------------------------
56
UNIT D206 ------------------------------------------------------------------------------------------------------------
57
UNIT A301 ------------------------------------------------------------------------------------------------------------
58
UNIT A302
59
UNITA303------------------------------------------------------------------------------------------------------------
60
UNIT A304 ------------------------------------------------------------------------------------------------------------
61
UNIT A305 ------------------------------------------------------------------------------------------------------------
62
UNIT B301 ------------------------------------------------------------------------------------------------------------
63
UNIT B302 ------------------------------------------------------------------------------------------------------------
64
UNIT B303 ------------------------------------------------------------------------------------------------------------
65
UNIT B304 ------------------------------------------------------------------------------------------------------------
66
UNIT C301
67
UNITC302------------------------------------------------------------------------------------------------------------
68
UNITC303------------------------------------------------------------------------------------------------------------
69
UNIT C304 ------------------------------------------------------------------------------------------------------------
70
UNIT D301 ------------------------------------------------------------------------------------------------------------
71
UNIT D302 ------------------------------------------------------------------------------------------------------------
72
UNIT D303 ------------------------------------------------------------------------------------------------------------
73
UNIT D304 ------------------------------------------------------------------------------------------------------------
74
UNIT D305 ------------------------------------------------------------------------------------------------------------
75
UNIT D306 ------------------------------------------------------------------------------------------------------------
76
SCHEMATIC DIAGRAMS
------------------------------------------------------------------------------------------------
77-93
FAN CURVES
94-102
10/09/2024
Page 4 of 102
4
TFSTING Am C.
SERVICES
TEST INSTRUMENT
CALIBRATION DATES
AA BC
INSTRUMENT
MANUFACTURER
MODEL NO.
SERIAL NO.
CALIBRATION
DATE
DIGITAL FLOW CAPTURE HOOD
ALNOR
EBT-731
EBT732043039
10/16/2023
DIGITAL THERMOMETER (AIR)
ALNOR
EBT-731
EBT732043039
10/16/2023
DIGITAL VEL GRID
ALNOR
EBT-731
EBT732043039
10/16/2023
DIGITAL MANOMETER (AIR)
ALNOR
EBT-731
EBT732043039
10/16/2023
VANE ANEMOMETER
ALNOR
RVA-801
A06246
4/11/2024
HYDRONIC MANOMETER
TELEMETRY
S-DP-250
2200129B
6/25/2024
ULTRASONIC FLOW METER
FUJI ELECTRIC SYS
FSCS
N9H1117T
5/3/2024
HUMIDITY SENSOR
TELEMETRY
PR-TH-1
2400217
7/19/2024
8" FLOW HOOD
TELEMETRY
CH-8D
2100134
6/25/2024
3 POUNDER FLOW HOOD
TELEMETRY
3 POUNDER
2400272B
6/20/2024
PVF MODULE
TELEMETRY
S-PVF-1
2400075C
6/26/2024
DUCT AIR LEAKAGE TEST MACHINE
ORIFLOW
COBRA
10090501
N/A
INFRARED CAMERA
FLIR
FLIR i7
601055235
N/A
PITOT TUBE
DWYER
160-12
N/A
N/A
PITOT TUBE
DWYER
160-24
N/A
N/A
PITOT TUBE
DWYER
160-36
N/A
N/A
PITOT TUBE
DWYER
160-60
N/A
N/A
10/09/2024
Page 5 of 102
4AC-
TESTING ANn Ca
SERVICES
PROJECT SUMMARY
AABC
1.0 THE ENVIRONMENTAL SYSTEMS WERE TESTED AND THE RESULTS ARE AS TABULATED ON THE ATTACHED DATA
SHEETS
2.0 COMMENTS ON SPECIFIC EQUIPMENT IS INCLUDED UNDER REMARKS SECTION ON INDIVIDUAL DATA FORMS
CONTAINED HEREIN.
10/09/2024
Page 6 of 102
4w-
TURTING
SIRVICI S
AABC
LEGEND SHEET
AHU
AIR HANDLING UNIT
AC OR ACU
AIR CONDITIONER UNIT
ACCU
AIR COOLED CONDENSING UNIT
ADJ P.D.
ADJUSTED PITCH DIAMETER
AMP
AMPERE
AVG
AVERAGE
B.H.P. BRAKE HORSEPOWER
C.D.
CEILING DIFFUSER
CFM
CUBIC FEET PER MINUTE
C.E.
CEILING EXHAUST
CH
CHILLER
CHWR
CHILLED WATER RETURN
CHW OR CHWS
CHILLED WATER SUPPLY
C.R.
CEILING RETURN
CT
COOLING TOWER
CWR
CONDENSER WATER RETURN
CW OR CWS
CONDENSER WATER SUPPLY
DB
DRY BULB
D.D.
DIRECT DRIVE
D.P.
DIFFERENCE, NET DECREASE OR INCREASE
DIA
DIAMETER
DISP
DISPLACEMENT
D.N.A.
DATA NOT AVAILABLE
D.N.L
DATA NOT LISTED
EAT
ENTERING AIR TEMPERATURE
EDC
ELECTRIC DUCT COIL
EDH
ELECTRIC DUCT HEALER
EF
EXHAUST FAN
EMCS
ENERGY MANAGEMENT CONTROL SYSTEM (S)
EWT
ENTERING WATER TEMPERATURE
FCU
FAN COIL UNIT
FH
FUME HOOD
FG
FLOOR GRILLE
F.E.
FLOOR EXHAUST OR RETURN
F.L.A
FULL LOAD AMPERAGE
FPB
FAN POWERED BOX
10/09/2024
Page 7 of 102
4AA
IL STING ANO C:
%l Il V ICl 5
AABC
FPM
FEET PER MINUTE
F.S.
FLOOR SUPPLY
F.S.R
FLOOR SUPPLY REGISTER
FT. HD
FEET OF HEAD
FTU
FAN TERMINAL UNIT
GPM GALLONS PER MINUTE
GFH GAS FIRED HEATER
HC
HEATING COIL
HEATER O.L.
THERMAL OVERLOAD PROTECTION FOR MOTORS
LOCATED AT THE MOTOR STARTER
HEPA
HIGH EFFICIENCY PARTICULATE AIR
H.F.
HEPA FILTER
HOA
HAND/OFF/AUTO SWITCH
H.P.
HORSEPOWER
HPS
HIGH PRESSURE STEAM
HRC
HEAT RECOVERY COIL OR HEAT RECLAIM COIL
HVAC
HEATING, VENTILATION AND AIR CONDITIONING
HWR
HOT WATER RETURN OR HEATING WATER RETURN
HWS
HOT WATER SUPPLY OR HEATING WATER SUPPLY
HX
HEAT EXCHANGER
I.D. INSIDE DIAMETER
LAT
LEAVING AIR TEMPERATURE
L.D.
LINEAR SUPPLY DIFFUSER
LPS
LOW PRESSURE STEAM
L.T.
LIGHT TROFFER
LWG
LOW WALL GRILLE
LWR
LOW WALL RETURN
LWT
LEAVING WATER TEMPERATURE
MAU/MUA
MAKE UP AIR UNIT
MBH
1,000 BTU'S PER HOUR
N.A.
NOT ACCESSIBLE
N.I.
NOT INSTALLED
N.T.
NOT TAKEN
N.V.L
NO VALID LOCATION
N.Z.
NOZZLE
O.D. OUTSIDE DIAMETER
OPEN NO TERMINAL DEVICE INSTALLED
O.S.A. MIN OUTSIDE AIR MINIMUM
OAT OUTSIDE AIR TEMPERATURE
10/09/2024
Page 8 of 102
4AP�
TESTING ANO C■
SERVICES
AABC
PF
POWER FACTOR
PHC
PREHEAT COIL
PHC
PHASE (S)
PMP
CIRCULATING PUMP
P.P
PERFORATED PLATE
PSI
POUNDS PER SQUARE INCH
P.T.
PITOT TRAVERSE
RA
RETURN AIR
RF
RETURN AIR FAN
R.G.
RETURN GRILLE
RHC
REHEAT COIL
RPM
REVOLUTIONS PER MINUTE
SA
SUPPLY AIR
SAT
SUPPLY AIR TEMPERATURE
S.D.
SUPPLY DIFFUSER
SEF
SMOKE EXHAUST FAN
SF (AIR)
SUPPLY FAN
S.F. (ELECT)
SERVICE FACTORS
SHC
STEAM HEATING COIL
S.P. "W.C."
STATIC PRESSURE RESISTANCE, MEASURED IN
INCHES OF WATER COLUMN
S.W.E.
SIDEWALL EXHAUST
S.W.R.
SIDEWALL RETURN
S.W.S.
SIDEWALL SUPPLY
TAB TESTING, ADJUSTING, AND BALANCING
TSP TOTAL STATIC PRESSURE
UH UNIT HEATER
V
VOLTS
VAV
VARIABLE AIR VOLUME
VD
VOLUME DAMPER
VFD
VARIABLE FREQUENCY DRIVE
VP
VELOCITY PRESSURE
W WATTS
WB WET BULB
W.G. WATER GAUGE
OF DEGREES FAHRENHEIT
DP DIFFERENTIAL (DELTA) PRESSURE OR PRESSURE
DROP
DT DIFFERENTIAL (DELTA) TEMPERATURE, NET
TEMPERATURE DECREASE OR INCREASE
PSI POUNDS PER SQUARE INCH
10/09/2024
Page 9 of 102
40A-
TESTING ANO Ca
SERVICES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT ID
EF-IDF-B
UNIT DATA
EQUIP. LOCATION
CEILING
AREA SERVED
ELEC B122
MANUFACTURER
GREENHECK
MODEL NUMBER
SP-A200-QD
SERIAL NUMBER
DESIGN CFM
23539850
150
FAN DATA
ACTUAL CFM
151
T.S.P. "W.C.
0.30
DESIGN FAN RPM
750
TESTED FAN RPM
MANUFACTURER
UNABLE TO TEST
GREENHECK
• ••
DATA
HORSEPOWER
1/40
VOLTS
115
AMPS
0.46
SERVICE FACTOR
1.00
MOTOR RPM
900
SPEED
VARIABLE
PHASE / HZ
1/60
OVERLOAD SIZE
THERMAL
RHEOSTAT SETTING LOW
AREA SERVED NO. CODE SIZE
ELEC B122 El EG 6"
AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
F. H. - 150 - 182 121% - 151 1010/0
EF-IDF-B
150
182 121%
151 1010/0
FORM: DIRECT DRIVE TEST DATA >2000 CFM
10/09/2024
Page 10 of 102
40A-
TESTING ANO Ca
SERVICES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT ID
EF-IDF-C
UNIT DATA
EQUIP. LOCATION
CEILING
AREA SERVED
ELEC C121
MANUFACTURER
GREENHECK
MODEL NUMBER
SP-A200-QD
SERIAL NUMBER
DESIGN CFM
23539841
150
FAN DATA
ACTUAL CFM
161
T.S.P. "W.C.
0.30
DESIGN FAN RPM
750
TESTED FAN RPM
MANUFACTURER
UNABLE TO TEST
GREENHECK
• ••
DATA
HORSEPOWER
1/40
VOLTS
115
AMPS
0.46
SERVICE FACTOR
1.00
MOTOR RPM
900
SPEED
VARIABLE
PHASE / HZ
1/60
OVERLOAD SIZE
THERMAL
SPEED SETTING LOW
AREA SERVED NO. CODE SIZE
ELEC C121 E1 EG 14X12
AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
0.71 210 150 252 180 120% 225 161 107%
EF-IDF-C
150
180 120%
161 107%
UNIT IS SET TO ITS MINIMUM SPEED SETTING.
FORM: DIRECT DRIVE TEST DATA >2000 CFM
10/09/2024
Page 11 of 102
40A-
TESTING ANO Ca
SERVICES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT ID
EF-IDF-D
UNIT DATA
EQUIP. LOCATION
CEILING
AREA SERVED
ELEC D122
MANUFACTURER
GREENHECK
MODEL NUMBER
SP-A200-QD
SERIAL NUMBER
DESIGN CFM
23539849
150
FAN DATA
ACTUAL CFM
164
T.S.P. "W.C.
0.30
DESIGN FAN RPM
750
TESTED FAN RPM
MANUFACTURER
UNABLE TO TEST
GREENHECK
• ••
DATA
HORSEPOWER
1/40
VOLTS
115
AMPS
0.46
SERVICE FACTOR
1.00
MOTOR RPM
900
SPEED
VARIABLE
PHASE / HZ
1/60
OVERLOAD SIZE
THERMAL
SPEED SETTING LOW
AREA SERVED NO. CODE SIZE
ELEC D122 El EG 6"
AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
F. H. - 150 - 177 1180/0 - 164 1090/0
EF-IDF-D
150
177 1180/0
164 1090/0
UNIT IS SET TO ITS MINIMUM SPEED SETTING.
FORM: DIRECT DRIVE TEST DATA >2000 CFM
10/09/2024
Page 12 of 102
40A-
TESTING ANO Ca
SERVICES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT ID
EF-LAUND
UNIT DATA
EQUIP. LOCATION
CEILING
AREA SERVED
LAUNDRY C122
MANUFACTURER
PANASONIC
MODEL NUMBER
FV-0511VKS2
SERIAL NUMBER
DESIGN CFM
30809M
50
FAN DATA
ACTUAL CFM
53
T.S.P. "W.C.
0.10
DESIGN FAN RPM
NOT GIVEN
TESTED FAN RPM
MANUFACTURER
UNABLE TO TEST
PANASONIC
• ••
DATA
HORSEPOWER
low
VOLTS
120
AMPS
0.27
SERVICE FACTOR
1.00
MOTOR RPM
VARIABLE
SPEED
3SPEED
PHASE / HZ
1/60
OVERLOAD SIZE
THERMAL
SPEED SETTING 50 CFM
AREA SERVED NO. CODE SIZE
LAUND C122 E1 EG 1OX10
AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
F. H. - 50 - 116 232% - 53 106%
EF-LAUND
50
116 232%
53 106%
FORM: DIRECT DRIVE TEST DATA >2000 CFM
10/09/2024
Page 13 of 102
40A-
TESTING ANO Ca
SERVICES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT ID
EF-MNT
UNIT DATA
EQUIP. LOCATION
CEILING
AREA SERVED
MAINT C123
MANUFACTURER
GREENHECK
MODEL NUMBER
SP-A390-QD
SERIAL NUMBER
DESIGN CFM
23705785
200
FAN DATA
ACTUAL CFM
358
T.S.P. "W.C.
0.33
DESIGN FAN RPM
927
TESTED FAN RPM
MANUFACTURER
UNABLE TO TEST
MCMILLAN
• ••
DATA
HORSEPOWER
1/12
VOLTS
115
AMPS
1.42
SERVICE FACTOR
1.00
MOTOR RPM
1350
SPEED
SINGLE
PHASE / HZ
1/60
OVERLOAD SIZE
THERMAL
RHEOSTAT SETTING NONE PROVIDED
AREA SERVED NO. CODE SIZE
MAINT C123 E1 EG 14X12
AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
F. H. - 200 - 358 179% - 358 179%
EF-MNT
200
358 179%
358 179%
UNABLE TO LOCATE ANY SPEED CONTROLLER FOR THIS FAN. NO OBJECTIONABLE NOISE OR DRAFTS OBSERVED.
FORM: DIRECT DRIVE TEST DATA >2000 CFM
10/09/2024
Page 14 of 102
4-
TESTING AND 1:..
SERVICES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
IHP-A5
• PROPERTY OFFICE, SECURE FILE, COPY/WORK, CONSULTATION
AA BC
=
UNIT ID
IHP-A5
I
EQUIP. LOCATION
CEILING
AREA SERVED
PROPERTY OFFICE
MANUFACTURER
MITSUBISHI
MODEL #
SEZ-KD12NA4
RIAL #
i
DESIGN CFM
16M01762
300
ACTUAL CFM
284
ESP
0.20
TESTED SPEED
HIGH
TESTED SETTING
MANUFACTURER
MODE: 8 SETTING: 3
MITSUBISHI
MOTOR
DATA
HORSE POWER
96 W
VOLTS
208
AMPS
0.72
SERVICE FACTOR
1.00
MOTOR RPM
VARIABLE
SPEED
3SPEED
PHASE / HZ
1/60
HEATER SIZE THERMAL
AREA SERVED NO. CODE SIZE
PROP OFF A102 I S5 12X12
AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
F.H. - 75 80 107% 68 910/0
SERV OFF A106 2 S5 12X12
F.H. -
75
65 87%
68 910/0
SERV OFF A107 3 S5 12X12
F.H. -
75
44 590/0
68 910/0
SERV OFF A112 4 S5 12X12
F.H. -
75
61 81%
80 107%
SUPPLY
300
250 83%
284 95%
UNIT IS SET TO ITS MAXIMUM SPEED SETTING.
FORM: FCU- VRF DUCTED- NO OSA- NO VAV- DIRECT DRIVE- TEST DATA
10/09/2024
Page 15 of 102
40A-
TESTING AND U.
SERVICES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
IHP-AS
• PROPERTY OFFICE, SECURE FILE, COPY/WORK, CONSULTATION
lqw
AA BC
AREA SERVED
NO.
CODE
SIZE
AK
DESIGN
FPM
CFM
INITIAL
FPM
CFM
% OF
DESIGN
FINAL
FPM CFM
7DESIGN
FORM ID: VELOCITY TEST SHEET
10/09/2024
Page 16 of 102
4-
TESTING AND 1:..
SERVICES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
IHP-A5
• PROPERTY OFFICE, SECURE FILE, COPY/WORK, CONSULTATION
AA BC
=
UNIT ID
IHP-A5
I
EQUIP. LOCATION
CEILING
AREA SERVED
PROPERTY OFFICE
MANUFACTURER
MITSUBISHI
MODEL #
SEZ-KD09NA4
RIAL #
i
DESIGN CFM
3XM22068
250
ACTUAL CFM
243
ESP
0.20
TESTED SPEED
HIGH
TESTED SETTING
MANUFACTURER
MODE: 8 SETTING: 3
MITSUBISHI
MOTOR
DATA
HORSE POWER
96 W
VOLTS
208
AMPS
0.59
SERVICE FACTOR
1.00
MOTOR RPM
VARIABLE
SPEED
3SPEED
PHASE / HZ
1/60
HEATER SIZE THERMAL
AREA SERVED NO. CODE SIZE
PROP OFF A103 I S5 12X12
AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
F.H. - 100 63 63% 90 900/0
SECURE A104 2 S5 12X12
F.H. -
50
50 1000/0
51 102%
COPY A105 3 S5 12X12
F.H. -
50
44 88%
51 102%
CUNSULT A108 4 S5 12X12
F.H. -
50
47 94%
51 102%
SUPPLY
250
204 82%
243 97%
UNIT IS SET TO ITS MAXIMUM SPEED SETTING.
FORM: FCU- VRF DUCTED- NO OSA- NO VAV- DIRECT DRIVE- TEST DATA
10/09/2024
Page 17 of 102
40A-
TESTING AND U.
SERVICES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
IHP-AS
• PROPERTY OFFICE, SECURE FILE, COPY/WORK, CONSULTATION
lqw
AA BC
AREA SERVED
NO.
CODE
SIZE
AK
DESIGN
FPM
CFM
INITIAL
FPM
CFM
% OF
DESIGN
FINAL
FPM CFM
7DESIGN
FORM ID: VELOCITY TEST SHEET
10/09/2024
Page 18 of 102
40A-
TESTING ANO Ca
SERVICES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
IHP-Al-A, B, IHP-A3-A, B
• COMMUNITY A101, MULTIPURPOSE Alll
AABC
UNIT ID
IHP-Al-A
UNIT
IHP-Al-B
DATA
IHP-A3-A
IHP-A3-B
EQUIP. LOCATION
WALL
WALL
WALL
WALL
AREA SERVED
COMMUNITY A101
COMMUNITY A101
MULTIPURPOSE Alll
MULTIPURPOSE A111
MANUFACTURER
MITSUBISHI
MITSUBISHI
MITSUBISHI
MITSUBISHI
MODEL NUMBER
MSZ-GS12NA
MSZ-GS12NA
MSZ-GS12NA
MSZ-GS12NA
SERIAL NUMBER
DESIGN CFM
2ZE11560
134/160/222/307/381
31E15224
FAN
134/160/222/307/381
DATA
2ZE07413
134/160/222/307/381
2ZE06731
134/160/222/307/381
ACTUAL CFM
134/160/222/307/381
134/160/222/307/381
134/160/222/307/381
134/160/222/307/381
TESTED SPEED
MANUFACTURER
HIGH
MITSUBISHI
HIGH
MOTOR
MITSUBISHI
DATA
HIGH
MITSUBISHI
HIGH
MITSUBISHI
HORSE POWER
0.04
0.04
0.04
0.04
NAMEPLATE VOLTS
208-230
208-230
208-230
208-230
NAMEPLATE AMPS
0.25
0.25
0.25
0.25
SERVICE FACTOR
1.00
1.00
1.00
1.00
MOTOR RPM
VARIABLE
VARIABLE
VARIABLE
VARIABLE
SPEED
5 SPEED
5 SPEED
5 SPEED
5 SPEED
PHASE / HZ
1/60
1/60
1/60
1/60
OVERLOAD RATING THERMAL
AREA SERVED NO. CODE SIZE
THERMAL THERMAL THERMAL
AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
DUCTLESS
FORM: FCU & AC- NO OSA- DUCTLESS- DIRECT DRIVE- TEST DATA
10/09/2024
Page 19 of 102
40A-
TESTING ANO Ca
SERVICES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
IHP-A4, IHP-IDF-A
• CORRIDOR A100, ELECTRIC A124
AABC
UNIT ID
IHP-A4
UNIT
DATA
IHP-IDF-A
EQUIP. LOCATION
CEILING CASSETTE
WALL
AREA SERVED
CORRIDOR A100
ELEC A124
MANUFACTURER
MITSUBISHI
MITSUBISHI
MODEL NUMBER
SLZ-KF09NA
PKA-Al2LA1
SERIAL NUMBER
DESIGN CFM
2YM05068
230/265/300
FAN
36MO1164
DATA
265/290/325/385
ACTUAL CFM
230/265/300
265/290/325/385
TESTED SPEED
MANUFACTURER
HIGH
MITSUBISHI
MOTOR
HIGH
DATA
MITSUBISHI
HORSE POWER
50 W
0.04
NAMEPLATE VOLTS
208-230
208-230
NAMEPLATE AMPS
0.20
0.55
SERVICE FACTOR
1.00
1.00
MOTOR RPM
VARIABLE
VARIABLE
SPEED
3 SPEED
3 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD RATING THERMAL
AREA SERVED NO. CODE SIZE
THERMAL
AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
DUCTLESS
FORM: FCU & AC- NO OSA- DUCTLESS- DIRECT DRIVE- TEST DATA
10/09/2024
Page 20 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-Al SUPPLY
ERV-Al EXHAUST
EQUIP. LOCATION
LVL 1 BLDG A CEILING
LVL 1 BLDG A CEILING
AREA SERVED
COMMUNITY A101
COMM A101/ STOR A123
MANUFACTURER
GREENHECK
GREENHECK
MODEL NUMBER
MINICORE-5-VG-F
MINICORE-5-VG-F
SERIAL NUMBER
23800619
•
23800619
DESIGN CFM
200
200
ACTUAL CFM
216
197
T.S.P. "W.C.
0.50
0.50
TESTED SPEED
VARIABLE
VARIABLE
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
GREENHECK
GREENHECK
HORSEPOWER
1/4
1/4
NAMEPLATE VOLTS
208
208
TESTED VOLTS
210
210
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.1
1.1
MOTOR RPM
1725
1725
SPEED
VARIABLE
VARIABLE
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED NO.
COMMUNITY A101 1
THERMAL THERMAL
CODE SIZE AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
S2 12X8 F.H. - 200 108 54% 216 1080/0
SUPPLY
200
108
54%
216
1080/0
COMMUNITY A101
E1
R2
12X8
F.H.
-
100
77
77%
152
152%
STOR A123
E2
R3
6X6
F.H.
-
50
21
42%
45
900/0
EXHAUST
150
98
65%
197
131%
UNIT DOES NOT HAVE INDEPENDENT SPEED CONTROL FOR SUPPLY/ EXHAUST MOTORS.
NO NOISE ISSUES OR DRAFTS OBSERVED.
UNIT RUNS AT A LOWER SPEED AND THEN RAMPS UP TO BALANCED SPEED WHEN CO2 SENSOR IS ACTIVATED.
(FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 21 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-2 (SUPPLY)
ERV-2 (EXHAUST)
EQUIP. LOCATION
BLDG A LVL 1 CEILING
BLDG A LVL 1 CEILING
AREA SERVED
BLDG A LVL 1 OFFICES
BLDG A LVL 1 OFFICES
MANUFACTURER
GREENHECK
GREENHECK
MODEL NUMBER
MINICORE-5-VG-F
MINICORE-5-VG-F
SERIAL NUMBER
23800620
•
23800620
DESIGN CFM
300
200
ACTUAL CFM
307
199
T.S.P. "W.C.
0.50
0.50
TESTED SPEED
6.7 VDC
3.8 VDC
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
GREENHECK
GREENHECK
HORSEPOWER
1/4
1/4
NAMEPLATE VOLTS
208
208
TESTED VOLTS
210
210
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.0
0.9
MOTOR RPM
1725
1725
SPEED
VARIABLE
VARIABLE
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
CONSULT A108
NO.
1
THERMAL
CODE SIZE
S6 6X6
AK
F.H.
•
FPM CFM
- 25
THERMAL
OF
FPM CFM DESIGN
37 148%
FPM CFM
25
OF
DESIGN
1000/0
COPY/ WRK A105
2
S6
6X6
F.H.
-
25
22
88%
24
96%
SECURE FILE A014
3
S6
6X6
F.H.
-
25
36
144%
24
96%
PROP OFFICE A103
4
S6
6X6
F.H.
-
25
39
156%
24
96%
CORRIDOR A100
5
S4
12X12
F.H.
-
100
85
85%
103
103%
SERVICES OFF A112
6
S6
6X6
F.H.
-
25
40
160%
24
96%
SERVICES OFF A107
7
S6
6X6
F.H.
-
25
21
84%
25
1000/0
SERVICES OFF A106
8
S6
6X6
F.H.
-
25
21
84%
25
1000/0
PROPERTY OFF A102
9
S6
6X6
F.H.
-
25
35
140%
33
132%
SUPPLY
300
336
112%
307
102%
BALANCING DAMPER FOR SUPPLY OUTLET #9 IS IN A FULL CLOSED POSITION, NO NOISE OR DRAFTS OBSERVED.
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 22 of 102
•rA
PROJECT:
LOCATION:
PROJECT NO:
CONTACT:
SYSTEM:
AREA SERVED:
AREA SERVED NO. CODE SIZE AK DESIGN INITIAL Oho OF FINAL Oho OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
REMARKS:
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-1 (SUPPLY)
ERV-1 (EXHAUST)
EQUIP. LOCATION
BLDG A LVL 1 CEILING
BLDG A LVL 1 CEILING
AREA SERVED
BLDG A LVL 1 MULTI Alll
BLDG A LVL 1 MULTI A111
MANUFACTURER
GREENHECK
GREENHECK
MODEL NUMBER
MINICORE-5-VG-F
MINICORE-5-VG-F
SERIAL NUMBER
23800621
•
23800621
DESIGN CFM
300
300
ACTUAL CFM
322
320
T.S.P. "W.C.
0.50
0.50
TESTED SPEED
VARIABLE
VARIABLE
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
GREENHECK
GREENHECK
HORSEPOWER
1/4
1/4
NAMEPLATE VOLTS
208
208
TESTED VOLTS
210
210
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.2
1.2
MOTOR RPM
1725
1725
SPEED
VARIABLE
VARIABLE
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED NO.
MULTI Alll 1
THERMAL THERMAL
CODE SIZE AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
S2 12X8 F.H. - 300 65 22% 322 107%
SUPPLY
300
65
22%
322
107%
TOILET A113
E1
R3
6X6
F.H.
-
75
26
35%
73
97%
MULTI Alll
E2
R2
12X6
F.H.
-
200
44
22%
215
108%
STORAGE A114
E3
R3
6X6
F.H.
-
25
10
40%
32
128%
EXHAUST
300
80
27%
320
107%
(BALANCING DAMPER FOR EXHAUST REGISTER #E3 IS IN A FULL CLOSED POSITION, NO NOISE OR DRAFTS OBSERVED.
UNIT RUNS AT A LOWER SPEED AND THEN RAMPS UP TO BALANCED SPEED WHEN CO2 SENSOR IS ACTIVATED.
(FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 24 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B101 SUPPLY
ERV-RES B101 EXHAUST
EQUIP. LOCATION
BLDG B LVL 1 UNIT B101
BLDG B LVL 1 UNIT B101
AREA SERVED
UNIT B101
UNIT B101
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
90
90
ACTUAL CFM
94
92
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
80CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.0
1.1
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG B LVL 1 B101
NO.
1
THERMAL
CODE SIZE
S1 4"
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
22
OF
DESIGN
1100/0
BLDG B LVL 1 B101
2
S1
4"
F.H.
-
20
27
135%
20
1000/0
BLDG B LVL 1 B101
3
S1
4"
F.H.
-
20
26
130%
21
1050/0
BLDG B LVL 1 B101
4
S1
4"
F.H.
-
30
22
73%
31
103%
SUPPLY
90
100
1110/0
94
104%
BLDG B LVL 1 B101
E1
Rl
6"
F.H.
-
40
47
1180/0
40
1000/0
BLDG B LVL 1 B101
E2
Rl
6"
F.H.
-
50
45
900/0
52
104%
EXHAUST
90
92
102%
92
102%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 25 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B102 SUPPLY
ERV-RES B102 EXHAUST
EQUIP. LOCATION
BLDG B LVL 1 UNIT B102
BLDG B LVL 1 UNIT B102
AREA SERVED
UNIT B102
UNIT B102
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
74
71
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG B LVL 1 B102
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
23 1150/0
FPM CFM
20
OF
DESIGN
1000/0
BLDG B LVL 1 B102
2
S1
4"
F.H.
-
20
28
140%
22
1100/0
BLDG B LVL 1 B102
3
Sl
4"
F.H.
-
30
25
83%
32
107%
SUPPLY
70
76
1090/0
74
106%
BLDG B LVL 1 B102
E1
Rl
4"
F.H.
-
70
63
900/0
71
1010/0
EXHAUST
70
63
900/0
71
1010/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 26 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B103 SUPPLY
ERV-RES B103 EXHAUST
EQUIP. LOCATION
BLDG B LVL 1 UNIT B103
BLDG B LVL 1 UNIT B103
AREA SERVED
UNIT B103
UNIT B103
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
50
50
ACTUAL CFM
51
49
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
50 CFM
60CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.7
0.7
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED NO.
BLDG B LVL 1 B103 1
THERMAL THERMAL
CODE SIZE AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
Sl 4" F.H. - 20 26 130% 21 1050/0
BLDG B LVL 1 B103
2
Sl
4"
F.H.
-
30
28
93%
30
1000/0
SUPPLY
50
54
1080/0
51
102%
BLDG B LVL 1 B103
E1
Rl
4"
F.H.
-
50
47
94%
49
98%
EXHAUST
50
47
94%
49
98%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 27 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B104 SUPPLY
ERV-RES B104 EXHAUST
EQUIP. LOCATION
BLDG B LVL 1 UNIT B104
BLDG B LVL 1 UNIT B104
AREA SERVED
UNIT B104
UNIT B104
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
50
50
ACTUAL CFM
53
49
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
50 CFM
60CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.7
0.7
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED NO.
BLDG B LVL 1 B104 1
THERMAL THERMAL
CODE SIZE AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
Sl 4" F.H. - 20 26 130% 22 1100/0
BLDG B LVL 1 B104
2
Sl
4"
F.H.
-
30
29
97%
31
103%
SUPPLY
50
55
1100/0
53
106%
BLDG B LVL 1 B104
E1
Rl
6"
F.H.
-
50
43
86%
49
98%
EXHAUST
50
43
86%
49
98%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 28 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C101 SUPPLY
ERV-RES C101 EXHAUST
EQUIP. LOCATION
BLDG C LVL 1 UNIT C101
BLDG C LVL 1 UNIT C101
AREA SERVED
UNIT C101
UNIT C101
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31101
•
31101
DESIGN CFM
70
70
ACTUAL CFM
76
74
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 1 C101
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
29 145%
FPM CFM
22
OF
DESIGN
1100/0
BLDG C LVL 1 C101
2
S1
6X4
F.H.
-
20
26
130%
21
1050/0
BLDG C LVL 1 C101
3
S1
6X4
F.H.
-
30
27
900/0
33
1100/0
SUPPLY
70
82
117%
76
1090/0
BLDG C LVL 1 C101
E1
Rl
6X6
F.H.
-
70
55
79%
74
106%
EXHAUST
70
55
1 79%
74
1 106%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 29 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C102 SUPPLY
ERV-RES C102 EXHAUST
EQUIP. LOCATION
BLDG C LVL 1 UNIT C102
BLDG C LVL 1 UNIT C102
AREA SERVED
UNIT C102
UNIT C102
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31101
•
31101
DESIGN CFM
70
70
ACTUAL CFM
74
72
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 1 C102
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
21
OF
DESIGN
1050/0
BLDG C LVL 1 C102
2
S1
6X4
F.H.
-
20
27
135%
21
1050/0
BLDG C LVL 1 C102
3
S1
6X4
F.H.
-
30
31
103%
32
107%
SUPPLY
70
84
120%
74
106%
BLDG C LVL 1 C102
E1
Rl
6X6
F.H.
-
70
83
1190/0
72
103%
EXHAUST
70
83
1 119%
72
1 1030/
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 30 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C103 SUPPLY
ERV-RES C103 EXHAUST
EQUIP. LOCATION
BLDG C LVL 1 UNIT C103
BLDG C LVL 1 UNIT C103
AREA SERVED
UNIT C103
UNIT C103
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
74
70
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
80CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.0
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 1 C103
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
28 140%
FPM CFM
21
OF
DESIGN
1050/0
BLDG C LVL 1 C103
2
S1
6X4
F.H.
-
20
26
130%
21
1050/0
BLDG C LVL 1 C103
3
S1
6X4
F.H.
-
30
31
103%
32
107%
SUPPLY
70
85
121%
74
106%
BLDG C LVL 1 C103
E1
Rl
6X6
F.H.
-
70
83
1190/0
70
1000/0
EXHAUST
70
83
1 119%
70
1 1000/
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 31 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C104 SUPPLY
ERV-RES C104 EXHAUST
EQUIP. LOCATION
BLDG C LVL 1 UNIT C104
BLDG C LVL 1 UNIT C104
AREA SERVED
UNIT C104
UNIT C014
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31101
•
31101
DESIGN CFM
90
90
ACTUAL CFM
94
95
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
80CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.0
1.1
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 1 C104
NO.
1
THERMAL
CODE SIZE
S1 6X4
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
24 120%
FPM CFM
20
OF
DESIGN
1000/0
BLDG C LVL 1 C104
2
S1
6X4
F.H.
-
20
23
1150/0
21
1050/0
BLDG C LVL 1 C104
3
S1
6X4
F.H.
-
20
28
140%
21
1050/0
BLDG C LVL 1 C104
4
S1
6X4
F.H.
-
30
51
170%
32
107%
SUPPLY
90
126
140%
94
104%
BLDG C LVL 1 C104
E1
Rl
6X6
F.H.
-
40
55
138%
42
105%
BLDG C LVL 1 C104
E2
Rl
6X6
F.H.
-
50
57
114%
53
106%
EXHAUST
90
112
124%
95
106%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 32 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D101 SUPPLY
ERV-RES D101 EXHAUST
EQUIP. LOCATION
BLDG D LVL 1 UNIT D101
BLDG D LVL 1 UNIT D101
AREA SERVED
UNIT D101
UNIT D101
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
60
50
ACTUAL CFM
62
51
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
50 CFM
50 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.7
0.7
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED NO.
BLDG D LVL 1 D101 1
THERMAL THERMAL
CODE SIZE AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
Sl 4" F.H. - 30 35 117% 31 103%
BLDG D LVL 1 D101
2
Sl
4"
F.H.
-
30
37
123%
31
103%
SUPPLY
60
72
120%
62
103%
BLDG D LVL 1 D101
E1
Rl
6"
F.H.
-
50
82
164%
51
102%
EXHAUST
50
82
164%
51
102%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 33 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D102 SUPPLY
ERV-RES D102 EXHAUST
EQUIP. LOCATION
BLDG D LVL 1 UNIT D102
BLDG D LVL 1 UNIT D102
AREA SERVED
UNIT D102
UNIT D102
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
74
68
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 1 D102
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
27 135%
FPM CFM
20
OF
DESIGN
1000/0
BLDG D LVL 1 D102
2
S1
4"
F.H.
-
20
28
140%
22
1100/0
BLDG D LVL 1 D102
3
Sl
4"
F.H.
-
30
23
77%
32
107%
SUPPLY
70
78
1110/0
74
106%
BLDG D LVL 1 D102
E1
Rl
6"
F.H.
-
70
96
137%
68
97%
EXHAUST
70
96
1 137%
68
1 97%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 34 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D103 SUPPLY
ERV-RES D103 EXHAUST
EQUIP. LOCATION
BLDG D LVL 1 UNIT D103
BLDG D LVL 1 UNIT D103
AREA SERVED
UNIT D103
UNIT D103
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
74
72
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 1 D103
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
17 850/0
FPM CFM
20
OF
DESIGN
1000/0
BLDG D LVL 1 D103
2
S1
4"
F.H.
-
20
25
125%
22
1100/0
BLDG D LVL 1 D103
3
Sl
4"
F.H.
-
30
32
107%
32
107%
SUPPLY
70
74
106%
74
106%
BLDG D LVL 1 D103
E1
Rl
6"
F.H.
-
70
62
89%
72
103%
EXHAUST
70
62
1 89%
72
1 1030/
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 35 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D104 SUPPLY
ERV-RES D104 EXHAUST
EQUIP. LOCATION
BLDG D LVL 1 UNIT D104
BLDG D LVL 1 UNIT D104
AREA SERVED
UNIT D104
UNIT D104
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
73
69
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 1 D104
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
21
OF
DESIGN
1050/0
BLDG D LVL 1 D104
2
S1
4"
F.H.
-
20
27
135%
21
1050/0
BLDG D LVL 1 D104
3
Sl
4"
F.H.
-
30
24
80%
31
103%
SUPPLY
70
76
1090/0
73
104%
BLDG D LVL 1 D104
E1
Rl
6"
F.H.
-
70
98
140%
69
990/0
EXHAUST
70
98
1 140%
69
1 99%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 36 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D105 SUPPLY
ERV-RES D105 EXHAUST
EQUIP. LOCATION
BLDG D LVL 1 UNIT D105
BLDG D LVL 1 UNIT D105
AREA SERVED
UNIT D105
UNIT D105
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
74
71
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 1 D105
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
21
OF
DESIGN
1050/0
BLDG D LVL 1 D105
2
S1
4"
F.H.
-
20
28
140%
21
1050/0
BLDG D LVL 1 D105
3
Sl
6"
F.H.
-
30
22
73%
32
107%
SUPPLY
70
76
1090/0
74
106%
BLDG D LVL 1 D105
E1
Rl
6"
F.H.
-
70
82
117%
71
1010/0
EXHAUST
70
82
1 117%
71
1 1010/
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 37 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D106 SUPPLY
ERV-RES D106 EXHAUST
EQUIP. LOCATION
BLDG D LVL 1 UNIT D106
BLDG D LVL 1 UNIT D106
AREA SERVED
UNIT D106
UNIT D106
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
90
90
ACTUAL CFM
95
93
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
90 CFM
100 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.2
1.3
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 1 D106
NO.
1
THERMAL
CODE SIZE
S1 4"
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
28 140%
FPM CFM
21
OF
DESIGN
1050/0
BLDG D LVL 1 D106
2
S1
4"
F.H.
-
20
28
140%
21
1050/0
BLDG D LVL 1 D106
3
S1
4"
F.H.
-
20
18
900/0
22
1100/0
BLDG D LVL 1 D106
4
S1
4"
F.H.
-
30
42
140%
31
103%
SUPPLY
90
116
129%
95
106%
BLDG D LVL 1 D106
E1
Rl
6"
F.H.
-
50
51
102%
51
102%
BLDG D LVL 1 D106
E2
Rl
6"
F.H.
-
40
42
1050/0
42
105%
EXHAUST
90
93
103%
93
103%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 38 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES A201 SUPPLY
ERV-RES A201 EXHAUST
EQUIP. LOCATION
BLDG A LVL 2 UNIT A201
BLDG A LVL 2 UNIT A201
AREA SERVED
UNIT A201
UNIT A201
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
90
90
ACTUAL CFM
92
97
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
80CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.1
1.2
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG A LVL 2 A201
NO.
1
THERMAL
CODE SIZE
S1 6X4
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
20
OF
DESIGN
1000/0
BLDG A LVL 2 A201
2
S1
6X4
F.H.
-
20
23
1150/0
21
1050/0
BLDG A LVL 2 A201
3
S1
6X4
F.H.
-
20
24
120%
20
1000/0
BLDG A LVL 2 A201
4
S1
6X4
F.H.
-
30
26
87%
31
103%
SUPPLY
90
98
1090/0
92
102%
BLDG A LVL 2 A201
E1
Rl
6X6
F.H.
-
40
53
133%
44
1100/0
BLDG A LVL 2 A201
E2
Rl
6X6
F.H.
-
50
41
82%
53
106%
EXHAUST
90
94
104%
97
108%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 39 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES A202 SUPPLY
ERV-RES A202 EXHAUST
EQUIP. LOCATION
BLDG A LVL 2 UNIT A202
BLDG A LVL 2 UNIT A202
AREA SERVED
UNIT A202
UNIT A202
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
73
73
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG A LVL 2 A202
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
27 135%
FPM CFM
21
OF
DESIGN
1050/0
BLDG A LVL 2 A202
2
S1
6X4
F.H.
-
20
24
120%
22
1100/0
BLDG A LVL 2 A202
3
S1
6X4
F.H.
-
30
26
87%
30
1000/0
SUPPLY
70
77
1100/0
73
104%
BLDG A LVL 2 A202
E1
Rl
6X6
F.H.
-
70
65
93%
73
104%
EXHAUST
70
65
1 93%
73
1 1040/
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 40 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES A203 SUPPLY
ERV-RES A203 EXHAUST
EQUIP. LOCATION
BLDG A LVL 2 UNIT A203
BLDG A LVL 2 UNIT A203
AREA SERVED
UNIT A203
UNIT A203
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
72
69
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
60CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG A LVL 2 A203
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
22
OF
DESIGN
1100/0
BLDG A LVL 2 A203
2
S1
6X4
F.H.
-
20
24
120%
20
1000/0
BLDG A LVL 2 A203
3
S1
6X4
F.H.
-
30
23
77%
30
1000/0
SUPPLY
70
73
104%
72
103%
BLDG A LVL 2 A203
E1
Rl
6X6
F.H.
-
70
59
84%
69
990/0
EXHAUST
70
59
1 84%
69
1 99%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 41 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES A204 SUPPLY
ERV-RES A204 EXHAUST
EQUIP. LOCATION
BLDG A LVL 2 UNIT A204
BLDG A LVL 2 UNIT A204
AREA SERVED
UNIT A204
UNIT A204
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
73
69
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
60CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG A LVL 2 A204
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
22
OF
DESIGN
1100/0
BLDG A LVL 2 A204
2
S1
6X4
F.H.
-
20
25
125%
20
1000/0
BLDG A LVL 2 A204
3
S1
6X4
F.H.
-
30
21
70%
31
103%
SUPPLY
70
72
103%
73
104%
BLDG A LVL 2 A204
E1
Rl
6X6
F.H.
-
70
82
117%
69
990/0
EXHAUST
70
82
1 117%
69
1 99%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 42 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES A205 SUPPLY
ERV-RES A205 EXHAUST
EQUIP. LOCATION
BLDG A LVL 2 UNIT A205
BLDG A LVL 2 UNIT A205
AREA SERVED
UNIT A205
UNIT A205
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
90
90
ACTUAL CFM
97
89
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.9
1.2
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG A LVL 2 A205
NO.
1
THERMAL
CODE SIZE
S1 6X4
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
21
OF
DESIGN
1050/0
BLDG A LVL 2 A205
2
S1
6X4
F.H.
-
20
24
120%
22
1100/0
BLDG A LVL 2 A205
3
S1
6X4
F.H.
-
20
24
120%
21
1050/0
BLDG A LVL 2 A205
4
S1
6X4
F.H.
-
30
26
87%
33
1100/0
SUPPLY
90
100
1110/0
97
1080/0
BLDG A LVL 2 A205
E1
Rl
6X6
F.H.
-
40
52
130%
42
105%
BLDG A LVL 2 A205
E2
Rl
6X6
F.H.
-
50
40
80%
47
94%
EXHAUST
90
92
102%
89
990/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 43 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B201 SUPPLY
ERV-RES B201 EXHAUST
EQUIP. LOCATION
BLDG B LVL 2 UNIT B201
BLDG B LVL 2 UNIT B201
AREA SERVED
UNIT B201
UNIT B201
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
90
90
ACTUAL CFM
93
91
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
80CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.0
1.1
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG B LVL 2 B201
NO.
1
THERMAL
CODE SIZE
S1 4"
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
29 145%
FPM CFM
20
OF
DESIGN
1000/0
BLDG B LVL 2 B201
2
S1
4"
F.H.
-
20
25
125%
20
1000/0
BLDG B LVL 2 B201
3
S1
4"
F.H.
-
20
24
120%
22
1100/0
BLDG B LVL 2 B201
4
S1
4"
F.H.
-
30
22
73%
31
103%
SUPPLY
90
100
1110/0
93
103%
BLDG B LVL 2 B201
E1
Rl
6"
F.H.
-
40
48
120%
42
105%
BLDG B LVL 2 B201
E2
Rl
6"
F.H.
-
50
45
900/0
49
98%
EXHAUST
90
93
103%
91
1010/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 44 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B202 SUPPLY
ERV-RES B202 EXHAUST
EQUIP. LOCATION
BLDG B LVL 2 UNIT B202
BLDG B LVL 2 UNIT B202
AREA SERVED
UNIT B202
UNIT B202
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
71
73
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
60CFM
80CFM
STATIC SETTING
N. /APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.7
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG B LVL 2 B202
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
20
OF
DESIGN
1000/0
BLDG B LVL 2 B202
2
S1
4"
F.H.
-
20
27
135%
20
1000/0
BLDG B LVL 2 B202
3
Sl
4"
F.H.
-
30
22
73%
31
103%
SUPPLY
70
74
106%
71
1010/0
BLDG B LVL 2 B202
E1
Rl
6"
F.H.
-
70
62
89%
73
104%
EXHAUST
70
62
89%
73
104%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 45 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B203 SUPPLY
ERV-RES B203 EXHAUST
EQUIP. LOCATION
BLDG B LVL 2 UNIT B203
BLDG B LVL 2 UNIT B203
AREA SERVED
UNIT B203
UNIT B203
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
50
50
ACTUAL CFM
52
51
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
50 CFM
60CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED NO.
BLDG B LVL 2 B203 1
THERMAL THERMAL
CODE SIZE AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
Sl 4" F.H. - 20 28 140% 20 1000/0
BLDG B LVL 2 B203
2
Sl
4"
F.H.
-
30
26
87%
32
107%
SUPPLY
50
54
1080/0
52
104%
BLDG B LVL 2 B203
E1
Rl
4"
F.H.
-
50
45
900/0
51
102%
EXHAUST
50
45
900/0
51
102%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 46 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B204 SUPPLY
ERV-RES B204 EXHAUST
EQUIP. LOCATION
BLDG B LVL 2 UNIT B204
BLDG B LVL 2 UNIT B204
AREA SERVED
UNIT B204
UNIT B204
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
50
50
ACTUAL CFM
54
52
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
50 CFM
50 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.7
0.7
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED NO.
BLDG B LVL 2 B204 1
THERMAL THERMAL
CODE SIZE AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
Sl 4" F.H. - 20 26 130% 21 1050/0
BLDG B LVL 2 B204
2
Sl
4"
F.H.
-
30
28
93%
33
1100/0
SUPPLY
50
54
1080/0
54
1080/0
BLDG B LVL 2 B204
E1
Rl
4"
F.H.
-
50
63
126%
52
104%
EXHAUST
50
63
126%
52
104%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 47 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C201 SUPPLY
ERV-RES C201 EXHAUST
EQUIP. LOCATION
BLDG C LVL 2 UNIT C201
BLDG C LVL 2 UNIT C201
AREA SERVED
UNIT C201
UNIT C201
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
74
77
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.9
1.0
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 2 C201
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
21
OF
DESIGN
1050/0
BLDG C LVL 2 C201
2
S1
6X4
F.H.
-
20
26
130%
20
1000/0
BLDG C LVL 2 C201
3
S1
6X4
F.H.
-
30
27
900/0
33
1100/0
SUPPLY
70
78
1110/0
74
106%
BLDG C LVL 2 C201
E1
Rl
6X6
F.H.
-
70
61
87%
77
1100/0
EXHAUST
70
61
87%
77
1100/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 48 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C202 SUPPLY
ERV-RES C202 EXHAUST
EQUIP. LOCATION
BLDG C LVL 2 UNIT C202
BLDG C LVL 2 UNIT C202
AREA SERVED
UNIT C202
UNIT C202
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
75
68
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 2 C202
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
22
OF
DESIGN
1100/0
BLDG C LVL 2 C202
2
S1
6X4
F.H.
-
20
25
125%
20
1000/0
BLDG C LVL 2 C202
3
S1
6X4
F.H.
-
30
24
80%
33
1100/0
SUPPLY
70
75
107%
75
107%
BLDG C LVL 2 C202
E1
Rl
6X6
F.H.
-
70
56
80%
68
97%
EXHAUST
70
56
80%
68
97%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 49 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C203 SUPPLY
ERV-RES C203 EXHAUST
EQUIP. LOCATION
BLDG C LVL 2 UNIT C203
BLDG C LVL 2 UNIT C203
AREA SERVED
UNIT C203
UNIT C203
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31023
•
31023
DESIGN CFM
70
70
ACTUAL CFM
74
69
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.9
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 2 C203
NO.
1
THERMAL
CODE SIZE AK
51 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
28 140%
FPM CFM
21
OF
DESIGN
1050/0
BLDG C LVL 2 C203
2
S1
6X4
F.H.
-
20
25
125%
20
1000/0
BLDG C LVL 2 C203
3
S1
6X4
F.H.
-
30
26
87%
33
1100/0
SUPPLY
70
79
113%
74
106%
BLDG C LVL 2 C203
E1
Rl
6X6
F.H.
-
70
61
87%
69
990/0
EXHAUST
70
61
87%
69
990/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 50 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C204 SUPPLY
ERV-RES C204 EXHAUST
EQUIP. LOCATION
BLDG C LVL 2 UNIT C204
BLDG C LVL 2 UNIT C204
AREA SERVED
UNIT C204
UNIT C204
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
90
90
ACTUAL CFM
94
94
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
80CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.1
1.1
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 2 C204
NO.
1
THERMAL
CODE SIZE
S1 6X4
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
22
OF
DESIGN
1100/0
BLDG C LVL 2 C204
2
S1
6X4
F.H.
-
20
26
130%
20
1000/0
BLDG C LVL 2 C204
3
S1
6X4
F.H.
-
20
24
120%
21
1050/0
BLDG C LVL 2 C204
4
S1
6X4
F.H.
-
30
28
93%
31
103%
SUPPLY
90
103
114%
94
104%
BLDG C LVL 2 C204
E1
Rl
6X6
F.H.
-
40
52
130%
44
1100/0
BLDG C LVL 2 C204
E2
Rl
6X6
F.H.
-
50
54
1080/0
50
1000/0
EXHAUST
90
106
1180/0
94
104%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 51 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D201 SUPPLY
ERV-RES D201 EXHAUST
EQUIP. LOCATION
BLDG D LVL 2 UNIT D201
BLDG D LVL 2 UNIT D201
AREA SERVED
UNIT D201
UNIT D201
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31101
•
31101
DESIGN CFM
70
70
ACTUAL CFM
74
72
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 2 D201
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 4"
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
21
OF
DESIGN
1050/0
BLDG D LVL 2 D201
2
S1
6X4
4"
-
20
28
140%
22
1100/0
BLDG D LVL 2 D201
3
S1
6X4
6"
-
30
23
77%
31
103%
SUPPLY
70
77
1100/0
74
106%
BLDG D LVL 2 D201
E1
Rl
6X6
6"
-
70
64
910/0
72
103%
EXHAUST
70
64
910/0
72
103%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 52 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D202 SUPPLY
ERV-RES D202 EXHAUST
EQUIP. LOCATION
BLDG D LVL 2 UNIT D202
BLDG D LVL 2 UNIT D202
AREA SERVED
UNIT D202
UNIT D202
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
74
70
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 2 D202
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
24 120%
FPM CFM
20
OF
DESIGN
1000/0
BLDG D LVL 2 D202
2
S1
4"
F.H.
-
20
27
135%
22
1100/0
BLDG D LVL 2 D202
3
Sl
6"
F.H.
-
30
28
93%
32
107%
SUPPLY
70
79
113%
74
106%
BLDG D LVL 2 D202
E1
Rl
6"
F.H.
-
70
81
116%
70
1000/0
EXHAUST
70
81
1 116%
70
1 1000/
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 53 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D203 SUPPLY
ERV-RES D203 EXHAUST
EQUIP. LOCATION
BLDG D LVL 2 UNIT D203
BLDG D LVL 2 UNIT D203
AREA SERVED
UNIT D203
UNIT D203
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31101
•
31101
DESIGN CFM
70
70
ACTUAL CFM
74
69
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 2 D203
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
29 145%
FPM CFM
21
OF
DESIGN
1050/0
BLDG D LVL 2 D203
2
S1
4"
F.H.
-
20
26
130%
21
1050/0
BLDG D LVL 2 D203
3
Sl
6"
F.H.
-
30
26
87%
32
107%
SUPPLY
70
81
116%
74
106%
BLDG D LVL 2 D203
E1
Rl
6"
F.H.
-
70
60
86%
69
990/0
EXHAUST
70
60
1 86%
69
1 99%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 54 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D204 SUPPLY
ERV-RES D204 EXHAUST
EQUIP. LOCATION
BLDG D LVL 2 UNIT D204
BLDG D LVL 2 UNIT D204
AREA SERVED
UNIT D204
UNIT D204
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
75
73
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 2 D204
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
22
OF
DESIGN
1100/0
BLDG D LVL 2 D204
2
S1
4"
F.H.
-
20
27
135%
22
1100/0
BLDG D LVL 2 D204
3
Sl
6"
F.H.
-
30
28
93%
31
103%
SUPPLY
70
80
114%
75
107%
BLDG D LVL 2 D204
E1
Rl
6"
F.H.
-
70
66
94%
73
104%
EXHAUST
70
66
1 94%
73
1 1040/
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 55 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D205 SUPPLY
ERV-RES D205 EXHAUST
EQUIP. LOCATION
BLDG D LVL 2 UNIT D205
BLDG D LVL 2 UNIT D205
AREA SERVED
UNIT D205
UNIT D205
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
75
71
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 2 D205
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
21
OF
DESIGN
1050/0
BLDG D LVL 2 D205
2
S1
4"
F.H.
-
20
27
135%
22
1100/0
BLDG D LVL 2 D205
3
Sl
6"
F.H.
-
30
29
97%
32
107%
SUPPLY
70
82
117%
75
107%
BLDG D LVL 2 D205
E1
Rl
6"
F.H.
-
70
83
1190/0
71
1010/0
EXHAUST
70
83
1 119%
71
1 1010/
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 56 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D206 SUPPLY
ERV-RES D206 EXHAUST
EQUIP. LOCATION
BLDG D LVL 2 UNIT D206
BLDG D LVL 2 UNIT D206
AREA SERVED
UNIT D206
UNIT D206
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
90
90
ACTUAL CFM
95
90
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
90 CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.2
1.2
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 2 D206
NO.
1
THERMAL
CODE SIZE
S1 4"
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
21
OF
DESIGN
1050/0
BLDG D LVL 2 D206
2
S1
4"
F.H.
-
20
28
140%
21
1050/0
BLDG D LVL 2 D206
3
S1
4"
F.H.
-
20
27
135%
22
1100/0
BLDG D LVL 2 D206
4
S1
4"
F.H.
-
30
26
87%
31
103%
SUPPLY
90
107
1190/0
95
106%
BLDG D LVL 2 D206
E1
Rl
6"
F.H.
-
50
45
900/0
48
96%
BLDG D LVL 2 D206
E2
Rl
6"
F.H.
-
40
46
1150/0
42
105%
EXHAUST
90
91
1010/0
90
1000/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 57 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES A301 SUPPLY
ERV-RES A301 EXHAUST
EQUIP. LOCATION
BLDG A LVL 3 UNIT A301
BLDG A LVL 3 UNIT A301
AREA SERVED
UNIT A301
UNIT A301
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31101
•
31101
DESIGN CFM
90
90
ACTUAL CFM
93
93
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
80CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.1
1.2
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG A LVL 3 A301
NO.
1
THERMAL
CODE SIZE
S1 6X4
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
21
OF
DESIGN
1050/0
BLDG A LVL 3 A301
2
S1
6X4
F.H.
-
20
23
1150/0
20
1000/0
BLDG A LVL 3 A301
3
S1
6X4
F.H.
-
20
24
120%
21
1050/0
BLDG A LVL 3 A301
4
S1
6X4
F.H.
-
30
26
87%
31
103%
SUPPLY
90
98
1090/0
93
103%
BLDG A LVL 3 A301
E1
Rl
6X6
F.H.
-
40
53
133%
42
105%
BLDG A LVL 3 A301
E2
Rl
6X6
F.H.
-
50
41
82%
51
102%
EXHAUST
90
94
104%
93
103%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 58 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES A302 SUPPLY
ERV-RES A302 EXHAUST
EQUIP. LOCATION
BLDG A LVL 3 UNIT A302
BLDG A LVL 3 UNIT A302
AREA SERVED
UNIT A302
UNIT A302
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
74
70
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
60CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG A LVL 3 A302
NO.
1
THERMAL
CODE SIZE AK
51 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
27 135%
FPM CFM
21
OF
DESIGN
1050/0
BLDG A LVL 3 A302
2
S1
6X4
F.H.
-
20
24
120%
20
1000/0
BLDG A LVL 3 A302
3
S1
6X4
F.H.
-
30
26
87%
33
1100/0
SUPPLY
70
77
1100/0
74
106%
BLDG A LVL 3 A302
E1
Rl
6X6
F.H.
-
70
85
121%
70
1000/0
EXHAUST
70
85
121%
70
1000/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 59 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES A303 SUPPLY
ERV-RES A303 EXHAUST
EQUIP. LOCATION
BLDG A LVL 3 UNIT A303
BLDG A LVL 3 UNIT A303
AREA SERVED
UNIT A303
UNIT A303
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
73
73
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
60CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.7
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG A LVL 3 A303
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
20
OF
DESIGN
1000/0
BLDG A LVL 3 A303
2
S1
6X4
F.H.
-
20
26
130%
20
1000/0
BLDG A LVL 3 A303
3
S1
6X4
F.H.
-
30
23
77%
33
1100/0
SUPPLY
70
74
106%
73
104%
BLDG A LVL 3 A303
E1
Rl
6X6
F.H.
-
70
84
120%
73
104%
EXHAUST
70
84
120%
73
104%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 60 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES A304 SUPPLY
ERV-RES A304 EXHAUST
EQUIP. LOCATION
BLDG A LVL 3 UNIT A304
BLDG A LVL 3 UNIT A304
AREA SERVED
UNIT A304
UNIT A304
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31101
•
31101
DESIGN CFM
70
70
ACTUAL CFM
73
70
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
60CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG A LVL 3 A304
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
28 140%
FPM CFM
22
OF
DESIGN
1100/0
BLDG A LVL 3 A304
2
S1
6X4
F.H.
-
20
24
120%
20
1000/0
BLDG A LVL 3 A304
3
S1
6X4
F.H.
-
30
23
77%
31
103%
SUPPLY
70
75
107%
73
104%
BLDG A LVL 3 A304
E1
Rl
6X6
F.H.
-
70
82
117%
70
1000/0
EXHAUST
70
82
117%
70
1000/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 61 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES A035 SUPPLY
ERV-RES A305 EXHAUST
EQUIP. LOCATION
BLDG A LVL 3 UNIT A305
BLDG A LVL 3 UNIT A305
AREA SERVED
UNIT A305
UNIT A305
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31101
•
31101
DESIGN CFM
90
90
ACTUAL CFM
20
93
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
80CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.1
1.2
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG A LVL 3 A305
NO.
1
THERMAL
CODE SIZE
S1 6X4
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
24 120%
FPM CFM
20
OF
DESIGN
1000/0
BLDG A LVL 3 A305
2
S1
6X4
F.H.
-
20
26
130%
21
1050/0
BLDG A LVL 3 A305
3
S1
6X4
F.H.
-
20
25
125%
20
1000/0
BLDG A LVL 3 A305
4
S1
6X4
F.H.
-
30
22
73%
32
107%
SUPPLY
90
97
1080/0
93
103%
BLDG A LVL 3 A305
E1
Rl
6X6
F.H.
-
40
53
133%
41
103%
BLDG A LVL 3 A305
E2
Rl
6X6
F.H.
-
50
42
84%
52
104%
EXHAUST
90
95
106%
93
103%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 62 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B301 SUPPLY
ERV-RES B301 EXHAUST
EQUIP. LOCATION
BLDG B LVL 3 UNIT B301
BLDG B LVL 3 UNIT B301
AREA SERVED
UNIT B301
UNIT B301
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
90
90
ACTUAL CFM
91
90
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
90 CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.1
1.1
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG B LVL 3 B301
NO.
1
THERMAL
CODE SIZE
S1 4"
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
20
OF
DESIGN
1000/0
BLDG B LVL 3 B301
2
S1
4"
F.H.
-
20
27
135%
21
1050/0
BLDG B LVL 3 B301
3
S1
4"
F.H.
-
20
24
120%
21
1050/0
BLDG B LVL 3 B301
4
S1
4"
F.H.
-
30
24
80%
29
97%
SUPPLY
90
101
112%
91
1010/0
BLDG B LVL 3 B301
E1
Rl
6"
F.H.
-
40
46
1150/0
42
105%
BLDG B LVL 3 B301
E2
Rl
6"
F.H.
-
50
47
94%
48
96%
EXHAUST
90
93
103%
90
1000/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 63 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B302 SUPPLY
ERV-RES B302 EXHAUST
EQUIP. LOCATION
BLDG B LVL 3 UNIT B302
BLDG B LVL 3 UNIT B302
AREA SERVED
UNIT B302
UNIT B302
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
71
71
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
60CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
1.0
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG B LVL 3 B302
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
27 135%
FPM CFM
20
OF
DESIGN
1000/0
BLDG B LVL 3 B302
2
S1
4"
F.H.
-
20
24
120%
20
1000/0
BLDG B LVL 3 B302
3
Sl
4"
F.H.
-
30
26
87%
31
103%
SUPPLY
70
77
1100/0
71
1010/0
BLDG B LVL 3 B302
E1
Rl
6"
F.H.
-
70
61
87%
71
1010/0
EXHAUST
70
61
87%
71
1010/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 64 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B303 SUPPLY
ERV-RES B303 EXHAUST
EQUIP. LOCATION
BLDG B LVL 3 UNIT B303
BLDG B LVL 3 UNIT B303
AREA SERVED
UNIT B303
UNIT B303
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
50
50
ACTUAL CFM
51
50
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
50 CFM
50 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.7
0.7
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED NO.
BLDG B LVL 3 B303 1
THERMAL THERMAL
CODE SIZE AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
Sl 4" F.H. - 20 26 130% 20 1000/0
BLDG B LVL 3 B303
2
Sl
4"
F.H.
-
30
28
93%
31
103%
SUPPLY
50
54
1080/0
51
102%
BLDG B LVL 3 B303
E1
Rl
4"
F.H.
-
50
62
124%
50
1000/0
EXHAUST
50
62
124%
50
1000/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 65 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES B304 SUPPLY
ERV-RES B304 EXHAUST
EQUIP. LOCATION
BLDG B LVL 3 UNIT B304
BLDG B LVL 3 UNIT B304
AREA SERVED
UNIT B304
UNIT B304
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
50
50
ACTUAL CFM
52
49
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
50 CFM
50 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED NO.
BLDG B LVL 3 B304 1
THERMAL THERMAL
CODE SIZE AK • OF OF
FPM CFM FPM CFM DESIGN FPM CFM DESIGN
Sl 4" F.H. - 20 26 130% 20 1000/0
BLDG B LVL 3 B304
2
Sl
4"
F.H.
-
30
27
900/0
32
107%
SUPPLY
50
53
106%
52
104%
BLDG B LVL 3 B304
E1
Rl
4"
F.H.
-
50
59
1180/0
49
98%
EXHAUST
50
59
1180/0
49
98%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 66 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C301 SUPPLY
ERV-RES C301 EXHAUST
EQUIP. LOCATION
BLDG C LVL 3 UNIT C301
BLDG C LVL 3 UNIT C301
AREA SERVED
UNIT C301
UNIT C301
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
73
70
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 3 C301
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
20
OF
DESIGN
1000/0
BLDG C LVL 3 C301
2
S1
6X4
F.H.
-
20
26
130%
20
1000/0
BLDG C LVL 3 C301
3
S1
6X4
F.H.
-
30
27
900/0
33
1100/0
SUPPLY
70
78
1110/0
73
104%
BLDG C LVL 3 C301
E1
Rl
6X6
F.H.
-
70
85
121%
70
1000/0
EXHAUST
70
85
121%
70
1000/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 67 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C302 SUPPLY
ERV-RES C302 EXHAUST
EQUIP. LOCATION
BLDG C LVL 3 UNIT C302
BLDG C LVL 3 UNIT C302
AREA SERVED
UNIT C302
UNIT C302
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31023
•
31023
DESIGN CFM
70
70
ACTUAL CFM
75
75
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.9
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 3 C302
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
20
OF
DESIGN
1000/0
BLDG C LVL 3 C302
2
S1
6X4
F.H.
-
20
26
130%
22
1100/0
BLDG C LVL 3 C302
3
S1
6X4
F.H.
-
30
24
80%
33
1100/0
SUPPLY
70
75
107%
75
107%
BLDG C LVL 3 C302
E1
Rl
6X6
F.H.
-
70
83
1190/0
75
107%
EXHAUST
70
83
1190/0
75
107%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 68 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C303 SUPPLY
ERV-RES C303 EXHAUST
EQUIP. LOCATION
BLDG C LVL 3 UNIT C303
BLDG C LVL 3 UNIT C303
AREA SERVED
UNIT C303
UNIT C303
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
75
73
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.9
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 3 C303
NO.
1
THERMAL
CODE SIZE AK
S1 6X4 F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
22
OF
DESIGN
1100/0
BLDG C LVL 3 C303
2
S1
6X4
F.H.
-
20
24
120%
21
1050/0
BLDG C LVL 3 C303
3
S1
6X4
F.H.
-
30
27
900/0
32
107%
SUPPLY
70
76
1090/0
75
107%
BLDG C LVL 3 C303
E1
Rl
6X6
F.H.
-
70
92
131%
73
104%
EXHAUST
70
92
131%
73
104%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 69 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES C304 SUPPLY
ERV-RES C304 EXHAUST
EQUIP. LOCATION
BLDG C LVL 3 UNIT C304
BLDG C LVL 3 UNIT C304
AREA SERVED
UNIT C304
UNIT C304
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31023
•
31023
DESIGN CFM
90
90
ACTUAL CFM
90
92
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
90 CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.2
1.2
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG C LVL 3 C304
NO.
1
THERMAL
CODE SIZE
S1 6X4
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
20
OF
DESIGN
1000/0
BLDG C LVL 3 C304
2
S1
6X4
F.H.
-
20
27
135%
20
1000/0
BLDG C LVL 3 C304
3
S1
6X4
F.H.
-
20
24
120%
19
950/0
BLDG C LVL 3 C304
4
S1
6X4
F.H.
-
30
26
87%
31
103%
SUPPLY
90
103
114%
90
1000/0
BLDG C LVL 3 C304
E1
Rl
6X6
F.H.
-
40
33
83%
43
108%
BLDG C LVL 3 C304
E2
Rl
6X6
F.H.
-
50
62
124%
49
98%
EXHAUST
90
95
106%
92
102%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 70 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D301 SUPPLY
ERV-RES D301 EXHAUST
EQUIP. LOCATION
BLDG D LVL 3 UNIT D301
BLDG D LVL 3 UNIT D301
AREA SERVED
UNIT D301
UNIT D301
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31023
•
31023
DESIGN CFM
70
70
ACTUAL CFM
71
73
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 3 D301
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
25 125%
FPM CFM
20
OF
DESIGN
1000/0
BLDG D LVL 3 D301
2
S1
4"
F.H.
-
20
28
140%
20
1000/0
BLDG D LVL 3 D301
3
Sl
6"
F.H.
-
30
24
80%
31
103%
SUPPLY
70
77
1100/0
71
1010/0
BLDG D LVL 3 D301
E1
Rl
6"
F.H.
-
70
82
117%
73
104%
EXHAUST
70
82
117%
73
104%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 71 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D302 SUPPLY
ERV-RES D302 EXHAUST
EQUIP. LOCATION
BLDG D LVL 3 UNIT D302
BLDG D LVL 3 UNIT D302
AREA SERVED
UNIT D302
UNIT D302
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
71
68
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
120
120
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 3 D302
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
26 130%
FPM CFM
21
OF
DESIGN
1050/0
BLDG D LVL 3 D302
2
S1
4"
F.H.
-
20
28
140%
19
950/0
BLDG D LVL 3 D302
3
Sl
6"
F.H.
-
30
23
77%
31
103%
SUPPLY
70
77
1100/0
71
1010/0
BLDG D LVL 3 D302
E1
Rl
6"
F.H.
-
70
79
113%
68
97%
EXHAUST
70
79
113%
68
97%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 72 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D303 SUPPLY
ERV-RES D303 EXHAUST
EQUIP. LOCATION
BLDG D LVL 3 UNIT D303
BLDG D LVL 3 UNIT D303
AREA SERVED
UNIT D303
UNIT D303
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
70
69
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 3 D303
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
28 140%
FPM CFM
19
OF
DESIGN
950/0
BLDG D LVL 3 D303
2
S1
4"
F.H.
-
20
24
120%
21
1050/0
BLDG D LVL 3 D303
3
Sl
6"
F.H.
-
30
26
87%
30
1000/0
SUPPLY
70
78
1110/0
70
1000/0
BLDG D LVL 3 D303
E1
Rl
6"
F.H.
-
70
81
116%
69
990/0
EXHAUST
70
81
116%
69
990/0
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 73 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D304 SUPPLY
ERV-RES D304 EXHAUST
EQUIP. LOCATION
BLDG D LVL 3 UNIT D304
BLDG D LVL 3 UNIT D304
AREA SERVED
UNIT D304
UNIT D304
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31023
•
31023
DESIGN CFM
70
70
ACTUAL CFM
74
68
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
70 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.8
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 3 D304
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
23 1150/0
FPM CFM
21
OF
DESIGN
1050/0
BLDG D LVL 3 D304
2
S1
4"
F.H.
-
20
27
135%
20
1000/0
BLDG D LVL 3 D304
3
Sl
6"
F.H.
-
30
26
87%
33
1100/0
SUPPLY
70
76
1090/0
74
106%
BLDG D LVL 3 D304
E1
Rl
6"
F.H.
-
70
79
113%
68
97%
EXHAUST
70
79
113%
68
97%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 74 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D305 SUPPLY
ERV-RES D305 EXHAUST
EQUIP. LOCATION
BLDG D LVL 3 UNIT D305
BLDG D LVL 3 UNIT D305
AREA SERVED
UNIT D305
UNIT D305
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
70
70
ACTUAL CFM
72
72
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
70 CFM
80CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
121
121
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
0.8
0.9
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 3 D305
NO.
1
THERMAL
CODE SIZE AK
S1 4" F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
28 140%
FPM CFM
20
OF
DESIGN
1000/0
BLDG D LVL 3 D305
2
S1
4"
F.H.
-
20
24
120%
21
1050/0
BLDG D LVL 3 D305
3
Sl
6"
F.H.
-
30
26
87%
31
103%
SUPPLY
70
78
1110/0
72
103%
BLDG D LVL 3 D305
E1
Rl
6"
F.H.
-
70
60
86%
72
103%
EXHAUST
70
60
86%
72
103%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 75 of 102
40A-
TESTING ANO Ca
SERV•CES
• • • HOUSING HOPE ELC FIELD APARTMENTS
• • EDMONDS, WA
••• • 2230199
• BRYCEHURLBUT
AABC
UNIT DATA
UNIT ID
ERV-RES D306 SUPPLY
ERV-RES D306 EXHAUST
EQUIP. LOCATION
BLDG D LVL 3 UNIT D306
BLDG D LVL 3 UNIT D306
AREA SERVED
UNIT D306
UNIT D306
MANUFACTURER
PANASONIC
PANASONIC
MODEL NUMBER
FV-10VE2
FV-10VE2
SERIAL NUMBER
31012
•
31012
DESIGN CFM
90
90
ACTUAL CFM
93
86
T.S.P. "W.C.
0.40
0.40
TESTED SPEED
90 CFM
90 CFM
STATIC SETTING
N. / APPL.
MOTOR DATA
N. / APPL.
MANUFACTURER
PANASONIC
PANASONIC
HORSEPOWER
68 W
68 W
NAMEPLATE VOLTS
120
120
TESTED VOLTS
119
119
NAMEPLATE AMPS
1.7
1.7
TESTED AMPS
1.1
1.1
MOTOR RPM
VARIABLE
VARIABLE
SPEED
6 SPEED
6 SPEED
PHASE / HZ
1/60
1/60
OVERLOAD SIZE
AREA SERVED
BLDG D LVL 3 D306
NO.
1
THERMAL
CODE SIZE
S1 4"
AK
F.H.
•
FPM CFM
- 20
THERMAL
OF
FPM CFM DESIGN
27 135%
FPM CFM
20
OF
DESIGN
1000/0
BLDG D LVL 3 D306
2
S1
4"
F.H.
-
20
26
130%
21
1050/0
BLDG D LVL 3 D306
3
S1
4"
F.H.
-
20
25
125%
21
1050/0
BLDG D LVL 3 D306
4
S1
6"
F.H.
-
30
22
73%
31
103%
SUPPLY
90
100
1110/0
93
103%
BLDG D LVL 3 D306
E1
Rl
6"
F.H.
-
50
44
88%
47
94%
BLDG D LVL 3 D306
E2
Rl
6"
F.H.
-
40
47
1180/0
39
98%
EXHAUST
90
91
1010/0
86
96%
FORM: DIRECT DRIVE HRU- HRV- ERV- DOAS LESS THAN 1K CFM TEST DATA
10/09/2024
Page 76 of 102
GENERAL NOTES
AW\ HOUSING
HOPE
1. we keep hope alive
LACES ALL. NDNLDNDITIOONED ��
SPACES ALL E lxspLAEG
.INS T""Tp l o) l a) 10 11 12
11
WITH IM INGM ININVFlNllGLAL.L UHONO 7 7
s WITH INO THHERMAL BRIDGING.
S. FINEITIAUTaIANirvo,ELECTRAcTE FN DESIGNS
cnEciiprve To lN000Rn AP G Doethwest
PINES °UNIITS SHALL RE CONCEALED
CEILINGN. WALL OR
lrvO SURFACE .—.---.—.—. .—---.—.— .—.—.—.—.---.—.——.—.—.—.—.—. —. .—.—.— ARCHITECTS
UIHANICAL CONTRACTOR SHALL ___ ___ _ _
IN TL REDpIRED FOR A
a� EH -FIRE IIII
DHopES MOTORD PUMPS
ALL MANUFANS. Fa ET 12 j rocxlxaw MRF xisFxj IIII IIIII E\ OPE
CLEARAN DES wR1ACTURE auTF`ra H"En"RE ° H I� ox-NOF ox RonFRT EEINF"si'sF N EII IF
j GroaFT TLL BE LOCATED AWAY nT c IryasF Pr - PROVIDED.TATS SECURE
OUR ESFOR w 'A - IIII
FALSE RE DIINGS UCH ASSUNLIGOPERABLE
0 CUP'6F URN 91110
E
G. AIpTE MINALLOCATIONSASSHOWNARE
OitDINATE E%ACi LOCATIONS OF AIR
ELEMERMENiS WGHHTS PIPING STRUCTURAL EQUIPMENT ® ® IIII
CTUR, .BL,ecs o,F , CORRIDORoETC 577 j
05k�� Y
35F S15F� MF eNs»yR�N
7. PROVIDE I All
MANUAL VOLUME DAMPERS ON
IANCINCH DUGOR ATS TO PROVIIEE MEANDEVICES OF
FAR AS POSSIBLE FR. . AIR
EGUIREp !� ° FFICE F E .RUNRY IIII .a
CTO BE PYE CATIONS FRVIiFs; ERNIIEllIPEl WITH REMOTE IFFs [-a7Fn[ UP H�
SHALL �RS (YOUNG REGULATOR TYPE) CI
ANYFLEEISLEDUCTWORKRUNSSHALL
R.
NOTALLEp WIT IN LENGTH ANpsHALL BE rvoTE.p RN
6H NO NINKpR SHARP B ---
SENDSRpRNs - --- --- --- — --- — — — --- m
E. NCLUDETpRNNGVANESGNALL
REGTAN6pLAR pUGT ELBOWS
,U WHERE POSSIBLE ARCIDUTILIZING)])9U -,�.. j ' ' YEN}l _ — __$ -
pEGREE ELBpWG W TH ppGTLENGTH
wETWTERTHENOFLESSTHAN� L IIIII, ; o
DIAMETER (OR EDpIVAIENT DWMETER) III III III:
CONERACi RsxALLCGGRpNATEW Ll
RD ITEDT TO MEET
THE C E A A NC � � 0
v o RMINATIONS MEETTHECLEARANDE9 I IIIIII W w
HANICAH CODE°TO OPERABLE NAL _
„ A � IIII
o oa pMESTrvTAKEGANpMEpnAN AL w =
C CO Z W
CD N
-4 CD m _IIII �-
o -,.-'-�--- ------ I IIIIIII N OC
-
—1 U Q
N
NFD =1
O J
cFIBLE1 cF331BLEl
3sIIII IIII � Lu � m
o _
o -I
aFv sF sareF =
to❑F. _- CONSTRUCTION
IIII
II .o II DOCUMENTS
77A❑ j - � III ISSUE OATS JAN. 3, 2023
o ❑
jI DID TI � it RFVUR.NwCHEDpLE
FlRE RIBFR III .III ) IIIII U6I1413023 CCpM�rRESU
o a III=IIIII
HELI
) owx wFe��HPwH) III11I FIRE RISER B B` 27 F7 CHro„3CP3 RFIC36
IF I11=1 � HEYPUN
- - - - =1 - - --- _--jll�
D
DOOR
-III 0
R R R III CONTENTS
MECHANICAL -
- = FLOOR PLAN -
20 23 24 - H 25 == LEVEL 1 -
\� =III— I I I I 1 BUILDING A& B
II -II =III=
CHEIRED OR—,
PROJECT
NO 2027037.00
MECHANICAL FLOOR PLAN - LEVEL 1 - BLDG A & B N� M2.11
rre-r-o•
1 2 ` aaJ o ou :W\ HOUSING
GENERAL NOTES I HOPE
we keep trope alive
1. ALL
A ALL. F , ,2
2. REFRIGERANT PIPING SHALL BE INSULATED1
INCLUDING CONTIN TLAD LRIDGNG. Ii LSLV,.<r/�SIR RTS WITH SUPPO
'DGO, ESIGNS
co TiONNSIPAND CONDENSATE PPINc k n — — ---- — — — — — — — — — — — — — LhwC
BT
I.
EDNONS To NO..R HEAT / ARCHITECTS •
REMREPIND WALL ORACEILING (NO SUURFACE EXHAFUNSFTALOUVERI I I{
NGI BID
9
"CALCOORDINATE PROVOISION OCONTRACT"F ALL REQUIRED I y
R EQUIPMENT LOCATED lJtllJ 111 ABOVE
CEILINGS, INCLUDING BUT NOT p-MAI A.
I \
LIMITED TO HEAT PUMPS BALANCING M
LAMPDEVICESD. ANDDD MPENE T y,uxrez ancF � i Ec OPE
RoCFROM�000ESFOREQUIPM NTARE°
o
FAINSE EADINGsSUCHASOPERABLEA i • :: e^
wB. GT UNIGHT. TC. ARE ID li
E. AIR OPPRERMINALLOCATIONS
OCA o aA SHO
INTS LIGHTS PIPINGS, EQUIPMENFAL - AUNG
-x°Ew U.SFpTvpF6 BLY
TEEM AUND S LLLL�®�
ELEMENTS LIGHTS
UND ❑ ® N �95F71 BE1IPFB
7. LL BRANCH DUCTS TO ROVIDE MEANS OF _ ® :.BIDER :.BEoFB I
BALANCING FOR AL RMINA
LUN oSSU EFMPoaMRTEMIPAL a,-x1l.o'ROBOF I°E _-----_- - - - - ----------
RED RED
R
BERVED. NY
i0 III IN ACCESSIBLE LGCATIONS i
BHALL BE EOUIPED R REMOTE HEAVY METALRIGIDa- -- --
ADTBATDRB YDBNGREGBATDRTYPE' RDNNDDNDTBDNLY
C. ANY FLEXIBLE BUCTw.RR RUNS SHALL r
HOT EXCEEDBINLENGTHANDBHALLBE FOR DRYER EXHAUST. II IIIIIII II IIIIIII
I m
INSTALL. WITH NO RN, OR I PaoVDELOUVEREDDOOR a+ W
SENDS"RNs. DRYER'ENTUPToaooF
D. N NING VANES ON ALL RM INAH Vk FURRED OEXHAU T //��
E rvcuinR°uGTELeows. WALL(2.e)TYPB) iii a— N 3
DEGRE ELBOWS WIiTH' ouaj'zINGTH so O I— w
cn III EXHAUST DUCT
A uP TO RooF
CONTRACTOR
ET NTAKE ARE DPS IN 1 III=III uol) 0 0
�B
mA
REEFER LENGTH I'r°TArcELOU ER
BETWEEN THEN of LESS THAN zR
METER (OR EOuIvuENT DwMETER� DRYER MANE UP AIR = o
,,. CONTRACT TO`ENSLCooaowATE WITH TArcE LOUVER
O NECT TO ErvsuREAU EznnusT IN BE LA _____ _____ - r----v
TERMINATIONS MEET THE CLEARANCES o o ; W 'M
REDUIRED INTxE2nie IUTERAALE AL I
p
i
oMEGn'R INGGDETDGPERABLE I IIIIIII i� J
l� (9 OPENINGS, INTAKES, AND MECHANICAL r -
� EQUIPMENT. 1 _ W
o-------------- ------ - - -- ------ - ----I
N EuFB B6oEB �EoEB BuFB BoEB ruLE J d
D 2 W Q
-97=- - - - ❑ _ CONSTRUCTION
DOCUMENTS
g.,.II a JAN.3, 2023
NECH
Hk esf ER
KEYPILAN
D1i0
EH -FIRE F I uxptian
.---.--—.---.— — — — OSI,A/2028 CCD Wt
LL
�T � ROVIDE LOUVERED DOOR
�5 16 17 16 19 20 CONTENTS
°0 IJ.J
MECHANICAL -
FLOOR PLAN -
LEVEL 1-
BUILDING C & D
CHECKED Ch.-
NO 2021031.00
ANICAL FLOOR PLAN - LEVEL 1 - BLDG C & D NE)M
n ME CH2.1 2
N O
(0o
m m
Co
O
O �
O
N
GENERAL NOTES
B. EFRIGERANTLPIPI GS ALL BE INSULATED
INCLUOIING CONTIRUSOUN INSULATION AT
SUPPORTS WITH NO THERMAL BRIG ING.
REFR
CON ECTiONS, ANo CONDENSATE PIPING
AND x cepN3 TO IN D00R HEAT
PUMPS UNITSL BE CONCEALED
BEHINDWALLOR CLEILING (NO SURFACE
4. A
COORDINATE PROVISION OF ALL REQUIRED
R EQUIPMENT LOCATED
CEILINGS IN.
LLIIM ITED TOO EAT P MLPSIBAANCINGT
DEVICES, M OTORIZED DAMPERS, FIRE T
ALL CLEARANCES FORE"U'p XEUM AR'ED
E. THERMOSTATSSNiNL SOILIRCESEFOR
WINDOWS o'RECTAUNUlGHT IF
A. AIR TERMINAL LOCATIONS AS SHOWN ARE
RDINATEEEXACT LLOCATTIIONS. FLAIR
COORDINATE
WITH cFILINGS, STRUCTURAL
ELEM
ENTS LIGHTS PIPING, EQUIPMENT,
ETC
ALL BNCRHRCPER.LEIAVIPOF
BALVOLUME A.A"NULNCING TOVLUMSHALL PROVIDE
'AMCIPER'CA
BE
FAR AS POSSIBLE FROM AIR T
MR"U"RED
e EDLIPEO WITH EOOLocano 6
ACTUATORS rOUNG REcUATOR TVPE)
DE6 IN LENGTTH ANios LBE
�NSTALLE� WITH NO KINK OR SHARP
CRN R. INCLUDE TUUING VANES ON ALL
RECTAN=R DUCTNG 12) SB
ELBOWS
lo. WHERE DEGREE s wiTxl .LOT LENGTH
BETWEEN
EQUIVALENT DIAMETER)
11. DIAMETER
SHALL OOR ORDINATE WITH
ARCHITECT
ALL
EXHA EST
aFRul'RED 11 DECLINATIONS IEIII R INTERNATIONALS
EENINGS, IN`ASES,A OPERABLE
EQUIPMENT.
�� T Y
AkF\ HOUSING
L� chwest
J ARCHITECTS
EGOTOPE
r�n�><rrru•Ior■n�
41
I
sB�
Ds1412023 CCDBDI
�o
MSD4
0
0
20 21
22
225
23
24
25
o0
CONTENTS
MECHANICAL -
FLOOR PLAN -
LEVEL 2 -
I
BUILDING A & B
n MECHANICAL FLOOR PLAN
- LEVEL 2 - BLDG A & B
PROJECT NO 2021031.00
N� ^A 2,2
cQ o
CDm
ON
0
o�
0
N
GENERAL NU ES
1. ALL IUINGKENSUFRIRANTLBATEO i0E B.
2. REFRIGERANT PIPING SHALL BE INSULA
TED
NOLDOONTINUISOUN INBMlATION AT
EUPP= NO THERMAL IRILDI IN.
B. HELP
FINE ELE.TNICA
CONNETIONSANAND CONNECTIONS TO°INOOOPHEATPING
BEHIND
WAIL oR CEILING (No SURFACE
MOUNTING
< RUINATEEROVVIISION OCONTRACTORF ALL
RENT EOCAEE.
AlllllPANCEILINGS, INCLUDING BUi Noi
TED
LIMITED T M HEAT ZEMPSA, SEIANCING
CA.PERS
AND
ENGLEETHAT
ALL MANUFACTURER MHE RENRoNoPOU"EAE
s AWAY
FROM FALSE WINDOWSANY POTENTIAL SUCH ns OPERABLE
S. S AS SHO
OXIMA ELOCONTRACTT1Rss AWN ARE
RAL
ETERMINALEMENTS, WITH
PIPING, QUIPMENT,
ETC
1. PROVIDE MANUAL VOLUMER—EMEnns OF
uLGNIALANEl
CINO FIR
ALLTG cR
VOLUMFAR AS NSI9LE5 ROMLAIR TEL0RM, AL As
SERVED AN,VOLUMEREouIREo
TO BE
SHALL EAEOOIPEA WITH REMOTECATIONs
ACTUATORS (YOUNG REGULATOR TYPE)
S.NOT o V IN LENGTH AND SHALL BE
INSTALLED WITH NO KINKOR SHARP
IUES. NCLDTURNING VANES ON ALL
DUCT
ws
DEGREE ertlNLENGTH 9010. wHD
BETWEEN THEN
THAN 2.
11. 2NTRACToa SHALL COORDINATE W, H
ARCHITECT TO ENSURE ALL EXHAUST
RE_F'MEET EENAICLEARANCES
DNTNTRTOA
MECHANICAL CODE
INTAKESA MANICAL
KIPMENT.
T T f
Y Y
15 16 17 18 19 20 21
AkF\ HOUSING
I unoc
DESIGNS
thwest
ARCHITECTS
EGOTOPE
file°
W °
a_ U 3
0
2 Z o
0J W
Z W w
C/) LLa
O J a
= wQ
CONSTRUCTION
DOCUMENTS
ISSUE DATE JAN. 3, 2023
[ascription
r�orsn a/zon cc° mt
°0 IJ.J
MECHANICAL -
FLOOR PLAN -
LEVEL 2 -
BUILDING C & D
MECHANICAL FLOOR PLAN - LEVEL 2 - BLDG C & D N�4) M 2.22
N O
(0o
m m
N
0
o�
O
N
GENERAL NOTES
1. RKIIN NON pONUITIONNEDSPACES ED
C. WITH IM INIMUMt PIIPINGHINSULATION NT
S WITH NO TTHHERMALNBRIDGING?
3. SUPPORTS WITH
PIPING, ELECTRICAL
A NO UNNECTIONS OIIN� ORTH pTPlx
BEHIND
PUMNDI GALL OR CE'HNG(NG SURFACE
MOU4. MECHANICAL CONTRACTORALL SHAAREQUIRED
ACCESS PANELS FOR EQUIPMENT LOCATED
ABOVE CEILINGS INCLUDING A UT N OF
PUMPS BALA MI NO
DEVICES MOTORIZED DAMPERSCFI E
CLEARANCES FOR EQUIPM NTRETHAT
ALL MANU 'A CTURER ET ARE
P"DEDD
s.FROM ANY EFALSE READINGSNTIAL souIDEswRwAr
UGH AS OPERABLE
ATMIACISSS. AIR TERMINAL LOCATIONSAPR
ORMINALSWCoNT SHALL
ITHACEILING9?SOTRUCTURAL
ELEMiS, LIGHTS PIPING, EQUIPMENT,
]. ETC.
MANUAVow.E OAEEE GN
OF
OR DUCTS TO ED M
AM
B=G TOR ALL TERMINAL DEVICES.
VOLUME DAMPERS SHALL 11 LOCATED AS
FAR AS POSSIBLE FROM AIR TERMINAL
TO BE ED INLACCESSIBLLE LOCATTIIONS D
SHALL BE aSS(YOUNNG REGUL TOR TYPE)
S. ACTUATORS
LEXTELE OUCT"RK RUNS SHALL
NOT EXCEED B IN LENGTH AND SHALL BE
INSTALLED WITH NO RINK OR SHARP
SENDSOLURNS
INCLUDE TURNING VANES IN ALL
RECTANGSEABUIIID. OSIBLLBOIUTLZING(2) SO
DEGREE ELBOWS WITH ILIT LENGTH
BETWEEN THEN o' LESS THAN .
OIA ETER(OREQUIVALENTDIAMETER)
it OCHRECTTO ENSD EOALLL EIXHAUSTITH
RMIINATIONS MEET THE CLEARANCES
REQU
INTERNATIONAL
AGE,INCAKES,A D MECHANICALT.
EQUIPMEN
I
(D--- - jt`!'� - - - -
II �:�
II
,0 ■■�::►�•'�[�
a 'I
.�
AkF\ HOUSING
L� chwest
J ARCHITECTS
EGOTOPE
=11ai12nrua001N�
ON1412023 GDDD01
KEYPLAN
MSNB
Ir77o
I
a a
20 21
22
22.5
23
24
25
NNTENTS
MECHANICAL -
FLOOR PLAN -
LEVEL 3 -
BUILDING A & B
n MECHANICAL FLOOR PLAN
- LEVEL 3 - BLDG A & B
PROJECT NO 2021031.00
NE) ^A 2,3
N O
(0o
m m
NN
O
O �
O
N
GENERALNOTES
1. ALL Iry NONLpONUITIGNRENU
E. WITH IMINIMUM1 PIPING INSULATION LATER
UDRTS WITH NO THE
RMFL BR_BNG?
]. SUPPORTS
RIEC "i.ANIoc'oN"N.'RAT'
CORRECT To INDOOR HEniPIN
PUMPS UNITS ORAL BE CONCEALED
BEHIND WA I MD GURFACE
MOUNT
A. MECHANI CONTRACTOR SHALLDOOR ALL UWED
PROVISIONACCESS PAN ELS FOR pUIPM ENT LOCATED
ABOVE CEILINGS, INCLU DING BUT NOT
ING
DEVICESi MOTORIZED DAPUMPSMPERSBALANCFIRE
DAMPERS IF— AND FANG.ENMURETPAT
ALL M AN U FAIT FOR E.U'PM°ENT ARED
FROM All SFALSE READINGSHALL SRIAOO
LCH AS OPERABLE
WINDOWS DECT SUNLIGHT ETC .
B. AIR TE MINAL LOCATIONS ASSHOWNARE
AppCOORDINATE
RMENLSWITHCoNT
Te IILINGSIPING,ETRRIUCTURAL
ELEMI. OVIDE MANUAL VOLUME DAMPERS ON
ALL BRAN PDUCT-01ROVIDEMPARS.F
BALANCING FOR ALL TERMINAL DEVICES.
VOLUME IAIIIRIIHALLIELIIATEIAI
SERVED AN'RED
ED IN ACCEeBRIBLE ME LOCAS RETIONS
'HALL BERs (YOUNG REGULAPOR TYPE)
B. LEIIBLE DUCTWORKLENGTH RUNS 'HALL
NOTAND SHALL BE
INSTALLED WITH NO KINK OR SHARP
'I. INCLUDE
III. O881BEE ABOIO UTILIZING (2) BO
DEGREE EI111111TH DUCT LENGTH
DIAMETER (OR EQUIVALENT oNMETER)
11. RClnreC: OENSUREA LEXHAUATlTH
RMINATIONS MEET THECLEARANCES
REDO
E 2111 INTERNATIONAL
nTO P.AALE
GCaNTAKES A D MECHANICAL
ECUIPMEN T.
=1I HOUSING
HOPE
i I w keeM none aRVe
DESIGNS
LID VVBS
west
ARCHITECTS
Q EGOT OPE
cly Nae
Euulaeal aarsax
8985E
u
15
16
17
18
19
20
21
a N3
O H
2 Z
Lu
U' J N
Z W �
N ILL
o �a
T 111 �
DOCUMENTS
� �
°0 IJ.J
NTENTS
MECHANICAL -
FLOOR PLAN -
LEVEL 3 -
BUILDING C & D
n MECHANICAL FLOOR PLAN - LEVEL 3 - BLDG C & D NE) M 2.32
IQ O
o
CD m
W N
W � O
O �
N � j
I ,
I �
I I
I
I
I �
I I
i
AkV\ HOUSING
L� chwest
J ARCHITECTS
EGOTOPE
Ill
a 3
O H
2 Zoo
0 J m 3
Z W w
N
o �a Q.
r�n�irrru•ior■n�
I � � 1 j' oo11412023 cco ao1
D I !-ii
HYPIAN
20 21 22 225 23 24
25 00NiENi5
MECHANICAL -
ROOFPLAN-
BUILDING A & B
MECHANICAL ROOF PLAN - BLDG A & B
NO 2021031.00
,A1
N�D M 2.41
U
Q Q
HOUSING
HOPE
w keep hope alive
.
DE
S CICT
ARCHHITTEE ARCTS
EGO OPE
wry Nae
w m
(L cl) 3
O F-
= Q Z o
0
0 J
m
CWC
C
Ap
O
AWL
O �
O
N
-ja
W Q
CONSTRUCTION
DOCUMENTS
ISSUECATEJAN.3,2023
�\
1\U/�
aruoalzaza cco aot
IJ ICJ
ED
CONTENTS
MECHANICAL -
ROOFPLAN-
BUILDING C & D
U ME CHANICAL ROOF PLAN - BLDG C & D
N�
PROJECT NO 2021031.00
M2.42
��
CD �
01 N
0
o IN)
0
N
I
of
22 225
&MECHANICAL TYPICAL UNIT PLAN -1BD MIRRORED
va•-v-o•
II O
O1'�1�'
—
s EXxADBTDN
0
22.5 23
n MECHANICAL TYPICAL UNIT PLAN - 1BD -UNIT B203
U va = r-o
GENERAL NOTES - TYPICAL UNIT PLANS
1. G'G FOesA"SE REALIN.B EDOF AS OPEHAD
E WINGOWS, DIECT
2. ON RIGCTWORK OEOUIPMENT
CATIONS ARE APPROXIMAITEi COINTRASCORS BHALALHNALSE OUST
ROUTING COORDINATEB ENLGHTINGNPIR T IPPING ETTE C.
OFALL
"V�C. DAMRANCH DUCTS SUCH
a. RIGID METAL OAL
THAT EVERY IUCTIGISHALL AE USED FOR ALL VENTILATION. (NO FLEX
S. CONLOTSTRACTORTO EN8U
EXHAUST TERMINATIONS IN UINITSEM EIET THE C EARTo C,ANSEERA BS REQUIRED IN
THE 2SIX INTERLE o
CAL EQUIPMENT.
A. RDINATERFINAL DIFINTAKES AND IFFUSERS AND ELEVATI GRILLE LOCATIONS WITH
ARCHIT1."TU EL (MI SIZE ]BkSB•) IN
CEILLINGEF6 R MAIINTENAHo VENTNC RAND FEACH TU RE NEE%HAILS F ERv UNIT.
E. IN EACH i
LIVING
SPACE AND BEDROOM.
REEEREUCE xeAT LOAD CALCuL
IS. PR
DOORS
ii AM ING. REFERENCIE ATR�CTFRAL PLANBFOR FO WITHIN
DETAILS12. DROPPED CEIRIN OR AND SOFFITS.
CAL
I�TONEERENIRIECTUREPINSFHTRINAI. RFCEACHTTALLAOR DEAILS.PLANS 1S. CHN IF DOMESTIC HO011 TO BE A MINIMUM OF TOO FM. REF CH
FOR DETAILS
SHEET NOTES
AkIF\ HOUSING
I HOPE
we keep hope alive
DE I S
R
llo_BF
A
ARCHCHITECEC TS
EGOTOPE
W °
a N 3
O H
= OZ o
0 J
Z WILL
w
� U Q
O Ja
2 wQ
CONSTRUCTION
DOCUMENTS
CONTENTS
MECHANICAL
TYPICAL UNIT
PLANS -1BD
CHECKEO --
NO 2021031.00
M5.01
AW\ HOUSING
GENERAL NOTES - TYPICAL UNIT PLANS
I HOPE
we keep hope alive
POTENTIAL
SE RECIN SG SUCH AS -AD E WINDOWS, DIRECT
LOCATIONS
2. ALL EQUIPMENT
CATIONS ARE SHALL JFINALSE DUCT
PIRATE.
T a
OEDED, AND
E NARO
COORDINATECOICONTRACTORS
ROUTING AS
COO OF ALL HVRAAD ELCEM ENT: WITH
aRUCTURnneun Hen aPIPINGC. ETCbERa ou Au BRANCH
S. NCH ou Ts sucH
AIR
FOR
DoE"G N S
LID we s t
ARCHITECTS
4. RIGID METAL OUCTIGISHALLA E USED ALL VENTILATION. (NO FLEX
DU1. CTS)
SHALL TH ARCHITECT TO EN " RE ALL
EMEIET
EXHAUST TERMINATIONS IN UCTOR
NITS THE C EARANCES REQUIRED IN
OPENINGe,
A. RDTHE 'X INTERHITINATERFINALINTAKES AND HDIFFUSERANICAL S AND I GRILLED LOCATIONS WITH
COORDINATE a AL RCP. QELEVATouRE
\
1.
cEouripEFsa moiniEnnH. VENTnc Rnno FEACH arcx uEeS GFERvunR.
EL IOF SIZE UNIT. MN
S. COVE HEATERS TO BE PROVIDE LATious FORRSGING. A
IC AT ALL'NT'P'PP DOORSITYWITHIN
OPE
y Nae
mBOXEDCUT
RRETO BE I
9
LED CEINGING.EFERECE EUPROVAL OFORMNTIS
ANOFFTe0CEPC CAL
SOG. INAL LOCATION PENDINGFURTHER
IPMENT
EA+M Lieu aats�x
^
\\//
\I.
ROINATION. REFERENCE ARCHITECTURAL FOR DETAILS.
DOMESTIC HO011 TO BE A MINIMUM OF IN��
P'NNFGRDESHEET
NOTEST.
NTC �N ERV INTAKE, ERV EXHAUST, AND RANGE HOOD
_4
aeoo.-AGGRNE`GATE
50 CFM 56,03E
FFR
AIR. OF TIE OPENINGS
NEG.aHALNGTECEEQ,MpaGIN.NA
SO
w °
2
a //) 3
(06
O"
= pZ
fD CO
C) J
oN
Z w
A
V) LL
N
1
UQ
O a ry
= wQ
CONSTRUCTION
DOCUMENTS
ISSUE e JAN. 3, 2023
MHEG
0
OMQ2023 GGGao,
22.5
23
MECHANICAL
n MECHANICAL TYPICAL UNIT PLAN - 1BD -UNIT B303
p
TYPICAL UNIT
-0'
PLANS-1 BD
NO 2021031.00
M 5.02
��
CD �
00 N
O
O A
C)
N
(
22 22.5
23
MECHANICAL TYPICAL UNIT PLAN-1BD.ADA-B
2
GENERAL NOTES - TYPICAL UNIT PLANS
ONEIGHi FG CFAL SE REAUINGC "LOCATED
GUCN AS GPERAB E WINGOWS, UIRECi
2. G EQUIPMENT
CATIONS ARE ANARO PROV a ONNIERAO ORS SNFTLHNALME DUCT
B ENLGHTINGNPIR T IPPING ETTE C.
OFALL
"V�C. DAMRANCH OUCTS SUCH
a. RIGID METAL UAL
THAT EVERY IUCTIGISHALL AE USED FOR ALL VENTILATION. (NO FLEX
1. CONLOTSTRACTORTO EN8U
EXHAUST TERMINATIONS IN UINITSEM EIET THE C EARTo C,ANCEERA BS REOUIREU IN
THE 2SIX INTERLE o
CAL EQUIPMENT.
A. RDINATERFINAL DIFINTAKES AND IFFUSERS AND GRILLE LOCATIONS WITH
ARCHIT
"TU
1. EL (MI SIZE ]BkSB•) IN
CEILLINGEF6 R MAIINTENAHo VENTNC RAND FEACH TU RE NEE%HA113 F ENV UNIT.
S. LIN EACH FOR SPACE AND BEDROOM.
IS. PREEREU RECE xeAT Lone CALCu
ALLPTTPR
DOORS
12 UNIT ERVARE BOXED CUT TO BE
REFERENCIIN OR AND SOFFITSE ATRCTFRAL PLANRFOR FO WITHIN
GETS'LL3.
CAL
I�TONEERENIRIECTUREPINSFHTRINAI. RFCEACHTTALLAOR DEAILS.PLANS 1S. CHN IF DOMESTIC HO011 TO BE A MINIMUM OF ISO FM. REF ARCH
FORDETAILS
NOTES
AkIF\ HOUSING
I HOPE
we keep hope alive
I S
R
LID _BF
A
ARCHCHITECEC TS
EGOTOPE
W °
a N 3
O H
= OZ o
0 J
Z WILL
w
� U Q
O Ja
2 wQ
CONSTRUCTION
DOCUMENTS
-Erg
CONTENTS
MECHANICAL
TYPICAL UNIT
PLANS - 1 BD.ADA
NO 2021031.00
M5.03
��
CD �
WN
O
O �
O
N
20 21
MECHANICAL TYPICAL UNIT PLAN - 213D MIRRORED
23
24
n MECHANICAL TYPICAL UNIT PLAN - 2BD
va•=v-o•
GENERAL NOTES - TYPICAL UNIT PLANS
SE M"TT' 'FALLREAUINGS SCIA'UCH AS OPERAS ANYE WINGOWS, DIRECT
2. POTENTIAL
ON RIGLL CTWORK AL CEOUIPMENT
CATIONS ARE APPROREINATEXIROUTINGMAITEi COINTRACNAL CORS aHALATIONS AL HNALIZE DUCT
ROUTING CooB E, LINEFDFDGHTINGNPIINUALIPPING ETTE C.
OFALL
"VRANCH DUCTS SUCH
THATN BE
a. RIGID METAL DEVERY IUCTIGISHALL AE USED FOR ALL VENTILATION. (NO FLEX
1. CONLOTSTRACTOR
EXHAUST TERMINATIONS IN UINITSEM EIET THE CALOOD,CLEARANC'ERAES RETHE 2SIX INTERQUIRED IN
CAL EQUIPMENT.
A. RDINATERFINAL DIFLED
INTAKES AND IFFUSERS AND ELEVATI GRILLE LOCATIONS WITH
ARCHIT1."TU EL (MI SIZE 28k3e•1 IN
CEILLINGEF6 R MAIINTENAHo VENTNC RAND FEACH TU RE NEE%HAILS F ERV UNIT.
S. LIN EACH roaBEING. NGSPACE AND BEDROOM.
REEEREUCE xeATLOAC CALCu
IS. PR
ALLPTTPR
DOORS
ii M IN.REFERECIET�LPNRFREAGNARETTRALAoGTS'LaFOR .
CAL
I�TONEERENIRIECTUREPINSFHTRINAI. RFCEACHTTALLAOR DEAILS.PLANS 1S. CHN IF DOMESTIC HO011 TO BE A MINIMUM OF ISO FM. REF CH
FORDETAILS
NOTES
AkIF\ HOUSING
I HOPE
— keep hope alive
I S
R
LID _BF
A
ARCHCHITECEC TS
EGOTOPE
W °
a N 3
O H
= OZ o
0 J
Z WILL
w
� U Q
O Ja
2 wQ
CONSTRUCTION
DOCUMENTS
CONTENTS
MECHANICAL
TYPICAL UNIT
PLANS -2BD
NO 2021031.00
M 5.04
AW\ HOUSING
GENERAL NOTES - TYPICAL UNIT PLANS
I HOPE
we keep hope alive
NC,TRREADINGS SCERINDOWS,DIRECT
OS FOFnLSE SUCHAS ORAS E W
NLIGCTWORK CEDUIP M ENT
2.
CATIONS ARE ANpRO PIRATE.SHALLJFINALSE DUCT
T a
I
O
COIN TRACTORS
ROUTING Go"
NEEDED, ANCC OR aAcirLOCATI LOCATIONS xvnc eLeRrnENTs wlix
CEMAN ERe ON ALLB GUCTs sucx
BRANCH
THAT EVERYAIR
CHDE I EC S
LID _BF
AR
ARCHITECTS
C —
RIGID OIUCTINGISHALLA E USED FOR ALL VENTILATION. (NO FLEX
CT1. RA SHALL TH ARCHITECT TO ENSURE ALL
EM
TERMINATIONSCTOR
EIET THE CLEARANCTo C 'ERAES REQUIRED ITHE N
EXHAUST IN UNITS
A. OPENINGe,
RD'X INTER NATIONAL MECHANICALINATERINTAIE1 AN'FINALLIFFANSMECHANICALERQS ANDI GRILLEDO OLOCATIONS WITH
IT
cING a AL RCP. QELEVATDNRE
\
1. EL IMINS¢E Nexse•11n
cRoorvpEFsaurnoiniEnnF. VENTnc Rnno FH aPcx uEeX GFERvunR.
S. COVE HEATERS LIN EACH LIVINGSPACE AND BEDROOM.
QLo DGALCU
RV ARE TO HIN THE
OPE
.. e"
,DVNp
Bc
RI-REIGTO
BOXED
ivae ceDervccaSTRUCTURAL LFR E,ANTI
. cauDOMCAL
IRIECTUREPINSFTRIUAIN. REFERENCE ACHTTALLAOR DEAIILS.
DSTOBEAMINIMUMOF,BBCFM.REFn Q
..o r.su .....,.
o
2
TES
T.
—11All
, Nr �AN ERV (TAKE, ERV ExxAusr, AND RANGE xGGQ
o.AGIIEIA
mlWT.
BXVGGNSHEETEN
RANGTGGELQGONNE OT
AR
NESHALNOT EXGEEDISO GOIN. IANY
3
f
I`
W m
sC CFM
a N 3
aI
O H�
2 0
w
cQo
CD CO
0Z
C7 J w
Co N
Z W
V)
O Ja
2 w Q
16
��
CONSTRUCTION
MECHANICAL TYPICAL UNIT PLAN - 2BD
1 114' - 1'-0'
- UNITS D105 D205 & D305
DOCUMENTS
ISSUE DATE JAN. 3, 2023
FEII
C_ ngion
OelT SUB CCDOO,
MECHANICAL
TYPICAL UNIT
PLANS -2BD
NO 2021031.00
M5.05
��
CD �
ON
0
o 4�-
0
N
I I v
24 25
n MECHANICA t PICAL UNIT PLAN - 3BD MIRRORED 6 n MECHANICAL TYPICAL UNIT PLAN - 3BD
u0 O
GENERAL NOTES - TYPICAL UNIT PLANS
NNLIGHT AOR FAL BE READINGS GUCH AS OPERABLE WINDOWS, DIRECT
2. p EpUIPMENT
CATIONS AREANNTE IMAVa CNN FaFCT.RIsIALLJFINALIZE DO T
ROUTINNEE BE D
B EDNALIGHLTOTINGMLADOING TCION9 PECN ALDL
xVeANOH OUOTS SUCH
4. RIGID METAL DIUCTINGISHALLABE USEDLFOR ALLVENTILATION.(NO FLEX
DUCTS)
1. CTOR SHALL TH ARCHITECT TO ENSURE ALL
EITAUIT RMINATIONS IN UNITS MEIET THE CLEARANCES REOUIED IN
THE 2R",NTER
'CAL
CODE
EL'
S. EIINATERFINALDL RCPIENUGLERSAND'LEVAIGRILLELOCATIONGWITH
ARC HIT].'CTUA soNlEL (MIN SIZE 20'xUe"( IN
CEILLING FOR MAINT ENANC NE " FOOD VENT OVERSIZED
TUTUREREM
U MOVAL'AHAUOF ERV UNIT.
SIS. ED. EACH inTEA s FoaNG SPACE AND BEDROOM.
CODES
ii RAAI ING. REFERENALLCEHSB ToT RUINTERIORCTU PAT PLANSI FOR RETAILS.
FOR ME GHANIGAL
IRPIEATIONOREFE"`NTS ANRENCE ARCHRreCTTURAL P NET
FOR DETAILS.
FOR1S. GFM OF DOMESTIC HOODS TO BEA MINIMUM OF 100 CHM. REF ARCH
PLANS DETAILS
NOTES
AkF\ HOUSING
I HOPE
— keep hope alive
DE I S
R
LID_ST
A
ARCHCHITECEC TS
EGOTOPE
W °
a N 3
O H
= OZ o
0 J
Z W ON
LL
� U Q
O Ja
2 W Q
CONSTRUCTION
DOCUMENTS
CONTENTS
MECHANICAL
TYPICAL UNIT
PLANS-3BD
PROJECT NO 2021031.00
IHIIT
M5.06
AW\ HOUSING
GENERAL NOTES - TYPICAL UNIT PLANS
I HOPE
. keephopealive
2.
POTENTIAL
SE RECIN SG SUCH AS -AD E WINDOWS, DIRECT
ALL EQUIPMENT
ATIONS
CATIONS ARE ANARO PIRATE.SHALLJFINALSE DUCT
T a
OEDED, AND
S.
COIN TRACTORS
ROUTING AS
COO OF ALL HVRAAD ELCEM ENT: WITH
NCH ou Ts sucH
aRUCTURnneun Hen aPIPINGC. ETCbEae ou Au BRANCH
AIR
FOR
DoE"G N S
LID we s t
ARCHITECTS
4.
RIGID METAL DUCTIGISHALLA E USED ALL VENTILATION. (NO FLEX
DU1. CTS)
TH ARCHITECT TO ENSURE ALL
SHALL INITSEM
A.
EXHAUST TERMINATIONS IN UCTOR
EIET THE CLEARANC'ERAES REQUIRED ITHE N
OPENINGe,
RD'X INTERHITINATERFINALINTAKES AND HDIFFUSERANICAL S AND I GRILLED LOCATIONS WITH
COORDINATE a AL acP. QELEVATouRE
\
1.
S.
cEouripEFsa"C'Ennnc Rnnlo FH arcx uEeS GFERvunR.
EL �OF SIZE UNIT. MN
COV1B. PREREAEHEAT Long PROVIDE
LATious FORRSGING. A
AT ALL'NT'P'PP DOORS
BOXED CUT AM ING. REFERENCE STPROVIDEDFORRUCTURAL ETAIMECHANICILLS.12. DROPPED CEIRIN OR AND SOFFITS To
OPE
I'll In' y Nae
.uM,�eu aats�x
11
EQUIPMENT ANDFU
RDINATION. RE ERIENCEI NAL ARCHI ECTTURALENDING PLANS FOR DHETAILS.
FOR1S. CHN IF DOMESTIC HO011 TO BE A MINIMUM OF WO FM.
PLANS DETAILS
NOTES4
NTET� ERV INTAKE, ERV EXHAUST AND RANGE HOOD
S 8 V CONNIESCHON TO RANGE HOOD. CONTRACTOR TO FIELD ONN—
AILTHROUGH
THE HR=lRANE SHALL NOT EXCEED GO, N ANY
a N 3
(06
ow o
fD
Q) J
o C)
aGFM F.
Z w
o
N
U a
�m
= wQ
,ER -RE
mC
CONSTRUCTION
k,
DOCUMENTS
e2
e
M
2 1 4 so 2R'FM
ISSUE e JAN. 3, 2023
REVISION SCHEDULE
—'MEG
q o SODFM oQF 40'FM
® a
Da a oza GGQDD,
aGFM
CONTENTS
MECHANICAL
TYPICAL UNIT
— —
— — — —
PLANS -3BD
MECHANICAL TYPICAL UNIT PLAN - 3BD MIRRORED -UNITS C204 & C304
2 1/4'- 1'-0'
MECHANICAL TYPICAL UNIT PLAN - 3BD MIRRORED - UNITS A201 &
1 -0.
01
UNNSR
OHEC—
ETND 2o2ia3,.0a
IHIII
M5.07
��
CD �
NN
O
O �
O
N
u
15 16 24 25
n MECHANICAL TYPICAL UNIT PLAN - 3BD.ADA-B n MECHANICAL TYPICAL UNIT PLAN - 3BD.ADA-A
ia•=r-o• ( 1/4•=1-0•
GENERAL NOTES - TYPICAL UNIT PLANS
NNLIGHi FOR FAL BE REAUIMAT
GB SUCH AB OPERABLE WIN OOWS, UIECT
2. U EQUIPMENT
LOCATIONS AREAPPROXIMATE.
NNTE IMAVR CONTRACTORS SHALL HNAL¢E OG WITH ?cT
ROUTINB AS
NEEDED E�LIGHANUALTING PBALANRNALING ET'oGACON9 DEAL xVAG ELEMENTS WITH
AM ON ALL eANOH DUCTS SUCH
THAT EVERY ASENCED
4. RIGID METAL UIUCTINGISHALLABE USEDLFOR ALLVENTILATION.(NO FLEX
DUCTS)
1. CTOR SHALL TH ARCHITECT TO ENSURE ALL
EXHAUST TERMINATIONS IN UNITS MEIET THE CLEARANCES REQU RED IN
THE 2C",NTBR
'CAL
GORE
EL,
B. HINATERFINALDL DOEIEN SLERBAND'LEVAIGRILLELOCATIONBWITH
ARC HIT].'CTUA soNlEL (MIN SIZE 20'x3e"( IN
CEILLING FOR MAiNT ENANC V'DE " FOOD VENT OVERSIZED
TUITIUREREM
U MOVALEXHAUOF ERV UNIT.
S. EACH IN EACH NINsPACE AND BEDROOM.
DOORS
ii NAAI ING. REFERENCEHST RUCTU RAL�PLANSI FOR DETAILS.
FOR ME CHANICAL
IRCIEATIONOREFEELNTB ANRENCE ARCHRreCTTURAL P NO
FOR oETAILB.
FOR1S. GFM OF DOMESTIC HOODS TO BEA MINIMUM OF 100 CFM. NET ARCH
PLANS DETAILS
NOTES
AkF\ HOUSING
I HOPE
we keep hope alive
IGNI
LID _BF
ARCHITECTS
EGOTOPE
W °
a N 3
O H
= OZ o
0 J
Z WLL
w
� U Q
O J a
2 wQ
CONSTRUCTION
DOCUMENTS
CONTENTS
MECHANICAL
TYPICAL UNIT
PLANS - 3BD.ADA
NO 2021031.00
M5.08
IQ O
CD W
W N
O
O �
O
N
—
Hom,
SO a / 0 11
7 (ABOVE)
ENLARGED PLAN SHEET NOTES GENERAL NOTES - ENLARGED PLANS
POTENTIAL SOURCES FOR FALSE READINGS SUCH AS OPERABLE WINDOWS UIRECT SUNLIGHT, ETC.
ALL CU
T III
T III
T III
T III
T III
eoDIRMENTLQQATIQNBaRBaRRRQxIMATe.DQNTRAQTQRBsxALLHNAH EDDDTRQDTIx G°QRDIxATE
FOR MECHANICAL EQI I 3. OVIDEMANUAL BALANCING WITH ARCHITECT
ONAALL1 BRANCH DUES SUCH THAT EVERY AIR TERMINAL CELEMENTS
N BEEBA ANCEEBTRUCTURE LIGHTING PIPING ETC
oN. RRO ILL E. DUCT"
E. ONS IN UNITS MEET THE CLEARANCES REQUIRED IN THE 201R INTERNATIONAL
ARIOR4 RIGID METALL CO ETO OPERA LEEo ENIN S INTAKES AND MECHANicu BID,FMEN aTl
E. 7. °OVINE ANEUNFFTEo, OVERSEEI ACc SS PANEL(MIN SIZE 28.361 iN CEIiiNCR oa MAINTENANCE FNo FUTURE REMOVAL of ERv UNIT.
oVIDE IC UNDERCUT AT ALL INTERIOR DOORS.
I AD IORIAN OF "IPTHICKNES AND 9HAEDBE CONTINUOUS WITHOBT CPENINDS FROM TH°EPA�,RHHANOL'NGAp Piu cE OR EEOuiFMENT TO THE
AIR OUTLET AND INLET HERMINALSSLOCATED ON THE OPPOSITE SIDE OF THE WALL ASSEMBLY.
AkF\ HOUSING
I HOPE
wD keep hope alive
DESIGNS
LID_XF
ARCHITECTS
EGOTOPE
::Le°
CONSTRUCTION
DOCUMENTS
IB.1111-r .— A ImA
MECHANICAL
ENGLARGED PLAN
- BUILDING A
CHECKED OR—,
PROJECT NO 2021031.00
M 5.09
LNGREENHECK
Building Value in Air.
Supply Fan Charts And Performance
Printed Date: 10/18/2023
Job: Housing Hope Edmonds
Mark: ERV-Al
Model: Minicore-54G-F
Supply
Total Volume
External SP
Total SP
RPM
Operating
Motor
Fan
(CFM)
(in. wg)
(in. wg)
Power (hp)
Qty
size
Qty
Type
Drive -Type
200
0.5
0.512
987
0.08
1
1/4
1
Forward Curve
Direct
Pressure ..
Weatherhood Filter Damper External Total
0.012 - 0.5 0.512
i,
1.0
m 0.8
3
c
E 0.6
Q)
N
a 0.4
m
0
F
0.2
0.0
0 1 2 3 4 5
Volume (CFM) x 100
0 Operating Bhp point
0 Operating point at Total External TP
Fan curve
- - - System curve
------- Brake horsepower curve
Supply Fan
8)
�
T'
a
r
m
c
A�
-----
o
` �4
----
--------
-
6
0.6
0.5
0.4
Q
t
0.3 3
0
d
N
0.2 m
m`
A
0.0
7
\\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj
CAPS 4.42.1122 Generated WNYW� *zgdorse.com Page 4 of 34
Page 94 of 10
LNGREENHECK
Building Value in Air.
Supply Fan Charts And Performance
Printed Date: 10/18/2023
Job: Housing Hope Edmonds
Mark: ERV-A2
Model: Minicore-54G-F
Supply
Total Volume
External SP
Total SP
Operating
Motor
Fan
Qty
size
Qty
Type
Drive -Type
(CFM)
(in. wg)
(in. wg)
RPM
Power (hp)
300
0.5
0.526
1060
0.11
1
1/4
1
Forward Curve
Direct
Pressure ..
Weatherhood Filter Damper External Total
0.026 - 0.5 0.526
AccordanceSound Performance in
Sound Power by Octave Band Lwa dBA Sones
62.5 125 250 500 1000 2000 4000 8000
79.2 78.4 72.6 65.6 66 63.7 61.7 56.5 1 72 1 60.5 1 10.7
Supply Fan
1.2
1.0
m 0.8
3
c
E 0.6
N
a 0.4
m
0
t-
0.2
00
0.6
0.5
0.4
Q
0.3 3
O
d
0.2
m`
0.1
0.0
0 1 2 3 4 5 6 7 8
Volume (CFM) x 100
0 Operating Bhp point
0 Operating point at Total External TP
Fan curve
- - - System curve
------- Brake horsepower curve
�O
60
m
a
m
t
ti
c
-
A,
v
-"
o
--
o
\\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj
CAPS 4.42.1122 Generated s� z(�dorse.com Pa e 15 of 34
P ge 95 of 1 o g
LNGREENHECK
Building Value in Air.
Supply Fan Charts And Performance
Printed Date: 10/18/2023
Job: Housing Hope Edmonds
Mark: ERV-A3
Model: Minicore-54G-F
Supply
Total Volume
External SP
Total SP
Operating
Motor
Fan
Qty
iz
Qty
Type
Drive -Type
(CFM)
(in. wg)
(in. wg)
RPM
Power (hp)
300
0.5
0.526
1060
0.11
1
1/4
1
Forward Curve
Direct
Pressure ..
Weatherhood Filter Damper External Total
0.026 - 0.5 0.526
AccordanceSound Performance in
Sound Power by Octave Band Lwa dBA Sones
62.5 125 250 500 1000 2000 4000 8000
79.2 78.4 72.6 65.6 66 63.7 61.7 56.5 1 72 1 60.5 1 10.7
Supply Fan
1.2
1.0
m 0.8
3
c
E 0.6
N
a 0.4
m
-
t-
0.2
00
0.6
0.5
0.4
Q
0.3 3
O
d
0.2
m`
0.1
0.0
0 1 2 3 4 5 6 7 8
Volume (CFM) x 100
0 Operating Bhp point
0 Operating point at Total External TP
Fan curve
- - - System curve
------- Brake horsepower curve
�O
a�
m
a
m
t
N
C
-
A
LU
-"
"
o
\\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj
CAPS 4.42.1122 Generated s� z(�dorse.com Pa e 26 of 34
P ge 96 of 1 o g
nA
Energy Recovery Ventilator
0
Specification Submittal Data / Panasonic ERV
Description
Ceiling or wall mount Cold Climate Energy
Recovery Ventilator (ERV) provides a tempered
air supply, humidity control, and a balanced
amount of exhaust to help maintain balanced,
positive or negative pressure throughout the
home. The Panasonic Intelli-Balance ERV is
engineered for use in any North America
climate zone. Version 2 includes new Hi/Lo
Occupant Controlled Boost Capability. Built-in
ASHRAE 62.2 Timing function helps ensure
code compliance.
Motor/Blower:
• ERV shall have Hil Speed Occupant
Controlled Boost Capability
• Two (2) enclosed DC brushless motors rated
for continuous run.
• ERV Supply and Exhaust ventilation rates
shall be manually adjustable for 50-60-70-80-
90-100 CFM.
• Power rating shall be 120 volts and 60 Hz.
• Motor equipped with thermal cut-off fuse
control.
• Removable, permanently lubricated, plug—in
motor.
Housing:
• 22 gauge galvanized steel body.
• Four 4" or 6" intake and exhaust ducts.
• Built in damper on Outdoor Air (OA) closes
during defrost function when the outdoor
temperature is too cold.
• Filters on supply and exhaust air extend the
life of the ERV core.
• (4) Pressure ports allow for easy airflow
verification.
• Pre -drilled mounting bracket can
accommodate 16", 19", or 24" on center.
Maintenance:
• MERV 8 filter included; MERV 8 (FV-
FL0810VE1) and optional MERV 13 (FV-
FL1310VE1) replacements available.
• Unobtrusive alarm notifies owner for filter
check and maintenance.
Warranty:
• DC Motors: 6 years from original purchase
date
IF All Parts: 3 Years from original purchase date.
Architectural Specifications:
ERV shall be ceiling or wall mount type with
built-in speed selectors for both Supply and
Exhaust air. Select from 50/60/70/80/90/100
CFM. ERV shall have 100 Net CFM on the
exhaust ports and 100 Net CFM on the supply
ports as tested in accordance with HVI 915 and
916 standards at 0.1 static pressure in inches
water gauge. ERV shall have 100 Net CFM on
the exhaust ports and Net 100 CFM on the
supply ports at 0.4" w.g. static pressure. ERV
shall have Hil Speed Occupant Controlled
Boost Capability. Power consumption shall be
no greater than 81 watts at 0.1 " w.g. and 100
watts at 0.4" w.g. static pressure. Apparent
Sensible Effectiveness for heating shall be no
less than 84% at 53 CFM net air flow under
32°F (0°C) as tested in accordance with
CSA-C439. Total Recovery Efficiency for cooling
shall be no less than 60% at 49 CFM net air flow
under 95°F (35°C). The supply port damper shall
close when outdoor temperatures are < 14°F
(-10°C) to prevent freezing of the core. The (2)
motors shall be totally enclosed DC brushless
motors rated for continuous run. DC motor
speed shall automatically increase when the fan
senses static pressure to maintain selected
CFM. ERV shall incorporate an ASHRAE 62.2
Intermittent Timing function for code
compliance. ERV shall have standby/low speed
to high speed control airflow capability as
desired by occupant. Power rating shall be
120v/60Hz. Duct diameters shall be no less than
4". ERV can be used to comply with ASHRAE
62.2, LEED, IAP, California Title-24, and WA
Energy Code
ERV Core Technology:
• Indoor and outdoor air passes through
Panasonic's capillary core technology. This
process tempers supply air while transferring
moisture and energy.
• Built in Frost Prevention Mode prevents the
core from freezing. Frost Prevention Mode
is intuitive and operates without homeowner
intervention.
• Core material permeated with anti -mold
treatment.
For complete Installation Instructions visit us.panasonic.com/ventfans
FV-10VE2
Temperate Climate ERV
FV-10VE2 optional E tenor Wall cap (see next page)
DC Motor Technology
When the ERV senses static pressure, its
speed is automatically increased to ensure that
the desired CFM is not compromised.
Model
Quantity
Comments
Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
Panasonic Life Solutions Company of America
IAQ Division
Two Riverfront Plaza
Newark, NJ 07102
us.panasonic.com/ventfans
Vi c U� us Page 2024 Panasonic
ee.nrien Page 97 of 102
IAQ19203ST
r7
LMGREENHECK
Building Value in Air.
Model: SP-A390
Ceiling Exhaust Fan
Standard Construction Features:
- Corrosion resistant galvanized steel scroll and housing - Sound absorbing
insulation - White designer non -yellowing grille - Rectangular outlet duct collar
with integral spring loaded backdraft damper - Double inlet forward curved wheel -
Plug type disconnect - Adjustable mounting brackets - Field rotatable discharge
Selected Options & Accessories:
Motor rated for continuous use
Motor with Thermal Overload
Motor with CSA Approval
Motor with 40 Degree C Ambient Temperature
UL/cUL 507 Listed - Electric Fan
Solid State Speed Control, 6 Amp, Shipped Loose
Isolation Kit, (PN: VI KIT-SP/CSP), Shipped Loose
Adjustable easy installation mounting bracket
Standard Grille
Polypropylene Wheel Material
Dimensional
Quantity 1
Weight w/o Acc's (lb) 24
Weight w/ Acc's (lb) 26
Performance
Requested Volume (CFM)
200
Actual Volume (CFM)
200
Total External SP (in. wg)
0.325
Fan RPM
927
" FLA (A)
1.42
Elevation (ft)
433
Airstream Temp.(F)
70
Air Density (lb/ft3)
0.074
Sones
2.0
Motor
Motor Mounted
Yes
" Input Watts (W)
135
Voltage/Cycle/Phase
115/60/1
Enclosure
ODP
M
0.5
m 0.3
rn
U)
a>
0.2
76
U)
0.1
M
Printed Date: 10/19/2023
Job: Housing Hope Edmonds
Mark: EF-MNT
Model: SP-A390
15.5
14.938
6.75 00 O 13.375
e� �o
1/4 in. threaded rod
(field provided) 14 11.875
Vibration Isolators
(from manufacturer) 8 1
MOUNTING BRACKET 11.25 $ 8
FR
M
- o
a�
�o
0
c°
30 60 90 120 150 180 210 240 270 300
Volume (CFM)
0 Operating point at Total External SP
Fan curve
-- - - System curve
Notes:
All dimensions shown are in units of in.
*FLA is approximate and will vary slightly with the motor.
Sones - calculated using AMCA 301 at 5 ft
** Wattage is shown at free air.
Wattage is approximate and may vary between motors.
WORLDWIDE
CERTIFIED
RRTIRGf Cimca
\\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj
CAPS 4.42.1122 Generated s� z(�dorse.com Pa e 1 of 4
P ge 98 of 1 o g
LMGREENHECK
Building Value in Air.
Model: SP-A200
Ceiling Exhaust Fan
Standard Construction Features:
- Corrosion resistant galvanized steel scroll and housing - Sound absorbing
insulation - White designer non -yellowing grille - Rectangular outlet duct collar
with integral spring loaded backdraft damper - Double inlet forward curved wheel -
Plug type disconnect - Adjustable mounting brackets - Field rotatable discharge
Selected Options & Accessories:
Motor rated for continuous use
Motor with Thermal Overload
Motor with CSA Approval
Motor with 40 Degree C Ambient Temperature
UL/cUL 507 Listed - Electric Fan
Solid State Speed Control, 6 Amp, Shipped Loose
Isolation Kit, (PN: VI KIT-SP/CSP), Shipped Loose
Adjustable easy installation mounting bracket
Energy Star Certified
Standard Grille
Polypropylene Wheel Material
Can Be Used to Comply with: ASHRAE 62.2, California Title 24, and Washington
State Energy Code
Dimensional
Quantity 1 0.6
Weight w/o Acc's (lb) 24
Weight w/ Acc's (lb) 26
0.5
Performance
Requested Volume (CFM)
150
Actual Volume (CFM)
150
Total External SP (in. wg)
0.3
Fan RPM
750
FLA (A)
0.46
Elevation (ft)
433
Airstream Temp.(F)
70
Air Density (lb/ft3)
0.074
Sones
1.5
Motor
Motor Mounted
Yes
" Input Watts (W)
30
Voltage/Cycle/Phase
115/60/1
Enclosure
ODP
W 0.3
rn
U)
a>
0.2
.6
rn
0.1
0
Printed Date: 10/19/2023
Job: Housing Hope Edmonds
Mark: EF-IDF-B
Model: SP-A200
15.5
14.938
6.75 00 O 13.375
e� �o
1/4 in. threaded rod
(field provided) 14 11.875
Vibration Isolators
(from manufacturer) 8 1
MOUNTING BRACKET 11.25 $ 8
O
-----------------
I m
0
c'
0
0
30 60 90 120 150 180 210 240
Volume (CFM)
Operating point at Total External SP
- Fan curve
- System curve
Notes:
All dimensions shown are in units of in.
*FLA is approximate and will vary slightly with the motor.
Sones - calculated using AMCA 301 at 5 ft
** Wattage is approximate and may vary between motors.
A RTCla
WORLDWIDE
CERTIFIED
RRTIRGf
\\orca\Public\Stephen\�/w1injobs\Housing Hope Edmonds.gfcj
CAPS 4.42.1122 Generated sz(�dorse.com
Page 99 of 162
Page 2 of 4
LMGREENHECK
Building Value in Air.
Model: SP-A200
Ceiling Exhaust Fan
Standard Construction Features:
- Corrosion resistant galvanized steel scroll and housing - Sound absorbing
insulation - White designer non -yellowing grille - Rectangular outlet duct collar
with integral spring loaded backdraft damper - Double inlet forward curved wheel -
Plug type disconnect - Adjustable mounting brackets - Field rotatable discharge
Selected Options & Accessories:
Motor rated for continuous use
Motor with Thermal Overload
Motor with CSA Approval
Motor with 40 Degree C Ambient Temperature
UL/cUL 507 Listed - Electric Fan
Solid State Speed Control, 6 Amp, Shipped Loose
Isolation Kit, (PN: VI KIT-SP/CSP), Shipped Loose
Adjustable easy installation mounting bracket
Energy Star Certified
Standard Grille
Polypropylene Wheel Material
Can Be Used to Comply with: ASHRAE 62.2, California Title 24, and Washington
State Energy Code
Dimensional
Quantity 1 0.6
Weight w/o Acc's (lb) 24
Weight w/ Acc's (lb) 26
0.5
Performance
Requested Volume (CFM)
150
Actual Volume (CFM)
150
Total External SP (in. wg)
0.3
Fan RPM
750
FLA (A)
0.46
Elevation (ft)
433
Airstream Temp.(F)
70
Air Density (lb/ft3)
0.074
Sones
1.5
Motor
Motor Mounted
Yes
" Input Watts (W)
30
Voltage/Cycle/Phase
115/60/1
Enclosure
ODP
W 0.3
rn
U)
a>
0.2
.6
rn
0.1
0
Printed Date: 10/19/2023
Job: Housing Hope Edmonds
Mark: EF-IDF-C
Model: SP-A200
15.5
14.938
6.75 00 O 13.375
e� �o
1/4 in. threaded rod
(field provided) 14 11.875
Vibration Isolators
(from manufacturer) 8 1
MOUNTING BRACKET 11.25 $ 8
O
-----------------
I m
0
c'
0
0
30 60 90 120 150 180 210 240
Volume (CFM)
Operating point at Total External SP
- Fan curve
- System curve
Notes:
All dimensions shown are in units of in.
*FLA is approximate and will vary slightly with the motor.
Sones - calculated using AMCA 301 at 5 ft
** Wattage is approximate and may vary between motors.
A RTCla
WORLDWIDE
CERTIFIED
RRTIRGf
\\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj
CAPS 4.42.1122 Generatedff `�nz02 dorse.com
Page 1 0 of 1
Page 3 of 4
LMGREENHECK
Building Value in Air.
Model: SP-A200
Ceiling Exhaust Fan
Standard Construction Features:
- Corrosion resistant galvanized steel scroll and housing - Sound absorbing
insulation - White designer non -yellowing grille - Rectangular outlet duct collar
with integral spring loaded backdraft damper - Double inlet forward curved wheel -
Plug type disconnect - Adjustable mounting brackets - Field rotatable discharge
Selected Options & Accessories:
Motor rated for continuous use
Motor with Thermal Overload
Motor with CSA Approval
Motor with 40 Degree C Ambient Temperature
UL/cUL 507 Listed - Electric Fan
Solid State Speed Control, 6 Amp, Shipped Loose
Isolation Kit, (PN: VI KIT-SP/CSP), Shipped Loose
Adjustable easy installation mounting bracket
Energy Star Certified
Standard Grille
Polypropylene Wheel Material
Can Be Used to Comply with: ASHRAE 62.2, California Title 24, and Washington
State Energy Code
Dimensional
Quantity 1 0.6
Weight w/o Acc's (lb) 24
Weight w/ Acc's (lb) 26
0.5
Performance
Requested Volume (CFM)
150
Actual Volume (CFM)
150
Total External SP (in. wg)
0.3
Fan RPM
750
FLA (A)
0.46
Elevation (ft)
433
Airstream Temp.(F)
70
Air Density (lb/ft3)
0.074
Sones
1.5
Motor
Motor Mounted
Yes
" Input Watts (W)
30
Voltage/Cycle/Phase
115/60/1
Enclosure
ODP
W 0.3
rn
U)
a>
0.2
.6
rn
0.1
0
Printed Date: 10/19/2023
Job: Housing Hope Edmonds
Mark: EF-IDF-D
Model: SP-A200
15.5
14.938
6.75 00 O 13.375
e� �o
1/4 in. threaded rod
(field provided) 14 11.875
Vibration Isolators
(from manufacturer) 8 1
MOUNTING BRACKET 11.25 $ 8
O
-----------------
I m
0
c'
0
0
30 60 90 120 150 180 210 240
Volume (CFM)
Operating point at Total External SP
- Fan curve
- System curve
Notes:
All dimensions shown are in units of in.
*FLA is approximate and will vary slightly with the motor.
Sones - calculated using AMCA 301 at 5 ft
** Wattage is approximate and may vary between motors.
A RTCla
WORLDWIDE
CERTIFIED
RRTIRGf
\\orca\Public\Stephen\winjobs\Housing Hope Edmonds.gfcj
CAPS 4.42.1122 Generatedff `�nz02 dorse.com
Page 1 1 of 1
Page 4 of 4
wh _n-er G reeo4;decr
VENTILATION: FAN
Specification Submittal Data / Panasonic Ventilation Fan
Description
Customizable ceiling mount ventilating fan, low sone and rated for continuous operation.
ENERGY STAR® rated and certified by the Home Ventilating Institute (HVI). Evaluated by the
Underwriters Laboratories and conforms to both UL and cUL standards.
Motor/Blower:
• Enclosed brushless ECM smart motor technology rated for continuous operation
• Adjustable ventilation rates at 50 — 80 —110 CFM
• Power rating of 120 volts and 60 Hz
• UL and cUL listed for tub/shower enclosure when GFCI protected.
• Motor equipped with thermal cutoff fuse
• Removable permanently lubricated plug-in motor
Housing:
• Environmentally friendly 26 gauge Zinc -Aluminum -Magnesium (ZAM) housing
• Integrated dual 4" or 6" diameter duct adapter
• Built-in damper reduces back draft and helps with blower door testing
• Built-in metal flange provides blocking for penetrations through drywall as an Air Barrier, and
assists with the decrease in leakage in the Building Envelope during blower door testing
• Suitable for installation in ceilings insulated up to R60
• Articulating and expandable installation bracket up to 24"
Grille:
• Attractive design using Poly Pro material
• Attaches directly to housing with torsion springs
• Includes a motion sensor cap for use as a cover when the motion sensor Plug 'n Play'"
module has not been selected
Warranty:
• ECM Motor: 6 Years from original purchase date
• ALL Parts: 3 Years from original purchase date
Architectural Specifications:
Customizable ceiling mount ventilation fan, ENERGY STAR® rated with multi -speed control (0,
30-100 CFM, in 10 CFM increments) and a built-in high/low adjustable time delay activated by a
wall switch, SmartAction Motion Sensor Plug 'N Play- module or Condensation Sensor Plug 'N
Play'" module. Features a built-in speed selector. Select from 50/80/110 CFM with <0.3 sone as
certified by the Home Ventilating Institute (HVI) at 0.1 w.g. with 51 /80/110 CFM and no more than
0.4/0.5/0.8 sones at 0.25 w.g. and 5189/108 CFM at 0.375 w.g. Power Consumption shall be no
greater than 3.1 /5.1 /9.9 watts at 0.1 w.g. and 6.2/9.6/15.4 watts at 0.25 w.g. and 9.6/13.4/20.0
watts at 0.375 w.g. ENERGY STAR® rated with efficiency of no less than 16.2/15.7/11.1 CFM/
watt at 0.1 w.g. and 8.3/8.3/7.1 CFM/watt at 0.25 w.g. and 5.3/5.9/5.4 CFM/watt at 0.375
w.g. The motor shall be enclosed with brushless ECM motor engineered to run continuously.
ECM motor speed shall automatically increase when the fan senses static pressure to maintain
selected CFM. Power rating shall be 120v/60Hz. Duct diameter shall be no less than 4", inclusive
of an integrated dual 4" or 6" duct adapter. Plug 'N Play" modules provide up to two additional
features. Select from Condensation Sensor, and SmartAction Motion Sensor. Fan shall be RoHS
Compliant and UL and cUL listed for tub/shower enclosure when GFCI protected. Also suitable
for installation in ceilings insulated up to R60. Fan can be used to comply with ASHRAE 62.2,
LEED, ENERGY STAR®, IAP, EarthCraft, California Title-24 and WA Ventilation Code.
isECM Motor Technology:
When fan senses static pressure, its speed is automatically increased to
ensure that the desired CFM is not compromised, which allows the fan to
perform as rated.
(P
FV-0511 VKS2
Built -In Self Adjusting
Airflow Capability
FV-0511VKS2
Model
Quantity
Comments
Project:
Location:
Architect:
Engineer:
Contractor:
Submitted by:
Date:
For complete Installation Instructions visit us.panasonic.com/ventfans
Ceiling Radiation Damper: WhisperGreen Select— is UL listed for use with the Panasonic Ceiling Radl WOV202"del #: PC-RD05C5, sold separately).
Page 102 of 102