APPROVED RESUB1 FIR2024-0119+Fire_Sprinkler_Plan+12.17.2024_2.50.25_PM+4674960BATHROOMS UNDER 55
S.F. DO NOT RE UIRE
PROTECTION PER
",
��
•
a
////
/ /////I
���•
I
r.•
IS
• _
-61-011
EXERCISE
C
.1'
M
�p Pgp�E
1
10'-3" 1 6'-5" 2'-
BASEMENT LEVEL PLAN
SCALE. 1/4 - 1-0
CLOSETS UNDER 24
S.F. DO NOT REQUIRE
PROTECTION PER
NFPA-13D 8.3.3. TYP.
CALC. 877 t`HR
BATH ROO1
S.F. DO NO
PROTECTI(
NFPA-13D
CLOSETS UNDER 24
S.F. DO NOT REQUIF
PROTECTION PER
NFPA-13D 8.3.3. TYP
N9?5? FIX/FIX/CAS
6 UPPER LEVEL PLAN
BATH ROON
S.F. DO NO'
PROTECTIC
NFPA-13D
TEST HEAD
mi -
IuFill 1100wimm0Ii\\
DESIGN DENSITY:I
CALC, S170rHR
BATHROOMS UNDER 55
S.F. DO NOT REQUIRE
PROTECTION PER
BATHROOMS UNDER 55
S.F. DO NOT REQUIRE
PROTECTION PER
N
O
NOTES
J��
REV
BY
CHK'D
DATE
DESCRIPTION
SPRINKLER INFORMATION
'---- -- -�
ECLIPSE FIRE SPRI\KLERS, LLC
It 1 8TH AX7 E \ ALGO\ A, WA 98001
= . HELLOGECLIPSEFIRE.CONI
ECLIPSE O 6 - ! (- 31 O:�
,..�,�
DESIGNED BY
is
PROJEC
7905 -
FIRE SPRINKLER HEAD LOCATION MAY VARY FROM PRINT
SYM CNT
TYPE
METAL
TEMP
K
NPT
MFG.
MODEL#
ESCUTCHEON
DRAWfJRY:
BUT WILL MAINTAIN LISTED HEAD SPACING.
14
PENDENT(14'x14')
BRASS
162°
3.7
1/2"
SENJU
SS8261
CONC.
ALL CEILING'S ARE FLAT UNLESS OTHERWISE NOTED
CHECKED BY:
DATE:
27 OCT, 2024
O
02
INTER. PENDENT
BRASS
205°
4.9
1/2"
SENJU
SS8464
DUE CARE WILL BE TAKEN TO ENSURE SPRINKLER HEAD
31
PENDENT(16'x16')
BRASS
162'
4.9
1/2"
SENJU
SS8464
CONC.
COVERAGE IS NOT OBSTRUCTED BY LIGHTS, FANS, ETC....
C
r
O
01
PENDENT
BRASS
360'
5.6
1/2"
VIKING
VK102
ELECTRICIANS WILL PROVIDE & HOOK UP POWER TO PUMP
PLUMBERS WILL PROVIDE WATER FOR THE OPTIONAL AUTOFILL
TOTAL HEADS 48
SCALE:
AS SPECIFIED
T:
EDMONDS RESIDENCE LOT- 2
240TH STREET SOUTHWEST, EDMONDS, WASHINGTON
JOB# DRAWING SHEET:
'IRE PROTECTION 1 OF 2
PLAN
5)AFCON 515 DOUBLE OFFSET HANGER
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER.
-0 #2530180 OFFSET CPVC HANGER
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER.
HANGER DETAILS
N.T.S
I
I
I
I
I
I
I
1
1
I
01
OI
01
Cn I
of
LbI
�I
I
I
I
I
I
I
I
I
I
HEX HEAD SELF
TAPPING SCREW
CPVC DOUBLE FASTENER STRA
TOLCO FIG. #24
do 0
HARDENED HEX HEAD SELF THREADING SCREW
IS FURNISHED WITH THE HANGER.
INSULATION CVPC PIPE
BY OTHERS
STAPLE
>I
LAIR GX�y
(UPPER FLOOR ONLY) L CEILING
INSULATION DETAIL
N.T.S
AI� A 5 U M M P,,, Y
BASEMENT LEVEL
MAIN LEVEL
UPPER LEVEL
TOTAL AREA
GARAGE
PORCH & DECKS
1931.00
sqF
1533.00
sqF
1 41 6.00
sq
F
4880.00
sqF
462.00
sq
F
377.00
sqF
HYDRAULIC CALCULATION SUMMARY
CALCULATED
DENSITY
LOCATION
REl'D FLOW AT
REQ'D PRESSURE
EXCESS RESIDUAL
AREA
USGPM/SQ.FT.
INFLOW NODE
AT INFLOW NODE
AT INFLOW NODE
SAFETY FACTOR
(14' X 14')
L.H 0.05 USGPM/SQ.FT. / 2 HEAD CALC
UPPER FLOOR
20.0 US GPM
49.2 PSI
15.8 PSI
24.30 %
(16' X 16')
L.H 0.05 USGPM/SQ.FT. / 1 HEAD CALC
UPPER FLOOR
13.0 US GPM
42.8 PSI
22.2 PSI
34.15%
_� __ __ __ 127.00' N88031'13 W
FIRE APPARATUS TURN -AROUND
- SOOPFrOEJI1LORK 7.50' SY BS
42" C
GRASS FLOW PATH
12" TRENCH DRAIN
0.00' ACCESS EASEMEN
(SOURCE)
127.00' S 8803113" E
N
SITE PLAN
scale 1/ 99 ] 9 O"
ROOF LEVEL RIDGE EL374.17'
UPPER LEVEL PLATE El 3.14'
UPPER LEVEL FLOOR 516:4.04'
MAIN LEVEL PLATE EL363.00'
MAIN LEVEL FLOOR EL353.90'
BASEMENT PLATE EL:352.84'
AVERAGE GRADE EL: 350.52'
BASEMENT FLOOR EL:343.7�_ -
N
6 ELEVATION DRAWING
scale 1/419 = 19-099
NOTES
N FIRE SPRINKLER HEAD LOCATION MAY VARY FROM PRINT
BUT WILL MAINTAIN LISTED HEAD SPACING,
ALL CEILING'S ARE FLAT UNLESS OTHERWISE NOTED
O DUE CARE WILL BE TAKEN TO ENSURE SPRINKLER HEAD
COVERAGE IS NOT OBSTRUCTED BY LIGHTS, FANS, ETC....
ELECTRICIANS WILL PROVIDE & HOOK UP POWER TO PUMP
PLUMBERS WILL PROVIDE WATER FOR THE OPTIONAL AUTOFILL
REV I BY ICHK'D I DATE I DESCRIPTION
S P RINUE R INFORMATION
SYM CNT
TYPE
METAL
TEMP
K
NPT
MFG.
MODEL#
ESCUTCHEON
14
PENDENT (14'x14')
BRASS
162'
3.7
1/2"
SENJU
SS8261
CONC.
O
02
INTER. PENDENT
BRASS
205'
4.9
1/2"
SENJU
SS8464
31
PENDENT (16'x16')
BRASS
162'
4.9
1/2"
SENJU
SS8464
CONC.
OO
01
PENDENT
BRASS
360°
5.6
1/2"
VIKING
VK102
rn
rn
rn
FLOW TEST SUMMARY
HEAD LAYOUT MAY BE
Static 65 PSI DIFFERENT THEN PRINT
Residual 20 PSI DUE TO LIGHT AND/OR
HEAT REGISTER
Flow 2000 GPM LOCATIONS BUT WILL
MAINTAIN LISTED
HEAD SPACINGS
FIRE SUPPRESSION DESIGN NOTES
1. CODES, STANDARDS AND APPROVALS
DESIGN, INSTALLATION, AND TESTING SHALL CONFORM TO THE FOLLOWING
1.1 NFPA-13D -EDITION 2016
1.2 NATIONAL FIRE PROTECTION ASSOCIATION # 13D
2.0 DESCRIPTION OF WORK
THE FOLLOWING FIRE PROTECTION SYSTEMS ARE INCLUDED IN THIS SECTION OF
2.1 NEW WET SPRINKLER SYSTEM
2.2 RESIDENTIAL LEVEL'S
DESIGN DENSITY OF 0.05 USGPM/SQFT 1 HEAD CALC 13 GPM PER HEAD
DESIGN DENSITY OF 0.05 USGPM/SQFT 2 HEAD CALC 10 GPM PER HEAD
3.0 PUMP SUPPLY INFORMATION
STATIC PRESSURE: 65 PSI
RESIDUAL PRESSURE: 20 PSI @ 2000 USGPM
4.0 MATERIALS & EQUIPMENT
ALL FIRE PROTECTION MATERIALS AND EQUIPMENT INSTALLED AS PART OF THIS
CONTRACT SHALL BE BE CUL LISTED AND FULLY CONFORM TO NFPA STANDARDS
4.1 CPVC FOR SIZES
3/4" - 2" UNLESS NOTED
FITTING'S GLUED OR GROOVED
4.2 HANGERS AND SUPPORTS
ALL HANGERS AND SUPPORTS SHALL BE CUL LISTED FOR FIRE PROTECTION USE
AND MEET THE NFPA REQUIREMENTS. ALL HANGER AND SUPPORTS TO BE
INSTALLED IN ACCORDANCE WITH NFPA AND THE MANUFACTURER'S
SPECIFICATIONS.
5.0 DESIGN STANDARDS
1. BATHROOMS UNDER 55 S.F DO NOT REQUIRE PROTECTION PER NFPA-13D 8.23.
2. CLOSETS UNDER 24 S.F DO NOT REQUIRE PROTECTION PER NFPA-13D 8.3.3.
3. SPRINKLERS ARE SPACED TO A MAX OF 16'x16' (256 SQ.FT.) 14'X14' (196 SQ.FT)
4. SPRINKLERS SHALL NOT BE REQUIRED IN ATTICS WITH OR WITHOUT
STORAGE PER NFPA-13D 83.5.
7-
ICPVC TO UPPER LEVEL
/ I" CPVC TO MAIN LEVEL
RISER SCHEMATIC
DESIGNED BYt PROJECT:
TOTAL HEADS 48
EDMONDS RESIDENCE LOT- 2
DRAWN BY:
CHECKED BY: 7905 - 240TH STREET SOUTHWEST,EDMONDS, WASHINGTON
DATE:
27 DATE:
2024 JOB# DRAWING SHEET: REV:
SCALE: FIRE PROTECTION 2 OF 2
AS SPECIFIED PLAN