REVIEWED BLD2024-1625+Manufacturer_Specifications_and_Installation_Instructions+12.10.2024_1.58.53_PM+4662747
BLD2024-1625 Job Name: System Reference: Date: Indoor Unit Outdoor Unit REVIEWED RECEIVED sec 11 2024 PKA-A18LA1 PUZ-A18NKA7 CITY OF EDMONDS INDOOR UNIT FEATURES • Selectable high sensible vs high latent capacity mode • UL 60335-2-40 compliant • Sleek, compact design • Simple installation • Airflow direction control • Auto fan mode • Suitable for: server rooms, daycare centers, classrooms, churches, small offices, and more • Multiple control options available: o kumo cloud° smart device app for remote access o Third -party interface options o Wired or wireless controllers OUTDOOR UNIT FEATURES • Variable speed INVERTER -driven compressor • Pre -charged with refrigerant volume for piping length up to 70 ft • Low ambient cooling down to 0°F providing 100% capacity • 24-hour continuous operation (cooling mode) • High pressure protection • Fast restart • Superior energy and operational efficiency • Seacoast protection` o External Outer Panel: Phosphate coating + Acrylic -Enamel coating o Fan Motor Support: Epoxy resin coating (at edge face) o Separator Assembly Valve Bed: Epoxy resin coating (at edge face) o Blue Fin treatment is an anti -corrosion treatment that is applied to the Heat exchanger coil to protect it against airborne contaminants. o Heat exchanger coil and base panel rated for 2,000 hours in accordance with ASTM B117 testing 'Seacoast protection standard from 2022 production Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Cooling at 95°F' Maximum Capacity Rated Capacity Minimum Capacity BTU/H 18,000 BTU/H 18,000 BTU/H 5,600 1,680 Maximum Power Input W Rated Power Input W 1,680 Moisture Removal Pints/h 5.8 Sensible Heat Factor 0.73 Power Factor [208V / 230A % 96.7 / 96.7 Heating at 47°F2 Maximum Capacity BTU/H 22,000 Rated Capacity BTU/H 19,000 Minimum Capacity BTU/H 5,400 Maximum Power Input W 2,150 Rated Power Input W 1,640 Power Factor [208V / 230A % 96.7 / 96.7 Heating at 17°F' Maximum Capacity BTU/H 13,600 Rated Capacity BTU/H 13,600 Maximum Power Input W 1,560 Rated Power Input W 1,560 Efficiency SEER2 20.2 EER2' 10.7 HSPF2 [IV] 9.2 COP at 47°F' 3.4 COP at 17°F at Maximum Capacity' 2.5 ENERGY STAR® Certified No Electrical Voltage, Phase, Frequency 208/230, 1, 60 Guaranteed Voltage Range VAC 198 - 253 Voltage: Indoor - Outdoor, S1-S2 VAC 208/230 Voltage: Indoor - Outdoor, S2-S3 V DC 24 Short-circuit Current Rating [SCCR] kA 5 Recommended Fuse/Breaker Size (Oudoor) A 15 Recommended Wire Size [Indoor - Outdoor] AWG 14 Power Supply Indoor unit is powered by the outdoor unit Indoor Unit MCA A 1.0 Fan Motor Full Load Amperage A 0.19 Fan Motor Output W 30 Fan Motor Type DC Motor Airflow Rate at Cooling, Dry CFM 265-310-375-450 Airflow Rate at Cooling, Wet CFM 215-255-320-375 Airflow Rate at Heating, Dry CFM 265-310-385-455 Sound Pressure Level [Cooling] dB[A] 34-39-44-48 Sound Pressure Level [Heating] dB[A] 34-39-44-48 Drain Pipe Size In. [mm] 518 [16] Coating on Heat Exchanger — External Finish Color White Munsell 0.7PB 9.2/0.4 Unit Dimensions W x D x H: In. [mm] 35-23/64 x 9-11/32 x 11-25/32 [898 x 237 x 299] Package Dimensions W x D x H: In. [mm] 38-3/16 x 13-25/64 x 14-11/64 [970 x 340 x 360] Unit Weight Lbs. [kg] 28 [12.7] Package Weight Lbs. [kg] 32 [14.4] Indoor Unit Operating Temperature Range Cooling Intake Air Temp [Maximum / Minimum]* °F 90 DB, 73 WB / 66 DB, 59 WB Heating Intake Air Temp [Maximum / Minimum] °F 82 DB 150 DB NOTES: AHRI Rated Conditions 'Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB (Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 'Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB Conditions 41-leating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB Select high sensible versus high latent capacity mode via function setting mode 08, "Fan speed" (accessible through Touch MA, Deluxe MA, kumo touch and kumo cloud app control options): • "High ceiling" mode = high sensible capacity Mode 08, setting 3 (factory default) Standard" mode = high latent capacity Mode 08, setting 2 *Outdoor Unit Operating Temperature Range (Cooling Air Temp (Maximum / Minimum)): • Wind baffles required to operate below 23°F DB in cooling mode. • Heat pump system with wind baffle: 0°F - 115°F. Refer to wind baffle documentation for further information. **Outdoor Unit Operating Temperature Range (Cooling Thermal Lock -out / Re -start Temperatures; Heating Thermal Lock -out / Re -start Temperatures): • System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures. ***Blue Fin Coating Standard from 2022 production: • PU(Y/Z)-A(12/18)NKA7 - Beginning with serial number 12U***** PU(Y/Z)-A(24/30/36/42)NKA7 - Beginning with serial number 1ZU***** Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trans HVAC US LLC. All rights reserved. Outdoor Unit MCA A 11.0 MOCP A 28 Fan Motor Full Load Amperage A 0.5 Fan Motor Output W 46 Airflow Rate [Cooling / Heating] CFM 1590 / 1590 Refrigerant Control LEV Defrost Method Reverse Cycle Coating on Heat Exchanger Blue Fin Coating*** Sound Pressure Level, Cooling' dB(A) 44 Sound Pressure Level, Heating2 dB(A) 46 Compressor Type INVERTER -driven twin rotary Compressor Model SNB130FQCMC-L1 Compressor Rated Load Amps A 7 Compressor Locked Rotor Amps A 12.0 Compressor Oil [Type H Charge] oz. FV50S H 16 External Finish Color Ivory Munsell 3Y 7.8/1.1 Base Pan Heater N/A Unit Dimensions W x D x H: In. [mm] 31-13/16 (2+7/16) x 11-13/16 x 24-13/16 [809 (+62) x 300 x 630] Package Dimensions W x D x H: In. [mm] 37-1/16 x 16-3/16 x 27-7/16 [941 x 411 x 697] Unit Weight Lbs. [kg] 100 [45] Package Weight Lbs. [kg] 112 [51] Outdoor Unit Operating Temperature Range Cooling Air Temp [Maximum / Minimum]* °F 115 DB 10 DB Heating Air Temp [Maximum / Minimum] °F 70 DB, 59 WB / 12 DB, 14 WB Heating Thermal Lock -out / Re -start Temperatures— °F 8 / 12 Refrigerant Type R410A Pre -Charged Refrigerant Amount Lbs, oz 4.0, 14.0 Maximum Pre -Charged Piping Length Ft. [m] 70.0 [21.0] Additional Refrigerant Charge Per Additional Piping Length oz./Ft. [g/m] 0.2 [19] Piping Gas Pipe Size O.D. [Flared] In.[mm] 1/2 [12.7] Liquid Pipe Size O.D. [Flared] In.[mm] 1/4 [6.35] Maximum Piping Length Ft. [m] 100 [30] Maximum Height Difference Ft. [m] 100 [30] Maximum Number of Bends 15 NOTES: AHRI Rated Conditions 'Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB (Rated data is determined at a fixed compressor speed) 2Heating at 477 (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 'Heating at 17*F (Indoor // Outdoor) *F 70 DB, 60 WB // 17 DB, 15 WB Conditions 4Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB H 5 DB, 4 WB Select high sensible versus high latent capacity mode via function setting mode 08, "Fan speed" (accessible through Touch MA, Deluxe MA, kumo touch and kumo cloud app control options): • "High ceiling" mode = high sensible capacity Mode 08, setting 3 (factory default) -Standard" mode = high latent capacity Mode 08, setting 2 *Outdoor Unit Operating Temperature Range (Cooling Air Temp (Maximum / Minimum)): Wind baffles required to operate below 23°F DB in cooling mode. Heat pump system with wind baffle: 0°F - 115°F. Refer to wind baffle documentation for further information. **Outdoor Unit Operating Temperature Range (Cooling Thermal Lock -out / Re -start Temperatures; Heating Thermal Lock -out / Re -start Temperatures): • System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures. ***Blue Fin Coating Standard from 2022 production: PU(Y/Z)-A(12/18)NKA7 - Beginning with serial number 12U***** • PU(Y/Z)-A(24/30/36/42)NKA7 - Beginning with serial number 1ZU***** Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Control Interface 3-Pin Connector IT Extender kumo station® for kumo cloud® Proton BACnet® and Modbus® Interface Thermostat Interface USNAPAdapter ❑ PAC-715AD ❑ PAC-WHS011E-E ❑ PAC-WHS01HC-E ❑ PAC-UKPRC001-CN-1 ❑ PAC-US445CN-1 ❑ PAC-WHS01UP-E Wireless Interface for kumo cloud® ❑ PAC-USWHS002-WF-2 Flush Mount Remote Temperature Sensor ❑ PAC-USSEN002-FM-1 Flush Mount Temperature Sensor ❑ PAC-USSEN001-FM-1 Remote Sensor Remote Temperature Sensor ❑ PAC-SE41TS-E Wireless temperature and humidity sensor for kumo cloud® ❑ PAC-USWHS003-TH-1 Deluxe Wired MA Remote Controllers ❑ PAR-40MAAU Simple Ductless Wired Remote Controller ❑ PAC-SDW01RC-1 Wired Remote Controller Simple MA Remote Controllers ❑ PAC-YT53CRAU-J Touch MA Controllers ❑ PAR-CT01MAU-SB kumo touch'" RedLINK'" Wireless Controller ❑ MHK2 Wireless Remote Controller Lockdown bracket for remote controller ❑ RCMKP1C13 Wireless MA Remote Controller ❑ PAR-FL32MA-E Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended] ❑ X87-721 Blue Diamond (MicroBlue) Mini Condensate Pump (110/208/230V) up to 18,000 BTU/H ❑ X86-003 Blue Diamond Sensor Extension Cable —15 Ft. ❑ C13-103 Drain Pan Level Sensor/Control ❑ SS610E Condensate Fascia Kit for MicroBlue Pump, mounts the MicroBlue and sensor directly beneath indoor unit ❑ T18-016 Refco Condensate Pump (100-240 VAC) ❑ GOBI-II Refoo Condensate Pump (100-240 VAC) up to 120,000 BTU/H ❑ COMBI Sauermann Condensate Pump ❑ S130-230 (30A/600V/UL) [fits 2" X 4" utility box] - Black ❑ TAZ-MS303 Disconnect Switch (30A/600V/UL) [fits 2" X 4" utility box] - White ❑ TAZ-MS303W 100' x 1/4" x 100' / 1/2" Lineset (Twin -Tube Insulation) ❑ MLS141212T-100 15' x 1/4" x 15' / 112" Lineset (Twin -Tube Insulation) ❑ MLS141212T-15 Lineset 30' x 1/4" x 30' / 1/2" Lineset (Twin -Tube Insulation) ❑ MLS141212T-30 50' x 1/4" x 50' / 1/2" Lineset (Twin -Tube Insulation) ❑ MLS141212T-50 65' x 1/4" x 65' / 1/2" Lineset (Twin -Tube Insulation) ❑ MLS141212T-65 14 Gauge, 4 wire MiniSplit Cable-250 ft. roll ❑ SW144-250 14 Gauge, 4 wire MiniSplit Cable-50 ft. roll ❑ SW144-50 Mini -Split Wire 16 Gauge, 4 wire MiniSplit Cable-250 ft. roll ❑ SW164-250 16 Gauge, 4 wire MiniSplit Cable-50 ft. roll ❑ SW164-50 Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. Air Outlet Guide Air Outlet Guide Centralized Drain Pan Drain Pan Control/Service Tool M- & P-Series Maintenance Tool Cable Set ❑ PAC-SJ07SG-E Centralized Drain Pan ❑ PAC-SG63DP-E ❑ PAC-SG64DP-E Control/Service Tool ❑ PAC-SK52ST ❑ M21 EC0397 USB/UART Conversion Cable (Required for all laptop connection) ❑ M21 EC1397 Drain Socket Drain Socket ❑ MAC-871 DS Hail Guards Hail Guard ❑ HG-A5 M-NET Converter M-NET Converter ❑ PAC-SJ96MA-E 14 Gauge, 4 wire MiniSplit Cable-250 ft. roll ❑ S144-250 14 Gauge, 4 wire MiniSplit Cable-50 ft. roll ❑ S144-50 Mini -Split Wire 16 Gauge, 4 wire MiniSplit Cable-250 ft. roll ❑ S164-250 16 Gauge, 4 wire MiniSplit Cable-50 ft. roll ❑ S164-50 Mounting Pad Condensing Unit Mounting Pad: 16" x 36" x 3" ❑ ULTRILITE1 18" Single Fan Stand ❑ QSMS1801 M 24" Single Fan Stand ❑ QSMS2401 M Stand Condenser Wall Bracket ❑ QSWB2000M-1 Condenser Wall Bracket - Stainless Steel Finish ❑ QSWBSS Outdoor Unit Stand —12" High ❑ QSMS1201 M Front Wind Baffle ❑ WB-PA4 Wind Baffle Rear Wind Baffle ❑ WB-RE4 Side Advanced Wind Baffle ❑ WB-SD4 Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved. REQUIRED SPACE(INDOOR UNIT) / AIRINLET W � LLy�4 F AIR OUTLET °7 c`i w o g _ 1-31 9704 case oeo MlorvaL / .SIN/ IN DMIWWW74STZaTION. /- 5-29/32150 MIN. 10-15/64260 MIN. LEFT DETAILS OF CUT OUT FOR PIPING HOLE D A Lll� C B N w C1 �q 14i1/6449.5 3/419 1-21/3250 3-2]/648] 3/4 0 SLEEVE THROUGH HOLE INSTALLATION PLATE TEMPC 02 1/64 02a1/fi4-�3- ry (OM-O8U) INDOOR UNIT rq v RILY FIXING HOLE TERM — so o CL� Ji II e3\ ZZ w WALL H( am 63164(25) 0 63164(25) 2-1/4(57.2) 23/4 69.7) 3-151 (82.2) 455164(123.5) FRONT FRONT(OPEN THE GRILLE) RIGHT REFRIGERANT PIPE,DRAIN PIPE EMERGENCY OPERATION SWITCH(HEAT) Z7EMERGENCY OPERATION SWITCH COOL 1. FOR CEILING CORNICE: CONSIDER THE DIMENSION 6-19164 160 FOR INSTALLATION. BOTTOM 2. MOUNTING BOLT FOR INSTALLATION PLATE: M10 OR W3/8 AUTO VANES TAPPING SCREW: NOMINAL DIAMETER • • • 5/32(4) LENGTH • • • 63/64(25) MIN SCREW TIGHT AT INSTALLATION PLATE HOLE {I 1/64(04.3)) ON THE UPPER AND LOWER SIDE EVENLY. DO NOT SCREW TIGHT ONLY IN LINE. 3. REFRIGERANT LIOUIDPIPE O1/4(06.351 PIPING GAS PIPE 01/2(012.7) DRAIN HOSE I CONNECTION 01 051/8(016) INSULATION -9/64 029 _ 4. LEFT PIPE: CONNECT DRAIN HOSE TO CONNECTION PORT C LOUVERS MANUAL RECEIVER ON THE LEFT SIDE OF DRAIN PAN. EXCHANGE DRAIN HOSE AND OF CAP UNDER PIPING CUT OUT AREA AND BUTT THEM AGAINST DRAIN PORT. 5. DRAIN PIPE EFFECTIVE LENGTH ... 19-11/18(500) REFRIGERANT PIPE,DRAIN PIPE UNDER PIPING CUT OUT AREA REFRIGERANT PIPE,DRAIN PIPE 3 3 A N 404.5<15-15/16> rn Air intake Installation I olt pitch v 00 v 500<19- 1/16> Air intake Air discharge <W A m_ M a N W N M C M � N � V y N � M a0 154.5 <6-3/32> 310 <12-7/32> 809<31-7/8> iin hole 2 2-U Shaped notched holes / (Foundation Bolt M10<W 3/8>) A A O M yis_ V O MO M A M m v val hole U� 23.2<15 Bolt M10 M 22 <7 IS > Terminal connection (Left t Power supply wiring ) �I \Right ... Indoor/Outdoor wiring/ Larth terminal _ ^ Service panel m M v N C 2- o 22.2<7/8> 1/2 conduit hole N A i2) Service port V o; v � U� Cb 62 <2-15/32> Free space around the outdoor unit (basic example) 100mm<3-15/16> or more as long as no obstacle is placed on the rear and right -and -left sides m of the unit Min.t00mm Min.350mm <3-15/i6> <13-25/32> Min.500mm '� Min.100mm <19-11/i6> <3-15/16> 2 sides should be open in the right, left and rear side. FORM# PKA-Al8LA1 & PUZ-Al8NKA7 - 202310 Unit: mm<in> Service panel for charge plug Connection for liquid pipe FLARE o6.35 (1/4F) Connection for �gas pipe FLARE o12.7 185.5 <7-5/16> FOUNDATION BOLTS Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts (Bolts, washers and nut must be purchased locally). <Foundation bolt height> 51 FOUNDATION E m E PIPING -WIRING DIRECTION Piping and wiring connection can be made from the rear direction only. 1340 Satellite Boulevard Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com Eta us Intertek Specifications are subject to change without notice. © 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.