Loading...
APPROVED RESUB1 FIR2024-0116+Fire_Sprinkler_Plan+12.17.2024_2.49.41_PM+4674955CLOSETS UNDER 24 S.F. DO NOT REQUIRE PROTECTION PER NFPA-13D 8.3.3, TYP. Approved with Conditions Fire Marshal Chris Burt 12/19/2024 12-19-2024 RESUB 1 PLAN REVIEW NOTES: APPROVED WITH CONDITIONS: 1. Approved set of plans must be on site at the time of inspection. Failure to provide the approved plan may result in a re -inspection fee. System drain(s):. If riser is above lowest grade, 2nd drain required and signage at riser indicating location is required. Systems required signage IAW NFPA 13D. 2. Coverage required to the following areas: Clothes closets, linen closets and pantries exceeding 24 square feet in area, with the smallest dimension greater than T and having wall and ceiling surfaces of gypsum board. Bathrooms more than 55 square feet in area. When fuel fired equipment is present on covered decks or porches, or if living space above, at least one quick -response intermediate temperature sprinkler shall be installed above equipment or area under living space. All fuel fired ON MAIN LEVEL SCALE. 14 1 NOTES REV BY CHK'D DATE DESCRIPTION SPRINK�.ER INFOIRMATION FIRE SPRINKLER HEAD LOCATION MAY VARY FROM PRINT SYM CNT TYPE METAL TEMP K NPT MFG. MODEL# ESCUTCHEON G>N BUT WILL MAINTAIN LISTED HEAD SPACING. 15 PENDENT (14'x14') BRASS 162° 3.7 1/2" SENJU SS8261 CONC. ALL CEILING'S ARE FLAT UNLESS OTHERWISE NOTED © 02 INTER. PENDENT BRASS 205° 4.9 1/2" SENJU SS8464 DUE CARE WILL BE TAKEN TO ENSURE SPRINKLER HEAD 31 PENDENT (16'x16') BRASS 162° 4.9 1/2" SENJU SS8464 CONC. COVERAGE IS NOT OBSTRUCTED BY LIGHTS, FANS, ETC.... OO 01 PENDENT BRASS 360° 5.6 1/2" VIKING VK102 ELECTRICIANS WILL PROVIDE & HOOK UP POWER TO PUMP PLUMBERS WILL PROVIDE WATER FOR THE OPTIONAL AUTOFILL TOTAL HEADS 49 HYDRAULIC NOTES NO. OF SPRINKLERS: DESIGN DENSITY: Q,Qj AREA OF DISCHARGE: 392 S ft SYSTEM DEMAND: 20.0 gpm RESIDUAL PRESSURE ® BASE OF RISER: 16.2 SI CAL C. ST/CKER BATHROOMS UNDER 55 S.F. DO NOT REQUIRE PROTECTION PER O 11 N UPPER LEVEL PLAN SCALE.14 1 0 DESIGNED BY JS WASHINOTON STATE DRAWN BY: ■ DEC 3t, 2a CERTIFICATE OF COMPETENCY III FIRE SPRINKLER SYSTEMS ■ JS iJohn Shakespeare i ■ 7566-0908-A*-H Level 1 � CHECKED BY: j Eclipse Fire Sprinklers, LLC DATE: ECLIPFS783DP 11 /28/24 27 OCT, 2024 signature Date SCALE: `----------------------------A AS SPECIFIED HYDRAULIC NOTES NO. OF SPRINKLERS: DESIGN DENSITY: Q,Qrj AREA OF DISCHARGE: 256 S ft SYSTEM DEMAND: 13.0 gpm RESIDUAL PRESSURE ® BASE OF RISER: 23.3 SI CAL C. 9T/CKER BATHROOMS UNDER 5 S.F. DO NOT REQUIRE PROTECTION PER NFPA-13D 8.3.2, (TYP. F I R2024-0116 PROJECT: Dec 17 2024 EDMONDS RESIDENCE- LOT 1 DE EILOP OF ENDTSOERDVCES DEPARTMENT 7901 - 240TH STREET SOUTHWEST,EDMONDS, WASHINGTON FIRE PROTECTION PLAN JOB# DRAWING SHEET: REV: 1 OF 2 I I I I I I I I I �uI OI T of OI Z� 0.00' ACCESS EASEMEN OI 0) �I I I I I I I I I I L N O SITE PLAN 1" WATEN METER (SOURCE) LOT 2 127.00' S 8935'01" E SCOPE OF WORK LOT 1 - I I 7.50' SY BSBL- � I o PAP to � o° o ��olPo I ° oP PROPOSED ■■ U z �v P 2-CAR LARGE p D �oP�r� °CD o CD° °Oj o "p D PROPOSED DWELLING U w o Z W o ® (BASEMENT S.O.G. = 343.75') - F W/� c J IO m� w T I� � p D to b p ° 1.0" SYSTEM RISER F- 29 O p°D O O I O ILb 0 p� T I p° - N ti CD I ° D D� CONCRETE WALK m° p I D p 31 I I 50'-O" I _ 7.50' SY BSBL I I 127.00' N 8F35'01" W ELEVATION DRAWING N scale 1 /411 = 1 1-0.I NALL 1 �1 NOTES FIRE SPRINKLER HEAD LOCATION MAY VARY FROM PRINT BUT WILL MAINTAIN LISTED HEAD SPACING, CEILING'S ARE FLAT UNLESS OTHERWISE NOTED DUE CARE WILL BE TAKEN TO ENSURE SPRINKLER HEAD COVERAGE IS NOT OBSTRUCTED BY LIGHTS, FANS, ETC.... ELECTRICIANS WILL PROVIDE & HOOK UP POWER TO PUMP PLUMBERS WILL PROVIDE WATER FOR THE OPTIONAL AUTOFILL :01:01:01 REV I BY ICHK'D I DATE I DESCRIPTION S PRINK�.ER INFORMATION SYM CNT TYPE METAL TEMP K NPT MFG. MODEL# ESCUTCHEON 15 PENDENT(14'x14') BRASS 162° 3.7 1/2" SENJU SS8261 CONC. O 02 INTER. PENDENT BRASS 205' 4.9 1/2" SENJU SS8464 @ 31 PENDENT(16'x16') BRASS 162° 4.9 1/2" SENJU SS8464 CONC. OO 01 PENDENT BRASS 360° 5.6 1/2" VIKING VK102 TOTAL HEADS 49 RISER SCHEMATIC J WASHINGTON STATE u�Eca,l,y� CERTIFICATE OF COMPETENCY FIRE SPRINKLER SYSTEMS John Shakespeare i 7566-0908-A*-H Level 1 i Eclipse Fire Sprinklers, LLC - ; ECLIPFS783DP 11 /28/24 ii�aAllr Date j FLOW TEST SUMMARY HEAD LAYOUT MAY BE DIFFERENT THEN PRINT Static 65 PSI Residual 20 PSI DUE TO LIGHT AND/OR HEAT REGISTER Flow 2000 GPM LOCATIONS BUT WILL MAINTAIN LISTED HEAD SPACINGS FIRE SUPPRESSION DESIGN NOTES 1. CODES, STANDARDS AND APPROVALS DESIGN, INSTALLATION, AND TESTING SHALL CONFORM TO THE FOLLOWING 1.1 NFPA-13D -EDITION 2016 1.2 NATIONAL FIRE PROTECTION ASSOCIATION #13D 2.0 DESCRIPTION OF WORK THE FOLLOWING FIRE PROTECTION SYSTEMS ARE INCLUDED IN THIS SECTION OF 2.1 NEW WET SPRINKLER SYSTEM 2.2 RESIDENTIAL LEVEL'S DESIGN DENSITY OF 0.05 USGPM/SQFT 1 HEAD CALC 13 GPM PER HEAD DESIGN DENSITY OF 0.05 USGPM/SQFT 2 HEAD CALC 10 GPM PER HEAD 3.0 PUMP SUPPLY INFORMATION STATIC PRESSURE: 65 PSI RESIDUAL PRESSURE: 20 PSI @ 2000 USGPM 4.0 MATERIALS & EQUIPMENT ALL FIRE PROTECTION MATERIALS AND EQUIPMENT INSTALLED AS PART OF THIS CONTRACT SHALL BE BE CUL LISTED AND FULLY CONFORM TO NFPA STANDARDS 4.1 CPVC FOR SIZES 3/4" - 2" UNLESS NOTED FITTING'S GLUED OR GROOVED 4.2 HANGERS AND SUPPORTS ALL HANGERS AND SUPPORTS SHALL BE CUL LISTED FOR FIRE PROTECTION USE AND MEET THE NFPA REQUIREMENTS. ALL HANGER AND SUPPORTS TO BE INSTALLED IN ACCORDANCE WITH NFPA AND THE MANUFACTURER'S SPECIFICATIONS. 5.0 DESIGN STANDARDS 1. BATHROOMS UNDER 55 S.F DO NOT REQUIRE PROTECTION PER NFPA-13D 8.2.3. 2. CLOSETS UNDER 24 S.F DO NOT REQUIRE PROTECTION PER NFPA-13D 8.3.3. 3. SPRINKLERS ARE SPACED TO A MAX OF 16'x16' (256 SQ.FT.) 14'X14' (196 SQFT) 4. SPRINKLERS SHALL NOT BE REQUIRED IN ATTICS WITH OR WITHOUT L STORAGE PER NFPA-13D 8.3.5. '5)AFCON 515 DOUBLE OFFSET HANGER HARDENED HEX HEAD SELF THREADING SCREW IS FURNISHED WITH THE HANGER. ;0 #2530180 OFFSET CPVC HANGER HARDENED HEX HEAD SELF THREADING SCREW IS FURNISHED WITH THE HANGER. HANGER DETAILS N.T.S AF�A SU BASEMENT LEVEL MAIN LEVEL UPPER LEVEL TOTAL AREA GARAGE PORCH & DECKS m m C P-"Y HEX HEAD SELF TAPPING SCREW CPVC DOUBLE FASTENER STRA TOLCO FIG. #24 ---=Cdo - �0 HARDENED HEX HEAD SELF THREADING SCREW IS FURNISHED WITH THE HANGER. INSULATION CVPC PIPE BY OTHERS STAPLE tvLAIR A 71QM)'� - (UPPER FLOOR ONLY) L CLILING INSULATION DETAIL N.T.S 1973.00 sq F 1635.00 sq F 1877.00 sq F 5485.00 sq F 462.00 sq F 40.00 sq F HYDRAULIC CALCULATION SUMMARY CALCULATED DENSITY LOCATION REQ'D FLOW AT REQ'D PRESSURE EXCESS RESIDUAL AREA USGPM/SQ.FT. INFLOW NODE AT INFLOW NODE AT INFLOW NODE SAFETY FACTOR (14' X 14') L.H 0.05 USGPM/SQ.FT. 12 HEAD CALC UPPER FLOOR 20.0 US GPM 48.8 PSI 16.2 PSI 24.92 (16' X 16') L.H 0.05 USGPM/SQ.FT. 11 HEAD CALC UPPER FLOOR 13.0 US GPM 41.7 PSI 23.3 PSI ECLIPSE FIRE SPRINKLERS, LLC 111 8TH AVE N ALGONA, WA 98001 HELLOGECLIPSEFIRE.CONI E 206- 74 7-3105 16 RESUB DESIGNED BY PROJECT: Dec 17 2024 EDMONDS RESIDENCE- LOT 1 DE EILOP OF END SORD CES DRAWN BY: DEPARTMENT CHECKED BY: 7901 - 240TH STREET SOUTHWEST,EDMONDS, WASHINGTON DATE: 27 OCT, 2024 SCALE: AS SPECIFIEI JOB# FIRE PROTECTION PLAN DRAWING SHEET: REV: 20F2