Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
REVIEWED RESUB2 BLD2022-1319+Energy_Code_Sheet_or_Envelope_Summary+4.3.2023_5.59.13_PM+3460831
408.1.2.2 COMMISSIONING ROLES & RESPONSIBILITIES ROLE COMMUNICATIONS AND RESPONSIBILITIES THE COMMISSIONING PROCESS WILL BE LED BY A CERTIFIED COMMISSIONING PROFESSIONAL (CCP). TBD* CERTIFIED COMMISSIONING LEAD, PLAN, COORDINATE, AND MANAGE THE COMMISSIONING PROCESS PROFESSIONAL (CCP) DEVELOP FUNCTIONAL TEST FORMS WITNESS FUNCTIONAL TESTING PERFORMED BY CONTRACTORS ASSESS TEST RESULTS AND RECOMMEND ACCEPTANCE TO OWNER OWNER RECEIVE ALL COMMISSIONING COMMUNICATIONS DETERMINE RESOLUTION TO COMMISSIONING ISSUES, AS NEEDED RECEIVE COPIES OF ALL COMMISSIONING COMMUNICATIONS ARCHITECT COORDINATE SUBMITTAL REVIEW PROCESS TO INCLUDE COMMENTS FROM CCP ASSIST WITH RESOLUTION OF COMMISSIONING ISSUES, AS NEEDED RECEIVE ALL COMMISSIONING COMMUNICATIONS GENERAL CONTRACTOR DISTRIBUTE DOCUMENTS TO TO TRADE CONTRACTORS, AS NEEDED SCHEDULE CONTRACTORS TO ATTEND COMMISSIONING MEETINGS COORDINATE WITH TRADE CONTRACTORS FOR FUNCTIONAL TESTING DIVISION 22, 23, AND 26 FOLLOW COMMISSIONING REQUIREMENTS IN THESE CONTRACT DOCUMENTS, INCLUDING PRIMARY RESPONSIBILITY FOR CONTRACTORS EQUIPMENT START-UP, PERFORMING FUNCTIONAL TESTING, AND CORRECTION OF DEFICIENCIES. DIVISION 22, 23, AND 26 RECEIVE COPIES OF ALL COMMISSIONING COMMUNICATIONS ENGINEERS AT THE END OF CONSTRUCTION: UPDATE BASIS OF DESIGN TO REFLECT AS -BUILT CONDITION ASSIST WITH RESOLUTION OF COMMISSIONING ISSUES, AS NEEDED *ENERGY CODE REQUIRES THAT THE CCP BE "AN INDIVIDUAL WHO IS CERTIFIED BY AN ANSI/ISO/IEC/ 17024-2012 ACCREDITED ORGANIZATION TO LEAD, PLAN, COORDINATE, AND MANAGE COMMISSIONING TEAMS AND IMPLEMENT THE COMMISSIONING PROCESS." PER SECTION C408.1.2.1, AN "IN-HOUSE COMMISSIONING DISCLOSURE AND CONFLICT MANAGEMENT PLAN" IS REQUIRED WHEN THE CCP IS CONTRACTED THROUGH THE ENGINEER, ARCHITECT, OR CONTRACTOR. COMMISSIONING REPORTS INCLUDING DESIGN REVIEW MEMOS, SUBMITTAL REVIEWS, SITE VISIT REPORTS, AND OTHER COMMISSIONING ISSUES ARE PUBLISHED DIRECTLY TO THE PROJECT TEAM, INCLUDING THE OWNER. THEREFORE, THE CERTIFIED COMMISSIONING PROFESSIONAL IS FREE TO IDENTIFY ANY ISSUES DISCOVERED AND REPORT DIRECTLY TO THE OWNER. 408.1.2 COMMISSIONING (Cx) PLAN THE TABLE BELOW INCLUDES THE COMMISSIONING ACTIVITIES REQUIRED BY ENERGY CODE. THESE ACTIVITIES WILL OCCUR THROUGHOUT CONSTRUCTION AND EXTEND THROUGH FINAL CLOSEOUT DOCUMENTS. THE CONTRACTOR'S COMMISSIONING RESPONSIBILITIES FOR THIS PROJECT ARE LISTED IN THE TABLE BELOW. COMMISSIONING ACTIVITES DIVISION 22 DIVISION 23 DIVISION 26 NOTES PLUMBING MECHANICAL ELECTRICAL SUBMITTAL REVIEW TBD TBD TBD COMMISSIONING PROCESS TO BE DETERMINED BY CCP ROUGH -IN SITE VISITS TBD TBD TBD COMMISSIONING PROCESS TO BE DETERMINED BY CCP YES: HEAT PUMP YES: LIGHTING COORDINATE WITH CCP TO ALLOW FOR CCP WITNESS EQUIPMENT START-UP WATER HEATERS, YES: VRF & TAB CONTROLS, WITNESS OF START-UP ACTIVITIES BOOSTER PUMPS ENERGY METERING SUBMITTED TO CCP VIA CONTRACTOR AS START-UP REPORTS YES YES YES COMMUNICATION THAT EQUIPMENT IS READY FOR FUNCTIONAL TESTING WORK PERFORMED BY CONTRACTOR'S TAB TEST AND BALANCE YES YES N/A SPECIALIST. CCP TO REVIEW PRELIMINARY TAB REPORT ALONG WITH START-UP REPORTS FUNCTIONAL TESTS YES YES YES TESTING IS WITNESSED BY CCP. TESTING IS CONDUCTED BY INSTALLER (NOTE 1) OPERATOR TRAINING YES YES YES CCP TO REVIEW AND VERIFY SYSTEM OPERATION TRAINING PER C103.6.4 CCP TO REVIEW AND VERIFY BUILDING CLOSEOUT DOCUMENTS YES YES YES DOCUMENTATION REQUIREMENTS IN C103.6: RECORD DOCUMENTS, 0&M MANUALS, ENERGY CODE COMPLIANCE FORMS. (NOTE 2) DEFERRED TESTING TBD TBD TBD COMMISSIONING PROCESS TO BE DETERMINED BY CCP NOTES 1. CONTRACTORS SHALL PROVIDE THE NECESSARY ASSISTANCE TO THE CERTIFIED COMMISSIONING PROFESSIONAL TO PERFORM COMMISSIONING DUTIES. CONTRACTORS SHALL BE RESPONSIBLE FOR TAKING CORRECTIVE ACTION IF ANY DEFICIENCIES ARE FOUND DURING COMMISSIONING. 2. CONTRACTOR SHALL COORDINATE WITH CCP TO ALLOW THEM TO ATTEND REQUIREMENT OWNER TRAINING. OWNER TRAINING BY CONTRACTORS FOR EACH PIECE OF EQUIPMENT OR SYSTEM SHALL INCLUDE: a. SYSTEM/EQUIPMENT OVERVIEW (WHAT IT IS, WHAT IT DOES, AND WHICH OTHER SYSTEMS OR EQUIPMENT DOES IT INTERFACE WITH) b. REVIEW OF AVAILABLE 0&M MATERIALS. C. REVIEW OF THE RECORD DRAWINGS ON THE SUBMIT SYSTEM/EQUIPMENT d. HANDS-ON DEMONSTRATION OF ALL NORMAL MAINTENANCE PROCEDURES, NORMAL OPERATING MODES, AND ALL EMERGENCY SHUTDOWN AND START-UP PROCEDURES. 408.1.2.5 COMMISSIONED SYSTEMS THE FOLLOWING EQUIPMENT WILL BE INCLUDED IN THE COMMISSIONING PROCESS. ENERGY CODE REQUIRES THAT THE CONSTRUCTION DOCUMENTS INCLUDE A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR SYSTEMS TO BE TESTED. TAG I EQUIPMENT NAME APARTMENT COMMISSIONING APT ERVS APARTMENT ENERGY RECOVERY VENTILATORS AND CONTROLS APT HEATERS APARTMENT BEDROOM HEATERS AND CONTROLS DIVISION 22: PLUMBING COMMISSIONING WH WATER HEATERS AND CONTROLS HWCP HOT WATER CIRCULATING PUMPS AND CONTROLS DIVISION 23: MECHANICAL COMMISSIONING ERVS ENERGY RECOVERY VENTILATORS AND CONTROLS FCU/HP SPLIT SYSTEM HEAT PUMPS (SINGLE ZONE, MULTI -ZONE, VRF/V) AND CONTROLS SF, EF FANS WITH CONTROLS TAB TEST AND BALANCE - VERIFY THAT TAB OCCURS PER CONSTRUCTION DOCUMENTS & ENERGY CODE REQUIREMENTS. THE COMMISSIONING TEAM DOES NOT PERFORM TAB DIVISION 26: ELECTRICAL COMMISSIONING LCPS LIGHTING CONTROL SYSTEMS FOR INTERIOR DAYLIGHTING AND/OR OCCUPANCY SENSING OS & VS OCCUPANCY & VACANCY SENSORS IN GARAGE, STAIRWELLS, AND COMMON AREAS RECEPTACLES RECEPTACLES CONTROLLED BY OCCUPANCY SENSORS LTG/FAN INTERLOCK LIGHT SWITCHES THAT CONTROL LIGHTS + FANS EH, BB, FAN HT ELECTRIC HEATERS, INDOORS AND CONTROLS EXT LIGHTING EXTERIOR LIGHTING CONTROLS (E.G. TIMECLOCK) ENERGY TRACKING AND ENERGY GENERATION ENERGY METERS END USE METERS, DATABASE, AND DATA ACQUISITION SYSTEM PER C409 RESIDENTIAL ENERGY CODE NOTES 1. THE FOLLOWING NOTES ONLY APPLY TO THE RESIDENTIAL PORTIONS OF THE PROJECT. BUILDINGS B,C & D AND LEVELS 2 & 3 OF BIULDING A 2. SEE MECHANICAL AND PLUMBING SCHEDULES FOR EQUIPMENT TYPE, CAPACITY AND EFFICIENCY. 3. PROVIDE THERMOSTAT CONTROLS CAPABLE OF A FIVE (5) DEGREE DEADBAND BETWEEN HEATING AND COOLING FOR HEAT PUMP SYSTEMS.. 4. PROVIDE AUTOMATIC SETBACK CONTROLS WITH NIGHT SETBACK AND SEVEN (7) DIFFERENT DAY TYPES. 5. PROVIDE DAMPERS FOR OUTSIDE AIR INTAKES AND EXHAUST FANS WHICH CLOSE AUTOMATICALLY WHEN THE SYSTEM IS OFF, EXCEPT FOR THOSE SYSTEMS WHICH OPERATE CONTINUOUSLY.. 6. PROVIDE A MEANS OF BALANCING EVERY AIR SUPPLY OUTLET AND AIR OR WATER TERMINAL DEVICE. 7. SIMULTANEOUS HEATING AND COOLING IN A ZONE IS NOT PERMITTED. 8. SEAL TRANSVERSE SEAMS OF ALL DUCTWORK. 9. SEALING TO CONTROL BUILDING ENVELOPE AIR LEAKAGE AND AIR TIGHTNESS TESTING IS REQUIRED PER 2018 WSEC SECTION R402.4, OPTIONAL CREDITS PURSUED THROUGH SECTION R406. 10. DUCTWORK AND PLENUMS SHALL BE THERMALLY INSULATED, SEALED AND TESTED IN ACCORDANCE WITH 2O18 WSEC SECTION R403.3. 11. ALL PIPING SHALL BE THERMALLY INSULATED TO MEET SPECIFICATIONS SET IN PIPE INSULATION TABLE ON SHEET P0.01 PLUMBING SCHEDULE AND GENERAL NOTES. 12. WATER HEATING EQUIPMENT AND STORAGE TANKS SHALL MEET THE MINIMUM REQUIREMENTS OF SECTION R403.5.5 OF THE 2018 WSEC. 13. A MINIMUM OF 90% OF INSTALLED LIGHTING FIXTURES SHALL BE HIGH EFFICACY PER SECTION R404.1 OF THE 2018 WSEC. 14. MINIMUM FAN PERFORMANCE SHALL MEET THE REQUIREMENTS OF TABLE R403.6.1 15. PROVIDE MICROPROCESSOR -BASED THERMOSTAT FOR HEAT PUMP CONTROLS. COMMERCIAL ENERGY CODE NOTES 1. THE FOLLOWING NOTES ONLY APPLY TO THE COMMERCIAL PORTIONS OF THE PROJECT; BUILDING A - LEVEL 1. 2. SEE MECHANICAL AND PLUMBING SCHEDULES FOR EQUIPMENT TYPE, CAPACITY AND EFFICIENCY. 3. PROVIDE THERMOSTAT CONTROLS CAPABLE OF A FIVE (5) DEGREE DEADBAND BETWEEN HEATING AND COOLING FOR HEAT PUMP SYSTEMS.. 4. PROVIDE AUTOMATIC SETBACK CONTROLS WITH NIGHT SETBACK AND SEVEN (7) DIFFERENT DAY TYPES. 5. PROVIDE DAMPERS FOR OUTSIDE AIR INTAKES AND EXHAUST FANS WHICH CLOSE AUTOMATICALLY WHEN THE SYSTEM IS OFF, EXCEPT FOR THOSE SYSTEMS WHICH OPERATE CONTINUOUSLY.. 6. PROVIDE A MEANS OF BALANCING EVERY AIR SUPPLY OUTLET AND AIR OR WATER TERMINAL DEVICE. 7. SIMULTANEOUS HEATING AND COOLING IN A ZONE IS NOT PERMITTED. 8. SEAL TRANSVERSE SEAMS OF ALL DUCTWORK. 9. SEALING TO CONTROL BUILDING ENVELOPE AIR LEAKAGE AND AIR TIGHTNESS TESTING IS REQUIRED PER 2018 WSEC SECTION C402.5.1 THROUGH C402.5.8, OPTIONAL CREDITS PURSUED THROUGH SECTION C406. 10. DUCTWORK AND PLENUMS SHALL BE THERMALLY INSULATED, SEALED AND TESTED IN ACCORDANCE WITH 2O18 WSEC SECTION C403.10.1 THROUGH 403.10.3.1. 11. ALL PIPING SHALL BE THERMALLY INSULATED TO MEET SPECIFICATIONS SET IN PIPE INSULATION TABLE ON SHEET P0.01 PLUMBING SCHEDULE AND GENERAL NOTES. 12. ALL ELECTRIC MOTORS GREATER THAN 1.0 HP SHALL MEET THE EFFICIENCY REQUIREMENTS OF 2018 WSEC SECTIONS C405.8(1) THROUGH C405.8(4). 13. WATER HEATING EQUIPMENT AND STORAGE TANKS SHALL MEET THE MINIMUM REQUIREMENTS OF SECTION C404.2 OF THE 2018 WSEC. 14. PROVIDE MICROPROCESSOR -BASED THERMOSTAT FOR HEAT PUMP CONTROLS. GENERAL NOTES 1. THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR EVERY OFFSET WHICH MAY BE REQUIRED. THE HVAC CONTRACTOR IS TO COORDINATE WITH ALL OTHER TRADES AND IS TO VERIFY ALL CLEARANCES BEFORE COMMENCING WORK. 2. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE LATEST EDITION OF THE WASHINGTON STATE ENERGY CODE (IECC), INTERNATIONAL MECHANICAL CODE (IMC), INTERNATIONAL BUILDING CODE (IBC), INTERNATIONAL FIRE CODE (IFC), AND OTHER APPLICABLE STATE AND LOCAL CODES AND ORDINANCES. 3. DUCT CONSTUCTION AND HANGINGS SHALL COMPLY WITH THE LATEST IMC AND WITH CURRENT SMACNA STANDARDS. 4. JOINTS OF DUCT SYSTEM SHALL BE SEALED WITH DUCT MASTIC. 5. DUCTS SHALL BE INSULATED AS INDICATED ON PLANS TO MEET THE REQUIREMENTS OF CURRENT CODES AND SPECIFICATIONS. 6. FLEXIBLE DUCTS SHALL ONLY BE USED WHERE SHOWN AND SHALL NOT EXEED 6 FT IN LENGTH UNLESS NOTED OTHERWISE. 7. PROVIDE EARTHQUAKE RESTRAINT FOR HVAC EQUIPMENT IN ACCORDANCE WITH THE CURRENT IBC. 8. PIPING PENETRATIONS OF FIRE RATED WALLS OR FLOOR SHALL BE SLEEVED AND FIRE STOPPED WITH LISTED MATERIALS SO AS TO MAINTAIN THE INTEGRITY AND RATING OF THE FLOOR OR WALL. 9. HVAC EQUIPMENT, VALVES, AND DAMPERS SHALL BE LOCATED IN EASILY ACCESSIBLE LOCATIONS, UNLESS SHOWN ON ARCHITECTURAL DRAWINGS. REQUIRED ACCESS PANELS SHALL BE PROVIDED BY THE HVAC CONTRACTOR AND INSTALLED BY THE GENERAL CONTRACTOR. 10. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF EXPOSED DUCTWORK AND GRILLES. 11. ALL DUCT DIMENSIONS INDICATE FREE AREA. SOUND LINING AND EXTERIOR INSULATION ARE LABELED AS SUCH. C406 ADDITIONAL EFFICIENCY PACKAGE OPTIONS THIS PROJECT WILL COMPLY WITH C406 ADDITIONAL EFFICIENCY CREDITS REQUIREMENTS (6 TOTAL CREDITS) VIA THE PACKAGES LISTED BELOW. THESE PACKAGES SHALL BE IMPLEMENTED THROUGHOUT ALL COMMERCIAL SPACE TYPES FOR THIS PROJECT. • C406.2 - MORE EFFICIENT HVAC PERFORMANCE; 3 CREDITS • C406.3.1 - REDUCED LIGHTING POWER, OPTION 1 (REFER TO ELECTRICAL PLANS FOR MORE INFO); 2 CREDITS • C406.4 - ENHANCED LIGHTING CONTROLS (REFER TO ELECTRICAL PLANS FOR MORE INFO); 1 CREDIT R406 ADDITIONAL EFFICIENCY PACKAGE OPTIONS THIS PROJECT WILL COMPLY WITH R406 ADDITIONAL EFFICIENCY CREDITS REQUIREMENTS (4.5 TOTAL CREDITS) VIA THE OPTIONS LISTED BELOW. THESE OPTIONS SHALL BE IMPLEMENTED THROUGHOUT ALL RESIDENTIAL SPACE TYPES FOR THIS PROJECT. • HEATING OPTION 3 - ELECTRIC RESISTANCE HEAT ONLY - FURNACE OR ZONAL (-1 CREDITS) • ENERGY OPTION 1.1 - EFFICIENT BUILDING ENVELOP (0.5 CREDITS) • ENERGY OPTION 2.3 -AIR LEAKAGE CONTROL AND EFFICIENT VENTILATION (2 CREDITS) • ENERGY OPTION 5.6 - EFFICIENT WATER HEATING (3 CREDITS) ,.,.,.,.,.,..,.,.,.,.,., REVIEWED BY CITY OF EDMONDS BUILDING DEPARTMENT: IBLD2022-1319- A BLD2022-1320 - B BLD2022-1321 -C BLD2022-1322- D HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1270 10031 SR 532, Suite B Stanwood, WA 98292 www.designsnw.com ECOTOPE 19 1 7 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 W A V♦ O �z � Z Q zO Lu C' J LLI Z W Lu w V Q = O �Cy') a c.0 N mc � 0 N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description RESUB Apr 04 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT CONTENTS: ENERGY CODE DOCUMENTATION - NOTES SCALE: 1/8" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: ECO,01 2018 Washington State Energy Code - Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Multifamily (effective February 1, 2021) Each dwelling unit in a residential building shall comply with sufficient options from Table R406.2 (fuel normalization credits) and Table 406.3 (energy credits) so as to achieve the following minimum number of credits: • Multifamily R2 Dwelling Unit: Y., , reacts Before selecting your credits on this Summary table, review the details in Table 406.3 (Multifamily), on page 3. Summaryable R406.2 and 406.3 Credits - select ONE heating option User Notes Heating Options Fuel Normalization Descriptions 1 Combustion heating minimum NAECAb 0.0 ❑ 2 Heat pump` 1.0 ❑ 3 Electric resistance heat only - furnace or zonal -1.0 0 Electric resistance heatin onl 4 DHP with zonal electric resistance per option 3.4 na ❑ 5 All other heating systems -0.5 1 ❑ Energy Options p Credits - select ONE Energy Credit Option Descriptions energy option from each category Efficient Building Envelope 0.5 Efficient Building Envelope 1.0 ❑ 1.1 Vertical Fenstration U = 0.24 1.2 1.4 Efficient Building Envelope 1.0 ❑ 1.5 Efficient Building Envelope 1.5 ❑ 1.6 Efficient Building Envelope 2.0 ❑ 1.7 Efficient Building Envelope El 0.5 ❑ 2.1 Air Leakage Control and Efficient Ventilation 1.0 ❑ 2.2 Air Leakage Control and Efficient Ventilation 1.5 ❑ 2.3 Air Leakage Control and Efficient Ventilation 2.0 El 0.25 Cfm/ft^2 max @ 50 Pa 2.4 Air Leakage Control and Efficient Ventilation 2.5 ❑ 3. la High Efficiency HVAC 1.0 ❑ 3.3a High Efficiency HVAC 1.0 ❑ 3.4 High Efficiency HVAC 2.0 ❑ 3.61 High Efficiency HVAC 3.0 ❑ 4.1 High Efficiency HVAC Distribution System 0.5 ❑ 5.1d Efficient Water Heating 0.5 ❑ 5.2 Efficient Water Heating 0.5 ❑ 5.3 Efficient Water Heating 1.0 ❑ 5.4 Efficient Water Heating 2.0 ❑ 5.5 Efficient Water Heating 2.5 ❑ 5.6 Efficient Water Heating L1 3.0 1HPWH Provided 6.1e Renewable Electric Energy (3 credits max) 1.0 7.1 Appliance Package 1.5 ❑ Total Credits 4.5 Calculate Total Clear Form a. An alternative neating source sizea at a maximum OT U.5 w/sT (equivalent) oT neatea floor area or 5uu w, whichever is bigger, may be installed in the dwelling unit. b. Equipment listed in Table C403.3.2(4) or C403.3.2(5) c. Equipment listed in Table C403.3.2(1) or C403.3.2(2) d. You cannot select more than one option from any category EXCEPT in category S. Option 5.1 may be combined with options 5.2 through 5.6. See Table 406.3. e. 1.0 credit for each 1,200 kWh of electrical generation provided annually, up to 3 credits max. See Table R406.2 for full requirements and complete option descriptions. f. Use the single radiobutton in the upper right of the second column to deselect radiobuttons in that group. Please print only pages 1 and 2 of this worksheet for submission to your building official. Prescriptive Path - Multifamily 2018 Washington State Energy Code-R 2018 Washington State Energy Code - Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Multifamilv (effective February 1.20211 Version 1.1 These requirements apply to Group R-2 buildings three stories or less in height above grade plane. Other Group R-2 buildings must comply with the commercial energy code. Project Information Contact Information Housing Hope ELC Field Apartments - Building A IShawn Cram, PE, Ecoto a Inc. Levels 2 & 3 3-Story Lowrise MF Building Direct: 206 322-5968 Instructions: This multifamily project will use the requirements of the Prescriptive Path below and incorporate the minimum values listed. Based on the size of the structure, the appropriate number of additional credits are checked as chosen by the permit applicant. Provide all information from the following tables as building permit drawings: Table R402.1- Insulation and Fenestration Requirements by Component, Table R406.2 - Fuel Normalization Credits and 406.3 - Energy Credits. y s9neE M Slunti Orem Authorized Representative Shanti OramreECN=Sn®o°ce Omo-c-.ou=o«gnew Date 09/23/2022 2022.09.231$:SS:SZ-0T W All Climate Zones (Table R402.1.1) R-Value a U-Factor a Fenestration U-Factor b n/a 0.30 Skylight U-Factor b n/a 0.50 Glazed Fenestration SHGC b,e n/a n/a Ceiling a 49 0.026 Wood Frame Wall g,h 21 int 0.056 Floor 30 0.029 Below Grade Wall `•h 10/15/21 int+TB 0.042 Slab d,f R-Value & Depth 10, 2 ft n/a R-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity that is less a than the label or design thickness of the insulation, the compressed R-value of the insulation from Appendix Table A101.4 shall not be less than the R-value specified in the table. The fenestration U-factor column excludes skylights. "10/15/21 +5TB" means R-10 continuous insulation on the exterior of the wall, or R-15 continuous insulation on b the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the basement wall at c the interior of the basement wall. "10/15/21 +5TB" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the wall. "5TB" means R- 5 thermal break between floor slab and basement wall. R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1. d For single rafter- or joist -vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth extends e over the top plate of the exterior wall. R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the required perimeter f slab insulation when applied to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall meet the requirements for thermal barriers protecting foam plastics. For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for g climate zone 5 of [CC 400. Int. (intermediate framing) denotes framing and insulation as described in Section A103.2.2 including standard h framing 16 inches on center, 78% of the wall cavity insulated and headers insulated with a minimum of R-10 insulation. lFor Building Officials Only 2 Prescriptive Path - Multifamily 2018 Washington State Energy Code-R CODE COMPLIANCE DOCUMENTS SHOWN ON THIS SHEET ONLY APPLY TO THE RESIDENTIAL PORTIONS OF THIS BUILDING. (BUILDINGS B, C, D & BUILDING A -LEVELS 20) AW\ HOUSING HOPE we keep hope alive DESIGNS 1 L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 w ww. designs nw. cont ECOTOPE 19 1 7 1 ST AvE, #300 SEATTLE WA 9a 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 W am Cn O Z Z Q ZO l� Lu C' J LL1 Z W Lu Cn � w V a U) = O J a c.0 M N mc L u7 N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # = Date Description 2 01/04/2023 IPERMITRESUBM. RESUB Apr 04 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT IKlJ►11a►11.'fi ENERGY CODE DOCUMENTATION - BUILDING A LEVELS2&3 SCALE: DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: ECO,02 2018 WSEC Compliance Forms for Commercial Buildings including Group R2, R3 & R4 over 3 stories and all Rl Administered by: ©2022 NEEA, All rights reserved Project & Applicant Information Project Title Housing Hope ELC Field Apartments Building A Level 1 - 2018 WSEC For Building Department Use: Date: Sep 28, 2022 Project Address 8215 236th St SW Edmonds, WA 98026 Applicant Name Shawn Oram Applicant Phone 206-322-3753 Applicant Email shawn@ecotope.com For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com General Occupancy All Commercial General Building Use Type Multifamily/Residential, Mixed Use Building Cond. Floor Area 4,153 General Project Types New Building New Bilding �.rAddliti.. Mechanical Sco a P Single Zone Systems &Equipment Multiple Zone Systems &Equipment Alteration Mechanical Scope Project Cond. Floor Area 4,153 Floors Above Grade 1 Compliance Method Compliance Method 1 - General Mechanical Project Description Level 1 of a 3 story "wood walkup" apartment containing Type B occupancy offices, supportive services, and small assembly rooms. Project Economizer DOAS Ventilation Higher Equipment Equipment Efficiency Type Mechanical Scope Exception(s) Provided? Efficiency Option Applied? Compliance Applied? Verification Mechanical Compliance New Single Zone Systems & Scope and Method Building Equipment No Yes Yes COMPLIES New Multiple Zone Systems & No Yes Yes COMPLIES Building Equipment Additional Efficiency Higher equipment efficiency and fan FEG Credits Included (AEC) Does building include occupancy classifications requiring Yes Does project include DOAS equipment? Yes DOAS? Based on project scope do TSPR requirements apply? No Do all systems comply with Appendix D standard reference design or qualify for an exception to No TSPR? Scope & Space Conditioning NEW BUILDING - SINGLE ZONE SYSTEMS & EQUIPMENT Compliance Verification COMPLIES Scope & Space Conditioning NEW BUILDING - MULTIPLE ZONE SYSTEMS & EQUIPMENT Compliance Verification COMPLIES 2018 WSEC Compliance Forms for Commercial Buildings including Group R2, R3 & R4 over 3 stories and all Rl Administered by: 02022 NEEA, All rights reserved Project & Applicant Information Project Title Housing Hope ELC Field Apartments Building A Level 1 - 2018 WSEC For Building Department Use: Date: Sep 28, 2022 Project Address 8215 236th St SW Edmonds, WA 98026 Applicant Name Shawn Oram Applicant Phone 206-322-3753 Applicant Email Shawn@ecotope.com For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com General Occupancy All Commercial General Building Use Type Multifamily/Residential, Mixed Use Building Cond. Floor Area 4,153 Project Scope New Building Space Conditioning Categories Fully Conditioned Project Cond. Floor Area 4,153 Floors Above Grade 1 Compliance Method Compliance Method 1 - General Envelope Project Description Level 1 of a 3 story "wood walkup" apartment containing Type B occupancy offices, supportive services, and small assembly rooms. Envelope Compliance Scope Scope Space Conditioning Category Compliance Method W Wg/Sgg per Category UA Calculation Adjustment Fenestration Alternates Compliance Verification and Method New Building Fully Conditioned Prescriptive 20.20% / 0% None selected No alternates selected COMPLIES Air Barrier Testing I Air barrier testing included in project scope I Air Barrier Comments Project Title Housing Hope ELC Field Apartments Building A Level 1 - 2018 WSEC Date Sep 28, 2022 Scope & Space Conditioning NEW BUILDING - FULLY CONDITIONED Compliance Verification COMPLIES Window -to -wall Ratio 20.20% 1 Skylight -to -roof -ratio 1 II° 1, vertical Fenestration Alternate No alternates selected Opaque Envelope Assemblies Insulation R-Values Walls Location in Documents Assembly ID Assembly Location Cavity Continuous (% penetration) Insulated Wall Furring U-Factor Net Area (SF) Wood -framed and other - Commercial A4.0 Wall Assembly 1 I 1 Exterior R-21 R-19.00 (> 0.08% - 0.12%) 2,232 Which insulation code target does wall comply with?: R-21 Cavity + Intermediate Framing U-Factor Source: U-Factor Source Description: Wall Framing Type (Standard, Inter., Advanced): Intermediate Framing Depth:2x6 Framing Spacing: Is this assembly exterior or interior?: Exterior Slab -on -grace Floors Location in Documents Assembly ID Assembly Location Slab Edge Under Slab F-Factor Perimeter Length (SF) Unheated slab A4.00 Floor Assembly 2 1 Floor Assembly 2 At grade level R-10 R-10 234 Slab Insulation Method: 2 ft vertical (from top of slab downward) F-Factor Source: F-Factor Source Description: Fenestration & Opaque Door Assemblies Insulation R-Values Vertical Fenestration Location in Documents Assembly ID Assembly Location Orientation Shading (PF) Fenestration SHGC Fenestration U-Factor Rough Opening (SF) Operable - Class AW or site built A7.2 Window Type A - DD Exterior South/East/West Facing I PF < 0.2 SHGC-0.38 U-0.4 469 U-Factor & SHGC Source: U-Factor Source Description: Is this assembly exterior or interior?: Exterior Operable - Class AW or site built A7.2 Window Type A - DD Exterior North Facing PF < 0.2 SHGC-0.51 U-0.4 96 U-Factor & SHGC Source: U-Factor Source Description: Is this assembly exterior or interior?: Exterior CODE COMPLIANCE DOCUMENTS SHOWN ON THIS SHEET ONLY APPLY TO THE COMMERCIAL PORTIONS OF THIS BUILDING. (BUILDING A -LEVEL 1) AW\ HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. cont ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 O 1 PH: (206) 322-3753 FAX: (206) 325-7270 05 W am Cn O WZ Z Q 0 l� W C' J LLJ Z llllllllllllllllllllll■ W llllllllllllllllllllll■ (� W W V Q O J a M C\I mc � t.C') CV 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # Date Description RESUB Apr 04 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT IK11I►11a►1b i ENERGY CODE DOCUMENTATION - BUILDING A LEVEL 1 SCALE: DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: ECO,03 2018 Washington State Energy Code - Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Multifamily (effective February 1, 2021) Each dwelling unit in a residential building shall comply with sufficient options from Table R406.2 (fuel normalization credits) and Table 406.3 (energy credits) so as to achieve the following minimum number of credits: • Multifamily R2 Dwelling Unit: 4.5 credits Before selecting your credits on this Summary table, review the details in Table 406.3 (Multifamily), on page 3. Summary able R406.2 and 406.3 Credits - select ONE heating option User Notes Heating Options Fuel Normalization Descriptions 1 Combustion heating minimum NAECAb 0.0 ❑ 2 Heat pump` 1.0 ❑ 3 Electric resistance heat only - furnace or zonal -1.0 0 Electric resistance heatin onl 4 DHP with zonal electric resistance per option 3.4 na ❑ 5 All other heating systems -0.5 ❑ Energy Options p Energy Credit Option Descriptions Efficient Building Envelope Efficient Building Envelope Credits - select ONE energy option from each category 1.1 0.5 0 Pertical Fenstration U = 0.24 1.2 1.0 1.0 1.5 ❑ ❑ ❑ 1.4 Efficient Building Envelope 1.5 Efficient Building Envelope 1.6 Efficient Building Envelope 2.0 ❑ 1.7 Efficient Building Envelope El 0.5 ❑ 2.1 Air Leakage Control and Efficient Ventilation 1.0 ❑ 2.2 Air Leakage Control and Efficient Ventilation 1.5 ❑ 2.3 Air Leakage Control and Efficient Ventilation 2.0 El 0.25 cfm/ft^2 max @ 50 Pa 2.4 Air Leakage Control and Efficient Ventilation 2.5 ❑ 3. la High Efficiency HVAC 1.0 ❑ 3.3a High Efficiency HVAC 1.0 ❑ 3.4 High Efficiency HVAC 2.0 ❑ 3.61 High Efficiency HVAC 3.0 ❑ 4.1 High Efficiency HVAC Distribution System 0.5 ❑ 5.1d Efficient Water Heating 0.5 ❑ 5.2 Efficient Water Heating 0.5 ❑ 5.3 Efficient Water Heating 1.0 ❑ 5.4 Efficient Water Heating 2.0 ❑ 5.5 Efficient Water Heating 2.5 ❑ 5.6 Efficient Water Heating 3.0 JHIPWH Provided 6.1e Renewable Electric Energy (3 credits max) 1.0 7.1 Appliance Package 1.5 ❑ Total Credits 4.5 Calculate Total Clear Form a. An alternative neating source sized at a maximum of u.5 w/ST (equivalent) Ot heated door area or 5UU W, whichever is bigger, may be installed in the dwelling unit. b. Equipment listed in Table C403.3.2(4) or C403.3.2(5) c. Equipment listed in Table C403.3.2(1) or C403.3.2(2) d. You cannot select more than one option from any category EXCEPT in category S. Option 5.1 may be combined with options 5.2 through 5.6. See Table 406.3. e. 1.0 credit for each 1,200 kWh of electrical generation provided annually, up to 3 credits max. See Table R406.2 for full requirements and complete option descriptions. f. Use the single radiobutton in the upper right of the second column to deselect radiobuttons in that group. Prescriptive Path - Multifamily 2018 Washington State Energy Code-R r 2018 Washington State Energy Code - Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Multifamilv (effective February 1, 2021) Version 1.1 These requirements apply to Group R-2 buildings three stories or less in height above grade plane. Other Group R-2 buildings must comply with the commercial energy code. Project Information Contact Information Housing Hope ELC Field Apartments - Building B Shawn Oram, PE, Ecoto a Inc. 3-Story Lowrise MF Building Direct: 206 322-5968 Instructions: This multifamily project will use the requirements of the Prescriptive Path below and incorporate the minimum values listed. Based on the size of the structure, the appropriate number of additional credits are checked as chosen by the permit applicant. Provide all information from the following tables as building permit drawings: Table R402.1- Insulation and Fenestration Requirements by Component, Table R406.2 - Fuel Normalization Credits and 406.3 - Energy Credits. D4-Y lig-M Snan60Nm Englneen�g, CN=Sh.n40rem Authorized Representative Shanti Oram ON:C=US.E=.ha @ewbcewn.0•-.oU•OeLgnantl Date 09/23/2022 CaY. 2023.03.2316074B0T All Climate Zones (Table R402.1.1) R-Valuea U-Factora Fenestration U-Factor b n/a 0.30 Skylight U-Factor b n/a 0.50 Glazed Fenestration SHGC b,e n/a n/a Ceiling a 49 0.026 Wood Frame Wall g,h 21 int 0.056 Floor 30 0.029 Below Grade Wall `h 10/15/21 int+TB 0.042 Slab d,f R-Value & Depth 10, 2 ft n/a R-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity that is less a than the label or design thickness of the insulation, the compressed R-value of the insulation from Appendix Table A101.4 shall not be less than the R-value specified in the table. b The fenestration U-factor column excludes skylights. "10/15/21 +5TB" means R-10 continuous insulation on the exterior of the wall, or R-15 continuous insulation on the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the basement wall at c the interior of the basement wall. "10/15/21 +5TB" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the wall. "5TB" means R- 5 thermal break between floor slab and basement wall. d R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1. For single rafter- or joist -vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth extends e over the top plate of the exterior wall. R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the required perimeter f slab insulation when applied to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall meet the requirements for thermal barriers protecting foam plastics. For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for g climate zone 5 of [CC 400. Int. (intermediate framing) denotes framing and insulation as described in Section A103.2.2 including standard h framing 16 inches on center, 78% of the wall cavity insulated and headers insulated with a minimum of R-10 insulation. For Building Officials Only Prescriptive Path - Multifamily 2018 Washington State Energy Code-R CODE COMPLIANCE DOCUMENTS SHOWN ON THIS SHEET ONLY APPLY TO THE RESIDENTIAL PORTIONS OF THIS BUILDING. (BUILDINGS B, C, D & BUILDING A -LEVELS 20) AW\ HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. cont ECOTOPE 19 1 7 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 W am Cn O �MMWZ Z Q ZO w C' J LL1 U) Z W (n LU Cl) LL w V Q U) = O J a c.0 M N mc � L0 N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # = Date Description 2 01/04/2023 IPERMITRESUBM. RESUB Apr 04 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT IKlJ►11a►11.'fi ENERGY CODE DOCUMENTATION - BUILDING B SCALE: DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: ECO,04 2018 Washington State Energy Code - Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Multifamily (effective February 1, 2021) Each dwelling unit in a residential building shall comply with sufficient options from Table R406.2 (fuel normalization credits) and Table 406.3 (energy credits) so as to achieve the following minimum number of credits: • Multifamily R2 Dwelling Unit: 4.5 credit! Before selecting your credits on this Summary table, review the details in Table 406.3 (Multifamily), on page 3. Summa able Heating Options Fuel Normalization Descriptions R406.2 and 406.3 Credits - select ONE heating option User Notes 1 Combustion heating minimum NAECAb 0.0 ❑ 2 Heat pump` 1.0 ❑ 3 Electric resistance heat only - furnace or zonal -1.0 0 Electric resistance heatin onl 4 DHP with zonal electric resistance per option 3.4 na ❑ 5 All other heating systems -0.5 ❑ Energy Options p Credits - select ONE Energy Credit Option Descriptions energy option from each category Efficient Building Envelope 0.5 Vertical Fenstration U = 0.24 Efficient Building Envelope 1.0 ❑ Efficient Building Envelope 1.0 ❑ Efficient Building Envelope 1.5 ❑ 1.1 1.2 1.4 1.5 1.6 Efficient Building Envelope 2.0 ❑ 1.7 Efficient Building Envelope El 0.5 ❑ 2.1 Air Leakage Control and Efficient Ventilation 1.0 ❑ 2.2 Air Leakage Control and Efficient Ventilation 1.5 ❑ 2.3 Air Leakage Control and Efficient Ventilation 2.0 El 10.25 cfm/ft^2 max @ 50 Pa 2.4 1 Air Leakage Control and Efficient Ventilation 2.5 ❑ 3. la High Efficiency HVAC 1.0 ❑ 3.3a High Efficiency HVAC 1.0 ❑ 3.4 High Efficiency HVAC 2.0 ❑ 3.61 High Efficiency HVAC 3.0 ❑ 4.1 High Efficiency HVAC Distribution System 0.5 ❑ 5.1d Efficient Water Heating 0.5 ❑ 5.2 Efficient Water Heating 0.5 ❑ 5.3 Efficient Water Heating 1.0 ❑ 5.4 Efficient Water Heating 2.0 ❑ 5.5 Efficient Water Heating 2.5 ❑ 5.6 Efficient Water Heating 3.0 0 HPWH Provided 6.1e Renewable Electric Energy (3 credits max) 1.0 0 7.1 Appliance Package 1.5 ❑ Total Credits 4.5 Calculate Total Clear Form a. An alternative nearing source sizea at a maximum OT U.5 W/sT tequivalent) oT neatecl tloor area or SUU W, whichever is bigger, may be installed in the dwelling unit. b. Equipment listed in Table C403.3.2(4) or C403.3.2(5) c. Equipment listed in Table C403.3.2(1) or C403.3.2(2) d. You cannot select more than one option from any category EXCEPT in category S. Option 5.1 may be combined with options 5.2 through 5.6. See Table 406.3. e. 1.0 credit for each 1,200 kWh of electrical generation provided annually, up to 3 credits max. See Table R406.2 for full requirements and complete option descriptions. f. Use the single radiobutton in the upper right of the second column to deselect radiobuttons in that group. Please print only pages 1 and 2 of this worksheet for submission to your building official. Prescriptive Path - Multifamily 2018 Washington State Energy Code-R 2018 Washington State Energy Code - Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Multifamilv (effective February 1. 2021) Version 1.1 These requirements apply to Group R-2 buildings three stories or less in height above grade plane. Other Group R-2 buildings must comply with the commercial energy code. Project Information Contact Information Housing Hope ELC Field Apartments - Building C Shawn Oram, PE, Ecoto a Inc. 3-Story Lowrise MF Building Direct: (206) 322-5968 Instructions: This multifamily project will use the requirements of the Prescriptive Path below and incorporate the minimum values listed. Based on the size of the structure, the appropriate number of additional credits are checked as chosen by the permit applicant. Provide all information from the following tables as building permit drawings: Table R402.1- Insulation and Fenestration Requirements by Component, Table R406.2 - Fuel Normalization Credits and 406.3 - Energy Credits. y.pn.a xr sne�u on,m Authorized Representative Shanti Oram '°sE�"°"`�"°E�"°`°°°`'s°a°" Date 09/23/2022 E �q. 2s aen80rem P022.092318:8931-0TW All Climate Zones (Table R402.1.1) R-Valuea U-Factora Fenestration U-Factor b n/a 0.30 Skylight U-Factor b n/a 0.50 Glazed Fenestration SHGC b,e n/a n/a Ceiling a 49 0.026 Wood Frame Wall g,h 21 int 0.056 Floor 30 0.029 Below Grade Wall `,h 10/15/21 int+TB 0.042 Slab d,f R-Value & Depth 10, 2 ft n/a R-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity that is less a than the label or design thickness of the insulation, the compressed R-value of the insulation from Appendix Table A101.4 shall not be less than the R-value specified in the table. b The fenestration U-factor column excludes skylights. "10/15/21 +5TB" means R-10 continuous insulation on the exterior of the wall, or R-15 continuous insulation on the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the basement wall at c the interior of the basement wall. "10/15/21 +5TB" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the wall. "5TB" means R- 5 thermal break between floor slab and basement wall. R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1. d For single rafter- or joist -vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth extends e over the top plate of the exterior wall. R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the required perimeter f slab insulation when applied to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall meet the requirements for thermal barriers protecting foam plastics. For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for g climate zone 5 of ICC 400. Int. (intermediate framing) denotes framing and insulation as described in Section A103.2.2 including standard h framing 16 inches on center, 78%ofthe wall cavity insulated and headers insulated with a minimum of R-10 insulation. IFor Building Officials Only 2 Prescriptive Path - Multifamily 2018 Washington State Energy Code-R CODE COMPLIANCE DOCUMENTS SHOWN ON THIS SHEET ONLY APPLY TO THE RESIDENTIAL PORTIONS OF THIS BUILDING. (BUILDINGS B, C, D & BUILDING A -LEVELS 20) AW\ HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. com ECOTOPE 19 1 7 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 05 W am Cn O �Z (n Z Q O w C' J LLJ U) Z W � F- LU Cl) LL w - V a U) = F- O J a c.0 M N mc L L0 N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # = Date Description 2 01/04/2023 IPERMITRESUBM. RESUB Apr 04 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT IKlJ►11a►11.'fi ENERGY CODE DOCUMENTATION - BUILDING C SCALE: DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: ECO,05 2018 Washington State Energy Code - Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Multifamily (effective February 1, 2021) Each dwelling unit in a residential building shall comply with sufficient options from Table R406.2 (fuel normalization credits) and Table 406.3 (energy credits) so as to achieve the following minimum number of credits: • Multifamily R2 Dwelling Unit: 4.5 credits Before selecting your credits on this Summary table, review the details in Table 406.3 (Multifamily), on page 3. Sum ma able Heating Options Fuel Normalization Descriptions R406.2 and 406.3) Credits - select ONE heating option User Notes 0.0 ❑ 1.0 ❑ 1 2 Combustion heating minimum NAECAb Heat pump` 3 Electric resistance heat only - furnace or zonal -1.0 El lElectric resistance heating ON ❑ ❑ ONE from each 4 DHP with zonal electric resistance per option 3.4 na 5 All other heating systems Energy Credit Option Descriptions -0.5 Credits - select energy option category Energy Options p 1.1 Efficient Building Envelope 0.5 vertical Fenstration U = 0.24 1.2 Efficient Building Envelope 1.0 ❑ 1.4 Efficient Building Envelope 1.0 ❑ 1.5 Efficient Building Envelope 1.5 El Efficient Building Envelope 2.0 ❑ 1.7 Efficient Building Envelope El 0.5 ❑ 2.1 Air Leakage Control and Efficient Ventilation 1.0 ❑ 2.2 Air Leakage Control and Efficient Ventilation 1.5 ❑ 2.3 Air Leakage Control and Efficient Ventilation 2.0 0 .25 cfm/ft12 max 50 Pa 2.4 Air Leakage Control and Efficient Ventilation 2.5 ❑ 3.1a High Efficiency HVAC 1.0 ❑ 3.3a High Efficiency HVAC 1.0 ❑ 3.4 High Efficiency HVAC 2.0 ❑ 3.61 High Efficiency HVAC 3.0 ❑ 4.1 High Efficiency HVAC Distribution System 0.5 ❑ 5.1d Efficient Water Heating 0.5 ❑ 5.2 Efficient Water Heating 0.5 ❑ 5.3 Efficient Water Heating 1.0 ❑ 5.4 Efficient Water Heating 2.0 ❑ 5.5 Efficient Water Heating 2.5 ❑ 5.6 Efficient Water Heating LJ 3.0 0 HPWH Provided 6. le Renewable Electric Energy (3 credits max) 1.0 ❑ 7.1 Appliance Package 1.5 ❑ Total Credits 4.5 Calculate Total Clear Form a. An alternative heating source sized at a maximum of U.5 W/st (equivalent) Ot heated tloor area or 5UU W, whichever is bigger, may be installed in the dwelling unit. b. Equipment listed in Table C403.3.2(4) or C403.3.2(5) c. Equipment listed in Table C403.3.2(1) or C403.3.2(2) d. You cannot select more than one option from any category EXCEPT in category S. Option 5.1 may be combined with options 5.2 through 5.6. See Table 406.3. e. 1.0 credit for each 1,200 kWh of electrical generation provided annually, up to 3 credits max. See Table R406.2 for full requirements and complete option descriptions. f. Use the single radiobutton in the upper right of the second column to deselect radiobuttons in that group. Please print only pages 1 and 2 of this worksheet for submission to your building official. Prescriptive Path - Multifamily 2018 Washington State Energy Code-R 2018 Washington State Energy Code - Residential Prescriptive Energy Code Compliance for All Climate Zones in Washington Multifamilv (effective February 1. 2021) Version 1.1 These requirements apply to Group R-2 buildings three stories or less in height above grade plane. Other Group R-2 buildings must comply with the commercial energy code. Project Information Contact Information Housing Hope ELC Field Apartments - Building D Shawn Oram, PE, Ecoto a Inc. 3-Story Lowrise MF Building Direct: 206 322-5968 Instructions: This multifamily project will use the requirements of the Prescriptive Path below and incorporate the minimum values listed. Based on the size of the structure, the appropriate number of additional credits are checked as chosen by the permit applicant. Provide all information from the following tables as building permit drawings: Table R402.1- Insulation and Fenestration Requirements by Component, Table R406.2 - Fuel Normalization Credits and 406.3 - Energy Credits. ogmiy ero^atl uy menu on,m Authorized Representative En:C=US,E•anew®emope.an,0•Eaape.OU•0esgnentl Date 09/23/2022 p anti ram ,�ee�.e"s�eeuo�m oer: zon.w.za ia:io:zs-oroa All Climate Zones (Table R402.1.1) R-Value a U-Factor a Fenestration U-Factor b n/a 0.30 Skylight U-Factor b n/a 0.50 Glazed Fenestration SHGC b,e n/a n/a Ceiling a 49 0.026 Wood Frame Wall g,h 21 int 0.056 Floor 30 0.029 Below Grade Wall `,h 10/15/21 int +TB 0.042 Slab d,f R-Value & Depth 10, 2 ft n/a R-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity that is less a than the label or design thickness of the insulation, the compressed R-value of the insulation from Appendix Table A101.4 shall not be less than the R-value specified in the table. b The fenestration U-factor column excludes skylights. "10/15/21 +5TB" means R-10 continuous insulation on the exterior of the wall, or R-15 continuous insulation on the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the basement wall at c the interior of the basement wall. "10/15/21 +5TB" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the wall. "5TB" means R- 5 thermal break between floor slab and basement wall. R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1. d For single rafter- or joist -vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth extends e over the top plate of the exterior wall. R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the required perimeter f slab insulation when applied to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall meet the requirements for thermal barriers protecting foam plastics. For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for g climate zone 5 of ICC 400. Int. (intermediate framing) denotes framing and insulation as described in Section A103.2.2 including standard h framing 16 inches on center, 78%ofthe wall cavity insulated and headers insulated with a minimum of R-10 insulation. IFor Building Officials Only 2 Prescriptive Path - Multifamily 2018 Washington State Energy Code-R CODE COMPLIANCE DOCUMENTS SHOWN ON THIS SHEET ONLY APPLY TO THE RESIDENTIAL PORTIONS OF THIS BUILDING. (BUILDINGS B, C, D & BUILDING A -LEVELS 20) AW\ HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. cont ECOTOPE 1 9 1 7 1 ST AVE, #300 SEATTLE WA 9a 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 05 W am Cn O �Z U) Z Q ZO w C' J LLI U) Z WU) Lu Cl) LL w - V a U) = O J a c.0 M N L u7 N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # = Date Description 2 01/04/2023 IPERMITRESUBM. RESUB Apr 04 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT IKlJ►11a►11.'fi ENERGY CODE DOCUMENTATION - BUILDING D SCALE: DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: ECO,06 COMMON AREA VENTILATION REQUIREMENTS ROOM ASHRAE PROPOSED ROOM # A100 ROOM NAME CORRIDOR AREA (SF) # PEOPLE USE 580 0 Corridors Ra SUPPLY Rp (CFM) 0 34.8 EXHAUST (CFM) 0 SUPPLY (CFM) RETURN (CFM) 175 0.06 100 A101 COMMUNITY 520 30 Multi -Purpose Assembly 0.06 5 181.2 0 200 150 A102 PROPERTY OFFICE 170 2 Office 0.06 5 20.2 0 25 0 A103 PROPERTY OFFICE 170 2 Office 0.06 5 20.2 0 25 0 A104 SECURE FILE 100 2 Office 0.06 5 16 0 25 0 A105 A106 COPY/WORK SERVICES OFFICE 100 2 Office Office 0.06 5 16 0 25 0 165 2 0.06 5 19.9 0 25 0 A107 SERVICES OFFICE 165 2 Office 0.06 5 19.9 0 25 0 A108 CONSULTATION 120 2 Office 0.06 5 17.2 0 25 0 A109 TOILET 53 0 Restroom 0 0 0 75 0 75 A110 STORAGE 53 0 Storage Multi -Purpose Assembly Office 0 0 0 25 0 25 A111 MULTIPURPOSE 700 48 0.6 5 660 0 675 575 A112 SERVICES OFFICE 166 2 0.06 5 19.96 0 25 0 A113 TOILET 53 0 Restroom 0 0 0 75 0 75 A114 STORAGE 59 0 Storage 0 0 0 25 0 25 RESIDENTIAL UNIT VENTILATION REQUIREMENTS ROOM OA CFM OA CFM ROOM NUMBER AREA # BDRS REQUIREMENT SUPPLLIED [SF] 1 [CFM] 30 [CFM] B103, B104, B203, B204, B303, B304, D101 0 - 1,500 SEE PLANS A202, A203, A204, A301, A302, A303, A304, 13101, B102, B201, B202, B301, B302, B304, C101, C102, C103, C104, C201, C202, C203, C204, C301, C302, C303, D101, D102, 500-1,000 2 35 SEE PLANS D103, D104, D105, D106, D201, D202, D203, D204, D205, D206, D301, D302, D303, D304, D305 501-1000 SEE PLANS A201, A205, A301, A305, B101, B201, B301, C104, C204, 3 40 C304, D106, D206, D306 RESIDENTIAL UNIT HEAT LOAD CALCULATION UNIT NUMBERS) AREA DESIGN HEATING LOAD, TOTAL HEATER CAPACITY PROVIDED OVERSIZE RATIO (MIN DHL/PROVIDED) DHL (VENTILATION + INFILTRATION + CONDUCTION) ROOM NAME [FTA2] 1W] (VV] (%] RES UNIT - A201 RES UNIT - A202 914 1,683 983 2,100 1,400 125% 142% 689 RES UNIT - A203 689 983 1,400 142% RES UNIT - A204 689 983 1,400 142% RES UNIT -A205 898 1,521 2,100 138% RES UNIT - A301 911 2,016 2,100 104% RES UNIT - A302 689 1,219 1,400 115% RES UNIT -A303 689 1,219 1,400 115% RES UNIT -A304 689 1,219 1,400 115% RES UNIT -A305 898 1,828 2,100 115% RES UNIT - B101 901 2,312 2,460 106% RES UNIT- B102 689 1,219 1,400 115% RES UNIT - 13103 478 857 980 114% RES UNIT- B104 432 1,170 11260 108% RES UNIT- B201 914 1,696 2,100 124% RES UNIT- B202 689 981 1,400 143% RES UNIT - B203 560 796 980 123% RES UNIT- B204 576 1,154 1,260 109% RES UNIT - B301 912 2,034 2,100 103% RES UNIT- B302 689 1,217 1,400 115% RES UNIT- B303 560 988 1,120 113% RES UNIT- B304 576 1,352 1,540 114% RES UNIT - C101 734 1,832 1,920 105% RES UNIT - C102 689 1,282 1,400 109% RES UNIT - C103 689 1,282 1,400 109% RES UNIT - C104 901 1,836 2,100 114% RES UNIT - C201 734 1,274 1,400 110% RES UNIT - C202 689 983 1,400 142% RES UNIT - C203 689 983 1,400 142% RES UNIT - C204 901 1,503 2,100 140% RES UNIT - C301 734 1,525 1,540 101% RES UNIT - C302 689 1,219 1,400 115% RES UNIT - C303 689 1,219 1,400 115% RES UNIT - C304 901 1,812 2,100 116% RES UNIT- D101 485 1,244 1,260 101% RES UNIT- D102 689 1,286 1,400 109% RES UNIT - D103 689 1,286 1,400 109% RES UNIT- D104 689 1,286 1,400 109% RES UNIT- D105 678 1,246 1,400 112% RES UNIT - D106 911 2,200 2,460 112% RES UNIT- D201 733 1,373 1,400 102% RES UNIT- D202 689 983 1,400 142% RES UNIT - D203 689 983 1,400 142% RES UNIT- D204 689 983 1,400 142% RES UNIT- D205 678 959 1,400 146% RES UNIT- D206 924 1,731 2,100 121% RES UNIT- D301 735 1,626 1,920 118% RES UNIT- D302 RES UNIT - D303 688 1,218 1,400 1,400 115% 115% 689 1,219 RES UNIT- D304 689 1,219 1,400 115% RES UNIT- D305 678 1,192 1,400 117% RES UNIT- D306 924 2,048 2,100 103% HOUSING HOPE we keep hope alive DESIGNS L v northwest ARCHITECTS 360. 629. 3441 P.O. Box 1 27 0 10031 SR 532, Suite B Stanwood, WA 98292 www. designs nw. cont ECOTOPE 1 9 17 1 ST AvE, #300 SEATTLE WA 9B 1 o 1 PH: (206) 322-3753 FAX: (206) 325-7270 W am Cn O �0 07 Z Q O W C' J Liu Z W `_ W Cl) LL W V Q U) O J a c� M N L N 00 CONSTRUCTION DOCUMENTS ISSUE DATE: JAN. 3, 2023 REVISION SCHEDULE Rev # I Date Description RESUB Apr 04 2023 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT inVILINIOLISM ENERGY CODE DOCUMENTATION SCALE: 12" = 1'-0" DRAWN: Author CHECKED: Checker PROJECT NO: 2021031.00 SHEET: ECO,07 1/3/23, 4:37 PM https://waenergycodes.com/print_ project_summary_form.php?k=aWQ9MTMOMzQmZnZpPTE4JmNOaTO=&print=1 LIGHTING COMPLIANCE SUMMARY 2018 WSEC Compliance Forms for Commercial Buildings including Group R2, R3 & R4 over 3 stories and all RI Administered by: ©2023 NF.F.A, All rights reserved Project & Applicant Information Project Title Housing Hope ELC Field Apartments Building ALevel 1-2018WSEC For Building Department Use: Date' Sep 29, 2022 Project Address 8215 236th St SW Edmonds, WA 98026 Applicant Name Shawn Oram Applicant Phone 206-322-3753 Applicant Email I shawn@ecotope.com For questions about this report, contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com General Occupancy All Commercial General Building Use Multifamily/Residential, Mixed Use Building Cond. Floor Area 4,153 Project Cond. Floor Area 4,153 New Building or Interior Lighting Alteration Floors Above Grade 1 General Project Types New Building Addition Parking Garage Lighting Lighting Scope e Compliance Method 1 - Lighting Scope Exterior Lighting Compliance Method General Interior lighting fixtures will be LED. Lighting will be energy efficient and shall be pendant, surface mounted, or recessed. Lighting systems shall be designed to provide illumination levels in Lighting Project Description accordance with the recommendations of the Illuminating Engineering Society (IES), consistent with Energy Code. Exterior lighting systems will be LED type. Lighting systems shall be designed to provide illumination levels in accordance with the recommendations of the Illuminating Engineering Society (IES), consistent with Energy Code. Lighting Compliance anCe Scope Project Type Interior /Exterior (Interior includes both interior &parking) Luminaire Replacement Scope p Compliance Method p LPA Calculation Adjustment Compliance Verification and Method New Building Interior Lighting Space by space Reduced lighting power density option COMPLIES New Building Exterior Lighting Not applicable to exterior COMPLIES Additional Efficiency Options included Reduced lighting power density credit Enhanced lighting controls credit Project Title Housing Hope ELC Field Apartments Building A Level 1 - 2018 WSEC Date Sep 29, 2022 Lighting Power Calculatio NEW BUILDING - INTERIOR LIGHTING Compliance Verification COMPLIES Compliance Method Space by space LPA Calculation Adjustment LPA x 0.8 Interior Lighting Power Allowance - Space by Space General Space Type Specific Space Type Ceiling Height (Ft) Gross Interior Area (SF) LPA (Watts/SF) Total Watts Allowed (SF x LPA x 0.8) Total Proposed Watts (LPD + Display LPD) Compliance Status Conference/meeting/multipurpose 1,211 0.97 1,175 Corridors General 577 0.41 237 Electrical/mechanical 251 0.43 108 Food preparation 136 1.09 148 Office Enclosed less than 250 sf 1,273 0.74 942 Restroom General 153 0.63 96 Storage room General 237 0.38 90 Proposed Total LPD 2154 Totals Calculation Adjustment Applied - LPA x 0.8 1 2,237 2,154 COMPLIES Proposed Lighting Power Density Watts or Total Watts Fixture Type Fixture ID Quantity of Wattage Limit Total Linear Watts per Linear Proposed Fixtures (#F) per Fixture Feet (LF) Foot (WpLF) (#F x WpF) or (WpF) (LF x WpLF) Individual Fixtures Horizontal surface -mount 1 SL-5 1 3 1 30 1 1 90 https://waenergycodes.com/pdnt_project_summaryform.php?k=aWQ9MTMOMzQmZnZpPTE4JmNOaTO=&p(nt=1 1/3 1/3/23, 4:37 PM https://waenergycodes.com/print_ project_summary_form.php?k=aWQ9MTMOMzC)mZnZpPTE4JmNOaTO=&print=1 Horizontal surface -mount SL-4 2 31 62 Troffer RL -2 13 15 195 Troffer RL-1 20 38 760 Suspended PL-1 6 31 186 Suspended PL-2 14 60 840 Under -cabinet UC 11 21 1 1 21 Proposed Total LPD 1 2154 Project Title Housing Hope ELC Field Apartments Building A Lcvel 1 - 2018 WSEC Date Sep 29, 2022 Proposed Fixtures Details NEW BUILDING - INTERIOR LIGHTING Fixture Type/Application Fixture ID Location in Documents Lamp IN pc New or Existing -to -Remain individual Fixtures Horizontal surface -mount SL-5 E2.11 LED New Fixttue Description: LED Surface Mounted fixture Are these fixtures located within a daylight zone?: No Do these fixtures require specific application lighting controls?: None required Horizontal surface -mount SL-4 E2.11 LED New Fixture Description: Surface mount led fixture Are these fixtures located within a daylight zone?: No Do these fixtures require specific application lighting controls?: None required Troll'cr RL-2 I E2.11 LED New Fixture Description: recessed 2X2 flat panel Are these fixtures located within a daylight zone?: No Do these fixtures require specific application lighting controls?: None required Trofl'cr RL-1 I E2.11 LED New Fixture Description: recessed 2x4 basket troffer Are these fixtures located within a daylight zone?: No Do these fixtures require specific application lighting controls?: None required Suspended PL-1 I E2.11 LED New Fixture Description: LED Suspended Mounted fixture Are these fixtures located within a daylight zone?: No Do these fixtures require specific application lighting controls?: None required Suspended PL-2 I E2.11 LED New Fixture Description: Pendant mounted linear fixture, round Are these fixtures located within a daylight zone?: Yes, controls provided Daylight zone location(s): Sidelit daylight zones (primary and/or secondary) Dimming method: Continuous dimming Do these fixtures require specific application lighting controls?: None required Under -cabinet UC I E2.11 LED New Fixture Description: LED undercabinet lighting Are these fixtures located within a daylight zone?: No Do these fixtures require specific application lighting controls?: None required Project Titlel Housing Hope ELC Field Apartments Building A Level 1 - 2018 WSEC Date Sep 29, 2022 Lighting Power Calculation IlEFNEW BUILDING - EXTERIOR LIGHTINCompliance Verification COMPLIES Exterior Lighting Zone ZONE 2 Base Site Allowance 400 Exterior Tradable Lighting Power Allowance Tradable Surface Tradable Surface Sub -Type Surface Area (SF) LPA (Watts/SF) Linear Feet (I.F) LPA (NN'atts/1.F) Total Watts Allowed (LPA x SF) or (LPA x LF) Total Tradable Proposed Watts Tradable Compliance Status Building grounds Walkways 10 feet and wider 366 0.10 37 Building entrances and exits Pedestrian entrances & exits 16 14 224 Uncovered parking areas and drives 1 1 5,357 1 0.04 1 1 214 Base Site Allowance 400 Totals 8751 208 1 COMPLIES https://waenergycodes.com/print_ project_summary_form.php?k=aWQ9MTMOMzQmZnZpPTE4JmNOaTO=&print=1 1/3/23, 4:37 PM https://waenergycodes.com/print_ project_summary_form.php?k=aWQ9MTMOMzQmZnZpPTE4JmNOaTO=&print=1 2/3 Proposed Tradable Lighting Power Density Fixture Type Fixture 1 D Tradable Surface Type Quantity of Fixtures (#F) Watts or Wattage Limit per Fixture (WpF) Total Linear Feet (LF) Watts per Linear Foot (WpLF) Total Watts Proposed (#F x WpF) or (LF x WpLF) Individual Fixtures Wall -mounted WL-3 Building grounds - Walkways 10 feet and wider 17 34 Wall -mounted WL74 Building grounds - Walkways 10 feet and wider 12 12 Wall -mounted WL-4 Building entrances and exits - Pedestrian entrances & exits 12 48 Wall -mounted WL-2 Uncovered parking areas and drives - 38 114 Tradable Proposed Total 208 https://waenergycodes.com/print_ project_summary_form.php?k=aWQ9MTMOMzQmZnZpPTE4JmNOaTO=&print=1 3/3 fffF DB ENGINEERS Travis Fitzmaurice Wartelle Balangue Engineers Inc. 1200 Westlake Ave. N., #509 Seattle, WA 98109 p:206-285-7228 1 info@tf-wb.com HOUSING HOPE we keep hope alive ` DESIGNS L v northwest ARCHITECTS 360. 629.3441 P.O. Bax 1270 10031 SR 532, Suite B Stanwood, WA 98292 www.designsnw.com r c architecture resource I collaborative 119 MAIN ST, STE #200 SEATTLE, WA 98104-2579 (206) 322-3322 1. FITWA L ������� co N CD 00 UU a O z z0 Q Lu W Z LLI co I— C� LL LU M U) V Q O �a Cs') N LLI Q to 00 PERMIT SET ISSUE DATE: SEPTEMBER 2022 REVISION SCHEDULE Rev # Date R R—cwuffl 1 10-19-2022 d S 2 01-25-2o2314pr023 3 03-30-2023 CITY Mnf~Set DEVELOPMENT SERVICES DEPARTMENT CONTENTS: WSEC LIGHTING COMPLIANCE SCALE: As indicated DRAWN: ELIAS CHECKED: MF PROJECT No: 2021031.00 E8.14