FIR2024-0117+Fire_Sprinkler_Equipment_Specification_Sheets+12.3.2024_3.41.25_PM+4650491RECEIVED FIR2024-0117 Dec 04 2024 CITY OF EDMONDS DEVELOPMENT SERVICES DEPARTMENT s - t GENERAL DESCRIPTION Senju Sprinkler Model RC-RES K-Factor: 4.9 SIN: SS8464 Residential Lead Free Flat Concealed Sprinkler, Pendent C &US LISTED I NSF/ANSI/(AN 61 &372 EU O's The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. They are decorative and fast responding. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc., which is concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The push -on and/or thread -on, thread -off design of the concealed cover plate assembly allows for easy installation of the cover plate. Therefore, the Model RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and unbeatable performance is desired. The Model RC-RES is designed for residential occupancies and is perfect for use in homes, hotels and other living quarters. The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13. The Model RC-RES has a 4.9 (70.6 LPM/bar12) K-factor that meets the required residential flow rates with minimal residual pressure, which allows for smaller pipe sizes and water supply requirements. For extended installation flexibility, the Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of pipe lengths. The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents to escape or evacuate in case of a fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes. "Lead Free" is defined in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA's Water Utility Council, and California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of pipes, plumbing fittings and fixtures. www.senjusprinkler.com Page 1 of 8 Document No.U085168 • 02-08-2021 WARNINGS The Model RC-RES must be installed and maintained in accordance with the rules stated herein as well as in compliance with the applicable standards of the National Fire Protection Association regulations and the standards of any other authorities having jurisdiction. In the event of this condition, consult the authorities having jurisdiction for guidance and approval. Failure to do so may impair the integrity of these devices. It is the responsibility of the installing contractor to provide a copy of this document to the owner or their representative, and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any related questions. TECHNICAL DATA • Approvals: 0 cULus Listed • UL-EU Listed (162°F (72°C) only) • NSF/ANSI/CAN 61, NSF/ANSI 372 • Sprinkler Identification Number (SIN): SS8464 • Maximum Working Pressure: 175psi (12.1bar) • Discharge Coefficient (Nominal K-Factor): 0 K = 4.9 GPM/psi1/2 (70.6 LPM/bars/2) • Temperature Rating: • 162°F (72°C) Sprinkler with 140°F (60°C) Cover Plate • 205°F (96°C) Sprinkler with 162°F (72°C) Cover Plate • Color Code (Sprinkler) • 162°F (720C): Uncolored • 205OF (96°C): White • Color Code (Cover Plate) • 140°F (60°C): No Mark • 162°F (72°C): White -Colored Mark • Vertical Adjustment: 1/2 inch (12.8 mm) • Cover Plate Finishes: 0 Standard Finishes: White, Ivory, Beige, Brown, Black, Nickel, Wood Grain o Custom Finishes: Custom color and custom pattern cover plates are available on special order. Contact a Senju Sprinkler representative with any custom orders. Please see chart on Page 8 for more detail. • Physical Characteristics: Ref. Figures 1 and 1.1 2-1/16" (652mm) a Lot No. Year of Manufacture SIN: SS8464 1-K-Factor: K4.9 4 Temperature Rating: 162°F/72 °C s or 205'F/96 °C z UL Mark B Control No: 6P37 ALS Mark: NSF 61/372 RES SPKR T Body (Copper Alloy) Deflector (Phosphorus Bronze) Gasket 2-518" (068mm) Meta,(PTF( a Fusible Metal (Solder) or 3-1/4" (083mm) s Heat Collector (Copper) or 2-5/8" square (o68mm 6 Cover Plate Assembly Figure 1: Model RC-RES K = 4.9 Marking (Deflector) Cover Plate Sprinkler (Top View) (Bottom View) Figure 1.1: Marking (Color Code) Ling: 162°F/72 °C or 205 °F/96 °C www.senjusprinkier.com Page 2 of 8 Document No.U085168 • 02-08-2021 OPERATION In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then the Cover Plate is released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and when sufficient heat from the fire is reached, internal components of the sprinkler fall apart. This leads to the water flow to be distributed on the affected fire area. (Ref. Figure 2) y Normal Condition Cover Plate Operation Sprinkler Operation Water Discharge Figure 2: Operation Process (For illustrative purposes only) DESIGN CRITERIA The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly implemented for safe and full results. Notes Residential Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar with automatic sprinkler system design, installation procedures, and techniques. Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the sprinkler system designer review and develop a working understanding of the complete list of criteria prior to initiating the design of the sprinkler system. Questions concerning sprinkler installation and usage criteria, which are not covered by the following instructions, should be submitted to your contracted company. Include sketches and technical details, as appropriate. In some instances, the requirements of this document may concern specifications which are more stringent, and which take precedence over those specified in NFPA 13, 13D, 13R, or by the authority having jurisdiction. The Model RC-RES must not be used in applications where the air pressure above the ceiling is greater than that below. Inspect all sprinklers after installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the cup are open and free from any air flow impediment. The spray from the sprinkler is distributed radially outward and downward from the sprinkler deflector. Consequently, the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers, overhangs or other parts of the dwelling structure. The number of sprinklers within each compartment (as defined by NFPA 13D, 13R, or 13) must be kept as few as possible while observing all guidelines relating to obstructions and spacing. Use only the Cover Plate provided for the Model RC-RES. The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces resulting from sprinkler operation could alter its orientation and its water distribution pattern. www.senjusprinkler.com Page 3 of 8 Document No.U085168 • 02-08-2021 Obstruction to Water Distribution Locations of sprinklers must follow the obstruction rules of NFPA 13, 13D and 13R for Residential Sprinklers. General Service Conditions The Model RC-RES must only be utilized in WET PIPE sprinkler systems. Heat Source Criteria Refer to NFPA 13D, 13R or 13 for the requirements relating to the prevention of possible activation of the Heat Responsive Element of Model RC-RES, due to the exposure of a heat source other than an actual fire. Precautionary Warnings for Corrosive Environments Model RC-RES sprinklers should not be installed where they may be subjected to a corrosive environment including the following: 1. Chlorine ion and Chloride environment Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this environment may result in sprinklers operating under Non -Fire conditions or Not Operating when exposed to an actual fire. 2. Sprinkler system piping with Copper Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for copper piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA (Copper Development Association) — Solder Joint) All residual flux must be removed from the interior and exterior of the copper piping by thoroughly flushing before installation of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and/or leakage in the sprinkler system. Hydraulic Design Criteria The minimum required sprinkler flow rates for systems designed to NFPA 13D or 13R are given in Table A as a function of temperature rating and the maximum allowable coverage area. The sprinkler flow rate is the minimum required discharge from the most hydraulically demanding sprinkler from each of the total number of "design sprinklers" as specified in NFPA 13D or 13R. For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Table A for NFPA 13D and 13R as a function of temperature rating and maximum allowable coverage area. • A minimum discharge of 0.1GPM/sq.ft. [4.07LPM/sq.m] over the "design area" comprised of the four most hydraulically demanding sprinklers for the actual coverage area being protected by the four sprinklers. www.senjusprinkler.com Page 4 of 8 Document No.U085168 • 02-08-2021 Table A. NFPA 13D & 13P Wet Pipe Hydraulic Design Criteria for Model SS8464 For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R or 13 as applicable. Maximum Maximum Ordinary Temperature Intermediate Temperature Coverage Rating 1620F (72°C) Rating 205`F (96°C) Minimum Area(a) Spacing Deflector to Installation Spacing Flow(b)GPM Pressure" Flow(b)GPM Pressure" Ft. x Ft. Ft. Ceiling 9 T Type Ft. (m) (m x m) (m) (LPM) PSI (bar) (LPM) PSI (bar) 12 x 12 12 13 7.0 13 7.0 Smooth (3.7 x 3.7) (3.7) (49.2) (0.48) (49.2) (0.48) Ceilings 3/8 to 7/8 Inches. 14 x 14 14 13 7.0 13 7.0 (4.3 x 4.3) (4.3) (49.2) (0.48) (49.2) (0.48) Beamed Ceilings per 16 x 16 16 13 7.0 13 7.0 NFPA 13D, Concealed 8 (4.9 x 4.9) (4.9) (49.2) (0.48) (49.2) (0.48) 13R or 13. Installed in (2.4) 18 x 18 18 17 12.0 17 12.0 (5.5 x 5.5) (5.5) (64.4) (0.83) (64.4) (0.83) beam 3/8 to 7/8 inches below bottom 20 x 20 20 21 18.4 21 18.4 (6.1 x 6.1) (6.1) (79.5) (1.27) (79.5) (1.27) of beam. a. For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the Next Higher Coverage Area listed. b. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details. Sprinkler Spacing Criteria The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond the coverage area calculated by using the specific hydraulic factors. (Ref. Table A) INSTALLATION The Model RC-RES must be installed in accordance with the following instructions: NOTES Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers which show deformation or cracking in either the Sprinkler or the Protective Cap. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to the sprinklers that could cause improper operation or non -operation. The Protective Cap must remain on the sprinkler during installation. After the installation is completed, the Protective Cap must be removed to place the sprinkler in service. Use a torque of 7 to 14 ft•lbs (9.5 to 19.0 N•m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended maximum torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler. Use only NR-H model wrench socket for installation of RC-RES sprinklers. Use of any other wrench or socket is prohibited and may cause damage to the sprinkler. In case of insufficient adjustment in Cover Plate installation, do not try to overly tighten, screw the sprinkler too loosely or make any modification to the cover plate assembly. Readjust the sprinkler fitting for a better fit. Do not rotate the Cap Removal Tool for RC to the left with force when placing the two hook arms into place. The installed sprinkler may become loosened, which may cause water leakage. www.senjusprinkler.com Page 5 of 8 Document No.U085168 • 02-08-2021 Spears® Technical Information 09-Dec-23 02:40:28 PM Part No: 4206-010 F1ameGuard® Elbow Desc: 1 CPVC FLAMEGUARD 90 ELL SOC MSRP: 8.84 Part Code: 070 Weight(lbs):0.121 Weight(kg):0.055 Weight(gm):55 Size: 1" Color: ORANGE Material: CPVC Connection Socket x Socket (90°) Type Standard G = 3/4 H = 1- 5/8 M = 1- 5/8 Iniection Molded Dimension References: G = (LAYING LENGTH) intersection of center lines to bottom of socket/thread; 90' elbows, tees, crosses; f 1/32 inch. H = Intersection of center lines to face of fitting; 90' elbows tees, crosses; f 1/32 inch. J = Intersection of center lines to bottom of socket/thread; 45' elbows; f 1/32 inch L = Overall length of fittings; f 1/16 inch. M = Outside diameter of socket/thread hub; f 1/16 inch. N = Socket bottom to socket bottom; couplings; f 1/16 inch. W = Height of cap; f 1/16 inch Typical Molded Dimension References The information printed here is based on current information & product design at the time of publication and is subject to change without notification. Spears® ongoing commitment to product improvement may result in some variation. No representation, guarantees or warranties of any kind are as to its accuracy, suitability for particular application or results to be obtained thereform. For verification of technical data or additional information, please contact Spears® Technical Service Department:: WEST COAST: (818) 364-1611 - EAST COAST: (717) 938-9006 (E)POTTER A The Symbol of Protection Features • Pre -assembled and pressure tested • Available in 1",1 1/4", 1 1/2", & 2" nominal pipe size models • Female adapter ships loose so riser can be installed in a confined space • Fits in standard 2X4 construction walls • Includes 3 way valve to allow for calibration of pressure gauge AWARNING • Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious injury or death could result. • Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. Description The RD13 Riser (with NPT connectors) is constructed from Listed CPVC products suitable for fire sprinkler services subject to the limitations and installation requirements of Flameguard® CPVC pipe and Spears® CPVC fittings. The RD13 Riser incorporates a VSR-SG flow switch, gauge, and drain/test valve. The VSR-SG flow switch is equipped with union connection to facilitate the installation and removal of the switch in confined spaces. Installation 1. Using appropriate sealant, thread the female adapter on to the main water supply. Then glue the riser assembly to the female adapter. Pipe the drain connection to an adequate drain location capable of handling the drain discharge. The riser can be mounted in the horizontal or vertical position. Direction of flow is indicated in Fig. 1. The waterflow switch must be located on the top or on the side of the pipe when installed in the horizontal position. This will prevent debris from entering the throat of the waterflow switch which could interfere with proper operation. 2. Following CPVC manufacturer's instructions for preparation and gluing of CPVC piping systems, glue the main riser to the main supply line for the sprinkler heads. NOTE. All glued connections must be completed and cured before the flowswitch is installed. (Continued on page 2). A CAUTION Do nrmayause e union nut, hand tighten only. Use of a wrenma damageto the union nut. RD13 Residential Riser FLOW SWITCH OPTIONAL Flow Switch Technical Specifications Dimensions See Fig 2 Service Pressure 175 PSI (12,07 BAR) Flow Sensitivity 4-10 GPM (15-38 LPM) - UL Range for Signal Maximum Surge 18 FPS (5.5 m/s) Two sets of SPDT (Form C) Contact Ratings 10.0Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 m Amps min. at 24V DC Resistive Environmental Temperature range: 40°F-120°F (4.5°C-49°C) Limitations Conduit Entrances Two knockouts provided for 1/2" conduit Specifications subject to change without notice Service Use Automatic Sprinkler NFPA- 13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 British Standard BS9251 Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com 5401152 - REV M • 6/20 PAGE 1 OF 3 (E)POTTER The Symbol of Protection Installation (Continued) RD13 Residential Riser 3. A thread sealant shall be used in making threaded connections. Teflon® thread tape is the recommended sealant. Some thread sealants other than Teflon thread tape contain solvents or other materials that may be damaging to CPVC. For other types of thread sealants, which have been specifically investigated and confirmed to be "System Compatible", refer to www.spearsmfg.com. Attach gauge to riser. Apply Teflon® tape to male fitting of gauge only. See Fig 1. 4. Check to make sure the proper paddle is installed on the switch. (Paddle size must match the riser pipe size and Tee manufacture.) 5. Install the flow switch to the RD13 Riser. Verify that the o-ring is properly positioned in its groove. Hand tighten the nut to the union after orienting the flow switch in the appropriate direction to detect waterflow. The paddle must not rub the inside of the Tee or bind in any way. The stem should move freely when operated by hand. See Fig. 1. NOTE. Do not leave switch cover off for an extended period of time. 6. The side of flow switch must be perpendicular with the riser piping. See Fig. 3. Testing The frequency of inspection and testing for the Model VSR-SG and its associated protective monitoring system, should be in accordance with applicable Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently.) If provided, the inspector's test valve (usually located at the end of the most remote branch line) should be used for test purposes. If there is no remote inspection test connection; a short length of hose may be connected to the discharge of the 1" drain line valve, or if the drain line is connected to a drain such as a slop sink or storm drain that will sufficiently handle the discharge of the main drain valve. The drain valve can be used to test the operation of the VSR-SG switch. A minimum flow of 10 GPM (38 LPM) is required to activate this switch. An orifice equal to the smallest sprinkler head orifice used in the system shall be attached to the drain line for testing purposes. Maintenance The VSR-SG waterflow switch should provide years of trouble -free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock number 1029030. There is no maintenance required, only periodic testing and inspection.. Removal • To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector, then disconnect wiring. • Loosen nut on union fitting. • Lift detector clear of pipe. Fig I Optional Cover Tamper Retard Adjustment Switch The delay can be adjusted by rotating the retard adjustment knob from 0 to the max setting (60-90 seconds). The time delay should be set at the DO NOT LEAVE minimum required to prevent false alarms. Retard COVER OFF ?� Adjusting —► FOR EXTENDED Knob PERIOD OF TIME Mount so arrow on base points WA ERFOLOWOF ® in direction of \ waterflow 0 1" Male 0 Fitting on DWO, #1063-3 All Sizes Riser may Important: be 1", 1/4", The paddles have raised lettering that show the pipe size and the TEE 1 1/2", or 2" manufacturer they are to be used with. The proper paddle must be used. The paddle must be properly attached and the screw that holds the paddle must be securely tightened. Kati 0 Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com 5401152 - REV M • 6/20 PAGE 2 OF 3 (E)POTTER RD 13 The Symbol of Protection Residential Riser Dimensions (See Chart Below) Fig 2 T NPT Adaptor (Shipped Loose) Orientation Fig 3 3 1/2" Gauge (Shipped Loose) 1" NPT — Drain Valve A CAUTION Flow switch must be properly orientated. Side of cover must be perpendicular with the pipe. Improper orientation could delay or prevent notification of waterfiow. *RD13 Risers (ASSEMBLED DIMENSIONS) Riser Size Model Number Part Number Dimension "A" Dimension `B" Dimension "C' Dimension "D" Dimension "E" Dimension "F" (in) (mm) (in) (mm) (in) (mm.) (in.) (mm) (in) (mm) (in) (mm) 1" RD13-100-1 1119067 19 483 15 3/4 400 18 457 14 5/8 371 12 1/4 311 10 1/2 267 1 1/4" RD13-125-1 1119077 19 5/8 498 16 1/2 419 18 1/2 470 15 3/8 391 12 1/2 318 10 5/8 270 1 1/2" RD13-150-1 1119087 N/A N/A 16 3/4 425 N/A N/A 15 5/8 397 12 3/4 324 10 3/4 273 2" RD13-200-1 1119097 N/A N/A 18 1/4 464 1 N/A I N/A 116 7/8 1429 13 3/8 340 11 1/8 1 283 Ordering Information Ordering Information Nominal Pipe Size Model Part Number 1" RD13 Riser 1119067 1 1/4" RD13 Riser 1119077 1 1/2" RD13 Riser 1119087 2" RD 13 Riser 1119097 Optional: Cover Tamper Switch Kit, stock no. 0090148 Replaceable Components: Retard/Switch Assembly, stock no. 1029030 Replacement VSR-G, stock no. 1144460 Gauge, Flow Switch, and NPT Adapter shipped loose in box. Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com [so sooi:z01s DESIGNING, MANUFACTURING, & DISTRIBUTING QUALITY SYSTEMS 5401152 - REV M • 6/20 PAGE 3 of 3 Spears® Technical Information 09-Dec-23 02:30:47 PM Part No: CP-007 Pipe F1ameGuard(k Pipe SDR 13.5 Desc: 3/4 FIRE SPRINKLER PIPE (15 FT.LENGTH) MSRP: 2.52 Part Code: 071 Weight(lbs):0.17 Weight(kg):0.077 Weight(gm):77 Size: 3/4" Color: ORANGE Material: CPVC Connection 15 Foot Length 11 - - L -------- 0-I Wall Thickness L = 180 AVG.O. = 1.050 Minimu = .078 D. m Wall Typical Pipe Dimension Reference I� L �I 0.D. Wall Thickness The information printed here is based on current information & product design at the time of publication and is subject to change without notification. Spears® ongoing commitment to product improvement may result in some variation. No representation, guarantees or warranties of any kind are as to its accuracy, suitability for particular application or results to be obtained thereform. For verification of technical data or additional information, please contact Spears® Technical Service Department:: WEST COAST: (818) 364-1611 - EAST COAST: (717) 938-9006 Spears® Technical Information 09-Dec-23 02:40:03 PM Part No: 4201-010 F1ameGuard® Tee Desc: 1 CPVC FLAMEGUARD TEE SOC MSRP: 10.94 Part Code: 070 Weight(lbs): 0.198 Weight(kg): 0.09 Weight(gm): 90 Size: 1" Color: ORANGE Material: CPVC Connection Socket x Socket x Socket Type Standard I -- L 10 G = 7/8 H = 1-13/16 L = 3- 5/8 M = 1- 5/8 Iniection Molded Dimension References: G = (LAYING LENGTH) intersection of center lines to bottom of socket/thread; 90' elbows, tees, crosses; f 1/32 inch. H = Intersection of center lines to face of fitting; 90' elbows tees, crosses; f 1/32 inch. J = Intersection of center lines to bottom of socket/thread; 45' elbows; f 1/32 inch L = Overall length of fittings; f 1/16 inch. M = Outside diameter of socket/thread hub; f 1/16 inch. N = Socket bottom to socket bottom; couplings; f 1/16 inch. W = Height of cap; f 1/16 inch Typical Molded Dimension References The information printed here is based on current information & product design at the time of publication and is subject to change without notification. Spears® ongoing commitment to product improvement may result in some variation. No representation, guarantees or warranties of any kind are as to its accuracy, suitability for particular application or results to be obtained thereform. For verification of technical data or additional information, please contact Spears® Technical Service Department:: WEST COAST: (818) 364-1611 - EAST COAST: (717) 938-9006 F, I GENERAL DESCRIPTION Senju Sprinkler Model RC-RES K-Factor: 3.7 SIN: SS8261 Residential Lead Free Flat Concealed Sprinkler, Pendent C@ US LISTED ALS N1F/ANSI/(AN61&372 's The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. They are decorative and fast responding. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc., which is concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The push -on and/or thread -on, thread -off design of the concealed cover plate assembly allows for easy installation of the cover plate. Therefore, the Model RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and unbeatable performance is desired. The Model RC-RES is designed for residential occupancies and is perfect for use in homes, hotels and other living quarters. The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13. The Model RC-RES has a 3.7 (53.3 LPM/bar12) K-factor that meets the required residential flow rates with minimal residual pressure, which allows for smaller pipe sizes and water supply requirements. For extended installation flexibility, the Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of pipe lengths. The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents to escape or evacuate in case of a fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes. "Lead Free" is defined in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA's Water Utility Council, and California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of pipes, plumbing fittings and fixtures. www.senjusprinkler.com Page 1 of 8 Document No.U08620A • 07-05-2023 WARNINGS The installation and maintenance of Model RC-RES must strictly adhere to the guidelines specified in this document, as well as comply with the standards and regulations set forth by the National Fire Protection Association (NFPA) and any other applicable Authorities Having Jurisdiction. Additionally, it is crucial that the final approval for installation is obtained from Authorities Having Jurisdiction. Failure to comply with these requirements may result in a compromise to the integrity and functionality of the devices. It is the responsibility of the installing contractor to provide a copy of this document to the owner or their representative, and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any related questions. TECHNICAL DATA • Approvals: 0 cULus Listed o NSF/ANSI/CAN 61, NSF/ANSI/CAN 372 • Sprinkler Identification Number (SIN): SS8261 • Maximum Working Pressure: 175psi (12.1bar) • Discharge Coefficient (Nominal K-Factor): 0 K = 3.7 GPM/psi1/2 (53.3 LPM/bar12) • Temperature Rating: 0 162°F (72°C) Sprinkler with 140OF (60°C) Cover Plate • 205°F (96°C) Sprinkler with 162°F (72°C) Cover Plate • Color Code (Sprinkler) • 162°F (72°C): Uncolored • 205°F (960C): White • Color Code (Cover Plate) 0 140OF (600C): No Mark • 1620F (720C): White -Colored Mark • Vertical Adjustment: 1/2 inch (12.8 mm) • Cover Plate Finishes: 0 Standard Finishes: White, Ivory, Beige, Brown, Black, Nickel, Copper, Wood Grain 0 Custom Finishes: Custom color and custom pattern cover plates are available on special order. Contact a Senju Sprinkler representative with any custom orders. Please see chart on Page 8 for more detail. • Physical Characteristics: Ref. Figures 1 and 1.1 1/2" NPT i 2-1/16" (052 mm) E 4 L s `v 2 6 N 2-5/8" (068 mm) or 3-1/4" (083 mm) or 2-5/8" square (E168 r Lot No. Year of Manufacture SIN: SS8261 K-Factor: K3.7 Temperature Rating: 162°F (72°C) or 205°F (96°C) ILL Mark Control No.: 6P37 AILS Mark: NSF 61/372 RES SPKR ,T Body (Copper Alloy) OO Deflector (Phosphor Bronze) OO Gasket(PTFE) ® Fusible Metal (Solder) 0 Heat Collector (Copper) © Cover Plate Assembly Figure 1: Model RC-RES K = 3.7 Color Code Marking (Deflector) SIN: SS8261 K-Factor: K3.7 Temperature Rating: -- 162°F (72°C) or 205°F(96°C) UL Mark Cover Plate Sprinkler (Top View) (Bottom View) Figure 1.1: Marking (Color Code) www.senjusprinkler.com Page 2 of 8 Document No.U08620A • 07-05-2023 OPERATION In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then the Cover Plate is released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and when sufficient heat from the fire is reached, internal components of the sprinkler fall apart. This leads to the water flow to be distributed on the affected fire area. (Ref. Figure 2) Normal Condition Cover Plate Operation Sprinkler Operation Water Discharge Figure 2: Operation Process (For illustrative purposes only) DESIGN CRITERIA The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly implemented for safe and full results. Notes Residential Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar with automatic sprinkler system design, installation procedures, and techniques. Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the sprinkler system designer review and develop a working understanding of the complete list of criteria prior to initiating the design of the sprinkler system. Questions concerning sprinkler installation and usage criteria, which are not covered by the following instructions, should be submitted to your contracted company. Include sketches and technical details, as appropriate. In some instances, the requirements of this document may concern specifications which are more stringent, and which take precedence over those specified in NFPA 13, 13D, 13R, or by the authority having jurisdiction. The Model RC-RES must not be used in applications where the air pressure above the ceiling is greater than that below. Inspect all sprinklers after installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the cup are open and free from any air flow impediment. The spray from the sprinkler is distributed radially outward and downward from the sprinkler deflector. Consequently, the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers, overhangs or other parts of the dwelling structure. The number of sprinklers within each compartment (as defined by NFPA 13D, 13R, or 13) must be kept as few as possible while observing all guidelines relating to obstructions and spacing. Use only the Cover Plate provided for the Model RC-RES. The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces resulting from sprinkler operation could alter its orientation and its water distribution pattern. www.senjusprinkler.com Page 3 of 8 Document No.1-108620A • 07-05-2023 Obstruction to Water Distribution Locations of sprinklers must follow the obstruction rules of NFPA 13, 13D and 13R for Residential Sprinklers. General Service Conditions The Model RC-RES must only be utilized in WET PIPE sprinkler systems. Heat Source Criteria Refer to NFPA 13D, 13R or 13 for the requirements relating to the prevention of possible activation of the Heat Responsive Element of Model RC-RES, due to the exposure of a heat source other than an actual fire. Precautionary Warnings for Corrosive Environments Model RC-RES sprinklers should not be installed where they may be subjected to a corrosive environment including the following: 1. Chlorine ion and Chloride environment Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this environment may result in sprinklers operating under Non -Fire conditions or Not Operating when exposed to an actual fire. 2. Sprinkler system piping with Copper Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for copper piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA (Copper Development Association) - Solder Joint) All residual flux must be removed from the interior and exterior of the copper piping by thoroughly flushing before installation of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and/or leakage in the sprinkler system. Hydraulic Design Criteria The minimum required sprinkler flow rates for systems designed to NFPA 13D or 13R are given in Table A as a function of temperature rating and the maximum allowable coverage area. The sprinkler flow rate is the minimum required discharge from the most hydraulically demanding sprinkler from each of the total number of "design sprinklers" as specified in NFPA 13D or 13R. For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Table A for NFPA 13D and 13R as a function of temperature rating and maximum allowable coverage area. • A minimum discharge of 0.1GPM/sq.ft. [4.07LPM/sq.m] over the "design area" comprised of the four most hydraulically demanding sprinklers for the actual coverage area being protected by the four sprinklers. www.senjusprinkler.com Page 4 of 8 Document No.U08620A • 07-05-2023 Table A. NFPA 13D & 13P Wet Pipe Hydraulic Design Criteria for Model SS8261 For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R or 13 as applicable. Maximum Maximum Ordinary Temperature Intermediate Temperature Coverage Rating 1620F (72°C) Rating 205`F (96°C) Minimum Area(a) Spacing Deflector to Installation Spacing Flow(b)GPM Pressure" Flow(b)GPM Pressure" Ft. x Ft. Ft. Ceiling 9 T Type Ft. (m) (m x m) (m) (LPM) PSI (bar) (LPM) PSI (bar) 12 x 12 12 10 7.3 10 7.3 Smooth (3.7 x 3.7) (3.7) (37.9) (0.50) (37.9) (0.50) Ceilings 3/8 to 7/8 Inches. Beamed 14 x 14 14 10 7.3 10 7.3 (4.3 x 4.3) (4.3) (37.9) (0.50) (37.9) (0.50) Ceilings per NFPA 3R or 3D. 3 Concealed 8 (24) 15 x 15 15 12 10.5 12 10.5 (4.6 x 4.6) (4.6) (45.4) (0.72) (45.4) (0.72) Installed in beam 3/8 to 7/8 inches 16 x 16 16 13 12.3 13 12.3 below bottom (4.9 x 4.9) (4.9) (49.2) (0.85) (49.2) (0.85) of beam. a. For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the Next Higher Coverage Area listed. b. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details. Sprinkler Spacing Criteria The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond the coverage area calculated by using the specific hydraulic factors. (Ref. Table A) INSTALLATION The Model RC-RES must be installed in accordance with the following instructions: NOTES Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers which show deformation or cracking in either the Sprinkler or the Protective Cap. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to the sprinklers that could cause improper operation or non -operation. The Protective Cap must remain on the sprinkler during installation. After the installation is completed, the Protective Cap must be removed to place the sprinkler in service. Use a torque of 7 to 14 ft•lbs (9.5 to 19.0 N•m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended maximum torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler. Use only NR-H model wrench socket for installation of RC-RES sprinklers. Use of any other wrench or socket is prohibited and may cause damage to the sprinkler. In case of insufficient adjustment in Cover Plate installation, do not try to overly tighten, screw the sprinkler too loosely or make any modification to the cover plate assembly. Readjust the sprinkler fitting for a better fit. Do not rotate the Cap Removal Tool for RC to the left with force when placing the two hook arms into place. The installed sprinkler may become loosened, which may cause water leakage. www.senjusprinkler.com Page 5 of 8 Document No.1_108620A • 07-05-2023 Installation Steps Step 1: The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface will be nominally 2 inches (50.8mm) as shown in Figure 3. Step 2: With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the Socket NR-H or Ratchet (3/8" drive) & Socket NR-H Combination (Ref. Figure 4). The teeth of the Socket must fit perfectly with the grooves on the Sprinkler for proper installation (Ref. Figure 4). Step 3: If desired, the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation can be started with a 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the "Vertical Adjustment" indicator on the Protective Cap to check for proper installation height (Ref. Figure 3). Make a Space Here Ave. 1/4" (6.4 mm) Min. 1/8" (3.2 mm) I E Vertical E Adjustment O o _ N E Mounting cq Surface � �i 2-3/8" (060 mm) Ceiling Hole Diameter Do Not Over -Tighten Groove on the Protective N4-x �/ � Tooth on the Socket Mounting Surface �I �I Socket NR-H Ratchet i 1 Correct Incorrect Figure 3: Installation Figure 4: Ratchet & Socket Step 4: Use the Cap Removal Tool for RC to remove the Protective Cap (Ref. Figure 5), and then push or screw a Cover Plate Assembly on the Cup of the Sprinkler by hand until its flange just has contact with the ceiling (Ref. Figure 6 and Figure 7). Stop tightening the Cover Plate Assembly once the flange has contact with the ceiling. If the ceiling has been lifted from its normal position in the process of tightening the Cover Plate Assembly, readjust the cover plate assembly as necessary. If the flange of the Cover Plate Assembly cannot contact the ceiling sufficiently, readjust the sprinkler fitting as necessary. When properly installed, there is a nominal 1/16 inch (1.6mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 6. Sprinkler Head Hookup Protective Cap r Cap Removal Tool 1 Pull down Step 1 Step 2 Step 3 Figure 5: Protective Cap Removal www.senjusprinkler.com Page 6 of 8 Document NO.U08620A • 07-05-2023 E 0 N Screw Cover Plate Assembly 2-5/8" (068 mm) or 3-1/4" (083 mm) or 2-5/8" square (068 mm) Figure 6: Installation (Cover Plate Assembly) E E v +I 00 V +I N Incorrect Correct Incorrect Figure 7: Installation (Correct and Incorrect) CARE & MAINTENANCE The following instructions must be implemented for the maintenance and service of the Model RC-RES. Notes Wet pipe sprinkler systems must be maintained at a minimum temperature of 40°F / 4°C to prevent freezing and bursting of the pipe and/or sprinklers. Automatic sprinklers are not to be tested with a heat source. Operation of the heat responsive element can result. Absence of a Cover Plate Assembly may delay the response time of the sprinkler in case of a fire. Install the cover plate assembly properly, as shown in Figure 6. Improper installation of the cover plate assembly may cause improper operation or non -operation. If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does not seal off any of the air gap. Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted cover plates. Non - factory applied paint may adversely delay or prevent sprinkler operation in case of a fire. Do not pull the Cover Plate. Separation may result. In preparation for maintenance of the fire protection system, permission to close the main control valve must be obtained from the proper authorities, and all affected parties by this action, and must be informed before the maintenance session can commence. Do NOT enclose any sprinklers within drapes, curtains, or valances. Do NOT hang anything from the sprinklers. Do NOT clean the sprinklers with soap and/or water, detergents, ammonia, cleaning fluids, or other chemicals. Remove dust, lint, cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently vacuuming with a soft bristle (i.e., dusting) brush attachment. Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of fire development and spread of these materials can reduce the ability of the sprinkler system to aid in the control of a fire involving such hazards. www.senjusprinkler.com Page 7 of 8 Document No.U08620A • 07-05-2023 Leaking or corroded sprinklers must be replaced. Automatic Sprinklers must be kept in a cool and dry place. Automatic sprinklers must never be physically altered, such as painted, plated, or coated, once shipped from the factory. If the sprinklers have been in any way modified, they must be replaced. Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation. Damaged units because of dropping, hitting, over -tightening, or wrench slippage, must be replaced. The Model RC-RES must only be replaced with pendent sprinklers which are listed for residential fire protection service and which have the same nominal K-Factor, the same coverage area, and the same or lower flow ratings (as indicated under Table A "Hydraulic Design Criteria"). When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first verify that the new construction will not violate the installation requirements of the applicable standards of NFPA. Alter the new construction and/or the sprinkler system to suit the requirements of this document and the applicable NFPA regulations. The owner is responsible for the maintenance of the sprinkler system, including inspection and testing of its compliance with this document, as well as the standards of the National Fire Protection Association (e.g., NFPA 25), and the regulations of any other authorities having jurisdiction. The owner should direct any questions regarding the above rules and regulations to the installing contractors or the sprinkler manufacturer. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with NFPA 25. LIMITED WARRANTY For details of warranty, refer to Sales Contract. ORDER PROCEDURE When placing an order, please contact a local distributor with the following information (Model Name, Temperature Rating and Finish). Sprinkler • Model: RC-RES SIN: SS8261, Residential Flat Concealed Sprinkler, Pendent, K3.7, Temperature: 162°F (72°C) or 205OF (96°C) Cover Plate Assembly • 2-5/8 inch (#8mm) or 3-1/4 inch (�83mm) or 2-5/8 inch square (❑68mm), Order separately from Sprinkler Please refer to the chart below for available sizes, temperature, and finishes. White Ivory Beige Standard Brown Finishes Black Nickel Copper Wood Grain Custom I Finishes Custom Custom Color Pattern 2-5/8" Round, 140°F O O - - - - - - O O 3-1/4" Round, 140°F O O O O O O O O O O 2-5/8" Square, 140°F O - - - - - - - O O 2-5/8" Round, 162°F O - - - - - - - O O 3-1/4" Round, 162°F O O O O O - - O O O 2-5/8" Square, 162°F O - - - - - - - O O Tools & Accessories • Socket NR-H for use with a 3/8" drive ratchet (not included) • Socket NR-H Plastic for use with a 1/2" drive ratchet (not included) • Cap Removal Tool for RC • Cover Plate Installation Tool www.senjusprinkler.com Page 8 of 8 Document No.U08620A • 07-05-2023 Sprinkler Gauge - Model FPPI-PG Fig.11-550 2000 WATER W. �W s Psi SPRINKLERek Description Model FPPI-PG pressure gauges feature an impact and corrosion resistant case made from ABS (plastic) or powder coated steel. Features phosphor bronze bourdon tube movement with white enameled brass dial face with large numbers for easy reading. Dual scale to 300 PSI/2000Kpa. UL/ULc Listed (EX26630) and FM Approved. Applications • Fire sprinkler systems • Suitable for aLL media that will not obstruct the pressure system or attack copper alloy parts Special Features • UL-Listed (UL-393), EX26630 • Factory Mutual (FM) approved • Reliable and economical The information contained herein is produced in good faith and is believed to be reliable but is provided for guidance and information purposes only. FPPI and its agents cannot assume Liability or responsibility for results obtained in the use or misuse of its product by persons whose methods and qualifications are outside and beyond our control. It is the user's responsibility to determine the suitability of, methods of use, preparation prior to use, and appropriate installation for all products purchased from FPPI. It is the user's sole responsibility to observe and adapt such precautions as may be advisable or necessary forthe protection of personnel and property in the handling and use of any of our products. Standard Features Design: EN 837-1 & ASME B40.100 Size: 4" (100 mm) Accuracy class: ± 3 2/3% of span (ASME B40.100 Grade B) The tolerance is reflected in the box associated with the zero mark on the face of the gauge. The value is considered zero when the pointer falls anywhere within this box. Ranges: 0/80 psi, retard to 250 psi (air) 0/300 psi (air, water, air/water) Working Pressure: Steady: 'A of full scale value Fluctuating:'/2 of full scale value Short time: full scale value Operating Temperature: Ambient: -40°F to 140°F (-40°C to 60°C) Media:140°F (+60°C) maximum Temperature Error: Additional error when temperature of 68°F (20°C) +0.4% for every 18°F (10°C) rising or falling. Percentage of span. 9:,ASC kk:p Engineered Solutions Specifications Bourdon Tube: Material: copper alloy C-type Pressure Connection: Material: copper alloy 74" NPT Lower mount (LM) Movement: Copper alloy Dial: White aluminum with stop pin; black and red Lettering Pointer: Black aluminum Case: Black poLycarbonate Powder coated steel (Air/Water Gauge only) Window: Snap -in clear poLycarbonate Item Numbers/Descriptions: 11-550-00 Water Gauge 11-551-00 Air Gauge 11-552-00 Air Gauge w/Retard 11-553-00 Air/Water Gauge 11-553-10 Air/Water Gauge w/Steel Case 11-558-00 Water Gauge, Personalized 11-559-00 Air/Water Gauge, Personalized 11-561-00 Air Gauge w/Retard, Personalized C&US FM LISTED APPROVED 10 FPPI An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: I I ❑ Approved Address: ❑ Approved as noted Contractor: ❑ Not approved Engineer: I Remarks: Submittal Date: Notes 1: Notes 2: FP-05.22 page 1 FP-SUB-11-550-v0120220505 9:,ASC kk:p Engineered Solutions Double Offset Hanger and Restrainer Fig.184 (Formerly Afcon Fig. 515) Size Range: 3/4" through T' Material: Carbon Steel Finish: Pre -Galvanized per ASTM A653 Service: Hanger and surge restraint for horizontal CPVC piping when installed on the side of the supporting structure. C:5 Listed with hardware provided on structural wood beams and composite wood beams 0" minimum). For wood structures with less than 1" thickness, wood blocks may be placed on the backside of the wood structure. #14xl" fastener provided must be fully engaged in the wood block. • Maybe installed with concrete, steel, and other structural members with fasteners which comply with the requirements of NFPA 13. Approvals: cULus Listed Installation: • Slide CPVC pipe through the double offset hanger and restrainer. • Secure the hanger to the supporting structure with the screws provided or with listed fasteners. Features: • Beveled edge design helps protect the CPVC pipe from any rough surface and eliminates pipe abrasion. • Easily attaches to wood structure with #14 x 1" hex washer head self -threading screw supplied with product. No pre -drilling required. • Bottom of pipe is offset 1'/z' from the structure. Eliminates wooden spacer blocks. Ordering: Specify CPVC pipe size, figure number and description. OCx2 Q+ + B L 1. CPVC Pipe Structure Fasteners x2 Fig.184 O O O Fig.184: Dimensions (in) • Weight (lbs) c&us LISTED CPVC Max. Hanger Approx. Pipe Size A B 0C H L Spacing (ft) Weight/100 3/4 T/2 Th 'A 31/8 5'/8 5/2 17 1 1'/2 Th 'A 31/8 5'/8 6 17 PROJECT INFORMATION APPROVAL STAMP Project: ❑ Approved Address: ❑ Approved as noted Contractor: ❑ Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SS-1.18 page 1 SS-SUB-184-v0120220526 Two Hole Standoff Hanger and Restrainer Fig.188R (Formerly Afcon Fig. 514) Size Range: 3/4" through 2" Material: Carbon Steel Finish: Pre -Galvanized per ASTM A653 Service: Hanger and surge restraint for horizontal CPVC, steel, and copper piping when installed on the top, bottom, and side of the supporting structure. Guide for vertical CPVC, steel, and copper piping when installed on the side of the supporting structure. • Horizontal and vertical seismic restraint per NFPA 13-2016 requirements. • May be installed with concrete, steel structural members, and other structural members with fasteners which comply with the requirements of NFPA 13. Approvals: cULus Listed Patents: No. 6,648,278 Installation: • Snap hanger over pipe. If needed, squeeze strap back around pipe. • CPVC pipe must be allowed to slide freely through the Fig.188R. • Secure hanger to mounting surface with screws provided or with listed fasteners. Features: • Beveled edge design helps protect the CPVC pipe from any rough surface and eliminates pipe abrasion. Easily attaches to wood structure with #10 x T' hex washer head self -threading screw supplied with product. No pre -drilling required. • Bottom of pipe is offset 172" from the structure. Eliminates wooden spacer blocks. Ordering: Specify CPVC pipe size, figure number and description. Hanger& Restrainer Hangs Restr; 4c ner V,ASC,. kk:p Engineered Solutions us tallation - Backing Nut iger =1 - At top fastener traint = 2 - On each fastener NFPA-13Dand NFPA-13R ANVIL, An ASC Engineered Solution PROJECT INFORMATION APPROVAL STAMP Project: I ❑ Approved Address: ❑ Approved as noted Contractor: ❑ Not approved Engineer: I Remarks: Submittal Date: Notes 1: Notes 2: SS-9.18 page 1 SS-SUB-188R-v0120220629 Two Hole Standoff Hanger and Restrainer (cont.) Fig.188R (Formerly Afcon Fig. 514) Hanger and Restrainer Fig.188R: Dimensions (in) • Weight (Lbs) CPVC A B 0C D E F Pipe Size PPPF" ASC / Engineered Solutions 0 G Max. Hanger Approx. Spacing (ft) Weight/100 (lbs) 3A 23/4 31/2 1/4 2 1 2% 11/2 5 /2 11 1 213/16 3'h 'A 23/16 1 21 A6 Th 6 12 TA 213/16 31/2 'A 25/16 1 31/4 Th 6/2 13 11/2 35/8 4'/4 1/4 2716 1 31/2 11/2 7 14 2 3"A6 43/8 'A 2"/16 1 4 Th 8 16 Pipe CPVC Steel & Copper SS-9.18 Fig.18BR: Listed Fasteners Wood and Composite Beams Screw Supplied or #10 x T' TEK Screw #14 x T' TEK Screw or'/V x 11/2" Lag Screw Steel (18ga. Minimum) #14 x 1" TEK Screw or 1/4" x T' TEK Screw #14 x 1" TEK Screw or W' x T' TEK Screw ANVIL An ASC Engineered Solution page 2 SS-SUB-188R-v0120220629 Page 1 of 8 ® MICROMATIC° STANDARD RESPONSE PENDENT N4 I Kj SPRINKLER VK102 (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 1. DESCRIPTION The Viking Micromatic® Standard Response Pendent VK102 Sprinkler is a small, thermosensitive, glass -bulb spray sprinkler available in several different finishes and temperature ratings to meet design requirements. The special Polyester, and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive environments and are listed/approved as indicated in the Approval Charts. Viking standard response sprinklers may be ordered and/or used as open sprinklers (glass bulb and pip cap assembly removed) on deluge systems. Refer to Ordering Instructions. 2. LISTINGS AND APPROVALS c @us cULus Listed: Category VNIV �M. FM Approved: Classes 2001, 2002, 2015, 2017, 2043 vas VdS Approved: Certificate G414006 & G414004 PCB LPCB Approved WARNING: Cancer and Reproductive Harm- www.P65Warnings.ca.gov E CE: Standard EN 12259-1, DOP_Sprinklers_LPCB_5-2-19 & DOP_VK102WAX_2-12-19 MED Certified: Standard EN 12259-1, EC -certificate 0832-MED-1003 China Approval: Approved according to China GB standard. UK CA UKCA Approved: Standard EN 12259-1; Certificate Number 0832-UKCA-CPR-S5029; UKCA DOC_S5029; 2021 NOTE: Other International approval certificates are available upon request. Refer to Approval Charts and Design Criteria for listing and approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Minimum Operating Pressure: 7 psi (0.5 bar)* Maximum Working Pressure: 175 psi (12 bar) wwp Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: 1/2" NPT, 15 mm BSPT Nominal K-factor: 5.6 U.S. (80.6 metric**) Glass -bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: 2-1/4" (57 mm) * cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). **Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass Deflector: Phosphor Bronze UNS-051000 (Not for FM Approval) or Copper UNS-C19500 Bulb: Glass, nominal 5 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-Cl1000 and Stainless Steel UNS-S30400 For Polyester Coated Sprinklers: Belleville Spring -Exposed For ENT coated Sprinklers: Belleville Spring - Exposed, Screw and Pipcap - ENT plated. Ordering Information: Refer to Table 1 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat -sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. Form No. F_031414 Rev 02 November 2023 Replaces Form No. F_031414 Rev 01 (added UKCA) Page 2 of 8 ® MICROMATIC° STANDARD RESPONSE PENDENT N4 I IQ SPRINKLER VK102 (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Micromatic° Standard Response Upright Sprinkler VK100 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. r � Figure 1: Sprinkler Wrenches Nominal Pipe Engagement 2-1 /4" 7116" (57 mm) (11 mm) Figure 2: Sprinkler Dimensions Form No. F_031414 Rev 02 November 2023 Page 3 of 8 ® MICROMATIC° STANDARD A A � RESPONSE PENDENT SPRINKLER VK102 (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 1: ORDERING Instructions: Using .. the •R• the sprinkler base part number, suffix for the desired Finish Sprinkler Size .. the suffix for 1: Finishes the desired 2: Temperature Ratings Base Part NPT No. Inch BSPT mm Description Suffix' Nominal Rating 1 Bulb Color Hazard Classification Max. Ambient Ceiling Temperature Suffix 12987 1/2 Brass A 135 °F (57 °C) Orange Ordinary 100 °F (38 -C) A 12989 15 Chrome F 155 °F (68 °C) Red Ordinary 100 -F (38 -C) B 20229 15 White Polyester 3,5 M-/W 175 °F (79 °C) Yellow Intermediate 150 °F (65 -C) D Black Polyester 3,5 M-/B 200 °F (93 °C) Green Intermediate 150 -F (65 -C) E Wax C 212 'F (100 'C) Green Intermediate 150 °F (65 °C) M Wax over Polyester V-/W 286 °F (141 °C) Blue High 225 -F (107 °C) G ENT 3,4,5 JN 360 °F (182 °C) Mauve Extra High 300 -F (149 °C) H 500 °F (260 °C) Black Ultra High 465 -F (240 °C) L Example: 12987MB/W = VK102 with White Polyester Finish and 155 °F (68 °C) Nominal temperature rating. This sprinkler is to be installed into an area with a maximum ambient temperature of 100 °F (38 °C) meaning if the area will experience temperatures above the maximum ambient rating, you shall use a higher temperature -rated sprinkler. Corrosion Resistant Coatings' • White Polyester and Black Polyester in all temperature ratings. • ENT in all temperature ratings except 135 °F (57 °C). • Wax -Coated Brass and Wax over Polyester' for sprinklers with the following temperature ratings: 155 °F (68 °C) Lt. Brown Wax 1 175 °F (79 °C) Brown Wax 1 200 °F (93 °C) Brown Wax 1 286 °F (141 °C) Dk. Brown Wax' Accessories Sprinkler Wrenches (see Figure 1): A. Standard Wrench: Part No. 21475M/B B. Standard Wrench for Wax Coated Sprinklers: Part No. 10896W/B C. Socket Wrench for Recessed Pendent Sprinklers: Part No. 13655W/B (A 1/2" ratchet is required, not available from Viking) D. Socket Wrench for Wax Coated Sprinklers: Part No. 13577W/B (A 1/2" ratchet is required, not available from Viking) E. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool': Part No. 15915 Sprinkler Cabinet: A. Up to 6 sprinklers: Part number 01724A (available since 1971). B. 6-12 Sprinklers: Part number 01725A (available since 1971). Footnotes 1 Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above. z. Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3. UL Listed as corrosion resistant. 4. FM Approved corrosion resistant. s. The corrosion resistant and corrosion proofing coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart(s). These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end -user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated. a. Sprinklers of Ultra -High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above 300 °F (149 °C). Where the ambient temperature around the Ultra -High temperature rated sprinkler is significantly reduced below 300 °F (149 °C), response time may be severely retarded. 7 Wax melting point is 170 °F (76 °C) for 286 °F (141 °C) temperature rated sprinklers. For more inforamation regarding wax coatings, refer to Bulletin Form No. F_010201. e. Allows use from the floor by attaching a length of 1" diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F 051808. Form No. F_031414 Rev 02 November 2023 Page 4 of 8 ® MICROMATIC° STANDARD RESPONSE PENDENT SPRINKLER VK102 (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Approval Chart 1 (UL) Temperature KEY Micromatic® Standard Response Pendent Sprinkler VK102 •+ Finish AlXFEscutcheon (if applicable) Maximum 175 PSI 12 bar WWP Sprinkler Thread Size Nominal Overall Length Listings and Approvals' Base Part SIN K-factor (Refer also to UL Design Criteria.) Number' NPT BSPT U.S. metric2 Inches mm cULus" VdS LPCB CE- MED. China Approval UKCA12 Al, B3, B1Y, C4, Al, B3, 12987 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al Al, B3, B1Y F1, G1Y B412 F2X -- D2, E5, G5Z B1Y Al, B3, B1Y, C4, Al, B3, 12989 VK102 -- 15 mm 5.6 80.6 2-1/4" 57 Al Al, B3, B1Y F1, G1Y B412 F2X -- D2, E5, G5Z B1Y 2022910 VK102 -- 15 mm 5.6 80.6 2-1/4" 57 E6 E6 NOTICElonger10139 Al, B3, B1Y, C4, VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 -- -- -- -- -- -- D2, E5, G5Z Al, B3, B1Y, C4, 10173 VK102 -- 15 mm 5.6 80.6 2-1/4" 57 Al Al, B3, B1Y -- F2X -- -- D2, E5, G5Z Al, B1Y, C4 B3, , 18020 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al Al, B3, B1Y F1, G1X F2X D2, E5, G5Z Approved Temperature Rating Codes A = 135 OF (57 -C), 155 OF (68 -C), 175 OF (79 -C), 200 OF (93 -C), 286 OF (141 -C), and 360 OF (182 °C) B = 135 OF (57 -C), 155 OF (68 -C), 175 OF (79 °C), and 200 OF (93 °C) C = 286 OF (141 °C) D = 500 OF (260 -C)' E = 155 OF (68 -C), 175 OF (79 -C), 200 OF (93 -C), 286 OF (141 °C), 360 OF (182 °C), and 500 OF (260 °C)' F = 155 OF (68 °C), 175 OF (79 °C), 200 OF (93 °C), 286 OF (141 °C), and 360 OF (182 °C) G = 155 OF (68 -C), 175 OF (79 °C), and 200 OF (93 °C) Approved Finish Codes 1 = Brass, Chrome, White Polyester's and Black Polyester5,5 2 = Brass and Chrome 3 = Wax -Coated Brass and Wax Over Polyesters 4 = High Temperature 200 OF (93 °C) Wax Coating (corrosion resistant); maximum ambient temperature allowed at ceiling = 150 OF (65 'C) 5 = ENT' 6 = Chrome Approved Escutcheon Codes X = Recessed with the Viking Model E-1, E-2, or E-3 Recessed Escutcheon Y = Standard surface -mounted escutcheon or recessed with the Viking Model E-1, E-2, or E-3 Recessed Escutcheon Z = Standard surface -mounted escutcheon or recessed with the Viking Model E-1 Recessed Escutcheon Footnotes 1 Base part number is shown. For complete part number, refer to Viking's current price schedule. Y. Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3. This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. a Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5cULus Listed as corrosion resistant. a. Other colors are available on request with the same Listings and Approvals as the standard colors. 7 Sprinklers of Ultra -High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above 300 °F (149 °C). Where the ambient temperature around the Ultra -High temperature rated sprinkler is significantly reduced below 300 T (149 °C), the response time of the Ultra -High temperature rated sprinkler may be severely retarded. 8. CE: Standard EN 12259-1, EC -certificate of conformity 0832-CPD-0021. a. MED Certified, Standard EN 12259-1, EC -certificate of conformity 0832-MED-1003 and 0832-MED-1008. 10-Approved according to China GB standard. 11 CE: Standard EC 12259-1, Declaration of Performance DOP_Sprinklers_LPCB_5-2-19 & DOP_VK102WAX_2-12-19 12. UKCA Approved: Standard EN 12259-1; Certificate Number 0832-UKCA-CPR-S5029; UKCA DOC S5029; 2021 Form No. F_031414 Rev 02 November 2023 Page 5 of 8 ® MICROMATIC° STANDARD RESPONSE PENDENT N4 I IQ SPRINKLER VK102 (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Approval Chart 2 (FM) Temperature KEY Micromati& Standard Response Pendent Sprinkler VK102 Finish p p Al X F Escutcheon (if applicable) Maximum 175 PSI (12 bar) WWP Sprinkler Base Part Number' SIN Thread Size Nominal K-Factor Overall Length FM Approvals' (Refer also to Design Criteria below.) NPT BSPT U.S. metricz Inches mm 12987 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B2, C3, D1, E4, G1Y, G4Z 12989 VK102 15 mm 5.6 80.6 2-1/4" 57 Al, B2, C3, D1, E4, G1Y, G4Z 202297 VK102 15 mm 5.6 80.6 2-1/4" 57 E5 NOTICEOffice) 10139 VK102 1/2" 15 mm 1 5.6 1 80.6 1 2-1/4" 57 Al, B2, C3, D1, E4, G1Y, G4Z 10173 VK102 15 mm 5.6 80.6 2-1/4" 57 Al, B2, C3, D1, E4, G1Y, G4Z 18020 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B2, C3, D1, G1Y Approved Temperature Rating Codes A = 135 °F (57 -C), 155 °F (68 -C), 175 -F (79 -C), 200 -F (93 -C), 212 -F (100 -C), 286 -F (141 -C), and 360 °F (182 °C) B = 135 -F (57 -C), 155 -F (68 -C), 175 -F (79 -C), 200 -F (93 °C), and 212 °F (100 °C) C = 286 °F (141 °C) D = 500 °F (260 -C)5 E = 155 -F (68 -C), 175 -F (79 -C), 200 -F (93 -C), 286 -F (141 -C), 360 -F (182 °C), and 500 °F (260 °C)5 F = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) G = 155 -F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) Approved Finish Codes 1 = Brass, Chrome, White Polyesters,6 and Black Polyesters,6 2 = Wax -Coated Brass (corrosion resistant) 3 = High Temperature 200 °F (93 °C) Wax Coating (corrosion resistant); maximum ambient temperature allowed at the ceiling = 150 °F (65 °C) 4 = ENT6 5 = Chrome Approved Escutcheon Codes Y = Standard surface -mounted escutcheon or recessed with the Viking Model E-1, E-2, or E-3 Recessed Escutcheon Z = Standard surface -mounted escutcheon or recessed with the Viking Model E-1 Recessed Escutcheon Footnotes Base part number is shown. For complete part number, refer to Viking's current price schedule. Y. Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3. This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 0. Other colors are available on request with the same Approvals as the standard colors. 5Sprinklers of Ultra -High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above 300 °F (149 °C). Where the ambient temperature around the Ultra -High temperature rated sprinkler is significantly reduced below 300 °F (149 °C), the response time of the Ultra -High temperature rated sprinkler may be severely retarded. 6. FM approved as corrosion resistant. 7 Approved according to China GB standard. Form No. F_031414 Rev 02 November 2023 Page 6 of 8 ® MICROMATIC° STANDARD A A � RESPONSE PENDENT SPRINKLER VK102 (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com DESIGN CRITERIA - UL (Also refer to Approval Chart 1.) cULus Listing Requirements: The Viking Micromatic° Standard Response Pendent Sprinkler VK102 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light, Ordinary, and Extra Hazard occupancies. • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. • Venting is not required. IMPORTANT. Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan- dards, whenever applicable. DESIGN CRITERIA - FM (Also refer to Approval Chart 2.) FM Approval Reauirements: The Viking Micromatic° Standard Response Pendent Sprinkler VK102 is is FM Approved as standard response Non - Storage pendent sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceil- ing slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Form No. F_031414 Rev 02 November 2023 Page 7 of 8 ® MICROMATIC° STANDARD TECHNICAL DATA RESPONSE PENDENT N41KJNG* I SPRINKLER VK102 (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com STANDARD FINISHES Step 1: Carefully slide the wrench sideways around the protective cap, ensuring engagement with the wrench flats. WAX COATED Step 1: Carefully slide the wrench sideways around the protective cap (not shown), ensuring engagement with the wrench flats. Figure 3: Installation with Recessed Wrenches *Requires a 112 ratchet - not available from Minimax. 13655W/B* Step 2: Carefully t t press the wrench upwards to engage with the wrench flats. 13577W/B* Step 2: Carefully press the wrench upwards to engage with the wrench flats. Form No. F_031414 Rev 02 November 2023 Page 8 of 8 ® MICROMATIC° STANDARD RESPONSE PENDENT N4 I Ki SPRINKLER VK102 (K5.6) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com Ceiling Opening Size: 2-5116" (59 mm) minimum 2-1/2" (64 mm) maximum 1-3/4" (45 mm) Installed with a standard 1/8" surface -mounted escutcheon Ceiling Opening Size: 2-5/16" (59 mm) minimum 2-1/2" (64 mm) maximum (541mm)V / \ (541mrr 1-1/8" (29 mm) I 1-3 Minimum " (45 mm) Maximum I I A' I 1-1/8" (29 mm) Id" " Minimum (51 mm) Maximum ^ Pv. ;am - Installed with a Model E-1 Installed with a Model E-2 Thread -on Recessed Escutcheon Recessed Escutcheon Figure 4: Installation Dimensions with Escutcheons Form No. F_031414 Rev 02 November 2023 Replaces Form No. F_031414 Rev 01 (added UKCA.) Page 1 of 4 CARE AND HANDLING Ila 7W7*j 11111wOF SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com SPRINKLERS ARE FRAGILE - HANDLE WITH CARE! General Handling and Storage: • Store sprinklers in a cool, dry place. • Protect sprinklers during storage, transport, handling, and after installation. • Use the original shipping containers. DO NOT place sprinklers loose in boxes, bins, or buckets. • Keep sprinklers separated at all times. DO NOT allow metal parts to contact sprinkler operating elements. For Pre -Assembled Drops: • Protect sprinklers during handling and after installation. • For recessed assemblies, use the protective sprinkler cap (Viking Part Number 10364). Sprinklers with Protective Shields or Caps: • DO NOT remove shields or caps until after sprinkler installation and there no longer is potential for mechanical damage to the sprinkler operating elements. • Sprinkler shields or caps MUST be removed BEFORE placing the system in service! • Remove the sprinkler shield by carefully pulling it apart where it is snapped together. • Remove the cap by turning it slightly and pulling it off the sprinkler. Sprinkler Installation: • DO NOT use the sprinkler deflector or operating element to start or thread the sprinkler into a fitting. • Use only the designated sprinkler head wrench! Refer to the current sprinkler tech- nical data page to determine the correct wrench for the model of sprinkler used. • DO NOT install sprinklers onto piping at the floor level. • Install sprinklers after the piping is in place to prevent mechanical damage. • DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings, pipe, or couplings in close proximity to sprinklers. Sprinklers can be damaged from direct or indirect impacts. • DO NOT attempt to remove drywall, paint, etc., from sprinklers. • Take care not to over -tighten the sprinkler and/or damage its operating parts! Maximum Torque: 1/2" NPT: 14 ft-Ibs. (19.0 N-m) 3/4" NPT: 20 ft-Ibs. (27.1 N-m) 1" NPT. 30 ft-Ibs. (40.7 N-m) A WARNING CORRECT INCORRECT (Original container used) (Placed loose in box) CORRECT INCORRECT (Protected with caps) (Protective caps not used) CORRECT INCORRECT (Piping is in place at the (Sprinkler at floor level) ceiling) (Special installation (Designated wrench not wrenches) used) WARNING: Cancer and Reproductive Harm- www. P65Warni ngs.ca.gov Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed. Never install sprinklers that have been dropped, damaged, or exposed to temperatures exceeding the maximum ambient temperature allowed. Sprinklers that have been painted in the field must be replaced per NFPA 13. Protect sprinklers from paint and paint overspray in accordance with the installation standards. Do not clean sprinklers with soap and water, ammonia, or any other cleaning fluid. Do not use adhesives or solvents on sprinklers or their operating elements. Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com. Form No. F_091699 18.10.11 Rev 16.1.P65 Replaces Form No. F_091699 Rev 16.1 (Added P65 Warning) Page 2 of 4 : 7W7 CARE AND HANDLING OF SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com PROTECTIVE SPRINKLER SHIELDS AND CAPS General Handling and Storage: Many Viking sprinklers are available with a plastic protective cap or shield temporarily covering the operating elements. The snap - on shields and caps are factory installed and are intended to help protect the operating elements from mechanical damage during shipping, storage, and installation. NOTE: It is still necessary to follow the care and handling instructions on the appropriate sprin- kler technical data sheets* when installing sprinklers with bulb shields or caps. WHEN TO REMOVE THE SHIELDS AND CAPS: NOTE: SHIELDS AND CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! Remove the shield or cap from the sprinkler only after checking all of the following: The sprinkler has been installed*. The wall or ceiling finish work is completed where the sprinkler is installed and there no longer is a potential for mechanical damage to the sprinkler operating elements. SHIELDS AND CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! Figure 1: Sprinkler shield being removed from a pendent sprinkler Figure 2: Sprinkler cap being removed from a pendent sprinkler. Figure 3: Sprinkler cap being re- moved from and upright sprinkler. HOW TO REMOVE SHIELDS AND CAPS: No tools are necessary to remove the shields or caps from sprinklers. DO NOT use any sharp objects to remove them! Take care not to cause mechanical damage to sprinklers when removing the shields or caps. When removing caps from fusible ele- ment sprinklers, use care to prevent dislodging ejector springs or damaging fusible elements. NOTE: Squeezing the sprinkler cap excessively could damage sprinkler fusible elements. • To remove the shield, simply pull the ends of the shield apart where it is snapped together. Refer to Figure 1. • To remove the cap, turn it slightly and pull it off the sprinkler. Refer to Figures 2 and 3. Refer to the current sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used. ©WARNING Never install sprinklers that have been dropped, damaged, or exposed to temperatures in excess of the maximum ambient temperature allowed. * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com. Form No. F_091699 18.10.11 Rev 16.1.P65 Page 3 of 4 CARE AND HANDLING OF SPRINKLERS -N11aN7G*JM The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com ACAUTION CONCEALED COVER ASSEMBLIES ARE FRAGILE! TO ASSURE SATISFACTORY PERFORMANCE OF THE PRODUCT, HANDLE WITH CARE. Concealed Sprinkler and Adapter Assembly with Protective Cap Concealed Sprinkler and Adapter Assembly (Protective Cap Removed) �� �i; ��� Cover Plate Assembly (Pendent Cover 12381 shown) GENERAL HANDLING AND STORAGE INSTRUCTIONS: • Do not store in temperatures exceeding 100 °F (38 °C). Avoid direct sunlight and confined areas subject to heat. • Protect sprinklers and cover assemblies during storage, transport, handling, and after installation. Use original shipping containers. Do not place sprinklers or cover assemblies loose in boxes, bins, or buckets. • Keep the sprinkler bodies covered with the protective sprinkler cap any time the sprinklers are shipped or handled, during testing of the system, and while ceiling finish work is being completed. • Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed. • Do not over -tighten the sprinklers into fittings during installation. • Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation. • Do not attempt to remove drywall, paint, etc., from the sprinklers. • Remove the plastic protective cap from the sprinkler before attaching the cover plate assembly. PROTECTIVE CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com. Form No. F_091699 18.10.11 Rev 16.1.P65 Page 4 of 4 : 7W7 CARE AND HANDLING OF SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com USE THE FOLLOWING PRECAUTIONS WHEN HANDLING WAX -COATED SPRINKLERS Many of Viking's sprinklers are available with factory -applied wax coating for corrosion resistance. These sprinklers MUST receive appropriate care and handling to avoid damaging the wax coating and to assure satisfactory performance of the product. General Handling and Storage of Wax -Coated Sprinklers: Store the sprinklers in a cool, dry place (in temperatures below the maximum ambient temperature allowed for the sprinkler temperature rating. Refer to Table 1 below.) • Store containers of wax -coated sprinklers separate from other sprinklers. • Protect the sprinklers during storage, transport, handling, and after installation. • Use original shipping containers. • Do not place sprinklers in loose boxes, bins, or buckets. Installation of Wax -Coated Sprinklers: Use only the special sprinkler head wrench designed for installing wax -coated Viking sprinklers (any other wrench may damage the unit). • Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after sprinkler installation to protect the corrosion -resistant properties of the sprinkler. • Use care when locating sprinklers near fixtures that can generate heat. Do not install sprinklers where they would be exposed to temperatures exceed- ing the maximum recommended ambient temperature for the temperature rating used. • Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant coating. Thereafter, inspect representative samples of the coated sprinklers in accordance with NFPA 25. Close up visual inspections are necessary to determine whether the sprinklers are being affected by corrosive conditions. Sprinkler Temperature Rating (Fusing Point) Wax Part Number TABLE 1 Wax Melting Point Maximum Ambient Ceiling Temperature Wax Color 155 °F (68 °C) / 165 °F (74 °C) 02568A 148 °F (64 °C) 100 °F (38 °C) Light Brown 175 °F (79 °C) 04146A 161 °F (71 °C) 150 °F (65 °C) Brown 200 °F (93 °C) 04146A 161 °F (71 °C) 150 °F (65 °C) Brown 220 °F (104 °C) 02569A 170 °F (76 °C) 150 °F (65 °C) Dark Brown 286 °F (141 °C) 02569A 170 °F (76 °C) 150 °F (65 °C) Dark Brown Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. AWARNING Never install sprinklers that have been dropped, damaged, or exposed to temperatures in excess of the maximum ambi ent temperature allowed. Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com. Form No. F_091699 18.10.11 Rev 16.1.P65 Replaces Form No. F_091699 Rev 16.1 (Added P65 Warning) Page 1 of 1 N4 I Ki REGULATORY AND HEALTH WARNINGS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com 1. DESCRIPTION Regulatory and Health Warnings applying to materials used in the manufacture and construction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions. ©WARNING STATE OF CALIFORNIA, USA Installing or servicing fire protection products such as sprinklers, valves, piping etc. can expose you to chemicals including, but not li- mited to, lead, nickel, butadiene, titaninum dioxide, chromium, carbon black, and acrylonitrile which are known to the State of California to cause cancer or birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov 2. WARRANTY TERMS AND CONDITIONS For details of warranty, refer to Viking's current list price schedule at www.vikinggroupinc.com or contact Viking directly. Form No. F 111218 18.11.15 Rev 18.1 New Bulletin