APPROVED BLD2024-1307+Structural_Analysis_or_Calculations+11.1.2024_10.15.08_PM+4598324GENERAL STRUCTURAL NOTES
(THE FOLLOWING APPLY UNLESS SHOWN OTHERWISE ON THE PLANS.)
A. GENERAL
1. ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL
CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL
BUILDING CODE (IBC), 2021 EDITION, AS AMENDED BY LOCAL JURISDICTION.
2. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH
ARCHITECTURAL DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTOR
SHALL VERIFY DIMENSIONS AND CONDITIONS FOR COMPATIBILITY AND SHALL
NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO CONSTRUCTION. SEE
ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND DIMENSIONS OF DOOR AND
WINDOW OPENINGS. SEE MECHANICAL DRAWINGS FOR SIZE AND LOCATION OF
MISCELLANEOUS MECHANICAL OPENINGS.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AND
THE METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES REQUIRED TO PERFORM
HIS WORK. STRUCTURAL DESIGN OF THE BUILDING IS BASED ON RESISTANCE
TO DEAD LOADS, CODE SPECIFIED LATERAL LOADS, AND MAXIMUM EXPECTED
SERVICE LOADS. NO CONSIDERATION HAS BEEN GIVEN TO LOADS WHICH WILL
BE INDUCED BY ERECTION PROCEDURES. THE CONTRACTOR SHALL VERIFY, TO
THE SATISFACTION OF HIMSELF AND THE OWNER, THE ABILITY OF THE
STRUCTURE TO RESIST ALL ERECTION LOADS WITHOUT EXCEEDING THE
ALLOWABLE STRESSES OF THE MATERIALS USED. WHERE ERECTION LOADS WOULD
OVERSTRESS THE STRUCTURE, THE CONTRACTOR SHALL SUBMIT DESIGN
DOCUMENTS FOR TEMPORARY BRACING AND STRENGTHENING, INCLUDING
FABRICATION AND ERECTION DRAWINGS, TO THE ARCHITECT FOR REVIEW.
THESE DOCUMENTS SHALL BEAR THE SEAL AND SIGNATURE OF A REGISTERED
STRUCTURAL ENGINEER IN THE STATE OF WASHINGTON. THE CONTRACTOR SHALL
PROVIDE, INSTALL AND IF NECESSARY REMOVE SUCH TEMPORARY WORK AS
REQUIRED.
4. CONTRACTOR -INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO
THE ARCHITECT AND STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO
FABRICATION OR CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS ONLY
WILL NOT SATISFY THIS REQUIREMENT.
5. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION.
WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED, BUT ARE OF SIMILAR
CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE
USED, SUBJECT TO REVIEW AND APPROVAL BY THE ARCHITECT AND THE
STRUCTURAL ENGINEER.
6. ALL STRUCTURAL SYSTEMS WHICH ARE TO BE COMPOSED OF COMPONENTS
TO BE FIELD ERECTED SHALL BE SUPERVISED BY THE SUPPLIER DURING
MANUFACTURING, DELIVERY, HANDLING, STORAGE AND ERECTION IN ACCORDANCE
WITH INSTRUCTIONS PREPARED BY THE SUPPLIER.
7. INSPECTIONS: INSPECTIONS OF THE WOOD FRAMING, THE STEEL REBAR AND
WOOD FORMS FOR CONCRETE FOOTINGS & FOUNDATIONS, AND CONCRETE SLABS
ARE REQUIRED PER IBC SECTION 109.3.
8. PRE -MANUFACTURED, PRE-ENGINEERED STRUCTURAL COMPONENTS SHALL
BE DESIGNED BASED ON THE CRITERIA PRESENTED IN THE CONTRACT
DOCUMENTS. THE COMPONENT DESIGNER IS RESPONSIBLE FOR CODE
CONFORMANCE, TEMPORARY AND PERMANENT BRACING AND ALL NECESSARY
CONNECTIONS, INCLUDING CONNECTIONS TO THE PRIMARY STRUCTURE, NOT
SPECIFICALLY CALLED OUT ON THE ARCHITECTURAL OR STRUCTURAL DRAWINGS.
SHOP DRAWINGS SHALL INDICATE THE MAGNITUDE AND DIRECTION OF ALL LOADS
IMPOSED ON THE PRIMARY STRUCTURE. SHOP DRAWINGS AND CALCULATIONS
SHALL BE SUBMITTED AS NOTED PREVIOUSLY.
B. DESIGN CRITERIA
1. DESIGN LOADS
ROOF LIVE LOAD 25 PSF (SNOW)
RESIDENTIAL LIVE LOAD 40 PSF
ALLOWABLE SOIL PRESSURE
1,500 PSF AT V-6" DEPTH
LATERAL EARTH PRESSURE
50 PCF
PASSIVE PRESSURE
300 PCF
COEFFICIENT OF FRICTION
0.4
C. RENOVATION
DEMOLITION: CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS BEFORE COMMENCING
ANY DEMOLITION. SHORING SHALL BE INSTALLED TO SUPPORT EXISTING CONSTRUCTION AS
REQUIRED AND IN A MANNER SUITABLE TO THE WORK SEQUENCES. DEMOLITION DEBRIS
SHALL NOT BE ALLOWED TO DAMAGE OR OVERLOAD THE EXISTING STRUCTURE. LIMIT
CONSTRUCTION LOADING (INCLUDING DEMOLITION DEBRIS) ON EXISTING FLOOR SYSTEMS
TO 40 PSF.
CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER SIZES, AND CONDITIONS
PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OF EXISTING CONSTRUCTION SHOWN
ON THE DRAWINGS ARE INTENDED AS GUIDELINES ONLY AND MUST BE VERIFIED. THE
CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER IS EXISTING CONDITIONS
DETERMINED DURING WORK VARY FROM THE EXISTING CONSTRUCTION SHOWN ON THE
DRAWINGS.
EXISTING REINFORCING SHALL BE SAVED WHERE AND AS NOTED ON THE PLANS. SAW
CUTTING, IF AND WHERE USED, SHALL NO CUT EXISTING REINFORCING THAT IS TO BE
SAVED.
A. ALL NEW OPENINGS THROUGH EXISTING WALLS, SLABS, AND BEAMS SHALL BE
ACCOMPLISHED BY SAW CUTTING WHEREVER POSSIBLE. CORNERS SHALL NOT BE OVER
CUT.
B. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND LOCATION OF MEMBERS
PRIOR TO CUTTING ANY OPENINGS.
C. SMALL ROUND OPENINGS SHALL E ACCOMPLISHED BY CORE DRILLING.
D. WHERE NEW REINFORCING TERMINATES AT EXISTING CONCRETE, DRILL AND EPDXY
CONTRACTOR SHALL CHECK FOR DRY ROT AT ALL AREAS OF NEW WORK. ALL ROT SHALL BE
REMOVED AND DAMAGED MEMBERS SHALL BE REPLACED OR REPAIRED AS DIRECTED BY
THE ENGINEER OR ARCHITECT.
ABBREVIATIONS
(THIS IS A COMPREHENSIVE LIST OF ABBREVIATIONS, SOME OF WHICH MAY NOT APPEAR ON THESE DRAWINGS.)
AB
ANCHOR BOLT
CL
CENTERLINE
(E)
ACI
AMERICAN CONCRETE INSTITUTE
CLR
CLEAR
EA
ADDL
ADDITIONAL
CMU
CONCRETE MASONRY UNIT
EF
ADJ
ADJACENT
COL
COLUMN
EL
AFF
ABOVE FINISHED FLOOR
CONC
CONCRETE
ELEC
AISC
AMERICAN INSTITUTE OF STEEL CONSTRUCTION
CONN
CONNECTION, CONNECT
ELEV
ALT
ALTERNATE
CONSTR
CONSTRUCTION
EMB
ANSI
AMERICAN NATIONAL STANDARDS INSTITUTE
CONT
CONTINUOUS
ENGR
APA
AMERICAN PLYWOOD ASSOCIATION
CONTR
CONTRACTOR
EQ
APPROX
APPROXIMATE; APPROXIMATELY
COORD
COORDINATE
EQUIP
ARCH
ARCHITECT; ARCHITECTURAL
CID
COMPLETE PENETRATION
ES
ASSY
CSK
COUNTERSINK; COUNTERSUNK
EW
ASTM
AMERICAN SOCIETY FOR TESTING & MATERIALS
CTR
CENTER
EXP
AWS
AMERICAN WELDING SOCIETY
CU FT
CUBIC FOOT
EXP JT
CU IN
CUBIC INCH
EXT
BD
CY
CUBIC YARD
BLDG
BUILDING
FD
BLKG
BLOCKING
d
PENNY (NAILS)
FDN
BM
DBL
DOUBLE
FF
BMU
BRICK MASONRY UNIT(S)
DEPT
DEPARTMENT
FLR
BOF
BOTTOM OF SLAB
DET
DETAIL
FLG
BOS
DIA
DIAMETER (SEE SYMBOLS)
FOC
BOT
BOTTOM
DIAG
DIAGONAL
FOM
BRG
BEARING
DIAPH
DIAPHRAGM
FOS
BEAM
DICA
DRILLED -IN CONCRETE ANCHOR
FS
C
STANDARD CHANNEL
DIM
DIMENSION
FT
CG
CENTER OF GRAVITY
DN
DOWN
FTG
CGS
CENTER OF GRAVITY OF STRANDS
DO
DITTO
CIP
CAST -IN -PLACE
DWG
DRAWING
GA
CJ
CONSTRUCTION JOINT/CONTROL JOINT
DWL
DOWELS
GALV
D. FOUNDATION
1. FOUNDATION EXCAVATION, BACKFILL AND COMPACTION SHALL CONFORM TO
SPECIFICATION REQUIREMENTS. THIS CONSTRUCTION WORK, INCLUDING
DRAINAGE, SHORING AND SUCH OTHER RELATED WORK AS REQUIRED, SHALL BE
CONDUCTED BY THE CONTRACTOR UNDER THE OBSERVATION AND DIRECTION OF
THE GEOTECHNICAL ENGINEER.
2. FOOTINGS SHALL BEAR ON SOLID UNDISTURBED EARTH (CONTROLLED,
COMPACTED STRUCTURAL FILL OR BOTH) AT LEAST 18" BELOW LOWEST ADJACENT
FINISHED GRADE. MATERIAL TO BE COMPACTED TO 95% MINIMUM OF MAXIMUM
DRY DENSITY AS DETERMINED BY ASTM D1557.
3. FOOTINGS MAY BE POURED IN NEAT EXCAVATIONS PROVIDED SIZE IS
INCREASED 3" AT EACH INTERFACE WITH SOIL.
4. ALL FOOTING EXCAVATIONS SHALL BE HAND CLEANED PRIOR TO PLACING
CONCRETE.
5. ALL ABANDONED FOOTINGS, UTILITIES, ETC. THAT INTERFERE WITH NEW
CONSTRUCTION SHALL BE REMOVED.
6. CONTRACTOR SHALL PROVIDE FOR DESIGN AND INSTALLATION OF ALL
CRIBBING, SHEATHING, AND SHORING REQUIRED TO SAFELY RETAIN
EXCAVATIONS.
7. BACKFILL BEHIND ALL WALLS WITH WELL DRAINING, GRANULAR FILL
MATERIAL, AND PROVIDE PERFORATED PIPE DRAINS AS DESCRIBED IN THE
SOILS REPORT. BACKFILL BEHIND WALLS SHALL NOT BE PLACED BEFORE THE
WALL IS PROPERLY SUPPORTED BY THE FLOOR SLAB, OR TEMPORARY BRACING.
ALL FOOTINGS SHALL BE CENTERED BELOW CENTERLINE OF COLUMNS OR WALLS
ABOVE, UNLESS NOTED OTHERWISE.
E. CONCRETE
1. ULTIMATE STRENGTH DESIGN PER INTERNATIONAL BUILDING CODE AND
ACI 318-19
2. CONCRETE FOR FOOTINGS AND SLABS -ON -GRADE SHALL CONFORM TO A 28-
DAY STRENGTH OF fc = 2500 PSI, SHALL CONTAIN NOT LESS THAN 5-1/2
SACKS OF CEMENT PER CUBIC YARD, AND SHALL BE PROPORTIONED TO PRODUCE
A SLUMP OF 5" OR LESS. CONCRETE EXPOSED TO EARTH OR WEATHER SHALL HAVE A
28-DAY STRENGTH OF f'c = 3000 psi.
THE MINIMUM AMOUNTS OF CEMENT AND MAXIMUM AMOUNTS OF WATER MAY
BE CHANGED IF A CONCRETE DESIGN MIX IS SUBMITTED TO THE
ENGINEER AND THE BUILDING OFFICIAL FOR APPROVAL TWO WEEKS PRIOR TO
PLACEMENT OF CONCRETE. THE CONCRETE PERFORMANCE MIX SHALL INCLUDE THE
AMOUNTS OF CEMENT, FINE AND COARSE AGGREGATES, WATER AND ADMIXTURES AS WELL AS
THE WATER -
CEMENT RATIO, SLUMP, CONCRETE YIELD AND SUBSTANTIATING STRENGTH DATA
IN ACCORDANCE WITH ACI 318, SECTION 5.3. CONTRACTOR MAINTAINS RESPONSIBILITY FOR
SPECIFIED PERFORMANCE OF CONCRETE PRODUCTS.
ALL CONCRETE EXPOSED TO FREEZING TEMPERATURES WHILE CURING AND
ALL CONCRETE PERMANENTLY EXPOSED TO WEATHER SHALL BE AIR -ENTRAINED
WITH AN AIR -ENTRAINING AGENT CONFORMING TO IBC SECTION 1904.2. TOTAL
AIR CONTENT SHALL BE IN ACCORDANCE WITH TABLE 1904.2.1 OF THE INTERNATIONAL
BUILDING CODE.
NO ADMIXTURES, OTHER THAN FOR AIR -ENTRAINMENT AS NOTED ABOVE,
SHALL BE USED WITHOUT PRIOR REVIEW BY THE STRUCTURAL ENGINEER.
ALL CONCRETE IN ELEVATED STRUCTURAL SLABS AND BEAMS SHALL BE
POURED MONOLITHICALLY UNLESS SHOWN OTHERWISE OR APPROVED BY THE
ENGINEER PRIOR TO PLACEMENT.
3. REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM
A615 (INCLUDING SUPPLEMENT S1), GRADE 60, fy = 60,000 PSI.
EXCEPTIONS: ANY BARS SPECIFICALLY NOTED ON THE DRAWINGS AS
GRADE 40, fy = 40,000 PSI.
WELDED WIRE FABRIC: ASTM A82 AND ASTM A185, SPLICE WITH AT LEAST ONE
FULL MESH. PLACE AT MID -DEPTH, OR SLIGHTLY ABOVE, OF SLAB. MATERIAL
TO BE SUPPLIED IN FLAT SHEETS.
4. REINFORCING STEEL SHALL BE DETAILED (INCLUDING HOOKS AND BENDS)
IN ACCORDANCE WITH ACI 315-02. LAP ALL CONTINUOUS REINFORCEMENT PER
NOTE D.5. PROVIDE CORNER BARS AT ALL WALL INTERSECTIONS. LAP CORNER
BARS PER NOTE D.5. LAP ADJACENT MATS OF WELDED WIRE FABRIC A MINIMUM
OF 8" AT SIDES AND ENDS.
5. REINFORCING STEEL LAPS AND EMBEDMENT SHALL BE AS NOTED BELOW,
UNLESS NOTED OTHERWISE:
DEVELOPMENT LENGTH 48 BAR DIAM.
DEVELOPMENT LENGTH, top bar* 64 BAR DIAM.
LAP SPLICE LENGTH 64 BAR DIAM.
LAP SPLICE LENGTH, top bar* 80 BAR DIAM.
*TOP BARS ARE HORIZONTAL REINFORCEMENT SO PLACED THAT MORE THAN
12" OF CONCRETE IS CAST IN THE MEMBER BELOW THE BAR.
ALL HOOKS SHALL BE "STANDARD" IN ACCORDANCE WITH ACI 318.
REINFORCING SHALL NOT BE TACK WELDED.
6. CONCRETE PROTECTION (COVER) FOR REINFORCING STEEL SHALL BE AS
FOLLOWS:
FOOTINGS AND OTHER UNFORMED SURFACES, EARTH FACE 3"
FORMED SURFACES EXPOSED TO EARTH (i.e. WALLS
BELOW GROUND) OR WEATHER 2"
SLABS AND WALLS (INTERIOR FACE) 1 112"
7. CONCRETE WALL REINFORCING - PROVIDE THE FOLLOWING UNLESS
DETAILED OTHERWISE:
6" WALLS #4 @ 16" HORIZ. #4 @ 18" VERTICAL 1 CURTAIN @ CENTER
8" WALLS #5 @ 18" HORIZ. #5 @ 18" VERTICAL 1 CURTAIN @ CENTER
8. EPDXY GROUTED ITEMS SPECIFIED ON THE DRAWINGS SHALL BE GROUTED WITH
SIMPSON SET ADHESIVE BY SIMPSON STRONG TIE, PER ER-5729, FOLLOWING
MANUFACTURER'S INSTALLATION INSTRUCTIONS
EXISTING
GL
EACH
GWB
EACH FACE
GYP
ELEVATION
ELECTRICAL
HDR
ELEVATOR
HNG
EMBED, EMBEDDED, EMBEDMENT
HORIZ
ENGINEER
HP
EQUAL
HS
EQUIPMENT
HT
EACH SIDE
EACH WAY
ID
EXPANSION; EXPOSED
IF
EXPANSION JOINT
IN
EXTERIOR
INCL
INFO
FLOOR DRAIN
INT
FOUNDATION
FAR FACE, FINISHED FLOOR
JT
FLOOR; FLOOR LINE
FLANGE
K
FACE OF CONCRETE
KO
FACE OF MASONRY
KSI
FACE OF STUD
FULL SIZE; FAR SIDE
LAB
FEET; FOOT
LB
FOOTING
LF
LLBB
GAUGE
LLH
GALVANIZED
LLV
F. CARPENTRY
1. GLUED LAMINATED MEMBERS SHALL BE FABRICATED IN CONFORMANCE WITH
ANSI STANDARD A190.1. EACH MEMBER SHALL BEAR AN AITC OR APA EWS
IDENTIFICATION MARK AND SHALL BE ACCOMPANIED BY AN AITC OR APA EWS
CERTIFICATE OF CONFORMANCE. ALL SIMPLE SPAN BEAMS SHALL BE DOUGLAS
FIR COMBINATION 24F-V4, Fb = 2,400 PSI, Fv = 240 PSI. ALL
CANTILEVERED BEAMS SHALL BE DOUGLAS FIR COMBINATION 24F-V8, Fb = 2400
PSI, Fv = 240 PSI. CAMBER ALL GLULAM BEAMS TO 2,000' RADIUS, UNLESS
SHOWN OTHERWISE ON THE PLANS.
2. FRAMING LUMBER SHALL BE GRADED AND MARKED IN CONFORMANCE WITH
WCLIB STANDARD GRADING RULES FOR WEST COAST LUMBER, LATEST
EDITION.
FURNISH TO THE FOLLOWING MINIMUM STANDARDS:
MEMBER SIZE SPECIES GRADE
MIN. BASIC DESIGN
STRESS
JOISTS AND RAFTERS: 2x-3x DF #2
Fb = 875 PSI
JOISTS AND RAFTERS: 4x DF #1
Fb = 1000 PSI
BEAMS AND STRINGERS: 6x-LRGR. DF #1
Fb = 1350 PSI
POSTS AND TIMBERS 6x-LRGR. DF #1
Fc = 1000 PSI
TOP AND BOTTOM PLATE AT
SHEARWALLS & BEARING WALLS: DF #2
Fb = 1000 PSI
STUDS, PLATES, &
MISC. LIGHT FRAMING:
DF #2
Fb = 875 PSI
ALL LUMBER WITH A LEAST DIMENSION OF 2" (NOMINAL) SHALL BE
STAMPED SURFACE -DRY AND SHALL HAVE A MOISTURE CONTENT WHEN SURFACED
AND WHEN INSTALLED OF NOT MORE THAN 19 PERCENT. LUMBER WITH A LEAST
DIMENSION OF 4" (NOMINAL) OR GREATER SHALL BE STAMPED SURFACE -GREEN
AND AIR-DRIED TO A MOISTURE CONTENT OF NOT MORE THAN 19 PERCENT PRIOR
TO ITS USE IN FRAMING THE STRUCTURE.
3. MANUFACTURED LUMBER SHALL BE AS MANUFACTURED BY TRUS JOIST
MacMILLAN OR APPROVED EQUAL. REQUESTS FOR APPROVAL AS EQUAL WILL
REQUIRE SUBMITTAL OF NER "NATIONAL EVALUATION REPORTS" EQUIVALENT
TO NER 292 FOR PARALLEL STRAND LUMBER (PSL), OR NER-481 FOR LAMINATED
STRAND LUMBER (LSL). THE MINIMUM ALLOWABLE DESIGN VALUES ARE AS FOLLOWS:
PSL - Fb = 2,900; Fv = 290 PSI; E = 2,000,000 PSI
LSL - Fb = 2,250; Fv = 400 PSI; E = 1,500,000 PSI
4. SHEATHING SHALL BE APA PERFORMANCE RATED PANELS PER APA
"PLYWOOD DESIGN SPECIFICATION, "INCLUDING APPLICABLE SUPPLEMENTS,
UNLESS NOTED OTHERWISE. PLYWOOD PANELS SHALL BE GRADE CD AND ALSO
CONFORM TO DOC PS-1 & PS-2. ALL PANELS SHALL BE IDENTIFIED AS
EXPOSURE 1 UNLESS NOTED OTHERWISE. PANEL RATING TO BE AS FOLLOWS
UNLESS NOTED OTHERWISE:
ROOF: 19/32" THICK, 32/16, (OR 5/8" THICK, 32/16)
WALLS: 15/32" THICK, 32/16, (OR 1/2" THICK, 24/0)
FLOORS: 23/32" (OR 3/4") THICK, TONGUE & GROOVE, 48/24
UNLESS NOTED OTHERWISE ON THE PLANS, ROOF AND FLOOR SHEATHING
SHALL BE LAID UP WITH GRAIN PERPENDICULAR TO SUPPORTS AND NAILED WITH
10d NAILS @ 6"oc TO FRAMED PANEL EDGES AND OVER STUD WALLS SHOWN ON
PLANS AND @ 12"oc (10"oc AT FLOORS) TO INTERMEDIATE SUPPORTS.
PROVIDE APPROVED SHEATHING EDGE CLIPS @ 16"oc AT UNBLOCKED ROOF
SHEATHING EDGES. ALL FLOOR SHEATHING EDGES SHALL HAVE APPROVED
TONGUE -AND -GROOVE JOINTS AND SHALL BE SUPPORTED WITH SOLID BLOCKING.
TOENAIL BLOCKING TO SUPPORTS WITH 16d NAILS, UNLESS NOTED OTHERWISE.
UNLESS NOTED OTHERWISE ON THE PLANS, WALL SHEATHING MAY BE LAID
UP HORIZONTALLY OR VERTICALLY, UNSUPPORTED EDGES SHALL BE BLOCKED AND
ALL EDGES SHALL BE NAILED WITH 10d @ 6"oc, NAIL WITH 10d @ 12"oc AT
INTERMEDIATE SUPPORTS. NAIL SHEAR WALL SHEATHING TO ALL HOLDOWN
STUDS USING EDGE NAIL SPACING WHEN HOLDOWN STUD DOES NOT OCCUR AT
PANEL EDGES.
SHEATHING NAILS SHALL BE DRIVEN FLUSH BUT SHALL NOT FRACTURE
THE SURFACE OF THE SHEATHING.
5. ALL WOOD PLATES IN DIRECT CONTACT WITH CONCRETE OR MASONRY
SHALL BE PRESSURE -TREATED WITH AN APPROVED PRESERVATIVE. PROVIDE
TWO LAYERS OF ASPHALT IMPREGNATED BUILDING PAPER BETWEEN UNTREATED
LEDGERS, BLOCKING, ETC., AND CONCRETE OR MASONRY. ALL METAL
CONNECTORS TO PRESSURE TREATED LUMBER SHALL BE HOT DIP
GALVANIZED, INCLUDING WASHERS, NAILS, SCREWS, AND SIMPSON STRONG -TIE
HANGERS, STRAPS, AND PLATES, AND BOLTS LESS THAN 1/2" DIAMETER.
6. NOTATIONS ON DRAWINGS RELATING TO FRAMING CLIPS, JOIST HANGERS
AND OTHER CONNECTING DEVICES REFER TO CATALOG NUMBERS OF CONNECTORS
MANUFACTURED BY THE SIMPSON STRONG -TIE COMPANY, SAN LEANDRO,
CALIFORNIA. EQUIVALENT DEVICES BY OTHER MANUFACTURERS MAY BE
SUBSTITUTED, PROVIDED THEY HAVE ICC APPROVAL FOR EQUAL OR GREATER
LOAD CAPACITIES. SUBMIT MANUFACTURER'S CATALOG AND ICC REPORTS TO
ARCHITECT AND ENGINEER FOR REVIEW WHEN REQUESTING SUBSTITUTIONS.
ALL SPECIFIED FASTENERS MUST BE USED AND PROPER INSTALLATION
PROCEDURES MUST BE OBSERVED IN ORDER TO OBTAIN ICC APPROVED LOAD
CAPACITIES. VERIFY THAT THE DIMENSIONS OF THE SUPPORTING MEMBER ARE
SUFFICIENT TO RECEIVE THE SPECIFIED FASTENERS.
STRUCTURAL CONNECTORS
ALL STRUCTURAL CONNECTORS TO BE BY SIMPSON STRONG TIE OR EQUAL. USE
ZMAX/HDG HOT DIPPED GALVANIZED OR STAINLESS STEEL CONNECTORS AS A
MINIMUM. USE FASTENERS GALVANIZED PER ASTM A153. ALL PRESSURE TRATED
LUMBER USED SHALL BE COMPATIBLE WITH ZMAX GALV. CONNECTORES, RE:
SIMPSON STRONG -TIE CORROSION INFORMATION.
GLUE -LAMINATED
LOC
LOCATION
OPP
OPPOSITE
STL
STEEL
GYPSUM WALL BOARD
LONGIT
LONGITUDINAL
OSB
ORIENTED STRAND BOARD
STRUCT
STRUCTURAL
GYPSUM
LSL
LONG SLOTTED HOLE
SYM
SYMMETRICAL
LVL
LAMINATED VENEER LUMBER
PAR
PARALLEL
HEADER
LWC
LIGHT WEIGHT CONCRETE
PERP
PERPENDICULAR
T
TOP
HANGER
PL
PLATE
T&B
TOP AND BOTTOM
HORIZONTAL
M
MISC SHAPE
PLWD
PLYWOOD
T&G
TONGUE AND GROOVE
HP SHAPE
MAS
MASONRY
PREFAB
PREFABRICATED
TEMP
TEMPERATURE
HIGH STRENGTH
MATL
MATERIAL
PROP
PROPERTY
THK
THICKNESS
HEIGHT
MAX
MAXIMUM
PSF
POUNDS PER SQUARE FOOT
THRU
THROUGH
MECH
MECHANICAL
PSI
POUNDS PER SQUARE INCH
TOB
TOP OF BEAM
INSIDE DIAMETER
MFR
MANUFACTURER
PSL
PARALLEL STRAND LUMBER
TOC
TOP OF CONCRETE; TOP OF CURB
INSIDE FACE
MIN
MINIMUM; MINUTE
PT
POST TENSION
TOF
TOP OF FOOTING
INCH
MISC
MISCELLANEOUS
TOL
TOP OF LEDGER
INCLUDE; INCLUDING; INCLUSIVE
MO
MASONRY OPENING
RD
ROOF DRAIN
TOM
TOP OF MASONRY
INFORMATION
REF
REFERENCE
TOS
TOP OF STEEL, TOP OF STRUCTURE
INTERIOR
(N)
NEW
REINF
REINFORCE; REINFORCING
TOW
TOP OF WALL
N
NORTH
REQ'D
REQUIRED
TS
TUBING, STRUCTURAL
JOINT
NF
NEAR FACE
RO
ROUGH OPENING
TYP
TYPICAL
NFPA
NATIONAL FOREST PRODUCTS ASSOC
KIP = 1000 POUNDS
NIC
NOT IN CONTRACT
SCHED
SCHEDULE
UBC
UNIFORM BUILDING CODE
KNOCK -OUT
NOM
NOMINAL
SEC
SECTION
UL
UNDERWRITER'S LABORATORY, INC.
KIPS PER SQUARE INCH
NS
NEAR SIDE
SHT
SHEET
LINO
UNLESS NOTED OTHERWISE
NTS
NOT TO SCALE
SHTG
SHEATHING; SHEETING
URM
UNREINFORCED MASONRY
LABORATORY
SIM
SIMILAR
UT
ULTRA -SONIC TEST
POUND
oc
ON CENTER
SPA
SPACING, SPACE, SPACES
LINEAL FOOT
OD
OUTSIDE DIAMETER
SPEC
SPECIFICATION
VERT
VERTICAL
LONG LEGS BACK-TO-BACK
OF
OUTSIDE FACE
SQ
SQUARE
LONG LEGS HORIZONTAL
OH
OPPOSITE HAND
STD
STANDARD
W
WIDE FLANGE
LONG LEGS VERTICAL
OPNG
OPENING
STIFF
STIFFENER
WP
WORK POINT
WWF
WELDED WIRE FABRIC
7. WOOD FRAMING NOTES - THE FOLLOWING APPLY UNLESS OTHERWISE
SHOWN ON THE PLANS:
7.1 ALL WOOD FRAMING DETAILS NOT SHOWN OTHERWISE SHALL BE
CONSTRUCTED TO THE MINIMUM STANDARDS OF THE INTERNATIONAL BUILDING
CODE. MINIMUM NAILING, UNLESS OTHERWISE NOTED, SHALL CONFORM TO
TABLE 2304.9.1 OF THE INTERNATIONAL BUILDING CODE. COORDINATE THE
SIZE AND LOCATION OF ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL
DRAWINGS.
7.2 WALL FRAMING: ALL STUD WALLS SHOWN AND NOT OTHERWISE NOTED SHALL BE
2x4 STUDS @ 16"oc AT INTERIOR WALLS AND 2x6 STUDS @ 16" AT EXTERIOR WALLS. TWO
STUDS MINIMUM SHALL BE PROVIDED AT THE END OF ALL WALLS AND AT EACH SIDE OF ALL
OPENINGS AND UNDER THE ENDS OF ALL BEAMS. UNLESS NOTED OTHERWISE A (2) 2x8
HEADER SHALL BE PROVIDED OVER ALL OPENINGS IN 2x4 STUD WALLS AND A (3) 2x8
HEADER OVER ALL OPENINGS IN 2x6 WALLS. SOLID BLOCKING FOR WOOD COLUMNS SHALL BE
PROVIDED THROUGH FLOORS TO SUPPORT BELOW. PROVIDE CONTINUOUS SOLID BLOCKING AT
MID -HEIGHT OF ALL STUD WALLS OVER 8' IN HEIGHT.
ALL STUD WALLS SHOWN ON STRUCTURAL DRAWINGS SHALL HAVE THEIR
LOWER PLATES ATTACHED TO WOOD FRAMING BELOW WITH 16d NAILS AT 12"oc
STAGGERED OR BOLTED TO CONCRETE WITH 5/8" DIAMETER ANCHOR
BOLTS AT 4'-0"oc, EMBEDED 7", LINO REFER TO THE STRUCTURAL PLANS AND SHEAR WALL
SCHEDULE FOR REQUIRED SHEATHING AND NAILING.
7.3 FLOOR AND ROOF FRAMING: PROVIDE DOUBLE JOISTS UNDER ALL
PARALLEL PARTITIONS AND AROUND ALL OPENINGS IN FLOORS OR ROOFS UNLESS
OTHERWISE NOTED. PROVIDE BRIDGING @ 8'-0"oc AND SOLID BLOCKING AT
ALL BEARING POINTS. COORDINATE THE SIZE AND LOCATION OF ALL OPENINGS
WITH ARCHITECTURAL AND MECHANICAL DRAWINGS.
TOENAIL JOISTS TO BEARING SUPPORTS WITH 16d NAILS. UNLESS NOTED
OTHERWISE, ATTACH JOISTS TO FLUSH HEADERS OR BEAMS WITH SIMPSON "U"
SERIES METAL JOIST HANGERS TO SUIT JOIST SIZE. ALL DOUBLE JOISTS,
BEAMS, AND SLOPED AND/OR SKEWED JOISTS SHALL BE CONNECTED TO FLUSH
MEMBERS WITH HU-SERIES JOIST HANGERS UNLESS NOTED OTHERWISE. SKEW AND
SLOPE ALL CONNECTORS AS REQUIRED. FACE -NAIL ALL MULTI -JOIST BEAMS
TOGETHER WITH 16d SPIKES @ 24"oc STAGGERED.
7.4 NAILS SHALL BE MANUFACTURED IN CANADA OR THE UNITED STATES
IN SIZES AND TYPES AS FOLLOWS, UNLESS NOTED OTHERWISE:
PNEUMATIC NAILING - PLAIN SHANK, COATED OR GALVANIZED
8d = .131 DIAMETER x 2-1/2" MINIMUM LENGTH
10d = .131 DIAMETER x 3" MINIMUM LENGTHTO
16d = .131 DIAMETER x 3-1/2" MINIMUM LENGTH
HAND NAILING - SINKERS, COATED
8d = 11-1/2 GAGE x 2-3/8"
10d = 11 GAGE x 2-7/8"
16d = 9 GAGE x 3-1/4"
SPECIAL CONDITIONS
CONTRACTOR TO COORDINATE ALL TRADES AND VERIFY DIMENSIONS IN THE FIELD.
OBTAIN OWNERS APPROVAL PRIOR TO ALL FIELD CHANGES. SEE ARCHITECTURAL
DRAWINGS FOR ALL FLOOR AND WALL OPENING DIMENSIONS AND LOCATIONS,
FLOOR AND WALL FINISHES, ETC.
= The following documentation shall be available
on
site for the building inspector:
•
Fxj COE APPROVED ARCHITECTURAL PLAN SET
■
COE APPROVED STRUCTURAL PLAN SET
[:]COE REVIEWED CALCULATION PACKET
■ ENERGY CREDIT WORKSHEET
'
SITE PLAN
•
■
CIVIL PLAN
i
■ CITY OF EDMONDS BUILDING DEPARTMENT 2021
•
1
BLD2024-1307
SYMBOLS
■ COLUMN CONTINUOUS
&
AND
@
AT
❑ COLUMN BELOW 1 SECTIONS
BEAM CAMBER
S100
CENTERLINE
0
DIAMETER; ROUND
�o�+ Qua+#
/4101
NUMBER; POUND
5 SIMPSON STRONG -TIE HOLDOWN
m
L
SQUARE
STRUCTURALANGLE
JL
DOUBLE ANGLE
�SIMPSON STRAP
PLATE
V
4�
z
LU
.�
>�
Q 00
� Q Cfl
W00
'L 00
C: 0-)
L
Lo O (.0
M
W
(n CV
z N
O 00
U)
Q 0-)
co Q
w
J w
Q CV 0
z z
Q 00
Q
W LU
RECEIVED
Nov 05 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
�^^ DEPARTMENT
v!
W
O
z
J
Q
Ill
z
W
0
REVISIONS:
CADD FILE:
24126
DATE: 10-30-2024
DRAWN: M. H.
CHECKED: C. BURT
S0.1
2`-
�j (E) BEAM w/ WALL INF II�L�
— Ililll �
- - (E) RAFTEICE
N
s? 3x5
(E) RAFTER BRACE j � � if o
__2 ---- -------- ----
00
N ao 00
N
LLI
avt Oast '
PARTIAL ROOF FRAMING
PLAN
314 1'_ pr
demo wall replace
with beam
.VVVV7IDEMO NON LOAN
BEARING
NOTE: , p
FLOOR FRAMING NOT SHOWN
BEAM
IT
(E) FOOTING TYP
' 0
:Z. a
'k D _dlA/S2.1g.
oo
F2.0 24
i EAM
m I
F-----'3-=---Orr
PARTIAL FOUNDATION PLAN
Q
NOTES:
1.) DO NOT SCALE DRAWINGS.
2.) VERIFY ALL DIMENSIONS INFIELD.
3.) ALL POSTS THIS LEVEL 4X4 U.N.O.
17777757577, DEMO NON LOAD
BEARING WALL
FOOTING SCHEDULE
MARK
SIZE
REINFORCEMENT
(BOT. EA. WAY)
(TOP EA. WAY)
F 1.5
V-6" x V-6" x 8"
2 #4
---
F2.0
2'-0" x 2'-0" x 10"
3 #4
---
F2.5
2'-6" x 2'-6" x 10"
4 #4
---
NOTES:
1.) CENTER ALL FOOTINGS ON COLUMN AND WALL TYPICAL, U.N.O.
2.) AT LOCATIONS WHERE FOOTINGS ARE SHOWN SHARING A
COMMON BEARING AREA, CAST MONOLITHICALLY w/ INDIVIDUAL
REINFORCING PER SCHEDULE & OVERLAP AS REQUIRED.
U
7
4�
z
CY)
w CM
V_
Q 00
C:
Cu Q (0
00
O
L
M
W
00 I= c)
(n N
Z N
O 00
0. vJ Q
W
J � cli
Q N 0
z � z
Q 0
G7 W
RECEIVED
Nov 05 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
Z DEPARTMENT
a
J
0-
z
O
Q
0
z
D
O
LL
REVISIONS:
CADD FILE:
24126
DATE: 10-30-2024
DRAWN: M. H.
CHECKED: C. BURT
FOOTING SIZE AND
REINF. PER PLAN,
SCHEDULE
EQ.
SIMPS N PB
SERIES OR EQUAL
POST PER PLAN
EQ.
O U
co a
.. a ° Lu
II It I it I-
PER PLAN AND SCHEDULE
TYPICAL INT. POST FOOTING
SECTION
SECTION
SECTION
3/4" = 1'-01,
3/4" = 1'-01,
JOISTS PER PLAN
SIMP 'U' FACE HAN
OR SIMP 'JB' TOP
FLANGE HANGER
Li I
BLOCK BETWEEN
JOISTS
(2) 16d l
EA BLOI
BEAM PLlx I L/ 11
BEAM / JOIST CONNECTION
SECTION
SECTION
SECTION
I rz
-) FLOOR
TRUCTURE
) JOIST
:R PLAN
3/4" = 1'-01,
3/4" = 1'-01,
SECTION
SECTION
SECTION
3/4" = 1'-01,
3/4" = 1'-01,
SECTION
SECTION
3/4" = 1'-01,
3/4" = 1'-01,
U
4�
z
wM
--
>�
Q 00
� Q Cfl
W
00
00
�� �
L
Lo O
M
W
00U)N
z
N
O
Q
Lu
�00
U)rn
J
Q
C-4
N
u
r)
z
z
J
W
CEIVED
Ov 05 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
U
w
U)
z
O
Q
r)
z
D
O
H
REVISIONS:
CADD FILE:
24126
DATE: 10-30-2024
DRAWN: M. H.
CHECKED: C. BURT
3/4" = 1'-0"
3/4" = 1'-0"
3/4" = 1'-0"
S2,1
FULL HEIGHT
STUD, TYP.
BEAM PER PLAN
O
z
a
U
0
9
U)
0
U)
N
WINDOW SILL
2- 2x BEARING
STUDS, TYP. U.N.O.
SEE PLANS I
n
2x SIL
PLAN:
SCHE
L
D
PLATE
& SHE,
JLE
SEE
ARWALL
TYPICAL STUD FRAMING DETAIL OPENING
SECTION
HEADER
PER PLAN
TYPICAL SINGLE
TRIMMER STUD.
MULTIPLE TRIMMER
STUDS WHERE
REQUIRED PER
PLAN OR PER
NOTES/SPECIFIC
DETAIL
STAGGER TOP PLATE
4'-0" MIN. TYPICAL
TYPICAL STUDS PER
PLAN/DETAIL
3- 16d
SINGLE FULL HEIGHT KING
STUD. MULTIPLE KING STUDS
WHERE REQ'D. PER PLAN
TYPICAL HEADER SUPPORT DETAIL
SECTION
3/4" = 1'-0" �� 3/4" = 1'-0"
2x4 STUDS 2x6 STUDS
2x4 PLATE 2x6 PLATE
(2)- 2x HEADER (3)- 2x HEADER
SPIKE EACH PIECE w/
(2)- ROWS 16d SINKERS
@ 12"oc, STAGGERED, TYP.
1/2" PLYWOOD
FILLER
1/2" PLYWOOD FILLER, TYP.
3 1/2" 5
4x HEADER, 6x HEADER,
PER PLAN PER PLAN
TYPICAL HEADER SECTIONS
SECTION
STRAP PER PLAN
SW END STUDS PER
STRAP PER PLAN
SW END STUDS PER
PLAN & HD SCHEDULE
BEAM PER PLAN.
PLAN & HD SCHEDULE
PANEL EDGE NAILING
PANEL EDGE NAILING
PANEL EDGE NAILING
PANEL EDGE NAILING
PERPENDICULAR NOT
PER SHEAR WALL
SW END STUDS PER
PER SHEAR WALL
PER SHEAR WALL
SW END STUDS PER
PER SHEAR WALL
SHOWN FOR CLARITY
SCHEDULE
PLAN & HD SCHEDULE
SCHEDULE
HD PER PLAN
SCHEDULE
PLAN & HD SCHEDULE
SCHEDULE
HD PER PLAN
O
O
WALL STUDS &
PROVIDE NAIL/CLIPS &
WALL STUDS &
PROVIDE NAIL/CLIPS &
WALL STUDS &
PROVIDE NAIL/CLIPS &
WALL STUDS &
PROVIDE NAIL/CLIPS &
SHEATHING
SPACING PER PLATE
SHEATHING
SPACING PER PLATE
SHEATHING
SPACING PER PLATE
SHEATHING
SPACING PER PLATE
PER PLAN
ATTACHMENT ON SW
PER PLAN
ATTACHMENT ON SW
PER PLAN
ATTACHMENT ON SW
PER PLAN
ATTACHMENT ON SW
SCHEDULE, STAGGER NAILS
SCHEDULE, STAGGER NAILS
SCHEDULE, STAGGER NAILS
SCHEDULE, STAGGER NAILS
SIMPSON CCQ/ECCQ -
PLAN - INTERSECTION AT STRAP
L/3 NOTCHES
PERMITTED
wry D/3
O
O a
v a
0 �
L
PLAN - INTERSECTION AT HDU
PLAN - CORNER AT STRAP
TYPICAL SHEAR WALL CORNERS & INTERSECTIONS
SECTION
(MIN. DISTANCE FROM EDGE OF
HOLE TO INSIDE FACE OF SUPPORT)
HOLE SIZE
2"
3"
4"
6"
MIN. DISTANCE
1'-0"
2'-0"
L/3 NOTCHES
PERMITTED , 4"0 & 6"0 HOLES FOR VENTING DUCTS
(LARGE SIZE HOLES). REFER TO ARCH.
FOR VENTING PLAN
TYP.
HOLES
0
�2x0OF
LARGER
HOLE
HOLE PERMITTED
WALL OR SUPPORT
D/3
.I
TYPICAL HOLE SIZE SHALL
NOT EXCEED 6". NO MORE
THAN(1) 6"0 HOLE IS
ALLOWED IN EACH SPAN.
ALLOWABLE CUTTING IN LSL,LVL, OR PSL MEMBERS
SECTION
3/4" = 1'-0"
3/4" = V-0"
PLAN - CORNER AT HDU
3/4" = 1'-0"
PLAN
BEAM TO WOOD POST CONNECTION
SECTION
3/4" = 1'-0"
8- 16d NAILS EA. SIDE OF SPLICE
(NO BOT. SPLICE IN THIS AREA)
16d @ 12"oc 4'-0" 4'-0" 16d @ 12"oc
STAGGER TYP. MIN. MIN. STAGGER TYP.
PLAN
TOP PLATE SPLICE
AT STUD CENTERLINE, TYP.
2- 16d EA SIDE OF
BOTTOM PLATE SPLICE
BOTTOM PLATE SPLICE
AT STUD CENTERLINE, TYP.
EXISTING STUD WALL TOP PLATE SPLICE
SECTION
EXTRA STUDS AS
SHOWN, SEE PLAN
FOR ADDITIONAL
POSTS AND TYPICAL
POSTS UNDER BM.
CROSS WALL
NAIL STUD TOGETHER
w/16d @ 12"oc TYP.
3/4" = V-0"
EDGE NAILING
PER SHEARWF
SCHEDULE,TY
THRU WALL
2- STUDS AT E,
HOLDDOWN M
PLAN FOR FOF
ADDITIONAL P(
AND TYPICAL F
UNDER BEAM
CROSS WALL PLAN CORNER PLAN
TYPICAL WALL INTERSECTION
SECTION
1 1 /2" 0
L3
1 /4"0
1 1 /2"0
2 1 /4"0
MAX. HOLE
SINGLE STUDS
MAX. HOLE
MAX. HOLE
MAX. HOLE
®
(NO
REINFORC
®
NO
®
REQUIRED)ING
REQUOECING
3/4" MIN.
3/4" MIN.
1 1/2" MIN.
°p
EA. SIDE
1 1/2" MIN.
EA. SIDE
EA. SIDE
EA. SIDE
3/4" MAX.
1 1 /4" MAX.��
2 1 /8"0 3 1 /4"0
MAX. HOLE MAX. HOLE
STRAP
REINFORCING
5/8" MIN. PSPN516Z 1" MIN.
EA. SIDE STRAP EA. SIDE
2x4 PLATES 2x6 PLATES
ALLOWABLE HOLES THROUGH TOP PLATES
SECTION
NOTES: 3/4" = 1'-0"
1) AT BOTTOM PLATES, FOLLOW GUIDELINES
SHOWN, EXCEPT USE CS16X2'-0" STRAP
2x4 STUDS (3x4 SIM.) 2x6 STUDS (3x6 SIM.)
ALLOWABLE NOTCHES IN STUDS
SECTION
NOTES: 3/4" = 1'-0"
1) NOTCHES SHALL NOT OCCUR IN MORE
THAN (2) SUCCESSIVE STUDS
2 1 /8"0
MAX. HOLE
5/8" MIN.
EA. SIDE
DOUBLE STUDS
(NO MORE THAN (2)
SUCCESSIVE STUDS
MAY BE BORED)
2x4 STUDS (3x4 SIM.)
3 1 /4"0
MAX. HOLE
1" MIN.
i EA. SIDE
2x6 STUDS (3x6 SIM.)
ALLOWABLE HOLES THROUGH STUDS
SECTION
NOTES: 3/4" = 1'-0"
1) NOTCHES SHALL NOT OCCUR IN MORE
THAN (2) SUCCESSIVE STUDS
3/4" = V-0"
U
4�
z
wM
--
Q00
Wco
.� o0
a) 1?
-+ —a
c: 0-)
O "(6
CO L
L0 O
M
W
�WN
z
N
O
w
�co
u)
Q
J
Q
N
U)
0
z
z
J
co
CO
w
RECEIVED
Nov 05 2024
r /CITY OF EDMONDS
ELOPMENT SERVICES
Z DEPARTMENT
O
U
w
�U)
V
Cz
G
<
0
LL
S3.1
BURT
ENGINEERING
Structural Calculations
VTL Salon Alteration
8311 212th St SW
Edmonds, WA 98026
BE Project # 24126
October 28, 2024
2021 International Building Code
18530 MERIDIAN AVE N.
SHORELINE, WA 98133
RECEIVED
Nov 05 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
BURT STRUCTURAL ENGINEERING
ENGINEERING BUILDING CODE CONSULTING
PROJECT V 1Tt, 5karJ PROJECT # ?-'l la DATE 10'07Z
SUBJECT U c' SHEET OF
F T)WtVV�l�-� 50 -24 BY CP3
S Cc, P F, : CD A/',5-rPv- c4` f-7-kTwv5 7v (0) Rvut Q & .
v✓A-u t ( ,vt ve t./ F-�A.vl 01-- UI M�
1,t9"5 PF—�I— 2,.07/t c6C
w p51—
5Ot t, = Isv 0 �'7(-
RECEIVED
Nov O5 2024
Vtl Hair salon 1 of 2
BURT STRUCTURAL ENGINEERING
ENGINEERING BUILDING CODE CONSULTING
PROJECT V ITL ,;Aia4 PROJECT #7-4 17,� DATE 10'Z7 Z
SUBJECT � I l7/ 5,7- !�, LAJ SHEET Z OF Z
Dmo (V D S, I" �� 2 � BY C i3
F�-Il ulc/UG:
�j� J�L�' T �,
G u,� �z�l Z �,� F -V `1
OF WAM
N off; AL4A7
ZV '
IJOrbr s4lA - � pcg5'
RECEIVED
Nov 05 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
PFPADTMEDT
Vtl Hair salon 2 of 2
Project Title:
Engineer:
Project ID:
Project Descr:
Wood Beam
RECEIVED
Nov 05 2024
E Dlry OF EDMONDs
DES
VE ^ SERVICES
Project File: vtl salon.ec6
LIC# : KW-06014812, Build:20.24.09.03 BURT ENGINEERING PLLC
(c) ENERCALC, LLC 1982-2024
DESCRIPTION: roof beam
CODE REFERENCES
Calculations per NDS 2018, IBC 2021, SDPWS 2021
Load Combination Set: ASCE 7-22 / IBC 2024 (L<=100psf)
Material Properties
Analysis Method : Allowable Stress Design
Fb +
2400 psi
E : Modulus of Elasticity
Load Combination ASCE 7-22 / IBC 2024 (L-100psf)
Fb -
1850 psi
Ebend- xx
1800ksi
Fc - Prll
1650 psi
Eminbend - xx
950ksi
Wood Species DF/DF
Fc - Perp
650 psi
Ebend- yy
1600 ksi
Wood Grade 24F-V4
Fv
265 psi
Eminbend - yy
850ksi
Ft
1100 psi
Density
31.21 pcf
Beam Bracing Beam is Fully Braced against lateral -torsional buckling
f
1
3.5x12
Span = 15.0 ft
2
Applied Loads
Service loads entered. Load Factors will be applied for calculations.
Beam self weight NOT internally calculated
and added
Uniform Load : D = 0.0150, S = 0.0250
ksf, Tributary Width = 14.0 ft, (roof)
DESIGN SUMMARY
Maximum Bending Stress Ratio =
0.662 1
Maximum Shear Stress Ratio
=
0.347 : 1
Section used for this span
3.5x12
Section used for this span
3.5x12
fb: Actual =
1,828.13 psi
fv: Actual
=
105.86 psi
Fb =
2,760.00 psi
F'v
=
304.75 psi
Load Combination
+D+0.70S
Load Combination
+D+0.70S
Location of maximum on span =
7.500ft
Location of maximum on span
=
14.015ft
Span # where maximum occurs =
Span # 1
Span # where maximum occurs
=
Span # 1
Maximum Deflection
Max Downward Transient Deflection
0.442 in Ratio =
407 > 360 Span: 1 : S Only
Max Upward Transient Deflection
0 in Ratio =
0 <360 n/a
Max Downward Total Deflection
0.575 in Ratio =
313 -180 Span: 1 : +D+0.70S
Max Upward Total Deflection
0 in Ratio =
0 <180 n/a
Maximum Forces & Stresses for Load Combinations
Load Combination Max Stress Ratios
Moment Values
Shear Values
Segment Length Span # M V CD
CM Ct CLx
Cv Cfu C i Cr M fb
F'b
V fv F'v
D Only
0.0
0.00 0.0 0.0
Length = 15.0 ft 1 0.391 0.205 0.90
1.00 1.00 1.00
1.000 1.00 1.00 1.00 5.91 843.8
2,160.0
1.37 48.9 238.5
+D+0.70S
1.00 1.00 1.00
1.000 1.00 1.00 1.00
0.0
0.00 0.0 0.0
Length = 15.0 ft 1 0.662 0.347 1.15
1.00 1.00 1.00
1.000 1.00 1.00 1.00 12.80 1,828.1
2,760.0
2.96 105.9 304.8
+D+0.5250S
1.00 1.00 1.00
1.000 1.00 1.00 1.00
0.0
0.00 0.0 0.0
Length = 15.0 ft 1 0.573 0.301 1.15
1.00 1.00 1.00
1.000 1.00 1.00 1.00 11.07 1,582.0
2,760.0
2.57 91.6 304.8
+0.60D
1.00 1.00 1.00
1.000 1.00 1.00 1.00
0.0
0.00 0.0 0.0
Length = 15.0 ft 1 0.132 0.069 1.60
1.00 1.00 1.00
1.000 1.00 1.00 1.00 3.54 506.3
3,840.0
0.82 29.3 424.0
+D+0.10S
1.00 1.00 1.00
1.000 1.00 1.00 1.00
0.0
0.00 0.0 0.0
Length = 15.0 ft 1 0.256 0.134 1.60
1.00 1.00 1.00
1.000 1.00 1.00 1.00 6.89 984.4
3,840.0
1.60 57.0 424.0
Project Title:
Engineer:
Project ID:
Project Descr:
RECEIVED
Nov 05 2024
CITY OF EDMONDS
DEVELOPMENT SERVICES
DEPARTMENT
Wood Beam
Project File: vtl salon.ec6
LIC# : KW-06014812, Build:20.24.09.03
BURT
ENGINEERING PLLC
(c) ENERCALC, LLC 1982-2024
DESCRIPTION: roof beam
Overall Maximum Deflections
Load Combination Span
Max. "" Defl Location in Span Load Combination
Max. "+^ Defl
Location in Span
+D+0.70S 1
0.5746
7.555
0.0000
0.000
Maximum Deflections for Load Combinations
Load Combination
Span Max.
Downward Defl Location in Span
Max. Upward Defl
Location in Span
D Only
1
0.2652 in
7.555 ft
0.0000 in
0.000 ft
+D+0.70S
1
0.5746 in
7.555 ft
0.0000 in
0.000 ft
+D+0.5250S
1
0.4973 in
7.555 ft
0.0000 in
0.000 ft
+0.60D
1
0.1591 in
7.555 ft
0.0000 in
0.000 ft
+D+0.10S
1
0.3094 in
7.555 ft
0.0000 in
0.000 ft
S Only
1
0.4420 in
7.555 ft
0.0000 in
0.000 ft
Vertical Reactions
Support notation :
Far left is #1
Values in KIPS
Load Combination
Support 1 Support 2
Max Upward from all Load Conditions
3.413
3.413
Max Upward from Load Combinations
3.413
3.413
Max Upward from Load Cases
2.625
2.625
D Only
1.575
1.575
+D+0.70S
3.413
3.413
+D+0.5250S
2.953
2.953
+0.60D
0.945
0.945
+D+0.10S
1.838
1.838
S Only
2.625
2.625